HomeMy WebLinkAbout; ECR - Ductile Iron Pipe Water Transmission Main; Soils Report; 1988-06-24DUCTILE IRON PIPE RESEARCHASSOCIM’ION ( 1%
245RiverchaseParkway,East Suite0 BirminghaqAL35244 (205)988-9870
June 24, 1988
Mr. Robert A. Johnston COSTA REAL MUNICIPAL WATER DISTRICT 5950 El Camino Real Carlsbad, California 92008
~~Yovr~Yto MichaelS.Tucker,P.E.
Regional Engineer
11161 Magnolia street
GardenGrove, California92641
(714) 53043%
Re: Soil Investigation Report El Camino Real 36" Ductile Iron Pipe Water Transmission main Carlsbad, California
Dear Bob:
Enclosed is a copy of the soil survey report concerning the soil analysis and potential stray current situation on the reference project. Potentially corrosive soil was found on the project as well as possible stray current interference in several locations. Details of the findings are included in the context of the report.
Polyethylene encasement is recommended for the entire project due to low soil resistivity and potential stray current interference.
It was a pleasure to be of assistance to you on this project, and I look forward to working with you in the future. If you have any questions about the report or findings, please call me.
Sincerely,
Regional Engineer
MST:sh Enclosures
,- SOIL INVESTIGATION REPORT
EL CAMINO REAL
36" DUCTILE IRON PIPE WATER TRANSMISSION MAIN
CARLSBAD, CALIFORNIA
JUNE 15-16, 1988
Reported by:
Michael S. Tucker, P.E. Regional Engineer &fames Vogel, P.E. Director of Regional Engineers
DUCTILE IRON PIPE RESEARCH ASSOCIATION 245 RIVERCHASE PARKWAY EAST SUITE 0 BIRMINGHAM, ALABAMA 35244 (205) 988-9870
SS88-104
r INDEX
3y
Procedures 1
Test Results 2
Observations 2
Conclusions 2
Recommendations 3
BXFiIBITS
Project Map
ANsI/AWWA C105/A21.5 - American National Standard for Polyethylene Encasement for Ductile Iron Piping for Water and Other Liquids
Test Results
I
II
III
This proposed water transmission line project involves approximately 12,000' of piping sizes 12" through 36" diameter. It is recommended that polyethylene encasement be installed on the entire project due to low soil resistivity and stray current interference.
INTR0DlJCT10y
Requested by: Robert A. Johnston Costa Real Municipal Water Dist. 5950 El Camino Real Carlsbad, California 92008 (619) 438-3367
The survey was conducted in a spirit of service and cooperation
for the purpose of identifying potentially corrosive conditions
relative to ductile iron piping systems.
PROJECT
Location: Carlsbad, California
/- Pipe Quantities: ml- LensthIfeeti
12" 20' 14" 360' 20" 1,904' 24" 938 ' 36" 8.772' TOTAL 11,994'
Date of Survey: June 15-16, 1988
Conducted by: Michael S. Tucker, P.E., Regional Engineer with DIPRA and Deon T. Fowles, P.E., Senior Regional Engineer with DIPRA, with preliminary information and mapping available through the engineering office of Costa Real Municipal Water District.
Representative test locations were selected along the route of
proposed pipe installation. Each was assigned a number which
corresponds to a number appearing in the soil analysis listing and on
r the project map, Exhibit I.
Page 2
A small diameter boring to approximate proposed pipe depth at
each location facilitated field testing and removal of soil specimens
for laboratory analysis. All field and laboratory procedures were
completed in accordance with Appendix A of ANSI/AWWA C105/A21.5
Standard, see w.
TEST RESULTS
Specific soil analysis results are listed in Exhibit III of this
report.
OSSERVATIONS
At four (4) locations along the project, the proposed
transmission main will cross or closely parallel a cathodically
F~ protected gasline. Potential profile electrical measurements were
conducted at these locations to assist in evaluating this possible
interference situation.
CONCUJSIONS
Stray direct current resulting from cathodic protection
systems can theoretically cause corrosion damage to other metallic
structures in the vicinity of the protected pipeline. Actual field
experience and theoretical consideration of the fact that ductile
iron pipelines are not electrically continuous indicate that stray
current corrosion on ductile iron pipe is a infrequent occurrence.
The difficulty in predicting stray current corrosion on ductile iron
pipe prior to installation, however, leads to recommendations which
experience has shown to greatly minimize the risk of stray current
r- corrosion on ductile iron pipe.
rC Page 3
f-
Polyethylene encasement is recommended for the entire project
due to low soil resistivity and potential stray current interference.
Total footage is 11,994'.
