HomeMy WebLinkAbout2728 LOKER AVE W; ; CB930204; PermitCity of Carlsbad
COMMERCIAL TENANT IMPROV Permit No:CB930204
2728 LOKER AV WEST
CTI
2090812900
3125 SF OPEN LIGHT MANUF. FROM EXISTING WAREHOUSE
Job Address:
Permit Type:
Parcel No:
Reference No:
PC #:
Project Title:
FINAL
03/01/1993
04/22/1993
04/22/1993
Status:
Applied:
Approved:
Issued:
Inspect Area:
Lot #:
Applicant:
SATTERLY, VIRGINA
2734 LOKER AV
CARLSBAD CA
619-431-7233
Owner:
CARLSBAD CROSSROADS LIMITED
00130104993 Strong Motion Fee $2.00
00136104221 Building Permit $108.00
00136104223 * ELECTRICAL TOTAL $20.00
00136104224 * MECHANICAL TOTAL $32.00
00136104885 Plan Check $70.00
30000004193 Enter Y to Autocalc Li $162.00
43000004193 (Lic Tx) C.$149.00
$543.00 $0.00 $543.00 $0.00Fees:Additional Fees:Total Fees:Balance:
;:\ U l 1 l• I i'J G 1:-' E F: J\i J 'I'
( ] L:,_ / ::: ·~ I •?, J I_) ::: : l J :l
P -:1 ·0j :;, .1. ,:, f. i
,Ji:,J:s 1-1•l(ir,:=-z~-: 272f: Lt)}~EF~ ,~\1 t·:(E:..-.1-~ Sui tr:=:
:-·,:. r.ntl t 'Yyr,:=-; :.'!J,·li 1E:Rl' J.Al, TENAillT u:.f'ROV£: :E:1JT
~ar~el No: Lut#:
\f,-1 J_:-1:.:tt l (_1r1: ::; ,~::: ::J 2
('on.2truc·<:!'..,,:. ~·-'.T••.:: \11'!
UCCllL•·'tt1cy G1 oup: r-;·: Re,f ,2.r encE-it:
r1r?scr :pt 1 ("fl: 312 5 SF Cif'E:~ LI:;I-:T r .. ·;~"':,n)F.
: f'RUi•'i E,US rING ~·;AR£H(,US2
SATTERLY, VIRGINA
;: 7:: 4 Ll)I-{ER ~~ \/ !,·JEST
A.Jjustm,2nt:J:
Total Fees:
F(?i? ,_:iescript :Lon
E;ui 1.-:iincr Pi.?rnn t ~ ~:· 1 ,:H 1 Ch;,:: l-:
::d::;r,:ini:r. Motic,n Fee
54.:;. (;(}
E::nt,:-.c · "V" l:o 'Autucalc· Li,:·,:·n.:::1:'!,
{ Li c Tx) (. t;,', 't) .•
., BUJ:LDHJ(:l TUTAL
Entei-"'·'. ., for Plumbing
Ent>:-:r. ... ,. ' for Elect.cic
Enter "Y" for r:.::·mod1?l
~ EU:'CTiUCAL TOTAL
Enter 't' for hechanical Issue
\_"--~ ,,. '. , -'·,
~~-. -l:' e e-.. /" , --
Each Bcii.ler/('ompres~:wr
I· ViECHlfr.JI CAL TOTAL
to lf, HJ? >
CITY OF CARLSBAD
l:'r(1 JECt .. 1.·_: ~.J~;,~1 11 ... :·1_
Dt:•Vr.?J..:,r.:-rnc;:>n t £1:,.,:
200tl 04/22/'93 (~00.1 01 02
C-PF{MT kA-3~(H)
16. :5u
1\t~ ~~=-i 10't 1 =
i'.\pr,-: ·:· :;u,:>:
j\ ~. / u
Fri t e·c ,::-'•i f. y :
587 1901
1 ll ::: . u r_:
::: • (, 'i
16 ;~ . (I : ) y
1l ,f,i. 9 tJ I_:
4-Jl lJ : I
r\
10 fl I) . r . .1.
1n . ll /) \~
...: u {_Ill
-_, l):_l ·-
16 . t~ ;J .. :,u -· -
,·,
·'
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
PLAN CHECK NO. 9.J-:J.o¥
City of Carlsbad Building Department a V 2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161 F.Sf.VAL ¼/1 $:(,rO
PLAN CK DEPOSIT /I.JV• -
VAi.ID. BY /.~
1. PfiltMII IYPR DATE !I
A -D Commercial LI New Butidmg D Tenant Improvement
B -)z{Industrial D New Building pf Tenant Improvement
C -0 Residential D Apartment D Condo D Single Family Dwelling D Addition/ Alteration
D Duplex O Demolition O Relocation D Mobile Home O Electrical D Plumbing 134-2 03/01/93 ,D01 01
S-P~;i<T
i)2 0 Mechanical D Pool LI Spa D Retaining Wall LI Solar O Other ____ _
FOR OFFICE USE ONLY
eree_ 'A-ZIP CODE AY TELEPHONE
NAME {)..4_ ~ ADDRESS
CI1Y STATE ZIP CODE DAY TELEPHONE
6
· OONTRAcl'oR ~ ADDREss 08ft? 7 Al~ ~ Dr. Sf-e · A :;· .&jb STATE{!//-ZIP CODE fcJ.f,:J./ DAYTELEPHONE 587-/'l'tJ/
~C. # JJCENSE CLASS CITY BUSINESS UC.#
DESI El~~ ~S ('i 4-A fi 17 /1~ _,,, _,,1
CITY • ~E L---V '-~ TELEPHDN~35 -fo010STATE IJC. #
1. WOlll<filtS' CiiMP.ENSA'l'ION
Workers' compensation Deciaratlon: I hereby afhrm that I have a cert1hcate of consent to self-msure issued by the Director of Industnal
Relations, or a certificate of Workers' Compensation Insurance by an admitted insurer, or an exact copy or duplicate thereof certified
by the Director of the insurer thereof filed with the Building Inspection Department (Section 3800, Lab. C).
INSURANCE COMPANY POIJCY NO. EXPIRATION DATE
cert1hcate of Exemption: I certtfy that m the performance of the work for which this penmt 1s issued, 1 shall not employ any person m any manner
so as to become subject to the Workers' Compensation Laws of California.
