HomeMy WebLinkAbout2870 Whiptail Loop; 106; CBC2016-0087; PermitCommercial Permit
(City of
Carlsbad
Print Date: 07/20/2018 Permit No: CBC2016-0087
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
Description:
Applicant:
2870 Whiptail Loop, 106
BLDG-Commercial
2091201000
$ 256,223.59
Work Class:
Lot#:
Reference #:
Construction Type
Bathrooms:
Orig. Plan Check#:
Plan Check#:
Tenant Improvement Status:
Applied:
Issued:
Permit
Fina led:
Inspector:
Final
Inspection:
ELEVATE: SHELL TO 1,058 SF OFFICE & 4,451 SF WAREHOUSE CREATING SUITE 106
Owner: Contractor:
Closed -Expired
12/21/2016
02/17/2017
AKrog
WARE MALCOMB ARCHITECTS A P G CARLSBAD I LLC TFW CONSTRUCTION DEVELOPMENT INC
LISA SMITH
6363 Greenwich Dr
San Diego, CA 92122-5947
619-829-2988
FEE
BUILDING PERMIT FEE $2000+
BUILDING PLAN CHECK FEE (BLDG)
1010 Coast Highway 101 S C/0 Raf Pacifica
Group (SlConb), 103
ENCINITAS, CA 92024
Po Box 220
DEL MAR, CA 92014
858-759-1223
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL EXPIR
FIRES Occupancies< 50,000sq. ft. Tl ED PER
GREEN BUILDING STANDARDS PLAN CHECK p MIT
MANUAL BUILDING PERMIT FEE ERA,,r HAs E)(p
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL SECTION 1064 4~~EDINAccoRDANcE~
PLUMBING BLDG COMMERCIAL NEW/ADDITION/REMODEL J_ . . AMENDED BY CM 1TH c.a.c.
PUBLIC FACILITIES FEES -inside CFO DATE _-c:lo-/8 . .C.18.04.030
SB1473 BUILDING STANDARDS FEE *---SIGNATURE:ff/i M,j/(
SEWER BENEFIT AREA FEES-E --J A.
SEWER CONNECTION FEE (General Capacity all areas) . -
STRONG MOTION-COMMERCIAL
TRAFFIC IMPACT Commercial-Industrial w/in CFO
Total Fees: $ 10,900.23 Total Payments To Date : $ 10,900.23 Balance Due:
AMOUNT
$1,183.35
$818.41
$89.00
$362.00
$166.00
$10.00
$55.00
$86.00
$4,663.27
$11.00
$1,298.84
$341.62
$71.74
$1,744.00
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as 11fees/exaction.11 You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees /exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees /exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
THE FOLLOWING APPROVALS REQUIRED PRIOR TO PERMIT ISSUANCE: 0PLANNING 0ENGINEERING 0BUILD1NG OFIRE OHEALTH 0HAZMATIAPCD
{'city of Building Permit Application Plan Check No.qCLC) \(o -00~ 7
1635 Faraday Ave., Carlsbad, CA 92008 Est. Value :2:5(, , 22 '-t
Carlsbad Ph: 760-602-2719 Fax: 760-602-8558 Plan Ck. Deposit email: building@carlsbadca.gov
(,Wis~~ www.carlsbadca.gov Date 12-/2-1/ I Co ISWPPP
JOB ADDRESS .2.B 7 Q W V\.i ,o ~ lootiS"'1.a. I 6<.,, SUITE#/SPACE#/UNIT#
1~0'7 lat> -1.Zo -,~ -
CT/PRQjECT # I LOT# I PHASE# l#l)FUNITS '#BEDROOMS # BATHROOMS ITENAf;\;;;~1~ I CONSTR. TYPE I occ. GROUP
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
Je11ar1 f }1>1/J 1'(11/e.lrl~ f lrl. v\ v,)1,4y e H obi. Se. 0 ff,'c.e. · (.?T 0 .ff? es,_ /058 I
ff WH 44St I
EXISTING USE I PROPOSED USE I GARAGE (SF) PATIOS (SF) I DECKS (SF) FIREPLACE IAIR CONDITIONING I FIRE SPRINKLERS
YES[), NoD vESONoD YESONoD
APPLICANT NAME L isc,.. Srv1,tJ... PROPERTY OWNER NAME "'AF P()l,c i F,' '"" Gt"°'f Primary Contact
ADDRESS 63 63 Gr rut r,.,t,,'cJ.,. Dr. ADDRESS /2 7 L.oma s Se.,.,fc,. re Or.
CITY 0 .,81 STATE ZIP Cit: • 'f, STATE ZIP $c:,,i IL 0 Cfj n.12? IJ(I 11 t t,f $ Cfl J2075
PHONEG/')_ 56'f-SJ1G I FAX PH760-'-f73-c:J838 IFAX7'60-'/96-.28 '17
EMAIL /s-,..,r/.. e)we((e_ rnalcomb. CofY1 EMAIL
DESIGN PROFESSIONAL CONTRACTOR BUS. NAME TTW (' OtU ~ nzue..n DtJ .
