HomeMy WebLinkAbout5791 VAN ALLEN WAY; ; FA130094; Permit9/15/2020 FA130094 Permit Data
City of Carlsbad
Fire Alarm Permit
Permit No: FA1300.94
Job Address: 5791 VAN ALLEN WY
Permit-Type:, FALARM
Parcel No: 2121304500
Lot #: 0
Reference No.:
PC #:
Project Title: LIFE TECHNOLOGIES
Status: APPROVED
Applied, 12/5/2013
Approved: 12/5/2013
Issued: 12/5/2013
Inspector:
Applicant: S
TYCO INTEGRATED SECURITY
3830 CALLEFORTUNADA
SAN DIEGO, CA
760458-0161
Owner:
MARARISK CARLSBAD L L C
C/O LIFE TECHNOLOGIES CORP
5791 VAN ALLEN WAY
CARLSBAD CA
Fees ($) Add'I Fees ($) Total ($). Balance ($)
286 0 286 '5 0
1/1
FILE COPY
Simplex TrueAlert® Multi-Candela Notification Appliances
- UL, ULC, CSFM Listed, FM Approved; SmartSyncT M Operation AudibleNisible Notification
MEA (NYC) Acceptance* with Horn and Synchronized Flash, Non-Addressable
Audible/visible (AIV) notification appliances with
efficient electronic horn and high output xenon
strobe, available for wall or ceiling mount
Operation is compatible with ADA requirements (refer
to important installation information on page 3)
Rugged, high impact, flame retardant thermoplastic
housings are available in red or white with clear lens
Operates over a two-wire SmartSync circuit to
provide:
Horns that are controlled separately from strobes on the
same two-wire circuit
"On-until-silenced" and "on-until-reset" operation on
the same two-wire pair
SmartSync horn activation of Temporal pattern, March
Time pattern (at 60 BPM), or on continuously
Strobe appliances on the same circuit operating at a
synchronized 1 Hz flash rate
Class B (Style Y) operation requires connection to a
compatible SmartSync NAC or to SmartSync Control
Module (SCM) 4905-9938
Class A (Style Z) operation when connected to the
4905-9938 SCM or with 4100U series fire alarm control
panel NACs
Wall mount A/Vs features:
Wiring terminals are accessible from the front of the
housing providing easy access for installation,
inspection, and testing
Covers are available separately to convert housing color
Available UL listed sound damper for locations
requiring attenuation of 5 to 6 dBA (stairwells, small
rooms, highly reverberant areas, etc.)
Optional adapters and wire guards:
Wall mount AN adapters are available to cover surface
mounted electrical boxes and to adapt to Simplexar
2975-9145 boxes
UL listed red wire guards are available for wall or
ceiling mount A/Vs
Visible notification appliance (strobe):
24 VDC xenon strobe; intensity is selectable as 15, 30,
75, or 110 candela with visible selection jumper secured
behind strobe housing
UL listed to Standard 1971
Regulated circuit design ensures consistent flash output
and provides controlled inrush current
Audible notification appliance (horn):
Low current, 24 VDC electronic horn with harmonically
rich sound output suitable for either steady or coded
operation (Temporal or 60 BPM March Time pattern)
UL listed to Standard 464
iJlb2
g!'!'
Wall and Ceiling Mount NVs
Multi-Candela TrueAlert A/Vs with horn and
synchronized strobe provide convenient installation
to standard electrical boxes. The enclosure designs are
both impact and vandal resistant and provide a convenient
strobe intensity selection. Since each model can be
selected for strobe intensity output, on-site model
inventory is minimized and changes encountered during
construction can be easily accommodated.
Wall mount AN housings are a one-piece assembly
(including lens) that mounts to a single or double gang, or
4" square standard electrical box. The cover can be
quickly removed (a tool is required) and covers are
available separately for color conversion.
Ceiling mount A/Vs install using standard 4" electrical
boxes. Color choice is determined by model number.
During installation, a selection plug at the back of the
housing determines the desired strobe intensity. An
attached flag with black letters on a highly visible yellow
background allows the selected intensity to be seen at the
side of the strobe lens.
