HomeMy WebLinkAbout2775 CARLSBAD BLVD; ; CB152742; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
10-16-2015 Commercial/Industrial Permit Permit No: CB152742
Building Inspection Request Line (760) 602-2725
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
Project Title:
Applicant:
2775 CARLSBAD BL CBAD
COMMIND Sub Type: COMM
2031430700 Lot#: 0
$33,423.00 Construction Type: 58
Reference#
ST.MICHAEL'S: 290 SF EXPANSION
TO EXIST NARTHEX.
Owner:
Status: ISSUED
Applied: 08/21/2015
Entered By: JMA
Plan Approved: 10/16/2015
Issued: 10/16/2015
Inspect Area
Plan Check #:
OCTAVI0/02ARCHITECTURE
STE 8
ST MICHAELS-BY-THE-SEA EPISCOPAL CHURCH
1089 N PALM CANYON DR
PALM SPRINGS CA 92262-4416
760-778-8165
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Building Permit Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge.Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'l Pot. Water Con. Fee
Reel. Water Con. Fee
Green Bldg Stands (SB1473) Fee
Fire Expedidted Plan Review
$303.73
$0.00
$212.61
$215.10
$0.00
$9.36
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$2.00
$0.00
P 0 BOX 127
CARLSBAD CA 92018
Meter Size
Add'l Reel. Water Con. Fee
Meter Fee
SDCWA Fee
CFD Payoff Fee
PFF (3105540)
PFF (4305540)
License Tax (31 04193)
License Tax (4304193)
Traffic Impact Fee (3105541)
Traffic Impact Fee (4305541)
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Master Drainage Fee
Sewer Fee
Redev Parking Fee
Additional Fees
HMP Fee
Green Bldg Standards Plan Chk
TOTAL PERMIT FEES
Total Fees: $855.70 Total Payments To Date: $855.70 Balance Due:
Inspector:
Fl NAL A~PR.O_V ~~
Date: ;;l. A (, · I b Clearance:
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$49.00
$63.90
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$855.70
$0.00
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
10-01-2015
Storm Water Pollution Prevention Plan {SWPPP) Permit
Permit No:SW150330
Job Address:
Permit Type:
Parcel No:
Reference #:
CB#:
Project Title:
Applicant:
OCTAVIO
760-778-8165
Emergency Contact:
ERNIE MELVIN
209-985-9991
2775 CARLSBAD BL CBAD
SWPPP
2031430700
CB152742
ST. MICHAEL'S:290 SF ADD TO
NARTHEX
SWPPP Plan Check
SWPPP Inspections
Additional Fees
TOTAL PERMIT FEES
Lot#: 0
Owner:
Status:
Applied:
Entered By:
Issued:
Inspect Area:
ISSUED
08/21/2015
JMA
10/01/2015
Tier: 1
Priority: L
ST MICHAELS-BY-THE-SEA EPISCOPAL CHURCH
P 0 BOX 127
CARLSBAD CA 92018
$48.00
$58.00
$0.00
$106.00
Total Fees: $106.00 Total Payments To Date: $106.00 Balance Due:
L
J . ;t (, . li~· _-rl. '·· GE ...... ------·-··--~·-~··· .-.--,~------~..--~ -=-·-·
{i ~ "'"" "i! ""["'f: f)'": .;)!GNA! I.Pf-.,t .. -.. -·····--·~--·--···--·~··-.. ········~-----
$0.00
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: PLANNING !ENGINEERING
City of
Carlsbad
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax: 760-602-8558
email: building@carlsbadca.gov
www.carlsbadca.gov
SUITE#/SPACE#/UNIT# JOB ADDRESS 2775 CARLSBAD BLVD. CARLSBAD CA 92208
!]BUILDING
Est. Value $108,714.00
Plan Ck. Deposit
Date 08.20.2015 SWPPP
APN
203 143 070 0
#BEDROOMS #BATHROOMS TENANT BUSINESS NAME OCC. GROUP
ST MICHAEL'S BY THE SEA A-3
THE PROPOSED PROJECT CONSIST OF BUILDING A NEW 290 S.F. NARTHEX EXPANSION TO THE EXISTING 4,125 S.F.
ST. MICHAEL'S BY THE SEA CHURCH. THE EXISTING UNCONDITIONED NARTHEX AREA IS 120 S.F. THE NEW UNCONDITIONED NARTHEX AREA WILL BE
410 S.F. AFTER COMPLETION.
PATIOS (SF)
NIA
FIREPLACE
YEsO
AIR CONDITIONING
N0!1Jl YES 0No!Z]
FIRE SPRINKLERS
YES0No!Z]
APPLICANT NAME-FR. DORAN STAMBAUGH, RECTOR
ADDRESS ADDRESS
2775 CARLSBAD BLVD.
CITY CITY STATE ZIP
CARLSBAD CA 92008
PHONE PHONE FAX 760.729.8901 NIA
EMAIL
frdoran@stmichaelsbythesea.org
1089 N. PALM CANYON DRIVE SUITE B
CIT STATE ZIP
PALM SPRINGS CA 92262
FAX
760.778.8165 760.406.7946
EMAIL
Octavio@o2arch.com I Lance@o2arch.com
STATE UC. #
LICENSED ARCHITECT I CA C-26815
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law !Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}).
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
0 I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
[2!1 have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. J-£w C~ 00~ ~ Gj Policy N~~-~---Expiration Date ..J.~,/'G.)..6"""_ __ ~-
This section need not be completed if the permit is for one hundred dollars ($1 00) or less. ' 0 Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, as provided for in of the Labor code, interest and attorney's fees.
2S CONTRACTOR SIGNATURE
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
D
D
D
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. DYes 0No
2. I (have I have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address I phone I contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address I phone I type of work):
2S PROPERTY OWNER SIGNATURE 0AGENT DATE
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Yes ./ No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? Yes ./ No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes ./ No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i} Civil Code}.
Lender's Name Lender's Address
I certify that I have read the application and state that the above information is correct and thatthe information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void ff the building or work authorized by such permit is not commenced within
180 days from the date of such permit or if ilding or work authorized by s permit is suspended or abandoned at any time after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code).
~APPLICANT'S SIGNATURE DATE
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602-8560, Email building@carlsbadca.gov or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008.
DELIVERY OPTIONS
PICK UP: CONTACT (Listed above)
CONTRACTOR (On Pg. 1)
MAIL TO: CONTACT (Listed above)
CONTRACTOR (On Pg. 1)
MAIL/ FAX TO OTHER:
J!S APPLICANT'S SIGNATURE
FAX
OCCUPANT (Listed above)
OCCUPANT (Listed above)
CO#: (Office Use Only)
CA
ASSOCIATED CB#
NO CHANGE IN USE j NO CONSTRUCTION
CHANGE OF USE j NO CONSTRUCTION
DATE
Inspection List
Permit#: CB152742 Type: COMMIND COMM
Date ___ l_~pecti~n Item Inspector Act ---
02/26/2016 89 Final Combo Rl
02/26/2016 89 Final Combo PO AP
01/05/2016 17 Interior Lath/Drywall PO AP
12/04/2015 84 Rough Combo PO AP
11/20/2015 17 Interior Lath/Drywall PO PA
11/19/2015 24 Rough/T opout PO AP
11/18/2015 84 Rough Combo PO NR
1 0/29/2015 11 Ftg/F oundation/Piers PO AP
1 0/28/2015 11 Ftg/Foundation/Piers PO NR
10/23/2015 11 Ftg/Foundation/Piers PO AP
07/23/2015 24 Rough/T opout PO AP
Monday, February 29, 2016
ST.MICHAEL'S: 290 SF EXPANSION
TO EXIST NARTHEX.
Comments
EMAILING CARD/FIRE@ 9:00
Page 1 of 1
"'~" ~ Cqy OF
CARLSBAD
Bundingoivision INSPECTION RECORD ~ IIIISPECTJON RECORD CARD WITH APPROVED
PLANs IVIUST BE KEPT ON THE JOB
1i:J CALL BEFORE 3:30pm FOR NEXT WORK DAY INSPECTION
1i:J FOR BUILDING INSPECTION CALL: 760-602-2725
OR GO TO: .WWW.Carlsbadca.gov/Building AND CLICK ON -Request Inspection"
DATE: tQ-\ (o-\b
CB152742 2775 CARLSBAD BL
ST. MICHAEL'S: 290 SF EXPANSION
TO EXIST NARTHEX.
COMMIND COMM
Lot#: OCTAVI0/02ARCHITECTURE
Required Prior to Requesting Building Final If Checked YES
Planning/Landscape 76()-944-8463 Allow 48 hours
CM&I (Engineering Inspections) 7 6D-438-3891 Call before 2 pm
Fire Prevention 7 60-602-4660 Allow 48 hours
~
Q)
s::::
s:::: co
0 en
E co
(.)
~ .c
""C
Q)
s::::
s:::: co
0 en
DATE: 10/8/15
JURISDICTION: Carlsbad
PLAN CHECK NO.: 15-2742
EsGil Corporation
In (}!artnersliip witli government for CBui{aing Safety
SET: II
PROJECT ADDRESS: 2775 Carlsbad Blvd.
PROJECT NAME: Replace Narthex forSt Michaels Church
CJ APPLICANT
CJ JURIS.
CJ PLAN REVIEWER
CJ FILE
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
~ The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted: (by:
Telephone#:
) Email:
Mail Telephone Fax In Person
REMARKS: The notes clouded in red on sheet E1.1 of the approved plans from EsGil
must be made to the city set of plans to make a 2"d set of approved plans.
By: Chuck Mendenhall
EsGil Corporation
D GA D EJ D MB D PC
Enclosures:
10/1/15
DATE: 9/3/15
JURISDICTION: Carlsbad
PLAN CHECK NO.: 15-2742
EsGil Corporation
In !Partners nip witfi government for <Bui{aing Safety
SET: I
PROJECT ADDRESS: 2775 Carlsbad Blvd.
PROJECT NAME: Replace Narthex forSt Michaels Church
~PLICANT
~~~RIS.
D PLAN REVIEWER
D FILE
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
I:8J The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
I:8J The applicant's copy of the check list has been sent to:
Lance O'Connell, o2 Architecture
e-mail
D EsGil Corporation staff did not advise the applicant that the plan check has been completed.
I:8J EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Lance O'Connell Telephone#: (760) 778-8165
Date contacted:~ i'3 (by~ Email: Otavio@o2arch.com or Lance@o2arch,com
~ail ~lephone Fax In Person
D REMARKS:
By: Chuck Mendenhall
EsGil Corporation
0 GA rgj EJ 0 M B 0 PC
Enclosures:
8/25/15
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
Ca;rlsbad 15-2742
9/3/15
PLAN REVIEW CORRECTION LIST
COMMERCIAL
PLAN CHECK NO.: 15-2742 JURISDICTION: Carlsbad
OCCUPANCY: A-3 USE: church
TYPE OF CONSTRUCTION: unknown ACTUAL AREA: 290 sf
ALLOWABLE FLOOR AREA: no change STORIES: one
SPRINKLERS?: Yes
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 9/3/15
FOREWORD (PLEASE READ):
HEIGHT: 9ft add'n only
OCCUPANT LOAD: 35 ( Narthex Only
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 8/25/15
PLAN REVIEWER: Chuck Me:ndenhall
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2013 CBC, which adopts the 2012 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 1 05.4 of
the 2012 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad 15-2742
9/3/15
Please make all corrections, as requested in the correction list. Submit FOUR new complete
sets of plans for commercial/industrial projects (THREE sets of plans for residential projects).
For expeditious processing, corrected sets can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will
route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire
Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining
sets of plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil Corporation is complete.
4. The cover sheet of the plans, sheet A0.1, indicates occupancy type is 'C'( religious). This is not
consistent with the code. The addition to the church is an A-3 occupancy.
5. The fire sprinkler notation on sheet AO.O under General Project Information indicates sprinkler
system NFPA 13D. this is a residential sprinkler system. The code requires sprinklers com pOly
with NFPA 13.
6. The double exit doors '1' shown on the floor plans must be equipped with panic hardware.
7. Each sheet of the structural plans must be stamped and signed by the responsible design
engineer.
8. The loading listed for new beam 100 is listed as DL=646# and LL=348#. See page 4 of the
calc's. these are not the loads use for the ENERCALC input on page 7 of the calc's.
9. The lateral support at grid line 'A' as shown on sheet S1.1 is based on cantilevered columns
HSS5X5X1/4. The lateral design along this line on page 15 of the calc's indicates" See
Printout". What printout? The design of the columns using ENERCALC on page 20 of the calc's
includes only vertical LL & DL. There is no lateral component applied to the column.
10. The design of the column base plate is based on a plate 21" X21" X 1". See page 23 of the
design calc's. detail 9/S1.2 referenced on the foundation plan lists the base plates as %"X
12X12. Plans must be consistent with the design.
11. How did you arrive at the lateral load applied to the top of the HSS steel collumns as listed on
page 23 of the calc's as 1.97K. where in the lateral design analysis do I find how you arrived at
this load?
12. The design of the spread footing supporting the HSS steel columns must include the lateral
moment applied at the base of the steel column. The design input on page 31 of the calc's
includes only vertical LL & DL.
NOTE: A complete structural review of the plans will be made after the items above have been
addressed and the plans are signed by the design engineer.
' Carlsbad 15-2742
9/3/15
DISABLED ACCESS REVIEW LIST
DEPARTMENT OF STATE ARCHITECT
TITLE 24
13. When alterations, structural repairs or additions are made to an existing building, that building, or
portion of the building affected, is required to comply with all of the followin!~ requirements, per
Section 11 B-202.4:
• The area of specific alteration, repair or addition must comply as "new" construction.
• A primary entrance to the building and the primary path of travel to the altered area, must
be shown to comply with all accessibility features.
• The path of travel shall include the existing parking.
• Existing toilet and bathing facilities that serve the remodeled area must be shown to comply
with all accessibility features.
Show on the plans the path of travel to the rerst rooms serving the area c,f remodel. Show
that these rest rooms comply with the following:
14. Show that passageways leading to sanitary facilities have required clear access widths. Show
that all doorways have:
a) ~32" clear opening.
b) A clear area:
i) ~60" in the direction of the door swing.
ii) ~44" away from the direction of door swing.
15. Note that the doorways leading to sanitary facilities shall be identified, per Section 11 B-
703.7.2.6, as follows:
a) An equilateral triangle %" thick with edges 12" long and a vortex pointing upward at men's
rest rooms.
b) A circle%" thick, 12" in diameter at women's rest rooms.
c) A 12" diameter circle with a triangle superimposed on the circle and within the 12"
diameter at unisex rest rooms.
d) The required symbols shall be centered on the door at a height of 5B"-60".
e) Braille signage shall also be located on the wall adjacent to the latch outside of the
doorways leading to the sanitary facilities.
16. Show that the accessible rest room is to be provided with a 60" minimum di1ameter clear space
measured from the floor to a height of 27 inches. Section 11 B-304.3. NOTE: Doors (other
than the door to the accessible toilet compartment) in any position may encroach into this space
by not more than 12 inches, per Section 11 B-603.2.3.
17. Show a sufficient space in the toilet room for a wheelchair to enter the room and close the door,
per Section 11 B-603.2. The space is required to be:
Carlsbad 15-2742
9/3/15
a) ;:::60" diameter.
b) AT-shaped space as shown in Figure 11 B-304.3.2.
c) Doors are not permitted to encroach into this space by more than 12 inches.
18. Show that the water closet is located in a space which provides:
a) A clear space at the water closet in compliance with Section 11 B-604.3.2 (this prohibits
any fixtures from encroaching into the clear space at the rear wall).
b) A clear space in front of the water closet measuring 60" wide by 48" in front. Section 11 B-
604.3.1. See the following figures.
i) Please notice that the 28" clearance required in the previous code (between the
water closet and the lavatory) has been changed to a 60" clearance as shown in
the figure.
/
\
\
f
I
Carlsbad 15-2742
9/3/15
.......,~~~··C::W!A:FtOORSPI'ICE
~~
MtliNW~ItfiSF'AtE
• (a) CI.URANCES AT WAfeR CLOSiT
19. Doors may swing into the restroom as long as there is a clearance of at least 30" x 48" beyond
the swing of the door. Section 11 B-603.2.3.
• RESTROOM FIXTURES AND ACCESSORIES
20. Show, or note, on the plans that the accessible water closets meet the following requirements,
per Sections 11 B-604.4 and 11 B-604.6:
a) The seat is to be ~17" but ~19" in height.
b) The controls for flush valves shall be:
i) Mounted on the side of the toilet area.
ii) Be ~44" above the floor.
21. Show, or note, on the plans that accessible urinals meet the following requirements, per Section
11 B-605:
a) The rim of at least one urinal shall:
i) Project at least 13% "from the wall.
· ii) Be ~17" above the floor.
b) The control mechanism is to be located ~44" above the floor.
c) ~30" x 48" clear floor space is provided in front of the accessible urinal.
i) 36"x48" clear floor space when the urinal is located in an alcove that exceeds 24"
in depth, per section 11 B-305.7.1.
22. Show that accessible lavatories comply with the following, per Section 11 B-·606:
a) ~30" x 48" clear space is provided in front for forward approach. The clear space may
include knee and toe space beneath the fixture.
b) When lavatories are adjacent to a side wall or partition, there shall be a minimum of 18" to
the center line of the fixture to the wall.
c) The counter top is ~34" maximum above the floor.
d) ~29" high, reducing to 27" at a point located 8" back from the front edge.
Carlsbad 15-2742
9/3/15
e) ;:::9" high x 30" wide and 17" deep at the bottom.
f) Hot water pipes and drain lines are insulated.
23. Show that grab bars comply with the following, per Sections 11 B-604.5 and 11 B-609:
a) Grab bars shall be located on each side or one side and the back of the water closet stall
or compartment.
b) They shall be securely attached 33" -36" above the floor, and parallel.
c) Grab bars at the side shall be located:
i) Be ;:::42" long with the front end positioned 24" in front of the stool.
ii) Total length of bars at the back shall be ;:::36".
d) The diameter, or width, of the grab bar gripping surface is ;:::1 %" but :52", or the shape
shall provide an equivalent gripping surface.
e) If mounted adjacent to a wall, the space between the wall and the grab bar shall be 1 Y2".
END OF ARCHITECTURAL & STRUCTURAL REVIEW
To speed up the review process, note on this list (or a copy) where each correction item has
been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review items,
please contact Chuck Mendenhall at Esgil Corporation. Thank you.
PLUMBING, MECHANICAL, ELECTRICAL, and ENERGY COMMENTS
PLAN REVIEWER: Eric Jensen
ELECTRICAL (2013 CALIFORNIA ELECTRICAL CODE)
1. Include on the electrical plan sheet E.1 0 emergency light fixtures powered from two sources.
Emergency light fixtures must be located in the Narthex and just outside tlhe double exit doors.
2. Include on sheet E1.0 the exit sign above the double exit doors as shown architectural sheet
A4.0.
ENERGY (2013 CALIFORNIA BUILDING ENERGY STANDARDS)
4. Please provide the addition envelope energy design.
5. All exterior lighting must be controlled by a photocell and an automatic scheduling control
device. EM 130.2(c)
6. Shut-Off Controls: Each floor, each space (not exceeding 5,000 square feet), and each type
(general, display, and ornamental) of lighting shall be individually capable of being
automatically shut-off when the building is unoccupied. Include the control design. (A
percentage of egress lighting is now included in the shut-off requirement). ES
130.1(c)
Carlsbad 15-2742
9/3/15
Note: If you have any questions regarding this Electrical, Plumbing, Mechanical, and Energy plan
review list please contact Eric Jensen at (858) 560-1468. To speed the review process, note on this
list (or a copy) where the corrected items have been addressed on the plans.
' Carlsbad 15-2742
9/3/15
[DO NOT PAY-THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 15-2742
PREPARED BY: Chuck Mendenhall DATE: 9/3/15
BUILDING ADDRESS: 2775 Carlsbad Blvd.
BUILDING OCCUPANCY: A-3
BUILDING AREA Valuation Reg. VALUE ($)
PORTION ( Sq. Ft.) Multiplier Mod.
Narthex 290 City Est 108,714
Air Conditioning
Fire Sprinklers
TOTAL VALUE 108,714
Jurisdiction Code cb By Ordinance
Bldg. Permit Fee by Ordinance $658.011
Plan Check Fee by Ordinance $427.711
Type of Review: Complete Review D Structural Only
0Repetitive Fee
..,... Repeats
D Other
0 Hourly
EsGil fee
1------tl Hr. @ • $368.491
Comments: In addition to the above fee, an additionalfee of $43 is due. (T/2 hour@
$86/hr.) for the CaiGreen review.
Sheet 1 of 1
macvalue.doc +
City of
Carlsbad
PLAN CHECK
REVIEW
TRANSMITTAL
DATE: PROJECT NAME: MICHAELS THE SEA
PLAN CHECK NO: 1 SET#: 1 ADDRESS:
VALUATION: SCOPE OF WORK:
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www .carlsbadca.gov
PROJECT ID:CB152742
DR APN: """'"""" .... """'
This plan check review is complete and has been APPROVED by:
D
LAND DEVELOPMENT ENGINEERING DIVISION
Final Inspection by Construction Management & Inspection Division is required: Yes No
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to:
Linda Ontiveros
760-602-2773
ValRay Nelson
760-602-27 41
VaiRay.Marshall@carlsbadca.gov
Remarks:
ST MICHAELS BY THE SEA ADDITION PlAN CHECK NO# 1
1. SITE PLAN
Provide a fully dimensioned site plan drawn to scale. Show:
, North arrow Driveway widths
Existing & proposed structures
Existing street improvements
Property lines (show all dimensions)
· Existing or proposed sewer lateral
Existing or proposed water service
Submit on signed approved plans:
1 Easements DWG No.
Right-of-way width & adjacent streets
Show on site plan:
I Drainage patterns and proposed site elevations. Show all high points.
:Building pad surface drainage must maintain a minimum slope of one percent towards an adjoining
•• 1 street or an approved drainage course.
ADD THE FOLLOWING NOTE: "Finish grade will provide a minimum positive drainage of 2% to swale
5' away from building".
1 Existing & proposed slopes and topography
1 Size, location, alignment of existing or proposed sewer and water service(s) that serves the project
Each unit requires a separate service; however, second dwelling units and apartment complexes are an
exception.
Sewer and water laterals should not be located within proposed driveways, per standards.
Include on title sheet:
Site address
Assessor's parcel number
1 Legal description/lot number
For commercial/industrial buildings and tenant improvement projects, include: total building
square footage with the square footage for each different use, existing sewer permits
showing square footage of different uses (manufacturing, warehouse, office, etc.) previously
approved.
Show all existing use of SF and new proposed use of SF.
Example:
Tenant improvement for 3500 SF of warehouse to 3500 SF of office.
Lot/Map No.: BLK 6 OF MAP 775
Subdivision/Tract:
Reference No(s):
E-36 Page 2 of 6 REV 6/01112
ST MICHAElS BY THE SEA ADDITION PLAN CHECK NO# 1
E-36
2. DISCRETIONARY APPROVAL COMPLIANCE
• Project does not comply with the following engineering conditions of approval for project no.:
3. DEDICATION REQUIREMENTS
• Dedication for all street rights-of-way adjacent to the building site and any storm drain or
utility easements on the building site is required for all new buildings and for remodels with a
value at or exceeding $ 24 000.00 , pursuant to Carlsbad Municipal Code Section 18.40.030.
Dedication required as follows:
4. IMPROVEMENT REQUIREMENTS
All needed public improvements upon and adjacent to the building site must be constructed
at time of building construction whenever the value of the construction exceeds
$120,000.00 , pursuant to Carlsbad Municipal Code Section 18.40.040.
Public improvements required as follows:
· Construction of the public improvements must be deferred pursuant to Carlsbad
Municipal Code Section 18.40. Please submit a recent property title report or current grant
deed on the property and processing fee, so we may prepare the necessary Neighborhood
Improvement Agreement. This agreement must be signed, notarized and
approved by the city prior to issuance of a building permit.
Future public improvements required as follows:
Page 3 of 6 REV 6/01112
ST MICHAELS BY THE SEA ADDITION PlAN CHECK NO# 1
E-36
5. GRADING PERMIT REQUIREMENTS
The conditions that require a grading permit are found in Section 15.16 of the Municipal
Code.
Inadequate information available on site plan to make a determination on grading
requirements. Include accurate grading quantities in cubic yards (cut, fill, import, export and
remedial). This information must be included on the plans. If no grading is proposed
write: "NO GRADING"
Grading Permit required. NOTE: The grading permit must be issued and rough grading
approval obtained prior to issuance of a building permit.
i Graded Pad Certification required. (Note: Pad certification may be required even if a grading
permit is not required.) All required documentation must be provided to your Engineering
Construction Inspector The inspector will then
provide the engineering counter with a release for the building permit.
No grading permit required.
Minor Grading Permit required. See additional comments for project-specific requirements.
6. MISCELLANEOUS PERMITS
:RIGHT-OF-WAY PERMIT is required to do work in city right-of-way and/or private work
·adjacent to the public right-of-way. Types of work include, but are not limited to: street
improvements, tree trimming, driveway construction, tying into public storm drain, sewer and
water utilities.
