HomeMy WebLinkAbout6860 AVENIDA ENCINAS; ; FA110032; PermitUttyot Uarlsbad
Fire Alarm Permit
Permit No: FA110032
6860 AVENIDA
Job Address: Status: ISSUED
ENCINAS
Permit Type: FALARM Applied 4/4/2011
Parcel No: 2144501900 Approved: 4/4/2011
Lot #: 0
Reference No.: Issued: 4/4/2011
PC #: Inspector:
Project Title: KAISER MEDICAL TWO FIRE ALARM INSPECTIONS @ $65/EA
Applicant:
POWER COMMUNICATION SYSTEMS
4643-A MISSION GORGE PL
SAN DIEGO, CA
619-583-7400
Owner:
KAISER FOUNDATION HEALTH PLAN INC
393 E WALNUT ST
PASADENA CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
130 0 130 0
I so
: POWER COMMUNICATION SY
FA(16052,
STEMS, INC.
SALES - SERVICE - ENGINEERING 4,4 rn0 Public Address * Paging * Intercom * Fire Alarm * Nurse Call * CCTV
I
I
I
0 0
SUBMITTAL
FIRE ALARM SYSTEM
KAISER PERMANENTE
CARLSBAD MOB
FIRE ALARM SYSTEM UPGRADE
6860 AVENIDA ENCINAS
CARLSBAD, CA 92008
I
I
I
I
I
I
1
I
I
I
I
I
OWNER:
I ELECTRICAL CONTRACTOR:
FIRE ALARM CONTRACTOR:
KAISER PERMANENTE
FULLER ELECTRIC
POWER COMMUNICATION SYSTEMS, INC. FA 1(0032.
I P.O. Box 600066, San Diego, CA 92160-0066 • 4643-A Mission Gorge Place, San Diego, *California 92120-4133
(619) 583-7400 • Fax: (619) 583-0647 License No. 636431—C7/C1O
I
I
TABLE OF CONTENTS
I
LIST OF MATERIAL . . . . . . . . . . . 1
I UL CERTIFICATE . . . . . . . . . . . 2
NICET CERTIFICATE. . . . . . . . . . . 3
BUSINESS LICENSE . . . . . . . . . . . 4
I CUT SHEETS
I 5000 MXL, MPS-6 . . . . . . . 5
5056 MME-KIT, MDL-1, MHD-2 . . . . . . 6
5079 MMB-3 . . . . . . . . 7
1 5026 MKB-2. . . . . . . . . 8
4000 5128C. . . . . . . . . 9
I
5073
3362
RCC-2 . . . . . .
PAD-3. . . . . . .
. . 10
. . 11
6175 FP-11, DB-11 . . . . . . . 12
I
6176
6187
FPT-11,DB-11 . . . . .
MSI-10B . . . . . .
. . 13
. . 14
6179 TRI-D, TRI-R . . . . . . . . 15
6170 TRI-136M . . . . . . . . 16
I
.
2584 ZR-MC-CR,ZH-MC-CR . . . . . . 17
2585 MOUNTING APPLIANCES . . . . . . 18
SHEET 302-ET-135,AP-P . . . . . . . 19
C.S.F.M. LISTINGS
7165-0067:0144 MXL, MMB-3, MKB-2, MPS-6,5128C . . . . 20
I 7300-0067:0172 MME-KIT, MHD-2 . . . . . . . 21
7300-0067:0152 RCC-2 . . . . . . . . . 22
7135-0067:0221 PAD-3. . . . . . . . . 23
I 7272-0067:0203 FP-11 . . . . . . . . . 24
7270-0067:0202 FPT-11 . . . . . . . . 25
7300-0067:0134 DB-11. . . . . . . . 26
I 7150-0067:0036 MSI-10B . . . . . . . . 27
7300-0067:0146 TRI-D, TRI-R, TRI-136M . . . . . . 28
I
7125-0067:0252
7125-0067:0248
ZR-MG-CR . . . . . .
ZH-MC-CR . . . . .
. . 29
. . 30
7270-0021:0001 302-ET-135 . . . . . . . . 31
I
WARRANTY . . . . . . . . . . . . 32
I
I
LIST OF MATERIAL
MODEL NO. MANUFACTURER DESCRIPTION QTY
MXL SIEMENS FIRE SAFETY FIRE ALARM CONTROL PANEL 1
MME-KIT it
" KIT INCLUDES MME-3 & MBR-MP 1
MDL-1
MHD-2
It
"
"
it
PLEXIGLASS DOOR INSERT
BOTTOM, DEAD FRONT, NO OPENINGS
1
1
MMB-3 "
it MXL MAIN BOARD - FAST PROCESSOR 1 ' MKB-2
MPS-6
"
"
it
"
DISPLAY/CONTROL KEYBOARD HINGED
MXL 6 AMP POWER SUPPLY
1
1
5128C " " 3 CHANNEL SLAVE COMMUNICATOR 1
RCC-2
REMOTE/CONTROL ANNUNCIATOR SMALL 1
PAD-3 " " P/S NAC EXT 6 AMPS 2
FP-11 " " SMOKE DETECTOR 3
FPT-11
HEAT DETECTOR 4
DB-11 " " DETECTOR BASE 7
MSI-10B " " MANUAL PULL STATION 26
TRI-D
DUAL INPUT MODULE 1
TRI-R " " SINGLE INPUT WITH RELAY 1
TRI-136M " " MONITOR MODULE 4
ZR-MC-CR
STROBE - CEILING 87
ZH-MC-CR " " HORN/STROBE - CEILING 23
302-ET-135 THERMOTECH HEAT DETECTOR 2
AP-P "
it ADAPTER PLATE 2
I
I
1
I
I
I
I
I
I
ID No: 66001 Underwriters Laboratories Inc ®Applican'
& Service Center No
Nurhb!orjk. IL 5n .os-. CA Expires: 1-MAR-2011
Mti.i. NY
A out-to orr!n icateO to pt afe
and cornmitted to quF strvic
S
CERTIFICATE OF COMPLIANCE
I S . THIS IS TO CERTIFY that the Alarm Service Company indicated below is included by Underwriters
UL Listing Mark in with Laboratories Inc. (UL) in its Product Directories as eligible to use the connection
Certificated Alarm Systems. The only evidence of compliance wiTh A's requirrnents Is the issuance of a
UL Certificate for the Ala,-rr System and the Certificate is current jr ier UL's Certiicate Verification Service. I This Certificate does not apply in any way to the communication cl-annel between the pntected property and
any facility that monitors signals from the protected property unless the use of a UL listed or Classified Alarm
Transport Company is specified on the Certificate.
SAN DIEGO CA
Listed Service From: '
I Alarm Service Company (967165-001) Service Cento (967165-001)
POWER COMMUNICATION SYSTEMS INC POWER COMMUNICATION SYSTEMS INC
MISSION GORGE PL 4643A MISSION GORGE PL
I
4643-A
• SAN DIEGO CA 92120 SAN DIEGO CA 92120
The Alarm Service Company Is Listed in the following Certificate Service Categories:
File - Vol No. CCN Listing Category
: S3669 -1 UUJS [Signal and Fire Alarm Equipment and Services] (Protective
Signaling Services) Local, Auxiliary, Remote Station and (
S Proprietary
***THIS CERTIFICATE EXPIRES ON 31-MAR-201
"LOOK FOR THE UL ALARM SYSTEM CERTIF1ATE"
I
O2APR-2010
2008 UL Fomi CS-CC S
S & ••/ 5, •'- )'5 ,:, 5'S •5 •. • SS•S •SS A i,.,'AA '
I
I
I
I
I
1
I
I
I
I
I
I
1
I
I
I .
F
I
I
I
NATIONAL'INSTITUTE FOR- CERTIFICATION.
