HomeMy WebLinkAbout2765 LOKER AVE W; ; CB153125; PermitQity of Carlsbad
11-13-2015
1635 Faraday Av Carlsbad, CA 92008
Commercial/Industrial Permit Permit No: CB153125
Building Inspection Request Line (760) 602-2725
Job Address: 2765 LOKER AV WEST CBAD
Permit Type: Tl Sub Type: INDUST Status: ISSUED
Applied: 09/23/2015
Entered By: SLE
Parcel No: 2090811800 Lot#: 0
Valuation: $48,329.00 Construction Type: NEW
Occupancy Group: Reference# Plan Approved: 11/13/2015
Issued: 11/13/2015
Inspect Area
Project Title: NORDSON: STORAGE RACKING
Applicant:
RAYMOND HANDLING SOLUTIONS, INC.
10261 MATERN PL
SANTA FE SPRINGS, CA
90670
562-944-8067
Building Permit
Add'I Building Permit Fee
Plan Check
Add'I Building Permit Fee
Plan Check Discount
Strong Motion Fee
Park Fee
LFM Fee
Bridge Fee
BTD #2 Fee
BTD #3 Fee
Renewal Fee
Add'I Renewal Fee
Other Building Fee
Pot. Water Con. Fee
Meter Size
Add'I Pot. Water Con. Fee
Reel. Water Con. Fee
Green Bldg Stands (SB1473) Fee
Fire Expedidted Plan Review
$400.09
$0.00
$280.06
$0.00
$0.00
$13.53
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$2.00
$0.00
Total Fees: Total Payments To Date:
Plan Check #:
Owner:
REAL TY ASSOCIATES FUND VIII LP
C/O TA ASSOCIATES REAL TY
1301 DOVE ST#860
NEWPORT BEACH CA 92660
Meter Size
Add'I Reel. Water Con. Fee
Meter Fee
SDCWAFee
CFO Payoff Fee
PFF (3105540)
PFF (4305540)
License Tax (3104193)
License Tax (4304193)
Traffic Impact Fee (3105541)
Traffic Impact Fee (4305541)
PLUMBING TOTAL
ELECTRICAL TOTAL
MECHANICAL TOTAL
Master Drainage Fee
Sewer Fee
Redev Parking Fee
Additional Fees
HMP Fee
Green Bldg Standards Plan Chk
TOTAL PERMIT FEES
$695.68 Balance Due:
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
$0.00
??
??
$695.68
$0.00
Inspector:
FINALAPPROV~
Date: I l/ > ' I ..S Clearance: ---------
NOTICE: Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You have 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth in Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
~ <('-If> ~ CITY OF
CARLSBAD
JOB ADDRESS z. {,{
Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Ph: 760-602-2719 Fax: 760-602-8558
email: building@carlsbadca.gov
www.carlsbadca.gov
SUITEt/SPACEt/U~IT#
0BUILDING OFIRE OHEALTH OHAZMAT/APCD
Plan Ck. Deposit
Date SWPPP
CT/PROJECT# LOT# PHASE# # OF UNITS # BEDROOMS # BATHROOMS TENANT BUSINESS NAME CONSTR. 1YPE OCC. GROUP
1'tordso·n
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
j2A&-J& STO/LAG6 t''IJT~U-ATlo-v JJll!r'-r 5TOl?-A-661vo,,-"1/~4,(.
/
11, ZA 0 1r:
EXISTING USE
(':,"\O"IZl>r G,~
DESIGN PROFESSIONAL
ADDRESS
CITY
PHONE
EMAIL
STATE
FAX
GARAGE (SF) PATIOS (SF) DECKS (SF) FIREPLACE
YEsO NO
STATE
t'f/,
FAX
EMAIL
CONTRACTOR BUS. NAME
ADDRESS 1 1 r /f/pJ' H,I ti 11c-
ZIP
ZIP
rzolb
STATE UC.# STATE LIC. C Cl1Y BUS. LIC.# 'i 2.701 . C6I Jll~ 22 OJ t-5
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prl r to its issuance, also requires the applicant for such permit to file a signed statement ttiat he Is licensed pursuant to the provisions of the Contractor's License Law [Chapter 9, commending with Section 7000 of Division 3 of the Business-and Professions Code] or that he is exemP.t therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars [$500]).
Workers' Compensation Declaration: I hereby a/fi1111 under penalty of pequfY one of the following declarations: . J:IJ have and will maintain a certificate of consent to self-ins~e forworkera' compensation as provided by S~tion 3700 of the Labor Code, for the performance of the work for which this permit is issued. _
~I have and will maintain workers' compensatlon1 as required by Section 3700 of the Labor Code, for the performance of the work for which this permtt is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. be() y c,r . . Polley No. (» C, 1(:,:, 7t;J I:? . Expiration Date </-ft? I -z..o 16
This section need not be completed ff the permit is for one hundred doiiara ($100) or less. · 0 Certificate of Exemption: I certify thatin the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workera' Compensation Laws of
Caiffomia. WARNING: Failure to secure workers' compensation coverage Is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damages as rovlded for on 3706 of the Labor code, interest and attorney's fees.
_$S CONTRACTOR SIGNATURE
I hereby a/fi1111 that I am exempt from Contractor's Ucense Law.for the following reason:
D
D
D
I, as owner of the property or my employees with wages as their sole compensation, will do li)e work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himseff or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
I, as owner of the property, am exclusively contracting with licensed contractora to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License-Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed purauant to the Contractor's License Law}.
I am exempt under Section ____ ,Business and Professions Code for this reason:
1. I peraonally plan to provide the major labor and materials for construction of the proposed property improvement 0Yes 0No
2. I (have / have not) signed an application for a building permit for the proposed work.
3. I. have contracted with the following peraon (firm) to provide the proposed construction (include name address / phone / contractors' license number}:
4. I plan to provide portions of the work, but I have hired the following peraon to coordinate, supervise and provide the major work (Include name/ address/ phone/ contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following peraons to provide the work indicated (include name/ address/ phone/ type of work}:
_$S PROPERTY OWNER SIGNATURE 0AGENT DATE
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? Yes No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? Yes No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? Yes No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name Lender's Address
I certify that! have read the application and statethatthe above infonnation is correct and that the infonnation on the plans is accurate. I agree to complywith all City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OFTHE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void ~ the building or mr1< authorized by such permitis not commenced within
180 days from the date of such permit or if the building or mrk au · ed by such pennit is suspended or abandoned at any time after the mr1< is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code).
~ APPLICANT'S SIGNATURE DATE 4-:J ?,-/ S
STOP: THIS SECTION NOT REQUIRED FOR BUILDING PERMIT ISSUANCE.
Complete the following ONLY if a Certificate of Occupancy will be requested at final inspection.
CERTIFICATE OF OCCUPANCY !Commercial Projects Only)
Fax (760) 602-8560, Email building@carlsbadca.gov or Mail the completed form to City of Carlsbad, Building Division 1635 Faraday Avenue, Carlsbad, California 92008.
I CO#: (Office Use Only)
CONTACT NAME OCCUPANT NAME
ADDRESS BUILDING ADDRESS
CITY STATE ZIP CITY STATE ZIP
Carlsbad CA
PHONE I FAX
EMAIL OCCUPANT'S BUS. LIC. No.
DELIVERY OPTIONS
PICKUP: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1)
ASSOCIATED CB# MAIL TO: CONTACT (Listed above) OCCUPANT (Listed above)
CONTRACTOR (On Pg. 1) NO CHANGE IN USE/ NO CONSTRUCTION
MAIL/ FAX TO OTHER:
CHANGE OF USE/ NO CONSTRUCTION
~ APPLICANT'S SIGNATURE DATE
Inspection List
Permit#: CB153125 Type: Tl
Q§l_!~ ____ Inspection Item ____ _
01/26/2016 19 Final Structural
12/03/2015 19 Final Structural
11/25/2015 19 Final Structural
Monday, April 04, 2016
INDUST
Inspector Act
PY NS
PB
PY
AP
NR
NORDSON: STORAGE RACKING
Comments
Page 1 of 1
<!~'> W ~ITY o,
CBl53125 2765 LOKERAVWEST
NORbSON: STORAGE RACKING CARLSBAD
B1,1ilding Division INSPECTION RECOR·D, Tl INDUST
@ INSPEC:YION RECORD CARD WITH.APPROVED
PLANS MUST BE f(EPT ON THE JOB
L0t#; HAYMOND HANDLING·SOLUTIONS, INC.
@ CAI.L BEFORE 3:30 run FOR NEXT WORK DAY INSPECTION Ec···o·· RD COPY
. .\·COPY @ FOR BUILDING INSPECTION CALL: 760-602-272·5
OR GO TO: www.Carlsbadca.gov/BuildingAND CLICI< ON
"Request lnspecti9R~'
DATE: , 3 1 ( J .
L.,,_ \ ,.... ,,,.,. ,i '<n. iJ)
NO YES l?eq&Jired-Prior to Requesting B&iHdiw!J Final If Checked YES D<lte lnsp·ector ·
Planning/Landscape 760-944-8463 Allow 48 hours
CM&I (Engineerlng Inspections) Call before 2 pin
Fire Preven~ion 760-602-4660 Allow 48·hours
Type of lnsMcti()n type of Inspection
CODE# BUILDING Inspector C'ODE # ELECTRICAL
#11 FOU,NDATIQN f!31 OEL~C11UC UNDJ:RGROUNQ ,0 OF£~
#12 REINFORCED:STEEt #34 RQl!~H ELECTRIC
#66 MA~ONRYPRE ~ROUT . #33. D!:LECUUC S~RVICJ: 0 TE,IVIPORARY ..
DGROUT D WALL ORAi.NS #3.5 PHOTO VOLTAIC
#1!) Tll,TPAN.E~ #,39· FIN~
#i1 f'OURSTRIPS CODE# • MECHANICAL' ' ' . ' ..
#11 COLUMN·FOOTINGS #41. UNDERGROOND DUCTS'~ PIPING
#14 SUBfRA\VIE D FLOOR O CEILING #44 DDUCT&PLENUM D ~f .. PJPl~G
_#15 . ROOF SHEATHING #43_ HEAT,J.\JR COND • .s'($JEIYJS
#13 EXT. SHEA,R PANEL~ -.C..-~~~--~------t-------1 'ff4~. FINAL
#16 INSU!.A'l'.IQN
#18 EXTERIOR LATH
#~7 INTERIOR LATH & _DRYWALL
#51 POQL EXCA/STE,E,L/BOND/FENCE
#5\; PREPl:AS'IER/FINAL
#19 FINAL
#22 OSEWER&Bl/C_O DPL/CO.
#2.1 !JNDER\ll,IOU~Q l'.JWASTE. D WTR
#24 TOP Qlff D WASTE D WTR
#27 TUB-&SHOWERPAN
#23 D G.ASTE~T O GA~J1!.PING
#25 WATE~ HEATER
#28 SOLAR WATER .
#29 FINA~
'Cone# STORM WATER,
#600 PRE-CONSTl,tU~TION MEETING
#603' FOLLOW UP INSPECTION
#605 NOTICETOCLEAN
#607 WRITTEN WARNING
#609 ,NOTICE OFVIOLATIQN
#610 VERBALWARNING
REV1012012
comm COMBO INSP~CTION ' ·
#81 UNDEff~RQUND (1~,1.2,2·1,31)
' #82 DRYWALL,EXT.IJ\T,11,,GA~TES (17,~B,23)
I #~3 RQQfSHEATfNG, EXT SHEAR (13,15)
#84 FRAME.ROIJG~ COM.BO (14,24,34,44)
#85 T-Bar·[14;~4,34,44) .
., .y. '·FI'RE : ' . ··: '
. A/S UNDERGRQ!JND VISUAL
. A/S'.UNDERt;l?OUND FLUSH
A/SOV_ERHEADVisiJ~L
A/SFINAL
F/AROUGH-IN
F/AFlf-!AL
FIXED EXTINGQJSHING $'(STEM ROU\l_H;IN
Fl)E!) EXTING ~YSTEl';, ll'(DRO~tATICTESt .
. FIXED EXTINGUISHING SYSTEM FINAL
MEDICAL GA~ PRESSURE TEST
MEP'ICAL GAS FINAL
\
(
Date lnspect9r
Date ln:spector
\
SEE Bl'<CK FOR SPECIAL NOTES
I
I
Section 5416. Health and Safety Cod~, State of California
(a) There shall be not less than .one· water closet for !':)ach 20 employees or fra.ctional part thereof working at a
construction job site. The water closet shall consist.of a patented' chE;!niical type. toilet.
(b) For the purpose of this section the term construction &ite shall mean the location 0.n which actual ,constmcfion of a
building is fn prbgress. · ·
(c) A violation of this section shail constitute a misdemeanor.
All construction or worl< for which a permit is required shail ~ei subjectto inspection and all such construction or work
shall remain accessible and exposed for inspedibn purpose~ µntil approved ,by the ,inspector. Worl< shall not l:le done
beyond the point indicrilted in E:lach succes~ive inspection without first obtaining ttie approval of the inspector.
EsGil Corporation
In (l'artnersliip witli qovemmentfor(]Jui(aing Safety
DATE: 11/6/2015
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 15-3125
PROJECT ADDRESS: 2765 Locker Ave. West
PROJECT NAME: Storage Racks for Nordson
SET: II
!: ..,PLICANT
~~~RIS.
CJ PLAN REVIEWER
CJ FILE
[8:1 The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
[8:1 EsGil Corporation staff did not advise the applicant that the plan check has been completed.
D EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted: (by:
Telephone #:
) Email:
Mail Telephone -OiM In Person
REMARK$: City to4Hed verify that the path of travel from the handicapped parking space to the
rack area and the bathroom serving the rack area comply with all the current disabled access
requirements~'{\
By: David Yao ' ~ (/vJ.-,-Enclosures:
EsGil Corporation
D GA D EJ D MB D PC 11 /3
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
EsGil Corporation
In <Partnersli.ip wit/i, government for {}Jui(aing Safety
DATE: 9/30/2015
JURISDICTION: City of Carlsbad
PLAN CHECK NO.: 15-3125
PROJECT ADDRESS: 2765 Locker Ave. West
PROJECT NAME: Storage Racks for Nordson
SET: I
DflPLICANT
~JURIS.
D PLAN REVIEWER
D FILE
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
IZ! The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
IZ! The applicant's copy of the check list has been s~nt to:
Javier Cambero
D EsGil Corporation staff did not advise the applicant that the plan check has been completed.
IZ! EsGil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Javier Cambero Telephone#: 562-315-3154
Date con;acted: \-9 \ ~ (by:® Email: Javier.cambero@raymondhs.net
~ail v1'~~n~ Fax In Person D REMARK~,,.,
By: David Yao Enclosures:
EsGil Corporation
D GA D EJ D MB D PC 9/24
9320 Chesapeake Drive, Suite 208 + San Diego, California 92123 + (858) 560-1468 + Fax (858) 560-1576
. City, of Carlsbad 15-3125
9/30/2015
GENERAL PLAN CORRECTION LIST
JURISDICTION: City of Carlsbad
PROJECT ADDRESS: 2765 Locker Ave. West
DATE PLAN RECEIVED BY
ESGIL CORPORATION: 9/24
REVIEWED BY: David Yao
FOREWORD (PLEASE READ):
PLAN CHECK NO.: 15-3125
DATE REVIEW COMPLETED:
9/30/2015
This plan review is limited to the technical requirements contained in the International Building
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, noise attenuation and disabled access. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. The approval of
the plans does not permit the violation of any state, county or city law.
• To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
• Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
D Yes D No
. City,of Carlsbad 15-3125
9/30/2015
Please make all corrections, as requested in the correction list. Submit FOUR new complete sets
of plans for commercial/industrial projects (THREE sets of plans for residential projects).
For expeditious processing, corrected sets can be submitted in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700.
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments.
2. Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete.
1. Provide a note on the plans indicating if any hazardous materials will be stored and/or
used within the building which exceed the quantities listed in IBC Tables 307.7(1) and
307.7(2).
2. City to filed verify that the path of travel from the handicapped parking space to the rack
area and the bathroom serving the rack area comply with all the current disabled access
requirements . Title 24, Part 2.
3. Obtain Fire Department approval.
4. Dimension all diagonal and horizontal brace locations for all racks on the plans.
5. Indicate the clearance from the new racks to the existing building walls and building
columns.
6. Provide a rack layout plan showing the location of all racks. Sheet A3-0 shows 'carton
flow" "radio shuttle". Where on the floor plan identify these racks?
7. Page 15 and 16 of the calculation shows type C INT and EXT have different load per
level. The plan appears to shows one type C only (?).
8. Page 21.1 of the calculation shows load at level 6 is 1784Ib. Where on the plan shows
the deck at level 6? Why is 1784Ib?
9. The floor plan does not identify the location of pushback. Please clarify.
10. The elevation and dimension of the pushback rack shall be clearly identified on the plan.
11. Sheet SCE 3 of 3 shows Pushback 1200Ib per level. Page 22.1 of the calculation shows
10501b per level. O.K.?
, City, of Carlsbad 15-3125
9/30/2015
12. The location, elevation and dimension of the Rivetier II shelving shall be clearly identified
on the plan.
13. The location, elevation, dimension and anchorage of the VLM-REMSTAR SHUTTLE
XP-HD-500 and MEG RS 350 shall be clearly identified on the plan.
14. The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform
the plan review for your project. If you have any questions regarding these plan review
items, please contact David Yao at Esgil Corporation. Thank you.
