HomeMy WebLinkAbout2669 GATEWAY RD; 102; CB090465; Permit04-29-2009
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Commercial/Industrial Permit Permit No
, Building Inspection Request Line (760) 602-2725
CB090465
Job Address
Permit Type
Parcel No
Valuation
Occupancy Group
Project Title
2669 GATEWAY RD CBAD St 102
Tl Sub Type
2131912200 Lot#
$42,447 00 Construction Type
HAPPINESS NAILS-1235 SF RETAIL
TO NAIL SALON
COMM
0
NEW
Applicant
HOI TRAN
323 ALAMO WAY
OCEANSIDE CA 92057
7146230773
Status
Applied
Entered By
Plan Approved
Issued
Inspect Area
Plan Check*
Owner
LNR CPI BRESSI RETAIL L L C
C/0 LNR PROPERTY CORP
4350 VON KARMAN AVE #200
NEWPORT BEACH CA 92660
ISSUED
03/23/2009
LSM
04/29/2009
04/29/2009
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
Pot Water Con Fee
Meter Size
Add'l Pot Water Con Fee
Reel Water Con Fee
Green Bldg Stands (SB1473) Fee
$372 57 Meter Size
$0 00 Add'l Reel Water Con Fee
$24217 Meter Fee
$0 00 SDCWA Fee
$0 00 CFD Payoff Fee
$891 PFF (3105540)
$0 00 PFF (4305540)
$0 00 License Tax (3104193)
$000 License Tax (4304193)
$000 Traffic Impact Fee (3105541)
$0 00 Traffic Impact Fee (4305541)
$0 00 PLUMBING TOTAL
$0 00 ELECTRICAL TOTAL
$0 00 MECHANICAL TOTAL
$0 00 Master Drainage Fee
Sewer Fee
$0 00 Redev Parking Fee
$0 00 Additional Fees
$1 00 HMP Fee
TOTAL PERMIT FEES
$000
$000
$000
$000
$000
$000
$000
$000
$000
$000
$11800
$35 00
$24 00
$000
$000
$000
$000
99
$801 65
Total Fees $801 65 Total Payments To Date $801 65 Balance Due $000
BUILDING PLANS
.IN STORAGE
.ATTACHED
Inspector
FINAL APPROVAL
Date /? / "2-1I
NOTICE Please take NOTICE that apnroval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions" You haJJe 90 days from the date this permit was issued to protest imposition of these fees/exactions If you protest them, you musl
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3 32 030 Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project NOR DOES IT APPLY to any
fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitations has previously otherwise expired
City of Carlsbad
1635 Faraday Ave , Carlsbad, CA 92008
760-602-2717 / 2718/2719
Fax 760-602-8558
www carlsbadca gov
Building Permit Application
Plan Check No
Est Value
Plan Ck Deposit
Date
JOB ADDRESS
_ZrCT/PROJ?
! DESCRIPTION OF WORK Include Square Feet of Affected Area(s)
« BEDROOMS
SUITES/SPACE S/UNIT'J
U BATHROOMS TENANT BUSINESS NAME CCKSTR TYPE OCC GROUP
EXISTING USE PROPOSED USE GARAGE (SF)
CONTACT NAME (If Different Fom Applicant)
ADDRESS — f J
"2> Z'^ /?^7/27ft LUfat.-.
CTTY {/ STATE ZIP
flf> ?/://>-& (Se . /?A *7~2.Q^f-
EMAIL
PROPERTY OWNER NAMELLfL CJ?/ Khe&t ££:-/-&,&., ttc.