ADDRESS ADDRESS -::::, -s;e 7l/fll() Ml~s;:10.u VA-t.Lev'Kd zoo
' CITY STATE ZIP
CITY SA-tu~? G, {) STATE CA-ZIP 7~/t5f
PHONE I FAX PHONE
I FAX/,?/4' -z 7 (.) -f/.f;t{ S" Ct>IC/ 2 2 0 (/-f J) I
EMAIL EMAIL + P cA,ue e~54-e>--+-+ W<' C>/\JSh.'u WOIJ . 6-G'ltJ I STATE LIC. # STATE LIC# t.f "2 I g 3 7 lc'l,.[ l CITY BUS. UC.#
(Sec, 7031.5 Business and Professions Code: Any Crty or Coun_ty which requires a permit to_construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the
applicant for such permit to file a <;igned statement that he is licensed pursuant to the provisions of the Contractor's License Law /Chapter 9, commending with Section 7000 of Division 3 of the
Business and Professions Code} or [hat he is exempt therefrom, and the basis for the alleged exemption. Any v1olat1on of Section 7031.5 by any applicant for a permit subJects the applicant to a civil penalty of not more than five hundred dollars ($500)).
WORKERS' COMPENSATION
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations D I have and wilt maintain a certificate of consent to self-Insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
[Z] I have and will maintain workers' compensatl~n, a required by Section 3700 of the Labor Code, for the performance)'! the work for which this>r,rmit is issued. My workers' compensation in~ance c,irier and policy
number are: Insurance Co. Policy No. '2_ {) £ZG;:> Z '±_ Expiration Date ()(&? D I I ::ic17
This section need not be completed if the permit is for one hundred dollars ($100) or less. 0 Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' CompensaUon Laws of
California. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civll fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, d ages as provided for In Section 3706 ~~ Labor code, Interest and attorney's fees.
NS CONTRACTORSIGNATURE Let---HI/ . ;R-<J OAGENT
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
D
D
D
I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of compleUon, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
I am exempt under Section Business and Professions Code for this reason:
1. \ personally plan to provide the major labor and materials for construction of the proposed property improvement. 0Yes 0No
2. I (have I have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address I phone I contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name I address I phone I contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address I phone I type of work):
NS PROPERTY OWNER SIGNATURE 0AGENT DATE
I
i
COMPLETE THIS SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registratiOfl form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Yes No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? Yes No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR 1$ MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I certify that I have read the application and state that the above infom1ation is oorrect and that the infom1at1on on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building oonstruction.
I hereby authorize representaWe of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMrT.
OSHA: An OSHA pennlt is required fCf excavations over 5'0' deep and demolition or construction of slrucb.Jres over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limltaoon and become null and void rr the building orwak authorized by such permit is not commenced within
180 days from the date of such permit or IT the b ing or work authorized by such permit is suspended or abandooed at any time after the wrnk is commenced fCf a period of 180 days (Section 106.4.4 UnIToon Building Code).
_IS APPLICANT'S SIGNATURE DATE
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
Fax (760) 602-8560, Email building@carlsbadca.gov or Mail the completed form to City ol Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008.
CO#: (Office Use Only)
CONTACT NAME OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY STATE ZIP CITY STATE
Carlsbad CA
PHONE FAX
EMAIL OCCUPANT'S BUS. LIC. No.
DELIVERY OPTIONS
PICK UP: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1)
MAIL TO: CONTACT (Listed above)
CONTRACTOR (On Pg. 1)
OCCUPANT (Listed above)
MAIL/ FAX TO OTHER:-------------~----
Ai APPLICANT'S SIGNATURE
ASSOCIATED CB#--------
NO CHANGE IN USE/ NO CONSTRUCTION
CHANGE OF USE/ NO CONSTRUCTION
DATE
ZIP
February 01, 2018
Owner/Tenant
2870 WHIPTAIL LOOP, Suite 106
Carlsbad CA q2010
{ City of
Carlsbad
PERMIT NUMBER: CBC2016-0087
RE: BUILDING PERMIT EXPIRATION ISSUE DATE: 02/17/2017
PERMIT TYPE: BLDG-Commercial, Tenant Improvement ADDRESS: 2870 WHIPTAIL LOOP, Suite 106
Our records indicate that your building permit will expire by limitation of time on 03/05/2018.
18.04.030 Section 105.5 amended -Expiration:
Every permit issued by the Building Official under the provisions of this code shall expire by limitation and become
null and void if the building or work authorized by such permit is not commenced within 180 calendar days from the
date of such permit, or if the building or work authorized by such permit is stopped at any time after the work is
commenced for a period of 180 calendar days, or if the building or work authorized by such permit exceeds three
calendar years from the issuance date of the permit. Work shall be presumed to have commenced if the permittee
has obtained a required inspection approval of work authorized by the permit by the Building Official within 180
calendar days of the date of permit issuance. Work shall be presumed to be stopped if the permittee has not
obtained a required inspection approval of work by the Building Official within each 180 day period upon the initial
commencement of work authorized by such permit.
