HomeMy WebLinkAbout2662 Gateway Rd; 155; CBC2018-0150; PermitCcityof
Carlsbad
Commercial Permit
Print Date: 02/28/2019
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
Description:
Applicant:
2662 Gateway Rd, 155
BLDG-Commercial
2132622100
$365,382.56
BEVMO: 7,856 SF Tl SHELL TO RETAIL
Owner:
Work Class:
lot#:
Reference#:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Plan Check#:
Tenant Improvement
ROB BOUCKE
8008 E Arapahoe Ct
Centennial, CO 80112-6839
720-529-8768
SHEA PROPERTIES MANAGEMENT CO INC
MICHAEL LAWSON
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
130 Vantis Or
Aliso Viejo, CA 92656-2691
858-562-6500
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
GREEN BUILDING STANDARDS PLAN CHECK & INSPECTION
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
PLUMBING BLDG COMMERCIAL NEW/ADDITION/REMODEL
PUBLIC FACILITIES FEES -inside CFO
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-COMMERCIAL
Total Fees: $9,836.78 Total Payments To Date: $9,836.78
Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Inspection:
Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Permit No: CBC2018-0150
Closed -Finaled
03/19/2018
08/30/2018
AKrog
2/28/2019 9:47:18AM
$0.00
$1,570.30
$1,099.21
$89.00
$170.00
$55.00
$86.00
$6,649.96
$15.00
$102.31
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
l'HE FOLL,"IING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: □PLANNING □ENGINEERING □BUILDING □FIRE □HEALTH □HAZMATIAPCD I
(city of Building Permit Application Plan Check NoQ3::_~ ti?-ntSD
1635 Faraday Ave., Carlsbad, CA 92008 Est. Value t/:J 5{,,y, 2-'K::J. G ~
Carlsbad Ph: 760-602-2719 Fax: 760-602-8558 Plan Ck. Deposit email: building@carlsbadca.gov
www.carlsbadca.gov Date · 7J/ / q / f'){ jSWPPP
JOB ADDRESS SUITl!I/SPACEf/UNrT# rPN 2662 Gateway Road Suite #155 213 -262 -09 -00
1..,,,c,,OJE..,,,.. I LOT# I PnASE,, I l'''\i1A-ff DATHROOr,,S I TENANT au .. ,NESS NAME r"O;B E I -~ Mou, N/A 1 Beverages & Morel
DESCRIPTION OF WORK: Include Squaf9 Feet of Affecuov Area(s)
TENANT IMPROVEMENT OF (E) VACANT 7,856 S.F. BUILDING SPACE FOR RETAIL FOOD MARKET. NEW INTERIOR PARTITIONS, DOORS,
CEILINGS, FINISHES, AND FIXTURES. NEW PLUMBING, NEW LIGHTING/ELEC, NEW HVAC DUCTWORK TO TIE INTO EXISTING ROOFTOP HVAC
UNITS. NO SITE WORK PROPOSED.
FIREPLACE EXISTING USE I PROPGSED USE
VACANT· MERCANTILE MERCANTILE I GARAG; (SF) PATIOS (SF) I DECKS (SF)
0 0 YESO
I AIR CONDITIONING I FIRE SPRINKLERS
N0 YESIZ)No □ YESIZ)No□
APPLICANT NAME Rob Boucke c/o MCG Architecture PROPERTY OWNER NAME Amber Wesley c/o Shea Properties Primary Contact
ADDRESS ADDRESS 8008 E. Arapahoe Court, Suite 100 130 Vantis Dr., Suite 200
CITY STATE ZIP CITY STATE ZIP Centennial co 80112 Aliso Viejo CA 92656
PHONE PHONE
720-529-8768 I FAX 949-389-7236 I FAX 949-389-7434
EMAIL EMAIL rboucke@mcgarchitecture.com Amber.Wesley@sheaproperties.com
DESIGN PROFESSIONAL Same as applicant CONTRACTOR BUS, NAME TBD
ADDRESS ADDRESS
CITY STATE ZIP CITY STATE ZIP
PHONE IFAX PHONE rAX
EMAIL EMAIL
]STATE UC.# STATE LIC.#
'CLASS
I CITY BUS. L\C.#
(Sec. 7031.5 Business and Professions Code: Any City or Cou,:ify which requires a permit to construct, alter, Improve, demolish or rel)a.lr any structure, prior to Its Issuance, also requires the applfcant for such permit to file a signed statement tflat he ts licensed pursuant to the provisions of the Contractor's License Law {ChaD'terB, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he Is exemDt therefrom, and the basis for the alleged exemption. Any vlolatlon of Section 7031.5 by any appllcan'ffor a permit subjects the appllcant to a clvll penalty of not more than five hundred dollars {$500)). .
WORKERS' COMPENSATION
Workers' Comp1111atlon Declaration:/ haret,y affl,m under penalty of perjury one of the following dec/aratlons:
B I have and will maintain a certfflcatt of conaent to nlf-ln1ure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit \a Issued.
I have 1nd°'w1u maintain workers' compensation, as reQulred by Section 3700 of the Labor Code, forth& performance of the work for which this permit Is Issued. My workers' compensatkln Insurance carrier and policy
number are: Insurance Co. __________________ Polley No. ____________ ExplratlonDate _______ _
T,bl§, section need not be completed If the permit Is for one hundred dollars ($1 00) or less. LJ Certificate of Exemption: I certify that In the performance of the work for which this pem,lt Is lssued, I shaU not employ any person In any manner so as to become subject to the Workers' Compensation Laws of
Callfomla. WARNING: Failure to secure workers' compensation coverage Is unlawful, and shall subject an employer to criminal penalties and clvll fines up to one hundred thousand dollars (&100,000), In
addition to the cost of compensation, damages II provided for In Section 3706 of the Labor code, lntarut and attorney's fffl.
2S C0NTRACTORSIGNATURE □AGENT DATE
OWNER-BUILDER DECLARATION
I hereby afflrm that I am exempt from Contractor's Ucanse Law for the fol/owing reason: D I, as owner of the property or my employees with wages as their sole compensation, will do the work end the structure Is not Intended or offered for sale {Sec. 7044, Business and Professions Code: The Contractofs
License Law does not apply to an owner of property who builds or Improves thereon, and who does such work himself or through his own employees, provided that S\Jch Improvements are not Intended or offered for
sale. If, however, the 'oulldlng or Improvement Is sold within one year of completion, the owner-bulkier wlti have the burden of proving that he did not bu Md or Improve for the purpose of sale).
□
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractors License Law does not apply to an owner of
property woo buOds or Improves thereor1i and contracts for Sl!Ch projects with contracto~s) lk:ensed purauant to the Contractors License Law).
I am exempt under Sectlon ___ ~•USlness and Professions Code for this reason:
1. 1 personaUy plan to provide the major labor and materials for construction of the proposed property Improvement 0Yes Do
2. I (have I have not) signed an appllcatlon for a buRding permit forth& proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (Include name address/ phone/ contractors' license number~
4. 1 plan to provide portions of the work, but I have hired the fellowing person to coordinate, supeNlse and provide the major work (Include name/ address/ phone I contractors' Rcense number):
5. I wll.l provide some of the work, but I have contracted (hired) the following persons to provide the work Indicated (Include name I address/ phone /type of work}:
2S PROPERTY OWNER SIGNATU □AGENT DATE
--~ -~ ---~--~ -
COMPLETE THIS SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY
--~ -~ ~ • ---J -
Is the appllcant or future bulldlng occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under SecOons 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Yes v No
ls the applicant or future building occupant required to obtain a permit from the air pollution control district or air Qualily management district? Yes Y No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes v No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND lllE AIR POLLUTION CONTROL DISTRICT.
I hereby affinn that there is a C011struclion lending agency for the perfonnance of the work this permit is Issued (Sec. 3097 (i) CMI Code).
I C8flffythat I have read the applk:atlon and state that the above Information Is conffl and that the Information on the plans Is accuratB. I agree to complyv.tth all City ordinances and State laws relating to bulldlng consbuctlon.