This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7125.0026:317 for allowable values and/or conditions concerning material presented in this
document. It is subiect to re-examination, revision, and possible cancellation. Accepted for
use - City of New Yojt Department of Buildings - MEA35-93E. Refer to page 2 for listing
status of wire guards. Additional listings may be applicable; contact your local Simplex
product supplier for the latest status. Listings and approvals under Simplex Time Recorder
Co. are the property of Tyco Safety Products Westminster.
Simplex multi-candela SmartSync two-wire horn/strobe appliance operalion is protected
under one or more of the fallowing U.S. Patent Numbers: 5559,492; 5,622,427;
5,865,527; 5,886,620; 6,281,789; 6,954,137; 7,005,971; and 7006,003.
S4906-0002-4 12/2007
Proper selection of visible notification is dependent on
occupancy, location, local codes, and proper applications
of: the National Fire Alarm Code (NFPA 72), ANSI
A 117.1; the appropriate model building code: BOCA,
ICBO, or SBCCI; and the application guidelines of the
Americans with Disabilities Act (ADA).
Multiple Strobes. When multiple strobes and their
reflections can be seen from one location, synchronized
flashes reduce the probability of photo-sensitive reactions
as well as the annoyance and possible distraction of
random flashing. The multi-candela strobes of these AJVs
are synchronized by the controlling SmartSync operation
NAC.
SmartSync operation mode allows a two-wire circuit to
provide the ability to activate both the horn and strobe on
the same NAC and then allow the horn to be silenced
while the strobe remains flashing. The horn operates as
"on-until-silenced" while the strobe operation is
"on-until-reset."
4006, 4008, 4100U, and 4010 Fire Alarm Control
Panels (refer to individual product data sheets for more
information)
4009 lONet NAC Extender (refer to data sheet
S4009-0002)
SmartSync Control Module (SCM) 4905-9938 (refer to
data sheet S4905-0003)
Additional SmartSync compatible notification
appliances include separate horns and combination
horn/strobe notification appliances.
Multi-Candela A/Vs
Model Mounting Housing Color "FIRE" Lettering
4906-9127 Red White
4906-9129 Wall White Red
4906-9128 Ceiling Red White
4906-9130 White Red
Wall Mount AN Accessories
Description
Horn with Multi-Candela Strobe; strobe intensity selectable as:
15, 30, 75, or 110 candela; operates with SmartSync two-wire
control
Model Description Dimensions
4905-9937 Red I Surface Mount Adapter Skirt; use to cover 1-1/2" (38 mm) deep 5-3/8" H x 5-1/4"W x 1-5/8" D
4905-9940 White surface mounted boxes (136 mm 133 mmx4l mm)
depth with strobe = 4-3/8" (111 mm)
4905-9931 Red Adapter Plate for mounting to Simplex 2975-9145 box (typically for 8-5/16" x 5-3/4" x 0.060" Thick
retrofit, may be mounted vertical or horizontal) (211 mm x 146 mm x 1.5 mm)
2975-9145 Red Mounting Box, requires Adapter Plate 4905-9931 7-7/8" x 5-1/8" x 2-3/4" D
(200 mm x 130 mm x 70 mm)
Optional Sound Damper; package of 20; field installed adhesive backed
4905-9838 horn output attenuator; reduces output 5 to 6 dBA 1-3/4" Diameter (44.5 mm)
NOTE: After Sound Damper installation, measure sound level to ensure with 0.31" (8 mm) sound opening
como(iance with aoolicable code requirements
SmartSync Control Module
Model I Description - Dimensions
4905-9938 SmartSync Control Module with Class B or Class A output; mounts in 4" 4" x 4-1/8" x 1-1/4" D
(102 mm) square box; refer to data sheet S4905-0003 for details (102 mm x 105 mm x 32 mm)
Replacement Covers for Wall Mount A/Vs
Model Description
4905-9994 Red cover with white "FIRE" lettering
4905-9995 White cover with red "FIRE" lettering
Wire Guards and Ceiling Mount AN Adapter
Model I Description I 49059961* Wall mount red wire guard with mounting plate, compatible with semi-flush I or surface mounted boxes
4905-9927' I I Red Wire Guard for mounting to flush mounted electrical box
4905-9928' I Ceiling I Red Adapter Plate, required to mount guard to surface
Mount J mounted electrical box
4905-9915 I White I Surface Mount Adapter Box Extension, use to cover
4905-9916 I I Red I 1-1/2" deep surface mounted boxes
Dimensions
5-1/8" H x5"Wx 1-1/2" D
(130 mmx127 mm x38mm)
Dimensions
6-1/16" H x 6-1/16" W x 3-1/8" D
(154 mm x 154 mm x 79 mm)
8-1/2' x 6-1/8" x 3"
(216 mm x 156 mm x 76 mm)
9" x 7"
(229 mm 178 mm)
4-3/4" x 6-7/8" x 1-1/2' deep,
(121 mm x 175 mm x 38 mm)
* UL listed by Space Age Electronics Inc.
