1982-08-03; City Council; 7105; Reclaimed Water Standards and Specifications
� AB# o r MTG... 8/3/82 DEPT. ENG X Z O v d a C� Z O 0 CIT )F CARLSBAD - AGBM JILL TITLE: ADOPTION OF RECLAIMED WATER STANDARDS AND SPECIFICATIONS ViPw 3 f1f DEPT. HD., CITY A'^' i CITY MGR. RECOMMENDED ACTION: Adopt Resolution No. adopting City of Carlsbad Standard Drawings and Specifications for rec acme water. ITEM EXPLANATION: As a step toward implementation of the City's policy to utilize waste water, Standard Drawings and Specifications must be approved for the construction of any reclaimed water system. These Standard Drawings and Specifications are based on established reclaimed water agencies standards, and modified to meet the approval of the City of Carlsbad Utilities Director. FISCAL IMPACT: Cost of reproducing such Standards and Specifications is recovered by over -the counter sales of them. EXHIBIT: A. Resolution No. C, 9 r j adopting City of Carlsbad Standard Drawings and Specifications for e �c aimed water. B. Standard Drawings and Specifications for reclaimed water (on file in the Engineering Department). 9 a } 1. DO 2 3 4 5 s 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 RESOLUTION NO. 6959 A RESOLUTION OF THE CITY COUNCIL OF THE CITY OF CARLSLzAD; CALIFORNIA, ADOPTING STANDARD DRAWINGS AND SPECIFICATIONS FOR RECLr",:TraED WATER WHEREAS, the City Council of the City of Carlsbad has instituted a policy to utilize waste water; and WHEREAS, the construction of a distribution system to carry out this policy is necessary; and WHEREAS, the establishment of standards for this construction is required; and WHEREAS, the City of Carlsbad has drawn up certain design standards f�.,- reclaimed water distribution to be used in conjunction with certain area -wide and industry standards; NOW, THEREFORE, BE IT RESOLVED by the City Council of the City of Carlsbad that the`Carlsbad Standard Drawings and Specifications for all Reclaimed I -later Systems" dated June, 1982 on file with the City Engineer and incorporated by this reference is adopted. PASSED, APPROVED AND ADOPTED by the City Council of the City of Carlsbad at a regular meeting held- the 3rd day of Augi= , 1982, by the following vote, to wit: AYES: Council Members Ca._Ler, I Jis, Chick and Anear NOES: None '/ 6,0� ABSENT: Council Marber Kulchin �z, � L. ATTEST: _ 4 R C SLR, Mayor AL'T4.4rRAN-ZA, City Clerk — (SEAL) 1Z h CITY OF CARLSBAD STANDARD DRAWINGS AND SPECIFICATIONS FOR ALL RECLAIMED WATER SYSTEMS 0 O ! � DRAWING NUMBER RW-1 RW-2 RW-3 RW-4 RW-5 RW-6 RW-7 RW-8 RW-9 RW-10 RW-11 RW-12 RW-13 RW-14 RW-15 = RW-16 { a t !''(W-17-1 'W-17-2 INDEX RECLAIMED WATER SYSTEM 1" Reclaimed Water Service 1-1/2" and 2" Reclaimed Water Service Reclaimed Water 1" and 2" Automatic Air and Vacuum Valves Reclaimed Water System 2" Blow -off Type Assembly Type E Reclaimed Water Main Valve Well Installation Reclaimed Water System Valve Stem Extension Reclaimed Water System Air and Vacuum Valve Enclosures Reclaimed Water System Meter Box Locations Reclaimed Water System Protection. Post Reclaimed Water System Concrete Thrust Blocks Reclaimed Water System Thrust Block Bearing Areas Reclaimed Water System Concrete Valve Blocking Reclaimed Water System Anchor Block (Vertical Bend Only) Pipe Bedding and Trench Backfill for Reclaimed Water Mains Potable and Reclaimed Water Line Separations Reclaimed Water System Concrete Meter Sox in Paved Area Reclaimed and Potable Water Standard Symbols Reclaimed and Potable Water Standard Symbols �M AV -----------------0 cc k4 W w 07 CC = a:z0y Qj 46 . N w ¢ W O' E �Oa uI- UIf OV C O �u Z �Gm ¢,v,,u, 41> 4W �>cQ 0. <U = . h 2 U¢J O Ch- yIt tiw v O W Jm¢ xK>- �� jy W� � >. cr< I J Lli oa ,nI-z•T• '10. juj w X ti O W n >� J a LU I- V :r h z 2 a' a ° cz N`L ? s } } SOW i R r0 Z. z 4 Q1 W > t4 0: v V 00 O O Q� O i �O¢LCYZ () CLti lU C) J J J r •� J W ,- 41 ., ,�- VJ W Q4JI's W \� �� 0. O j K h O 0. 