Description: ANGEL: 638 SF DETATCHED ADU (CONVERTING HOBBY ROOM)
FEE
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
Property Owner:
TODD ANGEL
2210 S PENINSULA DR
DAYTONA BEACH, FL 32118
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
GREEN BUILDING STANDARDS PLAN CHECK & INSPECTION
MECHANICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
PLUMBING BLDG RESIDENTIAL NEW/ADDITION/REMODEL
581473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-RESIDENTIAL
Total Fees: $798.46 Total Payments To Date: $798.46
{city of
Carlsbad
Permit No: CBR2020-0260
Status:
Applied:
Issued:
Finaled Close Out:
Inspector:
Final Inspection:
Balance Due:
Closed -Finaled
02/03/2020
08/26/2020
PDrei
03/24/2021
AMOUNT
$278.00
$194.60
$41.00
$175.00
$42.00
$62.00
$2.00
$3.86
$0.00
Please take NOTICE that approval of your project includes the 11 lmposition11 of fees, dedications, reservations, or other exactions hereafter
collectively referred to as 11fees/exaction.11 You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
c·cicyof
Carlsbad
RESIDENTIAL
BUILDING PERMIT
APPLICATION
B-1
Plan Check
Est. Value
PC Deposit ---------..,. "'-;z.o Date~"'"'---"'°''---'------
JobAddress )iJ\] e'{\,,e_ Suite: _____ APN: __________ _
CT/Project #: __________________ Lot#: ___ _
Electrical Panel UpgradeG/ no Fire Sprinklers: yes G:) Air Conditioning: yes JG)
BRIEF DESCRIPTION OF WORK: ____________________________ _
ltJ, Addition/New: &_ '.3~ Living SF, Deck SF, ___ Patio SF, _____ Garage SF
Is this to create an Accessory Dwelling Unit?@ No New Fireplace? Yes {§,if yes how many? __
0 Remodel: _____ SF of affected area Is the area a conversion or change of use ? Yes/ No
0 Pool/Spa: ____ SF Additional Gas or Electrical Features? ____________ _
□ Solar: ___ KW, ___ Modules, Mounted: Roof/ Ground, Tilt: Yes/ No, RMA: Yes/ No, Battery: Yes/ No
Panel Upgrade: Yes/ No
D Reroof: ___________________________________ _
D Plumbing/Mechanical/Electrical Only:
D Other:-----------------------------------
APPLICANT (PRIMARY fONTACT
Name: ~ 14-v---12
Address: 3 lfii I vle.
City: ~8~ State: C\,A Zip: 't'UVt'.)
Phone: 7/§, 2.2J./-5;RJ2.--2
Email: ±'l~e I 0 fXJ<e.,e.x d.. Coyy,
DESIGN PR
Name:_..LJ..!.Bd.:~:l,-__t.!...!w),l,!~~-----
Email:-==-'-'-''-""'"'--'""""=-'-"'=-="'--'=-"-'----
Architect State License: ___________ _
City: ~,q.=~=---:c-:,---·
Phone: _JJ.!!JQL~'=t::l:2~£ ________ _
Email: _.I'.:!.!.!!4:g_~J.2,~2-!:~~•c_:c(.)~,,.,L--------
CONTRACTOR BUSINESS
Name: _ _,_~-----------------
Address: ___________________ _
City: ________ State: ___ .Zip: ______ _
Phone: ___________________ _
Email: __________________ _
State License: ______ Bus. License: ______ _
(Sec. 7031.S Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he/she is licensed pursuant to the provisions of the Contractor's License Law
{Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}).
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
B-1 Page 1 of 2 Rev. 06/18
( OPTION A): WORKERS'COMPENSATION DECLARATION:
I hearby affirm under penalty of perjury one of the following declarations:
□ I have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the labor Code, for the performance of the
work which this permit is issued.
□ I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: ______________________ _
Policy No. ______________ Expiration Date: _________ _
□ Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to be come
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage Is unlawful, and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
CONTRACTOR SIGNATURE: □AGENT DATE: ----------------------------------
( OPTION B ): OWNER-BUILDER DECLARATION:
iereby affirm that I am exempt from Contractor's License Law for the following reason:
, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
44, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such work
himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
□ I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
□ I am exempt under Section ________ ,Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. □ Yes □ No
2. I {have/ have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (firm) to provide the proposed construction (include name address/ phone/ contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address/ phone/
contractors' license number):
5. I will provide some of the work, but I have contracted (hired the following persons to provide the work indicated (include name/ address/ phone type of work):
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
lender's Name: ______________________ Lender's Address: _____________________ _
ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? □ Yes □ No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? □ Yes □ No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? □ Yes □ No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES ANO THE AIR POLLUTION CONTROL DISTRICT.
APPLICANT CERTIFICATION:
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP
HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF
THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over S'O' deep and demolition or construction of structures over3 stories in height.
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void if the building or work authorized
by such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such permit is suspended or abandoned at any time
after the work is commenced eriocl of 180 da s (Secti n 106.4. · arm Building Code).
