Project Title: BURNS RES -ADDITION/REMODEL
194 SF 1ST FL ADDITION II 1,390 SF 2ND FL LOFT-GUEST ROOM
II 441 GARAGE BELOW II 152 SF BALCONY
Applicant:
GEIGER DANIEL
7378 CALLE CONIFERA
CARLSBAD CA 92009-8695
760-258-6469
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park in Lieu Fee
Park Fee
LFM Fee
Bridge Fee
Other Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
HMP Fee
Pot. Water Con. Fee
Meter Size
Add'l Pot. Water Con. Fee
Reel. Water Con. Fee
Green Bldg Stands (SB1473) Fee
Green Bldg Stands Plan Chk Fee
$875.94
$0.00
$613.16
$0.00
$0.00
$14.51
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$4.00
$0.00
Owner:
BURNS VICTOR V&KRISTIE T
2709 UNICORNIO ST
CARLSBAD CA 92009
Meter Size
Add'l Reel. Water Con. Fee
Meter Fee
SDCWA Fee
CFD Payoff Fee
PFF (3105540)
PFF (4305540)
License Tax (3104193)
License Tax (4304193)
Traffic Impact Fee (31 05541)
Traffic Impact Fee (4305541)
Sidewalk Fee
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Housing Impact Fee
Housing lnLieu Fee
Housing Credit Fee
Master Drainage Fee
Sewer Fee
Additional Fees
Fire Sprinkler Fees
TOTAL PERMIT FEES
Total Fees: $1,812.38 Total Payments to Date: $1,812.38 Balance Due:
Inspector:
FINAL APPROVk
Date: /z..-t'f'/ Clearance:
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$150.00
$85.00
$69.77
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$1,812.38
$0.00
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
f x · n f w i h h v I n iv n a N Tl E simil r hi t w i h at f limit i · I
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
11-04-2014
Storm Water Pollution Prevention Plan (SWPPP) Permit
Permit No:SW140215
Job Address:
Permit Type:
Parcel No:
Reference #:
CB#:
Project Title:
Applicant:
GEIGER DANIEL
2709 UNICORNIO ST CBAD
SWPPP
2153501600
CB141448
BURNS RES -ADDITION
7378 CALLE CONIFERA
CARLSBAD CA 92009-8695
760-258-6469
Emergency Contact:
VICTOR BURNS
760 672-8767
SWPPP Plan Check
SWPPP Inspections
Additional Fees
TOTAL PERMIT FEES
Status:
Lot#: 0 Applied:
Entered By:
Issued:
Inspect Area:
Tier:
Priority:
Owner:
BURNS VICTOR V&KRISTIE T
2709 UNICORNIO ST
CARLSBAD CA 92009
ISSUED
06/23/2014
SKS
11/04/2014
1
M
$52.00
$221.00
$0.00
$273.00
Total Fees: $273.00 Total Payments To Date: $273.00 Balance Due:
. ,~-u .. APPRQVA~
bArt! ~""'""....!.J~
444Qj,
$0.00
I THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: OFIRE
.4'~" "', ... W}j/ ~ CITY OF
CARLSBAD
JOB ADDRESS
CT/PROJECT #
ADDRESS
CITY
PHONE
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax: 760-602-8558
email: building@carlsbadca.gov
www.carlsbadca.gov
SUITEt/SPACEt/UNIT#
Plan Check No .
Est. Value
#BEDROOMS #BATHROOMS TENANT BUSINESS NAME
to\
STATE
FAX
EMAIL ~c L...,~·i.-'\,.
STATE LIC. # STATE LIC.#
0HEALTH D HAZMATIAPCO
FIRE SPRINKLERS
YESONo[iJ
ZIP crz.OC:l=f
ZIP
CITY BUS. LIC.#
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair an~ structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions ofthe Contractor's License Law !Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exem~t therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars (!ii500)).
WORKERS' COMPENSATION
Workers' Compensation Declaration: I hereby affirm under penalty of petjury one of the following declarations:
B I have and will maintain a certificate of consent to self·insure for workers' compensation as provided by Section 3700 of the Labor Code, for the pertonnance of the work for which this penn it is issued.
I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the perfonnance of the work for which this permn is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. Policy No. Expiration Date---------
~section need not be completed ffthe permn is for one hundred dollars ($100) or less.
U Certificate of Exemption: I certify that in the performance of the work for which this permn is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
Calffomia. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), In
addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees.
,8$ CONTRACTOR SIGNATURE 0AGENT DATE
D
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himse~ or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's Ucense Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's Uoense Law).
I am exempt under Section Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. DYes 0No
2. I (have I have not) signed an I penni! for the proposed work.
3. I have contracted with the the proposed construction (include name address I phone I contractors' license number):
4. I plan to i person to coordinate, supervise and provide the major work (include name I address I phone I contractors' license number):
following persons to provide the work indicated (include name I address I phone I type of work):
0AGENT
BOMPLETE THIS SECTION FOR NON·RI:SIDENTIAL BUILDING PERMITS ONLY
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration fonn or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Ll Yes Ll No
Is the applicant or future building occupant required to obtain a penni! from the air pollution control district or air quality management district? Ll Yes Ll No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Ll Yes Ll No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I certify that I have read the application and Slate that the alxMI infonnatlon Is correct and that the infonnatlon on the plans is accurate. I agree to comply with all City ordinances and State laws !elating to building consbuctlon.
I hereby authorize representative of the City of Carlsbad kl enter upon the above mentioned properly br inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABIUTIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permH is required for excavations over 5'0' deep and demoiHion or oonstruction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official the provisions of this Code shall expire by limHation and boo:lme nul and voKl ff the building oroork authorized by such penn it is not commenced ....;thin
180 days from the date of such pennH or ~the building authorized by such permH is suspended or abandoned at any time after the oork is oommenoed for a period of 180 days (Section 106.4.4 Unibnn Building Code).
~APPLICANT'S SIGNATURE DATE
Inspection List
CB141448 RESDNTL RAD BURNS RES - ADDITION/REMODEL
Date Inspection Item Inspector Act Comments
194 SF 1ST FL ADDITION // 1,390 SF 2ND
Permit#: Type:
29 Final Plumbing PB AP06/07/2016
23 Gas/Test/Repairs PB AP02/11/2016
23 Gas/Test/Repairs PB NR02/10/2016
39 Final Electrical PB NR10/19/2015
17 Interior Lath/Drywall PB AP10/08/2015
18 Exterior Lath/Drywall PB AP10/08/2015
18 Exterior Lath/Drywall PB CA10/01/2015
84 Rough Combo PB AP09/28/2015
84 Rough Combo PB NR09/14/2015
33 Service Change/Upgrade PB AP09/04/2015
13 Shear Panels/HD's PB AP07/29/2015
15 Roof/Reroof PB AP06/16/2015
11 Ftg/Foundation/Piers PB AP04/08/2015
31 Underground/Conduit-Wirin PB AP04/08/2015
22 Sewer/Water Service PB AP03/26/2015
Thursday, December 15, 2016 Page 1 of 1
PERMIT INSPECTION HISTORY REPORT (CB141448)
BLDG-Residential 06/23/2014Application Date:Permit Type:Owner:COOWNER BURNS VICTOR V &
KRISTIE T
Subdivision:Addition 11/04/2014Work Class:Issue Date:
2709 Unicornio St
Carlsbad, CA 92009
Address:12/05/2016Expiration Date:Status:
IVR Number: 700588
Closed - Finaled
Scheduled
Date Inspection Type Inspection No.Inspection Status Primary Inspector Reinspection CompleteActual
Start Date
12/15/2016 12/14/2016 BLDG-Final
Inspection
005467-2016 Passed Paul Burnette Complete
COMMENTS PassedChecklist Item
BLDG-Building Deficiency Yes
BLDG-Plumbing Final Yes
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
December 15, 2016 Page 1 of 1
NSI 420 Compass Road • Ocean~Jde •CA • 92054
Office (760) 2n -0404 • Fax~(760 453-2144
NARBETH STRU~~URAL INSPECTION IJOBNo. <DioAre: 6 /ll /lr ®
Authorized
j!j ACI ~ ICBO
Special Inspector
0 RBNFORCED _CONCRETE 0 srRUCT. STEEL ASSEMBL: 0 SPFAY·AEffi~DPROOANG . 0 PRe-sTRessED coNcRETE 0 "RBNFORoeo GYPSuM g oTHeR r~ L · ®
D RBNFORCED MASONRY D DEEP FOUNDATION
OWNER OR PROJECT NAME .bJ ""''"' ( <G-> •
CONSTR. MAT'L ~jE• GRADE, ETC.) @)i?ESIGN 1"7)1 SOURCE OF MFGR: ~ (JO)t T ·1STRENGTH \VI . ® ENGIN[.A. Co.s:IA B"~,
DESCRIBE MAT'L IMIX DESIGN, RE·BAR GRADE & MFGR. WELD-ROD, ETC.)
INSPEC~ ARRIVAL Ifill DETAIL..ED
TJON \!!/ TIME l.!.::l' REPORT OF
DATE DEPARTURE WORK
TIME INSPECTED
CONTR. DOING \1Ef'ORTED WORK
LAB. RECEMNG & TESTING CONSTR. "i~T'L SAMPLES
LOCATION OF WORK INSPECTED, TEST SAMPLES TAKEN, WORK REJECTED, J08 PROBLEMS, PROGRESS, REMARKS. ETC. @
INCLUDES INFORMATION ABOUT-AMOUNTS OF MATERIAL PLACED OR WORK PREFORMED, NUMBER, "TYPE & I DENT, NO'S OF
TEST SAMPLES TAKEN, STRUCT, CONNECTIONS (WElDS MADE, H.T. BOLTS TORQUED) CHECKI~. ETC.