I hereby aulholize _,,1at1ve of ~e Cfy of Carlsbad ID enter upon ~e above mentioned property for Inspection purpoees. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY Of CARLSBAD
AGAINST ALL LIABILmES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANYWAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OFTHIS PERMIT.
OSHA: An OSHA pennl Is requn!d for exa,V8Uor1S over s•~ deep end demolWon or c:onslructlon of mJchlles aver 3 siDlles In ~l
EXPIRATION: Every pennl Issued by the Bul~lng Offldal under ~e provlsklns of ~Is Code shall expire by nmllatlon end become nuH and vo~ ! the bul~"ll or work a~orlzed by such pem,t Is not comrr,nced ll'lm
180 days from the dale of such pennl or ! the b Ing or rk aulhorized by such pennlt Is suspended or abandoned at any tirre alter ~• work Is commenced ror a period of 180 days (Sedion 106.4.4 Uniform Bul~lng Code),
-@S' APPLICANT'S SIGNATURE DATE
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
CERTilFICATE OF OCCUPANCY (Commercial Pro1ccts 0 n I _v)
Fax (760) 602-8580, Email bullding@carlsbadca.gov or Mall the completed fonn to City of Carlsbad, Building DMslon 1635 Faraday Avenue, Carlsbad, Callfomla 92008.
CO#: (Office Uae Only}
CONTACT NAME Rocio Clough c/o BevMo! OCCUPANT l'IAME Beverages & Morel (dba BevMo!)
ADDRESS 1401 Willow Pass Road, Suite 900 BUILDING ADDRt.:J:a 2662 Gateway Road -Suite #155
Cl1Y STATE ZIP Cl1Y STATE ZIP Concord CA 94520 Carlsbad CA 92009
PHONE I FAX 925-609-607 4
EMAIL OCCUPANT'S BUS. LIC. No.
cloughr@bevmo.com Pending
DELIVERY OPTIONS
PICKUP: CONTACT (Usted above) OCCUPANT (Usted above)
CONTRACTOR (On Pg. 1)
~ MAIL TO: CONTACT (Listed above) "' OCCUPANT (Usted above)
ASSOCIATED CH
CONTRACTOR (On Pg. 1) NO CHANGE IN USE/ NO CONSTRUCTION
MAIL/ FAX TO OTHER:
CHANGE OF USE/ NO CONSTRUCTION
Jt! APPLICANT'S SIGNATURE ~~/7 DATE ??// C/2-o!R
I . -
PERMIT INSPECTION HISTORY REPORT (CBC2018-0150)
Permit Typo: BLDG-Commercial Application Dato: 03/19/2018 Owner: SHEA PROPERTIES
MANAGEMENT CO INC
Work Class: Tenant Improvement Issue Date: 08/30/2018 Subdivision:
Status: Closed -Finaled Expiration Date: 08/19/2019 Address: 2662 Gateway Rd, 155
Carlsbad, CA 92009
IVR Number: 10197
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Relnspection Complete
Checklist Item COMMENTS Passed
BLDG-Building Deficiency TCOok Yes
BLOG-Plumbing Final Yes
BLDG-Mechanical Final Yes
BLOG-Structural Final Yes
BLDG-Electrical Final Yes
02/2812019 02/28/2019 BLDG-Fina\ 084857-2019 Passed Andy Krogh Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Plumbing Final Yes
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
BLDG.Fire Final 083945-2019 Scheduled Cindy Wong Incomplete
Checklist Item COMMENTS Passed
FIRE· Building Final No
February 28, 2019 Page 3 of:
PERMIT INSPECTION HISTORY REPORT (CBC2018-0150)
Permit Type: BLDG-Commercial Application Date: 03/19/2018 Owner: SHEA PROPERTIES
MANAGEMENT CO INC
Work Class: Tenant Improvement Issue Date: 08/30/2018 Subdivision:
Status: Closed -Finaled Expiration Date: 08/19/2019 Address: 2662 Gateway Rd, 155
Carlsbad, CA 92009
IVR Number: 10197
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Relnspection Complete
12/19/2018 12/19/2018 BLDG-24 079354-2018 Failed Andy Krogh Reinspection Complete
Rough/Topout
Checklist Item COMMENTS Passed
BLOG-Building Deficiency Insulation on all hot water lines No
BLDG-44 079356-2018 Failed Andy Krogh Relnspection Complete
Rough/Ducts/Dampe
rs
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Seismic straps, cleats No
BLDG-97 Disabled 079355-2018 Passed Andy Krogh Complete
Accessibility
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Partial walk for sinks Yes
12/31/2018 12/31/2018 BLDG-24 080107-2018 Partial Pass Michael Collins Relnspectlon Incomplete
Rough/Topout
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Insulation on all hot water lines No
BLOG-Building Deficiency Hot water line insulation Yes
BLOG-33 Service 080109-2018 Cancelled Michael Collins Reinspection Complete
Change/Upgrade
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG44 080108-2018 Partial Pass Michael Collins Reinspection Incomplete
Rough/Ducts/Dampe ,.
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Seismic straps, cleats No
BLDG-Building Deficiency Straps at plenum, see card. Yes
01/03/2019 02/14/2019 BLDG-Fire Final 079676-2018 Failed Cindy Wong Relnspection Complete
Checklist Item COMMENTS Passed
FIRE-Building Final No
02/13/2019 02/13/2019 BLDG-14 083811-2019 Passed Andy Krogh Complete
F rame/Steel/Boltlng/
Welding (Decks)
02/2012019 02/20/2019 BLDG-Final 084174-2019 Partial Pass Andy Krogh Relnspection Incomplete
Inspection
February 28, 2019 Page 2 of
PERMIT INSPECTION HISTORY REPORT (CBC2018-0150)
Permit Type; BLDG-Commercial Application Date: 03/1912018 Owner: SHEA PROPERTIES
MANAGEMENT CO INC
Work Class: Tenant Improvement Issue Date: 0813012018 Subdivision:
Status: Closed -Finaled Expiration Date: 0811912019 Address: 2662 Gateway Rd, 155
Carlsbad, CA 92009
IVR Number: 10197
Scheduled Actual Primary Inspector Complete Date Start Date Inspection Type Inspection No. Inspection Status Relnspection
10/0312018 10/0312018 BLDG-21 071866-2018 Passed Andy Krogh Complete
Underground/Underf
loor Plumbing
10/09/2018 10/09/2018 BLDG-11 072192-2018 Passed Andy Krogh Complete
FoundatlonfFtg/Pler
s (Rebar)
10/22/2018 10/22/2018 BLDG-84 Rough 073560-2018 Passed Andy Krogh Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Do not lid hardlid without fire approval Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
10124/2018 10124/2018 BLDG-16 Insulation 073984-2018 Passed Andy Krogh Complete
10125/2018 1012512018 BLOG-14 074208-2018 Passed Andy Krogh Complete
Frame/SteellBoltlng/
Welding (Decks)
1012912018 10(29/2018 BLDG-17 Interior 074355-2018 Failed Andy Krogh Reinspection Complete
LathlOrywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Not ready No
1013012018 10/3012018 BLDG-17 Interior 074557-2018 Cancelled Andy Krogh Re inspection Complete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
11/01/2018 11101/2018 BLDG-17 Interior 074791-2018 Passed Andy Krogh Complete
LathlDrywall
1210512018 1210512018 BLDG-97 Disabled 077921-2018 Partial Pass Andy Krogh Relnspectlon Incomplete
Accesslblllty
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Partial walk for sinks Yes
12/13/2018 12113/2018 BLDG-33 Service 078669-2018 Falled Andy Krogh Reinspection Complete
Change/Upgrade
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
February 28, 2019 Page 1 of 3
'~~ ~ CITY Ol'
RECORD COPY
CBC2018-0150
2662 GATEWAY RD # 155 CARLSBAD
Building Division INSPECTION RECORD BEVMO 7,856 SF Tl SHELL TO RETAIL
[0 "'ISPECTION RECORD CARD WITH APPROVED
ANS MUST BE KEPT ON THE JOB
2132622100
3/19/2018
th-ALL BEFORE 3:00 pm FOR NEXT WORK DAY INSPECTION
0 FOR BUILDING INSPECTION CALL: 760-602-2725
OR GO TO: www.carl.sbadca.gov/BuildlnrND CLICK ON
"Request Inspection·· (} /l CBC2018-0150
DATE: 0 U
If "YES" is checked below that Division's approval is required nricff_toyeq_uestin a Final Building Inspection. If you have any questions
please call the applicable divisions at the phone numbers provided below. After all required approvals are signed off-fax to
760-602-8560. email to Q_I_Qgi11sp_~c;tiQns@._C:~_rJ~tJJ!dCa. ·_ ov or bring in a COPY of this card to: 1635 Faraday Ave., Carlsbad.
