HomeMy WebLinkAbout2754 AUBURN AVE; ; CB112382; Permit12-23-2011
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Residential Permit Permit No: CBl 12382
Building Inspection Request Line (760) 602-2725
2754 AUBURN AV CBAD
RESDNTL
1674900200
$63,230.00
0
COXSEY RES-
Sub Type:
Lot#:
Construction Type:
Reference #:
Structure Type:
Bathrooms:
ADD 480 SF TO
RAD
0
5B
status:
Applied:
Entered By:
Plan Approved:
Issued:
Inspect Area:
Orig PC#:
ISSUED
11/08/2011
LSM
12/23/2011
12/23/2011
EXTEND EXISITING BEDROOMS AND EXTEND KITCHEN Plan Check #
Applicant:
JOSH COXSEY
Owner:
2754 AUBURN AV
CARLSBAD CA 92010
760-420-6084
Building Permit $519.22 Meter Size
Add'l Building Permit Fee $0.00 Add'l Reel. Water Con. Fee $0.00
Plan Check $363.45 Meter Fee $0.00
Add'l Plan Check Fee $0.00 SDCWA Fee $0.00
Plan Check Discount $0.00 CFD Payoff Fee $0.00
strong Motion Fee $6.32 PFF (3105540) $0.00
Park in Lieu Fee $0.00 PFF (4305540) $0.00
Park Fee $0.00 License Tax (3104193) $0.00
LFM Fee $0.00 License Tax (4304193) $0.00
Bridge Fee $0.00 Traffic Impact Fee (3106541) $0.00
other Bridge Fee $0.00 Traffic Impact Fee (4305541) $0.00
BTD #2 Fee $0.00 Sidewalk Fee $0.00
BTD #3 Fee $0.00 PLUMBING TOTAL $150.00
Renewal Fee $0.00 ELECTRICAL TOTAL $30.00
Add'l Renewal Fee $0.00 MECHANICAL TOTAL $30.00
other Building Fee $0.00 Housing Impact Fee $0.00
HMP Fee $0.00 Housing InLieu Fee $0.00
Pot. Water Con. Fee $0.00 Housing Credit Fee $0.00
Meter Size Master Drainage Fee $0.00
Add'l Pot. Water Con. Fee $0.00 Sewer Fee $0.00
Reel. Water Con. Fee $0.00 Additional Fees $0.00
Green Bidg Stands (SB1473) Fee $1.00 Fire Sprinkler Fees $0.00
Green BIdg Stands Plan Chk Fee $0.00
TOTAL PERMIT FEES $1,099.99
Total Fees: $1,099.99 Total Payments To Date: $363.45 Balance Due: $736.54
Inspector:
FINAL APRROVAL
/•6 • /2-Date: Clearance:
NOTICE: Please take NOTICE that approval of your proiect Includes the Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as lees/exactlons." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth In Government Code Section 66020(a), and file the protest and any other required Information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connectton fees and capacity
changes, nor planning, zoning, grading or other similar application processing or sen/k» fees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which vou have previously been given a NOTICE similar to this, or as to which the statute of limitations has orevtouslv othenwise expired.
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Storm Water Pollution Prevention Plan (SWPPP) Permit
12-23-2011 Permit No:SW110423
Job Address:
Permit Type:
Parcel No:
Reference #:
CB#:
Project Title:
Priority:
2754 AUBURN AV CBAD
SWPPP
1674900200 Lot#: 0
CBl12382
COXSEY RES- ADD 480 SF TO
EXTEND EXISITING BEDROOMS AND KITCHEN
M
status: ISSUED
Applied: 11/08/2011
Entered By: LSM
Issued: 12/23/2011
Inspect Area:
Tier: 1
Applicant:
JOSH COXSEY
Owner:
2754 AUBURN AV
CARLSBAD CA 92010
760-420-6084
Emergency Contact:
JOSH COXSEY
760-420-6084
SWPPP Pian Check
SWPPP inspections
Additional Fees
$50.00
$210,00
$0.M
TOTAL PERMIT FEES $260.00
Total Fees: $260.00 Total Payments To Date: $260.00 Balance Due: $0.00
FINAL APPROVAL
DATE_
SIGNATURE
CITY OF
CARLSBAD
Building Permit Appiication
1635 Faraday Ave., Carlsbad, CA 92008
760-602-2717 / 2718 / 2719
Fax: 760-602-8558
www.carlsbadca.gov
Plan Check No.