Before such work can be recommenced, a new permit shall be obtained to do so, and the fee therefore shall be one
half the amount required for a new permit for such work, and provided that no changes have been made or will be
made in the original plans and specifications for such work, and provided further that such suspension or
abandonment has not exceeded one year. In order to renew action on a permit after expiration, the permittee shall
pay a new permit fee.
Any permittee holding an unexpired permit may apply for an extension of time within which work may commence
under that permit when the permittee ls unable to commence woi-k within the time period required by this section
for good and satisfactory reasons.
Please check below indicating your intentions and return this letter to us.
D Project abandoned. A new permit will be obtained prior to commencing work.
D Permit 180 day extension request, with written explanation including phone number and email address.
Request will not be considered without explanation
D Renewal permit requested.
If the project has been completed and only a final inspection is needed, please call the inspection request lille at
(760) 602-2725.
If you have any questions, please contact the Building Inspection Division at 760-602-2700.
Community & Economic Development
Building Division I 1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
' +¢,,?o, :SY' j , r; , PERMIT INSPECTION HIS\'l[@RY REJ?ORT (CBC2016•0087)
Pennit Type: BLDG-Commercial Application Date: 12/21/2016 Owner:
Work Class: Tenant Improvement Issue Date: 02/17/2017 Subdivision:
Status: Closed -Expired Expiration Date: 03/05/2018 Address:
IVR Number: 988
Scheduled Actual Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector
Checklist Item
BLDG-Building Deficiency
09/05/2017 09/05/2017 BLDG-17 Interior 033638-2017
Lath/Drywall
Checklist Item
BLDG-Building Deficiency
July 20, 2018
COMMENTS
Frame and single side demising walls
separating suites 102,103,104
Passed Andy Krogh
COMMENTS
Drywall demising walls separating suites
102,103,104
A P G CARLSBAD I LLC
2870 Whiptail Loop , 106
Carlsbad, CA
Reinspection Complete
Passed
Yes
Complete
Passed
Yes
Page 3 of 3
, ~$ \ , "" t Ye
_ _ PERMIT INSPECTION HIS;IJORY REPORT JCBC2016-0087)
' '! ~ ;; ~ ' "' ' ( "
Permit Type: BLDG-Commercial Application Date: 12/21/2016 Owner: AP G CARLSBAD I LLC
Work Class: Tenant Improvement Issue Date: 02/17/2017 Subdivision:
Status: Closed -Expired Expiration Date: 03/05/2018 Address: 2870 Whiptail Loop , 106
IVR Number: 988
Carlsbad, CA
Scheduled Actual Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete Date Start Date ·------·
Checklist Item COMMENTS Passed
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Not completed No
BLDG-44 Duct support wire tied off to fire sprinkler No
Rough-Ducts-Dampers pipe
04/06/2017 04/06/2017 BLDG-85 T-Bar, 019140-2017 Passed Andy Krogh Complete
Ceiling Grids,
Overhead
Checklist Item COMMENTS Passed
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
04/12/2017 04/12/2017 BLDG-Electric Meter 019696-2017 Passed Andy Krogh Complete
Release
04/26/2017 04/26/2017 BLDG-Fire Final 021323-2017 Passed Dominic Fieri Complete
Checklist Item COMMENTS Passed
FIRE-Building Final Yes
04/27/2017 04/27/2017 BLDG-Final 021485-2017 Partial Pass Andy Krogh Reinspection Incomplete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Ok to occupy Yes
BLDG-Plumbing Final Hot water at bathroom to be fixed No
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
07/12/2017 07/12/2017 BLDG-Final 028559-2017 Cancelled Andy Krogh Reinspection Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Ok to occupy Yes
BLDG-Plumbing Final Hot water at bathroom to be fixed No
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
08/16/2017 08116/2017 BLDG-17 Interior 031800-2017 Partial Pass Andy Krogh Reinspection Incomplete
Lath/Drywall
July 20, 2018 Page 2 of 3
t~'; iHV:' t' ,;'> 0 t c'
, :, PERMIT INSPECTION HISTORY REPORT (CBC2016-0087)
~"~ ' ~)
Permit Type: BLDG-Commercial Application Date: 12/21/2016 Owner:
Work Class: Tenant Improvement l~sue Date: 02/17/2017 Subdivision:
Status: Closed -Expired Expiration Date: 03/05/2018 Address:
IVR Number: 988
Scheduled Actual
Date Start Date
02/22/2017 02/22/2017
02/24/2017 02/24/2017
Inspection Type Inspection No.