IF MARKED 'YES", IT IS REQUIRED PRIOR TO ANY CONSTRUCTION
STORM WATER PRECON MEETING REQUIRED 760-602-2725 Allow 24 hours
IF MARKED "YES", APPROVAL REQUIRED PRIOR TO REQUESTING BUILDING
Fire Prevention 760-602-4660 Allow 48 hours
Planning/Landscape 760-944-8463 Allow 48 hours
CM&I {Engineering Inspections) 760-438-3891 Call before 2 pm
#34 ROUGH ELECTRIC/ EV CHARGER
#66 MASONRY PRE GROUT #33 □ ELEC SERVICE #32OTEMPORARY
□GROUT 0 WALL DRAINS #35 PHOTO VOLTAIC cl!n, TILT PANELS #38 SIGNS
#11 PDUR STRIPS. ~----------+-----+-----I BLDG• FINAL
#11 COLUMN FOOTINGS CODE -II MECHANICAL
#14 SUBFRAME □ FLOOR O CEILING #41 UNDERGROUND DUCTS & PIPING
#15 ROOF SHEATHING #44 □ DUCT & PLENUM □ REF. PIPING
#13 EXT. SHEAR PANELS #43 HEAT-AIR COND. SYSTEMS
#16 INSUIATION
#18 EXTERIOR IATH
#17 INTERIOR IATH & DRYWALL UNDERGROUND (11,12,21.31)
.... ,. ....... .-.
Date
Date
Date
COPY OF CARO
REQUIRED
Inspector
Ins ector
Ins ector
DRYWALL,EXTIATH, GAS TES (17,18,23)
#22 □ SEWER & BL/CO □ Pl/CO
#21 UNDERGROUN ASTE O WTR
#24 T0P0UT □WASTE □WTR
#27 TUB & SHOWER PAN
#23 □ GAS TEST □ GAS PIPING
#25 WATER HEATER
#28 S0IAR WATER
BLDG-FINAL
CODE# POOLS
#51 POOL EXCAV STEEL
#52 PLUMBING
-•1 ELEC / CONDUIT/ WIRING
) EQUIPOTENTIAL BOND
':,--, PREPIASTER / FENCE/ AIARMS
#57 GUNITE
Date
•
ROOF SH EATING, EXr SHEAR (13.15)
#84 FRAME ROUGH COMBO (14,24,34,44)
#85 T-Bar(14,24,34,44)
BLDG· FINAL OCCUPANCY
Date Ins ector
A/S UNDERGROUND FLUSH
A/S OVERHEAD VISUAL
Ins ector A/S OVERHEAD HYDROSTATIC
A/S FINAL
F/A ROUGH-IN
F/AFINAL
FIXED EXTINGUISHING SYSTEM ROUGH-IN
FIXED EXTING SYSTEM HYDROSTATIC TEST
FIXED EXTINGUISHING SYSTEM FINAL
BLDG·FINA_L ___ ····--------4------+-----+-"M:CE=D'-'IC::.:Ac:.L;:;GAccS:.:P_:_R=ES::.S:c:U:.:R:::E_:_TES::::.T_ ............. ~--4e------+------
MEDICAL GASl=INAL
REV9/17 SEE BACK FOR SPECIAL NOTES
Pro,ec1 BevMo
pered M,nh Tran • Healthy Bu,ldngs
# Reference/ System
Lighting and HVAC
2 Roof Top Units
Site Observation Report 1-10-19
Site Observation Report
Observation Dnc:r1ptlon
No Action Required: Lighting and HVAC dlst~bution and controls have been installed.
Action Required: A missing grill on one of the RTUs.
Page 1 of6
S.le Nltion eport #
O■te of Srte V1111
Jan"8 10 2019
Plan / Sketch / Photo
I
Healthy Buildings
Print Date: 1/11/2019
Project· BevMo
Prepal'ed Minh Tran • Healthy Buildings
# Refe,.nce / Syatem
Exhaust Fan
HVAC Labeling
Site Observation Report 1-10-19
Site Observation Report
Observation Oeacrfptlon
Action Required: No power and control to the exhaust fan.
and T earn to get this work done.
Action Required: Mechanical sub to place labels on RTUs
Site Observation Report.,.
Date of Srte Visit
Janua 10 2019
/~
GC to communicate with BevMo ~j •·
Page 2 of6
Plan I Sketch/ Photo
( ►
Healthy Buildings
Print Oate: 1/11/2019
ProJOct BevMo
Prepare<! Mtnh Tran -Healthy BUIidings
#
6
Reference/ System
Setting, -Progammable
Thenno1tat1
CO2 Sensors
Site Observation Report 1-10-19
Site Observation Report
Observation OeacrlpUon
No Action Required: Occupied and unoccupied achedulH and temperatures (1dj,) were set II per call
out on p(ana. BevMo to adjust based on their operation hours.
No Action ~quired: Verification of CO2 concentration levels. Per mechanical 1ublGC, BevMo/Team
has requested and approved the change/location of CO2 sentor110 they e1n Mt up their C:00,ers ■nd
configure ules areas.
Page 3 of 6
Sita bservatlon Report#·
Date or Site Visit.
Janua 10 2019
Plan / Sketch / Photo
( .
Healthy
Buildings
·-
Print Date: 1/11/2019
Site Observation Report
Project BevMo
Prepared Mmh Tran • Healthy Bu1ld1ngs
# Reference/ SY9tem Observation Oeecrtptlon
Domestic Hot Water Heater and No Action Required: Verification of domestic hot 'Miter heater system installation. Hot water piping
ln1ul1tion ln1t1ll1tion insulation were found to be lnstal•d
Sink in Sales Area Action Required: Faucet in the Sales Area was found to be leaking.
Sije Observation Report 1-10-19 Page 4 of 6
Sile Observation Report #
Date of Site Visit.
Janua 10 2019
Plan I Sketch/ Photo
I •
Healthy
Buildings
Print Dale: 111112019
Project· BevMo
Prepared Minh Tran • Healthy Buildings
#
10
Reference/ System
Lighting and Low Voltage
S'Mtc:Ms In Salet ArH
EM/ Inverter TetUng
$ije Observation Report 1-10-19
Site Observation Report
Observation Deacr1ptlon
Action Required: Plate to be installed after all aWtches lnatalled.
No Action Required: Verification of Inverter and emergency ltghting oper1lion,
Page 5 of 6
Site t>servat,on Report#"
Date of Site Visit
Janua 10 2019
I • ' He althy
Buildings
Plan / Sketch I Photo
Print Date: 1/11/2019
Project· BevMo
Prepared Minh Tran • Healthy Buildings
# Reference I System
11 Lighting Controls
Site Observation Report
Observation Oeacrlptlon
No Action Required: Verification of lighting control system and Nghting schedule. Lighting levels and
schedule cen be adjusted besed on BevMo operation schedule. O&M lralnl~lk lo be provided 10
BevMo staff by elec1rical sub.
12 Action Raqulred: Electrical aub to comptete the label and make some adjustments on primary zone of Lighting Control Box I Labeling dlytighllng controls as needed.
Site Observation Report 1-10-19 Page 6 016
Site Observation Report 'I
Date of Site VISrl
Janua 10 2019
( .