SIGNATURE DATE
8. OWNER-Bmmmt D.EcWtAuoN
Owner-Bmlder Deciaratlon: I hereby affirm that I am exempt from the Contractor's License Law for the followmg reason:
D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or
offered for sale (Sec. 7044, Business and Professions Code: The Contractor's Llcense Law does not apply to an owner of property who builds
or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended
or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden
/ of proving that he did not build or improve for the purpose of sale.). tJI' I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions
Code: The Contractor's Llcense Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects
with contractor(s) licensed pursuant to the Contractor's License Law).
D I am exempt under Section _______ Business and Professions Code for this reason:
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the
provisions of the Contractor's License Law (Chapter 9, commencing with Section 7000 of Division 3 of the Business and Professions Code)
or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit
subjects the applicant to a civil penalty of not more than five hundred dollars [$500]).
SIGNATURE DATE
COMPLETE THls sEctloN FOR NaN-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and
prevention program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act?
0 YES D NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district?
DYES D NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site?
0 YES ONO
IF ANY OF TIIE ANSWERS ARE YE.5, A FINAL CERTIFICATE OF ocx;m>ANCY MAY Nar BE ISSUED AFfER JULY 1, 1989 UNLF.SS TIIE APPUCANT
HAS MET OR IS MEETING TIIE REQUJREMENTS OF TIIE OFFICE OF EMERGENCY SERVICES AND TIIE AIR POLLUTION OON1ROL DISI1UCf.
9. wNS'lRUCl'ION I.RNDING AGRNCV
I hereby afhrm that there 1s a construction iendmg agency for the performance of the work for which this permit 1s issued (Sec 3097(1) C1VII Gode).
LENDER'S NAME LENDER'S ADDRESS
10. APPilCANT CER'l1FICATION
1 certify that I have read the apphcatlon and state that the above mformatton 1s correct. I agree to comply with all City ordmances and State laws
relating to building construction. I hereby authorize representatives of the City of Carlsbad to enter upon the above mentioned property for inspection
purposes. I ALSO AGREE ID SAVE INDEMNIFY AND KEEP HARMLESS TIIE CTlY OF CARISBAD AGAINSf ALL UABIIlTIES, JUDGMENTS, CDSTS
AND EXPENS.fS WHICH MAY IN ANY WAY ACCRUE AGAINSf SAID CTlY IN CDNSEQUENCE OF TIIE GRANTING OF TIIlS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
Expiration. Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the
building or work authorized by such permit is not commenced within 365 days from the date of such permit or if the building or work authorized by
such permit is suspended or abandoned at any time fter the work is commenced for a period of 180 days (Section 303(d) Uniform Building Code).
. ..L.-6---DATE: 3-/-;(-J
April 12, 1993
The City of Carlsbad
Building and Engineering
2075 Las Palmas Drive
Carisbad, Ca 92009
To Whom It May Concern:
RANDALL PRODUCTS
INTERNATIONAL
Plan Check #93-204 originally submitted for 3125 square feet of warehouse to Open Office
is to be changed to 3125 square feet of warehouse to Light Manufacturing. Work to be
done in that area includes light packing and assembly of orders which consist of plastic
bottles filled with shampoo, conditioner, bath gel, lotions, etc. Machinery will not be
utilized in that area. People will be working at tables only.
Sincerely,
Wrniam B. Randall
Randall Products International, Inc.
2724 Loker Avenue West
Carlsbad, California 92008
Telephone (619) 438-7488
Fax(619)438-2560
10/21/93
DATE
06/01/93
06/01/93
05/12/93
05/12/93
04/21/93
INSPECTION HISTORY LISTING
FOR PERMIT# CB930204
INSPECTION TYPE INSP ACT COMMENTS
Final Combo RI
Final Combo PK
Final Combo RI
Final Combo TP
Compliance.Investigatio TP
RI MH/WILLIE/986-2205
NR UTL SUPER OR APP'D PLANS
RI MH/WILLIE/986-2205 PAGER
PA UTILITY RELEASE/NOS RECHECK
CO LOBBY STAIRS HANDRAILS
HIT <RETURN> TO CONTINUE ..•
I
!.
l
', ~
I .
RCV BY:XEROX TELECOPIER 7010 ;10-21-93 2:15PM; 5871903--,
BYCOR INC ,(.:: TEL: 5871903 Oct 21,93
6194380894;l=I 2
14:18 No.020 P.02
' .,~, -~
\_ __ .I
r •
· City .oJ ~"!ilsbad · ;~~·;;~;l;~lr.~;~69;~ ,
INSPEOflON RECORD CARD WITH APPROVED PLANS
, MU.,ST BE K~PT ON THE JOB
CALL PRIOR TO 2:00 P.M.'FQ.R NEXT WORKDAY INSPEC1:10N
• 1 BUILDING INSPECTION: (619) 438 .. 3101 , ,
. ENGINEERING INSPECTION: (819) 438·3891 , .
I , . 11
J0a ADORES!, "Z:-"2 U / e fl(..ti & gv ~ IC:.~ T, -; ·
OWNERS NAME! ~ J\ . t-"r:" l ,._. ..
u~UQccve~Ncv OF"'~. · rn r=-~ .. TYPE CONST. DATE
CONTRACTOR
BUILDING If'
OTHER _P
· APPROVED TO COVER f)
· Typt of lntpo~tlon . Doto , 1nep&ct<ir Noto• .
Bt/ILhJNG ' ,. ~ I'
t-OUNDATION ,
f ., .
FtEIN FORCED STEEL f • " ,m . •• . '
MASONRY .. I ' . D GROUT 0 WALL DRAINS. ' I ' TILT PANELS 1#
POUR STRIPS . ~ . . ....
COLUMN FOOTl~GS ' re
SUB FRAME 0 FLOOR D CEILING I
ROOF SHEATHING . /} J ..
EXT. SHEAR PANELS
.
J'
I
I ~41'-' .,v ~-,.,
FRAME ? t , ,./..,,,,,...,'.sm --~~•-e, .. , ..57'~,JLt,..,,ed_,,
INSULATION · ;L,.,~ 1~ •. MJ,1 ujy 1UA1,. · . I
EXTERIOR LATH . • I , . , . ,. -INTERIOR LATH & DRYWALL ' \, I 'I f
FINAL ll! q_J tJ '4,...,--r. --ff .· !
PLUMBING I I I V ~ .. -·----,. 0 SEWER AND BL/CO 'O.,..PL/C0 f' ....
UNDERGROUND D WAST&C] WATER . . ,;t/p./4,.1 ..µ .
