HomeMy WebLinkAbout2780 LOKER AVE W; ; CB931358; PermitB U I L D I N G P E R M I T Permit No: CB931358
Project No: A9301948
Development No:
03/01/94 11:06
1
Page 1 of 1
Job Address: 2780 LOKER AV WEST
Permit Type: INDUSTRIAL TENANT IMPROVEMENT
Parcel No: 209-081-25-00
Valuation: 15,000
Construction Type: VN
Suite:
Lot#:
Occupancy Group: B2 Reference#:
Description: PARTITION WALLS 10' STORAGE
Appl/Ownr : LEIGH AEROSYSTEMS
2780 LOKER AVENUE WEST
CARLSBAD, CA 92008
*** Fees Required
Fees:
~djustments:
Total Fees:
Fee description
Building Permit
Plan Check
Strong Motion Fee
* BUILDING TOTAL
Enter "Y" for Plumbi
Enter "Y" for Electri
Remodel/Alter Per AMP
* ELECTRICAL TOTAL
Enter 'Y' for Mechanical
Install Furn/Ducts/Heat P
* MECHANICAL TOTAL
619
CITY OF CARLSBAD
Status:
Applied:
Apr/Issue:
Entered By:
930-4060
ISSUED
12/20/93
01/07/94
DC
.00
305.00
24.00
***
Ext fee Data
162.00
105.00
3.00
270.00
10.00
25.00
35.00
15.00
9.00
24.00
N
y
y
SP. ~~f ~i~~~1
~EARANCE _____ 1
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
PLAN CHECK NO.
City of Carlsbad Building Department a • 2075 Las Palmas Dr •• carlsbad, CA 92009 (619) 438-1161 F.sT. VAL PLAN CK __ D_EPOSIT ___ ..3_,.. .. -3 ....... ----
VAIJD. BY DC
1. PfiltM.I I IYl4: DATE /,,2, I ,,3D 7 9~
A -U Commercial LI New Bmldmg U Tenant Improvement
B -Mlndustrial U New Building lll'Tenant Improvement
C -0 Residential Cl Apartment Cl Condo O Single Family Dwelling O Addition/ Alteration
0 Duplex O Demolition D Relocation O Mobile Home O Electrical Cl Plumbing
0 Mechanical Cl Pool Cl Spa Cl Retaining Wall Cl Solar C Other ____ _
2. PRQJF.Cf INFORMATION FOR OFFICE USE ONLY
Address ~'?8 0 Lo/i~,-t_ Afil.C/J,tL~dA1J Buildmg or Smte No.
Nearest Cross Street /.4l 9")J ~ A-/-~,, 1J· U
LEGAL DESCRIPTION Lot No. sutxhVIs10n Name/Nupber 1 1(.*i:::IJ. ~2. "(Jb lfl4f·t:I ',3o50
0mt No. Phase No.
CHECK BEWW IF sOBMll IEb:
D 2 Energy Cales a 2 Structural Cales a 2 Soils Report D I Addressed Envelope
/!;fl-4/f/~ ,._)4ll5
# OF STORIES /
ADDRESS /;CJ, /7'7J' Jf'Jtj_
?v; tf·
NAME Gt:1~D o.v t-, HA,1ll..lS
CI1Y R.., >, r_ STATE c4-
ADDRESS f, o, 6o Ji f/'5 I
ZIP CODE 9-ltJ(; fl DAY TELEPHONE
CI1Y STATE
ADDRESS
ZIP CODE DAY TELEPHONE
6. CDN'tRAciOR
NAME t,w r,t,t_ ADDRESS
CI1Y STATE ZIP CODE
LICENSE C1ASS
ADDRESS
DAY TELEPHONE
STATE UC.# CI1Y BUSINESS UC. #
DESIGNER NAME
CI1Y OWrt~fJ(/L STATE ZIP CODE DAY TELEPHONE STATE UC. #
1. WOIUMts' WMP£NSA110N
Workers' Compensation beclaratton: I hereby affirm that I have a certthcate of consent to self-insure issued by the Director of lndustnal
Relations, or a certificate of Workers' Compensation Insurance by an admitted insurer, or an exact copy or duplicate thereof certified
by the Director of the insurer thereof filed with the Building Inspection Department (Section 3800, Lab. C).
INSURANCE COMPANY POLICY NO. EXPIRATION DATE
Certthcate of Exemption: I certify that m the performance of the work for whtch thts penmt ts issued, I shall not employ any person m any manner
so as to become subject to the Workers' Compensation Laws of California.
SIGNATURE DATE
s. oWN"mt-llOIIDER DECi.ARAl1oN
Owner-Bm@er Declaration: I hereby afftrm that I am exempt from the Contractor's License Law for the followmg reason:
I, as owner of the property or ·my employees with wages as their sole compensation, will do the work and the structure is not intended or
offered for sale (Sec. 7044, Business and Professions Code: The Contractor's Llcense Law does not apply to an owner of property who builds
or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended
or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden
of proving that he did not build or improve for the purpose of sale.).
Cl I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions
Code: The Contractor's Llcense Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects
with contractor(s) licensed pursuant to the Contractor's License Law).
Cl I am exempt under Section ________ Business and Professions Code for this reason:
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish, or repair
any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the
provisions of the Contractor's License Law (Chapter 9, commencing with Section 7000 of Division 3 of the Business and Professions Code)
or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit
subjects a licant to a ivil penalty of not more than five hundred dollars [$500]).
SIGNATIJRE f'-DATE / ~
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and
prevention program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act?
C YES ilt'NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? a YES D NO
Is the facility to be constructed within l,QOO feet of the outer boundary of a school site?
C YES 11:r"'NO
IF ANY OF 1lIE ANSWERS ARE YFS, A FINAL CERTIFICATE OF CXDJPANCY MAY NOf BE 1$UED AFTER JULY 1, 1989 UNLF.'iS 1lIE APPUCANT
HAS MET OR IS MEETING 1lIE REQUIREMENTS OF nm OFFICE OF EMERGENCY SERVICF.S AND nm AIR POI.LUTION CDNlllOL rnsnucr.
9. wNslR0CuON Lf:NDING AGENCY
I hereby afhrm that there ts a construction lending agency for the performance of the work for whtch thts permit ts issued (Sec 3097(1) CtVIl Code).