Est. Value 05,^BO
Pian Ck. Deposit 3 • 9S
Pate IVI y/ t ( SWPP 11 Q<4 gJS
JOB ADDRESS a SUITE#/SPACE#/UNIT# APN 10 - OZ. - oo
CT/PR0JECT# L0T# PHASE* # OF UNITS # BEDROOMS # BATHROOMS TENANT BUSINESS NAME CONSTR.TYPE OCC. GROUP
z DESCRIPTION OFJJJORK: Include Square Feet of Affected Areafs) lll^T^
(69>0) f^/a /Udihe^ ^ JiLm sic/< cP hn&^ . .P\/e^c^n^
EXISTING USE PROPOSED USE
l^4"7 no
GARAGE (SF)
(i?0O
PATIOS (SF) DECKS (SF) FIREPLACE UI.I AIR CONDITIONING FiRE SPRINKLERS
YESJfi #_IM^0 • YES • Nd^ YES • N(jJl^
APPLICANT NAME (Primary Contact) . V » APPLICANT NAME (Secondary Contact)
ADDRESS 3 ADDRESS J .
CITY 1 STATE ZIP CITY ^ , STATE ZiP
WiGNE
C7(pO) ^^o-(c:o8M
FAX PHONE FAX
tMAiL _\^\^(2D^^^ jg> VfiVlOO . CO »v\ EMAIL
PROPERTY OWNER NAME ' | . /) CONTRACTOR BUS. NAME r\ i f
ADDRESS 1 1
1
ADDRESS
CITY <~-^ ^ _ . STATE^ , . ZIP
AS Ai^tvi^.
CITY f\ . STATE ZIP
PHONE FAX PHONE / FAX
ElVIAIL EMAIL
ARCH/DESIGNER NAME & ADDRESS STATE LIC. # STATE L1C.# 1
7«?.iszt)
CITY BUS, LIC.#
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to fiie a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law (Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the appiicant to a civil penalty of not more than five hundred dollars {$500}).
W O ft M E B S C O IW P E « S A T I O N
tfUers' Compensation Declaration: I hereby affirm under pen^ of perjury one ofthe foiiowing declarations:
jPP I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this pemiit is issued.
O i liave and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the perfonnance of the vrark for which this permit is issued. My workers' compensation insurance earner and policy
number are: Insurance Co. . Policy No. . Expiration Date
is secfion need not be completed if the pemiit is for one hundred dollars ($100) or less.
Certificate of Exemption: I certify that in the perfomnance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensafion Laws of
California. WARNING: Failure to secure workers' compensation coverage Is unlawful, and sliall subject an employer to criminal penalties and civil fines up to one liundred ttiousand doiiars (&100,000), In
addition to the cost of compensation, damages as provided for in SectlonSTOSjttbei^bor code, interest and attorney's fees.
^CONTRACTORSIGNATURE ^^^^"^^^7^"^^ . -y OAGENT DATE //^7^//
?0, MH 1 R - * t.-|> B' P E ct A R A T « O -N
/ hefeby affimi fhaf / am exempf from Contractor's Ucense Law for the following reason:
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered fbr
sale. If, however, the building or Improvement is sold within one year of completion, the owner-builder will have (he burden of proving that he did not build or Improve for the purpose of sale).
f l, as ovmer of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
Cl 1 am exempt under Section Business and Professions Code for this reason:
1.1 personally plan to provide the major labor and materials for construction of the proposed property improvement Yes • No
2.1 (have / have not) signed an application for a building permit for the proposed work.
3.1 have contracted with the following person (firni) to provide the proposed construction (include name address / phone / contractors' license number):
4.1 pian to provide portions of the work, but i have hired the following person to coonlinate, supen/ise and provide the major work (include name / address / phone / contractors' license number):
5.1 will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone / type of vrark):
>£$'PR0PERTY OWNER SIGNATURE •AGENT DATE
'k FOR Milli RESIDE INITIAL BUILDING PlHMltS Eiliriiiiiiiiiii
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration fomi or risk management and prevention program under Sections 25505,25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? • Yes • No
Is the applicant or future building occupant required to obtain a pemiit from the air pollution control district or air quality management district? • Yes • No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? • Yes • No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPUCANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a construction lending agency for the performance of the work this permit Is issued (Sec. 3097 (i) Civil Code).
Lender's Name Lender's Address
I certif ttiat i have lead the application and state that the above Infomiation Is conect and ttiat the Infbmiation on the plans Is accurate. I agree to comply with all City ordinances and State laws relating to building consbuction.
I hereby aulhorize representative of Ihe City of Carlsbad to enter upon the above mentioned property fbr Inspectton puiposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CfTY OF CARLSBAD
AGAINST ALL UABILmES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CfTY IN CONSEQUENCE OF TME GRANTING OF THIS PERMfF.