~
TOP OUT ISI WASTE ltJ..wATER H 'rLI f f/1//4.. 'IJI\P(_._,r ~, ~ ....... .;----* AAJt.J,r' "-" TUB AND SHOWER PAN ,, I' '{ ,...,_ I /, {I,_ 4'1 ' ~ 1,-,;, F Jr.n•'I"• j I I
0 GAS TEST 0 GAS PIPINGl U/7/'l'J bl-'' 7j/,,/;,-;-/"'-' ~ .. ,/J ..
0 WATER HEATER 0 SOLAR WAJER ·. . I ' .
FINAL , • ', ELECTRICAL ' . /) .t.
0 ELECTRIC UNDERGROUNCb 0 UFEA • . ·7..IY1 t ' ROUGH ELECiAIC WALLS ,. ,. •v,t~ i -~1.t! .
ROUGH ELECTRIC CEILING , • /?JV fr.it.. t....JOl.,{_,f Zin ' 0 ELECTRIC SERVICE 0 TEMPORARY Ill 0 BONDING 0 POOL f#• '
FINP..L , I' • ,
MECHANICAL , J I
UNDERGROUND DUCTS & PIPING .,-z,~ .J.>,(! .w 1&d.f c;._ ;..;..J-pl..,/2 ..
0 OUCT & PLEM, 0 REF, PIPING ~ ., . , r L!"f;v;A"" ,D AA11JS .Pl ,,,,,.k, } .t:£' J :2. ~ .J4..
HEAT• AIR COND, _SYSTEMS i:::.,A:.I!. MA?~d::t. ~lt.k 'i :·~-
VENTILATING SYS:fEM$ r .l!:'"}_.-,; ~ il!!/.A, .... _ • ._. :;,_ i,J(!,
FINAL . _F I ... ~: • ,, . ,;.,, ,. __ .,, -·"/
. ..
CAl.l FOR FINAL INSPECTION WHEN ALL f ,., . .. iii' ~-.. .'-
APPfloPRIA TE ITEMS ABOVE HAVE BEEN APPR'oVEO
t:INAL Sign When Appropriate ',. Building Dept, (Inspections) ~ 438·3101
Fire Department .:. 931-2121
; Planning ,Department 438-1161
' ' Engineering Dept. !Inspections) 438-3891
Building Inspectors (7am-4pro . 438-3550 " ,.. , ·· ~--;.::-..,;..;..:.::..!....:.:::..:..::..:...:.....:.._::_..:.;.___:_=.:ia;;t____.:..=.;:::-=..::..,::....-1,--_~---1----+-----------'--~---Utilities/Majntenance • , . 438-021
c •
I
DATE:
ESGIL CORPORATION
9320 CHESAPEAKE DR., SUITE 208
SAN DIEGO, CA 92123
(619) 560-14-68
3 /.23/ 93 QAPPLICANT ~...,.D_I_C_T...,.,I"""O'""'N-=:::,
JURISDICTION: CITY OF CARLSBAD LJPLAfrCHECKER
QFILE COPY
PLAN CHECK NO: q3-2.04 SET: 7T QUPS
QDESIGNER
PROJECT ADDRESS: ___ 2_7_._2_,.3 ___ L_O~k---=ER......_ _____ A_..ll'-c. ___ \.-'\_vE.s1
PROJECT NAME: !<.ANIA l L PRO DJ.JC TS -~=---~-----""-=----~ .................. -----~ ........ --
D The plans transmitted herewith have been corrected where
necessary and substantially comply with the .jurisdiction's
building codes.
The plans transmitted herewith will substantially comply
ffiID_.with the jurisdic~ion's building codes when minor deficien-
cies identified h-e/ 0 kV are reso_l ved and
D
0
D
checked by building department staff.
The plans transmitted herewith have significant deficiencies
identified on the enclosed check list and should be corrected
and resubmitted for a complete recheck.
The check list transmitted herewith is for your information.
The plans are being held at Esgil Corp. until corrected
plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the
jurisdiction to return to the applicant contact person.
(I-·The applicant's copy of
.It) Tp,--I o Y D / O. /'> n I n 9 ·
the check list has been sent to:
· Crnr.op"tr I {7
3 6 .?. r:. ,' ft/2 Av,.,,
J
4=1-::2oo SD q210 I
Ill Esgil staff did not advise the applicant contact person that
plan check has been completed.
O Esgil ·staff did advise applicant that the plan check has
been completed. Person contacted: ------------
Date contacted: Telephone ff ---------------------
1!1 REMARKS : @ Na+,. .,, +b,, olao "--rl,,, &h•tid -P, "--Ge/»<¢/e of '"'f Pl I';}-
"--hliO· of · S: Coble. '-PPei P-fr rn,'ntAt,. a-f n(,ds,'de at'r w,-H,· ~
To+o, ( C(Yc.1A(o,..-f/tn1 ·. D=f? l?it:t /..p_ss I +han l.f-: cu/21c ffP-f--/7PY 171/17,,(f'~
-t I/
t2c.f1fqn
By: DAVID YAV Enclosures: -----------ESGIL CORPORATION ~/2/
OGA DcM
___ ......
DATE: 3
ESGIL CORPORATION
I
9320 CHESAPEAKE DR., SUITE 208
SAN DIEGO, CA 92123
(619) 560-1468
{O I q3
JURISDICTION: CITY O'F CARLSBAD
PLAN CHECK NO: 93-204 SET: .:r.
PROJECT ADDRESS: ___ ~_7~2-8,__ __ i_O_k_~~K-=---A---V.~¢:::=----~
PROJECT NAME: _ _,_R=A ......... N~D~~ ........... /_l _____ P._R~o-P~L~ic---..I-~-----
D
D
D
D
The plans transmitted herewith have been corrected where
necessary and substantially comply with the jurisdiction's
bu·ilding codes.
The plans transmitted herewith will substantially comply
with the jurisdiction's building codes when minor deficien-
cies identified~-~----------are resolved and
checked by building department staff.
The plans transmitted herewith have significant deficiencies
identified on the enclosed check list and· should be corrected
and resubmitted for a complete recheck.
The check list transmitted herewith is for your information.
The plans are being held at Esgil Corp. until corrected
plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the
jurisdiction to return to the applicant contact person.
· ll} The .applicant's copy of the check list has been sent to:
I11±~r,a~ o/cn1ninJ · I
36 3 t:iftb A•ce
Con c-P(t--$
# :2-oo SD C/2/0 /
i!3 Esgil staff did. not advise the applicant contact person that
plan check has been completed.
