HomeMy WebLinkAbout2855 CARLSBAD BLVD; ; CBC2018-0125; PermitPrint Date: 08/22/2019
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
2855 Carlsbad Blvd
BLDG-Commercial
2032310100
$90,000.00
Commercial Permit
Work Class: Cogen
Lot#:
Reference #:
Construction Type
Bathrooms:
Orig. Plan Check#:
Plan Check#:
{'city of
Carlsbad
Permit No: CBC2018-0125
Status:
Applied:
Issued:
Permit
Fina led:
Inspector:
Final
Inspection:
Closed -Expired
03/05/2018
09/14/2018
Description: FRONT PORCH COMMUNITIES: INSTALL 4 EV CHARGING STATIONS IN PARKING GARAGE -FIRST FLOOR
Applicant:
PAMELA SMITH
8330 Century Park Ct
San Diego, CA 92123-1530
760-298-9023
FEE
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
FIRE Special Equipment (Ovens, Dust, Battery)
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-COMMERCIAL
Owner: Contractor:
FRONT PORCH COMMUNITIES AND SERVICES NB BAKER ELECTRIC INC
800 N Brand Blvd
GLENDALE, CA 91203
818-254-4100
2120 Harmony Grove
ESCONDIDO, CA 92029
442-257-0877
Total Fees: $ 1,424.64 Tota I Payments To Date : $ 1,424.64 Balance Due:
AMOUNT
$583.20
$408.24
$404.00
$4.00
$25.20
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees /exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees /exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: □PLANNING □ENGINEERING □BUILDING □FIRE OHEALTtt OHAZMATIAPCD
{ City of Building Permit Application Plan Check No.~2.01 ~ -f)\? r~
1635 Faraday Ave., Carlsbad, CA 92008 Est. Value /Jq O, ()vi)
Carlsbad Ph: 760-602-2719 Fax: 760-602-8558 Plan Ck. Deposit email: building@carlsbadca.gov
www.carlsb1dca.gov Date '.2...--':\-\"t\ ISWPPP
JOB ADDRESS IUITEf/SPACit/UNITf
I"'" 203 2855 CARLSBAD BLVD., CARLSBAD, CA 92008 -231 -01 -00
CT/PROJECT# ILOT# I PHASE# I # Of UNITS I # IEDftOOMS # M.THROOMS
I~;;~B";~ BY THE SEA
I CONSTR. TYPE I occ. GROUP
DESCRIPTION OF WORK: Include Squa,e Feet of Alfedff Aru(s)
INSTALLATION OF 4 ELECTRIC CHARGING STATIONS
\ ~+ +b)( t)t R.-u ~cj Guxo..c~
EXISTING USE I PROPOSED USE IGARAGE (SF) PATIOS (SF) I DECKS (SF) FIREPLACE I AIR CONDITIONING I ARE SPRINKLERS
COM MERICAL COMMERCIAL YES[}, No(] YES □No □ YES□ND□
APPLICANT NAME PAMELA SMITH FOR SDG&E PROPERlYOWNERNAME FRONT PORCH COMMUNITIES & SERVIC Prlm•rv Contact
ADDRESS ADDRESS
8326 CENTURY PARK COURT 800 N. BRAND BLVD.
CITY STATE ZIP CITY STATE ZIP
SAN DIEGO CA 92123 GLENDALE CA 91203
PHONE IFAX PHONE FAX
760-298-9023
EMAIL EMAIL
PAMELAS@C2GROUP.US, PYDDOCS@C2GROUP.US
DESIGN PROFESSIONAL MICHAEL BAKER INTERNATIONAL CONTRACTOR BUS, NAME 'i>..,\c...,, l. I.e. ~+r.,-c. r.,. c.