OSHAiAnOSHApermltisrequiredlbr excavations overS'O'deepanddemolltlonor constmction of stnictures over 3 stories In height
EXPIRATION: Every pennit Issued by the Building Official under the provisions of this Code shall expire by limilatton and become null and void If Ihe buMing or woii< authorized by such pemiit Is not commenced within
180 days ton the date of such pemiit or it the building or work authorized by such pemiit B suspended orabandoned at any time after Ihe wok is commenced for a period of 180 days (Section 106.4.4 Unifonn Building Code).
^SS'APPUCANT'S SIGNATURE "^"'^^'^^^F-'—T*'^^^ MI DATE
Inspection List
Permit#: CBl 12382 Type: RESDNTL RAD
Date Inspection Item
08/06/2012 19 Final Structural
08/06/2012 89 Final Combo
02/14/2012 17 Interior Lath/Drywall
02/14/2012 18 Exterior Lath/Drywall
02/10/2012 16 Insulation
02/07/2012 84 Rough Combo
01/13/2012 13 Shear Panels/HD's
01/13/2012 15 Roof/Reroof
12/28/2011 11 Ftg/Foundation/Piers
12/28/2011 21 Underground/Under Floor
12/28/2011 24 Rough/Topout
-Rl
PD AP
PD AP
PD AP
PD AP
PD AP
PD AP
PD AP
PD AP
PD AP
PD WC
COXSEY RES- ADD 480 SF TO
EXTEND EXISITING BEDROOMS AND EXT
Inspector Act Comments
NOT SURE OF CODES
Tuesday, August 07,2012 Page 1 of 1
EsGil Corporation
In (Partnersliip •witti government for (BuiCcCing Safety
DATE: 11/30/2011 •APPUCANT
^JURIS.^
JURISDICTION: City of Carlsbad • PLANREVIEWER
• FILE
PLAN CHECK NO.: 112382 SET: II
PROJECT ADDRESS: 2754 Auburn Ave.
PROJECT NAME: Coxsey Addition
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
^ The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
I I The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to fonward to the applicant
contact person.
I I The applicant's copy of the check list has been sent to:
1^ Esgil Corporation staff did not advise the applicant that the plan check has been completed.
I I Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Email: Fax #:
Mali Telephone Fax In Person
AI REMARKS: Please transfer the cloudy redlines on Page 4 to all City sets prior to issuing the
permit.
By: Aaron Goodman Enclosures:
EsGil Corporation
• GA • EJ • PC 11/22/2011
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858)560-1468 • Fax (858) 560-1576
EsGil Corporation
In (Parttiersliip witR government for <BuiCding Safety
DATE: 11/15/2011 • APPLICANT
[>^0Ri^
JURISDICTION: City of Carlsbad • PCXNREVIEWER
• FILE
PLAN CHECK NO.: 112382 SET: I
PROJECT ADDRESS: 2754 Auburn Ave.
PROJECT NAME: Coxsey Addition
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
I I The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
3 The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
3 The applicant's copy of the check list has been sent to:
Josh Coxsey
2754 Auburn Ave., Carlsbad, CA 92010
I I Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Josh Coxsey Telephone #: 760-420-6084
Date contacted:/((i 5 ^'I (by: w;^) Email: ioshcoxsev@vahoo.com Fax #:
i. Mail >^ Telephone Fax In Person
• REMARKS:
By: Aaron Goodman Enclosures:
EsGil Corporation
• GA • EJ • PC 11/10/2011
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858)560-1468 • Fax (858) 560-1576
City of Carlsbad 112382
11/15/2011
GENERAL PLAN CORRECTION LIST
JURISDICTION: City of Carlsbad PLAN CHECK NO.: 112382
PROJECT ADDRESS: 2754 Auburn Ave.
DATE PLAN RECEIVED BY
ESGIL CORPORATION: 11/10/2011
DATE REVIEW COMPLETED:
11/15/2011
REVIEWED BY: Aaron Goodman
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the International Building
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, noise attenuation and disabled access. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. The approval of
the plans does not permit the violation of any state, county or city law.
• Please make all corrections and submit two new complete sets of prints to:
Esgil Corp. or to the bIdg. dept. of the juris.
• To facilitate reciiecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
• Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
• Yes • No
City of Carlsbad 112382
11/15/2011
1. Please make all connections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one of
two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carisbad, CA 92008, (760) 602-
2700. The City will route the plans to EsGil Corporation and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete.
2. Indicate on the Title Sheet of the plans the name of the legal owner and name of the
person responsible for the preparation ofthe plans. Section R106.1.1.
3. All sheets of plans must be signed by the person responsible for their preparation.
(California Business and Professions Code).