ADDRESS
^/27T fcV^/<w6>^- £300**. ^ 2/0
CITY STATE " ZIP
PHONE V : FAX
EMAIt> " "
ARCH/DESIGNER NAME 81 ADDRESS STATE LIC It
PATIOS (SF) DECKS (SF) FIREPLACE AIR CONDITIONING FIRE SPRINKLERS
YES D tt NO Q YES D NO D YES D NO D
APPLICANT NAME
ADDRESS
CITY STATE ZIP
PHONE FAX
EMAIL
CONTRACTOR BUS NAMC
ADDRESS - — /• ^/
CITY ' ST/TF "n
PHONED : FAX
EMAIL
STATE LIC i' CLASS CITY BUS 1 1C *
ec 70! 1 5 Business and Professions Code Any City or County which requires a permit to construct alter, improve demolish or repair any structure, prior to its issuance also requires the applicant for such permit to file a ngned statement that he is
censed pursuant to the provisions of the Contractors License Law {Chapter 9 commending with Section 7000 of Division 1 of the Business and Professions Code} or that he is exempt there from and the basis for the alleged exemption Any violation of
Workers' Compensation Declaration / hereby affirm under penally ot perjury one of the following declarations
C] I have and will maintain a certificate of consent to self insure lor workers compensation as provided by Section 3700 of the Labor Code for the performance of the work for which this permit is issued
C!) I have and will maintain workers compensation as required by Section 3700 of the Labor Code for the performance of the work for which this permit is issued My workers compensation insurance carrier and policy
number are Insurance Co Policy No Expiration Date
This section need not be completed if the permit is for one hundred dollars (S100) or less
I O Certificate of Exemption I certify that in the performance of the work for which this permit is issued I shall not employ any person in any manner so as to become subject to the Workers Compensation Laws of
I California WARNING Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
! addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees
i J& CONTRACTOR SIGNATURE DATE
I hereby affirm that I am exempt from Contractors License Law for the following reason
Jft^ I as owner of the properly or my employees with wages as their sole compensation will do the work and the structure is not intended or offered for sale (Sec 7044 Business and Professions Code The Contractor s
License Law does not apply to an owner of property who builds or improves thereon and who does such work himself or through his own employees provided that such improvements are nol intended or offered for
sale If however the building or improvement is sold within one year of completion the owner builder will have the burden of proving lhat he did not build or improve for the purpose of sale)
D I as owner of the property am exclusively contracting with licensed contractors to construct the project (Sec 7044, Business and Professions Code The Contractor s License Law does not aoply to an owner of
property who builds or improves thereon and contracts for such projects with contractor(s) licensed pursuant to the Contractor s License Law)
n I am exempt under Section Business and Professions Code for this reason
1 I personally plan to provide the major labor and materials for construction of the proposed properly improvement D Yes Cl No
2 I (have / have not) signed an application for a building permit for the proposed work
3 I have contracted with the following person (firm) to provide the proposed construction (include name address / phone / contractors license number)
4 I plan to provide portions of the work but I have hired the following person to coordinate supervise and provide the major work (include name / address / phone / contractors license number)
5 I will provide some of the work but I have contracted (hired) the following persons to provide tho work indicated (include name / address / phone / type of work)
^PROPERTY OWNER SIGNATURE DATE
Is the applicant or future building occupant required to submit a business plan acutely hazardous materials registration form or risk management and prevention program under Sections 25505 25513 or 25534 of the
Presley Tanner Hazardous Substance Account Acf Cl Yes Cl No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district' D Yes Cl No
Is the facility to be constructed within 1 000 feet of the outer boundary of a school site7 Cl Yes D No
IF ANY OF THE ANSWERS ARE YES. /
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec 3097 (i) Civil Code)
Lender's Name Lender's Address
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate I agree to comply with all City ordinances and State laws relating to building construction
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes I ALSO AGREE TO SAVE. INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS. COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT
OSHA An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stones in height
EXPIRATION Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized by such permit is not commenced within
^APPLICANT'S SIGNATURE DATE
City of Carlsbad
Final Building Inspection
Dept Building Engineering Planning CMWD St Lite
Plan Check #
Permit #
Project Name
Address
CB090465
HAPPINESS NAILS-1235 SF RETAIL
TO NAIL SALON
2669 GATEWAY RD #102 Lot
Date 05/18/2009
Permit Type Tl
Sub Type COMM
0
Contact Person NA
Sewer Dist CA
Phone 7147579050
Water Dist CA
Inspected .