. Ci~y; of Carlsbad 15-3125
9/30/2015
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad
PREPARED BY: David Yao
PLAN CHECK NO.: 15-3125
DATE: 9/30/2015
BUILDING ADDRESS: 2765 Locker Ave. West
BUILDING OCCUPANCY:
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
storage racks
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
Bldg. Permit Fee by Ordinance
Plan Check Fee by Ordinance
Type of Review: 0 Complete Review
Reg. VALUE
Mod.
per city
D Structural Only
D Repetitive Fee 3 Repeats
D Other
D Hourly
EsGil Fee ----IHr.@'
Comments:
($)
48,329
48,329
$400.09!
$260.061
$224.051
Sheet 1 of 1
macvalue.doc +
«~:t-. ~ CITY OF
CARLSBAD
PLANNING DIVISION
BUILDING PLAN CHECK
APPROVAL
P-29
Development Services
Planning Division
1635 Faraday Avenue
(760) 602-4610
www.carlsbadca.irnv
DATE: 9/23/15 PROJECT NAME: STORAGE RACKS PROJECT ID:
PLAN CHECK NO: CB153125 SET#: ADDRESS: 2765 LOKER AV W APN:
IZ! This plan check review is complete and has been APPROVED by the PLANNING
Division.
By: GINA RUIZ
A Final Inspection by the PLANNING Division is required D Yes ~ No
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check APPROVAL has been sent to: JAVIER.CAMBERO@RAYMONDHS.NET
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING ENGINEERING FIRE PREVENTION
760-602-4610 760-602-2750 760-602-4665
D Chris Sexton D Chris Glassen D Greg Ryan
760-602-4624 760-602-2784 760-602-4663
Chris.Sexton@carlsbadca.gov ChristoQher.Glassen@carlsbadca.gov Gregory.R}'.an@carlsbadca.gov
D Gina Ruiz D 1/alRay Marshall D Cindy Wong
760-602-4675 7 60-602-27 41 760-602-4662
Gina.Ruiz@carlsbadca.gov Va1Ra,'..Marshal1@carlsbadca.gov Cynthia.Wong@carlsbadca.gov
D D Linda Ontiveros D Dominic Fieri
760-602-2773 760-602-4664
linda.Ontiveros@carlsbadca.gov Dominic.Fieri@carlsbadca.gov
Remarks:
& ~ CITY OF
CARLSBAD
B
PLAN CHECK
REVIEW
TRANSMITTAL
COPY Community & Economic
Development Department
1635 Faraday Avenue
Carlsbad CA 92008
www.carlsbadca.gov
DATE: 10/06/2015 PROJECT NAME: NORDSON-ASYMTEK -RACKING PROJECT ID: CB153125
PLAN CK NO: SET#: 1/1 ADDRESS: 2765 LOKER AV WEST
~ This plan check review is complete and has been .APPROVED by the FIRE Division.
By: GR
A Final Inspection by the FIRE Division is required IZ! Yes D No
D This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan check comments have been sent to: Javier.cambero@raymondhs.net
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING ENGINEERING FIRE PREVENTION
'' , 16~602-4610 760,-602·2750 ,, -790,60~665 . ''
; ,' '
,.
D Chris Sexton D [Z] Greg Ryan
760-602-4624 760-602-4663
Chris.Sexton@carlsbadca.gov Gregory.Ryan@carlsbadca.gov
D Gina Ruiz D Linda Ontiveros D Cindy Wong
760-602-4675 760-602-2773 760-602-4662
Gina.Ruiz@carlsbadca.gov Linda.Ontiveros@carlsbadca.gov Cynthia.Wong@carlsbadca.gov
D D D Dominic Fieri
760-602-4664
Dominic.Fieri@carlsbadca.gov
Carlsbad Fire Department
Plan Review Requirements Category: TI, INDUST
Date of Report: 10-06-2015
BUILDING DEP''f11
COPY
Reviewed by: ¼ ;(}al(
Name:
Address:
RAYMOND HANDLING SOLUTIONS, INC.
10261 MATERN PL
Permit#:
Job Name:
Job Address:
SANTA FE SPRINGS, CA
90670
CB153125
NORDSON: STORAGE RACKING
2765 LOKER AV WEST CBAD'
Please review carefully all comments attached.
Conditions:
CITY OF CARLSBAD FIRE DEPARTMENT -APPROVED: w/ REQUIREMENT
THIS PROJECT HAS BEEN REVIEWED AND APPROVED FOR THE PURPOSES OF ISSUANCE OF BUILDING PERMIT.
THIS APPROVAL IS SUBJECT TO FIELD INSPECTION AND REQUIRED TEST, NOTATIONS HEREON, CONDITIONS IN
CORRESPONDENCE AND CONFORMANCE WITH ALL APPLICABLE REGULATIONS.
THIS APPROVAL SHALL NOT BE HELD TO PERMIT OR APPROVE THE VIOLATION OF ANY LAW.
REQUIREMENT:
PURSUANT TO CHAPTER 1/ SEC 105 AND CHAPTER 32 OF THE CARLSBAD FIRE CODE (2013} YOU SHALL IN
ADDITION TO ALL CONSTRUCTION PERMITS, BE REPOSNSIBLE TO COORDINATE WITH THE END USER OF THE
PROPOSED RACK SYSTEM TO OBTAIN FROM CARLSBAD FIRE DEPARTMENT AN 'ANNUAL' USE PERMIT.
PERMIT FEES AND APPLICATION CAN BE OBTAINED BY CONTACTING CHRISTINA WILSON AT 760-602-4665.
Entry: 10/06/2015 By: GR Action: AP
.,
St~tural
\., ts
ngineering
1615 Yeager Ave, La Verne, Ca. 91750 Tel: 909.596.1351 Fax: 909.593.8561
Project: NORDSON ASYMTEK
Project#: P-081115-2LV
Date: 10/23/15
CORRECTIONS:
Project#:
2765 LOKER AVE. WEST
CARLSBAD, CA 92010
Plan Review Responses
RECEIVED
OCT 3 0 2015
CITY OF CARLSBAD
Bl Ill DING DIVISION
4. PLEASE SEE REVISED SCE DRAWINGS FOR DIMENSION OF ALL DIAGONAL AND HORIZONTAL BRACE
LOCATIONS
7. PAGE 15 AND 16 SHOW ONLY ONE TYPE C: PAGE 15 ADDRESSES THE INTERIOR FRAME WHICH CARRIES
HALF OF THE LOADS FROM ITS BAY AND HALF OF THE LOADS FROM THE ADJACENT BAY, PAGE 16
ADDRESSES THE EXTERIOR FRAME WITH CARRIES ONLY HALF OF THE LOADS FROM ITS BAY. SO THE LOAD
SHOWED ON EXTERIOR FRAME IS ONLY 900 LBS PER LEVEL ( LOAD ON TYPE C IS 1800 LBS PER LEVEL).
PLEASE SEE NOTE AT BOTTOM OF PAGE 16.
8. PLESE SEE ELEVATION AND FLOOR PLAN FOR THE LOCATION OF DECK. LEVEL 6 IN ANALYSIS IS CREATED
TO SUPPORT 37" WIDE DECK ONLY ( RACK HAS 13 LEVEL+ DECK SUPPORT ABOVE LEVEL 5).
LOAD ON ONE SIDE = [TRIB. AREA] x [DEAD LOAD + LIVE LOAD]
= [(18.5 X 96)/144] X [10 + 125/2]
= 894 LBS
LOAD ON FRAME = 894 x 2
= 1788 LBS
10. PLEASE SEE REVISED SCE 3 OF 3 FOR ELEVATION AND DIMENSON OF PUSHBACK RACK
11. SHEET SCE 3 OF 3 SHOWS 1200 LBS PER PALLET. PAGE 22.1 SHOWS ACTUAL LOAD THAT EXTERIOR
COLUMN HAS TO CARRY FROM 1200 LBS PER PALLET. PAGE 22.2 SHOWS ACTUAL LOAD THAT INTERIOR
COLUMN HAS TO CARRY FROM 1200 LBS PER PALLET. (SEE NOTE AT BOTTOM OF PAGE 22.1 AND 22.2)
PLEASE FEEL FREE TO CALL WITH ANY QUESTIONS YOU MAY HAVE REGARDING THE ABOVE MATTERS.
SINCERELY,
~
DANNY PHI
o6 L5 312.5
Structural
Concepts
Engineering
1615 Yeager Ave
La Verne, Ca. 91750
Tel: 909-596-1351 Fax: 909-596-7186
Project Name : NORDSON ASYMTEK
Project Number : P-081115-2LV
Date : 09/02/15
Street Address : 2765 LOCKER AVE. WEST
City I State : CARLSBAD CA 92010
Scope of Work : STORAGE RACK
OCT 2 8 2015
Str~tural
\.,oncepts
~ Engineering ~ 1200 N, Jefferson Ste, Ste E Anaheim CA 92807 Tel· 714,632.7330 fax: 714 632,7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
TABLE OF CONTENTS
Title Page ............................................................................................................. .
Table of Contents .................................................................................................. .
Design Data and Definition of Components ......................................................... .
Critical Configuration ............................................................................................ .
Seismic Loads ...................................................................................................... .
Column ................................................................................................................. .
Beam and Connector ........................................................................................... .
Bracing ................................................................................................................. .
Anchors ................................................................................................................ .
Base Plate ............................................................................................................ .
Slab on Grade ...................................................................................................... .
Other Configurations ............................................................................................ .
NORDSON ASYMTEK TYPE A Page :J... of 3 ,Z
1
2
3
4
5 to 6
7
8 to 9
10
11
12
13
14to '30
8/17/2015
Str~tural
\.,oncepts
~ Engineering ~ 1200 N. Jefferson Ste Ste E Anaheim, CA 92807 Tel; 714,632,7330 fax: 714,632,7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Design Data
1) The analyses herein conforms to the requirements of the:
2012 /BC Section 2209
2013 CBC Section 2209A
ANSI MH 16.1-2012 Specifications for the Design of Industrial Steel Storage Racks '2012 RMI Rack Design Manual"
ASCE 7-10, section 15.5.3
2) Transverse braced frame steel conforms to ASTM A570, Gr.55, with minimum strength, Fy=55 ksi
Longitudinal frame beam and connector steel conforms to ASTM A570, Gr.55, with minimum yield, Fy=55 ksi
All other steel conforms to ASTM A36, Gr. 36 with minimum yield, Fy= 36 ksi
3) Anchor bolts shall be provided by installer per ICC reference on pfans and calculations herein.
4) All welds shall conform to AWS procedures, utilizing E70xx electrodes or similar. All such welds shall be performed
in shop, with no field welding allowed other than those supervised by a licensed deputy inspector.
5) The existing slab on grade is 611 thick with minimum 2500 psi compressive strength. Allowable Soil bearing capacity is 1000 psf.
The design of the existing slab is by others.
6) Load combinations for rack components correspond to 2012 RMI Section 2.1 for ASD level load criteria
Definition of Components
Frame
Height
: Product
A
Beam
Spacing
Column
Beam to Column
Connector
f:::ii:§§§~§§§§§li1=1====::!::t ====:::li:
Base Plate and
Anchors
Beam
Length
Front View: Down Aisle
(Longitudinal) Frame
NORDSON ASYMTEK TYPE A Page j of 3,,,2,
L Frame.J I~-Deoth 7
Section A: Cross Aisle
(Transverse ) Frame
Horizontal
Brace
Diagonal
Brace
8/17/2015
Str~tural
\.,oncepts
~ Engineering ~ 1200 N. Jefferson Ste. Ste E Anaheim CA 92807 TeJ· 714 632 7330 fax· 714 632 7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Configuration & Summary: TYPE A SELECTIVE RACK
T
48"
+ 60"
--t-
288" 60"
-t-
60"
--t-
60"
.I
,-r -96" --,r
Seismic Criteria # Bm Lvls
Ss=l.04, Fa=l.084 5
Component
Column Fy=55 ksi
Column & Backer None.
Beam Fy=55 ksi
Beam Connector Fy=55 ksi
Brace-Horizontal Fy=55 ksi
Brace-Diagonal Fy=55 ksi
Base Plate Fy=36 ksi
42" + 42" + IE-----!
288" 42" + >------
42" -+--
42" +->------
42" -+----I
_}-44" ,} _}-44" -+
**RACK COLUMN REACTIONS
ASDLOADS
AXIAL DL= 188 lb
AXIAL LL= 3,800 lb
SEISMIC AXl4L Ps=+/-5,439 lb
BASE MOMENT= 8,000 in-lb
Frame Depth Frame Height # Diagonals Beam Length Frame Type
44 in 288.0 in 7 96in Single Row
Description STRESS
Hannibal IF3013-3x3x13ga P=3988 lb, M=14316 in-lb 0.51-OK
None None N/A
HMH 41140/4.125" Face x 0.075" thk Lu=96 in I Capacity: 6175 lb/pr 0.26-OK
Lvl 1: 3 pin OK I Mconn=8982 in-lb I Mcap=15230 in-lb 0.59-OK
Hannibal 1-1/2xl-1/2x16ga 0.15-OK
Hannibal 1-1/2xl-1/2x16ga 0.17-OK
8x5x3/8 I Fixity= 8000 in-lb 0.75-OK
Anchor 2 per Base 0.5" x 3.25" Embed HILTI KWIKBOLTTZ ESR 1917 Inspection Reqd (Net Seismic Uplift=3390 lb) 0.808-OK
Slab &Soil 6" thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure 0.38-OK
Level I Load** I Story Force I Story Force Column I Column I Conn. Beam
Per Level Beam Spcg Brace Transv Long it. Axial Moment Moment Connector
1 1,600 lb 60.0 in 42.0 in 75Ib 57Ib 3,988 lb 14,316 11# 8,982 11# 3 pin OK
2 1,600 lb 60.0 in 42.0 in 150Ib 115Ib 3,150 lb 10,887 "# 7,181 "# 3 pin OK
3 1,600 lb 60.0 in 42.0 in 225Ib 172Ib 2,313 lb 9,170 11# 5,678 "# 3 pin OK
4 1,600 lb 60.0 in 42.0 in 300Ib 229Ib 1,475 lb 6,594 "# 3,353 "# 3 pin OK
5 1,200 lb 48.0 in 42.0 in 276Ib 211 lb 638Ib 2,527 "# 1,006 "# 3 pin OK
42.0 in
24.0 in
** Load defined as product weight per pair of beams Total: 1,027 lb 783Ib
NORDSON ASYMTEK TYPE A Page¼ of '3 ~ 8/17/2015
Str~tural
Voncepts
~ Engineering ~ 1200 N, Jefferson Ste, Ste E Anaheim, CA 92807 Tel; 714,632.7330 fax; 714,632.7763
By: DANNY PHI Project: NORDSON ASYMTEK
Seismic Forces Configuration: TYPE A SELECTIVE RACK
Lateral analysis is performed with regard to the requirements of the 2012 RMI ANSI MH 16.1-2012 Sec 2.6 & ASCE 7-10 sec 15.5.3
Transverse (Cross Aisle) Seismic Load 1· .. ,
V= Cs*Ip*Ws=Cs*Ip*(0.67*P*Prf+D) Vt
Csl= Sds/R "
= 0.1879 Cs-max* Ip= 0.1879 .....
Cs2= 0.044*Sds Vm1n= 0.015 ' ·
= 0.0331 Eff Base Shear=Cs= 0.1879 Transverse Elevation
Cs3= O.S*S1/R Ws= (0.67*PLRF1 * PL)+DL (RMI 2.6.2)
= 0.0505 .-----=_5._,4_67_1_b _______ ___,
Cs-max= 0.1879 Vtransv=Vt= 0.1879 * (375 lb+ 5092 lb)
Base Shear Coeff=Cs= 0.1879 Etransverse= 1,027 lb
limit States level Transverse seismic shear per upright
Level PRODUCT LOAD P P*0.67*PRF1 DL hi wi*hi
1 1,600 lb 1,072 lb 751b 60in 68,820
2 1,600 lb 1,072 lb ?Sib 120in 137,640
3 1,600 lb 1,072 lb 751b 180 in 206,460
4 1,600 lb 1,072 lb ?Sib 240in 275,280
5 1,200 lb 8041b 75 lb 288in 253,152
sum: P=7600 lb 5,092 lb 3751b W=5467 ib 941,352
LonQitudinal (Downaisle) Seismic Load
Project#: P-081115-2LV
Ss= 1.040
S1= 0.404
Fa= 1.084
Fv= 1.596
Sds=2/3*Ss*Fa= 0.752
Sd1=2/3*S1 *Fv= 0.430
Ca=0.4*2/3*Ss*Fa= 0.3006
(Transverse, Braced Frame Dir.) R= 4.0
Ip= 1.0
PRF1= 1.0
Pallet Height=hp= 48.0 in
DL per Beam Lvl= 75 lb
Fi Fi*(hi+hp/2)
75.1 lb 6,308-#
150.2 lb 21,629-#
225.2 lb 45,941-#
300.3 lb 79,279-#
276.2 lb 86,174-#
1,027 lb 1=239,332
Similarly for longitudinal seismic loads, using R=6.0 Ws= (0.67 * P~2 * P) + DL PRF2= 1.0 t-..."''''1 b,,,"-,J ~ (,,-...--.,9
Csl=Sdl/(T*R)= 0.1433
Cs2= 0.0331
Cs3= 0.0337
Cs-max= 0.1433
Level PRODUC LOAD P
1 1,600 lb
2 1,600 lb
3 1,600 lb
4 1,600 lb
5 1,200 lb
= 5,467 lb (Long,tudinal, Unbraced Dir.) R= 6.0
Cs=Cs-max*Ip= 0.1433 T= a.so sec I Vlong= 0.1433 * (375 lb + 5092 lb) I
Elongitudinal= 783 lb UmitStates Level LD"git. seismic shear per upright
P*0.67*PRF2
1,0721b
1,072 lb
1,072 lb
1,072 lb
8041b
DL
751b
751b
75 lb
75 lb
?Sib
hi wi*hi
60in 68,820
120 in 137,640
180 in 206,460
240in 275,280
288in 253,152
E'::~':'1 ~ ~~'i \~~~~
f~:-:';:J El f::-:~4 L~:~',;I
Fi Front View
57.2 lb
114.5 lb
171.7 lb
229.0 lb
210.6 lb
sum: ======5==09=2=1b=====3=7=5=1b===W===S=4=67=1=b=====94=1=3=5=2=======78=3=1b========
NORDSON ASYMTEK TYPE A Page")" of 3;:z_. 8/17/2015
StrJl.itural
\.,oncepts
~~~ Engineering .. ,r;:
--< 1200 N, Jefferson Ste, Ste E Anaheim, CA 92807 Tel: 714,632.7330 fax: 714,632 7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Downaisle Seismic Loads Configuration: TYPE A SELECTIVE RACK
Determine the story moments by applying portal analysis. The base plate is assumed to provide partial fixity.