He althy Buildings
Pion I Sk.tch I Photo -----------------------------
Print Date: 111112019
LEED Commissioning Deficiency Tracking Sheet
... _ Project Name BevMo
p,.,,_,wc1 by Minh Tran
Hai.ti • 1-a u1H: (fPTI DIIK-.d d\lfltle fliMl>On.i Perform-• Tttlirc • (PCVI ~ed duriflt P,-e-,funnlo~ Tnllflt verlfiUlicNI • (PCI -Horded bv lh■ cont~or O(t _. Pr•FuRCClonal Chkkh'1 • !FOi Ob«.NJ.d • lhe rnult r1' • Fi.Id ObteN•tiMI,; ""Cock: IAJ Ac:«¢..:1 byOWnllf", !Cl CouiKtrd, fO)~ .kt1o11 t-t: !All Nthk.ct,l(,c!Mef, (GCJ Gent<,! ~r.«or, IHJ EIKtrk.11 wb, (CS) Con1,og Sub. (PS) PNmb4nlSub, IMSI MKhlnialSub. IOSJ O.~Sub, [TS) TA&, IOltl Ow'1"'r's bp, MVltftdOf ·--~ lnue Atul9)'tllm RdEqptlO luu• O..cf'lpUon Tachntoal Comment ftEIPON.SE I ACTK>N ITEMS • o, ..
1 1/10/19 RoofTop Unit Outside Air Grill A mllelng grill on one of the Roor Top Units. Mechanlca1 eub to install • grill.
2 1/10/19 RoofTopUnitt Lat>eHng No tabeJs on Root Top Unitt. Mach■nical sub lo P'aO& labels oo Roof Top Unitl,
3 1110/19 Programmab$e Thermoatn Labelng No labe• on pc'ogrammat»e thermoetata. Meohan;c.t 1Ub to place labels on l)fogrammable
thennoetat1.
Roof Top Units-Outside Ak Ow.Ide A'I Oltaide Air Dampers on Roof Top Units WMt not open~ or GC to chedi. -Mth both Meehan.cal sube to verffy if the 4 1/10/19 modulating. Tl Mechanioal Sub wn n<X demonetrttl~ thti Oampera Dampen ope(8tion due to bbiMy between Tl & Shell projeota. operation of outside air dampera,
5 1/10/19 Exhauat Fan lnatallatlon No power/controll were lnatalld lmplemented GC to check 'Nilh BevMo and Team and CX>Ol'dlnate with
avbe to com~ete the lnttallatk>n.
Sett• -Progranvnable Mechanical sub programmed ttte Mtttinga of occup!ed Ind Completed by Tl Mecf'lanloll Sub BevMo to adjust 6 1/10/19 Th&rmostltl Sett"l)I unoccupied hourt I tempertturet baaed on eall out on the Meehank:al &Ub has comP'eted the programming. based oo their butlneu hours.. rnechanlcal pfaM.
7 m0119 Sink In h Salea Area LNk LHk WH found on h Wik., the SalH ........ GC to coordina" wff\ f>1umbirv 8Ub ID ohedt and oorTWCt N --• 1110/19 Plall on sw+tchea In S.laa Arte IMtalatlon Uphting / l,.ow Vtwbl~ awit:hN ID bt oorf1Mt»d and • platll ID ba Subs ID pa.c. • plata on 1h11 owrriCM llc,h1hg and IOW 'l'OMge _...,_ ~• WMn inttaladon i. dc>nt.
Eliec:ticcll SI.lb ~lld 1141 lltmp<WIII')' lighting echadulti from !5:00 S.vMo ID adjulll .... !Qhling achedule and 11,ghting law! beNd • 1/10/19 '""'""'-s.-AM 10 12:00 AM. El9c:trioal aub to pn:,vlda O&M n!Nng to Bloll'Mo on on lhalr bu.in.a hounl. O&M n lnlng to ba pn.wi(Md by EIKtrioal Sw
~oonlrOla.
,o 1/10/19 -eo,,,,.,. ....... E~I Sllb ID corrf)lell 1he lighting lavelt on clll)'lghting oontrnla Elamical Sub ID~-tome l'!'IOl'9 edjuttrnanta on ••ne.ded. clllyll0h1ltig oontroll •• nffdad. Pl•oe .. .,.,. on control boll.
~•10ft
... I
tlNl\hy .........
vpdl•r«i .,.,.
.... nufry 10 2019 ·-.. By
FPT
no MC
No MC
No MC
v .. MC
YN MC
No MC
No PC
No EC
No EC
No EC
'""'-i::..:111112019
LEED Commissioning Deficiency Tracking Sheet ·~ \ Healthy BuHd,ngs
Project Project Name: BevMo Update No
Prepared by-Minh Tran Date
January 10. 2019
_, -11 ..... source: (FPTJ Oi5COWf<d dunne Functional Perfonnona, Testing• (PCVJ 01,cowr<d dunnc PfHunctlon•I Testlnc -flatlon. [PC! R-.d by th<! contractor on a PrHunctional Checklist -(FOJ Oi5COWf<d as th<! re>Ult ot a F1'!td Obse<votlon;
lies Code: IA) Accepted by Owner, 1q COrrected, IOI Open; Adlon lly: IAEJ Archltoct/EncinN<, IGCJ -I Contractor, IESl Electrical Sub, ICSJ Controls Sub, (PS) P1umbln1 Sub, (MS( M«mnicol Sub, (OS) Oth<f Sub, (TSJ TAB, (Of!) Ownef', Rop, (VJ Vendor -...... Area /Syntm R.r/1:qptlO ...... Dncrlpllon Tedmlcal Comment RESPONSE I ACTION ITEMS Affects By • Date FPT
1 1/10/19 Roof Top Unit Outside />Jr Gil A missing grill on one of the Roof Top Units Mechanical sub to install a grill Complete no MC
2 1/10/19 Roof Top Units Labeling No labels on Roof Top Units Machanical sub to place labels on Roof Top Units Complete No MC
3 1/10/19 Programmable Thermostats Labeling No labels on programmable lhennostats Mechanical sub to place labels on programmable Complete No MC lhennostals
Roof Top Units -Outside AJr Outside Mr Outside Nr Dampers on Roof Top Units were not opening or GC to ched< with both Mechanical subs to vefify if the 4 1/10/19 Dampers Dampers modulalilg. Tl Mechanical Sub was not demonstrate the operation of outside air dampers Complete Yes MC
operation due to liability between Tl & Shell projects
5 1/10/19 Exhaust Fan lnstalalion No power/controls were inslaled/implemented GC to ched< with BevMo and Team and coordinate with Complete Yes MC subs to <X>fTlpiete the instalation
Settings -Programmable Mechanical sub programmed the settings of oca,pied and Completed by Tl Mechanical Sub. BevMo to adjust 6 1/10/19 Themlostats Settings unoccupied hours / temperattKes based on cal out on the Mechanical sub has <X>fTlpleted the programming based on their business hours No MC
mechanical plans
7 1/10/19 Sink in the Sates ma Leak Leak was found on the sink in the Sales P>rea GC to coordinate with P1umbing sub to check and com,ct the Complete No PC issue
8 1/10/19 Plate on Switches in Sales ma tnstallalion Lighting / Low Voltage switches to be coq,leted and a plate to be SUba to place a plate on the ovenide lighting and low ~ Complete No EC instaled swildles when ln&talation is done
EJedrical Sub competed the temperary lighting schedule from 5:00 BevMo to adµ! the lighting schedule and lighting level based 9 1/10/19 Lighting Schedule Settings AM to 12:00 tw,. Electric:al sub to provide O&M training to BevMo on O&M trainng to be provided by Electric:al Sub No EC
lighting a>ntrols. on their busineSS llouls
10 1/10/19 Lighting Controls Settings Eledrical Sub to complete the lighting levels on~ ccntrols Eledrical Sub to complete some more~ on Complete No EC •• needed daylighting a>ntrols as ,,,,__ Ptace labels on a>ntrol box
("'.nnv nl ~ Lw.18 loo 1-10-19 Page 1 of 1 Prtnt Date: 2/25/2019
✓• EsG1I
A SAFEbuilfCompany
DATE: 5/30/2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2018-0150
PROJECT ADDRESS: 2662 Gateway Rd.