Bv C/U\J\.C /
vInspected A
Bv U
Inspected
Bv
Comments
Date
Inspected ^
Date
Inspected
Date
Inspected
1 ' '( 0\ Aooroved ^
Approved
Approved
7"
Disapproved
Disapproved
Disapproved
CITY OF CARLSBAD
ELECTRIC AND GAS METER CLEARANCE
INTER-DEPARTMENT
ADDRESS:
S E O Service Equipment Only
Reason, If Denied
ELECTRIC METER
GAS METER
COMMERCIAL
RESIDENCE
NEW SERVICE
RELOCATE
TSPB
TEMP P/P
UP-GRADE
TEST METER
IRR PEDESTAL
COMMERCIAL
RESIDENCE
TEST METER
YES
NO
YES
NO
YES
NO
Time
Called In By Date Time
Called In To
City of Carlsbad Bldg Inspection Request
For 05/18/2009
Permit* CB090465
Title HAPPINESS NAILS-1235 SF RETAIL
Description TO NAIL SALON
Inspector Assignment PY
2669 GATEWAY RD
102 Lot 0
Type Tl Sub Type COMM
Job Address
Suite
Location
OWNER LNR CPI BRESSI RETAIL L L C
Owner
Remarks
Phone 7147579050
Inspector
Total Time
CD Description
19 Final Structural
29 Final Plumbing
39 Final Electrical
49 Final Mechanical
Requested By NA
EntepadBy CHRISTINE
Act Comments
Comments/Notices/Holds
Associated PCRs/CVs Original PC#
Inspection History
Date Description Act Insp Comments
05/04/2009 17 Interior Lath/Drywall AP PY
05/04/2009 23 Gas/Test/Repairs AP PY
05/01/2009 21 Underground/Under Floor AP PY
05/01/2009 84 Rough Combo AP PY
EsGil Corporation
In ^Partnership with government for (BuMing Safety
DATE 4/28/09 a APPLICANT
JURISDICTION City of Carlsbad a PLAN REVIEWER
a FILE
PLAN CHECK NO 09-0465 SET III
PROJECT ADDRESS 2669 Gateway Rd Suite 102
PROJECT NAME Happiness Nails & Spa - TI
IXl The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
The applicant's copy of the check list has been sent to
Esgil Corporation staff did not advise the applicant that the plan check has been completed
Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Telephone #
Date contacted (by ) Fax #
Mail Telephone Fax In Person
REMARKS
By Doug Moody Enclosures
EsGil Corporation
D GA D MB D EJ D PC LOG
9320 Chesapeake Drive, Suite 208 * San Diego, California 92123 + (858)560-1468 + Fax (858) 560-1576
EsGil Corporation
In Partnership with government for <Buifding Safety
DATE 4/22/09 a=4BEiJCANT
_
JURISDICTION City of Carlsbad a PLAN REVIEWER
a FILE
PLAN CHECK NO O9-0465 SET II
PROJECT ADDRESS 2669 Gateway Rd Suite 102
PROJECT NAME Happiness Nails & Spa - TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
XI The check list transmitted herewith is for your information The plans are being held al Esgil
Corporation until corrected plans are submitted for recheck
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
The applicant's copy of the check list has been sent to
Hoi Tran
323 Alamo Way, Oceanside CA 92057
Esgil Corporation staff did not advise the applicant that the plan check has been completed
Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Hoi Tran Telephone # 714-623-0773
Date contacted^W^f (b^^ Fax #
Mailv' Telephone /^ Fax In Person
REMARKS
By Doug Moody Enclosures
EsGil Corporation
D GA D MB D EJ D PC 4/20/09
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 4 (858)560-1468 + Fax (858) 560-1576
Carlsbad O9-O465
4/22/09
RECHECK CORRECTION LIST
JURISDICTION City of Carlsbad PLAN CHECK NO 09-O465
PROJECT ADDRESS 2669 Gateway Rd Suite 1O2 SET II
DATE PLAN RECEIVED BY DATE RECHECK COMPLETED
ESGIL CORPORATION 4/20/09 4/22/O9
REVIEWED BY Doug Moody
FOREWORD (PLEASE READ).
This plan review is limited to the technical requirements contained in the Building Code,
Plumbing Code, Mechanical Code, Electrical Code and state laws regulating energy
conservation, noise attenuation and disabled access This plan review is based on regulations
enforced by the Building Department You may have other corrections based on laws and
ordinances enforced by the Planning Department, Engineering Department or other
departments
The following items listed need clarification, modification or change All items must be satisfied
before the plans will be in conformance with the cited codes and regulations The approval of
the plans does not permit the violation of any state, county or city law
A Please make all corrections on the original tracings and submit new complete sets of
prints to
B To facilitate recheckmg, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans
C The following items have not been resolved from the previous plan reviews The original
correction number has been given for your reference In case you did not keep a copy of
the prior correction list, we have enclosed those pages containing the outstanding
corrections Please contact me if you have any questions regarding these items
D Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list If there are other changes, please briefly describe them arid where
they are located on the plans Have changes been made not resulting from this list"
QYes QNo
City^f Carlsbad 09-O465
4/22/09
Please make all corrections on the original tracings, as requested in the correction list
Submit three sets of plans for commercial/industrial projects (two sets of plans for
residential projects) For expeditious processing, corrected sets can be submitted in one of
two ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave , Carlsbad, CA 92008, (760) 602-2700
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments
2 Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468 Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete
These corrections are in response to items not fully addressed or as the result of
information provided, the text in bold print indicates the unresolved issue
4 Please provide the listing and installation in for the new pedicure chairs
5 Provide complete plumbing plans, including
a) Complete the dram, waste and vent plans to show all fixtures (The standpipe for
the washer)
b) Provide gas line plans and calculations for the new gas water heater, showing
pipe lengths and gas demands UPC Section 1217 0 No information provided.