7 �� Ort y '1'i ----'— 1 O I_ It i- O to w oz" V U 1 W U 2 �Oai W fu (,IJ ¢ O y W QQ y 2 u°h sNuj ct OV— - Q O Ox r ti:u C� rj W J W z W CZW: c Q �cJi z2 a� ww, «v, m ©0. V0. Co 100 S1ANDARD DRAWING ER SE-FRvlcE 7 Q Z a W ti w Q J 41 cz L(GEND ;N PLANS F)3il APPVOVED BY: RG 21494 I»�`' 4 1 •�l w o 2 ;' o U i4 ,•, ti `Lu 1 cA I 0. q J W q D cr ,O � G U Ct Q r� zoCj ��z krIn ul Qtu C Zy cz) 4 d �, �^ 4•� JV Cc to Lu tki CWc`. 2Z 4C G f j O Lis Uj W 4QJa �'J �y Z N Ijj W ^y a* a W Ir Q q O?a C aW 4 Q UQ 'W-j cr , OJ4 ti 0 =Z to ti 2 2py ti4 to m z S41y 3 Q,� O `q \• 40 O Q4� y N C) `l a t„ vz ova C a 7Q -J V 2 i W to WO Q to W I to "�� �W WAq to� J O ,t, W 1 IQ �14 0 C J Gym 40m 2� 0(A1 0c) a a 4i C J o Z4 wWJ OC 1-UQ dy cc z 4Qa O V of co wOZ Q �Jy O Q O'10 0 > j Cl r} �- Ujuj w W rz u w Uj o� U Q Owl C4 J r� Ur? N �E �� of Qz T C W } 0 fi U w C I LcGFA'D 7N f'LHiij _ �--_-••- -- _—_.....___.._.....�._..._.. M?s CITYOF —OF 'r_ _-CARLSBAD-- ,fA'�Jyi�!) 1cZA`a'.�I►_1:-_� APPROVED E �� 3 1.7 21494 na, r .; a C i I $ "-----",location See drawing of RW-7 for type and enclosures 3 -- R„e 112":10• Coupling required on steel mains Insulating bushing where require Water Main NOTE:' Silver Solder Joints required (D Double Strap Bronze Service Clamp or Tapping Sleeve. See Specifications. QCorporation Stoo (J Pipe x Tubing 900 Ell 990° Sweat Ell C5) Copper Tubing 6) Female Adaptor �) Air and Vacuum Valve LEGENU ON PLANS (5 2 -- 901 Ells frcat•v !r Ar++tavw "aart -_--- CITY OF CARLSBAD STA:;DARD DRAWT-tYG I - ; RECLAIMED WATER - 1" "M 2" ,1U T 10, l I C --! -- - - AI,1 $1AID �l CI;IJl9 �..>�1LVES APPROVED r Y Nuniber f, 3 .ter. C r VARIES WITH LOCATION OF RECLAIMED WATER LINE ��`''rJ bronze Service Clamp or Tapping Slteve. See Specificotions.— Dbl. Strap l 1 2" x 'A" Brass Nipple 2" Cast Iron Gate valve 14ith Bronze Interior Q) CD2" x b" Slack Nipple n. Concrete shall be 470-C�-2000 3 VValve ;sells SZe FtW-5 atIIifSol ar I.u'Pno✓ta 10AC4 CITY OF CARLSBAD STANDARD MItAWriJG RECLAIMED 'TI ER SYSTEM 2" BLOW -OFF ASSEMBLY TYPE E LEGEND ON PLAN e APPROVED BY RCE 21494- 04rE hr, wInq M 1 Valve 2 8" Asbestos Cement Pipe, Class 150 or 8" standard strength concrete pipe. 3 r is" Valve Well Capp tr.L AllS;:irt See Detail Below NOTES: 1. Provide clamp or felt to hold pipe sections (Item 2) together during backfill. 2. Pipe shall be saw or machine cut on each end, no beveled sections will be permitted. 3. The final adjustment to finish grade may be made with an asbestos cement ring of 1" minimum height. 4. See Standard Construction Details for Blocking Requirements. RON COVER WITH THE WORD `IRRIG" CAST THEREON IN T Ii,G IN,, OF LINE - GENERAL NO"'ES: DIRECTION 1. Clearance around c.cver shall permit lifting by hand without damage to pipe. Maximum clearance shall be 3/16". 2. See Standard Drawing RN/-6 for valve stem extension. 3. See Standard Drawing R'W-8 For valve blocking. �AY�40V%M JAr= i --- I CITY OF CARLSBAD STANDARD DRAWING ( CC 1 VALVE ,TELL I NSTALLAT I GN APIP ROV{=ii BY H-CE. 21494 oA rF Uraw iny) i i, 1q- 5 I p�in,cta va6cs. L7ale 1/4" Icss Iran 1.0. of can. — \ Finish Glad! 1 15itb" Opefiling Nut iV IyPIcal z d d t ! _3elC_j�j I 1 Louse typical 1/ 4 1/4"x 2" Disc flat stock •q •e--1 1/2" ©lack Icon Pipt I t t ELEVATION NOTES 1. f xicns,on to be used svl,cn top of valvt nut is !i or mo,e bciuw finish haute. 