HomeMy WebLinkAbout2817 CAZADERO DR | 2819 CAZADERO DR; ; CB012497; Permit06-12-2007
Job Address
Permit Type
Parcel No
Valuation
Occupancy Group
# Dwelling Units 2
Bedrooms 6
Project Title
City of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
Residential Permit Permit No CB012497
Building Inspection Request Line (760) 602-2725
2817 CAZADERO DR CBAD
RESDNTL
2153204500
$360,380 00
Sub Type DUP
Lot # 306
Construction Type VN
Reference #
Structure Type MF2-4
Bathrooms 5
3862 SF+1177 SF GAR, 2817 &
2819 CAZADERO DR
Status
Applied
Entered By
Plan Approved
Issued
Inspect Area
Ong PC#
Plan Check#
WITHDRAW
07/25/2001
RMA
Applicant
MARK WITHERALL
2912 LA COSTA AV
CARLSBAD CA 92009
760815-5994
Owner
HASHIMOTO LIVING TRUST 05-12-93
6053CHESBROAVE
SAN JOSE CA 95123
Building Permit
Add'l Building Permit Fee
Plan Check
Add'l Plan Check Fee
Plan Check Discount
Strong Motion Fee
Park in Lieu Fee
Park Fee
LFM Fee
Bridge Fee
Other Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'l Renewal Fee
Other Building Fee
HMP Fee
Pot Water Con Fee
Meter Size
Add'l Pot Water Con Fee
Reel Water Con Fee
$1,35044 Meter Size
$000 Add'l Reel Water Con Fee
$877 79 Meter Fee
$0 00 SDCWA Fee
$0 00 CFD Payoff Fee
$3604 PFF (3105540)
$0 00 PFF (4305540)
$0 00 License Tax (3104193)
$620 00 License Tax (4304193)
$0 00 Traffic Impact Fee (3105541)
$848 00 Traffic Impact Fee (4305541)
$0 00 Sidewalk Fee
$0 00 PLUMBING TOTAL
$0 00 ELECTRICAL TOTAL
$0 00 MECHANICAL TOTAL
$0 00 Housing Impact Fee99 Housing InLieu Fee
$0 00 Housing Credit Fee
Master Drainage Fee
SO 00 Sewer Fee
$0 00 Additional Fees
TOTAL PERMIT FEES
$000
$000
$000
$000
$6,558 92
$000
$000
$000
$970 00
$000
$000
$246 00
$6000
$10700
$2,925 00
$000
$000
$1224
$000
$000
$14,611 43
Total Fees $14,611 43 Total Payments To Date $877 79 Balance Due $13,73364
Inspector
FINAL APPROVAL
Date Clearance
NOTICE Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as 'lees/exactions" You have 90 days from the date this permit was issued to protest imposition of these fees/exactions If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a}, and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3 32 030 Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this proiect NOR DOES IT APPLY to any
fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the statute of limitations has previously otherwise expired
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
1635 Faraday Ave , Carlsbad, CA 92008
.'PROJECT INFOJplA7 >y *7 5* x
FOR OFFICE USE ONLY
PLAN CHECK NO
EST VAL
Plan Ck Deposit
Validated By
Address (include BIdg/Suite #}
Lot No Subdivision Name/Number
Business Name (at this address)
2^_
Unit No Phase No Total # of units
Existing Use Proposed Use
fjame Address City State/Zip Telephone #
S -, '^CONTRACTOR (f COMPANY NAME' '' ¥ !' *! ?"f >'" "" 'T '^P Kl^iiC^i*/'SI2! h! Hh'S.1, \ ,[,>" 'i !/!', i <s, 0"$ ^UrJ^, L,*'',' E '' ™i 'I ''I1* i')li r/*1. ~i<!" I -
(Sec 7031 5 Business and Professions Code Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Codel or that he is exempt therefrom, and the basis for the alleged
exemption Any violation of Section 7031 5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars [S500])
Name
State License #
Address
License Class
City State/Zip
City Business License #
Telephone #
Designer Name
State License #
Address City State/Zip Telephone
Workers' Compensation Declaration I hereby affirm under penalty of perjury one of the following declarations
Q I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued
Q I have and will maintain workers compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued My worker's compensation insurance carrier and policy number are
Insurance Company Policy No Expiration Date ___^_
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS [$1001 OR LESS)
[H CERTIFICATE OF EXEMPTION I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as
to become subject to the Workers' Compensation Laws of California
WARNING Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred
thousand dollars f$10u,00<J), in addition totoe cost of compensation damages as provided for in Section 3706 of the Labor code interest and attorney s fees
SIGNATURE jffl&svfi- ^-1^^^-^^^ DATE
I hereby affirm that I am exempt from the Contractor's License Law for the following reason
12 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
{Sec 7044, Business and Professions Code The Contractor s License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale If, however, the building or improvement is
sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale)
jjjfc I, as owner of the property, am exclusively contracting with licensed contractors to construct the project {Sec 7044, Business and Professions Code The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law)
Q I am exempt under Section Business and Professions Code for this reason
1 I personally plan to provide the major labor and materials for construction of the proposed property improvement £3 YES C^NO
2 I (have / have not) signed an application for a building permit for the proposed work
3 I have contracted with the following person (firm) to provide the proposed construction (include name / address / phone number / contractors license number)
4 I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone
number / contractors license number)
5 I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phone number / type
of work)
PROPERTY OWNER SIGNATURE DATE
' PERMITS ONLY,f|f ^"^7^ I ," l!! "!> H™ - » (\, ." 'SJi'ni If!!^' , , O" '" <'! 't !^C' "". ?J j|£llU $
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? Q YES Q NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? Q YES l~l NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Q YES Q NO
IF ANY OF THE ANSWERS ARE YES A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT
i8"" CONSTRUCTlONrLENDING^AGENCY» _KV S'J7 V '*>"„ lit" C, ' ' ^ * » >$ „ !< Tl- 1/V \i Yt^',1 ?,,,. , ;V"™I"™ ';j "'jfs s i" »~, 'J |t \'t JT ^/"7'Ti'J
