Loading...
HomeMy WebLinkAbout2810 Caribou Ct; ; PC2019-0081; PermitPERMIT REPORT Print Date: 05/08/2020 Job Address: Permit Type: Parcel No: Valuation: Occupancy Group: # Dwelling Units: Bedrooms: Bathrooms: Project Title: 2810 Caribou Ct BLDG-Plan Check 2091200300 $ 0.00 Plan Check Permit Work Class: Commercial Lot#: Project#: Construction Type Orig. Plan Check#: Plan Check#: {cityof Carlsbad Permit No: PC2019-0081 Status: Applied: Issued: PermitFinal Close Out: Inspector: Final Inspection: Closed -Finaled 11/14/2019 12/31/2019 05/08/2020 Description: INNOVATE CARLSBAD: SHELL TO OFFICE/WAREHOUSE AT SUITES 100, 120, 140 Applicant: WARE MALCOMB ARCHITECTS ANGELA RYAN 6363 Greenwich Dr San Diego, CA 92122-5947 619-564-5135 FEE Total Fees: Building Division Owner: Co-Applicant: VICTORY CARLSBAD OAKS INNOVATION CENTER LP TFW CONSTRUCTION DEVELOPMENT INC Po Box 220 1261 Prospect St C/0 Badiee Development, 9 DEL MAR, CA 92014 LAJOLLA,CA 92037 858-759-1223 AMOUNT Total Payments To Date : Balance Due: 1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov Page 1 of 1 Ccicyof Carlsbad COMMERCIAL BUILDING PERMIT APPLICATION B-2 1=t'-, 2DI 9 -c:oi-( Plan Check (J3 (2.D/9-0lf(( Est. Value j 1;2_ /<-(, Off. OL/ PC Deposit --------- Date ____,_q_,_/-'-2.+--'-'/........:...1-1-1-- Job Address 2810 Caribou Court Tenant Name: Badiee Development \()(') I \ zD I \40 Suite: 'A, C, E:, -e~ APN: 209-120-03 ----------- CT/Project#:, _________ Lot#:. ___ _ Occupancy: _B~S_-1 ______ Construction Type: _II_I-_B __ Fire Sprinklers: Yes 10 Air Conditioning: Yes o BRIEF DESCRIPTION OF WORK: FIRST GENERATION Tl WITH NEW LIGHTING, CEILINGS, NON-RATED/NON-LOAD BEARING PARTITIONS, ELECTRICAL, MILLWORK AND FINISHES WITH ASSOCIATED MECHANICAL, ELECTRICAL AND PLUMBING. IX] Addition/New: 26 104 New SF and Use, 8-Office, S-1, Warehouse New SF and Use, ____ Deck SF, ____ Patio Cover SF (not including flatwork) D Tenant Improvement: _____ SF, _____ SF, Existing Use ______ Proposed Use ______ _ Existing Use Proposed Use ______ _ □ Pool/Spa: ____ SF Additional Gas or Electrical Features? ____________ _ D Solar: ___ KW, __ Modules, ___ Mounted, Tilt: Yes/ No, RMA: Yes/ No, Panel Upgrade: Yes/ No D Plumbing/Mechanical/Electrical Only: _________________________ _ D Other: ______________ ~--------------------- f:;,1 e:...:a \LoCJ NA~. APPLICANT (PRIMARY) Name: WARE MALCOMB (BRITTANY MONTGOMERY) Address:3911 SORRENTO VALLEY BLVD1 SUITE 120 City: SAN DIEGO State~A Zip:9_2_12_1 __ Phone$!58.638. 7277 Email: bmontgomery@waremalcomb.com DESIGN PROFESSIONAL Name: _ ____,W ... A.._R=E_,,M.,_A=LC;..;:O=M=B....,(B=R=ITT"-'-'--AN .... Y ___ M __ O,_N __ T_...GO""'M=E=R....,Y}...__ Address: 3911 SORRENTO VALLEY BLVD, SUITE 120 City: SAN DIEGO State: CA Zip: 92121 Phone: 858.638.7277 Email: bmontgomery@waremalcomb.com Architect State License: C33185 ------------ PROPERTY OWNER Name: BADIEE DEVELOPMENT (SCOTT MERRY) Address: 1261 PROSPECT ST. STE. 9 City: LA JOLLA State: CA Zip: _9 __ 2_03 __ 7 __ _ Phone: 888.815.8886 Email: scott@badieedevelopment.com Name: -~ffi~~~~~!ttf~~t§!:!fd!:L~~~- Address: _-2.5a!i::m!!i:Eil~f:EHL ______ ~~.'2,- City: CARLSBAD Phone: ~Q.802.9107 Email: tffl't'iS@r.'JRi~080A&tFl:IG&ioRiRG,CQffi State License:. _____ Bus. License: BL f\J ~ 11..01. 3-</b (Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he/she is licensed pursuant to the provisions of the Contractor's License Law {Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civit penalty of not more than five hundred dollars {$500}1. 1635 Faraday Ave Carlsbad, CA 92008 B-2 Ph: 760-602-2719 Fax: 760-602-8558 Page 1 of2 Email: Building@carlsbadca.gov Rev. 06/18 ) .... ( OPTION A ): WORKERS'COMPENSATION DECLARATION: f hearby affirm under penalty of perjury one of the following declarations: □ I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the work which this permit is issued. □ I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy number are: Insurance Company Name: _____________________ _ Policy No. ______________ Expiration Date: _________ _ □ Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to be come . subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful, and shall subject an employer to crlmlnal penaltfes and civil fines up to $100,000.00, In addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code, Interest and attorney's fees. CONTRACTOR SIGNATURE: □AGENT DATE: ----------------------------------- ( OPTION B ): OWNER-BUILDER DECLARATION: I hereby affirm that I am exempt from Contractor's License Law for the following reason: □ I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale). □ I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law). □ I am exempt under Section ________ Business and Professions Code for this reason: 1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. □ Yes □ No 2. I (have/ have not) signed an application for a building permit for the proposed work. 3. I have contracted with the following person (firm) to provide the proposed construction (include name address/ phone/ contractors' license number): 4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address/ phone/ contractors' license number): S. