HomeMy WebLinkAbout2857 AVENIDA HELECHO; ; CB120654; Permit05-30-2012
City of Carlsbad
1635 Faraday Av Carlsbaci, CA 92008
Patio/Deck Permit Permit No: CBl20654
Building Inspection Request Line (760) 602-2725
Job Address: 2857 AVENIDA HELECHO CBAD
Permit Type: PATIO Status: ISSUED
Parcel No: 2552813700 Lot#: 0 Applied: 04/12/2012
Valuation: $3,449.00 Constmction Type: NEW Entered By: RMA
Reference*: Plan Approved: 05/30/2012
Issued: 05/30/2012
ProjectTitle: GAGE RES-360 SF PATIO COVER Inspect Area:
SOLID ROOF, GAS TO WALL HEATER & B-VENT FIREPLACE Plan Check#:
Applicant:
TERRACON
STEA
585 N TWIN OAKS VALLEY RD
SAN MARCOS CA 92069
760 471-5265
Owner:
GAGE WILLIAM P lll&JULIE L
2857 AVENIDA HELECHO
CARLSBAD CA 92009
Building Permit
Add'l Building Permit Fee
Plan Ctieck
Add'l Plan Ctieck Fee
Strong Motion Fee
Green BIdg Standards (SB1473) Fee
Renewal Fee
Add'l Renewal Fee
Ottier Building Fee
Additional Fees
TOTAL PERMIT FEES
$68.07
$0.00
$47.65
$0.00
$1.00
$1.00
$0.00
$0.00
$150.00
$0.00
$267.72
Total Fees: $267.72 Total Payments To Date: $267.72 Balance Due: $0.00
Inspector:
FINAL APPROVAL
Date: ^^^-^V^ Clearance:
NOTICE: Please take NOTICE fhat approval of your project includes the "imposition'' of fees, dedications, resen/ations, or other exactions hereafter collectively
refened to as lees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Govemment Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attacic,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or sewice tees in connection with this project. NOR DOES IT APPLY to any
fees/exactions of which vou have oreviouslv been oiven a NOTICE similar to this, or as to which the statute of limitations has Dreviouslv othenvise expired.
CITY OF
CARLSBAD
Building Permit Appiication
1635 Faraday Ave., Carlsbad, CA 92008
760-602-2717 / 2718 / 2719
Fax: 760-602-8558
www.carlsbadca.gov
Plan Check No.
Est. Value ^ V ^ ^
Plan Ck. Deposit
Date
Ck. Deposit
SWPP
SUITE#/SPACE#/UNIT# '°"°°""2gs7 /4i.£.vm ^ececMo ' ' |-^^si-z^i -^7
CT/PROJECT # I LOT # ^ I | PHASE # |# OF UNITS j # BEDROOMS # BATHROOMS j TENANT BUSINESS NAME I CONSTR. TYPE
I ^21 I I I I .1 , , , ,M
DESCRIPTIOtLOF WORK: /nclude Square Fast of Affected Area(s) ~ 'Z^ ~ ~" Jf 775 / //
pKopo5€i> U'T^o coveR ^Lr)lJ]- kj/l<;,J Lmt^A.-r^
TENANT BUSINESS NAME
DESCRIPTIOtLPF WORK: /ncluda Square Fast of Affected Xrsafs;
GARAGE (SIT PATIOS (SF) DECKS (SF isHNia USE 5.P D PATIOS (SF)
3k)
AIR CONDITIONING
YES •
RE SPRINK^RS
YES • N(^
APPUCANT NAME (Primary Coatact) APPUCANT NAME (Secondary Contact)
ADDRESS s. ht^ms&^ s?g: Q
_ « ^ STATE _ il ZiP_^
ADDRESS
CiTY
FAX _. , ,
CiTY STATE ZiP
PHONE> (760) ^'^0'<xoi ^^6-^'^^^ PHONE FAX
EMAIL EMAIL
PROPERTY OWNER NAME CONTRACTOR BUS. NAME
ADDRESS 2^ A^^PA %lec6c^o ADDRESS m X/v Tuav CPAks vMCt ^9,
PHONE yL. T . 1" _ 1 3Il3~^n"FAX PHONE FAX
EMAIL ^ EMAIL
ARCH/DESIGNER NAME & ADDRESS STATE LIC. # STATE LIC.#
(Sec. 7031.5 Business and Professions Code: Any City or County viihich requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the appllcantfor such permit to file a signed statement that he is licensed pursuantto the provisions ofthe Contractor's License Law (Chapter 9, commending with Section 7000 of Division 3 ofthe Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred doiiars ($500)).