J
.
THIS REPORT DOES NOT RELIEVE THE CONTRACTOR OF HIS RESPONSIBILJT'i' TO BUILD
. PER THE PLANS, SPECIFICAtiONS AND ALL APPLJCABLE CODES. •
TO THE BEST OF MY KNOWLEDGE, WORK INSPECTED WAS IN ACCORDANCE INSPECTOR (PRINI"OR;zli~ ~I(, #tJ f tJ MpH rlt @
WITH THE SOIL INVESTIGATION RECOMMENDATIONS. THE APPROVED PLANS, :
SPECIFI~TIONS, AND APPUCABLE SECTIONS OF THE u.s.c. BUILDING CODE, SIGNATURE . . 5. I
UNLESSOTHERWISENOTED. •• DATESIGNED G I I ]t /5"cEFmRCATE.NO •. ~).035 It<~
WHITE· NSI CANARY • Contractor PINK • Building Official
•
03/19/2015 13:32 FAX 7607211835 ACE WELDING ~001/001
FAX FROM: 1325 S Coast Hwy
Oceanside, CA 92054
WELDING AND FABRICATION INC.
r ·· ·---·-·-·-·-·-···-·~--·-·-·· ·-·· ·· ·------1---······· ··· I To: j Carlsbad Building Dept !·-···--···----··-·-·--·-·····-·-··-· . . j ---------·----------·---.. .. ................... ' ... .
~~~~-~any: __ j?ity~f~arls~~-.
I . l Fax: !(760) 602-8558
!-------·-··---·~--.. ·---~---·--·--·-------+--·-... .. ··--------·-··· ·······-····""'''""'' _____ , .. _ I Tel: \ (760) 602-2719 1-s~bje~=-··· lst,~~w~lding
1. ····---------·-·-·------········ ....• L ..... _ ..... --------·-·-··-··-·····-· . . ..... ___ ......... ___________ --·-----~--·-· ... .. . . ..... --·-·-·-------------..
Good Afternoon,
We are welding up steel columns and beams for:
2709 Unicornio
Carlsbad, CA 92009
Permit #CB141448
Tel: (760) 722-2588
Fax: (760) 721-1835
steve@aceweldjngoceanside.com
Cont. Lise #991341
LA City Lise #FB03013
Steve Wootten
03/19/15
We are an LA Certified shop (Lise #FB03013) and it is my understanding City of
Carlsbad accepts this certification and that we do not need special inspection on the
welding.
We will submit shop drawings to the engineer and have them stamped prior to
fabrication.
We will make sure that contractor has a copy of this letter and stamped shop drawing
on site.
Please contact me ASAP if there is anything else needed.
Thanks
Steve Wootten
DATE: 10/28/14
JURISDICTION: Carlsbad
PLAN CHECK NO.: 14-1448
EsGil Corporation
In q>artnersliip witli qovernment for aJuiftfina Safety
SET: II
PROJECT ADDRESS: 2709 Unicornio )l«'f~>(
l:l APPLICANT
l:l JURIS.
l:l PLAN REVIEWER
l:l FILE
PROJECT NAME: Room Additions/Deck/Remodel/Garage Extension for Burns
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
C8J The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
C8J EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#:
Date contacted: (by: )
Mail Telephone Fax In Person
~ REMARKS: 1) Complete special inspection!J~Iisted on cover sheet. 2) Engineer-of-
record to sign the structural sheets.
By: Ray Fuller Enclosures:
EsGil Corporation
0 GA 0 EJ 0 MB 0 PC 10/21/14
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
EsGil Corporation
In <Partnersliip witli (jo11ernment for (]Jui{tfino Safety
DATE: 07/03/14
JURISDICTION: Carlsbad
PLAN CHECK NO.: 14-1448
PROJECT ADDRESS: 2709 Unicornio ~~
SET: I
CJ~ICANT
~ ~~~~S. 0 PLAN REVIEWER
CJ FILE
PROJECT NAME: Room Additions/Deck/Remodel/Garage Extension for Burns
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Daniel Geiger
D EsGil Corporation staff did not advise the applicant that the plan check has been completed.
I:8J EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Daniel GeigJ5 Telephone#: (760) 258-6469
Date contacted: l-1 (b~ ) Email: danielgeigerdesign@gmail.com
LMail X Telephone')( Fax In Person
D REMARKS:
By: Ray Fuller Enclosures:
EsGil Corporation
D GA D EJ D MB D PC 06/26/14
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
Carlsbad 14-1448
07/03/14
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK NO.: 14-1448 JURISDICTION: Carlsbad
PROJECT ADDRESS: 2709 Unicornio Way
FLOOR AREA:
Additions 1584
Garage 441
Deck 152
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 07/03/14
DATE INITIAL PLAN REVIEW
COMPLETED: 07/03/14
FOREWORD (PLEASE READ):
STORIES: 2-3
HEIGHT: Varies
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 06/26/14
PLAN REVIEWER: Ray Fuller
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2013 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2012 IRC, 2012 IBC,
2012 UPC, 2012 UMC and 2011 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2012 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number. specification section. etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad 14-1448
07/03/14
1. Please make all corrections on the original tracings, as requested in the correction
list. Submit three sets of plans for residential projects. For expeditious processing,
corrected sets can be submitted in one of two ways:
1 ). Deliver all corrected sets of plans and calculations/reports directly to the City
of Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92009, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2). Bring one corrected set of plans and calculations/reports to EsGil
Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858)
560-1468. Deliver all remaining sets of plans and calculations/reports directly to
the City of Carlsbad Building Department for routing to their Planning, Engineering
and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete
2. Verify that the final sets of plans and any new calculations will be stamped and
signed by engineer and /or architect of record also.
3. Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 2013 California Residential Code, which adopts the 2012 IRC,
2012 UMC, 2012 UPC and the 2011 NEC. Section R106.1.
4. Please indicate on the plans whether the existing residence has a fire sprinkler
system installed. If so, then provide a note stating that any additions/alterations
will be provided with an automatic residential fire sprinkler system.
5. Plans to clearly reflect if proposed garage footings will be surcharging existing
retaining walls on the east side as no details provided that state if retaining walls
are supporting fill or a cut?
6. Where does keynote 4 apply as noted on 1.1 (9 ft high CMU wall)? If does
apply could not locate the design calculations and/or details on the plans?
Clearly specify height retaining if applies and whether this is a cantilevered or
restrained wall? Structural is reflecting a 4 ft high restrained wall by entry? Sheet
2.1 keynote 22 states to see sheet 6.2? Please clarify.
7. Please complete the City special inspection list for items listed on cover sheet,
epoxy anchors and soils compliance as noted on S-1 and 4" or less nailing.
Please provide one complete list of all items requiring special inspection.
8. Provide a copy of the project soil report. The City of Carlsbad requires a soils
report for any addition exceeding 500 sq ft and/or for any two/three story
construction. The report shall include foundation design recommendations based
on the engineer's findings and shall comply with Section R401.4. Please verify
report is current (as most reports expire after one to three years). Provide copies
of any updated reports and verify soils report addresses current code parameters
(IBC and not UBC) liquidation potential etc.
Carlsbad 14-1448
07/03/14
9. If applies: The soils engineer recommended that he/she review the foundation
excavations. Note on the foundation plan that "Prior to the contractor requesting
a Building Department foundation inspection, the soils engineer shall advise the
building official in writing that:
a) The building pad was prepared in accordance with the soils report,
b) The utility trenches have been properly backfilled and compacted, and
c) The foundation excavations, the soils expansive characteristics and
bearing capacity conform to the soils report."
10. Provide a letter from the soils engineer confirming that the foundation plan,
grading plan and specifications have been reviewed and that it has been
determined that the recommendations in the soils report are properly
incorporated into the construction documents (when required by the soil report).
11. Show distance from foundation to edge of cut or fill slopes ("distance-to-
daylight") and show slope and heights of cuts and fills. Section R403.1.7.
12. If applies : Where expansive or collapsible soils are known to exit, show on the
plans a controlled method of water disposal from roofs that will collect and
discharge roof drainage to the ground surface at least 5' from the foundation.
Section R801.3
13. Show on the plan the amperage of the relocated electrical service, and the
location of any sub*panels. Sub panels if provided cannot be placed in fire wall,
closets, and bathrooms or in any area where that does not provide a minimum
30" clear width, 36" clearance in front and adequate head clearance.
14. Please provide the required single line diagram, panel schedule and load
calculations as the additional 1584 sq ft places it over the 5000 sq ft requiring
this.
15. If the project required over 200 amps then please verify the following are
provided.
a) Single line to reflect correct bonding sizes for water (1/0 cu) and
grounding electrode .
b) Specify type of conduit and conductors proposed for all sub feeds,
Specify method of proposed grounding sub panels back to the main
service (i.e. conduit or conductor).
c) Sub panels if provided cannot be placed in fire wall, closets , bathrooms
or in any area where that does not provide a minimum 30" clear width, 36"
clearance in front and adequate head clearance.
d) Note on the single line diagram that the AIC rating for the service feeder
overcurrent devices is a minimum of 22,000 AIC and that the system is
designed as a "Series Rated System"(in order to limit available fault
currents to 10,000 amps on branch circuits).
