HomeMy WebLinkAboutDWG 357-6L; MS 95-11; PALMER WAY INDUSTRIAL PARK; 01-07' RECLAIMED WATER NOTES 1, ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE CARLSBAD MUNICIPAL WATER DISTRICT'S 'CARLSBAD RULES AND REGULA T!ONS FOR CONSTRUCTION OF RECLAIMED WATER MAINS' DATED OCTOBER 1993. 2. DRINKING FOUNTAINS SHALL BE PROTECTED FROM SPRAY OF RECLAIMED WATER BEST MANAGEMENT PRACTICES SHALL BE USED TO MINIMIZE RECLAIMED WATER ENCROACHMENT ON PUBLIC FACILITIES SUCH AS PICNIC TABLES, BBQ'S, PLAYGROUNDS, SAND TOT LOTS, ETC .. 3. BEST MANAGEMENT PRACTICES SHALL BE USED TO ELIMINATE OR CONTROL TO THE BEST EXTENT POSSIBLE PONDING, RUN-OFF, OVER-SPRAY AND MISTING. 4. HOSE BIBS ARE STRICTLY PROHIBITED. 5. ON SITE CROSS-CONNECTIONS BETWEEN RECLAIMED WATER LINES AND POT- ABLE WATER LINES IS STRICTLY PROHIBITED. 6. NO SUBSTITUTION OF PIPE MATERIALS WILL BE ALLOWED WITHOUT PRIOR APPROVAL BY THE CARLSBAD MUNICIPAL WATER DISTRICT 7. ALL MAINLINE PIPES SHALL HAVE WARNING TAPE PER CARLSBAD MUNICIPAL WATER DISTRICT'S RULES AND REGULATIONS. *8. THE IRRIGATION SYSTEMS SHALL BE RUN BETWEEN THE HOURS OF 10:00 P.M. AND 6:00AM. THE FOLLOWING MORNING. SPOT IRRIGATION COULD BE DONE AT A DIFFERENT TIME WITH QUALIFIED SUPERVISION PERSONNEL ON SITE. 9. PROVIDE A MINIMUM OF AT LEAST 18 INCHES OF COVER OVER ALL WIRING AND PIPING. 10. NON-DESIGNATED USE AREAS SHALL BE PROTECTED FROM CONTACT WITH RECLAIMED WATER, WHETHER BY WINDBLOWN SPRAY OR BY DIRECT APPLICATION THROUGH IRRIGATION OR OTHER USE. LACK OF PROTECTION, WHETHER BY DESIGN, CONSTRUCTION PRACTICE OR SYSTEM OPERATION, IS STRICTLY PROHIBITED. 11. IRRIGATION HEADS SHALL BE RELOCATED OR ADJUSTED TO PREVENT OVER- SPRAYING SIDEWALKS, STREETS AND NON-DESIGNATED USE AREAS. 12. RECLAIMED WATER QUICK COUPLING VALVES SHALL BE OF A TYPE DESIGNED FOR THE USE ON RECLAIMED WATER DISTRIBUTION SYSTEMS (SPIKES NOT INTERCHANGEABLE WITH POTABLE WATER QUICK COUPLING SPIKES) PER CARLSBAD MUNICIPAL WATER DISTRICT'S RULES AND REGULATIONS. 13. METERS SHALL BE SIZED BY THE CARLSBAD MUNICIPAL WATER DISTRICT. 14. ALL IRRIGATION PIPE SHALL BE STENCILED WITH THE WARNING "NON POTABLE WATER"OR "RECLAIMED WATER", COLOR CODED (PURPLE) AND LAID WITH WARNING TAPE AND STENCILING ORIENTED TOWARD THE TOP OF THE TRENCH PER CARLSBAD MUNICJPAL WATER DISTRICT'S RULES AND REGULATIONS. 15. ALL POTABLE WATER AND RECLAIMED WATER PIPING SHALL BE INSTALLED WITH THE STENCILING ORIENTED TOWARD THE TOP OF THE TRENCH. 16. WHEN A POTABLE WATER LINE AND RECLAIMED WATER LINE CROSS, THE RECLAIMED WATER LINE SHALL BE INSTALLED WITHIN A PROTECTIVE SLEEVE. THE SLEEVE SHALL EXTEND 10 FEET FROM EACH SIDE, FROM THE CENTER LINE OF POTABLE WATER LINE, FOR A TOTAL OF 20 FEET. 17. A 10 FOOT HORIZONTAL SEPARATION BETWEEN POTABLE WATER AND RECLAIMED WATER MAINS MUST BE MAINTAINED AT ALL TIMES. THE POTABLE LINE MUST BE INSTALLED ABOVE THE RECLAIMED WATER LINE. 18. A MINIMUM OF 12 INCHES OF VERTICAL SEPARATION BETWEEN UTILITIES MUST BE MAINTAINED AT ALL TIMES. *19. DEVELOPER/CONTRACTOR SHALL CONDUCT A CROSS-CONNECTION TEST AND COVERAGE TEST AS DIRECTED BY THE CARLSBAD MUNICIPAL WATER DISTRICT AND/OR THE SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEAL TH PRIOR TO ANY USE OF RECLAIMED WATER 20. QUICK COUPLING VALVES USED IN RECLAIMED WATER SYSTEMS SHALL CONFORM TO THE FOLLOWING RECLAIMED WATER QUICK COUPLING VALVES