APPLICANT SIGNATURE: _J,__3:~k:j~(.__J.'..._ __________ DATE: _:z_,_/3::.,/._2<J_ZCJ ___ _
1635 Faraday Ave Carlsbad, CA 92008
B-1
: 760-602-2719 Fax: 760-602-8558
Page 2 of2
Email: Building@carlsbadca.gov
Rev. 06/18
PERMIT INSPECTION HISTORY for (CBR2020-0260)
Permit Type: BLDG-Residential Application Date: 02/03/2020 Owner: TODD ANGEL
Work Class: Second Dwelling Unit Issue Date: 08/26/2020 Subdivision: PATTERSONS ADD
Status: Closed -Finaled Expiration Date: 08/26/2021 Address: 1317 PINE AVE
IVR Number: 24592 CARLSBAD, CA 92008
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Re Inspection Inspection
Date Start Date Status
Wednesday, March 24, 2021 Page 2 of 2
Cicyof
Carlstiad
OWNER-BUILDER
ACKNOWLEDGEMENT
FORM
M1
Development Services
BuikRncl)fvfsk,n
163S f~Avenoe
760-002•2719
www.c.artsbadc.a.gov
OWNER-BUILDER ACKNOWLEDGMENT FORM
To: Property OWner
Ari applbtion ffK construction permll(s) has be'en submitted in your ~me listlnt you .u the owner-builder of the
l)<ope,ty located at:
Site Address 1317 Pine Ave Cartsbad CA 92008
The Oty of ~rlsbad t•oty"') Is pr0Yld1n9 you with this Owner-8uilder Acknowledgment and Verification form
to Inform you of the r~billties and the poss.Ible risks assodited with typical consttuctlon activities Issued
in your nfflM! as the 0Wner-8uilder.
The City wm not Issue a coostructlon permit until you have read and Initialed your undermndin1 of each
provision in the Property OWnet Admowtedgment Metfon below and sign the fMm. Alt apnt ol the owner
cannot eaaate this ftOtlce unless~. the pr..-,tyoww, c:omplet,I the Ownef's AudM.Mlnd A,eflt form and
it ls accepted. by the Qty of cart:sbM.
INSTRUCTIONS: Please re.rd and Initial e.ic:h stmment ~ow to adcnowtedge your understanding and
verification of this lnfonnatfon by 5icnature at the bottom of the form. These are very important construction
refated Ktnowled&ments designed to inform the property owner of his/her obligtltions retated to the reiquested
permit actnrit~.
I. TA I undem~d a frequent priKtlce of unlicensed contractors Is to haw the prOJ)fftV ~r obtain an ·Owner
8ulfdet"' building permit thtlt erronltOUSty 1mplie$ that the property owner Is pr0111dlng his or her own labor and
material personally. I, as an Owner--8ultdff, may be ~d liable and subject to serious financial risk for arry injuri~
wst.ained by an unlicensed contractor and htS or her employees wti.le wort.,ng on my property. My homeowners
insurance may-not prOYlde coverage for those mJuries. I am willfully actlna as an Owner-Buildtt and am -,ware of
the hm1ts of my msurance coverage fo, injuries to workers on my property.
II. TA I u~tand buildln, ~lts are not required to be Signed by property ow~rs unless t~ are responsible
fOf the construction and ¥e not hlnr,g -, licensed contractor to assume th s responstbtlity.
Ill TA I un~rsund n a.n •owner•8u,lder"' tam the responsible party of record on th« permit. I under$tand that t
may protect mysetf from potential fiNoci~ risk by hiring a licensed contractor and ha"'r,g the permit filed in his
or her Nme instead of my own.
IV TA I understand contractors are required by law to be licensed and bonded In Calitomi.l and to list the T license
numbers on permits and contracts.
V. TA I understand if I employ or otherwise engage any pen.ons, other than Callfornla licensed contractors, and
the total vaJue of my construction is at least five hundred dollar$ {$SOO), indudin& labor and materials, 1 may be
considered •n "employer" under st~e and tede~ law.
Owner-Builder Adcnowk!dgement Continued
VI. TA I understand if I am co~dered an *employer· under state and federal law, I mun regis.ter with the ~late
and federal government, withhold payroll taxes, provide workers' compensation disablTlty lnsur.1nce, and
contribute to unemployment compensation for each *emptoyff. • I also understand my failure to abide by these
laws may subject me to serious financial risk.
VII TA I undentand under Califomia Contractors' State Lice~ Law, an Owner Builder who builds siogl~ family
residential structures cannot legally buiJd them with the intent to offer them for ~le. unras ;di work ts perfocmed
by ficensed subcontratton and the number of structures does not uc:eed four wlth,n arry alencur ye111, or an of
the wort is performed under contract with a fkensed genenil budding c:ontractof.
VIII TA I understand as an Owner Builder if I sell the property for which this permit IS issued, I may be htfd bble
for any financial or personal injuries sustained by any subsequent ownl!f(s) which result from any latent
construction defe-cts in the won:m.anshlp or materials.
IX TA I under..tand I may obtain more info,mabon reganfina my obliptJons as an •employer-from the Internal
Revenue Ser.nee, the United States Small Business Administration, the Cailifom~ Department of Benefit
Payments, and the Califomia Division of Industrial Accidents. I also undentand I may contact the Cahfom,a
Contractors' State Uce-n~ Board (CSU) at 1-800-321-CSLB (2752t or -w.cstb ca.gov for more information
about licensed COf'ltrac:tors.
X. TA I am aware of and coment to an Owner-8uilder buifdint permit applied fof In my n.,me, .ind undentand
th~ 1 am the party lqally and flnanc.ialty responsible for proposed construction Ktivity at the follow,ng addr~s ·
XI. TA I agrtt that. as the party legally and flnanoally responsibf efor this proposed construction activity. 1 will abide
by all appJtcable laws and require~nts that aovem Owner-8Uildt'rs as wetl u employers.
ltll TA I agree to notify the Issuer of this form Immediately of any additions. deletions, or changes to any of the
information I ha~ prollided on this form.