IN ENGINEERING ,TECHNOLOGIE'So
HEREBY CERTIFIES THAT
Ernest Power, III
HAS ATTAINED THE GRADE OF
LEVEL III
IN FIRE PROTECTION ENGINEERING TECHNOLOGY
FIRE ALARM SYSTEMS
AND RECOGNIZES THAT THROUGH EDUCATION,
EXPERIENCE, AND KNOWLEDGE THIS PERSON HAS
MET THE STANDARDS SET FORTH BY THIS INSTITUTE
Certification Valid through September 1, 2011
CERTIFICATION NUMBER 77846 -
CHA AN OF THE BOARD OF GOVERNORS, NICET
SPONSORED BY THE NATIONAL SOCIETY OF PROFESSIONAL ENGINEERS
I
I
I
I
I
I
1
I
I
1
I
I
I
I
I
I
I
I
I
State 0 Ca ifcmia
CONTRACTORS STATE LICENSE BOARD
ACTIVE LICENSE
Consumer
636431 Eritil
POWER COMMUNICATION SYSTEMS
INC
h .il iticri(s C-7 E1 0
lllII thL
E,dtvrI Date.0 1/3 1/20 1 2
SIEMENS Catalog Sheet
Fire Safety & Security Products
MXL
Advanced Protection System
ARCHITECT AND ENGINEER SPECIFICATIONS
MXL
Panel
FirePrinP application-specific detection
More than 2,000 intelligent input-device
capacity
Multiple Command Stations
Dynamic supervision of Intelligent Devices
Security-device monitoring
Sprinkler supervision
Detector-sensitivity readout! printout,
per NFPA 72 Chapter 7
Intelligent! Analog detection circuits:
- Style 6 (Class A) or Style 4 (Class B)
Conventional initiating circuits:
- Style D (Class A) or Style B (Class B)
Notification appliance circuits:
- Style Z (Class A) or Style Y (Class B)
Degrade-mode operation
Distributed processing
80-character backlit, alphanumeric display
32-character custom messages
Thermal-strip printer
Supervised remote printer
Compare system software
Fully field programmable, via laptop PC
Menu-driven operator commands
Central & distributed architecture
Up to 800-event history log with online
& off line reports
User help screens
Holiday schedule
System Overview
Logic-controlled output functions
Multiple levels of password protection
Automatic environmental compensation
for smoke detectors
One-person 'walk test' via 'loop,' 'zone'
or 'system'
Alarm verification by 'device' or 'zone'
Time-base controlled output functions
City Tie! Lease Line
Coded outputs
Supervised serial annunciator
Driver! Input Interface
16-gauge steel enclosure
Multi-language display
Intelligent interface to building!
process management systems
Operates as an interactive peer with
other MXL, MXL-IQs or MXLV systems
in a LifeLINK Network
Pre-alarm operation
NCC graphics
Pre-action Releasing (NFPA 13)
Halon & SilborixTM Approval
(NFPA 12A& NFPA 2001)
NEC 760 Power Limited Circuits
(€UL 864 Compliant)
UUKL Listed for Smoke Control
eUL 864 9th Edition Listed, OULC Listed;
CSFM, NYMEA, City of Chicago and
U.S. Coast Guard Approved
I
I
I
I
I
I
I
I
I
I
I
I
I
The MXL fire panel is a microprocessor-based
I advanced protection system. The use of the MXL
system's unique multiprocessor 'Network' design; as
well as its ability to utilize analog and conventional
detection devices, makes the MXL panel a highly I flexible and reliable fire-control system.
The MXL panel is ideally suited for commercial,
I institutional and industrial fire-detection and
notification applications. The MXL system
complies with the requirements of NFPA Standard
72, and is listed by Underwriters Laboratories (UL),
via their ®UL 864 gth Edition. tUnderwriter's' I Laboratories of Canada (ULC) also lists the MXL
panel for fire applications. The MXL system is
I
SIEMENS Industry, Inc. I Building Technologies Division
approved by CSFM, the City of Chicago and NYMEA for
use in those specific locales.
In addition to the standard fire applications, MXL is
also listed by ®UL - under the category 'UUKL for Smoke
Control.' The MXL panel can be used as a listed fireman's
smoke- control station in high-rise office buildings, malls
and other multi-level or vast structures. The MXL
system also complies with Uniform Building Code
Section 905 requirements for smoke control.
MXL is approved by the US Coast Guard for marine
applications such as ships and oil drilling platforms. The
MXL panel is listed by ®UL for releasing Halon 1301,
SinorixTM Engineered Fire Suppression System and
MXL 5000
System Overview -(continued)
pre-action or deluge sprinkler systems. These include
foam or water applications. MXL follows the releasing
requirements specified in the NFPA Standards 12A, 13
and 2001.
MXL Components
The basic MXL control unit consists of the following
sub-assemblies: MMB-3 Main Control Board; MPS-6!
MPS-1 2 Power Supply; MKB-2 Annunciator and
Keyboard; MME-3, MLE-6 or MSE-2 Enclosures.
Optional modules -which can be installed with the
MXL System - include: MOM-2/4 Expansion Card
Cage; ALD-21 Analog Loop Driver; CRM-4 Controllable
Relay Module; NIM-i W Network/Foreign Systems
Interface Module; REP-1 Network Repeater Module;
XLD-i "X" Series Loop Driver; CSM-4 Controllable
Signal Module; CZM-4 Conventional Zone Module;
PIM-i Peripheral Interface Driver; CMI-300 CXL
Modem Interface Module; PSR-i Remote Power
Supply; MXL-VDT Interactive Video Display Terminal;
NET-4 Style 4 Network Interface; NET-7 Style 7
Network Interface.
Additionally, the MXL system includes option modules
MOI-7 System Interface, MOD-16 Output Driven and
MID-16 Point Input Module. These option modules
can be used to drive graphic annunciators and
Fireman's Smoke Control Stations, or to monitor
foreign systems.
The MXL is compatible with a full line of intelligent
initiating devices highlighted by the FirePrintlM
application-specific detectors: Models FP-1 1 and FPT-
ii. The MXL panel is also compatible with FireFinder,
the NCC series of text and graphic command centers.
MXL Enhanced Main Board (MMB-3)
MMB-3
The function control of the MXL is contained on
the MMB-3 Main Control Board. Model MMB-3
offers a fast, integral microprocessor and
installation conveniences such as diagnostic LEDs
and removable terminal blocks for field wiring.
Model MMB-3 acts as the central controller for the
system, and includes two (2) ALD circuits and two
(2) notification appliance circuits. Model MMB-3
mounts in the MXL enclosure backbox.
SIEMENS Industry, Inc.
Building Technologies Division
Display I Keyboard (MKB-2)
MKB-2
The MKB-2 display! keyboard mounts on a hinged
frame in the MXLV enclosure, and provides:
Two-line, 80- character LCD display
indicator LEDs
display-control keys
numeric keypad
user-programmable function keys
all other keys necessary for operator control
These keys include but are not limited to: Acknowledge;
Silence and Reset. Model MKB-2 also includes spaces
for mounting the Model MMM-i microphone module
and the Model TMM-i telephone. Model MKB-2 is
supplied with two (2) blank plates for use when either
the microphone or telephone is omitted.
Display I Keyboard (MKB-5)
MKB-5
The MKB-5 display! keyboard mounts on the inner door
of any MXL enclosure backbox and provides:
6-1I4 VGA backlit, 80- character LCD display
indicator LEDs
12 programmable function keys
numeric keypad
user-programmable function keys
all other keys necessary for operator control
These keys include but are not limited to: Alarm;
Supervisory; Trouble and Security. Multiple MKB-5s can
be used in the system, each providing full control of the
MXL system. Up to four (4) Model MKB-5 can operate
in a fully supervised mode; each with independent
printer driver capability built-in.
MXL Components - (continued)
Model MPS-6 is a fully supervised power supply
that provides the MXL system with primary DC
power. Model MPS-6 is rated at 6.5 Amps, and
is unfiltered and unregulated. Model MPS-6
supplies power to the MXL Control Unit, and
supplies its expansion modules with power
required for normal operation. Model MPS-6
incorporates a circuit breaker on the primary
input, and includes a built-in AC-line filter
for surge and noise suppression. Model
MPS-6 mounts in the MXL enclosure backbox.
Power Supply (MPS-12)
Network Optional Module Card Cage (MOM-2)
MOM-2
Model MOM-2 provides the MXL main unit, remote
units or MXL small enclosures (Model MSE-2) with
card slots for optional modules. Each Model MOM-2
provides space for one (1) full-width module (Models:
ALD-21, CZM-4, and NIM-i R) or two (2) half-width
optional modules (Models: CSM-4, CRM-4, CMI-300,
NET-7, REP-1).
Analog Loop Driver (ALD-21)
I
I
I
I
I
I
MPS-12
Model MPS-1 2 is a fully supervised power supply
that provides the system with preliminary DC
power. Model MPS-12 is rated at 12 Amps, and
is unfiltered and unregulated. Model MPS-12
supplies power to Models PSR-1, MMB-2 and their
expansion modules with power required for
normal operation. Model MPS-12 incorporates
a resettable circuit breaker on the primary input,
and includes a built-in AC-line filter for surge and
noise suppression. Model MPS-12 mounts in the
MXL enclosure backbox.
Network Optional Module Card Cage (MOM-4)
—-?-'?.