Right-of-way permit required for:
Page 4 of 6 REV 6/01/12
ST MICHAElS BY THE SEA ADDITION PlAN CHECK NO#
E-36
7. STORM WATER
Construction Compliance
1 Project Threat Assessment Form complete.
Enclosed Project Threat Assessment Form incomplete.
Requires Tier 1 Storm Water Pollution Prevention Plan (E-29). Please complete attached form
and return (SW )
Requires Tier 2 Storm Water Pollution Prevention Plan. Requires submittal of Tier 2
SWPPP, payment of processing fee and review by city.
Post-Development (SUSMP) Compliance
Storm Water Standards Questionnaire.
· Project is subject to Standard Storm Water Requirements. See city Standard Urban
Storm Water Management Plan (SUSMP) for reference.
1 Indicate areas of impervious surfaces (patios,walkway, etc. ) and pervious areas (landscaping).
Project needs to incorporate low impact development strategie~s throughout in one or
more of the following ways:
1 Rainwater harvesting (rain barrels or cistern)
Vegetated Roof
· Bio-retentions cell/rain garden
· Pervious pavement/pavers
Flow-through planter/vegetated or rock drip line
' Vegetated swales or rock infiltration swales
Downspouts disconnect and discharge over landscape
. Other:
Page 5 of 6 REV 6/01112
ST MICHAElS BY THE SEA ADDITION PLAN CHECK NO # 1
Attachments:
E-36
8. WATER METER REVIEW
9. FEES
Domestic (potable) Use
What size meter is required?
Where a residential unit is required to have an automatic fire
extinguishing system, the minimum meter size shall be a 1" meter.
NOTE: the connection fee, SDCWA system capacity charge and the
water treatment capacity charge will be based on the size of the meter
necessary to meet the water use requirements.
For residential units the minimum size meter shall be 5/8", e~xcept where
the residential unit is larger than 3,500 square feet or on a lot larger than
one quarter (1/4) acre where the meter size shall be%".
Required fees have been entered in building permit.
Drainage fee applicable
Added square feet
Added square footage in last two years?
Permit No.
Permit No.
Project built after 1980
Impervious surface > 50%
Impact unconstructed facility
yes
yes
yes
yes
:no
Fire sprinklers required
Upgrade
No fees required
:yes
yes
no (is addition over 150' from center line)
10. ADDITIONAL COMMENTS
Engineering Application Storm Water Form Right-of-Way Application/Info. Reference Documents
Page 6 of 6 REV 6/01/12
Fee Calculation Worksheet
ENGINEERING DIVISION
Prepared by: Date: GEO DATA: LFMZ: I B&T:
Address: Bldg. Permit#:
Fees Update by: Date: Fees Update by: Date:
EDU CALCULATIONS: List types and square footages for all uses.
Types of Use: Sq.Ft./Units
Types of Use:
Types of Use:
Types of Use:
Sq.Ft.!Units
Sq.Ft./Units
Sq.Ft./Units
ADT CALCULATIONS: List types and square footages for all uses.
EDU's:
EDU's:
EDU's:
EDU's:
Types of Use: Sq.Ft./Units ADT's:
Types of Use:
Types of Use:
Types of Use:
FEES REQUIRED:
Sq.Ft.!Units
Sq.Ft./Units
Sq.Ft./Units
ADT's:
ADT's:
ADT's:
Within CFD:. 'YES (no bridge & thoroughfare fee in District #1, reduces Traffic Impact Fee) NO
1. PARK-IN-LIEU FEE: • iNW QUADRANT • NE QUADRANT JSE QUADRANT L~~.W QUADRANT
ADT'S/UNITS: I X FEE/ADT: I =$
2.TRAFFIC IMPACT FEE:
ADT'S/UNITS: IX FEE/ADT: I=$
3. BRIDGE & THOROUGHFARE FEE: DIST. #1 DIST.#2 ,DIST.#3
(USE SANDAG)ADT'S/UNITS IX FEE/ADT: I=$
4. FACILITIES MANAGEMENT FEE ZONE:
ADT'S/UNITS: IX FEE/SQ. FT./UNIT: I=$
5. SEWER FEE
EDU's IX FEE/EDU: I=$
BENEFIT AREA:
EDU's IX FEE/EDU: I=$
6. DRAINAGE FEES: PLDA: •· ._.HIGH MEDIUM :Low
ACRES: IX FEE/AC: I=$
7. POTABLE WATER FEES:
UNITS CODE CONN. FEE METER FEE SDCWA FEE TOTAL
W CITY OF
CARLSBAD
STORM WATER COMPLIANCE FORM
TIER 1 CONSTRUCTION SWPPP
E-29
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov·
STORM WATER COMPLIANCE CERTIFICATE
v' My project is not in a category of permit types exempt from the Construction
SWPPP requirements
v' My project is not located inside or within 200 feet of an environmentally
sensitive area with a significant potential for contributing pollutants to nearby
receiving waters by way of storm water runoff or non-storm water
discharge(s).
v' My project does not require a grading plan pursuant to the Carlsbad
Grading Ordinance (Chapter 15.16 of the Carlsbad Municipal Code)
v' My project will not result in 2,500 square feet or more of soils disturbance
including any associated construction staging, stockpiling, pavement
removal, equipment storage, refueling and maintenance areas that meets
one or more of the additional following criteria:
• located within 200 feet of an environmentally sensitive area or the
Pacific Ocean; and/or,
• disturbed area is located on a slope with a grade at or exceeding 5
horizontal to 1 vertical; and/or
• disturbed area is located along or within 30 feet of a storm drain inlet, an
open drainage channel or watercourse; and/or
• construction will be initiated during the rainy season or will extend into
the rainy season (Oct. 1 through April 30).
I CERTIFY TO THE BEST OF MY KNOWLEDGE THAT ALL OF THE ABOVE
CHECKED STATEMENTS ARE TRUE AND CORRECT. I AM SUBMITTING
FOR CITY APPROVAL A TIER 1 CONSTRUCTION SWPPP PREPARED IN
ACCORDANCE WITH THE REQUIREMENTS OF CITY STANDARDS.
I UNDERSTAND AND ACKNOWLEDGE THAT I MUST: (1) IMPLEMENT BEST
MANAGEMENT PRACTICES (BMPS) DURING CONSTRUCTION ACTIVITIES
TO THE MAXIMUM EXTENT PRACTICABLE TO MINIMIZE THE
MOBILIZATION OF POLLUTANTS SUCH AS SEDIMENT AND TO MINIMIZE
THE EXPOSURE OF STORM WATER TO CONSTRUCTION RELATED
POLLUTANTS; AND, (2) ADHERE TO, AND AT ALL TIMES, COMPLY WITH
THIS CITY APPROVED TIER 1 CONSTRUCTION SWPPP THROUGHOUT THE
DURATION OF THE CONSTRUCTION ACTIVITIES UNTIL THE
CONSTRUCTION WORK IS COMPLETE AND APPROVED BY THE CITY OF
CARLSBAD.
/'""'"'
io/f~
DATE .
E-29
STORM WATER POLLUTION PREVENTION NOTES
1. ALL NECESSARY EQUIPMENT AND MATERIALS
SHALL BE AVAILABLE ON SITE TO FACILITATE
RAPID INSTALLATION OF EROSION AND
SEDIMENT CONTROL BMPS WHEN RAIN IS
EMINENT.
2. THE OWNER/CONTRACTOR SHALL RESTORE
ALL EROSION CONTROL DEVICES TO
WORKING ORDER TO THE SATISFACTION OF
PROJECT INFORMATION
Site Address: 275 CARSLBAD BLVD
CARLSBAD CA 92208
Assessor's Parcel Number: 203-143-070-0
Project ID: _REPLACE NARTHEX ST MICHAELS
Construction Permit No.: 15-2742
THE CITY ENGINEER AFTER EACH RUN-OFF Estimated Construction Start Date 09.30.15
PRODUCING RAINFALL. /').
3. THE OWNER/CONTRACTOR SHALL INSTALL Project Duration . Months
ADDITIONAL EROSION CONTROL MEASURES -"'-•
AS MAY BE REQUIRED BY THE CITY \ Emergency Contact: _ ,
ENGINEERING OR BUILDING INSPECTOR DUE\ .... / . lli f ~ ~
TO UNCOMPLETED GRADING OPERATIONS OR Name: {::_;viii t (...., / V{ ~ V• "'1/ ~
UNFORESEEN CIRCUMSTANCES WHICH MAY ! t~ . l"'r,c "
ARISE. j 24 hour Phone: .2 b q · ")$' '5 -IL. '-(
4. ALL REMOVABLE PROTECTIVE DEVICES SHAL~
BE IN PLACE AT THE END OF EACH WORKING I
DAY WHEN THE FIVE (5) DAY RAIN I
PROBABILITY FORECAST EXCEEDS FORTY I
PERCENT (40%). SILT AND OTHER DEBRIS 1\
SHALL BE REMOVED AFTER EACH RAINFALL.
5. ALL GRAVEL BAGS SHALL BE BURLAP TYPE
WITH 3/4 INCH MINIMUM AGGREGATE.
6. ADEQUATE EROSION AND SEDIMENT
CONTROL AND PERIMETER PROTECTION BEST
MANAGEMENT PRACTICE MEASURES MUST BE
INSTALLED AND MAINTAINED.
SPECIAL NOTES
Page 1 of 3
Perceived Threat to Storm Water Quality
0 Medium
~~-
If medium box is checked, must attach a site plan
sheet showing proposed work area and location
of proposed structural BMPs
For City Use Only
CITY OF CARLSBAD
STANDARD TIER 1 SWPPP
Approved By:----------
Date:---------
REV 4/30/10
STORM WATER
COMPLIANCE
ASSESSMENT
B-24
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
I am applying to the City of Carlsbad for the following type(s) of construction permit:
lXI Building Permit 0 Right-of-Way Permit
D My project is categorically EXEMPT from
the requirement to prepare a storm water
pollution prevention plan (SWPPP) because it
only requires issuance of one or more of the
following permit types:
Electrical
Fire Additional
Fire Alarm
Fixed Systems
Mechanical
Mobile Home
Plumbing
Project Storm Water Threat Assessment Criteria*
Patio/Deck
I:Jhoto Voltaic
Re-Roofing
:Sign
:Spa-Factory
:Sprinkler
Water Discharge
No Threat Assessment Criteria
D My project qualifies as NO THREAT and is exempt from the requirement to prepare a storm water pollution prevention plan (SWPPP) because
it meets the "no threaf' assessment criteria on the City's Project Threat Assessment Worksheet for Determination of Construction SWPPP Tier
Level. My project does not meet any of the High, Moderate or Low Threat criteria described below.
Tier 1 -Low Threat Assessment Criteria
D My project does not meet any of the Significant or Moderate Threat criteria, is not an exempt permit type (See list above) and the project
meets one or more of the following criteria:
• Results in some soil disturbance; and/or
• Includes outdoor construction activities (such as saw cutting, equipment washing, material stockpiling, vehicle fueling, waste stockpiling).
Tier 2 -Moderate Threat Assessment Criteria
D My project does not meet any of the Significant Threat assessment Criteria described below and meets one or more of the following criteria:
• Project requires a grading plan pursuant to the Carlsbad Grading Ordinance (Chapter 15.16 of the Carlsbad Municipal Code); or,
• Project will result in 2,500 square feet or more of soils disturbance including any associated construction staging, stoc~:piling, pavement
removal, equipment storage, refueling and maintenance areas and project meets one or mane of the additional following criteria:
• Located within 200 feet of an environmentally sensitive area or the Pacific Ocean, and/or
• Disturbed area is located on a slope with a grade at or exceeding 5 horizontal to 1 vertical, and/or
• Disturbed area is located along or within 30 feet of a storm drain inlet an open drainage channel or watercourse, and/or
• Construction will be initiated during the rainy season or will extend into the rainy season (Oct. 1 through April :30).
Tier 3 -Significant Threat Assessment Criteria
D My project includes clearing, grading or other disturbances to the ground resulting in soil disturbance totaling one or more acres including any
associated construction staging, equipment storage, stockpiling, pavement removal, refueling and maintenance areas: and/or
D My project is part of a phased development plan that will cumulatively result in soil disturbance totaling one or more acres including any
associated construction staging, equipment storage, refueling and maintenance areas: or,
D My project is located inside or within 200 feet of an environmentally sensitive area (see City ESA Proximity map) and has a significant
potential for contributing pollutants to nearby receiving waters by way of storm water runoff or non-storm water dischargB(s).
I certify to the best of my knowledge that the above
checked statements are true and correct. I understand
and acknowledge that even though this project does
not require preparation of a construction SWPP, I must
still adhere to, and at all times during construction
activities for the permit type(s) check above comply
with the storm water best management practices
pursuant to Title 15 of the Carlsbad Municipal Code
and to City Standards.
'The City Engineer may authorize minor variances from the Storm
Water Threat Assessment Criteria in special circumstances where it
can be shown that a lesser or higher Construction SWPPP Tier Level is
warranted.
B-24
Project Address: Assessor Parcel No.
2775 CARLSBAD BLVD. CARLSBAD CA 92208 203-143-070-0
Dalil:
09.30.2015
ProjectiD:
I:IYES I:INO
Page 1 of 1 Rev.03/09
~··CITY 0 F
C RLSBAD
STORM WATER
STANDARDS
QUESTIONNAIRE
E-34
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
To address post-development pollutants that may be generated from development projects, the City requires that new development and
significant redevelopment priority projects incorporate Permanent Storm Water Best Management Practices (BMP's) into the project
design per the City's Standard Urban Stormwater Management Plan (SUSMP). To view the SUSMP, refer to the Engineering Standards
(Volume 4, Chapter 2) at www.carlsbadca.gov/standards.
Initially this questionnaire must be completed by the applicant in advance of submitting for a development application (subdivision,
discretionary permits and/or construction permits). The results of the questionnaire determine the level of storm water standards that
must be applied to a proposed development or redevelopment project Depending on the outcome, your project will either be subject to
'Standard Stormwater Requirements' or be subject to additional criteria called 'Priority Development Project Requirements'. Many
aspects of project site design are dependent upon the storm water standards applied to a project
Your responses to the questionnaire represent an initial assessment of the proposed project conditions and impacts. City staff has
responsibility for making the final assessment after submission of the development application. If staff determines that the questionnaire
was incorrectly filled out and is subject to more stringent storm water standards than initially assessed by you, this will result in the return
of the development application as incomplete. In this case, please make the changes to the questionnaire and resubmit to the City.
If you are unsure about the meaning of a question or need help in determining how to respond to one or more of the questions, please
seek assistance from Land Development Engineering staff.
A separate completed and signed questionnaire must be submitted for each new development application submission. Only one
completed and signed questionnaire is required when multiple development applications for the same project are submitted concurrently.
In addition to this questionnaire, you must also complete, sign and submit a Project Threat Assessment Form with construction permits
for the project
Please start by completing Step 1 and follow the instructions. When completed, sign the form at the end and submit this with your
application to the city.
1. Is your project LIMITED TO constructing new or retrofitting paved sidewalks, bicycle lanes or trails that meet
the following criteria: (1) Designed and constructed to direct storm water runoff to adjacent vegetated areas, or
other non-erodible permeable areas; OR (2) designed and constructed to be hydraulically disconnected from
paved streets or roads; OR (3) designed and constructed with permeable pavements or surfaces in
accordance with USEPA Green Streets uidance?
2. Is your project LIMITED TO retrofitting or redeveloping existing paved alleys, streets, or roads that are
designed and constructed in accordance with the USEPA Green Streets guidance?
YES NO
X
X
If you answered "yes" to one or more of the above questions, then your project is NOT a priority development project and therefore is
NOT subject to the storm water criteria required for priority development projects. Go to step 4, mark the last box stating "my
project does not meet PDP requirements" and complete applicant information.
If you answered "no" to both questions, then go to Step 2.
E-34 Page 1 of3 Effective 6/27/13
4f ,,~ \~~ CITY 0 F
CARLSBAD
STORM WATER
STANDARDS
QUESTIONNAIRE
E-34
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www .carlsbadca.gov
To determine if your project is a priority development project, please answer the following questions:
1. Is your project a new development that creates 10,000 square feet or more of impervious surfaces collectively
over the entire project site? This includes commercial, industrial, residential, mixed-use, and public
development rojects on public or private land.
2. Is your project creating or replacing 5,000 square feet or more of impervious surface collectively over the entire
project site on an existing site of 10,000 square feet or more of impervious surface? This includes commercial,
industrial, residential, mixed-use, and public development rojects on public or rivate land.
3. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a restaurant? A restaurant is a facility that sells prepared
foods and drinks for consumption, including stationary lunch counters and refreshment stands selling prepared
foods and drinks for immediate consumption.
4. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a hillside development project? A hillside development
project includes development on any natural slope that is twenty-five percent or greater.
5. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a parking lot. A parking Jot is a land area or facili~r for the
tempora parkin or stora e of motor vehicles used personally for business or for commerce.
6. Is your project a new or redevelopment project that creates 5,000 square feet or more of impervious surface
collectively over the entire project site and supports a street, road, highway freeway or driveway? A street,
road, highway, freeway or driveway is any paved impervious surface used for the transportation of
automobiles, trucks, motorcycles, and other vehicles.
7. Is your project a new or redevelopment project that creates or replaces 2,500 square feet or more of
impervious surface collectively over the entire site, and discharges directly to an Environmentally Sensitive
Area (ESA)? "Discharging Directly to" includes flow that is conveyed overland a distance of 200 feet or less
from the project to the ESA, or conveyed in a pipe or open channel any distance as an isolated flow from the
project to the ESA i.e. not commingles with flows from adjacent lands).*
8. Is your project a new development that supports an automotive repair shop? An automotive repair sl"wp is a
facility that is categorized in any one of the following Standard Industrial Classification (SIC) codes: 5013,
5014, 5541, 7532-7534, or 7536-7539.
9. Is your project a new development that supports a retail gasoline outlet (RGO)? This category includes RGO's
that meet the following criteria: (a) 5,000 square feet or more or (b) a project Average Daily Traffic (ADT) of
1 00 or more vehicles er da .
1 O.ls your project a new or redevelopment project that results in the disturbance of one or more acres of land and
are expected to generate pollutants post construction?
YES NO
X
X
X
X
X
X
X
X
X
X
11.1s your project located within 200 feet of the Pacific Ocean and (1) creates 2,500 square feet or more of x
impervious surface or (2) increases impervious surface on the property by more than 10%?
If you answered "yes" to one or more of the above questions, you ARE a priority development project and are therefore subject to
implementing structural Best Management Practices (BMP's) in addition to implementing Standard Storm Water Requirements such
as source control and low impact development BMP's. A Storm Water Management Plan (SWMP) must be submitted with your
application(s) for development. Go to step 3 for redevelopment projects. For new projects, go to step 4 at the end of this
questionnaire, check the "my project meets PDP requirements" box and complete applicant information.
If you answered "no" to all of the above questions, you ARE NOT a priority development project and are therefore subject to
implementing only Standard Storm Water Requirements such as source control and low impact development BMP's required for all
development projects. A Storm Water Management Plan (SWMP) is not required with your application(s) for development. Go to step
4 at the end of this questionnaire, check the "my project does not meet PDP requirements" bc>x and complete applicant
information.
E-34 Page 2 of3 Effective 6/27113
:::~l~i,;'> "\"~ 'C I T Y 0 F
CARLSBA
STORM WATER
STANDARDS
QUESTIONNAIRE
E-34
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
Does the redevelopment of impervious surface in an amount of lelss than
50% of the surface area
If you answered "yes, the structural required for Priority Development apply only to the creation or replacement of
impervious surface and not the entire development Go to step 4, check the "my project meets PDP requirements" box and
complete applicant information.
If you answered "no," the structural BMP's required for Priority Development Projects apply to the entire development. Go to step 4,
check meets PDP box and information.
My project meets PRIORITY DEVELOPMENT PROJECT (PDP) requirements and must comply 1!1Vith additional stormwater
criteria per the SUSMP and I understand I must prepare a Storm Water Management Plan for submittal at time of application.
I understand flow control (hydromodification) requirements may apply to my project Refer to SUSMP for details.
My project does not meet PDP requirements and must only comply with STANDARD STORMWATER REQUIREMENTS per
the SUSMP. As part of these requirements, I will incorporate low impact development strategies throughout my project.
Applicant Information and Signature Box
2775 CARLSBAD BLVD. CARLSBAD CA 92208 Accessor's Parcel Number(s): 203-143-070-0
Applicant Name: o2 Ar~hitecture . Applicant Title:
Date: 09.30.2015
This Box for City Use Only
City Concurrence: I YES I NO
I I
By:
Date:
Project ID:
*Environmentally Sensitive Areas include but are not limited to all Clean Water Act Section 303(d) impaired water bodies; areas
designated as Areas of Special Biological Significance by the State Water Resources Control Board (Water Quality Control Plan for the
San Diego Basin (1994) and amendments); water bodies designated with the RARE beneficial use by the Statte Water Resources
Control Board (Water Quality Control Plan for the San Diego Basin (1994) and amendments); areas designated as preserves or their
quivalent under the Multi Species Conservation Program within the Cities and County of San Diego; and any other equivalent
environmentally sensitive areas which have been identified by the Copermittees.
E-34 Page 3 of3 Effective 6/27113
Erosion Control Tracking Non-Storm Water Waste Management and Materials
BMPs Sediment Control BMPs Control Management BMPs Pollution Control BMPs BMPs
c c c E E 0 ""0 0 0 "" Q) ""0 Q) c 13 t5 c Cl co E c E ""0 "' 0 c ·E co c co 2 2 :.0 0.. Q) .2:! co "' E (i) ~ ·::; ~ co Cl a; Ci)"' Ci) c Cl "' .2:! :2 Cl ""OQ) c c 2: ·;:: :;:: c:r .~ co c ~1 c-0.. Q) c 0 Best Management Practice c co ~ ·a. .E c"' UJ c "'-ciS :c "' !.:! OJ -0 Q) 0 Q) '-' ~ co "" u ~5i (BMP) Description ~ c E Q)Cl co c 0'-0 "' ""0 03 Q) :2 c "' u ~(f) -~ I-.!!2 Cl ~ ·~ OJ ·m c ~~ c u c "' ~.~ ~J Q) :; g c: co co -g~ 0"' ~g 0 ::J .2:!~ -"' "' 0 ~ cc Cl J:::o Q) ~ :2 (50> 0 Q) IJ)l:: co L..Jts ,.§1~ .~;;: '2 .~ .512 Jj (ij ·a. -e ~ c co Q) E -"' ~ -:::> .0 <n= ·;:: 0.. ~ ""0 .s::.c Q) LL u a; Q) :::> ""0 E.s:! :se =-o Q)-.0 ~ -"' co u C1l 0 0.. :.0 .0 co -~ co ·-co u -e·-Q) !.:! !!! u c .s::Q) !11 c c Q) ~ co !.:! 0 -Q) .s::. .0 -co co .se COOl b5& ~tt 0 ~u a ·a. 0 C1l '-' UJO U5 i:i5 (/) 0 u: '-' (f)> (/) (1)0.. U5.E 0.. :2 (/) :c 0:2
CASQA Designation ~ 1';-co q> ..... ..... ~ "'i :z :z ~ "? 0 ..... ~ ..... <? J; "? ~ t;J <? "'i "( <l? "? c.) ..... uJ ..... ~ ch 0 0 c.) UJ UJ uJ (/) (/) ~ ~ ~ :2 ~ ~ UJ UJ UJ (/) (/) (/) (/) (/) (/) (/) I-I-z z z z $ Construction Activity UJ (/)
Grading/Soil Disturbance
I~ Trenching/Excavation X X
Stockpiling
Drilling/Boring
I~ Concrete/Asphalt Saw '(.. cutting
1-K. Concrete flatwork :r.. X.
Paving
Conduit/Pipe Installation .~ ..
I'lL Stucco/Mortar Work X X ':{;,
I~ Waste Disposal '}(
IX Staging/Lay Down Area "X:
Equipment Maintenance
and Fueling
Hazardous Substance
Use/Storage
Dewatering
Site Access Across Dirt
Other(list}:
Instructions: Begin by reviewing the list of construction activities and checking the box to the left of any activity that will occur during the proposed construction. Add any other activity descriptions in the
blank activity description boxes provided for that purpose and place a check in the box immediately to the left of the added activity description. For each activity descrribed, pick one or more best
management practices (BMPs) from the list located along the top of the form. Then place an X in the box at the place where the activity row intersects with the BMP column. Do this for each activity that was
checked off and for each of the selected BMPs selected from the list. For Example -If the project includes site access across dirt, then check the box to the left of "Site Access Across Dirt". Then review
the list for something that applies such as "Stabilized Construction Ingress/Egress" under Tracking Control. Follow along the "Site Access Across Dirt" row until you get to the "Stabilized Construction
Ingress/Egress" column and place an X in the box where the two meet. As another example say the project included a stockpile that you intend to cover with a plastic sheet. Since plastic sheeting is not on
the list of BMPs, then write in "Cover with Plastic" in the blank column under the heading Erosion Control BMPs. Then place an X in the box where the "Stockpiling" row intersects the new "Cover with
Plastic" column.