16. Owner/designer to sign the CF1-R forms.
Carlsbad 14-1448
07/03/14
17. The energy calculations seem to correctly reflect sq footage to be 5853 total with
addition. The cover sheet notes the total sq footage to be 4279? Please clarify
how this was derived and why energy calculations are 1660 sq ft higher?
18. A portion of bathroom 1 and enclosed hallway on 2.1 appears to be added sq
footage. If this is correct then could not determine for example why foundation
plan did not reflect required footings?
19. Recheck plans for tempered window locations i.e. within 2 ft of interior/exterior
doors, within a 5 ft radius of tub area (unless 5 ft above per 2013 IRC) shower
areas (unless 5 ft above inlet of shower) and stairwells if applicable. Section
R308.4 See replacement 4050 at bedroom 2 as within 2 ft of door 2. Should
consider existing 2070 at entry to be tempered due to new door 25.
20. Noting window 6 to be a 1430 and appears should be a 3014 instead? The
window schedule notes it to be a 3050? The elevations on 3.0 seem to reflect
some thing different. Please clarify and verify if needs to be tempered.
21. Door 6 from garage to laundry room to be a self-closing door, self latching
either 1-3/8" solid core or a listed 20 minute assembly, for openings between
garage and dwelling. Section R302.5.1. The plans are reflecting hollow core?
The current code as added the words "Self Latching".
22. The garage shall be separated from the residence and its attic area by not less
than%" gypsum board applied to the garage side (at walls). Garages beneath
habitable rooms shall be separated by not less than 5/8" Type X gypsum board.
Section R302.6
23. Sheet 2.2. is reflecting adding a balcony to a existing deck off the living room.
How is this to be done? Appears may be demoing existing deck and rebuilding
and if that is the case then scope of work on cover sheet needs to reflect this.
24. Could not locate where type of deck material was noted. Specify on the plans
the following information for the deck materials, per Section R 106.1.1:
Manufacturer's name and ICC approval number, or equal. One of the decks is
noting the slope to 1/8" and the minimum is 1/4".
25. Provide guard details for both exterior and interior locations and reference to all
applicable locations on the plans. (Section R312) No details provided for the
deck off the living room and for new deck off the wetbar keynote 2 on 2.2. states
36 inch glass railing? Plans need to clearly detail and reference require guards.
a) Shall have a height of 42" (may be 34" along the sides of stairs).
b) Openings between railings shall be less than 4". The triangular openings
formed by the riser, tread and bottom element of a guardrail at a stair
shall be less than 6".
c) Shall be detailed to show capability to resist a concentrated load of 200
pounds in any direction along the top rail. Table R301.5.
Carlsbad 14-1448
07/03/14
26. The plans are reflecting glass railings. Detail and reference on the plans the
connections to show capability to resist a concentrated load of 200 pounds in
any direction along the top rail. Table R301.5. Plans to reflect thickness of the
glass railing and must be tempered. Detail and reference the glass guard to be
supported on all four sides per Section 2407. If not providing a top rail then
provide design calculations and details to show that glass railing can resist
lateral forces per Section 1607.7.1 and must obtain Building Official approval
per Section 2407.1.2
27. It is unclear if existing entry porch deck and/or stairs are being demolished and
rebuilt. Identified so add to scope of work and provide details.
28. Provide stairway and landing details for both exterior and interior locations
and reference to all applicable locations on the plans. Section R311.7.
a) Maximum rise is 7 -3/4" and minimum run is 1 0".
b) Minimum headroom is 6'-8".
c) Minimum width is 36".
d) A nosing (between %" and 1-%") shall be provided on stairways with solid
risers. Exception: No nosing is required if the tread depth is at least 11
inches. Section R311. 7 .4.3
e) Open risers are only permitted if the opening between treads does not
permit the passage of a 4" diameter sphere. Section R311.7.4.3
29. Provide handrail details for both exterior and interior locations and reference
to all applicable locations on the plans. (Section R311.7.7)
a) Shall be provided on at least one side of each stairway with four or more
risers.
b) Handrails and extensions shall be 34" to 38" above nosing of treads and
be continuous.
c) The handgrip portion of all handrails shall be not less than 1-1/4 inches
nor more than 2 inches in cross-sectional dimension. See Section
R311.7.7.3 for alternatives.
d) Handrails projecting from walls shall have at least 1-1/2 inches between
the wall and the handrail.
e) Ends of handrails shall be returned or shall have rounded terminations or
bends.
30. If applies: Show the sizes/locations of roof/deck drains and overflows. Minimum
3" required if runs horizontal, 2" in vertical and minimum scupper size is 4".
Plans to reflect how water is being diverted to drains i.e. crickets etc.
31. The left corner on sheet 2.2 is noting this to be storage. This is considered a
bedroom and must be provided with required egress, smoke detectors etc.
32. Show or note that exterior doors may swing outward only if the exterior landing
is not more than 1% inches lower than the top of the threshold. R311.3.1. See
doors 12 and 14 on 2.2. Recheck all locations.
Carlsbad 14-1448
07/03/14
33. No architectural or structural details provided for landing and stairs as shown out
side of kitchen on 2.2. Cannot complete plan check until items like these are
reviewed closely and addressed by both architect and engineer-of-record of
record.
34. For stairs and landing leading to loft clearly note minimum 36" clear width
required.
35. Could not determine what the height of the walls at slope ceilings are to be .
See lines A, A.5 and b for example.
36. Show the thickness of the butted glass, whether or not tempered and to be
supported on all four sides. See windows 18 and 19 at corner of media room.
37. Show or note on plans that all rake walls are to be ballooned framed.
38. Specify on the plans that any existing smoke alarms that are more than 10
years old will be replaced. Section R314.3.2.
39. Show that carbon monoxide alarms will be provided outside each separate
sleeping area in the immediate vicinity of the bedrooms and on each story.
Section R315.2.
40. Show that smoke alarms will be provided in all existing bedrooms, hallways
leading to bedrooms and on each floor Section R314.3.1.
41. Detail the dryer exhaust duct design from the dryers to the exterior. Verify dryer
vent termination will be a minimum of 3 ft from any opening. The maximum
length is 14 feet with a maximum of two 90-degree elbows or provide the
manufacturer's duct length specification description on the plans: Include the
dryer specifications (manufacturer, model, and fuel type) as well as the duct
description (size and type). CMC Section 504.3.
42. Include on the plans the following specifications for any new electrical devices
being installed :
a) Tamper resistant receptacles required for all new locations .
b) Weather resistant type for any new receptacles installed in damp or wet
locations (outside).
c) Arc-fault protection for all new outlets (not just receptacles) located in
rooms described in NEC 21 0.12(8): Family, living, bedrooms, dining,
halls, etc.
d) GFCI protected outlets for any new locations described in NEC 210.8:
Kitchens, garages, bathrooms, outdoors, within 6' of a sink, etc.
43. Could not determine why 220 shown at wet bar on 5.2 ?
44. Could not determine how lights in storage (change to bedroom) comply with T-
24 as no dimmers shown for example?
Carlsbad 14-1448
07/03/14
45. In bathrooms, laundry rooms, and utility rooms all fixtures must be high efficacy
style or be controlled by a vacancy sensor. Dimmers not a option in laundry
rooms and could not determine how lav sinks comply?
46. Specify on the plans the following information for the roof materials, per Section
R 1 06.1.1: Manufacturer's name and ICC approval number, or equal.
47. Specify slope of required cricket (minimum%" per ft) and approved type of
roofing material i.e. Gl flashing, hop mop or torch down.
48. Specify on the plans for any new plumbing fixtures being added: New water
closets shall use no more than 1.28 gallons of water per flush, kitchen faucets
may not exceed 1.8 GPM, lavatories are limited to 1.5 GPM, and showerheads
may not exceed 2.0 GPM of flow. CPC Section 403 and 408.
49. Residential ventilation requirements:
• Kitchens require exhaust fans (either intermittent/1 00 cfm or continuous/5 air
changes/hour), ducted to the exterior. Detail compliance by including a
complying exhaust fan or a ducted range hood to the exterior. Note: CFM
and noise rating ("Sone") must be specified on the plans.
• Bathrooms require exhaust fans (minimum 50 cfm) to be ducted to the
exterior. Note: CFM and noise rating ("Sone") must be specified on the
plans. A bathroom is defined "as a room with a bathtub, shower, or spa or
some similar source of moisture".
• Mechanical whole house ventilation must be provided. Include the following
information: Fan sizing (cfm), "Sone" specification, and the duct sizing and
length. Note: The information must match or exceed the design found on
CF-6R-MECH energy forms.
• All fans installed to meet the preceding requirements must be specified at a
noise rating of a maximum 1 "Sone" (for the continuous use calculation) or 3
"Sone" (for the intermittent use calculation).
• For additions exceeding 1, 000 sq. ft: Compliance with the above ventilation
requirements must be shown on the plans. The whole house ventilation CFM
shall be based upon the entire (existing and addition) square footage, not just
the addition.
50. Specify on the plans whether the existing house was built before or after 1994.
For additions or improvements to a residence built before 1994, note on the
plans that existing "noncompliant" fixtures (toilets that use more than 1.6 gallons
of water per flush, urinals that use more than one gallon of water per flush,
showerheads that have a flow capacity of more than 2.5 gallons of water per
minute, and interior faucets that emit more than 2.2 gallons of water per minute)
shall be replaced. Certification of compliance shall be given to the building
inspector prior to final permit approval. California SB407.
51. Noting existing 3020 at master shower on 2.1 and appears to be 5030 per floor
plan and elevations?