MOM-4
The Model MOM-4 Card Cage provides the MXL
main unit or remote units with card slots for
option modules. Each Model MOM-4 supplies
connection space for either two (2) full-width
option modules: (Models ALD-21, CZM-4,
NIM-1 R, XLD-1) or four (4) half-width option
modules: (Models CSM-4, CRM-4, CMI-300,
NET-7, REP-1) or a combination of one (1) full
and two )2) half-width modules.
SIEMENS Industry, Inc.
Building Technologies Division
ALD-21
Model ALD-21 is a MXL network-option module that
supplies two (2) intelligent analog circuits utilizing
Fire Safety "1", "IL, and FP series intelligent devices.
Model ALD-21 occupies two (2) addresses on the MXL
Network and through the use of unique
communication-protocol devices connected to the
circuits of Model ALD-21. The circuits are dynamically
supervised by the MXL control panel. Up to 60
programmable input and output devices may be
connected to each of its two (2) circuits. Each circuit
may be wired as Class B (Style 4) or Class A (Style 6).
Controllable Signal Module (CSM-4)
CM-4
Model CSM-4 provides two (2) fully supervised,
programmable notification-appliance circuits.
Model CSM-4 supplies two (2) Class B (Style Y)
or Class A (Style Z)-type output circuits for the
supervision and control of listed audible or visual
notification appliances such as: horns, bells,
strobes, etc.
Each circuit can provide up to 1.5 amps (24 VDC)
of current to power notification appliances. Model
CSM-4 is also used for suppression-agent releasing
(SinorixTM, Halon, Pre-Action Sprinkler and Deluge)
systems. Leased line and municipal-tie connections
are also possible with Model CSM-4.
I
I
I
I
I
U
I
[1
I
U
I
1
I
MXL Components - (continued)
Controllable Relay Module (CRM-4)
- i1!1flUt!U,j
1E1 ti
I iiirW
CRM-4
Model CRM-4 is designed to provide auxiliary
control of building functions such as: door-
holder release, elevator capture, smoke control,
lock release, etc. Model CRM-4 provides four
(4) fully programmable relays. Each relay
contains one (1) set of SPDT contacts rated
at 2 amps 30 VDC /120 VAC resistive.
Communication Module (NET-4)
NET-4
Model NET-4 is a plug-in-type module used to
provide communication between the Fire Safety
MXL panel and various other MXL remote
modules. Model NET-4 is designed to plug into
an edge-connector-type slot on the Model PSR-i
Network Supply. Model NET-4 provides NFPA
Style 4-type communication: fully digital;
RS-485 operating at 19.2K Baud rate.
Style 7 Network Interface Card (NET-7)
;1
••_•
-. --
NET-7
Model NET-7 is a microprocessor-controlled MXL
network-interface module that allows the wiring
of the MXL RS-485 network in a NFPA Style 7
configuration. Model NET-7 plugs into a half slot
of the Models MOM-2/4 card cage at the MXL
command center (MMB-2) and at the Model PSR-1
or Model MOM-4 slot at the MXL remote units
(MXLR, MXLRV).
SIEMENS Industry, Inc.
Building Technologies Division
Model NET-7 provides two (2) independent and fully
supervised communication paths, allowing system
operation through an open and short circuit. Model
NET-7 also isolates the power supplies at each remote
unit, providing the ability to localize ground-fault
conditions. The communication for Model NET-7
operates at 19.2K Baud rate and is fully digital.
Network Repeater Module (REP-1)
wflWll1Uk,LI
r 1 v- ir
REP-i
Model REP-1 provides the ability to configure the
local or global networks of the MXL panel in a 'star'
or 'daisy-chain' configuration. Model REP-11 provides
two (2) Style 4 or one (1) Style 7 RS-485 network
circuits. Through the use of Model REP-1, the MXL's
local network (MXL-MXLR) can be expanded up to
64 nodes.
Remote Power Supply (PSR-I)
PSR-1
Model PSR-1 is a microprocessor-controlled remote
power supply and battery charger for
use with the MXL panel. Model PSR-i operates
in conjunction with either a Model MPS-6 or
MPS-1 2, providing 6 or 12 Amps of power for
use with various MXL modules. When used with
a Model NET-4 or Model NET-7 plug-in communication
module, Model PSR-i becomes
a part of the MXL panel's internal network. Model
PSR-1 acts as an interface between remote-option
modules and the MXL.
MXL Components - (continued)
Peripheral Interface Driver (PIM-1)
'IM-1
Model PIM-i is a MXL option module that provides
a bidirectional, isolated RS-232 port for connection
to peripheral devices, such as: printers, CRTs,
VDTs, color graphics, alphanumeric pagers and
remote diagnostics hardware. Model PlM-i
mounts in the MXL enclosure, and connects to
Model MMB-3, providing a screw-terminal block
for connection of RS-232. A number of supervised
and non-supervised formats are available for
Model PlM-1.
Output I Input Module (MOI-7)
MOI-7
Model M0I-7 is a MXL RS-485 network module
that provides a fully programmable serial interface
to Model MOD-1 6 output drivers and MID-1 6 input
drivers. When used with Model MOD-16 drivers,
Model M0I-7 provides a serial-annunciator output
or relay driver. When used with Model MID-16,
Model M0I-7 provides programmable inputs.
Each Model M0I-7 can operate up to eight (8)
Model MOD-1 6 drivers and eight (8) Model MID-1 6
drivers simultaneously. Each Model MOD-1 6
output and Model MID-1 6 input is independently
programmable, via the MXL custom software.
MXL /(V) Standard Size Enclosure (MME-3)
MME-3
Output Driver (MOD-16)
MOD-16
Model MOD-1 6 is an output-driver module used in
conjunction with Model M0I-7, as a part of the Fire
Safety MXL System. Up to eight (8) Model MOD-1 6s
can be connected to a Model M0I-7 interface module.
Each Model MOD-i6 provides 16 open-collector,
current-sinking outputs, which are rated at 24 VDC,
50mA. Model MOD-16 outputs are programmable, via
the MXL custom software.
Programmable Input Driver (MID-16)
MID-16
Model MID-1 6 is an input module used in conjunction
with Model M0I-7, as a part of the Fire Safety MXL
System. Up to eight (8) Model MID-1 6s can be
connected to a single Model M0I-7, along with eight
(8) Model MOD-1 6 output-driver modules. Each
Model MID-16 provides a non-supervised input,
which can monitor normally open contact devices.
Each Model MID-1 6 input can be separately used as
a part of the MXL custom programming logic. These
inputs can be individually set for: Alarm, Supervisory,
Trouble, Security or Status usage. Further, the Model
MID-1 6 inputs can also be configured to provide
supervision for lamps driven by Model MOD-1 6
outputs. Screw terminals and connectors are provided
on the Model MID-1 6 modules for interface to
monitored devices.
SIEMENS Industry, Inc.
Building Technologies Division
MXL Components - (continued)
The Model MME-3 enclosure set consists of a sheet-
metal back box and door with key-lock. Model
MME-3 can be used for the MXL System, MXLV
Voice Command Console, MXLR Transponder,
MXLRV Voice Transponder or Amplifier Equipment
(via the Model MSR-1 Rail Kit). To mount MXL I
MXLV modules in Model MME-3, the Model MBR-MP
removable-module mounting plate is required.
Using the Model MBR-MP mounting plate -one
(1) Model MMB, or one (1) Model PSR-1, and up
to three (3) expansion cardcages (Model MOM or
Model 0MM) can be mounted in the Model MME-3
enclosure. When used to mount MXL amplifiers
(Model EL-410), the Model MBR-MP module is not
required. Instead, up to three (3) Model EL-410
amplifiers may be installed in Model MME-3, via
three (3) Model MSR-1 Rail Kits. When amplifiers
are mounted in any enclosure, always install Model
MDG-1 grills in the door for proper ventilation.
Model MME-3 is designed for surface of semi-flush
mounting, and includes various knockouts for wire
and conduit entry. The door in the Model MME-3
set has two (2) cutouts for clear lenses, blank
plates or grills - depending on the application -
and contains a key-lock.
MXL MME-3 and MLE-6 Modules
Mounting Plates (MBR-MP)
MBR-MP
The Model MBR-MP MXL IV Module Mounting Plate
is required for use in both Models MME-3 and
MLE-6 enclosures in order to mount all MXL and
MXLV equipment. Model MBR-MP is not necessary
if the Models MME-3 and MLE-6 enclosures are
to be used only for mounting of amplifiers (EL-41 0)
Model MBR-MP is a removable MXL /V module
mounting plate that allows the Model MME-3 or
Model MLE-6 enclosure to be shipped to the job
site for wiring and conduit installation, while the
system hardware (electronics) is mounted to the
studs on Model MBR-MP - pre-wired, programmed
and tested - prior to delivery and installation at
the job site.