LENDER'S NAME LENDER'S ADDRESS
lo. APPIJcAN't cmtlMCA'11oN
l certify that l have read the appltcat10n and state that the above mformatton ts correct. [ agree to comply wtth all Ctty ordinances and State laws
relating to building construction. I hereby authorize representatives of the City of Carlsbad to enter upon the above mentioned property for inspection
purposes. I AISO AGREE 10 SAVE INDEMNIFY AND KEEP HARMI.F.SS 1lIE CTlY OF CARISBAD AGAINSf AIL UABIUTIF.S, JUDGMENTS, CDSTS
AND EXPENSES WIIlCH MAY IN ANY WAY ACDUJE AGAINSf SAID CTlY IN CDNSEQUENCE OF 1lIE GRANTING OF 11IlS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height.
Expiration. Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the
building or work authorized by such permit is not commenced within 365 days from the date of such permit or if the building or work authorized by
such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days (Section 303(d) Uniform Building Code).
DATE: I J-l'lj 7 APPLICANTS SIGNATU:~ j /fatu;
WHITE: File YEU..OW: Applicant PINK: Finance
.,, .
CITY OF CARLSBAD
INSPECTION REQUEST
PERMIT# CB931358 FOR 03/~/94
DESCRIPTION: PARTITION WALI.S 10' STORAGE~!
TYPE: ITI
INSPECTOR AREA TP
PLANCK# CB931358
OCC GRP B2
CO~STR. TYPE VN
STE: LOT: JOB ADDRESS: 2780 LOKER AV WEST
APPLICANT: LEIGH AEROSYSTEMS
CONTRACTOR:
PHONE: 619
PHONE: 93=1 OWNER:
REMARKS: RS/LEE
SPECIAL INSTRUCT:
TOTAL TIME:
--RELATED PERMITS--PERMIT# TYPE
AS940008 ASTI
PHONE:
INSPECTOR-~~'----------
STATUS
ISSUED
CD LVL DESCRIPTION ACT COMMENTS
19 ST Final Structural $ _________ _
29 PL Final Plumbing
39 EL Final Electrical
49 ME Final Mechanical 1=------------------------------------------------------------
***** INSPECTION HISTORY*****
DATE
031594
030794
030794
030794
030794
022894
020794
011494
011294
011094
011094
021793
DESCRIPTION
Rough/Ducts/Dampers
Final Structural
Final Plumbing
Final Electrical
Final Mechanical
Final Combo
Compliance Investigation
Interior Lath/Drywall
Interior Lath/Drywall
Frame/Steel/Bolting/Welding
Rough Electric
Final Combo
ACT
AP co co co
co
co co
AP
NR
AP
AP co
INSP
TP
TP
TP
TP
TP
TP
TP
PD
TP
TP
TP
PD
COMMENTS
DUCTS SUP & RES
ND MECH PLANS
SEE NOTES
T-BAR INSP,C/0 LEFT
.• FAX COVER SHEET
• No. of Pages (Incl. cover):
• Destination FAX Number:
TO:
FROM:
DATE:
SUBJECT:
3
278-8539
ATTN: Mike
Chris-Air
Gene Ward
February 28, 1994
Building Inspection Cert.
LEIGH
Aerosystems Corporation
2780 Loker Avenue West
Carlsbad, CA 92008
Tel: (619) 930-4060
FAX: (619) 9304064
Comment the inspector wrote is, "Submit mechanical plan with
heating and cooling system for storage rooms# 1,2, and 3, as
built for approval. Permit required for mechanical work".
These are "storage" rooms and require temperature control for the
equipment to be stored. He said just the outlets and ducting
plan is required.
Mike, this is all we need for a final inspection, so we would
appreciate getting this cleared as soon as possible. The
following two (2) pages are a rough ceiling plan we used for the
sprinklers; perhaps you could use.
If you need anything from me, please give me a call.
Thanks,
4 /,U,pvC
Gene Ward
l0'd P90p0[66l9 d~OJ SW31SASO~3~ H8137 6c:01 P66l-Bc-a3~
FINAL BUitDING INSPECTION
DEPT: BUILDING ENGINEERING' FIRE PLANNING U/M WATER
PLAN CHECK#: CB931358
PERMIT#: CB931358
PROJECT NAME: PARTITION WALLS 10' STORAGE
ADDRESS:· 2780 LOKER AV WE~T
CONTACT PERSON/PHONE#: MH/GENE/930-4060
SEWER DIST: CA WATER DIST: CA
DATE: 02/17/94
PERMIT TYPE: ITI
BY: {,,L{l, INSPECTE~ft . ~t~!ECTED: c:;) !cJt-fM<J APPROVED L DISAPPROVED
INSPECTED
BY:
INSPECTED
BY:
COMMENTS:
DATE
INSPECTED:
DATE
INSPECTED:
APPROVED DISAPPROVED
APPROVED DISAPPROVED
DATE:
ESGIL CORPORATION
9320 CHESAPEAKE DR., SUITE 208
SAN DIEGO, CA 92123
(619) 560-14-68
LJ APPLICANT
JURISDICTION:
~DIC11IOI!>
nXiicHECKER
PLAN CHECK NO:
QFILE COPY
QUPS
0DESIGNER
PROJECT ADDRESS: ~13D \...o\~L< Q..>.NL,
PROJECT NAME: I\ I \ I --'----"--------------'---
D
D
0
D
The plans transmitted herewith have been corrected where
necessary and substantially comply with the .jurisdiction's
building codes. ·
The plans transmitted herewith will substantially-comply
with the jurisdic~ion's building codes when minor deficien-
cies identified-=-------------are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies
identified on the enclosed check list and should be corrected
and resubmitted for a complete recheck.
The check list transmitted herewith is for your information.
The plans are being held at Esgil Corp. until corrected
plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the
jurisdiction to return to the applicant contact-person.
0 The applicant's copy of the check list has been sent to:
IJ Esgil staff did not advise the applicant contact person that
plan check has been comnleted. -.