ADDRESS ADDRESS fl 9755 CLAIREMONT MESA BLVD lct-"<8 f c...c.d-.... Oc..lc:...s
CITY STATE ZIP CITY STATE
{ C,
ZIP 't 2.oJ-.~ SAN DIEGO CA 92124 l~c.o~\, ~o
PHONE IFAX PHONE . .,_ '-f :r _ FAX
858-810-157 858-614-5001 7bo-~ ;;i.oo r
EMAIL EMAIL
BRIAN.EREMITA@MBAKERINTL.COM llc..-t~d .() h• I,. --d ~J-.,.., '~ . (.o-
TSTATE LIC. '75339 STATE LIC,#
~: .I-C '{' I t\L;{'~-~ I ( .!' s f w-u.,~~"
{Sec. 7031.5 Business and Professions Code: Arry C~ or County which requires a permit to constn,~l ~lter, improve, demolish or repair any structure, prior to Its issuance, alao "-"'uires the applicant for such permit to file a •~ statement that he is licensed pursuant to the i:wovlsions of me Contractor's Ucensa Law {Chapter i, commendlnl with Section 7000 of Division 3 of the
&la.inns and Professions Code} or that he• exempt therefrom, and the basis for the allet:ed exemption. Any vlotatlon of Section 7031.5 by any appllcantfor a permit subjects the apptieant to a
clvll penalty of not more than five hundred dollars ($500}).
WORKERS' COMPENSATION
Womrs'Compenutlonlltcllrotion:1-ytllfml-,,.,,.i,rofporju,y""of""folowi>g-
□ I h!vt and will maintain a certfflcate of consent to self-Insure for worker&' compeftlltion • pRNicllcl by Section 3700 of thl Labor Code, for thl performancl of tha work for which lhil permit is issued.
~ and wtn molntol•-• -• u roqulred by Section 3700 of \he i...Cade. lollhl porto,,,,.., oflhl-lolwh<h tlil pomit II iuuod. My"°"""' corrfll'lllion--and policy
...,,.., .. ,......,..eo. ol~ llar'_,L,\. ~ 1..,., C, PolcyNo. fti..,,'-~P--~-y.,oo Exp;ralionD11t_3.,_-~/_· ~lt~---
lbl. section need not be competed I !ht permit ii for ont hundrtd dollars ($1CIO) or leu. LJ Centflcala of Exemption: I ~ that In lht performance of 1ht work for whlctl this pemit la luued, I shall not employ any person In any manner so as to btcome subject lo 1ht Workers' Compensation Laws ol
Calfomla. WARNING: Fallurt to MC&n workln:' compensation CO'ffla89 ii unlawful, and shall subject., employer to crlmlnal penattles and cMI ftnu up to one hundNd thousand doftart (&100,000~ In
addition to the coat of compenutlon, ~ for in Section 3708 of the Labor codt, lnllrtlt and attomtf• fHs.
AS COHTRACT0R SIGNATURE cc-~
I hetuy lfflnn t1llt I am exempt from Conttlclor'a l..Jcenlt UW for the folowrig ru,on; D I, as owner of the property or my employHI with~ 11 lhlir lOII c:ompenutlon, v.ill do the work and the structure ii not Intended or oflnd for salt (Sec. 7044, Buslntss and Proltalons Code: Tht Contrlclor'a
Licenu Law don not apply to., owner of pRJptrty who builds or impro\lel therton, and who does 1uch work himHlf or through his own employtea, proYidld 1h11 IUCh i1iprow1m1nts 111 not lnltndtd or offnd for
salo. ff, llowewr, lhl blilding or i~ II IOld wilNn one yur of c:omplllion. lht ownor-buildorwill havo lhl burden of plOYing 1h11 ht did nol blild or implo,o lol lhl purpooe of salo). D I, u owner of lhl proptrty, am txc:IUlivtly oonlracling wlh lc:tnsed c:onlrlclors lo COl\ltruc:t h project (Sec. 7044, Buslnea and Proffflions Code: The Contractor's Licenle Law does not apply to an owner of