This process allows for faster, more efficient
system start-ups with less chance of the sensitive
electronics being damaged while field wiring and
conduit are connected to the system enclosure.
SIEMENS Industry, Inc.
Building Technologies Division
The Model MBR-MP mounting plate bolts to the Model
MME-3 or Model MLE-6 enclosures for easy installation
on the job site. Model MBR-MP also has handles to
allow easy transport and mounting.
The MBR-MP contains mounting studs for one (1)
Model MMB or Model PSR-1; one (1) Model PlM-1; one
(1) Model TBM-2, and up to three (3) Model MOM or
Model 0MM card cages or two (2) cardcages and one
(1) TSP-40 Printer (same mounting studs as the Model
MBR-2 enclosures).
Model MBR-MP is ordered and shipped separately from
the Models MME-3 and MLE-6 enclosures.
MXL 1(V) Large Size Enclosure (MLE-6)
MLE-6
The Model MLE-6 enclosure set consists of a sheet-metal
back box and door with two (2) key-locks. Model MLE-6
can be used for the MXL system, MXLV Voice Command
Console, MXLR Transponder, MXLRV Voice Transponder
or Amplifier Equipment (via the Model MSR-1 Rail Kit.)
To mount MXLIV modules in Model MLE-6, the Model
MBR-MP removable module mounting plate is required
with the Model MBR-3MP option available for use.
Using the Model MBR-MP mounting plate, one (1) Model
MMB or Model PSR-1 and up to three (3) expansion
cardcages (Model MOM or Model 0MM) can be mounted
in Model MLE-6. If additional card cages are required,
the Model MBR-3MP optional card cage mounting plate
can also be installed in Model MLE-6 - below the MBR-
MP. Model MBR-3MP allows mounting of an additional
three (3) Model MOM or Model 0MM module expansion
cardcages.
Various combinations of hardware can be installed in
Model MLE-6. If only amplifiers are to be installed in
Model MLE-6, no Model MBR-MP or Model M13R-3MP
plates are required. Instead, up to five (5) Model EL-410
amplifiers can be installed by using five (5) Model MSR-1
rail kits. The Model MLE-6 can also be used to mount up
to three (3) MXL cardcages and two (2) amplifiers.
This configuration would be typical of a remote, voice
transponder cabinet. In this configuration, one (1)
Model MBR-MP would be used in the upper half of
Model MLE-6 to mount the MXL modules, while the
lower half would use two (2) Model MSR-1 rail kits to
mount up to two (2) Model EL-41 0 amplifiers.
MXL Components - (continued)
Model MLE-6 is designed for surface or semi-flush
Mounting, and includes various knockouts for wire
and conduit entry. The door supplied with the
Model MLE-6 set has three (3) cutouts for either
clear lenses, blank plates or grills - depending on
the application. The door also contains twp (2)
key-locks, which are keyed the same.
Various combinations of dead-front mounting
plates are possible with the Model MLE-6 enclosure
A typical MXLV installation would have one (1)
Model MKB-2 at the top, and two (2) Model
MHD-3 dead- front plates in the middle [for 14
VSM I VLM I VFM modules per plate] and one (1)
or two (2) Model MHD-2 lower dead-front plates.
MLE-6 Optional Cardcage Mounting Plate
(MBR-3MP)
MBR-3MP
Model MBR-3MP is an optional MXL I MXLV card
cage mounting plate for use exclusively in the
Model MLE-6 enclosure. When installed in the
Model MLE-6 backbox, Model MBR-3MP adds the
option of mounting up to an additional three (3)
Model MOM or Model 0MM expansion card cages.
Clear Lens (MDL)
MDL
Model MDL is a clear Plexiglas® lens that fits in one
(1) of the two (2) openings in the Model MME-3
enclosure door, or in one (1) of the three (3)
openings in the Model MLE-6 enclosure door.
One (1) lens is included in the Model MDL-1 package
Sheet Metal Blank Plate (MDB-1)
MDB-1
Model MDB-1 is a sheet-metal blank plate that fits in
one (1) of the two (2) openings in the Model MME-3
enclosure door, or in one (1) of the three (3) openings
in the Model MLE-6 enclosure door.
One (1) blank plate is in the Model MDB-1 package.
SIEMENS Industry, Inc.
Building Technologies Division
Upper or Middle Dead-Front Panel (MHD-1)
MHD-1
Model MHD-1 is a hinged sheet-metal panel that attaches
to the Model MME-3 or the MLE-6 enclosure backbox, and
fits in the upper or the middle section of the Model MME-3
backbox, or the upper or either of the two (2) middle
sections of the Model MLE-6 backbox.
Model MHD-1 has an opening with a cover plate for
the Model TSP-40 printer (when used), and attaches
to the backboxes with screw fasteners. Once in place,
Model MHD-1 covers and protects modules and wiring;
providing dead-front construction to that area.
Lower Dead-Front Panel (MHD-2)
MHD-2
Model MHD-2 is a hinged sheet-metal panel that attaches
to the Model MME-3 or the MLE-6 enclosure backbox, and
fits in the lower section of the Model MME-3, and on the
lower two (2) sections of the Model MLE-6 backbox.
Model MHD-2 has no openings and attaches to the
backboxes with screw fasteners. Once in place, Model
MHD-2 covers and protects modules and wiring; providing
dead-front construction to that area.
Middle Dead-Front Plate for Mounting Switch
and LED I Fan-Control Modules (MHD-3)
F-1.1
MHD-3
Model MHD-3 is a hinged sheet-metal panel that attaches
to the Model MME-3 or MLE-6 enclosure backbox, and fits
in either the middle of the upper sections of the Model
MME-3 or MLE-6 enclosures. Model MHD-3 has openings
for two (2) rows of Model VSM-1 Switch Modules; Model
VLM-1 LED Annunciator Modules; Model VFM-1 Fan
Control Modules, or Model VSB-1 Blank Plates.
Model MHD-3 has openings for two (2) rows of Model
VSM-1 Switch Modules; Model VLM-1 LED Annunciator
Modules; Model VFM-1 Fan Control Modules, or Model
VSB-1 Blank Plates. Each row can mount up to seven
(7) modules, totaling 14 modules for each Model
MHD-3. Model MHD-3 attaches to the backboxes with
screw fasteners, and is hinged for easy access to the
rear of the modules inside the enclosure.
I
ii
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
MXL Components - (continued)
Middle Dead Front Plate for the Switch/LED!
Fan-Control Modules with Printer Cutout (MHD-4)
Model MHD-4 is a hinged sheet-metal panel that
attaches to the Model MME-3 or the MLE-6 enclosure
backbox, and fits in the middle section of both
enclosures.
Model MHD-4 has openings for two (2) rows of Model
VSM-1 Switch Modules; Model VLM-1 LED Annunciator
Modules; Model VFM-1 Fan Control Modules, or Model
VSB-1 Blank Plates. Each row has space to mount four
(4) modules, totaling eight (8) modules for each Model
MHD-4.
Model MHD-4 also has a cutout to display the Model
TSP-40 Internal Thermal Strip Printer. Model MHD-4
mounts to the backboxes with screw fasteners, and is
hinged for easy access to the rear of the modules and
inside of the enclosure. When in place, Model MHD-4
covers and protects modules and wiring, providing
dead-front construction to that area.
When the Model MLE-6 enclosure is used with the Model
MBR-MP mounting plate for installation of MXL or MXLV
equipment, up to two (2) Model MSR-1 Rail Kit rows can
also be installed in Model MLE-6 for mounting of either
two (2) Model EL-410 amplifiers or some complement of
System 3-type mount modules. MPS-1 2 transformer!
supply, can accept NET-4 or NET-7 network interfaces, and
includes diagnostic LEDs and two (2) system relays. Model
PSR-1 mounts in the upper section of the MXL enclosure
backbox.
MXL Small Enclosure (MSE-2)
MSE-2
Model MSE-2 is a small MXL enclosure capable of housing
an MMB-2 or PSR-1 and MPS-6 or MPS-1 2. When expansion
is required the MSE-2 provides for mounting of either one
(1) MOM-2 or OMM-2. MSE-2 is part of the MXL-SS and
MXLV-SS packages.
Thermal Strip Printer (TSP-40A)
Rail Kit (MSR-1) S
MSR-1 TSP-40A
Model MSR-1 is a System 3TMtype rail kit that fits into
either the Model MME-3 or MLE-6 enclosure backbox.