Carlsbad 14-1448
07/03/14
52. Noting existing 4080 at living room on 2.2 and appears to be a 8040 per west
elevation on 4.2?
53. Could not determine why sheet index does not reflect sheet 7.0 (door /window
schedule)?
• RESIDENTIAL GREEN BUILDING STANDARDS
The California Building Standards Commission has adopted the Green Building
Standards Code which became effective January 1, 2011 and must be enforced by the
local building official. The following mandatory requirements for residential construction
must be included on your plans. CGC Section 1 01.3. }he Sta~~ards apply to newly
constructed residential buildings, ltQflg with~ ~d,djtlonslaltitatlons thatincrease the
building's conditioned ~rea, volume or size. CGC Section 303.1.1. Provide a sheet on
the plans labeled "Green Building Code Requirements" and include the following
notes as applicable.
54. Storm water drainage/retention during construction. Note on the plans:
Projects which disturb less than one acre of soil shall manage storm water
drainage during construction by one of the following: A. Retention basins. B.
Where storm water is conveyed to a public drainage system, water shall be
filtered by use of a barrier system, wattle or other approved method. CGC
4.106.2.
55. Grading and paving. Note on the plans that site grading or drainage system will
manage all surface water flows to keep water from entering buildings (swales,
water collection, French drains, etc.). CGC 4.1 06.3. Exception: Additions not
altering the drainage path.
56. Note on the plans that when a shower is provided with multiple shower heads,
the sum of flow to all the heads shall not exceed 2.0 gpm@ 80 psi, or the
shower shall be designed so that only one head is on at a time. CGC
4.303.1.3.2.
57. Recycling. Note on the plans that a minimum of 50% of construction waste is to
be recycled. CGC 4.408.1.
58. Recycling. Note on the plans that the contractor shall submit a Construction
Waste Management Plan to the jurisdiction agency that regulates waste
management, per CGC 4.408.2.
59. Operation and maintenance manual. Note on the plans that the builder is to
provide an operation manual (containing information for maintaining appliances,
etc.) for the owner at the time of final inspection. CGC 4.41 0.1.
60. Pollutant control. Note on the plans that during construction, ends of duct
openings are to be sealed, and mechanical equipment is to be covered. CGC
4.504.1.
Carlsbad 14-1448
07/03/14
61. Pollutant control. Note on the plans that VOC's must comply with the
limitations listed in Section 4.504.3 and Tables 4.504.1, 4.504.2, 4.504.3 and
4.504.5 for: Adhesives, Paints and Coatings, Carpet and Composition Wood
Products. CGC 4.504.2.
62. Interior moisture control. Note on the plans that the moisture content of wood
shall not exceed 19% before it is enclosed in construction. The moisture content
needs to be certified by one of 3 methods specified in Section 4.505.3. Building
materials with visible signs of water damage should not be used in construction.
The moisture content must be determined by the contractor by one of the
methods listed in CGC 4.505.3.
63. Indoor air quality. Note on the plans that bathroom fans shall be Energy Star
rated, vented directly to the outside and controlled by a humidistat. CGC
4.506.1.
64. Note on the plans that prior to final inspection the licensed contractor, architect
or engineer in responsible charge of the overall construction must provide to the
building department official written verification that all applicable provisions
from the Green Building Standards Code have been implemented as part of the
construction. CGC 1 02.3.
65. Plans and calculations need to be reviewed by engineer or record to verify that
they are complete and that they reflect a complete vertical and lateral load path
from roof sheathing to foundation below. Some examples are listed below.
66. Recheck plans for correct shear wall lengths. 1st line checked was line 3 on 6.4
where noting length to be 9ft instead of 16.7. Recheck all locations. ·
67. Recheck plans for correct type of shear wall. 1st line checked was line 3 on 6.4
where noting it to be type 1 and on 6.3 it is type 3.
68. Could not determine what happen to point load from RB-1 (8.5 kips)? Verify
continuous load path to foundation and that foundation is adequate .
69. Could not determine where some of bearing points were to take place? For
example see FB1 on 6.3 with a design span of 9.5 ft.
70. Could not determine why on6.2 the posts are shown directed in line with FB16
and 17 as shown offset by a 1ft?
71. Cantilevered column detail 9/S4 does not reflect seismic bends, base plate size,
depth below base plate to soils, if a pad with steel /bolts to be provided etc. It
appears to be referencing detail 6 which does not apply? Detail 9/S-4 seems to
reflect 4 ft depth and notes on 6.1 state 5 ft?
72. Please reference a retrofit spread footing detail as shown at bath1 area on 6.1?
Carlsbad 14-1448
07/03/14
73. Please provide the Steel Strong walls details referencing on the plans.
Foundation plan to clearly reflect size, type and length of hold down bolts
proposing.
74. Please verify detaii13/S4 is referenced to all applicable locations on the plans
and could not determine why this is referenced to line 1 on 6.1 as this is a new
footing?
75. Could not locate where plans reflected 16ft of shear (either existing or proposed
for line 2 on 6.2 or the 13 ft for line B)?
76. Could not determine why noting two 9 ft of shear panels for line C on 6.1 and on
6.2 it is correctly noted as 9ft and 5ft?
77. Detail 3/S5 noting maximum 4' clear and should be 3.99" as must be less than 4"
per item 28(e) above.
78. Referencing detail 3/S5 and 6/S5 to line D on 6.2. One detail states 4 ft o.c and
other 5 ft o.c for post? Please clarify.
79. Two detail 1 O's on S4 and could not determine why referencing detail 1 O/S2 to
W1 0 x45 On line 1 on 6.2?
80. If detail is to be 1 O/S4 instead then could not determine why detail states 24" o.c.
for welded bolts and note on 6.2 states 36" o.c.?
81. Detail 9/S2 above SSW on line 1 is reflecting shear transfer (A-35's) to be per
shear schedule. Shear schedule does not address transfer above Steel Strong
Walls?
82. Could not determine how detail 13/S3 applies as referenced to left of line 1 on
6.2.
83. Please recheck placement of post for hold downs for line 1 on 6.2 at south side
of the 7 ft shear panel as appears to be missing?
• CITY OF CARLSBAD REQUIREMENTS
84. When special inspection is required, the designer shall complete the city's "Special
Inspection Agreement".
85. All new residential buildings, including additions, require a soils report. An update
letter is required if the report is more than 3 years old. If a room addition is less
than 500 sq. ft. in area and only one story, then a soils report is not required.
The maximum allowable soil bearing value used in any design must be 1000 psf
for this exception.
Carlsbad 14-1448
07/03/14
86. Plans to reflect finish grade to be sloped away from foundations at a 2% slope
(allowed per City policy which less restrictive than the 5% slope given in the
CBC/CRC).
87. Please go thru plans very carefully to verify architectural and structural complete.
• To speed up the review process, note on this list (or a copy) where each correction
item has been addressed, i.e., plan sheet, note or detail number, calculation page,
etc.
• Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly describe
them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes ( ) No ( )
• The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468,
to perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Ray Fuller at Esgil Corporation. Thank
you.
Carlsbad 14-1448
07/03/14
~~~> "~ CITY OF
CARLSBAD
SPECIAL INSPECTION
AGREEMENT
B-45
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed
requires special inspection, structural observation and construction material testing.
'roject/Permit: _________ _ Project Address; ________________ _
A. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are Owner-Builder
D. (If you checked as owner-builder you must also complete Section B of this agreement.)
Name: (Please print.__ ___ -=--::------------::-,.,-,-------------::--c--------
tFirotl IMI) (Loot)
Mailing Addres...._ _______________________________ _
Email_· ------------------------Phone: __________ _
I am: OProperty Owner OProperty Owner's Agent of Record OArchitect of Record OEngineer of Record
State of California Registration Nurnbe · Expiration Date: _______ _
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the state of California, that I have read,
understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural
observations, construction materials testing and off-site fabrication of building components, as prescribed in the statement of
special inspections noted on the approved plans and, as required by the California Building Code.
Signatur....._ ______________________ Date:------------
8. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor I builder I owner-builder.
Contractor's Company Name:. __________________ Please check If you are OWner-Builder Cl
Name: (Please print)----------------------------------
(First) {M I) (last)
Mailing Address: ________________________________ _
Email: ________________________ Phone: __________ _
state of California Contractor's License Number: __________ Expiration Date: _______ _
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the
building official;
I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualified person within our (the contractor's) organization to exercise such control.
• I will provide a ffnal report/ letter In compliance with CBC Section 1704.1.2 prior to requesting ffnal
Inspection.
Signature~: _______________________ ,Date:-----------
B-45 Page 1 of 1 Rev. 08/11
i. ' I ~
Carlsbad 14-1448
07/03/14
[DO NOT PAY-THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 14-1448
PREPARED BY: Ray Fuller DATE: 07/03/14
BUILDING ADDRESS: 2709 Unicornio Way
BUILDING OCCUPANCY: R3 U TYPE OF CONSTRUCTION: VB
BUILDING AREA Valuation
PORTION (Sq. Ft.) Multiplier
Addition 1584 .)cj 131.73
Garage 441 / 26.61
Decks 152 --15.57
Air Conditioning 1584 4.19
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance ---------------------------3 Bldg. Permit Fee by Ordinance """
~-----~-·. -------·--~--·--·---
·-----------·-----------·---------~--
Plan Check Fee by Ordinance ""'
--· -·-·-·-----·---·---·----·---·------------·
Type of Review: 0 Complete Review
D Repetitive Fee ~3 Repeats
D Other
O Hourly
EsGil Fee
Comments: Add Y2 hour Cal Green $43.00
Reg. VALUE
Mod.