Seismic Story Forces
Vlong= 783 lb
Vcol=Vlong/2= 392 lb
Fl= 57Ib
F2= 115 lb
F3= 172 lb
Seismic Story Moments Conceptual System
Typical Frame made , -~-o~~: columns
Mbase-max= 8,000 in-lb
Mbase-v= (Vcol*hleff)/2
<=== Default capacity hl-eff= hl -beam clip height/2
= 57 in
= 11,158 in-lb <=== Moment going to base
Mbase-eff= Minimum of Mbase-max and Mbase-v
= 8,000 in-lb
M 1-1= [Veal* hleff]-Mbase-eff
= (392 lb * 57 in)-8000 in-lb
= 14,316 in-lb
Mseis= (Mupper+Mlower)/2
Mseis(l-1)= (14316 in-lb+ 10887 in-lb)/2
= 12,601 in-lb
LEVEL hi Axial Load
1 60in 3,988 lb
2 60 in 3,150 lb
3 60 in 2,313 lb
4 60 in 1,475 lb
5 48 in 638Ib
M 2-2= [Vcol-(Fl)/2] * h2
= [392 lb -57.3 lb]*60 in/2
= 10,887 in-lb
Mseis(2-2)= (10887 in-lb+ 9170 in-lb)/2
= 10,028 in-lb
Summary of Forces
Column Moment** Mseismic** . Mend-fixity
14,316 in-lb 12,601 in-lb 230 in-lb
10,887 in-lb 10,028 in-lb 230 in-lb
9,170 in-lb 7,882 in-lb 230 in-lb
6,594 in-lb 4,561 in-lb 230 in-lb
2,527 in-lb 1,264 in-lb 173 in-lb
Mconn= (Mseismic + Mend-fixity)*0.70*rho
Mconn-allow(3 Pin)= 15,230 in-lb
**all moments based on limit states level loading
NORDSON ASYMTEK TYPE A Page b of 3Q_,.
h2
h1 h1eff II
Beam to Column
Elevation
rho= 1.0000
Mconn** Beam Connector
8,982 in-lb 3 pin OK
7,181 in-lb 3 pin OK
5,678 in-lb 3 pin OK
3,353 in-lb 3 pin OK
1,006 in-lb 3 pin OK
8/17/2015
COL
Str~tural
l,oncepts
~;:;? Engineering ~ 1200 N. Jefferson Ste. Ste E Anaheim. CA 92807 Ief: 714,632 7330 fax: 714,632 7763
By: DANNY PHI Project: NORDSON ASYMTEK
Column (Longitudinal Loads) Configuration: TYPE A SELECTIVE RACK
Section Properties
Section: Hannibal IF3013-3x3x13ga
Aeff = 0.757 in/\2
Ix = 1.320 in/\4
5x = 0.879 in/\3
rx = 1.320 in
Qf= 1.67
E= 29,500 ksi
Loads Considers loads at level 1
Iy = 0.871 in/\4
Sy= 0.574 in/\3
ry = 1.080 in
Fy= 55 ksi
Cmx= 0.85
COLUMN DL= 187 lb Critical load cases are: RMI Sec 2.1
Kx = 1.7
Lx = 57.9 in
Ky= 1.0
Ly= 42.0 in
Cb= 1.0
Project#: P-081115-2LV
r3-00:in7
1
y-·-·r·-·-y 3.000in
f0.090 in _J_
X:
'=3--0.75 in
COLUMN PL= 3,800 lb Load Case 5:: (1+0.105*Sds)D + 0.75*(1.4+0.14Sds}*B*P + 0.75*(0.7*rho*E)<= 1.0, ASD Method
Meo!= 14,315 in-lb axial load coeff: 0.7902426 * P seismic moment coeff: 0.5625 * Meo!
Sds= 0.7516 Load Case 6: : (1 +0.104*Sds)D + (0.85+0.14Sds)*B*P + (0.7*rho*E}<= 1.0, ASD Method
1 +0.105*Sds= 1.0789 axial load coeff: 0.66866 seismic moment coeff: 0.7 * Meo/
1.4+0.14Sds= 1.5052 By analysis, Load case 6 governs utilizing loads as such
Moment=Mx= 0.7*rho*Mcol
l+0.14Sds= 1.1052
0.85+0.14*Sds= 0.9552
B= 0.7000
rho= 1.0000
Axial Analysis
Axial Load=Pax= 1.105224*187 lb+ o.955224*0.7*3soo lb
= 2,748 lb = 0.1 * 14315 in-lb
= 10,021 in-lb
Kxl.x/rx = 1.7*57.9375"/1.3196"
= 74.6
Fe= nA2E/(KL/r)max/\2
= 52.3ksi
Pn= Aeff*Fn
= 30,681 lb
P/Pa= 0.17 > 0.15
Bending Analysis
KyLy/ry = 1 *42"/1.08"
= 38.9
Fy/2= 27.5 ksi
Qc= 1.92
Check: Pax/Pa+ (Cmx*Mx)/(Max*µx) ~ 1.0
P/Pao + Mx/Max ~ 1.0
Pno= Ae*Fy
= 0.757 in/\2 *55000 psi
= 41,635Jb
Pao= Pno/Qc
= 416351b/1.92
= 21,685 lb
Fe> Fy/2
Fn= Fy(l-Fy/4Fe)
= 55 ksi*[l-55 ksi/(4*52.3 ksi)]
= 40.5 ksi
Pa= Pn/Qc
= 30681 lb/1.92
= 15,980 lb
Myield=My= Sx*Fy
= 0.879 in/\3 * 55000 psi
= 48,345 in-lb
Max= My/Qf Per= nA2EI/(KL)max/\2
= 48345 in-lb/1.67
= 28,949 in-lb
µx= {l/[1-(Qc*P/Pcr)]Y-1
= {1/[1-(1.92*2748 lb/39617 lb)]Y-1
= 0.87
Combined Stresses
= n/\2*29500 ksi/(l.7*57.9375 in)A2
= 39,617 lb
(2748 lb/15980 lb)+ (0.85*10021 in-lb)/(28949 in-lb*0.87) =
(2748 lb/21685 lb) + (10021 in-lb/28949 in-lb) =
0.51
0.47
< 1.0, OK
< 1.0, OK
(EQ C5-1)
(EQ C5-2)
** For companson, total column stress computed for load case Sis: 46.0% q loads 3204.679546 lb Axial and M= 7515 in-lb
NORDSON ASYMTEK TYPE A Page 1 of 3~ 8/17/2015
'St'Ctural
~~:ineering . ~ 1200 N. Jefferson Ste, Ste F Anaheim, CA 92807 Tel: 714.632.7330 Fax: 714.632.7763
By: DANNY PHI Project: NORDSON ASYMTEK
BEAM Contiguration: TYPE A SELECTIVE RACK
DETERMINE ALLOWABLE MOMENT CAPACITY
A) Check compression flange for local buckling (82.1)
w= c -2*t -2*r
= 1.75 in -2*0.075 in -2*0.075 in
= 1.450 in
w/t= 19.33
!=lambda= [1.052/(k)"0.5] * (w/t) * (Fy/E)"0.5
= [1.052/(4)"0.5] * 19.33 * (55/29500)"0.5
= 0.439 < 0.673, Flange is fully effective
B) check web for local buckling per section b2.3
fl(comp)= Fy*(y3/y2)= 49.12 ksi
f2(tension)= Fy*(y1/y2)= 100.88 ksi
Y= f2/fl
= -2.054
k= 4 + 2*(1-Y)"3 + 2*(1-Y)
= 67.08
flat depth=w= y1 +y3
Eq. B2.3-5
Eq. B2.3-4
Eq. B2.1-4
Eq. B2.1-1
= 3.825 in w/t= 51 OK
!=lambda= [1.052/(k)"0.5] * (w/t) * (f1/E)"0.5
= [1.052/(67.08)"0.5] * 3.825 * (49.12/29500)"0,5
= 0.267 < 0.673
be=w= 3.825 in
bl= be(3-Y)
= 0.757
b2= be/2
= 1.91 in
bi +b2= 2.667 in > 1.2525 in, Web is fully effective
Determine effect of cold working on steel yield point (Fya) per section A7.2
Fya= C*Fyc + (1-C)*Fy (EQ A7.2-1)
Lcorner=Lc= (p/2) * (r + t/2) ·
0.177 in C= 2*Lc/(Lf+2*Lc)
Lflange-top=Lf= 1.450 in = 0.196 in
Eq B2.3-2
Project#: P-os1115-2Lv
2.75 in
t5in 4
T
4,125 in
1.625 in
J_
0,075 in
Beam= HMH 41140/4 125" Face x 0 075" thk
Ix= 2.196 in"4
Sx= 1.021 in"3
Ycg= 2.723 in
t= 0.075 in
Bend Radius=r= 0.075 in
Fy=Fyv= 55.00 ksi
Fu=Fuv= 65.00 ksi
E= 29500 ksi
top flange=b= 1.750 in
bottom flange= 2.750 in
Web depth= 4 1,c: in ~ Fy -
m
m= 0.192*(Fu/Fy) -0.068 (EQ A7.2-4)
= 0.1590
Be= 3.69*(Fu/Fy) -0.819*(Fu/Fy)"2 -1.79
= 1.427
depth !
since fu/Fv= 1.18
and r/t= 1
then Fye= Be* Fy/(R/t)"m
= 78.485 ksi
< 1.2
< ?OK
(EQ A7.2-2)
Thus, Fya-top= 59.61 ksi (tension stress at top)
Fya-bottom= Fya*Ycg/(depth -Ycg)
= 115.71 ksi (tension stress at bottom)
Check allowable tension stress for bottom flange
Lflange-bot=Lfb= Lbottom -2*r*-2*t
= 2.450 in
Cbottom=Cb= 2*Lc/(Lfb+2*Lc)
= 0.126
Fy-bottom=Fyb= Cb*Fyc + (1-Cb)*Fyf
= 57.97 ksi
Fya= (Fya-top)*(Fyb/Fya-bottom)
= 29.86 ksi
(EQ A7.2-3)
if F= 0.95 Then F*Mn=F*Fya*Sx=I 28.96 in-k
Ycg y1
j_
y1= Ycg-t-r= 2.573 in
y2= depth-Ycg= 1.403 in
y3= y2-t-r= 1.253 in
·St,Ctu,a1 .
~~:gineering ~ 1200 N. Jefferson Ste, Ste F Anaheim, CA 92807 Tel: 714.632.7330 Fax: 714.632.7763
By: DANNY PHI Project: NORDSON ASYMTEK
BEAM Contiguration: TYPE A SELECTIVE RACK
RMI Section 5.2, PT II
Section
Beam= HMH 41140/4.125" Face x 0.075" thk
Ix=Ib= 2.196 in"4
Sx= 1.021 in"3
t= 0.075 in
Fy=Fyv= 55 ksi
Fu=Fuv= 65 ksi
Fya= 59.6 ksi
E= 29500 ksi
F= 50.0
L= 96in
Beam Level= 1
P=Product Load= 1,600 lb/pair
D=Dead Load= 75 lb/pair
1. Check Bending Stress Allowable Loads
Mcenter=F*Mn= W*L *W*Rm/8
W=LRFD Load Factor= 1.2*D + 1.4*P+l.4*(0.125)*P
FOR DL=2% of PL,
W= 1.599
Rm= 1 -[(2*F*L)/(6*E*Ib + 3*F*L)]
RMI 2.2, item 8
1 -(2*50*96 in)/[(6*29500 ksi*2.196 in"3)+(3*50*96 in)]
= 0.976
if F= 0.95
Then F*Mn=F*Fya*Sx= 57 .82 in-k
Thus, allowable load
per beam pair=W= F*Mn*8*(# of beams)/(L *Rm*W)
= 57.82 in-k * 8 * 2/(96in * 0.976 * 1.599)
= 6,175 lb/pair allowable load based on bending stress
Mend= W*L *(1-Rm)/8
= (6175 lb/2) * 96 in * (1-0.976)/8
= 0,889 in-lb @ 6175 lb max allowable load
= 0,230 in-lb @ 1600 lb imposed product load
2. Check Deflection Stress Allowable Loads
Dmax= Dss*Rd
Rd= 1-(4*F*L)/(5*F*L + 10*E*Ib)
= 1 -(4*50*96 in)/[(5*50*96 in)+(10*29500 ksi*2.196 in"4)]
= 0.971 in
if Dmax= L/180 Based on L/180 Deflection Criteria
and Dss= 5*W*L "3/(384*E*Ib)
L/180= 5*W*L "3*Rd/(384*E*Ib*# of beams)
solving for W yields,
W= 384*E*I*2/(180*5*L "2*Rd)
= 384*2.196 in"4*2/[180*5*(96 in)"2*0.971)
= 6,177 lb/pair allowable load based on deflection limits
Project#: P-os1115-2Lv
2.75in
V,5in f
T 1.625 in
4.125 in
l~ 0.075 in
0111111111111111111111111111111111111111100 ·~=::W;::=======::::;1ill= ---' ' :;-~-,----,...,-....,-~-.,.....,.....,....,,
Cl Id
..... ...... . . . . . . . . . . .