I hereby affirm that there is a construction lending agency for the performance of the work for which this permit is issued {Sec 3097(i) Civil Code)
LENDER S NAME _ _____ LENDER S ADDRESS _ ______
9 'APPLICANT CERTIFICATION^' "I-: .-p-n 7-«-r;T;<," ' $r^ «~ 'f»'^ ¥ ;• •»'„ I <n\ •' ~trt V* Yl,/s *' ';','j f|,5s ;,A,W< " V'l > T^f'i^:.^
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate I agree to comply with all
City ordinances and State laws relating to building construction I hereby authorize representatives of the CitV of Carlsbad to enter upon the above mentioned
property for inspection purposes I ALSO AGREE TO SAVE INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT
OSHA An OSHA permit is required for excavations over 5'0" deep and demolition or construction of structures over 3 stories in height
EXPIRATION Every permit issued by the building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work
authorized by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned
at any time after the work is commenced for a penqcLpf 180 djjys (Section 1064 4 Uniform Building Code)
APPLICANT S SIGNATURE DATE
WHITE File YELLOW Applicant PINK Finance
04/22/2002
MARKWITHERALL
2912 LA COSTA AV
CARLSBAD CA92009
Re
Application Date 07/25/2001 0 00 00
Plan Check # CB012497
Address 2817 CAZADERO DR
Expiration Date 07/25/2002 0 00 00
Permit Type RESDNTL
Description 3862 SF+1177 SF GAR, 2817 &
2819 CAZADERO DR
You applied to have your plans checked on the date noted above To date, the related building
permit has not been obtained The original plan review application will expire as no building permit
has been issued
Plans submitted and not retrieved from the building department prior to the plan check expiration
date noted above will be destroyed
The provisions of sections 304 (d) of the Uniform Building Code state
"Section 304 9d) Expiration of Plan Review
Applications for which no permit is issued within one year following the date of
application shall expire by limitation, and plans and other data submitted for review
may thereafter be returned to the applicant or destroyed by the Building Official
In order to renew action on an application after expiration, the applicant shall
resubmit plans and pay a new plan review fee"
In order to provide better service, please indicate your handling choice for the plans originally
submitted and return this letter to the Building Department
Project Abandoned - I will pick up plans within 10 days
Project Abandoned - Plans may be destroyed
If you have any questions, please contact the Building Department at (760) 602-2718
Raenette Abbey
Building Department
EsGil Corporation
In Partners/tip with government foT ftuiltfiTig Safety
DATE September 20, 2001
JURISDICTION Carlsbad
PLAN CHECK NO 01-2497 SET II
PROJECT ADDRESS 2817 & 2819 Cazadero St.
PROJECT NAME Duplex for Mark Witherall
O.APPUCANT
Q PLAN REVIEWER
Q FILE
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
XI The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
XI The applicant's copy of the check list has been sent to
Mark Witherall
2912 La Costa Ave , Carlsbad, CA 92009
Esgil Corporation staff did not advise the applicant that the plan check has been completed
X] Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Mark Witherall Telephone # (760) 815-5994
Date contacted c*-3uo-<* (by. &v) Fax # (760)635-3844
Mail ~~ Telephone Fax-^ In Person
REMARKS.
By Sergio Azuela
Esgil Corporationn MB n E PC
Enclosures
9/13 trnsmtl dot
9320 Chesapeake Dnve, Suite 208 + San Diego, California 92123 + (858)560-1468 + Fax (858) 560-1576
^ Carlsbad 01-2497 II
September 20, 2001
RECHECK PLAN CORRECTION LIST
JURISDICTION Carlsbad PLAN CHECK NO 01-2497
PROJECT ADDRESS 2817 & 2819 Cazadero St. SET II
DATE PLAN RECEIVED BY DATE RECHECK COMPLETED
ESGIL CORPORATION 9/13 September 20, 2001
REVIEWED BY Sergio Azuela
FOREWORD (PLEASE READ).
This plan review is limited to the technical requirements contained in the Uniform Building Code, Uniform
Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and disabled access This plan review is based on regulations enforced
by the Building Department You may have other corrections based on laws and ordinances enforced by
the Planning Department, Engineering Department or other departments
The following items listed need clarification, modification or change All items must be satisfied before the
plans will be in conformance with the cited codes and regulations Per Sec 10643, 1997 Uniform
Building Code, the approval of the plans does not permit the violation of any state, county or city law
N
A Please make all corrections on the original tracings, as requested in the correction list Submit
three sets of plans for commercial/industrial projects (two sets of plans for residential
projects) For expeditious processing, corrected sets can be submitted in one of two ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave , Carlsbad, CA 92008, (760) 602-2700 The City will
route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire
Departments
2 Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468 Deliver ail remaining
sets of plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete
B To facilitate rechecking, please identify, next to each item, the sheet of the plans upon which
each correction on this sheet has been made and return this sheet with the revised plans
C The following items have not been resolved from the previous plan reviews The original correction
number has been given for your reference In case you did not keep a copy of the prior correction list,
we have enclosed those pages containing the outstanding corrections Please contact me if you have
any questions regarding these items
D Please indicate here if any changes have been made to the plans that are not a result of corrections
from this list If there are other changes, please briefly describe them and where they are located on
the plans Have changes been made not resulting from this list?