BLDG-21 014428-2017
Underground/Underf
loor Plumbing
BLDG-12 Steel/Bond 014731-2017
Beam
BLDG-14
Frame/Steel/Bolting/
Welding (Decks)
014678-2017
Checklist Item
BLDG-Building Deficiency
BLDG-31
Underground/Condu
it -Wiring
BLDG-34 Rough
Electrical
014730-2017
014679-2017
Checklist Item
BLDG-Building Deficiency
02/27/2017 02/27/2017 BLDG-14 014763-2017
Frame/Steel/Bolting/
Welding (Decks)
Checklist Item
BLDG-Building Deficiency
02/28/2017 02/27/2017 BLDG-34 Rough
Electrical
014764-2017
Checklist Item
BLDG-Building Deficiency
03/01/2017 03/01/2017 BLDG-14 014959-2017
Frame/Steel/Bo Iii ng/
Welding (Decks)
Checklist Item
BLDG-Building Deficiency
03/06/2017 03/06/2017 BLDG-24
Roughffopout
015573-2017
03/08/2017 03/08/2017 BLDG-16 Insulation 015809-2017
04/04/2017 04/04/2017 BLDG-85 T-Bar,
Ceiling Grids,
Overhead
July 20, 2018
018639-2017
Inspection Status Primary Inspector
Passed Andy Krogh
Passed Andy Krogh
Failed Andy Krogh
COMMENTS
Requires hazmat form completed and
submitted
Passed Andy Krogh
Failed Andy Krogh
COMMENTS
Requires hazmat form completed and
submitted
Failed Andy Krogh
COMMENTS
Still constructing walls
Failed Andy Krogh
COMMENTS
Still constructing walls
Passed Andy Krogh
COMMENTS
Frame, rough electrical, single side drywall
Passed Andy Krogh
Passed Andy Krogh
Failed Andy Krogh
AP G CARLSBAD I LLC
2870 Whiptail Loop , 106
Carlsbad, CA
Reinspection Complete
Complete
Complete
Reinspection Complete
Passed
No
Complete
Reinspection Complete
Passed
No
Reinspection Complete
Passed
No
Reinspection Complete
Passed
No
Complete
Passed
Yes
Complete
Complete
Reinspection Complete
Page 1 of 3
,~f
~ CITY O f
CARLSBAD
Building Division INSPECTION RECORD
0 INSPECTION RECORD CARD Wini APPROVED
PLANS MUST BE KEPT ON THE JOB
CBC2016-0087
2870 WHIPTAIL LOOP
ELEVATE: SHELL TO 1.058 SF OFFICE & 4.451 SF
WAREHOUSE CREATING SUITE 100
# 106
0 CALL BEFORE 3:00 pm FOR NEXT WORK DAY INSPECTION ..,~~ORD COP¥e1201000
0 FOR BUILDING INSPECTION CALL: 760-602-2725 .,. 1/12/2017
CBC2016-0087
Required Prior to Requesting Build Ing Final lf Checked YES
Planning/Landscape 760-944-8463 Allow 48 hours
CM&I (Engineering Inspections) 76o-438-389T Call before 2 pm
Fire Prevention 760-{,02-4660 Allow 48 hours
MASONRY PRE GROUT #33 ELECTRIC SERVICE O TEMPORARY
OGROUT 0 WALL DRAINS #35 PHOTO VOLTAIC
#10 TILT PANELS #53 ELEC/CONDUIT/WIRING
#11 POUR STRIPS #39 FINAL
#11 COLUMN FOOTINGS c oo< # MECHANICAL
#14 SUBFRAME O FLOOR O CEILING #41 UNDERGROUND DUCTS & PIPING
#15 ROOF SHEATHING #44 0 DUCT & PLENUM O REF. PIPING
#13 EXT. SHEAR PANELS #43 HEAT-AIR COND. SYSTEMS
#16 INSULATION #49 FINAL
#18 EXTERIOR LATH cooc" COMBO INSPECTION
#17 INTERIOR LATH & DRYWALL #81 UNDERGROUND (11,12,21,31)
#51 POOL EXCA/STEEL/BOND/FENCE #82 DRYWALL,EXT LATH, GAS TES (17,18,23)
#55 PREPLASTER/FINAL #83 ROOF SH EATING, EXT SHEAR (13,15)
#84 FRAME ROUGH COMBO (14,24,34,44)
#85 T-Bar(14,24,34,441
FINAL OCCUPANCY (19,29,39,49)
#21 UNDERGROUND OWASTE O WTR
#24 TOP OUT O WASTE OWTR
#27 TUB & SHOWER PAN
#23 OGASTEST OGAS PIPING A/S UNDERGROUND FLUSH
#25 WATER HEATER A/S OVERHEAD VISUAL I
#28 SOLAR WATER A/S OVERHEAD HYDROSTATIC
#29 FINAL A/SF,NAl
Com II STORM WATER F/AROUGH-IN
#600 PRE-CONSTRUCTION MEETING F/AFINAL
#603 FOLLOW UP INSPECTION FIXED EXTINGUISHING SYSTEM ROUGH-IN
#605 NOTICE TO CLEAN FIXED EXTING SYSTEM HYDROSTATIC TEST
#607 WRITTEN WARNING FIXED EXTINGUISHING SYSTEM FINAL
#609 NOTICE OF VIOLATION MEDICAL GAS PRESSURE TEST
#610 VERBAL WARNING MEDICAL GAS FINAL
REV 10/2016 SEE BACK FOR SPECIAL NOTES
Section 5416. Health and Safety Code, State of California
(a) There shall be not less than one water closet for each 20 employees or fractional part thereof working at a construction
job site. The water closet shall consist of a patented chemical type toilet.