2, Paint ail finished surlaces with asphalt varnish, REyus•» All A►-+Awu cwrt CITY OF CARLSBAD TOP VIEW CO I �II • 1! I BOTTOM VIEW co M. s'rANDARD DRAWING I RECLAIMED 'CATER SYSTEM VALVE STEM EXTENSION APPRO`*FD 13Y t7CE. 21494 UAf_ Dra� win< D t)wnbe.r(� ��` 6 C C o� 3'IG" Strel Covet eon6nunut %Held to Cylinder // \\-5 • 112" dia holes i O � r 1_N T I ---- o ^ O t' 1 1l2% 1 1r2" Angle Q placct) Weld to Cylinder PLAN Valve Sue M3 H 1" & 2" 14" 24" _14_ 30" TYPE A NOTE : ENCLOSURE SHALL BE PAINTED GREEN THE WORDS`"RECLAIMED WATER"USING Ij" HIGH BLOCK LETTERS USING RED PAINT 'SHALL BE STENCILED ON SIDE OF ENCLOSURE FACING STREET. REV13040141 JAPPAD-40 IOArz -01 '•-3•e" Anchm Dolls and Nutt (3 places) U f 1 t Ol Steel enclosure, paint as specified O2' x 2' pod , 470-C-2000 concrete, f CITY OF CARLSBAD STANDARD DRAWING RECLAIMED WATER SYSTEM AIR AND VACUUM VALVE ENCLOSURES APPROVED SY: R.C.E 21494 DA r E DrawingR11-'_ 7 Number TYPE 'A1 -- — WITH OR I?ITHOUT COt.N-11ItC1AL \ Ufl fILSIDLNTIAL SIOCIYALK • `— Curb or asplull berm thler Box Sidewalk Curb Sidewalk Meter Box 12" t_.__ J is Cutb 0 a 1-Suer Box Sidewalk f 1 .. ...r, • Agency to dtleimine slitmalt REILat•u 1x A"'tewu awre C TYPE •A2 CONTIGUOUS SIDEWALK TYPE B NON CONTIGUOUS SIDEI ALK TYPE C NO CURB Road Sutlace thler Box, TYPE D NO CUH3 Road Surface Mew Box CITY OF CARLSBAD STANDARD DRAWING � APPROVED BY RECLAIMED WATER SYSTEM 1 R.C.E. 21494 DA fE METER BOX LOCATIONS Dr(1WIncl -- Plumber few-- 8 I 4" tool i.�, • (:rtrd 4lo end i:aintld in a;coldancn Nil Siondords. 4iP • C - 2000 conuelt v.3#1"14r IAPPIRUVLd JDArt CITY OF CARLSBAD STANDARD DRAWING RECLAINF� 1jATER SYSTE,,1 PROTECTION POST AP0ROVED A'r R.C.E. 21494 1 F Ur;rwi,rlcl n � •� tiuroh.r I� t t y V Jr it rl� 0/1 I f a ~ .L•.i4 c:' /-- - / r 0l2 TEE HORIZONTAL OR WYE VER•rICAL BEND $rparalors. tell or equal ICilVor CQUbI- r r •� <• CROSS BLOCKING ---$txi P731►. (,"Cidrd to pipe) 4 Re lrers Blind Flang! STI EL PIPE PLAN uEAD END BLOCKING Li f t Hook requi red Cast Iron Cap or Plug Bond Brc•11,cr %%Ircn required by Agency A C. PIPE. ELEVATION NOTES 1. concrete shall be 470-C-2000 2. See Standard D_awiltg Rw- I I for bearing areas re.•,.,�, e� .arrta,..+ '"r' CITY OF CARLSBAD STrIMMARD DRAWING APPROVED RY t - YSiC1RCCLAIiQED t-IA ER SI 214�4 _ u � i F COI,p.rTE THRUT LOCKS twnq Rld-10hhtmli.-�Y- , t a 0 10 Plpe Diameter in Inches NOTES I. Ilatrd gill M ilsi test plesalre and hcaung values of dry toils. 1. Values Iru^, c,rves a,e for lees a,ul deadends, i.e., straiyhl line thrust. 10r W lir•1:l 1.4 value hCn, curve. For 45' I,, nd 0 U talue t1wn curve. rm 21 UP 6c.,41: 0 4 v.,h,e (roll, curve. 3. For cond,l,uus ,,,I covered Ily curves, spacial thrust blocks must lit eo mpuled and approved .101JI-41sif lwlP40W• la.ar, 12 14 16 CITY OF CARLSBAD STANDARD DjurlelxfiG 1 APPROVED BY RECLAIMED WATER SYSTEM_— -- T111RUST BLOCK BEARING AREAS RCE. 21494 "oars Dr.1wa rig ( f113:111)e r TYPE A 'THRUST BLOCK \� Trench Bottom 1P" min Anchor 5/8" dia. rein(, bars thus Bricks under V/ hub only l Oearlr•.g V •a ai shown TYPE B THRUST BOCK i NOMS : i 1. Coi;rzote shalt he 470-C-•2000 ( 2. Type i1 ::1::;11 I-- used unless S110W.1 on plans t .: ?� ^��'•;•; �— (Toss hatched arra for key into Trench well. i A a al,V1.]I•JI It ll?•f OJl.1 .,. r•( ` "�— CITY OF CARLSBAD r'fAilbrlirD �; APPROVED UY : t ;nwirac RE' CLAztlED i.1ATE� S Y S 49 t)aI'E; EM J_.. r A -j r,'� C _ 1 RC-L 21494 -- Ph.mbe r r12 4 15 bars l—Y' minimum cover Concrete shall be 470 C•2000. •% { •' • VIA ' `•, fit'` / � rr � •may.