D Structural Only
1-------liHr @ •
($)
208,660
11,735
2,367
6,637
229,399
$1,205.221
$783.391
$674.921
Sheet 1 of 1
macvalue.doc +
«~~\ ~ CITY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
DATE: 7/15/14 PROJECT NAME: Burns residential addition PROJECT ID:
PLAN CHECK NO:CB141448 SET#: I ADDRESS: 2709 Unicornio St APN:215-350-16
VALUATION: $145,141 APPLICANT CONTACT: danielgeigerdesign@gmail.com
ui/ Tli~ ;n check review trans~i;t~ ;l; itify you of clearance by.
LAND DEVELOPMENT ENGINEERING DIVISION
Final Impe c tion by the Construction & Inspection Division is required: Yes No X
rf!!j For status from a division not marked below, please call 760-602-2719
lXI lhis plan check review is NaCOMPLm Items missing or incorrect are listed below
760-602-2773
Linda.Ontiveros@carlsbadca.gov
Remarks: Complete storm water compliance forms, E-29, E-34 --forms were not
completed at project submittal.
«~~' ~ CITY OF
CARLSBAD
STORM WATER COMPLIANCE FORM
TIER 1 CONSTRUCTION SWPPP
E-29
STORM WATER COMPLIANCE CERTIFICATE
' My project is not in a category of permit types exempt from the Construction
SWPPP requirements
' My project is not located inside or within 200 feet of an environmentally
sensitive area with a significant potential for contributing pollutants to nearby
receiving waters by way of storm water runoff or non-storm water
discharge(s).
' My project does not require a grading plan pursuant to the Carlsbad
Grading Ordinance (Chapter 15.16 of the Carlsbad Municipal Code)
' My project will not resu~ in 2,500 square feet or more of soils disturbance
including any associated construction staging, stockpiling, pavement
removal, equipment storage, refueling and maintenance areas that meets
one or more of the additional following criteria:
located within 200 feet of an environmentally sensitive area or the
Pacific Ocean; and/or,
disturbed area is located on a slope with a grade at or exceeding 5
horizontal to 1 vertical; and/or
disturbed area is located along or within 30 feet of a storm drain inlet, an
open drainage channel or watercourse; and/or
construction will be initiated during the rainy season or will extend into
the rainy season (Oct. 1 through April 30).
I CERTIFY TO THE BEST OF MY KNOWLEDGE THAT ALL OF THE ABOVE
CHECKED STATEMENTS ARE TRUE AND CORRECT. I AM SUBMITTING
FOR CITY APPROVAL A TIER 1 CONSTRUCTION SWPPP PREPARED IN
ACCORDANCE WITH THE REQUIREMENTS OF CITY STANDARDS.
I UNDERSTAND AND ACKNOWLEDGE THAT I MUST: (1) IMPLEMENT BEST
MANAGEMENT PRACTICES (BMPS) DURING CONSTRUCTION ACTIVITIES
TO THE MAXIMUM EXTENT PRACTICABLE TO MINIMIZE THE
MOBILIZATION OF POLLUTANTS SUCH AS SEDIMENT AND TO MINIMIZE
THE EXPOSURE OF STORM WATER TO CONSTRUCTION RELATED
POLLUTANTS; AND, (2) ADHERE TO, AND AT ALL TIMES, COMPLY WITH
THIS CITY APPROVED TIER 1 CONSTRUCTION SWPPP THROUGHOUT THE
DURATION OF THE CONSTRUCTION ACTIVITIES UNTIL THE
CONSTRUCTION WORK IS COMPLETE AND APPROVED BY THE CITY OF
CARLSBAD.
W-2-.!JL.;.TceA A(
~~~~~Ii:iRE) ll/4/i 1 OWl '""""'"_,,E) DATE
E-29
STORM WATER POLLUTION PREVENTION NOTES
1. ALL NECESSARY EQUIPMENT AND MATERIALS
SHALL BE AVAILABLE ON SITE TO FACILITATE
RAPID INSTALLATION OF EROSION AND
SEDIMENT CONTROL BMPS WHEN RAIN IS
EMINENT.
2. THE OWNER/CONTRACTOR SHALL RESTORE
ALL EROSION CONTROL DEVICES TO
WORKING ORDER TO THE SATISFACTION OF
THE CITY ENGINEER AFTER EACH RUN-OFF
PRODUCING RAINFALL.
3. THE OWNER/CONTRACTOR SHALL INSTALL
ADDITIONAL EROSION CONTROL MEASURES
AS MAY BE REQUIRED BY THE CITY
ENGINEERING OR BUILDING INSPECTOR DUE
TO UNCOMPLETED GRADING OPERATIONS OR
UNFORESEEN CIRCUMSTANCES WHICH MAY
ARISE.
4. ALL REMOVABLE PROTECTIVE DEVICES SHALL
BE IN PLACE AT THE END OF EACH WORKING
DAY WHEN THE FIVE (5) DAY RAIN
PROBABILITY FORECAST EXCEEDS FORTY
PERCENT (40%). SILT AND OTHER DEBRIS
SHALL BE REMOVED AFTER EACH RAINFALL.
5. ALL GRAVEL BAGS SHALL BE BURLAP TYPE
WITH 3/41NCH MINIMUM AGGREGATE
6. ADEQUATE EROSION AND SEDIMENT
CONTROL AND PERIMETER PROTECTION BEST
MANAGEMENT PRACTICE MEASURES MUST BE
INSTALLED AND MAINTAINED.
SPECIAL NOTES
Page 1 of 3
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
Project ID: ------------
Construction Permit No.:---------..,,...
Estimated Construction Start Date I I / ~~~
Project Duration 4 Months
Emergency Contact:
Name:\/(CTof(. 'Btl~Nt;..
24hourPhone:7bO· 671. ·876
Perceived Threat to Storm Water Quality
0 Medium
!lr'Low
If medium box is checked, must attach a site plan
sheet showing proposed work area and location
of proposed structural BMPs
For City Use Only
CITY OF CARLSBAD
STANDARD TIER 1 SWPPP
Approved By:---------
Date:---------
REV 4/30/10
Erosion Control Tracking Non-storm Water Waste Management and Materials Sediment Control BMPs Control BMPs BMPs Management BMPs Pollution Control BMPs
c: c: c: "E "E 0 "0 .Q ~ 0> iii "' -g "' c: 13 c: E ~ "0 rJ "' .5 ~ ~ 0> .Q. "' c: $ ·e "' -g~ E 0> ·~ ~ ~ c: ::J ~ 0> ~ $ ::;: ~ 0. Q) c: ~"' 2: ~ "' <T "' .~ Best Management Practice c: ~ c<! "'"' "' ~ "' ·a. 8!1 0 Q) Q) w .2: "' .t: "' " ill 0> "' c: I Q) "E s (BMP) Description -+ "' c: 1-E 0> u "' ]:l "0 Qj .. ::;: ~ .!,! .,en i!1 ~ "' "' "' "' i!1 5 ~@ ~f iJ
0 ::l Q) ~ "' ::J ~ Q) "E 'a ;;:.5 0> "0:., ~ ~ ::J Q) ~ ::;: 0 "' mE "'"' )j 0 oe> 0 Q) et: "' §~ ~~ ~~ f ~ ~ ·a. t! ~ ~ ~ €~ ~ 5 -"' ~ j5 .0 .0 -"' i~ "' u. 0 .8 "0 :.a~ :2 dl ~ !!' ffi iil!'l "' 1ii ~ ~ 5 "'~ .Q "' != :5 .ee bi~ ~ 0 0 (.!) wo en iii en u u:: (.!) en> en rna.. ii5et: a.. ::. en :I: u
CASQA Designation -+ '7 "' '1' ~ "' "f ~ 'f/ :1; "' 0 ~ ~ ;;; "' '7 "' ~ ":' "' "f '1 'f/ "' u u u c.) uJ w w w w ~ en en en ~ ~ ~ ~ ~ ~ w w w en en en en en en en 1-1-z z z z Construction Activity w en
Grading/Soil Disturbance -Trenching/Excavation
Stockpiling
Drillif191Bori119_
~ Concrete/Asphalt Saw >< cutting • Concrete flatwork ~>«"
Pavir1g_ • ConduiUPipe Installation
1e Stucco/Mortar Work !!>< • Waste Disposal ~
Staging/Lay Down Area
Equipment Maintenance
and Fuelina
Hazardous Substance
Use/Storage
Dewatering
Site Access Across Dirt
Otherjlist):
Instructions: Begin by reviewing the list of construction activities and checking the box to the lefl of any activity that will occur during the proposed construction. Add any other activity descriptions in the
blank activity description boxes provided for that purpose and place a check in the box immediately to the left of the added activity description. For each activity descrribed, pick one or more best
management practices (BMPs) from the list located along the top of the form. Then place an X in the box at the place where the activity row intersects wrth the BMP column. Do this for each activrty that was
checked ott and for each of the selected BMPs selected from the list. For Example -If the project includes site access across dirt, then check the box to the left of "Site Access Across Dirt". Then review
the list for something that applies such as "Stabilized Construction Ingress/Egress" under Tracking Control. Follow along the "Site Access Across Dirt" row until you get to the "Stabilized Construction
Ingress/Egress" column and place an X in the box where the two meet. As another example say the project included a stockpile that you intend to cover with a plastic sheet. Since plastic sheeting is not on
the list of BMPs, then write in "Cover with Plastic" in the blank column under the heading Erosion Control BMPs. Then place an X in the box where the "Stockpiling" row intersects the new "Cover with
Plastic" column.