O Esgil staff did advise applicant that the plan check has
been completed. Person contacted: ------------
Date contacted: Telephone# ------------------0 REMARKS: ---------------------------
By:' J)AVID YAO
ESGIL CORPORATION $'/~
Enclosures: -----------
0GA--WtM
PLAN CORRECTION SHEXr
PLAN CHECK NO. : _____ q_3_-_2._<J_4-____ _
JURisn1crroN: ____ c ..... a....._i::: .... /s ........ h __ o.._J ______ _
1'0:
36.3
CA 9 2 /0 l
PRO.JEC'I DATA
OCCUPANCY: __________ b' ___ -_~-----
BUlLDING USE: ______ o_.P __ ~....__1_
1 c_-e..-=-----
TYPE OF CONSTRUCTION: ____ V_-N_....c.... ____ _
ACI.'1JAL AREA: _____ ...,.3 ..... /_:?---__ l ..... -_~----
AI.J:.OWABLE AREA: _______________ _
STORIES: _________ ...-.__ ______ _
HEIGB:r: ______ ...._ ___________ _
OCCUPAH'I LOAD: _____ __.._"'-+---------
RE-f.ARKS: __________________ _
Date plans received by jurisdiction:
Date plans received by Esgil Corporation: 3/4
Date initial plan check completed:
___ 3_,__·/2"--'/D _____ .By: YA---o J
Applicant contact person:
µ, qyt o, l'ltl e ~ ( 0. r)"-Tel. __ 2_3...r-_-_6_6_Cf...___O
. . . FORE.1oK>RD: . PLEASE READ
Plan check is limited to technical requirements
contained in the Uniform Building Code, Uniform
Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the
handicapped. The plan check is based on
regulations enforced by the Building Inspection
Department. You may have other corrections based
on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department
or other departments. Code sections cited are
based on the 1991 UBC. Clearance from those
departments may be required prior to the issuance
of a building permit.
The circled items listed need clarification,
modification or change. All items must be
satisfied before the plans will be in conformance
with the cited codes and regulations. Per Sec.
303(c), 1991 Uniform Building Code, the approval of
the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, note on this list
(or a copy) where each correction item has been
addressed, i.e., plan sheet, specification, etc.
Be sure to enclose the marked up list when you
. submit the revised plans.
HO'J:E: PAGE NUMRERS ARE NO'I ]l{ SEQUENCE AS PAGES HAVING NO l'l'.JiMS HEEDING CORREc:rIOHS WERE DELETIID.
LIST NO. 40 TENANT IMPROVEMENT WITHOUT SPECIFIC :i::tIBRGY ZONE; PATA OR POLICY SUPPLEMENTS, 1991 UBC
(0
!·
I
G
I
@
Please make all corrections on the original
tracings and submit two new sets of prints, to:
Esgil Corporation, 9320 Chesapeake Drive,
Suite #208, San Diego, CA 92123,
(619) 560-1468.
Please make all corrections on the original
tracings and submit two new sets of prints, to:
The jurisdiction's building department.
Indicate on the Title Sheet of the plans; the
name of the legal owner and name of person
responsible for the preparation of the plans.
Section 302(d).
Each sheet of the plans must be signed by the
person responsible for their preparation, even
though there are no structural changes.
Business and Professions Code.
Plans and calculations shall be signed by the
California state licensed engineer or architect
·where there are structural changes to existing
buildings or structural additions. Please
include the California license number, seal,
date of license expiration and date plans are
signed. Business and Professions Code.
Provide the correct address and suite number of
tenant space on the plans. Section 302(d).
Provide a note on the site plan indicating the
previous use of the tenant space or building
being remodeled. Section 302.
When the character of the occupancy or use
changes within a building, the building must be
made to comply with current Building Code
requirements for the new occupancy. Please
provide complete details to show the building
with comply. Section 502.
UBC Section 304 requires the Building Official
to determine the total value of all
construction work proposed under this permit.
The value shall include all finish work,
painting, roofing;. electr~cal, plumbing,
heating, air conditioning, elevator, fire
extinguishing systems . and any other permanent
equipment. Please provide a signed copy of the
designer's or contractor's construction cost
estimate of all work proposed.
Provide a plot plan showing the distance from
the building to the property lines and the
location of tenant space (or remodel) within
the building.
plo"d Jb-e
8/4/92
l
l
f·
r·
On the first sheet of the plans indicate:
Type of construction of the existing building,
present and proposed occupancy classifications
of the remodel area and the occupant load of
the remodel areas and the floor where the
tenant improvement is located.
Provide a note on the plans indicating if any
hazardous materials will be stored and/or used
within the building which exceed the
quantities listed in UBC Tables 9-A and 9-B.
A complete description of the activities and
processes that will occur in this tenant space
should be provided. A listing of all
hazardous materials should be included. The
materials listing should be stated in a form
that would make classification in Tables 9-A
and 9-B ;-ossible. The building official may
require a technical report to . identify and
develop methods of protection from hazardous
materials. Section 901(f).
If control areas are used for exceeding the
exempt amounts of hazardous materials from
Tables 9-A and 9-B, they shall be constructed
of not less that required for a one-hour
occupancy separation. Section 404.
The number of control areas within a building
used for retail/wholesale stores shall not
exceed two; the number of control areas in
buildings with other uses shall not exceed
four. Footnote 1, Tables 9-A and 9-B.
The aggregate quantity of any hazardous
materials "in use" and "in storage" shall not
exceed the quantity listed in Tables 9-A and
9-B for "storage". Footnotes 2 and 3, Tables
9-A and 9-B.
r::;-'\ Provide a statement on the Title Sheet of the V plans that this project shall comply with
Title 24 and 1991 UBC, UMC and UPC and 1990
NEC.
I
/.
I·
Provide a fully dimensioned floor plan showing
the size and use of all rooms or areas within
the space being improved or altered. Draw the
plans to scale and indicate the scale on the
plan. Section 302(d).
Indicate the use of all spaces adjacent to the
area being remodeled or improved.
Show any existing fire rated area separation
walls, occupancy separation walls, demising
walls, shafts or rated corridors. Identify
and provide construction details for proposed
new fire rated walls.
Specify on the plans the fire ratings of
assemblies to protect penetrations or proposed
openings in.existing or new fire walls, floor-
ceiling assemblies or roof-ceiling assemblies.
-f-o k:e
p)~o,J-€ J
2
2/·
/
/6.
0
t·
Identify existing walls to be removed,
exis~ing walls to remain and proposed new
walls. Identify bearing walls, non-bearing
walls, and shear walls.