The installation procedures and material specifications for
polyethylene encasement are outlined in ANSI/AWWA C105/A21.5
Standard, (See Exhibit 111.
The foregoing report and recommendations are based upon
examinations and tests which were made in accordance with generally
accepted professional engineering standards and considered necessary
in the circumstances.
By:
Regional Engineer
. ,
. . ., .:
.iml
w.
.
II I : ti !i ” .
.I \I\
Xl’ I *. f I
\\\ 1 .,\\Q.?q ;
.e OJ
f7
’ . . .i I
:.&
1L
-
I
_-
I u -m . . 1. I& a
.e s ‘. . w 1 ::. ,, . ,o :-a?~ .:. .~ ,’ .a “. u.f-:I’
2 D. ‘Q,. . . . z .I .
2:
. .~,
;.~‘a _’ s .‘- a .-
:z-.
k ~0 )I)
. .
. 43 ,
: ’
-I ‘.,
is 0: ..
ts ’
5 ,a 0
6
qp&&J = ., & - I . /IIF -- . . .
.
+
s,
+ +r
%
./.. - . -
? .\
q,
‘-
/ /
ANSIJAWWA C105/A21.5-82
[Revision of ANSI/AWWA C105-72 (R77)]
B
for
POLYETHYLENE ENCASEMENT FOR DUCTILE-IRON PIPIl$iF&X3sWATER AND OTHER
ADMINISTRATIVE SECRETARIAT
AMERICAN WATER WORKS ASSOCIATION
CO-SECRETARIATS
AMERICAN GAS ASSOCIATION
NEW ENGLAND WATER WORKS ASSOCIATLON
First edition appraved by American National Skmdards lnstiture. Inc., Dec. 27. 1972.
Revisededirion approvedby American Narionol Smndards Instirute. Inc.. May26 1982.
Published by
AMERICAN WATER WORKS ASSOCIATION 6666 West Quincy Avenue, Denver, Colorado 80235
I
American National Standard
An American National Standard implies a consensus of those substantially concerned with its scope and provisions..An American National Standard is intended as aguide to aid the manufacturer, the Consumer, and the general public. The existence of an American National Standard does not in any respect preclude anyone, whether he has approved the standard or not, from manufacturing, marketing, purchasing, or using
products, processes, or procedures not conforming to the standard. American National
Standards are subject to periodic review, and users are cautioned to obtain the latest
editions. Producers of goods made in conformity with an American National Standard are encouraged to state on their own responsibility in advertising and promotion material or on tags or labels that the goods are produced in conformity with particular American National Standards. CAUTION NOTICE. Thii American National Standard may be revised or
withdrawn at any time. The procedures of the American National Standards Institute require that action be taken to reaffirm, revise, or withdraw this standard no later than five (5) years from the date of publication. Purchasers of American National Standards may receive current information on all standards by calling or writing the American National Standards Institute, 1430 Broadway, New York, N.Y. 10018, (212) 354-3300.
I
Copyright e 1982 by Am&an Water Works Association Printed in USA
ii
Committee Personnel
Subcommittee 4, Cast-Iron Pipe and Fittings, which reviewed this standard, had the following personnel at that time:
TROY F. STROUD, Chairman
KENNETH W. HENDERSON, Vice-Chairman
User Members Producer Members
S. C. BAKER A. M. HORTON
B. W. FRANKLIN J. P. JOHNSON
K. W. HENDERSON HAROLD KENNEDY JR.
R. C. HOLMAN J. H. MILLER
M. G. HOOVER J. H. SALE
D. A. LINCOLN T. F. STROUD
W. H. SMITH T. B. WRIGHT
Standards Committee A21, Cast-Iron Pipe and Fittings, which reviewed and approved this standard, had the following personnel at the time of approval:
ARNOLD M. TINKEY, Chairman
THOMAS D. HOLMES, Vice-Chairman
JOHN I. CAPITO, Secretary
Organizotion Represented American Gas Association American Society for Testing and Materials American Water Works Association
Name of Representative H. J. FORR
GEORGE LUCIW*
G. S. ALLEN
R. A. ARTHUR
D. R. BOYD
J. I. CAPITO*
K. W. HENDERSON
a *Nonvoting liaison
111
Committee Personnel (continued)
American Water Works Association
Canadian Standards Association Ductile Iron Pipe Research Association
Manufacturers’ Standardization Society of the Valve and Fittings Industry Naval Facilities Engineering Command
New England Water Works Association
Underwriters’ Laboratories, Inc.
