HomeMy WebLinkAbout2830 AVENIDA VALERA; ; CB920864; Permit5 BUILDING PERMIT Permit No: CB920864
O$/L-/9& 10: 45 Project No: A9201924
Pag4 1 of 1 Development No:
Job Address: 2830 AVENIDA VALERA Suite :
Permit Type: SINGLE FAMILY DWLNG - DETACHED Parcel No: 216-460-25-00 Lot#: 17
I Valuation: 212,693
Construction Type: VN 9010 08/3/92 0001 01 02 Occupancy Group: R3/M1 Reference#: 92-636 stmr IS%#?&7.00 Description: 2365 SF + 661 SF GARAGE PLAN 4 Applied: 08/24/92
: PHASE 1 Apr/Issue: 08/25/92.
Validated Ry: MDP
Appl/Ownr : FLELDSTONE/LA COSTA ASSOC. 619 546-8226
5465 MOREHOUSE DRIVE #250
SAN DIEGO, CA 92121
*** Fees Required *k* *** Fees Collected & Credits *** - ____________________--------
Fees :
Adjustments :
Total Fees:
Fee description ___________--------_
Building Permit
Plan Check
Strong Motion Fee
or manually enter
Enter F.M.F./G.M.F
Enter "Y" to Autoc
Enter "Y" to Autoc
Enter "Y" to Autaca * BUILDING TOTAL
Enter "Y" for Plumbi
Each Plumbing Fixtur
Each Building Sewer Each Water Heater and/or
Gas Piping System
Each Vacuum Breaker
.oo
350.00
12,787.00
Ext fee Data ___________-----
1035.00
673.00
21.00
2200.00
3871.00 Y
3573.00
362.00 Y
530.00 Y
12983.00
7.50 Y
40.00
6.50
2.50
2.50
5.00
310.00 06
408. oa
PLUMBING TOTAL
Enter "Y" for Electric Issue Fee >
* ELECTRICAL TOTAL
Enter 'Y' for Mechanical Issue Fee>
Each Install/Reloc Appliance Vent >
x MECHANICAL TOTAL
Single Phase Per AMP >
Install Furn/Ducts >
Each Hood/Fireplace >
0
0
125
0
0
1
4
1
0
64.00
10.00 Y
.25 31.25
41.00
15.00 Y
9.00 9.00
4.50 18.00
6.50 6.51)
49.00
ClTY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
1
FINAL BUILDING INSPECTION I
DEPT: BUILDING ENGINEERING FIRE PUNNING U/M
PLAN CHECK#: CB920864
PERMIT#: CB920864
PROJECT NAME: 2638 SF + 661 SF GARAGE PLAN
PHASE 1
4
WATER
DATE :
PERMIT 04/23/93 TYPE: SFD
ADDRESS: 2830 AVENIDA VALERA
CONTACT PERSON/PHONE#: ALLISON/438-0468
SEWER DIST: LC WATER DIST: CA
INSPECTED DATE
BY: INSPECTED: 7/23,/q&APPROVED 2 DISAPPROVED - -
INSPECTED DATE
BY: INSPECTED : APPROVED - DISAPPROVED -
INSPECTED DATE
BY: INSPECTED : APPROVED - DISAPPROVED -
FINAL BUILDING INSPECTION
DEPT: BUILDING ENGINEERING FIRE PLANNING U/M WATER
+,A 8 !93 APPROVED BY: INSPECTED:
INSPECTED DATE
INSPECTED DATE
BY: INSPECTED: APPROVED
INSPECTED DATE
BY: INSPECTED : APPROVED
)o DISAPPROVED -
- DISAPPROVED -
- DISAPPROVED -
r
FINAL BUILDING INSPECTION .\
DEPT: BUILDING ENGINEERING FIRE U/M
N CHECK#: CB920864 p" .WIT#: CB920864
PROJECT NAME: 2638 SF + 661 SF GARAGE PLAN
PHASE 1
ADDRESS: 2830 AVENIDA VALERA
CONTACT PERSON/PHONE#: ALLISON/438-0468
SEWER DIST: LC WATER DIST: CA
4
WATER
DATE: 04/23/93
PERMIT TYPE: SFD
DATE
INSPECTED: s/z/lr! APPROVED - / DISAPPROVED __ INSPECTED
BY:
INSPECTED DATE
BY: INSPECTED: APPROVED - DISAPPROVED -
INSPECTED DATE
BY: INSPECTED : APPROVED - DISAPPROVED __
FINAL BUILDING INSPECTION *