WORKERS' COMPENSATION
Workers' Compensation Declaration: / hereby affirm under penafly ofpeijury one ofthe following declarations:
n I have and will maintain a certificate of consent to self-insure for woriters' compensafion as provided by Section 3700 of the Labor Code, for the performance of the woric for which this penult is issued,
n I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the perfomiance of the work for which this permit is issued. My wori<ers' compensation insurance canier and policy
number are: Insurance Co. Policy No. Expiration Date
This section need not be completed Ifthe permit is fbr one hundred dollars ($100) or less.
QfaHCertificateof Exemptian: I certify that in the performance of the work for which this permit Is Issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation coveraggJsJiQlawfui, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), In
addition to the cost of compensation, damages as provlded^itJii'SScHoii STgfranhe Labor code, interest and attorney's fees.
vfif CONTRACTOR SIGNATURE rgfAGENT DATE
O W N E R-8 U I L D El? DECLARATION
/ hereby affinn that I am exempt from Contractor's Ucense Law for the following reason:
• I, as owner of the property or my employees with wages as their sole compensation, will do the woric and the structure Is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contrador's
License Law does not apply to an ovmer of property who builds or improves thereon, and who does such woric himself or through his own employees, provided that such Improvements are not Intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
• I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or Improves thereon, and contiacts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
• I am exempt under Section Business and Professions Code for this reason:
1.1 personally plan to provide the major labor and materials for construction of the proposed property improvemenL • Yes • No
2.1 (have / have not) signed an application for a building pemiit for the proposed woric.
3.1 have contracted with the following person (fimn) to provide the pmposed conslruction (include name address / phone / contractors' license number):
4.1 plan to provide poriions of the woric, but I have hired the following person to coordinate, supen/ise and provide the maj or woric (include name / address / phone / contractors' license number):
S. I will provide some of the work, but I have contracted (hired) the following persons to provide the woric indicated (Include name / address / phone / type of woric):
PROPERTY OWNER SIGNATURE •AGENT DATE
COMPLETE THIS SECTION FOR NON-RESIOENTIAL BUILDING PERMITS ONLY
is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration fonn or risk management and prevention program under Sections 25505,25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? • Yes • No
Is the applicant or future building occupant requited to obtain a pemiit from the air pollution contral district or air quality management district? • Yes n No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? ID Yes O No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
CONSTRUCTION LENDING AGENCY
I hereby affirm that there is a construction lending agency for the performance of the wori< this permit is Issued (Sec. 3097 (1) Civil Code).
Lender's Name Lender's Address
APPLICANT CERTIFICATION
I certif that I have read die application and slate that the above Intbrmation Is conect and that the Infbmiation on the plans Is accurate. I agree to comply with all C% oidlnances and State laws relating to building constmcdon.
I hereby authorize representative of the City of Carisbad to enter upon the above mentioned property fbr inspection puiposes. I ALSO AGREE TO SAVE, INDEH/INIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA An OSHA permit Is required for excavations over 5'0' deep and demolition or constmdion of stmctures over 3 stories in heighL
EXPIRATION: Eveiy pemilt issued by Ihe BuikJing Official under the provlskms of this Code shall expire by limltatkin and become nul and vokl if the bulkflng or woric authorized by such pemiit is not commenced within
180 days fiom the date of such pennit or If the bulkflng or woric authoiized by such r°miitj; twpptnH or abandoned at any time after Ihe woric Is commenced for a period of 180 days (Sectkin 106.4.4 Unifbmi BuikJing Code).