property who buldl or~ lhfflon, Ind Ollllrldl fol such projocll wilh -<1) -pu11U1111 to lhl Conllldol'I ~ I.aw). D I am exempt undar Section ___ ,Business and ProtHlionl Code for 1h11 renon:
1. I ,,.,....1y plan to plovide lhl major llbar ond rnolorioll fol-of lhl p,_,cl pioptrty -mont. OY11 O,
2. I (hovo I havo not) lignod on IP!'lk:llion fol I building pomit for lhl p,_,cl -·
3. 1 hovl controclld wi1h lhl -ng -(firm) lo plovide lhl p,_,cl cons1rudion (includt nomo odd,_ I phone I-.-• 1icente number):
4. I pion to plovide po,1iont of lht-1<. bu1 I hovl hiod lht 1-.ig por,on to COOldinoto, _,.... and plovide \he mojar-(includ< nomo I oddlffl I pllone I controdarl' liconlo runbtr):
5. I wil p!OYi<lt 10111e of lhl -• bu1 I hovl controclld (hl!od} lhl following pe!SOOI lo provide lhl -lndk:lltd (includo nomo I -I phono I typo of-):
,IS PROPERTY OWNER SIGNATURE DATE
COMPLETE THIS SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Yes No
Is the applicant or Mure building occupant required to obtain a permit from the air pollution control district or air Quality management district? Yes No
Is lhe facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLIITION CONTROi. DISTRICT.
CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance of the work this permit 1s issued (Sec 3097 (1) C1V1I Code).
Lender's Name Lender's Address
APPLICANT CERTIFICATION
I COltit,ttlatl have n,ad the IIPl>Hcatlon and -ttlatthe aba,<e lnfonnation ls C0119Ct and 1llat the lntonnation on the plans Is aca,rate.1-to complywlth all City_ and Stale laws 191atingto bulldlrC COl1SlnJction.
I heleby aulhorize 18p18SE1111alive cj the City cj Carlsbad ti enler upon lhe at,o,e ....-property for nspection purposes. I ALSO AGREE TO SAVE, -IFY AND KEEP HARMLESS 11-IE CITY OF CARLSBAD
AGAINST ALL LIABILmEs. JUDGMENTS. COSTS AND EXPENSES WHICH MAY IN ANYWAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTNG OF THIS PERMIT.
OSHA: />n OSHA penntt is l8quied for excavalior$ r,,er 5U" deep and demolhion or construction of siuclJ"5 °"" 3 stooes n height.
EXPIRATION: Every permit -by the ~ ()Ilic;; the pro,isions of lhis Code shall expie by nilation and -nui and void ff the buidi"g or-au1horized by such penntt is not -wilhil
180 days from the dale of such penntt or ff lhe buidi"g or Pf!, "'!1-,qby such perml is susper<led or abandoned at any lire after lhe -is coom., ICOd for a period of 180 days (Sedion 1116.4.4 U!iform Buiklilg Code).
,I!$ APPLICANT'S SIGNATURE DATE
• STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602-8560, Email building@cadsbadca.gov or Mall the completed form to City of Cansbad, Building OM~on 1635 Faraday Avenue, cansbad, C.lifomia 92008.
CONTACT NAME
ADDRESS
CITY STATE
PHONE
EMAIL
DELIVERY OPTIONS
PICKUP:
MAIL TO:
CONTACT (Listed above)
CONTRACTOR (On Pg. 1)
CONTACT (Listed above)
CONTRACTOR (On P~ 1)
MAIL/ FAX TO OTHER: ___ _
A, APPLICANTS SIGNATURE
FAX
OCCUPANT (Listed above)
OCCUPANT (Listed above)
ZIP
CO#: (Olflce Uoe Only)
OCCUPANT NAME
BUILDING ADDRESS
CITY STATE
Csrlsbad CA
OCCUPANTS BUS. UC. No.