To learn more about what each BMP description means, you may wish to review the BMP Reference Handout prepared to assist applicants in the selection of appropriate Best Management Practice
measures. The reference also explains the California Storrnwater Quality Association (CASQA) designation and how to apply the various selected BMPs to a project.
E-29 Page 2 of 3 REV 4/30/10
«~» ~ CITY OF
CARLSBAD
STORM WATER
STANDARDS
QUESTIONNAIRE
E-34
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
To address post-development pollutants that may be generated from development projects, the City requires that new development and
significant redevelopment priority projects incorporate Permanent Storm Water Best Management Practices (BMP's) into the project
design per the City's Standard Urban Stormwater Management Plan (SUSMP). To view the SUSMP, refer to the Engineering Standards
(Volume 4, Chapter 2) at www.carlsbadca.gov/standards.
Initially this questionnaire must be completed by the applicant in advance of submitting for a development application (subdivision,
discretionary permits and/or construction permits). The results of the questionnaire determine the level of storm water standards that
must be applied to a proposed development or redevelopment project. Depending on the outcome, your project will either be subject to
'Standard Stormwater Requirements' or be subject to additional criteria called 'Priority Development Project Requirements'. Many
aspects of project site design are dependent upon the storm water standards applied to a project.
Your responses to the questionnaire represent an initial assessment of the proposed project conditions and impacts. City staff has
responsibility for making the final assessment after submission of the development application. If staff determines that the questionnaire
was incorrectly filled out and is subject to more stringent storm water standards than initially assessed by you, this will result in the return
of the development application as incomplete. In this case, please make the changes to the questionnaire and resubmit to the City.
If you are unsure about the meaning of a question or need help in determining how to respond to one or more of the questions, please
seek assistance from Land Development Engineering staff.
A separate completed and sigoed questionnaire must be submitted for each new development application submission. Only one
completed and signed questionnaire is required when multiple development applications for the same project are submitted concurrently.
In addition to this questionnaire, you must also complete, sign and submit a Project Threat Assessment Form with construction permits
for the project.
Please start by completing Step 1 and follow the instructions. When completed, sign the form at the end and submit this with your
application to the city.
1. Is your project TO constructing new or retrofitting paved sidewalks, bicycle lanes or trails that meet
the following criteria: (1) Designed and constructed to direct storm water runoff to adjacent vegetated areas, or
other non-erodible permeable areas; OR (2) designed and constructed to be hydraulically disconnected from
paved streets or roads; OR (3) designed and constructed with permeable pavements or surfaces in
with Green Streets
2. LIMITED TO retrofitting or redeveloping existing paved or roads that are
in accordance with the USEPA Green
YES NO
v
If you answered "yes" to one or more of the above questions, then your project is NOT a priority development project and therefore is
NOT subject to the storm water criteria required for priority development projects. Go to step 4, mark the last box stating "my
project does not meet PDP requirements" and complete applicant information.
answered "no" to both 2.
E-34 Page 1 of 3 Effective 6/27113
STORM WATER
STANDARDS
QUESTIONNAIRE
E-34
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
o determine if your project is a priority development project, please answer the following questions:
1. Is your project a new development that creates 10,000 square feet or more of impervious surfaces collectively
over the entire project site? This includes commercial, industrial, residential, mixed-use, and public
on land.
2. Is your project creating or replacing 5,000 square feet or more of impervious surface collectively over the entire
project site on an existing site of 10,000 square feet or more of impervious surface? This includes commercial,
and on land.
3. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a restaurant? A restaurant is a facility that sells prepared
foods and drinks for consumption, including stationary lunch counters and refreshment stands selling prepared
4. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a hillside development project? A hillside development
project includes development on any natural slope that is twenty-five percent or greater.
5. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a parking lot. A parking lot is a land area or facility for the
of motor
6. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a street, road, highway freeway or driveway? A street,
road, highway, freeway or driveway is any paved impervious surface used for the transportation of
and other vehicles.
7. Is your project a new or redevelopment project that creates or replaces 2,500 square feet or more of
impervious surface collectively over the entire site, and discharges directly to an Environmentally Sensitive
Area (ESA)? "Discharging Directly to" includes flow that is conveyed overland a distance of 200 feet or less
from the project to the ESA, or conveyed in a pipe or open channel any distance as an isolated flow from the
flows from •
8. Is your project a new development that supports an automotive repair shop? An automotive repair shop is a
facility that is categorized in any one of the following Standard Industrial Classification (SIC) codes: 5013,
501 5541 7532-or 7536-7539.
9. Is your project a new development that supports a retail gasoline outlet (RGO)? This category includes RGO's
that meet the following criteria: (a) 5,000 square feet or more or (b) a project Average Daily Traffic (ADT) of
100 or more vehicles
10.1s your project a new or redevelopment project that results in the disturbance of one or more acres of land and
are expected to generate pollutants post construction?
Pacific Ocean
surface on the
2,500 square feet or more of
than 10%?
v
v
v
v
v
v
answered "yes" to one or more of the above questions, you ARE a priority development project and are therefore subject to
plementing structural Best Management Practices (BMP's) in addition to implementing Standard Storm Water Requirements such
source control and low impact development BMP's. A Storm Water Management Plan (SWMP) must be submitted with your
laPIPiicatiio n(s) for development. Go to step 3 for redevelopment projects. For new projects, go to step 4 at the end of this
uestionnaire, check the "my project meets PDP requirements" box and complete applicant information.
you answered "no" to all of the above questions, you ARE NOT a priority development project and are therefore subject
plementing only Standard Storm Water Requirements such as source control and low impact development BMP's required for
lopment projects. A Storm Water Management Plan (SWMP) is not required with your application(s) for development. Go to
the end of this questionnaire, check the "my project does not meet PDP requirements" box and complete ap1plic:a111tl
E-34 Page 2 of 3 Effective 6/27113
STORM WATER
STANDARDS
QUESTIONNAIRE
E-34
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
If you answered "yes," the structural BMP's required for Priority Development Projects apply only to the creation or replacement of
impervious surface and not the entire development. Go to step 4, check the "my project meets PDP requirements" box and
complete applicant information.
If you answered "no," the structural BMP's required for Priority Development Projects apply to the entire development. Go to step 4,
check the meets PDP irements" box and com icant information.
D My project meets PRIORITY DEVELOPMENT PROJECT (PDP) requirements and must comply with additional stormwater
criteria per the SUSMP and I understand I must prepare a Storm Water Management Plan for submittal at time of application.
I understand flow control (hydromodification) requirements may apply to my project. Refer to SUSMP for details.
My project does not meet PDP requirements and must only comply with STANDARD STORMWATER REQUIREMENTS per
the SUSMP. As part of these requirements, I will incorporate low impact development strategies throughout my project.
Applicant Information and Signature Box
UI\JICt>tt!:..Nl () $7. Accessor's Parcel Number(s):2.l$-:S I;; D ... I "
Applicant Title:.~-~k lL':c:::.~ T -:---:-:----L:~L.::!L-1::=--::::l~~~~......__.~~ Date:
This Box for City Use Only
City Concurrence: NO
By:
Date:
Project ID:
* Environmentally Sensitive Areas include but are not limited to all Clean Water Act Section 303(d) impaired water bodies; areas
designated as Areas of Special Biological Significance by the State Water Resources Control Board (Water Quality Control Plan for the
San Diego Basin (1994) and amendments); water bodies designated with the RARE beneficial use by the State Water Resources
Control Board (Water Quality Control Plan for the San Diego Basin (1994) and amendments); areas designated as preserves or their
quivalent under the Multi Species Conservation Program within the Cities and County of San Diego; and any other equivalent
environmentally sensitive areas which have been identified by the Copermittees.
E-34 Page 3 of 3 Effective 6/27113
«~,\
~ CITY OF
CARLSBAD
PLANNING DIVISION
BUILDING PLAN CHECK
REVIEW CHECKLIST
P-28
DATE: 10-24-14 PROJECT NAME: PROJECT ID:
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www .carlsbadca .eov
PLAN CHECK NO: CB 14-1448 SET#: 2 ADDRESS: 2709 Unicornio Way APN: 215-350-16-00
[g) This plan check review is complete and has been APPROVED by the Planning
Division.
By: Chris Sexton
A Final Inspection by the Planning Division is required 0 Yes [gl No
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to: danielgeigerdesign@gmail.com
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
~ Chris Sexton D Kathleen Lawrence D Greg Ryan
760-602-4624 760-602-27 41 760-602-4663
Chris.Sexton@carlsbadca.gov Kathleen. Lawrence@carlsbadca .gov Gregory.Ryan@carlsbadca.gov
D Gina Ruiz D Linda Ontiveros D Cindy Wong
760-602-4675 760-602-2773 760-602-4662
Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@carlsbadca.gov
D D D Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Remarks:
REVIEW#:
1 2 3
~DO
~DO
~DO
~DO
~DO
Plan Check No. CB 14-1448 Address 2709 Unicornio St Date 6-24-14 Review# 1
Planner Chris Sexton Phone (760) 602-4624
APN: 215-350-16-00
Type of Project & Use: addition Net Project Density: 1.0 DUlAC
Zoning: R-1 General Plan: RLM Facilities Management Zone:§
CFD (in/out) #_Date of participation: __ Remaining net dev acres: __
(For non-residential development: Type of land use created by this permit: __ )
Legend: ~ Item Complete
Environmental Review Required:
0 Item Incomplete -Needs your action
YES 0 NO 0 TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
Discretionary Action Required: YES 0 NO 0 TYPE __
APPROVALIRESO. NO. DATE
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval: __
Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES 0 NO 0
CA Coastal Commission Authority? YES 0 NO 0
If California Coastal Commission Authority: Contact them at -7575 Metropolitan Drive,
Suite 103, San Diego, CA 92108-4402; (619) 767-2370
Determine status (Coastal Permit Required or Exempt):
Habitat Management Plan
Data Entry Completed? YES 0 NO 0
If property has Habitat Type identified in Table 11 of HMP, complete HMP Permit application
and assess fees in Permits Plus
(AIP/Ds, Activity Maintenance, enter CB#, toolbar, Screens, HMP Fees, Enter Acres of
Habitat Type impacted/taken, UPDATE!)
lnclusionary Housing Fee required: YES D NO D
(Effective date of lnclusionary Housing Ordinance-May 21, 1993.)