To learn more about what each BMP description means, you may wish to review the BMP Reference Handout prepared to assist applicants in the selection of appropriate Best Management Practice
measures. The reference also explains the California Stormwater Quality Association (CASQA) designation and how to apply the various selected BMPs to a project.
E-29 Page 2 of 3 REV 4/30/10
PLANNING DIVISION
BUILDING PLAN CHECK
APPROVAL
P-29
Planning Division
1635 Faraday Avenue
{760) 602-4610
www.carlsbadca.!2"ov
DATE: 10/9/15 PROJECT NAME: St. Michael's by the Sea PROJECT ID: RP 15-12
PLAN CHECK NO: CB152742 SET#: ,.ADDRESS: 2775 Carlsbad Blvd APN: 203-143-070
~ This plan check review is complete and has been APPROVED by the Planning
Division.
By: Austin Silva
A Final Inspection by the Planning Division is required 0 Yes ~No
You may also have corrections from one or more of the divisions lisb~d below. Approval
from these divisions may be required prior to the issuance of a buildJ'ng permit.
Resubmitted plans should include corrections from all divisions.
~ This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check APPROVAL has been sent to: octavio@o2arch.com
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING
760-602~4610
D Chris Sexton
760-602-4624
Chris.Sexton@carlsbadca.gov
Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
D Austin Silva
760-602-4631
Austin.silva@carlsbadca.gov
Remarks:
ENGINEERING
760-602-2750
.. RIRE PREVENTION
760-602-4665
~~··· 'W CITY OF
CARLSBAD
PLAN CHECK
REVIEW
TRANSMITTAL
DATE: 10/5/15 PROJECT NAME: narthex
PLAN CHECK NO: cb152742 SET#: II
PROJECT ID:
ADDRESS: 2775 cbd
Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
APN:
1:8:1 This plan check review is complete and has been A~!!lil~io by the fire Division.
By: cwong
A Final Inspection by the Division is required ~Yes D INo
D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to octavio@o2arch.com &USPS
You may also have corrections from one or more of the divisions list~~d below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
D Chris Sexton D Kathleen Lawrence D Greg Ryan
760-602-4624 760-602-27 41 760-602-4663
Chris.Sexton@carlsbadca.gov Kathleen.Lawrence@carlsbadca.gov Gregory.Ryan@carlsbadca.gov
D Gina Ruiz D Linda Ontiveros ~ Cindy Wong
760-602-4675 760-602-2773 760-Ei02-4662
Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@carlsbadca.gov
D D D Dominic Fieri
760-Ei02-4664
Dominic.Fh~ri@carlsbadca.gov
10/5/15
**APPROVED:
Page 1 of3
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE
OF A BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE
DEPARTMENT NOTATIONS, CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH
ALL APPLICABLE CODES AND REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE
LAW.
***Bubble All Changes***
1. Provide OL calculations and MOE plan.
2. One set of doors are being omitted-sliding doors are not considered viable egress
doors.
3. Sheet A1.0: There is a note that says hardware is to be determined later. Clarify type of
hardware or at a minimum the minimum CFC/CBC standards.
4. Sheet E1.0: Include both new and existing EM lighting. It shall meet the following
requirements:
The power supply for means of egress illumination shall normally be prc&vided by the
premises' electrical supply. This shall be for a duration of no less than 90 minutes and be
placed in accordance with §1006.3 CFC 2013 edition. Make changes to~ illustrate
compliance.
The means of egress, including the exit discharge, shall be illuminated c;1t all times the
space served by the means of egress is occupied. The means of egress mumination level
shall not be less than 1-foot candle at the walking surface. CFC 1006.2, 2013 edition.
Both existing and new exit signs shall be illuminated internally or externally at all times.
Illumination shall be provided by emergency back up power for a duration not less than 1
1/2 hours in case of power failure. Indicate on reflective ceiling AND el1ectrical sheets.
CFC 1006.3, 2013 edition.
5. Sheet AO.O:State Occupancy type per CBC,2013 edition. "C" is not a recognized type.
6. Sheet AO.O: Clarify why this building has a 130 system.
7. Add the following or similar note:
Page 2 of3
"(If required) Complete plans and specifications for fire alarm systems, fire extinguishing
systems, including automatic sprinklers and wet and dry standpipes; ine!rtjhalocarbon
systems and other special types of automatic fire protection systems and appurtenances
thereto shall be submitted to Carlsbad Fire Department for review and approval PRIOR to
installation. (CFC 901.2)"
Fire Sprinkler systems per CFC 903,2010 and NFPA 13,2013
Fire Alarm per CFC 907 and 907.2,2010 and NFPA 72,2013
Page 3 of3
Carlsbad Fire Departrnent
Plan Review
N~une:
/\ddrt'i~s:
Requirerrumts Category: COMMfND , COMM
OCTA Vl0/02ARCliiTECTURE
sn:s s
1()89 N PALM CANYON DR
PALM SPftlNCiS CA
92262,.4416
Job Nmne:
Job Address:
S'TJvHCHAEL'S: 290 Sf EXPANSION
2775 CARLSBAD BL CBAD
INC · · •v'ewis_incomplete. At this time, this oftice cannot
adequately concllwt a review to determine compliance with tl .. ~ . ~~!ee review
carefully all comments attached. Please res necessary plans and/or specifications, ~~'clouded",
to this oflke for review and apQr,. · · .
Cond: CON0008536
[NOT MET]
l, Provide OL calculations and MOE plan.
2. One set of doors EU'e beh1g omitted ~ sliding doors a.re 11.ot com;idered viable egress doors.
3. Sheet ALO: Ther~~ is a notethat says hardware is to be determined later. Cbu·ify type of
hardware or at a minirrmm the minimum CFC/CBC stand~lrds.
4. Sheet El.O: Include both new and existing EM lighting. It sh~:tllrneet the follo\v:ir1g
r·equirern~nts:
The pow~~r supply for means of egn~ss illuminati<m shall normally be provided by the prernises'
electricttl supply. This shall be for a duration of no less than 90 mimnes and be placed in
accordance with § 1006.3 CFC 2013 edition. Make changes to illustrate compliance.
The means of egr~ss, including the exit discharge, shall be illuminated at aU times the space
served by the means of egress is occupied. The means of egress illumination level shall not be less
than 1 ~foot candle at the walking surface. CFC 1006,2, 2013 edition.
Both existing and new exit signs shall be illuminated internally or externally at all tirnes.
Illumination shall bt) provided by emergency back up power for a duration not less than 1 1/2 hours
in case of power failure. Indicate on ref1ective ceiling AND electrical sheets.
CFC 1006.3, 2013 edition.
5. Sheet AO.O:State Occupancy type per CBC,2013 edition. "C" is not u recognized type.
6. Sheet AO.O: Clarify why this building has a 13D systern.
7. A.dd the following or sirnilar note:
"(Ifrequired) Cmnplete plans and specifications tor fire alann systems, fire extinguishing
systems, including autmnatic sprinklers HJ'ld wei and dry standpip~es; inert/h~tlocarbott syster.t'ls and
other special types of automatic fire prot~ction systems and appurtenances thereto shall be
submitted to Carlsbad Fire Departrnent for review and approval PRIOR to installation. (CFC 901.2)''
Fire Sprinkler systems per C'F'C 903,2010 and NFPA 13,2013
Fire Alarrn per CFC 907 and 907.2,20 1 0 and NFPA 72, 2013
Entry: 09/04/2015 By: ewong Action: CO
Cond: CON0008586
[MET]
**APPROVED:
TIIIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUEANCE OF A
BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTIONS, ANY REQUIRED TESTS, FIRE DEPARTMENT
NOTATIONS,
CONDITIONS IN CORRESPONDENCE AND COMPLIANCE WITH ALL APPLICABLE CODES AND
REGULATIONS.
TI~ns APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE ANY VIOLATION OF THE LAW.
Entry: 10/05/2015 By: cwong Action: AP
STRUCTURAl DESIGN CAlCULATIONS
ENTRY EXTENSION
ST. MICHAEL'S BY-THE-SEA
EPISCOPAL CHURCH
2775 CARlBAO BlVD
CARLSBAD, CA 92008
TABLE OF CONTENTS
Section 1 ~-Calculation Objective/Purpose
Section 2 --Design Basis
Section 3 ~-Analysis and Design
Project No: 15-1050
Revision No: B
Issued For: Arch Comrn
c
PCC
Dated: 6/2/2015 9/11/2015
1. CALCULATION OBJECTIVE /PURPOSE
This calculation booklet is for structural calculation for Extension of Entry
at the referenced church in Carlsbad, California
2. DESIGN BASIS
A. Codes and Standards:
CBC 2013 (IBC 2012)
AISC 13th Edition
ASCE 7-10
AO 318-11
B. Materials
Steel Fy = 50 ksi ASTM A-992 WF, WT
Steel Fy = 46 ksi ASTM A-500 Gr B HSS
Steel Fy = 36 ksi ASTM A-36 All other shapes and plates
High Strength Bolts = ASTM A-32SN
Anchor Bolts = ASTM A307 Gr 36 Gafvanised
Electrodes = E70XX
Concrete f'c = 2500 psi minimum; 3000 psi foundations
C Foundations
Site Class -D
{ Values below to be used if there is no Soils Report)
Spread Footings/Mats
Bearing Capacity--1500 psf with 1/3 increase for wind/seismic
Passive pressure --225 pcf
Coefficient of Friction --0.35
Subgrade modulus --200 psi/in
D. Soils Report
Soils Report By: None Available
Code Minimums used in this project
E. Wind Speed 123mph (Conservative)
GRAVITY ANALYSIS:
FOR HEADER SIZES, SEE STANDARD DETAIL SHEET
Roof DL = 20 psf; LL = 20psf
~~~..;..p_an ____ +,~~/;...h_l ____ -+,~~/-h-2 ___ ---ll:idtn
Rafters
R1 14.5 0.0
Beam 100 Load computations
Taqtt
100
101
Wall DL (12psf x 3'-6") =
Low Roof Dl = 20psf x 8.5ft) =
Low Roof Ll = 20psf x 8.5ft) =
Total DL=
Total Ll =
Span
24.0
24.3
Load Width
Load above
7.0
0.0
5.0
42.0 plf
168.0 plf
168.0 plf
210.0 pif
168.0 plf
8.0
1.3 2 x 12 DF #2
Use
5.125 x 15 GLB (24F-V4-DF/DF)
6. 75 x 12 GLB (24F-Y4-DF/DF}
Wood Beam
Description Roof Rafters
CODE REFERENCES
Calculations per NOS 2012. IBC 2012, CBC 2013, ASCE 7-10
Load Combination Set: IBC 2012
..... Material Propf:!rtiE!~
Analvsis Method : Allowable Stress Design
Load Combination lBC 2m2
Fb. Tension
Ft~-Comor
=c. Pril
900.0 psi
900 Ops1
E · Modulus of Elasti.::itv
Wood Species
Wood Grade
Beam Brac1ng
'f
Applied Loa(fs
: Douglas Fir -Larch
·No.2
Beam is Braced
Beam self weight calculated and added to loads
r=c;.
Fv
Ft
lateral-torsion buckling
y
Span"' 14.50 It
1.350.0
625.0
180.0
575.0 psi
y
Uniform Load· 0 "() G20 Lr = 0.020 Tributary Width= .330 't iRoofl
DESIGN SUMMARY
Maximum Bending Stress Ratio
Section used for th1s span
fb: Actual
1
2x12
Ma>nmum Shear Stress Ratio
Section used for this span
fv. Actual
F8 . Allowable 900.00pS1 Fv . Allowable
Load Combination
Location of max1mum on span
Span# where maximum occurs
Maximum Deflection
Max Downward L+Lr+S Deflection
Max Upward L+Lr+S Deflection
Max Downward Total Deflection
Max Upward Total Deflection
7.25Dft
0 093 m
0.000 m
0200 Ill
0.000 in
Maximum Forces & Stresses for Load Combinations
Load Combination Max Stress Ratios
Segment Lengm Span# M '·/
"*'D4i
Length= 1450 It 0 336 0095 t 000 100
+D+L+H 1.000 100
Length = 14.50 ft 0 336 0.095 1000 1,00
+D+Lr*H 1.000 1.00
Length "' 14 50 ft 0 631 0.179 1.000 100
+D+S+H 1000 100
Length" 14.50 ft 0.336 0.095 1.000 100
+D+G750Lr+D750L +H 1000 t.oo
Length = 14.50 ft 0.557 0.158 1000 100
+D+G.750L +D750S+H 10.00 lOG
Ra!io =
Ratio=
Ratto=
Ratio=
Cm
100 tOO
100 100
100 tOO
100 1.00
100 1.00
tOO 100
tOO 100 too tOO
1JJG 100
1 JD 100
Load Combination
Location cf maximum on span
# whe:e mzwmum occurs
<360
<180
Moment Values ,,
CL tv1 fb L
100 1X10 080 302.76
100 100
100 100 0.80 30276
tOO 1.00
100 100 t50 567.89 toe tOO
100 tOO 080 302.76
1.00 1.00
tOO 1,00 132 501.61
~ ~ GJ
Ebend-xx '1 ,600.0ksi
Eminbenc-xx. 580.0ksi
F't· ~i
0.00 0.00
900.00 019
0.00 0.00
:100.00 0.19
0.00 0.00
~)00 00 0.36
0 00 0.00
HOO.CO 0.19
000 0.00
900.00 0.32
0.00 0.00
32.210pd
•
ru :1
2x12
32.16 psi
180.00 psi
+D+Lr+H
G.OOOft
Shear Values
tv Pv
0.00 0.00
!7.15 180.00
0.00 0.00
17.15 180.00
0.00 0.00
3216 18000
0.00 0.00
17.15 180.00 coo 0.00
28.41 180.00
0.00 OOD
,Wood Beam
Roof Ratters
Load Combination Max Stress Ratios
Span# M V
1 0.095
Length= 14.50 fl 0.336 0.095
+0+070E+H
Length= 14,50 tt 1 O<l36 0 095
+0+0.750Lr+O. 750L +0.450W+H
Length: 14.50 ft 1 0.557 0 158
+0-t0.750L +0.7508+0450\N+H
Length = t 4.50 ft 1 0.335 0 095
+D+J.750L +0.7508+0 5250E+H
Length-"' ~450ft 1 0.336 0.095
+D 60D+O 60W+0.60H
Length"' 14.50 ft 0 202 0.057
+0.60D+070E+D.60H
Length"' ~450ft 1 0.202 0.057
Overall Maximum Deflections
Load Comtltnation
Vertical Reactions
L.oad Combination
overalfMAxliiium
OveraH MINimum
+D+H
+D+L+H
+D+Lf.,.H
+D+S+H
+D+0.750Lr+0.750L +H
+0-tO. ?50L -tO. 750S+H
+D-t0.60W+H
+D+070E+H
+D+0.750Lr+0.750L+0.450W+H
+D+0.750L+G.750S+0450W+H
+D+0.750L+0750S+fJ525E+H
+D.60D+0.50vV+0.50H
+0 500+0 70E +i) SOH
DOnly
LrOnly
L
S Only
WOnly
EOnly
H Only
Span
Support i
....... 0413
0 132
0220
0.220
0413
0.22[)
0.365
0.220
0.220
0.220
0.365
0.220
0220
0.132
0_220
0.193
c ,~ c, '-~' l
1.000 tOO 1.00
1.000 1 JO tOO
1.000 1.00 100
1.COG 100 1.00
1.000 uo 100
1.COG 100 100
1 000 100 100
1.COO 100 1.00
1.COC tOO 100
1.000 1.00 i 00
1.00() 100 100
1000 too 1.00
1.00G i 00 i.OO
1.000 100 100
1 coo 100 100
Max. Del' Locat!Or in Span
Support2
6~413
0.132
0220
0.220
0413
0.220
0.365
0.220
0220
0 220
0365
0.220
0.220
0.132
0.132
I) 220
0.183
Moment Vaiues Shear Values
m c t r M VL fb F'b \j r• F'v
100 100 1 00 0.80 302.76 900.00 O,l9 17,15 180.00
100 1 00 100 0.00 0.00 0.00 00[)
tOO l 00 1.00 0 80 302.76 900.00 0.19 17 j5 180.00
'1,00 tOO 1 00 0.00 0.00 0.00 0.00
tOO 100 100 OJ30 302.76 900.00 ()49 17.15 180.00
100 !()0 1,00 0.00 0.00 0.00 0.00
i 00 tOO tOO 1.32 501.51 900.00 0.32 28.41 '!80.00
tOO 1 00 100 0.00 0.00 0.00 0.00
1.00 lllO 100 [)80 302 75 900.00 0.19 17.15 18000
1 00 tDO 100 0.00 0.00 0.00 0.00
1 00 100 -1DO 0.80 30276 900.00 0 .. 19 17.15 113000
100 too 100 0.00 000 0.00 000
HlO '1.00 1.DD 048 18165 :JODDO 0.12 '0.29 18000
100 1.00 100 ODO 0.00 0.00 000
1 00 too 1 OD 048 18Hi5 900.00 0 12 10.29 18000
Max. ··+'' Def\ Loca1ion in Span
notation Far ieflis # 1 Values in KIPS
Wood Beam
Description : Plan ChecK Revtsed!DO
CODE REFERENCES
Calculations per NOS 2012, [8C 2012, CBC 2013, ASCE 7-10
Load Combrnation Set: lBC 2012
Material e~e>P~i"t;ies
Method A1!owable Stress
Combination JBC 2012
Fb ·Tension
Fb·
2,400.0
1,850.0
,650.0 ps;
650.0 psi
265.0 ps;
E .. lv1oduius of Elasticity
Wood S;:,ec1es
Wood Grade
Beam
Applied Loads
. DF/DF
: 24F-V4
Beam IS Braced
Beam self weight calculated and added to loads
Fe. Prli
Fe. Perp
Fv
Ft
lateraHorsion
5 i25xf5
Span"' 240ft
Uniform Load 0 =D. 1680. Lr ~ O.i680. Tribularv \i\lidth" tO !Roof!
Uniform Load: 0 = 0.0420, Tnbutarv Width"' 1.0 lt
Eoe!Jd-xx. 1 ,800.0ksl
Eminbend. xx 930.0 ksi
Eoend· vv 1 .600.0ksi Emi~>bend yy 830 o ksi
1100.0 Density 32.210pcf
DESIGN SUMMARY mt;f"UWi'*J: 11111.
Maximum Bending Stress Ratio
Section used for this span
fu Actual
FB : Allowable
Load Combination
Location of maximum on soan
Span# where maximum occurs
Maximum Deflection
Max Downward L +Lr+S Deflec:l!on
Max Upward L+Lr+S Deflection
Max Downward Total Deflection
Max Upward Total Deflection
5.125x15
1.776.64psi
2,315.91 psi
+D*-l. .. ..r+H
12,00Gft
0.486 in
0.000 in
1.144 in
0.000 in
Maximum Forces & Stresses for Load Combinations
Load Combinat;on Max Stress Ratios
Segment Length Span# M V' c!
+{)+H
Length"' 24.0 ft 0.441 Q_180 0 965 100
+D+~~+H 0 965 100
Length= 240ft 0441 0180 0965 1.00
+D+Lr+H 0965 1 00
Length= 24.0 ft o~,..,..,. .101 0.314 0 965 1 00
+D+S+i-l 0965 tOG
Length = 24.0 ft 0.441 0.180 0.965 1 00
+!}+0 750Lr+0750L +H 0.965 1.00
Maximum Shear Stress Ratio
Ratio"'
Rat1o"'
Ratio=
Rallo"'
Cm
1.00 .00
100 .00
100 .00
100 .DO
100 .00
100 .00
1 DO .DO
1.00 .00
Section used for this span
fv: Actual
Fv • Allowable
Load Cornbmallon
Location of max1mum on span
#where maximum occurs
<360
<180
Moment Values
M tb
100 100 16.36 t02138
100 teo
100 1.00 1636 1,02138
100 100
100 1 00 28.45 t77GJ34
100 100
tOO tOO 16.36 1.G21J8
1{10 100
Lengtt1 ;;; 24.0 ft 0.686 11280 0865 1.00 .00 25 4~ 1.587 83
F'b
000
2315.91
0 00
2:l15 91
000
2315.91
0.00
2:l15.91
0 00
231591
{L3i4 : 1
5.125x15
83.08 psi
265.00 psi
+D+Lr+H
v
0.00
2 45
O:JO
245
MO
4.26
0.00
2.45
0.00
181
0 OOOft
Span# 1
Shear Values
tv Fv
0.00 0.00
47.76 265.00
0.00 0.00
47.76 26500
000 0.00
83,08 265.00
0.00 0.00
47.76 265.00
0.00 0,00
74.25 265.00
Wood Beam
Description : PJ<m Check Revised100
Load Combination Max Stress Ratios
M V
Length = 24 .0 ft i 0.441 0.180
"D+060W+H
Length"' 24.0!: 0 44 i 0 180
+D+D.?OE+H
Length= 24.0 ft 0.441 0.11.10
+D+D750Lr+() 750L +0450W+H
Lengtr. "24 0 It 1 0 686 0.280
•D+0.750L ..0. 7508+0.450\l'v+H
Lengtr "24.0 fl 1 0.441 0.1 BO
+0+0.750L+0.750S+().5250E+H
:..erg!h "240ft 1 0.441 0.180
+() 500..0 50W+0.60H
Lergth,24.0fl 0.265 0.108
+0.50D+070E+0.60H
Length= 24.0 ft 1 0 265 0 108
Overall Maximum Deflections
load Combination
Vertical Reactions
Loan Combination
overaiCMAximum
Overafl MINimum
+D+H
+D+l+H
+D+Lr+H
+D+S+H
+D+0750Lr+0750L +H
+D+075DL +0750S+H
+D+0.60W+H
+D+0.70E+H
+D+'J.750Lr+{l,750L +0450\.Y+H
+D+O 7 50L +(). 7508+0.450VV +H
+D+<J?50L +07508+0 525E+H
+0.60D+0.60W-rlJ.60H
+() 60D+070E..O SOH
DOniy
Lr Only
L Only
S Only
W'Only
E Only
H Only
Span
Support 1
4.142
1.636
2726
2726
4.742
2.726
4 238
2.726
2.726
2726
4238
2726
2.726
1.636
1636
2726
2A}16
0965 100
0 965 1.00
0.965 100
0 965 1.00
0965 1.00
0.965 1 00
0 865 1 00
0.955 tOO
0,965 1.00
() 965 100
0.955 tOO
0.965 100
0.865 100
0 965 tOO
0.965 lOG
Suppor. 2
4,742····
1.636
2J2&
2,726
4.742
2.726
4.238
2,726
:t726
2]26
4.238
2 726
2.726
1.335
1.635
2726
2.016
tvkn1enr Values Shear Values
Cm c .~ M F'b v tv F'v \_,..t L
100 ~.00 100 CLOO 000 0.00 0.00
1.00 100 1.{)0 H\0 16.36 1021.38 2315 91 2.45 47.76 265.00
100 100 100 1,00 0.00 0 00 0.00 0.00
1.00 100 100 1.00 16.36 1,02138 2315.91 245 47.76 265.00
tOO tOO 1.00 1.00 0.00 0.00 0.00 0.00
100 100 1.00 100 16.36 1.021.38 2315.91 245 4?.76 26500
100 teo "1.00 100 0.00 0.00 0.00 001)
1.00 1.00 tOO 1 eo 25.43 1,587.83 <'31591 3.81 74.25 26500
tOO i_GQ OG tOO 0.00 0.00 0.00 0.00
i.GD 100 HJO '1 00 16.36 \02138 ~:315 9i 2.45 4776 265.00
1.00 100 1.00 1.GO 0.00 0.00 0.00 0.00
100 100 iCO iJtO 1636 1.02~ 38 2315 91 245 47.76 265.00
100 1,00 100 1 GO COD 000 000 0.00
100 100 100 100 981 612.83 i~315,9i 147 28.66 26500
1 OD !.00 l()[) 100 0.00 0.00 0.00 0.00
1.00 100 100 !_CO 981 612,83 2315.91 147 26.66 25500
Load Cornbinaton Max."+" Dell Location in Span
D. DOD
Support notabon Far left !S #i Values in !\IPS
CODE REF4=RENCES
Calculations per NOS 2012. !BC 2012. CBC 2013. ASCE 7-10
Load CombinatiOn Set· lBC 2012
Material Pr()perties
Ai!owabie Stress
JBC 2012
Wood
VVood
Seam
DF!DF
24F-V4
Beam is
DE$1GN SIJMMAF('f
Maxirnum Stress Ratio
Section used for this span
fu. Actual
FB . AHowabie
Lead Combination
Br.aced
Location of maximum on span :.:
# where maximum occurs
Maximum Deflection
Max Downward L+Lr+S Deflection
Max Upward L+Lr+S Deflec!Jon
Max Downward Total Deflection
Max Upward Totai Deflection
Fb-~ension
!ateraHorsa:m
Span 2.: 670 n
2.400 o ;;si
1.850,0 PSI
1.650 0
G50 0
265 0 pSi
1 100.0 DSi
l'L75x1Z
Maxunum Shear Stress Ratto
Sech:>n used for thiS span
fv · Actual
0.277 in Ratio"'
.. {) 169 in Ratio "'
0 590 in Rat1o =
-0.360 ;r; Ratio"'
Fv A!lovvab:JS
Load C>r!lbinaFon
Location ol maximum en span
F where rna;:t:!rnurn occu:-s
Maximum Forces & Strtsses for Load Combinations . ·-loa;i Combina!ion Ma• Stress Rat:os Moment '/alues
Spanil M v 0j Cr m .~ M fb 'v L
+D+H
Lengtfl 70 [i 1 0155 0067 1.000 100 tvo 1 ()()
Lengtn ~ 5.670!; 2 0.319 O.t~S 1.000 i.CD
i 00 387 286 96
:':}fj t3:j,6>1
Ebend-n
Ern:nbeno xx
Fb
0.00
1350 00
v
1 800 Oksi
930 Oksi
600 Oksi
830 Oksi
32c21
0 2.59 . 1
6.75x12
68.71 psi
26~) GO psi
Sne~r \Jalues
!·w
iJOD
54
Fv
000
3644 26500
t.Aax S!res:. Rakos Load Combmation
Segmenl Length
.. eng!f' ~ 24,(,7!) n
Length ~ 7.0 it
Span# M
~ 7.0!1
Length ~ 5670 f1
:.ength " 24 61'0 ft
Length_:.; 7 {} h
Length "' 7,.0 !1
Length " 5fl7C ft
Length= 24.£70 l1
Length ". 7 .Q it
3
4
1
2
3
4
1
2
3
4
Length = ro it 1
Length" 5.570 fl 2
Lengtr1" 24.670 ft 3
L.tmgth = 7 0 It 4
•D+0750Lr+0750L-+i
length = 7.0 It i
Length = 5 670 1\ 2
Lengtll ~ 24.670 ft 3
Lengl\l = HH! 4
+D+O?OOL +0750S-+i
Length" 7 0 fl
Length = 5.670 !1
Length~ 24.670 ft
Length= 7 C f!