APPLICANT'S SIGNATURE DATE ^l-/i-iz
Inspection List
Permiti^: CBl20654 Type: PATIO
Date Inspection Item Inspector Act
GAGE RES- 360 SF PATIO COVER
SOLID ROOF, GAS TO WALL HEATER & B
Comments
08/10/2012 19 Final Structural -Rl
08/10/2012 19 Final Structural PB AP
07/12/2012 18 Exterior Latti/Drywall PB AP
07/09/2012 15 Roof/Reroof PB WC
07/09/2012 84 Rougti Combo PB AP
06/20/2012 11 Ftg/Foundation/Piers PB AP
06/15/2012 14 Frame/Steel/Bolting/Weldin PB AP
06/15/2012 15 Roof/Reroof PB AP
06/07/2012 39 Final Electrical PB PA
Monday, August 13,2012 Page 1 of 1
EsGil Corporation
In (partnersfiip witli government for (BuiCfing Safety
DATE: 05/29/12 • APPLICANT
• JURIS.
JURISDICTION: Carlsbad • PLAN REVIEWER
• FILE
PLAN CHECK NO.: 12-0654 SET: III
PROJECT ADDRESS: 2857 Avenida Helecho
PROJECT NAME: Attached Patio Cover/Remodel /Fireplace for Gage Residence
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
3 The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
I I The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
I I The applicant's copy of the check list has been sent to:
1X1 EsGil Corporation staff did not advise the applicant that the plan check has been completed.
I I EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Date contacted: (by: ) Email:
Mall Telephone Fax In Person
^ REMARKS: Transfer clarification note concerning gas line as noted in red ink on A-1 to set(s)
at the City.
By: Ray Fuller Enclosures:
EsGil Corporation
• GA • EJ • PC (P) 05/21/12
9320 Chesapeake Drive, Suite 208 • San Diego, Califomia 92123 • (858)560-1468 • Fax (858) 560-1576
EsGil Corporation
In ^PartnersRip with government for (BuiCtCing Safety
DATE: 05/02/12 aAEEMCANT
JURISDICTION: Carlsbad IXTEANREVIEWER
• FILE
PLAN CHECKNO.: 12-0654 SET: II
PROJECT ADDRESS: 2857 Avenida Helecho
PROJECT NAME: Attached Patio Cover/Remodel /Fireplace for Gage Residence
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
I I The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
XI The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to fonrt/ard to the applicant
contact person.
^ The applicant's copy of the check list has been sent to:
M.A. Design & Drafting
2180 Chablis Ct. Ste 109 Escondido, Ca. 92029
I I EsGil Corporation staff did not advise the applicant that the plan check has been completed.
EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Derek Berg Telephone #: (760) 390-0007 Fax #: (866) 894-2824
Date contacted: 31^1 \Z- (by: pE-) Email: madesign@vmail.com
^ Mail ^ Teleptione ^ Fax In Person
• REMARKS:
By: Ray Fuller Enclosures:
EsGil Corporation
• GA • EJ • PC 04/30/12
9320 Cliesapeake Drive, Suite 208 • SanDiego, Califomia92123 • (858)560-1468 • Fax(858) 560-1576
Carlsbad 12-0654
05/02/12
NOTE: The items listed below are from the previous correction list. These
remaining items have not been adequately addressed. The numbers of the items
are from the previous check list and may not necessarily be in sequence. The
notes in bold font are current.
1. The following note should be given with each correction list:
Please make all corrections, as requested in the correction list. Submit
three sets of plans for residential projects. For expeditious processing, corrected
sets can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
2. Verify that the final sets of plans will also be signed by the person responsible for
their preparation. Submitted plans were not signed by the designer.