PROJECT NAME: BevMo Tenant Improvement
SET: II
□ APPLICANT
,_P-.J,l.JRIS.
[8J The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck. -,
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
[8J EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacted:,----no Telephone#:
-(0&(1/ ) Email: Date contacted:
Mail Telephone
0 REMARKS:
By: Jason Pasiut
EsGil
Fax In Person
Enclosures:
5/21/2018
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: 3/27/2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2018-0150
✓• EsG1I
A SAFEbui!t Company
SET: I
PROJECT ADDRESS: 2662 Gateway Rd.
PROJECT NAME: BevMo Tenant Improvement
0 APPLICANT /a JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
[g] The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
0 The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
[g] The applicant's copy of the check list has been sent to:
Rob Boucke
0 EsGil staff did not advise the applicant that the plan check has been completed.
[g] EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Rob Boucke Telephone#: 720-529-8768
Date contacted: 3/2, /it"(by:~ Email: rboucke@mcgarchitecture.com
~ Telepho;;;-_!ax In Person
0 R RKS:
By: Jason Pasiut
EsGil
3/20/2018
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
~arlsbad CBC2018-0150
3/27/2018
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK#.: CBC2018-0150
OCCUPANCY: M, S2
TYPE OF CONSTRUCTION: VB
ALLOWABLE FLOOR AREA: within
SPRINKLERS?: YES
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 3/19/2018
DATE INITIAL PLAN REVIEW
COMPLETED: 3/27/2018
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
USE: Retail Sales
ACTUAL AREA: 7 ,856sf
STORIES: 1
HEIGHT: unchanged
OCCUPANT LOAD: 114
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 3/20/2018
PLAN REVIEWER: Jason Pasiut
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2016 CBC, which adopts the 2015 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list {or a copy} where each
correction item has been addressed, i.e., plan sheet number. specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
C.arlsbad CBC2018-0150
3/27/2018
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Jason Pasiut
PLAN CHECK#.: CBC2018-0150
DATE: 3/27/2018
BUILDING ADDRESS: 2662 Gateway Rd.
BUILDING OCCUPANCY: M, S2
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
7856 46.51
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction C.Ode cb By Ordinance
---------------,
1~~7 u~c B~~~!ng Permit Fe~--~_.}
Type of Review 0 Complete Review
Reg. VALUE
Mod.
D Structural Only
D Repetitive Fee ------;-i Repeats _,
□ Other
D Hourly
EsGII F-
1-----------11 Hr. @ *
Comments:
($)
365,383
365,383
$1,570.36!
$1,020.731
$895.111
Sheet 1 of 1
Carlsbad CBC2018-0150
3/27/2018
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one
of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-
2700. The City will route the plans to EsGil and the Carlsbad Planning, Engineering and
Fire Departments.
2. Bring IlYQ corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake
Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of
plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by EsGil is complete.
• WALK IN COOLER
1. Provide the manufacturer standard plans and installation instructions/listing
information for the cooler walls and refrigeration equipment being proposed.
CMC 935.
a) Show electrical loads and show that the equipment meets UL 471 and 427.
b) Show connection details for corners and roof including fasteners.
c) Show foam thickness and flame-spread information.
2. Show location of indirect drain / floor sink and detail drain pipe size and required
airgap. CPC418.4.
3. Refrigerated Spaces that are less than 3,000 square feet shall meet the
requirements of the Appliance Efficiency Regulations for walk-in coolers or
freezers contained in the Appliance Efficiency Regulations (California Code of
Regulations, Title 20, Sections 1601 through 1608). Note on the plans whether
this installation meets these requirements. CEC 120.6 (a)
4. Will there be or is there a floor drain within the cooler? CPC 801.3.2.
5. Please note or show that all electrical penetrations into the cooler shall be sealed
per section 300-7 of the NEC.
6. Please provide a roof plan showing the location of the new condensing unit.
• STRUCTURAL
7. Please provide Special Inspection program information for SI that may be
proposed for the racks that exceed 8'. CBC 1705.12.7.
Nextpage
Carlsbad CBC2018-0150
3/27/2018
• ELECTRICAL
8. A GFCI protected receptacle outlet is required within 25 feet and on the same
level as the mechanical equipment (heating, air-conditioning, and refrigeration
equipment). Please include on the plans. NEC 210.63.
• END OF REVIEW
To speed up the review process, please note on this list (or a copy} where each
correction item has been addressed, i.e., plan sheet, note or detail number, calculation
page, etc.
Please indicate here if any changes have been made to the plans that are not a result
of corrections from this list. If there are other changes. please briefly describe them
and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate: □ Yes □ No
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review
items, please contact Jason Pasiut at Esgil. Thank you.
Sl'ECIAL PRODUCTS
TANK.SUPPORTS
MACHINERY
RACICBLOOS
SHEDS
MEZ1.ANtNES
F0011NOS
CONVEYORS
TALL SUPPORTS
HEADElt STEEL
SORT PLATFORM
PICK MODULES
ROOFVERD'lCATION
I 130 E. Cypress St
•• Q.~
I!::::=#=~~~~~~
l\lATEIUt.LHAND RING
STORAGE RACKS
SELECTIVE
DRIVE-IN
PUSH BACK
FLOWP.ACK
CANTILEVER
OTHER SERVICES
SEISMIC ANALYSIS
PERMIT ACQUISITION
EGR.ESS PLANS
ST ATE A!'PROV A!.S
PRODUCT TES'nNG
Licensed In All 50 States
LIGHT DUTY STORAGE FIXTTJRES
FOR
BevMo!
2662 GATEWAY ROAD., SUITE #155
CARLSBAD, CA 92009
JOB #:18-0484
SALE. FATEEN, P.E.
315/2018
EXPIRES
OEC 3 l 2019
SHELVING
METAL
METALJWOOD
MOVABLE
OONDOLAS
LOCKW
CAlWALKS
Covina CA 91724 TEL : 909-869-0989
SPECIALS PRODUCTS
Sl!UITLES
VLM
CAROUSELS
VRC
MODULAR. omCES
FENCES
,,!>l
""' •· .
'"'
cec2.o ,s,-o,so
SEIZMIC
INC. PROJECT BEVMOI
FOR BEVMO!
MATERIAL HANDLING ENGINEERING
TEL: (909) 869--0989 / FAX: (909) 869--0981
1130 E CYPRESS STREET, COVINA, CA 91724
SHEET NO. 2
CALCULATED BY TB
DATE 3/5/2018
MULTIFUNCTION UNIT ANALYSIS
PROJECT SCOPE:
PROVIDE SEISMIC ANALYSIS DF LIGHT DUTY STORAGE RACK TO CONFORM TO THE REGULATIONS SET BY
THE 2016 CBC. CRITICAL CONFIGURATION ANALY2ED.
PARAMETE :
THE LIGHT DUTY STORAGE FIXTURE USED IN THIS PROJECT CONSISTS OF GONDOLA TYPE SHELVING
COMPONENTS. THE STABILITY OF THE SHELVING DEPENDS ON THE BRACED FRAME (PEG BOARDS AND
HORIZONTAL BRACES) ALONG THE LONGITUDINAL DIRECTION. ALONG THE TRANSVERSE DIRECTION,
THE SHELVING RELIES ON A CANTILEVER FRAME SYSTEM FOR STABILITY.