DEPT: BUILDIHG ENGINEERING FIRE PLANNING U/M
PLAN CHECK#: CB920864
PERMIT#: CB920864
PROJECT NAME: 2638 SF + 661 SF GARAGE PLAN 4
PHASE 1
WATER
DATE :
PERMIT
04/2 3/93
TYPE: SFD
ADDRESS: 2830 AVENIDA VALERA
CONTACT PERSON/PHONE#: ALLISON/438-0468 SEWER DIST: LC WATER DIST: CA
BY: INSPECTED: +m APPROVED - / DISAPPROVED - DATE
INSPECTED DATE
BY: INSPECTED: APPROVED - DISAPPROVED -
INSPECTED DATE
BY: INSPECTED: APPROVED - DISAPPROVED -
4
4 e-4
CITY OF CARLSBAD
INSPECTION REQUEST
f
PERMIT# CB920864 FOR 05/06/93 INSPECTOR AREA PY
DESCRIPTION: 2638 SF + 661 SF GARAGE PLAN 4 PLANCK# CB920864
TYPE: SFD CONSTR. TYPE VN JOB ADDRESS: 2830 AVENIDA VALERA STE : m: 17 APPLICANT: FIELDSTONE/LA COSTA ASSOC. PHONE: 619 CONTRACTOR: PHONE :
OWNER: PHONE:
PHASE 1 OCC GRP R3/Ml
REMARKS: XH/ALLISON/438-0468 SPECIAL INSTRUCT:
TOTAL TIME:
CD
19 29 39
49
LVL DESCRIPTION
ST Final Structural PL Final Plumbing EL Final Electrical ME Final Mechanical
/
CT COMMENTS
'\ **+** INSPECTION HISTORY *****
DATE 030893
030493 030493 030393 030193
030193
022493
022293
021893
021793
021193
020393
020293
020193
012993
012993
123192
101492
100292
DESCRIPTION Gas/Test/Repairs
Exterior Lath/Drywall
Gas/Test/Repairs Gas/Test/Repairs
Exterior Lath/Drywall
Interior Lath/Drywall
Interior Lath/Drywall
Insulation Frame/Steel/Bolting/Welding Rough Combo
Rough Combo Rough/Topout Rough/Topout Rough/Topout
Shear Panels/HD's
Rough/Topout
Roof/Reroof
Ftg/Foundation/Piers
Underground/Under Floor
ACT INSP COEnaENTS AP PY AP PY
AP PY
CA PY NR PY
AP PY
NR PY
AP PY PA PY co PY CO PY NS PY
AP PY co PY
AP PY
NR PY
AP MP
AP MP AP MP
UPSTAIRS BEDROOM (EAST) CEIL
SEE IWSP NOTES
OK To WRAP
PERMIT# CB9 DESCRIPTION :
TYPE: SFD JOB ADDRESS:
INSPECTOR AREA PY PLANCK# CB920864 OCC GRP R3/M1 CONSTR. TYPE VN Y LOT: 17 2830 AVENIDA VALERA STE :
CITY OF CARLSBAD INSPECTION REQUEST 864 FOR 02/17/93 2638 SF + 661 SF GARAGE PLAN 4
PHASE 1
APPLICANT: FIELDSTONE/- COSTA ASSOC. PHONE: 619 546-8226
CONTRACrOR: PHONE:
OWNER: PHONE :
SPECIAL INSTRUCT:
REMARKS: RS/ALLISON/438-0468 INSPECTOR
TOTAL TIME:
t --RELATED PERMITS-- PERMIT# TYPE STATUS
CB930072 ISSUED
CD LVL DESCRIPTION ACT COMMENTS
14 ST Frame/Steel/Bolting/Welding 24 PL Rough/Topout
34 EL Rough Electric
44 ME Rough/Ducts/Dampers
***** INSPECTION HISTORY *****
DATE 021193 020393 020293 020193 012993 012993
123192 101492 100292
DESCRIPTION Rough Combo Rough/Topout Rough/Topout Rough/Topout Shear Panels/HD's . Rough/Topout
Roof /Reroof
Ftg/Foundation/Piers
Underground/Under Floor
ACT co NS AP co AP NR
AP
AP
AP
INSP PY PY PY PY
PY
PY
MP
MP
MP
COMMENTS
OK TO WRAP
7895 convoy court
Sin Diego, California 92111 PROFESSIONAL REGISTERED INSPECTIONS, INC . Phone 292.066
GLUE - LAM. FABRICATION STRUCT. STEEL ASSEMBLY
wnicn REOUIREO APPROVAL BY PRE-STRESSED CONCRETE REINFORCED GYPSUM
. (UIR DCIIOM. nc4An v-
0
INSP".