ASSOCIATEDCBf-----------
NO CHANGE IN USE/ NO CONSTRUCTION
CHANGE OF USE/ NO CONSTRUCTION
DATE
ZIP
PERMIT INSPECTION HISTORY REPORT (CBC2018-0125)
Permit Type: BLDG-Commercial Application Date: 03/05/2018 Owner:
Work Class: Cogen Issue Date: 09/14/2018 Subdivision:
Status: Closed -Expired Expiration Date: 07/30/2019 Address:
IVR Number: 9886
Scheduled Actual Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector
01/31/2019 01/31/2019 BLDG-34 Rough
Electrical
082685-2019
August 22, 2019
BLDG-Final
Inspection
Checklist Item
BLDG-Building Deficiency
082686-2019
Checklist Item
BLDG-Building Deficiency
BLDG-Electrical Final
Partial Pass Michael Collins
COMMENTS
Partial electrical.
Failed Michael Collins
COMMENTS
No van accessible space.
FRONT PORCH COMMUNITIES
AND SERVICES
TOWN OF CARLSBAD AMENDED
2855 Carlsbad Blvd
Carlsbad, CA 92008
Reinspection Complete
Reinspection
Passed
Yes
Reinspection
Passed
No
No
Incomplete
Complete
Page 1 ol 1
January 14, 2019
PAMELA SMITH
8330 CENTURY PARK CT
SAN DIEGO, CA 92123-1530
RE: BUILDING PERMIT EXPIRATION
PERMITlYPE: BLDG-Commercial, Cogen
{city of
Carlsbad
PERMIT NUMBER: CBC2018-0125
ISSUE DATE: 09/14/2018
ADDRESS: 2855 Carlsbad Blvd
Carlsbad, ca 92008-2902
Our records Indicate that your building permit will expire by limitation of time on 03/13/2019.
18.04.030 section 10S.S amended -Expiration:
Every permit issued by the Building Official under the provisions of this code shall expire by
limitation and bemme null and void if the building or work authorized by such permit is not
commenced within 180 calendar days from the date of such permit, or if the building or work
authorized by such permit is stopped at any lime after the work is commenced for a period of 180
calendar days, or if the building or work authorized by such permit exceeds three calendar years
from the issuance date of the pennit. Work shall be presumed ID have commenced if the permittee
has obtained a requiTed inspection approval of work authorized by the pem1it by the Building
Official within 180 calendar days of the date of permit issuance. Work shall be presumed ID be
slDpped if the permittee has not obtained a required inspection approval of work by the Building
Official within each 180 day period upon the initial commencement of work authorized by such
permit.
Before sudl work can be recommenced, a new permit shall be obtained ID do so, and the fee
therefore shall be one half the amount required for a new permit for such work, and provided that
no changes have been made or will be made in the original plans and specifications fur such work,
and provided fuTther that such suspension or abandonment has not exceeded one year. In order ID
renew action on a permit alter expiration, the permittee shall pay a new permit fee.
Any permittee holding an unexpiTed permit may apply ror an extension of lime within which work
maycommenoe under thatpennitwhen thepermitteeis unable to commence work within the time
period required by this section ror good and satisfactory reasons.
Please check below indicating your intentions and return this letter to us.
D Project abandoned. A new permit will be obtained prior to commencing work.
D Permit 180 day extensiOn request, with written explanation including phone number and email address.
Request will not be considered without explanation
D Renewal permit requested.
If the project has been completed and only a final inspection is needed, please call the
inspection request Dne at (760) 602-272S.
If you have any questions, please contact !he Building Inspection Division at 760-602-2700.
Community & Economic Development
Building Division! 1635 Faraday Avenue, Carlsbad, CA 92008-7314 ! 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
DATE: 6/8/18
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2018-0125
✓• EsG1I
A SAFE built Company
SET: II
PROJECT ADDRESS: 2855 Carlsbad Boulevard
~~LICANT
/JURIS.
PROJECT NAME: Carlsbad by the Sea 4 EV Charging Stations/Site "A"
IZI The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
IZI EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted:
Mail Telephone
0 REMARKS:
By: Eric Jensen by CM
EsGil
Telephone#:
Email:
Enclosures:
6/1/18
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: March 16, 2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2018-0125
✓• EsG1I
SETI
PROJECT ADDRESS: 2855 Carlsbad Boulevard
□ APPLICANT
_?JURIS.