+0+060\IV-+1
Length" 7.0 tl
Length = 5.67G h
Length = 24.670 ft
Length= 7 f!
•D+0.70E4f-l
i
2
3
4
1
2
3
4
Length= 7.0 ft 1
Length ~ 5.670 ft 2
Lenqti1 = 24 670 ft 3
Lengtt-"7Oft 4
+D+0.750LHJ?50L +0 450W4f-l
!..engW1" 7 ft 1
Length~ 5.&TO n 2
Length = 24 670 f! 3
Length" ft 4
+O+C?SCL +0 750S+0.450W4f-l
Length " 7 't 1
Length 5.6?0 ft 2
Lengtr = 24 670ft 3
Length= 7 ft 4
+D+0.75GL +C 750S+C.5250E«<H
Length" 7 it 1
Length = 5 6?0 fl 2
Length"' 24.6701: 3
length ~ 7 0 it 4
-HJ.60D+0.60W+O 6GH
Length " 7.0 H
Length .~ 5 670 f!
Length " 24 6 70 fl
Length~ 7.0 it
..{Ji)OD •fl ?CE •{) SOH
Length" 7 0 t
Length"' 5.670 ft
1
2
3
4
1
2
rn:n
0155
(} 155
(1319
0 333
() 155
0 292
OOG't
0 628
0,29.2
0155
0 333
155
(1.258
0.531
0654
?58
G.i55
0333
0155
0.155
319
0.333
0155
155
0.319
0333
Q t55
258
0 531
0 554
0258
<55
0.319
0 155
155
0 319
0 333
CU}93
0191
C20D
0093
0.093
0.191
(I 138
0.138
0 067 ons
() 138
() 138
0126
0259
0259
0.259
0.067
0.138
0 138
0.138
011
0229
0.229
0220
OD67
138
0138
0067
13&
138
138
o;;~
0.138
0138
G.133
0.11
0229
0229
0.229
0.136
Q_i38
0.138
t1067
0138
138
0.138
0040
(}083
0083
0083
0.040
Moment V a1ues
{L957
tOOD
[l,\}57
tOGO
tQ(! 1.00
1
'on : oo
100
UD
m
1 (JD
1 no
100
1.00
00
CL
1 co 1(}0
100 GO
~no
100
~ .ooo 1 no 1 oo teo too
0 957 1 00 1 ()(] ~ Q(J i (1(1
1000 HO '.GO
tOOQ 1-00 tOO
05
7.96
15 Oi
1J)00 '1.00 1 CO :} 87
0 957 1 GO 100 1 00 100 1 DO
i.OCD 1,(;0 100 1 00 ·i 00
1 ono GA",
1~ ~
1.000 1.00 1.00 1.00 1 00 1 00
~.OCO
0.957
1000
i COD
1000
257
1 000
100
1.0::,
100 H/J
1 00
1 OD
1 00
1,00
100 i 00
1.DG
00 i ~)0
87
ll7
387
,~ ~
1<JGO 1.0D 1 Q() 1 00 96
1 ()(}[)
645
tDOD tOO 1 00 1 GC 13}0 1325
?57 :3.25
1000
957
1.000 tOO 1.0D ~.GO 1 00 tOC
UYJU ; 00 1 CD 1 00 3.8?
1 000 tOO ·1.00 1 CO tOG
0,357 tOO 1.00 'i X~J 7 9£
tOGO HJO 100 100 100 100 387
~-OGO
1.000
i.OOO
GB57
!.00(}
1 OQO
1.000
1 DO 1
100 1,()(!
1 ou 100
t00
100 100
Hl(} 100
4 DD 1 GO
1 GO 1.(h)
100 1 00 1 00
1 :)0 'LCD 1.00
1.00 1 (!(>
100 100 1.00
i.DO i DO 1.00
1.00
2.32
4/8
4 7B
2 32
2 32
589 84
28€ 96
286 9S
:;,&~! 84
589 84
90
1770.99
1350J)i)
0
1!/099
541 03 1850 00
1 ~12.09 "850.00
t112.09 i//(J99
54'*
CoJO
256 96 1!150 Q(i
589 64 1850 GO
589 84 99
0 00
477 S 1 OC:
981 53 lBSO 00
286
589 84
589.84
28595
58984
559S4
286 96
0 00
~ 85~) }0
1850 00
sc~
0 DC
';850 00
1650 00
iS5CLDO
0
589 i:l4 1.350 co
28fi96 185!~1.00 uoo
477
98153
477 51 1850 (II)
28~).9*1
589.84
58S.84
286 95 t€.5li 00
286 96 185(UJD
589.84 1850 1}0
58fLS4 1770,99
286.96 1850 00
17217 1850[)()
185QOO
(lOG
~72 1l O!J
Shear Values
w F'v
00
0.85
1 97
1 97
:J.95
OOG
36 44
44
0.00
17.64
36 44
36.44
3644
0.00
66 71
68.71
71
o no o.oo
26500
2650!)
000
265 00
265 OG
2650(1
255
000
26500
265 OG
25500
265
GOO
64 255.00
:}fi44 265 00
1 97 36 44 265DO
0 .!4 265 UD
0 OG 0.00 0.00
255
3 60 65 265.00
€0.65 2€5
0 00
D.OC
17.F4
36.44
36.44
1? 64
4A
44
3S 44
(L95 54
i 9/ 4C
:)95 :)644
1 59 60 65
OC DD
095 1764
197 3644
36 44
0% 3644
QC
0 95 1764
197 3644
197 36 44
0 95 36 44
00 000
0?7 1059
1.13 21.87
p 21.87
057 21 87
0.00 Q.OO
?65JG
2650()
265.00
265.00
:)
265,[10
26500
2650i}
265.00
0 00
265 00
265(!()
265
265 on
2E5.0G
2€5 00
2€.5 ]C
265 00
00C
265.08
265 O·J
265 OJ
265 QiJ
0
265 00
265
26S.DO
265.00
265.00
26500
2.6500
265 00
OX1C
2SS,OC
Wood Beam
Load Combination
8(-'l:lment Length Span#
Leng!h = 24 670 it 3
Lengtn = it 4
Max Stress Ratio>
M V
Overall Maximum Deflections
Load Combinabon Span
Vertical Reactions
LC·ad C:ombirat;on
O>.·eraH tAAXimum
Overall MiNimum
+'J·m
¥0•L+H
~t)+Lr..r-H
•O+S+H
.-D+D.750Lr..0.750L +H
-i-D+{),750L +Q_T50S +H
+0+{},61'J~V-+-H
,;J+'i 7DE+H
.-D..Q750Lr+0.750L •{l,45()'1\1,;H
+0..0 750l +DJtiOS4J.450W+H
-<-0-«i 750L..0750S+D.525E+H
4J&0D+l1 E4,')~v,~{160H
.{) 600+D 70E -«1 60H
J
4
Support 1
Max.'." Dell
00000
0.500
!1834
cl &34
834
1388
Gt834
534
Ci 534
use c 534
334
0 600
0 834
() 738
LOdlti01 11 Span
0.000
13.116
13 1 16
1.971
3
--t9~;
3285
5.467
3_288
3286
5A67
3.286
3.28\i
3.285
2.909
1735
2 891
2 391
4 812
2.891
2Jl9i
2560
Mornenl Values
lA flJ Fb
0414
0.0000
3593
v
Stlear Values
f11 F'v
265.00
?0500
3 086
3.086
7 DOD
{
Wood Beam ENER.CALC, iNC 1983-2014, Bulk!:€ 14.8.1il Ver:6.14.6.31
Description : Typical Beam on Glid 1 or 2 fv13x;mum Span ~ 5 3ft
CODE REFERENCES
Calculations per NOS 2012, IBC 2012, CBC 2013, ASCE 7-10
Load Combination Set: IBC 2012
Material j3r9perties
Analvsis Method : Allowable Stress Design
Load Combination lBC 20~2 Fb Ters;on
Fb-
Fc ·· Prll
1000ps;
iOOO pSi
1500 psi
E . Modulus of Elasticity
Ebend-xx
Eminbend-xx
Wood Species
Wood Grace
: Douglas Fir-Larch
No.1
Fe~
Fv
Ft
625
180 psi
675
Beam Bracing Bearn is Ful!y Braced lateral-torsion
Applied Loads
Beam self weioht calculated and added to loads
Uniform Load : D = 0.020. Lr"' 0 020 , T nbJtarv Width"' 4 fl rRuof;
DESIGN SUMMARY
Maximum Bending Stress Ratio
Section used for thts span
fb. Actual
FB : Allowable
Load Combmation
location oi maximum on spar
Span# v;here maximum occurs
Maximum Deflec!lon
Max Downward l+Lr+S Deflection
Max Upward L+lr+S Deflection
Max Downward Total Deflection
Max Upward Total Deflection
6x12
i ,OOO.OOpsi
2665ft
;I! 1
0.000111
0.000 in
ooo·J in
0.000 rn
Maximum Forces & Stresses for load Combinations
Loac Combination Max Stress Ratios
Segment Length Span# M v cd c c I
+D+H
Length ~ 5.330 ft 0.012 0.008 1.000 iOD
;.{)+L+H 1000 100
Length " 5.330 ft 0012 0008 1.000 1.00
;.{)+Lr+H 1.000 tOO
Length "'5.330 ft 11019 OD12 1000 100
+D+S+H 1 000 100
Length ~ 5.330 ft 0.012 0008 1()()0 100
+0-t{l.750Lr..0.750L +H 1000 1 00
Length " 5.330 ft 0.017 0.011, UllJC lOG
;.{)+0750L .;{).750S+H 1_000
Maxtmum Shear Stress Ratio
SectJOil used for this span
fv ·Actual
Ratio=
Ratio"'
Ratto=
RaM=
Cm
100 100
teo 100
100 100
100 100
1.00 100
1 00 tOO
tOO 100
100 1.00
tOO t 00
Fv Allowable
Load Comoinaton
Locat1on ,:/maximum on span
Span ;;: wl1ere maximum occurs
<360
<IBC
Moment Values
(' ~ M ib '-' \.,
100 1.00 0.12 12.00
100 100
100 100 0.12 12,00
1.00 100
100 100 019 19.03
100 tOO
U10 tOO 0.12 12.00
100 100
~.oo ; oc fL~7 1:28
; DC
Fb \1
0.00 0.00
1000 00 005
Q,QO 0.00
1000.00 0.06
0.00 (JOO
1000.00 0.09
0.00 000
1000.00 0.06
G 00 000
1000 00 0.08
000 0.00
1700ksi
620ksi
32.21 pet
6x12
2.20 psi
HlO.OO psi
+C+U+H
4.377 ft
# 1
S.'lear Values
fv
0.00
F'v
0.00
t39 18000
0.00 000
138 180.00
0.00 D.OO
2.20 180.00
0.00 0.00
139 18000
0.00 000
2,(10 18000
1)()0 0.00
l ! j
Wood Beam
Description · Typical Beam on Grid 1 or 2 Max~tnum Sp;n 5.31!
Load Cmrbinanor Max Stress Ratios
Segment
Length= s.:no It
+O+D601N+H
Length "' 5.330 ft
+O+D?OE+H
Span#
1
Length = 5.330 ft
+D+D.750Lr+D.750L +D.450VV+H
Length= 5.330 ft 1
+D+D ?SOL -+~J750S+D.450W +H
Length = 5 330 fl 1
+D+D 750L +G750S+D5250E+H
Length = 5.330 It 1
-MJ.60D+D 50W+D.60H
Length = 5· 330 It
-MJ 60D+D70E+D 60:-1
[) 012
{)012
0.012
0.017
0.012
0012
0.007
Lengtr = 5.330 ft 1 0. 007
Overall Maximum Deflections
Load Combination
·;.D+Lr+H
\i
0008
0.008
(),()08
0011
0008
0008
0.005
0.005
Span
1
Vertical Reactions
Loac Comomation Support 1
·· o';eiaiiMAXimum
Overall MIN1mum
+D+H
+D+L+H
+D+Lr+H
+C:I+S+H
+0+0750Lr+D 750L +H
-D-MJ.750L +D.750S+P
~D+0.50W+H
+0-MJ.TOE+H
..,J+O. 750Lr+D.750L +0.450W+H
+0+0. 750l +D750S~O 450\IV+H
+0+0. 750l-+0.750S+0.525E+H
+0.6GD+0.60W+D.60H
+0.60D+0.70E+O SOH
DOniy
LrOnly
LOnly
SOnly
wor::y
EOnly
HOnly
6144
0053
0.091
0.091
0.144
0091
0131
0091
0091
0091
0.131
0.091
0091
0055
O.G55
0.091
0053
\...> C; Cr Cm ,., CL c. t
1.000 1.00 100 100 1.00 100
tOGO 100 100 100 100 100
1.000 1.00 100 100 100 i.CO
1000 100 100 100 tOO 1CO
1000 1 OG tOO 100 100 1.CO
1.000 tOO 100 100 100 100
1.000 100 100 100 100 1.00
1.000 100 100 1 GO i co HO
1.GOO 100 tGO 1 00 100 1 co
1.000 100 100 1.00 1.00 !.CO
1.000 100 100 1 00 100 teo
1000 100 100 100 100 1.00
1.000 1 oc 100 100 100 1.00
1.000 100 100 1 00 100 1.00
1.000 100 tOO 100 1.00 100
..
Max Deft Locatwn in Span Load Comb1na!ion
Support notat.on. Far left IS #1
Support 2
0.144
0,053
CWS1
0.081
~Ji44
0091
0 ;31
0.091
0.091
0091
0 ~31
0.091
0.091
0,055
0.055
0091
CLDS3
Moment Values Shear Values
M fb F'b v hi F'v
0 12 12\JO 1000.00 0.06 139 180.00
0.00 000 0.00 0.00
0.12 ~2.00 1000 00 0 06 139 18000
0.00 000 0.00 080
012 1200 100000 0.06 139 18000
GOO 0 00 0.00 000
0.17 1728 100000 0.08 200 18000
0.00 0.00 0.00 0 DO
0.12 ;2.00 100000 0.06 139 180 00
0.00 0 00 0.00 0.00
012 1200 100000 0.06 139 18000
0.00 0.00 000 000
007 7.20 10DODO 0.04 0.83 18000
GOO 000 000 0.00
ow 7.20 1000.00 004 0.83 180 00
Max "+~Dell Lccation in Span
Values in KIPS
lATERAl ANALYSIS
From Enercak Print-outs, V(EQ) = 0.1236W (see page 13 of this booklet)
V(ASD-EQ) = 0.1236 X 1.3 )( 0.7 = 0.1124W
Approx Waif Length= 100ft; Estimated Watl Wt = 100*12 = 1200 lbs
Approx additional plan area= 35 x 15 = 525 sq.ft
Equivalent plan area loadng = 1200/525 = 2.28psf;
miniurr;
Est. ASD Seismic Shear:;::: 0.1124 x (20 +4) psf =
Est ASD EQ Shear= 0.1124 x (20 +4)x6.5/2.5psf =
2.69 psf
6.99 psf
(for Type V Walls}
{for Cant. Colmns))
( See Page 15 of this booklet }
The above load is used in the Tabulation on page 15 of this booklet
lATERAl ANALYSIS:
LATERAL ANALYSIS 15 LIMITED TO THE AREA OF THE NEW BEAMS.
EXISTING BEAM AREAS ARE NOT INCLUDED JN THESE CALCULATIONS
EQ:
Grid Width Length Resistance
ft ft ft
A 15/2 50 {2} HSS 5x5x1/4 Columns
B 45/2 so =16.5
1 50/2 14 {2) HSS 5x5x1/4 Columns
2 44/2 14 :::;6.25
St. Michaels Church ............................................ ,_,
. R!s~.c_a_tegory ..... .
Risl< Category of Buildmg or Other Structure · ''l" and otm:r structures that represent a low nazard to rJna:> life in the
Seismic importance Factor
1 166 g. 0.2 sec response
4469 g, 1.0 sec response
Site,(;~ff.~nd Oesigl)q~ego_ry.
Sile Ciass1ficetion 'D"'; Shear Wave Velocity' BOO to 12DC rt:sec
Site CoeffiCients Fa &c Fv
(usmg straight-Nne mte~oofation ,~ .. om table values)
Maximum Cons1dered Earthquake A.xeieration S MS"' Fa • Ss
S M1 = Fv • Si
Fa
Fv
Desig1 Spectral Axeieration s S M2~ 2!3
s
Seismic Design Category
~R~~isting~y~~el!!_ ..
Basic Seismic Force Resisiing System Bearing Wal! Systems
Latitude
Longitude
Loca!IOn ·
1.55
1.205
0.803
0463
33. 1 58 deg North
i 17 326 deg '!·;est
ASCE 7-10, F'age? Table 1.5-1
ASCE 7-1!), Page 5. Table 15-2
ASCE 7-10 11.4 i
ASCE 7-10 Table2031
ASCE 7-10 Tai;Je 114-1 & 11.4-2
ASCE 7¥10 Eq, 11.4-1
ASCE 7-10 Eq 114-2
ASCE !-10 Eq. 11.4-3
Light .framed wafls sheathed wlwood structura~ panels rated for shear msislance or steel sheets.
Response Modification CoelfiC1eflt " R ··
System Overstrength Factor 'Wo"
Deflection Amplification Factor "Cd"
eppl!cabie tOtdnores.
!350
3 00
4.00
Building heigh\ Limits :
Category ··A & 8" Limit
Category ·c· Urn!!:
Categmy 'D" Lint
Category "E'· Limit
Category 'F Umit
Limit= 65
Urn;t= G5
Urr<::: 65
Se1smic Design Category oi D. E. or F therefore Redundancy· Factor" p •· = 1.3
Lateral Force Procedure
Equi••alenl Lateral Force Procedure
Structure Type for Building Period Caiculatior. All Other Stn;ctural Systems
" C! ' value 0 020 "tm" · Height from base to highest level " 250ft
"x" value 0.75
" Ta ".llpproximate functementai period using Eq. 12.8-7
"TL" · Lmlr,HJeriod transition penod per ASCE 7-D Maps 22-12 -> 22-16
" ~s ·: ~!t!5Pl?"!5.e qqt}f'fi<:i~Jit
S 02: Short Period Design Spectral Response
".R " . Response Modification Factor
"1" Seismic Importance Factor
::::
=
0.224 sec
8.000 sec
Buildmg PeriOd" Ta ,, Calculated frorn Approximate Method selected
6.50
From Eq 12.8-2, Preliminary Cs
From Eo 12.8-3 & 12.8-4. Cs need not exveed
From Eq 12.8-5 & 12.8-6, Cs not be less than
Cs : Seismic Response Coefficient "'
ASCE 1-10 Secticn12.34
ASCE 7-10 Section 12.8.2
UseASCEJJ,M
ASCE7·10 Section 12.8.!.1
= 0.124
= 0.318
:::: 0.035
0.1236
2013 CBC CODE (ASCE 7~10) WIND tOAD CALCULATIONS
Wind Risk Category
Bask Wind Speed =
for Occupancy I
Wind Directionality
Factor, l<d
Exposure Category
Velocity Pressure
Exposure Coef, l<z
Topographic Effect
Factor, l<zt
Enclosure Class
123
0$5
c
0.85
1.00
1
Wind Imp. Factor, I 1
f'resstnB " O.OO;!S6 "
Figure 26.5-lC ASCE 7-10
Section 26.6 ASCE 7-10
Section 26.7.3 ASCE 7-10
Table 27.3-1 ASCE 7-10; zg =
Section 26.8 ASCE 710
26.8-1
Section 26.10 ASCE 7 10
lve!odty Prr~ssmH"' 2¢1 psf J
~
load
alpha"' 95, z<15 ft
(;rid A b.,.,
l{unf
St. MICHAEL's CHURCH -·SUMMARY OF LATERAL DESIGN FOR EQ/WIND LOADS (1-STORY)
IA·ttcpitl
r:urrent
Tributary I Lt'''el
<\rt>n 'sf) 1 / ' ~--\·e~tftJ!>H l'~'hHl~l~~n
fft!Jcd\t'
I'I!Hdlllfli
ASO
t>nrrent
Lt>'dEQ
Lmtd Ill»~
_ t}~tHtnlug
t:urrrllt I (;uvt>-l'lling I Sht<.l\r fmm
Ltwd Wl!!d Lateral Aoo>t
tnod (II") tnad tlbsj (LI>sl
'l'ot•l
{;ovtrnin)t
Sb•ar (ll>sl
Curn·m Lt•n•f
Sbti!t Woll
IA't1gth tft}
t't.u:n;nt
lxvd 'rvt;tl
wan L<•~•• Ill nit Shear
\ftl c l/' ~t
l·· .. -~ ....... _ _,._ ,,_, .... ,+ .... -.. , ........... +··"""~~'''''"'' --+
f>ro~s l!plift in
Lbs
Type of' Shear
Wall
(2) HSS
5x5x0.25
Column
Uuldowns
(4} 1" dia
F-1554
Gr.36
Anchors
·1 vpt· 6!. .... l'Hlll?_:::'~l'>c '
(4) 1" dia
(2) HSS I F~1554
5x5x0.25 Gr.36
1 50 1-~ 350 t •. iJ<J 28 ,, 2-1.f7 Column Anchors
i''
~ .. ~--·'~·-.. -·-+-·-.. ····-~--~· .. ·+·
2X 9 1\,N I l\!17 T~!:K' 6C Hill :'-Sl1S25 ---+ .. ·--··~+---~----
............. t ........ .,., .. __ +---~---+-----~--+,····-· .................... ~·--···~--
\sSiJ,!Dnltllt nf Sht'ar lo ( antilr\ t•r ( 'olunm~
( irkl i\
(!rid!
I
\iwnher (lfCo!umn;;
i\Sl) H) Slwar P~r ( 'olu!lln
Numh~r of ( 'olumns
2
!.l! l lhs
2
AS!) I (l Sh~tn f'cr t t•lunm 122:1 II">
~-~~-r~~-+----+~-~--~--t"'"'' ''""'--+------~
lkami1-!01Rc(1dionl.nadll Llh:l ?9k
I \C l\1inimm11 /\ \iall <.>ad 1J ,, I (H..: I !Ol
"'"' ........ l .. ''"'"' ..... "'""' ........................ J
NAJLING
15 GA SP,
f!l\6" O~C. EN
®6" O~C BN
lG GA. SP
.\070 # /F'T
12iiJ .11/FT
_oad Table: See code report listings below
Vertical HDU
lnstallaiion
It These products are available with addit'onal corrosion protection. Additional orca wets c~ this page
may also be available with this option. check with Simpson Stror>g·Tie !or details.
I:Umensions fasteners
Model ,, {itt)
Ga Anchor No. w H B i so Soltma.
(in.}
I
I B·SDS ':'/X1 OTT2Z EP~\s 1% B·SDS Vlxi I' 1HiDS ,,,~x2V?"
