Loading...
HomeMy WebLinkAbout5600 AVENIDA ENCINAS; ; AS140261; PermitUity 01 Uarlsbad Sprinkler Permit Permit No: AS140261 5600 AVENIDA Job Address: Status: ISSUED ENCINAS Permit Type: SPRINK Applied 9/29/2014 Parcel No: 2100905000 Approved: 10/6/2014 Lot #: 0 Reference No.: Issued: 10/6/2014 PC #: Inspector: Project Title: AVEN IDA ENCINAS BLDG B BLDG B: 36,140 SF -ALL PIPING TO BE CLASS 150 CEMENT ASBESTOS OR CLASS 50 DUCTILE IRON. -ALL FITTINGS TO BE CAST IRON, MECHANICAL JOINT, AND/OR FLANGE WITH APPROPRIATE GLANDS, RUBBERS, AND T-BOLTS UNLESS NOTED OTHERWISE. -PIPING TO BE RETAINED WITH APPROVED THRUST BLOCKS AND/ OR UL LISTED RETAINER GLANDS. -ALL PIPING TO BE BURIED A MINIMUM OF 3'-0" TO TOP OF PIPE. - UNDERGROUND PIPE TO BE TESTED SEPARATELY AND FLUSHED CLEAN PRIOR TO FINAL CONNECTION. -UNDERGROUND PIPING TO BE TESTED AT 200 PSI FOR TWO HOURS. -RISE-UP PIECES AND PIECES UNDER FOOTING TO BE CLASS 50 DUCTILE IRON. -FIRE SERVICE CONNECTION PAID FOR AND INSTALLED BY OTHERS. - FLANGE TO BE SET AT 6" ABOVE FINISHED FLOOR. Applicant: INDUSTRIAL FIRE SPRINKLER CO INC 3845 IMPERIAL AV SAN DIEGO CA 619-266-6030 619-266-6035 Owner: MART-CARLSBAD L L C 221 15TH ST DEL MAR CA Fees ($) Add'l Fees ($) Total ($) Balance ($) 350 0 350 0. SEE PERMIT A5140260 5600 AVENIDA ENCINAS FOR CALS & PLANS