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name/ address/ phone/ type of work), OWNER SIGNATURE: □AGENT --------------------------DATE: _____ _ CONSTRUCTION LENDING AGENCY, IF ANY: I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (il Civil Code). Lender's Name: ____________________ _ Lender's Address: ____________________ _ ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY: Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 2550S, 2S533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? □ Yes !i':I No Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? □ Yes J1t1 No Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? □ Yes 11:.1 No IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT. APPLICANT CERTIFICATION: I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building construction. I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I AlSO AGREE TO SAVE, I NDEMNIFV AND KEEP HARMLESS THE CITY OF CARISBADAGAINST ALL LIABILITIES, JUDGMENTS, COSTS ANO EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height. EXPIRATION: Every permit issued by the Building Official under the provisions of this COde shall expire by limitation and become null and void if the building or work authorized by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code). APPLICANT SIGN.ATURE: ~ I tcz:vszv DATE: 'l · i J · I '1 1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov B-2 Page 2 of2 Rev. 06/18 Ccicyof Carlsbad COMMERCIAL BUILDING PERMIT APPLICATION B-2 Plan Check Jt20 jq-CQ8 I Est. Value PC Deposit --------- Date --------- Job Address ___________________ Suite: ____ APN: __________ _ Tenant Name: _________________ CT/Project#: __________ Lot#: ___ _ Occupancy: _________ Construction Type: ____ Fire Sprinklers: yes/ no Air Conditioning: yes/ no BRIEF DESCRIPTION OF WORK: ___________________________ _ D Addition/New: ___________ New SF and Use, ___________ New SF and Use, ____ Deck SF, Patio Cover SF (not including flatwork) D Tenant Improvement: ______ SF, ______ SF, Existing Use ______ Proposed Use ______ _ Existing Use Proposed Use ______ _ 0 Pool/Spa: _____ SF Additional Gas or Electrical Features? ------------- D Solar: ___ KW, __ Modules, ___ Mounted, Tilt: Yes/ No, RMA: Yes/ No, Panel Upgrade: Yes/ No D Plumbing/Mechanical/Electrical Only: _________________________ _ D Other: --------------------------------------- APPLICANT (PRIMARY) PROPERTY OWNER Name: __________________ Name: ____________________ _ Address: Address: ___________________ _ City: ________ State:. ___ Zip: ____ City: __________ State:, ___ Zip: ____ _ Phone: Phone: ____________________ _ Email: Email: ____________________ _ DESIGN PROFESSIONAL Name: _________________ _ Address: _________________ _ City: ________ State:. __ ..... Zip: ___ _ Phone: ________________ _ Email: _________________ _ Architect State License: ___________ _ CONTRACTOR BUSINESS ( ~ Name: Ted t.Jeeit..S _ T F W _J_ Address: 71Hc,1a /1,55,.;,., fkJley Rd. ')v;./-e.. Q.a.t;J, City: 7a.n Ore ,o State: c~ Zip:------ Phone: &"S&~ 35] -7o5q Email: +-eel (..,J:Ld.$ .tf-(ft +:fy C4"1 s fad,,~ · c:.a.-.. State License: ~l;B",] Bus. license: BLQ5/l bl10 (Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, 7!;1r; IJta:?demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he/she is licensed pursuant to the provisions of the Contractor's License Law {Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)). 1635 Faraday Ave Carlsbad, CA 92008 B-2 Ph: 760-602-2719 Fax: 760-602-8558 Page 1 of 2 Email: Building@carlsbadca.gov Rev. 06/18 ( OPTION A): WORKERS'COMPENSATION DECLARATION: I hearby affirm under penalty of perjury one of the following declarations: 0 I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 ofthe Labor Code, for the performance ofthe work which this permit is issued. □ I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' ,9{l~ensation insurance carrier and policy number are: Insurance Com,Ra~ Name: _ _,"5:_-f-c.__'-""'"-f-_,,e~C,,,"""'&"""':+,CLI-/)....,_ ____________ _ Policy No, ':::11)$ ] L;:, J--4--Expiration Date: ~{_o~-~:;J...G/,~~----1 □ Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to be come subject to the workers' compensation laws of California. WARNING: Failure to secure workers compensation coverage Is unlawful, and shall subject an employer to criminal penalties and civil fines up to $100,000.00, In addltlo compensation, damages as provided for In Section 3706 of the Labor code, Interest and attorney's fees_ CONTRACTOR SIGNATURE: ( OPTION B ): OWNER~BUILDER DECLARATION: I hereby affirm that I am exempt from Contractor's license Law for the following reason: D I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale {Sec. 7044, Business and Professions Code: The contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within one year of completion, the owner•builder will have the burden of proving that he did not build or improve for the purpose of sale). □ I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law). 0 I am exempt under Section ________ Business and Professions Code for this reason: 1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. □ Yes D No 2. I (have/ have not) signed an application for a building permit for the proposed work. 3. I have contracted with the following person (firm) to provide the proposed construction (include name address/ phone/ contractors' license number): 4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address/ phone/ contractors' license number): 5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name/ address/ phone/ type of work): OWNER SIGNATURE: □AGENT DATE: ______ _ -------------------------- CONSTRUCTION LENDING AGENCY, IF ANY: I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec, 3097 (i] Civil Code). Lender's Name: _____________________ Lender's Address: ____________________ _ ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY: Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? D Yes D No Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? D Yes D No Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? □ Yes □ No IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT- APPLICANT CERTIFICATION: I certify that I have read the application and state that the above information is correct and that the information on the plans is accur.ite. I agree to comply with all City ordinances and State laws relating to building construction. I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY Of CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANYWAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height. EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code). APPLICANT SIGNATURE: ______________________ DATE: ________ _ 1635 Faraday Ave Carlsbad, CA 92008 B-2 Ph: 760-602-2719 Fax: 760-602-8558 Page 2 of2 Email: Building@carlsbadca.gov Rev. 06/18 DATE: DEC. 18, 2019 JURISDICTION: CARLSBAD ✓• EsG1I A SAFEbullfCompar-:y PLAN CHECK#.: 2019-0461 (A::..