M. G. HOOVER
R. J. Kocot.
G. M. KRALIK
D. M. KUKUK
R. L. LEE
J. H. MILLER
W. H. SMITH
A. M. TINKEY
D. L. TIPPIN
THURMAN UPCHURCH
L. W. WELLER
w. F. SEMENCHUK*
T. D. HOLMES
HAROLD KENNEDY JR.
P. I. MCGRATH JR.
L. L. NEEPER
T. F. STROUD
T. C. JESTER
s. C. BAKER
ALBERT HELT
w. CAREYt
L. J. DOSEDLO
*Nonvoting liaison
tAkemate
iv
Table of Contents
SEC.
Fanward
1. History of Standard . .
Il. History of Polyethylene Encasement.
III. Research . IV. Useful Life of Polyethylene
V. Exposure to Sunlight . VI. Options . , .
VII. Major Revisions .
standaml
5-1 scope..........................
5-2 Definition. . . . 5-3 Materials . . . .
PAGE
VI
VI
vii
vii vii
vii
vii
SEC.
5-4 Installation. . . .
T..M9
5.1 TubeandSheetSizes . . . . . . . . .
fwm
5.1 Method A . . . . . . . . . . . . . . . . . . .
5.2 Method B . .
5.3 Method C . .
AppemUxA . . . . . . . . . . . . . . . . . . . .
Appendfx Table
A. I Soil-Test Evaluation
PAGE
2
2
3
. 3
3
5
7
Foreword
lkis foreword is for information only and is not a part of ANSI/A WWA Cl05
I. History of Standard
In 1926, ASA (now ANSI) Committee A21, Cast-Iron Pipe and Fittings, was organized under the sponsorship of AGA, ASTM, AWWA, and NEWWA.
The current sponsors are AGA, AWWA,
and NEWWA, and the present scope of Committee A21 activity is standardiza-
tion of specifications for cast-iron and
ductile-iron pressure pipe for gas, water,
and other liquids, and fittings for use with
such pipe. These specifications are to
include design, dimensions, materials, coatings, linings, joints, accessories, and methods of inspection and test.
In 1958, Committee A21 was reorgan- ized. Subcommittees were established to
study each group of standards in accor- dance with the review and revision policy
of ASA (now ANSI). The present’scope
of Subcommittee 4, Coatings and Lin-
ings, is to review the matter of interior and exterior corrosion of gray and ductileiron pipe and fittings and to draft standards for the interior and exterior protection of gray and ductile-iron pipe
and fittings.
In accordance with this scope, Sub-
committee 4 was charged with the respon-
sibility for: 1. Development of standards on polyethylene encasement materials and their installation as corrosion protection,
when required, for gray and ductile cast- iron pipe and fittings. 2. Development of procedures for the investigation of soil to determine when polyethylene protection is indi-
cated.
In response to these assignments, Sub- committee 4 has:
Developed ANSI A21.5-1972
(Ak’WA ClOS-72), Standard for Poly-
ethylene Encasement for Gray,and Duc-
tile Cast-Iron Piping for Water and Other Liquids.
2. Developed Appendix A outlining soil-investigation procedures. In 1976, Subcommittee 4 reviewed the 1972 edition and submitted a recommen-
dation to Committee A21 that the stand-
ard be reaffirmed without change from
the 1972 edition, except for the updating of this foreword.
In 1981, Subcommittee 4 again reviewed the standard. The major revi- sions incorporated into the current edi- tion as a result of that review are listed in Sec. VII of this foreword.
II. History of Polyethylene Encase-
ment
Loose polyethylene encasement was first used experimentally in the United States for protection of cast-iron pipe in corrosive environments in 1951. The first
vi
POLYETHYLENE ENCASEMENT FOR DUCTILE-IRON PIPING vii
field installation of polyethylene wrap on
cast-iron pipe in an operating water sys- tem was in 1958 and consisted of about
600 ft (180 m) of 12-in. pipe installed in a waste-dump fill area. Since that time,
hundreds of installations have been made
in severely corrosive soils throughout the
United States in pipe sires ranging from
454 in. in diameter. Polyethylene encase- ment has been used as a soil-corrosion preventative in Canada, England, France, Germany, and several other countries since development of the procedure in the United States.
III. Research
Research by the Cast Iron Pipe Research Association (CIPRA)* on sev-
eral severely corrosive test sites has indi-
cated that polyethylene encasement
provides a high degree of protection and
results in minimal and generally insignifi- cant exterior surface corrosion of gray and ductile cast-iron pipe thus protected. Investigations of many field installa- tions in which loose polyethylene encase- ment has been used as protection for gray and ductile cast-iron pipe against soil cor- rosion have confirmed CIPRA’s findings with the experimental specimens. These
field installations have further indicated
that the dielectric capability of polyethyl- ene provides shielding for gray and duc- tile cast-iron pipe against stray direct current at most levels encountered in the
field.