Ucenst'd contractol'$ are regulated by hrws desllned to protect the public. If you contract with someone who
does not have a license, the Contractor's State License Board may be unable to as.sist you with any financial toss
you may sustain u a result of a complaint. Your only remedy against unlicensed Contracton may bl! in civil coun.
It Is aJso tmpo,Unt for you to understand that if an unlicensed Contractor or empfoyff of that Individual or fwm
is in1ured while worting on your property, you may be held liable for damaees. ff you obtain a permit ~ <>virMr-
Buixkr and wish to hire contnletors. )'OU wiD be responsible for verlfyint whethet or not those contnM:tors are
properly licensed and the sntus of their workers' compensation ca11en1ge. ·
IWfa,e o buildillQ IH!rmit a,n M Issued, this form must ~ camplt!tttl, slgMd by the propt!rty OWMr and rt:turMd
to tM Cit,, of Carlsbad Build/NJ DNlslon.
,~.,...,_p,Mlllitof t,f ,-,ur, ffl« IMW,,.,. OtWI .... stawt J 11/flHt! •~-,;ro,,,t#d o,t CM /«ffi .W tll« "'t' ~ lftdudinO...,
~ to SlllJt INJ}omt. • OW mrl Qllrl'l!rt I --tllfllt 11-ft 11w ~ ID conwli lllltll ,.,.a/Ulllid pno,to~ vi.fvrwl, Mil I,-
(Mer (IJ c01Wllrtld ...at JtflolCOIIIWJ pnor ID_.., rNs for,,, or(lt "-~.,,,. rif1l,t. lit ai,;ilftiJ tNs 1-...,.,.,, ,,.. otMa of -.,r--,t
Todd Angel --------Property Owner Name (PRINT)
2
Building Permit Inspection History Finaled
(City of
Carlsbad
Permit Type:
Work Class:
Status:
Scheduled
Date
01/12/2021
01/29/2021
03/24/2021
PERMIT INSPECTION HISTORY for (CBR2020-0260)
BLDG-Residential Application Date: 02/03/2020
Second Dwelling Unit Issue Date: 08/26/2020
Closed -Finaled Expiration Date: 08/26/2021
IVR Number: 24592
Owner: TODD ANGEL
Subdivision: PATTERSONS ADD
Address: 1317 PINE AVE
CARLSBAD, CA 92008
Actual Inspection Type Inspection No. Inspection Primary Inspector Reinspectlon Inspection
Start Date Status
01/12/2021 BLDG-84 Rough 147991-2021 Failed Peter Dreibelbis
Combo(14,24,34,44)
Checklist Item
BLOG-Building Deficiency
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout
BLDG-34 Rough Electrical
BLDG-44
Rough-Ducts-Dampers
COMMENTS
Has electrical issues, and building has to
be brought up to code
01/29/2021 BLDG-84 Rough
Combo(14,24,34,44)
149448-2021 Failed Tony Alvarado
Checklist Item
BLDG-Building Deficiency
BLDG-Building Deficiency
COMMENTS
Has electrical issues, and building has to
be brought up to code
January 29, 2021: (Building deficiencies).
ADU not approved.
1. Accessory dwelling unit originally
constructed without Community
development department clearances,
approvals, or permits.
2. Electrical, plumbing, mechanical,
residential building code minimum
clearance, title 24 lighting-energy and fire
life safety requirements need to be
addressed prior to final building occupancy
sign-off.
3. Inform owner Todd Angel and contractor
representative Michael, regarding
electrical, mechanical, and plumbing items
to be repaired or modified/altered prior to
building Inspector final occupancy
clearance.
03/24/2021 BLDG-Final Inspection 153345-2021 Passed Tim Kersch
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
COMMENTS
Relnspectlon
Passed
No
No
No
No
No
Relnspectlon
Passed
No
No
Passed
Yes
Yes
Yes
Yes
Yes
Incomplete
Incomplete
Complete
Wednesday, March 24, 2021 Page 1 of 2
DATE: 8/25/2020
JURISDICTION: Carlsbad
-01..GO
PLAN CHECK#.: cbR-2020-260
✓• EsG1I
A SAFEtJuilt Cmnr,any
SET III
PROJECT ADDRESS: 1317 Pine
PROJECT NAME: Convert Garage to ADU
□ APPLICANT
□ JURIS.
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted: (by:~
Telephone#:
Email:
Mail Telephone Fax In Person
~ REMARKS: set Ill was submitted as 8x11 energy design sheets. set II is being approved with
() jupplemental energy design. Applicant to provide energy design to the city to match plan set
~,t"being approved.
By: Richard Moreno Enclosures:
EsGil
8/13/2929
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
✓• EsG1I
A SAFfbuitrCompany
DATE: 2/28/2020
JURISDICTION: Carlsbad
PLAN CHECK#.: cbR2-2020-260
PROJECT ADDRESS: 1317 Pine
PROJECT NAME: Convert Garage to ADU
SET: I
-~T /tiJC;~GAN
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
[g] The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
[g] The applicant's copy of the check list has been sent to:
Todd Angel
D EsGil staff did not advise the applicant that the plan check has been completed.
[g] EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Todd Angel Telephone#: 760-224-8822
Date contacted: 2./;;;,)c€J (b~ ) Email: tangel@pacex1.com
Mail Telephone Fax In Person
0 REMARKS:
By: Richard Moreno
EsGil
2/3/2020
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad cbR2-2020-260
2/28/2020
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK#.: cbR2-2020-260
PROJECT ADDRESS: 1317 Pine
FLOOR AREA:
638 sq-ft
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 2/28/2020
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
STORIES: 1
HEIGHT: n/a
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 2/3/2020
PLAN REVIEWER: Richard Moreno
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2019 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2018 IRC, 2018 IBC,
2018 UPC, 2018 UMC and 2017 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2018 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad cbR2-2020-260
2/28/2020
PLANS
1. The following note should be given with each correction list:
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil is complete.
2. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
3. Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 2019 California Residential Code, which adopts the 2018 IRC,
2018 UMC, 2018 UPC and the 2017 NEC. Section R106.1.
STANDARDS FOR PLANS AND DRAWINGS
4. Paper Size --For most plans, select one of the following sizes: 18" x 24", 24" x
36", or 30" x 42". For sign permit drawings, 8 1/2 "x 11" or 8 1/2" x 14" is
preferred. For single-family no sensitive clearing and grading, 11" x 17". For
small building projects, 11" X 17" will be accepted as long as the detail is
sufficient and readable. Be consistent; don't mix sizes of drawings (exception:
maps for recording). Do not attach information with clips, tape, or staples.
5. Lettering on sheets must never be less than 1/8-inch in height.
6. Drawing Quality --The drawing should be easy to read, with all lines and letters
dark enough to provide good contrast with the paper. Brown line prints, pencil
drawings (including corrections or alterations), and microfilm copies of plans
cannot be accepted
Carlsbad cbR2-2020-260
2/28/2020
7. Scale --Be consistent and indicate your scale using a bar symbol (for plan
reproduction integrity). All site drawings are to be in a scale of 1" = 10', 1" = 20',
or 1" = 30'. Architectural building plans and elevations are to be 1 /8" = 1' or 1 /4"
= 1 ', with 1 /6" = 1' or 1 /20" = 1' for larger structures. In certain cases, staff may
approve use of a smaller scale before plan preparation.
8. Show the required ventilation for attics (or enclosed rafter spaces formed where
ceilings are applied directly to the underside of roof rafters). The minimum vent
area is 1/150 of attic area (or 1/300 of attic area if at least 40% (but not more
than 50%) of the required vent is located no more than 3' below the ridge) and
remaining vents located at the lower third of the of the attic space. Show on the
plans the area required and area provided. Section R806.2.
a) When using a radiant barrier, California energy design affects the attic
ventilation area requirement: If using the Prescriptive method for energy
compliance, then the attic vent area must be at the 1 /150 area: If using
the Performance method, either the 150 or 300 areas may be used, as
documented on the energy forms. Section RA4.2.1.
9. For garage conversions: CRC Section R506 requires a vapor retarder for all
slabs below conditioned space. Please provide verification that a vapor retarder
was installed at the time of construction; or demonstrate how slab will be
moisture-proofed. Include product manufacturer, method of application, and ICC
(or equal) approval.
MECHANICAL
10. Show on the plans the location, type and size (Stu's) of all heating and cooling
appliances or systems.
11. Every dwelling unit shall be provided with heating facilities capable of maintaining
a room temperature of 68 degrees F at a location 3 feet above the floor and 2
feet from exterior walls in all habitable rooms. Show basis for compliance. CRC
303.10.
12. Detail the dryer exhaust duct design from the dryer to the exterior. The maximum
length is 14 feet with a maximum of two 90-degree elbows or provide the
manufacturer's duct length specification description on the plans: Include the
dryer specifications (manufacturer, model, and fuel type) as well as the duct
description (size and type). CMC Section 504.4.2.1.
13. Show how makeup air will be provided for the washer and dryer enclosure. The
code requires an opening with a minimum of 100 square inches of makeup air
(can be louvered door). CMC 504.4.1
Carlsbad cbR2-2020-260
2/28/2020
ELECTRICAL
14. Show on the plan the amperage of the electrical service, the location of the
service panel and the location of any sub-panels. If the service is over 200
amperes, submit a single line diagram, panel schedules, and provide service
load calculations.
15. A receptacle outlet must be installed in every kitchen, family room. dining room,
living room, sunroom. parlor, library, den, bedroom, recreation room, and similar
room or area so that no point along the wall space is more than 6 feet, measured
horizontally along the floor line, from a receptacle outlet CEC 210.52(A)
16. Include on the plans the following specifications for electrical devices installed in
dwellings: CEC Article 210 & 406
a) Tamper resistant receptacles for all locations described in 210.52 and
550.13.(i.e. all receptacles in a dwelling).
b) Weather resistant type for receptacles installed in damp or wet locations
(outside). 406.4(0)(6).
c) Arc-fault protection for all outlets (not just receptacles) located in rooms
described in NEC 210.12(A): Kitchens, laundry areas, family, living,
bedrooms, dining, halls, etc.
d) GFCI protected outlets for locations described in NEC 210.8(A): Laundry
areas, kitchen dishwashers, kitchens, garages, bathrooms, outdoors,
within 6' of a sink, etc.
17. Per CEC Article 210.11 (C) 1, note on the plans that there will be a minimum of 2
small appliance branch circuits within the locations specified in Article 210.52(6),
i.e., kitchen and dining areas.
18. Per CEC Article 210.11 (C)3, note on the plans that bathroom circuiting shall be
either:
a) A 20-ampere circuit dedicated to each bathroom, or
b) At least one 20 ampere circuit supplying only bathroom receptacle outlets.
19. Show on the plans a wall receptacle within 36" of each lavatory in the bathroom.
CEC 210.52(0).
20. An ADU may have a separate utility service installed, or sub fed via existing
service with adequate capacity. ADU's require electrical load calculations per CEC
220.83 to justify existing electrical service size is adequate.