6 Ploase indicate the water connections to the pedicure chairs to be equipped with
approved reduced pressure back flow prevention on the water line plan Please clarify
the plumbing plans to indicate what the direct waste receptor is? Where and what is
the direct waste receptor shown on the water line plan9
7 Detail the water heater flue (vent) terminations as per UPC, Section 5170 Minimum 8
foot from a vertical wall or similar obstruction (parapet wall, screen wall building wall) or
extend vent termination to above tho top of the wall No information provided
8 Ploase revise the plumbing plans to show the required clean-outs per section 70 7 and
719 of the UPC Please provide a cleanout at the new washer
9 Ploase provide electrical plans No plans provided
10 Ploaoo provide panel schedules, indicate new and existing loads No panel schedules
were provided
11 Ploase revise the electrical plans to show the dedicated roceptacles for the pedicure
chairs to be GFCI protoctod The plans are incomplete, please show the circuits
City.of Carlsbad 09-O465
'4/22/09
feeding the new pedicure chairs and indicate the receptacles that are GFCI
protected.
12 When new rooms or spaces are constructed and the existing mechanical system is not to
be altered other than relocation of existing duct work, please note or show mechanical
ventilation will be provided capable of supplying the minimum rate of outside air required
per minute per occupant as shown in Table 4-1 of the UMC (supply air to waxmq and
break rooms) The plans are unchanged, please correct
13 Please revise the plans to show the exhaust fan for the nail salon to provide the required
ventilation per Table 4-4 of the mechanical code ( 6 cfm/sqft a minimum of 535 cfm)
Plans are unchanged.
14 When alterations, structural repairs or modifications or additions are made to an existing
building, that building, or portion of the building affected, is required to comply with all of the
requirements for new buildings, per Section 1134B 2 These requirements apply as follows
a) Existing sanitary facilities that serve the remodeled area must be shown to comply
with all accessibility features It is unclear from the plans if the restrooms
servicing the tenant improvement are disabled accessible, please provide a
dimensioned restroom plans showing the restroom to be accessible
compliant.
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i e , plan sheet, note or detail number, calculation page, etc
Please indicate here if any changes have been made to the plans that are not a tesult of
corrections from this list If there are other changes, please briefly describe them and
where they are located in the plans
Have changes been made to the plans not resulting from this correction list? Please
indicate
Yes Q No a
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123, telephone number of 858/560-1468, to perform
the plan review for your project If you have any questions regarding these plan review
items, please contact Doug Moody at Esgil Corporation Thank you
EsGil Corporation
In (partnership ivitfi government for Quitting Safety
DATE 4/1/09
JURISDICTION City of Carlsbad
PLAN CHECK NO 09-0465 SET I
PROJECT ADDRESS 2669 Gateway Rd Suite 102
PROJECT NAME Happiness Nails & Spa - TI
PLAN REVIEWER
a FILE
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
XI The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
The applicant's copy of the check list has been sent to
Hoi Tran
323 Alamo Way, Oceanside CA 92057
Esgil Corporation staff did not advise the applicant that the plan check has been completed
XI Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Hoi Tran Telephone # 714-623-0773
Date contacted ^/3/Ol (by^£0) Fax #
Mail v/xte|ephone v Fax In Person
REMARKS
By Doug Moody Enclosures
EsGil Corporation
D GA D MB D £J D PC 2/26/09
9320 Chesapeake Drive, Suite 208 + San Diego California 92 123 * (858)560-1468 ^ Fax (858) 560-1576
City of Carlsbad O9-0465
4/1/09
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO O9-0465
OCCUPANCY B
TYPE OF CONSTRUCTION VB
ALLOWABLE FLOOR AREA
SPRINKLERS'? No
REMARKS
DATE PLANS RECEIVED BY
JURISDICTION 3/28/09
DATE INITIAL PLAN REVIEW
COMPLETED 4/1/09
JURISDICTION City of Carlsbad
USE Nail Salon
ACTUAL AREA 1235sf
STORIES 1
HEIGHT
OCCUPANT LOAD 22
DATE PLANS RECEIVED BY
ESGIL CORPORATION 2/26/09
PLAN REVIEWER Doug Moody
FOREWORD (PLEASE READ)
This plan review is limited to the technical requirements contained in the International Building
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, noise attenuation and access for the disabled This plan
review is based on regulations enforced by the Building Department You may have other
corrections based on laws and ordinances enforced by the Planning Department, Engineering
Department, Fire Department or other departments Clearance from those departments may be
