Description: AMS FIREPLACE: RUN GAS LINE FROM WAREHOUSE TO SHOWROOM
Applicant:
AMERICAN PATIOS INC
JEREMY ANDERSON
926 Olive Ave
Fallbrook, CA 92028-1544
760-451-9669
FEE
BUILDING INSPECTION FEE
Owner:
A P G CARLSBAD I LLC
1010 Coast Highway 101 S C/0 Raf Pacifica
Group (SlConb), 103
ENCINITAS, CA 92024
PLUMBING, ELECTRICAL, AND MECHANICAL PERMIT
Total Fees: $ 235.00 Total Payments To Date : $ 235.00
(City of
Carlsbad
Permit No: CBC2018-0485
Status:
Applied:
Issued:
Permit
Fina led:
Inspector:
Final
Inspection:
Closed -Expired
08/23/2018
10/22/2018
AMOUNT
$65.00
$170.00
Balance Due: $0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees /exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees /exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
c·cicyof
Carlsbad
COMMERCIAL
BUILDING PERMIT
APPLICATION
B-2
PI a n Check -'--""'-""""'""'--'-..,,_-!1--~""---L.U-
E st. Value
PC Deposit ---------
Date 'i/o23)/Z
Job Address ·z a & '-( v,,)~; phc· I (_cp{) .1 bO APN: -------
Tenant Name: /4W1S -,::,·ec pbc. ,Le.. CT/Project#: _________ Lot#: ___ _
Fire Sprinklers: yes/ no Air Conditioning: yes/ no
BRIEF DESCRIPTION OF WORK: ,-.i=......l:d..:::;:.[s.'4..J..L_-IJ.J..t.~>-l...-.1=..."4:Z,:::X..J..Q.C.._L2'"-...j__..../L.!:c:::!.!;a....i.l:'.3,._
D Addition/New: ___________ New SF and Use, ___________ New SF and Use,
____ Deck SF, Patio Cover SF (not including flatwork)
D Tenant Improvement: ______ SF,
_____ SF,
Existing Use ______ Proposed Use ______ _
Existing Use Proposed Use ______ _
0 Pool/Spa: ____ SF Additional Gas or Electrical Features? -------------
D Solar: ___ KW, __ Modules, ___ Mounted, Tilt: Yes/ No, RMA: Yes/ No, Panel Upgrade: Yes/ No
~ Plumbing/Mechanical/Electrical Only: --16.;:?c.,d'-'--"...S"---"'L::....!1..,· M..=C---..:::: _______________ _
D Other: ---------------------------------------
APPLICANJ; (PRIMARY) p
Name: /t-J.mer1CAh4-b·o,s hvic
Address: q2.., Ce of; Y-C, A-,le .
Citv: £a ;ibrcrd( State: (d4 Zip: qU?2K
Phone: 7@4 -L/st--q,:,,:;.q
Email:~¢:11• 62,ame-r,~4:sn{½,, /,c:>..,s.;kc.,
I ,-01,<--,
DESIGN PROFESSIONAL
Name: ~ r L~~e ~,[
Address:i2o rv~ Ud.
City: San b,5.,, State:C-M Zip:qztz. t
Phone: x:~K-57 a -3 z. 7 o
Email=--------,.--,,c----,=-=----
Architect State License: 11(/ 3o08: ?=--
CONTRACTOR BUSINESS f), Ii
Name: t4 {AAo/l,C@l')/4~0 Tnc,
Address: qz_" cO/i°vc:.. Av-c.. •
City: ha f/f,yy-£' . State:C:.-# Zip: c?zozlf
Phone: fe& -lf,'>f ~ q42 Gq
Email: --<)e,r.,,.f(~_.,'c;..., {)<-l-/4·o.J.:znc, C() "'--1
State License:,_..1..,_,_-1-...J....!""""'-Bus. Lice.;;e, (iU).S /,;}lf/ 57)
(Sec. 7031.S Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he/she is licensed pursuant to the provisions of the Contractor's license law
{Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.S by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}).
1635 Faraday Ave Carlsbad, CA 92008
B-2
Ph: 760-602-2719 Fax: 760-602-8558
Page 1 of 2
Email: Building@carlsbadca.gov
Rev. 06/18
( OPTION A}: WORKERS'COMPENSATION DECLARATION:
I hearby affirm under penalty of perjury one of the following declarations:
□ I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is issued.