IV. Useful Life of Polyethylene
Tests on polyethylene used in the pro- tection of gray and ductile cast-iron pipe have shown that after 20 years of expo- sure to severely corrosive soils, strength
loss and elongation reduction are insignif- icant. Studies by the Bureau of Reclama-
*CIPRA became the Ductile Iron Pipe Research
Association in 1979.
tion of the US Department of the
Interiort on polyethylene film used underground showed that tensile strength was nearly constant in a 7-yr test period
and that elongation was only slightly affected. The Bureau’s accelerated soil-
burial testing (acceleration estimated to be live to ten times that of field condi- tions) showed polyethylene to be highly resistant to bacteriological deterioration.
V. Exposure to Sunlight
Prolonged exposure to sunlight will
eventually deteriorate polyethylene film. Therefore, such exposure prior to back- tilling the wrapped pipe should be kept to a minimum. If several weeks of exposure prior to backfilling are anticipated, Class C material should be used (see Sec. 5- 3.1.1).
VI. options
This standard includes certain options, which, if desired, must be specified. These options are: 1. Color of polyethylene material (Sec. 5-3). 2. Installation method-A, B, or C (Sec. 54)-if there is a preference.
VII. Major Revisions
The major revisions in this edition con- sist of the following: 1. Reference to gray cast-iron pipe in the title and throughout the standard was deleted because gray iron pipe is no
longer produced in the United States. 2. Metric conversions of all dimen- sions are included in this standard. Metric dimensions are direct conversions of cus- tomary US inch-pound units and are not
those specified in International Organiza-
tion for Standardization (ISO) standards.
tlaboratory and Field Investigations of Plastic
Films, US Dept. of the Interior. Bureau of Reclama-
tion, Rept. No. ChE-82 (Sept. 1968).
ANSVAWWA ClO5/A21.5-82
[Revision of ANSI/AWWA ClO5-72 (R77)]
Amerfcen NaUonel Standard for
Polyethylene Encasement for
Ductile-Iron Piping for Water and Other Liquids
sec. 5-1 Scope
This standard covers materials and
installation procedures for polyethylene
encasement to be applied to underground
installations of ductile-iron pipe. This
standard also may be used for polyethyl- ene encasement of fittings, valves, and
other appurtenances to ductile-iron pipe
systems.
Sec. 5-2 Deflnltkm
5-2.1 Polyethylene encasement: The encasement of piping with polyethyl-
ene film in tube or sheet form.
Sec. 5-3 Materlals
5-3.1 Polyethylene. Polyethylene film shall be manufactured of virgin
polyethylene material conforming to the following requirements of ASTM Stand- ard Specification D-1248-78-Polyethyl-
ene Plastics Molding and Extrusion Materials:
I
5-3.1.1 Raw material used to manic
facture polyethylene film. Type: I
Class: A (natural color) or C (black)
Grade: E-l
Flow rate (formerly melt index):’
0.4 maximum
Dielectric strength: Volume resistivity,
minimum ohm-cm-’ = 10’5
5-3.1.2 Polyethylene film. Tensile strength: 1200 psi (8.3 MPa) minimum Elongation: 300 percent minimum Dielectric strength: 800 V/mil (31.5 V/pm) thickness minimum
5-3.2 Thickness. Polyethylene film
shall have a minimum thickness of 0.008
in. (8 mil, or 200 wm). The minus toler-
ance on thickness shall not exceed 10 per-
cent of the nominal thickness.
5-3.3 Tube size or sheet width. Tube size or sheet width for each pipe diameter shall be as listed in Table 5.1.
2 ANSI/AWWA CIOS/A21.5-82
TABLE 5.1
Tube and Sheet Sizes
Nominal Pipe Diameter
in.
