HomeMy WebLinkAbout2822 STATE ST; ; CBC2019-0106; PermitBuilding Permit Finaled
Print Date: 05/05/2020
Job Address:
PermitType:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
ProjectTitle:
2822 State St
BLDG-Commercial
2031810500
$7,953.21
Commercial Permit
Work Class: Tenant Improvement
Lot#:
Reference #:
Construction Type
Bathrooms:
Orig. Plan Check#:
Plan Check#:
{'cityof
Carlsbad
Permit No: CBC2019-0106
Status: Closed -Finaled
Applied: 03/06/2019
Issued: 03/05/2020
PermitFinal
Close Out:
Inspector: PBurn
Final
Inspection: 05/05/2020
Description: CARLSBAD THEATER: 171 SF T.I. (CONVERTING AN EXISTING RESTROOM INTO 2 UNISEX/HANDICAP RESTROOMS))
Applicant: Owner:
AVENT DESIGN 2822 STATE STREET LLC
LISA AVENT
28720 Sandhurst
ESCONDIDO, CA 92026-680S
619-889-9481
2808-2822 State St
CARLSBAD, CA 92008-1630
FEE
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
ELECTRICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
FIRE A-1 Occupancies -Tl
MECHANICAL BLDG COMMERCIAL NEW/ADDITION/REMODEL
PLUMBING BLDG COMMERCIAL NEW/ADDITION/REMODEL
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-COMMERCIAL
Total Fees: $1,205.50 Total Payments To Date: $1,205.50
Contractor:
REX CLARK HOME IMPROVEMENTS
1158 Avenida Frontera
Oceanside, CA 92057-7733
760-390-4012
Balance Due:
AMOUNT
$97.22
$68.05
$41.00
$908.00
$39.00
$49.00
$1.00
$2.23
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as 11fees/exaction.11 You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Buildin Division
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov Page 1 of 1
-,., ...... ,,,
( City of
Carlsbad
Job Address 2822 State Street
Tenant Name: Carlsbad Theater
COMMERCIAL
BUILDING PERMIT
APPLICATION
B-2
Plan Check Cf;(<fg9 f ~ -Q//l
Est. Value _J~_ 3 · ;;?/
PC Deposit #?,: £-6 '>-
Date 3-0 -i q
Sulte: ___ APN:2c6-I~ --Ds-OO
CT /Project#: Lot#: -3 2-
Fire Sprinklers: yes/ no Air Con~tloning: yes/ no • n
BRIEF DESCRPTIONOFWORK:1,icJ &Uk ffiU) b.CWA£~ Cc.errw
r~~-1illv1r\ $, .
l " I D Addition/New: _____ 1....:.... _____ New SF and Use, ___________ New SF and Use,
___ Deck SF, ___ Patio Cover SF (not including flatwork)
l I'! I SF, Existing us-;rhtv½'.:\ D Tenant Improvement: Proposed Use'::\:h{W::{
_____ SF, Existing Use ______ Proposed Use _____ _
0 Pool/Spa: ____ SF Additional Gas or Electrical Features? ___________ _
D Solar: ___ KW, __ Modules, ___ Mounted, Tilt: Yes/ No, RMA: Yes/ No, Panel Upgrade: Yes/ No
D Plumbing/Mechanical/Electrical Only: _______________________ _
□ Other: ------------------------------------
PROPERTY OWNER
+-"'--"--.=:,,--L.-'-"-''+,"---++e---:,;-+.--,--Name: K t?c, ...::..:r.w~:::r,<-,-::=====~~~+ Address: _________________ _
City: _________ State: ___ Zip: ____ _
--"=~.z,..:Of+J..:w'-1....J\,,:---::--::cr--r--Phone: _________________ _
Email: Email: __________________ _
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he/she Is licensed pursuant to the provisions of the Contractor's Ltcense Law
{Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code; or that he/she Is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031,5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500)).
1635 Faraday Ave Carlsbad, CA 92008
B-2
Ph: 760-602-2719 Fax: 760-602-8558
Page 1 of2
Email: Bullding@carlsbadca.gov
Rev. 06/16
-,) .....
( OPTION A): WORKERS'COMPENSATION DECLARATION:
I hearby affirm under penalty of perjury i1!1f. of the following declarations:
□ I have and will maintain a certificate of consent to self-Insure for workers' compensation provlded by Section 3700 of the Labor Code, for the performance of the
work which this permit ls Issued.
IJ'I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit Is issued.