O Esgil staff did advise applicant that the plan check has
been completed. Person contacted: -------------
Date contacted: _________ Telephone# _______ _
D REMAR~S: ---------------------------
By: Q, \' ~{l_d,y<,. .. Enclosures:_~~-o-~-k-______ _
ESGIL CORPORATION '\3-
OcM
D.~TE:
ESGIL CORPORATION
9320 CHESAPEAKE DR., SUITE 208
SAN DIEGO, CA 92123
(619) 560-1468
JURISDICTION:
?LAN CHECK NO: (..b q3_ 13 53 SET: Z
PROJECT ADDRESS:_---::~~?~?~o=--~L~o~k~,rt.-.A~v~<...~-------
PROJECT NAME: //, /. -----'--------------------
D
D
D
II
D
The plans transmitted herewith have been corrected where
necessary and substantially comply with the jurisdiction's
building codes.
The plans transmitted herewith will substantially comply
with the jurisdic~ion's building codes when minor deficien-cies identified _____________ are resolved and
checked by building department staff.
The plans transmitted herewith have significant deficiencies
identified on the enclosed check-list and should be corrected
and resubmitted for a complete recheck.
The check list transmitted herewith is for your information.
The plans are being held at Esgil Corp. until corrected
plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the
jurisdiction to return to the applicant contact person.
9 The applicant's copy of the check list has been sent to:
0¢2,/1 ,.Jd$or, ~o. pc>,c. 3i'-{~ --:Z, s,;=-, C..,,
II Esgil staff did not advise the applicant contact person that
plan check has been completed.
O Esgil staff did advise applicant that -the plan check has been completed. Person contacted: ___________ _
Date contacted: _________ Telephone# _______ _
D REMARKS: ---------------------------
By: Al, ~ADr2.~' Enclosures: __ "'-~'-o~~~-'-=-------
ESGIL CORPORATION / f). ~ I
0 GA D CM (31>c
PLAN CHECK NO.: Co -13 -1358 ( :£)
rnsn1cnoN: Ca y f 2 t;,A..d
PROJECT DA'.I:A )
OCCUPANCY: 'iG;::,-~
BUil.J)ING USE: _ __,,a .... 1.,.,.,~..:..' ...,4-=-i/...:Y-.A"""""'"'<--= .... · h'-'-"o...,cJ-=~:;;.;..,_=---
TYPE OF CX>NSIRDC'.tIOH:_...,,.,¥'. __ ..;a_a...;.;!'-... '--------
ACIUAL ARF.A: A, )p t;..}:u. ""· ~ ,.__
ALLaiABLE ARF.A: ___ NQ'""""-"CbA::;....a:; .... t'l...i~ .... ,------
S'l'ORIES: _____ 0 ________________ _
BEIGHr: __ 1:a1.,.i..:,.:::=~-----------------
SPRDUCLERS: _ _..,,..~~) .... ,_L=-------------
OCCOPAHI LOAD:_..,.$ .... 0-_________ _
Date plans received by jurisdiction:
Date plans received by Esgil Corporation:
Date initial plan check completed:
___ 1 ..... J,+-] _d_l.....,..I ..... :1 ...... 3.....__By:_ .... S-......a .... d=-ve.. _____ _ I
Applicant contact person:
_ _.;;;;'b=-,.._l .,_I _____ Tel. C, 3o ,.. i..t-oLPD
FORE.WRD: .PLF.ASE READ
Plan check is limited to technical requirements
contained in the Uniform Building Code, Uniform
Plumbing Code, Uniform Mechanical Code, National
Electrical Code and i;;tate laws regulating energy
conservation, noise attenuation and access for the
handicappe~. The plan check is based on
regulations enforced by the Building Inspection
Department. You may have other corrections based
on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department
or other departments. Code sections cited are
based on the 1991 UBC. Clearance from those
. ·· ... -
departments may be required prior to the issuance · .-_. ·: _
R»IARKS: ____________________ _
of a building permit.
Ihe circled items listed need clarification,
modification or change. All items must be
satisfied before the plans will be in conformance
with the cited codes and regulations. Per Sec.
303(c), 1991 U~iform Building Code, the approval of
the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, note on this list
(or a copv) where each correction item has been
addressed, i.e., plan sheet, specification, etc.
Be sure to enclose the marked up list when vou
. submit the revised plans.
:NOTE: PAGE HtJmERS ARE HO? Ilf ~ AS PAGES HAVING NO IlE1S NEEDING CORREcrIONS WERE Dll.EIED.
LIST NO. 40 TENANT IMPROVEMENT WITHOUT SPECIFIC ENERGY ZONE DATA OR POLICY SUPPLEMENTS, 1991 UBC
-··--
.. · ..
. .. -·
• ··v
. --.·.-:-,·
0
I
G
G
)·
I
I
'
)·
r·
Please make all corrections on the original
tracings and submit two new sets of prints, to:
Esgil Corporation, 9320 Chesapeake Drive,
Suite #208, San Diego, CA 92123,
(619) 560-1468.
Please make all corrections on the original
t~acings and submit two new sets of prints, to:
The jurisdiction's building department.
Indicate on the Title Sheet of the plans, the
name of the legal 9wner and name of person
responsible for the preparation of the plans.
Section 302(d).
Each sheet of the plans must be signed by the
person responsible for their preparation, even
.though there are no structural changes.
Business and Professions Code.
Plans and calculations shall be signed by the
California state licensed engineer or architect
where there are structural changes td existing
buildings or structural additions. Please
include the California license number, seal,
date of license expiration and date plans are
signed. Business· and Professions Code.
Provide the correct address and suite number of
tenant space on the plans. Section 302(d).
Provide a note on the site plan indicating the
previous use of the tenant space or building
being remodeled. Section 302.
When the character of the occupancy or use
changes within a building, the building must be
made to comply with current Building Code
requirements for the new occupancy. Please
provide complete details to show the building
with comply. Section 502.
· UBC Section 304 requires the Building Official
to determine the total value of all
construction work proposed under this permit.
Ihe value shall include all finish work,
painting, roofing·, electrical, plumbing,
heating, air conditioning, elevator, fire
extinguishing systems and any other permanent
equipment. Please provide a signed copy of the
designer's or contractor's construction cost
estimate of all work proposed.
Provide a plot plan showing the distance from
the building to the property lines and the
location of tenant space (or remodel) within
tlle building.