QYes QNo
Carlsbad 01-2497 II
September 20, 2001
3 A smoke detector is missing at the Entry on the first floor of the Unit 2
7 Guardrails (Section 509 1)
a) Shall be detailed showing adequacy of connections to resist the horizontal
force prescribed in Table 16-B,
i) It appears that the post spacing is 16'-6" as shown on the plans
This spacing will be clearly inadequate Please clearly show on
plans the post spacing Also the detail provided does not show the
connection between the railing and the exterior wall and the lag
bolts provided appear to be subjected to withdrawn tension forces,
instead of shear forces Please clarify
10 Provide ICBO, or UL # for the roof assembly
21 The following anchor bolt requirements shall apply in Seismic Zones 3 and 4, per
Section 18066.1
a) The minimum nominal anchor bolt diameter shall be 5/8-inch (for Seismic
Zone 4 only) Note This will require a minimum distance from the ends
of sill plates to be 4-3/8" (and a maximum of 12")
0 Revise details 1 and 2 on sheet S-1
48 Please clearly show on detail B of sheet 7
4 That surface water will dram away from building
4 A perforated pipe and a filter (gravel) material backfill on the back side of the
retaining wall (to mitigate hydrostatic pressure)
If you have any questions regarding these plan review items, please contact Sergio
Azuela at Esgil Corporation Thank you
EsGil Corporation
In yartnersHif vsitfi. government for tBui&tnff Safety
DATE April 30, 2O02 a APPLICANT
JURISDICTION Carlsbad Q PLAN REVIEWER
a FILE
PLAN CHECK NO 01-2497 SET I & II
PROJECT ADDRESS 2817 & 2819 Cazadero St.
PROJECT NAME Duplex for Mark Witherall
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on'the enclosed check list
and should be corrected and resubmitted for a complete recheck
The check list transmitted herewith is for your information The plans are"' being held at Esgil
Corporation until corrected plans are submitted for recheck
/
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person
The applicant's copy of the check list has been sent to
Esgil Corporation staff did not aSvise the applicant that the plan check has been completed
f
Esgi! Corporation staff did advise the applicant that the plan check has been completed
Person contacted - Telephone #
Date contacted (by ) Fax #
Mail Telephone Fax In Person
REMARKS Plans are sent back to the City by the attached City request
By Sergio Azuela Enclosures
Esgil Corporation
D GA D MB D EJ D PC LOG trnsmtldot
9320 Chesapeake Drive, Suite 208 * San Diego, California 92123 * (858)560-1468 + Fax (858) 560-1576
3PR-30-2002 TUE 09:17 Afl CITY OF CftRSLBAD FAX NO. 760 602 8558 P. 01
1635 Faraday Av
Cartsbad CA 92008
Phone (760) 602-2718
Fax (760)602-8558
CITY OF CARLSBAD
BUILDING
DEPARTMENT
To;From; Raenette Abbey
Fax:Pages:
Phono:Date:
Re:cc-
D Urgent D For Revlaw D Please Comment D Pleas* Reply H Please Recycle
• Comments:
,1PR-3Q-20Q2 TUE 09:18 AN CITY OF CARSLBAD FAX NO. 760 602 8558 P. 02
EsGi[ Corporation
2« fPartnersfap w{tf\ govtmnunt for Quitting Safety
DATE: September 20, 2OO1
JURISDICTK3N Carlsbad Q PLAN REVIEWER
0 FILE
PLAN CHECK NO. O1-2497 SET XI
PROJECT ADDRESS 2817 & 2819 Cazadero St.
PROJECT NAME Duplex for Mark Wit he rail
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significantdc^ciencies identified on the enclosed check list
and should be corrected and resubmttted fb^rcomplete recheck
X] The check list transmitted herewith is for your^fcpnatjorA The plans are being held at Esgil
Corporation until corrected plans are
The applicant's copy of thej|necj< lis\isl^lojjja for the jurisdiction to forward to the applicant
contact person
/<] The applicant's copy of the checkjisj;!hais been sent to:
MarkWrtherall W^
2912 La Costa Ave., Carlsbad, CA 92009
Esgil Corporation staff did not advise the applicant that the plan check has been completed
Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Mark Witherall Telephone #- (760) 815-5994
Date contacted. ^-2*°"* (by £w) Fax #. (760)635-3844
Mail ~- Telephone Fax^ In Person
REMARKS.
By Sergio AzueJa Enclosures;
Esgil Corporation
D GA n MB Q EJ D PC 9/13 trnsmUdQl
9320 Chesapeake Dnve, Suite 208 + San Diego, California 92123 * (858)560-1468 * Fax (858) 560-1576
EsGil Cbrporation
-. ' In Partnership with government for 'Building Safety
DATE August 7, 2001 OAPELiqANT
JURISDICTION Carlsbad
a FILE
PLAN CHECK NO 01-2497 SET I
PROJECT ADDRESS 2817 & 2819 Cazadero St.
PROJECT NAME Duplex for Mark Witherall
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck
X] The check list transmitted herewith is for your information The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck
The applicant's copy of the check list is'enclosed for the jurisdiction to forward to the applicant
contact person
The applicant's copy of the check list has been sent to
Mark Witherall
2912 La Costa Ave , Carlsbad, CA 92009
Esgil Corporation staff did not advise the applicant that the plan check has been completed
X] Esgil Corporation staff did advise the applicant that the plan check has been completed
Person contacted Mark Witherall Telephone # (760) 815-5994
Date contacted &-&** (by BE*) Fax # (760)015-5944
Mail-'' Telephone-^ Fax^ In Person " ^
REMARKS
By Sergio Azuela Enclosures
Esgil Corporation
C] GA D MB D EJ D PC 7/26 trnsmtl dot
9320 Chesapeake Drive, Suite 208 * San Diego, California 92123 + (858)560-1468 + Fax (858) 560-1576
Carlsbad 01-2497
August 7, 2001
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK NO 01-2497 JURISDICTION Carlsbad
PROJECT ADDRESS 2817 85 2819 Cazadero St.