DATE
LOCATIONS OF WORK INSPECTED. TEST SAMPLES TAKEN, WORK REJECTED, JOB PROBLEMS, PROGRESS: REMARKS, ITC.
INCLUDKS INFORMATION ABOUT -AMOUNTS OF MATERIAL PLACED OR WORK PERFORMIDI NUMBER. TYPE. b IDENT.NO*S.
OF TEST sAMPCLa TAKEN: STRVCT. CONNECTIONS (WIELDS MADE. n.1. BOLTS TORQUIED) CnceKcoz LTC.
I I
DATE OF REPORT REGISTER NUMBER
7895 Convoy Court San Diego, California 921 11
Phone 292-066 PROFESSIONAL REGISTERED INSPECTIONS, INC . . -- --- ---
FOR WEEK < I ENDING ON ...... dih.2 .... 6 ............, 19L. INo.p$//
COVERING WORK PERFORMED 3 REINFORCED CONCRETE 0 STR~CT. STEEL ASSEMBLY GLUE - LAM. FABRICATION
THE SPECIAL INSPECTOR OF 0 REINFORCED MASONRY 0 PILE DRIVING .................................................... WHICH REQUIRED APPROVAL BY ~PRE-STRESSED CONCRETE 0 REINFORCED GYPSUM 0 OTHER
0WN.ER OR PROJECT NAME
C0NSTR.MAT.L. (VYPE, GRAOE. CTC.) DESIGN STRENGTH -
1
LOCATIONS OF WORK INSPECTED, TEST SAMPLES TAKEN. WORK REJECTED. JOB PROBLEMS. PROGRESS; REMARKS, ETC. INSP'N.
DATE INCLUDES INFORMATION ABOUT -AMOUNTS OF MATERIAL PLACED OR WORK PERFORMED: NUMBER. TYPE. b IDENT.NO*S.
OF TEST SAMPLES TAKEN; STRUCT. CONNECTIONS IWELOS MADE. H.T. BOLTS TORQUED1 CHECKED: ETC.
Cr-
DATE OF REPORT REGISTER NUMDER
PROFESSIONAL REGISTER INSPECTIONS, INC,
7895 Convoy Court t15 Eian Diego, Cab 92111 JOB NO.: 4911
~~ JOB: FAIRWAVS
ADDRESS : 2830 AVENIDA VALERA
OWNER: FIELDSTONE COMPANY CONTRACTOR: MUELLER LEWIS CONCRETE
CLIENT: MUELLER LEWIS CONCRETE ENGINEER : JEM 111
ARCHITECT: BERKUS GRQUP BLOG AUTH: CITY OF CARLSBAC!
INSPECTOR: JEFFREY GAYLER PERMIT NO,: CB92-0864 PLAN FILE!
FIELD
SAMPLE OF: CONCRETE
LOCATION OF SPECIMEN
IN JOB OR STRUCTURE: LOT""n3
MIX NO.: 6525 MADE BY: JEFFREY GAYLER
PROPORTIONS: SLUMP: 5 "
ADMIXTURE: @ATE MADE2 10/20/92
TYPE OF CEMENT: I1 DATE RECEIVED: 10/22/92
CONC. SUPPLIER? NELSQN & SLOAN SOURCE OF ROCK:
TICKET NO,: 4 04 0 8 it INSPECTOR SIGN:
LABORATORV TEST OATA
7 DAYS 19 OAYS 28 @AVS 28 DAYS
SPECIUEN MARKINGS: 9284 1 92842 92843
DATE TESTED: 10/30 11/17 11/17
AREA-SQa IN 28 + 28 28.28 28.28
ULTIMATE LOAD-LBS: 54500 . . e UNIT STRESS-LBS: . : 1930 .