4. Provide a statement on the Title Sheet of the plans stating that this project shall comply
with the 2010 California Residential Code, which adopts the 2009 IRC, 2009 UMC, 2009
UPC and the 2008 NEC. Section R106.2.
5. The "minimum construction specification" handout submitted is out of date and it is from
the City of San Diego, not Carisbad. Please add the correct framing specifications to the
plans. Your plans aren't that far off. Please check with the City of Carlsbad for their
construction specifications.
6. In dwelling units within which fuel-burning appliances are installed (and in dwelling units
having attached garages), show the locations of permanently wired carbon monoxide
alarms with battery backup, per Section R315:
a) Outside each separate sleeping area in the immediate vicinity of the bedrooms.
• NOTE: When more than one carbon monoxide alarm is required to be installed, the
alarm devices shall be interconnected in such a manner that the actuation of one
alarm will activate all of the alarms in the unit.
City of Carlsbad 112382
11/15/2011
7. When alterations, repairs or additions are proposed for dwelling units within which fuel-
burning appliances are installed (and in dwelling units having attached garages), the
dwelling unit shall be provided with carbon monoxide alarms located as required for
new dwellings; the carbon monoxide alarms shall be interconnected and hard wired.
Exception: Carbon monoxide alarms in existing areas need not be interconnected and
hard wired where the alterations or repairs do not result in the removal of interior wall or
ceiling finishes exposing the structure, unless there is an attic, crawl space, or basement
available which could provide access for hard wiring and interconnection without the
removal of interior finishes. Section R315.2.
8. Specify on the plans the following information for the roof materials, per Section
R106.1.1:
a) Class A roof covering
b) Manufacturer's name.
c) Product name/number.
d) ICC approval number, or equal.
9. Show the required ventilation for attics (or enclosed rafter spaces formed where ceilings
are applied directly to the underside of roof rafters). The minimum vent area is 1/150 of
attic area (or 1/300 of attic area if at least 50% (but not more than 80%) of the required
vent is at least 3 feet above eave vents or cornice vents). Show on the plans the area
required and area provided. Section R806.2.
10. Note on the plans: "Attic ventilation openings shall be covered with corrosion-resistant
metal mesh with 1/8" minimum to VA" maximum openings. Section R806.1.
11. Show on plans that wood shall be 6" minimum above finish grade. Section R404.1.6.
12. Note on plans that surface water will drain away from building and show drainage
pattern. The grade shall fall a minimum of 6" within the first 10 feet. Section R401.3.
13. Foundation anchorage in Seismic Design Categories C, Do, Di and D2. In addition to
the requirements of Section R403.1.6, the following requirements shall apply to wood
light-frame structures in Seismic Design Categories Do, Di and D2 in Seismic Design
Category C. R403.1.6.1
1. Plate washers conforming to Section R602.11.1, 0.229"x3"x3", shall be provided for
all anchor bolts over the full length of required braced wall lines. Properly sized cut
washer shall be permitted for anchor bolts in wall lines not containing braced wall
panels.
2. Interior braced wall plates shall have anchor bolts spaced at not more than 6 feet
(1829 mm) on center and located within 12 inches (305 mm) of the ends of each
plate section when supported on a continuous foundation.
3. Interior bearing wall sole plates shall have anchor bolts spaced at not more than 6
feet (1829 mm) on center and located within 12 inches (305 mm) ofthe ends of each
plate section when supported on a continuous foundation.
City of Carlsbad 112382
11/15/2011
14. The following locations shall require the use pressure-preservative treated wood (Section
R317.1):
a) All sill plates that rest on concrete exterior walls and are less than 8" above
exposed ground.
b) Sills and sleepers on a concrete slab that is in direct contact with the ground
(unless separated from such slab by an impervious moisture barrier).
c) Wood siding, sheathing and wall framing on the exterior of a building having a
clearance of less than 6" from the ground.
15. Show stud size, height and spacing on the plans. Maximum allowable stud heights shall
be per Table R602.3(5).
16. Show double top plate with minimum 48" lap splice. Section R602.3.2.
17. Provide truss details and truss calculations for this project. Specify truss identification
numbers on the plans. The truss design drawings must contain all the infomiation listed
in Section R802.10.
18. Provide roof framing plan. The elevation on sheet 6 shows the ridge of the dwelling
ending at the intersecting ridge of the garage. See the elevations and roof plan on sheet
4. To create the ridgeline shown on the elevation, 3 to 4 trusses will need to be replaced
over the existing dwelling and to complete the roof framing, over-framing is required
between the garage and dwelling roof. Please revise and complete the roof framing plan.
Section R106.1.