-2019~ 0ET: IV PROJECT ADDRESS: 2810 CARIBOU COURT f PPLICANT JURIS. PROJECT NAME: INNOVATE CARLSBAD -T.I., SUITES A, C, E & G D The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's building codes. IZ! The plans transmitted herewith will substantially comply with the jurisdiction's building codes when minor deficiencies identified below are resolved and checked by building department staff. D The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. D The check list transmitted herewith is for your information. The plans are being held at EsGil until corrected plans are submitted for recheck. D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant contact person. D The applicant's copy of the check list has been sent to: IZ! EsGil staff did not advise the applicant that the plan check has been completed. D EsGil staff did advise the applicant that the plan check has been completed. Person contacted: Brittany Montgomery Telephone#: 858-638-7277 Date contacted:! 2f uilt'tby:~Yl,t) Email: bmontqomery@waremalcomb.com Mail Telephone Fax In Person REMARKS: The applicant to slip sheet partial Set IV Plans into Set Ill Pl By: ALI SADRE, S.E. Enclosures: EsGil 12/12 9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576 ✓. EsG1I A SAFEbuilfCompany DATE: DEC. 10,2019 JURISDICTION: CARLSBAD PLAN CHECK#.: 2019-0461 (PC.2..D19-c:Qs~T: III PROJECT ADDRESS: 2810 CARIBOU COURT □ APPLICANT □ JURIS. PROJECT NAME: INNOVATE CARLSBAD -T.I., SUITES A, C, E & G D The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's building codes. D The plans transmitted herewith will substantially comply with the jurisdiction's codes when minor deficiencies identified below are resolved and checked by building department staff. D The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. ~ The check list transmitted herewith is for your information. The plans are being held at EsGil until corrected plans are submitted for recheck. PLEASE SEE BELOW 0 The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant contact person. ~ The applicant's copy of the check list has been sent to: D EsGil staff did not advise the applicant that the plan check has been completed. ~ EsGil staff did advise the applicant that the plan check has been completed. In Person Telephone #: 858-638-7277 Email: bmontgomery@waremalcomb.com ee attached for remaining items from previous list. By: ALI SADRE, S.E. Enclosures: EsGil 12/04 9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576 CARLSBAD 2019-0461 DEC. 10, 2019 GENERAL 1. Please make all corrections, as requested in the correction list. Submit FOUR new complete sets of plans for commercial/industrial projects (THREE sets of plans for residential projects). For expeditious processing, corrected sets can be submitted in one of two ways: 1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will route the plans to EsGil and the Carlsbad Planning, Engineering and Fire Departments. 2. Bring IWQ corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of plans and calculations/reports directly to the City of Carlsbad Bldg. Department for routing to their Planning, Engineering & Fire Dept. NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the City Planning, Engineering and Fire Departments until review by EsGil is complete. 2. To facilitate rechecking, please identify, next to each item, the sheet of the plans upon which each correction on this sheet has been made and return this sheet with the revised plans. 3. Please indicate here if any changes have been made to the plans that are not a result of corrections from this list If there are other changes, please briefly describe them and where they are located on the plans. Have changes been made not resulting from this list?□ Yes □ No PLANS 4. Please update the notes on Sheets A0.4 & A0.4a, for the 2016 edition of the Green Building Code, as opposed to 2013 GBC. These updated sheets were not included in the resubmitted package. The submitted architectural sheets were partial sets and more than ½ the sheets are missing. MISCELLANEOUS 5. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the plan review for your project. If you have any questions regarding these plan review items, please contact ALI SADRE, S.E. at EsGil. Thank you. DATE: OCT. 14,2019 JURISDICTION: CARLSBAD PLAN CHECK#.: 2019 04 l ✓. EsG1I A SAFEbuilfCompany PROJECT ADDRESS: 2810 CARIBOU COURT D APPLICANT D JURIS. PROJECT NAME: INNOVATE CARLSBAD -T.I., SUITES A, q, E & G ,o6 120 '-,~o 0 The plans transmitted herewith have been corrected where necessary and substantially comply with the jurisdiction's codes. D The plans transmitted herewith will substantially comply with the jurisdiction's codes when minor deficiencies identified below are resolved and checked by building department staff. 0 The plans transmitted herewith have significant deficiencies identified on the enclosed check list and should be corrected and resubmitted for a complete recheck. [gj The check list transmitted herewith is for your information. The plans are being held at EsGil until corrected plans are submitted for recheck. D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant contact person. [gj The applicant's copy of the check list has been sent to: 0 EsGil staff did not advise the applicant that the plan check has been completed. ~ EsGil staff did advise the applicant that the plan check has been completed. Person contacted: Brittany Montgomery Telephone#: 858-638-7277 Date contacted: (by: ) Email: bmon tgomery@waremalcomb.com Mail Telephone Fax In Person 0 REMARKS: By: ALI SADRE, S.E. Enclosures: EsGil 9/30 9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576 CARLSBAD 2019-0461 OCT. 14,2019 GENERAL PLAN CORRECTION LIST JURISDICTION: CARLSBAD PLAN CHECK#.: 2019-0461 PROJECT ADDRESS: 2810 CARIBOU COURT SCOPE= T.I. (#A, C, E & G)-P1 FLR.; STORIES= ONE+ MEZZ.; SPRINKLERS= YES; OCCUPANCY= B/S1; HEIGHT= NO CHANGE; CONST.