-SEISMIC
-MAIN STEEL
• ANCHOR
-SLAB
-SOIL
V= (2/3) x Fax Ss x Ix Ws / R
Fy = 36,000 PSI
3/8" 121 x 2-5/16" MIN. EMBED. HILT! KB-TZ WEDGE ANCHOR (ICC ESR-1917)
5 IN x 2,500 PSI
500 PSF
---N.ib ,✓ '~
I , ' ,
PARllClE
BOARD
SHELF SHELVING COMPONENTS:
1 = UPRIGHT
Con ur ti ns:
48"W x 24"0 x 102"H
36'W X 18"0 X 102"H
Levels
6
s
3 = ANCHORS
4 = ANCHOR PLATE
7 = BASE DECK
9= REAR BEAM
10 = FRONT BEAM
11 = SUPPORT BEAM
14 = BASE DECK CONNECTOR
15 = SHELF SUPPORT
Loads
lOOLB/LVL
100 LB/LVL
CRITICAL
SEIZMIC
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909) 869--0989 / FAX: (909) 869-0981
1130 E CYPRESS STREET, COVINA, CA 91724
PROJECT
FOR
BEVMOI
BEVMOI
SHEET NO. 3
CALCULATED BY TB
DATE 3/5/2018
LOADS & SEISMIC DISTRIBUTION: MULTIFUNCTION UNIT ANALYSIS
V = (2/3) x Fax Ss x Ix Ws / (R) TYPICAL MULTI-FUNCTION FIXTURI:
F"" Wl~ -ffi .. Ss = 1.039 ~ I Fa= 1.0844 Rgond. = 3
I= 1 Rtrans.multi. = 4 II
SDS = 0.751127733 Rlong. = 4
.,_..
n
DL = 10 LB rr LL-cant. = 100 LB #ofLVLS = S e)TYP.
LL-top= 100 LB # of LVLS = 1 c:=
GONQOLA
Wg = (0.67*wLL+wDL) x #LVL
,.
•" """"' ""-"·
= 385 LB ''""' = -,,
V(max) = (2/3) x 1.0844 x 1.039 x 1 x Wg / (R ) -= 0.751 W/R
I 1; I
-'
MULTI-UNIT top LEVEL ' , ...
Wm= (0.67 x wLL+wDL) x #LVL Iii '@ = 77LB " mONTIIEW ......
V(min) = (2/3) x 1.0844 x 1.039 x 1 x Wm/ (R)
= 0.75 W/R
Vtrans.(g) = 0.250 W <==Wg+Wm Vtrans.(m) = 0.188 Wg
= 116 LB = 7 LB
INTERIOR COLUMNS ARE TAKING HALF THE LOADS
Vlong. = 0.188 w <==Wg+Wm WITH REGARDS TO THE TOP LEVEL ONLY AND THE
= 87LB REST BY THE (2) EXTERIOR COLUMNS.
LEVEL hx wx hxwx Filtrans,J FJ!lono.l Movt.
l 19.3 IN 110 LB 2,118 IN-LB 7LB 5 LB 127 IN-LB
2 33.31N llOLB 3,658 IN-LB llLB 9 LB 378 IN-LB
3 47.31N 110LB 5,198 IN-LB 16 LB 12 LB 763 IN-LB
4 61.31N llOLB 6,738 IN-LB 21LB 16LB 1,283 IN-LB
5 75.3 IN llOLB 8,278 IN-LB 261B 19 LB 1,936 IN-LB
6 102.0 IN 110 LB 11,220 IN-LB 35 LB 26 LB 3,558 IN-LB
660LB 37.208 IN-LB 116 LB 87 LB 8,046 IN-LB
TRAN~VERSE ANALYSIS: d = 18.0 IN
Ptotal(g) = 385 LB Ptotal(m) = 60 LB <== Wm/4 + V(m) x 102/dshelf
Mcol(g) = Movt = 8,046 IN-LB Mcol(m) = 737 IN-LB
SEIZMIC
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909) 869-0989 / FAX: (909) 869-0981
1130 E CYPRESS STREET, COVINA, CA 91724
COLUMN ANALYSIS (TRANSVERSE) Back Post
SECTION PROPERTIES BASED ON THE EFFECTIVE SECTION.
P= (1+-0.115.,)DL+-0.7S•(l+-0.14SoslPL
= S62LB
M= 0.7S•0.7*Mselsmlc
= 4,224 IN-LB
Kxl.x/rx = 2.1 *102 IN/1.07 IN
= 200.2 <=== (Kl/r)max
Kyly/ry = 1 *16 IN/0.6 IN
= 26.7
Fe= n•2E/(KL/r)max•2
= 7.3 KS!
Fy/2= 18.0 KS!
SINCE, Fe < Fy/2
THEN, Fn= Fe
FLEXURE
= 36 KSl*[l-36 KSl/(4*7.3 KSI)]
= 7.3 KS!
Pn= Aeff*Fn
= 6,975 LB
Oc= 1.92
Pa= Pn/Oc
= 6975 LB/1.92
= 3,633 LB
P/Pa= 0.15 > 0.15
CHECK: P/Pa + (Cmx•Mx)/(Max•µx) S 1.00
P/Pao + Mx/Max S 1.00
Pno= Ae*Fy
= 0.96 !N•2 *36000 PSI
= 34,560 LB
Pao= Pno/Oc
= 34560 LB/1.92
= 18,000 LB
Myield=My= Sx*Fy
THUS,
= 0.83 IN•3 • 36000 PSI
= 29,880 IN-LB
Max= My/Of
= 29880 IN-LB/1.67
= 17,892 IN-LB
Per= n•2El/(KL)max•2
= n•2•29500 KSl/(2.1 *102 IN)•2
= 6,917LB
PROJECT
FOR
SHEET NO.
CALCULATED av
DATE
BEVMO!
BEVMOI
4
TB
3/5/2018
SECTION PROPERTIES
Aeff = 0.960 !N•2
Ix= 1.090 IN'4
Sx = 0.830 !N•3
rx = 1.070 IN
ly = 0.340 IN'4
Sy= 0.380 IN'3
ry = 0.600 IN
Kx = 2.1
Lx = 102 IN
Ky= 1.00
Ly= 16.0 IN
Fy= 36 KSI
E= 29,500 KS!
Of• 1.67
Cmx= 0.85
Cb= 1.0
µx= {1/(1-(0c*P/Pcr)]}"-l
= {l/[1·{1,92*0 LB/6917 LB)]}"-1
= 1.00
(562 LB/3633 LB)+ (0.85*4224 IN-LB)/(17892 IN-LB*1) =
(562 LB/18000 LB)+ (4224 IN-LB/17892 IN-LB)=
0.36
0.27
< 1.00, OK
< 1.00, OK
SEIZMIC
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909) 869-0989 / FAX: (909) 869-0981
1130 E CYPRESS STREET, COVINA, CA 91724
COLUMN ANALYSIS (TRANSVERSE) Front Post
SECTION PROPERTIES BASED ON THE EFFECTIVE SECTION.
P. 60 LB
M= 5161N-LB
KxlJ</rx= 2.1•102 IN/0.77 IN
= 278.2
KyLy/ry = 2.1 *102 IN/0.611 IN
= 350.6 <== (Kl/r)max
Fe= n•2E/(KL/r)max•2
= 2.4 KSI
Fy/2= 18.0 KSI
SINCE, Fe < Fy/2
THEN, Fn= Fe
FLEX RE
= 36 KSl*[l-36 KSl/(4*2.4 KSI)]
= 2.4 KSI
Pn= Aeff*Fn
= 854 LB
Cle= 1.92
Pa= Pn/Oc
= 854 LB/1.92
= 445 LB
P/Pa= 0.14 < 0.15
CHECK: P/Pa + Mx/Max s 1.00
Pno= Ae*Fy
= 0.361INA2 *36000 PSI
= 12,978 LB
Pao= Pno/Oc
= 12978 LB/1.92
= 6,759 LB
Myield=Mr-Sx*Fy
THUS,
= 0.244 IN•3 • 36000 PSI
= 8,795 IN-LB
Max= My/Of
= 8795 IN-LB/1.67
= 5,266 IN-LB
Per= n•2El/(KL}max•2
= n•2*29500000 PSl/(2.1*102 IN)•2
= 1,385 LB
PROJECT
FOR
BEVMOI
BEVMOI
SHEET NO. S
CALCULATED BY TB
DATE 3/5/2018
P.
