HomeMy WebLinkAbout2704 GATEWAY RD; ; CB143052; Permit01-14-2015
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Cogeneration Permit Permit No:CB 143052
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
2704 GATEWAY RD CBAD
COGEN Sub Type: SOLAR
2132630900 Lot #: 0
$26,900.00 Constuction Type: NEW
Reference #:
WATER WORKS - SOLAR HEATING
SYSTEM FOR INDOOR POOLS // ROOF-MOUNTED
Status: ISSUED
Applied: 11/06/2014
Entered By: SKS
Plan Approved: 01/14/2015
Issued: 01/14/2015
Inspect Area:
Plan Check #:
Applicant:
SUNTREK INDUSTRIES INC
STE 215
5 HOLLAND
IRVINE CA 92618-2577
949-337-9748
Owner:
C B AQUATIC VENTURES LLC
25 WATERWORKS WAY
IRVINE CA 92618
Building Permit $259.21 PLUMBING TOTAL $0.00
Add'l Building Permit Fee $0.00 ELECTRICAL TOTAL $0.00
Plan Check $181.45 MECHANICAL TOTAL $0.00
Add'l Plan Check Fee $33.55 Additional Fees $0.00
Plan Check Discount
Strong Motion Fee
Green Bldg Stands (SB1473) Fee
$0.00
$3.50
$1.00
TOTAL PERMIT FEES $478.71
Total Fees: $478.71 Total Payments To Date: $478.71 Balance Due: $0.00
Inspector:
FINAL APPROVAL
Date: /^'Z7 •'/^ Clearance:
NOTICE: Please take NOTICE that approval of your project includes the Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
refered to as "fees/exactions." You have 90 days from the date this permit was Issued to protest Imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth In Govemment Code Section 66020(a), and file the protest and any other required Infonnation with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTII^IED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which vou have previouslv been given a NOTICE similar-to this, or as to which the statute of limitations has previously otherwise expired.
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: •NNING •ENGINEERING 'ILOING FIRE •HEALTH QHAZMAT/APCD
Plan Check No. CJb ^^ "^^^ ^
^Cityof
Carlsbad
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax:760-602-8558
email; building@carlsbadca.gov ^
www.carlsbadca.gov /y^~~^
Est. Value "Z^^^OO —P^c^-'
Plan Ck. Deposit \gl . ^ f
Date
)eposit / j^/ • ^
JOB ADDRESS
|LOT# I PHASES I# OF UNITS I/BEDROOMS
SUITE#/SPACE#/UNIT#
CT/PROJECT # tt BATHROOMS TENANT BUSINESS NAME CONSTR. TYPE
DESCRIPTION OF WORK: /nc/ude Square Feet of Affected Area(s;
EXISTING USE PROPOSED USE GARAGE (SF) PATIOS (SF) DECKS (SF) FIREPLACE
YESQ# NC^ I
AIR CONDITIONING
YES QNO I I
FlRESPRINKLERS
YES I |NO| I
APPLICANT NAME
Primary Contact
PROPERTY OWNEI
ADDRESS
5 HOIUA.^ ^^'^
ADDRESS
CITY STATE ZIP CITY STATE
<1T
ZIP
PHONE FAX PHONE
EMAIL EMAIL
DESIGN PROFESSIONAL TIM V/. CONTRACTOR BUS. NAME
ADDRESS ADDRESS 5 l/.ff^M "^^'5
CITY STATE ZIP
<^l3
STATE ZIP iV-
PHONE FAX PHONE FAX
EMAIL EMAIL
>l«l t Lll_. ft
f /
CLASS CITY BUS. LIC.#
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construcL alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuantto the provisions ofthe Contractor's License Law (Chapter 9, commending with Section 7000 of Division 3 ofthe Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a
civil penalty of not more than five hundred dollars ($500)).
i.:
Workers' Compensation Declaration: //lereiy affirm under penalty of perjury one of the following declarations:
11 have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
[1 have and will maintain workers' compensation, as required Jay Section 3700 of the Labor Code, for the performance of Ihe work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. .<i^g^'v4^ ^O^^-f Policy No. jl ^ ^ ^ Expiration Date /'/'
This section need not be completed if the permit is for one hundred dollars ($100) or less.
I I Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compgpsation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand doiiars (&100,000), in
addition to the cost of compensation, damages ^.firtSm^jor inSection 3706 of the<tabDr^ode, Interest and attomey's fees.
• AGENT DATE » ^ . i ^ JS^ CONTRACTOR SIGNATURE
—T
eAaborci
/ hereby affimi f/iaf / am exempt from Contractor's Ucense Law for the following reason:
I I I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I I I, as owner of the property, am exclusively contracting with licensed contractors io construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's Ucense Law).
• I am exempt under Section _ _Business and Professions Code for this reason:
1.1 personally plan to provide the major labor and materials for construction of the proposed property improvement. Qves I |No
2.1 (have / have not) signed an application for a building permit for the proposed work.
3.1 have contracted with the following person (firni) to provide the proposed constmction (include name address / phone / contractors' license number):
4.1 plan to provide portions of the work, but I have hired the following person to coordinate, supen/ise and provide the major work (include name / address / phone / contractors' license number);
5.1 will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone / type of work):
^efpROPERTY OWNER SIGNATURE QAGENT DATE
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505,25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Yes No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? Yes No
Is the facility to be constnjcted wilhin 1,000 feet of the outer boundary of a school site? Yes No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a construction lending agency for the perfomiance of the work this pennit Is issued (Sec. 3097 (I) Civil Code).
Lender's Name Lender's Address
I certify that I have read the application and state that the above Infoimation is conect and that the infbtmaton on the plans is accurate. I agree to comply with ail City ordinances and State laws relating to buiiding constniction.
I hereby authorize lepresentative of the City of Carlsbad to enter upon the above mentioned property Ibr inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST Aa LIABILITIES JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMfT,
OSHA: An OSHA pennit is required fbr excavations over 5'0' deep and demolition or constmction of stmctures over 3 stories in height.
EXPIRATION; Every pennit issued by the Building Oflicial under the provisions of this Code shall expire by lirnitation and become null and void if the building or work authorized by such permit is not commenced within
180 days from the date of such pemiit or if the building or vw4.atIIfiorized by such permit is suspended or abaria^ed at any time after the wort( is commenced for a period of 180 days (Section 106.4.4 Uniform Building Cods).
APPLICANT'S SIGNATURE DATE
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602-8560, Email buildlna(S)cai1sbacica.qov or Mall the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, Califomia 92008.
C0#: (Office Use Only)
CONTACT NAME OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY STATE CITY STATE ZIP
Carlsbad CA
PHONE FAX
EMAIL OCCUPANT'S BUS. LIC. No.
DELIVERY OPTIONS
PICK UP: CONTACT (Listed above) OtXUPANT (Listed above)
CONTRACTOR (On Pg. 1)
IVIAIL TO: CONTACT (Listed above)
CONTRACTOR (On Pg. 1)
IVIAIL / FAX TO OTHER:
OCCUPANT (Listed above) ASSOCIATED CB#-
NO CHANGE IN USE / NO CONSTRUCTION
CHANGE OF USE / NO CONSTRUCTION
jgf APPLICANT'S SIGNATURE DATE
Inspection List
Permit*: CB143052 Type: COGEN SOLAR
Date Inspection Item
01/23/2015 35 Photo Voltaic (PV)
01/23/2015 35 Photo Voltaic (PV)
01/23/2015 39 Final Electrical
01/23/2015 39 Final Electrical
Inspector Act
Rl
PB AP
Rl
PB AP
WATER WORKS - SOLAR HEATING
SYSTEM FOR INDOOR POOLS // ROOF-M
Comments
PM PLEASE
PM PLEASE
Monday, January 26, 2015 Page 1 of 1
... ^^H^
CARLSBAD INSPECTION RECORD
Building Diy ision ••^'»'*-^««>'«'«T**->»^«^*-'
a INSPECTION RECORD CARD WITH APPROVED
PLANS MUST BE KEPT ON THE JOB
0 CALL BEFORE 3:30 pm FOR NEXT WORK DAY INSPECTION
0 FOR BUILDING INSPECTION CALL: 760-602-2725
OR GO TO: www.Carlsbadca.qov/BMHdinq AND CLICK ON
"Request Inspection"
DATE: J fU |,<-
IF "YES" IS CHECKED BELOWTHAT DIVISION'S APF
IF YOU HAVE ANY QUESTIONS PLEASE CALL THE AI
ALL REQUIRED APPROVALS ARE SIGNED OFF- FAX
BRING IN A COPY OF THIS CARD TO: 163S FARADA
AT 760-602-2700 BETWEEN 7.30 AM - 8.00 AM TH
CB143052 2704 GATEWAY RD
WATER WORKS - SOLAR HEATING
SYSTEM FOR INDOOR POOLS // ROOF-MOUNTED
COGEN SOLAR
Lot# SUNTREK INDUSTRIES INC
PRIOR TO REQUESTING A FINAL BUILDING INSPECTION.