19. Show on the plans the location, type and size (BTU's) of all heating and cooling
appliances or systems.
20. Every dwelling unit shall be provided with heating facilities capable of maintaining a room
temperature of 68 degrees F at a location 3 feet above the floor and 2 feet from exterior
walls in all habitable rooms. Show basis for compliance. CRC 303.8.
21. Show the minimum 30" deep unobstructed working space in front of the attic installed
furnace. Section CMC Section 904.11.4.
22. The access opening to attics must be large enough to remove the largest piece of
mechanical equipment and be sized not less that 30" x 22". CMC Section 904.11.1.
23. Note that passageway to the mechanical equipment in the attic shall be unobstructed,
have continuous solid flooring not less than 24 inches wide, and be not more than 20
feet in length from the access opening to the appliance. CMC Section 904.11.
24. Show a permanent electrical receptacle outlet and lighting fixture controlled by a switch
located at the entrance for furnaces located in an attic. CMC Section 904.11.5.
25. Note on the plans that receptacle outlet locations will comply with CEC Article 210.52(A).
City of Carlsbad 112382
11/15/2011
26. Include on the plans the following specifications for electrical devices installed in
dwellings: CEC Article 210 & 406
a) Tamper resistant receptacles for all locations described in 210.52 (i.e., all
receptacles in a dwelling).
b) Weather resistant tvpe for receptacles installed in damp or wet locations (outside).
c) Arc-fault protection for all outlets (not just receptacles) located in rooms described
in NEC 210.12(B): Family, living, bedrooms, dining, halls, etc.
d) GFCI protected outlets for locations described in NEC 210.8: Kitchens, garages,
bathrooms, outdoors, within 6' of a sink, etc.
27. For a single-family dwelling unit (and for each unit of a duplex), show that at least one
receptacle outlet accessible at grade level will be installed outdoors at the front and back
ofthe dwelling. CEC Article 210.52(E). This receptacle must be GFCI protected.
28. Show on the plans that countertop receptacle outlets comply with CEC Artiicle 210.52(C):
In kitchens a receptacle outlet shall be installed at each counter space 12 inches or
wider; Receptacles shall be installed so that no point along the wall line is more than 24
inches; Island and peninsular countertops 12 inches by 24" long (or greater) shall have at
least one receptacle. (Counter top spaces separated by range tops, refrigerators, or
sinks shall be considered as separate counter top spaces).
29. Per CEC Article 210.11(C)3, note on the plans that bathroom circuiting shall be either:
a) A 20 ampere circuit dedicated to each bathroom, or
b) At least one 20 ampere circuit supplying only bathroom receptacle outlets.
30. Show on the plans a wall receptacle within 36" of each lavatory in the bathroom. CEC
210.52(D) &E3801.6.
31. The energy compliance forms submitted are out of date. Provide a Prescriptive or
Performance energy design to show compliance with current 2008 energy efficiency
standards. Information and Forms are available at:
www.enerav.ca.aov/title24/2008standards.
32. The version of the energy computer program that you have used is no longer current.
Provide new calculations, using updated residential computer energy programs. As of
August 1, 2010, they are the following:
• MICROPAS 8.1
• EnergyPro 5.1
• CALRES 2008 v. 1.1
33. The regulations require a completed and signed Form CF-1 R (all pages) to be either
imprinted on the plans, included with the plans, taped to the plans, or "sticky backed" on
the plans.
City of Carlsbad 112382
11/15/2011
34. Include all applicable sections of the MF-1R form with the plans.
35. Show on the plans compliance with the residential energy lighting requirements
(Mandatory requirement):
a) In the kitchen at least one-half of the wattage rating of the fixtures must be high
efficacy with non-high efficacy fixtures switched separately. Note: Approximately
% of the fixtures will be required to be of the high efficacy variety.
b) All other rooms require any installed fixtures to be high efficacy or be controlled by
a vacancy sensor or dimmer. (Closets under 70 square feet are exempt).
c) Outdoor liahting fixtures that are attached to a building are required to be high
efficacy or controlled by a combination photo-control/motion sensor.
yVofe; Generally a high efficacy style of fixture is fluorescent, complete with electronic
ballasts. Regular incandescent, quartz halogen and halogen MR lamps do not comply.
36. Specify on the plans the make, model, type and efficiency of the space heating (or
cooling) system.
37. All hot water piping from the heating source to the kitchen fixtures must be insulated (2"
or less pipe size = 1" thick insulation; greater than 2" pipe size = 1 Yt" insulation).
Prescriptive Method requirement.