SECTION PROPERTIES
µx= {1/[1-{0c*P/Pcr)])A-1
Aeff = 0.361 IN•2
Ix= 0.218 IN•4
Sx = 0.244 IN•3
rx= 0.770 IN
ly = 0.135 IN•4
Sy = 0.149 IN•3
ry = 0.611 IN
Kx = 2.1
Lx = 102.0 IN
Ky= 2.1
Ly= 102.0IN
Fr-36 KSI
E= 29,500 KSI
Clf= 1.67
Cmx= 0.85
Cb= 1.0
= {1/[1-(1.92*60 LB/1385 LB)])A-1
= 0.92
(60 LB/445 LB)+ (516 IN-LB/5266 IN-LB)= 0.11 < 1.00,OK
SEIZMIC
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909} 869-0989 / FAX: (909} 869-0981
1130 E CYPRESS STREET, COVINA, CA 91724
BASE AND ARM ANALYSIS
ARM CHECK:
CHECK TENSION CAPACITY:
ARM SPAN = 22.0 IN
LOAD = 110 LB/LEVEL
M = LOAD x (ARM SPAN/2}
= 110 LB/LEVEL x 22 IN/2
= 1,210 LB-IN
ASSUME ONLY THE TOP CLIP IN TENSION
TENSION CAPACITY = T = 0.6Fy x A
= 0.6 x 36000 PSI x 0.09 IN'2
= 1,944 LB
MOMENT CAPACITY = T x d
= 1944 LB x 1.125 IN
PROJECT BEVMO!
FOR BEVMOI
SHEET NO. 6
CALCULATED BY TB
DATE 3/5/2018
= 2,187 LB-IN > 1210 LB THEREFORE OK
CHECK FOR SHEAR CAPACITY:
Varm = LOAD/2
= (n'2E/(Kl/r}max•2 + }/ 2
= S5 LB/LEVEL
SHEAR CAPAOTY = 0.4Fy • A
= 0.4 x 36000 PSI X 0.09 IN'2
= 1,296 LB > SS LB THEREFORE OK
Mcol(total) = 4,224LB-IN
fb = Mcol(total}/Sx
= 4224 LB-IN/ 1.18 IN'3
= 3,580PSI
Fb = 0.6 x 36000 PSI
= 21,600PSI
fb/Fb = 3580 PSI / 21600 PSI
= 0.17 < 1.00 THEREFORE OK --..,..
A= 0.090 IN'2
Fy = 36,000 PSI
d = 1.125 IN
Sx = 1.18 IN•3
Fb = 36,000PSI
SEIZMIC
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909) 869-0989 / FAX: (909) 869-0981
1130 E CYPRESS STREET, COVINA, CA 91724
MULTI-FUNCTION SHELVING ANALYSIS
CONNECTION CHECK
Mconn = Vcol • H
= 737 LB-IN
SHEAR CAPACITY OF TAB:
Pallow = 0.4Fy • AREA
= 0.4 X 36000 PSI x 0.0788 IN•2
= l,134LB
Mallow= Pallow • dist.
= ((1134 LBx4 IN)+ 1134 LB x2 IN /2)
= 5,670 LB-IN > 737 LS-IN THEREFORE OK
BEAM CHECK
Mbeam(seis) = 737 LB-IN
Mbeam(stat) = wl•2/8
w = 77 LB/LEVEL
= 0.802 LB/IN
Mbeam(stat) = 0.802 LB/IN x 48IN•2 / 8
= 231 IN-LB
Mbeam(total) = Mbeam(stat) + Mbeam(seis)
= 968 IN-LB
fb = Mbeam(total)/Sx
= 968 LB-IN/ 0.894IN•3
= 1,083 PSI
Fb= 0.6x Fy
= 21,600 PSI
lb/Fb= o.os < 1.0 THEREFORE OK
PROJECT BEVMOI
FOR BEVMO!
SHEET NO. 6
CALCULATED BY TB
DATE 3/5/2018
Fy = 36,000 PSI
AREA OF TAB= 0.0788 IN•2
Sx = 0.8940 IN•3
LENGTH OFTAB = 4.0 IN
LONGTITUDINAL LENGTH OF BEAM= 48.0IN
SEIZMIC
INC.
MATERIAL HANDLING ENGINEERING
TEL: (909) 869-0989 / FAX: (909) 869-0981
1130 E CYPRESS STREET, COVINA, CA 91724
OVERTURNING ANANLYSIS
FUU Y LOADED:
Puplift = [(OMovt-0.9*Mst) / d] x # of occurrence
= (116091-0.9*4158] IN-LB/ 18 IN) x 1
= 686 LB
INTERACTION EQN. PER 4.2.Z OF ICC ESR-1917
(686 LB/ 1580 LB) + (58 LB/ 1800 LBJ =
TOP LOADED:
Vtop = 34 LB
LEVEL hx wx hxwx
1 19.3 IN 10 LB 193 IN-LB
2 33.3 IN lOLB 333 IN-LB
3 47,3 IN 10 LB 473 IN-LB
4 61.3 IN 10 LB 613 IN-LB
5 75.3IN 10 LB 753 IN-LB
6 102.0 IN 87 LB 8,874 IN-LB
11,237 IN-LB
Puplift = [(OMovt -0.9*Mst) / d] x # of occurrence
= ([6327 IN-LB -0.9*1233 IN-LB)/ 18 IN) x 1
= 290 LB
INTERACTION EQN. PER 4.2.2 OF ICC ESR-1917
[290 LB/ 1580 LBJ + (34 LB/ 1800 LBJ =
PROJECT
FOR
BEVMOI
BEVMO!
SHEET NO. 7
CALCULATED BY TB
DATE 3/S/2018
ALLOWABLE TENSION = 790 LB
ALLOWABLE SHEAR= 900 LB
# OF ANCHORS/ B.P. = 2
d = 18.0 IN
# OF OCCURRENCE = 1
ANCHOR AT EVERY BAY
O= 2
0.47 < 1.2 THEREFORE OK
Fl(trans.) A(long.) Movt.
lLB 0 LB 11 IN-LB
l LB lLB 34 IN-LB
lLB lLB 68 IN-LB
2LB lLB 115 IN-LB
2 LB 2 LB 173 IN-LB
27LB 21LB 2,763 IN-LB
34 LB 26 LB 3,164 IN-LB
0.19 < 1.2 THEREFORE OK
,.
SAN DIEGO REGIONAL OFFICE USE ONLY -. ;; RECORD ID I HAZARDOUS MATERIALS PLAN CHECK I . . 1.\·· I I QUESTIONNAIRE BP DATE
Business Name Business Contact Telephone I
Beverages & Morel (dba BavMol) Carl Laughlin 925.609.6152
APNt
ProtCI Addn,ss City State Zip Code
26 2 Gateway Road • Suite #155 Ca~sbaa CA 92009 213-262-09-00
Mailing Address City State Zip Code Plan FIie#
1401 WILLOW PASS ROAD, STE 900 CONCORD CA 94520
Project ContlCI Applicant E-mail Teleph!)ne# ..... ---
Rob Boucke (c/o MCG Architecture\ rboucke""~architecture.com 720.529.8768 x514
The lotlowln untlona re 1911111 tho facl I 1clivltle1, NOT the 1pectflc project dncrlptlof:\ C::: \.., '-·· l V 1.-LJ p Illy'
: n cate r ng t tem, r your iness use, process. or ston, any o t e
applicant must contaet the fin, Protaetlon Agency with Jurladldlon pnor to plan submittal.
Occupancy Rating: Mercantile F1clllty'1 Squirt Footagt (lncklding proposed projeCI): 7,856 Sq Ft.
1. EicplosiYe or Blasting Agents 5. Organic Peroxides 9. Water Reaet1ve1
2. Compn,ssed Gases 6. Oxidizers 10. Cryogenics
13. ~ .. ~~-~:,;::~~~\~~~~
14. ~-
3. Flammable/Combustible Liquids 7. Pyrophorlc$ 11. HlghlyToldcorToldc Materials 15. None of These.
4. Flammable Solids 8. Unstable ReaCIIYes 12. Radloactlves
ques ns yes, app ,cant must contact unty o n go 1 , an OlegO, CA 92123.
can (858) 50~700 prior to the Issuance of a building pannlL
FEES ARE REQUIRED Project Completion Data: Jan. 2019 Expected Date of Occupancy: Feb 2019
YES NO (for new conatructlon or n,modeBng projeclil)
1. D l!D Is your buSlnesa listed on the n,ver1eslde of thla form? (check an that apply).
2. D l!D WIit your businesa dispose of Hazardous Substances or Medical Wasta In any amount7
3. D 12:1 WIii your business stOrt or handle Hazanlous Substances In quantlties gn,ater than or equal to 55 gallons, 500
4. D
5. □
8. D
7. □ a. D
pounds and/or 200 cubic feet? lXI WIit. your bUBiness ston, or hlndle carctnogens/raproduetlve toJdns In any quantity?