I 3 8'Yit 3Y, 6·SDS %'1:2>':
I HDU4·SDS2.5 3 HJ1'0n 3}~ !O·SfJS x2·.;
I H!JU5-SOS2.5 14 3 3% 1 ;~.-~.) i4·SDS ~>!2
I HIJU8-SDS2.5 iO 3 16?'1! 3!fi 1"-< 20-SDS
I HDU11-SDS2 5 H) ,.,
,) 22' 1 >·" 30-SDS ·::x2' ·
I 7 3 3fi-SDS
1. See Holdcw(1 and Tension Tie General Noles.
2. Noted HDU14 allowable loads are based or: a 5 1/2" w,de post {6x6 m.r~.).
3. HDU14 requires heavy hex anchor nut to achieve tabulated loads [supplied w1th ho!down).
4, Loads are applicable to Installation on e1ther narrow or wide face of post
:;ode Reports (PDFs):
OTT1Z
IAPMOUES
ER !CC·ESESR CITY OF LOS ANGELES
ESR-2330 I ESR-2523 '
f;:SR-2330 I ESR-2523 •
TVOICill HDU Tie
£letwe~n Floors
Minimum
Wood
Member
Thickness
{itt)
1
3
3
3
3
3
3>?
4:4
4x6"
5~·i·"'
Horizor~tal HOU Offset
Installation
{Plan View)
See Hoklown and Tension
Tie General Notes.
Allowable Tension toads
(160)1
Deflection at
DftSP SPf/Hf Allowable toad
tin.}
1825 1800 0.105
2145 18:35 0.123
2145 2105 lli28
3075 2215 O.OBB
4565 32H:) 0.114
5&45 4G65 0115
6970 5020 0116
7870 5665 0113
953o 636~ 0.
1117.f! R>J45 0
10770 7755 012?
10435 OT17
14445 10350 (1.177
lEGACY REPORTS
STATE OF FLORIDA ICC·ES NER ICC-ES ER ICC-ES ES
OTT2Z
OTT2Z-SOS2.5
HDU See specific model numbers lor code listings.
HOU11-SDS2.5
HOU14·SDS2.5
HOU2-SOS2 .• 5
..
· Steel Column
Description · Check Steel Columns on Gnd A with verhcal and ialera! ioacts
Code Reftmmces
Calculations per AlSC 360-10. IBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used: IBC 2012
Generallnformation ' ~~~···· -~--'~~-·········
Steel Section Name : HSS5x5x1/4
.Allowable Strength
Overall Column Height
& Bottom
9.0 it
Free Bottom Fixed Analysis Method •
Steel Stress Grade
Fy . Steel Yield
Brace conciit;on for deflection
E . Elasii~ Bend'rn[J ModuJJs
Load Corrbination ·
Applied
36.0 ksi
ksi
!BC 20'!2
.X-X
140.252 1bs *Dead load Factor
AXIAL LOADS ..
R.oof Axial Load aj 90ft 0 "' 3.3CJ, LR"' 2.90 k
BENDING LO.A.DS
Lat Point Load at9.0 it
DESIGN SUMMARY •••••••••••m-""
Bending & Shear Check Results
PASS Max. Axiai+Bending Stress Raila ::
Load Comtlinatiorr
Loca110n of max.above basa
At maximum location valves are ,
Pa ·Axial
Pn ' ; A!iowable
Ma-x · Applied
l\11n-x! Omega · .Mowable
Ma·y · Applied
Mn-y f Ornega . Allowable
Maximum Shear Stress Ratio""
Load Combination
Location ol max.above oase
At maxmurn location vaiues are .
Va: Applied
Vn 1 Omega · Allowable
Load Combination Results
+D+L+!-'
+D+Lr+H
+D+S+H
+D-{l750lr-HJ750L +H
+D+0.750L +(L750S+H
+D+0.60W+H
+D+.HOE+H
+D+OJ50lr+O. 750L "'{).450W+H
+D+075Cl +0 750S+O 450'/\I+H
+0-{)750l +0750S+0.5250E+H
+~J 600+0 60VV+0.60H
+D 60D-r{}70E+0.60H
:1
+D+070E+H
0.0 ft
3.440 K
92.695 h
-8.259 k··ft
13671 k-11
0.0 k-it
13.671 kAt
: 1
+D+0.70E+H
0.0 ft
Maximum Axial +Bending Stress Ratios
Stress Ra::o Status Location
0.037 0.00 f!
0037 0.00 f!
0.068 0.00 it
0.037 0.00 It
0.061 0 00 ft
0.037 0 00 ft
0.037 0.00 ft
0.623 0.00 ft
0.061 O.OOft
0.037 0.00 f!
0.472 0.00 fj
0.022 0.00 ft
0.6i5 0.00 ft
alongY·YAn
Maximum SERVICE load Reactions.,
X-X
X-X
along Y-Y
Bcttom along Y -Y
Maximum SERVICE Load Deflections .
0 0 k
0.0 k
OOk
1.311 k
Y-Y L180 1n at 9.0f! above base
load combination : E
X-X 0.0 in al 0 Oft above base
for :oad combination ·
~ .. ~'
Maximum Shear 1;;:atios
Stress Ratio Status location
0 000 0 00 ft
0.000 0.00 It
0.000 0.00 ft
0.000 0.00 ft
0.000 0.00 ft
0 000 0.00 ft
0,000 Pt\S~S 0,00 ft
0.035 0.00 fi
0.000 0.00 it
0.000 0.00 li
0.027 0.00 fj
0.000 0.00 ft
0.035 0.00 ft
Steel Column
Descnption : Check Steel Columns or: Grid A. Wilh vertical and lateral loads
Maximum Reactions • Unfactored
Load Combination
+O+H
+D+L+H
+O+Lr+H
+D+S+H
+D+O 750Lr+0.750L +1-i
+D+O 75DL+O 750S+H
+D+0.60W+H
+D+O.?OE+H
.. c;+0.750Lr+O 750L +0450W+H
+D+0750L+0750S+0.450W+H
+0+0750L +0 750S+0525E+H
+0.60D+C6DW+0.60H
+0 600+0 70E .,{) 601-i
DCnly
Lr
LOniy
s
W Only
EOnly
H Omy
X<~ Axis Reaction
@Base @Top
K
k
k
k
K
Maximum Deflections for Load Combinations • Unfactored Loads
, .. -~ ---~----Load Combination Max. X-X Deflec!ion Distance
1!1
~J+L+H 0.0000 0.000 tt
+D+Lr+H 0.0000 in 0,:)00 ft
+0+3+1-i 00000 in 0000 ft
+0+0 750Lr+O. 750l +1-i 0.0000 !11 0.000 ft
+0+0 750L +0.750S+H 00000 m OJJOO ft
+D+OGOW+H 0.0000 J.ODO ft
+0+0 70E+H 00000 in 0.000 it
+0+0.750Lr+C.750L+0.450W+H LOOOO 1r 0000 ft
+0+0 750L+0.750S+0450VJ+H 0.0000 In !:LOOO ft
+0+0750L+075DS+0525E+H 0 0000 In 0.000 ft
.;{) 60D+0.50W+0.60H 0.0000 in 0 000 ft
+0 OOD-H) 70E+O 60H 0.0000 lrJ (1000 fr
D 00000 ir 0.000 h
Lr Oniy 0.0000 in 0.000 ft
L Only 0.0000 fn 0.000 ft s 0.0000 Wl 0.000 ft
VV Oniy 0.0000 0000 f1
E Only 0.0000 in O.GOO it
H Only 00000 in 0000 ft
~r?!eel Secti(ll'}f'~()E~rtie~ HSS5x5x1/4
'{-Y AXIS Reaction
@Base @Top
-0918
-0 688
-D 918
·1 311
Max. Y-Y Defiectior<
m
000 in
0000 lll
0000 ;n
0000 lf1
0.000 lfl
0.000 in
0626 in
0.000 in
0.000 in
0620 in
0.000 iP
0.826 lfl
OOOG '0
0.000 ·n
0008 in o.oo: in
0000 in
1180 in
0000 lfl
k
k
k
k
k
k
¥
K
k
k
k
Distance
0000
O:JOO
0.000
0000
0 000
0000
9 000
0000
0.000
t!OOO
0000
9.000
0.000
0000
0.000
0.000
0.000
9000
0,000
tt
ft
ft
ft
ft
ft
ft
4 H
ft
ft
ft
ft
It
ft
!t
ft
It
f!
f!
Axial Reaction
@Base
3.440k
3.440 k
6340 k
3440 k
5.6'5 k
3.440 k.
3 440 k
3440 k
5.615 k
3440 k
3440 k
2.064 k
2.064 k
3.440 k
2.900 k
k
Steel Column
Descnotion • Check Stee! Columns on Grid f;!, with vertical and lateral ioads
...... S~~~l§e~icm Propelties ~ HSS5x5x1/4
DeJ}!h 5000 ln XX J
Sxx 6.41 ;n'3
Wl(1ll1 5.000 m R XX 1 930 m
WaiiThick 0 250 if! Zx 610 rrr'3
Area 4300 in'2 I YY 15.000 in"'4 10.500 in"3
\<Veight 15 584 plf s yy 6.410 in"'3
R yy := 1930 m
Yen 0.000 m
M-x Loads
c ¢!
6 X 0 0 (J)
!fl I< :;;; f2'3
"' I
y "1' ...
Loads are total entered vah1€L Arrows do noi reHect absolute chrecbon,
Steel Column
Description : Check Steel Columns on Grld 1 wJ1q vertical and lateral loads
Code References
Calculations per AISC 360-10, !BC 2012, CBC 2013. ASCE 7-10
Load Combinations Used: lBC 2012
General Information
Steel Section Name .
Analysis Method :
Steel Stress Grade
Fy Steel Yield
HSS5x5x1/4
Allowable Strength
Overall Column
& Bottom
Brace condition ior deflection
9.0 It
Free, Bottom Fixed
columns
E Elastic Bending Modulus
load Combination
_ApQii~d .~fr.<l~.~····
Column self
AXi.ii,l _OADS ..
360 l<Si
29,000.0 ksi
IBC 2012
Roof A.xialloac al9.0 ft D " ' l-R ::: tG k
BENDiNG LO,ii.DS
ASD EQ Lat. Po;nt Load at S 0 ft 1v1x-x. E;: 1.223 K.
DESIGN SUMMARY
Bending & Shear Check Results
Max. Axiai+Bendino Stress Ratlo :::
Load Cornbmatror
Location of max.above base
Al maximum location values am
Pa. Ax1al
Po ! Omega : Ailowable
MiH Applied
Mn·x! Omega Allowable
Ma-y · Applied
Mn-y f Omega Allowable
PASS Maxlrnum Shear Stress Ratio=
Load Combiflation
Location of maxabove base
At maximum location values are
Va ,Applied
Vr ! Omega . Allowable
load Combination Results
.. , Load. Gombin?tiP11
+D+H
+D+L+H
+0-"Lr+H
+D~S+H
+D+0750LHJ750l +H
+D+0,750L '1{i.750S+H
+D+OSOW+H
+D+O 70E"'"H
+D+O. 750lr+0.750L +{}.45CW+H
+D+0.750L +Zl750S+O 450W+H
+D+O 750L -tiJ750S+O 5250E+H
+0.6DD+0.60W+0.60H
+0.500+0 70E+0.60H
0 012
0012
0.023
0.012
0.020
0.012
0012
0.570
0.020
0.012
0.429
0,007
0567
+D+0.70E+H
0.0 fi
1
U40 k
92.695 k
-7,705 k.-ft
13.671 k;-fj
0,0 k-ft
13.671 k.-ft
+0+0.70E+H
0.0 ft
O.OOft
O.OOft
0.0011
000ft
O.OO!t
0 OOft
0.00 1t
0.00 fi
0 OOft
0 OOft
0.00ft
0 OOft
0 OOft
c ..
aXIS
against buchnng a tong Y ~ Y AxiS
Maximum SERVICE load Reactions , .
along .X-X 0.0 k
0.0 k
0.0 k
Botlc:n along X-X
; 00 Y -Y
Y-Y 1.223 k
Maximum SERVICE Load Deflections ...
Y-Y UOI in at 9. Oft above base
load combination : E
X. X 0.0 in at 0 Oft above base
for load comb1na1ion .
MaximJm Shear Ratios
Stress Ratio Status location
0.000 0.00 It
0.000 0.00 ft
0.000 0.00 f'c
0.000 0.00 ft
0 000 0.00 ft
0.000 0.00 ft
0.000 0.00 ft
0.033 0 00 ft
0.000 0,00 ft
0.000 0.00 ft
0 025 0.00 ft
0.000 0.00 ft
0.033 0.00 tt
teal Column
Descr:plion: Check Steel Columns on Grid 1 with vertical and lateral oads
Maximum Reactions • iJnfactored
Load Combination
+D+H
+D+~+H
+D+<Jrl
+D+S+M
;{J-HJ750Lr+8750L +H
+D-ti:l. 75DL -!{1. 75GS+H
+0+860\N+H
+::i+870E+H
+0+8 750Lr+8J50L +8 450W+H
+D+0.750L +0.750S+8.450W+H
+D+0750L +0750S+0.525E+H
+0 500+8 60W·+O 60H
+0 5GD+{l70E-t{) 60H
D
X-X Axis Reactioo
@Base @Top
k
k
k
k
k
k
k
k
k
k
k
L Only k
so~ k w k
E Only k
H k
Maxrmum Deflections for Load Combinations • iJnfactored loads
Load Combmation
+D+l+H
+D+lr+H
+D+S+H
.._D+0750Lr+0750L +1-1
"'D+0750L +0750S+H
+D+OGOW+H
+D+O.?OE+H
+D+0.750Lr+0.750L+0.450W+H
.;{)+Q.750L+0.750S...0.450W+H
+D+O. 750L +8750S+O 525E+H
+0 600-t{).I:JOVV-t{) 60H
+JBOD..C,_7QE+OSOH
D
LrOnly
L Oniy
SOnly
WOnly
EOnly
H Only
0.0000 m
0.0000 in
0.0000 If)
0.0000
0 0000 :n
0.0000 111
0.0000
0.0000 in
00000 i!1
0.0000 n
(LOOOJ
00000
G,OODO
0 0000 c.oooo
0.0000
00000
0 0000
00000
ir
!n
. Steel Se~~c:>£lP.rop~r:tlEI~ ............. .. HSS5x5x1J4
Distance
fj
11C00 t!
11000 ft
0.000 fl
0.000 ft
0000 ft
0.000 ft
0.000 ft
0.000 fl
0.000 ft
0.000 ft
0.000 ft
0.000 ft
0 000 " " 0000 ft
G 000 " " 0.000 ft '
G GOO i1
0.000 ft c.ooo ft
Y-Y Axis Reaction
@Base @Top
-0.855
-0,642
-0,856
-1.223
Q_QQJ in
O.OCIJ in
0.000 If\
CdJQQ 111
OJJOQ in
0008
in
0.000 in
0000 in
0578 in
ODCD In
0.77~ m
n
0.000 ln
0 000 if1
i) OOJ iq
CLOGO ID
101 ln
0000 :n
,{
k
k
k
k
k
k
Distance
0()00
0.000
0000
0.000
0.000
0.000
0.000
0000
ODOO
9.000
1000
9.000
0000
GOOD
0000
0.00(!
0,000
SJJOO
0-000
lt
It
!t
lt
fl
ft
It
ft
fi
lt
!t
!t
if ~ i
it
ft
ft
ft
ft
ft .
Axiai Reaction
@Base
1.140 k
1140 k
2.140 k
11401\
1.890 k
1140 k
1140k
t140 k
1890 k
1.140 k
1140 k
0684 )<:
0.684 k
1.140 k
1000"
k
Steel Column
Description : ChecK Steei Columns on Grid ! wit~ vert1cal and lateral loads
\!Jidth
Wai!Th1ck
Area
Ycg
"' c 0 m
HSS5x5x1/4
5.000 ir
!],250 in
4.300 inA2
15 584 plf
() 000 in
y
. (;.(JOin
R XX
Zx
I yy
s yy
Ryy
X
6.41 in'·3
1.930 in
7.f310 lr/'3
16.000 111''4
6.410 ir:'3
1 930 in
"" 0
" .E' ,0 "' I
c
M-x Loads
I .,
Loads are mtai entered \laiue c Arrows do not reflect absolute direct>orL
Steel Base Plate
Description . Base Plate is Checked for Maximum moment conditions (Columns on Gnd 1.1
Code References
Calculations per AISC Design Guide# 1, IBC 2012, CBC 2013, ASCE 7-10
load Combination Set: IBC 2012
"'w
General information
Materia! Properties
,AISC Des1gn Method Allowable Strength Des:gn
Steel Plate Fy 36.0 hSt
Concrete Support f'c 3.0 ksi
Assurned Beanng Area ·Full Beanng
Column & Plate
Steel Section. HSS5x5x1/4
Deptn 5in
5m
0.233in
Width
Flange ihicKness
Web ihickness in
Area
lxx
Q c
Allowable
4 3 in"2
irl"·4
irA4
Plate Dimensions
t\ Length 18.0 lr
18.0 lfl
1 .Q If]
Dimensions
alono "X"
LengH1 ~ 'Z
36.0 ir
36.0 in 8 · \IV!dth
Thickness
Applied Loads
D . Dead Load .
L Live--·
Lr : Roof Live
S: Snow
vV ·Wind
E . Earthquake
H · Lateral Eanh
p.y
1.0 k
1.0 k
k
k
k
k
v.z
k
0-1580 k
M·X
k-fi
i<.-11
k·ft
k-It
7.920 k-it
k-ft
" P ""Gravity ioact. '+"sign is downward "..:· Moments create h1gher soil pressure al +Z edge.
"+' Shears push plate towards ... z edge.
Anchor Bolts
Anchor Bolt or Rod Description i .G
i~<1ax ofT ens ion or Puiiout Capac1ty
Shear Capacity .•. ., ...
Eoge distance ·bolt to plate ....
Numoer of Bolls in eacr, Row
Number of Bolt Rows . --..
7.847 k
5.719
2.50 In
20
10
Factor 2.50
5.10 ksi
• •
. ..
Base Plate is Ci1ecked for Maximum moment condittons (Cntumns on Gnd i l
Governrng Load Combinat;on
Governing Load Case Type
Design Plate Size
Pa . Axial Load __
Ma·Moment.
Load Comb. : +D+H
loading
Pa · Axial load
Design Plate Heigh:
Design Plate V'iidth
A i . Plate Area
A2: Support Area .
SQrti A21A1)
'm' ..
• n"
X.
Lambda
n·
n· 'i..ambda
l =maxim. n. n")
Load Comb.: +D+L+H
Loadin.g
Pa · Axial Load ..
Des~gn Plate Height .....
Design Plate Width .
A 1 : Plate Area
A2: Svpport Area
sqrr( A21Ai)
Distance for Moment Calculation ·~--'m'.
X ..
Lambda
n·
• Lambda ..................... ..
L " max(m. n. n'') .
Ailowable Strenqtr Desiqn
+0+0.70E+H
Axial+ Moment, U2 < Eccen:rici:v, Tenston on Be
1'·6" X 1'-6" X 1"
1 OODk
5.544 k-rt
1000 k
18.000 m
18.000
324000 !n'2
1296 000 in'·2
2000
6J325 in
6.625 in
0.000 in'2
0.000
0.010 in ::won in
6625in
tOOO k
18 000 ir;
18.000 in
324000 in'2
1,296 000 Jn''2
:::coo
6.625 tn
6.625 tn
CJ.OOO tn'2
0000
0 010 in
0.000 in
6.625 in
Mu : Max_ Moment " .
fb . Max. Bending Stress
Fb . Allowable :
Bending Stress Ratio
fu Max. Piale Beanng Stress
Fp . Allowaole :
mm( O.s5•fc'sqrt(A2iA 1) IP
Bearing Stress Ratio
Tens1on in each Bolt
Aiiowabie Bolt Tens1on
Tension Stress Ratio
fa . Max Bearing Pressure
Stress Ratio ...................... .
fb Acl!JaJ
Fb : Allowable
Stress Ratio ............. ., .... ..
fa . Max Bearing Pressure
Stress Ratio ..................... ..
1.721 k-111
6.884 kSI
21.557 kSI
2.040 ksi
2 040 ksi
Strsss OK
i.869
7.847
Axial Load Only, No Moment
2040 ksi
0.003 Ksi
0.002
O.J68 k-in
0.271 ksi
21.557 KSI
0.013
Axial Load Only, No Moment
2.040 ks:
0.003 ks:
0.002
0058 k-in
0.271 ksi
21.557 ksi
0.013
. Steel Base Plate
Description • Base Plate is ChEcked tor Maximum morrent conditions (Columns Gl'\ Grid 1 l
load Comb. : +D+lr+H
loading
Pa · Axia\ Load
Design Plate Height
Design Plate Width __
.A. i : Plate Area
.A-2: Support Area .. .
sort\ A21A1)
• f1"
X ..
Lambda
n'
n' 'Lambda.
L" max(m, n .. n") ....
load Comb. : +D+S+H
Loading
Pa • Axial Load .
Des1gn Plate He1ght ....
Des1gn Plate 'Nidth .
A: . Pla!e Area .
A2 Support Area
sort( A21A1)
2.000 k
18.000 1!1
18000 in
324000 in'2
1295000 in'2
2000
6 625 in
6J325 In
0.000 in'•2
0000
0010 in
0.000 lf1
6 625 in
1000 k
1BOOO in
18000 in
324.000 ir'·2
1,296.000 ir'·2
2.000
6.625 in
"n" 6.525 1n
X .. . . 0.000 1n·'2
Lambda 0.000
rt' Q (]1Q I[)
n' • Lambda 0 GOO 10
L" max(n\ n. n") 6 625 :n
fa · Max Beanng Pressure
Stress Ratio .... ._ ............ ,., ..
fh · Actl;a:
Fb Ailowatlie.
Stress Ratio ...... >« .. ._ ........
ib Actual
Fb Allowable
Stress Ratio ...... ._ .... , ........
Axial Load Only, No Moment
2.040 ksi
0.006 ksi
0.003
0 135 k-in
0.542 ksi
21557 ksi
0.025
Axial Load Only, No Moment
2.040 ksi
0003 ksi
0.002
0.068 k·in
0.27! ksi
21.557 ksi
0.013
load Comb. : +D+0.750lr+0.750l+H Axial Load Only, No Moment
A 1 Plate Ar€a
A2: Support Area __ .
sqrt{ A21A1)
Distance for Moment Calculation
~, m r. • ._,
1750 k
18.000 10
18.000 li1
324.000 in'2
1.296.000 Hl'2
2.000
6.625 n
6.625
0.000 ln'2 oooc
0010 ii1
0.000 in
6.625 in
fa tv1ax. Searing Pressure
Stress Ratio ..................... ..
tb .Actual
Fb : A\lowab!e
Stress Ratio ................... ..
2.040 ksi
0005KSI
0.003
0119k-in
0474 ks'
21.557 ks;
0.022
Steel Base Plate
Description Base Plate is Checked for Maximum moment conditiOns \Columns on Grk1 1)
Load Comb. : +D+0.750l+0.750S+H
Loading
Pa Ax1al Load
Design Plate Height ..
Des1gn Pia\e W1dth
A 1 : Plate Area
A2: Support Area
sqrt( A2iA1)
··n"
X
Lambda ..
n'
n· ·Lambda
L = max(m, n, n")
Load Comb. : +D+O.GOW+H
Load ...
Design Plate Height
Design Plate Vvidth ...
A 1 . Plate Area
A2 Support Area
sqrt( .tl2i A 1
"n"
X ..
Lambda ..
r'
r' • Lambda ..
L ~ max(m. n, rl")
Load Comb. : +D~O.SOW+H
load:ng
Pa : Axial Load
Design Plate Height .. .
Design Plate Width
A 1 _ ?late Area
A2: Supped Area ...
SQrt( A21A'1
Distance for Moment Calculation
"m".
H n ,,
X
Lambda
n' .. .. ................. .
n·· Lambda
i.DOO k
18 000 111
18000
324 000 inA2
1 296 :JOO in'2
2.000
6525 in
6.625 in
0 000 in'2
tlOOO
0.010 ill
C.OOC m
6.525 in
ooc h
18000 in
18.000 n
324 000 ~·2
t296000 m'2
2000
6.625 In
6 625 tn
0 000 tn'2
0.000
0010
0000 m
6.625 :n
1.000 k
18 ODC
18.000 'n
324.000 in'2
1.?9(},()00 i'1'2
2.00C
6.625 (I
6625
lJ lJ()() lfiA2 c ()()(!
0.010 !fl
0.000
6.625 !f)
flearing Stresses
Fp ·Allowable
!a Max. Bear.ng Pressure
Stress Ratio ...................... .
fb: Actual
;:ob : Allowable
Stress Ratio ................... ..
fa : Max. Bearng Pressure
Stress Ratio ...................... .
0 1ate 8end1r1g Stresses
Mmax ·oo Fu • L A2 i 2
ftl Actual
Fb : Aiiowable
Stress Ratio .................... .
fb Actual
Fb . Aliowable ..
Stress Ratio .................... .
Axial Load Only, No Moment
2.040 Ksi
0.003 ksi
0.002
0.068 k-!!l
0271 ksi
21.557 ksi
0.013
Axial Load Only, No Moment
2 040 ksi
0.003 ksi
0.002
0.068 k-in
0 271 ksi
21557 KSI
0.013
Axial Load Only, No Moment
2 040 ksi
C.003ksl
0.002
0 068 k-in
0.271 kSi
21557 ksi
0.013
..