38. Residential ventilation requirements:
• Kitchens require exhaust fans (either intermittent/100 cfm or continuous/5 air
changes/hour), ducted to the exterior. Detail compliance by including a complying
exhaust fan or a ducted range hood to the exterior. Note: CFM and noise rating
("Sone") must be specified on the plans.
• All fans installed to meet the preceding requirements must be specified at a noise
rating ofa maximum 1 "Sone" (for the continuous use calculation) or 3 "Sone" (for the
intermittent use calculation).
39. Specify on the plans: "The return air plenum serving the mechanical equipment must be
fully ducted from the equipment to the conditioned space. Drop ceilings, wall cavities
and equipment platforms may not be used as plenums."
40. Specify, on the plans, that the duct insulation must be a minimum of (Prescriptive
requirement):
Climate Zones: 7 = R-4.2
41. The replacement windows in an addition or alternation must meet the U-factor and Solar
Heat Gain Coefficient (SHGC) of the component package. (Prescriptive requirement)
42. To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
City of Carlsbad 112382
11/15/2011
43. Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes a No a
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number of 858/560-1468, to perform the plan
review for your project. If you have any questions regarding these plan review items, please
contact Aaron Goodman at Esgil Corporation.
Thank you.
City of Carlsbad 112382
11/15/2011
[DO NOT PAY- THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad PLAN CHECK NO.: 112382
PREPARED BY: Aaron Goodman DATE: 11/15/2011
BUILDING ADDRESS: 2754 Auburn Ave. Set I
BUILDING OCCUPANCY: R-3 TYPE OF CONSTRUCTION: V-B
BUILDING
PORTION
AREA
( Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
SFD Addition 480 131.73 63,230
Air Conditioning
Fire Sprinklers
TOTAL VALUE 63,230
Jurisdiction Code cb By Ordinance
BIdg. Permit Fee by Ordinance I •
Plan Check Fee by Ordinance
Type of Review:
EH Repetitive Fee
Repeats
0 Complete Review
• Other
j—j Hourly
EsGff Fee
• Structural Only
Hr.
$482.13
$313.38
$269.99
Comments:
Sheet 1 of 1
macvalue.doc +
^ CITY OF
CARLSBAD
BUILDING PLANCHECK
CHECKLIST
E-36
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
ENGINEERING Plan Check for CB 11-2382 Review # 1 Date: November 9, 2011
^(z.\l }\
Project Address: 2754 Auburn Avenue APN: 167-490-02-00
Project Description: Valuation:
ENGINEERING Contact: Linda OntlverOS
Phone: 760-602-2773
Email: linda.ontiveros@carlsbadca.gov
Fax: 760-602-1052
STOP!
Please
Read
X Please make the necessary Any outstanding issues will be marked with
corrections to the plans or specifications for compliance with applicable codes
and standards. Submit corrected plans and/or specification to the Building
division for resubmittal to the Engineering Division.
Items that conform to permit requirements are marked with
ATTACHMENTS:
Engineering Application
Storm Water Form
ENGtNiERfNG
Right-of-Way Application/Info. Sheet
Reference Documents
OFFICIAL USE ONLY
HORI^ATION TO ISSUE BUILDING PiRMIT
DATE: I
Notification of Engineering APPROVAL has been sent to
via on
E-36 Page 1 of 6 REV 4/30/11
CB 11-2382
1. SITE PLAN
Review* 1
I
Provide a fully dimensioned site plan drawn to scale.
Show:
LIJ
SEE STREET PROFILE LX.i
SECTION AND PLAN r^~\
FROM IMROVEMENT r 1
DRAWINGS (ATTACHED), X]
iS/.J North arrow
[Y,J/5xisting & proposed structures
I .yd Existing street improvements
L_!f!U Propefty lines (show ail dimensions)
L/J^^ments
C2J Right-of-way width & adjacent streets
L .ZD Driveway widths
L ; Existing or proposed sewer lateral
1. _Jj Existing or proposed water service
Submit on signed approved plans:
DWG No.
Show on site plan
x,„„
LXJ
[^J Draioage patterns
Building pad surface drainage must maintain a minimum slope of one percent towards an adjoining
street or an approved drainage course.
^DD THE FOLLOWING NOTE: "Finish grade will provide a minimum positive drainage of 2% to swale
5' away from building".
] Existing & proposed slopes and topography
]size, location, alignment of existing or proposed sewer and water service(s) that serves the project.
Each unit requires a separate service; however, second dwelling units and apartment complexes are an
exception.
J Sewer and water laterals should not be located within proposed driveways, per standards.