Minimum Polyethylene Width
In. (cm)
Flat Tuk Sheet
3 14 (35) 28 (70)
4 16 (41) 32 (82)
6 20 (51) ‘lo (102)
8 24 (61) 48 (122)
10 27 (69) 54 (137)
12 30 (76) 60 (152)
14 34 (86) 68 (172)
16 37 (94) 74 (188)
18 41 (104) 82 (208)
20 45 (114) 90 (229)
24 54 (137) 108 (274)
30 67 (170) 134 (340)
36 81 (206) 162 (41 I)
42 95 (241) 190 (483)
48 108 (274) 216 (549)
54 I21 (307) 242 (615)
Sec. 5-4 InNatlatkm fashion lengthwise until it clears the pipe ends. 5-4.1 General. The polyethylene
encasement shall prevent contact between
the pipe and the surrounding backfill and
bedding material but is not intended to be
a completely airtight and watertight enclosure. Overlaps shall be secured by the use of adhesive tape, plastic string, or any other material capable of holding the polyethylene encasement in place until backfilling operations are completed. 54.2 Pip. This standard includes three different methods of installation of
polyethylene encasement on pipe. Meth-
ods A and B are for use with polyethylene
tubes and method C is for use with polyethylene sheets. 542.1 Method A. (Refer to Figure 5.1.) Cut polyethylene tube to a length approximately 2 ft (0.6 m) longer than
that of the pipe section. Slip the tube around the pipe, centering it to provide a I-ft (0.3-m) overlap on each adjacent pipe
section, and bunching it accordion-
0 11,
Lower the pipe into the trench and
make up the pipe joint with the preceding
section of pipe. A shallow bell hole must
be made at joints to facilitate installation of the polyethylene tube. After assembling the pipe joint, make the overlap of the polyethylene tube. Pull the bunched polyethylene from the preceding length of pipe, slip it over the end of the new length of pipe, and secure it in place. Then slip the end of the polyethylene from the new pipe section
over the end of the first wrap until it
overlaps the joint at theend of the preced-
ing length of pipe. Secure the overlap in place. Take up the slack width to make a snug, but not tight, fit along the barrel of the pipe, securing the fold at quarter points. Repair any rips, punctures, or other damage to the polyethylene withadhesive tape or with a short length of polyethyl- 0
POLYETHYLENE ENCASEMENT FOR DUCTILE-IRON PIPING 3
ene tube cut open, wrapped around the
pipe, and secured in place. Proceed with
installation of the next section of pipe in
the same manner. 542.2 Method B. (Refer to Figure
5.2.) Cut polyethylene tube to a length
approximately 1 ft (0.3 m) shorter than
that of the pipe section. Slip the tube
around the pipe, centering it to provide 6 in. (I5 cm) of bare pipeateachend. Make polyethylene snug, but not tight; secure ends as described in Sec. 542.1.
Before making up a joint, slip a 3-ft
(0.9-m) length of polyethylene tube over the end of the preceding pipe section, bunching it accordion-fashion length-
wise. After completing the joint, pull the
3-ft (0.9-m) length of polyethylene over the joint, overlapping the polyethylene previously installed on each adjacent sec- tion of pipe by at least 1 ft (0.3 m); make snug and secure each end as described in Sec. 542.1. Repair any rips, punctures, or other damage to the polyethylene as described
in Sec. 542.1. Proceed with installation
of the next section of pipe in the same manner.
542.3 M&rod C. (Refer to Figure
5.3.) Cut polyethylene sheet to a length
approximately 2 ft (0.6 m) longer than
that of the pipe section. Center the cut
length to provide a I-ft (0.3-m) overlap on
each adjacent pipe section, bunching it
Figure 5.1. Method A: One length of polyethylene tube for each length of pipe, overlapped at joint.
Flgure 5.2 Method B: Separate pieces of polyethylene tube for barrel of pipe and for joints. Tube over joints overlaps tube encasing barrel.
Flgure 5.2 Method C: Plpellne completely wrapped with flat polyethylene 8heet.
4 ANSI/AWWA C105/AZl.S-82
until it clears the pipe ends. Wrap the
polyethylene around the pipe so that it
circumferentially overlaps the top quad- rant of the pipe. Secure the cut edge of
polyethylene sheet at intervals of approxi-
mately 3 ft (0.9 m). Lower the wrapped pipe into the trench and make up the pipe joint with the preceding section of pipe. A shallow bell hole must be made at joints to facilitate installation of the polyethylene. After completing the joint, make the overlap as described in Sec. 542.1. Repair any rips, punctures, or other damage to the polyethylene as described in Sec. 54.2.1. Proceed with installation of the next section of pipe in the same
manner.
5-4.3 Pipe-shaped appurtenances. Cover bends, reducers, offsets, and
other pipe-shaped appurtenances with polyethylene in the same manner as the
pipe.
5-4.4 Odd-shaped appurtenances. When valves, tees, crosses, and other odd-shaped pieces cannot be wrapped practically in a tube, wrap with a tlat sheet or split length of polyethylene tube by
passing the sheet under the appurtenance and bringing it up around the body. Make seams by bringing the edges together, folding over twice, and taping down. Handle width and overlaps at joints as described in Sec. 542.1. Tape
polyethylene securely in place at valve-
stem and other penetrations.