21. A separate (detached building with a separate foundation and slab) ADU requires
a separate ground electrode system per CEC 250.32
Carlsbad cbR2-2020-260
2/28/2020
22. Show at least one wall switch-controlled lighting outlet to be installed at the
exterior side of outdoor entrances or exits. CEC Article 210.70.
PLUMBING
23. Show water heater size (1st hour rating), type, and location on plans. Note: For
both new dwellings and additions the Energy Standards (150.0(n)) requires a gas
input rating of 200,000 Btu for both tank and instantaneous gas water heaters.
(Also) Provide a gas piping design for the gas system.
24. Note on the plans that "combustion air for fuel burning water heaters will be
provided in accordance with the Plumbing Code".
25. Specify on the plans: Water conserving fixtures: New water closets shall use no
more than 1.28 gallons of water per flush, kitchen faucets may not exceed 1.8
GPM, lavatories are limited to 1.2 GPM, and showerheads may not exceed 1.8
GPM of flow. CPC Sections 407,408,411,412.
26. Specify on the plans whether the existing house was built before or after 1994.
For additions or improvements to a residence built before 1994, note on the
plans that existing "noncompliant" fixtures (toilets that use more than 1.6 gallons
of water per flush, urinals that use more than one gallon of water per flush,
showerheads that have a flow capacity of more than 2.5 gallons of water per
minute, and interior faucets that emit more than 2.2 gallons of water per minute)
shall be replaced. Certification of compliance shall be given to the building
inspector prior to final permit approval. California SB407.
ENERGY CONSERVATION
27. For plans submitted for plan check on or after 1/3/2020, provide an energy
design detailing compliance with the Mandatory Measures and either the
Performance or Prescriptive Methods of compliance. The Prescriptive design
and the latest Performance software programs are available at:
http://www.energy.ca.gov/title24/2019standards/index.html
28. All domestic hot water piping to have the following minimum insulation installed:
½" pipe (1/2" insulation);¾" pipe (1" insulation); 1" to 1-½" pipe (1-½"
insulation). CPC 609.11 & ES 150.00)
a) Additionally, the ½" hot water pipe to the kitchen sink, and the cold-water
pipe within 5' of the water heater both require 1" minimum insulation. ES
150.OG)
Carlsbad cbR2-2020-260
2/28/2020
Residential Energy Lighting Requirements: ES 150.0(k)
29. All installed luminaires shall be high-efficacy in accordance with ES TABLE
150.0-A.
a) Luminaries must have a label certified for airtight construction.
b) Light sources that are not marked "JAB-2019-E" shall not be installed in
enclosed luminaires. ES 150.0(k)
30. In bathrooms, garages, laundry rooms, and utility rooms at least one luminaire
shall be controlled by a vacancy sensor.
31. Dimmers or vacancy sensors shall control all LED style luminaires. Two
exceptions: Fixtures installed in hallways or (closets under 70 square feet).
32. Recessed can light fixtures shall be IC listed, air-tight labeled, and not be
equipped with a standard medium base screw shell lamp holder. ES 150.0(k)
33. SFD outdoor lighting fixtures that are attached to a building are required to be
high efficacy, be manually on/off switch controlled, and have both motion sensor
and photocell control. See ES 150.0(k) 3 for additional control options.
34. Masonry walls shall be insulated to meet the wall insulation requirements of
TABLE 150.1-A or B. ES150.0(c).5
Residential ventilation requirements: ES 150.0(o)/ASHRAE 62.2
35. Kitchens require exhaust fans with a minimum 100 cfm ducted to the exterior.
Detail compliance by including a complying exhaust fan or a ducted range hood
to the exterior.
36. Bathrooms require exhaust fans (minimum 50 cfm) to be ducted to the exterior.
A bathroom is defined "as a room with a bathtub, shower, or spa or some similar
source of moisture".
37. Residential bathroom exhaust fans shall be energy star rated and shall be control
by a humidistat capable of an adjustment between 50 and 80% humidity.
CalGreen 4.506.1. Exception: Control by a humidistat is not required if the
bathroom exhaust fan is also the dwelling whole house ventilation.
38. Mechanical whole house ventilation must be provided. Identify the fan providing
the whole house ventilation (complete with CFM and Sone rating) on the
floorplans. For additions 1,000 square feet or less, whole house ventilation is not
required. For additions over 1,000 square feet, the whole house ventilation CFM
shall be based upon the entire (existing and addition) square footage, not just the
addition.
a) All fans installed to meet all of the preceding ventilation requirements must
be specified at a noise rating of a maximum 1 "Sone" (continuous use) or
3 "Sone" (intermittent).
Carlsbad cbR2-2020-260
2/28/2020
MISCELLANEOUS
39. To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
40. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
41. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Richard Moreno at EsGil. Thank you.
MISCELLANEOUS
42. To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
43. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
44. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Richard Moreno at EsGil. Thank you.
Carlsbad cbR2-2020-260
2/28/2020
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Richard Moreno
BUILDING ADDRESS: 1317 Pine
BUILDING OCCUPANCY:
BUILDING
PORTION
Remodel
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb
------
; r i F 1997 UBC Bu ldIng Pe mt ee
1997 UBC Plan Check Fee ----------------
Type of Review:
AREA
( Sq. Ft.)
638
.... _j
···3
Valuation
Multiplier
By Ordinance
Complete Review
D Other
PLAN CHECK#.: cbR2-2020-260
DATE: 2/28/2020
Reg. VALUE ($)
Mod.