• r. Pipe Cubic Ft. Of Concrete Nominal Required per 100 P.S.I. Prcuure• aia 45° 12 171° 11_1_/4` _ _ 2 —_ —4-- _ G ; 5—___. lA _ —] � 10^ •—• 21 r1 12 • • 16 Increase volumes shown in propo.tron to pres:ures existing Khen pressure testing pipeline. Special design required. 451 ; 12 1/21 ; 11 1140 C rIQYrDnw -1 aY IA•iiAO+R• OArc CITY OF CARLSBAD STANDAw) Di2.r WING APPROVED BY: RECLAIIMEr01rr,'VATCR SYSTEM ►: c; r. 21494 DA N' ANCHN BLOCK Dr.4swin(1 ! ~� (VERTICAL BEND ONLY) WMI)or M-1— 13 L H t N 4 U � z; N n. O Trench Width I C o.... n n Invert Elevation t 1 2 Minimum clearance for SECTION 3 " a smaller plastic pipe.6"minimum cleoronce for 4" and larger pipelines, tyO'fs:S regardless of type. 1. For tronclhing in streets see Standard Construction Details for resurfacing- 2. M .in;linatas minimum relative compaction. 3. Unless otherwise shown on the: plans, ttte total cover over the pipe shall bc:3�/,!Feret or a; direci eci by the c-n ji.neer. (atvra(•.��r �r-11-11r�aart '! CITY OF CARLSBAD STANDAkD DRAW1w;S wj APPROVED BY: ! --- PIPE BEDDING AND TI?ejCH I3ACKIFI11 R.CE 21494 i,.1Ti= FUR RECLAHW D WATER MANS u``►4wt,"q ,►I_ 14 I 1 PARALLEL CONSTRUCTION PERPENDICULAR CONSTRUCTION IF ANY RECLAIMED WATER LINE IS PLANNED IN ANY OF THE ZONES SHOWN ABOVE, SPECIAL CONSTRUCTION WILL BE REQUIRED FOR THE RECLAIMED WATER LINE AS SHOWN BELOW. ZON E CONSTRUCTION REQUIREMENT A MINIMUM PIPE CLASS 2 x WWP; 4' MINIMUM SEPARATION; NO COMMON TRENCHES. B MINIMUM PIPE CLASS 2 x WWP; MECHANICAL COMPRESSION JOINTS 4' BOTH SIDES OF CROSSING. C DO NOT LOCATE ANY RECLAIMED WATER LINE IN THIS ZONE. NOTES ! I. 2 x WWP - WA ER LINE ATHE ORG VI WATER EN POINTP`�ESSURE OF RECLAIMED 2. CNiL& C STEEL PIPE PART 2; SECTION 207-IO)OR Pti-RMASTRAN (PART 2A; SECTION 207-21 ) SHALL BE USED TO PROVIDE A MNIUMUM PIPE CLASS OF 2x WWP WHEN REQUIRED. ViSIG� uAl L 9Y AnPRGVi C CITY OF CARLSBAD STANDARD DRAWIi`IG POTABLE AND RECLAIMED WATER LINE SEPARATIONS APPROVED BY: R.C.E. 21494 D1TI: Di2AWiNG F�v��r` c, NU,MBEl� -I- �I 11 K 1 I 1 1 1 ! i I I I i 1 1 I 1 I rk N e rfvu.� �r ,Ipeevto cart APPROVED BY CITY OF CARLSBAD STANDARD DRAWING -- RECLAIMED WATER SYSTEM - � '--- _ R.CE. 21494 DATE: CONCRETE METER BOX Drawl-- (i !G - - -- --- — _- 1- - IN PAVED AREA uucxi)er io SYHGGL DESCRIPTION STAID. D;JG. NO. FR_iM__j Reclaimed plater Meter RW-1 , RW-2 Automatic Air & Vacuum Valves RW-7 60 2" Blow -off assembly R14-4 Type E Reduced Pressure Type Backflow Prevention Unit / Double Check Backflow Prevention Uni t P� Booster Pump i Pressure Regulator ~C Master Flow Control Pressure Relief Valve P.O.C. Point of Connection AWN ,, Gate Valve -Line Size C Automatic Controller -Denoting 'No. of Stations i — �= CITY OF CARLSBAD Sir"%NDARD DRA'N:�;G APPRQvED B7 -- RECLAIMED WATER STANDARD SYNIHOL.S PCEE 21494 DATE C�2AN:tvl�+ GRAW:NG RY/- l7 -1 i 1 S'rMBut_ DESCRIPTION ORemote Control Valve !Manual Control Valve Anti -Syphon Manual Control Val re Atmospheric.Vacuum Breaker Swing Check ..Val ve Spring Loaded Check Valve Quick Coupling Valve HB Nose Bibb Sleeve or Conduit & Size --------. Existing Sleeve or Conduit & Size r_ Electrical Line C----- Control 1ti ri ng A I Control Sequence LOT' Remote Control Valve Size VS-0i Gallons Per Minute I Detail Number Sheet Number 2" 10-5-5 Sub -injected Tee Strainer a Size Sub -injected Flow Control Valve 8, Size R Reclaimed Water Pressure Line & Size Existing Reclaimed tJat-er Pressure Line & Size R4,._ Reclaimed 1-later Non -Pressure Line 2. E Size R._ Existing Reclaimed Water Non - Pressure Line a Size CfTY OF CARLSBAD STANDAPD CRAW ,.