USED IN RECLAIMED WATER SYSTEMS SHALL HAVE ACME TYPE THREADS (SPIKES NOT INTERCHANGEABLE WITH POTABLE WATER QUICK COUPLER SPIKES) AND PURPLE COLORED LOCKING COVERS PERMANENTLY ATTACHED TO THE VALVE. QUICK COUPLING VALVES SHALL BE NELSON #7645, HUNTER #HV1 OOA-RL-NP OR APPROVED EQUAL 21. THE REQUIRED CROSS CONNECTION INSPECTION SHALL BE DONE BY EITHER THE CARLSBAD MUNICIPAL WATER DISTRICT AND/OR THE SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH. COPIES OF INSPECTION REPORTS WILL BE FORWARDED TO THE NON-INSPECTING PARTY. '22. DEVELOPER SHALL SHOW THE LOCATION OF RECLAIMED WATER SIGNS 'DO NOT DRINK" ON.THESE PLANS. '23. AN ON-SITE USER/SUPERVISOR SHALL BE DESIGNATED IN WRITING. THIS INDIVIDUAL SHALL BE FAMILIAR WITH PLUMBING SYSTEMS WITHIN THE PROPERTY, WITH THE BASIC CONCEPTS OF BACKFLOW/CROSS-CONNECTION PROTECTION, AND THE SPECIFIC REQUIREMENTS OF A RECLAIMED WATER SYSTEM. COPIES OF THE DESIGNATION SHALL BE PROVIDED TO THE CARLSBAD MUNICIPAL WATER DISTRICT AND SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH. IN CASE OF EMERGENCY CONTACT RON LISTER AT (760) 741-9800 OR AFTER HOURS CONTACT RON LISTER AT (760] 741-9800 24. ALL PUBLIC AND PRIVATE POTABLE WATER MAINS SHALL BE SHOWN ON THE IMPROV~ENJS PLANS. · _ · • ITEMS NUMBERS 9, 19, AND 23 SHALL BE REQUIRED JUST PRIOR TO THE ACTUAL USE OF RECLAIMED WATER ITEM NUMBER 22, THE SIGNAGE PLAN, SHALL BE A PART OF THIS IRRIGATION PLAN BUT THE ACTUAL SIGNS AND TAGS WILL BE INSTALLED JUST PRIOR TO USE OF RECLAIMED WATER 25. ON RECLAIMED WATER SYSTEMS, ALL APPURTENANCES (SPRINKLER HEADS, VALVE BOXES, ETC.) SHALL BE COLOR CODED PURPLE PER AWWA GUIDELINES AND SECTION 4049.54 OF THE CALIFORNIA HEALTH AND SAFETY CODE. LANDSCAPE PLANS FOR --,--::.~~~~-,_ ..... __ -~ .. ~---,.....---~ l-'ill'-"1<U.<lO'I PALMER WAY INDUSTRIAL PARK .P.,U.MfR W,._"'f 0 ~ Lt) PROPOSED FACILITY FOR HOT DOG ON A STICK CARLSBAD, CALIFORNIA 0 SIGNAGE NOTES THE FOLLOWING GUIDELINES FOR THE SUE OF RECLAIMED WATER ARE TO BE PERMANENTLY POSTED INSIDE THE DOOR OF EACH CONTROLLER WHERE THEY ARE EASILY VISIBLE. PLACE ON 8-1/2" X 11" SJZED SIGN. COLOR PURPLE BACKGROUND WITH BLACK LETTERING. I. GUIDELINES FOR RECLAIMED WATER USE: 1. IRRIGATE BETWEEN THE HOURS OF 1000 P.M. AND 6:00 A.M. ONLY WATERING OUTSIDE THIS TIME FRAME MUST BE DONE MANUALLY WITH QUALIFIED SUPERVISORY PERSONNEL ON SITE. NO SYSTEM SHALL AT ANY TIME BE LEFT UNATTENDED DURING USE OUTSIDE THE NORMAL SCHEDULE. 2. IRRIGATE IN A MANNER THAT WILL MINIMIZE RUN OFF, POOLING, AND PONDING. THE APPLICATION RATE SHALL NOT EXCEED THE INFILTRATION RATE OF THE SOIL TIMERS MUST BE ADJUSTED SO AS TO BE COMPATIBLE WITH THE LOWEST SOIL INFILTRATION RATE PRESENT THIS PROCEDURE MAY BE FACILITATED BY THE EFFICIENT SCHEDULING OF THE AUTOMATIC CONTROL CLOCKS, i.e. EMPLOYING THE REPEAT FUNCTION TO BREAK UP THE TOTAL IRRIGATION TIME INTO CYCLES THAT WILL PROMOTE MAXIMUM SOIL ABSORPTION. 3. ADJUST SPRAY HEADS TO ELIMINATE OVERSPRAY ONTO AREAS NOT UNDER THE CONTROL OF THE CUSTOMER FOR EXAMPLE, POOL DECKS, PRIVATE PATIOS AND LOTS, AND STREETS AND SIDEWALKS. 4. MONITOR AND MAINTAIN THE SYSTEM TO MINIMIZE EQUIPMENT AND MATERIAL FAILURE. BROKEN SPRINKLER HEADS, LEAKS, UNRELIABLE VALVES, ETC. SHOULD BE REPAIRED AS SOON AS THEY BECOME APPARENT. 