HomeMy WebLinkAbout5814 VAN ALLEN WAY; ; AS070295; Permit9/15/2020 AS070295 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 58I4 VAN ALLEN WY
Permit Type: SPRINK
Parcel No:
Lot #: 0.
Permit No: AS070295
Status: ISSUED
1Applied 12/26/2007
Approved: 12/27/2007
Reference No.: . I Issued: 12/27/2007
- PC #: Inspector:
Project Title: T.D. AMERITRADE TI FIRE SPRINKLER PLAN CHECK &
INSPECTION
Applicant: Owner:
SCHMIDT FIRE PROTECTION CO INC
4760 MURPHY CANYON RD
SAN DIEGO, CA 92123
858-279-6122
Fees ($) Add'l Fees ($) Total ($) Balance ($)
130 . 0. 130 0
October 12, 2007 Sprinkler 41a
MICROFAST® AND
4J I F(I Ir1Gi I:II[u.r.if MicrofastHP® QUICK
RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcsvikingcorp.com
1. DESCRIPTION
Viking Microfasta and MicrofastHP® Quick Response Pendent Sprinklers are small,
.thermosensitive, glass-bulb spray sprinklers available in several different finishes and
temperature ratings and K-Factors to meet design requirements. The special Polyester
and Teflon® coatings can be used in decorative applications where colors are desired.
In addition, these coatings have been investigated for installation in corrosive at-
mospheres and are cULus listed as corrosion resistant as indicated in the Approval
Chart. (Note: FM Global has no approval classification for Teflon® and Polyester coat-
ings as corrosion resistant.)
2. LISTINGS AND APPROVALS
-cULus Listed: Category VNIV
FM Approved: Class 2020
-,,,NYC Approved: Calendar Number 21-76-A and MhA 83--h, volume lb
ABS Certified: Certificate 04-H5407984C-PDA
VdS Approved: Certificate G4040095, G4040097, G4060056, G4060057, G4880045, G4930038, and G4980021
LPC Approved: Ref. No. 096e/03 and 096e104
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40130, and
0786-CPD-40170
WED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008
NOTE: Other International approval certificates are available upon request.
-Refer to the Approval Chart on page 41d and Design Criteria on page 41e for cULus and FM approval requirements that must be
followed.
3. TECHNICAL DATA
Specifications:
Available since 1987.
Minimum Operating Pressure: 7 psi (0.5 bar)
Maximum Working Pressure: Sprinklers 12282 and 12290 are rated for
use with water working pressures ranging from the minimum 7 psi
(0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pres-
sure (HP) sprinklers can be identified by locating "250" stamped on
the deflector. All other Part Nos. not mentioned above are rated to a
maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
'Thread size: Refer to the Approval Chart
Nominal K-Factor: Refer to the Approval Chart
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: Refer to the Approval Chart
Viking Technical Data may be found on
The Viking corporation's Web site at
hftp://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
Material Standards:
Frame Casting: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-051000 or Copper UNS-C19500 for Sprinklers 06662B, 06666B, 06765B, and 12104. Copper
UNS-C19500 for Sprinkler 12282. Brass UNS-C26000 for all other Sprinklers.
Bushing (for Sprinklers 06718B, 06720B, and 12290): Brass UNS-C36000
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-530400
Pip Cap Attachment: Brass UNS-C36000
Ejector Spring (for Sprinkler 12104): Stainless Steel
Form No. F_081296 Replaces page 41 a-f, dated September 20, 2007.
(Updated VdS and CE Approval.)
A 01-0115
Sprinkler 41 b October 12, 2007
MICROFAST® AND
MicrofastHP® QUICK
RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcsvikingcorp.com
for Teflon® Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-Teflon® Coated
For Polyester Coated Sprinklers: Belleville Spring-Exposed
Ordering Information: (Also refer to the current Viking price list.)
Order Microfast and MicrofastHP® Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler fin-
ish and then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome-Enloy® = F, White Polyester = M-/W, Black Polyester = M-/B, and Black Teflon® = N
Temperature Suffix (°F/°C): 135°/68° =A, 155°/68° = B, 175"/79° = D, 2000/930 = E, and 2860/1410 = G
For example, sprinkler VK302 with a 1/2" thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 06662BAB
Available Finishes And Temperature Ratings:
Refer to Table 1 ,
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches:
Standard Wrench: Part No. 10896W/B (available since 2000).