\)G RECLAIMED WATER STANDARD SYEtii GLS APC-R0vF1) aY • RCZ 21494 CATS t�U�rFf4 4 k 17 Z Z� Z Ms PART 1 SECTION 200 TO SECTION 212-3.3 STANDARD CONSTRUCTION MATERIALS FOR OFFSITE OR CITY OWNED RECLAIMED WATER SERVICE For use in connection with "Standard Specifications for Public Works Construction" 1982 Edition All work done under this contract shall be done in accordance with the Standard Specifications for Public Works Construction, 1982 Edition using these Standard Construction Materials for Reclaimed Water Service. All references to measurement and payment in Part 3 of the Standard Specifications for Public Works Construction are deleted. (6/82) j�) PART 1 CONSTRUCTTON MATERIALS FOR RECLAIMED WATER SERVICE SECTION 207 - PIPE 207-7 Asbestos Cement Pressure Pipe All offsite reclaimed water Asbestos Cement Pressure Pipe 4" or greater shall be as specified herein. 207-7.1 General In second paragraph replace "Class 150" with "Class 200". *207-7.4 Special Construction Considerations Special construction requirements shall be incorporatted into the asbestos cement reclaimed water piping as shown on City Standard Drawing RW-15 whenever basic separation between reclaimed and potable waterlines cannot be maintained. 207-17 Plastic Water Mains 207-17.2.3 PVC Pipe Less Than 4 Inches The rigid unplasticized compound from which the PVC pipe, fittings and appurtenances shall conform to ASTM D1784, Class PVC 12454- B for polyvinyl chloride. Pipe PVC pipe shall be Schedule 80 and shall conform to ASTM D1785; PVC 1120. Fittings PVC fittings shall conform to the requirements of. ASTM 2467 for socket type. Flanges shall be 150-pound, flat -face, socket - type unless otherwise shown. The outside diameter and drilling of flanges shall conform to ANSI B16.5, Class 150. * Added Sections (6/82) Part 1-1 P c i r t 1 1 f � r S i i P t t t Flange Caskets Neoprene full -face gaskets 1/8-inch think of 45 to 60 durometer ("A" scale) hardness are required for flanged joints. Flange Bolting Bolts, washers, and nuts for making up flanged joints on PVC pipe shall be stainless steel Type 303 or 304. t Page 1-la �5 Solvent Primer Socket type connections shall be primed Primer furnished by the supplier of the PVC pipe and fittings. Solvent Cement Socket type connections shall only be joined by heavy duty solvent cement furnished by the supplier of the PVC pipe and fittings, and shall conform to ASTM D2564. *207-17.2.4 PVC Pipe 4 Inches and Greater All offsite reclaimed water PVC piping 4 inches and greater shall be as specified herein. A fiberglass composite pipe compound having an inner core of PVC overwrapped with continuous fiberglass and bonded with epoxy resin. The pipe shall have been tested by the manufacturer to a pressure of 350 psi or greater at 73°F and shall be of the bell and spigot type and shall have the same outside dimension as cast iron pipe to facilitate connections to standard mechanical joint fittings and shall provide for expansion and contraction at each joint. The Pipe shall be Permastran pipe as manufactured by Johns -Manville or approved equal. The p'pe shall be installed as per the pipe manufacturer and shall be painted along the top of the pipe as described herein. Cast iron mechanical joint (CIMJ) fittings blocks placed in shall be used and thrust accordance with Reclaimed Water Standard Drawings. CIMJ couplings shall be used for transition to 3" and smaller PVC pipe with special rubber gaskets as per the reinforced fiberglass pipe manufacturer. *Added Section (6/82) Part 1-2 *207-•17.4.5 Other P.ipe Materials for Distribution and Transmission Mains Because of special conditions, other types of pipe may be specified. Specificati..rts for pipe ma.4erial, other than those included in these specifications, will be