(b) For the purpose of this section the term construction site shall mean the location on which actual construction of a
building is in progress.
(c) A violation of this section shall constitute a misdemeanor.
All construction or work for which a permit is required shall be subject to inspection and all such construction or work
shall remain accessible and exposed for inspection purposes until approved by the inspector. Work shall not be done
beyond the point indicated in each successive inspection without first obtaining the approval of the inspector.
DATE ADDITIONAL NOTES
3(t(t7 r::~" .O<.€. ~r~.J, ~~--~'Cl-ft a ~)) , , I I '\} I -
..
,
EsGil Corporation
In (J!artnersfiip witfi qo..,ernment for r/Jui(aing Safety
DATE: 02/06/2017
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: C2016-0087 SET: II
PROJECT ADDRESS: 2870 Whiptail Loop, Bldg. "A", Suite 106
D APPLICANT
...-a-JURIS.
D PLAN REVIEWER
D FILE
PROJECT NAME: OFFICE/WAREHOUSE TI FOR ELEVATE HYDROGENICS
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:-~
Date contacted: --~
Telephone#:
(b~) Email:
Mail Telephone Fax In Person
D REMARKS:
By: Sergio Azuela
EsGil Corporation
D GA D EJ D MB D PC
Enclosures:
01/30/2017
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
EsGil Corporation
In <Partnership with qo..,emment for (}Juifaing Safety
DATE: 01/06/2017
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: C2016-0087 SET: I
PROJECT ADDRESS: 2870 Whiptail Loop, Bldg. "A", Suite 106
D~ICANT ~~~~~s. D PLAN REVIEWER
0 FILE
PROJECT NAME: OFFICE/WAREHOUSE TI FOR ELEVATE HYDROGENICS
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
D EsGil Corporation staff did not advise the applicant that the plan check has been completed.
~ EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Lisa Smi~() Telephone#: 619-564-5126
Date contacted: / -lo (b~) Email: lsmith@waremalcomb.com
JI_ Mail X Telephone\} M Fax In Person
D REMARKS:
By: Sergio Azuela
EsGil Corporation
D GA 1:8:J EJ D MB D PC
Enclosures:
12/27/2016
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
City of Carlsbad C2016-0087
01/06/2017
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: C2016-0087
OCCUPANCY: B, and S-1
TYPE OF CONSTRUCTION: III-B
ALLOWABLE FLOOR AREA:
SPRINKLERS?: Yes
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 12/21/2016
DATE INITIAL PLAN REVIEW
COMPLETED: 01/06/2017
FOREWORD (PLEASE READ):
JURISDICTION: City of Carlsbad
USE: Office/Warehouse
ACTUAL AREA: 10,994 SF (TI space only)
STORIES: 1
HEIGHT:
OCCUPANT LOAD: 20
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 12/27/2016
PLAN REVIEWER: Sergio Azuela
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2013 CBC, which adopts the 2012 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2012 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
City of Carlsbad C2016-0087
01/06/2017
• GENERAL
1. Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
• PLANS
2. Provide a Building Code Data Legend on the Title Sheet. Include the following
code information for each building proposed:
+ Occupancy Classification(s). Revise the plans to show the Occupancy
Classification for the adjacent space to the Proposed Tl space, to check for
any possible Fire Barrier requirements at the demising wall between the two
spaces.
+ Height
3. Provide a note on the plans indicating if any hazardous materials will be stored
and/or used within the building which exceed the quantities listed in IBC Tables
307.1 (1) and 307.1 (2).
4. A complete description of the activities and processes that will occur in this
tenant space should be provided. A listing of all hazardous materials should be
included. The materials listing should be stated in a form that would make
classification in Tables 307.1 (1) and 307.1 (2) possible. The building official may
require a technical report to identify and develop methods of protection from
hazardous materials. Section 414.1.3.
• EXITS
5. Exit doors shall provide a clear width of not less than 32" when open 90 degrees
(i.e., a 3' wide door), and must have a minimum height of 6 feet 8 inches.
Maximum leaf width is 4 feet. Section 1008.1.1.
a) Revise the plans to show all specifications for the existing exit doors.
Section 107.2.3.
City of Carlsbad C2016-0087
01/06/2017
6. Regardless of occupant load, a floor or landing not more than Y, inch below the
threshold is required on each side of an egress door. Section 1008.1.7.
7. Note on the plans: "All egress doors shall be readily openable from the egress
side without the use of a key or special knowledge or effort." Section 1008.1.9.
In lieu of the above, in a Group B, F, Mor S occupancies (or places of religious
assembly or Group A occupancies having an occupant load of 300 or less), you
may note on the plans "Provide a sign on or near the exit door, reading THIS
DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED." This
signage is only allowed at the main exit. Section 1008.1.9.3.