5. EDUCATE ALL MAINTENANCE PERSONNEL ON A CONTINUOUS BASIS ON THE ON THE PRESENCE OF RECLAIMED WATER PERSONNEL MUST BE INFORMED THAT RECLAIMED WATER IS MEANT FOR IRRIGATION PURPOSES ONLY, AND IS NOT APPROVED FOR DRINKING PURPOSES, HAND, TOOL WASHING, ETC. GIVEN THE HIGH TURNOVER RATE OF EMPLOYEES IN THE LANDSCAPING INDUSTRY, IT IS IMPORTANT THIS INFORMATION BE DISSEMINATED ON AN ALMOST DAILY BASIS. IT IS YOU, THE LANDSCAPE CONTRACTOR, WHO IS RESPONSIBLE FOR EDUCATING EACH AND EVERY ONE OF YOUR EMPLOYEES. 6. OBTAIN PRIOR APPROVAL OF ALL PROPOSED CHANGES AND MODIFICATIONS TO ANY PRIVATE ON SITE FACILITIES. SUCH CHANGES MUST BE SUBMITTED TO AND APPROVED BY THE DISTRICT ENGINEERING OFFICE AND DESIGNED ACCORDANCE WITH DISTRICT STANDARDS. 7. ALL RECLAIMED WATER SPRINKLER CONTROL VALVES SHALL BE TAGGED WITH INDENTIFICATION TAGS. A TAGS SHALL BE WEATHERPROOF PLASTIC 3/4" PURPLE IN COLOR WITH THE WORDS "WARNING -RECLAIMED WATER -DO NOT DRINK" ON ONE SIDE AND "AV/SO-AGUA IMPURA -NO TOVAR"ON THE OTHER SIDE. IMPRINTING SHALL BE PERMANENT AND BLACK IN COLOR USE TAGS AS MANUFACTURED BY T. CHRISTY ENTERPRISES OR APPROVE EQUAL B. ONE TAG SHALL BE ATTACHED TO EACH VALVE AS FOLLOWS: 1. ATTACH TO VALVE STEM DIRECTLY OR WITH PLASTIC TIE WRAP OR 2. ATTACH TO SOLENOID WIRE DIRECTLY OR WITH PLASTIC TIE WRAP OR 3. ATTACH TO VALVE COVER WITH EXISTING VALVE COVER BOLT. 8. ALL SPRINKLER HEADS SHALL BE IDENTIFIED AS RECLAIMED WATER SPRINKLER HEADS. II. EACH AUTOMATIC CONTROLLER AND ITS ASSOCIATED EQUIPMENT SHALL BE IDENTIFIED WITH A SIGN BEARING THE WORDS "RECLAIMED WATER USE FOR IRRIGATION" IN ENGLISH AND SPANISH WITH BLACK LETTERS 1" HIGH ON A PURPLE BACKGROUND. THE SIGN SHALL BE PLACED SO THAT IT CAN BE READILY SEEN BY ANY OPERATIONS PERSONNEL USING THE EQUIPMENT k 1 r----BLACK LOGO -r----PURPLEBACKGROUND 1" BLACK LETTERS ------36"-r (PRIVATE) I/ -vo,.w:, :"' "\ PROJECT SITE PMO R ·--~.,..,,.------------· / ,/ , ~ /-- / LEGEND 1" WATER METER/FUTURE RC.W. a::: \ ·' \ / ' / ' ' 'I \, CARLSB:D 1-1,"}" REDUCED PRESSURE BACKFLOW PREVENTER ----PROPOSED IRRIGATION MAINLINE GATE VALVE ,....-c4--+--n ··-·-·--i- i I --vJ-'------>PROPOSED POTABLE WATER LINE SHEET INDEX ---\;','{ ---POTABLE WATER MAIN (IN STREET) .INSPECTION PROCEDURES COVER SHEET.. ...... .. ................ SHEET 1 IRRIGATION PLAN .................................... SHEET 2 & 3 PLANTING PLAN ... ········--·······-··---------------SHEET 4 & 5 LANDSCAPE DETAILS-----------------------······· SHEET 6 ~fl,J-1 --RECLAJMED WATER MAIN (IN STREET) ~;'j AREA OF RECLAIMED WATER USE LANDSCAPE SPECIFICATIONS ............... SHEET 7 • "DO NOT DRINK" SIGN LOCATION . I. CITY CONSTRUCTION INSPECTION SHALL INCLUDE A LOCATION PIPE LINES. B. TRENCH DEPTH. C. REQUIRED SEPARATION (HORIZONTAL AND VERTICAL) D. PIPE IDENTIFICATION (P.O.C.) POINT OF CONNECTION. E. LOCATION AND IDENTIFICATION OF SPRINKLER HEADS. F. WARNING SIGNS AT THE SITE AND ON THE TRUCKS HAULING RECLAIMED WATER {IF RECLAIMED WATER IS USED FOR CONSTRUCTION). AN APPROVAL LETTER REGARDING THE INSPECTION OF THE PROJECT SHALL BE OBTAINED'FROM THE CITY AND DISTRICT, AND BE FORWARDED TO THE SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH PRIOR TO FINAL INSPECTION APPROVAL 11. DISTRICT FINAL INSPECTION SHALL tNCLUDE A COVERAGE TEST, AFTER COMPLETION OF THE SPRINKLER SYSTEM TO DETERMINE THE ADEQUACY OF COVERAGE ON THE APPROVED USE AREA AND PROTECTION OF AREAS NOT APPROVED FOR RECEIVING