PROJECT NAME: Carlsbad by the Sea 4 EV Charging Stations/Site "A"
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
[;gJ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
D EsGil staff did not advise the applicant that the plan check has been completed.
[;gJ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Pamela Smith
Date contacted: 3(16 /18' (by~ Email:
Telephone#: 760 298-9023
pamelas@C2GROUP. US
(fMail Telep~e
0 REMARKS:
By: Eric Jensen
EsGil
Fax In Person
Enclosures:
03/08
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBC2018-0125
March 16, 2018
GENERAL PLAN CORRECTION LIST
JURISDICTION: Carlsbad
PROJECT ADDRESS: 2855 Carlsbad Boulevard
DATE PLAN RECEIVED BY
ESGIL: 03/08
REVIEWED BY: Eric Jensen
FOREWORD (PLEASE READ):
PLAN CHECK#.: CBC2018-0125
DATE REVIEW COMPLETED:
March 16, 2018
This plan review is limited to the technical requirements contained in the International Building
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, noise attenuation and disabled access. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. The approval of
the plans does not permit the violation of any state, county or city law.
• Please make all corrections, as requested in the correction list. Submit FOUR new complete
sets of plans for commercial/industrial projects (THREE sets of plans for residential projects).
For expeditious processing, corrected sets can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will
route the plans to EsGil and the Carlsbad Planning, Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake
Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of plans
and calculations/reports directly to the City of Carlsbad Building Department for routing to their
Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by EsGil is complete.
• To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
• Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
□ Yes □ No
Carlsbad CBC2018-0125
March 16, 2018
ELECTRICAL and ENERGY COMMENTS
PLAN REVIEWER: Eric Jensen
ELECTRICAL (2016 CALIFORNIA ELECTRICAL CODE)
1. Remove Note 3 from the Scope of Work, Title Sheet.
2. Clarify the primary routing of the Service conductors at the ramp and ultimately through
the wall to the service. I'm trying to determine if the service conductors are routed
through the building, not allowed per CEC 230.3.
3. Van accessible space required via CBC 11 B-228.3.2.
4. On the single line diagram, describe what is meant by "Bond to the existing structure"?
(Co-ordinate with grounding design, sheet 10.)
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite 208, San
Diego, California 92123; telephone number of 858/560-1468, to perform the plan review for
your project. If you have any questions regarding these plan review items, please contact Eric
Jensen at Esgil. Thank you.
Carlsbad CBC2018-0125
March 16, 2018
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Eric Jensen
PLAN CHECK#.: CBC2018-0125
DATE: March 16, 2018
BUILDING ADDRESS: 2855 Carlsbad Boulevard
BUILDING OCCUPANCY:
BUILDING AREA Valuation Reg.
PORTION ( Sq. Ft.) Multiplier Mod.