Steel Base Plate
Description : Base Plate is Checked for Maximum moment concl!tons (Columns Gnd 1)
Load Comb. : +0+0.70E+H
Load ..
tvla Moment ..
Eccentric1ty .
A 1 · Plate Area
A2 Support Area ..
sort\ A21A!)
'K . Beanng Length
Mpl · Plate Moment
Load Comb.: +D-0.70E+H
Loadmg
Pa. Axial Load ...
Ma: Moment ......
Eccentncity
A 1 ; Plate Area
A2 · Support Area
sqrt{ A2fA 1 )
·A' , Bearing Length
Mpi : Piate Moment
tOGO K
5 544 ~-It
66528
324,000 inA2
1296 000 in'2
2000
6.625 in
0258 :n
0.143 t-in
1000 k
5 544 k-ft
66.528 lf1
324.000 in"2
1.296.000 1n·'2
2.000
6.625 tr
0.258 in
0.143 k-in
Load Comb. : +D+0.750Lr+0.750L+0.450W+H
Loading
Pa · A.xiai Load ..
Design Plate Height
Design Plate Width
A 1 · Plate Area
A2: Support Area ..
sqrt( A2iA1)
"n".
X ..
i..amboa
n·
rl' "Lambda
L ~ max(m. n, n"l
'1750 k
18 DOD 1n
18 DOD in
324 000 ln'2
~ .296 000 in'2
2000
6.625 in
6.625 in o.ooo ~In
0.000
001!) in
0.000 In
6.625 in
T ensior . Allowable
Stress Ratio ................... .
Dist from Boitto Col Edge ..
Effective Bolt V'iidth for Bending ..
Plate Moment from Bolt Tens1on .
Bearing Stresses
Fp ·Allowable ...
fa · f'J1ax Beanng Pressure
Stress Ratio ................... .
Allowable
Stress Ratio ................... .
Tension · F.liowable
Stress Ratio "" ............... ..
Dis! from Boltto CoL Edge . . . .
Effective Sol! Width for Bending .....
Plate Moment from BoltTension .
ia . Max Searng Pressure
Stress Ratio .................. ..
Fb . Ai:owable
Stress Ratio ..-............. ., ..
Bearing Stresses
F p Aiiowabie ...
fa : Max Bearing Pressure
Stress Ratio ..................... ..
fb: Actual .
Fb Allowable .
Stress Ratio .................... .
Axi•~f Load+ Moment, Ecc. > U2
1.869 k
7.84/k
0.238
4.125 in
16.500 in
C.934 k-in
2.040 ksi
(set equal to Fp !
1.000
i721 k·m
6.884 kSI
21.557 kSJ
0.319
Axial Load + Moment, Ecc. > L/2
t86S k
7 847k
0.238
4125 in
16.500 in
0.934 k-In
2.040 ksi
1 set equal to Fp;
1.000
~.721 k-in
6.884 ks:
2~.557 kSi
0.319
Axial Load Only, No Moment
2.040 ksi
Q 005 kSI
0.003
D.119k·in
0474 ksi
21.557 ksi
0.022
..
Steel Base Plate
Descript;on , Base Plate fS Chec~:ed tor Max1murF mome11 conditions (Columns on Grid 1 j
Load Comb. : +0+0.750Lr+0.750L-0.450W+H
A 1 : Plate Area
A2 :Support Area .
sqt:( A2iM)
. n,
X
Lambda ........... ,
n'
n' ·Lambda
L;:; max{m! ll n"}
1750 k
18.000 in
18.000 in
32 4 000 in·' 2
1.296 000 .n'2
2.000
6 625 in
63325 1n
CU}OD tn''2
0,(l00
0.010 in
0.000 in
6.625 in
Load Comb.: +0+0.750L+0.750S+0.450W+H
Load ...
Design Plate Hei!Jht
Des;gn Plate Width .
A1 Plate Area ..
A2 Support Area
sqrt( A2fA ., )
X
Lambda.
n'
n' • Lambda
L " max(m, n, n"l
1.000 k
18,000 iO
18.000 in
324 000 ;n'2
1 296.000 rn'2
2000
6525 in
iHi25 1n
0.000 •n·'-2
0.000
0 010 in
0.000 rn
6625 in
Load Comb. : +0+0.750L+0.750S-0.450W+H
A1 • Plate Area ..
A2• Support Area
sqr!( A2!A1 )
X
Lambda
n'
n' • Lambda
L" max(m, n. n")
1.000 k
18.000 n
18.000 ;n
324 COO rn"2
1.296 000 in·'2
2.000
6625 in
6 625 in
0.000 in'2
0000
0.010 II!
0.000 in
6.625 rn
~aring Stresses
Fp Allowable
fa : f·-Aal. Bearing Pressure
Stress Ratio ................ "" ... .
!b Actual
Fb Allowable ..
Stress Ratio ................... ..
Pressure
Stress Ratio ..................... ..
it. /v;tual
Fb AHcwable ..
Stress Ratio ................... ..
fb, Actual
Fb . Allowable
Stress Ratio .................... .
Axial Load Only, No Moment
2.040 k.si
0 005 ksi
0.003
0.119 k-111
0.474 kSl
21.557 ks:
0.022
Axial Load Only, No Moment
2040 ksi
0.003 ksi
0.002
0.068 k-in
Ci.2:71 ksi
21557 ksi
0.013
Axial Load Only, No Moment
2.040 ksi
0.003 ks:
0.002
0.068 1\-in
0.271 ksi
21.557 ksi
0.013
Steel Base Plate
Description . Base Plate is Checked for Maximum moment conditions (Columns on Grid i!
Load Comb.; +0+0.750L+0.750S+0.5250E+H
LoadiD.£l
Pa . Axial Load ..
Ma ·Moment
Eccentncity .............. ..
A 1 Plate Area
A2 : Supper' Area
So11( A2JA1 )
"A" : Beanng Length
Mol : Plate Moment
1 000 k
4.158 k·ft
49.896 in
324 000 in'2
1,296.000 in~2
2.000
6 625 in
0199 in
0111 k·n
Load Comb.: +0+0.750L+0.750S-0.5250E+H
Loadina ~,alload ..
Ma ·Moment
Ecoontr;city
A1 : Plate Area
A2 · Suoport Area
sqrt{ A2iA1 I
"A" · Beanng Length
Mo! Plate Moment
1 000 k
4.153 k·ft
49896 in
324.000 in'2
1.296.0GO in'2
2.000
6 625 in
[) 199 lf1
0.111 k·in
Load Comb. : +0.600+0.60W+0.60H
~ Pa . Axial Load ..
Design Plate Height ....
Design Plate Width .
A 1 : Plate Area
A2 Support Area
sqrt( A21A1)
"r,'
X.
:..amooa ..
n' .......
n· • Lambda ......................... .
L = max(m, n. n")
OJlOO k
1SOOO ir
1fHlOO ir
32LOOO 10'2
1,296.000 in"2
2.000
6.625 in
6.625 in
O.OOD in'2
0.000
O.OHl in
0.000 ir
ii625 ir
Tension. Allowable .
Stress Ratio .................. ..
Dist from Bolt to Col. Edge ..
Effective Bole Width for Bencmg ....
Piate Moment from Bolt Tension
ia . Max. Bearing Pressure
Stress Ratio ................... .
tb: Actual
Fb · Allowable ..
Stress Ratio ................... .
Tens1on Allowable
Stress Ratio ......... .,. ...... ..
Dist from Bolt to Cot Edge .
Effective Bolt W:dlh for Bendmg .
Plate Moment from Bolt Tension
!a . Max. Beanng Presswe
Stress Ratio ................... .
lb : Actual , .
Fb Allowable
Stress Ratio .... "' ........... ..
;3earing Stresses
Fp · Allowable
fa Max. Bearing Pressure
Stress Ratio ...................... .
fb. Actual
Fb Allowable
Stress Ratio ................... ..
Axial Load+ Moment Ecc. > U2
1327 k
7.847 k
0.169
4125 in
16.500 in
0.664 k-in
2.040 ksi
' set equal to Fp)
1.000
1331 k-If'
5.326 kSI
21557 kSI
0.247
Axial Load+ Moment, Ecc. > U2
1327 k
7847 k
0.169
4.125 in
16.500 IG
0 664 k-in
2.040 kSi
{ sel equal to Fp}
1.000
1331 k·i!1
5326 ksi
21557 ksi
0.247
Axial Load Only, No Moment
2.040 ksi
0.002 ksi
0.001
0.041 k-in
0 Hl3 ksi
21557 ksi
0.008
Description : Base Plate is Checked for Maximum morneflt conditions (Columns on Grid
Load Comb. : +0.600-0.GOW+O.GOH
Load
Design Plate Height ..
Design Plate Width
A 1 : P:ate Area
A.2 Support Area
sqrt( A2/Ai)
X.
Lambda
n'
n' 'Lambda ..
L "' max(m. n, n") ,. .
Load Comb. : +0.60D+0.70E+0.60H
Load ..
Ma. Moment ..
Eccentricity .
A 'i . Plate Area
A2 Support Area
sqrt( A2/A 1 )
',A," : Bearing Length
Mp! · Plate Momenl
Load Comb.: +0,60D-0.70E+0.60H
Load"
Ma. Moment
Eccentricity ..
A 1 Plate .Area .
A2 Support Area
sqrt( A21A1)
Calculate plate moment from bearing ..
"m'.
"A* , Beanng Length
Mpl Plate Momenl
0600"
18.000 in
1RDOD in
324.000 m'2
1 .296 000 in'i
2000
6.625 in
ti625 w
0.000 ir'2
CJDOO
0.()10 in
0000 in
6,625 in
0.600 k
5.544 k·ft
110.880 in
324 o:)o rn'2
1,296 JJJO rn'2
2.000
6J325 rn
0.249 ill
0.138 k-in
11600 k
5544 k-ft
110880 lr1
324 000 111'2
1,296.000 inA2
2.000
6 625 in
0.249 in
0 138 ~-in
!a Max. Beahlg Pressure
Stress Ratio ..................... ..
fb: Actt;a!--
i"b Allowable
Stress Ratio ............. .., ... ,
T ensior : Aliowaoie
Stress Ratio ................... .
Dnt. frorr Bert to CoL !:dge
S.ffective Sol: Width lor Bendi119 .
Plate Moment from Bolt Tension ..
!a ; Ma~. Bearmg Pressure
Stress Ratio ................... .
Fb Allowable
Stress Ratio ................... .
Tension · Aliowab:e ..
Stress Ratio ................... .
Dist from Bolt to Col Edge
Effective Bolt V\lidth tor Berdng ..
Plate Moment fron Boil T ensocm ..
fa _ iv1a:c Bearing Pressure
Stress Ratlo .................. ..
Plate Bending $tresses
Mmax.
fb Actual ..
Fb Allowable ..
Stress Ratio .................. ..
Axial Load Only, No Moment
2.040 ksi
IJ.DG2ksi
0.001
0.041 k-m
0.163 ksi
21.557 ksi
0.008
Axial Load+ Moment, Ecc. > L/2
1.984 k
7.847 k
0.253
4.125 in
13.500 in
0.992 k-in
2.040 KSI
1 set equal to Fp;
1.000
1.660 k-in
6.641 ksi
21 557 ksi
0.308
Axial Load+ Moment, Ecc. > U2
1.984 k
7.847 k
0253
4.125 in
16.500 lfl
0.992 k-in
2.040 ksi
{set equal to Fp J
1.000
1.660 k-in
6.641 ksi
21.557kSI
0.308
GRADE BEAM CAPACITY CALCULATIONS
Reqd ASD Moment =
Grade Beam Width =
Grade Beam Depth "'
Concrete Strength =
R/F Strength=
#of Bars T/B =
Bar Size=
Area of 1 bar=
Reqd USD Moment=
Stress Block, a =
Mn=
7.92 kip-ft
12 in
18 in
2500 psi
60000 psi
2
5
0.31 inA2
13.464 kip-ft
1.46 in
530866 lb -in
Or
44.2 kip-ft
3SUi:. ki · '
. General Footing
Description . Typrcai Footing is checked for maximum column axial loads. No moments are transferred Moments are carried by the Grade Beams
Code References
Calcu!aUons per AC! 318-11, lBC 2012, CBC 2013, ASCE 7-10
Load Combinations Used : IBC 2012
General Information
Material rc : Concrete
ly: Rebar Yield
Ec : Concrete Elastic Modulus
Concrete Density
(p Values Flexure
Shear
Analysis Settings
Mm Steel % Bendmg Reinf
Min Allow % Temo Reinf.
Min Overturning Safety Factor
MiG Sliding Safety Factor
Add Ftg Wt for Soil Press•Jre
Use ftg wt for stability, moments & shears
Add Pedestal Wt for Soil Pressure
Use Peoestal wt for stab1:ity, mom & shear
Dimensions
Width para:lello X-X Axis
Length parallel to 2-Z Axis
Footmg Thicknes
Pedestal dimensions ..
px : parallel to X-X Axis
pz. parallel to Z-Z A:~is
He;ght
Rebar Centerline to Edge of Concrete ..
.at Bottom of -
. ~f!if"'f<>.rcing
Bars parallel to X-X Axis
Number of Bars
Reinforcing Bar Size
Bars parallel to Z-Z Axis
Number of Bars
Reinforcing Bar Siz1
Bandwidth Distribution Check (AC!
Direction Requ:ring Closer Separation
# Bars required within zore
# Bars raouired or each side of zone
~ppli~d Loads
P . Colurnn Load
OB : Overburden
M-xx
M-zz
V-x
V-z
:::
" ...
"
4.0 !!
4.0 ft
18.0 in
in
m
in
3.0 In
5.0
# 5
5.0
# 5
n/a
n/a
n/a
2.50 ksi
60.0 ksi
3,1220ksi
145.0
0.90
0.750
0.00090
1.0
1.0 ' 1
Yes
Yes
No
No
Lr
2.90
Values
Bearing
Increase Beanng By Footing
Soi! Pass!Ve Res:stance
Soil/Concrete Fnction Coeff
De ott',
s'oil surface
'""'"lwd.ua:: pressure increase per fool of dept:=
when footmg base is below
Increases based on plar dimension
?.llowable pressure increase per foot of dep1 =
when max11nurn or width is grealer:;t
z
L s w
X
m 0. (0: ro
·~ !I
"i
E
1.50 ksf No
250.0 pcf
0.40
ft
ksf
ft
ksf
ft
k
ksl
k-ft
k-ft
k
k
General-Footing
Description · Footing is cnecked for maximum column axial loads. No moments are transferred into
DESIGN SUMMARY , ·"·······
Min. Ratio Item
P,il,S$
PASS
PASS
0.4033
nla
nli:l
Soil Bearing
Overturning -X-X
Overturning -Z-Z
nla
Pft.SS nla
-X-X
Siiding-Z-Z
Pil.SS nhl
().04239
PASS 0.04239
PASS 004238
0.04239
PASS 0.02920
PASS 0.02920
0.02920
0.0292C
PASS 0.05797
Detailed Results
S()i_! .!3~~~il1_g .~ ..
Rotation Ax.is &
... _Lo<Jd ~Qrnl:linatiQI'J·~,
X-X. +D+H
X-K +D+L+H
X-X. +D+Lr+H
X-X. +D+S+H
XX +0+0 750Lr+0.750L +H
X-X, +O+OJ50L+0.750S+H
X-X.
X-X.
X-X. +D+0.750Lr+0750L +0.450W+H
XX +D+0.750l+0.750S+0450W+H
X.-X. +0+0.750L +0.750S+0.525E+H
X-X .. -+l).60D+0.60W-+~160H
X-X. +060D-+JJ70E+0.60H z_z. ...-o.,.f-i
Z-Z. +D+L+H
ZZ. +D+Lr+H
Z-Z. +D+S+H
Z-Z. +D+0.750Lr-+{L750L+H
Z-Z. +D+0750L +0750S+H
Z-Z. -+D+O 60W+H
Z-l +D+070E+H
2-Z. +D+0.750Lr+O 750L·+'1450W+H
+D+O 750L +0. 750S+0.450W+H
-+D-+0 .750L -+0 750S+O .525E +H
Z-Z. +0.60D+0.60W-+l0.60H
Z-Z +0.60D+0.70E-+l0.60H
Overturning Stability
Rotation Axis &
Load Combination ...
Footmg Has NO Overturning
Sliding Stability
Force Application Axis
Load Combination ...
Footing Has NO Siiding
Gross Allowable
1.50
1.50
1,50
1_50
50
150
1,50
'!50
1.50
; 50
150
L50
150
1.50
1.50
150
1.50
150
1"50 1.50
1.50
1.50
Applied
0 6050 ksf
0.0 k-f!
0.0 k-ft
0.0 k
0.0 k
0.0 k
~.075 Ht
1.075 k ft
1,075 k-ft
1.075 k-ft
2.190
2 190 psi
2.190
2.190 psi
8.696 psi
Xecc Zecc
nfa 0.0
nfa 0.0
n!a 0.0
rua 00
n/a
n/a
n!a 1}0
n/a 0.0
n!a Q{)
r/a OJ}
n!a f\ 0 U,\,.
nia G.O
nla 0.0
0.0 nla
0-0 nla OD nra
0.0 n!a
O.G nla
0.0 n!a
0.0 nta
0.0 n/a
0.0 nia 01' ,v n/a
0{1 n!a
0.0 n!a
0.0 nla
Overturning rvt()lll~"t
Sli~ing ~()r~e .....
Capacity Governing load Combination
1.50 ksf +D+Lr+H about Z-Z axis
0 0 k-1: No Overturning
0.0 k-tt No Overturning
0.0 k No
0.0 k No Sliding
0.0 k No
25.361 k-fl ~ t20D-+1.60Lr+0.50L +i .60H
25.361 k fl +120D+1.60Lr+0.50L +1 .60H
25.361 k-fl +1.200+1 60Lr+0.50L +1.60H
25.361 k-f! +120D+1.60Lr-+050L +1 .60H
75.0 pSI +1.20D+l60Lr-+l0.50L+1 60H
75,C psi .... 120D+160Lr+0.50L +1.60H
7<;() { V<V +1.20D+1.60Lr+0.50L +1.60H
75J +1.20D+t60Lr+0.50L+160H
1500 +1201J+{ .60Lr+0.50L +1 60H
Actual Soi!Bearing Stress Actual f Allowable
+Z Left -X +X Ratio
0.4238 n/a nia
0.4238 nla n/a
0.6050 n/a nta
0.4238 n/a n/a
0.5597 0.5597 nia nia
0.4238 0.4238 ri/a n1a
0.4238 nla nia
0.4238 nla nia
05597 0.5597 nia nia
0.4238 0.4238 1';/3 n/a
04238 04238 n/a nla
0.2543 02543 r:Ja n/a
0.2543 02543 r:ia nra
nla nia 0.4238 04238
nia n/a 0.4238 0.4238
n!a nia 0.6050 0.6050 n;a nra 04238 0.4238
11!3 nh':l 0.5597 05597
rva nia {\4238 0.4238
n!a n;a 0.4238 04238
rva nla 0.4238 0.4238 n;a rra 0.5597 0.5597
n;a nia 0.4238 0.4238
nia n/a 0.4238 04238
nla nia 0.2543 02543 nia n/a 0.2543 0.2543
.... . ........................ Resisting M()El.~L-Status
All units k
Resi~tillJlForce .. SlidinR~ItfetyRatio
General Footing
Description , Typical
Footi~9 Flexure
Flexure Axis & Load Combination
X-X. + 1 400+1.60H
X-X. +1 400+1.60H
is check eo for milximum c:;iumn axial loads No moments ere transferred mto footing. Moments are c.arried by the Grade Seams
Mu Which Tension@ As Req'd Gvm.As Actual As Phi*Mn Status k-ft Side? Bot or Top? inf,2 !rr'2 m'2 k"ft
0.5775 .,.z Bottom () i944 Min Ternc% CL387~5 25.361 o~:
0.5775 -Z Bottom 0.1944 Min Terno% 0.3875 25361 OK
...
Descnption 1ypie<JI Footing IS checked for max;nun cciumn ax1alloads No moments are translermo into tioments are mrned by the Grade Beams
Fo()~ng Flexure
Flexure Axis & Load Combination Mu Which Tension@ As Req'd Gvm,As Actual As Phi'Mn
~At Side? Bot or Top? in"2 inA2 in'2 k.~ft
X-X. +i 200+0 50i..r+1 .60L+1.60H 0.5763 +Z Bot! om 0.1944 Min Temoc,t, 0.3875 25.361
X-X. + 1200+{) 50Lr +I 60L + i,60H OJ3763 -Z Bottom 01944 Mtn Terno% 03875 25361
X~K +1.200+1 .60:.. +0.50S+1.6CH 04950 +Z Bottom 0.1944 Min Terno 0;;., 03875 25.361
X-X. +1200+1 60L+D.50S+160H 0.4950 -Z Bottom 0.1944 Mu1 Terno% 0 387~3 25.361
X-.K +120D+160Lr+D.50L+1.60H 1.075 +Z Bottom 0.1944 Mm Temo% 0387lj 2536'\
X-X. +i.20D+t60Lr41).50L +1.60H 1075 -Z Bottom 0.1944 Mm Temo% 0.387:5 25.361
X-X + 1 20D+t60Lr+0.50VV+1.60H ~ .075 +Z Bottom 0.1944 Mrn Temp% 0.387i) 25.361
X-X +1 .20D+1.60Lr+D.50W+1 .60H i.075 ~z Bottom 01944 MinTemo% 0.387!5 25.361
X-X. +1.2004{1.5CL +1.60S+1.60H 0.4950 +Z Bottom 0.1944 MinTemo% O.J87!i 25.36!