Show safety glazing in the following
locations, per Section 5406(d·):
a. Where the nearest edge of glazing is
within a 24-inch arc of either side of a
door in a closed postion (W1less there is
an intervening wal 1 between the door and
the glazing or if the glazing is 5 1 -011 or
higher above the walking surface).
b. Glazing greater than 9 square feet with
the bottom edge less than 1811 above the
floor and the top edge greater than 3611
above the floor ( unless the · glazing is
more than 3611 horizontally away from
walking surfaces or if 'a complying
protective bar is installed).
c. Glazing in shower and tub enclosures
(including windows within 5 feet of tub
or shower floor).
Provide a section
partitions. Show:
view of all new interior
0 Type, size and spacing of studs. Indicate
gauge for metal studs. Specify
manufacturer and approval number or
indicate 11to be ICBO approved".
Method of attaching top and bottom plates
to structure. (NOTE: 'f2L9f partition
must be secured to roof orrToor framing,
W1less suspended ceiling has been designed
for partition lateral load).
Wall sheathing material and details of
attachment (size and spacing of
fasteners).
Show height of partition and suspended
ceiling, and height from floor to roof
framing or floor framing.
Provide notes and/or details to show that the
floor and wall finish in toilet rooms are
surfaced with a smooth hard non-absorbent
material extending five inches up the wall.
Similar surfacing shall be provided on the
walls from the floor to a height of 4 feet
around urinals and within water closet
compartments. Section 5~0(b).
Note on the plans: 11All interior finishes must
comply with Chapter 42 of the UBC". Specify
"Class ____ .flame spread .rating (minimum) for ____________ "
Note on plan that suspended ceilings shall
comply with UBC Tables 47-A and 23-P.
In buildings having floors and roofs of .wood
frame construction, other than dwelling or
hotel occupancies, draft stop the area between
the ceiling and floor above so that no
concealed space exceeds 1,000 s.f. and no
horizontal dimension exceeds 60 L.F. (if space
has sprinklers, then 31000 s.f. and 100 L.F.).
Section 2516(f).
7/8/92 'r1/~rs1
I·
jo.
,.
j·
r·
l
/6.
/1.
f.
fo·
t·
In buildings having floors and roofs of wood
frame construction, other than dwelling or
hotel occupancies, draft stop the area between
the ceiling and roof above so that no
concealed space exceeds 3,000 s.f. and no
horizontal dimension exceeds 60 L.F. (if space
has sprinklers, then 9,000 s.f. and 100 L.F.).
Section 2516(f).
Storage areas exceeding 1000 sq. ft. in
connection with wholesale or retail sales
shall be separated from the public area by a
one-hour occupancy separation. If the entire
building has an automatic sprinkler system,
then the occupancy separation need not be
provided. Section 702(c).
An automatic sprinkler system shall be
installed in rooms used by the occupants for
the consumption of alcohol and in accessory
uses where the total area of such unseparated
rooms and assembly uses exceeds 5000 square
feet. Section 3802(c).
The tenant space and new and/or existing
facilities serving the remodeled area must be
accessible to and functional for the
physically disabled. See the attached
correction sheet. Title 24, Part 2.
The width of the required level area on the
side into which doors swing shall extend 24
inches past the strike edge for exterior doors
and 18 inches past the strike edge for
interior doors. Section 2-3304, Title 24.
Specify lever-type hardware for passage doors
on floors accessible to the disabled. Section
2-3304, Title 24.
If both sexes will be employed and the number
of employees e~ceeds four, provide separate
toilet facilities for men and women. If "both
sexes will be employed and the total number of
employees will not exceed four11 , and only one
restroom is provided, note the words in
quotation above on the floor plan. Section
705(c).
A --:---:--,,----hour occupancy separation is required between. _______ occupancy and
the _____ occupancy. Table 5-B.
Ducts penetrating occupancy or area separation
walls must have fire dampers. Section 4306
(j).
In areas where the occupant load exceeds __ ,
two exits are required. See. _______ _
Table 33-A.
Provide an exit analysis plan (may be 8 1/211 x
1111 .or any convenient size).
Exits should have a minimum separation of one-
half the-maximum overall diagonal dimension of
the building or area served. Section 3303(c).
1
4/
f·
f·
/a·
r·
;.
/i.
I· r·
The maximum nwnber of required exits and their
required separation must be maintained until
egress is provided from the structure. Section
3303(a).
Rooms with more than 10 occupants may have .Qng
exit through .Qng adjoining room. Revise exits
to comply. Section 3303(e).
Exit signs are required whenever two exits are
required. Show all required exit sign
locations. Section 3314 (a).
Show that exits are lighted with at least one
foot candle at floor level. Section 3313(a).
Show the locations of existing exits from the
building and show the path of travel from the
remodel area to the existing exits.
Note on the plans: "All exits are to be
openable from inside without the use of a key
or special knowledge". In lieu of the above,
·in a Group B occupancy, you may note "Provide a
sign on or near the exit doors reading THIS
DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS".
This signage is only allowed at the main exit.
Section 3304(c).
Exit doors should be a minimum size of 3 feet.
by 6 feet 8 inches with a minimum door swing of
90 degrees. Maximum leaf width is 4 feet.
Section 3304(f).
Exit doors should swing in the direction of
egress when serving an occupant load of 50 or
more or when serving any hazardous area.
Section 3304(b). Applies to door(s) ___ _
Regardless of occupant load, a floor or landing
not more than 1/2 inch below the threshold is
required on each side of an exit door used for
disabled access (may be 111 maximum where not
used for disabled access). Section 3304(i).
Doors should not project more than 7 inches
into the required corridor width when fully
opened, nor more than one-half of the required
corridor width when in any·position. Section
3305(d).
Revolving, s_liding and ove~:'h~d doors are not
permitted as exit doors if the occupant load
exceeds 9 or the exit door-serves a hazardous
area. Section 3304(h).
Provide panic hardware in Group A,E,H-l,H-2,H-3
and I occupancies. Chapter 33.
Double acting doors are not allowed when
serving a tributary occupant load of more than
100, or when part qf a fire assembly, or part
of smoke and draft control ass.emblies or when
equipped with panic hardware. Section
3304{b).
5/28/92
/
I·
f
I
I·
f·
f·
Corridors must provide continuous protection
to the exterior of the building.
Interruptions by an intervening room is not
permitted. Foyers, lobbies or reception rooms
constructed-as required for corridors are not
considered intervening rooms. Section 3305.