prepared with the plans for the particular conditions requiring variations from these specifica- tions. *207-19 Service Clamps for Permastran Pipe The following service clamps are approved for use with Permastran pipe in accordance with the manufacturer's Installation Guide: APAC Style 1-107 and 1-108 Clow Style 3407 and 3408 Ford Style 101S, 101N, 202S and 202N Rockwell Style 238 and 239 Cascade Style CS1 and CS2 Two (2) inch service clamps shall only be r usod on 12" permastran pipe. One and one- half (1-1/2) inch service clamps shall be used on 8", 10" and 12" Permastran pipe only. One (1) inch service clamps may be used on 4" through 12" Permastran pipe. When larger service outlets are required than allowed above, a stainless steel tapping sleeve shall be used which meets the installation require- ments set by the manufacturer of the 4 Permastran pipe. Tapping sleeves should be assembled in accordance with the manufac- turer's directiono and the bolt torqued to 50 ft-lbs for a 150 psi hydrostatic test to approximately 85 ft-lbs for a 350 psi hydrostatic test. Actual torque to be • determined by the manufacturer's of the tapping sleeve and the Permastran pipe, depending upon the pressure used for the hydrostatic test. *Added Section (6/82) Part 1-3 PART 2 SECTION 300 TO SECTION 311-1.11 CONSTRUCTION METHODS FOR OFFSITE OR CITY OWNED RECLAIMED WATER SERVICE For use in connection with "Standard Specifications for Public Works Construction" 1982 Edition All work done under this contract shall be done in accordance with the Standard Specifications for Public Works Construction, 1982 Edition, using these Construction Methods for Reclaimed Water Service. All references to measurement of payment in part 3 of the Standard Specifications for Public Works Construction are deleted. (6/82) �)(z PART 2 CONSTRUCTION METHODS FOR RECLAIMED WATER SERVICE CONDUIT CONSTRUCTION SECTION 306 - UNDERGROUND 9 *306-1.1.7 Trench Undercut for the installation of When excavating er in diameter, 4 inches and plastic pipe ut S 1nWhen trench shall bbottomroftthex the pipe. below the outside of 3 inches excavating for the installation the trench shall be plastic pipe, and smaller p th of two (2) deP `s excavated to a minimum All inches below the bottom of the pipe. w the bbeorefilled trench undercut1sexb�Trelnshallches bottom of the bedding material. with 9 Trench Over -Excavation ' *306-1.1.8 to six The trench shall be refilled as bottom of plastic inches below the outside "Y pipe. 3 0 6 -1. 2. 1 Bedding .---------- the method Plastic pipe shall be bedded using lined and coated called for bedding mortar f steel pipe. Field Jointing o Solvent Welded PVC Pipe 306-1.2.9f the fist i Delete the second sentence aragraphsrshall be ' paragraph. The following p ' added: fittings and appurtenances shall be PVC pipe joints, except provided with solvent welded where otherwise shown. solvent welded joints shall be made in accordance with ASTM D2855. Part 2-1 *Added Section (6/82) C�I The ends of the plastic pipe shall be cut square and smooth, beveled, and wiped clean. Primer shall first be applied to the outside of the Pipe and the inside of the fitting socket with a small paint brush. After priming, solvent cement shall be applied to the outside of the pipe and inside of the fitting socket with a small paint brush. Solvent shall be applied in such a manner that no material is deposited on the interior surface of Lila pine or extruded into the interior of the pipe during joining. The coated surfaces shall be immediately pushed snugly together and the pipe rotated approximately 1/4 turn to insure uniform