4S AT THE PHONE NUMBERS PROVIDED BELOW. AFTER
. EMAIL TO BLDGINSPECTIONS@CARLSBADCA.GOV OR
, CA 92008. BUILDING INSPECTORS CAN BE REACHED
NO YES Required Prior to Requesting Building Final If Cfiecked YES Date inspector Notes
4 Pfanning/Landscape 760-944-8463 AJIow48hourj
/ CM&I (Engineering Inspections;) 760-438-3891 Call before 2 pm
/ Fire Prevention 760-602-4660 Allow 46 hours
CODES BUILDING
#11 FOUNDATION
REV )(K!0f2
Carlsbad 14-3052
November 18, 2014
EsGil Corporation
In (PartnersHip •with government for (BuiCding Safety
DATE: November 18, 2014 • APPLICANT
• JURIS.
JURISDICTION: Carlsbad • PLAN REVIEWER
• FILE
PLANCHECKNO.: 14-3052 SET: I
PROJECT ADDRESS: 2704 Gateway Road
PROJECT NAME: Waterworks Solar Pool Heat
^ The plans transmitted herewith have been corrected where necessary and substantially
comply with the jurisdiction's codes.
I I The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed
check list and should be corrected and resubmitted for a complete recheck.
I I The check list transmitted herewith is for your information. The plans are being held at
Esgil Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to forward to the
applicant contact person.
I I The applicant's copy of the check list has been sent to:
3 EsGil Corporation staff did not advise the applicant that the plan check has been
completed.
I I EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Email:
Mail Telephone Fax In Person
• REMARKS:
By: Eric Jensen Enclosures:
EsGil Corporation
• GA • EJ • MB • PC 11/06
Carlsbad 14-3052
November 18, 2014
[DO NOT PAY- THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLANCHECKNO.: 14-3052
PREPARED BY: Eric Jensen DATE: November 18, 2014
BUILDING ADDRESS: 2704 Gateway Road
BUILDING OCCUPANCY:
BUILDING
PORTION
AREA
( Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code Cb By Ordinance
Bldg. Permit Fee by Ordinance
Plan Check Fee by Ordinance
Type of Review: • Complete Review
$215.00
• Structural Only
• Repetitive Fee
"^^^ Repeats
Based on hourly rate
• Other
• Hourly
EsGil Fee $86.00
Hrs. @
$172.00
Comments:
Sheet 1 of 1
macvalue.doc +
^ CITY OF
CARLSBAD
PLANNING DIVISION
PLANCHECK REVIEW
APPROVAL
P-28
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www.carLsbadca.sov
DATE: 1/7/15 PROJECT NAIVIE: SOLAR PANELS & ROOF MOUNTED EQUIPMENT PROJECT ID:
PLAN CHECK NO: CB143052 SET#: ADDRESS: 2704 GATEWAY RD
^ This plan check review is complete and has been APPROVED by the
PLANNING Division.
By: GINA RUIZ
A Final Inspection by the PLANNING Division is required • Yes ^ No
You may aiso have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a buiiding permit.
Resubmitted plans shouid include corrections from ali divisions.
• This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: AARON@SUNTREKSOLAR.COIVI
For questions or clarifications on tlie attached checl<list please contact the following reviewer as marked:
PLANNING
760-602-4610
ENGINEERING
760-602-2750
FIRE PREVENTION
760-602-4665
rn Chris Sexton
760-602-4624
Chrls.Sexton@carlsbadca.gov
r~| Kathleen Lawrence
760-602-2741
Kathleen.Lawrence@carlsbadca.fiov
Greg Ryan
760-602-4663
Gregory.Ryan@carlsbadca.gov
X Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
1 Linda Ontiveros
760-602-2773
Linda.Ontiveros@carlsbadca.gov
Q Cindy Wong
760-602-4662
Cvnthia.Wong@carlsbadca.gov
Chris Garcia
760-602-4622
Chrls.Garcla@carlsbadca.gov • 1 Dominic Fieri
760-602-4664
Dominic.Flerl@carlsbadca.fiov
Remarks:
REVIEW #:
Plan Check No. CB143052 Address 2704 GATEWAY RD Date 1/7/15
Review # 3
Planner GINA RUIZ Phone (760) 602- 4675
Type of Project & Use: SOLAR PANELS & ROOF MOUNTED EQUIPMENT
Zoning: P-C General Plan: Pi Facilities Management Zone: IjO
CFD (in/out) #_Date of participation: Remaining net dev acres:
(For non-residential development: Type of land use created by this permit: )
12 3 Legend: ^ Item Complete • Item Incomplete - Needs your action
^ • • Environmental Review Required: YES • NO ^ TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
^ • • Discretionary Action Required: YES • NO ^ TYPE
APPROVAL/RESO. NO. DATE
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval:
• • Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES O NO El
CA Coastal Commission Authority? YES Q NO El
If California Coastal Commission Authority: Contact them at - 7575 Metropolitan Drive,
Suite 103, San Diego, CA 92108-4402; (619) 767-2370
Determine status (Coastal Permit Required or Exempt): T.l. EXEMPT
• • Habitat Management Plan
Data Entry Completed? YES • NO E
If property has Habitat Type identified in Table 11 of HMP, complete HMP Permit application
and assess fees in Permits Plus
(A/P/Ds, Activity Maintenance, enter CB#, toolbar. Screens, HMP Fees, Enter Acres of
Habitat Type impacted/taken, UPDATE!)
• • Inclusionary Housing Fee required: YES • NO E
(Effective date of Inclusionary Housing Ordinance - May 21, 1993.)
Data Entry Completed? YES • NO •
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct
Housing Y/N, Enter Fee, UPDATE!)
• • Housing Tracking Form (form P-20) completed: YES • NO • N/A E
p-28 Page 2 of 3 07/11
Site Plan:
E • •
City Council Policy 44 - Neighborhood Architectural Design Guidelines
• • 1. Applicability: YES • NO E
• • 2. Project complies: YES • NOD
• •
Zoning:
1. Setbacks:
Front:
Interior Side:
Street Side:
Rear:
Top of slope:
Required
Required.
Required.
Required
Required
Shown
Shown
Shown
Shown
Shown
• • 2. Accessory structure setbacks:
Front: Required.
Interior Side: Required.
Street Side: Required
Rear: Required.
Structure separation: Required.