2 S4906-0002-4 12/2007
IF ~ ILRI le
Removable cover
(tool required)
Wall Mount or Ceiling Mount, Common Specifications
Rated Voltage Range UL Listed Rating
ULC Listed Rating
Regulated 24 DC' see Note 1 below
20 VDC to 30 VDC per ULC S526-M878
Flash Rate and Synchronized NAC Loading 1 Hz; with up to 35 synchronized strobes maximum per NAC
Environmental; Temperature and Humidity 32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C)
Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2) ; two wires per
terminal for in/out wiring
Horn Output Characteristics 2400 to 3700 Hz sweep, modulated at 120 Hz rate
Horn Output Voltage
Ratings Sound Type (see Note 2)
16 VDC 24 VDC 33 VDC
Steady Coded Steady Coded Steady Coded
N
UL 464 Reverberant Chamber
(see Note 2 e Anechoic Chamber
86 dBA 82 dBA 88 dBA 84 dBA 90 dBA 86 dBA
92 dBA 91 dBA 94 dBA 95 dBA 96 dBA 96 dBA
Housing Dimensions (with lens) 5-1/8" H x 5"W x 2-3/4" D (130 mm x 127 mm x 70 mm)
Wall Maximum RMS Current Rating per
Strobe Setting (see Note 3 below)Mount
15 Cd . 30 Cd 75 Cd 110 Cd
75 mA 116 mA 221 mA 285 mA
Reference RMS Currents 18 VDC
at other voltages 24 VDC
67 mA 103 mA 196 mA 253 mA
50 mA 77 mA 147 mA 190 mA
Housing Dimensions (with lens) 4-3/4 L" x 64/8"Wx 2-5/8"D (121 mm x 175 mm x 67 mm)
Ceiling
mount
Maximum RMS Current Rating per
Strobe Setting (see Note 3 below)
15 Cd 30 Cd 75 Cd . 110 Cd
86 mA 132 mA 250 mA 320 mA
Reference RMS Currents 18 VDC
at other voltages 24 VDC
76 mA 117 mA 222 mA 284 mA
57 mA 88 mA 167 mA 213 mA
NOTES:
"Regulated 24 DC" refers to the voltage range of 16 to 33 VDC per UL Standard 1971, Signaling Devices for the Hearing Impaired,
changes effective May 1, 2004. This voltage range is the absolute operating range. Operation outside of this range may cause
permanent damage to the appliance. Please note that 16 VDC is the lowest operating voltage that is allowed at the last appliance on the
NAC under worst case conditions.
Coded values are typical of the output measured with a Temporal coded or a March Time coded pulse and with a sound level meter
reading on a "fast" setting. Under the same test conditions, coded horn output "peak" sound level readings are typically 4 dBA higher.
Anechoic horn output ratings are typically more representative of actual installed sound output.
Currents are with horn on steady. The maximum RMS current listed is the device nameplate rating. Strobe designs are constant wattage
and the maximum RMS current rating occurs at the lowest allowable operating voltage. (RMS is root mean square and refers to the
effective value of a varying current waveform.)