FLOOR AREA Duplex Dwelling 3,862 SF STORIES 2
Garage 1,177 SF
HEIGHT 23 FT
REMARKS
DATE PLANS RECEIVED BY
JURISDICTION 7/25/01
DATE INITIAL PLAN REVIEW
COMPLETED August 7, 2001
DATE PLANS RECEIVED BY
ESG1L CORPORATION 7/26
PLAN REVIEWER Sergio Azuela
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled This plan review
is based on regulations enforced by the Building Department You may have other corrections
based on laws and ordinance by the Planning Department, Engineering Department, Fire
Department or other departments Clearance from those departments may be required prior to
the issuance of a building permit
Present California law mandates that residential construction comply with the 1998 edition of
the California Building Code (Title 24), which adopts the following model codes 1997 UBC,
1997 UPC, 1997 UMC and 1996 NEC (all effective 7/1/99)
The above regulations apply to residential construction, regardless of the code editions adopted
by ordinance
The following items listed need clarification, modification or change All items must be satisfied
before the plans will be in conformance with the cited codes and regulations Per Sec 106 4 3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad 01-2497
August 7, 2O01
• PLANS
1 Please make all corrections on the original tracings, as requested in the correction
list Submit three sets of plans for commercial/industrial projects (two sets of plans
for residential projects) For expeditious processing, corrected sets can be
submitted in one of two ways
1 Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave , Carlsbad, CA 92008, (760)
602-2700 The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments
2 Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments
NOTE Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete
2 Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 1998 edition of the California Building Code (Title 24), which
adopts the 1997 UBC, UMC and UPC and the 1996 NEC
• FIRE PROTECTION
3 Show locations of permanently wired smoke detectors with battery backup
a) Inside each bedroom
b) Centrally located in corridor or area giving access to sleeping rooms
c) On each story
d) When sleeping rooms are upstairs, at the upper level in close proximity to
the stair
• NOTE Detectors shall sound an alarm audible in all sleeping areas of the unit
Section 310 9 1
• GENERAL RESIDENTIAL REQUIREMENTS
4 Provide a fully dimensioned floor plan showing the size of all rooms Also clearly
show the type and size of all windows on the floor plans Section 106 3 3
5 Glazing in the following locations should be of safety glazing material in
accordance with Section 2406 4 (see exceptions)
a) Fixed and sliding panels of sliding door assemblies and panels in swinging
doors other than wardrobe doors
Carlsbad 01-2497
August 7, 2001
b) Doors and enclosures for hot tubs, whirlpools, saunas, steam rooms,
bathtubs and showers and in any portion of a building wall enclosing these
compartments where the bottom exposed edge of the glazing is less than
60 inches above a standing surface and drain inlet
c) Fixed or operable panels adjacent to a door where the nearest exposed
edge of the glazing is within a 24-inch arc of either vertical edge of the door
in a closed position and where the bottom exposed edge of the glazing is
less than 60 inches above the walking surface
• Clearly show on plans which are the particular doors and windows that
will be provided with safety glass (general notes are not adequate to
resolve this correction).
• EXITS, STAIRWAYS, AND RAILINGS
6 Required exit doorways shall be not less than 36" in width and not less than 6'8"
in height Section 10033 1 3
a) Clearly show on plans all door sizes and types
7 Guardrails (Section 509 1)
a) Shall be detailed showing adequacy of connections to resist the horizontal
force prescribed in Table 16-B
8 Provide stairway and landing details Sections 1003 3 3
a) Minimum headroom is 6'-8"
9 Handrails (Section 1003 3 3 6)
a) Handrails and extensions shall be 34" to 38" above nosing of treads and
be continuous
b) Ends of handrails shall be returned or shall have rounded terminations or
bends
• ROOFING
10 Specify on the plans the following information for the roof materials, per Section
10633
a) Manufacturer's name
b) Product name/number
c) ICBO approval number, or equal
11 Per local ordinance, a Class "A" roof is required
Carlsbad 01-2497
August 7, 2001
12 Balconies and decks exposed to the weather and sealed underneath shall be
sloped a minimum of % inch per foot for drainage Section 1402 3
a) Please clearly show it at the bridge floor
13 Show the required ventilation for attics (or enclosed rafter spaces formed where
ceilings are applied directly to the underside of roof rafters) The minimum vent
area is 1/150 of attic area (or 1/300 of attic area if at least 50% of the required
vent is at least 3 feet above eave vents or cornice vents) Show area required
and area provided Section 1505 3
14 Where eave vents are installed, insulation shall not block the free flow of air A
minimum of 1" of air space shall be provided between the insulation and the roof
sheathing To accommodate the thickness of insulation plus the required 1"
clearance, member sizes may have to be increased for rafter-ceiling joists
Section 15053
15 Note on the plans "Attic ventilation openings shall be covered with
corrosion-resistant metal mesh with mesh openings of 1/4-inch in dimension "
Section 15053
• GARAGE AND CARPORTS
16 Show a self-closing door, either 1-3/8" solid core or a listed 20 minute
assembly, for openings between garage and dwelling Section 302 4
a) Please clearly specify self-closing.