Shown
Shown
Shown
Shown
Shown
• • 3. Lot Coverage: Required Shown
• • E
EDO
• • E
Screening of Equipment:
ADDED
Required YES Shown SECTIONS NOT SHOWN SECTION
5. Parking: Spaces Required Shown
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required Shown
Additional Comments #1. ARE THE NEW ROOF MOUNTED HEATERS AND PUMPS A PART OF THIS PERMIT? IF
so. PLEASE ADD SECTIONS SHOWING THAT THE NEW ROOF MOUNTED EQUIPMENT WILL BE SCREEN6B
FROM VIEW FROM ADJACENT PROPERTIES/STREETS WITHIN 600 FEET. AN EXAMPLE HAS BEEN ATTACHED
FOR YOUR REFERENCE. ALONG WITH THE POLICY FOR ROOF MOUNTED SCREENING & THE CONDITIONS OF
APPROVAL STATING SCREENING IS REQUIRED. PLEASE BE ADVISED THIS IS A HIGHLY VISABLE AREA-ANB
THE PROPERTY IS LOWER THAN THE STREET SO MORE SCREENING/ADDITIONAL PARAPET HEIGHT MAY BE
NEEDED TO SCREEN THE NEW EQUIPMENT. THE SOLAR PANELS THEMSELVES DO NOT NEED TO BE
SCREENED, ONLY THE NEW HEATERS/PUMPS (IF APPLICABLE^
PLANCHECK #2: THE SCREENING EXHIBIT DOES NOT SHOW HOW THE EQUIPMENT IS SCREENED AS IT DOESNT STATE WHAT-IS
GOING TO SCREEN THE EQUIPMENT. A STREET VIEW HAS BEEN INCLUDED SHOWING HOW VISIBLE THE
ROOF AREA IS AND HOW ADDITIONAL PARAPETS/SCREENS WILL BE REQUIRED FOR ANY PROPOSED
EQUIPMENT ON THE ROOF (ALL EXISTING EQUIPMENT WAS NOT APPROVED BY PERMITS). EXCLUDING
SOLAR PANELS THEMSELVES AS THEY DO NOT REQUIRE SCREENING.
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER GINA RUIZ DATE 1/7/15
p-28 Page 3 of 3 07/11
CITY
CARLSBAD
O F
PLAN CHECK
REVIEW
TRANSMITTAL
BUiLUING DEPT.,—
COPY
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
DATE: 1V12/2014
PLAN CHECK NO: 1 SET#: 1
PROJECT NAME: Waterworks CBD
ADDRESS: 2704 Gateway Rd
PROJECT ID: CB143052
APN:
•
This plan check review is complete and has been APPROVED by the FIRE Division.
By: GR
A Final Inspection by the FIRE Division is required |^ Yes • No
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: A. HIII - suntrek ind.
You may also have corrections from one or more of the divisions Usted below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should Include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING
760-602-4610
ENGINEERING
760*02-2750
FIRE PREVENTION
760*02-4665
1 1 Chris Sexton
760-602-4624
Chrls.Sexton@carlsbadca.eov
1 1 Kathleen Lawrence
760-602-2741
Kathleen.Lawrence@carlsbadca.gov
X Greg Ryan
760-602-4663
Gregorv.Rvan@carlsbadca.gov
1 1 Gina Ruiz
760-602-4675
Glna.Ruiz@carlsbadca.gov
1 1 Linda Ontiveros
760-602-2773
Linda.Ontiveros@carlsbadca.eov
Q Cindy Wong
760-602-4662
Cvnthia.Wong@carlsbadca.gov
• • 1 1 Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Carlsbad Fire Department
BUILDING DEF
COPY
Plan Review
Date of Report:
Name:
Address:
Requirements Category: COGEN , SOLAR
11-12-2014
SUNTREK INDUSTRIES INC
5 HOLLAND
STE 215
IRVINE CA
92618-2577
Reviewed by:
Permit #: CB143052
Job Name:
Job Address:
WATER WORKS - SOLAR HEATING
2704 GATEWAY RD CBAD
INCOMPLETE The item you have submitted for review is incomplete. At this time, this office cannot
adequately conduct a review to determine compliance with the applicable codes and/or standards. Please review
carefully all comments attached. Please resubmit the necessary plans and/or specifications, with changes
"clouded", to this office for review and approval.
Conditions:
Cond: CON0007841 [NOT MET]
1. Provide the appropriate codes and standards list on the Title sheet of your submittal and include the Carlsbad
Fire Code.
If you cite codes and standards tiiat are not customarily a part of a municipal library sucii as ASTM, ANSI, ASME etc.
tiien provide ttie text from ttiose standards to enable verification of your design.
2. Revise plans to comply with Section 605.11 ofthe California Building and Fire Codes. You should also focus on
Sec. 605.11.3 Access and Pathways. Begin with a 6'0" clear perimeter around the roof edge (parapit) and 4'0" clear
access pathway to and around any smoke/heat vents or skylights that could be used for ventilation.
3. Plan sheets (all) shall have a scale.
Entry: 11/12/2014 By: GR Action: CO
VINCI & ASSOCIATES
Struchiral Cinrjineers
STRUCTURAL CALCULATIONS
FOR
POOL THERMAL
SOLAR SYSTEM
Waterworks CartWbad
2704 Gateway^^
Carlsbad, /CA 92009
ENT: SunTrek
09-3457
NOV 08 ZOH
175E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360
p 805.496.2100 • f 805.496.2442 • evinci@VinciSE.com
DATE: 10/14/2014
PROJECT: Waterworks Carlsbad
CLIENT:
2704 Gateway Road
Carlsbad, CA 92009
SunTrek
VINCI & ASSOCIATES SHEET
S/ruc/ura/ Gncfineers JOB NO.:
175E.WILBURROAD, STE 103 -THOUSANDOAKS, CA 91360 ENGR.:
p 805.496.2100 • f 805.496.2442 • evinci@VinciSE.com
09-3457
JRV
DESIGN DATA:
ROOF DESIGN LOAD:
ROOFING ( Built Up )
SHEATHING
ROOF RAFTERS / TRUSS
MISCELLANEOUS
ROOF RAFTER/TRUSS DESIGN DEAD LOAD
CEILING & INSULATION
MISCELLANEOUS
DESIGN DEAD LOAD =
DESIGN LIVE LOAD =
DESIGN SNOW LOAD =
WIND^ DESIGN CRITERIA:
BASIC WIND SPEED
WIND EXPOSURE
NUMBER OF STORIES
SOLAR MODULE
Solar Module Width:
Solar Module Length: =
Solar Module Dead Load =
Number of PV Modules =
Number of PV Mounts to Roof =
Solar Module Vertical Support Point Load:
15.429 ft^ (See sheet 1) x 1.50 psf
TOTAL AREA OF ADDED SOLAR PANELS
( 2.00 ft X 54.0 ft) X ( 15 Modules ) =
5
2
2
1
10.0
3.25
1.25
14.5
20
0
110
c
1
psf
psf
psf
psf
psf
mph
in
in
psf
24
648
1.5
15
105
23.1 lbs
1620.0 ft^
DATE: 10/14/2014
PROJECT: Waterworks Carlsbad
2704 Gateway Road
CLIENT:
Carlsbad, CA 92009
SunTrek
VINCI & ASSOCIATES SHEET
S/ruc/ura/ Gnrpneers JOB NO.
175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360 ENGR
p 805.496.2100 • f 805.496.2442 • evincl@VlnclSE.com
09-3457
JRV
DESIGN CONNECTfON TO ROOF TO RESIST WIND UPLIFT
rnr.njKfMaitwxH)
ZONE 3 UPLIFT = 49.4 psf -1.5 psf
Design Force = ( Uplift x (0.6)) -1.5 psf
Net Uplift = 29.6 psf
7.00 Connections per Module (MIN)
15 Modules, 105 Connections
Therefore - Trib Area = 108 / 7.00
UPLIFT / CONN. = 15.4 ft^ x 29.6 psf
= 457 lbs/conn
For Rainbuster 12000 Adhesive
FALLOW = 25 lbs/in
for 24" adhesive
PALLOW = 27.49" x 25 lb/in
= 687.265 lbs > 457 lbs
Thttraforo O.K.
FACTOR OF SAFETY:
F.O.S. = 1.50 > 1.5
Theroforo O.K.