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
---------·,
1997 UBC Building Permit Fee • I
1997 UBC Plan Check Fee
Type of Review: 0 Complete Review
VALUE
D Structural Only
D Repetitive Fee ·,.. I Repeats
--_ __J
D Other
D Hourly
EsGII Fee
1-------11 Hr. @ •
Comments:
($)
60,000
$445.401
$289.51 I
$253.BBI
Sheet 1 of 1
( City of
Carlsbad
DETERMINATION OF PROJECT'S
SWPPP TIER LEVEL AND
CONSTRUCTION THREAT LEVEL
E-32
Development Services
Land Development Engineering
1635 Faraday Avenue
760-602-2750
www.carlsbadca.gov
I'm applying for: □ Grading Permit □ Building Permit □ Right-of-way permit D Other
Project Name: Power Your Drive -MF170343 (Site A) Project ID: _____ DWG #/CB# ____ _
Address· 2855 Carlsbad Blvd Carlsbad CA 92008 APN 203-231-01-00 Disturbed Area· 0 005 Ac , ,
Section 1: Determination of Project"s SWPPP Tier Level SWPPP
Tier (Check applicable criteria and check the corresponding SWPPP Tier Level, then go to section 2) Level
Exemgt -No Threat Project Assessment Criteria
My project is in a category of permit types exempt from City Construction SWPPP requirements. Provided no
significant grading proposed, pursuant to Table1, section 3.2.2 of Storm Water Standards, the following permits
are exempt from SWPPP requirements: D Exempt
D Electrical □ Patio D Mobile Home D Plumbing □ Spa (Factory-Made)
D Fire Sprinkler D Mechanical D Re-Roofing D Sign D Roof-Mounted Solar Array
Tier 3 -Significant Threat Assessment Criteria -(See Construction General Permit (CGP) Section I.Bl*
□ My project includes construction or demolition activity that results in a land disturbance of equal to or greater
than one acre including but not limited to clearing, grading, grubbing or excavation; or,
D My project includes construction activity that results in land disturbance of less than one acre but the
construction activity is part of a larger common plan of development or the sale of one or more acres of
disturbed land surface; or,
D My Project is associated with construction activity related to residential,
development on lands currently used for agriculture; or
commercial, or industrial D Tier3
D My project is associated with construction activity associated with Linear Underground/Overhead Projects
(LUP) including but not limited to those activities necessary for installation of underground and overhead
linear facilities (e.g. conduits, substructures, pipelines, towers, poles, cables, wire, towers, poles, cables,
wires, connectors, switching, regulating and transforming equipment and associated ancillary facilities) and
include but not limited to underground utility mark out, potholing, concrete and asphalt cutting and removal,
trenching, excavation, boring and drilling, access road, tower footings/foundation, pavement repair or
replacement, stockpile/borrow locations.
D Other per CGP
Tier 2 Moderate Threat Assessment Criteria: My project does not meet any of the Significant Threat
Assessment Criteria described above and meets one or more of the following criteria:
□ Project requires a grading plan pursuant to the Carlsbad Grading Ordinance (Chapter 15.16 of the Carlsbad
Municipal Code); or,
□ Project will result in 2,500 sq. ft. or more of soils disturbance including any associated construction staging,
stockpiling, pavement removal, equipment storage, refueling and maintenance areas and project meets one
or more of the additional following criteria: D Tier2
• located within 200 ft. of an environmentally sensitive area or the Pacific Ocean; and/or,
• disturbed area is located on a slope with a grade at or exceeding 5 horizontal to 1 vertical; and/or
• disturbed area is located along or within 30 ft. of a storm drain inlet, an open drainage channel or
watercourse; and/or
• construction will be initiated during the rainy season or will extend into the rainy season
/Oct. 1 -Aor. 301
Tier 1 -Low Threat Assessment Criteria
liZI My project does not meet any of the Significant or Moderate Threat criteria above, is not an exempt permit
type per above and the project meets one or more of the following criteria: liZI Tier 1 • results in some soil disturbance; and/or
• includes outdoor construction activities (such as roof framing, saw cutting, equipment washing, material
stockoilinn vehicle fuelinn waste stocknilinal
* Items hsted are excerpt from CGP. CGP governs cntena for tnggers for Tier 3 SWPPP. Developer/owner shall confirm coverage under the current CGP
and any amendments, revisions and reissuance thereof.