Beam
Length
Allowable Deflection= L/180
= 0.533 in
Deflection at imposed Load= 0.138 in
Id Cl
Thus, based on the least capacity of item 1 and 2 above: Allowable load= 6,175 lb/pair
Imposed Product Load= 1,600 lb/pair
Beam Stress= 0.26 Beam at Level 1
_c::;,1._, ,_,1., ·--·
c::
' . . nn1noort1nn 1200 N. Jefferson Ste, Ste F Anaheim, CA 92807 Tel: 714.632.7330 Fax: 714.632.7763
By: DANNY PHI Project: NORDSON ASYMTEK Project #: P-081115-2L V
3 Pin Beam to Column Connection TYPE A SELECTIVE RACK
I he beam end moments shown herein show the result of the maximum induced fixed end monents form se1sm1c + static loads and the code
mandated minimum value ot 1.5%(DL+PL)
Mconn max= (Mseismic + Mend-fixity}*0.70*Rho
= 8,982 in-lb Load at level 1
Connector Type= 3 Pin
Shear Capacity of Pin
Pin Diam= 0.44 in Fy= 55,000 psi
Ashear= (0.438 in)"2 * Pi/4
= 0.1507 in"2
Pshear= 0.4 * Fy * Ashear
= 0.4 * 55000 psi * 0.1507in"2
= 3,315 lb
Bearing Capacity of Pin
tcol= 0.090 in
Omega= 2.22
Fu= 65,000 psi
a= 2.22
Pbearing= alpha * Fu * diam * tcol/Omega
= 2.22 * 65000 psi * 0.438 in * 0.09 in/2.22
= 2,562 lb < 3315 lb
Moment Capacity of Bracket
Edge Distance=E= 1.00 in Pin Spacing= 2.0 in
C= P1+P2+P3 tclip= 0.18 in
= Pl +Pl *(2.5"/4.5")+Pl *(0.5"/4.5")
= 1.667 * Pl
Mcap= Sclip * Fbending
= 0.127 in"3 * 0.66 * Fy
= 4,610 in-lb
Pclip= Mcap/(1.667 * d)
C*d= Mcap = 1.667
= 4610.1 in-lb/(1.667 * 0.5 in)
= 5,531 lb
Thus, Pl= 2,562 lb
Mconn-allow= [P1 *4.5"+Pl *(2.5"/4.5")*2.S"+Pl *(0.5"/4.5")*0.5"]
= 2562 LB*[4.5"+(2.5"/4.5")*2.5"+ (0.5"/4.5")*0.5"]
= 15,230 in-lb > . Mconn max, OK
NORDSON ASYMTEK TYPE A Page 9 of '3~
Fy= 55,000 psi
Sclip= 0.127 in"3
d= E/2
= 0.50 in
rho= 1.0000
8/17/2015
Str~tural
l,oncepts
~ Engineering
~. 1200 N, Jefferson Ste, Ste E Anaheim, CA 92807 Tel; 714,632.7330 fax: 714.632,7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Transverse Brace Configuration: TYPE A SELECTIVE RACK
Section Properties
Diagonal Member= Hannibal 1-1/2x1-1/2x16ga Horizontal Member= Hannibal 1-1/2x1-1/2x16ga
Area= 0.273 inA2
r min= 0.496 in
Fy= 55,000 psi
K= 1.0
r 1.SOOin ~ Area= 0.273 inA2
r min= 0.496 in
Fy= 55,000 psi
K= 1.0
r-1.500 in -,
Qc= 1.92
[J}·;, [7}•;,
~ I=,.-0.25in ~ ~ 0.25in
Frame Dimensions
Diagonal Member
Bottom Panel Height=H= 42.0 in
Frame Depth=D= 44.0 in
Column Width=B= 3.0 in
Clear Depth=D-B*2= 38.0 in
X Brace= NO
rho= 1.00
..-o I Load Case 6: : a.±JJ..1()4£5,.,-."tl.."'"2,J_,.,tJ,...+-r-rl(r,;0".8.;;:'5:-;+0.;;.-;14.;,:Si:::'ds~;J~*B*P + [0.7*rho*E]<= 1.0, ASD Method
Vtransverse= 1,027 lb
Vb=Vtransv*0.7*rho= 1027 lb * 0,7 * 1
= 719Ib
Ldiag= [(D-B*2)A2 + (H-6")A2)A1/2
= 52.3 in
Pmax= V*(Ldiag/D) * 0.75
= 641Ib
(kl/r)= (k * Ldiag)/r min
= (1 x 52.3 in /0.496 in )
= 105.4 in
Fe= piA2*E/(kl/r)A2
= 26,208 psi
axial load on diagonal brace member Since Fe<Fy/2/
T
l==========l 1
Pn= AREA*Fn
= 0.273 in A 2 * 26208 psi
= 7,155_1b
Pallow= Pn/Q
= 7155 lb /1.92
= 3,726 lb
Pn/Pallow= 0.17
Horizontal brace
Vb=Vtransv*0.7*rho= 719 lb
(kl/r)= (k * Lhoriz)/r min
= (1 x 44 in) /0.496 in
= 88.7 in
Since Fe>Fy/2, Fn=Fy*(l-fy/4fe)
= 34,564 psi
Pn/Pallow= 0.15
NORDSON ASYMTEK TYPE A
<= 1.0 OK
<= 1.0 OK
Fn= Fe B ,jt
Fe= piA2*E/(kl/r)A2
= 37,006 psi
Pn= AREA*Fn
= 0.273inA 2*34564 psi
= 9,436 lb
= 26,208 psi
Check End Weld
Lweld= 2.5 in
Fu= 65 ksi
tmin= 0.060 in
Typical Panel
Configuration
Weld Capacity= 0.75 * tmin * L * Fu/2.5
= 2,925 lb OK
Fy/2= 27,500 psi
Pallow= Pn/Qc
= 9436 lb /1.92
= 4,915 lb
8/17/2015
St~tural
voncepts
~f? Engineering ~ 1200 N. Jefferson Ste, Ste E Anaheim, CA 92807 Tel; 714,632,7330 fax: 714.632.7763
By: DANNY PHI Project: NORDSON ASYMTEK
Single Row Frame Overturning Configuration: 1YPE A SELECTIVE RACK
Loads
Critical Load case(s):
1) RMI Sec 2.2, item 7: (0.9-0.2Sds)D + (0.9-0.20Sds)*B*Papp -E*rho
Vtrans=V=E=Qe= 1;027 lb
DEAD LOAD PER UPRIGHT=D= 375 lb
PRODUCT LOAD PER UPRIGHT=P= 7,600 lb
Papp=P*0.67= 5,092 lb
Wst LCl=Wstl=(0.74968*0 + 0.74968*Papp*1)= 4,098 lb
Product Load Top Level, ptop= 1,200 lb
DL/Lvl= 75 lb
Seismic Ovt based on E, L(Fi*hi)= 239,332 in-lb
heiqhtf depth ratio= 6.6 in
A) Fullv Loaded Rack
Load case 1:
Movt= L(Fi*hi)*E*rho
= 239,332 in-lb
Sds= 0.7516
(0.9-0.2Sds)= 0.7497
(0.9-0.2Sds)= 0.7497
B= 1.0000.
rho= 1.0000
Frame Depth=Df= 44.0 in
Htop-lvl=H= 288.0 in
# Levels= 5
# Anchors/Base= 2
hp= 48.0 in
h=H+ho/2= 312.0 in
Mst= Wst1 * Df/2
= 4098 lb * 44 in/2
= 90,156 in-lb
Project#: P-081115-2LV
SI EV ON DE EL ATI
T= (Movt-Mst)/Df
= (239332 in-lb -90156 in-lb)/44 in
= 3,390 lb Net Uplift per Column
I Net Seismic Uolift= 3,390 lb Strenoth Level
B) Too Level Loaded Onlv
Load case 1:
0 Vl=Vtop= Cs* Ip * ptop >= 350 lb for H/D >6.0 Movt= [Vi *h + V2 * H/2]*0.7*rho
= 0.1879 * 1200 lb = 83,543 in-lb
= 225 lb T = (Movt-Mst)/Df
Vleff= 350 lb Critical Level= 5 = (83543 in-lb -25976 in-lb)/44 in
V2=VoL= Cs*Ip*D Cs*Ip= 0.1879 = 1,308 lb Net Uplift per Column
= 701b
Mst= (0.74968*D + 0.74968*Ptop*1) * 44 in/2
= 25,976 in-lb
I Net Seismic Uolift= 1,308 lb Strenath Level
Anchor
Check (2) 0.5" x 3.25" Embed HIL TI KWIKBOLT TZ anchor(s) per base plate.
Special inspection is required per ESR 1917.
Fully Loaded:
Top Level Loaded:
Pullout Capacity=Tcap= 1,961 lb L.A. City Jurisdiction? NO
Shear capacity=Vcap= 2,517 lb Phi= 1
(1695 lb/1961 lb)Ai + (256 lb/2517 lb)Al =
(654 lb/1961 lb)"i + (87 lb/2517 lb)Al =
NORDSON ASYMTEK TYPE A Page\\ of 3~
0.97
0.37
Tcap*Phi= 1,961 lb
Vcap*Phi= 2,517 lb
<= 1.2 OK
<= 1.2 OK
8/17/2015
Str~tural
\.,oncepts
~'~ Engineering ~ 1200 N, Jefferson Ste Ste E Anaheim CA 92807 Tel: 714,632.7330 Fax· 714 632 7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Base Plate Configuration: TYPE A SELECTIVE RACK
Section
p ..-a-..
Mb
Baseplate= 8x5x3/8
Eff Width=W = 8.00 in
Eff Depth=D = 5.00 in
Column Width=b = 3.00 in
Column Depth=dc = 3.00 in.
a= 3.00 in
Anchor c.c. =2*a=d = 6.00 in
N=# Anchor/Base= 2
Fy = 36,000 psi I b 1--L
L = 2.50 in
Plate Thickness=t = 0.375 in
----w
Downaisle Elevation
Down Aisle Loads Load Case 5: : (1 +0.105*Sds)D + 0.75*[(1.4+0.14Sds)*B*P + 0.75*(0.7*rho*El<= 1.0, ASD Method
COLUMN DL= 188 lb Axial=P= 1.078918 * 187.5 lb+ 0.75 * (1.505224 * 0.7 * 3800 lb)
COLUMN PL= 3,800 lb = 3,205 lb
Base Moment= 8,000 in-lb Mb= Base Moment*0.75*0.7*rho
1+0.105*Sds= 1.0789 = 8000 in-lb* 0.75*0.7*rho
1.4+0.14Sds= 1.5052 .---------=_4 ___ ,_20_0_in_-l_b ______________ __,
B= 0.7000 Axial Load P = 3,205 lb Mbase=Mb = 4,200 in-lb
Ml= wLA2/2= fa*LA2/2 Axial stress=fa = P/A = P/(D*W)
= 80 psi
Moment Stress=fb = M/S = 6*Mb/[(D*B"2]
= 78.8 psi
Moment Stress=fbl = fb-fb2
= 29.5 psi
M3 = (1/2)*fb2*L *(2/3)*L = (1/3)*fb2*L" 2
= 103 in-lb
S-plate = (l)(t" 2)/6
= 0.023 in"3/in
fb/Fb = Mtotal/[ (S-plate )(Fb)]
= 0.70 OK
Tanchor = (Mb-(PLapp*0.75*0.46)(a))/[(d)*N/2]
= -1,349 lb No Tension
= 250 in-lb
Moment Stress=fb2 = 2 * fb * L/W
= 49.2 psi
M2= fbl *L A2)/2
= 92 in-lb
Mtotal = Ml +M2+M3
= 445 in-lb/in
Fb = 0.75*Fy
= 27,000 psi
F'p= 0.7*F'c
= 1,750 psi
Tallow= 1,961 lb
OK
OK
Cross Aisle Loads CnticalloadcaseRMISec2.1, 11em1:r1+0.11sr1sJoL +r1+0.11sosJPL•o.1s+a•o.1s<=1.o,AS0Method Check uplift load on Baseplate
EffE
Effe
Pstatic= 3,205 lb
Movt*0.75*0.7*rho= 125,649 in-lb
Frame Depth= 44.0 in
P=Pstatic+Pseismic= 6,061 lb
Pseismic= Movt/Frame Depth
= 2,856 lb
Check uplift forces on baseplate with 2 or more anchors per RMI 7 .2.2.
When the base plate configuration consists of two anchor bolts located on either side
f the column and a net uplift force exists, the minimum base plate thickness
hall be determined based on a design bending moment in the plate equal
o the uplift force on one anchor times 1/2 the distance from
he centerline of the anchor to the nearest edge of the rack column"
b =Column Depth= 3.00 in
L =Base Plate Depth-Col Depth= 2.50 in
fa = P/A = P/(D*W)
= 152 psi
Sbase/in = (l)(tA 2)/6
= 0.023 inA3/in
fb/Fb = M/[(S-plate)(Fb)]
= 0.75 OK
NORDSON ASYMTEK TYPE A
M= wLA2/2= fa*LA2/2.
= 474 in-lb/in
Fbase = 0.75*Fy
= 27,000 psi
Page \l of 3~
Uplift per Column= 3,390 lb
Qty Anchor per BP= 2
Net Tension per anchor= Ta= 1,695 lb
c= 2.50 in
Mu=Moment on Baseplate due to uplift= Ta*c/2
= 2,119 in-lb
Splate= 0.117 inA3
fb Fb *0.75= 0.502 OK
8/17/2015
Str~tural
l,oncepts
~:;j Engineering ~ 1200 N. Jefferson Ste. Ste E Anaheim, CA 92807 Tel: 714.632.7330 Fax: 714,632.7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Slab on Grade Configuration: TYPE A SELECTIVE RACK
a
.. ·.-:-:-:-:-:-:::::::::::::::::~~l~b·· .· .. . . . . . . . . . . . . . . . . . . . . :')·: -:·r··:::·.·.·.·.·.·.·.·.·.·.·.·.·.·.·.·.·.·.·.·.·.·.·:~:: .. . . . . . ... . . . . . . .. . . . . . . <> r--e-~---: > :-:-:· D :-, b e
<::::::::::: , : : Cross :-
·-:::::::: ~---·c ----' : Aisle ::
Concrete
rx-,,_,_/~_-1 -
.·:-:-:-!-:-: : . . ..... .
.·.·.·. .2.J·.·.·.·.··.· . . . . .... . . . . . . ~--------· ..... . . ·.·.~ .. ·r··.·.·.·.·.·.·.· .. ·.·.·.·.·.·.·.·.·.·-r-·.·.·.·.· ·. ·.·.·.·.·.·. ' ........ B ........ • ·.·.·.·.· . . . . . . . . . . . . . . . . ....... . . . . . . . . . . . . . . . . ............. .
· ·.: .. <::::::::::::::::::::::<<::Down Aisle : :::-·
fc= 2,500 psi
tslab=t= 6.0 in
teff= 6.0 in
phi=0:;= 0.6
Soil
fsoil= 1,000 psf
Movt= 167,532 in-lb
Frame depth= 44.0 in
. . . . . . . . ........ .
SLAB ELEVATION
Baseplate Plan View Sds= 0.752
0.2*Sds= 0.150 Base Plate
Effec. Baseplate wldth=B= 8.00 in
Effec. Baseplate Depth=D= 5.00 in
width=a= 3.00 in
depth=b= 3.00 in
· 'Jc= 0.600 ·
/3=8/D= 1.600
F'c"0.5= 50.00 psi
Column Loads
DEAD LOAD=D= 188 lb per column
unfactored ASD load
PRODUCT LOAD=P= 3,800 lb per column
unfactored ASD load
Papp= 2,546 lb per column
P-seismic=E= (Movt/Frame depth)
= 3,807 lb per column
unfactored Limit State load
B= 0.7000'
rho= LOOOO
Sds= 0.7516
1.2 + 0.2*Sds= 1.3503
0. 9 -0.20Sds= 0.7497
Puncture
Apunct= [(c+t)+(e+t)]*2*t
= 258.0 in"2
Fpunctl= [(4/3 + 8/(3*/3)] * 'J,., *(F'c"0.5)
= 90. psi
Fpunct2= 2.66 * 'A. * (F'c"0.5)
= 79.8 psi
Fpunct eff= 79.8 psi
Slab Bending
Pse=DL+PL+E= 7,833 lb
Asoil= (Pse*144)/(fsoil)
= 1,128 in.1\2
X= (L-y)/2
= 8.4 in
Fb= 5*(phi)*(fc)"0.5
= 150. psi
NORDSON ASYMTEK TYPE A
midway dist face of column to edge of plate=c= 5.50 in
midway dist face of column to edge of plate=e= 4.00 in
Load Case 1) (1.2+0.2Sds)D + (1.2+0.2Sds)*B*P+ rho*E RMI SEC 2.2 EQTN 5
= 1.35032 * 188 lb + 1.35032 * 0.7 * 3800 lb + 1 * 3807 lb
= 7,653 lb
Load case 2) (0.9-0.2Sds)D + (0.9-0.2Sds)*B*Papp + rho*E RMI SEC 2.2 EQTN 7
= 0.74968 * 188 lb + 0.74968 * 0.7 * 2546 lb + 1 * 3807 lb
= 5,284 lb
Load case 3) 1.2*D + 1.4*P RMI sEc 2.2 EQTN 1,2
= 1.2*188 lb + 1.4*3800 lb
= 5,545 lb
Load case 4) 1.2*D + 1.0*P + LOE •0J1a-11 s,c,.2.,,Eqtno-s
= 7,833 lb
Effective Column Load=Pu= 7,833 lb per column
L= (Asoil)"0.5
= 33.59 in
M= w*x"2/2
= (fsoil*x"2)/(144*2)
= 247.8 in-lb
Page \?J of 3 ~
fv/Fv= Pu/(Apunct*Fpunct)
= 0.380 < 1 OK
y= (c*e)"0.5 + 2*t
= 16.7 in
s-slab= 1 *teff" 2/6
= 6,0 inA3
fb/Fb= M/(S-slab*Fb)
= 0.275 < 1, OK
8117/2015
StrJitural
\.,oncepts
;ifii:?J Engineering ~ 1200 N. Jefferson Ste Ste E Anaheim. CA 92807 Tel· 714,632 7330 Fax; 714,632 7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Configuration & Summary: TYPE B SELECTIVE RACK
T
48"
+ 60"
-t-
2 88" 60"
-t-
60"
-t-
60"
,I
'
Seismic Criteria # Bm Lvls
$s=1.04, Fa=l.084 5
Component
Column Fy=55 ksi
Column & Backer None
Beam Fy=55 ksi
Beam Connector Fy=55 ksi
Brace-Horizontal Fy=55 ksi
Brace-Diagonal Fy=55 ksi
Base Plate Fy=36 ksi
Anchor 2 per Base
Slab & Soil
Level I Load**
Per Level Beam Spcg
1 8001b 60.0 in
2 8001b 60.0 in
3 8001b 60.0 in
4 8001b 60.0 in
5 6001b 48.0 in
** Load defined as product weight per pair of beams
NORDSON ASYMTEK TYPE B
288"
7"""
24" + _ __,
42" +--
42" +·---1
42" --+--
42" --+-
42" +--
42" ~ t"-----l
_}--44" ,} _}-44" -:f'
**RACK COLUMN REACT1ONS
ASDLOADS
AXIAL DL= 188 lb
AXIAL LL= 1,900 lb
SEISMIC AXIAL Ps=+/-2,.912 lb