REFER TO NEXT SHEET FOR
UPLIFT FORCE CALCUUKTIONS
ZONE 2 UPLijsf = 31.2 psf -1.5 psf
Design Force = ( Uplift X (0.6)) -1.5 psf
Net Uplift = 17.2 psf
7.00 Connections per Module (MIN)
15 Modules, 105 Connections
Therefore - Trib Area = 108 / 7.00
UPLIFT/CONN. = 15.4 ft^ x 17.2 psf
= 266.1 lbs/conn
For Rainbuster 12000 Adhesive
FALLOW = 25 lbs/in
for 24" adhesive
FALLOW = 24.00" x 25 lb/in
600 lbs > 266 lbs
Therafora O.K.
FACTOR OF SAFETY:
F.O.S. = 2.25 > 1.5
Therafora O.K.
ZONE 1 UPLIFT = 22.2 psf -1.5 psf
Design Force = ( Uplift x (0.6)) -1.5 psf
Net Uplift = 13.3 psf
7.00 Connections per Module (MIN)
15 Modules, 105 Connections
Therefore - Trib Area = 108 / 7.00
UPLIFT/CONN. = 15.4 ft^ x 13.3 psf
= 205.4 lbs/conn
For Rainbuster 12000 Adhesive
FALLOW = 25 lbs/in
for 24" adhesive
FALLOW = 24.00" x 25 lb/In
600 lbs > 205 lbs
Th»nifore O.K.
FACTOR OF SAFETY:
F.O.S. = 2.92 > 1.5
Thereforo O.K.
VINCI A ASSOCIATES
SXT-u-'.tvroJ «'F»fftTt**-i PRO IFPT
W«S-Tt.ftKB Vtl.l.*aB. C« •'•SB* /-«| ICklT
» ULIbIM 1
Wa'SE!«^dii<il"^*^<* . '.. ..ife.-^^i • - , .• PAGE
>?i£&H^1^|{$a('^<^''sbad, QASSSXi^^^A DESIGN BY
fn^^^lHiliiy DATE 'AOffW*:! REVIEW BY
3
IRV
/ASCE 7-10/CBC 2013
INPUT DATA
Exposure category (B, C or D)
Importance factor, pg 77, (0.87, 1.0 or 1.15)
Basic wind speed (IBC Tab 1609.3.1 Vas)
Topographic factor (Sec.6.5.7.2, pg 26 * 45)
Building height to eave
Buiiding height to ridge
Building length
Building width
Effective area of components (or Solar Panel area)
V
Kz,
he
hr
L
B
A
. C
1 00
110
:%i •.
14
18
54
38
108
Category II
* mph
Flat
ft
ft
"ft
ft
ft^
DESIGN SUMMARY
Max horizontal force normal to building length, L, face
Max horizontal force normal to building length, B, face
Max total horizontal torsional load
Max total upward force
13.47 kips
10.39 kips
92.24 ft-kips
36.00 kips
ANALYSIS
Velocity pressure
qh = 0.00256 Kh K,
where:
22.64 psf
qh = velocity pressure at mean roof height, h. (Eq. 6-15, page 27)
K(, = velocity pressure exposure coefficient evaluated at height, h, (Tab. 6-3, Case 1 ,pg 79) =
K<) = wind directionality factor. (Tab. 6-4, for building, page 80) =
h = mean roof height =
< 60 ft, [Satisfactory]
< Min (L, B), [Satisfactory]
Desiqn pressures for MWFRS
P = qhI(GCp,HGCp,)]
0.86
0.85
16.00
where: p = pressure in appropriate zone. (Eq. 6-18, page 28). 10 psf (Sec. 6.1.4.1 & 6.1.4.2)
G Cp, = product of gust effect factor and external pressure coefficient, see table beiow. (Fig. 6-10, page 53 & 54)
G Cp, = product of gust effect factor and internal pressure coefficient.(Fig. 6-5, Enclosed Building, page 47)
= 0.18 or -0.18
a = width of edge strips, Fig 6-10, note 9, page 54, MAX[ MIN(0.1B, 0.1L, 0.4h), MIN(0.04B, 0.04L), 3] = 3.80
Net Pressures (psf), Basic Load Cases
Roof angle 9 = 11.89 Roof angle 0 = 0.00
Surface GCp, Net Pressure with C3Cp, Net Pressure with GCp, (+GCp,) (-GCpi) C3Cp, (+GCp,) (-GCpi)
1 0.46 6.33 14.49 0.40 4.98 13.13
2 -0.69 -19.70 -11.55 -0.69 -19.70 -11.55
3 -0.42 -13.60 -5.45 -0.37 -12.45 -4.30
4 -0.35 -12.10 -3.95 -0.29 -10.64 -2.49
1E 0.70 11.71 19.86 0.61 9.74 17.89
2E -1.07 -28.30 -20.15 -1.07 -28.30 -20.15
3E -0.60 -17.74 -9.59 -0.53 -16.08 -7.93
4E -0.53 -16.00 -7.84 -0.43 -13.81 -5.66
5 -0.45 -14.27 -6.11 -0.45 -14,27 -6.11
6 -0.45 -14.27 -6.11 -0.45 -14.27 -6.11
Net Pressures (psf). Torsional Load Cases
Surface
Roof an glee = 11,89
Surface GCp, Net Pressure with Surface GCp, (+GCp,) (-GCpi)
IT
2T
3T
4T
0.46
-0.69
-0.42
-0.35
1.58
-4.92
-3.40
-3.02
3.62
-2.89
-1.36
-0.99
Surface
Roof angle e = 0.00
Surface GCp, Net Pressure witii Surface GCp, (+GCpi) (-GCpi)
1T
2T
3T
4T
0.40
-0.69
-0.37
-0.29
1.25
-4.92
-3.11
-2.66
3.28
-2.89
-1.08
-0,62
2E 2 J ZONE 2/3 BOUNDARY
REFERENCE CORNER
KIND DIRECTION WIND DIRECTION
REFD?ENCE CORNER
WIND DIRECTION WIND DIRECTION
Transverse Direction Longitudinal Direction Transverse Direction Longitudinal Direction
Bosic Load Cases Torsional Load Cases
4
Basic Load Cases in Transverse Direction Basic Load Cases In Longitudinal Direction
Area Pressure (k) with Area Pressure (k) with
Surface (ft') (+GCpi) (-GCpi) Surface (ft') (+GCp,) (-GCpi)
1 650 4.11 9.41 1 496 2.47 6,51
2 901 -17.75 -10.40 2 839 -16.52 -9,69
3 901 -12.25 -4.91 3 839 -10.45 -3.61
4 650 -7.86 -2.56 4 496 -5.27 -1.23
IE 106 1.25 2.11 IE 112 1.10 2.01
2E 148 -4.18 -2.97 2E 210 -5.94 -4.23
3E 148 -2,62 -1.42 3E 210 -3.37 -1.66
4E 106 -1.70 -0.83 4E 112 -1.55 -0.64
V Horiz. 13.47 13.47 Horiz. 10.39 10.39
Vert. -36.00 -19.28 Vert. -35.50 -18.77
Min. wind Horiz, 9.72 9.72 Min, wind Horiz. 6.08 6,08
Sec, 6.1,4,1 Vert. -20,52 -20.52 Sec, 6,1,4,1 Vert. -20,52 -20.52
Torsional Load Cases in Transverse Direction Torsional Load Cases In Longitudinal Direction
Surface Area Pressure (li) with Torsion (fi-k) Surface Area Pressure (k)wi«h Torsion (ft-k) Surface
(ft') (+GCpi) {-GCp,) (+GCp,) (-GCpi) Surface
(ft') (+GCpi) (-GCpi) (+GCp,) (-GCp,)
1 272 1,72 3.93 20 46 1 192 0.95 2.52 5 14
2 377 -7.42 -4.35 -18 -10 2 629 -12.39 -7.26 34 20
3 377 -5.12 -2.05 12 5 3 629 -7.83 -2.71 -22 -8
4 272 -3.29 -1.07 38 12 4 192 -2.04 -0.48 11 3
IE 106 1.25 2.11 29 49 IE 112 1.10 2.01 17 30
2E 148 -4.18 -2.97 -20 -14 2E 210 -5.94 -4.23 17 12
3E 148 -2.62 -1.42 13 7 3E 210 -3,37 -1.66 -9 -5
4E 106 -1.70 -0.83 39 19 4E 112 -1,55 -0.64 24 10
IT 378 0.60 1.37 -8 -18 IT 304 0.38 1.00 -3 -9
2T 524 -2,58 -1.51 7 4 2T 839 -4.13 -2.42 -23 -13
3T 524 -1.78 -0.71 -5 -2 3T 839 -2.61 -0.90 15 5
4T 378 -1.14 -0.37 -15 -5 4T 304 -0.81 -0.19 -7 -2
Total Horiz. Torsional Load , MT 92 92 Total Horiz. Torsional Load, Mr 57.3 57.3
Design pressures for comoonents and cladding
P = qhI(G Cp).{G Cp,)]
where: p = pressure on component. (Eq. 6-22, pg 28)
Pmin= 10.00 psf (Sec. 6.1.4,2, pg 21)
G Cp = external pressure coefficient.