= 11I-B; USE= WAREHOUSE DATE PLAN RECEIVED BY ESGIL: 9/30 REVIEWED BY: ALI SADRE, S.E. FOREWORD (PLEASE READ): DATE REVIEW COMPLETED: OCT. 14,2019 This plan review is limited to the technical requirements contained in the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws regulating energy conservation, noise attenuation and disabled access. This plan review is based on regulations enforced by the Building Department. You may have other corrections based on laws and ordinances enforced by the Planning Department, Engineering Department or other departments. The following items listed need clarification, modification or change. All items must be satisfied before the plans will be in conformance with the cited codes and regulations. The approval of the plans does not permit the violation of any state, county or city law. GENERAL 1. Please make all corrections, as requested in the correction list. Submit FOUR new complete sets of plans for commercial/industrial projects (THREE sets of plans for residential projects). For expeditious processing, corrected sets can be submitted in one of two ways: 1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will route the plans to EsGil and the Carlsbad Planning, Engineering and Fire Departments. 2. Bring IWQ corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of plans and calculations/reports directly to the City of Carlsbad Bldg. Department for routing to their Planning, Engineering & Fire Dept. NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the City Planning, Engineering and Fire Departments until review by EsGil is complete. 2. To facilitate rechecking, please identify, next to each item, the sheet of the plans upon which each correction on this sheet has been made and return this sheet with the revised plans. 3. Please indicate here if any changes have been made to the plans that are not a result of corrections from this list. If there are other changes, please briefly describe them and where they are located on the plans. Have changes been made not resulting from this list?□ Yes □ No PLANS 4. Please note on the plans that all the site items including parking, ramps, curbs, walks, etc. are HG accessible subject to field verification. CARLSBAD 2019-0461 OCT. 14,2019 5. Please revise the sheet index to match the content of the plans. I.e., as submitted, sheets AD.1, AD.2, M2.3 were missing from the plans. Also, add Sheet M2.0 to the Sheet Index and revised P0.1 to P1 .0 to match the plans. 6. Please dimension the meeting room and the adjacent office on sketch 2/A2. 3. 7. Please dimension the conference room on sketch 1/A2.5. 8. Please label the window adjacent to door #106 on 1 /A2.2. 9. Please provide interior elevation plans with references, on the floor plans, for all the interior glazing. See the next item as well. 10. Please complete the blank bubbles under legend on floor plans, starting on Sheet A2.2. Similarly, complete the blank bubbles on detail F/A8.1. 11. Please update the notes on Sheets A0.4 & A0.4a, for the 2016 edition of the Green Building Code, as opposed to 2013 GBC. 12. Please identify the thickness of the interior glazing & specify they are tempered on plans. Sec. 2406.4. Also, show they are adequate for 5-psf lateral force. ASCE 7-10, Sec. 13.5.9. CITY POLICY 13. For plans submitted to the City on or after 4/12/19, the following Electric Vehicle requirements apply, per Carlsbad ordinance: Accessibility to comply with CBC Table 11 B-228.3.2.1 and space design of 11 B-812.6 is required. Please show compliance on plans. with the City Policy. as follows: Non-residential: Carlsbad amended the California Green Code, as follows. The California Green Code provisions apply to new buildings and to alterations (if the alteration shows parking spaces being added): • "EVSE capable": 1" raceway terminating into an adequately sized (amperes) panel and an enclosure (parking end) the location identified on the building plans. If common use parking is available at least one capable space is required. • "EVSE ready": Panel capability, 40A 2 pole breaker, 1" raceway, No. 8 conductors installed to the anticipated charger location. • "EVSE installed": Panel capability, 40A 2 pole breaker (per space), 1• raceway (per space), electrical vehide charging equipment and No. 8 conductors installed to the charger location. TABLE 5.106.5.3.3 TOTAL NUMBER OF NUMBER OF REQUIRED EV NUMBER OF REQUIRED EVSE ACTUAL PARKING SPACES SPACES INSTALLED SPACES 0-9 1 1 10-25 2 1 26-50 4 2 51-75 6 3 76-100 9 5 101-150 12 6 151-200 17 9 201 and over 10 percent of tota11 50 percent of required EVSE Installed spaces1 1. Calculation for EV spaces and EVSE Installed spaces shall be rounded up to the nearest whole number. The "Number of Required EVSE Installed Spaces" column in the table will require a completed EV charging station design. The "Number of Required EV Spaces" column in the table may be "capable", "ready'', or "installed." (See definitions). Accessibility to comply with CBC Table 11 B-228.3.2.1 and space design of 11 B-812.6 is required. CARLSBAD 2019-0461 OCT. 14,2019 MISCELLANEOUS 14. Please see attached for any P/M/E corrections. 15. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform the plan review for your project. If you have any questions regarding these plan review items, please contact ALI SADRE, S.E. at EsGil. Thank you. PLUMBING AND MECHANICAL COMMENTS PLAN REVIEWER: Connor Reuss SET: I PLUMBING (2016 CALIFORNIA PLUMBING CODE) 16. Cleanouts are required to be installed above all urinals. Please address on the plans. CPC 707.4 17. Describe the method of compliance for temperature limitations for the following fixture types: public use lavatories limited to 110 degrees F per Energy Standards 11 0(c)(3). Note: The water heater thermostat may not be used for compliance. 18. Please correct sheet P1 .0 to state that all domestic (i.e. potable) hot water piping will have a minimum insulation for the following pipe sizes: ½" pipe (½" insulation);¾" pipe (1" insulation); 1"-1 ½" pipes (1 ½" insulation); 2" pipes are larger (2" insulation). CPC 609.11 & ES 150.0U) 19. All tenants are required to have access to the janitors sink. Please address. CPC Table 422.1. 