29,673
29,673
D Structural Only
/
D Repetitive fee
.... j Repeats □ Hourly
EsGil Fee
1------11 Hr. @ *
L.._ ___ $1_a_1_.o--'2I /
Comments:
Sheet 1 of 1
~ Cityo1
Carlsbad
n ~:~:. ... . CERTIFICATION OF SCHOOL FEES PAID ►~-'~ .. ·:•--.. ~':!r:~
This form must be completed by t he City, the applicant , and the appropriate school districts and returned to the City pnor
to issuing a building permit. The City will not issue any building permit without a completed school fee form.
Project # & Name:
Permit #: CBR2020-0260 -------------------
Project Address: 1317 PINE AVE -------------------
Assessor's Parcel #: 2050523000 ----'-----------------
Project Applicant: TODD ANGEL -------------------( 0 w n er Name)
Residential Square Feet:
New/Additions: -------------------
Second Dwelling Unit: 638 -------------------
Commercial Square Feet:
New/Additions:
City Certification:City of Carlsbad Building Division Date: 11/20/2020
( ertificat1on of ApplicanUOwners. The person executing this declaration ("Owner") certifies
under penalty of perjury that (1) the information provided above is correct and true to the
best of the Owner's knowledge, and that the Owner will file an amended certification of
payment and pay the additional fee if Owner requests an increase in the number of
dwelling units or square footage after the building permit is issued or if the initial
aetermination of units or square footage is found to be incorrect. and that (2) the Owner is
the owner/developer of the above described project(s), or that the person executing this
declaration is authonzed to sign on behalf of the Owner.
lZ] Carlsbad Unified School District
6225 El Camino Real
Carlsbad CA 92009
Phone: (760) 331-5000
EJ Encinitas Union School District
-101 South Rancho Santa Fe Rd
Encinitas. CA 92024
Phone: (760) 944-4300 x1166
[J San Dieguito Union H.S. District
684 Requeza Dr.
Encinitas, CA 92024
Phone: (760) 753-6491 Ext 5514
(By Appt. Only)
D San Marcos Unified Sch. District
255 Pico Ave Ste. 100
San Marcos, CA 92069
Phone: (760) 290-2649
Contact: Katherine Marcelja
(By Appt.only)
D Vista Unified School District
1234 Arcadia Drive
Vista CA 92083
Phone: (760) 726-2170 x2222
SCHOOL DISTRICT SCHOOL FEE CERTIFICATION
(To be completed by the school district(s))
THIS FORM INDICAT ES THAT THE SCHOOL DISTRICT REQUIREMENTS
FOR THE PROJ ECT HAVE BEEN OR WILL BE SATISFIED.
Th e undersigned, being duly authorized by the applicable School District, certifies that the developer, builder,
or owner has satisfied the obligation for school facilities. This is to certify that the applicant listed on page 1
h as paid all amounts or completed other applicable school mitigation determined by the School District. The
City may issue building permits for this project.
C~
rngnature of Authorized School District Official:_:)_, ...::.a;.-'.'.'\._,__f2->-+-...._r...._'."'C':-,.,___=\,"/4 ... .,L.:x...,_,:')'.""'\.."""''-:'.X::>..:......;,.___~J_=--1.__,'>,-~\--\~f'.""L"--'\.,.,__,.J_,,.....,.~...,. r
-ti C i , I I e: _ _:>, t, ? S, • • ) '-\~ ):v\-1• \ , \.-.
Name of School District:_-ti;C,Jli/.AR'i-lLSi;f-B.PADMUMINlrl,"IFH!IEte-D_sc_H_O_OL_D_IS_TR_lC_T _____ Phone: 'l l.t c .3 iJ . s~ ('(
6225 El CAMINO R~L
Community & EconomiJ:~.c.\~09suilding Division
1635 !=araday Avenue I Carlsbad, CA 92008 760-602-2719 I 760-602-8558 fax I building@carlsbadca.gov
C cicyof
Carlsbad
PURPOSE
CLIMATE ACTION PLAN
CONSISTENCY CHECKLIST
8-50
Development Services
Building Division
1635 Faraday Avenue
(760) 602-2719
www.carlsbadca.gov
This checklist is intended to assist building permit applicants identify which Climate Action Plan (CAP) ordinance
requirements apply to their projects. The completed checklist must be included in the building permit application. It may be
necessary to supplement the completed checklist with supporting materials, calculations or certifications, to demonstrate
full compliance with CAP ordinance requirements. For example, projects that propose or require a performance approach
to comply with energy-related measures will need to attach to this checklist separate calculations and documentation as
specified by the ordinances.
NOTE: The following type of permits are not required to fill out this form
❖ Patio I ❖ Decks I ❖ PME (w/o panel upgrade) I ❖ Pool
..i1 If an item in the checklist is deemed to be not applicable to a project, or is less than the minimum required by ordinance,
an explanation must be provided to the satisfaction of the Building Official.
A Details on CAP ordinance requirements are available on the city's website .
..i1 A CAP Building Plan template (form B-55) shall be added to the title page all building plans. This template shall be
completed to demonstrate project compliance with the CAP ordinances. Refer to the building application webpage and
download the latest form.
Project Name/Building
Permit No.:
Property Address/APN:
____________ BP No.: ~c;20, ()~(oO
1317 P,ftt ~ ~\,--\sbcf C.V'r q2CV€7;
Applicant Name/Co.:
Applicant Address: l-3 lv :Ptkt.. fue.
Contact Phone: Contact Email:
Contact information of person completing this checklist (if different than above):
Name:
Company
name/address:
Applicant Signature: 1 a.JI = ~
B-50
Contact Phone:
Contact Email:
Page 1 of 6
Date: _;;i..-1-,/~3+-/:io.~!.2-o~--1
Revised 08/19
City of Carlsbad Climate Action Plan Consistency Checklist
Use the table below to determine which sections of the Ordinance Compliance checklist are applicable to your project.