• ACCESSIBILITY
8. Provide notes and details on the plans to show compliance with the enclosed
"Disabled Access" Review List.
• NON-RESIDENTIAL GREEN BUILDING STANDARDS
(Additions and Alterations)
The California Building Standards Commission (BSC) has adopted the Green Building
Standards Code which became effective January 1, 2011, and must be enforced by the
local building official. The Green Building Standards apply to nonresidential additions
or tenant improvements throughout California. These standards apply to
nonresidential additions of 1,000 sq. ft. or larger or alterations (tenant
improvements) with a value of $200.000 or more. CGC Section 301.3. Provide a
sheet on the plans labeled "Green Building Code Requirements" and include the
following notes as applicable.
9. Documentation. Note on the plans that a building "Systems Manual" as listed in
CGC Section 5.410.2.5 shall be delivered to the building owner or representative
and the facilities operator. Further, note on the plans that the "Systems Manual"
shall contain the required features listed in CGC Section 5.410.2.5.1.
10. Note on the plans that prior to final inspection the licensed contractor, architect
or engineer in responsible charge of the overall construction must provide to the
building department official written verification that all applicable provisions
from the Green Building Standards Code have been implemented as part of the
construction. CGC 102.3.
To speed up the review process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number, calculation
page, etc.
Please indicate here if any changes have been made to the plans that are not a result
of corrections from this list. If there are other changes, please briefly describe them
and where they are located in the plans.
City of Carlsbad C2016-0087
01/06/2017
Have changes been made to the plans not resulting from this correction list?
Please indicate: 0 Yes O No
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding these plan
review items, please contact Sergio Azuela at Esgil Corporation. Thank you.
PLUMBING, MECHANICAL, ELECTRICAL, and ENERGY COMMENTS
PLAN REVIEWER: Eric Jensen
PLUMBING (2013 CALIFORNIA PLUMBING CODE)
1. This occupancy will require a service sink. Please provide. CPC Table 422.1
MECHANICAL (2013 CALIFORNIA MECHANICAL CODE)
2. Include an explanation of the roof access design on the plans: existing, new,
located where, etc?
ELECTRICAL (2013 CALIFORNIA ELECTRICAL CODE)
3. Include a description for the transformer grounding electrode itself.
ENERGY (2013 CALIFORNIA BUILDING ENERGY STANDARDS)
o The energy is fine as submitted.
Note: If you have any questions regarding this Electrical, Plumbing, Mechanical, and
Energy plan review list please contact Eric Jensen at (858) 560-1468. To speed the
review process, note on this list (or a copy) where the corrected items have been
addressed on the plans.
DISABLED ACCESS REVIEW LIST
• REMODELS, ADDITIONS AND REPAIRS
1. When alterations, structural repairs or additions are made to an existing building,
that building, or portion of the building affected, is required to comply with all of the
following requirements, per Section 11 B-202.4:
• The area of specific alteration, repair or addition must comply as "new"
construction.
• A primary entrance to the building and the primary path of travel to the
altered area, must be shown to comply with all accessibility features.
• The path of travel shall include the existing parking.
City of Carlsbad C2016-0087
01/06/2017
• SITE PLAN REQUIREMENTS
2. Clearly show that the site development and grading are designed to provide
access to all entrances and exterior ground floor exits, as well as access to normal
paths of travel, per Section 11 B-206. Where necessary to provide access, shall
incorporate pedestrian ramps, curb ramps, stairways and handrails, etc.
a) Clearly show the details for all applicable elements included in the route of
access shown between the building and the entrance to the proposed Tl
space.
b) Clearly show on plans the complete route of access between the Public
Way and the proposed Tl space.
• ACCESSIBLE PARKING
3. Show that the accessible parking spaces are located, per Section 11 B-208.3.1 as
follows:
a) On the shortest possible route to an accessible entrance, when serving a
particular building.
• DOORS
4. Show or note that all hand-activated door opening hardware meets the following
requirements, per Section 11 B-404.2. 7:
a) Is to be centered <'.34" but S44" above floor. Revise the plans to show 34"
minimum, instead of 30" at DOOR NOTE # 8 on sheet A5.1.
END OF DOCUMENT
City of Carlsbad C2016-0087
01/06/2017
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad PLAN CHECK NO.: C2016-0087
PREPARED BY: Sergio Azuela DATE: 01/06/2017
BUILDING ADDRESS: 2870 Whiptail Loop, Bldg. "A", Suite 106
BUILDING OCCUPANCY: B, & S-1
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
Office Tl 1058
Warehouse Tl 4451
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code Cb By Ordinance
Bldg. Pernit Fee by Ordinance ...
j Plan Check Fee by Ordinance .,..
Type of Review: 17 Complete Review
r Repetitive Fee , jT Repeats
• •
r Other
r Hourly
EsGil Fee •
Reg. VALUE ($)
Mod.
r Structural Only
~Hr.@*
256,224
256,224
)
$662.71]
Comments: In addition to the above fee, an additional fee of $43.00 is due (0.5 hour@
$86.00/hr.) for the CalGreen review.