Data Entry Completed? YES 0 NO 0
(AIP/Ds, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct
Housing Y/N, Enter Fee, UPDATE!)
~ 0 0 Housing Tracking Form (form P-20) completed: YES 0 NO 0 N/A 0
P-28 Page 2 of 3 07111
Site Plan:
IZIOO
IZIOO
IZIOO
IZIOO
IZIOO
IZIOO
IZIOO
IZIOO
OIZIO
Provide a fully dimensional site plan drawn to scale. Show: North arrow, property lines,
easements, existing and proposed structures, streets, existing street improvements, right-of-
way width, dimensional setbacks and existing topographical lines (including all side and rear
yard slopes). Provide legal description of property and assessor's parcel number.
City Council Policy 44-Neighborhood Architectural Design Guidelines
1. Applicability: YES 0 NO 0
2. Project complies: YES 0 NOD
Zoning:
1. Setbacks:
Front:
Interior Side:
Street Side:
Rear:
Top of slope:
Required 20' Shown 20'
Required 9.6' Shown 9.6'
Required .1[ Shown .1[
Required 19'2" Shown 19'2"
Required __ Shown __
2. Accessory structure setbacks:
Front: Required __ Shown __
Interior Side: Required __ Shown __
Street Side: Required __ Shown __
Rear: Required __ Shown __
Structure separation: Required __ Shown __
3. Lot Coverage: Required <40% Shown 25%
4. Height: Required <30' with min 3:12 Shown <30'
5. Parking: Spaces Required ~ Shown ~
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required __ Shown __
Additional Comments 1) Per the Carlsbad Municipal Code. the wet bar sink cannot exceed 2
square feet and the waste drain line cannot exceed one and a half dimensions in diameter.
Please show the dimensions of the wet bar sink. The cabinetry or cabinet space cannot
exceed eight linear feet. Gas lines or electrical wires exceeding 110 volts is not permitted.
Sheet 5.2 220 volts. please change. A copy of the code ordinance is attached. Please also
see the definition of a kitchen.
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER Chris Sexton DATE 10-24-14
P-28 Page 3 of3 07/11
Janet Altar
From:
Sent:
To:
Cc:
Subject:
Sjirk,
Will Foss
Friday, July 25, 2014 10:32 AM
z3beach
Marty Montgomery; victor@vburns.com; Janet Altar
RE: Soil bearing value
The city will consider this email and your analysis as a limited soils report.
Janet,
Please print and note as file copy.
Will
From: z3beach [mailto:z3beach@aol.com]
Sent: Friday, July 25, 2014 9:09AM
To: Will Foss
Cc: Marty Montgomery; victor@vburns.com
Subject: Soil bearing value
Dear Mr. Foss,
Regarding plan check 14-1448, 2709 Unicornio Way. the Burns residence addition/remodel
When I prepared the plans for a two story addition to the Burns residence, I had reasons to believe that the existing
structure is founded on solid grounds most likely Torrey Pines Sandstone), no evidence of any settlement. Below the
topsoil around the house the soil looks like a combination of "Sandy Gravel" and Silty Sand" with respective bearing
values per Table 1806.2 of 3,000 psf and 2,500 psf. Because the addition extends only 10ft from the existing
foundations, I concluded that using the CBC Table 1806.2 minimum bearing capacity of 1,500 psf, would eliminate the
need for a full on soil investigation.
Please consider waiving the requirement for a soil report as stated in items 8, 9 & 10, to void an unnecessary
expense to the Owner, regards,
Sjirk W. Zijlstra AlA lie. # C 12076
Zijlstra Archittecture
1
CITY OF
CARLSBAD
CERTIFICATION OF
SCHOOL FEES PAID
B-34
Development Services
Building Department
1635 Faraday Avenue
760-602-2719
www .carlsbadca.gov
This form must be completed by the City, the applicant, and the appropriate school districts and returned to the City
prior to issuing a building permit. The City will not issue any building permit without a completed school fee form.
Project Name: BURNS ADDITION/REMODEL Project 10: CT/MS:
Building Permit
Plan Check Number: _,C:<.!:B"-'1'-'4~14_,_4-'-'8"------------------------
Project Address: 2709 UNICORNIO ST
A.P.N _,2.....,1'-"~5"'-'·3..,.5,..0.::.~-1'-"!6-"'-0..,.0 ____________________ _
Project Applicant
(Owner Name): BURNS VICTOR V&KRISTIE T
Project Description: 1.584 SF ADDITION/REMODEL
Building Type: --~.:R!>AIEo!oSwiD""'Eioo.JNLS.T.LJILCAu.L....._ ___________________ _
Residential: NEW DWELLING UNIT(S)
Square Feet of Living Area in New Dwelling/s
Second Dwelling Unit: Square Feet of Living Area in SOU
Residential Additions: 1,584 Net Square Feet New Area
Commercial/Industrial: Net Square Feet New Area
City Certification of
Applicant Information: -~·.J.JI\fw'RI.lo.l..FaNu:A:L..J;SAc..oK.x.AuM::.u...<2ui..l.<2-'-------------DL.l.Clatu:ea-·.u9u.f2:.LI2'-lOo.L11..!:4L..__
SCHOOL DISTRICTS WITHIN THE CITY OF CARLSBAD
0 Carlsbad Unified School District
6225 El Camino Real
Carlsbad CA 92009 (760-331-5000)
0 Encinitas Union School District
101 South Rancho Santa Fe Rd
Encinitas, CA 92024
(760-944-4300 x1166)
0 Vista Unified School District
1234 Arcadia Drive
Vista CA 92083 (760-726-2170)
IZI San Marcos Unified School District
255 Pico Ave Ste. 100
San Marcos, CA 92069 (760-290-2649)
: Contact: Nancy Dolce (By Appt. Only)
0 San Dieguito Union High School District-By Appointment Only
710 Encinitas Blvd.
Encinitas, CA 92024
(760-753-6491)
Certification of ApplicanVOwners The person executing this declaration ("Owner") certifies under penalty of perjury
that (1) the information provided above is correct and true to the best of the Owner's knowledge. and that the Owner
will file an amended certification of payment and pay the additional fee if Owner requests an increase in the number
of dwelling units or square footage after the bw · mit is issued or if the initial determination of units or square
footage is found to be in rrect. and that (2) th Owner i he owner/developer of the above described project(s). or
that the perso executin t is declaration is au orized to si non behalf of the Owner.
Signature: ~\J' ---------------------Date:
B-34 Page 1 of 2 Rev. 03109
SCHOOL DISTRICT SCHOOL FEE CERTIFICATION
(To be completed by the school district(s))
********************************•***************************************************************•**
THIS FORM INDICATES THAT THE SCHOOL DISTRICT REQUIREMENTS FOR THE
PROJECT HAVE BEEN OR WILL BE SATISFIED.
SCHOOL DISTRICT:
The undersigned, being duly authorized by the applicable School District, certifies that
the developer, builder, or owner has satisfied the obligation for school facilities. This is
to certify that the applicant listed on page 1 has paid all amounts or completed other
applicable school mitigation determined by the School District. The City may issue
building permits for this project.
SIGNATURE OF AUTHORIZED SCHOOL
DISTRICT OFFICIAL
TITLE
NAME OF SCHOOL DISTRICT
DATE
PHONE NUMBER
Page2 of2
& v1 AAarcas L)V1 cf'f?cl
tl/3)1'1
Rev. 03109
{"city of
Carlsbad
SEWER DISTRICT
CERTIFICATION
B-19
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www .ca rlsbadca .gov
I:8J Leucadia Wastewater District
1960 La Costa Ave.
Carlsbad, CA 92009
760-753-0155
D Vallecitos Water District
201 Vallecitos de Oro
San Marcos, CA 92069
760-7 44-0460
The following project has been submitted for building permits:
Plan Check No. C"""""'Bx14:r...1o4=4..._8 _____________ ___.,Du.a....,te.._._,1 O .... I3,..,0..._/..L:14:I..__
Property Owner BURNS VICTOR V&KRISTIE I
Project Address 2709 UNICORNIO ST
Assessor's Parcel No~. _.2'""15""-~3>LC50""-'-'-16""-~o_...o ________________ _
Project Description 1,584 SF ADDITION/REMODEL
City Certification: --SFL...j'R~f....,N ..... A~S"""A"'""K"""A'"'"'M~o'-"v ..... oL--______ _.....Dcu.at...,e._· .....,1 o~/.....,30~/....,14~--
Please indicate in the space below that the owner has entered into an agreement to have
your agency provide public sewer service to the premises, and/or if the existing service is
adequate for this project and all required fees have been paid.