For alterations and additions to existing buildings, attach Building Permit Valuation worksheet.
Building Permit Valuation (BPV) from worksheet: $ ______ _
I Conllruc:tlon Type
D Residential
□ New construction
□ Additions and alterations:
~ BPV < $60,000
□ BPV ~ $60,000
□ Electrical service panel upgrade only
□ BPV ~ $200,000
D Nonresidential
□ New construction
□ Alterations:
□ BPV ~ $200,000 or additions~ 1,000
square feet
□ BPV ~ $1,000,000
□ ~ 2,000 sq. ft. new roof addition
I ComplltaSlcllan(s) I Notll:
A high-rise residential building is 4 or more stories, including a
Low-rise High-rise mixed-use building in which at least 20% of its conditioned floor
area is residential use
2A, 3A, 1B, 2B,
4A 3B, 4A
N/A N/A All residential additions and alterations
1A, 4A 4A 1-2 family dwellings and townhouses with attached garages
only
*Multi-family dwellings only where interior fin ishes are removed
1A, 4A* 1B, 4A* and significant site work and upgrades to structural and
mechanical, electrical, and/or plumbing systems are proposed
1 B, 2B, 3B, 4B and 5
1B,5
1B,2B,5 Building alterations of.:: 75% existing gross floor area
2B,5 1 B also applies if BPV.:: $200,000
Checldlat 111m
Checklhe8JlPRIPIWalmes,~ltnotflllPlc:alMS1d__.llms,nprwdaSIWdn9cabllall00881ddocumentallon•nac111-,.
1. Energy Efficiency
Please refer to Carlsbad Municipal Code (CMC) sections 18.21.155 and 18.30.190, and the California Green Building Standards Code (CALGreen) for
more information when completing this section.
A. D Residential addition or alteration 2! $60,000 building permit valuation. D N/A _________ _
See CMC section 18.30.190. D Exception: Home energy score ~ 7
(attach certification)
Year Built Single-family Requirements Multi-family Requirements
D Before 1978 Select one:
D Duct sealinQ D Attic insulation D Cool roof D Attic insulation
D 1978 and later Select one:
D Lighting package D Water heating Package
D Between 1978 and 1991 Select one:
D Duct sealing D Attic insulation D Cool roof
D 1992 and later Select one:
D Lighting package D Water heating package
B. D Nonresidential* new construction or alterations 2! $200,000 building permit valuation,
or additions 2! 1,000 square feet D N/A
Updated 8/ 15/20 I 9
,
2
I City of Carlsbad Climate Action Plan Consistency Checklist
See CMC 18.21.155 and CALGreen Appendix AS, Division AS.2-Energy Efficiency.
A5.203.1.1 Choose one: □ .1 Outdoor lighting □ .2 Warehouse dock seal doors / □ .3 Restaurant service water heating (comply with California Energy Code section 140.5, as amended) □ NIA
□ .4 Daylight design PAFs □ .5 Exhaust air heat recovery /
AS.203.1 .2.1 □NIA7 Choose one as applicable: □ .95 Energy budget □ .90 Energy budget
A5.211.1**
/4A □ On-site renewable energy
A5.211.3** / □ Green power (if offered by local utility provider, 50% minimum renewable sources) □ NIA
A5.212.1 / □ Elevators and escalators □ NIA
A5.213.1 / □ Steel framing □ NIA
** For alterations ~ $1,000,000 BPV and affecting > 75% existing gross or area, or alterations that add 2,000 square feet of new roof addition: comply
• Includes hote~lmotels and high~se resKlenli~ buiijings 7'
with CMC 18.30.130 instead.
2. Photovoltaic Systems I
A. D Residential new construction (for low-ri~nlial building pennll applications submitted after 1/1/20). Refer to 2019 califomia
Energy Code section 150.1(c)14 for requirem ts. Notes: 1) High-rise residential buildings are subjectto nonresidential photovoltaic
requirement (28 below) instead. 2) If proje includes installation of an electric heat pump water heater pursuant to CMC 18.30.150(8)
(high-rise residential) or 18.30.170(8) (lo -rise residential), increase system size by .3kWdc if PV offset option is selected.
Floor Plan ID (use additional CFA I #d.u. Calculated kWdc* Exception
sheets if necessary)
7 □
I □
I □
I □
I Total System Size: kWdc
kWdc a (CFAx.572) / 1,000 t 15 X #d.u.)
*Formula calculation where A= conditional floor area, #du = number of dwellings per plan type
If proposed system size is r ss than calculated size, please explain.
B. D Nonresidential new construction or alterations ~$1,000,000 8PV and affecting ~75% existing floor area, or addition that increases roof
area by ~2,doo square feet Please refer to CMC section 18.30.130 when completing this section. Note: This section also applies to
high-rise residential and hotel/motel buildings.
Choose one of the following methods:
□ Gross Floor Area (GFA) Method
GFA:
□If < 10,000s.f. Enter: 5 kWdc
Min. System Size:
□ If ~ 1 O,OOOs.f. calculate: 15 kWdc x (GFA/10,000) **
___ kWdc
**Round building size factor to nearest tenth, and round system size to nearest whole number.
□ Time-Dependent Valuation Method
Updated 8/15/2019 3
City of Carlsbad Climate Action Plan Consistency Checklist
Annual TDV Energy use:*** ______ x .80= Min. system size: ____ _ kWdc
***Attach calculation documentation using modeling software approved by the California Energy Commission.
3. Water Heating
A. D Residential and hotel/motel new construction
Please refer to CMC sections 18.30.150 and 18.30.170 when completing th is section.