My workers' compensation \nsurance carrier and policy number are: Insurance Company Name:_
Policy No. _______ Expiration Date:_
~ Certificate of Exemption: I certify tl1at in the performance of the work for whlcl1 th!s permit is Issued, I shall not employ any person in any manner so as to be come
~Ject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful, and shall subject an employer to
criminal penalties and clvll fines up to $100,000.00, In addition the to the cost of compensation, damages as provided for In Section 3706 of the Labor Code,
Interest and attorney's fees. ~ / /7,
CONTRACTOR SIGNATURE: -~..L.......-4.o-"'-=-b""""~==---"-----------~AGENT DATE: ' 3 l,s-_/2 0
( OPTION B ): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's license Law for the following reason:
O t, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale {Sec.
7044, Business and Professions Code: The Contractor's license Law does not apply to an owner of property who builds or improves thereon, and who does such work
hlmself or through his own employees, provided that such improvements are not lntended or offered for sale. If, however, the bulldlng or improvement Is sold within
one year of completlon, the owner-builder will have the burden of proving that he did not build or Improve for the purpose of sa1e).
□ I, as owner of the property, am excluslvely contracting with licensed contractors to construct the project (Sec. 7044, Buslness and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or Improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's license Law).
□ I am exempt under Section _______ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. □ Yes □ No
2. r {have/ have not) signed an application for a buildlna permit for the proposed work.
3.1 have contracted with the following person (firm) to provide the proposed construction {include name address/ phone/ contractors' license number):
4. I p1an to provide portions of the work, butt have hired the followlng person to coordinate, supervise and provide the major work (include name/ address/ phone/
contractors' llcense number):
5. I wlll provide some of the work, butt have contracted {hired) the following persons to provide the work Indicated (Include name/ address/ phone /type of work):
OWNER SIGNATURE: _________________ □AGENT DATE: _____ _
CONSTRUCTION LENDING AGENCY, IF ANY:
r hereby affirm that there is a construction lending agency for the performance of the work this permit ls Issued jSec. 3097 (I) Clvil Code).
Lender's Name: ___________________ _ Lender's Address: ___________________ _
ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future bulldlna occupant required to submit a business plan, acutely hazardous materials registration form or r!sk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? □ Yes □ No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? □ Yes □ No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? □ Yes □ No
IF A.NY OF THE ANSWERS ARE YES, A FINALCERTIACATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR 15 MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT,
APPLICANT CERTIFICATION:
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for Inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP
HARMLES.S THE CITY OF CARLSBAD AGA!NST All LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WH1CH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF
THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over S'(j deep and demol!tion or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the Bui
by such permit Is not commenced within 1
after the work Is commenced for a rlod
Official under the provisions of this Code shall expire by limitation and become null and void If the budding or work authorized
s from the date such permit or if the building or work authorized by such permit ls suspended or abandoned at any time
days (Section 1 .4 Uniform BuKdlng Code).
APPLICANT SIGNATURE: ~-,L.i..U.......6:::::L~=========--..,.---DATE: -'-?,,+/1,1,-w ti-/ 1-,/ r<---
1635 Faraday Ave Carlsbad, CA 92008
8-2
Ph: 760-602-2719 Fax: 760-602-8558
Page 2 of 2
Email: Building@carlsbadca.gov
Rev. 06/18
PERMIT INSPECTION HISTORY for (CBC2019-0106)
Permit Type: BLDG-Commercial Application Date: 03/06/2019 Owner: 2822 STATE STREET LLC
Work Class: Tenant Improvement Issue Date: 03/05/2020 Subdivision: SEASIDE LANDS
Status: Closed -Finaled Expiration Date: 09/08/2020 Address: 2822 STATE ST
IVR Number: 17488 CARLSBAD, CA 92008-1630
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Reinspectlon Inspection
Date Start Date
Tuesday, May 5, 2020
Checklist Item
BLOG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
COMMENTS
Status
Passed
Yes
Yes
Yes
Yes
Yes
Page 2 of 2
Building Permit Inspection History Finaled
{'city of
Carlsbad
PERMIT INSPECTION HISTORY for (CBC2019-0106)
Permit Type: BLDG-Commercial Application Date: 03/06/2019 Owner: 2822 STATE STREET LLC
Work Class: Tenant Improvement Issue Date: 03/05/2020 Subdivision: SEASIDE LANDS
Status: Closed -Finaled Expiration Date: 09/08/2020 Address: 2822 STATE ST
IVR Number: 17488 CARLSBAD, CA 92008-1630
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Re Inspection Inspection
Date Start Date Status
03105/2020 03/05/2020 BLDG-84 Rough 121353-2020 Failed Paul Burnette Relnspectlon Incomplete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-14 No
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout No
BLDG-34 Rough Electrical No
BLDG-44 No
Rough-Ducts-Dampers
03106/2020 03106/2020 BLDG-21 121699-2020 Passed Chris Renfro Complete
Underground/Underflo
or Plumbing
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
03110/2020 03110/2020 BLDG-84 Rough 121809-2020 Passed Peter Dreibelbis Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
03/12/2020 03/12/2020 BLDG-17 Interior 122067-2020 Passed Peter Orelbelbls Complete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
05/04/2020 05/04/2020 BLDG-Final Inspection 126395-2020 Failed Paul Burnette Relnspectlon Incomplete
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-Plumbing Final No
BLDG-Mechanical Final No
BLDG-Structural Final No
BLDG-Electrical Final No
05/05/2020 05/05/2020 BLDG-Flnal Inspection 126551-2020 Passed Paul Burnette Complete
Tuesday, May 5, 2020 Page 1 of 2
DATE: 4/26/2019
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2019-0106
PROJECT ADDRESS: 2822 State St.