8/4/92
(::\ On the first sheet of the lans ind · a · Q ype o construction o the exis..t.inwuilding,
present and proposed occupancy classifications
of the remodel area and the occupant load of
the remodel areas and the floor where the
f·
f·
tenant imptovernent is located.
Provide a note on the plans indicating if any
hazardous materials will be stored and/or used
within the building which exceed the
quantities listed in UBC Tables 9-A and 9-B.
A complete des·cription of the activities ,md
processes that will occur in this tenant space
should be provided. A listing of all
hazardous materials should be included. The
materials listing should be stated in a form
that would make classification in Tables 9-A
and 9-B ~ossible. The building official may
require a technical report to identify and
develop methods of protection from hazardous
materials. Section 901(f).
If control areas are used for exceeding the
exempt amounts of hazardous materials from
Tables 9-A and 9-B, they shall be constructed
of not less that required for a one-hour
occupancy separation. Section 404.
The number of control areas within a building
used for retail/wholesale stores shall not
exceed two; the number of control areas in
buildings with other uses shall not exceed
four. Footnote 1, Tables 9-A and 9-B.
l/j. The aggregate quantity of any hazardous
/ materials "in use" and "in storage" shall not
· exceed the quantity listed in Tables 9-A and
9-B for "storage". Footnotes 2 and 3, Tables
9-A and 9-B.
Q Provide a statement on the Title Sheet .of the ~ 1 plans that this project shall comply with
Title 24 and 1991 UBC, UMC and UPC and 1990
NEC.
0 Provide a fully dimensioned floor plan shov~
the size and use of all rooms or areas within
. the space being improved or a!tered. Draw the
plans to scale and indicate the scale on the
plan. Section 302(d). "",z.,O :>f'~'=5..,T-'+) •
1~ Indicate the use of all spaces adjacent to the
'/' area being remodeled or improved. r·
I·
Show any existing fire rated area separation
walls, occupancy separation walls, demising
walls, shafts OJ;' rated corridors. Identify
and provide-construction details for proposed
new fire rated walls.
Specify on the plans the fire ratings of
assemblies to protect penetrations or proposed
openings in existing or new fire walls, floor-
ceiling assemblies or roof-ceiling assemblies.
2
f·
Identify existing walls to be removed,
existing walls to remain and proposed new
walls. Identify bearing walls, non-bearing
walls, and shear walls.
Show safety glazing in the following
locations, per Section 5406(d):
a. Where the nearest edge of glazing is
within a 24-inch arc of either side of a
door in a closed postion (unless there is
an intervening wan between the door .and
the glazing .or if the glazing is 5' -011 or
b.
c.
higher above the walking surface).
Glazing greater than 9 square feet with
the bottom edge less than 1811 above the
floor and the top edge greater than 3611
above the floor (unless the glazing is
more than 3611 horizontally away from
walking surfaces o_r if a complying
protective bar is installed) •.
Glazing in shower and tub enclosures
(including windows· within 5 feet of tub
or shower floor), ~ Provide a section view of all new interior
\~ partitions. Show:
I·
G
G
1·
Type, size and spacing of studs. Indicate
gauge for metal studs. Specify
manufacturer and approval number or
indicate "to be ICBO approved".
Method of attaching top and bottom plates
to structure. (NOTE: Top of partition
must be secured to roof or floor framing,
unless suspended ceiling has been designed
for partition lateral load). /C,6:, 11t 'Jer ~Iv~ p,,.,,
Wall sheathing material and details of
attachment (size and spacing of
fasteners).
Show height of partition and suspended
ceiling, and height from floor to roof
framing or floor framing.
Provide notes and/or details to show that the
floor and wall finish in toilet · rooms are
surfaced· with a smooth hard non-absorbent
material extending five inches up the wall.
Similar surfacing shall be provided on the
walls from the floor to a height of 4 feet
around urinals and within water closet
compar_tments. Section Sl0{b).
Note on the plans: "All interior finishes must
comply w~ Chapter 42 of the UBC". Specify
"Class Jp... flame spread rating (minimum)
for C:Zc 2: , II
Note on plan that suspended ceilings shall
COll!PlY with UBC Tables 47-A and 23-P.
In buildings having floors and roofs of wood
frame construction, other than dwelling or
hotel occupancies, draft stop the area between
the ceiling and floor above so that no
concealed space exceeds 1,000 s.f. and no
horizontal dimension exceeds 60 L.F. (if space
has sprinklers, then 3,000 s.f. and 100 L.F.).
Section 2516(f).
7/8/92
G
i
I·
In buildings having floors and roofs of wood
frame construction, other than dwelling or
hotel occupancies, draft stop·the area between
the ceilin and roof above so a
concea e space exceeds 31000 s.f. and no
horizontal dimension exceeds 60 L.F. (if space
has sprinklers, then 9,000 s.f. and 100 L.F.).
Section 2516(f).
Storage areas exceeding 1000 sq. ft. in
connection 1.:ith wholesale or retail sales
shall be separated from t..~e public area by a
one-hour occupancy separation. If the entire
building has an automatic sprinkler system,
then the occupancy separation need not be
provided. Section 702(c).
An automatic sprinkler system shall be
installed in rooms used by the occupants for
the consumption of alcohol and in accessory
uses· where the total area of such unseparated
rooms and assembly uses exceeds 5000 square
feet. Section 3802(c).
0oi The tenant space and new and/or existing \Q facilities serving the ~emodeled area must be
accessible to and functional for the
physically disabled. See the attached
G
f·
correction sheet. Title 24, Part 2.
J1~ ,..rr.z a.,l( e.,,_ ,~T,;: c,..l;r,:; & Y<. ~ .<.., Co,. I ,
The width o the re uire v e
si e into which doors swing shall extend 24
inches past the strike edge for exterior doors
and 18 inches past the strike edge for
interior doors. Section 2-3304, Title 24.
,n e.,t,sJ,'ii C6rr,dtJY
Specify leve-type hardware for passage doors
on floors accessible to the disabled. Section
2-3304, Title 24 •.
If both sexes will be employed and the number
of employees exceeds four, provide separate
toilet facilities for men and women. If "both
sexes will be employed and the total number of
employees will not exceed four", and only one
restroom is provided, note the words in
quotation above on the floor plan. Section
705(c).