L"_cJTh7
lr
fl
Mounting Holes:
4" square (4)
Single gang (2)
Double gang (3)
Transparent housing \ and lens assembly -
Intensity selection
plug, accessible only I .75 I from rear of housing; (is
factory setting is15 od .V I
Strobe intensity
viewing slot
IMPORTANT! WALL MOUNT
INSTALLATION HEIGHT REFERENCE
Bottom of lens
is either even
with, or slightly Electrical
above bottom box outline
of compatible
boxes
NFPA 72 requires 89'(2.03 m)
that the entire lens minimum
be not less than
80" and not greater
than 96" above the
finished floor
Mounting is compatible with
single gang, double gang, and
4" (102 mm) square boxes,
1-1/2" (38 mm) deep, by others
Optional 4905-9838
Sound Damper, field attached
to attenuate Sound 5 to 6 dBA
Wiring access hole
Wring terminals for
SmartSync operation
S4906-0002-4 12/2007
Ceiling reference, 4 (102 mm) square box,
surface mounted box /" 1-1/2" (38 mm) minimum depth
C
Ceiling reference,
flush mounted bo:
Optional 4905-99151-9916 Adapter,
recommended for surface mounted box
Wiring terminals are
located behind the housing
Optional 4905-9928 Adapter Plate,
required for surface mounted electrical box
Four mounting clamps included, two each side -
Optional 4905-9927
Red Wire Guard
-----------------------------------
Strobe intensity viewing slot
Intensity selection plug,
accessible only from rear of lens
housing; factory setting is 15 cd ----------------------------
4905-9931 Adapter Plate
45 Box
4905-9931 Adapter Plate
4905-9961 Optional Wire Guard
(shown here for reference only,
can be used on other mounting options)
Surface Mounting Reference
with Optional Adapter Skirt
and Optional Wire Guard
Surface mount conduit and
box shown for reference
4" (102 mm) square I
box profile, 1-1/2 i
(38 mm) deep
Optional
4905-9961
Wire Guard
~7
Optional Surface Mount Adapter Skirt,
1-1/2" deep: 4905-9937, Red;
4905-9940, White (conduit knockouts
are provided on all four sides)
Tyco is a registered trademark of Tvco International Services GlvIBH and is used under license. Simplex the Simplex logo, IDNet TnseAlert, and SmartSync are trademarks of
Tyco International Ltd and its affiliates and are used under license. NFPA 72 and National Fire Alarm Code are trademarks of the National Fire Protection Association (IVFPA).
- mplex Tyco Safety Products Westminster- Westminster, MA • 01441-0001 • USA S4906-0002-4 12/2007
www.tycosafetyproducts-usa-wm.com
02007 Tyco Safely Products Westminster All tights reserved All specifications and other information shown were current as ofdocument revision date and are subject to change without notice.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0026:91 Page 1 of 1
CATEGORY: FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: rSimplexloo Simpl)Drive, Westminster, MA 01441-0001
Contact: Paul Mattern (978) 731-8542 Fax (978) 731-8881
Email: pmattern@tycoint.com
DESIGN: Models 4906-9127, 4906-9129 wall mount and Models 4906-9128 and 4906-9130 ceiling
mount multi-candela horn/strobes. Refer to listee's data sheet for detailed product description
and operational considerations.
RATING: Electrical: 16-33 Vdc
Candela: 15, 30, 75, 110cd
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction. For indoor use only.
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as multi-candela horn/strobes with a signaling appliance suitable for the hearing
impaired when used with listee's separately listed fire alarm control units. All models require
the use of Model 4905-9938 (CSFM Listing No. 7125-0026:235) sync control module unless
the horn/strobes are used with the listee's Model 4010 (CSFM Listing No. 7170-0026:226) or
4100 (CSFM Listing Nos. 7170-0026:250 and 7165-0026:251). Refer to listee's Installation
Instruction Manual for details.