□ I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: ______________________ _
Policy No. _______________ Expiration Date: __________ _
. ~ertificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to be come
1l5t,Ject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage ls unlawful, and shall subject an employer to
criminal penalties and civil fines up to $100,000. in addition the t the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
CONTRACTOR SIGNATURE:
( OPTION B ): OWNER-BUILDER DECLARATION:
I hereby affirm that/ am exempt from Contractor's License Law for the following reason:
□ I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's license Law does not apply to an owner of property who builds or improves thereon, and who does such work
himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's license Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
0 I am exempt under Section ________ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for coiistruction of the proposed property improvement. □ Yes O No
2. I (have/ have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address/ phone/ contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address/ phone/
contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name/ address/ phone/ type of work):
OWNER SIGNATURE: □AGENT DATE: _____ _ ----------------------
CONSTRUCTION LENDING AGENCY. IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name: _____________________ _ Lender's Address: _____________________ _
ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? 0 Yes O No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 Yes □ No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? □ Yes O No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
APPLICANT CERTIFICATION:
I certify that 1 have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP
HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF
THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over S'O' deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Buil
by such permit is not commenced within 1
after the work is commenced for a period
APPLICANT SIGNATURE:
1635 Faraday Ave Carlsbad, C
B-2
Ph: 760-602-2719 Fax: 760-602-8558
Page 2 of2
Email: Building@carlsbadca.gov
Rev. 06/18
PERMIT INSPECTION HISTORY REPORT (CBC2018-0485)
Permit Type: BLDG-Commercial Application Date: 0812312018 Owner: AP G CARLSBAD I LLC
Work Class: P/MIE Issue Date: 10/22/2018 Subdivision:
Status: Closed -Expired Expiration Date: 05/14/2019 Address: 2864 Whiptail Loop , 100
IVR Number: 13412 Carlsbad, CA 92010
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete
1012512018 1012512018 BLDG-23 074286-2018 Failed Andy Krogh
Gas/Test/Repairs
Reinspection Complete
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Medium pressure gas test requires 24 hour No
clock test, regulators max height per SDGE
standard 1 O' from ground
BLDG-31 074180-2018 Failed
Underground/Condu
Andy Krogh Reinspection Complete
it -Wiring
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Wrong code No
1012612018 1012612018 BLDG-14 074334-2018
Frame/Steel/Bolting/
Failed Andy Krogh Reinspection Complete
Welding (Decks)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Wrong permit called in No
1110712018 11107/2018 BLDG-23 075456-2018 Partial Pass Andy Krogh Reinspection Incomplete
Gas/Test/Repairs
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Medium pressure gas test requires 24 hour No
clock test, regulators max height per $OGE
standard 1 O' from ground
BLDG-Building Deficiency Low pressure side test ok. Clock for No
medium test not reading correctly
BLDG-31 075457-2018 Failed Andy Krogh Reinspection Complete
Underground/Condu
it -Wiring
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Wrong code No
11114/2018 11/14/2018 BLDG-23 075964-2018 Partial Pass Andy Krogh Reinspection Incomplete
Gas/Test/Repairs
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Medium pressure gas test requires 24 hour Yes
clock test, regulators max height per SDGE
standard 1 O' from ground
BLDG-Building Deficiency Start 24 gas test Yes
BLDG-Building Deficiency Low pressure side test ok. Clock for Yes
medium test not reading correctly
1111512018 1111512018 BLDG-23 076164-2018 Passed Andy Krogh Complete
Gas/Test/Repairs
August 19, 2019 Page 1 of 2
April 16, 2019
AMERICAN PATIOS INC
ATTN: JEREMY ANDERSON
926 OLIVE AVE
FALLBROOK, CA 92028-1544
RE: BUILDING PERMIT EXPIRATION
PERMIT TYPE: BLDG-Commercial, P/M/E
Ccityof
Carlsbad
PERMIT NUMBER: CBC2018-0485
ISSUE DATE: 10/22/2018
ADDRESS: 2864 Whiptail Loop, Suite 100
carlsbad, Ca 92010-6712
Our records indicate that your building permit will expire by limitation of time on 05/14/2019.
18-04-030 Section 105_5 amended -Expiration:
Every permit issued by the Building Official under the provisions of this code shall expire by
limitation and beoome null and void if the building or wock authorized by such permit is not
commenced within 180 calendar days from the date of such permit, or if the building or work
authorized by such permit is stopped at any time after the work is commenced for a period of 180
calendar days, or if the building or work authorized by such permit exceeds three calendar years
from the issuance date of the permit. Work shall be presumed to have commenced if the permittee
has obtained a required inspection approval of work authorized by the permit by the Building
Official within 180 calendar days of the date of permit issuance. Work shall be presumed to be
stopped if the permittee has not obtained a required inspection approval of work by the Building
Official within each 180 day period upon the initial commencement of work authorized by such
permit.
Before such work can be recommenced, a new permit shall be obtained to do so, and the fee
therefore shall be one half the amount required for a new permit for such work, and provided that
no changes have been made or will be made in the original plans and specifications for such work,
and provided further that such suspension or abandonment has not exceeded one year. In order to
renew action on a perm it after expiration, the permittee shall pay a new perm it fee.
Any permittee holding an unexpired permit may apply for an extension of time within which wock
may commence under that permit when the permittee is unable to commence work within the time
period required by this section fur good and satisfactory reasons.
Please check below indicating your intentions and return this letter to us.
D Praject abandoned. A new permit will be obtained prior to commencing work.
D Permit 180 day extension request, with written explanation including phone number and email address.
Request will not be considered without explanation
D Renewal permit requested.