7. It is unclear how the exterior fireplace and framing will maintain clearances to
slab etc. It appears per foundation plan that you are proposing to built up slab
area but none of the details provided reference this? Please clarify. Still
applies. The plans to clearly detail that fireplace and framing will be above
slab height and that interior finish of walls wiii be appropriate as subject to
moisture.
9. The plans did not adequately address the vertical and no lateral support
provided. The 4 x12 does not be appear to be adequate to support the weight of
roof material, framing and stucco lid. In addition the plans did not address the
existing header where door opening occurs as must support as must be capable
of supporting additional 300- 340#'s a ft. Still applies. Could not locate where
existing type of roofing was noted or if trusses are two point or three point
bearing. Assuming from site plan that the trusses are two point bearing
spanning 40 ft and comp shingles then the existing load is 600 #'s a ft and
the existing 4 x12 spanning 10 ft would be over stressed unless it was
select structural. What you are proposing is to add an additional 300 #'s a
ft using a 20# live load to be conservative. In this case would have to be 3
V2 X 117/8" PLM with 4 x post and depending on depth of existing footing-
spread footings may be required as City of Carlsbad limits soil bearing to
1000 psf. Appears will need design calculations to justify lateral and
vertical.
Carlsbad 12-0654
05/02/12
11. The revised plans are reflecting a gas isometric for added fireplace and
gas heater. The isometrics did not address any FAU's or gas dryer if
applicable. The gas sizes are undersized and would need to completely
redo existing gas lines. If possible could show a new separate gas lien
from the gas meter to the fireplace/gas heater. The gas line then could be
3/4" for up to 150 ft. If choose this method then just show a separate line
from the meter to fireplace and gas heater noting BTU's and total length of
run and delete existing portion.
• City to place soils stamp on plans at issuance.
• To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
• Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction
list? Please indicate:
Yes ( ) No ( )
The jurisdiction has contracted with Esgil Corporation located at 9320
Chesapeake Drive, Suite 208, San Diego, California 92123; telephone number of
858/560-1468, to perform the plan review for your project. If vou have anv
questions reaardino these plan review items, please contact Rav Fuller at
Esoii Corporation. Thank vou.
EsGil Corporation
In Partnersfiip with government for (Buififing Safety
DATE: 04/20/12 • APPLICANT
OKlURIS.
JURISDICTION: Carlsbad • PLAN REVIEWER
• FILE
PLAN CHECK NO.: 12-0654 SET: I
PROJECT ADDRESS: 2857 Avenida Helecho
PROJECT NAME: Attached Patio Cover/Remodel /Fireplace for Gage Residence
I I The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
I I The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
I I The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
XI The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
I I The applicant's copy of the check list is enclosed for the jurisdiction to fonward to the applicant
contact person.
^ The applicant's copy of the check list has been sent to:
M.A. Design & Drafting
2180 Chablis Ct. Ste 109 Escondido, Ca. 92029
I I EsGil Corporation staff did not advise the applicant that the plan check has been completed.
EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Derek Berg Telephone*: (760) 390-0007 Fax #: (866)894-2824
Date contacted: (by: ) Email: madesign@vmail.com
Mail Telephone Fax In Person
• REMARKS:
By: Ray Fuller Enclosures:
EsGil Corporation
• GA • EJ • PC 04/16/12
9320 Chesapeake Drive, Suite 208 • SanDiego, Califomia92123 • (858)560-1468 • Fax (858) 560-1576
Carlsbad 12-0654
04/20/12
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK NO.: 12-0654 JURISDICTION: Carlsbad
PROJECT ADDRESS: 2857 Avenida Helecho
FLOOR AREA:
Patio Cover 360
Fireplace
Replace windows with door
STORIES: 1
HEIGHT: 10 ft per CBC
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 04/12/12
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 04/16/12
DATE INITIAL PLAN REVIEW
COMPLETED: 04/20/12
PLANREVIEWER: Ray Fuller
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the International
Residential Code, International Building Code, Uniform Plumbing Code, Uniform Mechanical
Code, National Electrical Code and state laws regulating energy conservation, noise attenuation
and access for the disabled. This plan review is based on regulations enforced by the Building
Department. You may have other corrections based on laws and ordinance by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Present California law mandates that construction comply with the 2010 edition ofthe California
Code of Regulations (Title 24), which adopts the following model codes: 2009 IRC, 2009 IBC,
2009 UPC, 2009 UMC and 2008 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2009 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list for a copy) where each
correction item has been addressed, i.e.. plan sheet number, specification section, etc.
