CITY OF CARLSBAD - AGENDA BILL qc ma: TO ADOPT BY REFERENCE THE NATIONAL
ELECTRIC CODE (1987 EDITION) A WITH CITY DEPT. Am HD, I DEPT. CA 1. MODIFICATIONS I CITY MGR
*
RECOMMENDED ACTION:
Title the ordinance by the first reading and set a public heal
for N5-aY adopting the 1987 Edition of the National Electri
Code by reference.
ITEM EXPLANATION
State law requires the City to adopt the building standards ado1
by the State Department of Housing and Community Developmen which are substantially the same ‘as the requirements containec the most recent edition of the National Electric Code of National Fire Protection Association (Health and Safety Code Secl
17922 (a) (5)). The City may modify those standards to meet 1( conditions as are reasonably necessary because of local climacl
geographical, or topographical conditions. (Health and Safety ( Section 17958 . 5 (a) ) . As done previously, this ordinance will al: the standard published code in certain respects as a result of 1( conditions.
No fee increases have been requested.
FISCAL IMPACT
None.
EXHIBITS
Ordinance No. 15’2f adopting the 1987 Edition of the Natic Electric Code as published by the National Fire Protec.
Association.
j
! .. .. !I e 0 t%
1
2
3
4
ORDINANCE NO. NS-27
AN CXDINANCE OF THE CITY COUNCIL OF THE CITY OF CARLSBAD, CALIFORNIA, AMENDING TITLE 18, CHAPTER 18.12 AND TO ADOPT REFERENCE THE NATIONAL ELECTRICAL CODE (1987 EDITION).
5 The City Council of the City of Carlsbad does ordain as
6 follows:
7 SECTION 1: That Title 18, Chapter 18.12 of the Carlsbad
8
9
Municipal Code is amended by the amendment of Section 18.12.01
to read as follows:
10
11
12
13
14
18.12.010 AdoDted. The National Electrical Code (1987
Edition), copyrighted by the National Fire Protection Associat is hereby adopted by reference as the electrical code of the ( except for the changes, additions, and amendments set forth ir this chapter which shall supersede the provisions of said cod€
SECTION 2: That Title 18, Chapter 18.12 of the Carlsbad
Municipal Code is amended by the amendments of Sections 18.12,
15
16
through 18.12.270, except Sections 18.12.241, 18.12.246,
18.12.251 and 18.12.270, to read as follows:
17 11 I1 MODIFICATIONS
18
19
20
21
22
23
24
25
26
27
28
18.12.245 Article 250-81(c) amended Grounding Electrode
18.12.250 Article 331-3(1) amended Electrical Nonmetallic System
Tubing
18.12.245 Article 250-81(c) Concrete Encased Electrode amended.
The primary qroundinq method shall be that which is referred to as the 'Ufer Ground' consisting of 20 feet or mor
Copper Conductor #4 (minimum) or larger sized from N.E.C. Tab
250-904, vlGrounding Electrode Conductor for AC Systemst1. The copper conductor shall be placed three inches up from the bottom and a, three-inch clearance from the sides of the concr footing and supported by a Reinforcing Bar #4 or larger completely encased in concrete. When below ground, the coppe electrical conductor shall be encased in concrete (or in rigi nonmetallic conduit from six inches inside the concrete roofi to the service equipment.
unbroken to its termination at the service connection.
The copper electrode conductor shall be continuous and
////
i
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
I
0 0
'IFor sinsle-family residential use only (UP to and inclu
200 amp service), the concrete encased electrode (rebar) may used subject to the following requirements:
1. The Rebar #4 (1/2") or larger to which the grounding electrode conductor is connected must be a minimum of 20 feet long, unbroken.
2. The total developed length of rebar placed three inc up from the bottom of the foundation must be no less than 20 feet. Where splices are necessary to obtain the required 20
of rebar, they must be made so that the two bars overlap by n
less than 15 inches and are secured by at least two steel tie
wires. The splice shall occur at the opposite end from the
extended location.
3. The rebar may only extend out of the slab in a dry location.
4. The rebar must extend out of the slab at least six
inches and not more than 18 inches and the point of connectio
the grounding electrode connector must be accessible.