Corridors and exterior exit balconies serving
10 or more occupants must be a minimum 44
inches wide and 7 feet high to the lowest
projection. Corridors serving less than 50
occupants may be a minimum of 36 inches in
width. Section 3305(b).
When two exits are required, dead end
corridors and exit balconies are limited to 20
feet. Section 3305(e).
Corridors serving 30 or more occupants shall
have walls and ceilings of one-hour
construction. Show compliance or clearly show
on plans which of the following exceptions has
been satisfied:
a. Corridors greater than 30 feet wide when
the occupants have an exit independent
from the corridor.
b. Exterior sides of exterior exit
balconies.
c. Corridor walls and ceilings need not be
of fire-resistive construction within
office spaces having an occupant load of
100 or less when the entire story in
which the space is located is equipped
with an automatic sprinkler system
throughout and smoke detectors are
installed within the corridor in
accordance with their listing.
d. Within office spaces occupied by a single
tenant, partial height partitions which
form corridors and which do not exceed 6
feet in height need not be fire
resistive, provided they are constructed
in accordance with Section 1705 and are
not more than three fourths of the floor-
to-ceiling height. Section 3305 (g).
Section 3305 (g), Exception 5, cannot be used
for non-rated corridors in a fully sprinklered
office space if the occupant load in the space
exceeds 100.
Section 3305(g), Exception 5 does not apply to
common corridors where the corridor serves as
an exit for non-office areas (manufacturing,
warehouse, etc.).
Section 3305(g), Exception 5 is applicable
only for corridors on one floor; the corridors
on the lower level(s) must be rated if these
lower corridors have openings into them from
other levels.
4
f· ;,.
/1·
Provide evidence of Health Department approval
(for restaurants or for tenants using X-ray
equipment).
If nonflarranable supply cylinders for medical
gas systems are located inside buildings, show
how they comply with UBC Section 702(c)4.
ELECTRICAL
Submit plan showing location of all panels.
Submit panels schedules.
Submit electrical load calculations
Indicate existing main service ~ize.
Indicate existing total main service load.
Indicate new additional loads.
Indicate wiring method, i.e. EMT, metal flex.
Show exit signs on the electrical lighting
plan(s). As per Section 3313 and 3314 of the
1991 UBC, provide two sources of power to exit
signs and exit illumination.
Provide receptacle(s) within 25 1 of HVAC
units. UMC Section 509.
Provide multiple switch lighting controls per
Title 24, Part 6.
Provide mechanical ventilation in all rooms
capable of supplying a minimum of 5 cubic feet
per minute of outside air with a total
circulation of not less than 15 cubic feet per
minute per occupant. Section 605 and 705, UBC. .
Provide mechanical plans showing existing and
proposed HVAC equipment, ducts and access to
equipment.
Detail access and working clearances to HVAC
equipment.
Detail dispos1:1,l of main condensate drainage
from air conditioning _units. (UMC Section
510)
Detail overflow (secondary) . condensate
discharge from air conditioning units that are
in a ceiling space. {UMC Section 1205)
Fire rated corridors are not to be used to
convey air to or from rooms. UMC Section
1002.
PLlMBIBG
Provide gas line plans and calculations,
showing pipe lengths and gas demands. UPC
Section 1219.
8/4/92
Provide drain, waste and vent plans.
Provide water line sizing calculations. UPC
Section 1009.
Detail how floor drain trap seal is to be
maintained. UPC Section 707 (floor drain trap
priming).
Show P & T valve on water heater and detail
drain line route from P & T valve to the
exterior. UPC Section 1007{e).
Show 1/4" per 1211 slope on drain and waste
lines. UPC Section 407.
Provide a drinking fountain at each floor
level in assembly occupancies (except drinking
and dining establishments). UBC Section 605.
Note on the plans that new water closets and
associated flushometer valves, if any, shall
use no more than 1. 6 gallons per flush and
shall meet performance standards established
by the American National Standards Institute
Standard Al12.19.2, and urinals and associated
flushometer valves, if any, shall use no more
than one gallon per flush and shall meet
performance standards established by the
American National Standards Institute Standard
A112.19.2. H & S Code, Section 17921.3(b).
Provide complete energy design calculations,
including all existing design and new energy
design for this building. See attached non-
residential energy design checklist.
-uarf. For remodels in an existing conditioned space,
/--show that the remodeled space will not use
more energy than the existing space or show
the remodeled space will conform to latest
energy design ~rds. ~ P~\'Dc. .STh"'ti=MEIJT OJJ
MISCELLANEOUS ~t.) .$ Tr\-A-'T 1*.R.t= \~ Uo .1. · ..kl AC.. ~ e&.J eu, v CoM'1t .. u,o c:e.
,.,2. Please see additional-corrections or remarks\~
that follow. t,.)Oi
,-?n:\ To speed up the recheck process, note on this ~~n ~ list (or a copy) whee each correction item has
been addressed, i.e., plan sheet, note or
detail number, calculation page, etc.
~ Please indicate here if any changes have been C7 made to the plans that are not a result of
corrections from this list. If there are
other changes, please briefly describe them
and where they are located in the plans.
Have changes been made to the plans not
resulting from this correction list? Please
check.
____ Yes -----'No
6
' .
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number
of 619/560-1468, to perform the plan check for your
project. If you have any questions regarding these plan check items, please contact _______ _
"QAJ/ID
at Esgil Corporation
Thank you.
Enclosures:
'(AO
1. ____________________ _
2. _______________________ _
3. _____________________ _
8/4/92 7
-J: ... ,,. f
Jurisdiction_--=-CA._._.,_,~=Ls=B~A=D"'--_ Date, 3 /ro
Prepared bys
DAVID YA--o VALUATION AND PLAN CHECK FEE
D Bldg. Dept.
0 Esgil
PLAN CHECK NO. __ q~~---~~~~-
BU I LDING ADDRESS __ 2-..:..7-:-)-. ..... 8_...._ __ Lo_.._..._k. ___ P._r _ _..A----"'-c...e ___ 1;..:.:ftJ.__-P;,...:...r,.__t ________ _
APPLICANT/CONTACT 'Xl1if;J,c,-y pion n/1Jf ~Plt_ PHONE NO. 2.. 3.I'---6690
I (7 j
BUILDING OCCUPANCY B -..:?..... DESIGNER PHONE ------V--N (s-,:>k;.7 CONTRACTOR PHONE I> -----TYPE OF CONSTRUCTION
BUILDING PORTION BUILDING AREA VALUATION VALUE / MULTIPLIER
l'-7~ · =s 11/4-1<r"' 7-&r-f~
/\ ?