54.5 Openings in encasement. Pro-
vide openings for branches, service taps,
blow-offs, air valves, and similar appurte-
nances by making an X-shaped cut in the polyethylene and temporarily folding back the film. After the appurtenance is installed, tape the slack securely to the appurtenance and repair the cut, as well as any other damaged areas in the polyethylene, with tape.
54.6 Junctions between wrapped
and unwrappedpipe. Where polyethyl- ene-wrapped pipe joins an adjacent pipe that is not wrapped, extend the polyethyl- ene wrap to cover the adjacent pipe for a distance of at least 2 ft (0.6 m). Secure the end with circumferential turns of tape.
54.7 Backfillforpolyethylene-
wrapped pipe. Use the same backtill material-as that specified for pipe without polyethylene wrapping, exercising care to prevent damage to the polyethylene wrap- ping when placing backfill. Backfill mate- rial shall be free from cinders, refuse, boulders, rocks, stones, or other material
that could damage polyethylene. In gen- eral, backfilling practice should be in accordance with the latest revision of AWWA C600, Standard for Installation
of Ductile-Iron Water Mains and Their
Appurtenances.
6’,
0 1’ I
Appendix A
Notes on Procedures for Soil Survey Tests and Obsewations
and Their Interpretation to Determine Whether Polyethylene
Encasement Should Be Used
This appendix is for information only and is not a part of ANSI/A WWA CIOS.
In the appraisal of soil and othercondi- tions that affect the corrosion rate of gray and ductile cast-iron pipe, a minimum number of factors must be considered. They are outlined here. A method of eval- uating and interpreting each factor and a method of weighing each factor to deter- mine whether polyethylene encasement should be used are subsequently de- scribed.
Soil Survey Tests and Observations
1. Earth Resistivity
(a) Four-pin (b) Single-probe (c) Saturated-sample 2. pH 3. Oxidation-reduction (redox) po- tential
4. Sulfides
(a) Azide (qualitative) 5. Moisture content (relative) (a) Prevalence 6. Soil description
(a) Particle size
(b) Uniformity
(4 Type (d) Color 7. Potential stray direct current (a) Nearby cathodic protection utilizing rectifiers (b) Railroads (electric) (c) Industrial equipment, includ- ing welding equipment. (d) Mine transportation equip- ment 8. Experience with existing installa-
tions in the area I. Earth resisfivity. There ate three methods for determining earth resistivity:
four-pin, single-probe, and soil-box. In the field, a four-pin determination should be made with pins spaced at approximate pipe depth. This method yields an aver- age of resistivity from the surface to a
depth equal to pin spacing. However,
results am sometimes difficult to interpret
where dry topsoil is underlain with wetter soils and where soil types vary with depth. The Wenner configuration is used in con-
5
4 ANSI/AWWA CtOS/AZl.S-82
nection with a soil resistivity meter, which is available with varying ranges of resist-
ance. For all-around use, a unit with a capacity of up to lo4 ohms is suggested because of its versatility in permitting both field and laboratory testing in most soils. Because of the aforementioned diff-
culty in interpretation, the same unit may
be used with a single-probe that yields
resistivity at the point of the probe. A boring is made into the subsoil so that the probe may be pushed into the soil at the desired depth. Inasmuch as the soil may not be typi- cally wet, a sample should be removed for resistivity determination, which may be
accomplished with any one of several laboratory units that permit the introduc- tion of water to saturation, thus simulat- ing saturated field conditions. Each of these units is used in conjunction with a soil resistivity meter. Interpretation of resistivity results is extremely important. To base an opinion on a four-pin reading with dry topsoil averaged with wetter subsoil would prob- ably result in an inaccurate premise. Only by reading the resistivity in soil at pipe depth can an accurate interpretation be made. Also, every effort should be made to determine the local situation concern-
ing groundwater table, presence of shal-
low groundwater, and approximate percentage of time the soil is likely to be
water saturated.
With gray and ductile cast-iron pipe,
resistance to corrosion through products
of corrosion is enhanced if there are dry periods during each year. Such periods seem to permit hardening or toughening
of the corrosion scale or products, which
then become impervious and serve as bet-
ter insulators. In making field determinations of resis-
tivity, temperature is important. The result obtained increases as temperature
decreases. As the water in the soil approaches freezing, resistivity increases greatly, and, therefore, is not reliable.
Field determinations under frozen soil conditions should be avoided. Reliable results under such conditions can be obtained only by collection of suitable subsoil samples for analysis under labora- tory conditions at a suitable temperature.