Aluminum or copper-clad aluminum electrode conductor sha not be used in concrete, outside or in any other corrosive environment. It
18.12.250 Article 331-3(1) amended - Electrical Nonmetal Tubinq. The use of electrical nonmetallic tubing and fitting shall be permitted concealed within walls and floors, where t walls and floors provide a thermal barrier of material which at least a 15-minute finish rating as identified in listings fire-rated assemblies and there is a continuous ground cable the main panel throughout the system.
SECTION 3: That Title 18, Chapter 18.12 of the Carlsbad
Municipal Code is amended by adding Sections 18.12.241,
18.12.246, 18.12.251 and 18.12.270 to read as follows:
I11 ADDITIONS
18.12.241 Articl 230-79 Rating of Disconnect 18.12.246 Article 310-5 Minimum Size of Exception No. 11 added Conductors 18.12.251 Article 333-6 amended Uses Not Permitted 18.12.270 Article 384-13 General
18.12.241 Article 230-79 Ratinq of Disconnect. The Sew Disconnecting Means shall have a rating not less than 100 amp or with approval of the administrative authority a rating not
less than the load to be carried, determined in accordance wi Article 220. In no case shall the rating be lower than speci in (a), (b), (c), or (d) below.
////
2.
-. e e
I,
1 II .I.
2
3
4
5
18.12.246 Article 310-5 Minimum Size of Conductors.
Exception No. 11 added. Branch Circuit Conductors for comme and industrial buildings for receptacle outlets and lighting shall be a minimum #12 AWG copper.
18.12.251 Article 333-6(b) amended - Uses not Permitted
Type A.C* cable shall not be used in Group A, B, E, H and I occupancies as defined in the Uniform Building Code; (Commerc and Industrial buildings).
6 Exception to Commercial Buildings Only: A complete factory
7
designed and assembled A.C. Cable Electrical System for ligh
the Building Official. or movable walls and U.L. approved may be used with approval
8
9
10
11
12
13
14
15
16
17
18
19 I
20
21
22
23
24
25
26
27
28
18.12.270 Article 384-13 General. First sentence shall amended to read:
"All panel boards shall have a rating not less than 100 amperes or with approval of the Administrative Authority not
than the minimum feeder capacity required for the load comput
in accordance with Article 220.
EFFECTIVE DATE: This ordinance shall be effective thirt
days after its adoption, and the City Clerk shall certify to
adoption of this ordinance and cause it to be published at le
once in the Carlsbad Journal within fifteen days after its
~ adoption- INTRODUCED AND FIRST READ at a regular meeting of the
Carlsbad City Council held on the 19th day of
July , 1988 and thereafter
/I//
////
////
////
////
////
////
////
////
3.
I -
,I e 0
I/
1
2
3
4
5
6
PASSED AND ADOPTED at a regular meeting of said Council
on the 16th day Of August , 1988, by thc
following vote to wit:
AYES: Council Members Lewis, Kulchin, Mamaux and Larson
NOES: None
ABSENT: Council Member Pettine
7 (L. ,/;/: ,,,,(.
8 4 /5 .' /f ' ,i .I 1
, , : /./ . l, 9 CUUDE A. LEWIS,- Mayor
10
15
14
13
12
11
ATTEST:
17
16
18
ALETHA L. RAUTENKRANZ, City C\yerk
(SEAL)
//I/
////
////
////
////
1 ////
///I
////
/I//
////
//I/
////
////
////
//I/
19 I
20
21
22
23
24
25
26
27
28
4. !I
*. .I
I. e e
NOTICE OF PUBLIC HEARING
ADOPTION OF THE 1987 ELECTRICAL CODE
NOTICE IS HEREBY GIVEN that the City Council of the City of Carlsbad, will hold a pul:
hearing on Tuesday, August 16, 1988, at 6:OO P.M., in the City Council Chambers, 120(
Elm Avenue, Carlsbad, California, to consider the adoption by reference of the
National Electrical Code (1987 Edition) with modifications.
Copies of the National Electrical Code (1987 Edition) and copies of the Ordinance art
on file in the City Clerk's Office, 1200 Elm Avenue, Carlsbad, California, and are
open to public inspection.
If you challenge the adoption of the 1987 National Electrical Code in court, you may
be limited to raising only those issues you or someone else raised at the public hear
described in this notice, or in written correspondence delivered to the City of Carls
City Clerk's Office at or prior to the public hearing.
APPLICANT: City of Carlsbad
PUBLISH: August 5, 1988 CARLSBAD CITY COUNCIL