I )
I I
\_ r l \~~ f?-yr~
'--' -' ,.
I
_./ ' j I J.
Air Condi t1onina; · --ru ~ ~, -'l ~ r /;:,A
Commercial -I '7 @ j ,
Residential @
Res. or Comm.
Fire Snrinklers ·@
Total Value 7~
,?-...
COM MEN TS._: __________________________ _,:_ _
SHEET _ ..... (.-0 F __ /_
12/87
City of Carlsbad
M3U·hh44iih·l•l4·Eiihef401
BUILDING PLANCHECK CHECKLIST
DATE: 8 NlAR 93 PLANCHECK NO.CB93--0204
BUILDING ADDRESS: 2.7 28 LOKEP. A'\IE V\J,
PROJECT DESCRIPTION: _i:;.;.ND-= .. =·~T...,.. .. .L:=.:;.... _______________ _
ASSESSOR's PARCEL NUMBER: 209~ O@{·-20 EST. VALUE. _____ _
ENGINEERING DEPARTMENT
APPROVAL
The item you have submitted for review has been
approved. The approval is based on plans,
information and/or specifications provided in your
submittal; therefore any changes to these items
after this date, including field modifications, must
be reviewed by this office to insure continued
conformance with applicable codes. Please review.
carefully all comments attached, as failure to
comply with instructions in this report can result in
suspension of permit to build.
ATTACHMENTS
D Dedication Application
D Dedication Checklist
DENI.AL
Please see the attached report of deficiencies
marked with J~f, Make necessary corrections to
plans or specifications for compliance with
applicable codes and standards. Submit corrected
plans and/or specifications to this office for review.
By: S., .st'.2t{EDELL Date: 8 MAQ g3
By: __________ Date:, ___ _
By: _________ Date: ___ _
CONTACT PERSON
D Improvement Application
D Improvement Checklist NAME: ______________ _
D Future Improvement Agreement
ADDRESS: ______________ _
PHONE: ______________ _
P:\doca\chklst\bp0001.frm REV 6/5/92
2075 Las Palmas Dr.• Carlsbad, CA 92009-1576 • (619) 438-1161 • FAX (6~ 9) 438-0894 @
/ •
BUILDING PLANCHECK CHECKLIST
SITE PLAN
1 s)'/ 2ndv' 3rdv'
~-D D 1. Provide a fully dimensioned site plan drawn to scale. Show:
A North Arrow
8. Existing & Proposed Structures
C. Existing Street Improvements
D. Property Lines Easements
E. Easements
F. Right-of-Way Width & Adjacent Streets
D D
N/A
D · 2. Show on site plan:
D D D
N/A
D D D
N./1~
(0 D D
A Drainage Patterns C. Existing Topography
B. Existing & Proposed Slopes
3. Show on a section drawing or include a note stating that there is a minimum of 6"
difference between the finished floor and the finished grade elevation adjacent to the
structure.
4. Include note: "Surface water to be directed away from the building foundation at a 2%
gradient for no less than 5' or 2/3 the distance to the property line ·(whichever is less)."
On graded sites, the top of any exterior foundation shall extend above the elevation
_of the street gutter at point of discharge or the inlet of an approved drainage device
a minimum of 12 inches plus two percent" (per 1990 UBC 2907(d)5.).
5. Include on title sheet
A. Site address
8. Assessor's Parcel Number
C. Legal Description
For commercial/industrial buildings and tenant improvement projects, include: Total
building square footage with the square footage for each different use, existing sewer
permits showing square footage of different uses (manufacturing, warehouse, office,
etc.) previously approved. ·
EXISTING PERMIT NUMBER DESCRIPTION
P:\docs\chklst\bp0001.frm Page 1 of 4 REV 6/5/92
'-•/ BUILDING PLANCHECK CHECKLIST
N./A DISCRETIONARY APPROVAL COMPLIANCE
1 st./ 2nd./ 3rd./ D D D 6. Project does not comply with the following Engineering Conditions of approval for Project No. ________________________ _
Conditions were complied with by: ______ _ Date: --------
N/A DEDICATION REQUIREMENTS
D D D 7. Dedication for all street Rights-of-Way adjacent to the building site and any storm
drain or utility easements on the building site is required for all new buildings and for
remodels with a value at or exceeding $ ______ -pursuant to Code Section ,
18.40.030.
Dedication required as follows: _________________ _
Attached please find an application form and submittal checklist for the dedication
process. Provide the completed application form and the requirements on the
checklist at the time of resubmittal.
Dedication completed by ____________ _ Date: ____ _
IMPROVEMENT REQUIREMENTS
D D D Sa. All needed public improvements upon and adjacent to the· building site must be
constructed at time of building construction whenever the value of the construction
exceeds __________ -pursuant to Code Section 18.40.040.
Public improvements required as follows: ______________ _
Please have a registered Civil Engineer prepare appropriate improvement plans and
submit them together with the requirements on the attached checklist for a separate
plancheck process through the Engineering Department. Improvement plans must be
approved, appropriate securities posted and fees paid prior to issuance of permit.
Attached please find an application form and submittal checklist for the public
improvements requirements. Provide the completed application form and the
requirements on the checklist at the time of resubmittal.
Improvement Plans signed by: __________ _ Date: ___ _
P:\docs\chklst\bp0001.frm Page 2 of 4 REV 6/5/92
I.I
1st./ 2nd./ 3rd./ D D D
BUILDING PLANCHECK CHECKLIST
Sb. Construction of the public improvements may be deferred pursuant to code Section
18.40. Please submit a recent property title report or current grant deed on the
property and processing fee of $ _________ so we may prepare the
necessary Future Improvement Agreement. This agreement must be signed, notarized
-and approved by the City prior to issuance of a Building Permit.
Future public improvements required as follows: ___________ _
D D D Sc. Enclosed please find your Future Improvement Agreement. Please return signed and
notarized Agreement to the Engineering Department.
D D
D D
io
D
D
D
D
Future Improvement Agreement completed by: ____________ _
Date: __________ _
8d. No Public Improvements required. SPECIAL NOTE: Damaged or defective
improvements found adjacent to building site must be repaired to the satisfaction of
the City Inspector prior to occupancy.
~ GRADING PERMIT REQUIREMENTS
The conditions that invoke the need for a grading permit are found in Section 11.06.030
of the Municipal Code.
9a. Inadequate information available on Site Plan to make a determination on grading
requirements. Include accurate grading quantities (cut, fill import, export).