A -~....,...,...---hour occupancy separation is
required between _____ ...,..,_occupancy and
the ______ occupancy. Table 5-B.
Ducts penetrating occupancy or area separation
walls must have fire dampers. Section 4306
(j). .
C\ In areas where the occupant load exceeds 3o, \J two exits are required. See._=1;,:,-'",.'-'"'"-'.;>,._ ___ _
Table 33-A.
· ?A. Provide an exit analysis plan (may be 8 l/211 x
/~ 1111 or any convenient size). ~ Exits should have a minimum separation of on~-V half the maximum overall diagonal dimension of
the building or ~ea served. Section 3303(c).
~ '1t !>"8
3
G
I·
G
r·
f·
G
4/
0
j·
f·
¥·
r·
The maximum number of required exits and their
required separation must be maintained until
egress is provided from the structure. Section
3303(a). S....,....."fl 38
Rooms with more than 10 occupants may have~
exit through~ adjoining room. Revise exits
to comply. Section 3303(e).
Exit signs are required whenever two exits are
required. Show ali required exit sign
locations. Section 3314 (a).
Show that exits are lighted with at least one
foot candle at floor level. Section 3313(a).
Show the locations of existing exits from the
building and show.the path of travel from the
~emodel area to the existing exits.
Note on the plans: 11All exits are to be
openable from inside without the use of a key
or special knowledge". In lieu· of the above,
in a Group B occupancy, you may note "Provide a
sign on or near the exit doors reading THIS
DOOR TO REMAIN UNLOCKED DURING BUSINESS HOURS".
This signage is only allowed at the main exit.
Section 3304(c).
Exit doors. should be a minimum size of 3 feet
by 6 feet 8 inches with a mini.mum door swing ~f ·
90 degrees. Maxi.mum leaf width is 4 feet.
Section 3304(f).
Exit doors should swing in the direction of
egress when serving an occupant load of 50 or
more or when serving any hazardous area.
Section 3304{b). Applies to door(s) ___ _
Regardless of occupant load, a floor or landing
not more than 1/2 inch below the threshold is
required on each side of an exit door used for
disabled access (may be 111 maxi.mum where not
used for disabled access). Section 3304{i).
Doors should not project more than 7 inches
into the required corridor width when fully
opened, nor more than one-half of the required
corridor width when in any position. Section
3305(d).
Revolving, sliding and overhead doors are not
permitted as exit doors if the occupant load
exceeds 9 or the exit door serves a hazardous
area. Section 3304(h).
Provide panic hardware in Group A,E,H-l,H-2,H-3
and I occupancies. Chapter 33.
Double acting doors are not allowed when
serving a tributary occupant load of more than
100, or when part of a fire assembly, or part
of smoke and draft control assemblies or when
equipped with panic hardware. Section
3304(b).
5/28/92
G Corridors must provide continuous protection
to the exterior of the building.
· Interruptions by an intervening room, is not
permitted. Foyers, lobbies or reception rooms
constructed as requi-red for corridors are not
consJdered intervening rooms. Section 3305.
~sr 5S I Corridors and exterior exit balconies serving
10 or more occupants must be a minimum 44
inches wide and 7 feet high to the lowest
I·
0
proje<;tion. Corridors serving less than 50
occupants may be a mini.tr.Jill of 36 inches in
width. Section 3305(b).
When two exits are required, dead end
corridors and exit balconies are limited to 20
feet. Section 3305(e).
Corridors serving 30 or more occupants shall
have walls and ceilings of one-hour
construction. Show compliance or clearly show
on plans which of the following exceptions has
been satisfied:
./· Corridors greater than .30 feet wide when
the occupants have an exit independent
from the corridor.
0
!·
G
I
Exterior sides of exterior exit
balconies.
Corridor walls and ceilings need not be
of fire-resistive construction within
office spaces having an occupant load of
100 or less when the entire story in
which the space is located is equipped
with an automatic sprinkler system
throughout and smoke detectors are
installed within the corridor in
accordance with their listing.
Within office spaces occupied by a single
tenant, partial height partitions which
form corridors and which do not exceed 6
feet-in height need not be fire
resistive, provided they are constructed
in accordance with Section 1705 and are
.not more than three fourths of the floor-
to-ceiling height. Section 3305 (g).
Section 3305(g), Exceptions, cannot be used
for non-rated corridors in a fully sprinklered
office space if the occupant load in the space
exceeds 100.
Section 3305{g), Exception 5 does not apply to
common corridors where the corridor serves as
an exit for non-office areas (manufacturing,
warehouse, etc.).
Section 3305(g), Exception 5 is applicable
only for corridors on one floor; the corridors
on the lower level(s) must be rated if these
lower corridors have openings into them from
other·levels.
4
Section
to the Y If non-rated cor~idors are used per
3305(g), Exe. 5, provide a reference
corridors on the floor plan, noting:
1. Corridors are non-rated per Section
3305(g), Exception 5.
G
G
0
f
2·. Smoke detectors shall be maximum 30 1 on
center.
3. Power supply shall be dedicated branch
circuit. · Circuit disconnecting means
shall be accessible only to authorized
personnel and shall be clearly marked FIRE
ALARM CIRCUIT CONTROL, with a lock-on
device. ·
If a tenant space utilizes Section 3~05(g),
Exception 5, then that tenant space shall be
separated from adjacent spaces by a demising
wall constructed as for a one-hour corridor
wall. oJ1'lL / V"-"1!.~o~
Clearly show where the non-rated corridor
system terminates and a rated corridor system
coimnences.
One-hour fire-rated corridors shall have
interior door openings protected by tight-
fitting smoke and draft control assemblies
rated 20 minutes, except openings in interior
walls of exterior exit balconies. Doors shall
be maintained self·cloi:iing or be automatic-
closing by action of a smoke detector per
Section 4306(b). Poors shall be gasketed to
provide a smoke and draft seal where the door
meets the stop on sides and top. Section
3305(h).
Total area of all openings, except doors, in
any portion of an interior corridor, shall not
exceed 25 percent of the area of the corridor
wall of the room which it is separating from
the corridor.· Such openings shall be protected
by fixed glazing listed and labeled for a fire-
protection rating of at least 3/4-hour.
Section 330S(h).
0 Show rated corridors, lobbies, reception or
foyers cross-hatched on the floor plans.