BASE MOMENT= 8,000 in-lb
Frame Depth Frame Height # Diagonals Beam Length Frame Type
44 in 288.0 in 7 48in Single Row
Description STRESS
Hannibal IF3013-3x3x13ga P=2088 lb, M=5971 in-lb 0.21-OK
None None N/A
HMH 41140/4.125" Face x 0.075" thk Lu=48 in I Capacity: 12054 lb/pr 0.07-OK
Lvl 1: 3 pin OK I Mconn=4129 in-lb I Mcap=15230 in-lb 0.27-OK
Hannibal 1-1/2x1-1/2x16ga 0.08-OK
Hannibal 1-1/2x1-1/2x16ga 0.09-OK
8x5x3/8 I Fixity= 5971 in-lb 0.52-OK
0.5"' x 3.25" Embed HILTI KWIKBOLTTZ ESR 1917 Inspection Reqd (Net Seismic Uplift=1818 lb) 0.433-OK
6" thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure 0.2-OK I Story Force I Story Force Column I Column I Conn. Beam
Brace Transv Longit. Axial Moment Moment Connector
42.0 in 40 lb 31 lb 2,088 lb 5,971 "# 4,129 "# 3 pin OK
42.0 in 801b 61 lb 1,650 lb 5,828 "# 3,759 "# 3 pin OK
42.0 in 120 lb 91 lb 1,213 lb 4,913 "# 2,959 "# 3 pin OK
42.0 in 1601b 1221b 7751b 3,542 "# 1,719 "# 3 pin OK
42.0 in 1501b 1141b 3381b 1,370 "# 480 11# 3 pin OK
42.0 in
24.0 in
Total: 5491b 4191b
Pa(;le \4 of 3~ 8/17/2015
Strjil,itural
l,oncepts
~"-"=--_----.~ .. -A:~--=-: Engineering
~~-:->""-···.:u· 1200 N, Jefferson Ste Ste E Anaheim. CA 92807 Tel; 714 632 7330 fax· 714 632 7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2L V
Configuration & Summary: TYPE C INT SELECTIVE RACK
T
60"
+ 60" +-288" 48"
+-
60"
-t-
60"
. .I
' ,.-1"-r--195" -----.!,~
Seismic Criteria # Bm Lvls
Ss=1.04, Fa=i.084 5
Component
Column Fy=55 ksi
Column & Backer None
Beam Fy=55 ksi
Beam Connector Fy=55 ksi
Brace-Horizontal Fy=SS ksi
Brace-Diagonal Fy=SS ksi
Base Plate Fy=36 ksi
288"
42" + >-----a<
42" +---,
42" + ,________,,,
42" -+-l<c----l
42" -+-,__ _ __,,
42" +----l
.,r--44" -f ,-f-44" --t'
**RACK COLUMN REACTIONS
ASDLOADS
AXIAL DL= 188 lb
AXlAL LL= 3,500 lb
SHSMIC AXIAL Ps=+/-5,345 lb
BASE MOMENT= 8,000 in-lb
Frame Depth Frame Height # Diagonals Beam Length Frame Type
44 in 288.0 in 7 195in Single Row
Description STRESS
Hannibal IF3013-3x3x13ga P=3688 lb, M=12328 in-lb 0.44-OK
None None N/A
Struc C8x11.5 w/(0) front to back brace(s) Lu=146.3 in I Capacity: 4577 lb/pr 0.39-OK
Lvl 3: 4 pin OK I Mconn=5310 in-lb I Mcap=27197 in-lb 0.2-OK
Hannibal 1-1/2x1-1/2x16ga 0.14-OK
Hannibal 1-1/2x1 -1/2x16ga 0.16-OK
8x5x3/8 I Fixity= 8000 in-lb 0.71-OK
Anchor 2 per Base 0.5'' x 3.25" Embed HILTI KWIKBOLTTZ ESR 1917 Inspection Reqd (Net Seismic Uplift=3446 lb) 0.808-OK
Slab &Soil 6" thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure 0.36-OK
Level I Load** I Story Force I Story Force Column I Column I Conn. Beam
Per Level Beam Spcg Brace Transv Long it. Axial Moment Moment Connector
3 1,800 lb 48.0 in 42.0 in 208Ib 158Ib 2,813 lb 7,740 "# 5,310 "# 4 pin OK
4 1,800 lb 60.0 in 42.0 in 282Ib 215Ib 1,875 lb 7,299 "# 4,027 "# 4 pin OK
5 1,800 lb 60.0 in 42.0 in 356Ib 272Ib 938Ib 4,074 "# 1,472 "# 4 pin OK
42.0 in
24.0 in
** Load defined as product weight per pair of beams Total: 952Ib 726Ib
NORDSON ASYMTEK TYPE C INT Page \<of g ~ 8/17/2015
Str~tural
\.,oncepts
~~~ Engineering ~ 1200 N Jefferson Ste, Ste E Anaheim, CA 92807 Te(: 714 632 7330 fax: 714,632.7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Configuration & Summary: TYPE F SELECTIVE RACK
T
60"
168" + 168"
60"
~ ~ -
T
15" +.-
15" + 42" + 42" + 42" +
**RACK COLUMN REACTIONS
ASDLOADS
AXIAL DL= 75 lb
AXIAL LL= 2,800 lb
SEISMIC AXIAL Ps=+/-2,065 lb
BASE MOMENT= 8,000 in-lb
--1--106" ---,,r
Seismic Criteria # Bm Lvls
Ss=l.04, Fa=l.084 2
Component
Column Fy=55 ksi
Column & Backer None
Beam Fy=55 ksi
Beam Connector Fy=55 ksi
Brace-Horizontal Fy=55 ksi
Brace-Diagonal Fy=55 ksi
Base Plate Fy=36 ksi
Anchor 2 per Base
Slab & Soil
Level I Load**
Per Level Beam Spcg
1 2,800 lb 60.0 in
2 2,800 lb 60.0 in
** Load defined as product weight per pair of beams
NORDSON ASYMTEK TYPE F
Frame Depth Frame Height # Diagonals Beam Length Frame Type
44 in 168.0 in 5 106in Single Row
Description STRESS
Hannibal IF3014-3x3x14ga P=2875 lb, M=7966 in-lb 0.33-0K
None None N/A
HMH 44140/4.5" Face x 0.075" thk Lu=106 in I Capacity: 6257 lb/pr 0.45-0K
Lvl 1: 3 pin OK I Mconn=S018 in-lb I Mcap=12691 in-lb 0.4-0K
Hannibal 1-1/2x1-1/2x16ga 0.1-0K
Hannibal 1-1/2x1-1/2x16ga 0.12-0K
8x5x3/8 I Fixity= 7966 in-lb 0.59-0K
0.5" x 3.25" Embed HILTI KWIKBOLTTZ ESR 1917 Inspection Reqd (Net Seismic Uplift=602 lb) 0.192-0K
6" thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure
Brace
42.0 in
42.0 in
42.0 in
15.0 in
15.0 in
Total:
I Story Force I Story Force
Transv Long it.
2441b 1861b
4891b 373 lb
7331b 5591b
Pagel7 of 3:Z..
Column I Column I Conn.
Axial Moment Moment
2,875 lb 7,966 "# 5,018 "#
1,438 lb 5,591 "# 2,230 "#
0.22-0K
Beam
Connector
3 pin OK
3 pin OK
8117/2015
Str~tural
\.,oncepts
~.:;} Engineering ~ 1200 N Jefferson Ste. Ste E Anaheim, CA 92807 IeI; 714 632 7330 Fax· 714 632 7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2L V
Configuration & Summary: TYPE C EXT SELECTIVE RACK
T
60"
288" + 60"
t
168"
' J
' '
Seismic Criteria # Bm Lvls
Ss=1.04, Fa=l.084 3
Component
Column Fy=SS ksi
Column & Backer None
Beam Fy=SS ksi
Beam Connector Fy=55 ksi
Brace-Horizontal Fy=SS ksi
Brace-Diagonal Fy=55 ksi
Base Plate Fy=36 ksi
Anchor 2 per Base
Slab &Soil
Level j Load**
Per Level Beam Spcg
1 9001b 168.0 in
2 9001b 60.0 in
3 9001b 60.0 in
"""7"""
24" +-42" + 1-----al
42" + IE----l
288" 42" + 42" + IE----l
42" +-!-------at
42" ..d..:--l"-------l
_}-44" -f ,r'-44" ---f
Frame Depth Frame Height # Diagonals
44 in 288.0 in 7
Description
Hannibal IF3013-3x3x13ga
None
Struc C8x11.5 w/(0) front to back brace(s)
**RACK COLUMN REACTIONS
ASDLOADS
AXJAL DL= 113 lb
AXIAL LL= 1,350 lb
SEISMIC AXIAL Ps=+/-2,278 lb
BASE MOMENT= 8,000 in-lb
Beam Length Frame Type
195in Single Row
STRESS
P=1463 lb, M=l5862 in-lb 0.94-OK
None N/A
Lu=146.3 in I Capacity: 4552 lb/pr 0.20-OK
Lvl 1: 4 pin OK I Mconn=6727 in-lb I Mcap=27197 in-lb 0.25-0K
Hannibal l-1/2xl-1/2x16ga 0.05-OK
Hannibal 1-1/2xl-1/2xl6ga 6.06-OK
8x5x3/8 I Fixity= 8000 in-lb 0.45-OK
0.5'' x 3.25" Embed HILTI KWIKBOLT TZ ESR 1917 Inspection Reqd (Net Seismic Uplift=1516 lb) 0.35-OK
6" thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure 0.15-OK
j Story Force j Story Force Column I Column I Conn. Beam
Brace Transv Longit. Axial Moment Moment Connector
42.0 in 941b 721b 1,463 lb 15,862 "# 6,727 "# 4 pin OK
42.0 in 1271b 971b 9751b 3,293 "# 1,819 "# 4 pin OK
42.0 in 161 lb 123 lb 4881b 1,838 "# 666 "# 4 pin OK
42.0 in
42.0 in
42.0 in
24.0 in
** Load defined as product weight per pair of beams Total: 3821b 291 lb I Notes I LOADS SHOW 1800 LBS PER LEVEL
NORDSON ASYMTEK TYPE C EXT Page lG of ~ '2.. 1018/2015
Str~tural
\.,oncepts
~ Engineering . ~ 1200 N, Jefferson Ste, Ste E Anaherm, CA 92807 Tel· 714,632.7330 fax: 714.632 7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Configuration & Summary: TYPE G SELECTIVE RACK
T
64"
t
2 88" 64"
-t-288"
64"
+
90"
.I
----')s,->--------,<
24" +---,
42" +----42" +--42" +---42" +--42" 4-,_____,.
42"
~ i<-----l
**RACK COLUMN REACTIONS
ASDLOADS
AXIAL DL= 150 lb
AXIAL LL= 3,200 lb
SEISMIC AXIAL Ps=+/-4,712 lb
BASE MOMENT= 8,000 in-lb
,.-e--(--106" --,,r ,f-44" -;;f
Seismic Criteria # Bm Lvls Frame Depth Frame Height # Diagonals Beam Length Frame Type
Ss=l.04, Fa=l.084 4 44 in 288.0 in 7 106in Single Row
Component Description STRESS
Column Fy=55 ksi Hannibal IF3013-3x3x13ga P=3350 lb, M=20580 in-lb 0.83-OK
Column & Backer None None None N/A
Beam Fy=55 ksi HMH 44140/4.5" Face x 0.075" thk Lu=106 in I Capacity: 6257 lb/pr 0.26-OK
Beam Connector Fy=55 ksi Lvl 1: 3 pin OK I Mconn=10593 in-lb I Mcap=15230 in-lb 0.7-OK
Brace-Horizontal Fy=55 ksi Hannibal 1-1/2x1-1/2x16ga 0.12-OK
Brace-Diagonal Fy=55 ksi Hannibal 1-1/2x1-1/2x16ga 0.14-OK
Base Plate Fy=36 ksi 8x5x3/8 I Fixity= 8000 in-lb 0.64-OK
Anchor 2 per Base 0.5" x 3.25" Embed HILTI KWIKBOLT TZ ESR 1917 Inspection Reqd (Net Seismic Uplift=2992 lb) 0.708-OK
Slab &Soil 611 thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure 0.32-0K
Level I Load** I Story Force I Story Force Column I Column I Conn. Beam
Per Level Beam Spcg Brace Transv Long it. Axial Moment Moment Connector
1 1,600 lb 90.0 in 42.0 in 1041b 801b 3,350 lb 20,580 "# 10,593 "# 3 pin OK
2 1,600 lb 64.0 in 42.0 in 1781b 1361b 2,513 lb 9,240 "# 5,863 "# 3 pin OK
3 1,600 lb 64.0 in 42.0in 253 lb 193 lb 1,675 lb 7,064 "# 4,023 "# 3 pin OK
4 1,600 lb 64.0 in 42.0 in 3271b 249 lb 8381b 3,984 "# 1,551 "# 3 pin OK
42.0 in
42.0 in
24.0 in
** Load defined as product weight per pair of beams Total: 8621b 65716
NORDSON ASYMTEK TYPE G Page\g of 3 ~ 8/17/2015
Str~tural
\.,oncepts
~ Engineering ~ 1200 N Jefferson Ste Ste E Anaheim, CA 92807 Tel; 714,632,7330 Fax· 714 632,7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Configuration & Summary: TYPE J SELECTIVE RACK
' T
64"
192" + 192"
90"
' ' -
r
12" + 42" + 42" + 42" + 42" +-
**RACK COLUMN REACTIONS
ASDLOADS
AXl4L DL= 75 lb
AXl4L LL= 2,000 lb
SEISMIC AXl4L Ps=+/-1,903 lb
BASE MOMENT= 8,000 in-lb
~-r--106" ---_,r
Seismic Criteria # Bm Lvls
Ss=l.04, Fa=l.084 2
Component
Column Fy=55 ksi
Column & Backer None
Beam Fy=55 ksi
Beam Connector Fy=55 ksi
Brace-Horizontal Fy=SS ksi
Brace-Diagonal Fy=55 ksi
Base Plate Fy=36 ksi
Anchor 2 per Base
Slab &Soil
Level I Load**
Per Level Beam Spcg
1 2,000 lb 90.0 in
2 2,000 lb 64.0 in
** Load defined as product weight per pair of beams
NORDSON ASYMTEK TYPE J
Frame Depth Frame Height # Diagonals Beam Length Frame Type
44 in 192.0 in 5 106in Single Row
Description STRESS
Hannibal IF3014°3x3x14ga P=2075 lb, M=9661 in-lb 0.47-OK
None None N/A
HMH 44140/4.5" Face x 0.075" thk Lu=106 in I Capacity: 6257 lb/pr 0.32-OK
Lvl 1: 3 pin OK I Mconn=5011 in-lb I Mcap=12691 in-lb 0.39-OK
Hannibal 1-1/2x1-1/2x16ga 0.08-OK
Hannibal 1-1/2xl -1/2x16ga 0.09-OK
8x5x3/8 I Fixity= 8000 in-lb 0.51-OK
0.5'' x 3.25" Embed HILTI KWIKBOLT1Z ESR 1917 Inspection Reqd (Net Seismic Uplift=842 lb) 0.225-OK
6" thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure
Brace
42.0 in
42.0 in
42.0 in
42.0 in
12.0 in
Total:
I Story Force I Story Force
Transv Long it.
1961b 1501b
3361b 2561b
5321b 4061b
Column I Column I Conn.
Axial Moment Moment
2,075 lb 9,661 "# 5,011 "#
1,038 lb 4,099 "# 1,629 "#
0.18-OK
Beam
Connector
3 pin OK
3 pin OK
8/17/2015
Str~tural
voncepts
~-& Engineering ~ 1200 N Jefferson Ste Ste E Anaheim CA 92807 Tel· 714,632 7330 Fax· 714 632 7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Configuration & Summary: TYPE K SELECTIVE RACK
-T
64"
192" + 90"
-----1---144"
Seismic Criteria # Bm Lvls
Ss=l.04, Fa=l.084 2
Component
Column Fy=55 ksi
Column & Backer None
Beam Fy=55 ksi
Beam Connector Fy=55 ksi
Brace-Horizontal Fy=55 ksi
Brace-Diagonal Fy=SS ksi
Base Plate Fy=36 ksi
Anchor 2 per Base
Slab &Soil
Level I Load**
Per Level Beam Spcg
1 2,400 lb 90.0 in
2 2,400 lb 64.0 in
** Load defined as product weight per pair of beams
NORDSON ASYMTEK TYPE K
T
12" + 42"
192" + 42" + 42" + 42" +
--f-44" --,,.j,-
Frame Depth Frame Height # Diagonals
44 in 192.0 in 5
Description
Hannibal IF3014-3x3x14ga
None
HMH 44140/4.5" Face x 0.075" thk
**RACK COLUMN REACTIONS
ASDLOADS
AXIAL DL= 75 lb
AXIAL LL= 2,400 lb
SEISMIC AXIAL Ps=+/-2,260 lb
BASE MOMENT= 8,000 in-lb
Beam Length Frame Type
144in Single Row
STRESS
P=2475 lb, M=12967 in-lb 0.62-OK
None N/A
Lu=144 in I Capacity: 3649 lb/pr 0.66-OK
Lvl 1: 3 pin OK I Mconn=7436 in-lb I Mcap=12691 in-lb 0.59-OK
Hannibal 1-1/2x1-1/2x16ga 0.09-OK
Hannibal 1-1/2x1-1/2x16ga 0.11-OK
8x5x3/8 I Fixity= 8000 in-lb 0.55-OK
0.5" x 3.25" Embed HILTI KWIKBOLTTZ ESR 1917 Inspection Reqd (Net Seismic Uplift=998 lb) 0.267-OK
6" thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure
Brace
42.0 in
42.0 in
42.0 in
42.0 in
12.0 in
Total:
I Story Force j Story Force
Transv Long it.
2331b 178 lb
3991b 3041b
6321b 4821b
Page J..-Oof 3 ~
Column I Column j Conn.