Model MSR-1, which comes with a U-bracket and
a Z-bracket, allows the following modules -or any
other System 3-type module - to be mounted in
the Model MME-3 or Model MLE-6 enclosure:
Model EL-410 amplifier
Model PS-35 power supply
Model BC-35 battery charger
Model M01-7 I/O interlace
Model MID-1 6 input driver
Model MoD-i6 output driver
Model PS-5A power supply
Model SYS3-MPFO
[for mounting the D2300CP fiber-optic interface
modules, or the ccu pager interface]
When used in the Model MME-3 enclosure three (3)
Model MSR-1 Rail Kits can be installed to mount up
to three (3) rows for up to three (3) EL-41 0 amplifiers.
When used in the Model MLE-6, up to five (5) MSR-1
Rail Kit rows can be installed to allow mounting for up
to five (5) EL-410 amplifiers.
SIEMENS Industry, Inc.
Building Technologies Division
Model TSP-40A is a thermal strip printer, designed as an
event-logging device for the MXL panel, providing a
permanent-history report of all system activity. Model
TSP-40A mounts in the MXL enclosure, and its printout is
visible through a window in the locked-door enclosure.
Printouts are automatically spooled on a take-up reel for
easy records storage.
Remote Command Console (RCC-1)
RCC-1
Model RCC-1 is a remotely located MXL annunciator display
module. Model RCC-1 contains an 80-character LCD
display and control keypad (MKB), as well as a PS-51\17
network interface.
MXL Components - (continued)
Model RCC-1 modules can be located anywhere that
annunciation or control is required. Model RCC-1
can be programmed for display only, or can provide
display and system control. Remote printers, VDT, or
graphics computers can be located throughout a
facility -if Model PlM-1 is added to Model RCC-1.
®UL Listed Parallel Printer (PAL-11)
5-Volt Power Supply I Network Interface (PS-5N7)
I
I
I
I
r)-p1,
PAL-1
Model PAL-1 is a UL Listed, supervised parallel-system
printer for the MXL panel. Model PAL-1 connects
to Model MKB-5 to provide the MXL panel with a
®UL Listed, supervised parallel-system printer.
B6 Intelligent Control Point (ICP)
ICP
Model ICP is a field-mounted output module that is
capable of being programmed to either a remote bell
or horn -or to a speaker or telephone zone. Model ICP
communicates with the MXL fire panel, via ALD loop.
Line-Isolator Module (LIM-1)
LIM-i
Model LIM-i is a short-circuit isolator module for use
on the analog loops of the MXL panel. Model LIM-1 is
capable of providing Style 4 or Style 6 wiring of the
ALD loop. Multiple short-circuit isolators can be used
on a single ALD loop to prevent loss of protection in
the event of a short circuit.
Model PS-5N7 is a 5V power supply and MXL local-network
interface module. Model PS-51\17 is an integral part of
Model RCC-1 - Model PS-51\17 can be used to provide a
Style 4 or Style 7 network interface for either a remote
transponder for the MXLV panel (with either Model
TBM-2, ACM-1 and VSM-i I VLM-i I VFM-1), or to drive
Model 0MM-1 and associated MXLV cards.
5-Volt Power Supply (PS-5A)
Model PS-5A provides 5 Volts for powering Model MOI-7.
Model PS-5A obtains its power from the 24-Volt power
supply in the MXL system. Models MOI-7 and PS-5A both
mount on System 3 rails, and can also be mounted
externally to the MXL system. Models M0l-7 and PS-5A
typically drive remote-graphics annunciators or monitor
foreign systems and devices.
Network Interface Module (NIM-IW)
NIM-1W
Model NIM-1W allows for the interconnection or
networking of up to 63 MXL panels. Model NlM-i W
provides a RS-485 communications path in either Style 4
or Style 7 wiring configurations. Model NIM-1 W allows
MXL panels to have inter-panel logic, as well as
communicate in a peer-to-peer manner. Model
NIM-iW can be programmed via CSGM logic as a
Foreign System Interface to communicate with
external-building management systems.
I
I
Li
I
I
I
I
I
1
I
I
I
I
I
I SIEMENS Industry, Inc.
Building Technologies Division
Details for Ordering
Model
Number
Siemens
Installation-
Sheet Number
Description
CZM-1 315-090725 Conventional Zone Module
ILl-i I 1H! 1A! 1AH 315-092724 Intelligent Ion Detectors
ILP-1 IlPLT-1 315-092594 Intelligent Photo Detectors
ILl-i 315-093336 Intelligent Heat Detectors
ILl-i B /1 BH 315-093234 Intelligent Ion High Velocity Detectors
ILP-2 315-095028 FirePrintTM Application-Specific Detection
MSI-1 OB I 20B 315-093329 Intelligent Manual Station
MS-MI 315-092169 Intelligent Metal Manual Station
TRI-136 I 1361)1 B6R 315-093315 Intelligent Monitor Module [single! dual with array]
TRI-136M 315-094547 Intelligent Mini-Monitoring Module
ICP 315-092471 Intelligent Control Point
UM-1 315-092135 Line-Isolator Module
FP-1 1 315-095921 Intelligent FirePrintTm Detector
TRI-S!DIR 315-096242 Intelligent Monitor Module
Note: For further details, refer to MXL IOM manual: 315-092036.
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Femwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario March 2010 Building Technologies Division Tel: (973) 593-2600 (S11) L6T 5E4 I Canada Supersedes ht dated FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 R,.
URL: www.SBT.Siemens.com/FIS FAX: (905) 799-9858
MLE-6
Door
I
I
Catalog Sheet SIEMENS Fire Safety & Security Products
MXL I MXLV
Fire Alarm Enclosures & Equipment
Models: MME-3, MBR-MP, MLE-6, MBR-3MP, MDL-1, MD13-1, MDG-1,
MHD-1, MHD-2, MHD-3, MHD-4u
ARCHITECT AND ENGINEER SPECIFICATIONS
I
I
I
I
I
I
I
I
I
I
MME-3
Door
MME-3
Enclosure
Enclosure & Door Package (MME-3)
Standard Size MXL Enclosure
Removable Module Mounting Plate
(MBR-MP)
Hinged Locking Door with Optional
Inserts for Clear Lens, Grill, Blank Plate
Mounting for (1) MMB or PSR-1, and up to
(3) card cages (Model MOM or 0MM)
4&UL 864 9th Edition Listed, OULC Listed
Enclosure
Enclosure & Door Package (MLE-6)
Large-size MXL Enclosure
Removable Module Mounting Plates
(M BR-M P & M BR-3M P)
Hinged dual-lock door with optional inserts
for Clear Lens, Grill, Blank Plate
Mounting for (1) MMB or PSR-1, and up to
(6) card cages (Model MOM or 0MM);
or up to (3) card cages and (2) EL-410
amplifiers (MSR-1 Rail Kits)
€UL 864 91h Edition Listed, ®ULC Listed
I
I
I
I
I
I MXL/MXLV 5056
I SIEMENS Industry, Inc.
Building Technologies Division
Product Overview
The Models MME-3 and MLE-6 enclosures provide a
complete set of hardware for mounting all MXL and MXLV
modules for various system I size requirements.
Included in the enclosure series are back box and door sets;
removable mounting plates and clear lenses; louvered
ventilation grill plates, and blank plates for use with the
enclosure doors. Dead-front covers for standalone use -
with switch and I or annunciator modules and a strip
printer -are also available.
The Models MME-3 and MLE-6 enclosures are approved for
operation within the temperature range of 320 to 120°F
(0°C to 49°C).
MXL I MXLV Components
MME-3
MXL I MXLV Standard Size Enclosure
The Model MME-3 enclosure set consists of a sheet-metal
back box and door with key-lock. Model MME-3 can be used
for the MXL System; MXLV Voice Command Console;
MXLR Transponder; MXLRV Voice Transponder, or Amplifier
Equipment (using the MSR-1 Rail Kit).
To mount MXL I MXLV modules into Model MME-3, the
Model MBR-MP removable module mounting plate is
required. One (1) MMBorone (1) PSR-1, and upto three (3)
expansion card cages (Models MOM or 0MM) can be
mounted in the Model MME-3 enclosure, via use of the
Model MBR-MP mounting plate.
When used to mount MXL amplifiers (Model EL-41 0), Model
MBR-MP is not required, but up to three (3) Model EL-41 0
amplifiers may be installed into Model MME-3, via use of
three (3) Model MSR-1 rail kits. When amplifiers are
mounted in any enclosure, Model MDG-1 grills must be
installed on the door for proper ventilation.