17 Provide an 18" raised platform for any FAD, water heater, or other device in the
garage which may generate a flame or spark UMC Section 303 1 3, UPC
Section 510 1
• FOUNDATION REQUIREMENTS
18 Note on the plan the soils classification, whether or not the soil is expansive and
note the allowable bearing value Section 106 3 3
19 Note on plans that surface water will dram away from building and show drainage
pattern Section 1804 7
a) Clearly show it on plans adjacent to the retaining wall (see details A and B
on sheet 7)
20 Show distance from foundation to edge of cut or fill slopes ("distance-to-
daylight") and show slope and heights of cuts and fills Chapter 18
Carlsbad 01-2497
August 7, 2001
21 The following anchor bolt requirements shall apply in Seismic Zones 3 and 4, per
Section 18066 1
a) The minimum nominal anchor bolt diameter shall be 5/8-inch ((or Seismic
Zone 4 only) Note This will require a minimum distance from the ends
of sill plates to be 4-3/8" (and a maximum of 12")
i) Revise the shear wall schedule, shear walls A to G
b) Plate washers (minimum size of 2" x 2" x 3/16") shall be used on each
anchor bolt
i) Clearly show it on plans for all anchor bolts
22 If required, show size, embedment and location of hold down anchors on
foundation plan Section 106 3 3
23 If hold downs are required, note on plan that hold down anchors must be tied in
place prior to foundation inspection Section 108 5 2
• FRAMING
24 Specify truss identification numbers on the plans
25 Please show in the calculations how the redundancy was determined, per
Section 1630 1 1
26 In Seismic Zones 3 and 4, the allowable shear wall values for drywall in Table
25-I must be reduced 50 percent when considering earthquake loads This does
not apply to wind loads Footnote 1
a) Please revise the values given in the shear wall schedule for walls A to E
27 Detail shear transfer connections, including roof and floor diaphragms, to shear
walls Section 2315
a) Also cross-reference details to plans
28 Specify nail size and spacing for all floor and roof diaphragms Indicate required
blocking Maintain maximum diaphragm dimension ratios Sections 2315 and
2513
29 Show location of attic access with a minimum size of 22"x30", unless the
maximum vertical headroom height in the attic is less than 30". Access must be
provided to each separated attic area, shall be located in a hallway or other
readily accessible location and 30" headroom clearance is required above the
opening Section 1505 1
30 Specify plywood and/or particle board thickness, grade and panel span rating
Table 23-II-E-1
Carlsbad O1-2497
August 7, 2001
• MECHANICAL (UNIFORM MECHANICAL CODE)
31 Show minimum 30" deep unobstructed working space in front of furnace
Section 307, UMC
a) At Unit 1 the plans are showing 24"
32 Specify on the plans the following information for the fireplace(s), per Section
10633
a) Show height of chimney above roof per I C B O approval or UBC Table
31-B
b) Note on the plans that approved spark arresters shall be installed on all
chimneys UBC, Section 3102 3 8
33 Provide dryer vent to outside The maximum length is 14 feet with two 90-degree
elbows UMC, Section 504 3 2
• ELECTRICAL (NATIONAL ELECTRICAL CODE)
34 Note on the plans that receptacle outlet locations will comply with NEC Art
210-52(a)
35 For a single-family dwelling unit (and for each unit of a duplex), show that at least
one receptacle outlet accessible at grade level will be installed outdoors at the
front and back of the dwelling NEC Art 210-52 (e) This receptacle must be
GFCI protected
36 Note on the plans that bathroom receptacle outlets shall be supplied by a
minimum of one 20-ampere branch circuit Such circuits shall have no other
outlets This circuit may serve more than one bathroom NEC Art 210-52(d)
37 Show on the plan that receptacle outlets in hallways comply with NEC Art
210-52(h), which reads as follows
For hallways of 10 feet or more in length at least one receptacle outlet shall be
required
38 Show at least one wall switch-controlled lighting outlet to be installed in every
habitable room, in bathrooms, hallways, stairways, attached garages, and
detached garages with electric power, and at the exterior side of outdoor
entrances or exits At interior stairways show 3-way switching for lighting outlets
at each floor level where there are six or more steps NEC Art 210(a)
39 Show on the plan that ground-fault circuit-interrupter protection complies with
NEC Art 210-8, which reads as follows
All 125-volt, single-phase, 15- and 20- ampere receptacles installed in
bathrooms, garages, basements, outdoors, kitchen counters and at wet bar
sinks
Carlsbad 01-2497
August 7, 2001
• PLUMBING (UNIFORM PLUMBING CODE)
40 In the garage, provide an adequate barrier to protect water heater from vehicle
damage An 18" platform for the water heater does not satisfy this requirement
UPC, Section 5103
41 Show T and P valve on water heater and show route of discharge line to exterior
UPC, Section 608 5
• ENERGY CONSERVATION
42 The window schedule shall clearly describe the required U-factor and solar heat
gam coefficient (SHGC) values and demonstrate compliance with the Title 24
energy calculations
43 Show the make, model, type and efficiency of the space heating (or cooling)
system
44 Provide fluorescent general lighting (40 lumens per watt minimum) in kitchen(s)
and bathrooms (containing a tub or shower)
45 Note on the plans "The manufactured windows shall have a label attached
certified by the National Fenestration Rating Council (NFRC) and showing
compliance with the energy calculations "
• MISCELLANEOUS
46 Please provide a complete detail of the framing at the stairway well of Unit 1
47 Please provide drag/strut members and connections at "re-entrant corners" to
comply with Section 1633 2 9 items 6 and 7
CARLSBAD SPECIAL CODE REQUIREMENTS
48 Show details for waterproofing masonry walls below grade where interior finished
floor exists (City Policy No. 80-8)
49 Nails for shear transfer connection (using A35's, etc ) may not be driven parallel to
the flanges of TJI's (i e , along the sides), per city policy, unless specific written
approval from Trus-Joist Macmillan is first obtained Details or notes on the plans
should make this clear Nails may be driven perpendicular to TJI flanges
50 New residential units must be pre-plumbed for future solar water heating Note
"two roof jacks must be installed" where the water heater is in the one story garage
and directly below the most south facing roof (City Ordinance No 8093)
Carlsbad 01-2497
August 7, 2001
51 Note "two 3/4" copper pipes must be installed to the most convenient future solar
panel location when the water heater is not in a one story garage and is not directly
below the most south facing roof (City Ordinance No 8093)
52 All piping for present or future solar water heating must be insulated when in areas
that are not heated or cooled by mechanical means (City Policy)
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i e , plan sheet, note or detail number, calculation page, etc
Please indicate here if any changes have been made to the plans that are not a result
of corrections from this list If there are other changes, please briefly describe them
and where they are located in the plans
Have changes been made to the plans not resulting from this correction list? Please
indicate
Yes Q No U
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123, telephone number of 858/560-1468, to
perform the plan review for your project If you have any questions regarding these plan
review items, please contact Sergio Azuela at Esgil Corporation Thank you
Carlsbad O1-2497
August 7, 20O1
JURISDICTION Carlsbad
VALUATION AND PLAN CHECK FEE
PLAN CHECK NO 01-2497
PREPARED BY Sergio Azuela DATE August 7, 2001
BUILDING ADDRESS 2817 & 2819 Cazadero St. Duplex for Mark Witherall
BUILDING OCCUPANCY. R-3&U-1 TYPE OF CONSTRUCTION VN
BUILDING
PORTION
Dwelling
Garage
-
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code
AREA
(Sq Ft)
3862
1177
3862
cb
Valuation
Multiplier
8200
2300
300
By Ordinance
Reg
Mod
VALUE ($)
316,684