Axial Moment Moment
2,475 lb 12,967 "# 7,436 "#
1,238 lb 4,867 "# 2,898 "#
0.21-OK
Beam
Connector
3 pin OK
3 pin OK
8/17/2015
Strjil.itural
l,oncepts
~ Engineering ~ 1200 N Jefferson Ste Ste E Anaheim, CA 92807 Te(· 714 632 7330 fax· 714 632 7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Configuration & Summary: TYPE CARTON FLOW SELECTIVE RACK
...:, r 22"...,, r 22"...,,, r 22" _,,,
22".., '°
22"...,, '°
~
24" + -
42" I~
-->I..-" 42" /
2
22"...,, is-
88" 22"...,, r DECK 6" ...:, r 26"...,,, ,:-22"
'°
2
·-/ -"k-88" 42" " .. "---+ / 42" + /
22"...,,
22" __,, ,:-
,:-
22"...,, r 6" '
42" "---+ '
42" /
...,,I,_-,,
{'--96" ----,r .,f-44" -;;j,
DECK , ..._
/
**RACK COLUMN REACTIONS
ASDLOADS
AXIAL DL= 525 lb
AXIAL LL= 4,794 lb
SEISMIC AXIAL Ps=+/-fi666 lb
BASE MOMENT= 8,000 in-lb
Seismic Criteria # Bm Lvls Frame Depth Frame Height # Diagonals Beam Length Frame Type
Ss=l.04, Fa=l.084 14 44 in 288.0 in 7 96 in Single Row
Component Description STRESS
Column Fy=55 ksi Hannibal IF3013-3x3x13ga P=4982 lb, M=5875 in-lb 0.31-OK
Column & Backer None None None N/A
Beam Fy=55 ksi HMH 44140/4.5" Face x 0.075" thk Lu=96 in I Capacity: 6894 lb/pr 0.09-OK
Beam Connector Fy=55 ksi Lvl 2: 3 pin OK I Mconn=4086 in-lb I Mcap=15230 in-lb 0.27-OK
Brace-Horizontal Fy=55 ksi Hannibal l-1/'2:x.l-l/2x16ga 0.2-OK
Brace-Diagonal Fy=55 ksi Hannibal l-1/2xl-l/2x16ga 0.24-OK
Base Plate Fy=36 ksi 8x5x3/8 I Fixity= 803 in-lb 0.97-OK
Anchor 2 per Base 0.5" x 3.25" Embed HILTI KWIKBOLT TZ ESR 1917 Inspection Reqd (Net Seismic Uplift=3866 lb) 0.942-OK
Slab &Soil 611 thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure 0.49-OK
Level I Load** I Story Force I Story Force Column I Column I Conn. Beam
Per Level Beam Spcg Brace Transv Long it. Axial Moment Moment Connector
1 6001b 6.0 in 42.0 in 41b 31b 5,319 lb 804 "# 2,337 "# 3 pin OK
2 6001b 22.0 in 42.0 in 18 lb 141b 4,982 lb 5,875 "# 4,086 "# 3 pin OK
3 600 lb 22.0 in 42.0 in 321b 241b 4,644 lb 5,799 "# 4,012 "# 3 pin OK
4 600 lb 22.0 in 42.0 in 461b 351b 4,307 lb 5,665 "# 3,898 "# 3 pin OK
5 6001b 22.0 in 42.0 in 601b 461b 3,969 lb 5,472 "# 4,074 "# 3 pin OK
6 1,788 lb 26.0 in 42.0 in 205 lb 1561b 3,632 lb 6,169 "# 2,575 "# 3 pin OK
7 600 lb 6.0in 24.0 in 81 lb 621b 2,700 lb 1,189 "# 1,824 "# 3 pin OK
8 600 lb 22.0 in 95 lb 721b 2,363 lb 4,022 "# 2,676 "# 3 pin OK
9 6001b 22.0 in 1091b 831b 2,025 lb 3,625 "# 2,377 "# 3 pin OK
10 600 lb 22.0 in 123 lb 941b 1,688 lb 3,168 "# 2,037 "# 3 pin OK
11 600 lb 22.0 in 1371b 1051b 1,350 lb 2,653 "# 1,656 "# 3 pin OK
12 6001b 22.0 in 151 lb 115 lb 1,013 lb 2,078 "# 1,233 "# 3 pin OK
13 600 lb 22.0 in 165 lb 1261b 6751b 1,444 "# 769 "# 3 pin OK
14 600 lb 22.0 in 1791b 137 lb 338 lb 752 "# 263 "# 3 pin OK
** Load defined as product weight per pair of beams Total: 1,404 lb 1,071 lb
Notes !LEVEL 6 SUPPORT 125 PSF LIVE LOAD, 10 PSF DEAD LOAD DECK (37" WIDE AISLE)
NORDSON ASYMTEK TYPE CARTON FLOW P~geJ.l.\ of) 1.. 10/8/2015
·SC:ru,.,,1
~~:ineerinq ~ 1200 N. Jefferson Ste, Ste F Anaheim, CA 92807 Tel: 714.632.7330 Fax: 714.632.7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Beam
The beam to column connection is assumed to provide partial end fixity for the beam frame. The end moment calculated herein is added
to the lateral force force portal moment when analyzing the connection capacity.
Section Properties 96" DOWN AISLE DECK BEAM TYPICAL.
Loads
Bendin
Deflection
Beam Member= HMH 44140/4.5" deep x 0.075" thk
Beam at Level= 1
Beam Type= Step
Beam Weight= 4.0 lb/ft
Thickness= 0.075 in
t-1.750i{
1.625 in Ix= 2.720 in"4
Sx= 1.168 in"3
Length=L= 96.0 in
Lu= 96.0 in
Fy= 55,000 psi
Deft Criteria -L/ 240
Impact Factor (a)=(l-25%/2)= 1.000 T J_
% End Fixity= 15 %
Dist Load=w= 17.4 lb/in
Mcenter= B*(wl "2/8)
= 0.904*(wl" 2/8)
Mends= 0*Mmax(fixed ends)
= (wL "2/12)*0.15
= 0.0125*wL" 2
Fb= 0.6 * Fy
= 33,000 psi
Fb-eff= 33,000 psi
Mcenter= 0.113 * wL"2
= 18,120 in-lb
M= 18,120 in-lb
fb= (M/Sx)/a
= 15,514 psi
Deft-allow= L/240
= 0.400 in
4.500 in
LL= 125 psf
DL= 10 psf
Trib width= 1.550 ft
ltz:::z::==::z::;J0.075in
0 = 0.15
Coeff B= 0.113/0.125
= 0.904
Mcenter= Mcenter(simple ends) -0*Mcenter(fixed ends)
= wL "2/8 -(0.15 * wL "2/12)
= wL" 2/8 -wL" 2/80
= 0.113 * wL"2
Mends= 0.0125*wL"2
= 2,004 in-lb
fb/Fb= 15514 psi/33000 psi
= 0.47
Deft= B * [5wL "4/(384*E*Ix)]
<= 1.0, OK
= [5*17.4 lb/in*(96 in)"4/(384*29.Sx10"6 psi * 2.72 in"4)]*0.904
0.217 in <= 0.4 in, OK
bending= 0.47
clefl= 0.54
Pagel_\. l. of 3 ~
Str~tural
\.,oncepts
-:-; -Engineering
1200 N. Jefferson Ste Ste E Anaheim CA 92807 Tel· 714 632 7330 fax· 714 632,7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Configuration & Summary: PUSHBACK EXT RACK
~1.
\()\-;
,-Ge>" t,1========11
\CC
J
**RACK COLUMN REACTIONS
ASDLOADS
AXIAL DL= 75 lb
AXIAL LL= 1,050 lb
SEISMIC AXIAL Ps=+/-1,399 lb
BASE MOMENT= 8,000 in-lb
Seismic Criteria # Bm Lvls Frame Depth Frame Height # Diagonals Beam Length Frame Type
Ss=l.04, Fa=l.084 2 42 in 260.0 in 8 54in Single Row
Component Description STRESS
Column Fy=SS ksi EAB 3.54x2.36x0.088 P=1125 lb, M=5743 in-lb 0.33-OK
Column & Backer None None None N/A
Beam Fy=SS ksi EAB 2.36"x2.36"x0.118 " tube Lu=54 in I Capacity: 7379 lb/pr 0.14-OK
Beam Connector Fy=SS ksi Lvl 1: 3 pin OK I Mconn=3476 in-lb I Mcap=14891 in-lb 0.23-OK
Brace-Horizontal Fy=SS ksi 1.18x0.984x0.05 Tube 0.08-OK
Brace-Diagonal Fy=SS ksi 1.18x0.984x0.05 Tube 0.07-OK
Base Plate Fy=36 ksi 8x5x3/8 I Fixity= 5742 in-lb 0.34-OK
Anchor 2 per Base 0.5" x 3.25" Embed HILTI KWIKBOLTTZ ESR 1917 Inspection Reqd (Net Seismic Uplift=816 lb) 0.2-OK
Slab &Soil 6" thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure 0.11-OK
Level I Load** I Story Force I Story Force Column I Column I Conn. Beam
Per Level Beam Spcg Brace Transv Long it. Axial Moment Moment Connector
1 1,050 lb 106.0 in 30.0 in 981b 741b 1,125 lb 5,743 "# 3,476 11# 3-iu1OK
2 1,050 lb 106.0 in 30.0 in
30.0 in
30.0 in
30.0 in
30.0 in
30.0 in
30.0 in
1951b 1491b 563 lb 3,941 "# 1,466 "# 3·-M,OK
** Load defined as product weight per pair of beams Total: 293 lb 2231b
Notes !LOADS SHOW 1200 LBS PER PALLET (1-WIDE x 7-DEEP)
NORDSON ASYMTEK PUSHBACK EXT Page22J of ~ 2 9/1/2015
StrJ'itural
l,oncepts
~'.~ Engineering ~ 1200 N, Jefferson Ste, Ste E Anaheim, CA 92807 Tel· 714 632 7330 fax: 714,632.7763
By: DANNY PHI Project: NORDSON ASYMTEK Project#: P-081115-2LV
Configuration & Summary: PUSHBACK INT RACK
T
"''-" \vv
JJ,o" tll=======ll
\o,u
_I
,f--54"---{ {-42"r-42" f-42",r42" r--42"-f42" h211 f-42"-t
**RACK COLUMN REACTIONS
ASDLOADS
AXIAL DL= 75 lb
AXIAL LL= 2,100 lb
SEISMIC AXIAL Ps=+/-2,661 lb
BASE MOMENT= 8,000 in-lb
Seismic Criteria # Bm Lvls Frame Depth Frame Height # Diagonals Beam Length Frame Type
Ss=l.04, Fa=l.084 2 42 in 260.0 in 8 54in Single Row
Component Description STRESS
Column Fy=SS ksi EAB 3.54x2.36x0.088 P=2175 lb, M=13888 in-lb 0.79-0K
Column & Backer None None None N/A
Beam Fy=SS ksi EAB 2.36"x2.36"x0.118 " tube Lu=54 in I Capacity: 7379 lb/pr 0.28-0K
Beam Connector Fy=SS ksi Lvl 1: 3 pin OK I Mconn=7662 in-lb I Mcap=14891 in-lb 0.51-0K
Brace-Horizontal Fy=SS ksi 1.18x0.984x0.05 Tube 0.16-0K
Brace-Diagonal Fy=SS ksi 1.18x0.984x0.05 Tube 0.14-0K
Base Plate Fy=36 ksi 8x5x3/8 I Fixity= 8000 in-lb 0.42-0K
Anchor 2 per Base 0.5'' x 3.25" Embed HILTI KWIKBOLTTZ ESR 1917 Inspection Reqd (Net Seismic Uplift=1550 lb) 0.375-0K
Slab &Soil 6" thk x 2500 psi slab on grade. 1000 psf Soil Bearing Pressure 0.21-0K
Level I Load** I Story Force I Story Force Column I Column I Conn. Beam
Per Level Beam Spcg Brace Transv Long it. Axial Moment Moment Connector
1 2,100 lb 106.0 in 30.0 in 186Ib 142Ib 2,175 lb 13,888 "# 7,662 "# 3rci!, OK
2 2,100 lb 106.0 in 30.0 in 371 lb 283Ib 1,088 lb 7,507 "# 2,801 "# 3 tv~K
30.0 in
30.0 in
30.0 in
30.0 in
30.0 in
30.0 in
** Load defined as product weight per pair of beams Total: 557 lb 425Ib
Notes !LOADS SHOW 1200 LBS PER PALLET (1-WIDE x 7-DEEP)
NORDSON ASYMTEK PUSHBACK INT Page12 .2of ?, "L 9/1/2015
Str~tural
UonEts ~ ngineering ~ 1200 N. Jefferson Ste, Ste F Anaheim, CA 92807 Tel: 714.632.7330 Fax: 714.632.7763
Light Duty Shelving Analysis
St'}Litural
\.,onfWlts ;ffif Cngineering
1200 N, Jefferson Ste, Ste E Anaheim, CA 92807 Ter: 714 632,7330 fax: 714,632.7763
By: S.P. Project: NORDSON ASYMTEK Project#: P-081115-2
Design Data Configuration: Rivetier II Shelving : 216 in x 36 in x 18 in
1) The analyses of the light duty storage fixtures conforms to the requirements of the 2012 IBC, 2013 and ASC 7-10
2) Steel minimum yield, Fy= 36 ksi unless otherwise noted on the plans or analysis herein.
3) Anchor bolts shall be provided by installer per ICC reference on the calculations herein.
4) All welds shall conform to AWS procedures, utilizing E70xx electrodes or similar. All such welds shall be performed
in shop, with no field welding allowed other than those supervised by a licensed deputy inspector.
5) Slab on grade is 6 in thick concrete with f'c=2500 psi & 1000 psf allowable soil bearing pressure
NORD50N A5YMTEK-P-08 / I I 5-2-5HELVING Page 4 of 3 -2_, 8/19/2015
St~tural
vonjW>tS
;iiff Cngineering
·· · 1200 N. Jefferson Ste Ste E Anaheim CA 92807 TeJ; 714.§32.7330 fax; 714.§32.77§3
By: S.P. Project: NORDSON ASYMTEK Project#: P-081115-2
Summary of Results Configuration: Rivetier II Shelving : 216 in x 36 in x 18 in
_r-36 5/167
Shelf Configuration
Seismic Coeff: Ss= 1.040 D'.P, F[lQ!!II S1= 0.404 El.EYAI!Q!i
Fa= 1.084
Fv= 1.596
Steel Fy= 36,000 psi
Column
Beam
Beam Rivet
12
TYP
15
TYP
I 78 5/16
~
illY8I!Q!i
Component Summary
WPSS LURHD Ll-7 /8"x14ga
WPSS SS Double Rivet Beam
1/4" Diam Rivetx 1-1/2" Spacing
I# of Levels= 17
D= 18.0 in
H= 216.0 in
L= 36.0 in
Location Elevation
hl= 3.0 in
h2= 15.0 in
h3= 15.0 in
h4= 15.0 in
h5= 15.0 in
h6= 15.0 in
h7= 15.0 in
h8= 15.0 in
h9= 14.0 in
hlO= 3.0 in
hll= 12.0 in
h12= 12.0 in
h13= 12.0 in
h14= 12.0 in
h15= 12.0 in
h16= 12.0 in
h17= 12.0 in
Total Height= 216.0 in
Anchor** (2) 3 /8" x 2" Embed Hilti Kwikbolt TZ per post (ICC ESR 1917) Inspection Required. Net Uplift=1015 lb
Base Plate
Slab on Grade
Notes
5-3/4 x 3-5/8 x 10 ga RDSFP@T Post, 3-1/2 x 3-5/8 x 10 ga RSSFP@ L Post
6 in thick concrete with f'c=2500 psi & 1000 psf allowable soil bearing pressure
Column Reactions {ASD):
Axial column DL= 51 lb
Axial column LL= 980 lb
Axial column seismic load=+/-1,015 lb
NORD5ON ASYMTEK-P-O81 I I 5-2-5HELVING
Load
1001b
1001b
1001b
1001b
1001b
1001b
1001b
1001b
3601b
1001b
1001b
1001b
1001b
1001b
1001b
1001b
1001b
0.55 OK
0.37 OK
0.47 OK
0.89 OK
0.07 OK
0.15 OK
8/19/2015
St~tural
\.,on~ts ~ ngin~!~i~~efferson ste, ste E Anaheim, CA 92so1 JeJ: 714,632 7330 fax: 714,632,ZZ63
By: S.P. Project: NORDSON ASYMTEK Project#: P-081115-2
Seismic Forces Configuration: Rivetier II Shelving : 216 in x 36 in x 18 in
Vl= S05 *W/R
V2= [0.4*ap*S05*Ws*(1+2*z/h)/(Rp/Ip )]
V3= 0.044*Sds
V4= 0.S*S1/R
Vl= 0.1879
V2= 0.1879
V3= 0.0331
V4= 0.0000
Vminimum= 0.015
Seismic Coeff=Cs= 0.1879
(Either Direction)
Cs*Ip= 0.1879
Down Aisle Seismic Shear (Longitudinal)
Wlong= Z:(LL *0.67 +DL)
i.
hb ! ,
M l.