20. Specify if any natural gas-powered appliances are under this permit. If so, please provide the proper CPC 1216.2 Table, the total developed length, and the load for each appliance. CPC 1216.0 21. Per CPC Appendix A, a 2" water supply can only handle a 45 gpm at 2.1 permissible friction loss. The calculations on sheet P1 .0 specify 80 gpm. Please address. MECHANICAL (2016 CALIFORNIA MECHANICAL CODE) 22. Buildings of more than 15' in height shall have an inside means of access that meets the design requirements of CMC 304.3.1.1. Please provide City approval for use of an outside ladder is required. 23. Please show the required 42 inches tall "Guards" (guard rails) or building parapets height where appliances, mechanical equipment, fans, roof hatch openings or other components that require service are located within 10 feet of a roof edge or open side of a walking surface. CBC 1015.6 & 1015.7 CARLSBAD 2019-0461 OCT. 14, 2019 24. Specify compliance with CMC 603.4.1 for length limitations for factory made flexible air ducts (5') and use (not to be used for rigid elbows or fittings). 25. Per City of Carlsbad, roof mounted equipment must be screened and roof penetrations should be minimized (City Policy 80-6). Note: If you have any questions regarding this Plumbing and Mechanical plan review list please contact Connor Reuss at (858) 560-1468. To speed the review process, note on this list (or a copy) where the corrected items have been addressed on the plans. ELECTRICAL, and ENERGY COMMENTS PLAN REVIEWER: Morteza Beheshti ELECTRICAL (2016 CALIFORNIA ELECTRICAL CODE) 1. Emergency illumination is required outside at the exit discharge when there are two or more exits required . Please provide. 2. Exist signs seem to be facing the wrong direction. Please review. 3. Please indicate the ground electrode for the transformers. CEC 250.30 4. Please provide a GFI receptacle outlet installed within 25' of the rooftop units and within 6' of break room or other sinks. CEC 210.8 and 63 Note: If you have any questions regarding this Electrical and Energy plan review list please contact Morteza Beheshti at (858) 560-1468. To speed the review process, note on this list (or a copy) where the corrected items have been addressed on the plans. CARLSBAD 2019-0461 ;' OCT. 14, 2019 [DO NOT PAY-THIS IS NOT AN INVOICE] VALUATION AND PLAN CHECK FEE JURISDICTION: CARLSBAD PREPARED BY: ALI SADRE, S.E. BUILDING ADDRESS: 2810 CARIBOU COURT BUILDING OCCUPANCY: B/Sl; 111-B/SPR. BUILDING AREA Valuation PORTION (Sq. A.J Mulipler T.I. 26104 Air Conditioning Fire Sprinklers PLAN CHECK#.: 2019-0461 DATE: OCT. 14,2019 Reg. VALUE ($) Mod. ' TOTAL VALUE 1.214,097 Jurisdiction Code CB 1997 UBC Building Permit Fee IN!il; 1997 UBC Plan Check Fee By Ordinance Type Of Review: P: Complete Review r Repetitive Fee ~ Repeats ,. Comments: r Other r Holaty EaGU Fee "· 7 , r Structural Only Sheet 1 of 1 \ I flllconstruction 7460 Mission Valley Road, #200 San Diego, CA 92108 RFI #002 Date: 1-7-20 Number of pages including cover 2 sheet: To: From: Adam Nichol Ware Malcomb Barry Zeller TFW Construction Architects Phone: 858-638-1359 Demising Wall Studs Fax phone: Innovate Carlsbad CC: Phone: 951-239-5036 REMARKS: [&I Urgent D For your review O Reply ASAP [&I Please comment 1. Reference F/A8.1 and 12/A8.1. The metal stud chart is only for studs with 1 ¼" flanges, we would like to use 1 5/8" flanged studs. See chart attached, the highlighted line is the proposed product. THIS ASSEMBLY IS ACCEPTABLE AS LONG AS IT MEETS THE LIMITING HEIGHTS TABLE L/240 (5PSF/L240) AND ALL OTHER ICC-ESR REQUIREMENTS. -RESPONSE BY ATN @ WMSD ON 1-7-2020 Limiting Wall Heights -Curtain Wall (S) Stud Spacing !5 psf 15 paf 20 psf 25 psf Member (in) o.c. IJ120 IJ240 11360 L/240 11360 l/600 L/240 11360 IJ600 IJ240 11360 IJ600 800S137-33 12 43' 9' 34'8" 30' 4' 24' 1' 21' O" 17'8" 21' 10" 19' 1' 16'1' 2C1 3" 17'8' 14' 11· 800S137-33 16 3f19' 31' 6' 27' 6" 21'10" 19'1' 16'1' 19' 10" 17'4' 14'7" 18'5' 16'1' 13' 7" 800S137-33 24 34' 11 276' 24' 1' 19'1" 16'8" 14' 1' 17'0"f 1S2" 12'9" 15' 3"f 14' 1' 11' 10" 800S162-33 12 45'5" 36' o· 31'6" 25'0" 21' 10" 18' 5' 22 8" 19' 10" 16'8' 21' 1' 18' 5' 1S6" 800S162-33 16 41' 3" 32' 9' 28' r 22' 8" 19' 10" 16' 8" 20'7" 18'0" 1S2" 19' 2" 16'8" 14' 1" 800S162-33 24 36'0' 28'7" 25'0" 19'10" 17'4" 14'7" 18'0" 1S 9' 13' 3' 16'3"f 14'7" 12' 4" 800S200-33 12 47'6" 37'8" 32'11' 26' 1' 22' 10" 19' 3" 23' 9" 2C1 9" 176" 22' O" 19'3" 16' 3' 800S200-33 16 43' 2' 34' 3' 29' 11· 23' 9' 2C1 9• 17'6" 21'7" 18' 10' 15' 10" 20· o· 17'6" 14' 9" 800S200-33 24 37' 8' 29' 11· 26' 1· 2C19" 18'1' 1S 3' 18' 10" 16' 5" 13' 10" 16' 10"1 15'3" 12' 10" 8005137-43 12 47' a· 37' 10" 33' O" 26' 2" 22' 11' 19' 3' 23' 10" 2C19• 17'6' 22 1' 19'3' 16' 3' 800S137-43 16 43' 3' 34' 4' 30' O' 23' 1(1' 20' 9" 17' 6' 21'7" 18'11" 15' 11· 20' 1' 17' 6" 14' 9' 800S137·43 24 3710" 30' o· 26' 2' 'ZJ 9' 18'2" 1S 4' 18'11' 16'6" 13'11' 17'6" 1S4' 12'11' 800S162-43 12 49' 6" 3f1 3' 34' 4' 27 3' 23' 9' 20' O" 24' 9' 21'7" 18' 2' 22'11' 20'0" 16'1 1" 800S162-43 16 44' 11· 35' 8' 31' 2' 24' 9" 21· r 18' 2" 22 5• 19' r 16'6' 'ZJ 10' 18' 2" 1S4" 800S162-43 24 3f13' 31' 2' 27'J' 21'7" 18' 10" 1S11" 19'7" 172" 14' 5' 18'2" 1s11· 13' 5" 800S200-43 12 51' 9' 41' 1' 35' 11' 28' 6' 24• 10" 21· o· 25' 10" 22 r 19'1' 24' o· 21· O" 17'8" 800S200-43 16 47'0" 37'4' 32' r 25'10" 227" 19'1" 23' 6" 2C1 6" 174' 21' 10" 19' 1' 16'1' 800S200-43 24 41' 1' 32' r 28' 6" 22 r 19' 9' 16'8" 20' 6' 17' 11' 15' 1' 19'1' 16' 8' 14' O" 800S137-54 12 51' 2' 4C17' 35' 5' 28' 1' 24' 7' 2(1 ff' 25'7' 22'4' 18'10" 23' 9" 20' 8' 17 6' 800S137-54 16 46' 5' 36' 1 O" 32' 2' 25'7" 224" 18' 10" 23' 2" 2C1 3" 17 1' 21' 6" 18' 10" 1S 10" 800S137-54 24 4C1 r 32' 2" 28' 1' 22' 4' 19'6' 16' 5• 2(1 3• 178" 14' 11· 18' 10" 16' 5• 13' 10- 800S162-54 12 53' 2" 42' 2" 36' 10" 29' 3" 25' 6' 21' 6" 26' r 23' 2" 19'7" 24'8" 21' 6" 18' 2' 800S162-54 16 48' 'J' 38' 4' 33' 6" '207" 23' 2" 19'T 24'1' 21' 1· 17 9' 225' 19'7" 16'6" 800S162-54 24 42'2" 33' 6" 29' 3• 23' 2" 20' 3• 17 1· 21' 1' 18' 5• 15' 6' 19'7" 17'1' 14'5" 8005200•54 12 55' 7' 44', 38' r 30' r 26' 9' 22' 6" 27' 9' 24' 3" 20' 6' 2S 9" 22' 6' 19'0' 800S200-54 16 50' 6' 4C11" 35' o· 27 9" 24' 3' 20' 6" 25' 3' 22' 1' 18' 7' 23' 5' 20' 6" 17'J' 800S200·54 24 44'2" 35'0' '3(17" 24'3" 21' 2' 17'10" 22 1' 19'3" 16' 3• 2C1 6" 17 10" 15' 1· 800S137-68 12 54' 1 O' 43' 6' 38' O" 30' 2" 26' 4• 22' 'J' 2? 