see table beiow, (Fig. 6-11, page 55-58)
Walls
T"" Zone I Zonel 2 1 — Id 1 = 1 =
l'\--2-
Roof fi<7' Roof fl>7'
Effective
Area (ft')
Zonel Zone 2 Zone 3 Zone 4 Zone 5 Effective
Area (ft') GCp -GCp GCp -GCp GCp -GCp GCp -GCp GCp -GCp
Comp. 108 0.30 -0.80 0.30 -1.20 0.30 -2.00 0.82 -0.92 0.82 -1.04
Comp. & Cladding
Pressure
(psf)
Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Comp. & Cladding
Pressure
(psf)
Posltfvs Negative Posntva Negative PosltIv* Negative Poattlve Negative PoBltlve Negative
Comp. & Cladding
Pressure
(psf) 10.87 -22.19 10.87 -31,25 10.87 -49.36 22,59 -24.85 22,59 -27.51
Note: If the effective area is roof Solar Panel area, the only zone 1, 2 , or 3 apply.
DATE: 10/14/2014
PROJECT: Waterworks Carlsbad
2704 Gateway Road
Carlsbad, CA 92009
CLIENT: SunTrek
VINCI & ASSOCIATES
StrucluraJ Gnrfineers
175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360
p 805.496.2100 • f 805.496.2442 • e vinci@VinciSE,com
SHEET:
JOB NO.: 09-3457
ENGR,: JRV
LATERAL FORCES: (Base Shear Calculations - 2013 CBC)
SEISMIC:
Site Class: D (Use D if unknown)
Si= 0.402 (USGS Software)
Fv= 1.5 (Table 1613.3.3(2))
I = 1.0 (Table 11.5-1 ASCE 7-10)
R= 6.5 (Table 12.2-1 ASCE 7-10)
SMS= Fa*Ss= 1.036 (Eq. 16-37)
SMI= FV*SI= 0.603 (Eq. 16-38)
TL = 8 s (Figure 22-12 ASCE 7-10)
T = C,*(hn)''= 0.145 s (Eq. 12.8-7)
hn= 14.0 ft
* *GOVERNS * *
Ss= 1.04 (USGS Software)
Fa= 1.0 (Table 1613.3.3(1))
SDS -
SDI -
C,=
X =
^Iz * SMS -
^/s * SMI ~
0.69
0.40
(Eq. 16-39)
(Eq. 16-40)
0.02 (Table 12.8-2 ASCE 7-10)
0.75 (Table 12.8-2 ASCE 7-10)
VM,N =(SDS)/(R/I) = 0.11 W (Eq. 12.8-2 ASCE 7-10)
NEED NOT EXCEED:
IF T <TL USE:
V = (SDI)/T*(R/I) =
IFT;>TL USE:
V = (SDinTL)/-p*(R/i) =
SHALL NOT BE LESS THAN:
V =
0.43 W
23.61 W
0.01 W
(Eq. 12.8-3 ASCE 7-10)
(Eq. 12.8-4 ASCE 7-10)
(Eq. 12.8-5 ASCE 7-10)
Design Maps Summary Report Page 1 ofl
QSGS; Design Maps Summary Report
User-Specified Input
Building Code Reference Document 2012 International Building Code
(which utilizes USGS hazard data available in 2008)
Site Coordinates 33.12904°N, 117.25214°W
Site Soil Classification Site Class D - "Stiff Soil"
Risk Category I/II/III
1 2
S mapquest \
USGS-Provided Output
Ss = 1.036 g
Si = 0.402 g
S„s= 1.125 g
S„i = 0.643 g
SDS = 0.750 g
SDI = 0.428 g
For information on how the SS and SI values above have been calculated from probabilistic (risk-targeted) and
deterministic ground motions in the direction of maximum horizontal response, please return to the application and
select the "2009 NEHRP" building code reference document.
MCER Response Spectrum
0.00
0.00 0.20 o.«o o.eo o.eo i.oo 1.20 no i.eo i.so 2.00
Period, T (sec)
Design Response Spectrum
n
0.00 1.00 0.20 0.40 o.eo o.eo 1.00 1.20 no i.eo i.so 2.00
Period, T (sec)
Although this information is a product ofthe U.S. Geological Survey, we provide no warranty, expressed or implied, as to the
accuracy of the data contained therein. This tool is not a substitute for technical subject-matter l<nowledge.
http://ehp3-earthqiiake.wr.usgs.gov/desigmnaps/us/surnmary.php?template=minimal&lati... 10/14/2014
DATE: 10/14/2014
PROJECT: Waterworks Carlsbad
2704 Gateway Road
Carlsbad, CA 92009
VINCI & ASSOCIATES
S/ruc/ura/ Cinqineers
175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360
p 805.496.2100 • f 805.496.2442 • evinci@VinciSE.com
SHEET:
JOB NO.: 09-3457
ENGR.: JRV
CLIENT: SunTrok
LATERAL FORCES 2013 CBC: (BASE SHEAR - Conservative)
Fi
SEISMIC BASE SHEAR:
V = 0.11 W (SEE PREVIOUS)
ROOF =
WALLS =
WIND LOADS:
Ps = Akz, LPS3O (Eq. 6-1)
A= 1.21 Ps3aA =
lw= 1.00 Ps30B =
kzt= 1.00 Ps30C =
Ps30D •
19.20-
-10.00
12.70
-5.90
psf
psf
psf
psf
FIULT:
FIASD-
(4 ft + 14ft/2)x (23.2704psf+12.12 psf )
389.29 lb/ft X 0.6
15
7
21.5
0.106
7
^;:IROOF= 4.0 ft
/ hi = 14.0 ft
PSF
2.28 PSF
PsA 23.27 psf
PsB -12.12 psf
Psc 15.39 psf
PsD -7.15 psf
389 lb/ft
Governs
234 lb/ft
DATE: 10/14/2014
PROJECT: Waterworks Carlsbad
2704 Gateway Road
Carlsbad, CA 92009
VINCI & ASSOCIATES
S/ruc/ura/ Gnqineers
175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360
p 805.496.2100 • f 805.496.2442 • evinci@VinciSE.com
SHEET:
JOB NO.:
ENGR.:
8
09-3457
JRV
CLIENT: SunTrek
CHECK IMPACT OF NEW SOLAR PANELS ON SEISMIC LOAD
C •
r SCH «pvc suMny «
Eot»>Me>jt mkK MTV-
• •
^PWWtT WALL
. %HI>aoOSTE.RPUWP'
TOTAL ROOF AREA:
( 90.0ft X 121 ft ) + ( Oft X 0.0ft
(0.0 ft X 0.0 ft ) + ( 0.0 ft X 0.0 ft
EXISTING ESTIMATED SEISMIC LOAD (BASE SHEAR)
) +
) = 10920 ft^
10920 ft 2.28 psf 24946.9 lbs
AREA OF ADDED SOLAR PANELS
( 54.00 ft X 2.00 ft) X ( 15 PANELS ) = 1620.0 ft^
WEIGHT OF PANELS: 1.5 psf
ADDED SEISMIC LOAD:
1.5 psf X
% INCREASE =
1620.0 ft^ X 0.11
258.2
24946.88
258.2 lbs
1.0% < 10%
Therefore O.K.