27,071
11,586
355,341
$1,335.04
1994 UBC Plan Check Fee
Type of Review
D Repetitive FeeRepeats
0 Complete Review
D
Other
Hourly
Esgil Plan Review Fee
Structural Only
Hour
$867.78
$747.62
Comments
Sheet 1 of 1
macvalue doc
City of Carlsbad
~ '—™~ ^ V^H^HW^H^Mw^^^^V^^^^^^^^WM^^^^^B^^^^^^^^^M^^^^^HPublic Works — Engineering
BUILDING PLANCHECK CHECKLIST
DATE PLANCHECK NO CB
BUILDING ADDRESS \r
PROJECT DESCRIPTION
ASSESSOR'S PARCEL NUMBER EST VALUE *3GO ,
ENGINEERING DEPARTMENT
APPROVAL
The item you have submitted for review has been
approved The approval is based on plans,
information and/or specifications provided in your
submittal, therefore any changes to these items after
this date, including field modifications, must be
reviewed by this office to insure continued
conformance with applicable codes Please review
carefully all comments attached, as failure to comply
with instructions in this report can result in
suspension of permit to build
A Right-of-Way permit is required prior to
construction of the following improvements
Please
marked
or sp
codes ar
DENIAL
the) attached report of deficiencies
ake necessary corrections to plans
fs for compliance with applicable
sandards Submit corrected plans and/or
specifications to this office for review
By Date
FOR OFFICIAL USE ONLY,
HORIZATION TO ISSUE BUILDING PERMIT:" '
Date'
ATTACHMENTS
Dedication Application
Dedication Checklist
Improvement Application
Improvement Checklist
Future Improvement Agreement
Grading Permit Application
Grading Submittal Checklist
Right-of-Way Permit Application
Right-of-Way Permit Submittal Checklist
and Information Sheet
Sewer Fee Information Sheet
ENGINEERING DEPT CONTACT PERSON
Name Casey R Arndt
City of Carlsbad
Address 1635 Faraday Avenue, Carlsbad, CA 92008
Phone (760) 602-2775
CFDJNFORMATION
Parcel Map No
Lots
Recordation
Carlsbad Tract
, CA 9200^-7314 - (76O) 6O2-272O - FAX (760)
BUILDING PLANCHECK CHECKLIST
SITE PLAN
Provide a fully dimensioned site plan drawn to scale Show
orth Arrow
ting & Proposed Structures
ing Street Improvements
bperty Lines
Easements
ght-of-Way Width & Adjacent Streets
fiveway widths f/vcf- /te^kx/^
.xisting or proposed sewer lateral
"sting or proposed water service
Existing or proposed irrigation service
CD 2 Show on site plan
Drainage Patterns
Building pad surface drainage must maintain a minimum slope of one
.percent towards an adjoining street or an approved drainage course
THE FOLLOWING NOTE "Finish grade will provide a minimum positive
drainage of 2% to swale 5' away from building "
istmg & Proposed Slopes and Topography
type, location, alignment of existing or proposed sewer and water service (s)
serves the project Each unit requires a separate service, however, second
Dwelling units and apartment complexes are an exception
ewer and water laterals should not be located within proposed driveways, per
standards
elude on title sheet
Jite address
jsessor's Parcel Number
£T Legal Description
For commercial/industrial buildings and tenant improvement projects, include
total building square footage with the square footage for each different use,
existing sewer permits showing square footage of different uses (manufacturing,
warehouse, office, etc ) previously approved
EXISTING PERMIT NUMBER DESCRIPTION
H \Developmenl Servicea\MASTERS\CHECKUST5\Buildmg Plancheck Cklsl Form do
BUILDING PLANCHECK CHECKLIST
3
n
RD DISCRETIONARY APPROVAL COMPLIANCE
4a Project does not comply with the following Engineering Conditions of approval for
Project No
n n 4b All conditions are in compliance Date
n
DEDICATION REQUIREMENTS
5 Dedication for all street Rights-of-Way adjacent to the building site and any storm
drain or utility easements on the building site is required for all new buildings and
for remodels with a vafue at or exceeding S 15.000 . pursuant to Carlsbad
Municipal Code Section 18 40 030
Dedication required as follows
Dedication required Please have a registered Civil Engineer or Land Surveyor
prepare the appropriate legal description together with an 8 W x 11" plat map and
submit with a title report All easement documents must be approved and signed
by owner(s) prior to issuance of Building Permit Attached please find an
application form and submittal checklist for the dedication process Submit the
completed application form with the required checklist items and fees to the
Engineering Department in person Applications will not be accept by mail or fax
Dedication completed by Date
D
IMPROVEMENT REQUIREMENTS
6a All needed public improvements upon and adjacent to the building site must be
constructed at time of building construction whenever the value of the
construction exceeds $ 75.000 .... pursuant to Carlsbad Municipal Code Section
18 40 040
Public improvements required as follows
Attached please find an application form and submittal checklist for the public
improvement requirements A registered Civil Engineer must prepare the
appropriate improvement plans and submit them together with the requirements
on the attached checklist to the Engineering Department through a separate plan
check process The completed application form and the requirements on the
H \DevBlopment Se s\MASTERS\CHECKLISTS\Bui(ding Plancheck Cklst Form do
BUILDING PLANCHECK CHECKLIST
1ST 2r >RD
n
checklist must be submitted in person Applications by mail or fax are not
accepted Improvement plans must be approved, appropriate securities posted
and fees paid prior to issuance of building permit
Improvement Plans signed by Date
6b Construction of the public improvements may be deferred pursuant to Carlsbad
Municipal Code Section 1840 Please submit a recent property title report or
current grant deed on the property and processing fee of $310 so we may
prepare the necessary Future Improvement Agreement This agreement must be
signed, notarized and approved by the City prior to issuance of a Building permit
n n
n
Future public improvements required as follows
6c Enclosed please find your Future Improvement Agreement
agreement signed and notarized to the Engineering Department
Please return
Future Improvement Agreement completed by
Date
6d No Public Improvements required SPECIAL NOTE Damaged or defective
improvements found adjacent to building site must be repaired to the satisfaction
of the City Inspector prior to occupancy
GRADING PERMIT REQUIREMENTS
The conditions that invoke the need for a grading permit are found in Section
11 06 030 of the Municipal Code
7a Inadequate information available on Site Plan to make a determination on grading
requirements Include accurate grading quantities (cut, fill import, export) -
7b Grading Permit required A separate grading plan prepared by a registered Civtl
nrr? Engineer must be submitted together with the completed application form
T^f attached NOTE The Grading Permit must be issued and rough grading
approval obtained prior to issuance of a Budding Permit
n n
Grading Inspector sign off by Date
7c Graded Pad Certification required (Note Pad certification may be required even
if a grading permit is not required )
i3\MASTERS\CHeCKLlSTS\Buildma Plancheck Cklsl Foim doc
D D
BUILDING PLANCHECK CHECKLIST
7d No Grading Permit required
7e If grading is not required, write "No Grading" on plot plan
MISCELLANEOUS PERMITS
8 A RIGHT-OF-WAY PERMIT is required to do work in City Right-of-Way and/or
private work adjacent to the public Right-of-Way Types of work include, but are
not limited to street improvements, tree trimming, driveway construction, tying
into public storm dram, sewer and water utilities
Right-of-Way permit required for
INDUSTRIAL WASTE PERMIT If your facility ts located in the City of Carlsbad
sewer service area, you need to contact the Carlsbad Municipal Water District,
located at 5950 El Cammo Real, Carlsbad, CA 92008 District personnel can
provide forms and assistance, and will check to see if your business enterprise is
on the EWA Exempt List You may telephone (760) 438-2722, extension 7153,
for assistance
Industrial Waste permit accepted by
Date
10 NPDES PERMIT
Complies with the City's requirements
L Elimination System (NPDES) permit.