NOTE:
07-22-2004
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2013 (ListingExp) (ne30,2014)
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division
Simplex TrueAlert® Multi-Candela Notification Appliances
UL, ULC, CSFM Listed, FM Approved; Visible Notification Appliances with Synchronized Flash;
MEA (NYC) Acceptance* Non-Addressable, SmartSyncTm Operation Compatible
Visible only (VIO) 24 VDC notification appliances
with high output xenon strobe, available for wall
or ceiling mount:
UL listed to Standard 1971
Intensity is selectable as 15, 30, 75, or 110 candela with
visible selection jumper secured behind strobe housing
Operation is compatible with ADA requirements (refer
to important installation information on page 3)
Polarized input allows connection to compatible reverse
polarity, supervised notification appliance circuit (NAC)
Regulated circuit design ensures consistent flash output
and provides controlled inrush current
Rugged, high impact, flame retardant thermoplastic
housings are available in red or white with clear lens
Strobes provide synchronized flash for use with:
4006, 4008, 4010, and 4100U Series fire alarm control
panels with NACs selected to provide strobe
synchronization or SmartSync two-wire control"
4009 IDNetTM NAC Extenders
Separate strobe Synchronization Modules that are
available for Class B or Class A operation
Separate SmartSync Control Modules (SCMs) that
provide Class B or Class A output from conventional
NAC inputs
Strobe housings provides flexible, easy, and
convenient semi-flush or surface wall mounting:
Rear of housing does not extend into box
Wall mount strobes easily mount to single gang, double
gang, or 4-inch square outlet box
Ceiling mount strobes mount to single gang boxes
Wall mount strobe features:
Wiring terminals are accessible from the front of the
housing providing easy access for installation,
inspection, and testing
Covers are available separately to convert housing color
Optional adapters and wire guards:
Wall mount strobe adapters are available to cover
surface mounted electrical boxes and to adapt to
Simplex® 2975-9145 boxes
UL listed red wire guards are available for wall or
ceiling mount strobes
This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Using
7125-0026:316 for allowable values andlor conditions concerning material presented in
this document It is subject to re-examination, revision, and possible cancellation. Refer to
page 2 for lining status of wire guards. Additional listings may be applicable; contact your
local Simplex product supplier for the latest status. listings and approvals under Sirrçlex
Time Recorder Co. are the property of Tyco Safety Products Westminster.
Wall Mount Strobes
FIRE
Ceiling Mount Strobes
Multi-Candela TrueAlert synchronized strobes
provide convenient installation to standard electrical
boxes. The enclosure designs are both impact and vandal
resistant and provide a convenient strobe intensity
selection. Since each model can be selected for intensity
output, on-site model inventory is minimized and changes
encountered during construction can be easily
accommodated.
Wall mount strobe housings are a one-piece assembly
(including lens) that mounts to a single or double gang, or
4" square standard electrical box. The cover can be
quickly removed (a tool is required) and covers are
available separately for color conversion.
Ceiling mount strobes install using standard single gang
electrical boxes. Color choice is determined by model
number.
During installation, a selection plug at the back of the
housing determines the desired strobe intensity. An
attached flag with black letters on a highly visible yellow
background allows the selected intensity to be seen at the
side of the strobe lens.
Proper selection of visible notification is dependent on
occupancy, location, local codes, and proper applications
of: the National Fire Alarm Code (NFPA 72), ANSI
A117. 1; the appropriate model building code: BOCA,
ICBO, or SBCCI; and the application guidelines of the
Americans with Disabilities Act (ADA).
Simplex multi-candela SmartSync twa-wire honr/slrcbe appliance operation is protected
under one or more of the following U.S. Patent Numbers: 5,559,492; 5,622,427; 5,865,527;
5,886,620; 6,281,789; 6.954,137; 7,005,971; and 7,006,003.
S4906-0001-3 512008
Multiple Strobes. When multiple strobes and their
reflections can be seen from one location, synchronized
flashes reduce the probability of photo-sensitive reactions
as well as the annoyance and possible distraction of
random flashing. These multi-candela strobes are
synchronized over a two-wire circuit when connected to
compatible NACs, to compatible Synchronized Flash
Modules, or to SmartSync Control Modules.
Some applications desire the audible notification
appliances to be capable of being silenced before the
alarm condition is reset (on-until-silenced) while the
visible notification appliances are kept activated until the
alarm condition is reset (on-until-reset). SmartSync
operation mode provides this function using a single
circuit (two-wire operation).
Class B SmartSync two-wire control is available
from:
4006, 4008, 4100U, and 4010 Fire Alarm Control
Panels (refer to individual product data sheets for more
information)
4009 IDNet NAC Extender (refer to data sheet
S4009-0002)
SmartSync Control Module (SCM) 4905-9938 (refer to
data sheet S4905-0003)
Class A SmartSync two-wire control is available
from 4 100U NACs and from the 4905-9938 SCM.
Additional SmartSync compatible notification
appliances include separate horns and combination
horn/strobe notification appliances.