X-X. +1.20D+D.50L +1.60S+1.60H 0.4950 -Z Bottom 0.1944 Min TemP% 0.3875 25.361
X-X. +120D+HOS+D.50W+1.60H 0.4950 +Z Bottom 0.1944 f•..1in Temo% 0.3875 25.361
X-X + 1.200+ 1 .60841) 50W+ 1 .60H .z Bouom 0.1944 Min Temo% 0.387ti 25.361
X-X. +120D41)50Lr41) 50L+VV+1.60H +Z Bottom 0.1944 rJin Temp% CJ87t} 25361
X-X +1.20D+D.50Lr+0.50L +W+l.60H -Z Bottom 0.1944 Min Temo% 0.3875 25.361
X-X +t20D+(t50L +050S+W+160H 049:50 +Z Boll om 0.1944 t·hn Temc% 0.3876 25.361
X-X . .-1.20041) 50L+0 50S+W+1 0.4950 .z Bottom 0.'1944 Min Temc% 03875 25.361
X-X. +1.20D41).50L41)70S+E+1 0.4950 +Z Bottom 0.1944 Min TemP% 03875 25.361
X-X. + 120D+0.50L +O?OS+E+ 1 60H -Z Bottom 0.1944 \Ain Temo% 0.3875 25.361
X-K 41) 90D+W+~'J90H +Z Bottom 0.1944 MinTemo% 0387£1 25361
X-X. +D90D+W4{1.90H 0.3713 -Z Bottom 0.1944 !v\in Temo% 0.387:'> 25.361
:X:-X. 41).900+E41) 90H 03713 +Z Bottom 0.1944 Min Temn% 0387E! 25.361
X-X. 41).90D+E+O 90H -Z Bottom 0.1944 Min Temo% 0.3876 25.361
Z-Z. +t400+1.60H -X Botton 0.1944 Mm Temo% 03875 25.361
Z-Z +140D+1.60H 0.5775 +X Bottom 0.1944 Min TemP%, 0.3875 25 361
+ 12QD41)5Qlr+ tOOL +i .60H 0.6763 .x Bottom 0.1944 MinTemo% 0.3875 25361
+1.20D+D.50Lr+1.60L +1.60H 06763 +X Bolt om 0.'\944 MinTemo% 0.3875 25.361
Z·Z.+1.20D-..i .60L +050S+1.60H 04950 -X Bottom 0.1944 Min Temo% 03875 25.361
Z-Z. +1.20D+1.60L +0.50S+1.60H 04950 +X Bottom 0.1944 MlnTemo% 0.3875 25.361
Z-Z. +1.200+1 .6Qlf41} SOL+ 160H 1.075 -X Bottom 0.1944 Min Temo% 0.3875 25361
Z-Z. +1.20D+160Lr41)50L+160H 1.075 +X Bottom ();944 Min Temo% 0 3875 25.361
Z-Z. +1.20D+t60Lr41) 50W+160H 1,075 X Bottom 0.1944 Mm Temo% D 3875 25.361
Z-2. +120D+Hi0Lr41).50W+1 .60H :075 +X Bottom 01944 Min Temo ~·'0 03875 25361
Z-Z. + 1.20D41).50L +L50S+t60H 0.4950 -X. Bottom 01944 Min Temo% 0.3875 25.361
Z-Z. +1.200+0.50L+160S+1.60H +X Bottom 0.1944 Min Temc% 0.3875 25.361
Z-Z. + 120D+IcOS+0.50W+i .60H -X Bottom 0.1944 Min iemo% QJ875 25.361 z.z. +1.20D+t60S+D.50W+i50H 0.4950 +X Bottom 0 i944 Min Temo% OJ875 25 361
Z -Z .... 120041) 50Lr41).50L +W+ 1 SOH 0.6763 -X Bottom 0.'\944 Min TemD% 0.3875 25.361
Z-Z. + 1.20D+0.50Lr+0.50L +\:'li+ 1 60H +X Bottom 0.1944 Min Temo% 0,3875 25.361
Z-Z. +UOD+O 50L 41).50S+W+t60H -X Bottom 0.1944 Min Temo% 0,387!5 25.361
Z-Z. +1.20041) 50L +{)50S+W+1 J30H +X Bottom 0.1944 Min Ternc% 03875 25.361
Z-Z. _,_1.20D+0.50L 41).70S+E+1.60H X Bottom (L 1944 Min Temo% ll3875 25361
Z-Z. +120D+D50L41).7GS+E+160H +X Bottom 0.1944 Min Temo% 25.361
..0 900+W41)90H -X Bottom CL19!4 Min Tenro% 25.361
+D.90D+W41).90H 0.3713 +X Bottom 0,1944 Min Temp% 25 361
Z-Z +D.90D+E+0.90H 0,3713 -X Bottom 0,1944 Min Temo% 0.3875 25.361
Z-Z. +0 90D+E+O 90H 0.3713 +X Bottom 0.1944 MinTemo% 0.3875 25.361
One Way Shear
Load Combination ... Vu@-X Vu@+X .. Yu@:2: .. yu@+Z Vu:Max PhiVn Vu /Phi*Vn
+1.400+1 .SOH U76csi 1176 osi ·": .>j-t"< .' i. l !b OSI 1176 osi 1.17€ osi 75 osi 0.01569
+1.20D+D.50Lr+1.60L +1.60H U78osi 1378osi 1378 osi 1.378 osi 1.378 nsi 75 osi 0.01837
+120D+1.60L +050S+1.60H l.008osi 1008csi 1008 PSi 1 008 osi 1008 osi 75 PSi 0.01344
+1.200+1 .60Lr+0.50L +1.60H 2.19nsi 2J9 osi 2.19 osi 2.19 osi 219osi 75 osi 0.0292
+1.20D+160Lr41).501N+1.60H 2.19osi 2.19osi 219 DSI 2 19 osi 219osi 7:5 osi 00292
+1.20D+0.50L+160S+1.60H 1.008 osi 1.008 OS' 1.008 csi l 008 PSI 1008osi 7:5 osi 0.01344
+1.20D+1.60S+0.50W+1.60H OSI 1.008os' 1.008osi i 008 PSI 1 008 osi 75 osi 001344
+ 1 200+0 50Lr+D.50L +W+ 1.60H PSi 1.378 osi 1378 osi 1378 osi 1378 osi 75 osi 0.01837
+120D41)50L+0 50S+W+1.60H osi osi osi 1.008 osi 1.008osi 75 osi 0.01344
•1.20D41).50L+0.70S+E+1.60H osi 1 osi osi 1.008 OSl 1.008osi 75 PSi 0 01344
41).90D+W+D.90H 0.7563osi 07563osi 07563 PSI 07563 PSi 0.75630S1 75 osi 0.01008
+0.90D+E41},90H 07563DSI 07563osi 0.7563 osi 0.7563 osi 0.7563 osi 75 DSi 0.01008
Status
OK OK OK OK OK OK OK
01(
OK OK
OK OK OK OK OK
OK
OK
OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK OK
OK
OK
Status
't f
OK
OK
OK
OK OK OK OK OK OK OK OK
OK
•'
General Footing
Description : Typical is checked for maximum column axia,> loads No moments are transferred nto footing. Moments are carried by the Grade Beams
Punching Shear
Loae!Combination~,------~ .. ,
+t40D+1.6QH
-.1 200+0 50Lr+i BOL +1 60H
+1.200+160L+050S+1.60H
+1 .200+1 .60Lr+0.50L+1 .60H
+ 1.200+ 160Lr+O 50W+1 60H
+1200+0 50L+1 .60S+1 .60H
+1.20D+160S+0.50W+1.60H
+1.20D+0.50Lr+0.50L +W+1.60H
+1 .200+0.50L +0.50S+W+1 .60H
+ 1 .200+0 50L +O..?OS+E+ 1 .60H
+0.90D+W+0.90H
+<J 90D+E +0 .90H
Vu
4.371
5.47
4,004
8696
B.696
4.004
4.004
547
4.024
4.004
3.003
3.003
Phi*Vn
50:>:>
50ns:
50
50cs
5Q:c;
500~,:
50,
SOns.
5(): . .<::
50:s-
50:·,>;
50m-
Vu 1 Phi*Vn
003114
0.03647
0.02669
0.05797
0.05797
!}02669
0.02669
0.03647
0.02669
0.02669
0.02002
!),02002
All umts k
Status
~,----~1~------------------------------------------------------------------~ BUILDING ENERGY ANALYSIS REPORT
PROJECT:
Narthex Addn, St. Michaels By-The-Sea Church
2775 Carlsbad Blvd.
Carlsbad, CA 92008
Project Designer:
02 Architecture
1089 N. Palm Canyon Drive, Suite B
Palm Springs, CA 92262
(760) 778-8165
Report Prepared by:
Tim Scott
Scott Design and Title 24, Inc,
77085 Michigan Drive
Palm Desert, CA 92211
(760) 200-4780
Job Number:
Date:
8/18/2015
The EnergyPro computer program has been used to perform the calculations summarized in this compliance report. This program has approval and is
authorized by the California Energy Commission for use with both the Residential and Nonresidential 2013 Building Energy Efficiency Standards.
This program developed by EnergySoft, LLC -www.energysoft.com.
EnergyPro 6. 7 by Energy Soft User Number: 6712 10:
Cover Page
Table of Contents
TABLE OF CONTENTS
Form L TI-01-E Indoor Lighting
Form L TI-02-E Lighting Controls
Form L TI-03-E Indoor Lighting Power Allowance
Form L T0-01-E Outdoor Lighting
Form L T0-02-E Outdoor Lighting Controls
Form L T0-03-E Outdoor Lighting Power Allowances
l EnergyPro 6.7 by Energy Soft Job Number: ID: User Number: 6712
1
2
3
9
12
16
20
23
STATE OF CALIFORNIA
INDOOR LIGHTING
---................ -·· -·-··-··-----· ·--· ·-·· -· ...... -· ·-· ·-........................................
CERTIFICATE OF COMPLIANCE NRCC-LTI-01-E i
Indoor Lighting (Page 1 of~6)
Project Name: Narthex Addn, St. Michaels By-The-Sea Church Date Prepared: 8/18/2015
------
A. General Information
Climate Zone: Conditioned Floor Area : 410
7 Unconditioned Floor Area : 0
Building Type: GZI Nonresidential D High-Rise Residential D Hotel/Motel
D Schools D Relocatable Public Schools ~ Conditioned Spaces D Unconditioned Spaces
Phase of Construction: D New Construction I!] Addition D Alteration
Method of Compliance: D Complete Building I!] Area Category D Tailored
Project Address: 2775 Carlsbad Blvd.
--
B. Lighting Compliance Documents (select yes for each document included)
For detailed instructions on the use of this and all Energy Efficiency Standards compliance documents, refer to the Nonresidential Manual published by the California Energy Commission.
YES NO FORM TITLE
,( NRCC-LIT-01-E Certificate of Compliance. All Pages required on plans for all submittals.
,( NRCC-LIT-02-E Lighting Controls, Certificate of Compliance, and PAF Calculation. All Pages required on plans for all submittals.
,( NRCC-LIT-03-E Indoor Lighting Power Allowance
,( NRCC-LIT-04-E Tailored Method Worksheets
,( N RCC-LIT -05-E Line Voltage Track Lighting Worksheets
----
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
INDOOR LIGHTING
,_,,__. IH~ ........... '-11 '-'1 '-1~._..v,._.._..., 'oJ'•-" ,,_, '-'' •~•• _., "'"' ~· ,,_,~ ....... I _.,,,.,.VIIVII.._._.,.._,, •
CERTIFICATE OF COMPLIANCE NRCC-LTI-01-E
Indoor Lighting (Page 2 of ~6)
Project Name: Narthex Addn, St. Michaels By-The-Sea Church Date Prepared: 8/18/2015
C. Summary of Allowed Lighting Power
Conditioned and Unconditioned space Lighting must not be combined for compliance
Indoor Lighting Power for Conditioned Spaces Indoor Lighting Power for Unconditioned Spaces
Watts Watts
Installed Lighting 105 Installed Lighting 0 1. NRCC-LTI-01-E, page 4 + NRCC-LTI-01-E, page 4 +
2. PORTABLE ONLY FOR OFFICES
NRCC-LTI-01-E, page 3 +
3. Minus Lighting Control Credits -0 Minus Lighting Control Credits -0 NRCC-LTI-02-E, page 2 NRCC-LTI-02-E, page 2
4. Adjusted Installed Lighting Power = 105 Adjusted Installed Lighting Power = 0 (row 1 plus row 2 minus row 3) (row 1 minus row 3)
5. Complies ONLY if Installed~ Allowed Complies ONLY if Installed~ Allowed
6. Allowed Lighting Power 615 Allowed Lighting Power 0 __ Conditioned NRCC-LTI-03-E, page 1 Unconditioned NRCC-LTI-03-E, page 1
D. Declaration of Required Installation Certificates !
Declare by selecting yes for all Installation Certificates that will be submitted. (Retain copies and verify forms are completed and signed.)
YES NO Form/Title
I NRCI-LTI-01-E-Must be submitted for all buildings D Field Inspector
I NRCI-LTI-02-E-Must be submitted for a lighting control system, or for an Energy Management Control System (EMCS), D Field Inspector to be recognized for compliance.
NRCI-LTI-03-E-Must be submitted for a line-voltage track lighting integral current limiter, or for a supplementary D Field Inspector I overcurrent protection panel used to energize only line-voltage track lighting, to be recognized for compliance.
NRCI-LTI-04-E-Must be submitted for two interlocked systems serving an auditorium, a convention center, a D Field Inspector I conference room, a multipurpose room, or a theater to be recognized for compliance.
I NRCI-LTI-05-E-Must be submitted for a Power Adjustment Factor (PAF) to be recognized for compliance. D Field Inspector
I
NRCI-LTI-06-E-Must be submitted for additional wattage installed in a video conferencing studio to be recognized for
compliance.
D Field Inspector
-
E. Declaration of Required Certificates of Acceptance
Declare by checking all of the Certificates of Acceptance that will be submitted. (Retain copies and verify forms are completed and signed.)
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
INDOOR LIGHTING
····---. ~.-··------~--· ·-·· -· •••••• -· ·-· --•................. w ......................
CERTIFICATE OF COMPLIANCE NRCC-LTI-01-E
Indoor Lighting (Page 3 of .6)
Project Name: Narthex Addn, St.Michaels By-The-Sea Church Date Prepared: 8/18/2015
YES NO Form/Title
.f NRCA-LTI-02-A-Must be submitted for occupancy sensors and automatic time switch controls . D Field Inspector
.f NRCA-L TI-03-A-Must be submitted for automatic daylight controls . D Field Inspector
.f NRCA-LTI-04-A-Must be submitted for demand responsive lighting controls . D Field Inspector
A separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces. Installed Lighting Power listed on this Lighting Schedule is only for:
D CONDITIONED SPACE D UNCONDITIONED SPACE
F. Indoor Lighting Schedule and Field Inspection Energy Checklist
D The actual indoor lighting power listed on this page and on the next page includes all installed permanent and planned portable lighting systems.
D When Complete Building Method is used for compliance, list each different type of luminaire on separate lines.
D When Area Category Method or Tailored Method is used for compliance, list each different type of luminaire by each different function area on separate lines
D Also include track lighting in schedule, and submit the track lighting compliance form (NRCC-LTI-05-E) when line-voltage track lighting is installed.
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
INDOOR LIGHTING
'-"' ._...,... I~ I ,,_,..., '-I I ...., I '-I ~ ... w ,.._....,._. ,_,....,, I...., '-'' ,._,. '-"I U ~" I ,_,~,_I , ...... I ............. IVIIVII.._..._..,._. I W
CERTIFICATE OF COMPLIANCE NRCC-LTI-01-E
Indoor Lighting (Page 4 of 6)
Project Name: Narthex Addn, St. Michaels By-The-Sea Church I Date Prepared: 8/18/2015
G. Installed Portable Luminaires in Offices-Exception to Section 140.6{a)
0 This section shall be filled out ONLY for portable luminaires in offices (As defined in §100.1). All other planned portable luminaires shall be documented on next page of
this compliance form.
0 This section is used to determine if greater than 0.3 watts of portable lighting is planned for any office
0 Fill out a separate line for each different office. Small offices that are typical (having the same general and portable lighting) may be grouped together. This allowance
shall not be traded between offices having different lighting systems.
Office Portable Luminaire Schedule Office Installed Portable Luminaire Watts Per Square Foot Office Location Field Inspector
1 2 3 4 5 6 7 8 9 10
Installed IfF :5 0.3,
.-z portable 0 Vl Watts enter -..a Identify Office area in c: c: ~ ~ ~. 3 luminaire per zero; "lJ ..,
::J c-"' ro ExG which these portable QJ QJ "' Complete Luminaire Description QJ rtl watts in 0 square "' -~· """'I --luminaires are installed -rtl rtl 0 n· ro foot (i.e., LED, under cabinet, furniture mounted Watts per "' -this office rtl .... ifF> 0.3,
direct/indirect) Lumina ire (B XC) (DIE) (F-0.3)
D D
D D
D D
D D
D D
Enter sum total of all pages into NRCC-LTI-
Total installed portable luminaire watts that are greater than 0.3 watts per square foot per office: Ol-E; Page 1
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
INDOOR LIGHTING
CEC-NRCC-L TI-01-E (Revised 05/15) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-LTI-01-E
Indoor Lighting (Page 5 of 6)
Project Name: Narthex Addn, St. Michaels By-The-Sea Church I Date Prepared: 8/18/2015
A separate Lighting Schedule Must Be Filled Out for Conditioned and Unconditioned Spaces. Installed Lighting Power listed on this Lighting Schedule is only for:
121 CONDITIONED SPACE 0 UNCONDITIONED SPACE
C. INDOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY CHECKLIST
Luminaire Schedule Installed Watts Location Field Inspector 1
A B c D E F G H
How wattage was
determined ro ~
"0 ro
Q) Vl .... .8 Vl = :.c .... Q) :; 00 ~ -~ 2 +" 0 tlll Complete Luminaire Description Q) .... OD-Vl c ro c. ·ro ~ <! c u aJ ro = -~ ~ Q) 1-Vl c ~ z :co ..c c
E E (i.e, 3 lamp fluorescent troffer, +" ·-0 0 E ·-Primary Function area in which +" E u E J:S t:; X ro Q) ro u ('() => E s 3 u.J 0 u ..... z 3 ~s~ z .:!::! F32T8, one dimmable electronic ballast) u .;: <! "" these luminaires are installed Pass Fail
15 W LEI 15 WLED 15.0 D IZl 7 105 Religious Worship D D
D D D D
D D D D
D D D D
D D D D
D D D D
D D D D
D D D D
D D D D
INSTALLED WATIS PAGE TOTAL: 105 Enter sum total of all pages into
NRCC-LTI-01-E; Page 2
L___ ------
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
INDOOR LIGHTING
---... ·---.. -. -. ·--·-----· . -, -· ·-·· -· ...... -··-· ·-. --·······--·-·.
CERTIFICATE OF COMPLIANCE N RCC-L TI-01-E
Indoor Lighting (Page 6 oL6)
Project Name: Narthex Addn, St. Michaels By-The-Sea Church Date Prepared: 8/18/2015
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Tim Scott Documentation Author Signature: ~~
Company: Scott Design and Title 24, Inc, Signature Date: 811812015
Address: 77085 Michigan Drive CEA Certification Identification (if applicable):
City/State/Zip: Palm Desert, CA 92211 Phone: (760) 200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance
(responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of
Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance
documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
s. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the
enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the
builder provides to the building owner at occupancy.
Responsible Designer Name: Responsible Designer Signature:
Company: 02 Architecture Date Signed:
Address: 1089 N. Palm Canyon Drive, Suite B License:
City/State/Zip: Palm Springs, CA 92262 Phone: (760) 778-8165
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
---... ,._ .... ~ .. ---. ·-··~----·.---. __ , ...... ______
CERTIFICATE OF COMPLIANCE NRCC-LTI-02-E
Indoor Lighting-Lighting Controls (Page 1 of))
Project Name Narthex Addn, St. Michaels By-The-Sea Church I Date Prepared: 811812 Q 15
The NRCC-LTI-02-E shall be used to document all mandatory and prescriptive lighting controls that are applicable to the project.
Mandatory Lighting Control Declaration Statements (Indicate if the measure applies by checking yes or no below.)
YES NO Control Requirements
Lighting shall be controlled by self-contained lighting control devices which are certified to the Energy Commission according to the Title 20 Appliance
,f Efficiency Regulations in accordance with Section 110.9.
Lighting shall be controlled by a lighting control a system or energy management control system in accordance with §110.9. An Installation Certificate
,f shall be submitted in accordance with Section 130.4(b).
,f
One or more Track Lighting Integral Current Limiters shall be installed which have been certified to the Energy Commission in accordance with §110.9 and
§130.0. Additionally, an Installation Certificate shall be submitted in accordance with Section 130.4(b).
A Track Lighting Supplementary Overcurrent Protection Panel shall be installed in accordance with Section 110.9 and Section 130.0. Additionally, an
,f Installation Certificate shall be installed in accordance with Section 130.4(b).
All lighting controls and equipment shall comply with the applicable requirements in §110.9 and shall be installed in accordance with the manufacturer's
,f instructions in accordance with Section 130.1.
,f All luminaires shall be functionally controlled with manually switched ON and OFF lighting controls in accordance with Section 130.1(a).
General lighting shall be separately controlled from all other lighting systems in an area. Floor and wall display, window display, case display, ornamental,
,f and special effects lighting shall each be separately controlled on circuits that are 20 amps or less. When track lighting is used, general, display,
ornamental, and special effects lighting shall each be separately controlled; in accordance with Section 130.1(a)4.
The general lighting of any enclosed area 100 square feet or larger, with a connected lighting load that exceeds 0.5 watts per square foot shall meet the
,f multi-level lighting control requirements in accordance with Section 130.1(b).
,f All installed indoor lighting shall be equipped with controls that meet the applicable Shut-OFF control requirements in Section 130.1(c).
,f Lighting in all Daylit Zones shall be controlled in accordance with the requirements in Section BO.l(dj and dayiit zones are shown on the pians.
Lighting power in buildings larger than 10,000 square feet shall be capable of being automatically reduced in response to a Demand Responsive Signal in
,f accordance with Section 130.1(e).
Before an occupancy permit is granted for a newly constructed building or area, or a new lighting system serving a building, area, or site is operated for
,f normal use, indoor lighting controls serving the building, area, or site shall be certified as meeting the Acceptance Requirements for Code Compliance in
accordance with Section 130.4.(a). The controls required to meet the Acceptance Requirements include automatic daylight controls, automatic shut-OFF
controls, and demand responsive controls.
L__
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 201S
STATE OF CALIF
---... ·---·. ---. ·--·-----· ·--· ·-·· -· ...... -··-· ............................ __ ,._..,. -.
CERTIFICATE OF COMPLIANCE NRCC-LTI-02-E
Indoor Lighting-Lighting Controls (Page 2 of 3)
Project Name Narthex Addn, St. Michaels By-The-Sea Church I Date Prepared: 811812015
A separate document must be filled out for Conditioned and Unconditioned Spaces. This page is used only for the following:
ILl CONDITIONED SPACES 0 UNCONDITIONED SPACES
MANDATORY AND PRESCRIPTIVE INDOOR LIGHTING CONTROL SCHEDULE, PAF CALCULATION, and FIELD INSPECTION CHECKLIST
PAF Credit Calculation 2
"' --1 -·
.,
(!) -
(!)
n "" )> o._ ,...,. (')
0 ;l:l (') ::l c:~~ n (!) (!) "" OQ "'' OJ ~no .c '0 '0
Standards Complying With 1 a.~~ A ..... ::l c ,...,. (!)
"tl X C1l rl" -· OJ (') "'' ::l ,...,.
::l (!) 0 )> o._ "'' (!) (')
( ..f all that apply, or enter 'E' if Exempted) .---· 0 0 Lighting Control Schedule OQ o._ -., -,...,.-o._ (!) "''
A B c D E F G H I J K L M N 0
Type/ Description of Lighting
Control (i.e.: occupancy sensor, # <.01 <.01 <.01 <.01 <.01 <.01 <.01 I-' I-' I-' I-' I-' I-' .j:> I-' w w w w w .j:> "tl Location in Building automatic time switch, of ? ? 0 0 ? ? ? OJ
.,
O'l "" OJ
I-' ..2. I-' I-' ..!::. O'l "" dimmer, automatic daylight, Units w 2: ..'2. 0:: (!) w 0::
N
etc ... )
-0 D
D D
D D
D D
D D
D D
D D
Control Credit PAGE TOTAL (Sum of Column M): 0
IF MULTIPLE PAGES ARE USED, ENII:K SUM IU IAL Ot-Controi Credit for aii pages HERE (Sum of all Column iv1): 0
Enter Control Credit total
into NRCC-LTI-01-E; Page
1.
1. §130.1(a) =Manual area controls; §130.0{b) =Multi Level; §130.1(c) =Auto Shut-Off; §130.1(d) =Mandatory Daylight; §130.1{e) =Demand Responsive; §140.6{d) =
Additional lighting controls installed to earn a PAF; §140.6(d} =Prescriptive Secondary Side/it Daylight Controls.
2. Check Table 140.6-A for correct Factor. PAFs shall not be traded between conditioned and unconditioned spaces. As a condition to earn a PAF, an Installation Certificate is
also regujred to be filled out, signed, and submitted. ----
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STA
... ·---.. --. ·--·-----· . --· ·-·· --· ...... ~··-· .................................................
CERTIFICATE OF COMPLIANCE NRCC-L TI-02-E
Indoor Lighting-Lighting Controls (Page 3 of 3)
Project Name Narthex Addn, St. Michaels By-The-Sea Church Date Prepared: 8/18/2015
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Tim Scott Documentation Author Signature: d~
Company: Scott Design and Title 24, Inc, Signature Date: 811812015
Address: 77085 Michigan Drive CEA Certification Identification (if applicable):
City/State/Zip: Palm Desert, CA 92211 Phone: (760) 200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance
(responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of
Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance
documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the
enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the
builder provides to the building owner at occupancy.
Responsible Designer Name: Responsible Designer Signature:
Company: 02 Architecture Date Signed:
Address: 1089 N. Palm Canyon Drive, Suite B License:
City/State/Zip: Palm Springs, CA 92262 Phone: (760) 778-8165
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STA
---... ·---.. ~--. ---·-----· . --• •-•• -• "''' '-••-•' ' ...,.._..ov.,~.,._...._.,_.,,
CERTIFICATE OF COMPLIANCE N RCC-L TI-03-E
Certificate of Compliance-Indoor Lighting Power Allowance (Page 1 of4)
Project Name Narthex Addn, St. Michaels By-The-Sea Church I Date Prepared: 8/18/2015
ALLOWED LIGHTING POWER
A separate page must be filled out for Conditioned and Unconditioned Spaces. This page is only for:
JZJ CONDITIONED spaces D UNCONDITIONED spaces
A. SUMMARY TOTALS OF LIGHTING POWER ALLOWANCES
D If using Complete Building Method for compliance, use only the total in column (a) as total allowed building watts.
D If using Area Category Method, Tailored Method, or a combination of Area Category and Tailored Method for compliance, use only the total in column (b) as the total
allowed building watts
(a) (b)
1. Complete Building Method Allowed Watts. Documented in section B of NRCC-LTI-03-E (below on this page)
2. Area Category Method Allowed Watts. Documented in section C-1 of NRCC-LTI-03-E (below on this page) 615
3. Tailored Method Allowed Watts. Documented in section A of NRCC-LTI-04-E 0
TOTAL ALLOWED BUILDING WATTS. Enter number into correct cell on NRCC-LTI-01, Page 2, Row 1 1615
D Check here if building contains both conditioned and unconditioned areas.