Model MME-3 is designed for surface of semi-flush
mounting, and includes various knockouts for wire and
conduit entry. The door for Model MME-3, which contains
a key-lock, has two (2) cutouts for clear lenses, blank
plates or grills—depending on the application being used
MBR-MP
MME-3 & MLE-6 MXL Module Mounting Plate
The Model MBR-MP MXL I MXLV module mounting plate
is required for use in Models MME-3 and MLE-6 enclosures
to mount all MXL and MXLV equipment. However, Model
MBR-MP is not necessary if Models MME-3 and MLE-6
enclosures are to be used only for mounting of amplifiers
(e.g. - Model EL-41 0).
Model MBR-MP is a removable MXL/ MXLV module
mounting plate that allows the Model MME-3 or Model
MLE-6 enclosures to be shipped to the job site for
installation of wiring and conduit; while the system
hardware (e.g. -electronics) is mounted to the studs
of Model MBR-MP, pre-wired, programmed and tested
prior to delivery and installation at the job site.
SIEMENS Industry, Inc.
Building Technologies Division
The aforementioned process allows for more efficient
system start-ups; as well as a reduced chance of the
sensitive electronics being damaged while field wiring
and conduit are connected to the Models MME-3 and
MLE-6 enclosures.
The Model MBR-MP mounting plate bolts to either the
Model MME-3 or MLE-6 enclosures for easy installation on
the job site. Model MBR-MP also has handles to allow easy
transport and mounting.
Model MBR-MP contains mounting studs for one (1) Model
MMB or PSR-1; one (1) PlM-1; one (1) TBM-1, and up to
three (3) Model MOM or 0MM card cages - or two (2) card
cages, and one (1) TSP-40 Printer (same mounting studs as
the Model MBR-2 enclosures).
Model MBR-MP is ordered and shipped separately from the
Models MME-3 and MLE-6 enclosures.
MBR-MP M BRA P (with MXL equipment connected)
MLE-6
MXL I MXLV Large-Size Enclosure
The Model MLE-6 enclosure set consists of a sheet-metal
back box and door with two (2) key-locks. Model MLE-6 can
be used for the MXL system; MXLV Voice Command
Console; MXLR Transponder; MXLRV Voice Transponder, or
Amplifier Equipment (using the
Model MSR-1 rail kit).
To mount MXL I MXLV modules into the Model MLE-6
enclosure, the Model MBR-MP removable module
mounting plate is required, while Model MBR-3MP is
optionally available for use.
Using the MBR-MP mounting plate, one (1) MMB or
PSR-1 and up to three (3) expansion card cages
(Model MOM or 0MM) can be mounted into Model
MLE-6. If additional card cages are required, the Model
M13R3MP optional card cage mounting plate can also be
installed inside Model MLE-6 - below Model MBR-MP.
Model M13R-3MP allows mounting of an additional three (3)
Model MOM or 0MM expansion card cages. Various
combinations of hardware can be installed into Model
MLLE-6. If amplifiers are the only equipment to be
installed inside Model MLE-6, then, no Model MBR-MP or
M13R-3MP plates are required.
MXL I MXLV Components - (cont.'d)
Instead, up to five (5) Model EL-41 0 amplifiers can be
installed by using five (5) MSR-1 rail kits. Model MLE-6 can
also beused to mount up to three (3) MXL card cages and
two (2) amplifiers.
This configuration would be typical of a remote voice-
transponder cabinet. In this configuration, one (1) MBR-
MP would be used in the upper half of Model MLE-6 to
mount the MXL modules; while the lower half would
use two (2) Model MSR-1 rail kits to mount up to two
(2) Model EL-410 amplifiers. Model MLE-6 is designed for
surface or semi-flush mounting, and includes various
knockouts for wire and conduit entry.
The door supplied with the MLE-6 set has (3) cutouts for
clear lenses, blank plates or grills- depending on the
application. The door also contains two (2) key-locks, which are
keyed the same. Various combinations of dead-front
mounting plates are possible with the Model MLE-6
enclosure. A typical MXLV installation would have one (1)
Model MKB-2 at the top, and two (2) MHD-3 dead-front plates
in the middle — totaling 14VSM /VLM /VFM modules per
plate - and one (1) or two (2) MHD-2 lower dead-front plates.
MLE-6 MLE-6
(with MBR-MP &• (with door closed)
(2) Amplifiers]
MBR-3MP
MLE-6 Optional Card Cage Mounting Plate
Model MBR-3MP is an optional MXL I MXLV card-cage
mounting plate, used exclusively in the Model MLE-6
enclosure. When installed in the Model MLE-6 back box,
Model MBR-3MP adds the option of mounting up to an
additional three (3) Model MOM or 0MM expansion
card cages.
MUK-$MI-'
MDL-1
Clear Lens
Model MDL-1 is a clear Plexiglas® lens that fits in either
two (2) openings of the Model MME-3 enclosure door, or
in one (1) of three (3) openings in the Model MLE-6
enclosure door. One (1) lens is included in the Model
MDL-1 package.
MOL-1
MDB-1
Sheet-Metal Blank Plate
The Model MD13-1 is a sheet-metal blank plate that fits in
either two (2) openings of the Model MME-3 enclosure
door, or in one (1) of the three (3) openings in the Model
MLE-6 enclosure door. One (1) blank plate is included in the
Model MD13-1 package.
MDB-1
MDG-1
Louvered Ventilation Plate
Model MDG-1 is a louvered plate that mounts in either
two (2) openings of the Model MME-3 enclosure door, or
in one (1) of three (3) openings of the Model MLE-6
enclosure door. Model MDG-1 is required on MXLV
systems to provide ventilation for the enclosures when
using either Model EL-41 0 or Model ZAC-30 audio
amplifiers. One (1) MDG-1 plate is included in the
Model MDG-1 package.
MDG-1
I
I
I I
I
I
I
I
ri
I
I
I
I
I
I
I
I
I
I
k SIEMENS Industry, Inc.
Building Technologies Division
MXL I MXLV Components - (cont.'d)
MHD-1
Upper or Middle Dead Front Panel
Model MHD-1 is a hinged sheet-metal panel that attaches
to either Model MME-3 or MLE-6 enclosure back box.
Model MHD-1 fits in either the upper or the middle section
of the Model MME-3 back box - or either of the two (2)
middle sections of the Model MLE-6 backbox.
Model MHD-1 has an opening with a cover plate for the
Model TSP-40 printer (when used), and attaches to the back
boxes with screw fasteners. When in place, Model MHD-1
covers and protects modules and wiring; providing dead-
front construction in that area.
Each row can mount up to seven (7) modules, ttaling
14 modules for each Model MHD-3. Model MHD-3
attaches to the back boxes with screw fasteners.
Model MHD-3 is hinged for easy access to the rear of
the modules and inside of the enclosure.
MHD-1
MHD-2
Lower Dead Front Panel
Model MHD-2 is a hinged sheet-metal panel that attaches
to either Model MME-3 or MLE-6 back boxes. Model
MHD-2 mounts in the lower section of Model MME-3, and
on the lower two (2) sections of the Model MLE-6 backbox.
There are no openings for Model MHD-2, and it attaches to
the enclosures with screw fasteners. When in place, Model
MHD-2 covers and protects modules and wiring; provid-
ing dead-front construction in that area.
MHD-2
N1HD-3
Middle Dead Front Plate for Mounting Switch! LED!
Fan Control Modules
Model MHD-3 is a hinged sheet-metal panel that
attaches to Model MME-3 or MLE-6 back boxes. Model
MHD-3 fits in the middle or upper sections of the
enclosures. Model MHD-3 has openings for two (2) rows of
Model VSM-1 switch modules; Model VLM-1 LED-
annunciator modules; Model VFM-1 fan-control modules, or
Model VS13-1 blank plates.
SIEMENS Industry, Inc.
Building Technologies Division
MHD-3
MHD-4
Middle Dead Front Plate for the Switch/LED/Fan
Control Modules with Printer Cutout
Model MHD-4 is a hinged sheet-metal panel that attaches to
Model MME-3 or the MLE-6 back boxes. Model MHD-4 fits
in the middle section of the Model MME-3 or the MLE-6
enclosures. Model MHD-4 has two (2) rows for mounting
of Model VSM-1 switch modules; Model VLM-1 LED-
annunciator modules; Model VFM-1 fan-control modules or
Model VS13-1 blank modules.
Each row has space to mount four (4) modules, totaling
eight (8) modules for each Model MHD-4 panel. Model
MHD-4 also has a cutout to display the Model TSP-40 internal
thermal-strip printer. Model MHD-4 mounts to the back
boxes with screw fasteners, and is hinged for easy access
to the rear of the modules; as well as inside the enclosure.
When installed, Model MHD-4 covers and protects modules
and wiring, providing dead-front construction in that area.
MHL)-4
VSB-1
Switch Blank Plate
Model VSB-1 is a blank plate that covers one (1) opening
in either Model MHD-3 or MHD-4 dead-front panels,
and attaches to Model MHD-series panels with screw
fasteners.