Be sure to enclose the marked UP list when vou submit the revised plans.
Carlsbad 12-0654
04/20/12
1. The following note should be given with each correction list:
Please make all corrections, as requested in the correction list. Submit four
new complete sets of plans for commercial/industrial projects (three sets of plans
for residential projects). For expeditious processing, corrected sets can be
submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
2. Verify that the final sets of plans will also be signed by the person responsible for
their preparation.
3. Notes in ink and changes in ink to be on vellums or CAD drawings so as to be a
permanent part of the plans. On Sheet 2 noting ICC-ESR 1364 for fireplace.
The number you provided is for stone veneer. P[lease provide a listing for direct
vent fireplace proposing and verify listed for exterior use.
4. Could not determine what the BTU's are to be for the wall mounted gas heater
and for fireplace. Please provide manufacturer's specs. The plan are noting in
ink to tap off a existing 1" line unless had a complete plumbing isometric that
included all the gas loads and their respective BTU's and lengths to each
appliance would not be able to determine ifthe 1" is adequate. In lieu of this it
appears that plumbing contractor and building inspector would need to verify.
5. Please provide the manufacturer's cut sheets for the gas heater that will reflect
distance to combustibles. The plan are noting a wall mounted gas heater above
the new door and appears may not be adequate space between top of door
jamb and ceiling (depending on clearances required )
6. Note on plans that all metal within 5 ft of pool to be bonded per NEC 680-22.
7. It is unclear how the exterior fireplace and framing will maintain clearances to
slab etc. It appears per foundation plan that you are proposing to built up slab
area but none of the details provided reference this? Please clarify.
8. The ledger connection needs to be reviewed closely . The connections appear to
be in adequate and are subject to withdrawal.
Carlsbad 12-0654
04/20/12
9. The plans did not adequately address the vertical and no lateral support
provided. The 4 x12 does not be appear to be adequate to support the weight of
roof material, framing and stucco lid. In addition the plans did not address the
existing header where door opening occurs as must support as must be capable
of supporting additional 300- 340#'s a ft.
10. The plans did not address the lateral stability for proposed patio cover.
• City to place soils stamp on plans at issuance.
• To speed up the review process, note on this list (or a copy) where each correction
item has been addressed, i.e., plan sheet, note or detail number, calculation page,
etc.
• Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly describe
them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction
list? Please indicate:
Yes ( ) No ( )
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468,
to perform the plan review for your project. Ifyou have any questions regarding
these plan review items, please contact Ray Fuller at Esgil Corporation. Thank
you.
Carlsbad 12-0654
04/20/12
[DO NOT PAY- THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 12-0654
PREPARED BY: Ray Fuller DATE: 04/20/12
BUILDING ADDRESS: 2857 Avenida Helecho
BUILDING OCCUPANCY: U TYPE OF CONSTRUCTION: VB
w BUILDING
PORTION
AREA
( Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE
Patio Cover 360
Flre Place
Replace Window;
with Door
Mis elect
gas line
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code Cb By Ordinance
BIdg. Permit Fee l)y Oidinanoe
Plan Check Fee by Ordinance ^
Type of Review: • Complete Review
•Repettive Fee ^ Repeats
Based on fiourly rate
• Other
^ Hourly
EsGil Fee
$107.50
• Structural Only
Hr. @*
$86.00
Comments:
Sheet 1 of 1
macvalue.doc +
r/
<yi
•
§
•
n
? " "
hi.
Co..
Mil
a