distribution of cement. Excess cement on the exterior of the joint shall be wiped clean immediately after assembly. Care shall be exercised in assemblying a pipeline with solvent welded joints so that stress on previously made joints is avoided. Handling of the pipe following jointing, such as lowering the assembled pipeline into the trench, shall not occur prior to the set times specified in ASTM D2855. The pipeline shall not be exposed to water for 24 hours after the last solvent welded joint is made. *306-1.2.13 Utility Crossings, Separation and Protection All utility crossings, separation and protection requirements shall conform to the City's Standard Drawings for separation between reclaimed water mains and conflicting utilities. *306-1.2.14 Installation of PVC Pipe PVC pipe installation shall be in accordance with ASTM D2774 and these Standard Specifications. Provisions for protection of runs from damage due to thermal expansion, contraction and thrust shall be made in accordance with the manufacturer's instructions and these Standard Specifications. The pipe shall be snaked in the trench. If required by the Engineer, the pipe shall be cooled by filling it with water prior to backfilling. The pipeline shall not be exposed to water for 24 hours after the last solvent welded joint is made. *Added Section (6/82) Part 2-2 !a *306-1,2.15 Stogy ape of Plastic Pire Plastic pipe, fittings, and appurtenances shall be stored under cover in a flat, horizontal position, and protected from the sun and elements until ready for installation. 306-1.4.5 Water Pressure Test for Offsite or City Owned Reclaimed ? r e WatSys tems The maximum allowable leakage for "Permastran" pipe shall be: " y" LEAKAGE ALLOWABLE - GALLONS PER 1000 FT. }; (50 JOINTS) PER HOUR r� Test Pressure (PSI) Pipe Size 50 100 150 200 250 411 611 38 .54 .66 .77 .85 • .81 8„ .99 1.15 1.28 .76 1.08 1.32 z`3 1.53 1.71 10" .96 1.35 1.66 1.91 2.14 M° 1211 1.15 1.62 1.99 2.30 2.56 v Hydrostatic testing of reclaimed water lines shall be performed using potable water. Reclaimed water will not be introduced into the reclaimed system until all tests have passed and the system is ready fir acceptance by the City, except for making the connection to the City's. existing reclaimed water distribution system. See Section 306-1.4.9, "Placing Offsite or City Owned Reclaimed Water System into Service." *306-1.4.8 Disinfection Disinfection of Reclaimed Water Distribution System is not required. *Added Section (6/82) Part 2-3 J/ *306-1.4.9 Placing Offsite or City Owned Reclaimed Water System into Service The Contractor's reclaimed water system shall have passed all compaction and hydrostatic tests required. All work, except for the tie-in to the City's reclaimed water distribution system shall have been completed and ready for acceptance by the City. Upon approval by the City, the Contractor shall tie his piping system into the City owned reclaimed water distribution system. Immediately after the tie-in is made, the I Contractor shall complete all required work as expeditiously as possible in order that the City Council may accept the project. No meters shall be installed by the City until such time as the City Council his accepted the offsite or City owned reclaimed water system. *306-8 Meters All reclaimed water meters shall be installed by the City. Unless otherwise shown on the plans, no reclaimed water meters s'iall be installed until the City has accepted the offsite or City owned reclaimed water system and has approved the customer reclaimed water facilities. *306-9 Pipe Identification - Reclaimed Water Systems All buried reclaimed