B. COMPLETE BUILDING METHOD LIGHTING POWER ALLOWANCE
A B c D
WATTS COMPLETE ALLOWED
TYPE OF BUILDING (From §140.6 Table 140.6-B) PER (fe) X BLDG. AREA = WATTS
Total Area:
Total Watts. Enter Total Watts into section A, row 1 (Above on this page)
C -1 AREA CATEGORY METHOD TOTAL LIGHTING POWER ALLOWANCES (C-2 plus C-3) Watts
Total from section C-2 . 615
Total from section C-3 . 0
Total Watts. Enter Total Watts into section A, row 2 (Above on this page) . 615
--
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
--~ ................................. .__ ........ w ............... ....,..,, ....... "-"~""U ... II '-'' '1.1'1111£"""\ L-l'IIIL..I'\'-J I VVIVIIVIIVVIVI'ill ·-"
CERTIFICATE OF COMPLIANCE NRCC-LTI-03-E
Certificate of Compliance-Indoor Lighting Power Allowance (Page 2 ot 4)
ProiectName Narthex Addn, St. Michaels By-The-Sea Church I Date Prepared: 8/18/2015
A separate page must be filled out for Conditioned and Unconditioned Spaces. This page is only for:
llJ CONDITIONED spaces D UNCONDITIONED spaces
C -2 AREA CATEGORY METHOD GENERAL LIGHTING POWER ALLOWANCE
D Do not include portable lighting for offices. Portable lighting for offices shall be documented only in section B of NRCC-LTI-01-E.
D Separately list lighting for each primary function area as defined in §100.1 of the Standards.
A B c D
'
AREA CATEGORY (From §140.6 Table 140.6-C) WATTS ALLOWED
Location in Building Primary Function Area per Table 140.6-C PER (te) X AREA (te) = WATTS
Narthex Zone Religious Worship 1.50 410 615
TOTALS 410
Enter sum total Area Category allowed watts into section C-1 of NRCC-LTI-03-E (this compliance form) 615
WATIS
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
--~ --------··-·· -·······-··-·· . ~ .............. ~-·-··
CERTIFICATE OF COMPLIANCE NRCC-LTI-03-E
Certificate of Compliance-Indoor Lighting Power Allowance (Page 3 of'4)
Project Name Narthex Addn, St. Michaels By-The-Sea Church I Date Prepared: 8/18/2015
A separate page must be filled out for Conditioned and Unconditioned Spaces. This page is only for:
1:21 CONDITIONED spaces D UNCONDITIONED spaces
C-3 AREA CATEGORY METHOD Additional Lighting Wattage Allowance {from Table 140.6-C Footnotes)
A B c 2 D E F G
ALLOWED
Additional Wattage WATIS
Primary Sq Ft or Watts Allowance Description(s) and Quantity of Special Total Design Smaller of
Function linearft 1 Allowed (B X C) Luminaire Types in each Primary Function Area Watts 3 D or F
TOTALS-Enter into TOTAL AREA CATEGORY METHOD ADDITIONAL ALLOWANCES-Section C-1 0
1. Use linear feet only for additional allowance for white board or chalk board. All other additional Area Category allowances shall use watts per square foot.
2 . Additional watts are available only when allowed according to the footnotes on bottom ofTable 146-C, which include: Specialized task work; Ornamental lighting;
Precision commercial and industrial work; Per linear foot of white board or chalk board; Accent, display and feature lighting; and Videoconferencing Studio lighting ..
3. Luminaire classification and wattage shall be determined in accordance with §130.0(c) of the Standards.
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
___ ,.,, .... .._._,, ___ ................... --··-..,,,._., ....,,., • .,,._, • .._,,.._., V''-'IYOIYII....,.._..I....,>•
CERTIFICATE OF COMPLIANCE N RCC-L TI-03-E
Certificate of Compliance-Indoor Lighting Power Allowance (Page 4 of'4)
Project Name Narthex Addn, St. Michaels By-The-Sea Church Date Prepared: 8/18/2015
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Tim Scott Documentation Author Signature: d~
Company: Scott Design and Title 24, Inc, Signature Date:811812015
Address: 77085 Michigan Drive CEA Certification Identification (if applicable):
City/State/Zip: Palm Desert, CA 92211 Phone: (760) 200-4 780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance
(responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of
Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance
documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the
enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the
builder provides to the building owner at occupancy.
Responsible Designer Name: Responsible Designer Signature:
Company: 02 Architecture Date Signed:
Address: 1089 N. Palm Canyon Drive, Suite B License:
City/State/Zip: Palm Springs, CA 92262 Phone: (760) 778-8165
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
:::,I A It:: Ut-l_;ALit-UKNIA
OUTDOOR LIGHTING
CEC-NRCC-L T0-01-E (Revised 05/15) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE N RCC-L T0-01-E
Outdoor Lighting (Page 1 of 4)
Project Name: Narthex Addn, St. Michaels By-The-Sea Church Date Prepared: 8/18/2015
Project Address: 2775 Carlsbad Blvd. Carlsbad, CA 92008 Total Illuminated Hardscape Area
0
General Information
Phase of Construction: D New Construction 0 Addition D Alteration
Outdoor Lighting Zone (OLZ) D OLZ-1 0 OLZ-2 Gi:l OLZ-3 0 OLZ-4
I have confirmed with the AHJ which OLZ applies to this site. For default lighting zone designations, see Title 24 Part 6, §10-114
LIGHTING COMPLIANCE DOCUMENTS (check box for each document included)
For detailed instructions on the use of this and all Energy Efficiency Standards compliance documents, refer to the Nonresidential Manual
published by the California Energy Commission.
(;zl NRCC-LT0-01-E Certificate of Compliance
Ql NRCC-L T0-02-E Outdoor Lighting Controls Certificate of Compliance
(;zl NRCC-L T0-03-E Outdoor Lighting Power Allowance Certificate of Compliance
Summary of Allowed Outdoor Lighting Power Watts
1. I Sum Total ALLOWED Outdoor Lighting Wattage from NRCC-LT0-03-E, page 1 = I 58
Complies ONLY if Installed~ Allowed ;
2. I Sum Total INSTALLED Outdoor lighting Wattage from NRCC-LT0-01-E, page 3 58
Declaration of Required Installation Certificates-Declare by checking all Installation Certificates that will
be submitted. (Retain copies and verify forms are completed and signed.)
121 NRCI-LT0-01-E-Must be submitted for all buildings D Field Inspector
121 NRCI-LT0-02-E-Must be submitted for a lighting control system, or for an D Field Inspector
Energy Management Control System (EMCS), to be recognized for compliance.
Declaration of Required Certificates of Acceptance-Declare by checking all of the Certificates of
Acceptance that will be submitted. (Retain copies and verify forms are completed and signed.)
0 NRCA-LT0-02-A-Must be submitted for outdoor lighting controls. D Field Inspector
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
;, I A It: Ur \JALirUKNIA
CALIFORNIA ENERGY COMMISSION e OUTDOOR LIGHTING
CEC-NRCC-L T0-01-E (Revised 05/15)
CERTIFICATE OF COMPLIANCE NRCC-L T0-01-E
Outdoor Lighting (Page 2 of 4)
Project Name: Narthex Addn, St. Michaels By-The-Sea Church I Date Prepared: 8/18/2015
Schedule of luminaires exempt from the outdoor lighting power requirements in §140.7
Name or Symbol Description of exempt luminaire in accordance with the exemptions
Schedule of luminaires exempt from the cutoff requirements in §130.2(b)
Name or Symbol Description of exempt luminaire in accordance with the exemptions
Schedule of luminaires exempt from the outdoor lighting control requirements in §130.2(c)
Name or Symbol Description of exempt luminaire in accordance with the exemptions
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
OUTDOOR LIGHTING
CEC-NRCC-L T0-01-E (Revised 06/14) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-LTO-Ol~E
Outdoor Lighting (Page 3 of'4)
Project Name Narthex Addn, St. Michaels By-The-Sea Church Date Prepared: 8/18/2015
---------
A. OUTDOOR LIGHTING SCHEDULE and FIELD INSPECTION ENERGY CHECKLIST
Luminaire Schedule Installed Watts Location Cutoff Field
Inspector
A B c D E F G H I
How wattage was ~ -I determined ~ 0 OJ ~ ~ r-z .......... c c ~ "' OJ c
Name or 3 ~ :P ~-3 n -· -Primary Function area in which Gl " ., Complete Luminaire Description -· ..... ..., n "" n ::J o-X ;::, :J ::xl OJ OJ
::J "' , m m g. ~ "' Item Tag o n ,_. n OJ ro these luminaires are installed OJ -~-"0 w 0 "' 3 0 ~-.., -v;· ~ !:!. ..., ro 0 0.. ro o ::J ro ..., z ~ o :r "' ...... OJ iii" oq :P Qj -;:;-"" ro a. 00 c ;:+ -8" OJ
15 W LED 15 W LED 15.0 D lrJ 3 45 Main Entrance D D
13 w 13 W LED 13.0 r:J D 1 13 Other Entrance/Exit D D
D D D D
D D D 0
D D D D
D D D D
D D D D
D D D D
D D D D
D D D D
D D D D
D D D D
D D D D
D D D D ..... ,...., 0 D w LJ
D D D D
D D D D
D D D D
D D D D
INSTALLED WATIS PAGE TOTAL: Enter sum total of all pages (Sum Total
58 INSTALLED Outdoor lighting wattage) into 58
NRCC-L T0-01-E; Page 1
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance June 2013
STATE OF CALIFORNIA
OUTDOOR LIGHTING
----·----~· ·-·· -••••••• -· ~-· ..................... ow .. w ......................
CERTIFICATE OF COMPLIANCE NRCC-LTO-U1."E
Outdoor Lighting (Page 4 ofA)
Project Name: Narthex Addn, St. Michaels By-The-Sea Church ______ I Date Prepared: 8/18/2015
-
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Tim Scott Documentation Author Signature: d~
Company: Scott Design and Title 24, Inc, Signature Date:811812015
Address: 77085 Michigan Drive CEA Certification Identification (if applicable):
City/State/Zip: Palm Desert, CA 92211 Phone: (760) 200-4 780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance (responsible
designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of Compliance
conform to the requirements of Title 24, Part 1 and Part 6oft he California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance documents,
worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the enforcement
agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the builder provides to the
building owner at occupancy.
Responsible Designer Name: Responsible Designer Signature:
Company: 02 Architecture Date Signed:
Address: 1089 N. Palm Canyon Drive, Suite 8 License:
City/State/Zip: Palm Springs, CA 92262 Phone: (760) 778-8165
-·-·-··------·-·-·----·----·-----·-
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance June 2013
STATE OF CALIFORNIA
---····---·----··--·-----· ·-._,,,._., .._,'"""'...._'"'-'""-'' '-'"-'IVIIVII ....... '-'1'-"1'0 ·-
CERTIFICATE OF COMPLIANCE N RCC-L TO-Cf'2··E
Outdoor Lighting Controls (Page 1 of,,3)
Project Name Narthex Addn, St. Michaels By-The-Sea Church Date Prepared: 8/18/2015
The NRCC-LT0-02-E shall be used to document all mandatory outdoor lighting controls that are applicable to the project.
Mandatory Outdoor Lighting Control Declaration Statements
Check all that apply:
D Lighting shall be controlled by self-contained lighting control devices which are certified to the Energy Commission according to the Title 20 Appliance
Efficiency Regulations in accordance with §110.9(a).
D Lighting shall be controlled by a lighting control system or energy management control system in accordance with §110.9. An Installation Certificate
shall be submitted in accordance with §130.4(b).
Ill All lighting controls and equipment shall comply with the applicable requirements in §110.9 and shall be installed in accordance with the manufacturer's
instructions in accordance with §130.1
D Part-Night Outdoor Lighting Controls, as defined in Section 100.1(b), shall meet the requirements in Section 110.9(b)S
D All outdoor incandescent luminaires rated over 100 watts, determined in accordance with Section 130.0(c), shall be controlled by a motion sensor.
D All outdoor luminaires rated for use with lamps greater than 150 lamp watts, determined in accordance with Section 130.0(c), shall comply with
Backlight, Uplight, and Glare (collectively referred to as "BUG") in accordance with Section 130.2(b)
D All installed outdoor lighting shall be controlled by a photocontrol or outdoor astronomical time-switch control in accordance with Section 130.2(c)1
IZl All installed outdoor lighting shall be circuited and independently controlled from other electrical loads by an automatic scheduling control in
accordance with Section 130.2(c)2
D All installed outdoor lighting, where the bottom of the lumina ire is mounted 24 feet or less above the ground, shall be controlled with automatic
lighting controls in accordance with Section 130.2(c)3
D For Outdoor Sales Frontage, Outdoor Sales Lots, and Outdoor Sales Canopies lighting, an automatic lighting control in accordance with Section
130.2(c)4
D For Building Facade, Ornamental Hardscape and Outdoor Dining lighting, an automatic lighting control in accordance with Section 130.2(c)S
IZl Before an occupancy permit is granted for a newly constructed building or area, or a new lighting system serving a building, area, or site is operated for
normal use, indoor lighting controls serving the building, area, or site shall be certified as meeting the Acceptance Requirements for Code Compliance in
accordance with §130.4.(a). Outdoor lighting controls shall comply with the applicable requirements of Section 130.2(c) and Reference Nonresidential
Appendix NA7.8
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
OUTDOOR LIGHTING CONTROLS
CEC-NRCC-L T0-02-E (Revised 05/15) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE
Outdoor Lighting Controls
Project Name Narthex Addn, St. Michaels By-The-Sea Church l Date Prepared: 8/18/2015
MANDATORY OUTDOOR LIGHTING CONTROL SCHEDULE and FIELD INSPECTION CHECKLIST
Standards Complying With Outdoor Lighting Control Schedule (v' all that apply, or enter 'E' if Exempted)
A B c D E F G H
Type/ Description of Lighting Control (i.e.
motion sensor, photocontrol, outdoor # (.()'> (.()'> (.()'> (.()'> (.()'>
I-' I-' I-' I-' I-'
Location and Application of w w w w w
!=> !=> !=> !=> astronomical time-switch control, of 0
Luminaires being controlled N N N N N ~ ~ n-centralized time-based zone lighting Units a;-.!2..
I-' N w ':iS:
control)
~
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance
I
(.()'>
I-' w !=> N
.!2.. U'1
N RCC-L T0-02-E
(Page 2 of3) ,,
I
-I ' "'T'1
(0 :::;.; iii' (/) 0:: .... )>
:xl n :J ro n .0 (0 (/)
c "0 "0 -· .... (0
..... OJ n (0 :J .... a. n 0
(0 .....
N 0
"0 "'T'1 OJ OJ (/)
(/) -
D D'
D D
D D
D D
D D
D D
D 0
D D
D D
D D
0 0
D D
D D
D D
D D
D D
D D
May 2015
STATE OF CALIFORNIA
OUTDOOR LIGHTING CONTROLS
CEC-NRCC-LT0-02-E (Revised 05/15) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-LT0-03"-E
Outdoor Lighting Controls (Page 3 of 3)
Project Name Narthex Addn, St. Michaels By-The-Sea Church I Date Prepared: 8/18/2015
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: T" S 1m cott Documentation Author Signature: ~~
Company: Scott Design and Title 24, Inc, Signature Date: 811812015
Address: 77085 Michigan Drive CEA Certification Identification (if applicable):
City/State/Zip: Palm Desert, CA 92211 Phone: (760) 200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance
(responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of
Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance
documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the
enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the
builder provides to the building owner at occupancy.
Responsible Designer Name: Responsible Designer Signature:
Company: 02 Architecture Date Signed:
Address: 1089 N. Palm Canyon Drive, Suite B License:
City/State/Zip: Palm Springs, CA 92262 Phone: (760) 77 8-8165
-----------------------------
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
OUTDOOR LIGHTING POWER ALLOWANCES
CEC-NRCC-L T0-03-E (Revised 05/15) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-LT0-03-E
Outdoor Lighting Power Allowances (Page 1 of4)
Project Name Narthex Addn, St. Michaels By-The-Sea Church I Date Prepared: 8/18/2015
A. OUTDOOR LIGHTING POWER ALLOWANCE SUMMARY
1. General Hardscape Lighting Power Allowance (Site Total from Section B of NRCC-LT0-03-E) 11. 0
2. Additional Specific "use it or lose it" Lighting Power Allowances listed in each of these cells shall be identical to total allowed watts
determined in Section C-1 to C-4 of NRCC-LT0-03-E.
PER APPLICATION PER UNIT LENGTH PER HARDSCAPE AREA PER SPECIFIC AREA
from Section C-1 (SALES FRONTAGE) (ORNAMENTAL LIGHTING) from Section C-4.
from Section C-2 from Section C-3
58 + 0 + 0 + 0 = I 2. 58
3. Sum Total ALLOWED Outdoor Lighting Wattage (add rows 1 and 2) I 3. 58
B. GENERAL HARDSCAPE LIGHTING POWER ALLOWANCE FROM TABLE 140.7-A
Area Wattage Allowance (AWA) Linear Wattage Allowance (LWA) Initial Wattage Total General Hardscape
Allowance (IWA) Lighting Allowance
A B c D E F G H I
Illuminated AWA Per Perimeter Length of LPA per LWA IWA Name of area AWA{BxC) D+G+H Hardscape Area Square Foot General Hardscape Linear Foot {Ex F) {Watts)
TOTAL 0
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
---····---------------------------------------------
CERTIFICATE OF COMPLIANCE NRCC-L TO-O<~~E
Outdoor Lighting Power Allowances (Page 2 of 4)
'
ProiectName: Narthex Addn, St. Michaels By-The-Sea Church Date Prepared: 8/1S/20 1S
---···------·-·· --
c. ADDITIONAL "USE IT OR LOSE IT11 OUTDOOR LIGHTING POWER ALLOWANCES FOR SPECIFIC APPLICATIONS i
0 The additional specific outdoor lighting power allowance shall be the smaller of the allowed lighting power or the actual lighting power used.
I 0 Use Outdoor Lighting Zone (OLZ) that is documented on page 1 of NRCC-LT0-01-E to calculate the specific wattage allowances. I
C-1. WATTAGE ALLOWANCE PER APPLICATION-Table 140.7-B
i
0 Available only for qualifying locations, which include Building Entrances or Exits; Primary Entrances to Senior Care Facilities, Police Stations, Hospitals, Fire Stations, and
Emergency Vehicle Facilities; Drive Up Windows; Vehicle Service Station Uncovered Fuel Dispenser I
0 If more than one luminaire type is used per location, use multiple rows for that location
A B c D E F G H I J
ALLOITED WAITS DESIGN WAITS
Wattage
Name of Location for Number of Allowance per Allotted Lumina ire
which allowance is qualifying qualifying Watts Code or Luminaire Watts per Design Watts Allowed Watts
claimed locations location (B X C) Symbol Luminaire Description Quantity luminaire (G x H) (smaller of D or I)
Main Entry 1 90 90 15 W LED 15 WLED 3 15.0 45 45
Cry Room Entry 1 90 90 13 w 13 W LED 1 13.0 13 13
Sum total allowance per application on this site: 58
C-2. WATTAGE ALLOWANCE PER UNIT LENGTH (Sales Frontage) from Table 140.7-B
0 If more than one luminaire type is used per location, use multiple rows for that location
A B c D E F G H I J
ALLOITED WAITS DESIGN WAITS
Name of Location for Wattage Allotted Luminaire
which allowance is Linear feet of Allowance per Watts Code or Lumina ire Watts per Design Watts Allowed Watts
claimed C-:lloC" l:rnn+-.I'Tro -'UI'-.;J I IUIIL06'C linear foot (B X C) Syrnbol Luminaire Description Quantity luminaire (G x H) (smaller of D or I)
Sum total allowance for sales frontage on the site:. 0
---------------------
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
-------·----··---------· ·----..... --------. --·······------
CERTIFICATE OF COMPLIANCE NRCC-L TO-O~
Outdoor Lighting Power Allowances {Page 3 of 4) ,_
Project Name: Narthex Addn, St. Michaels By-The-Sea Church Date Prepared: 811812015
---· --------------
C-3. WATTAGE ALLOWANCE PER SQUARE FOOT OF HARDSCAPE AREA (Ornamental Lighting) -Table 140.7-B
D Allowance for the total site illuminated hardscape area. Luminaires qualifying for this allowance shall be rated for 100 watts or less as determined in accordance with
Section 130.0{c), and shall be post-top luminaires, lanterns, pendant luminaires, or chandeliers.
D If more than one luminaire type is used per location, use multiple rows for that location
A B c D E F G H I J
ALLOTTED WATTS DESIGN WATTS
Name of area for which Wattage Allotted Lumina ire
ornamental allowance is Square feet of Allowance per Watts Code or Luminaire Watts per Design Watts Allowed Watts
claimed Hardscape square foot (B x C) Symbol Luminaire Description Quantity lumina ire (G x H) (smaller of D or I)
Sum total allowance for ornamental lighting on the site:. 0
C-4. WATTAGE ALLOWANCE PER SQUARE FOOT OF SPECIFIC AREA-Table 140.7-B
D Allowances for Building Facades; Outdoor Sales Lots; Vehicle Service Station Hardscape; Vehicle Service Station Canopies; Sales Canopies; Non-sales Canopies; Guard
Stations; Student Pick-up/Drop-off zone: Outdoor Dining; Special Security Lighting for Retail Parking and Pedestrian Hardscape.
D If more than one luminaire type is used per location, use multiple rows for that location
A B c D E F G H I J
ALLOTTED WATTS DESIGN WATTS
Name of Location for Wattage Allotted Lumina ire
which allowance is Illuminated Area Allowance per Watts Code or Lumina ire Watts per Design Watts Allowed Watts
claimed of Application square foot (B x C) Symbol Luminaire Description Quantity lumina ire (G x H) (smaller of D or I)
I
'
Sum total allowance for specific area on the site: 0
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
STATE OF CALIFORNIA
OUTDOOR LIGHTING POWER ALLOWANCES
CEC-NRCC-LT0-03-E (Revised 05/15) CALIFORNIA ENERGY COMMISSION
CERTIFICATE OF COMPLIANCE NRCC-LT0-~37~
Outdoor Lighting Power Allowances (Page 4 of4)
Project Name: Narthex Addn, St. Michaels By-The-Sea Church Date Prepared: 8/18/2015
DOCUMENTATION AUTHOR'S DECLARATION STATEMENT
1. I certify that this Certificate of Compliance documentation is accurate and complete.
Documentation Author Name: Tim Scott Documentation Author Signature: d~
Company: Scott Design and Title 24, Inc, Signature Date: 811812015
Address: 77085 Michigan Drive CEA Certification Identification (if applicable):
City/State/Zip: Palm Desert, CA 92211 Phone: (760) 200-4780
RESPONSIBLE PERSON'S DECLARATION STATEMENT
I certify the following under penalty of perjury, under the laws of the State of California:
1. The information provided on this Certificate of Compliance is true and correct.
2. I am eligible under Division 3 of the Business and Professions Code to accept responsibility for the building design or system design identified on this Certificate of Compliance
(responsible designer).
3. The energy features and performance specifications, materials, components, and manufactured devices for the building design or system design identified on this Certificate of
Compliance conform to the requirements of Title 24, Part 1 and Part 6 of the California Code of Regulations.
4. The building design features or system design features identified on this Certificate of Compliance are consistent with the information provided on other applicable compliance
documents, worksheets, calculations, plans and specifications submitted to the enforcement agency for approval with this building permit application.
5. I will ensure that a completed signed copy of this Certificate of Compliance shall be made available with the building permit(s) issued for the building, and made available to the
enforcement agency for all applicable inspections. I understand that a completed signed copy of this Certificate of Compliance is required to be included with the documentation the
builder provides to the building owner at occupancy.
Responsible Designer Name: Responsible Designer Signature:
Company: 02 Architecture Date Signed:
Address: 1089 N. Palm Canyon Drive, Suite B License:
City/State/Zip: Palm Springs, CA 92262 Phone: (760) 778-8165
---
CA Building Energy Efficiency Standards-2013 Nonresidential Compliance May 2015
BA
Project Address:
PLUMBING,
ELECTRICAL,
MECHANICAL
WORKSHEET
B-18
2775 CARLSBAD BLVD. CALRSBAD CA 92008
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
j3uilding@carlsbadca.gov
Permit No.:
Information provided below refers to worl:? being done on the above mentioned permit only.
This form must be completed and returned to the Building Division before the permit can be issued.
B-18
Building Dept. Fax: (760) 602-8558
Number of new or relocated fixtures, traps, or floor drains ....................................................... NONE
New building sewer line? ......................................................................................... Ves ___ No X
Number of new roof drains? ............................................................................................................... 2
Install/alter water line?......................................................................................................................... NO
Number of new water heaters?......................................................................................................... NONE
Number of new, relocated or replaced gas outlets? .................................................................... NONE
Number of new hose bibs? .................................................................................................................. NONE
Residential Permits:
New/expanded service: Number of new amps:
Minor Remodel only: Ves__ No
Commercial/Industrial:
Tenant Improvement: Number of existing amps involved in this project:
Number of new amps involved in this project:
New Construction: Amps per Panel:
200 AMPS
70AMPS
70 AMPS Single Phase ............................................................... Number of new amperes ________ _
Three Phase, ................................................................ Number of new amperes ________ _
Three Phase 480 ........................................................ Number of new amperes ________ _
Number of new furnaces, A/C, or heat pumps? ............................................................................ NONE
New or relocated duct worl:?? .......................................................................... Ves No X
Number of new fireplaces? ................................................................................................................. NONE
Number of new exhaust fans? ............................................................................................................. NONE
Relocate/install vent?............................................................................................................................. NONE
Number of new exhaust hoods? ......................................................................................................... NONE
Number of new boilers or compressors? ........................................................... Number of HP NONE
Page 1 of 1 Rev. 03/09