DATE: 10/14/2014
PROJECT: Waterworks Carlsbad
2704 Gateway Road
Carlsbad, CA 92009
VINCI & ASSOCIATES SHEET
S/ruc/ura/ Cinqineers JOB NO.:
175 E. WILBUR ROAD, STE 103 • THOUSAND OAKS, CA 91360 ENGR.:
p 805.496.2100 • f 805.496.2442 • evinci@VinciSE.com
09-3457
JRV
CLIENT: SunTrek
CHECK IMPACT OF NEW SOLAR PANELS ON GRAVITY LOAD
T Sf»* 40 PVT BllPPiy ft
RETUBN PIPING TD POOL ^
FOU#»MCMT*nEA. *5TW -V"^
• •
FCXH. WATTRONRO
HHPBOOCTBIPUMF
- HHPeOOSTFPPUMp.
POOL rawfwcMTBai
TOTAL ROOF AREA:
( 90.0 ft X 121 ft ) + ( Oft
(0.0ft X 0.0ft ) + ( 0.0ft
EXISTING ESTIMATED ROOF DEAD LOAD
X
X
10920 ft 14.50 psf
0.0 ft ) +
0.0 ft ) =
158340 lbs
AREA OF ADDED SOLAR PANELS
( 54.00 ft X 2.00 ft) X ( 15 PANELS ) =
WEIGHT OF PANELS: 1.5 psf
ADDED GRAVITY LOAD:
1.5 psf X
% INCREASE =
10920 ft^
1620.0 ft^
1620.0 ft^ X 1.00
2430.0
158340
2430.0 lbs
1.5% < 10%
Therefore O.K.
WATERWORKS CARLSBAD
2704 GATEWAY ROAD
CARLSBAD, CA 92009
POOL THERMAL SOLAR SYSTEM
City of Carlsbad
Building Division
JAN 14 2015
APPROVED BY
ISSUED BY
PROJECT LOCATION
POOL 1
SITE LOCATION (D
SCOPE OF WORK
1. THE DESIGN BUILD CONTRACTORS SHALL FURNISH AND INSTALL SWIMMING POOL SOLAR HEATING SYSTEM, INCLUDING. BUT NOT LIMITED TO: SOLAR COLLECTORS, ASSOCIATED MANIFOLDS, SOLAR COLLECTOR CONNECTION HARDWARE, SOLAR COLLECTOR MOUNTING/INSTALLATION HARDWARE, DIGITAL SOLAR CONTROL SYSTEM, AND ALL APPURTENANCES.
2. FURNISH AND INSTALL DIGfTAL SOLAR CONTROLLER AC POWER AND ROOF TOP SENSOR SHALL BE LOCATED ON THE POOL
EQUIPMENT BUILDING ROOF.
3. FURNISH AND INSTALL ROOF SUPPORTS AND COLLECTOR
ANCHORS.
4. FURNISH AND INSTALL PIPE FASTENERS, MOUNTING HARDWARE,
AND RIGID PIPE CLAMPS FOR PIPING UPTHE WALL.
POOL SYSTEM SIZE: 1500 SQFT
OPTIMUM FLOW RATE: 150-225 GPM
DESIGN FLOW RATE: 187GPM
SHEET INDEX
PT-1 VICINITY MAPAND PROJECT LOCATION
PT.2 PARTIAL ROOF PLAN - POOL THERMAL SYSTEM
PT.3 SYSTEM FLOW DIAGRAM
PT4 ATTACHMENT DETAIL
PT.5 CO^^•ROUPUMP SPEC SHEET
PT.6 COLLECTOR/MANIFOLD SPEC SHEET PT-7 PUMP WIRING DIAGRAM
STANDARDS
ALL WORK SHALL BE PERFORMED IN ACCORDANCE
WITH THE APPLICABLE EDITIONS OF ALL NATIONAL, STATE, AND LOCAL CODES, LAWS, REGULATIONS, AND
ORDINANCES, INCLUDING THE FOLLOWING:
AMERICAN NATIONAL STANDARDS INSTrTUTE (ANSI) AMERICAN SOCIETY OF TESTING MATERIALS (ASTM)
AMERICAN WATERWORKS ASSOCIATION (AWA)
AMERICAN WELDING SOCIETY(AWS)
2013 CALIFORNIA ELECTRICAL CODE (CEC)
DELIVERY, STORAGE, AND INSTALLATION SHALL COMPLYWITH SPECIFICATION SECTION 13563.
ALL PIPING SHALL BE SCHEDULE 40 PVCJ^STM
FITTINGS, SOLVENT WELDED.
PROJECT SHALL COMPLY WITH THE 2013 CALIFORNIA
BUILDING, RESIDENTIAL, ELECTRICAL, AND PLUMBING ENERGY CODES.
CARBON MONOXIDE ALARMS ARE REQUIRED TO BE INSTALLED IN EXISTING DWELLING UNITS OR SLEEPING
UNITS WITH A FOSSIL FUELBURNING HEATER ORAPPLIANCE,
FIREPLACE, ATTACHED GARAGE. CARBON MONOXIDE ALARM
SHALL BE LOCATED IN EACH AREAGMNG ACCESS TO A SLEEPING ROOM AND ON EACH STORY DWELLINGS WfTH
MORE THAN ONE STORY CARBON MONOXIDE ALARMS ARE
PERMITTED TO BE SOLELY BATTERY OPERATED WHERE NO CONSTRUCTION IS TAKING PLACE.
OCCUPANCY GROUP: A.3/B
CONSTRUCTION TYPE: V/B
PROJECT LOCATION
1 —. W i'
VICINITY MAP ($)
SUNTREK
Your Solar Energy Company
SUNTREK INDUSTRIES
5 HOLLAND #215
IRVINE, CA 92618
C-46 Lie. #859460
(949) 348-9276
PROJECT
POOLTHERMAL SOLAR
SYSTEM
LOCATION
Q
<
OQ
CO _l
< o
CO
o
I
LU
Q O)
< O
a: <j>
I—
5co
NOV 06
DESIGNER
ARI GONZALEZ
COVER PAGE
SITE PLAN
REVISIONS
?014
my SHEET NO.
E NORTH
PARAPET WALL
PARAPET WALL
ONLY
C I AT E S
ID OAKS, CA 91360
inci@VinciSE.com
SOLAR
COLLECTORS
TYPICAL ADHESIVE CONNECTION
PT.4 y FOR ALL COLLECTORS EVERY 3"
BALLASTED SYSTEM
POOL HEATER ON ROOF
72 HP BOOSTER PUMP ON ROOF
'A HP BOOSTER PUMP ON ROOF
POOL EQUIPMENT BELOW
ROOF PLAN - POOL THERMAL SYSTEM
POOL1
TRUE NORTH
SUNTREK
Your Solar Energy Company
SUNTREK INDUSTRIES
5 HOLLAND #215
IRVINE, CA 92618
C-46 LIC. #859460
(949) 348-9276
PROJECT
POOL THERMAL SOLAR
SYSTEM
LOCATION
Q
< CD
CO —I
< O
CO
a: o
I
LU
Q Oi < o
IS
LU Q <
!< CQ
CM O
DESIGNER
ARI GONZALEZ
SITE PLAN
REVISIONS
SHEET NO.