RECLAIMED WATER B. WARNING SIGNS AND LABELS. C. QUICK COUPLING VALVES. D. ALL ASPECTS OF THE IRRIGATION CONDITIONS, INCLUDING WINDBLOWN SPRAY, RUNOFF AND PONDING. E. REQUIRED PROTECTION OF ALL RESIDENTIAL AREAS. F. REQUIRED PROTECTION OF WELLS, STREAMS, RESERVOIRS. ETC. G. CROSS CONNECTION. ltl. ANNUAL INSPECTION SHALL INCLUDE: A COMPLETE INSPECTION WHICH SHALL COVER PART A PART BAND ' PART G OFT HE DISTRICTS FINAL INSPECTION. ,~" ( "1<;;) • I DECLARATION OR RESPONSIBLE CHARGE I HEREBY DECLARE THAT I AM THE LANDSCAPE ARCHITECT OF THE WORK FOR THIS PROJECT, THAT I HAVE EXERCISED RESPONSIBLE CHARGE OVER THE DESIGN OF THIS PROJECT AS DEFINED IN SECTION 6703 OF THE BUSINESS PROFESSIONS CODE AND THE DESIGN IS CONSISTENT WITH CURRENT STANDARDS. I UNDERSTAND THAT THE CHECK OF PROJECT DRAWINGS AND SPECIFICATIONS BY THE Cl"TY OF CARLSBAD AND THE SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEALTH IS CONFINED TO A REVIEW ONLY AND DOES NOT RELIEVE ME. AS LANDSCAPE ARCHITECT OF WORK, OF MY RESPONSIBILITIES FOR PROJECT DESIGN. THESE PLANS HAVE BEEN PREPARED IN SUBSTANTIAL CONFORMANCE WITH THE APPROVED LANDSCAPE CONCEP1PLAN, WATER CONSERVATION PLAN, FIRE SUPPRESSION PLAN, AND ALL CONDITIONS OF APPROVAL RELATED TO LANDSCAPING. DARSONO CUNNINGHAM, A.S.L.A. CALIF. RLA NO. 2418 4901 MORENO BLVD. #807 SAN DIEGO, CA 92117 OWNER/DEVELOPER (619) 27 4-2650 RON LISTER 3365 LAKE VIEW TERRACE ESCONDIDO, CA 92029 (760) 741-9800 APPROVED FOR PLANTING AND IRRIGATION ONLY, INCLUDING PRECISE REVISIONS MUST BE MADE BY PUBLIC El'IGINEER'S SIGNATURE REQUIRED ON PAGE 1 ONLY LOCATION OF PLANTING APPROVED AREAS. HEALTH ENGINEER, CITY PLANNING DIRECTOR, £18:t~~~ER cf J z:/ 2 6' AND DISTRICT ENGINEER PRIOR TO DATE IMPLEMENTATION IN FIELD "AS TITLE REVIE'v.'ED BY, INSPECTOR Landscape Architecture Planning 4901 Morena Blvd., Suite 807 San DieQo, GA 92117 RLA.12418 BUILT" DATE DATE WARNING RECLAIME WATER DONO DRINK RECLAIMED WATER AVISO -AGUA IMPURA NOTOMAR I S~ET I ') CARLSBAD MUNICIPAL WATER DISTRICT CITY OF CARLSBAD I S7ETS I PLANNING DEPARTMENT SIZE: 12" x 36" .060 ABS PLASTIC OR STICK ON VINYL SIGNS ALSO .016 ALUMINUM 1" BLACK LETTERS ~-2" BLACK LETTERS (fit!l:) Jll' ,: 18'' . ellb AUNl!,llM -~0/t> 1-ee F\.1'5flC ~ e(ICj<-~ VIN11.-9la-(<l, f 7'/ .c( "f)/ .,,:l1. .. -:;-/ _ __,_. ·r•·-: ~ _, _z . .,· / ;_,.':'.-:f-!-;->-:<.a:-. - WILLIAM E. PLUMMER, OISTR ENGR. R.C.E. 28176 SAN DIEGO COUNTY DEPARTMENT OF ENIJIROrErT)Lf EAL.J:.H()_ -i,.,J , ) '---;;., ~ ----•'· - APP.ROVED BY: . , -:,:·_. -y /,. -,,..j {:_ '-c' ( • i,;.-~---., DATE 4-1.... "t-<t8 OATE INITIAL DATE INl11AL DATE ENGINEER OF WORK REVISION DESCRIPTION OTHER APPROVAL !f»§J{Uj})/~lf€ ~Ytfl 1f v7F,:~llFNJ)]~ 11{~[&:,~{1= ffeI'#JlfkfJ:f. I PROPOSED FACILITY FOR; I HOT DOG ON A STICK / FIRST MECHANICALI CARLSBAD, CALIFORNIA -_- APPROVED_ . /. ' / _r-_· -.~ ,-. --,· ,·-·-•:o':"1 ./.-;-~ ..,,: -~ . .; ... 7 _,,f'" 1':"~~ •. e:-> ASSISTANT PLANNING DIRECTOR D.~TE OWN BY: PROJECT NO. . DRAWING NO. DATE INl11AL CHKD BY: CITY APPROVAL RV'v.'D BY1 MS 96-11 357-GL co -.:t N I r-,. O') . Cl ~ :!i . u / i I I J / j , i / · ~ 12 STATION AUTO !TIC .._---IRRIGATION CONT~~LLER "A" --~-/' _:::-,....=--__ t:r-:--l=-1 C=-"'"'-:..-'T.:_l::,:::.._:F'_P__,:T>--'-..':'.'.&~L:::E,--'N}>;~T!....':i:::'.:..f<_H:...:..::.__ETEl.c:'..'..f<~. -- / -e--U:t:v~ AU,, f<E.:::::lfalHE"D NATI:!