Sheet 1 of 1
macvalue.doc +
City of San Diego
Development Services
1222 First Ave., MS-401
San Diego, CA 92101
(619) 446-5000
FORM
Hazardous Materials os-165 Reporting J •••••• 2014 THE CITY OF SAN 0/li:GO
All non-residential projects (except retaining walls, fences and similar projects) must have a completed Hazardous Materials Re-
porting Form at the time of project submittal. This information is used to determine the occupancy classification of the proposed .
, structure(s) along with the fire and life safety protection systems and procedures required. For information regarding the comple !
: tion of this form, see lnformati n Bulletin 116.
SECTION I: GENERAL INFORMATION
f ···-..
Project Name:
[ Hydrogenlcs
: Tenant Name:
f Hydrogenlc~_ USiA, Inc.
, Job Address:
2870 Whlptall Loop, Carlsbad, 92010
r Project Contact Name: -
; Rob Del Core
SECTION m HAZARDOUS MATERIALS SUMMARY
Project Number: For City Use Only
Permit Number: For City U,e Only
Building/Unit/Suite Number:
A7
Contact Phone Number:
(858) 386-8930
i Will this business use, store or dispense any of the following hazardous materials listed below? O NO or !I YES
i . I
1 If the answer is YES, then circle the hazardous 1naterials classifications below and complete the Chemical Classification Form j
I and Summary Sheets contained in Section IV belo,v.
I
i 1.
i 2. i 3.
I
' t:
6.
Combustible/Flammable Liquids
Combustible Fiber
Compressed Gases
Corrosives
Cryogenics (Inert or Oxidizing)
Explosives or Blasting Agents
7.
8.
9.
10.
IL
12.
Fireworks
Flammable Gas
Flammable Solids
01'ganic Peroxides
Oxidizers
Oxidizing Gas
SECTION ID: HAZARDOUS PROCESS SUMMARY
' Will this business perform any of the hazardous processes listed below?
13.
14.
15.
16.
Pyrophorics
Toxics/Highly Toxics
Unstable Reactives
Water Reactives
0 NO or I!} YES
If, the answer is YES, then circle the hazardous process below and complete the Chemical Classification Form and Summary
Sheet (if necessary) contained in Section IV below. A Technical Report may be required for complex projects at the discretion of
1 the hazardous materials plan reviewer. j
I 1. i 2.
'3.
4.
Dipping Operations
Dry Cleaning
Dust-Producing Operations
Industrial Ovens/Kilns
5.
6.
7.
8.
Metal Plating
Organic Coatings
Powder Coatings
Printing
SECTION IV: HAZARDOUS MATERIALS CLASSIFICATION
I 9. Refrigeration> 220 lbs ofA-1 or
30 lbs of others
10. Semiconductor Fabrication
11. Spray Finishing
12. Welding/Cutting
I I i The classification of all chemicals stored and in use at the business is required in order to determine the requirements in the ;
: California Building and Fire Codes. Attached is a sample Chemical Classification Form required to be completed. The hazardous I
, materials submittal must include an inventory of all chemicals along with a summary sheet detailing the total amounts for each ! 1 hazardous classification. Each building or control area must have a separate summary sheet.
SECTION V: DECLARATION
1 I declare under penalty of perjury that1 to the best ofmy knowledge, the responses made herein are true and correct.
I Rob Del Core -~~4J_~rte._, Feb 20 2017
, Name of Owner/Occupant/Authorized Agent (circle one) Signature Date
I
For City Uae Only Group H -. Occupancy OR Cl Not an H Occupancy
Ci~ Employee: Date: Control Area(o)
Printed on recycled paper. Visit our web site at www sandies;o qov,,deve;opment·serv;ces.
Upon request, this Information Is available In alternative formats for persons with disabilities.
DS-165 (01-14)
City of San Diego • Development Services Department • Hazardous Materials Reporting -=-----
~----------------
Project Name:
Hydrogenics
I------- -------
Page 2 of 10 ____ .c:_
Project Number:
CHEMICAL CLASSIFICATION SUMMARY TABLE
COMMON CHEMICAL % I
MATERIAL QUANTITY QUANTITY LOCATION HAZARDOUS
CASII STATE IN USE CLASSIFICA-
NAME NAME CONC (Liquid, Solid, Gas) STORED (Open/Clooe) (Storage & Use) TIONS :
Hydrogen H2 100 I Gas 30 kg <1g stored In certiflad
commercial bottles. Used
for testing hydrogen fuel
I
cell systems.
T
I I I
I i
I
I
i
I
I
I I
!
I I I
-t I I
I I
i I
I I
I I
I I I I
-
!
I
I
I I
i
i I I I ! i I i
• SAN DIEGO REGIONAL
HAZARDOUS MATERIALS
QUESTIONNAIRE
OFFICE USE ONLY
RECORD ID#
PLAN CHECK-.i)i;\.\=~-'.Ul-13-:· ~"~g~M-BP~--~CXl..,,--4""'"!~9'1=----I
BP DATE
Business Name
_!:lydr'ogenics USA. Inc.