PT-2
pnni THERM MOUNTING NOTF.S
ROOF TYPE: TAR AND GRAVEL
MODULE WEIGHT 1.5 PSF WITH WATER
POOL SYSTEM SIZE: 1500 SQFT
OPTIMUM FLOW RATE: 150-225 GPM
DESIGN FLOW RATE: 187GPM
NOTES:
1. CONTROL WIRING CONNECTS TO LINE
SIDE OF EXISTING POOL PUMP TIME
CLOCK. 240V AC
2. ALL ROOF PIPING SHALL BE BLACK SCH.
40 PVC ASTM FITTINGS, SOLVENT WELDED
3. ALL PIPING FROM EQUIPMENT TO ROOF
SHALL BE SCH. 40 PVC ASTM FITTINGS,
SOLVENT WELDED
4. FILTF?ATION FLOW RATES WILL NOT BE
AFFECTED BY THE SOLAR POOL SYSTEM
VACUUM RELIEF
VALVE (TYP)
SOLAR TEMPERATURE
SENSOR
SOLAR COLLECTOR
& MANIFOLD ON ROOF
®
SOLAR DIGITAL
CONTROL PANEL
120 V
GATE
VALVE
CHECK
VALVE
FROM POOL
FILTER OUTLET
(2) 72 HP BOOSTER
PUMP
3 TIED TO
GAS HEATER
CHECK
VALVE
WATER TEMPERATURE
SENSOR
SYSTEM FLOW DIAGRAM
SUNTREK
Your Solar Energy Company
SUNTREK INDUSTRIES
5 HOLLAND #215
IRVINE, CA 92618
C-46 LIC. #859460
(949) 348-9276
PROJECT
POOL THERMAL SOLAR
SYSTEM
LOCATION
Q
< CD
CO _l a:
< o
CO
:^
LU
D O) < °
LU Q <
< CQ
o a: <
DESIGNER
ARI GONZALEZ
SYSTEM FLOW
DIAGRAM
REVISIONS
SHEET NO.
PT-3
5'-0-O.C.
COLLECTOR MANIFOLD OR
SWS/SWR PIPING
GATE CLAMP
(TYP. FOR EACH HEADER)
1/2" RGS PIPE
TAR & GRAVEL ROOF
EPDM ELASTOMER
WATER TUBING, SEE
DETAIL 'D', SHEET PT-3
-1/2" RGS PIPE
ROOF ADHESIVE FOR WITH OF
COLLECTOR ARRAY. TOP
RAINBUSTER 12000, SILICON
ELASTOMERIC ADHESIVE
SEALANT
MSOLARCOLLEC
BALLASTED SYSTEM
STRUCT
VINCI &
Sirucluri.
175 E. WILBUR ROAD, SUITE H
P- 805.496.2100
MOUNTING DETAIL
ONLY
C I A T E S
ISAh D OAKS, CA 91360
\ nci@VlnclSE.com
%
RalnBuster 12000
RainBuster 12000 RTV Silicone Sealant/Adhesive is an acetoxy-based high performance
sealant/adhesive designed to prevent leaks, ft is formulated with 100% silicone and is NSF
approved for food service areas. Ideal for use in window glazing, spa manufac^ring and
perimeter sealing in varied Industrial applications. Available in clear and colors. Contact Top
Industrial at 1.800.473.1617 for more information.
Meets the Qualifications of:
FDA (Food and Drug Administration): 21 CFR 175.105 and 21 CFR 177.2600
National Sanitation Foundation (NSF) Standard 51
B\ ADHESIVE SPEC
SUNTREK
Yoar Solar Energy Company
SUNTREK INDUSTRIES
5 HOLLAND #215
IRVINE, CA 92618
C-46 LIC. #859460
(949) 348-9276
PROJECT
POOL THERMAL SOLAR
SYSTEM
LOCATION
Q
< CD
CO
—I
< o
CO
:^
LU
Q O)
< O
a: o)
5 CD
CM O
DESIGNER
ARI GONZALEZ
ATTACHMENT
DETAIL
REVISIONS
SHEET NO.
PT-4
WhisperFIOHigh Performance Pump
Quiet. Efficient. Durable.
The WhisperPTqDump delivers maximum circulation
efficiency at tlie lowest operating cost and long, trouble-
free life with minimal maintenance. Our legendary
hydraulic design has been ref ned over 40 years for
superior performance. No wonder more than 2 million
Pentair pumps have been selected by poo! professional||
• Unique FunnelFladiffuser and high-efficiency || n
impeller maximize water flow and energy efficiency
while minimizing turbulence and noise.
• Energy-efficient motor with commercial-grade frame,
rustproof stainless steel shaft, and permanently
lubricated, sealed bearings for long life.
• Available in single-speed and two-speed models.
• Ideal for pool and spa combinations and for
operating in-f oor cleaning systems.
• One-year limited warranty. See wan'anty for details.
Performance Curves
3 HP Sp««j 2 HP H9I Speed I!,« HP Hi^ Spcwj I HP SpMd 'A HP Hl# SpMd I,* HP Hi^ Sp«»J
Available
Pentair
Pool Products*
A A CIRCULATION PUMP
Solar Collectors-
Additional Notes;
1. Solar Collectors lay flat on roof NOTTO EXCEED 3'MIGHT FROM ROOF SURFACE.
OR MAX BUILDING HEIGHT
2. Solar Collectors will not exceed maximum building height
3. Solar Energy appurtenances shall be screened to the maximum extent
possible without compromising the effectiveness of the solar collectors
and shall be painted a color similar to the color of the surface upon which
they are mounted.
4. All PVC piping exposed to sunlight shall be protected from UV radiation.
5. A time switch or similar control mechanism shall be installed (existing) as a
part of the pool water circulation control system that will allow the pump to
be set or programmed to nin only during off-peal< electric demand period, and
for the minimum time necessary to maintain the water conditbn required by applicable
public health standards. Sec.114(b)3ii, 2008 Building Efficiency Standards..
Max
Building
Height
B ASOLAR COLLECTOR DEPICTION AND NOTES
SolarTouch Control Panel
Solqri
ouch
Water 60F
Target Temp 80F
System
Status eoo«
. OPERATION-
Menu: Press to access menu and scroll through options.
Less/More: Press arrows to lower or raise target temperature.
Move cursor up/down to adjust setting
within menus.
Enter: Press to select a menu item. Save a setting.
Disable and Re-Enable SolarTouch system:
Press and hold Enter tor three seconds.
FOfBuppVM Rflinproirf (TYPE 3) Conlrot Patwl In indoor <K outdoor ues,3ujUM«Ici •Miraning pool.spa lppkcation«.
ELECTRICAL RATINGS:
INPUT POWER; 120 VAC .4AMP cr Z40VAC, iAMP HV£0 hi,
COWttCT TO OWE SOUflCE OliY, SEE AC WIRING DIAGRAM IMSIDE EIJCLOSURE.
OUTPUTS:
LOW VOLTAGE: 24 VAC WGH VOLTA^: I30UTED DRV CONTACT- MAKMUM 240 VAC, 50^ HZ, 10 AhlP
PER RELAY CONTACT OUTPUT
Pentair Water
(T) Liquid Crystal Display (LCD): The system LCD displays backlighting for easy
viewing ofthe menu items and status messages. Each button press will light the
display. When an event message is displayed, the backlight will also be on.
(2) System Status LED indicator: When indicator is green, the system is running
normally. If indicator is red an error occurred. See page 10 for error conditions.
(3) Menu Button: Access Main Menu and exit menus. Press and hold this button to
access the Advanced Menu. Scroll through menu options. While in a menu or sub-
menu, access a previous menu level or item. If no menu activity is detected after 30
seconds, the main screen is displayed. All menu settings are permanently saved
and retained even after the unit is power off.
(4) Less / More buttons: Lower or Raise target water temperature.
Move cursor Up/Down to adjust menu setting within menus.
(5) Enter button: Select a menu item and save a menu setting. Press this button to
view Solar water set point temperature setting. The display will automatically revert
back to the monitoring water and solar temperatures after 30 seconds from the last
selection. Note: Press and hold the Enter button to disable Heating, Cooling and
Freeze Protect (display shows "SolarTouch Disabled"). Press and hold the Enter
button again to enable SolarTouch.