SPECIFIED STRENGTH
AT 28 DAVS-PSI:
DISTRIBUTION: 'MVELLER LEWIS CONCRETE
FIELOSTONE COMPANY
JEM I11
CITY OF CARLSBAD
2500
1 ENGINEER
n n -. _.._
...
FOUNDATION OBSERVATION REPORT
0 ADDlTIONAL OBSERVATION REQUIRED PERMIT NO.: PIAN FILE NO.: I I ]A SUBSTANTIAL CONFORMANCE
~
0 PURPOSE OF OBSERVATION 0 7 0
0
(r- 0 Other: 'j. ,: f i , -- ,.* 12
Verify soil conditions exposed are similar to those anticipated. Verify footing excavations extend to minimum depth recommended in soil report. Verify foundation reinforcement complies with minimum recommended in soil report.
Verify slab reinforcement, sand bedding and moisture barrier comply with minimum
recommended in soil report. -
f', ' - ,-
," 0 APPLICABLE SOIL REPORT ITIZE: FLk,,$, 1 hd.,... i ,,, 7-2 3 *?-- R/,rr/loy, 1
d/ (2 / DA~: 7-d- 24,ot
0 SOIL REPORT RECOMMENDATIONS BASED ON SS ExpansionCondition; OVERYLOW OLOW . KMEDIUM HIGH 0 VERY HIGH
E9 FillGeometry
0 Other:
FootingDepth: Eli2I"Es jX181"~s OUINCHES
Interior Slab Reinforcement: 0 &10/10 0 6~&6/6 13 NO. 3 Q 24 INCHES ' 0 NO. 3 @ 18 INCHES
Slab Bedding Material and Thickness: Foundation Width:
If yes, identify and dmi
dsubtantial co~mmce with soil Report (see "Purpose of mation.).
0 Substantial con&mnmce with Foundation plans.
0 MINIMUM FOUNDATION RECOMMENDATION
Footing Reinforcement: 0 NO. 4 T&B 0 ZN0.4 T&B 0 NO5 T&B OTHER: /.JT
Vapor Barrier:
FOUNDATION PLAN REVIEWED: YES0 NO v
0 OB ERVATIONS:
0 Other:
0 COMMENTS:
NUIE IT IS ASSUMED THAT ALL FOOTING EXCAVATIONS WILL BE CLEANED OF LOOSE MATERIAL PRIOR TO
PLACING CONCRETE AND THAT THE SOIL MOIW CONTENT WIU BE MAINTAINED.