I
Include on title sheet:
/~1 Site address
PLEASE UST THE
INFORMATION AS
SHOWN AT THE
BOTTOM OF THIS PAGE
FOR
X
I / 1 Msessor's parcel number
^^fLegai description/lot number
For commercial/industrial buildings and tenant improvement projects, include: total building
square footage with the square footage for each different use, existing sewer permits
showing square footage of different uses (manufacturing, warehouse, office, etc.) previously
approved.
PROPERTY INFORMATION FOR 2754 AUBURN AVENUE, CARLSBAD, CA
Lot/Map No.: LOT NO.: 230 / MAP NO.: 10865
Subdivision/Tract: TEMPLIN HEIGHTS UNIT 3 / CT 82.1|,
Reference No(s): DWG 217-4 / PE 2.83.53
E-36 Page 2 of 6 REV 4/30/10
CB 11-2382 Review* 1
2. DISCRETIONARY APPROVAL COMPLIANCE
/ I Project does not comply with the following engineering conditions of approval for project no.:
NA
3. DEDICATION REQUIREMENTS
Dedication for all street rights-of-way adjacent to the building site and any stomn drain or
utility easements on the building site is required for all new buildings and for remodels with a
value at or exceeding $ 20.000.00 , pursuant to Carlsbad Municipal Code Section 18.40.030.
For single family residence, easement dedication will be completed by the City of Carlsbad,
cost $605.00.
./J Dedication required as follows:
NA
4. IMPROVEMENT REQUIREMENTS
All needed public improvements upon and adjacent to the building site must be constructed
at time of building construction whenever the value of the construction exceeds
$100.000.00. pursuant to Carlsbad Municipal Code Section 18.40.040.
Public improvements required as follows:
NA
Construction of the public Improvements must be deferred pursuant to Carisbad
IVIunicipal Code Section 18.40. Please submit a recent property title report or current grant
deed on the property and processing fee of $ 441 00 so we may prepare the necessary
Neighborhood Improvement Agreement. This agreement must be signed, notarized and
approved by the city prior to issuance of a building permit.
VJ Future public improvements required as follows:
NA
E-36 Page 3 of 6
CBl 1-2382
Review # 1
5. GRADING PERMIT REQUIREMENTS
The conditions that require a grading permit are found in Section 15.16 of the Municipal
Code.
Jinadequate infonnation available on site plan to make a determination on grading
requirements. Include accurate grading quantities in cubic yards (cut, fill, import, export and
remedial). This information must be Included on the plans. If no grading is proposed
write: "NO GRADING"
Grading Permit required. NOTE: The grading permit must be issued and rough grading
approval obtained prior to issuance of a building permit.
Graded Pad Certification required. (Note: Pad certification may be required even if a grading
permit is not required.) All required documentation must be provided to your Engineering
Construction Inspector per the attached list. The inspector will then
provide the engineering counter with a release for the building permit.
I / 1 No grading permit required.
I Minor Grading Pennit required. See attached marked-up submittal checklist for project-
specific requirements.
6. MISCELLANEOUS PERMITS
V I RIGHT-OF-WAY PERMIT is required to do work in city right-of-way and/or private work
adjacent to the public right-of-way. Types of work include, but are not limited to: street
improvements, tree trimming, driveway construction, tying into public storni drain, sewer and
water utilities.
I 1 Right-of-way permit required for:
E-36 Page 4 of 6 REV 6/30/10
CB 11-2382 Review* 1
t/
STORM WATER
Construction Compliance
I r"/l Project Threat Assessment Form complete.
I r I Enclosed Project Threat Assessment Form incomplete.
j/j Requires Tier 1 Storm Water Pollution Prevention Plan. Please complete attached fonn
and return (SW 11-423 )
Requires Tier 2 Stomn Water Pollution Prevention Plan. Requires submittal of Tier 2
SWPPP, payment of processing fee and review by city.
Post-Development (SUSMP) Compliance
IF ANY OF THE LOW IMPACT !
DEVELOPMENT STRATEGIES
EXIST FOR THIS SITE, PLEASE
MAKE A NOTE OF IT.
FOR MORE INFORMATION
REGARDING ANY OF THE
! STRATEGIES LISTED, PLEASE
1 VISIT THE LINK BELOW AND
I DOWNLOAD BROCHURE:
Storm water Low Impact
Development (LID)
"/J Storm Water Standards Questionnaire complete.
/
Storm Water Standards Questionnaire incomplete. Please make the corrections, re-sign
the questionnaire and resubmit with next submittal.