Wrench for coated and/or recessed sprinklers: Part No. 12144W/B** (available since 2003)
NOTE: RECESSED PENDENT SPRINKLERS WITH PROTECTIVE CAPS MUST USE WRENCH 12144W/B.
""A 1/2"ratchet is required (not available from Viking).
Sprinkler Cabinets:
Six-head capacity: Part No. 01724A (available since 1971)
iB. Twelve-head capacity: Part No. 01725A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
it Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7... AVAILABILITY
TJie Viking Microfast® and MicrofastHP® Quick Response Pendent
prinklers are available through a network of domestic and
international distributors. See The Viking Corporation web site for
.the closest distributor or contact The Viking Corporation.
8 GUARANTEE
For details of warranty, refer to Viking's current list price schedule
or contact Viking directly.
Wrench
Flats Protective
Sprinkler
Cap
10896 Q
Figure 1:
Standard Sprinkler Wrench 10896W/B
October 12, 2007 Sprinkler 41c
MICROFAST® AND I
',*I I KIW*j MicrofastHP® QUICK I
RESPONSE PENDENT I
SPRINKLERS I
The Viking Corporation, 210 N Industrial Park Road, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcsvikingcorp.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum Ambient Bulb Color Classification Temperature Rating' Ceiling Temperature'
Ordinary 135°F (57 °C) 100 °F (38 °C) Orange
Ordinary 155°F(68°C) 100°F(38°C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler Finishes: Brass, Chrome-Enloy®, White Polyester, Black Polyester, and Black Teflon®
Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black Teflon®
Footnotes
1. The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
- Jurisdiction. Refer to specific installation standards.
3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on
pges 41d. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through
the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the
coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with
Polyester and Teflon® coatings.
Sprinkler Wrench
12144//B** for
installing coated
and/or recessed
pendent sprinklers Carefully slide the
th protective caps. - wrench sideways
S
------ ' around the protective -- cap, ensuring engage-
ment with the sprinkler
A 1/2 ratchet is required wrench flats,
:not available fron Viking).
Figure 2: Wrench 12144W/B for Coated and/or Recessed Pendent Sprinklers
Sprinkler 41d October 12, 2007
MICROFAST® AND
'I 11(1 Is16 i:iir.qu.y.v., MicrofastHP® QUICK
RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcsvikingcorp.com
Approval Chart r-Temperature KEY
Fin h
is Microfast® and MicrofastHP11 Quick Response Pendent Sprinklers t Escutcheon (if applicable)
Maximum 175 PSI (12 bar) WWP
Sprinkler Thread Size Nominal Overall Listings and Approvals3
Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.)
Part No.' NPT
_
BSP U.S. metric2 Inches mm cULus4 FM5 NYC- VdS LPCB I s
Standard Orifice
06662B VK302 1/2" 115 mm [ 5.6 1 80.6 [ 2-1/4" 1 58 1 AiX, B1Y I A3X, 133Y AiX, 131Y A3 A3X, 133Y C3X, E3Y13 C3X, E3Y'5
Large Orifice
0666613 VK352 3/4" 20 mm 8.0 115.2 2-3/8" 60 AiX, B1Y A2X, 132Y AiX, B1Y -- -- F3X, E3Y13 --
12164 VK352 3/4" 20 mm 8.0 115.2 2-1/4" 58 -- -- -- G3 -- -- -
06765B VK352 1/2" 15 mm 8.0 115.2 2-3/8" 60 AiX, B1Y - AIX, BIY A3 -- -- --
Small Orifice'
067181310 VK329 1/2" 15 mm 2 40.3 2-3/16" 56 AiX, B1Y A2X AiX, B1Y -- -- -- --
06720 1 VK331 1/2" 15 mm 4.2 60.5 2-1/4" 58 AiX, B1Y -- AiX, 131Y -- -- -- --
0693213 VK331 -- 10 mm 4.2 60.5 2-3/8" 60 -- -- -- A3 -- G214 --
Maximum 250 PSI (17 bar) WWP
Standard Orifice
Srinkler Thread Size Nominal Overall Listings and Approvals'
Base SIN K-Factor Length (Refer also to Design Criteria on page 41e.)