C^SOLAR CONTROL
SUNTREK
Your Solar Energy Company
SUNTREK INDUSTRIES
5 HOLLAND #215
IRVINE, CA 92618
C-46 LIC. #859460
(949) 348-9276
PROJECT
POOL THERMAL SOLAR
SYSTEM
LOCATION
Q
<
CQ
CO
—I
< o
CO
)^
Ul
Q O) < °
a: 05 <
I— *t
CM O
DESIGNER
ARI GONZALEZ
CONTROL/PUMP
SPEC SHEET
REVISIONS
SHEET NO.
PT-5
SRCCSearch Collector Record Detail https://secureclb.fsec.ucf.edu/srcc/coll_detail?srcc_id=2005004A
SOLAR COLLECTOR
CERTIFICATION AND RATING
CERTIFIED SOLAR COLLECTOR
BRCCl
SUPPLIER: Suntrek Industries, Inc
5 HoUand, Building 215
Irvine, CA 92618 USA
MODEL:
COLLECTOR TYPE: SunTrek Unglazed Flat-Plate
SRCC OG-100 CERTIFICATION#: 2005004A
ALL SIZES OFTHIS COLLECTOR MODS. ARE CERTIFIED
COLLECTOR THERMAL PERFORMANCE RATING
1 Megajaules Per Square Meter Per Day ThousandsofBTUPerSquareFootPerDay |
1 CATEGORY
(Ti-Ta)
CLEAR
DAY
MILDLY
CLOUDY
CLOUDY
DAY
CATEGORY
(Ti-Ta)
CLEAR
DAY
MILDLY
CLOUDY
CLOUDY 1
DAY
A (-5"C) 19.7 15.7 11.8 A (-9°F) 1.7 1.4 1.0 1
B (5-C) 12.7 8.9 5.1 B (9°r) 1.1 0.8 0.4
|c (20 °C) 5.5 2.2 0.0 C (36 "F) O.S 0.2 0.0 j
p (50 °C) 0.0 0.0 0.0 D (90 "F) 0.0 0.0 0
|E (80 °Cl 0.0 0.0 0.0 E (1*1 "F) 0.0 0.0 0.0 1
A- Pool Heatmg (Warro Climate) B- Pool Heating (Cool Climate) C- Water Heating (Wann Climate) D- Water Heating (Cool Climate) E-
Air Conditioning
Original Ortification Date: 10 -JUN-05
COLLECTOR SPECIFICATIONS
GrosiArea: 3.869m^ 41.64«'
Dry Weight: 21.3 kg 47.1b
Test Pressure; 414. KPa 60. psig
COLLECTOR MATERIALS
Frame: None
Cover (Outer): None
Cover (Inner): None
Net Aperature Area: 3.87 41.64 ft^
Fluid Capacity: 8.7 liter 2.3 gal
Pressure Drop
Flow AP
mils gpm Pa inHjO
V 11. . . . Tube-EPDM/ Absorber Matenal: ^, Plate - None
Absorber Coating: None
TECHNICAL INFORMATION
EfQcieucy Equation [NOTE: Based on gross area and (P)=Ti-Ta]
SI UMTS:
I p vrms:
q=0.8S6
q=0.8S6
-17J3390 (P)/I
-3.15906 (P)/I
0.03856 CP)^/I
0.00377 (ffa
Insulation Side:
Insulation Back:
Y INTERCEPT
0.860
0.860
None
None
SLOPE
-17.678 W/m'.°C
-3.114 Btu/hr.ft^.°F
Incident Angle Modifier [(S)=iycose - 1,0=<8<=60'']
Kto= 1 -0.083 (S) 0.059 (S)^
KTO=1 -0.03 (S) Linear Fit
REMARKS: Tests conducted outdoois.
Model Tested:
Test Fluid:
Test Flow Rate:
SunTrek
Water
70.1 ml/sjn^ 0.1032 gpm/tf
Technical Specifications for Suntreic Solar Pool Collectors
SUNTREK
Your Solar Energy Compai^
Collector: E)(truded Ethylene Propylene Diene Monomer (EPDM) elastomer extrusion
Water channel: ID = .190", OD = .333" Weight: 11b. per square foot dry, 1.5 Ib. per square foot wet
Manifold: Polypropylene; 2" in diameter, 72 channels
Maximum operating temperature: 160°
Maximum operating pressure: 40 psi
BTU rating: 1024 sqft/day
Optimum flow rate: 1 gpm per 0.1 sqft
1 sq. foot Volumetric capacity = .053 +/- 2% US Gallons (.201 +/- 2% Liters)
Made in the USA
US Patent #: Des. 420,420
Head Loss: .008' per sqft @. 1 gp m per sqft
- 6.0"-
.190"
EPDM Elastomer Water Channels
• 28"-
24"-
One Piece Polypropylene Manifold
Engineered for maximum performance, Suntrek solar pool heaters are designed unique continuous turbulent flow
water channels, this innovative design improves the transformation of solar energy into thermal energy for heating
your pool water The material used for the Suntrel< thermal heater is EPDM elastomer, which under normal operating
conditions will have a useful Ife of more than 20 years. The Suntrek heater becomes virtually a permanent part of
your pool and adds considerable value to your home or business.
Corporate Headquarters: 5 Holland #215 Irvine, CA 92618 (949) 348-9276 Fax (949) 348-1626
www.sijntreksolar.com
SOLAR COLLECTOR & MANIFOLD DETAIL
NO SCALE
SUNTREK
Yoor Sohtr Energy Campatty
SUNTREK INDUSTRIES
5 HOLLAND #215
IRVINE, CA 92618
C-46 LIC. #859460
(949) 348-9276
PROJECT
POOL THERMAL SOLAR
SYSTEM
LOCATION
Q
<
CO
a:
< o
CO
)^
o
I
LU
Q 03 < °
1"
I— *^
CM O
DESIGNER
ARI GONZALEZ
COLLECTOR SPEC
SHEETS
REVISIONS
SHEET NO.
PT-6
Solar pump wiring
(Disables solar cx:)ntrol and
solar pump when the primary
pool pump is shut off.)
Suntouch
Solar Control pump •5 CO
0
Transformer
240V '
Booster
punp relay
NVO
Primary
Pool Pump
Pool Timedock
^ - CM S
2 1 .i 1
A/C Sub Panel
Une1 240vpooi
pump breakers
240v solar
pump breakers
240v solar
pump breakets
Une 2
240vpooi
pump breakers
240v solar
pump breakers
240v solar
pump breakets
Line 1
240vpooi
pump breakers
240v solar
pump breakers
240v solar
pump breakets
Line 2
240vpooi
pump breakers
240v solar
pump breakers
240v solar
pump breakets
Line 1
240vpooi
pump breakers
240v solar
pump breakers
240v solar
pump breakets Line 2
240vpooi
pump breakers
240v solar
pump breakers
240v solar
pump breakets
WIRING DIAGRAM
SUNTREK
Your Solar Energy Company
SUNTREK INDUSTRIES
5 HOLLAND #215
IRVINE, CA 92618
C-46 LIC. #859460
(949) 348-9276
PROJECT
POOL THERMAL SOLAR
SYSTEM
LOCATION
Q
<
OQ
CO
_l
< o
w
a: o
I
LJJ
Q 03 < °
Cfl o)
I"
I—
CM O
DESIGNER
ARI GONZALEZ
PUMP
WIRING DIAGRAM
REVISIONS
SHEET NO.
PT-7
CB143052 2704 GATEWAY RD
SOLAR HEATING '
Final Inspection required by:
a Plan • CM&I • Fire a
SW •ISSUED GCV.
Approved Date By
BUILDING
PLANNING
ENGINEERING
FIRE Expedite? Y N It /IT-/
DIGrTAL FILES Required? Y N
HazMat
APCD
Health
Forms/Fees Sent Reed Due? By
Encina Y N
Fire Y N
HazHealthAPCD Y N
PE&M Y N
School Y N
Sewer Y N
Stormwater Y N
Special Inspection Y N
CFD: Y N
LandUse: Density: ImpArea: FY; Annex: Factor:
PFF: Y N
Comments Date Date Date Date
Building
Planning IZ'I'N
Engineering
Fire
Need7
• Done
• Done
• Done