required prior to the issuance of a building permit
Code sections cited are based on the 2007 CBC, which adopts the 2006 IBC
The following items listed need clarification, modification or change All items must be satisfied
before the plans will be in conformance with the cited codes and regulations Per Sec 105 4 of
the 2006 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i e , plan sheet number, specification section, etc
Be sure to enclose the marked up list when you submit the revised plans
City of Carlsbad O9-O465
4/1/O9 •
Please make all corrections on the original tracings, as requested in the correction
list Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects) For expeditious processing, corrected sets can be
submitted in one of two ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave , Carlsbad, CA 92008, (760)
602-2700 The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments
2 Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete
1 Each sheet of the plans must be signed by the person responsible for their
preparation, even though there are no structural changes Business and
Professions Code
2 Please correct the Building Code Data Legend on the Title Sheet to show the
following code information for the tenant space proposed
* Floor Area to show 1235sf
3 Please clarify the plans several rooms are shown as new (waxing and break) yet
the wall legend shows _them as existing and the construction detail on sheet A3 is
not referenced Please correct
4 Please provide the listing and installation in for the new pedicure chairs
5 Provide complete plumbing plans, including
a) Complete the dram, waste and vent plans to show all fixtures (The
standpipe for the washer)
b) Provide gas line plans and calculations for the new gas water heater,
showing pipe lengths and gas demands UPC Section 1217 0
6 Please indicate the water connections to the pedicure chairs to be equipped with
approved reduced pressure back-flow prevention on the water line plan Please
clarify the plumbing plans to indicate what the direct waste receptor is9
7 Detail the water heater flue (vent) terminations as per UPC, Section 517 0
Minimum 8 feet from a vertical wall or similar obstruction (parapet wall, screen
wall building wall) or extend vent termination to above the top of the wall
8 Please revise the plumbing plans to show the required clean-outs per section
707 and 719 of the UPC
lCity of Carlsbad O9-O465
4/1/09 -
9 Please provide electrical plans
10 Please provide panel schedules, indicate new and existing loads
11 Please revise the electrical plans to show the dedicated receptacles for the
pedicure chairs to be GFCI protected
12 When new rooms or spaces are constructed and the existing mechanical system
is not to be altered other than relocation of existing duct work, please note or
show mechanical ventilation will be provided capable of supplying the minimum
rate of outside air required per minute per occupant as shown in Table 4-1 of the
UMC (supply air to waxing and break rooms)
13 Please revise the plans to show the exhaust fan for the nail salon to provide the
required ventilation per Table 4-4 of the mechanical code ( 6 cfm/sqft a
minimum of 535 cfm)
14 When alterations, structural repairs or modifications or additions are made to an
existing building, that building, or portion of the building affected, is required to
comply with all of the requirements for new buildings, per Section 1134B 2 These
requirements apply as follows
a) A primary entrance to the building and the primary path of travel to the
altered area, must be shown to comply with all accessibility features
b) Existing sanitary facilities that serve the remodeled area must be shown to
comply with all accessibility features
To speed up the review~process, note on this list (or a copy) where each
correction item has been addressed, i e , plan sheet, note or detail number,
calculation page, etc
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list If there are other changes, please briefly
describe them and where they are located in the plans
Have changes been made to the plans not resulting from this correction list?
Please indicate
Yes a No a
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123, telephone number of
858/560-1468, to perform the plan review for your project If you have any
questions regarding these plan review items, please contact Doug Moody at
Esgil Corporation Thank you
Qity of Carlsbad O9-0465
4/1/09
[DO NOT PAY- THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION City of Carlsbad PLAN CHECK NO 09-O465
PREPARED BY Doug Moody DATE 4/1/09
BUILDING ADDRESS 2669 Gateway Rd Suite 102
BUILDING OCCUPANCY B TYPE OF CONSTRUCTION VB
BUILDING II AREA
PORTION (Sq Ft)
Tl
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code
RIHn Porrnit FPP hv Ordinal
1235
cb
Valuation
Multiplier
34 37
By Ordinance
nrp ^ !