5' 23• 11· 20 2' 25' 5' 22' 3" 18' 9' 800S137-68 16 49' 10' 3f16" 34' 6" 275' 23'11" 2(12" 24' 11' 21'9' 18'4' 23' 1" 20' 2' 170' 800S137-68 24 43' 6' 34' 6" 30' 2" 23' 11· 2a 11· 11 r 21' 9' 19' O" 16'0" 20' 2' 11 r 14' 10' 800S162-68 12 57 o· 4S 3" 39' 6' 31• 4' 215• 23' 1' 28' 6' 24' 11' 21' O" 26' 5• 23' 1' 19' 6' 800S162-68 16 51' 10" 41' 1" 35' 11' 28' 6" 24' 11' 21' O" 25' 11" 22' 7' 19'1' 24' 0" 21 ' O' 17'8" 800S162-68 24 4S3' 35'11" 31'4' 24' 11" 21' 9' 18' 4' 227" 19' 9' 16'8' 21' O' 18'4" 1S 5" 800S200-68 12 59'9" 47'5' 41'5' 32' 1 c,• 28' 8' 24' 2' 29' 10" 26' 1" 22' O" 278" 24' 2" 2C1 s· 800S200-68 16 54' 3• 43' 1' 377" 29' 10" 26' 1' 22' O" 27 1' 23' 8" 20' O' 2S2" 22' O" 18' 6" 800S200-68 24 47 s· 37' r 32' 10-26' 1· 22 9" 19' 2" 23' 8' 2C1 ff' 17 5' 22' O' 19'2" 16'2" 8005137-97 12 60' 10" 48' 'J' 42' 2' 33' 5' 29' 3' 24' ff' '3(15' 26'7" 225' 28' 2" 24' 8' 20' 9" 800S137-97 16 5S 3' 43' 10" 38' 4' 30' s· 26' r 22' 5' 21 r 24' 1· 2C1 4• 2S7" 225' 18' 10' 800S137-97 24 48' 3' 38' 4" 33' 5' 26' r 23', 19' 7' 24' 1' 21' 1' 17'9' 22' s· 19' 7' 16'6" 800S162-97 12 63' 4' 50' 3" 43' 11' 34' 10" 3C15' 25' 8' 31'8' 27' 8" 23'4' 29' 5' 25'8' 21' ff' 800S162-97 16 fil'7" 4S8' 3f111" 31'8" 278" 23' 4• 28' 9' 2S 1' 21'2" 26' 8" 23' 4" 19'8" 800S162-97 24 50' 3' 39' 11' 34' 10'' 27 8" 24' 2' 2C14" 25' 1' 21' 11' 18'6' 23' 4• 20' 4' 172" 800S200-97 12 66' 5' 52' 9" 46' 1' 36' 7' 31' 11' 26' 11" 33'' 29' o· 24'5' 30' 10" 26' 11· 22' 8" 800S200-97 16 60' 4' 47' 11' 41' 10" 33' 2" 29' O" 24• 5• '3(12' 26' 4" 22' 3' 28' O" 24' 5' 20' 7" 800S200-97 24 52' 9' 41' 10" 36' 7' 29' O" 25' 4' 21' 4• 26' 4• 23' o· 19' 5· 24' 5' 21' 4' 18'0" "f • denotes stress controlled section, all other sections are deflection controlled See page 16 for Wall Height Table Notes ~ SSMA 30 paf 35 paf 40 psf 50 psf IJ240 IJ360 IJ600 IJ240 11360 IJ600 IJ240 11360 IJ600 IJ240 11360 l/600 19'1' 16'8" 14' 1' 18' 1' 1S 10" 13'4' 17'0"f 1S 2" 12' 9' 1S 3"f 14' 1· 11' 10" 17'0"f 1S2" 12'9' 1S9't 14'4' 12'1' 14' 9't 13' 9" 11'7" 13'2'f 12' 9' 1(19' 13'111 13'3" 11' 2" 12'10"1 12'7" 10'7" 12'0"f 12'0" 10'1" 10'9"! 10'9"1 9' 5' 19' 10" 17'4" 14• r 18' 10" 16' s· 13' 10" 18'0" 1S 9' 13' 3" 16' 3"f 14'7" 12'4" 18'0" 1S 9" 13' 3" 16' 10"1 14' 11' 12'7" 1S 9't 14' 3' 12'0" 14' 1'f 13' 3• 11' 2" 14'10"1 13'9" 11'7" 13' 9't 13'0" 11'0" 12'10, 12'6' 1(16" 11'6'f 11'S, 9' 9' 2(19' 18'1" 1S3' 19'8" 17' 2" 14'6" 18' 10-16' 5• 13 10-16'10"1 1S3' 12' 10" 18'10" 16' 5· 13'10" 17'5'f 1S7" 13' 2" 16'4'1 14'11" 12'7" 14'7'f 13' 10" 11'8" 1S 5'f 14'4' 12'1' 14' 3'f 13' 8' 11' 6' 13' 41 13' o· 11'0' 11' 111 11' 1n 1(1 2" 20' 9' 18' 2' 15'4' 19' 9" 17 3' 14'6" 18' 11' 16' 6' 13' 11' 17 6' 1S4' 12'11' 18' 11· 16' 6" 13' 11" 17'11' 1S 8' 13' 2' 172' 1SO" 12' 8" 1S 11' 13' 11' 11'9" 16'6' 14'5' 12' 2' 1S8" 13' 8" 11'6' 1SO" 13'1" 11'0' 13'5'f 12'2" 10' 3' 2r r 18' 10" 15• 11· 2C16" 1711' 1s1· 19'7" 172" 14' 5' 18' 2' 15' 11' 13' 5• 19'7" 17' 2' 14• 5• 18' 8" 16' 3" 13' 9' 1710" 1ST 13' 1' 16' 6' 14' 5• 12'2" 17' 2" 14' 11" 12'7" 16' 3" 14' 2' 12'0" 1ST 13'7" 11' 5' 14'31 12'7" 1(18' 22 r 19' 9' 16'8' 21' 5' 18'9' 1S 10" 'ZJ 6" 17 11' 15' 1' 19'1' 16'8' 14'0" 20' 6" 1711' 1S 1' 19'6' 17'0" 14'4' 18' 8' 16'3" 13' 9' 17'4' 1S1" 12'9" 1711' 1S8" 13'2" 170" 14' 10' 12' 6" 16' 3' 14'3" 12' O" 15'0"1 13' 2" 11'1' 22' 4' 19' 6" 16'5" 21' 2' 18'6" 1S7' 20' 3" 17'8" 14' 11' 18' 10" 16' 5' 13' 10" 203' 178" 14' 11' 19' 3' 16' 10" 14'2" 18' 5• 16'1" 13' r 17' 1' 14' 11' 12'7" 17'8' 1SS' 13'0" 16' 10" 14'8' 12'4" 16' 1' 14' O" 11' 10' 14· 11· 13• o· 11'0" 23' 2" 2C13" 171' 22' O" 19'3" 16' 3' 21' 1' 18' 5• 1S6" 19'7" 17'1' 14' 5' 21· 1· 18' 5· 1S6" 2(1 O" 176' 14'9" 19' 2" 16' 9" 14'1" 17' 9' 15'6" 13'1' 18' 5• 16' 1· 13'7" 176" 1S 3" 12' 10" 16'9' 14'7" 12'4' 1S6" 13• r 11'5' 24' 3• 21' 2" 1710" 23' 1' 20' 2" 170" 22' 1· 19'3" 16' 3' 20' 6" 17' 10" 1S1' 221· 19' 3" 16' 3' 20' 11' 18' 3' 1s5• 2C1 o· 17'6" 14' 9' 18'7" 16' 3" 13'8" 19' 'J' 16' 10" 14' 2" 18'3" 16'0' 13'6" 176" 1S3" 12'10" 16'3" 14'2" 11'11" 23'11' 2(111" 177" 22'9' 19'10' 16'9' 21' 9' 19' O' 16'0" 2(12" 17'7" 14' 10" 21' 9' 19'0" 16' o· 208" 18'0" 1S2" 19' 9' 173' 14'6' 18' 4' 16' O' 13'6" 19' o· 16' r 14'0" 18' O" 1S9' 13'3" 173' 1S1' 12'8' 16'0" 14'0" 11'9" 24' 11' 21' 9' 18' 4' 23' 8' 20' 8' 17' 5' 227" 19' 9' 16' 0· 21' 0" 18' 4' 1S 5' 227" 19' 9' 16' 8" 21'6" 18'9' 15' 10" 206" 1711' 15' 1" 19'1' 16'8' 14' O' 19'9' 173" 14' 6' 18' 9' 16' 5• 13' 10" 17'11" 1S8" 13'2" 16'8" 14'6" 12'3" 26' 1' 22' 9' 19' 2' 24• 9' 21' r 18'3" 23' ff' 20' ff' 17' 5' 22 O" 19' 2' 16' 2' 23' 8' 2C18' 175' 22' 6" 19'8' 16' 7' 21'6" 18' 9' 15' 10' 20' O" 17 5' 14'8" 208' 18'1' 15'3" 19'8" 172" 14' 6' 18' 9' 16' s· 1310" 115' 15''J' 12'10" 26'7" 23' 2" 19'7" 2S 3' 22 O' 18'7" 24' 1' 21' 1" 179' 22' 5' 19• r 16'6" 24' 1' 21' 1' 17' 9" 22 11" 20'0" 16' 10' 21' 11' 19' 2" 16' 2' 204' 17' 9' 1SO" 21' 1" 18'5" 15' 6' 20' O' 17 6" 14' 9' 19'2" 16'8" 14'1' 17'9" 15' 6' 13'1' 27 ff' 24' 2" 20' 4' 26' 'J' 22' 11' 19' 4' 25'1' 21'11' 18'6' 23' 4• 2(14' 17' 2' 25'1" 21' 11" 18'6" 23' 10" 2C110" 17' 7' 22' 10" 19' 11' 16' 10" 21'2" 18'6" 1ST 21' 11' 19' 2' 16' 2' 20'10' 18'2" 1S4' 19' 11' 175" 14'8' 18'6' 16'2" 13'7" 29' O" 25' 4' 21' 4" 27 6" 24' 1' 20 'J' 26' 4' 23' O" 10· 5· 24• 5· 21' 4" 18' O" 26' 4" 23' O" 19'5' 2S O" 21' 10" 18' 5' 23'11"2(1 11' 177" 22' 3" 19' 5' 16'4' 23' o· ro 1· 16' 11· 21' 10" 19' 1' 16'1' 2(111' 18' 3" 15• s· 19' 5' 16'11' 14''J' 19 ECEIVED NOV CLIMATE ACTION PLAN 8 zm ve lo pme nt Services Ccityof Carlsbad PURPOSE CONSISTENCY CHEC ! 