If the project has been completed and only a final inspection is needed, please call the
inspection request line at (760) 602-2725-
If you have any questions, please contact the Building Inspection Division at 760-602-2700.
Community & Economic Development
Building Division I 1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
February 28, 2019
AMERICAN PATIOS INC
ATTN: JEREMY ANDERSON
926 OLIVE AVE
FALLBROOK, CA 92028-1544
RE: BUILDING PERMIT EXPIRATION
PERMIT TYPE: BLDG-Commercial, P/M/E
(cityof
Carlsbad
PERMIT NUMBER: CBC2018-0485
ISSUE DATE: 10/22/2018
ADDRESS: 2864 Whiptail Loop, Suite 100
Carlsbad, Ca 92010-6712
Our records indicate that your building permit will expire by limitation of time on 05/14/2019.
18.04.030 Section 105.5 amended -Expiration:
Every permit issued by the Building Official under the provisions of this code shall expire by
limitation and beCDme null and void if the building or wort authorized by sum permit is not
commenced within 180 calendar days from lhe dam of such permit, or if the building or wort
authorized by such permit is stopped at any time aftBr lhe wortc is commenced fol" a period of 180
calendar days, or if the building or wort authorized by sum permit exceeds three calendar years
from lhe issuance date of the permit. Work shaU be presumed ID have commenced if lhe permittee
has obtained a required inspection approval of work authorized by the permit by lhe Building
Official within 180 calendar days of lhe dam of permit issuance. Wortc shaU be presumed ID be
slDpped if lhe permitme has not obtained a required inspection approval of wortc by lhe Building
Official within ead! 180 day period upon the initial commencement of work authorized by such
permit.
Before such work can be recommenced, a new permit shall be obtained ID do so, and the fee
therefore shall be one half lhe amount required fol" a new permit for such work, and provided that
no manges have been made or will be made in lhe original plans and specifications li>r sum wortc,
and provided further lhat such suspension or abandonment has not exmeded one year. In order ID
renew action on a permit after expiration, Iha permitme shall pay a new permit fee.
Any permitme holding an unexpired permit may apply li>r an extension of time within which wort
may commence under that permit when lhe permitme is unable to commence wortc within Iha time
period required by !his section li>r good and satisfacmry reasons.
Please check below indicating your intentions and return this letter to us.
D Project abandoned. A new permit will be obtained prior to commencing work.
D Permit 180 day extension request, with writ!Bn explanation including phone number and email address.
Request will not be considered without explanation
D Renewal permit requested.
If the project has been completed and only a final inspection is needed, please call the
inspection request line at (760) 602-2725.
If you have any questions, please contact the Building Inspection Division at 760-602-2700.
Community & Economic Development
Building Division I 1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
DATE: OCT. 15, 2018
JURISDICTION: Carlsbad
PLAN CHECK#.: cbc2018-0485
✓• EsG1I
A .'::AFEbuilf Company
SET II
PROJECT ADDRESS: 2864 Whiptail Loop Way Apt. 100
PROJECT NAME: New Gas Piping
□ APPLICANT
..,....E::r1J UR IS
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
American Patios Inc.
~ EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacted.;...· --
Date contacted:
Mail Telephone
0 REMARKS:
By: Connor Reuss
EsGil
Fax
Telephone#: 760-451-9669
( . ) Email: Jeremy@americanpatioslnc.com
n Person
Enclosures:
10/8/18
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: Sept. 5th, 2018
JURISDICTION: Carlsbad
PLAN CHECK#.: cbc18-0485
✓• EsG1I
SET: I
PROJECT ADDRESS: 2864 Whiptail Loop Way Apt. 100
PROJECT NAME: New Gas Piping
□ APPLICANT
□ JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
American Patios Inc.
D EsGil staff did not advise the applicant that the plan check has been completed.
~ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone#: 760-451-9669
Date contacted:
Mail Telephone
0 REMARKS:
By: Connor Reuss
EsGil
(by: ) Email: Jeremy@americanpatioslnc.com
Fax In Person
Enclosures:
8/27/2018
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
:Carlsbad cbclS-0485
Sept. 5th, 2018
PLUMBING AND MECHANICAL COMMENTS
PLAN REVIEW NUMBER: cbclS-0485
PLAN REVIEWER: Connor Reuss
SET: I
PLUMBING (2016 CALIFORNIA PLUMBING CODE)
1. Please provide an accessible shut-off valve installed prior to the regulator PRV-1, PRV-2,
PRV-3, and PRV-4. CPC 1208.7.5(1) & 1210.11
2. The Gas Calculation PRV Tables (PRV-1 through PRV-2) state that CPC Table
1216.2(6) was used for sizing. This table cannot be used for sizing gas pipes with a 9"
w.c. Please correct the statement to the proper CPC Ch. 12 table.
Note: If you have any questions regarding this Plumbing and Mechanical plan review list
please contact Connor Reuss at (858) 560-1468. To speed the review process, note on
this list (or a copy) where the corrected items have been addressed on the plans.