7
7
Deck DL= 10 psf
Deck LL= 60 psf
Ss= 1.04
Sl= 0.40
Fa= 1.08
V
Trib Area=A= 9.0 ft"2
Deck level LL= 270 lb
Deck level DL= 90 lb
Fv= 1.60
Sds= 0.752
Sdl= 0.430
Elevation
Cross Aisle Seismic Shear (Transverse)
Wtransv= Z:(LL*0.67+DL)
= 1,415 lb
R=Rp= 4.00
Ip= 1.00
ap= 2.5
z/h= 0.00
# of levels= 17
Depth= 18.0 in
Product LL/Shlf= 100 lb
DL/Shlf= 6 lb
= 1,415 lb
Vlong=VL= 0.1879 * 1415.2 lb
= 2661b
Vtransverse=VT= 0.1879 * 1415.2 lb
= 2661b
VJ2= 133 lb
Transverse Distribution
Level LL
1 1001b
2 100 lb
3 1001b
4 100 lb
5 1001b
6 100 lb
7 100 lb
8 100 lb
9 360 lb
10 1001b
11 100 lb
12 100 lb
13 1001b
14 100 lb
15 100 lb
16 100 lb
17 100 lb
Sum: 1,960 lb
Transverse Column Loads
Pstatic DL= 51 lb
Pstatic LL= 980 lb
Mconn= 7,839 in-lb
DL hi wi*hi
61b 3in 318
61b 18in 1,908
61b 33in 3,498
61b 48in 5,088
61b 63 in 6,678
61b 78in 8,268
61b 93in 9,858
61b 108in 11,448
61b 122in 44,652
61b 125in 13,250
61b 137in 14,522
61b 149in 15,794
61b 161 in 17,066
61b 173in 18,338
61b 185in 19,610
61b 197in 20,882
61b 209in 22,154
102 lb W=2062 lb 233,332
Movt= 38,049 in-lb
Pseismic= Movt/D
= 2,114 lb
"1transv=M = 939 in-lb
Fi Fi*hi
0.4 lb 1 in-lb
2.2 lb 40 in-lb
4.0 lb 132 in-lb
5.8 lb 278 in-lb
7.6 lb 479 in-lb
9.4 lb 733 in-lb
11.2 lb 1,042 in-lb
13.1 lb 1,415 in-lb
50.9 lb 6,210 in-lb
15.1 lb 1,888 in-lb
16.6 lb 2,274 in-lb
18.0 lb 2,682 in-lb
19.5 lb 3,t40 in-lb
20.9 lb 3,616 in-lb
22.4 lb 4,144 in-lb
23.8 lb 4,689 in-lb
25.3 lb 5,288 in-lb
120 lb Movt=38048,6 in-lb
Moment Resisting Dbl Rivet Beams
Vn hb Mn
133.00 lb 3in 399 in-lb
125.18 lb 15in 939 in-lb
117.35 lb 15in 880 in-lb
109.53 lb 15in 821 in-lb
101.71 lb 15in 763 in-lb
93.88 lb 15in 704 in-lb
86.06 lb 15in 645 in-lb
78.24 lb 15in 587 in-lb
70.41 lb 14in 493 in-lb
62.59 lb 3 in 94 in-lb
54.76 lb 12in 329 in-lb
46.94 lb 12in 282 in-lb
39.12 lb 12in 235 in-lb
31.29 lb 12in 188 in-lb
23.47 lb 12in 141 in-lb
15.65 lb 12in 94 in-lb
7.82 lb 12in 47 in-lb
Smllarly, Mlong= 798 in-lb
Mconn-long= 798 in-lb
Mconn
669 in-lb
909 in-lb
851 in-lb
792 in-lb
733 in-lb
675 in-lb
616 in~lb
540 in-lb
293 in-lb
211 in-lb
305 in-lb
258 in-lb
211 in-lb
164 in-lb
117 in-lb
70 in-lb
23 in-lb
Longitudinal Column Loads
Pstatic= Z:(LL +DL)
= 1,031 lb
Mlong= ~*VJVT
= 798 in-lb
NORD50N A5YMTEK-f'-08 I I I 5-2-5HELVING Page ~G, of 3 ~ 8/19/2015
St~tural
VoniW'ts ::ii4 Cngineering ~ 1200 N, Jefferson Ste. Ste E Anaheim, CA 92807 JeJ: 714.§32.7330 fax: 714 632.7763
By: S.P. Project: NORDSONASYMTEK Project#: P-081115-2
Transverse Column Loads (Weak Axis Bending) Configuration: Rivetier II Shelving : 216 in x 36 in x 18 in
Net Section Properties
Column= WPSS LURHD L1-7/8"x14ga
Aeff = 0.471 inA2
Ix (downaisle) = 0.297 inA4
Sx (downaisle) = 0.158 inA3
rx (downaisle) = 0.794 in
Iy (crossaisle) = 0.177 inA4
Sy (crossaisle) = 0.129 inA3
ry (crossaisle) = 0.614 in
Fy= 36 ksi
Axial DL= 51 lb
Axial LL= 980 lb
Pseismic= 2,114 lb
Loads Load case: (Fully Loaded)
Qf= 1.67
E= 29,500 ksi
Cb= 1.0
Cmx= 0.85
Kx= 1.0
Lx = 15.0.in
Ky= 1.0
Ly= 15.0 in
Axial=P= DL+0.75LL+0.75*0.7*Pseismic
= 1,896 lb Moment=My= 939 in-lb
Axial Analysis
KxLx/rx = 1*15"/0.7942"
= 18.9
Fe= nA2E/(KL/r)maxA2
= 487.7ksi
Pn= Aeff*Fn
= 16,629 lb
P/Pa= 0.22
Bending Analysis
> 0.15
KyLy/ry = 1 *15"/0.6139"
= 24.4
Fy/2= 18.0 ksi
Qc= 1.92
Check: P/Pa + (Cmy*My)/(May*µ) :,; 1.0
P/Pao +My/Mays; 1.0
Pno= Ae*Fy Pao= Pno/Qc
,-i-~18"
,l,.-1 7/8"=i=1 7/8"--J
Fe> Fy/2
Fn= Fy(1-Fy/4Fe)
= 36 ksi*[l-36 ksi/(4*487.7 ksi)]
= 35.3 ksi
Pa= Pn/Qc
= 16629 lb/1.92
= 8,661 lb
Myield=My= Sy*Fy
= 0.471 inA2 *36000 psi
= 16,942 lb
= 169421b/1.92
= 8,824 lb
= 0.129 inA3 * 36000 psi
= 4,658 in-lb
May= My/Qf
= 4658 in-lb/1.67
= 2,789 in-lb
µ= {1/[1-(Qc*P/Pcr)]}A-1
= {1/[1-(1.92*1896 lb/384193 lb)]}A-1
= 0.99
Combined Stresses
Per= nA2EI/(KL)maxA2
= nA2*29500000 psi/(1*15 in)A2
= 384,193 lb
(1896 lb/8661 lb)+ (0.85*939 in-lb)/(2789 in-lb*0.99) =
(1896 lb/8824 lb)+ (939 in-lb/2789 in-lb) =
0.51
0.55
< 1.0, OK
< 1.0, OK
NORD50N A5YMTEK-F-08 I I 15-2-5HELVING Page~) of 3~
(EQ C5-1)
CEO C5-2)
8/19/2015
St~tural
\.,on..w:,ts
~ Cngineering ~ 1200 N. Jefferson Ste. Ste E Anaheim. CA 92807 Jel: 714,632.7330 fax: 714,632 7763
By: S.P. Project: NORDSON ASYMTEK Project#: P-081115-2
Longitudinal Column Loads (Strong Axis Bending) Configl!ration: Rivetier II Shelving : 216 in x 36 in x 18 in
Net Section Properties
Column= WPSS LURHD Ll-7/8"x14ga
Aeff = 0.471 in"2
Ix (downaisle) = 0.297 in"4
Sx (downaisle) = 0.158 in"3
rx (downaisle) = Q.794 in
Iy (crossaisle) = 0.177 in/\4
Sy (crossaisle) = 0.129 in"3
ry (crossaisle) = 0.614 in
Fy= 36 ksi
Axial DL= 51 lb
Axial LL= 980 lb
Pseismic= O lb
Loads Load Case: (Fully Loaded)
Qf= 1.67
E= 29,500 ksi
Cb= 1.0
Cmx= 0.85
Kx= 1.0
Lx = 15.0 in
Ky= 1.0
Ly= 15.0 in
Axial=P= DL+0.75LL+0.75*0.7*Pseismic
= 7861b Moment=Mx= 798 in-lb
Axial Analysis
KxLx/rx = 1*15"/0.7942"
= 18.9
Fe= n"2E/(KL/r)max"2
= 487.7ksi
Pn= Aeff*Fn
= 16,629 lb
P/Pa= 0.09
Bending Analysis
< 0.15
Check: P/Pa + My/May :5 1.0
Pno= Ae*Fy
KyLy/ry = 1 *15"/0.6139"
= 24.4
Fy/2= 18.0 ksi
Qc= 1.92
Pao= Pno/Qc
Fe> Fy/2
Fn= Fy(1-Fy/4Fe)
= 36 ksi*[l-36 ksi/(4*487.7 ksi)J
= 35.3 ksi
Pa= Pn/Qc
= 16629 lb/1.92
= 8,661 lb
Myield=My= Sx*Fy
= 0.471 in"2 *36000 psi
= 16,942 lb
= 169421b/1.92
= 8,824 lb
= 0.158 inA3 * 36000 psi
= 5,699 in-lb
May= My/Qf
= 5699 in-lb/1.67
= 3,412 in-lb
µ= {1/(1-(Qc*P/Pcr)]}"-1
= {1/[1-(1.92*786 lb/384193 lb)]}"-1
= 1.00
Combined Stresses
Per= n"2EI/(KL)max"2
= n/\2*29500000 psi/(1 *15 in)"2
= 384,193 lb
(786 lb/8661 lb)+ (798 in-lb/3412 in-lb) = 0.32 < 1.0, OK
NORD50N A5YMTEK-P-08 I I I 5-2-SHELVING Page;,~ of 3 ~
(EQ C5-3)
8/19/2015
St'}liitural
\.,on~ts
~ Cngineering
· · 1200 N, Jefferson Ste. Ste E Anaheim cA 92807 Tel: 714,§32,7330 fax: 714 632,7763
By: S.P. Project: NORDSON ASYMTEK Project#: P-081115-2
Double Rivet Beam Configuration: Rivetier II Shelving : 216 in x 36 in x 18 in
1-3/32" 1-1
Downaisle beam Beam Type= WPSS SS Double Rivet Beam
Ix= 0.2060 inA4
Sx= 0.123 inA3
~ t=14ga l T• rrrrrrrr
Fy-beam= 36,000 psi
Shelf Span=L= 35 in
Check Beam Bending
Shelf DL= 6 lb
Shelf LL= 100 lb
Shelf LL+DL= 106 lb
Load=w=LL*0.67/(2*L)= 12.9 plf
M= w * LA2/8
= 165 in-lb
fb= M/Sx
= 1,338 psi
Fb= 0.6 * Fy
21,600 psi
fb/Fb= 0.06 OK
Check DRB Beam Rivets For Static.+ Seismic Loads
Check load case: DL+0.75LL + 0.75*0.?*Mseismic
Rivet Spacing=d= 1.5 in
Rivet diameter= 0.25 in
Fy-rivet= 36,000 psi
M*0.7*0.75= 493 in-lb
C= M/d
= 329 lb
Shear capacity= Rivet Area * 0.4 * Fy-rivet
~. ~ .
,:,) .,.. N t
SS Dbl Rivet Beam
Downaisle beam
L
Shelf Plan View
Check Beam Deflection
E= 29,500,000 psi
D= 5 * w * LA4/(384 * E * Ix)
= 0.0036 in
Dallow= L/140
tmin= 0.075 in
Fu= 58,000 psi
W= (LL *0.75+DL)/4
= 201b
=
-t-
d
_J_
0.25in OK
= ((0.25 in)A2 * pi/4] * 0.4 * 36000 psi
= 7071b
Bearing capacity= Rivet Diam * tmin * Fu * 1.2
= 1,305 lb
Effective Shear= [(W/2)A2 + CA2)A0.5
= 329 lb OK
NORDSON ASYMTEK-F-081 I 15-2-SHELVING
w
Beam to Column
Page -i; of 3;:z.._,,,
Column
Rivet
Beam
8//9/2015
By: S.P. Project: NORDSON ASYMTEK Project#: P-081115-2
Anchors Configuration: Rivetier II Shelving : 216 in x 36 in x 18 in
Check load case: 0.6D + 0.67LL + 0.7V
Loads
Vtrans=V= 266 lb
DL/Frame= 102 lb
LL/Frame= 1,960 lb
Wst=(0.6*DL+ 0.67LL)total= 1,374 lb
LL @ TOP= 100 lb
DL/Lvl= 6 lb
DL *0.60= 4 lb
Lateral Ovt Forces=I(Fi*hi)*l.15*0.7= 30,629 in-lb
Fully Loaded rack
Vtrans= 266 lb
Movt= l(Fi*hi)
Frame Depth=D= 18.0 in
Htop-lvl= 216.0 in
# Levels= 17
# Anchors/End= 2
~
T,
SIDE ELEVATION
Mst= Wst * D/2 Uplift=T= (Movt-Mst)/D
V
= 30,629 in-lb = 1374 lb * 18 in/2
= 12,366 in-lb
= (30629 in-lb -12366 in-lb)/18 in
= 1,015 lb
Top Level Loaded Only
Critical Level= 17
Vtop= Cs * LLtop
Vtop= 0.188 * 100 lb
= 191b
Mst= 0.6*(LL-top) *D/2
= (100 lb*0.6) * 18 in/2
= 540 in-lb
Hgt@ Lvl 17= 216.0 in
Movt= Vtop*Htop*l.15
= 19 lb * 216 in * 1.15
= 4,720 in-lb
Uplift= T = (Movt-Mst)/D
= (4720 in-lb -540 in-lb)/18 in
= 2321b
Anchor Net Seismic Max Uplift=! 1,015 LB
Check (2) 3/8" x 2" Embed Hilti Kwikbolt TZ anchor(s) per footplate **
Special inspection is required per ICC ESR 1917.
** Alternate approved anchor: Powers Power Stud+ SO2, 3/8" diam x 2.375" min embedment, (~) per footplate
** ALL SINGLE ROW SHELVING POSTS MUST BE ANCHORED. BACK TO BACK TIED UNITS SHALL BE ANCHORED AT THE AISLE SIDE POSTS ONLY
Fully Loaded:
Top Level Loaded:
Pullout capacity=Tcap= 550 lb
Shear Capacity=Vcap= 450 lb Phi= 1.00
Tcap*Phi= 550 lb
Vcap*Phi= 450 lb
(508 lb/550 lb)"l + (67 lb/450 lb)"l =
(116 lb/550 lb)"l + (5 lb/450 lb)"l =
NORDSON ASYMTEK-P-081 I 15-2-SHELVING Page 30 of 3--;i_,
1.07
0.22
<= 1.2 OK
<= 1.2 OK
8/19/2015
St'}'itural
Von~ts
~ Cngineering
· 1200 N Jefferson ste, Ste E Anaheim, CA 92soz JeJ: 714,632.7330 fax: 714.632.7763
By: S.P. Project: NORDSON ASYMTEK Project#: P-081115-2
Base Plate Configuration: Rivetier II Shelving : 216 in x 36 in x 18 in
Section
Actual base plate forT Post is 5.75 in x 3.625 in x 14 ga, but a smaller area is considered to be effective due to the rigidity limitations of the baseplate
Width=B = 4.00 in
Depth=D = 2.00 in
Plate Thickness=t = 0.075 in
Cross Aisle Loads
Column Width=b = 3.750 in
Column depth=b = 1.875 in
L = 0.13 in
Fy = 36,000 psi
Axial DL= 51 lb
Axial L= 980 lb
Pseismic= 2,114 lb
DL+0.75LL + 0.75*0.7*Pseismic= 1,896 lb
L = Base Plate Depth-Col Depth
= 0.13 in
fa = P/A = P/(D*B)
= 237 psi
Sbase/in = (1)(t"2)/6
= 0.001 in"3/in
fb/Fb = M/[(S-plate)(Fb)J
= 0.07 OK
NORD5ON A5YMTEK-F-08 I I I 5-2-5HELVING
M= wl "2/2= fa*L "2/2
= 2 in-lb/in
Fbase = 0.75*Fy
= 27,000 psi
i 53/4"
I (f)
l
CONNECT TO UPRIGHT
W/ (2) 1/4' TEK SCREWS
RDSFP FOOTPLATE
Page31 of 5:?.,.
1'
11/27
(f) ,[D
CONNECT TO UPRIGHT
W/ (1) 1/4' TEK SCREW
RSSFP FOOTPLATE
w
8/19/2015
St~tural
\., onw,W>ts ;{fiJ Cngineering
. 1729 S. Doyq(ass Rd. Ste B, CA 92806 Te(: 714,456,0056 fax· 714 456,0066
By: S.P. Project: NORDSON ASYMTEK Project#: P-081115-2
Slab on Grade
SLAB ELEVATION
Base Plate
B= 4.00 in
D= 2.00 in
Load Case 1: Product + Seismic
Product DL= 51 lb
Product LL= 980 lb
Puncture I
Pu= 1.2DL + 1.0LL + 1.0*E
= 2,838 lb
Apunct= [(c+t)+(e+t)J*2*t
= 216.0 inA2
Slab Bending I
Asoil= (P*144)/(fsoil)
= 409 in"'2
X= (L-y)/2
= 2.7 in
Fb= 5*(phi)*(fc)"'0.5
= 162.5 psi
Load Case 2: Static Loads
Puncture
DL= 51 lb
Pu= 1.2*DL + 1.6*LL
= 1,492 lb
Apunct= [(c+t)+(e+t)J*2*t
= 216 in"'2
Slab Bending
Asoil= (Pu*144)/(fsoil)
= 215 inA2
X= (L-y)/2
= O.Oin
Fb= 5*(phi)*(fc)"'0.5
= 162.5 psi
Configuration: Rivetier II Shelving : 216 in x 36 in x 18 in
width=a= 3.75 in
depth=b= 1.88 in
Baseplate Plan View
Concrete
fc= 2,500 psi
tslab=t= 6.0 in
phi=0= 0.65
Soil
fsoil= 1,000 psf
Movt= 38,049 in-lb
Frame depth= 18.0 in
eff. baseplate width=c= 4.00 in
eff. baseplate depth=e= 2.00 in
P-seismic=E= Movt/Frame depth
= 2,114 lb
(Strength Design Loads)
L= (Asoil)A0.5
= 20.22 in
M= w*xA2/2
= (fsoil*x"'2)/(144*2)
= 25 in-lb
I
LL= 980 lb
L= (Asoil)"'0.5
= 14.66 in
M= w*xA2/2
= (fsoil*xA2)/(144*2)
= O in-lb
Fpunct= 2.66*phi*sqrt(fc)
= 86.5 psi
fv/Fv= Pu/(Apunct*Fpunct)
= 0.15 < 1.00K
y= (c*e)A0.5 + t*2
= 14.8 in
S-slab= l*tA2/6
= 6.0 inA3
fb/Fb= M/(S-slab*Fb)
= 0.03 < 1.0 OK
I
Fpunct= 2.66*phi*sqrt(fc)
= 86.5 psi
fv/Fv= Pu/(Apunct*Fpunct)
= 0.08 < 1.0 OK
y= (c*e)"'0.5 + t*2
= 14.8 in
S-slab= 1*tA2/6
= 6.0 inA3
fb/Fb= M/(S-slab*Fb)
= 0.00 < 1.0, OK
Seismic C
NORD50N ASYMTEK-F-081 I I 5-2-5HELVING Page 3:t, of S ~ 8/19/2015
~St~p'-ural
f~•f»fr"!C~S
.,,,===.; . C:ngineering
1615 Yeager Ave., La Verne, CA 91750 Tel: 909.596.1351 Fax: 909.593.8561
··-------=====================================
VLM ANALYSIS
-----=====================================
St~tural
l,onifiPts
~ Cngineering
1200 N Jefferson Ste Ste E Anaheim, CA 92807 Tel· 714.632.7330 fax: 714 632 7763
By: BOBS Project: NORDSON Project#: P-081115-2LV
Design Data Configuration: REMSTAR SHUTTLE XP HD-500
1) The analyses of the storage equipment conforms to the requirements of the 2013 CBC, 2012 IBC & ASCE 7-10
2) Anchor bolts shall be provided by installer per ICC reference on the calculations herein. The installer must provide
any special inspection as called out on plans or calculations, or as required by the ICCC report indicated herein.