I
I MXL I MXLV Components - (cont.'d) Details for Ordering
VSB-1
VSB-P
Plastic Switch Blank Plate
Model VSB-P is a plastic, blank-switch plate. Model VSB-P is
a direct replacement for Model VS13-1. Six (6) plates are
included in the Model VSB-P package.
MSR-1
Rail Kit
Model MSR-1 is a System 3TMtype rail kit that fits into
either Model MME-3 or MLE-6 enclosures. Model MSR-1
comes with a U-bracket and a Z-bracket, and allows
modules, such as: Model EL-41 0 amplifier; Model PS-35
power supply; Model BC-35 battery charger; Model
M0I-7 I/O Interface; Model MID-16; Model MOD-1 6;
Model PS-5A; Model SYS3-M PFO (for mounting the Model
D2300CP fiber-optic interface modules or the CCU
interface), or any other System 3-type module required
to be mounted in the Model MME-3 or MLE-6 enclosures.
When used in the Model MME-3 enclosure, three (3) Model
MSR-1 rail kits can be installed to mount up to three (3)
rows - for up to three (3) Model EL-41 0 amplifiers.
When used in Model MLE-6, up to five (5) Model MSR-1
rail-kit rows can be installed, allowing up to five (5) Model
EL-41 0 amplifiers.
When Model MLE-6 enclosure is used with Model MBR-MP
mounting plate for installation of MXL I MXLV equipment,
up to two (2) MSR-1 rail-kit rows can also be installed in
Model MLE-6 for mounting - either two (2) Model EL-410
amplifiers, or some complement of System 3-type mount
modules.
Model Number Part Number Description
MXL/V Medium/Standard Enclosure
MME-3 500-694209 (Backbox and door pkg.) Requires
MBR.MP to mount MXL/V modules.
Removeable module mounting plate
MBR.MP 500.694210 needed for MME-3 and MLE.5
Enclosure. Allows mounting of up to
(3)card cages (MOM/OMM)
MME-3R 500-694892 Red version of MME-3 Enclosure
MXL/V large Enclosure (8ackbox MLE-6 500-694530 and door pkg.) Requires MBR-MP to
mount MXL/V modules.
Card cage Expander Mounting Plate
for use with MlE6 allows mounting
MIIR.31MP 500.694532 of up to (3) additional cardcages
(MOM/OMM) in the MIE.6 for a
maximum total at (6) MOM or 0MM
card cages in the MLE-6
MLE6R 599694893 Rod version of MLE.6 Enclosure
Kit consisting of (1) MBR.MP.
MIE-KIT 599694530 (1) MBR-3MP and (1) MLE- cables
(without enclosures)
MDL-i 500-692069 (1) Clear Lens
MOB-i 500-692010 (1) Sheet Metal Blank
MDGi 500-692213 (1) Louver Door Plate
MHO-1 500-092011 (i) Dead Front Panel
MIIO-2 500-092072 (II Dead Front Panel
MHD-3 500-092073 Ill Dead Front Pane)
MHO-4 500-092074 Ill Dead Front Panel
VSB-1 500-092075 (1) Switch Blank
VSB-P 500-648552 (6) Plastic Switch Blank
MSR-1 500-092078 lii Rail Kit
I
I
I
I
I
L
I
I
I
I
I
I
I
U
I
LI
I
MSR-1
SIEMENS Industry, Inc.
Building Technologies Division
Mounting Diagram
2,02V
'
2862 52.0'
39125
&3.fl
2125"
MME-3 Back box VNMILE-6
(Shown In Inches)
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Femwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
Building Technologies Division Tel: (973) 593-2600 (SIP) L6T 5E4 I Canada November 2009
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905)799-9937 Supersedes sheet dated 11/06
URL: www.SBT.Sjemerts.com/FlS FAX: (905) 799-9858 1)
On-board, diagnostic ground-fault LEDs
Built-in Style 4 or Style 7 local module network
'RealTime' Clock
®UL 864 9th Edition Listed, ®ULC Listed
11
I
I
I
I
-Catalog Sheet SIEMENS Fire Safety &Security Products
MXL / MXLV
Fire Alarm Enclosures & Equipment
Model: MMB-3
ARCHITECT AND ENGINEER SPECIFICATIONS
MXL/ MXLV System main-control
microprocessor
Supports 6 Amps. (Model MPS-6) or
12 Amps. (Model MPS-12) power
supply
Two (2) isolated ALD Circuits:
Class A- (Style 6)or
Class B- (Style 4)
No shielded wire required on ALD circuits
Supports up to 50 total ALD circuits
Monitor and Control up to 60 analog I
intelligent input devices & 60
programmable device relays per ALD circuit
Removable terminal blocks for all field
connections
On-board, 16 bit microprocessor
Fully field programmable, via laptop PC
System firmware capable to Flash
memory upload •
Product Overview
The functions and controls for the MXL Control Panel are
performed by the Model MMB-3 Main Control Board. The
Model MMB-3 controls and monitors the following:
input-device identity; network communications, and
operator commands, which are each entered through the
Model MKB annunciator! keyboard. All operations are
supported by either the Model MPS-6 or Model MPS-12
power supply—eliminating the need for external power
supplies. Model MMB-3 is a direct replacement of Models
MMB-1 and MMB-2. Hence, Model MMB-3 is able to
provide total backward compatibility.
Specifications
Model MMB-3 provides two (2) Analog Loop Driver (ALD)
circuits. Each ALD loop can be configured as 'Class B' (Style 4)
or 'Class A' (Style 6), and each can monitor and control up to
60 analog input devices and 60 programmable device
relays. Style 4 or Style 6 ALD circuits are software-
programmable, which eliminates the need for jumpers.
Model MMB-3 is equipped with two (2) programmable
and 'Class B' (Style Y) or 'Class A' (Style Z) notification-
appliance circuits. Each circuit can activate up to 1.5
Amps of Siemens Industry, Inc. - Fire Safety audible
and visual notification appliances. Model MMB-3
includes a built-in battery charger and transfer circuit.
The charger is microprocessor-controlled, and
incorporates a 'brownout' circuit that switches the
MXL system to standby batteries during the reduction
and ! or loss of the primary source AC to avoid
inconsistent system operation and damage to the
batteries.
Upon command, Model MMB-3 is capable of displaying
the 'RealTime' battery voltage, AC voltage, charge
current, and other power data on the Model MKB
alphanumeric display. Model MMB-3 also has a 24 VDC,
1 Amp. output that powers the Model CZM-1 B6
modules. Model MMB-3 is designed with a built-in
mounting bracket.
U
I MXL/mxLv 5079
SIEMENS Industry, Inc.
Building Technologies Division
Details for Ordering
Model Part
Number Number Description
MMB-3 500-648860 MXL Main control Board
(with MBP-MP plate)
Specifications - (cont.'d)
Model MMB-3 mounts directly to the Model MBR-MP
mounting plate for mounting in either the Model MME-3
or MME-6 backbox enclosure. Model MMB-3 can also be
mounted in the Model MBR-2 or MBR-1 enclosures—with
Model MBR-1 requiring additional mounting brackets.
The on-board, 16-bit microprocessor -along with
nonvolatile EPROM and Flash memory - allow the MXL
system to be custom configured to meet a wide range of
customer requirements. Model MMB-3 provides a port
for connection to a laptop computer, allowing for off-
line field programming. Complete system configuration
can be easily uploaded, downloaded, and edited.
Changes can be verified using Model CSG-M custom
programming software with integrated CompareTM
system software.
Program options include (but are not limited to):
Smoke-detector environmental compensation
with two (2) maintenance-alert levels
History logging
Output-control (by event)
check and change time-based control
Detector sensitivity
Alarm verification by device or zone
32-character, custom alphanumeric messages
System operation passwords and NAC coding
Application-specific detection using FirePrintTM
System firmware is also resident in Flash memory, and
can be upgraded by software upload - eliminating the
need for upgrade chips.
Model MMB-3 supports local, main-remote networking,
via Style 4 or Style 7 wiring. This setup allows a single
MXL system to be distributed throughout a facility.
Model MMB-3 can then support up to 48 additional ALD
circuits (50 total), and a total of 3,000 addressable input
devices and programmable device relays. No additional
module is required in the enclosure with Model MMB3
to use Style 7 local network wiring.
Model MMB-3 is approved for operation over the
temperature range of 32°F (0°C) and 120°F (49°C).