-,
9b. Grading Permit required. A separate grading plan prepared by a registered Civil
Engineer must be Submitted together with the completed application form attached.
NOTE: The Grading Permit must be issued and rough grading approval obtained prior
to issuance of a Building Permit.
Grading Inspector sign off by: Date:
9c. No Grading Permit required.
BUILDING PLANCHECK CHECKLIST
P:\docs\chklst\bp0001.frm Page 3 of 4 REV 6/5/92
1st./ 2nd./ 3rd./
D D D
N/A
MISCELLANEOUS PERMITS
10. A.RIGHT-OF-WAY PERMIT is required to do work in City Right-of-Way and/or
private work adjacent to the public Right-of-Way. Types of work include, but are not
limited to: street improvements, trees, driveways.
A separate Right-of-Way permit issued by the Engineering Department is required for
the following:---------...:.--------------
Please complete attached Right-of-Way application form and return to the Engineering
Department together with the requirements on the attached Right-of-Way checklist, at
the time of resubmittal.
gJ D .-D 11. A SEWER PERMIT is required concurrent with the building permit issuance. The fee
is noted in the fees section on the following page.
D D D
N/A
12. INDUSTRIAL WASTE PERMIT is required. Applicant must complete Industrial
Waste Permit Application Form and submit for City approval prior to issuance of a
Permit.
Industrial waste permit accepted by: ______ _ Date: ----
P:\docs\chklat\bp0001.frm Page 4 of 4 REV 6/5/92
,'.-----------------------------------CALCULATIONS WORKSHEET
J
EDU CALCULATIONS:
l~:~l. x 3 i25f=r-= L,74 ED0 --0. ~2.&Ae8--(Dll.Se:. Ci?..BD(!}
ADT CAL LATIONS: · . /
, ---~' _, 2 -(pJ~N' -.i. '3i2.SFi2.::-43.tSl+J)T
i'"'· FTL
WITHIN CFO:
JZf NO
N./A
PARK AREA:_______ FEE/UNIT: _ _,_,_-.r
·~ 2.TRAFFIC IMPACT FEE
ADT's: ·44 -.:....:....---
~ 3. BRIDGE AND THOROUGHFARE EE
• I
ADT's: 44
N/A O 4. FACILITIES MANAGEMENT F
ZONE: ____ _
N/A O ·s. PUBLIC FACILITIES F
N/A
:£21. 6. SEWER FEES PE IT No. SEg30012.,
FEE/EDU: lbl0
FEE: 1'1/EDU I
LATERAL REQUIRED (2,500 DEPOSIT)
"'2 REMARKS: E931L TO VER.I Pi r-T -
P:\doca\chklat\bp0001.frm
EDU's: I a I 2=.
ADT's: 44
REV 6/5/92
PLANNING CHECKUsr
Plan Check No. t/J-~elf Address r)7;2_g-bokfr lk:(. [/.
Planner DAVID RICK Phone 438-1161 ext . ..__;;4i.a:3.=.:28:.!--__ _
(Name)
APN: __ -=---:)_D...;...f_,..._o_g ___ /_,._2._] ___________ _
T(j Type of Project and Use _____ .,.-__________ _
Zone PtJ Facilities Management Zone _____ S-__
Legend
C2J Item Complete
@ Item Incomplete· Needs your action
1, 2, 3 Nurnber·in circle indicates plancheck number where deficiency was
identified
~D D Environmental Review Required: YES
DATE OF COMPLETION:
NO ~TI'PE __ _
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval_. _____________________ _
C:YD D Discretionary Action Required: YES NO /TYPE __ _
APPROVAL/RESO. NO. ___ DATE: _____ _
PROJECT NO. ___ _
OTHER REIATED CASES: ___________________ _
Compliance v,ith conditions of approval? If not, state conditions which require action. Conditions of Approval ______________________ _
if O O California Coatal Commmion Permit Required: YES _ NO /
DATE OF APPROVAL:
San Diego Coast Disttict, 3111 Camino Del Rio North, Suite 200, San Diego, CA. 92108-1725
(619) 521-8036
Compliance with conditions of approval? If not, state conditions which require action. Conditions of Approval ______________________ _
efoo
Q/o.o
;~D
' ·i. . . "··
Landscape. Plan Required: YES ........-: NO . , /
See attached submittal tequirements fot landscape. plans . ' ' . ' . '
Site Pfai,.:
Zoil.ing:.
1.
2.
3.
4.
Pr0vide a fully .dimensioned site ,plan drawn to scale... Show: No"rth
arrow, property 'lih~·s, easements, existing and proposed structures,
stre~t$, · existing street ~provemertts, right-of-way width and
4imensioned setbacks. ·
Show:. ·on Site Plan: · F1rush floor .elevations, elevations 0f finish grade
. . \ .. adjacent. to.bu.ilw,ng, e;<isdng topograp}:,.kal lines, -existing. and proposed
slopes and driveway. ·
. .
· .Provide _legal description of prop·erty.
Provide a~sessor's :Pc)rce·i number.
: o .o· CJ tv!+ 1. Setbacks:
2.
3 ..
·Freme:
-Int. Side: .
. $ treet Side:
Rear:
,i .. ot coverage:
Height:_
f\equfred
:Required
· Required .
Reqlli.red
· Required
. Requ,i.r~d
· Spaces Requ'.ired
G~est' Spaces: Req~
. )
OKTO ISSUE AND ·~N$REO APPROVAl.INTO.COMP~R
.Jef=-shown . JJ:;>q
Shown., ---------------Shown ___ _____ __ Shown __
Shown --.......... ____
________ Shown---"---
/ Dr: Shown· I Q1 __ shown __
DATE
P_LNCKFRM
·• ..
City of Carlsbad 92171-1
Fire Department, • Bureau of Prevention
Plan Review: Requirements Category: Building Plan Check
Date of Report: Thursday, March 4, 1993
Contact Name
Address
City, State
Marianne Elam
Reviewed by:~
363 5Th Avenue
San Diego CA 92101
Bldg. Dept. No. _9_30_2_0_4 ___ _ Planning No.
Job Name Randall Products
Job Address 2728 Loker w ------------------Ste. or Bldg. No. ____ _
~ Approved -The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
D Disapproved -Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1st. __ _ 2nd~--3rd~--
Other Agency ID
CFD Job# __ 92_1_7_1-_1_ File# ___ _
2560 Orion Way • Carlsbad, California 92008 • (619) 931-2121