Multi-Candela Visible Notification Appliances (Strobes)
Model Mounting Housing Color "FIRE" Lettering Description
4906-9101 Red White Wall Multi-candela strobe with intensity selectable as: 4906-9103 White Red 15, 30, 75, or 110 candela; synchronized flash rate; 4906-9102 Red White
4906-9104 Ceiling SmartSync two-wire control compatible
White Red
Wall Mount Strobe Adapters
Model Description Dimensions
4905-9937 Red I Surface Mount Adapter Skirt; use to cover 1-1/2" (38 mm) 5-318"Hx5-114"Wx1-518"D
(136mm x 133mm x 41 mm) 4905-9940 White deep surface mounted boxes Total depth with strobe = 4-3/8" (111 mm)-
4905-9931 Red Adapter Plate for mounting to Simplex 2975-9145 box (typically for 8-5/16" x 5-314" x 0.060" Thick
retrofit, may be mounted vertical or horizontal) (211 mm x 146 mm x 1.5 mm)
2975-9145 Red Mounting Box, requires Adapter Plate 4905-9931 7-7/8" x 5-118" x 2-3/4" D
(200 mm x 130 mm x 70 mm)
Ceiling Mount Strobe Adapter
Model Description Dimensions
4905-9910 Surface Mount Adapter Plate; zinc plated; required for mounting to 4-7/8" x 3-1/8" x 0.060" D
handy box; not needed when using 4905-9926 guard 1 (124 mm x 79 mm x 1.5)
Synchronization Modules (refer to data sheet S4905-0003 for additional information)
Model Description Dimensions
4905-9914 Class B I Synchronized Flash Module; epoxy encapsulated with I 1-3/8" x 2-7/16" x 13/16" in/out 18 AWG (0.82 mm2) wire leads, rated for 2 A NAG,
4905-9922 Class A requires 10 mA for power (35 mm x 62 mm x 20 mm)
SmartSync Control Module with Class B or Class A output; mounts in I 4" x 4-1/8' x 1-1/4" D 4905-9938 j 4" (102 mm) square box
- j -
(102 mm x 105 mm x 32 mm)
Replacement Covers and Guards
Model Description Dimensions
4905-9992 Redcover with white "FlRE" lettering I 5-1/8" Hx5"Wx 1-1/2" 0
4905-9993 Whitecover withred"FIRE"lettering For Wall mount strobes (130 mm x 127 mm x 38 mm)
4905-9961 " Wall 6-1/16' Hx6-i/16'Wx3-1/8" D
Red wire guard with mounting plate, compatible with (154 mm x 154 mm x 79 mm)
4905-9926" Ceiling mount semi-flush or surface mounted boxes 6-1/8" x 4-3/8" x 2-7/8" deep
(156mmxliimmx73mm)
* UL listed by Space Age Electronics Inc.
2 S4906-0001-3 5/2008
Mounting Holes:
4" square (4)
Single gang (2)
Double gang (3)
Transparent housing
and lens assembly
Intensity selection .75 plug, accessible only
from rear of housing; 15
factory setting is 15 cd
Wall Mount or Ceiling Mount, Common Specifications
Rated Voltage Range UL Listed Rating
ULC Listed Rating
Regulated 24 VDC see Note 1 below
20 VDC to 30 VDC per ULC S526-M878
Flash Rate 1 Hz
Synchronized NAC Loading Up to 35 synchronized strobes maximum per NAC
Temperature Range 32° to 122° F (0° to 50° C)
Humidity Range 10% to 93%, non-condensing at 100° F (38° C)
Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two wires per
terminal for in/out wiring
Housing Dimensions (with lens) 5-1/8" H x 5" W 2-3/4" D (130 mm x 127 mm x 70 mm)
Wall
Mount
Maximum RMS Current Rating per
Strobe Setting (see Note 2 below)
15 cd 30 cd 75 cd 110 cd
60 mA 94 mA 186 mA 252 mA
Reference RMS Currents 18 VDC
at other voltages 24 VDC
53 mA 84 mA 165 mA 24 mA
40 mA 63 mA 124 mA
Housing Dimensions (with lens) 4-3/4" Lx 2-5/16"W x 2-5/8" D (121 mm x 75 mm x 67 mm)
Ceiling
Mount
Maximum RMS Current Rating per
Strobe Setting (see Note 2 below)
15 cd 30 cd 75 cd 110 cd
75 mA 125 mA 233 mA 316 mA
Reference RMS Currents 18 VDC
at other voltages 24 VDC
67 mA 111 mA 207 mA 281 mA
50 mA 83 mA 155 mA 211 mA
NOTES:
"Regulated 24 VDC" refers to the voltage range of 16 to 33 VDC per UL Standard 1971, Signaling Devices for the Hearing
Impaired, changes effective May 1, 2004. This voltage range is the absolute operating range. Operation outside of this range
may cause permanent damage to the strobe. Please note that 16 VDC is the lowest operating voltage that is allowed at the last
appliance on the NAC under worst case conditions.