Part No' NPT BSP U.S. metric2 Inches mm cULus4 FM NYC" VdS LPCB CE 0
12282 VK317 1/2" 15 mm 5.6 80.6 2-1/4" 58 AiX, B1Y - AIX - -- -- --
Maximum 250 PSI (17 bar) WWP
-
... Small Orifice9
T1229019 VK342 1/2" 115 mm 2.8 I 40.3 2-3/16" 56 I AiX, B1Y I - AIX --
Approved Temperature Ratings Approved Escutcheons
-A - 135 ¶F (57 "C) 155 "F (68 "C) 175 "F (79 "C) 200 "F (93 "C), Approved Finishes X - Standard surface-mounted escutcheon or
and 286 *F
B-- 135 "F (57 "d), i55"' (68 "C), 175 "F (79 "C), and 200 "F (93 "C) 1 - Brass, Chrome-Enloy, White Poly- the Viking Microfast Model F-i Adjustable
C - 155 "F (68 "C), 175 "F (79 °C), 200 °F (93 "C), and 286 "F ester78, Black Polyester'.', and Black Escutcheon12
- (141 "C) Teflon 7 V - Standard surface-mounted escutcheon or
ii- 135 °F (57 "C), 155 "F (68 "C), 175 "F (79 "C), and 286 "F 2- Brass and Chrome-Enloy® the Viking Microfast® Model F-i Adjustable
- (141 "C) 3-Brass, Chrome-Enloy®, White Polyester8, Escutcheon12 or recessed with the Viking
: C), and 286 oF (141 and Black Polyester8 Micromatic® Model E-i or E-2 Recessed
.G- 155 "F (68 "C) Escutcheon
Footnotes
Base part number is shown. For complete part number, refer to Viking's current price schedule.
-Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 36T-his table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
Lted,by Underwriters Laboratories Inc. for use in the U.S. and Canada.
FM Approved for use only in wet-pipe sprinkler systems (or preaction systems qualifying as wet systems) for protection of occupancies described in the Factory
1utuaI'Engineering and Research Loss Prevention Data Sheets and Technical Advisory Bulletins.
-Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA.
cULus Listed as corrosion resistant.
Other colors are available on request with the same Listings and Approvals as the standard colors.
Listingsand Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only.
"'The sprinkler orifice is bushed.
."Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 16.
2The'Viking Microfast® Model F-i Adjustable Escutcheon is considered a surface-mounted escutcheon because it does not allow the fusible element of the
..sprinkler to be recessed behind the face of the wall or ceiling. .13?( Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003.
1(( Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40130 and 0786-CPD40170.
15 MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008.
ty
Installed with a
standard 1/8' surface—
mounted escutcheon,
1/2'
RPT
(15. rim)
W9, awx 2-1/4'
1-5/8' (58 mm)
(41 mm)
Pendent Sprinkler
06662B (VK302) Installed with a Microfast
Model F-i Adjustable Escutcheon
1-1/2' (38.1 mm)
Minimum
2'
(50.8 mm)
Maximum
I.
October 12, 2007 Sprinkler 41e
MICROFASP AND
Microfasti-1136 QUICK
RESPONSE PENDENT
SPRINKLERS
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
i e1ePh01e: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
DESIGN CRITERIA
(Also refer to the Approval Chart on page 41d)
cULus Listing Requirements:
Micrdfast® and MicrofastHP® Quick Response Pendent Sprinklers are cULus Listed as indicated in the Approval Chart for installation in accordance with
the latest edition or NFPA 13 for standard spray sprinklers.
Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where allowed by
the installation standards being applied, with hydraulically calculated wet systems only).
The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
FM Approval Requirements:
For installation in accordance with the latest applicable FM Loss Prevention Data Sheets and Technical Advisory Bulletins. FM Global Loss Prevention
Data Sheets and Technical Advisory Bulletins contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design,
ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
.'Standards, whenever applicable.
Ceiling Opening Size:
2-5/16' (58.7 mm) minimum 2-1/8' 2-1/2' (63,5 mm) maximum (54 mm)
Figure 3: Sprinkler VK302 Dimensions with a Standard Escutcheon and the Model F-I Adjustable Escutcheon
p
Sprinkler 41f October 12, 2007
•• MICROFAST® AND N I1I MicrofastHP® QUICK
RESPONSE PENDENT
SPRINKLERS
111r, VIRIIIJ uipuiaiiuii, LIV II IIIUULIIW rwl% r%UaU, 142LIIIJ lvii tU.JU
"Telephone: 269-945-9501 Technical Services 877-384-5464 Fax: 269-945-4495 Email: techsvcs@vikingcorp.com
Replaces page 41a-f, dated September 20, 2007.
(Updated VdS and CE Approval.)