of the National Pollutant Discharge
The applicant shall provide best
management practices to reduce surface pollutants to an acceptable level prior to
discharge to sensitive areas Plans for such improvements shall be approved by
the City Engineer prior to issuance of grading or building permit, whichever
occurs tltst
Required fees are attached
Q No fees required
WATER METER REVIEW
12a Domestic (potable) Use
Ensure that the meter proposed by the owner/developer is not oversized
Oversized meters are inaccurate during tow-flow conditions If it is oversized, for
the life of the meter, the City will not accurately bill the owner for the water used
• All single family dwelling units received "standard" 1" service with 5/8" service
H \Davelop RS\CHECKL I STSVB milling P^ck Cklsl Form doc
iRD
D 12b
BUILDING PLANCHECK CHECKLIST
• If owner/developer proposes a size other than the "standard", then
owner/developer must provide potable water demand calculations,
which include total fixture counts and maximum water demand in gallons
per minute (gpm) A typical fixture count and water demand worksheet is
attached Once the gpm is provided, check against the "meter sizing
schedule" to verify the anticipated meter size for the unit
• Maximum service and meter size is a 2" service with a 2" meter
• If a developer is proposing a meter greater than 2", suggest the
installation of multiple 2" services as needed to provide the anticipated
demand (manifolds are considered on case by case basis to limit
multiple trenching into the street)
Irrigation Use (where recycled water is not available)
All irrigation meters must be sized via irrigation calculations (in gpm) prior
to approval The developer must provide these calculations Please follow
these guidelines
1 If the project is a newer development (newer than 1998), check the recent
improvement plans and observe if the new irrigation service is reflected on
the improvement sheets If so, at the water meter station, the demand in
gpm may be listed there Irrigation services are listed with a circled "I",
and potable water is typically a circled "W" The irrigation service should
look like
STA 1 +00 Install 2" service and
1 5 meter (estimated 100 gpm)
If the improvement plans do not list the irrigation meter and the
service/meter will be installed via another instrument such as the building
plans or grading plans (w/ a right of way permit of course), then the
applicant must provide irrigation calculations for estimated worst-case
irrigation demand (largest zone with the farthest reach) Typically, Larry
Black has already reviewed this if landscape plans have been prepared,
but the applicant must provide the calculations to you for your use Once
you have received a good example of irrigation calculations, keep a set for
your reference In general the calculations will include
• Hydraulic grade line
• Elevation at point of connection (POC)
• Pressure at POC in pounds per square inch (PSI)
• Worse case zone (largest, farthest away from valve
• Total Sprinkler heads listed (with gpm use per head)
• Include a 10% residual pressure at point of connection
In general, all major sloped areas of a subdivision/project are to be
irrigated via separate irrigation meters (unless the project is only SFD with
no HOA) As long as the project is located within the City recycled water
H \Developmenl Se 8\MASTEBS\CHECKLIST5\Buildmg Planchsck Cklut Form doc
1ST 2f ,RD
D
BUILDING PLANCHECK CHECKLIST
service boundary, the City intends on switching
services/meters to a new recycled water line in the future
12c Irrigation Use (where recycled water is available)
these irrigation
1 Recycled water meters are sized the same as the irrigation meter above
2 If a project fronts a street with recycled water, then they should be
connecting to this line to irrigate slopes within the development For
subdivisions, this should have been identified, and implemented on the
improvement plans Installing recycled water meters is a benefit for the
applicant since they are exempt from paying the San Diego County Water
Capacity fees However, if they front a street which the recycled water is
there, but is not live (sometimes they are charged with potable water until
recycled water is available), then the applicant must pay the San Diego
Water Capacity Charge If within three years, the recycled water line is
charged with recycled water by CMWD, then the applicant can apply for a
refund to the San Diego County Water Authority (SDCWA) for a refund
However, let the applicant know that we cannot guarantee the refund, and
they must deal with the SDCWA for this
Additional Comments:
H \Development SB s\MASTERS\CHECKLISTS\Buildmg Plarcheek Cklsl Form do
D
ENGINEERING DEPARTMENT
FEE CALCULATION WORKSHEET
Estimate based on unconfirmed information from applicant
Calculation based on building plancheck plan submittal
Address Bldg Permit No
Prepared by f Date Oy W"2tg> f Checked by Date
EDU CALCULATIONS List types and square footages for all uses
Types of Use A]\^ Scl Ft /Units
Types of Use Sq Ft /Units
APT CALCULATIONS List types and square footages for all uses
Types of Use "V^OiP-K Sq Ft /Units
Types of Use Sq Ft /Units
EDU's
EDU's
ADT's
ADT's
FEES REQUIRED
WITHIN CFD D YES (no bridge & thoroughfare fee in District #1, reduced Traffic Impact Fee)
1 PARK-1N-LIEU FEE
FEE/UNIT
PARK AREA & #
X NO UNITS = $
C3
TRAFFIC IMPACT F££
ADT's/ONITS / , v.<7^-L_— -"
BRIDGE AND THOROUGHFARE FEE
/^~^\ " OADT'sitfNITS ) "lot./ > ^ — J^ —
FACILITIES MANAGEMENT FEE ;si
/JNlTi/SQ FT (^
X /E^/ADT "7%D ^$ f IIIc^ , - ... , (-r
(DIST #1 X DlST #2 DIST #3 )
X ^EE>ADT UM =S ^f
!ONE (£/
X FEE/SO FT /pNTM ^ I C? - $ C^2-O
5 SEWER FEE
EDU's
BENEFIT AREA
EDU's
6 SEWER LATERAL ($2,500)
D 7 DRAINAGE FEES PLDA T>
ACRES e 3>4
8 POTABLE WATER FEES
UNITS CODE CONNECTION FEE
X FEE/EDU
X FEE/EDU
HIGH /LOW
= $
X FEE/AC = t 12.