✓• EsG1I
A SAFEbu1lt Co1T1pany
SET II
PROJECT NAME: Carlsbad Theatre Tenant Improvement
□ APPLICANT
□ JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
~ The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: ;:. ()\ Telephone#:
Date contacted: (by~) Email:
Mail Telephone Fax In Person
~ REMARKS: Applicant to slip sheet the set II sheets into the approved set I plans prior to permit
issuance.
By: Jason Pasiut
EsGil
4/19/2019
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: 3/18/2019
JURISDICTION: Carlsbad
PLAN CHECK#.: CBC2019-0106
PROJECT ADDRESS: 2822 State St.
✓• EsG1I
A SAFEbuilt Company
SET: I
PROJECT NAME: Carlsbad Theatre Tenant Improvement
□ APPLICANT
M JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
IZ] The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
IZ] The applicant's copy of the check list has been sent to:
Lisa Avent
D EsGil staff did not advise the applicant that the plan check has been completed.
IZ] EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Lisa Avent Telephone#: 619-889-9487
Date contacted:3/lfllt:\ (by:~) Email: aventdesign@outlook.com
t, Mail ✓ Telephone1,wi Fax In Person
0 REMARKS:
By: Jason Pasiut
EsGil
3/11/2019
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBC2019-0106
3/18/2019
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK#.: CBC2019-0106
OCCUPANCY: A-1
TYPE OF CONSTRUCTION:
ALLOWABLE FLOOR AREA: complies
SPRINKLERS?:
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 3/6/2019
DATE INITIAL PLAN REVIEW
COMPLETED: 3/18/2019
FOREWORD (PLEASE READ):
JURISDICTION: Carlsbad
USE: Theatre
ACTUAL AREA: 1 71 sf
STORIES: 2
HEIGHT: unchanged
OCCUPANT LOAD:
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 3/11/2019
PLAN REVIEWER: Jason Pasiut
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2016 CBC, which adopts the 2015 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBC2019-0106
3/18/2019
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one
of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil is complete.
• PLANS
3. Provide a Building Code Data Legend on the Title Sheet. Include the following
code information for each building proposed:
♦ Occupancy Classification(s)
♦ For Mixed Occupancy Buildings, state whether the "nonseparated" or
"separated" option was chosen from Sections 508.3/508.4.
♦ Type of Construction
♦ Sprinklers: Yes or No
♦ Floor Area
♦ Occupant Load
4. Please provide a minimum plumbing facilities calculation based on occupant
load of facility.
a) Update the restroom design and plumbing plans if applicable.
b) This A-1 facility appears to be large enough to require more facilities than
are shown, including separate facilities for each gender, urinal(s) and
drinking fountains. Refer to CPC Table A and Table 422.1.
5. Please update the unisex restroom sign detail on sheet A-1 to be compliant with
11B-703.7.2.6.3. There are no images on the approved signs.
• END OF REVIEW
Carlsbad CBC2019-0106
3/18/2019
To speed up the review process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number, calculation
page, etc.
Please indicate here if any changes have been made to the plans that are not a result
of corrections from this list. If there are other changes, please briefly describe them
and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate: □ Yes □ No
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number of 858/560-1468, to perform the
plan review for your project. If you have any questions regarding these plan review
items, please contact Jason Pasiut at Esgil. Thank you.
Carlsbad CBC2019-0106
3/18/2019
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Jason Pasiut
BUILDING ADDRESS: 2822 State St.
BUILDING OCCUPANCY: A-1
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code #N/A
--
P rmi Fee ... 1997 UBC Building e t ---~
1997 UBC Plan-C_he_ck_F_;~_----•~I
Type of Review: 0 Complete Review
D Repetitive Fee
;;-] Repeats
Comments:
D Other
D Hourly
EsGil Fee
PLAN CHECK#.: CBC2019-0106
DATE: 3/18/2019
Reg. VALUE ($)
Mod.
D Structural Only
,------ilHr.@ *
#NIAi
Sheet 1 of 1
Carlsbad CBC2019-0106
3/18/2019
/DO NOT PAY-1111S IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Jason Pasiut
BUILDING ADDRESS: 2822 State St.