Project is subject to Standard Stonn Water Requirements. See city Standard Urban
Storm Water Management Plan (SUSMP) for reference.
httD://www.carlsbadca.aov/business/buildina/Documents/EnaStandsw-stds-vol4-ch2.pdf
Project needs to incorporate low impact development strategies throughout in one or
more of the following ways:
r~] Rainwater harvesting (rain barrels or cistern)
Vegetated Roof
I I Bio-retentions cell/rain garden
I I Pervious pavement/pavers
CIJ Flow-through planter/vegetated or rock drip line
Q]] V^etated swales or rock infiltration swales
0Downspouts disconnect and discharge over landscape
http://vyww.carlsbadca.gov/busines8/building/permitting-process/Pages/Engineering_Applications.aspx
E-36 Page 5 of 6 REV 4/30/10
CB 11-2382 Review* 1
9. WATER METER REVIEW
. Domestic (potable) Use
Where a residential unit is required to have an automatic fire
extinguishing system, the minimum meter size shall be a 1" meter.
NOTE: the connection fee, SDCWA system capacity charge and the
water treatment capacity charge will be based on the size of the meter
necessary to meet the water use requirements.
For residential units the minimum size meter shall be 5/8", except where
the residential unit is larger than 3,500 square feet or on a lot larger than
one quarter (1/4) acre where the meter size shall be
8. FEES
Required fees have been entered in building permit.
Drainage fee applicable
Added square feet
Added square footage in last two years?
Permit No.
Permit No.
Project built after 1980
Impervious surface > 50%
Impact unconstructed facility
Fire sprinklers required | |yes
Upgrade yes
No fees required
yes no
I lyes I Ino
I I yes Q no
•J ,
yes I ^no
[^no (Is addition over 150' from center line)
•no
10. Additional Comments
E-36 Page 6 of 6 REV 4/30/10
I
csi
C/l
^ ^ s « s s
oil
<o (d w a. a. a.
Sl • •
• •
PLANNING DEPARTMENT
BUILDING PLAN CHECK REVIEW CHECKLIST
Plan Check No. CB 11-2382 Address 2754 Auburn Avenue
Planner Chris Sexton Phone (760) 602-4624
APN: 167-490-02
Type of Project & Use: addition Net Project Density: 1.0 DU/AC
Zoning; RJ. General Plan: RLM Facilities Management Zone: 2
CFD (in/out) #_Date of participation: Remaining net dev acres:.
Circle One (For non-residential development: Type of land used created by this permit:
J
Legend: ^ Item Complet4 • kem Incomplete - Needs your action
Environmental Review RequiredT^ YES • NO • TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
Discretionary Action Required: YES • NO • TYPE
APPROVAL/RESO. NO. DATE
PROJECT NO.
OTHER RELATED CASES:
Compiiance with conditions or approval? If not, state conditions which require action.
Conditions of Approval:
n n Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES O NO D
CA Coastal Commission Authority? YES D NO Q
If California Coastal Commission Authority: Contact them at - 7575 Metropolitan Drive, Suite 103,
San Diego, CA 92108-4402; (619) 767-2370
Determine status (Coastal Permit Required or Exempt):
• • Habitat IVIanagement Plan
Data Entry Completed? YES • NO •
if property has Habitat Type identified in Table 11 of HMP, complete HMP Permit application and
assess fees in Permits Plus
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, HMP Fees, Enter Acres of Habitat Type
impacted/taken, UPDATE!)
• • Inclusionary Housing Fee required: YES • NO Q
(Effective date of Inclusionary Housing Ordinance - May 21,1993.)
Data Entry Completed? YES • NO •
(A/P/Ds, Activity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct Housing Y/N,
Enter Fee, UPDATE!)
• • Housing Tracking Form (form P-20) completed: YES • NOD N/AD
Rev 6/11
Site Plan:
• • Provide a fully dimensional site plan drawn to scale. Show: North arrow, property lines, easements,
existing and proposed structures, streets, existing street improvements, right-of-way width,
dimensional setbacks and existing topographical lines (including all side and rear yard slopes).
Provide legal description of property and assessor's parcel number.
Policy 44 - Neighborhood Architectural Design Guidelines
lEl • • 1. Applicability: YES • NO •
• • • 2. Project complies: YES • NOQ
• •
• •
Zoning:
1. Setbacks:
Front:
Interior Side:
Street Side:
Rear:
Top of slope:
Required 201 Shown 20'
Required r Shown 7'6"
Required Shown.
Required 14: Shown 31'
Required Shown.
2. Accessory structure setbacks:
Front: Required.
Interior Side: Required.
Street Side: Required,
Rear: Required.
Structure separation: Required.
Shown
Shown
Shown
Shown.
Shown
• • 3. Lot Coverage: Required >40% Shown 34%
• • 4. Height: Required >30: Shown >301
• •
• • •
5. Parking: Spaces Required 2 Shown 2
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required Shown
Additional Comments
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTE
Rev 6/11