Interpretation of resisiivity. Because
of the wide variance in results obtained
under the methods described, it is difficult specifically to interpret any single reading without knowing which method was used. It is proposed that interpretation be based on the lowest reading obtained, with consideration being given to other
conditions, such as normal moisture con- tent of the soil in question. Because of the
lack of exact correlation between expe- riences and resistivity, it is necessary to assign ranges of resistivity rather than specific numbers. In Table A. 1, points are assigned to various ranges of resistivity. These points, when considered along with points assigned to other soil characteris- tics, are meaningful.
2. PH. In the pH range ofO.0 to4.0, the soil serves well as an electrolyte, and total acidity is important. In the pH range of 6.5 to 7.5, soil conditions are optimum for sulfate reduction. In the pH range of
8.5 to 14.0, soils are generally quite high
in dissolved salts, yielding a low soil resistivity.
In testing pH, glass and reference elec- trodes are pushed into the soil sample and a direct reading is made, following suit- able temperature setting on the instru- ment. Normal procedures are followed
for standardization.
3. Oxidation-reduction (redox) po-
tenfial. The oxidation-reduction (re- dox) potential of a soil is significant because the most common sulfate- reducing bacteria can live only under an- aerobic conditions. A redox potential
POLYETHYLENE ENCASEMENT FOR DUCTILE-IRON PIPING 7
0
0
greater than +I00 mV shows the soil to be
sufficiently aerated so that it will not sup- port sulfate reducers. Potentials of 0 to +lOO mV may or may not indicate anae-
robic conditions; however, a negative
redox potential definitely indicates anae- robic conditions under which sulfate reducers thrive. This test also is accom- plished using a pH meter, with platinum and reference electrodes inserted into the
TABLE A. 1
Soil- Test Evaluation*
Soil Charactcristicr Points
Resistivity-ohm-cm (based on
single-probe at pipe depth or
water-saturated soil box):
<700,, ....................... 10
700-1000 ......................... 8 1000-1200 ......................... 5
12w1500 ......................... 2
15004000 ......................... I
>Moo.. ....................... 0
pH: o-2 ............................... 5
2-4. .............................. 3
4-6.5 ............................. 0
6.5-7.5.. .......................... Ot
7.5-8.5.. .......................... 0
>8.5 ............................. 3
Redox potential:
>+lOOmV .................. 0
+50to+l00mV .................. 3.5
oto+50mv.. ................ .4
Negative .................. 5
Sulfides:
Positive ........................... 3.5
Trace. ............................ 2
Negative ........................... 0
Moisture:
Poor drainage, continuously wet ..... 2
Fair drainage, generally moist ....... I
Good drainage, generally dry ........ 0
*Ten points-corrosive to gray or ductile caet-
iron pipe: protection is indicated.
tlf sulfides are present and low or negative
redox-potential results are obtained, three points
shall be given for this range.
soil sample, which permits a reading of potential between the two electrodes. It
should be noted that soil samples removed from a boring or excavation can
undergo a change in redox potential on
exposure to air. Such samples should be tested immediately on removal from the excavation. Experience has shown that heavy clays, muck, and organic soils are often anaerobic, and these soils should be regarded as potentially corrosive. 4. Sulfdes. The sulfide determina- tion is recommended because of its field expediency. A positive sulfide reaction
reveals a potential problem due to sulfate-
reducing bacteria. The sodium azide-
iodine qualitative test is used. In this
determination, a solution of 3 percent
sodium azide in a 0.1 N iodine solution is introduced into a test tube containing a
sample of the soil in question. Sulfides
catalyze the reaction between sodium
azide and iodine, with the resulting evolu-
tion of nitrogen. If strong bubbling or
foaming results, sulfides are present, and the presence of sulfate-reducing bacteria is indicated. If very slight bubbling is noted, sulfides are probably present in small concentration, and the result is noted as a trace. 5. Moisture content. Since prevail- ing moisture content is extremely impor- tant to all soil corrosion, every effort must be made to determine this condition. It is
not proposed, however, to determine spe-
cific moisture content of a soil sample,
because of the probability that content varies throughout the year, but to ques- tion local authorities who are able to
observe the conditions many timesduring
the year. (Although mentioned under item 1, Earth Resistivity, this variability
factor is being reiterated to emphasize the
importance of notation.)
6. Soil description. In each investi-
gation, soil types should be completely described. The description should include
8 ANSI/AWWA ClOS/A21.5-82
color and physical characteristics, such as
particle sire, plasticity, friability, and uni- formity. Observation and testing will reveal whether the soil is high in organic
content; this should be noted. Experience
has shown that in a given area, corrosivity
may often be reflected in certain types and
colors of soil. This information is valua-
ble for future investigations or for deter- mining the most likely soils to suspect.