Pro,ted Address
Business Contact
Rob Del Core
City
Telephone#
Stale
_ _J -9 0 X
APN#
Applicant E-mail
A7
State Zip Code Plan Filo#
I CA 92130-
Telephone#
Maihng Address
12707 High Bluff Drive
Carlsbad 2870 Whiptail Loop
ProJect Contact
City
San Diego
__J
Occupancy Rating:
1 Explosive or Blasbng Agenls
2 Compressed Gases
3 Flammable/Combusl1bla Liquids
4 Flammable Solids
Organic Peroxides
Oxidizers
Pyrophorics
Unstable Readives
13 Corrosives
14 Other Health Hazards
15 None of These
quesbons as yes, applecant must_contact the aunty o an iego ~ard9~1 aterials DJV~~· '6:00. rtand Avenue. Surte 110 an Diego. CA 92123
Call (858) 505-6700 prior to the 11suance of a building pennlt ~ () k"'t Yz. ~ I Z. {P I 6 tf~ 1-12...
FEES ARE REQUIRED Projed Completion Data J Expedec/ Dato of Occupancy O CalARP Exempt
1
2
3
4
5
6
7
8
YES NO {for new construction or remodehng prOj&dS) 181 D Is your business IISted on the reverse side of th,s fonn? (check all that apply) 0 181 Will your business dispose of Hazardous Substances or Medical Waste 1n any amount? D 181 Will your business store or handle Hazardous Substances m quantflie1 greater than or equal to 55 gallons, 500
D
D D D D
pounds and/or 200 cubic feet? 181 Will your business store or handSe carcmogens/reproduct1ve to,uns in any quantity?
~ W1U your business use an existing or install an underground storage tank?
""' Will your business store or handle Regulated Substances (CalARP)? 181 Wdl your business use or install a Hazardous Waste Tank System (Trtle 22 Article 10)?
~ Wdl your business store petroleum in tanks or containers at your facility with a total faethty storage capacity equal to
or realer than 1.320 allons? Cal1fomia's Abov round Petroleum Sta e Act
Date ln,t,als
0 CalARP Required
I
Date lmtiats
0 CalARP Complete
I
Date
PART HI; SAN DIEGO COYNV: AIR POLLUTION CONTROL DISTRICT <APCP>: The following questions are intended to identity the maJonty of air pollution issues at the planning stage. our proJ&d may require addillonal measures not identified by these questions Some residential proJects may be exempt from
APCO requirements For more comprehensive requirements, please contact APCO at c_lt"!~_:i_c:?~.r~J?.@;:.Q_c.:(,)_~Jtt:1. .. ~.<!...9.Q.Y, (858) 586.2650. or 10124 Old Grove Road
San Diego. CA 92131
YES NO
1 D 181 Will the proJed disturb 160 square feet or more of existing building matenals?
Will any load supporting strudural members be removed? If yes, contact APCD prior to 1Ssuance of a building or demolition permit A
notification may be required at least 10 wor1ung days pnor to commenang demolrt1on 2 D 181
3 D
4 D
5 D
6 D
0 (ANSWER ONLY IF QUESTION 1 or 2 IS YES) Has on asbestos survey been parfonned? D (ANSWER ONLY IF QUESTION 1 or 215 YES) Based on the survey results. will the proJed dl51urb any asbestos containing material? II yes.
contact APCO prior to the issuance of a budding or demolrt1on pennrt A notification may be required at least 10 working days pnor to
commencing asbestos removal
[81 Will the project or associated construction equipment emit air contaminants? See the reverse side of this fonn or the APCO factsheet
(www sdapcd org/mfg-'facts perm ts pdf} for typical equipment requiring an APCO permit If yes. contad APCO prior to the issuance of a bu1k:hng
permit D (ANSWER ONLY IF QUESTION 5 IS YES) Will the projed or assoc,ated construction equipment be located w1thm 1.000 feet of a school
bounda ?
Briefly descnbe business activities. Briefly descnbe proposed project·
Zero emission vehicle engineering S('I \ ic'('S
I dedare under penalty of perjury that to the be&t of my knowledge and behef t a responses made herein are true and corred
£2,Q!?. 'i:v'" '--Co,Z,a --'e'="':i,,;=;w='-------------a,f1 / 2 v f 201 }
Date Name of Owner or Authorized Agent Signature of ONner or Authorized Agent
FOR OFFICAL USE ONLY: FIRE DEPARTMENT OCCUPANCY CLASSIFICATION _______________ -,----,------------
BY· DATE:
EXEMPT OR NO FURTHER INFORMATION flEQUIREO RELEASED FOR OCCUPANCY
COUNTY-HMO' APCD APCD COUNTY-HMO APCO
• A stamp m this box 2DJX exempts businessea from complet1 Matenals Business Plan Other permitting requirements may std\ apply
HM-9171 (08115) County of San Diego -OEH -Hazardous Materials 01v1s1on