8-50 CAfliLSBAO G [)1\11'S10 Building Division 1635 Faraday Avenue (760) 602-2719 www.carlsbadca.gov This checklist is intended to assist building permit applicants identify which Climate Action Plan (CAP) ordinance requirements apply to their projects. The completed checklist must be included in the building permit application. It may be necessary to supplement the completed checklist with supporting materials, calculations or certifications, to demonstrate fu ll compliance with CAP ordinance requirements. For example, projects that propose or require a performance approach to comply with energy-related measures will need to attach to this checklist separate calculations and documentation as specified by the ordinances. NOTE: The following typeOf permits are not reRuired to fill out this form ' < ' ❖ Patio I ❖ Decks I ❖ PME (w/o panel upgrade) I ❖ Pool ..,. If an item in the checklist is deemed to be not applicable to a project, or is less than the minimum required by ordinance, an explanation must be provided to the satisfaction of the Building Official. ..,. Details on CAP ordinance requirements are available on the city's website . ..,. A CAP Building Plan template (form B-55) shall be added to the title page all building plans. This template shall be completed to demonstrate project compliance with the CAP ordinances. Refer to the building application webpage and download the latest form. Project Name/Building Permit No.: Property Address/APN: Applicant Name/Co.: Applicant Address: Contact Phone: ____ BPNoQ5aol't4'61 ioq-lZ-o • o~ 1;) \QQ , -SJ,,\. 7.,-. 7.-,'f S Contact Email: Contact information of person completing this checklist (if different than above): Name: Company name/address: Contact Phone: Contact Email: Applicant Signature, ~ filWv Date, "I' "7., 1 ·1-0 \"J 8-50 Page 1 of 6 Revised 08/19 City of Carlsbad Climate Action Plan Consistency Checklist Use the table below to determine which sections of the Ordinance Compliance checklist are applicable to your project. For alterations and additions to existing buildings, attach Building Permit Valuation worksheet. Building Permit Valuation (BPV) from worksheet:$ I , '1. ll../ ,01 ·f. Ol./ Construction Type D Residential D New construction D Additions and alterations: D BPV < $60,000 D BPV ~ $60,000 D Electrical service panel upgrade only D BPV ~ $200,000 ~ Nonresidential D New construction D Alterations: ~BPV ~ $200,000 or additions~ 1,000 square feet J,f_ BPV ~ $1,000,000 D ~ 2,000 sq. ti. new roof addition Complete Sectlon(sj Notes: A high-rise residential building is 4 or more stories, including a Low-rise High-rise mixed-usJ building in which at least 20% of its conditioned floor area is residential use 2A, 3A, 1B, 2B, 4A 3B, 4A N/A N/A All residential additions and alterations 1-2 family dwe.llings and townhouses with attached garages 1A, 4A 4A only *Multi-family dwellings only where interior finishes are removed 1A, 4A* 1B, 4A* and significant site work and upgrades to structural and mechanical, electrical, and/or plumbing systems are proposed 1 B, 2B, 3B, 4B and 5 1B, 5 1B, 2B, 5 Building alterations of~ 75% existing gross floor area 2B, 5 1 B also applies if BPV ~ $200,000 t applicable and exception items, and provide s,uppor:ting calculations and documentation as necessary. 1. Energy Efficiency Please refer to Carlsbad Municipal Code (CMC) sections 18.21.155 and 18.30.190, and the California Green Building Standards Code (CAL Green) for more information when completing this section. A D Residential addition or alteration ~ $60,000 building permit valuation. D N/A _________ _ See CMC section 18.30.190. D Exception: Home energy score~ 7 (attach certification) Year Built Single-family Requirements Multi-family Requirements D Before 1978 Select one: D Duct sealing D Attic insulation D Cool roof D Attic insulation D 1978 and later Select one: D Lighting package D Water heating Package □ Between 1978 and 1991 Select one: □ Duct sealing □ Attic insulation D Cool roof D 1992 and later Select one: D Lighting package D Water heating package B. JZI Nonresidential* new construction or alterations<! $200,000 building permit valuation, or additions~ 1,000 square feet D N/A Updated 8/15/2019 2 City of Carlsbad Climate Action Plan Consistency Checklist See CMC 18.21.155 and CALGreen Appendix A5, Division A5.2 -Energy Efficiency. AS.203.1.1 Choose one: D .1 Outdoor lighting D .2 Warehouse dock seal doors □ .3 Restaurant service water heating (comply with California Energy Code section 140.5, as amended) D .4 Daylight design PAFs □ .5 Exhaust air heat rec<:Nery AS.203.1.2.1 Choose one as applicable: □ .95 Energy budget ~ .90 Energy budget AS.211 .1 .. □ On-site renewable energy AS.211.3 .. D Green power 0f offered by local utility provider, 50% minimum renewable sources) \.'j vn\lt\'j pCSVl(A,0v [Ji NIA Nd\: off-eY--e.e( AS:2..\(. 3 AS.212.1 D Elevators and escalators NIA AS.213.1 D Steel framing N/A • lndudes hotels/motels and high-rise residential buildings .. For alterations ~ $1,000,000 BPV and affecting > 75% existing gross floor area, or alterations that add 2,000 square feet of new roof addition: comply with CMC 18.30.130 instead. 2. Photovoltaic Systems A D Residential new construction (for low-rise residential building permit applications submitted after 1/1/20). Refer to 2019 California Energy Code section 150.1(c)14 for requirements. Notes: 1) High-rise residential buildings are subjectto nonresidential photovoltaic requirement (28 below) instead. 2) If project includes installation of an electric heat pump water heater pursuant to CMC 18.30.150(8) (high-rise residential) or 18.30.170(8) (low-rise residential), increase system size by .3kWdc if PV offset option is selected. Floor Plan ID (use additional CFA #d.u. Calculated kWdc* sheets if necessary) Total System Size: kWdc = (CFAx.572) / 1,000 + (1 .15 x#d.u.) 