< L--UJ E0 cP~I !-J:t:i Fb7>,BLe i~TE: R L-, I lJE<::, CTf Plc.>-[;J 0 ' \ SCALE: 1" = 20' I I IRRIGATION CALCULATIONS IRRIGATION LEGEND · 1-1/2" R.CV. #A-7 = 32 GP M SYMBOL MANUFACTURER DESCRIPTION RAD FULL HALF QTR PSI - STATIC WATER PRE.SSURE-100.0 P.S.L V Q RAINBIRD #1800-10 LOW ANGLE SPRAY RAINBIRD #1800-12 LOW GALLONAGE SPRAY RAIN BIRD #1800-15 STANDARD SPRAY ~INBIRD #1800-15SST SIDE/END STRIP SPRAY RAINBIRD #1402 BUBBLER 10' .79 .39 30 ),( V "v 12' 2.6 DESIGN PRESSURE ..................................... 30.0 P.S.I. ~ cb .65 30 1.30 LATERAL LINE ....... ...................................... 3.5 PS I. 0 15' 3.7 1.85 .93 30 MAIN LINE (330 LF. -2") _ . ..... _ . 2.8 PS I □ [I 4'X15' 1 21 .61 30 RC.V ... .. . . .. . . . . . . ___ . 1.5 PS.I 1-1/4" BACKFLOW PREVENTER ................ 13.0 P.S.I. 0 0.5 30 1-1/4" PRESSURE REGULATOR .................. 8.0 P.S.I. Ci) 1" WATER METER... .. .. .. ........................ 6.0 P.S.I. HUNTER #PGS-ADJ-03 ROTOR SPRINKLER (QTR.) 30' 90 30 TOTAL PRESSURE REQUIRED.......... 64.8 P.S.I. @ HUNTER #PGS-ADJ-05 ROTOR SPRINKLER (HALF) 34' 1.60 30 30 --.....,;:-__ '. • 1. 2. 3. 4. 5. 6. 7. IRRIGATION NOTES ® © ® (1) ® -$ ~ ® N ® H HUNTER #PGS-360-08 ROTOR SPRINKLER (FULL) 37' HUNTER #PGH-ADJ-03 HIGH POP ROTOR SPR. (QTR.) 30' HUNTER #PGH-ADJ-05 HIGH POP ROTOR SPR. (HALF) 34' HUNTER #PGP-ADJ-03 POP-UP ROTOR SPR. (QTR.) 30' HUNTER #PGP-ADJ-05 POP-UP ROTOR SPR (HALF) 34' RAINBIRD #PESB SERIES REMOTE CONTROL VALVES 3.2 .90 30 1.50 30 .90 30 1.60 30 RAINMASTER RME12SE 12 STATION AUTOMATIC IRRIGATION CONTROLLER NELSON #7645 1" QUICK COUPLING VALVE WIPURPLE LOCKING COVER WILKINS #975XL 1-1/4" REDUCED PRESSURE BACKFLOW PREVENTER WILKINS #500YSBR 1-1/4" PRESSURE REGULATING VALVE HAMMOND #HV8201 BALL VALVE (LINE SIZE) ALERTLINE/PACIFIC CAL CL 200 LATERAL LINE ( ~~1-l;) ALERTLINE/PACIFIC CAL PVC SCH 40(1-1/2"<); CL 315 (2">) (ftl~) PVC CL/ . SLEEVE {TWO SIZES LARGER THAN INSIDE PIPE) PVC CL . : _I IRRIGATION CONTROL WIRE CONDUIT ( '2.':) _[SJ; POINT OF CONNECTION (1" IRRIGATION WATER METER· BY OTHERS) THE IRRIGATION PLAN IS DRAWN DIAGRAMMATICALLY. LOCATE ALL PIPING AND EQUIPMENT IN PLANTING AREAS WHERE POSSIBLE. ALL LATERAL END RUNS SHALL BE 1/2" SIZE UNLESS SHOWN OTHERWISE. r"'l.-~IB PVC.- ALL VALVES SHALL BE INSTALLED IN VALVE BOXES. LOCATE ALL QUICK COUPLING, REMOTE CONTROL AND GATE VALVES ADJACENT TO WALKS OR CURBS. ONE RCV. PER VALVE BOX . ALL IRRIGATION PIPE UNDER VEHICULAR PAVING SHALL BE INSTALLED IN PVC ~;fa SLEEVES (30" MIN. COVER). ALL PIPE UNDER OTHER PAVING AREAS SHALL BE INSTALLED IN PVC~ SLEEVES (18" MIN. COVER). CONTROLLER WIRES LOCATED UNDER STREET AND OTHER PERMANENT IMPROVEMENTS SHALL BE INSTALLED IN SEPARATE PVC CL 315 SLEEVES (30" COVER UNDER VEHICULAR PAVING; 18" COVER UNDER OTHER PAVING) SLEEVES SHALL BE AT LEAST TWICE THE DIAMETER OF THE PIPE OR WIRE BUNDLE TO BE ENCLOSED, WITH A MINIMUM OF 2" DIAMETER SIZE. METALLIC BACKED LOCATING TAPE SHALL BE INSTALLED ALONG THE SLEEVE. c,:t1ee-. SPRINKLER HEADS WITHIN ';f~. FEET OF PEDESTRIAN OR VEHICULAR PAVING SHALL BE 12" POP-UP. LAWN/TURF, WHEN SPECIFIED, SHALL BE 4'" POP-UP. ALL OTHER SPRINKLER HEADS SHALL BE INSTALLED ON RISERS, 6" ABOVE FINISH GRADE. ADJUST ALL SPRAY HEADS TO ELIMINATE THROW ONTO WALLS, WALKS, WINDOWS, ETC .. INSTALL ANTI-DRAIN VALVES UNDER SPRINKLER HEADS TO PREVENT LOW HEAD DRAIN AND PREVENT EROSION/RUN-OFF DUE TO SITE TOPOGRAPHY, UNLESS FACTORY INSTALLED CHECK VALVES ARE SPECIFIED. THERE SHALL BE NO LOW HEAD DRAINAGE. SERVICEABLE CHECK VALVES LOCATED IN VALVE BOXES OR ON RISERS (ABOVE GRADE) ARE REQUIRED WHERE ELEVATION DIFFERENTIAL MAY CAUSE LOW HEAD DRAINAGE. 