PROFESSIONAL REGISTER INSPECTIONS, INC,
7895 Convoy Court IC15
San Diego, Ca. 92111 JOB NO.: 491 1
JOB: FAIRWAYS
ADD R E S S : 2830 AVENIDA VALERA
QWNER: FIELDSTQNE CQMPANY CONTRACTOR : MUE L L E R LEWIS CONCRETE
CLIENT : MUELLER LEWIS CONCRETE ENGINEER : JEM I11
ARCHITECT: BERKUS GROUP * BLDG AVTH: CITY QF CARLSBAD
INSPECTOR: JEFFREY GAYLER PERMIT NO. : c~92-oa61.t PLAN FILE:
FIELD
SAMPLE OF: CONCRETE
MIX NO.: 6525
PROPORTIONS:
ADMIXTURE:
LOCATION OF SPECIMEN
IN JOB QR STRUCTURE: LOT #17
MADE BY:
SLUMP:
*JEFFREY GAYLER
5 "
DATE MADE: 10/20/92
TYPE OF CEMENT: 11 DATE RECEIVED: 10/22/92
CONC, SUPP.LIER: NELSQN & SLQAN SOURCE OF ROCK:
TICKET NO.: 4 0 4 0 8 1.r INSPECTOR SIGN:
LABORATCRY TEST @ATA
7 DAYS 19 RAYS 28 DAYS 28 DAYS
SPECIMEN MARKINGS: 92a~+ I 92842 92843
DATE TESTED: 10/30 11/17 11/17
AREA-SQ.1N.t
ULTIMATE LOAD-LBS: 54500 72500 72000
UNIT STRESS-LBS: : 1930 : 2560 : 2550
SPECIFIED STRENGTH
AT 28 DAYS-PSI:
DISTRIBUTION: MUELLER LEWIS CONCRETE
F IELESTONE COMPANY
CITY QF CARLSBAO
JEM I11
2500
ENGINEER '
7895 Convoy Court PROFESSIONAL REGISTERED INSPECTIONS, INC San Diego, California 921 11
FIELDSTONE COMPANY
cot4 TP. DOING REPOR rEo WOPK 1/2" 8, 7 STRAND, 270 KSI CABLE, MIX #6525,
MUELLER LEWIS CONCRETE
LAB. RECEIVING L TESTING CONSTR. IAA1.L. SA\*OL.E~
GAUGE 8C826, GAUGE #C8105
INSP'N.
DATE -
-.
I P.R.,I., INC. ----__ -
L3ChTIONS OF WORK INSP€CTED, TEST SAMPLES TAKEN, WORK REJECTED, JOB PROBLEMS, PROGRESS, REMARKS, ETC.
1,ICL';DES IHF04LTA TION 4EIOIJ r - ALAOIJNTS OF MATERIAL FLACED OR WOAV PERFOAhIED: tJU*IBER. TYPE. & 13E'I ?.*l'O'S.
-)r .E57 9nrAr'.cs YhYFrl. 51nlJrT. C@*l*IECTlONS 174FI CS'.rArF, 1i.T. BOLTS TOROUEDI CUECYCD: ETC.
Lot #2
0 3
i1 4
# 5
d 6
#7 f 8
#9
# 10
bll
#12
#13
814
#15
#16
4T17
The post tension concrete work requiring special inspection was,
to the best of my knowledge, in conformance with the approved
plans and specifications and the applicable workmanship provisions
of the Uniform Building Code,
83 thru 11.
3203 Sitio Rosalia
3207 Sitio Rosalia
3212 Sitio Rosalia
3208 Sitio Rosalia
3204 Sitio Rosalia
2808 Avenida Valera
2810 Avenida Valera
2812 Avenida Valera
2814 Avenida Valera
2816 Avenida Valera
2818 Avenida Valera
2820 Avenida Valera
2822 Avenida Valera
2826 Avenida Valera
2828 Avenida Valera
2830 Avenida Valera
CB920-840
CB920-848
CB920-855
CB9 20-859
CB920-849
CB920-84 1
CB9 20-83 6
CB920-860
CB920-850
CB920-861
CB920-843
CB920-837
CB920-862
CB920-851
CB920-863
CB 9 2 0-8 64
1988 Edition. Inspection reports
Lot 1109
lll0
11111
8112
#113
1114
#115
#ll6
#117
ill18
#126
#127
#128
. 8129
#130
2825 Vista Mariana CB920-839
2823 Vista Mariana CB920-866
2821 Vista Mariana CB920-844
2817 Vista Mariana CB920-854
2815 Vista Mariana CB920-834
2811 Vista Mariana CB920-857
2809 Vista Mariana CB920-846
2807 Vista Mariana CB920-858
2805 Vista Mariana CB920-835
2803 Vista Mariana CB920-847
2811 Avenida Valera CB920-845
2813 Avenida Valera CB920-853
2815 Avenida Valera CB920-838
2817 Avenida Valera CB920-865
2819 Avenida Valera CB920-852
28 Day Compression test that did not reach the required PSI
Lot #3 - 2940 - 45 Days
#6 - 2970 - 60 Days
Remaining lots did meet required PSI. /d 384s.
DALE REGLI
SIGNAC~RE OF REGISTERED INSSF- -2~ r
4/12/93 280
-cj <'E.'.. ,,**: DATE OF REPORT