□ For systems serving individual dwelling units choose one:
□ Heat pump water heater AND Compact hot water distribution AND Drain water heat recovery (low-rise
residential only)
□ Heat pump water heater AND PV system .3 kWdc larger than required in CMC section 18.30.130 (high rise
residential hotel/motel) or CA Energy Code section 150.1 (c) 14 (low-rise residential)
□ Heat pump water heater meeting NEEA Advanced Water Heating Specification Tier 3 or higher
□ Solar water heating system that is either .60 solar savings fraction or 40 s.f. solar collectors
□ Exception:
□ For systems serving multiple dwelling units, install a central water-heating system with all of the following:
□ Gas or propane water heating system
□ Recirculation system per CMC 18.30.150(8) (high-rise residential, hotel/motel) or CMC 18.30.170(8) (low-
rise residential)
□ Solar water heating system that is either:
□ .20 solar savings fraction
□ .15 solar savings fraction, plus drain water heat recovery
□ Exception:
B. D Nonresidential new construction
Please refer to Carlsbad Ordinance CMC section 18.30.150 when completing this section.
□ Water heating system derives at least 40% of its energy from one of the following (attach documentation):
□ Solar-thermal □ Photovoltaics □ Recovered energy
□ Water heating system is (choose one):
□ Heat pump water heater
□ Electric resistance water heater(s)
□Solar water heating system with .40 solar savings fraction
□ Exception:
Updated 8/ 1 5/20 19
'
4
\ City of Carlsbad Climate Action Plan Consistency Checklist
4. Electric Vehicle Charging
A D Residential New construction and major alterations•
Please refer to Carlsbad Ordinance CMC section 18.21.140 when completing this section.
D One and two-family residential dwelling or townhouse with attached garage:
D One EVSE Ready parking space required D Exception ·
D Multi-family residential: D Exception :
Total Parking Spaces EVSE Soaces
Proposed Capable Ready I Installed /
I /
Calculations:
EVSE Installed= Total EVSE Spaces x .50 (rounded up to nearest whole number)
EVSE other= Total EVSE spaces -EVSE Installed
(EVSE other may be "Capable," "Ready'' or "Installed.")
/
/
l Total
I
Total EVSE spaces= .10 x Total parking (rounded up to nearest whole num~7
. ' . . .. *MaJor alterations are. (1) for one and two-family dwellings and townhouses with attach:d.Jz.rages, alterations have a bu1ld1ng permit valuation ~ $60,000
or include an electrical service panel upgrade; (2) for multifamily dwellings (three units o~r t:e without attached garages), alterations have a building permit
valuation ~ $200,000, interior finishes are removed and significant site work and upg/, s to structural and mechanical, electrical, and/or plumbing
systems are proposed.
B. D Nonresidential new construction (includes hotels/motels) i Exception :
Total Parking Spaces I EVSE Spaces
Proposed Capable I Rea"dv I Installed I Total
I I I I
Calculation: Refer to the table below: I
Total Number of Parking Spaces provided Number of reo6ired EV Spaces Number of reauired EVSE Installed Spaces
□ 0-9 I 1 1
□ 10-25 I 2 1
□ 26-50 I 4 2
□ 51-75 I 6 3
□ 76-100 I 9 5
□ 101-150 I 12 6
□ 151-200 I 17 9
□ 201 and over I/ 10 oercent of total 50 oercent of Reau ired EV Spaces
I
(
Updated 8/15/2019 5
City of Carlsbad Climate Action Plan Consistency Checklist
5. D Transportation Demand Management (TOM): Nonresidential ONLY
An approved Transportation Demand Management (TOM) Plan is required for all nonresidential projects that meet a threshold of employee~enerated ADT.
City staff will use the table below based on your submitted plans to determine whether or nor your permit requires a TOM plan. lfTDM is applicable to your
permit, staff will contact the applicant to develop a site-specific TOM plan based on the permit details.
Acknowledgment:
Employee ADT Estimation for Various Commercial Uses
EmpADTfor
first 1,000 s.f.
EmpADTI
1000 s.f.1
Office (all)2 20
Restaurant 11
Retaib 8
Industrial 4
Manufacturing 4
Warehousin 4
1 Unless otherwise noted, rates estimated from /TE Trip
Generation Manual, 1 (JlhEdition
13
11
4.5
3.5
3
1
2 For all office uses, use SAN DAG rate of 20 ADT/1 ,000 sf to
calculate employee ADT
3 Retail uses include shopping center, variety store, supermarket,
gyms, pharmacy, etc.
Other commercial uses may be subject to special
consideration
Sample calculations:
Office: 20,450 sf
1. 20,450 sf/ 1000 x 20 = 409 Employee ADT
Retail: 9,334 sf
1. First 1,000 sf = 8 ADT
2. 9,334 sf -1,000 sf= 8,334 sf
3. 8,334 sf/ 1,000 x 4.5 + 8 = 46 Em lo ee ADT
I acknowledge that the plans submitted may be subject to the City of Carlsbad's Transportation Demand Management Ordinanc.e. I agree to be contacted should
my permit require a TOM plan and understand that an approved TOM plan is a condition of permit issuanc.e.
Applicant Signature: __________________ _ Date: ______ _
Person other than Applicant to be contacted for TDM compliance (if applicable):
Name (Printed): ___________________ _ Phone Number: _____ _
Email Address: ___________________ _
Updated 8/15/2019 6