E-32 Paoe 1 of2 REV. 02/16
SWPPP Section 2: Determination of Project's Construction Threat Level Construction
Tier (Check applicable criteria under the Tier Level as determined In section 1, check the Threat
Level corresponding Construction Threat Level, then complete the emergency contact and Level sl11nature block below)
Exempt -Not Applicable -Exempt
Tier 3 -High Construction Threat Assessment Criteria: Ml£ Project meets one or more of the
following:
D Project site is 50 acres or more and grading will occur during the rainy season
□ Project site is located within the Buena Vista or Agua Hedionda Lagoon watershed, inside or
within 200 feet of an environmentally sensitive area (ESA) or discharges directly to an ESA □ High D Soil at site is moderately to highly erosive (defined as having a predominance of soils with
Tler3 USDA-NRCS Erosion factors k, greater than or equal lo 0.4)
□ Site slope is 5 to 1 or steeper
□ Construction is initiated during the rainy season or will extend into the rainy season
(Oct. 1 -April 30)
□ Owner/contractor received a Storm Water Notice of Violation within oast two vears
Tier 3 -Medium Construction Threat Assessment Criteria D Medium □ All projects not meeting Tier 3 High Construction Threat Assessment Criteria
Tier 2 -High Construction Threat Assessment Criteria: Ml£ Project meets one or more of the
following:
□ Project is located within the Buena Vista or Agua Hedionda Lagoon watershed, inside or
within 200 feet of an environmentally sensitive area (ESA) or discharges directly to an ESA
□ Soil at site is moderately to highly erosive (defined as having a predominance of soils with □ High USDA-NRCS Erosion factors k, greater than or equal to 0.4)
Tier 2 □ Site slope is 5 to 1 or steeper
□ Construction is initiated during the rainy season or will extend into the rainy season
(Oct. 1 -Apr. 30)
□ Owner/contractor received a Storm Water Notice of Violation within past two years
□ Site results in 10,000 sq. fl. or more of soil disturbance
Tier 2 -Medium Construction Threat Assessment Criteria □ Medium □ My project does not meet Tier 2 High Threat Assessment Criteria listed above
Tier 1 -Medium Construction Threat Assessment Criteria: Ml£ Project meets one or more of the
following:
□ Owner/contractor received a Storm Water Notice of Violation within past two years □ Medium □ Site results in 500 sq. ft. or more of soil disturbance Tier 1 □ Construction will be initiated during the rainy season or will extend into the rainy season
(Oct.1 -April 30)
Tier 1 -Low Construction Threat Assessment Criteria 0Low IZI My project does not meet Tier 1 Medium Threat Assessment Criteria listed above
I certify to the best of my knowledge that the above statements are true and correct. I will prepare and submit an appropnate tier level SWPPP as detennlned above
prepared in accolllance with the City SWPPP Manual. I understand and acknowledge that I must adhere to and comply with the stonn water best management
practices pursuant to Title 15 of the Carlsbad Municipal Code and to City Standallls at all times during construction activities for the pennit type(s) checked above. The
City Engineer/Building Official may authorize minor variances from the Construction Threat Assessment Criteria in special circumstances where it can be shown that a
lesser or higher SWPPP Tier Level is waminted.
Emergency Contact Name: Telephone No:
Owner/Owner's Authorized Agent Name: Title:
SCOTT DAVIS, PE Civil Engineer
Owner/Owner's Authorized Agent Signature: Date:
FOR CITY USE ONLY
Yes No
City Concurrence:
By:
Date:
E-32 Page 2 of 2 REV. 02/16
SIEMENS
VersiCharge™ Electric Vehicle
Charging Stations
-
RECEIVE
All VersiCharge devices feature: MAR O D
Easy to install 5 20/8
The included mounting bracket is easily attached to manY.~J;fa'leOlittcJ!2f@Fl!J..ded screws.
Universal VersiCharge units can either be plugged in belo~ bli\leijj~~e /)''it~fu<f}
installation is possible with all VersiCharge models. IV/Sf ON
Cost effective option available
For installations which do not require the unit to be plugged into the wall, the VersiCharge
hardwire (HW) model is a very cost effective option without sacrificing any convenience.
Delay button
A simple, multi-setting delay timer has been built into the Siemens VersiCharge to allow
the user to delay charging up to 8 hours with the press of a button. Charging sessions
automatically start after the delay timer has completed.
Charging status indicating halo
An LED halo on every VersiCharge makes reading the charging status of the unit from a
distance seem like second nature.
Maximum power adjustment switch
Installing electrical vehicle chargers into older homes can be a challenge. With the
Siemens VersiCharge, the EVSE power output can be adjusted to match facility capability.
Increments range from a maximum power setting of 7 .2 kW down to 1.8 kW.