~ Provide a complete architectural section of V the corridor, or exterior exit balcony,
showing all fire-resistive materials and
details of construction for all floors, walls,
ceiling and all penetrations. Section
0
3305(g).
Show the location of fire dampers. Provide
fire dampers at duct penetrations of fire-
rated occupancy and area separations, shafts
and corridor ceilings. Combination fire/smoke
dampers are required at duct penetrations of
rated corridor walls. Section 4306(j).
8/4/92
G
I·
G
If a room with an exhaust fan has a door
opening into a rat~d corridor, show how make-
up air will be provided to the room. The door
cannot be undercut, nor can a louver in the
door be provided. Section 3305(h)l.
If building exceeds two stories and· has an
elevator opening into a rated corridor, show
how the smoke and draft control provision of
Section 3305(h) will be met. Either provide a
separated elevator lobby or a second door at
the ele\'atcr entry oeeting the provision.
Section 3305(j).
If a second door is provided at the elevator
entry, note that it will be readily openable
from the car side without a key, tool or
special knowledge or effort. Section 5106.
New provisions in Chapter 43 of the 1991 UBC
require special treatment of penetrations at
fire-resistive assemblies. Provide typical
details on the plans showing how the fire-
resistive integrity will be maintained at the
f o 11 owing conditions ( Inc 1 u de the
manufacturers' names and .ICBO numbers (or
equal) for any sealant):
A, THROUGH-PENETRATIONS (through the entire
assembly):
1. Fire-resistive bearing walls and/or
walls requiring protected openings shall
have penetrations protected with through-
penetration fire stops having an F-
rating, I-rating or complying with UBC
Standard 43-1, depending on their
locations, sizes and combustibility.
2. Fire resistive floor/ceiling assemblies.
shall have pen~trations protected with
through-penetration fire stops having and
F-rating, T-rating or complying ~ith UBC
Standard 43-1, depending on their sizes,
combustibility and whether the
penetrations are in walls above.
B. MEMBRANE-PENE'IRATIONS (through only one
side of an assembly):
. 1. Fire-resistive walls (whether bearing· or
not and whether requiring fire protected
openings or not) shall have penetrations
protected with membrane-penetration fire
stops having an F-rating or complying
with UBC Standard 43-1, depending on
their size and combustibility. Limited
steel electrical. outlet boxes (not
exceeding 16 sq •. in., nor more than 100
sq. in. for any 100 sq. ft. of wall)
require no protection.
2. Fire-resistive ceilings shall have no
penetrations, except for noncombustible
sprinkler pipes and steel electrical
outlet boxes as described above.
NOTE: The plans should indicate the various
fire-stop ratings · require·d for all
penetrations.
Provide a note on the plans stating
"Penetrations of fire-resistive walls, floor-
ceilings and roof-ceilings shall be protected
. as required in UBC Sections 4304 and 430511 •
5
I·
I·
r· G
G
G
Ja.
I· ,.
f·
J'·
Provide evidence of Health Department approval
(for restaurants or for tenants using X-ray
equipment).
If nonflammable supply cylinders for medical
gas systems are located inside buildings, show
how they comply with UBC Section 702(c)4.
ELECTRICAL
Submit plan showing location of all panels.
Submit panels schedules.
Submit electrical load calculations
Indicate existing main service size.
Indicate existing total main service load.
Indicate new additional loads.
Indicate wiring method, i.e. EMT, metal flex.
Show exit signs on the electrical lighting
plan(s). As per Section 3313 and 3314 of the
1991 UBC, provide two sources of power to exit
signs and exit illumination.
Provide receptacle{s) within 25 1 of HVAC
units. UMC Section 509.
Provide multiple switch lighting controls per
Title 24, Part 6.
MECIANICAL
Provide mechanical ventilation in all rooms
capable of supplying a minimum of 5 cubic feet
per minute of outside air with a total
circulation of not less than 15 cubic feet per
minute per occupant. Section 605 and 705,
UBC.
Provide mechanical plans showing existing and
proposed HVAC equipment, ducts and I access to
equipment.
Detail access and working clearances to HVAC
equipment.
Detail disposal of main condensate drainage
from· air conditioning units. (UMC Section
510}
Detail overflow (secondary) co_ndensate
discharge from air conditioning units that are
in a ceiling space. (UMC Section 1205)
Fire rated corridors are not to be used to
convey air to or from rooms. UMC Section
1002.
PLtlmING
Provide gas line plans and calculations,
showing pipe lengths and gas demands. UPC
Section 1219.
8/4/92
Provide drain, waste and vent plans.
Provide water line sizing calculations. UPC
Section 1009.
G
Detail how floor drain trap seal is to be
maintained. UPC Section 707 (floor drain trap
priming).
Show P & T valve on water heater and detail
drain line route from P & T valve to the
exterior. UPC Section 1007(e) •• Al.=so :;,I-.,,..) c .. .::.c.,>-_,
1
1
·f·
.k t... s~,s '"'" c... s ~"'t, \o..-it. Show 1/411 per 12" s ope on drain and waste
lines. UPC Section 407.
Provide a drinking fountain at each floor
level in assembly occupancies (except drinking
and dining establishments). UBC Section 605.
Note on the plans that new water closets and
associated flushometer valves, if any, shall
use no more than 1. 6 gallons per flush and
shall meet performance standards established
by the American National Standards Institute
Standard All2.19.2, and urinals and associated
flushometer valves, if any, shall use no more
than one gallon per flush and shall meet
performance standards established by the
American National Standards Institute Standard
Al12.19.2. H & S Code, Section 17921.3{b).
EHERGI
G Provide complete energy design calculations,
including all existing design and new energy
design for this building. ice: alilc:Wieiil "'"
~acidU'ltial efte~gy dicis;a &beak•ict .Q. For remodels in an existing conditioned space, \J show that the remodeled space will not use
more energy than the existing space or show
the remodeled space will conform to lates.t
energy design standards.
. :==:dditional corrections or remarks
that follow.
Io speed up the recheck process, note on this
list (or a copy} whee each correction item has
been addressed, i.e., plan sheet, note or
detail number, calculation page, etc.
,Q Please indicate here if ~y changes have been Q made to the plans that _ are not a result of
corrections from this list. If there are
other changes, please briefly describe them
and where they are located in the plans.