Permits will not be issued until this form is completed and returned to our office .
...••...••...•............................................•....•...•....•..•••...•••..••...••.......•....•.........
This space to be completed by District Personnel
I certify the district requirements for sewer service have been satisfied.
Approved by ~ Date ll { '1 ft"'{
Title FIELD SERVICES SPECIALIST
•....•...••..•••..•••.••••.•••.••••.•••.••...•..........................................•...•...•••..•••.••••.•••.••
B-36 Page 1 of 1 Rev. 03/09
' .
SDf!f Request for Service
A~SempraEnergyutnity" Residential Single Family Dwelling
Please complete and submit this request along with the REQUIRED plans to the applicable SDG&E Project Management office.
Project Information
1:8:1 Electric
D New Electric Overhead Service 0 New Electric Underground Service D Electric Removal Relocation 0 Electric Rewire
Really? they
0 New Gas Service 1:8:1 Gas Service Relocation 0 Gas Service Removal
Thomas Guide
Coord.
print these
still?
Project Address/Location 2709 Unicornio Street City Carlsad State ...:Co:...A:___ Zip 92009
Nearest Cross Street ..:B:..:a:=.sa::l.:::to'------------Assessor's Parcel# 215-350-16-00 Building Permit # CB141448
Applicant I Company Name Victor Burns Phone # 760 672 8767
Applicant Address 2709 Unicornio Street City Carlsad State ...:Co:...A:___ Zip 92009
(include whether individual, partnership, corporation-including
Legal name to appear on contract ....:V:.::ic:::;to:::.:r....:V:..::e:.:.:rn:.:.:o::.:.n:...:B:::.:u::.:.r:.::ns::....... ________ an incorporated association, state of incorporation or LLC)
Name of person authorized to sign contracts ....:Vc::ic:.:.to::::r~o~r-=:-K::-:ri=.st::.:ie:....:B~u;:;:.r;.:;nso--:--::-:-:--c:--':"'7:---
First Name, Middle Initial, Last Name
Title Owners
Mailing address for contract 2709 Unicornio Street City -=C:..::a""rl""sb:;.;;a;..:;d ____ _ State ....:C;.;..A:___ Zip 92009
Primary Contact Information (pnmary contact person relaying information between applicant and SDG&E representative)
Name of Primary Contact ....:V:..:.;ic:.:.to~r....:B:;.;;u;,;.;rnc:.:s;.__ _____________ _ Company ________________ _
Phone # Cell # 760 672 8767 Fax# ______ _ Email address victor@vburns.com
Mailing Address 2709 Unicornio Street City Carlsbad State ...:Co:...A:___ Zip 92009
Project Timeline
Grading start date ..:D:..:e;..:;c..:2;..:;0..:..14"-------Trench start date..:D:;.;;e:..::c..:2:..:0..:..14"------Requested meter set date ..:..F..:e=.b-=2.::.01..:..:5'------
Applicant Design and Installation Options
Applicant Design and Applicant Installation Options may be available based on the scope of your project. If you would like more Information
regarding these options, please contact the Planning Office in the area in which your project resides.
SDG&E's tariffs, including Rule 15 F and G, can be accessed at http://www.sdge.com/regulatory/tariff/current tariffs.shtml
Construction Information
Will temporary electric service be required? 181 No DYes If yes, date needed
If temporary electric service is required, will it be a temporary service at the permanent base (TSPB)?
Will existing SDG&E electric overhead facilities require undergrounding? 181 No 0 Yes
Will any existing SDG&E gas or electric facilities require relocation or removal? D No 181 Yes
Are you planning to install any self-generation equipment (photovoltaic or wind generation)?
Proposed Joint Trench Utilities 0 Gas 181 Electric 0Phone D CATV
Load Information
Total square footage ..::4~9:::80::....... ___ _
D No DYes
If yes, date needed
If yes, date needed
D No 181 Yes
Jan 2015
If existing service, what is your: Gas meter# -=0..:.1:.24.:...:7....:1..:9..:..1 ------Electric meter# ...:0:=.5;:;.;37...:8;..:;9;:;.;89'--------
IMPORTANT NOTE: Do NOT install your electric main switch or gas house line until the meter location is approved by SDG&E.
RequestForService-RESIDENTIAL.doc 1 of 2
..
Load Information Continued
Electric Load Information
New Main Switch Size
(Service Termination Enclosure) ...;4:..::0c:c0 ____ amps
Existing Main Switch Size
(Service Termination Enclosure) ...::2:..::0c:c0 ____ amps
Voltage: (select one)
181120/240 Volt, 3-wire, 10 0 208/120 Volt, 4-wire, 30 D 240/120 Volt, 4-wire, 30
Please provide load information for applicable appliances
Lighting 5 kW Electric Oven ..:::2~ ___ kW
__,__ ____ kW Freezer --'------kW Refrigerator
Laundry Dryer __,__ ____ kW Outdoor Lighting ..::::2~---kW
Water Pump 4 hp Air Conditioning -'4 ____ Tons
Electric Water Heater D Standard or D Tankless kW
Other Electric Load (specify) Ham Radio Equipment I Welder etc. Intermittent use -4 kW
Natural Gas Load Information
Gas Service Delivery 181 y. psig 0 Other ( ___ psig) Pressure Requested:
Please provide load information for applicable appliances
Laundry Dryer 35000 BTU/h Pool/ Spa -=3~00;::.:0;..:;0.=..0 ___ BTU/h
Gas Range 40000 BTU/h Gas Oven ..::3:.:::.60:::.=0:..:0 ___ BTU/h
Log Lighter ..=2=..:50:..:.00=----BTU/h BBQ ..=2:.:::.50:::.=0:..:::0 ___ BTU/h
Gas Water Heater 181 Standard or D Tankless -'4-=-00;::.:0:..:::0 ___ BTU/h
Other gas load (specify)
D Other
Electric Range -'4~----kW
Dish Washer kW
Pool/ Spa 4 kW
Heat Pump kW
D Propane
Furnace ...::8-=-00=..::0:..:::0 ___ BTU/h
It is the responsibility of the Applicant to notify SDG&E in writing in the event of any added or change in loading or
characteristics of appliances (including panel size) installed upon the premises to be supplied by SDG&E.
Attachments -Submit 2 copies of the following with application (may not be applicable to rewires)
A. Site plan showing roads, sidewalk, driveways, location of fire hydrants and other structures, proposed future improvements,
and proposed location of gas and electric meters. (Meter locations are subject to SDG&E approval).
B. Grading plans (if grading will be done)
C. Assessors parcel map showing all easements, rights-of-way, property lines, etc.
D. Architectural Exterior Elevations
Once SDG&E receives your completed request and the required attachments we will be able to start your project.
IDPSS For Internal Use Only._ __________ __,
Metro Service Order Team Northeast Service Order Team North Coast Service Order Team Eastern Service Order Team
701A 33rd Street 571 Enterprise Street 4940 Carlsbad Blvd 904 W. Main St.
San Diego, CA 921021 Escondido, CA 92029 Carlsbad, CA 92008 El Cajon, CA 92020
619-230-7800 760-480-7642 760-931-7309 619-441-3969
RequestForServ1ce-RESIDENTIAL.doc 2 of2
\_ Cicyof
Carlsbad
SPECIAL INSPECTION
AGREEMENT
8-45
Development Services
Building Division
1635 Faraday Avenue
760...602-2719
www.carlsbadca.gov
In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed
requires special inspection, structural observation and construction material testing.
Project/Permit: Ct> J 1... / q lt' ~
A. THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNER/AUTHORIZED AGENT. Please check if you are OWner-Builder
Cl. (If you checked as owner-builder you must also complete Section B of this agreement.)
Name: (Please print) V \ VIU n._ v BU(l..N 5
(First) (M.I.) (Last)
Mailing Address· 1-t 0 0, V.t..J \ L.--OC'\. N \ 0 <; Tn.ICULi\
Email· V tv+ov-e_ V burN 5. 0\o ~ Phone: I ~0 ~( '-<b] ~J
I am: ~roperty Owner QProperty Owner's Agent of Record QArchitect of Record QEngineer of Record
State of California Registration Numbel...·------------Expiration Date: _______ _
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the State of California, that I have read,
understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural
observations, construction materi testing and off-site fabrication of building components, as prescribed in the statement of
special insp~ctiorfo' nN the ved plans and, as required by the California Building Code.
Signature· \j J , Date:l 0 Cir GO l '-/
8. CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor I builder I owner-builder.
Contractor's Company Name:. __________________ Please check if you are ONner-Builder ~
Name: (Please print) __ \J.:,.._L__;<:..7l"-u~-=-...:..n.....___;;:_ _____ V _________ IS __ V_CL_l"S_::....:::.5 ___ _
(First) (M.I.) (Last)
Mailing Address: 7.-I 0 ~ U ~ l CDC\... N \. D C:::, --r-
Em ail: V\.. ui:::o .r-e Vbv r N 5 ~ l.fi:J ~ Phone:l ~ () to l 7_ ~ t "l
State of California Contractor's License Number: _________ Expiration Date:-------
• I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
• I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the
building official;
• I will have in-place procedures for exercising control within our (the contractor's) organization, for the method and
frequency of reporting and the distribution of the reports; and
• I certify that I will have a qualifi p on within our (the contractor's) organization to exercise such control.
• I will rovi e a final r rt I etter i com liance with CBC Section 1704.1.2 rior to uestin final
ins tion
B-45 Page 1 of 1 Rev. 08/11