water piping shall be painted and installed with warning tape as specified below. Offsite or City owned piping: *Added Section (6/82) Part 2-4 I (6/82 ) 2) I) The top 180° surface Portion of the exterior shall area of the be spray paintedcwithed water Piping and allowed to dry after installed then red" enamel installation the trench and pipe is Of warning tapePrior to The paint shall be suitable fiber and backfill. glass application, for PVC and red and trench subsequently removed ny pipe painted Shall be removed from the immediatetfrom t,._ �• Ile job site 2) The plastic warning With black tape shall the wordsr,Printing on a red fieldbe PrePared The CAUTION: RECLAIMED having overall width WATERLINE," inches, of the tape shall be 6 Warning (caution) tap e Pe shall be as 10020 M RoadriffolSh Company, Houstiny`�awa (P• Inc., Texas 70033 0• 8Ox 33�48) or 800-231-6074 (Phone: 713- 9l . - ') °r approved equal. 0070 Warning tapes shall on top of the be installed directl shall be centered.. T.helongitudinall y be continuous warning y and Piping and in its covers g tape shall ten shall fastened. on the length b be feet y Plastic to each pipe apart. Othertape no more than 10 securing the than means Work, may betausedpe during backfill of of if. =table for the as be by the the Customer City. owned or onsite piping: 1) The top 180. surface Portion of the exterior shall aSPnaOf the reclaimed be y painted water pi and allowed to dryPing installed afterthe "red" enamel installation the trench and pipe is warning Prior to Any pipe painted g tape and backfill. removed from red and subs. from the the trench shall g11ently job site immediately .be `entoved The Plastic with warning tape shall be the words, Printing t a prepared The width "CAUTION: RECLAIMED having" overall WATERLINE, shall be 3 inches. Part 2-5 Warning (caution) tape shall be as manufactured by Griffoiyn company, Inc., 10020 Mykawa Road, (P. 0. Box 33248), ltouston, Texas 77033(Phone eg713-943-0070) or 800-231-6074) or approved Warning tapes shall be installed directly on top of the pipe longitudinally and shall be centered. The warning tape shall be installed continuous for the entire length of the pipe and shall be fastened to each pipe length by plastic adhesive tape banded around the pipe and warning tape at no more than. 5- foot intervals. All risers between the pipes and control valves or sprinkler heads shall be painted red and installed with warning tape. pi a Identification - Customer Owned or *306-9.1 Onsite Potable Water systems All projects that incorporate reclaimed water systems and all projects that are within 100 feet of reclaimed water systems that are not physically separated by a barrier such as a street or wall, as determined by the City, shall have all buried potable piping identified as follows: Same as Section 306-9 above, except that all pipe shall be painted "light blue" and plastic warning tape shall have blacwords, printing on a blue field having the "CAUTION: WATERLINE BURIED BELOW." *Added Section Part 2-6 (6/82) a� r PART 3 SECTION 400 TO SECTION 400-4.5 ALTERNATE ROCK PRODUCTS, ASPHALT CONCRETE, BASE MATERIAL FOR OFFSITE OR CITY OWNED 1 RECLAIMED WATER SERVICE i 1 For use in connection with "Standard Specifications for Public Works Constructin" o I 1982 Edition ll be one accordance All work done under ecificationsthis tforadn PublicWorksConstruction, with the StandardP Standard Construction Materials for 1982 Edition, using these Reclaimed Water Service. and payment in Part 3 of the All references to measurement Standard Specifications for Public Works Construction are y deleted. " (6/82)