'Fonmula calculation v.tiere CFA = conditional floor area, #-Ou = number of dv.iellings per plan type If proposed system size is less than calculated size, please explain. Exception D □ D D kWdc 8.~onresidential new construction or alterations 2:$1,000,000 BPV and affecting 2:75% existing floor area, or addition that increases roof area by 2:2,000 square feet Please refer to CMC section 18.30.130 when completing this section. Note: This section also applies to high-rise residential and hotel/motel buildings. Choose one of the following methods: 'fJ. Gross Floor Area (GFA) Method GFA: 1-c ( I oL/ Min. System Size: ~ kWdc I D If < 10,000s.f. Enter: 5 kWdc C&l!_f ~ 10,000s.f. calculate: 15 kWdc x (GFA/10,000)"" **Round building size factor to nearest tenth, and round system size to nearest whole number. D Time-Dependent Valuation Method Updated 8/15/2019 3 City of Carlsbad Climate Action Plan Consistency Checklist Annual TDV Energy use: ...... ______ x .80= Min. system size: ____ _ kWdc ***Attach calculation documentation using modeling software approved by the California Energy Commission. 3. Water Heating A D Residential and hotel/motel new construction Please refer to CMC sections 18.30.150 and 18.30.170 when completing this section. □ For systems serving individual dwelling units choose one: □ Heat pump water heater AND Compact hot water distribution AND Drain water heat recovery (low-rise residential only) □ Heat pump water heater AND PV system .3 kWdc larger than required in CMC section 18.30.130 (high rise residential hotel/motel) or CA Energy Code section 150.1(c) 14 (low-rise residential) D Heat pump water heater meeting NEEA Advanced Water Heating Specification Tier 3 or higher D Solar water heating system that is either .60 solar savings fraction or 40 s.f. solar collectors □ Exception: D For systems serving multiple dwelling units, install a central water-heating system with all of the following: D Gas or propane water heating system D Recirculation system per CMC 18.30.150(8) (high-rise residential, hotel/motel) or CMC 18.30.1 ?0(B) (low- rise residential) D Solar water heating system that is either: D .20 solar savings fraction D .15 solar savings fraction , plus drain water heat recovery □ Exception: B. D Nonresidential new construction Please refer to Carlsbad Ordinance CMC section 18.30.150 when completing this section. D Water heating system derives at least 40% of its energy from one of the following (attach documentation): D Solar-thermal D Photovoltaics D Recovered energy D Water heating system is (choose one): D Heat pump water heater □ Electric resistance water heater(s) □Solar water heating system with .40 solar savings fraction □ Exception: Updated 8/1 5/2019 ::. 4 City of Carlsbad Climate Action Plan Consisten cy Checklist 4. Electric Vehicle Charging A. ----~ . .Jsidential New construction and major alterations* __ ,f'_lease refer to Carlsbad Ordinance CMC section 18.21.140 when com letin this section. · 1ne and two-family residential dwelling or townhouse with attached garage; • )ne EVSE Ready parking space required □ Exception : --□-~ulti-family residential· D Exception · Total Parking Spaces EVSE Spaces Proposed Capable I Ready I Installed I I Calculations: Total EVSE spaces= .10 x Total parking (rounded up to nearest 'M'lole number) EVSE Installed= Total EVSE Spaces x .50 (rounded up to nearest 'M'lole number) EVSE other= Total EVSE spaces -EVSE Installed (EVSE other may be "Capable," "Ready" or "Installed.") I Total I *Major alterations are: (1) for one and two-family dwellings and townhouses with attached garages, alterations have a building permit valuation ;:: $60,000 or include an electrical service panel upgrade; (2) for multifamily dwellings (three units or more without attached garages), alterations have a building permit valuation ;:: $200,000, interior finishes are removed and significant site work and upgrades to structural and mechanical, electrical, and/or plumbing systems are proposed. B D Nonresidential new construction (includes hotels/motels) D Exception · Total Parking Spaces EVSE Spaces Proposed Capable I Ready I Installed I Total I I I Calculation: Refe r to the table below: Total Number of Parkinq Spaces provided Number of required EV Spaces Number of required EVSE Installed Spaces □ 0-9 1 1 □ 10-25 2 1 D 26-50 4 2 D 51-75 6 3 □ 76-100 9 5 D 101-150 12 6 □ 151-200 17 9 D 201 and over 1 0 percent of total 50 percent of Required EV Spaces Updated 8/15/2019 5 City of Carlsbad Climate Action Plan Consistency Checklist 5. . Transportation Demand Management (TOM): Nonresidential ONLY l An approved Transportation Demand Management (TOM) Plan is required for all nonresidential projects that meet a threshold of employee-generated ADT. City staff will use the table below based on your submitted plans to determine whether or nor your permit requires a TOM plan. If TOM is applicable to your permit, staff will contact the applicant to develop a site-specific TOM plan based on !he permit details. Acknowledgment: Office (all)2 20 Restaurant 11 Retaib 8 Industrial 4 Manufacturing 4 Warehousin 4 , Unless otherwise noted, rates estimated from /TE Trip Generation Manual, 1(JlhEdition 13 11 4.5 3.5 3 1 2 For all office uses, use SAN DAG rate of 20 ADT/1 ,000 sf to calculate employee ADT 3 Retail uses include shopping center, variety store, supermarket, gyms, pharmacy, etc. Other commercial uses may be subject to special consideration Sample calculations: Office: 20,450 sf 1. 20,450 sf/ 1000 x 20 = 409 Employee ADT Retail: 9,334 sf 1. First 1,000 sf = 8 ADT 2. 9,334 sf -1,000 sf= 8,334 sf 3. 8,334 sf/ 1,000 x 4.5 + 8 = 46 Em lo ee ADT I acknowledge that the plans submitted may be subject to the City of Carlsbad's Transportation Demand Management Ordinance. I agree to be contacted should my permit require a TOM plan and understand that an approved TOM plan is a condition of permit issuance. Date: 9_:• 21-2-Q/C) Person other than Applicant to be co Name (Printed): ________ _;__ __________ _ Phone Number: _____ _ Email Address: ___________________ _ Updated 8/15/2019 6 •