METER FEE SDCWA FEE IRRIGATION
1 of 2
Word\Docs\Misforms\Fee Calculation Worksheet Rev 7/1^/00
Parcel 12153204500 Location |2817 CAZADERQ DR CBAD
Status |"CTr!li
Date [r[InPaiceL/Geo Data
Parcel Number 1215 320 45 00
ii lAr-i iiiji-iTn I i\ ;mr- Tni rync -I •"!
Up'^ il"hi EKIt Back
Parcel Address J2817 CAZADERO DR CBAD
Map Book No )
Zip Code |92003
Quadrant
RedevArea|Y/N}
LFMZ
Coastal 2onelY/NJ JFT
Census Tret 20011
Zoning |R-2
Gen Plan RM
Date Acquired 108/30/199lL
ParkDist |~4~
FireDist |T"
Water Dist fT™*
SewerDist |LC
School Disl |CT"
Drainage Disl |D
Beach QverlayZonelY/N] [FT
Bridge/Thrfare f?
.IIUj •Swr BenArea j
Fire SupressionZone(Y/N) [
ComMsSvOLZone|Y/N) f"
CFDNo F~0
Improvement Area j 0
CFD Annex Date I /
Slail fifeSnagll/32 'PERMITS'Plus iPlanTrack/LandUseEn 303PM
PLANNING DEPARTMENT
BUILDING PLAN CHECK REVIEW CHECKLIST
Plan CheckfllNfo
Planner
APN
Address
Phone (760) 602-.
Type ol
Zoning
CFD fi
Circl
Droject & Use _
L- General Plan:
One
.Date of participation-
Net Project Density
Facilities Management Zone
DU/AC
Remaining net dev acres
(For non-residential development' Type of land used created by
this permit }
Legend: X Item Complete Item Incomplete - Needs your action
Environmental Review Required: YES NO X TYPE
DATE OF COMPLETION:
Compliance with conditions of approval7 If not, state conditions which require action
Conditions of Approval1 '_ _ I _
Discretionary Action'Required:
APPROVAL/RESO NO/
PROJECT NO.
YES
DATE
TYPE
OTHER RELATED CASES
Compliance with conditions or approval7 If not, state conditions which require action
Conditions of Approval
Coastal Zone Assessment/Compliance
Project site located in Coastal Zone7 YES
CA Coastal Commission Authority7 YES
If California Coastal Commission Authority Contact them at - 7575 Metropolitan Drive, Suite 103,
San Diego CA 92108-4402, (619) 767-2370
Determine status (Coastal Permit Required or Exempt):
Coastal Permit Determination Form already completed7 YES NO
If NO, complete Coastal Permit Determination Form now
Coastal Permit Determination Log #
Follow-Up Actions
1) Stamp Building Plans as "Exempt" or "Coastal Permit Required" (at minimum
Floor Plans) ' '•'" ' J v " ' ••''.. ' ' ?
2) Complete Coastal Permit Determination Log as neededt
H \ADMIN\COUNTER\BldgPlnchkRevChklst
Inclusionary Housing Fee required: YES >^ NO
(Effective date of Inclusionary Housing Ordinance - May 21, 1993")
Data Entry Completed? YES -s/ NO -^_ " -
(A/P/Ds, Activity Maintenance, enter CBff, toplbar, Screens, Housing Fees, Construct Housing Y/N, Enter Fee, UPDATE')
Site Plan: — ',
1. Provide a fully dimensional site plan drawn to scale Show North arrow,
V, property lines, easements, existing and proposed structures, streets, existj
\ i /<Sp topographical lines {including all side an
•y ' _
\ 2. Provide legal description of property ancA , — ,
i / ry_
Zoning:
1 . Setbacks rv
Fronf Required ^
Interior Side1 Required *-7
Street Side. Required
Rear: Required j&
Top of slope: Required r~) I
Nr/r-, r-i\i 2. Accessory structure setbacks:
(^ Front Required (M
v Interior Side: Required
Street Side: Required
Rear Required
Structure separation: Required
-
\f\ ' £~ **\\ 3. Lot Coverage: Required -^— '
d rear yard slopes)A ^
assessors parcel number.
^ fy\wJ
~) ^} 1 1 ^
Shown 2x jf
*' Shown ^f
Shown
Shown ^fc?'
f_ Shown
& €P*^
^ Shown
Shown
Shown
Shown
Shown
/
7w / "C&vt(-y6 Shown ^° /&
4 Heiqhf Required ^30 Shown
5. Parking:Spaces Required Shown
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required 'J.— Shown
'-X /-v f\
Comments/ /
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER
H \ADMIN\COUNTER\BldgPlnchkRevChklst