12:1 ""111 yo..-business I.A an e,dsflntl or Install an underground storage tanl<? li1l Will you, blfslnen store or handle Regulated Substances (CalARP)? i WIH your bullnesa use or lnstaH a Hazardous Waste Tank System (fdle 22, Articie 10)?
.., VWI your busln88S aton, petroleum In tanks or containers at yo..-facility with a total fadtlly alorage capacity equal to
or n,ater than 1,320 allons? CatWomla's Above ound Patroleum Star e Act •
0 CalARP Exempt
lritiall
0 CalARP Required
tnitilll
0 CalARP Complete
1nitia,
P I· DIE UNTY Al POLLUTI N CONTROL IS IC D : Any YES' anlWlr n,qulrM a stamp from APC. D 10124 Old Grove Road, San ego, . (' stamp n,qu,rid If Q1 Yes .lll!I Q3 Yes .lll!I Q4-Q8 No]. The following questions an, Intended
to Identify the maJonty air on ossues at the p annlng stage. Projects may n,quln, additional measures not identified by these questions. For comprehensive requirements contact APCO. Residences are typically ...,mpt, except -those with man, than one building' on the property; slngle building• with mon, than fOII'
dweWng units; townhornes; condos; mixed-commercial use; dallblrata bums; resldencH forming part of a larger project. ['Excludes garages & amall outbuildings.]
YES NO 1. D Kl Will the project dlstllll 180 squan, feet or m0rt of existing building matelials?
2. D ll!I WIit any load supporting structural membl11 bl n,moved? NotlllcaUon may bl n,qulred 1 O working days prtor to commencing demollion.
3. O O (ANSWER ONLY IF QUESTION 1 or 2 IS YES) Has an asbestos survey been perfonned by a Certified Asbestos Consultant or Sile Surveillance
Technician? 4. 0 0 (ANSWER ONLY IF QUESTION 3 IS YES) Based on the survey mutts, will the project disturb any asblslol containing material? NotlflcaUon
may bl required 10 working days prior to commencing asbestos n,moval.
5. □
e. D
\XI VWI the project or associated construetlon equipment emit elr contaminants? See the reverse aide of this form or APCD factsheet
(www.sdapcd.0(90nfol(acls{pem1lts.pdn for typlcal equipment requiring an APCO panntt. 0 (ANSWER ONLY IF QUESTION 5 IS YES) Will the project or associated construetlon equlpmern be located within 1,000 feet of a school
bounda
Briefly describe business actMtlea: Briefly describe proposed project:
BY:
t of my knowledge and belief t e responses made hen,ln an, true and colT8Ct.
' Cht!Jr'1I 0,N =s1:-n-.a7ture-o-:f o=wner--or-:Au-:th:-orlz-:-ed-.--:-•-n-:-t ---
FOR OFFICAL USE ONLY:
DATE: I I
g 1-:J-f /'y
Date
EIEMl'TOR NO FURTHER INfOIUAATION R!QUllll!D Rl!LW!O FOR BUI.DING PfftlllT IUT NOT FOR OCCUPANCY RILEAIEO FOR OCCUPANCY
COUNTY-HMO' APCO COUNTY-HMO APCO COUNTY-HMO APCO
• A stamp In this box Al!ll! 8ll8ll1PIS businesses from completing or updating • Hazardous Materials Business Plan. Other permlttlng requln,ments may still apply,
ELISE ROTHSCHILD
Director
., .. ~
<!Countp of ~an 1!lie~o
DEPARTMENT OF ENVIRONMENTAL HEALTH
FOOD AND HOUSING DIVISION
P.O. BOX 129261, SAN DIEGO, CA 92112-9261
Phone: (858) 505-6659 FAX: (858) 505-6824
1 (800) 253-9933
www.sdcdeh.org
AMY HARBERT
Assistant Director
PLAN APPROVAL SHEET
DBA:BEVMO DA fE: 6/20/18
SITE: 2662 GATEWAY RD #155 CARLSBAD 92009
BUSINESS OWNER: SAA
PC #: DEH20 l8-FFPP-009353
Plans are approved contingent upon the following:
1) Department of Environmental Health -Food and Housing Division {DEH-FHD) stamped plans shall be printed on a
minimum 11" by 17" size paper to scale. Ensure each sheet is the same size and legible. A paper copy of the plans must be
maintained at the jobsite to construct from and available for the Specialist to review at the time of your inspections.
2) Changes to equipment layout, menu, or application must be submitted for approval. Chai;ges made without approval will make the
plan approval null and void.
3) Obtain local Building Department and all applicable agencies permits and approvals PRIOR TO FINAL INSPECTION AND
APPROVAL TO OPERATE BY TIIlS DEPARTMENT.
4) All food and utensil-related equipment shall be ce1tified to applicable sanitation standard~ by an ANSI accredited testing agency.
5) Upon completion of 50%-80% of construction, call (858) 505-6660 to schedu le a mid-in~pection. In lieu of a plumbing inspection
by DEH, ensure that the plumbing is constructed to these standards:
a. Floor sinks shall be installed ½ exposed and equipped with an appropriate grill cowr if no access is provided for cleaning.
b. Drain lines shall slope ¼" per foot, shall not exceed 15' in length and shall terminate a minimum of I" above the floor sink
with a legal air gap or otherwise approved by the enforcing agency. Drain lines shall not intersect walkways or door ways.
c. No condensate drainage of any kind can drain to the mop sink.
d. 3-co·mpartment sinks, preparation sinks, dump sinks, and any other plumbed equipment must drain indirect to a floor sink.
e. Grease traps/interceptors, if required by the local waste water authority must be loc.1ted outside of the food preparation, food
storage, or warewashing areas.
f. Floor surfaces must be sloped I :50 to required floor drains.
g. Conduits of all types shall be installed within walls as practicable. When otherwise i.1 stalled, they shall be mounted or enclosed
in a chase so as to facilitate cleaning.
6) Owners and/or operators must pass an approved and accredited Food Safety Ce1tification course. Proof of successful completion of
this course is to be furnished at the final inspection.
7) All equipment is to be in place and functional. At the time when the final inspection is requested, tbe facility shall have all utilities
operational and all refrigeration shall have an ambient air temperature of38°F or below .ind shall be equipped with a thermometer
accurate to+/-2°F in lhe warmest section of the unit.
8) Seal all cracks, gaps and crevices in counters, cabinets, around metal flashing, sink back splashes, around pipes and cbnduits with
silicone sealant.
9) AN AIR BALANCE REPORT IS REQUIRED IF THE FACILITY HAS VENTIL1, TION HOODS
10) ANY FOOD PROCESSING AREAS MUST BE COMPLETELY ENCLOSED. PERABL
WALL PANELS GARAGE ROLL-UP DOORS OR OTHER MEANS OF RE1'1> ~RI
NOT FULLY ENCLOSED ARE NOT APPROVED.
11) Be advised a licable ·urisdiction re uirements that result in chan
Department of Environmental Health plans.
Plans reviewed by: C. PENN, REHS
revisions to the
CALL (858) 505-6660 AT LEAST 10 WORKING DAYS IN ADVANCE TO SCHEDULE MID AND FINAL INSPECTIONS. A FINAL INSPECTION
MUST BE CONDUCTED AND AN ENVIRONMENT AL HEAL TH PERMIT SHALL BE ISSUED PRIOR TO OPENING AND OPERATING THIS FOOD
ESTABLISHMENT.
"Environmental and public health through leadership, partnership and science"