Have changes been made to the plans not
resulting from this correction list? Please
check.
____ Yes _____ .No
6
The jurisdiction has contracted with Esgil
Corporation located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number
of 619/560-1468, to perform the.plan check for your
project. If you have any questions regarding these plan check items, please contact. _______ _
s~ dr-«
at Esgil Corporation
.Thank you.
Enclosures:
2. ____________________ _
3. _____________________ _
8/4/92 7
I·
J. The surface of ramps r· resistant. 2-3307{g)
shall be slip-
I·
I·
)·
j
I·
I·
I·
I·
A 60" :intermediate landing is required
at maximum elevation change of 30'' and
7211 landing at each change of direction
(over _30 degrees). 2-3307(d.l)
Landings are required at top and bottom .
of ramps. 2-3307(d.l)
Bottom landing shall be mini.I.r..i:n of 7211
in the direction of travel. Fig. 2-33-
llA
Top landing shall be 60" x 60" i:;inimum.
2-3307(d.l)
h'ben · door swings onto top landing,
mini::ru.m depth of landing required is
door width plus 4211 • 2-3307(d.l_.)
Top landing shall have 6011 .min. width
w~en door swings onto the landing, with
2411 on strike side of door at exterior
ramp, or 1811 at interior ramp.
2-3307{d.l)
Ramp handrails are required on each side
of ramp, when slope exceeds l·in 15. 2-
3307(e.l)
Ramp handrails shall be continuous,
located 30"-3411 in height above ramp
surface, with 1211 extensions beyond top
and bottom, and the ends returned.
2-3307{e.l)
m,i Handrails shall be 1-1/411 to 211 cross
/ section, spaced minimum of 1-1/211 from
wall. 2-3307{e.l)
I· A 211 high curb or wheel guide rail
centered 311 .:!: 111 above ramp surface is
required on both sides where not
otherwise bounded by walls when·the ramp
exceeds 10 feet in length.
2-3307(h.l)
SPECIAL ACCESS LIFIS
a. Lifts may be provided between levels, :in
lieu of elevator,· when the vertical
distance between .. landings, structural
elevator, structural design· and
safeguards are as allowed by the State
of California, Department of Industrial
Relation~, Division of Occupational
Safety and Health. .2-5107(a) .
The lift platform shall be of sufficient
si~e to acco1.1modate a wheelchair
(30"x48"). 2-5107{a)
/· There shall be a level and clear floor
area or landing {60"x60") at each level
for access to the lift. 2·5107(a) l HAZARDS
a. Provide 8011 headroom from .walkway
/ surface to any overhanging obstruction.
2-3326(b)
/
• Headroom of
maintained for
etc. 2-522(f)
80'' minimum shal 1 be
walks, corridors, aisles,
c/. Protruding objects with leading edges
/ between 27" and 80" above finished floor
shall not protrude more than 411 into
walks, corridors, etc. 2-522(f)
f Free standing objects mounted on posts
between 27" and 80" above the floor may
project a caximum of 1211 • 2-522(f)
/ Abrupt changes in level exceeding 411
adjacent to walks, except between walks
and adjacent streets or drives, shall be
identified by 611 high .. .-arning curbs above
walk surface. 2-3326(a)
EN'IRANCES AND CIRCOLATION
()ENTRANCES, DOORS, VESTIBULES AND CORRIDORS
(. All primary entrances to buildings shall
be accessible to the handicapped.
2-330l(f)
!· All required passage doors shall have 3211
clear opening at 90 degrees (3611 door).
2-3304(f)
I At least one of a pair of doors shall
• meet the minimum 3211 clear entrance width
requirement. 2-3304(f)
@ Threshold shall be no higher than 1/2"
above the floor. Edge to be beveled with
a slope no greater than l in 2, if more
than 1/411 • 3304{i.l)
0 Exterior level landing may slope up to
1/411 per. foot in any direction for
surface drainage. 2-413 ·
@ Door hardware shall be of the lever or
push type, mounted 3011 to 4411 above the
floor and be operable with a maximum
effort of 8.5 lbs. for exterior doors and
5 lbs. for :interior doors. 2-3304(c), 2-
3304(i.2)
W The lower 1011 of the door shall be of
smooth, plane surface (no recess or trap)
except at automatic and sliding doors.
2-3304(i.3)
Building entrance(s) shall be identified
by sign with the International Symbol of
Accessibility. Show location on plan.
The symbol shall be a white figure on
blue background. 2-522(b)
Y At turnstile, provide an access gate, 3211
clear width opening, within 30 feet of
·turnstile. 2-3304(i.4)
I There shall be a clear area on each side
of door, 6011 deep :in direction of door
swing and 4411 deep in opposite direction
of door swing. 2-3304(i.~)
20. BATHING FACILITIES
;l
I
One such facility shall
provided for the public,
employees. 2-511.l{a)
comply 1,;hen
clients or
Shower compartment shall be 4211 .,;ide,
4811 deep, with a 3611 wide entrance.
2-511.l(a)
Show on the plans that the handicapped
bathing facilities shall conform to
requirements of Sec. 2-Slla-9, 5-1505
and 5-1506, i.e., folding seat, flexible
shower hose, etc.
GENERAL REQUim{EXtS
1. DRINKING FOUNTAIN
.4.. Drinking fountains shall be within
{-alcoves. The alcove shall be not less
than 3211 wide by 1811 deep. 2-511.l(c)
I
c.
When the enforcing agency determines
that it would create .an unreasonable
hardship to locate the water fountain in
an alcove, the water .fountain may
project into the path of travel, and the
path of travel shall be identifiable to
the blind as follows:
(1.) The surface of the path of travel
at the water fountain shall be textured
so that it is clearly identifiable by a
blind person using a cane. The minimum
textured area shall extend from the wall
supporting the water fountain to 1 foot
beyond the front edge of the water
fountain and shall extend 1 foot beyond
each side of the water fountain, or
(2.) Wing walls shall be provided on
each side of the water fountain. The
wing walls shall project out from the
supporting wall at least as far as the
water fountain to within 6 inches of the
surface of the ·path of travel. Also,
there shall be a. minimum of 32 inches
clear between the wing walls.