8. INSTALL (1) W.C.S. "RAIN-GUARD" RAIN SHUT-OFF DEVICE PER CONTROLLER PER MANUFACTURER'S RECOMMENDATIONS. 9. IFANY EXISTING HARDSCAPE, IRRIGATION OR LANDSCAPE INDICATED ON THESE PLANS IS DAMAGED OR REMOVED DURING DEMOLITION OR CONSTRUCTION, IT SHALL BE REPAIRED AND/OR REPLACED IN KIND AND EQUIVALENT SIZE. 10. ALL EQUIPMENT SHALL BE COMPATIBLE WITH RECLAIMED WATER. ALL WORK WITH RECLAIMED WATER SHALL COMPLY WITH CARLSBAD COMMUNITY WATER DISTRICTS RECLAIMED WATER REQUIREMENTS, AS WELL AS THE CITY OF CARLSBAD'S "LANDSCAPE MANUAL". PARTICULAR CARE SHALL BE TAKEN TO ASSURE THAT ALL EQUIPMENT IN THE RECLAIMED WATER SYSTEM SHALL BE WELL MARKED WITH ALL THE WARNING DEVICES REQUIRED BY THE SAN DIEGO ~-COUNTY-loF ENVIRONMENTAL HEALTH, CARLSBAD COMMUNITY WATER DISTRICT AND THE CITY OF CARLSBAD. 'ALERTLINE' OR 'PACIFIC CAL' PIPE SHALL BE INSTALLED. ---CONTROLLER SEQUENCE 11. PROVIDE CLEAN BACKFILL MATERIAL WITH NO LARGE ROCKS FOR ALL IRRIGATION TRENCHES. REFER TO IRRIGATION SPECIFICATIONS. SHEET L-7-l -f) -RC.V SIZE . ~~~,~~~rnl~l~i~~ Landscape Architecture Planning 4901 Morena Blvd .• Suite 807 San Diego, CA 92117 R.L.A. #2418 12. IRRIGATION INSTALLATION IN THE GENERAL UTILITY EASEMENT (G.U.E.) SHALL BE IN ACCORDANCE WITH UTILITY COMPANY'S REQUIREMENTS FOR MATERIAL AND MINIMUM SEPARATION. APPROVED FOR PLANTING AND IRRIGATION ONLY, INCLUDING PRECISE LOCATION OF PLANTING AREAS. "AS BUILT" TITLE _______ _ REVIE\./ED BY1 INSPECTOR DATE DATE t---t-----t------------+-----lf---+--+---11 SH2EET I CITY OF CARLSBAD I SHE7ET. s I PLANNING DEPARTMENT ::==:::'...'.:::==========.:.:== 0A TE INITIAL DATE INlllAL DATE INITIAL ENGINEER OF WORK REVISION DESCRIPTION OTHER APPROVAL ~TY APPROVAL fF!tJlf,_JtfJf!ElPs. llftf fil 'lf Dril!l©l1JJf£ '!rl?iOfel IL rPi'JfF?.f}[ PROPOSED FACILITY FOR: HOT DOG ON A STICK / FIRST MECHANICAL CARLS!:JAO, CALIFORNIA APPROVED ASSISTANT PLANNING DIRECTOR OWN BY: ---1 PROJECT NO. CHKD BY: __ _ RV\./D BY• MS 96-11 DATE DRAWING NO. 357-6L OQ ,q- N I r-- CT. C $ :i L ~e::ive ,.l;s[.l. l'<E?l>li-Jf O l~ll::J< LI !J E0 ?~i[la,i fl?ThEJ..A?, f',::;,'1)-s .~LE.·· ~-,J>TE,1< LlUe.& lTTf'IO-l,) __ -1-------1" IRRIGATION WATER METER ..------1-1/4" REDUCED BACKFLOW PREVENTER ,.----1-1/4" PRESSURE REGULATOR PALMER WAY --- 12 STATION AUTOMATIC .. ---4 IRRIGATION CONTROLLER "B" V SCALE: 1" =-20' 0 I)/) I HE.7]::J< 0LE.E>/E,;;,,u..., ~ I f'1 ED ~ IJPTE:-F' L-iUfh C~..,;;al lld:1 ~Bl£, l~f< l..,fl!Eb CJTFIC.Psl..,) ,------1" IRRIGATION WATER METER ,-----1-1/4" REDUCED BACKFLOW PREVENTER .----1-1/4" PRESSURE REGULATOR 1---t----t1rrt----W------I-----+- . 12 STATION AUTOMATIC __ IRRIGATION CONTROLLER "C" SEE SHEET 2 FOR IRRIGATION LEGEND AND NOTES APPROVED FOR · PLANTING AND IRRIGATION ONLY, INCLUDING PRECISE . LOCATION OF PLANTING AREAS. "AS BUILT" RCE ___ EXP. ___ _ DATE REVIEWED BY: INSPECTOR DATE ·--+--.. -~---·-----------+--+---+---1----1 I SH~ET I crrxNN~r ~~~~~N~AD I SH~~s I !P't'?J8=1!1!