Soil uniformity is important because of the possible development of local corro- sion cells due to the difference in potential between unlike soil types, both of which are in contact with the pipe. The same is true for uniformity of aeration. If one segment of soil contains more oxygen than a neighboring segment, a corrosion cell can develop from the difference in potential. This cell is known as a differen-
tial aeration cell. There are several basic types of soils
that should be noted: sand, loam, silt,
clay, muck. Unusual soils, such as peat or
soils high in foreign material, also should
be noted and described.
7. Potential stray direct current. Any soil survey should includeconsidera- tion of possible stray direct current with which the gray or ductile cast-iron pipe
installation might interfere. The wides- pread use of rectifiers and ground beds for cathodic protection of underground structures has resulted in a considerable threat from this source. Proximity of such cathodic protection systems should be
noted. Among other potential sources of
stray direct current are electric railways,
industrial equipment (including welding
equipment), and mine-transportation equipment.
8. Experience with existing installa- tions. The best information on corrosiv- ity of soil with respect to gray and ductile cast-iron pipe is the result of experience
with these materials in the area in ques-
tion. Every effort should be made to
acquire such data by questioning local
officials and, if possible, by actually
observing existing installations.
Soil-lest Evaluation
When the soil-test procedures de- scribed herein are employed, the follow- ing tests are considered in evaluating corrosivity of the soil: resistivity, pH, rcdox potential, sultides, and moisture. For each of these tests, results are catego-
tired according to their contribution to corrosivity. Points are assigned based on experience with gray and ductilecast-iron
pipe. When results of these five test-
observations are available, the assigned
points are totaled. If the sum is equal to
ten or more, the soil is corrosive to gray or ductile cast-iron pipe, and protection against exterior corrosion should be pro- vided. This system is limited to soil corro-
sion and does not include consideration of stray direct current. Table A.1 lists points assigned to the various test results. General. These notes deal only with gray and ductile cast-iron pipe, the soil environment in which they will serve, and
methods of determining a need for
polyethylene encasement.
F
rest Results
Station/ a Location
1 Sta. 491 - El Camino Real.
2 Sta. 470 - El Camino Real.
3 Sta. 447 - El Camino Real.
4 Sta. 420 - El Camino Real.
5 Sta. 404 - El Camino Real.
6 Sta. 372 - El Camino Real.
EXHIBIT III
Resistivity Redox ohm-cm. mv. m
1,040 +220 7.0
440 +215 6.6
480 +228 6.9
560 +244 6.4
+242 6.6
1,080 +239 6.8
Soil sulfides DescriDtion
Negative Brown silty clay,
8’, moist.
Negative Brown clay, 5', moist.
Negative Brown clay, 5', moist,
Negative Brown clay, 5', moist.
Negative Brown clay, 5', moist.
Negative Brown silty clay, 5', moist.
DIPRA SURFACE POTENTIAL GRADIENT SURVEY PORU SC-87
pate 6-16-88 Conducted by Michael S. Tucker, P.E. L Deon Fowles, P.E_.
droject Name El Camino Real 36" DIP Transmis~sion P/S of gasline
Survey Location Carlsbad, California
Rectifier Output Dist. between anode bed h DI pipeline
Soil Resistivity in area 700 Gas pipeline owner
Phone number
Remarks Anode bed is remote - one north of project and one south
Survey Length Proposed Existing Pipe age
Pipe sizes Joint type Pipe type
sta. 441
North 25' - 16.1
North 50' - 32.1
-6.3
Sta. 485’50 Sta. 485’50
Station 6 + Or Field Direction - Reading
North 50' - 11.0
North 75' + 21.0
NorthlOO' + 5.1
S/W 25' + 27.0
S/W 50' - 7.1
s/w 75' + 2.5
DIPRA SURFACE POTENTIAL GRADIENT SURVEY FORM SC-87
y?ate - - Conducted by -1 S. Tucker. & new
Project Name El Camino Real 36" DIP Transmission P/S of gasline
Survey Location Carlsbad, California
Rectifier Output Dist. between anode bed 6 DI pipeline
Soil Resistivity in area 700 Gas pipeline owner
Phone number
Remarks Anode bed is r~~,n+n - - north of Droiect and uuth
Survey Length Proposed Existing Pipe age
Pipe sizes Joint type Pipe type
Sta. 373
1 Station &It or/ Field Direction - Reading
(mv)
South 25' + 9.9
/-.South 50' t 13.8 ,-
South 75' + 13.5
South 100' + 17.5
South 125' + 17.7
North 25' + 14.5
North 50' + 22.G
Ncrth 75' + 20.5
North 100' + 21.4
Sta. 401
IStation &I+ or! Field 1 Station & + or Field
Direction - ReadinS