Note on the plans that drinking fountain
shall conform to requirements of
Sec. 2-511c and 5-1507. 1· PUBLIC TELEPHONE
/
• Provide space 3011 x 4811 for forward or
parallel approach to telephone.
2-511.l(d)
'If. Note on the plans that public telephone
/ shall· conform to requirements of
(::\ Sec. 2-511.l(d_).
V, ELECIRlCAL REQUIRoo:NTS
0 15, 20 and 30 amp receptacle outlets
shall be installed not less than 1211
above floor. 3-210-50(e)
0 Center of switches shall be located.not
less than 3611 ·nor mor·e than 4811 above
the floor. 3-380-S(c)
/ • PLUMBING REQUIREMENTS .
/
. Where kitchenettes are provided at
employee break rooms, conference areas,
customer lounges, etc., the faucet
controls at kitchen sinks shall be
operable with one hand and shall not
require tight grasping, pinching or
twisting of the ',,,Tist (i .. e., use lever-
operated, push-type, etc.). If self-
closing valves are used, they shall
re1:1ain open for at least 10 seconds.
5-1508 . .
GROOP A OCCUPANCY REQUim{EXtS
f AUDITORIUMS, ASSEMBLY HALLS, THEATRES, ETC.
I Seating and toilet facilities for the
handicapped shall be accessible from the
main lobby or primary entrance.
I
;I.
I
2-6ll(b)
This structure requires -----,,,---,----
wheelchair seating spaces. In theaters
and auditoriums, the seating shall be
provided in a variety of locations so as
to provided a choice of admission prices.
2-6ll(b)
Each wheelchair space shall be 6011 x 3011
and level. 2-611(b)
When the seating capacity exceeds 300,
the wheelchair spaces shall be in more
than one location. 2-611(b)
rl. This structure requires ------,,.,,--/ -seats for semi-ambulant persons. Clear
).
leg space shall be at least 2411 •
2-6ll(b)
Stages, enclosed and unenclosed
platforms, orchestra pits, ticket booths,
and refreshment sales facilities shall be
made accessible. 2-611(b)
2j{: STADIUMS, GRANDSTANDS,. BLEACHERS, PAVILIONS,
/ GYMNASIUMS
This structure requires --------wheelchair seating spaces. In theaters
and auditoriums, the seating shall be
provided in a variety of locations so as
to provided a choice of admission prices.
2-6ll(c)
I When the seating capacity exceeds 300,
the wheelchair spaces shall be in more
than one location. 2-6ll(c)
1~
i.
I
Ticket booths must be accessible from
both sides. 2-611{c)
Participation areas such as ball courts.,
exercise rooms, tracks, and clubrooms
must be accessible. 2-6ll(c)
Spectator and participant sanitary and
locker facilities must conform to the
requirements of Chapter 2-5.
2-61l(c)
Date 1 )). / ~ l \ ~~ Jurisdiction LA<\::i~N;\
Prepared bys
60-4r~ VALUATION AND PLAN CHECK FEE
D :Sldg, Dept.
~sgil
PLAN CHECK NO, C .. :t::,q2,-\559 (J:) -BUILDING ADDRESS _,.ci'-l .... :8 ..... 0-.... N....,__,_IL....,,: __ .,, ___ {) __ ,V(._--=--'----------------
APPLI CANT/CONTACT __ '.s;:,-=-----' \ .... \_____ PHONE NO. __ U ____ ~_,.. __ + __ o .... h~Q,.___
BUILDING OCCUPANCY --~P=-~~,4.'--'"--DESIGNER PHONE ------
TYPE OF CONSTRUCTION __ --s:z-=-~-~N-'------CONTRACTOR PHONE ------
BUILDING PORTION BUILDING AREA VALUATION VALUE
MULTIPLIER ~. \,· \o) Ob-JS-5o, ("J"'OO -I '
Air Conditionine:
Comrner·c.ial @
Residential (cl
Res. or Comm.
Fire S'Drinklers @
Total Value ~o, znro,
,,--
Building Perm it Fee $ ___________________ $_ .... ;>"""8:-_~~·_,:5,c.i,::O __
Plan Check f'ee $ $ 1'8'4 ,q5 -"----------------------'"---'-.:::-'--.:..:::..--
COM MEN TS ... :-----------------------------
SHEET (D OF (D
12/87
:·: . ~ : ..
. : •.·
.... · -.
··,.:.·--~ .. -:"-.. .. . -.::-::· ; a-_;. __ -:
.-· •.
/~::::~::/
-.:··
.. : .·•
..... ..
·.-........ ~
. _: .... .-
.•;;. :.-
PLANNING/ENGINEERING APPROVALS
PERMIT NUMBER CB f 7-1 3,S ?DATE __ /.--,?;,._~_;?_o_/2_1/'_3 __
I
ADDRESS __ -t::c;),,,,,_7 __ ~_Q __ L_~_~__;_~_/€'..,.___,_4_~_&-_-'-tcPL..C...)Jf'"'-~C'--/ __
RESIDENTIAL
RESIDENTIAL ADDITION MINOR
( < $10,000.00)
TENANT IMPROVEMENT
PLAZA CAMINO REAL
VILLAGE FAIRE
COMPLETE OFFICE BUILDING
· OTHER
PLANNER 9):Jc_; DATE lZ / z,.Jr1 TI
.,,
ENGINEER .~¥ DATE <~
.
C:\WP51\FILES\BLDG.FRM Rev 11 /15/90
r,
City of Carlsbad . 93230
· Fire Department • Bureau of Prevention
Plan Review: Requirements Category: Building Plan Check
Date of Report: Monday, January 3, 1994 Reviewed by:~
Contact Name Bill Nelson
Address Po Box 3842 -----------------
City, State Rancho Santa Fe CA 92067
Bldg. Dept. No. 93-1358 Planning No.
Job Name Pacific Snax -----------------
Job Addre~s _2_7_80_L_o_ke_r _______________ _ Ste. or Bldg. No. ____ _
~ Approved -The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office ·to insure continued conformance·with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
D Disapproved -Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1st_· __ 2nd __ _ 3rd. __ _
Other Agency ID
CFD Job# __ 93_2_3_0 __ File# ___ _
2560 Orion Way • Carlsbad, California 92008 • (619) 931-2121