{JiE;/H; ~Wfal '1f O(jl!]tI:JJll!J~ Vff?Ofal/L !FftJfRIJ{ PROPOSED FACILITY FOR~ t----+---if-----·------------+--+---+---+---1 HOT DOG ON A STICK / FIRST MECHANICA 4901 Morena Blvd., Suite 807 San Diego, GA 92117 R.L.A. #241 B ---+-----1-·-····· ··-·----------+------+---+--+-----1 ;='='='====='=C=A:::::R=L:=;:=S,=:B=,,A=D=-=,=C=A=L=IF=O=R=N=IA===== ---+-----+-. ---·------------+---+----t----t---1 APPROVED.___,.--:~/:~-~-_,-r·.~.:.°-'" ----•~,;/- ===-=--=-:--=-----r·-·--=--·-·-_· -=----=----=----=----=----=----=----=----=----=----=----=----=----=----=----=----=------=--~+----=----=----=--:1----=----=--~+1---=----=----=--~+----=----=---=---1 ;:;;-,-A;;:s-;s-_::;IS-.;:;T-A;N:::::T-::-P:::l.: .... ,:::::A-::N-N;l:::::N-G;o;1R;E~C-T;;O;R;~-;:,-;;=-=-~~DA=:T:::E===~ 0 A TE INITIAL DA TE INITIAL OA TE INITIAL -==-+=.--. ----------------+--+----+--=-+..,.,,.-----ii D'M--J BY: ---PROJECT NO. I DRA1MNG NO. ENGINEER Of WORK REVlSION DESCRIPTION OniER APPROVAi. QTY -'PPROVAL 2~ :{:--MS 96-11 357-GL • ' ~ ~~~~----------------------------~------------------------...ill!!!!!'lllll!l~!ll!l[lllll~---IIDlllil----.... LA MESA BLUEPRONJ ~ -5/" ~ 0 ... (' " (l (l ' .. ,c _. .. "' (. .,..,_ ..----------'Y' STRAINER 12' MIN. ._ _____ REDUCEOPRESSUREBACKFLOW PREVENTER W/(2) GATE VALVES BRASS UNION --,i--BRASS/COPPER ELL 11-r-BRASS/COPPER RISER (NIPPLE) FINIS11 GRADE PVC Tl1REAOED ADAPTER --- ..__ __ 1 CU. FT.CONCRETE THRUST NOTE: APPLY TWO (2) COATS BLOCK. ENAMEL PAINT TO ABOVE GRADE BACKFLOW ASSEMBLY -APPROVED RECLAIMED WATER WARNING COLOR REDUCED PRESSURE BACKFLOW PREVENTER tN,Eff,Al-l, ~ C,,fvl,W,O, 610, tw6-, 4-W~UJ 9 ;.. SHRUB ROOT BALL TO BE FLUSH W/FINISH GJIAOE. :."': ·~ti}I 'v,.)(:X')l)f;• ~,+·---PLANTING TABLETS PER , :, · ,,:t MANUFACTU REA'S RECOMMENDATION ···:lJ :: ·~: "-.><.xn~}~>: BACKFlLL (PEA SPECIFICATIONS) NATIVE SOIL +---2 X ROOT BALL DIAMETER SHRUB PLANTING ~.k~r===n----'CINCH-TIE'. LOCATE AT MIN. HEIGHT REQUIRED TO PROVIDE SUPPORT. 1,.1----2" • 10' LODGE POLE ,-.1-1----· ROOT BALL FLUSH W/ FINISH GRADE 4" HIQM TEMPORARY [ WATER BASIN ---FINISH GRADE / ' '-XA,'v"I liO'-'M---PLANTING TABLETS PER MFTRS RECOMMENDATION -1---BACKFILL (PER SPECS) -l------2 x ROOT BALL DIAMETER BREATHER TUBE : 4" PER. PIPE: 2 PER 24" BOX TREE; 1 PER 15 GALLON TREE TREE PLANTING & STAKING 12' MIN. "SNAP•TrtE• WIRE r---------CONNECTORSANO EXPANSION COILS, 10 WFIAPS AROUND 1/2" PIPE · PURPLE 12' X ur 11n1111 PLASTIC ------VALVE BOX WITH LOCKING COVER. FINISH GRADE ,------11-REMOTE CONTROL VALVE DR ASS UNION ANO NIPPLES PVC ELL 4" MIN a• MAX PURPLE r----12•~ 18' ~nl!l!II PLASTIC VALVE BOX W/ LOCKING LIO MARKED "IRA. G.V." r---GATE/BALLYALYE --FINISH GRADE r---~1--BRASS UNION & NIPPLE ,--+!---PVC SCH 40 ADAPTER PURPLE .,_ ______ 10" ROUND ftl'tl!l!II PLASTIC VALVE BOX. F!NISH GRADE i----111----QUICK COUPLING VALVE BRASS NIPPLE, LENGTH AS REQUIAED ~---6" DEPTH PEA GRAVEL /-ll---90 ELL ,-11----BRASS-STREET ELL ~-BRASS NIPPLE 6" MIN. LENGTH IATERAL LINE BRASS STREET ELL FINISH GRADE (GROUND COVER) (2) 16d GALV. NAILS "'"71'--MAIN LINE CONTROL WlflES FROM ..,_ _____ IRRlOATION CONTROLLER REMOTE CONTROL VALVE ,...... ________ CURBbWALK OR FOUN ATION ;_-:.,J.4~ ·:.:/_ ._ .. :-~:- ..................... ~-= .: ,----POP-UP SPRINKLER f 4• MIii. r FINISII GRADE 11-,.-Tf r--PVC SCH 80 NIPPLE 1.-.!J-.V --2 PVC SCH 40 ELLS · (T x T) ,........ __ PVC SC" 40 TEE (Sx S xT) f2_ ..... c:;;;;~~~)=~J-PVC LATERAL LINE PVC SCII 80 NIPPLE PVC SCll 40 ELL -----. S IDEll'ALK· I ~ '------1 CU FT PEA GRAVEL ~---BRASS NIPPLE -----PVCSCH40ADAPTER GATE/BALL VALVE ~ lo FINISH GRADE ~11~1~ ! II*---PVC SCH 80 RISER ~ 1 --2 PVC SCH 40 ELLS (TxT) ,....... __ PVC SCH 40 ree ·~-lllllllia,t::_ [S x S x T) :;;.;..:;;;;-i;~~Jm.att;I-PVC LATERAL LINE PVC SCH 10 NIPPLI! PVC SCH ~o !LL ----< #4 REBAR STABILIZER 36" MIN LENGTH, SECURED W/--1 2 STAINLESS STEEL STRAPS , .....__PVCSCH40TE~ ..._ ______ PVC MAIN LINE DEPTH AS REQUIRED NOTE: QUICK COUPLER SHALL .QUICK COUPLER BE APPROVED FOR USE WITH RECLAIMED WATER. - .c s I= . ... ,. - fo . a••J ... ,,. ,&,"~';, -,:;: ·,; . Eii..' :. ' ' ,. -~ > 1. .,_ • • _., tf. ::_'_Jr~-~~.·-.>~-: ~ _:J'.. . '.,.:t / / "' (!) . " ~ . ,-, :_-~ • :i-.. ,, .... ... --~,,_. ' ·. ,( ~ ', ........ -, . ' • ~ ., ' • • <' ' VANDAL PRO OF ENCLOSURE WALL MOUN T CONTROLLER 1.20VON-OFF SWITCH UIT 120VAC CONO OR ES SWEEP ElLF CONTAOLWIR STAINLESS ST EEL MOUNTING ST MANUFACTUR UOS PEA ER -Fl NISH GRADE l POP-UP SPRINKLER CURB MFTER BOX II' /M[T[R SHRUB SPRINKLER CONTROLLER IIN ENCLOSURE! · 2" X 4" RWD HEADER FINISH GRADE (TURF) 11.1---2"X4"X18"POINTED. RWDSTAKE REDWOOD HEADER ' 00 POTABLE SERVI CE LI NE~ ~-□'-0" MJN, TO POTABLE MAINLINF JN STREET -•.•I ·-:--;,1 ii I:', .. ,1 ! RECLAIMED WATFR IRRIGATION MAINL!Nt W/SLEEVE NOTE: All RECLAIMED WATER IRRIGATION PIPE AND SLEEVE SHALL BE PURPlt AND LABELED AS SPECIFIED IN: -STANDARD SPFCIFICATJONS FOR PRIVAIL 1RRIGATION SYSTEMS -CARLSBAD RECLAMATION RULES AND REGULATIONS FOR CONSTRUCTION OF RFCI AIMED WATER MAINS 'OCIOBER 1993. POTABLE MAINLINE CROSSING POI All LE MA Hlll NE fSt!:: IMPROVEMENT DRAWINGS I~ 3.5 FffT 12" MINIMUM REO!IIRED vunJCAL > SEPARATION SLEEVE RFCAllMEfJ WAIER IRRIGATJON----~ MA I NL! NC NOTE: VERIICAL CLEARANCE OF 12" MINIMUM IS MANDATORY WHEN CROSSING PAlH OF A POT!\BLE WATER LINE. HISTALLAI ION OF RECLAIMED WATER IRRIGATION MAINLINE 24" FRm\ FAC[ OF SIDE'IIALK \,ILL PROVIDE IHE NECESSARY 10'-0" HOR!70NTAL CLtARANCE FROM POTABLE MAINLINF JN THE STREET, POTABLE SERVICE LINE CROSSING APPROVED FOR PLANTING "AS darsnnn (619}274-2650 m~r~u~1Jff ffi~~rni~rrrni Landscape Architecture Planning 4901 Marnna lllvd , Suite 807 San Diego, CA 92117 RLA. #2418 BUILT" 4"ROUNDORATE---.,.. EDGE OF SIDEW AUC AND IRRIGATION ONLY, FINISH GAAD.E/_ SURFACE ' •' . ' NOTE: WRAP B'REATHER TUBE· WITH FILTER FABRIC ' __ _,,,,"-/ TREE PLANTING BREATHER TUBE EQUAL " • . .:. ., . ' ..... :'· _._, . . . . ' .·. : , .. ·., .... , . :-. ROOT RIEA, OR EQUAL 24' 'DEEP ROOT' COITTROL BAR INSTALL PER M RECOMMENDA ]- ANUFACTURER'S TJONS. TREE 12' EQUAL ' . . . : ~·.: _',:.: ._ :•>: ~-i ,' ... _ :_ ~~;. ~ .• •·• .:~~ --- . tit w ii: ~ ' ' ~ . ., ROOT CONTROL BARRIER .. :... •. · .. ti) ti) !:l cc 0 <O ,. DATE INITIAL ENGINEER OF WORK REVISION DESCRIPTION INCLUDING PRECISE TITLE DATE LOCATION OF PLANTING REVIE\,/ED llY• AREAS. INSPECTOR DATE I SH~ET I CITY OF CARLSBAD I SH~ETS I PLANNING DEPARTMENT lf!#lfUiJJ!cff!2 ~Wfal 'Y' OC1]@1jjj£TfTJP0/4\/L, rPfalfflf% PROPOSED FACILITY FOR; HOT DOG ON A STICK / FIRST MECHANICAL CARLSBAD, CALIFORNIA APPROVED ,. J ~ ,. -,--~ ,.,,.,,.. .. ____ o»"l _-,. .. > I: d;t'; ... ·~:, -,'~~;. AS.SI ST ANT PLANNING DIRECTOR DATE DWN BY: PROJECT NO. DRAWING NO. DATE INITIAL DATE INITIAL CHKD BY: OTHER APPROVAL crrv APPROVAL RV\,/D BY, MS 96-11 357-6L