BUILDING OCCUPANCY: A-1
BUILDING AREA
PORTION ( Sq. Ft.)
Tl
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Gode cb
.. 1 f 1997 UBC Bur1dmg Permit Fee L_J
I 1997 UBC Pran Check Fee '. '.!.i
Valuation
Multiplier
By Ordinance
Type of Review: P' Complete Review
r Repetitive Fee
j :..,.i Repeats
..
Comments:
r Other
r Hourly
EsGII Fee ..
Reg.
Mod.
PLAN CHECK#.: CBC2019-0106
DATE: 3/18/2019
VALUE ($)
7,953
7,963 ,
r Structural Only
1-------11 Hr. @ •
$59.0Bl
Sheet 1 of 1
SAN DIEGO REGIONAL OFFICE USE ONLY
0 ~
HAZARDOUS MATERIALS .,. < ,, .•
QUESTIONNAIRE
Busi7• N_,;'j'e k -6 /1 ,i LM1 .., M rr, . Business Contact
Pro)ecr,,.ddress '
Mailing Address
Project Contact
City
City
Applicant E-mail
Organic Peroxides
Oxidizers
Pyrophorlcs
Unstable Reactives
questions s yes. app ,cant must contact the ounty o an ego
Call (858) 505•6700 prior to the issuance of a building permit.
RECORD ID# PLAN CHECK#
Telephone#
State Zip Code
State Zip Code
Telephone#
Water Reactives
BP DATE I
APN#
Plan FIie#
13. Corrosives
14. Other Health Hazards e:; None of These.
I
: If the answer to any of the an Diego, CA 92123.
FEES ARE REQUIRED Project Completion Date: Expected Date of Oc<::upancy:
YES 1 (for new construction or remodeling projects)
1. D Is your business listed on the reverse side of this form? (check all that apply}.
2. D Win your business dispose of Hazardous Substances or Medical Waste In any amount?
3. D WiU your business store or handle Hazardous Substances in quantities greater than or equal to 55 gallons, 500
pounds and/or 200 cubic feet?
0 CaiARP Exempt
I
Date Initials
0 CalARP Required
I
4.
5.
6.
7.
8.
D Will your business use an existing or install an underground storage tank?
D Will your business store or handle Regulated Substances (CalARP)?
D l Will your business store or handle carcinogens/reproductive toxins In any quantity?
D Will your business use or Install a Hazardous Waste Tank System (ntle 22, Artlde 10)? D Will your business store petroleum in tanks or containers at your facility with a total faclllty storage capacity equal to
or realer than 1,320 eUons? California's Abov round Petroleum Sto e Act .
Date Initials
0 CalARP Complete
Date Initials
ART Ill· I O RP L CONTR I T APCD • Any YES• answer requires a stamp from APCO 10124 Old Grove Road, San
o. A 2131 3PcdC~P@sdc0UDIY-C8·90V ( ) 0). rNo stamp required If Q1 Yes l!lit 03 Yes insl 04-06 No). The following questions are intended
to i entity the majority o 7 r pollution Issues at the planning stage. Projects may require additional measures not Identified by these questions. For comprehensive
requirements contact APCO. Residences are typically exempt, except -those With more lhan one building* on lhe property; single buildings Wilh more than folK
iwe~~i un~~;;~~;;;~;~;:;~;;,~;;;{;.;;be;;;;;•~;;;;~;~~g:::,: •1:::::::~·:,::::•:0::::n: ::~:~::ull~ngs.J
3, O ~ (ANSWER ONLY IF QUESTION 1 or 2 IS YES) Has an asbestos survey been performed by a Certlfted Asbestos Consultant or Site Surveillance
Technician?
4. D □ (ANSWER ONLY IF QUESTION 31S YES) Based on the survey results, wfll the project disturb any asbestos containing material? Notification
may be required 10 working days prior to commencing asbestos removal.
5. 0 Will the project or associated construction equipment emit air contaminants? See the reverse side of this form or APCO factsheet
OWW-sdaocd org1tnfg(fags1permits.pdf) for typical equipment requiring an APCD permit.
6. D D (ANSWER ONLY IF QUESTION 5 IS YES) Will the project or associated construction equipment be located within 1,000 feet of a school
bound•
Briefly
t to the best of my knowledge a 3 I ff I /1
Name Date
FIRE DE CY CLASSIFICATION·
BY: DATE: I I
EXEMPT OR NO FURTHER INFORMATION REQUIRED RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY
COUNTY-HMO* APCD COUNTY-HMO APCD COUNTY-HMO APCD
·A stamp 1n this box 2.ll!i. exempts busmesses from completing or updating a Hazardous Materials Busmess Plan. Other permitting requrrements may still apply.
I-IM-9171 (08/15) County of San Diego -DEH -Hazardous Materials Division
. "----·-···· ----