Designed for the user and the environment
Integrated holster keeps dust and debris out of plug. 60% recycled material with matte finish
is rugged, durable, and easy to clean. The SAE J1 772 connector is ergonomically designed
for user comfort. The 20' cord is easily stored with the integrated cord management system.
Flexible demand response profile
To support advanced demand response programs, all VersiCharge models feature variable
amperage demand response and allow consumers to take advantage of utility rate
programs. This feature ensures the energy demand from the EVSE can be curtailed with a
reduced impact to the end user.
www.usa.si emens.comNersiCha rge
Wall Mounted EVSE
(
' 1, ,,
)
I
J -,/.
Mounting Bracket
14.5" W X 16.0" H x 6.5" 0
2.5" X 16.9"
(front of unit excluding connector)
15" minimum clearance
recommended for connector
when inserted Install at a minimum of 18" off the ground
VersiCharge Electric Vehicle Chargers Accessories --Color Feeder Location iif:ili::HF Description
VC30XXXU* Universal VersiCharge 30 A Grey Rear/Bottom/Hardwired
Hardwired
VCMNTGBRK Spare Parts Mounting Bracket
VC30XXXHW* Hardwired VersiCharge 30A Grey
*'XXX' serves a s a placeholder for color. Currently a light grey color is available ('GRY')
Parameters
-"'·· r
Essentials
Electrical
Mechanical
Safety
and
Operational
Attribute Universal Model Hardwired Model
Part Number
Amperage
Input voltage
Cord Length
Wall Weight
Dimensions
Output power
Enclosure
Plug in Installation
Permanent Installation
Circuit requirement
Input power connections
Recommended branch breaker
Connector
Standards Compliance
EMC
Operating temperature
Storage temperature
Operating humidity
VC30XXXU
20ft
14.5 lbs
NEMA4
VC30XXXHW
30Amps
208-240VAC
14 ft
12.5 lbs
14.5" W x 16.0" H x 6.5" D
1.BkWto 7.2 kW
NEMA 1
Yes {below or behind unit)
Yes
No
Yes
40Amperes*
Line 1, Line 2, Earth Ground
40 Ampere double pole
(Siemens: Q240 plug in type, B240 boh on type)
SAEJ1772
UL, SAE J1772, NroD 625
FCC Part 15 Class B
·30'C to +50° C
-40"C to +60"C
Maximum 95% non-condensing
• Adjustment of amperage output possible via dial in the unit, will effect the power output of charger.
• Black
Michael Baker We Make a Difference
INTERNATIONAL
LETTER OF TRANSMITTAL
To: DATE: March 02, 2018
City of Carlsbad JOB No: 160935
1635 Faraday Avenue
Carlsbad, CA 92008 REFERENCE:
Power Your Drive -
Carlsbad By the Sea
MF170343A
DESCRIPTION:
First Submittal
ATTN: Submittal Intake
SENT To You V1A:
□ E-Mail
No. of
0 Mail
D Your Pick-Up
D Blueprinter
181 Michael Baker
Messenger
No. of DESCRIPTION
D Overnight Delivery (Carrier)
D Other Courier
Copies Originals
1 1
4 Sets
1 1
2 Sets
1 2
1 2
SENT FOR YOUR:
D Files
Building Permit Application
Building Plans
Check for Submittal Fees ($408.24)
Cut Sheets
Storm Water Compliance Form (E-29)
Determination of Project's SWPPP Tier Level and Construction
Threat Level (E-32)
D Approval
D Signature
181 Review
D Use
D Comments
D Information
D Per Your Request
□-------
REMARKS: Attached please find the first submittal package for the Power Your Drive Carlsbad By the Sea
Site A MF170343A project. Please contact me if you have any questions. Thank you.
COPIES TO: File
MBAKERINTL.COM
MICHAEL BAKER INTERNATIONAL
BY:
Amanda Daniels
Project Coordinator
Land Development Department
9755 Clairemont Mesa Boulevard I San Diego, CA 92124
Office, 858.614-50001 Fax, 858.614-5001