Reg
Mod
VALUE ($)
42,447
42,447
$343 83
Plan Check Fee by Ordinance ^ ;
Type of Review 0 Complete Review
I I Repetitive Fee~~] Repeats
D Other
r-i Hourly
EsGil Fee
Structural Only
Hr @*
$223 49
$192 54
Comments Square footage shown on plans incorrect
Sheet 1 of 1
macvalue doc *•
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER CB 09-0465 DATE3/24/9
ADDRESS 2669 Gateway
RESIDENTIAL ADDITION-
MINOR (< 17,000.00)
RETAINING WALL
VILLAGE FAIRE
POOL/SPA
TENANT IMPROVEMENT
COMPLETE OFFICE BUILDING
OTHER
PLANNER Chris Sexto
ENGINEER
DATE 3/24/9
DATE
ll\AIIMIN\aii:NTLR/l1UNMNfi/raiNffll[M;AI'l'linVAl5
Carlsbad -Fire Department
Plan Review Requirements Category TI, COMM
Date of Report 04-29-2009
HOI TRAN
Reviewed
Name
Address
323 ALAMO WAY
OCEANSIDE CA
92057 ,DG. DEPT COPY
Permit # CB090465
Job Name
Job Address
HAPPINESS NAILS-1235 SF RETAIL
2669 GATEWAY RD CBAD St 102
INCOMPLETE The item you have submitted for review-Ts^ncBfflpletesasAiathistime, this office cannot
adequately conduct a review to determine compliance_wj=thj^^appfa6^1e^odes'-ana%^taadards Please review
carefully all comments attached_J^£a£e!*esfrf5nntthe necessary plans and/or specifications,
to this office for
Conditions:
Cond CON0003394
[NOT MET]
1 General Info - Correct note - this building is Spnnklered Add the following note for derferred
submittals
"(If required) Complete plans and specifications for fire alarm systems, fire
extinguishing systems, including automatic sprinklers and wet and dry standpipes, halon systems and
other special types of automatic fire protection systems and appurtances thereto shall be submitted
to Carlsbad Fire Department for review and approval PRIOR to installation (CFC 901 2)"
2 Show egress illumination The means of egress, including the exit discharge, shall be
illuminated at all times the space served by the means of egress is occupied The means of egress
illumination level shall not be less than 1-foot candle
at the walking surface CFC 1006
3 Add door hardware schedule to door schedule It shall comply with the following
Only mam exterior door or doors are permitted to be equipped with key-operated locking devices
from the egress side in accordance with CFC 1008 183 All others shall be no knowledge, single
action in accordance with CFC 1008 1 8 and 1008 1 8 4
Entry 04/14/2009 By cwong Action CO
Cond CON0003439
[MET]
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE OF A
BUILDING PERMIT
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS. FIRE DEPARTMENT
NOTATIONS.
CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH ALL APPLICABLE CODES AND
REGULATIONS
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE LAW
Entry 04/29/2009 By cwong Action AP
Carlsbad Fire Department
Plan Review Requirements Category Tl, COMM
Date of Report 04-14-2009 Reviewed by
Name HOI TRAN
Address
323 ALAMO WAY
OCEANSIDE CA
92057
Permit # CB090465
Job Name HAPPINESS NAILS-1235 SF SHELL
Job Address 2669 GATEWAY RD CBAD St 102
INCOMPLETE The item you have submitted for review is incomplete At this time, this office cannot
adequately conduct a review to determine compliance with the applicable codes and/or standards Please review
carefully all comments attached Please resubmit the necessary plans and/or specifications, with changes "clouded",
to this office for review and approval
Conditions:
Cond CON0003394
[MET]
1 General Info - Correct note - this building is Sprmklered Add the following note for derferred
submittals
"(If required) Complete plans and specifications for fire alarm systems, fire
extinguishing systems, including automatic sprinklers and wet and dry standpipes, halon systems and
other special types of automatic fire protection systems and appurtances thereto shall be submitted
to Carlsbad Fire Department for review and approval PRIOR to installation (CFC 901 2)"
2 Show egress illumination The means of egress, including the exit discharge, shall be
illuminated at all times the space served by the means of egress is occupied The means of egress
illumination level shall not be less than 1-foot candle
at the walking surface CFC 1006
3 Add door hardware schedule to door schedule It shall comply with the following
Only main exterior door or doors are permitted to be equipped with key-operated locking devices
from the egress side in accordance with CFC 1008 1 8 3 All others shall be no knowledge, single
action in accordance with CFC 1008 1 8 and 1008 1 8 4
Entry 04/14/2009 By cwong Action /?|O