The maximum RMS current listed is the device nameplate rating. Strobe designs are constant wattage and the maximum RMS
current rating occurs at the lowest allowable operating voltage. (RMS is root mean square and refers to the effective value of a
varying current waveform.)
Mounting is compatible with
single gang, double gang, and
4" (102 mm) square boxes,
1-1/2" (38 mm) deep, by others
Wiring access hole
IMPORTANT! WALL MOUNT
INSTALLATION HEIGHT REFERENCE
Bottom of lens
is either even
with, or slightly r ,._Electrical
above bottom I r box outline
of compatible
boxes
t
NFPA 72 requires 89'(2.03 m)
that the entire lens minimum
be not less than
80" and not greater
than 96" above the
finished floor
Removable cover Strobe intensity
(tool required) viewing slot
3 S4906-0001-3 5/2008
Single gang box (Wiremold
V5744S) 2-114 (57 mm)
deep, supplied by others
Handy box, 1-1/2(38 mm) deep
(RACO 650 or equal) or single gang
box, 2-1/2" (64 mm) deep (RACO 519
or equal) supplied by others
Also can be attached to boxes
mounted to drop ceiling T-bar with
clips (ERICO No. 512 or equal)
4905-9910 Adapter Plate, required for
AD
C) 00 JI(//
surface mount with handy box unless
using the 4905-9926 wire guard
mount strobe
Optional 4905-9926 wire guard
with mounting plate
Strobe intensity
viewing slot
Intensity selection plug,
accessible only from rear of lens:
L-ousing; factory setting is 15 cd --
145 Box
Surface Mounting Reference
with Optional Adapter Skirt
and Optional Wire Guard
Surface mount conduit and
box shown for reference
4" (102 mm) square
box profile, 1-1/2"
(38 mm) deep
Optional
4905-9961
Wire Guard
Strobe
~7
Optional Surface Mount Adapter Skirt,
1-1/2" deep: 4905-9937, Red;
4905-9940, White (conduit knockouts
are provided on all four sides)
4905-9931 Adapter Plate
4905-9931 Adapter Plate
4905-9961 Optional Wire Guard
(shown here for reference only,
can be used on other mounting options)
Tyco is a registered trademark of Tyco International Services G?vIBH and is used under lice nse Simplex, the Simplex logo, IDNe4 Tn,eAlert, and SmartSync are trademarks of
Tyco International Ltd and its affiliates and are used under lice,ise JVFPA 72 and National Fire Alarm Code are registered trademarks of the National Fire Protection
Association (NFPA).
£Sirrii3Iex Tyco Safety Products Westminster" Westminster, MA • 0 144 1-0001 • USA S4906-0001-3 5/2008
www.tycosafetyproducts-usa-wm.com
2008 Tyco Safety Pmthicts Westminster. All rights reserved Allspeciftcations and other information shown were current as of document revision date and are subject to change without notice.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. (725-0026:031) Page 1 of 1
CATEGORY: (25 -FIRALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Simplex 100 Simplex Drive, Westminster, MA 01441-0001
Contact: Paul Mattern (978) 731-8542 Fax (978) 731-8881
Email: pmaftern@tycoint.com
DESIGN: (Models 4906-9101, -9102, -9103, and -9104mu1t1-candela, non-addressable, synchronizable
strobe lights. Models 4906-9101 and -9103 are for wall mount. Models 4906-9102 and -9104
are for ceiling mount. Synchronizing modules are required for synchronizing strobe lights if
the interconnected control unit does not provide NAC synchronization capabilities. Refer to
listee's data sheet for additional detailed product description and operational considerations.
RATING: Electrical: 16-33 VDC
Candela: 15, 30, 75, and 110 cd
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as strobe lights for use with separately listed compatible fire alarm control units. For
indoor use only. Refer to listee's Installation Instruction Manual for details.
These units can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation
Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
NOTE:
06-23-04
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineenng staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2013 Listing Expires (June 30, 20141
Authorized By: JAMES PARSEGIAN, Program Coordinator
Fire Engineering Division