3) All welds shall conform to AWS procedures, utilizing E?0xx electrodes or similar. All such welds shall be performed
in shop, with no field welding allowed other than those supervised by a licensed deputy inspector.
4) The slab on grade is 6" thick with minimum 2500 psi compressive strength. Soil bearing capacity is 1000 psf.
Existing slab on grade checked only for puncture and bending.
Configuration: REMSTAR SHUTTLE XP HD-500
REMSTAR
SHUTTLE
XP
H
D L~
Vertical Carousel System
Page A of G
Configuration
D= 120.98 in
H= 328.75 in
L= 109.45 in
Dead Load= 14,645 lb
Live Load= 49,677 lb
Anchors= (8) 5/8" diam x 4" Embed
HILT! KWIK BOLTTZ #1917 per base
~~~~:ineering
1200 N Jefferson Ste. Ste E Anaheim CA 92807 Tel· 714 632 7330 fax· 714 632 7763
By: BOB S Project: NORDSON Project#: P-081115-2L V
Seismic Forces Configuration: REMSTAR SHUTTLE XP HD-500
Lateral analysis is performed with regard to 2013 CBC, 2012 IBC & ASCE 7-10
Veq12.s-2= Sos*I*W /R
Veql3.3-1= 0.4 * ap *Sos* W * (1 + 2*z/h)/(Rp/Ip)
Veql3.3·3= 0.3* Sos* Ip* W
Sos= Fa * Ss * (2/3)
= 1.01173
Veq12.8-2= 0.4047
Veq 13.3-1= 0.1619
Veq 13.3-3= 0.3035
Vminimum= 0.000
Cs=Seismic Coeff= 0.4047
V=Cs/1.4= 0.2891
W-DL= 14,645 lb
W-LL= 49,677 lb
(Either Direction)
V= 0.289065714285714 * (14645 lb+ 49677 lb)
= 18,593 lb
H= 328.8 in
Depth= 121.0 in
Vmin= 0.015
(ASCE 7-10, TABLE 13.6-1)
Fa= 1.08
Ss= 1.40
R= 2.50
Ip= 1.00
PLRF= 1.00
ap= 1.0
Rp= 2.5
z/h= 0.00
Fl=
r-i;-1
I
V H ~r
H/2
t
Carousel Side Elevation
Movt= V * H/2 Mst= (0.9 * WDL + WLL) * D/2
Anchor
= 3,056,224 in-lb Load Case 1: (DL + LL+ E;
= 695,849 in-lb Load Case 2: (DL + E)
T = (Movt -Mst)/D
= -6,167 lb
= -838 lb
Load Case 1: (0.9*DL + LL+ E)
Load Case 1: (0.9*DL + LL+ E)
Check (8) 5/8" diam x 4" Embed HILTI KWIK BOLT TZ anchor(s) unit.
Special inspection is required per ICC #1917.
Pullout Capacity=Tcap= 1,250 lb
Shear Capacity=Vcap= 1,840 lb
Tcap*Phi= 1,663 lb
Vcap*Phi= 2,447 lb
L.A. City ? NO
Phi= 1.33
(0 lb/1663 lb)"l.66 + (2324 lb/2447 lb)"l.66 = 0.92
= (14645 lb* 0.9 + 49677 lb)* 120.98 in/2
= 3,802,250 in-lb Load Case 1: (0.9*DL + LL+ E)
= 797,288 in-lb Load Case 1: (0.9*DL + LL+ E)
Tmax= 0 lb
# Anchor/side= 4
Shear/Anchor= 2,324 lb
<= 1.0 OK
Page 0 of a,
St~tural
Von~ts ·-~-,---" r Cngineering
.,:/' 1200 N. Jefferson Ste Ste E Anaheim. CA 92807 Te!· 714.632 7330 fax: 714 632.7763
By: BOBS Project: NORDSON Project#: P-081115-2LV
Slab on Grade Configuration: REMSTAR SHUTTLE XP HD-500
Base Assembly
Base width=B= 4.00 in
Base Length=D= 5.50 in
Concrete
fc= 2,500 psi
tslab=t= 6.0 in
phi=0= 0.60
Soil
fsoil= 1,000 psf
Movt= 3,056,224 in-lb
Frame depth= 120.98 in
# columns=N= 8
Load Case 1: Product+ Seismic
Product DL= 1,831 lb
Product LL/post= 6,210 lb
Puncture I
Pu= 1.2PDL + 1.0PLL + 1.0*E
= 14,722 lb
Apunct= [(B+t)+(D+t)J*2*t
= 258.0 in"2
Slab Bending I
Asoil= (P*144)/(fsoil)
= 2,120 in"2
X= (L-y)/2
= 14.7 in
Fb= 5*(phi)*(fc)"0.5
= 150. psi
Load Case 2: Static Loads
Puncture
PDL= 1,831 lb
Pu= 1.2*PDL + 1.6*PLL
= 12,132 lb
Apunct= [(B+t)+(D+t)J*2*t
= 258 in"2
Slab Bending
Asoil= (Pu*l 44)/(fsoil)
= 1,747 in"2
X= (L-y)/2
= 12.6 in
Fb= S*(phi)*(fc)"0.5
= 150. psi
p
L
SLAB ELEVATION
P-seismic=E= Movt/Frame depth
= 6,316 lb
(Strength Design Loads)
L= (Asoi/)"'0.5
= 46.04 in
M= w*x"2/2
= (fsoil*x"2)/(144*2)
= 748 in-lb
PLL= 6,210 lb
L= (Asoil)"0.5
= 41.80 in
M= w*x"2/2
= (fsoil*x" 2)/(144*2)
= 547 in-lb
Page c. of C:,
Fpunct= 2.66*phi*sqrt(fc)
= 79.8 psi
fv/Fv= Pu/(Apunct*Fpunct)
= 0.72 < 1.0OK
y= (B*D)"'0.5 + t*2
= 16.7 in
S-slab= 1 *t" 2/6
= 6.0 in"3
fb/Fb= M/(S-slab*Fb)
= 0.83 < 1.0OK
Fpunct= 2.66*phi*sqrt(fc)
= 79.8 psi
fv/Fv= Pu/(Apunct*Fpunct)
= 0.59 < 1.0 OK
y= (B*D)"0.5 + t*2
= 16.7 in
s-slab= 1*t"2/6
= 6.0 in"3
fb/Fb= M/(S-slab*Fb)
= 0.61 < 1.0, OK
,Stu'_M·t1-ural
1,f?'''
t.,. ,··.nci!:gineering
1615 Yeager Ave., La Verne, CA 91750 Tel: 909.596.1351 Fax: 909.593.8561 .. ···---=---============================================
·--=======================================
MEG RS 350
\
--...... ,_ -=-=======================================
5i~~:ineering
..... 1200 N. Jefferson Ste Ste E Anaheim. CA 92807 Tel· 714.632 7330 fax· 714 632 7763
By: BOBS Project: NORDSON Project#: P-081115-2LV
Design Data Configuration: KARDEX REMSTAR MEG RS 350
1) The analyses of the storage equipment conforms to the requirements of the 2013 CBC & ASCE 7-10
2) Anchor bolts shall be provided by installer per ICC reference on the calculations herein. The installer must provide
any special inspection as called out on plans or calculations, or as required by the !CCC report indicated herein.
3) All welds shall conform to AWS procedures, ·utilizing E70xx electrodes or similar. All such welds shall be performed
in shop, with no field welding allowed other than those supervised by a licensed deputy inspector:
4) The slab on grade is 6" thick with minimum 2500 psi compressive strength. Soil bearing capacity is 1000 psf.
Existing slab on grade checked only for puncture and bending.
Configuration: KARDEX REMSTAR MEG RS 350
REMSTAR
MEG RS
350
H
D L~
Vertical Carousel System
Page G of G
Configuration
D= 50.10 in
H= 324.00 in
L= 121.10 in
Dead Load= 11,180 lb
Live Load= 15,000 lb
Anchors= (8) 3/4" diam x 4-3/4" Embed
HILT! KWIK BOLT lZ #1917 per base
St'('.;tural
~~n~:ineering
... ';;;{ 1200 N. Jefferson Ste Ste E Anaheim, CA 92807 Te!· 714 632 7330 fax: 714 632 7763
By: BOBS Project: NORDSON Project#: P-081115-2LV
Seismic Forces Configuration: KARDEX REMSTAR MEG RS 350
Lateral analysis is performed with regard to 2013 CBC & ASCE 7-10
Veq12.8-2 Sos*I*'w'I/R
Veq 13.3-1 = 0.4 * ap *Sos* W * (1 + 2*z/h)/(Rp/Ip)
Veql3.3·3= 0.3* Sos* Ip* W
Sos= Fa * Ss * (2/3)
= 0.75157
Veq12.8 2 0.2147
Veq 13.3-1=; 0.1203
Veq 13.3-3= 0.2255
Vminimum= 0.000
Cs=Seismic Coeff= 0.2255
V=Cs/1.4= 0.1611
W-DL= 11,180 lb
W-LL= 15,000 lb
(Either Direction)
V= 0.161050714285714 * (11180 lb+ 15000 lb)
= 4,216 lb
H= 324.0 in
Vm;n= 0.015
(RMI Sec 2.5.1.2)
Fa= 1.08
Ss= 1.04
R 3.50
Ip= 1.00
PLRF= 1.00
ap= 1.0
Rp= 2.5
z/h= 0.00
~I
I V H
T H/2
Anchor Pt Depth= 50.1 in Carousel Side Elevation
Dpth of Equip = 50.1 in
Anchor
Movt= V * H/2
= 682,992 in-lb
= 291,667 in-lb
T= (Movt -Mst)/D
= 2,217 lb
= -660 lb
Load Case 1: (DL +LL+ E;
Load Case 2: (DL + E)
Load Case 1: (DL + LL+ E)
Load Case 2: (DL+E)
Mst= (1-0.2*Sds)*(WDL + WLL) * D/2
= 0.683(11180 lb + 1SOOO lb) * 50.1 in/2
= 571,902 in-lb Load Case 1: (DL + LL+ E)
= 324,724 in-lb Load Case 2: (DL+E)
Tmax= 2,217 lb
Check (8) 3/4" diam x 4-3/4" Embed HILTI KWIK BOLT TZ anchor(s) unit.
Special inspection is required per ICC #1917.
Pullout Capacity=Tcap= 2,178 lb
Shear Capacity=Vcap= 2,839 lb
Tcap*Phi= 2,178 lb
Vcap*Phi= 2,839 lb
L.A. City ? YES
Phi= 1.00
(554.25 lb/2178 lb)"1 + (527 lb/2839 lb)"1 = 0.44
Page f of G
# Anchor/side= 4
Shear/Anchor= 527 lb
<= 1.2 OK
St~tural
'!
~~n~;:ineering
__ _ _ _ _ -::::--=-=· =,.-=====::::::!:12!::!0=0=N!!:::. :!:Je!::!ff:!::e::!::rs~o~n=S=t=e,=S=te!::::!::F=A!::!n~ah=e~im:!:!::::, C:::!A==92=8=0=7 =T=el=: 7=1=4=.6=3~2-=73=3=0=F=a~x=: 7=1=4=.6=32=·=77=6=3==========
By: BOBS
~--::= •. ,:: •• :
Slab :m Grade
Base Assembly
8,1se width=B= 5.00 in
E-A~:i' 1_ength=D= 8.00 in
Concrete
f'c= 2,500 psi
PP.nd t.slab=t= 6.0 in
phi=0= 0.60
Soil
fsoil= 1,000 psf
Movt= 682,992 in-lb
f"rame depth= 50.10 in
~ columns=N= 4
Project: NORDSON Project#: P-081115-ZLV
Configuration: KARDEX REMSTAR MEG RS 350
p
SLAB ELEVATION
Jo~ !_'.;ase 1: Product + Seismic
.. --: ·ocluct DL= 2,795 lb P-seismic=E= Movt/Frame depth
= 9,543 lb
(Strength Design Loads)
P·'.). J,. :t LL/post= 3,750 lb
---·-----..------------------------------------------, Pur.ct ,:· = I ____ __.
Pu= 1.2PDL + 1.0PLL + 1.0*E + 0.2*SDs*PDL
= 17,533 lb
Apunct= [(B+t)+(D+t)]*2*t
= 300.0 in"'2
Fpunct= 2.66*phi*sqrt(f'c)
= 79.8 psi
fv/Fv= Pu/(Apunct*Fpunct)
= 0.73 < 1.0 OK --------,--------------------------------------------1 Slab E E.nding I
Asoil= (P*144)/(fsoil) y= (B*D)A0.5 + t*2 L= (Asoil)"'0.5
= 50.25 in = 2,525 in"'2 = 18.3 in
x= (L-y)/2 M= w*x"'2/2 S-slab= l*t"'2/6
= 16.0 in = (fsoil*x"'2)/(144*2) = 6.0 in"'3
Fb= 5*(phi)*(f'c)A0.5 = 885 in-lb fb/Fb= M/(S-slab*Fb)
~---·------=_1_5_0 ..... p'"""s_i _______________________ = __ o_._9_8 __ <_1._0_O_K ______ ___,
load Case 2: Static Loads
PDL= 2,795 lb PLL= 3,750 lb
D,Jr':t :'·.,
Pu= 1.2*PDL + 1.6*PLL Fpunct= 2.66*phi*sqrt(f'c)
= 9,354 lb = 79.8 psi
A.punct= [(B+t)+(D+t)]*2*t fv/Fv= Pu/(Apunct*Fpunct)
= 300 in"'2 = 0.39 < 1.0 OK ---------------------------------------"-'---------l s.at: E ,, ding
Asoil= (Pu*144)/(fsoil)
= 1,347 in"'2
X= (L-y)/2
= 9.2 in
Fb= 5*(phi)*(f'c)"'0.5
= 150. psi
L= (Asoil)"'0.5
= 36.70 in
M= w*xA2/2
= (fsoil*x"'2)/(144*2)
= 293 in-lb
Page~ of G,
y= (B*D)A0.5 + t*2
= 18.3 in
s-slab= 1 *t"'2/6
= 6.0 in"'3
fb/Fb= M/(S-slab*Fb)
= 0.33 < 1.0, OK
KLAUSBRUCKNER
AND ASSOCIATES
2495 Truxtun Road, Suite 205
San Diego, CA 92106 ..,_ ____ _._.._"""""""' __ """""""' __________ """""""' __ =-·~
Tel: (619) 677-2004
Fax: (619) 677-2444
NORDSON ASYMTEK
RECEl\fED
SEP 2 3 2015
CITY OF CARLSBAD
BUILDING O!VIS!ON
2765 Loker Avenue
Carlsbad, CA
High-Piled Combustible
Storage Report
Rev 1.1
September 3, 2015
·)-
I--u
1,,
2.
3,
.4,
Ot=:Fltlt;·l)'SI; ONLY
'D. r-1\,1) ''l ~ RECORD IIJ. ; . ..-·r.:-9:· ··+· · r-:"M,-=-------------,..,d k.1-I ,.u J • HHMBP #: ... ~~-',;,,· ... ·: ""', ·, ...... · ...,.. ____ ..,.......,.._
BP DATE,_ .. _-_· .. .,.··~_,·-=~'-· --·
0 CalARP Exempl
f!
Date ·· ·1nlllals
0 CalARP Required
.. I ..
Date lnltlals
0 CalARP Complete
I
Dale lnlUals
FIRE DEPARTMENT OCCUPANCY OLASSIFICA-11~1)!;...,· ---------'""'"'------;.....;.,.,,-_,--....,,._..,... ____ .,....., __ -=..,..,.---,.-
BY:. DATE:· .. ·• r_-<-~r
EXEMPTORNOFURTHERl~fO~TIONREQUJtiED IJ!!MITBU]'.r_i01-F0R_l!CCl!.P~Nl:'t. :_~: . ~ .. RE!.~SEDJ'.0~:occ_uP~.fil'._ --..
CO!JNTY:HMD' AF'CD ~P.CD __ CQJ,!NJ:MIMD J .•. APCC!