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes. For
the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Femwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
Building Technologies Division Tel: (973) 593-2600 1501 L6T 5E4 I Canada
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937
URL: www.SBT.Siemens.com/FIS FAX: (905) 799-9858
November 2009
Speredea sheet dated I2103
(Reel)
I
I SIEMENS Fire Safety
1 MKB=2
I MXL/MXLV Display/Keyboard
ENGINEER AND ARCHITECT SPECIFICATIONS
Full Command Keyboard
80 Character LCD Display
Automatic Backlight
High Resolution Supertwist LCD
Programmable Function Keys
Partial System Disable LED
Power LED
Alarm, Supervisory, Trouble And Security LED's
Audibles Active/Silenced LED with Local Audible
Menu Driven Operator Commands
User Help Screens
Printer Control Keys
Display Control Keys
I
I
I
I
I
Tactile Membrane Switches With Audible Feedback
Hinged Panel For Easy Access
Listed and ULC Listed, CSFM, FM, NYMEA,
City of Chicago Approved
Description
I
I
The MKB-2 is a display/keyboard module for use with the
Siemens Building Technologies, Fire Safety Division MXL
and MXLV systems.The MKB-2 is supplied on a hinged
frame and mounts on the enclosure backbox. It provides
a complete operator interface including an 80 character
backlit supertwist LCD for display of all system
information.The LCD shows events in sequential
order and includes event type, device type and location,
the time of the event and an indication if the event has
been acknowledged.
The MKB-2 also provides a set of keypads used to
execute system commands such as Acknowledge,
Silence, Reset as well as disarming of devices for
maintenance and generation of system diagnostic reports.
From the keypad the operator is able to change the
sensitivity setting of smoke detectors, check device
voltages, obtain system power reports, disarm input and
output devices and manually toggle remote and local
relays. All commands are menu driven and a Help key
allows the operator to get further explanation of the
command structure. Operator actions are prompted so
training is kept to a minimum.
The MKB-2 also provides a set of 12 programmable
functions keys.The keys can be configured to activate
functions such as Drill, Fan Shutdown, Door Release, etc.
LEDs on the MKB-2 in conjunction with a local audible,
indicate active conditions such as Alarm, Supervisory,
Trouble and Security.The LEDs flash and the audible
sounds until events are acknowledged. Additional LEDs
indicate Audibles Silenced, Power On and Partial System
Disable.The Partial System Disable LED illuminates
whenever an input or output device is disarmed.
Display control keys allow the operator to Hold or Ad-
vance the scrolling display and view additional active
events.
Multiple MKB-2s can be used in the system each
providing full control of the MXL system. Up to four
MKB-2s can operate in a fully supervised mode, each
with independent printer driver capability (using a PIM-1).
The hinged panel allows easy access to the rear of the
MKB-2 and the other modules in the rear of the enclosure
backbox.The MKB-2 is covered by a clear lens (MDL-1) as
a part of the MDR-2 lockable door.
CATALOG NUMBER 5026
I
I
I
I
I
I
I
When used in MXLV applications, the MKB-2 has
removable plates on either side of the keyboard to allow
mounting of the MMM-1 (Microphone Master Module)
and theTMM-i (Telephone Master Module). The MKB-2
also has mounting studs available for the ACM-1 in MXLV
applications.
This equipment is approved for operation over the
temperature range of 0°C to 49°C.
Ordering Information
Model
Number Description Part Number
MKB-2 Display/Keyboard 500-892077
PIM-) Printef Interface 500-691324
Refer to Installation Instructions P/N 315-092087
MK13-2 Controls and Indicators
I i 00,M 01. 1Q00 PTIQ0IROQ0CS 01VQM MOt
1!!1 0 ALARM 0 POWER
[
EI
AUDIBLES PARTIAL 0 SILENCED SYSTEM
o SUPERVISORY
I ' W-KII 0 TROUBLE LJLJ
I EIi 0 SECURITY
ALT ALT
IItirEII III1EiIIwEII
AU E.1111 Lr IIHEflIcII
FIGURE 1
MKB-2 Panel
Mounting Diagram
FIGURE 2
Installing the MKB-2Annunciator/Keypad
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 1/04 Brampton, Ontario
Tel: (973) 593-2600 Siemens Building Technologies FAX: 19731 593-6670 Fire Safety Website: www.sbt.siemens.com/fis
EM
SFS-IG
Printed in U.S.A.
Canada L6T 5E4
Tel: (905) 799-9937 January 2004
FAX: (905) 799-9858 Sopetsedes sheet doted 5/02
5129
5230 5128
SIEMENS Fire Safety
Silent Knight 5128 ,and 5129
FourChannel Digital Communicator,
ENGINEER AND ARCHITECT SPECIFICATIONS
864 Listed. Meets NFPA 72 Chapter 4, for
Central Station/Remote Station Monitoring
DL Listed as a Slave Communicator for
Connection to System 3TM SXL-EX°, PXL',
and MXL Fire Alarm Control Panels
Four Fully Supervised Input Channels
Dual Phone Line Interface and Line
Fault Monitoring
Automatic 24 HourTest
Reports in Eight (8) Standard Communication
Formats
Local Keypad Programmer/Annunciator (5230)
Remote Programming (Up/Down Loading)
Relay Output for System Alarm or Trouble
Conditions
Compact Size Allows Mounting in Most Control
Cabinets, also Available in Separate Enclosure
(Model 5129)
I
I
I
I
I
I
Ii
I
I
I
Description & Feature
Siemens BuildingTechnologies, Fire Safety Division offers
the Silent Knight Models 5128 and 5129 four channel, dual
line digital communicators. These "slave" communicators
are designed to monitor UL listed fire alarm control
panels.The model 5128 is specifically designed and listed
to be mounted in the System 3TM SXL-EX, MXL and PXL
system enclosures. Power from these fire alarm controls
drive the 5128.
Programming and troubleshooting time is minimized by
user friendly English language messages available with
both the Model 5230 local programmer and PC based
remote downloading software, Model 5561.
Channel Inputs
Four supervised, or unsupervised, channel inputs can be
configured as either voltage inputs, active high or low
inputs, or contact closure inputs. The System 3TM using
the CSI-35 module, provides a combination of contact
closures and active high voltage input to activate the
5128/29. The SXL-EX, MXL and PXL use a contact closure
for each channel.
The preset channels are programmed as follows:
Channel 1 Alarm (Fire)
Channel 2 Trouble (Fire)
Channel 3 Sprinkler Supervisory
Channel 4 Alarm (Undefined)
Phone Line Monitors
Two phone line circuits detect phone line faults by
monitoring their voltages. Reporting of a fault as a trouble
condition is delayed by 40-90 seconds; if the condition
persists, an audible trouble in the communicator will
sound and the trouble reported to the central station. To
ensure phone line accessibility the 5128 and 5129 are
equipped with line seizure.
Test Functions
After power-up, the 5128 and 5129 self-test system
status. A watchdog circuit on the microprocessor resets
the communicator if a failure occurs. Additionally, a
24-hour auto test can be programmed to a central station
at a precise time.The installer can also initiate a manual
test using the Model 5230 programmer.
I
I
I
I
I
I
I CATALOG NUMBER 4000
I
Programming/Downloading
The Model 5230 LCD keypad programmer can be
temporarily connected to program or troubleshoot the
communicator on site. English language messages
assist in entering data, changing the 24-hour test time and
describing conditions currently in effect. A ring detector on
the 5128 and 5129 allows one call
downloading when used with optional remote
programming software and modem Model 5561.
AC Monitoring
All Fire Safety Fire Alarm Control Panels, as well as the
Model 5128 and 5129 communicators, can be programmed
to delay transmission of this signal to a central station as
required by Underwriters' Laboratories. The System 3 T
transmits this signal via an active high output from the
Model CSI-35 central station interface.
Technical Specification
Electrical: Input - 24VDC from UL
listed fire control panel.
Maximum DC Load: Standby - 84mA
Alarm - 154mA
AC Monitoring Input: AC trouble output from
System 3 T CSI-35
module
Relay Output: Form Cat 1A24VDC/24
VAC for Alarm orTrouble
Indicator Lights: Green LED Power On;
Red LED Phone Line
Trouble;Yellow LED Input
Fault and SystemTrouble
Connection: Screw terminals for phone
line and relay outputs. Color
coded flying leads for
control panel inputs
Reporting Formats: Communicates via SK 3/1;
5K4/2; SESCOA3/1; SK
FSK (4/2); Radionics BFSK
14 and 23; SIA 8/S1A20
formats
Telephone Requirements: FCC registration No.
AC6USA-75160-AL-E
Ringer Equivalence - 0.913
Type of Jack - RJ31X (two
required)
Approvals: UL 864 listed, NYMEA and
CSFM approved for SXL-EX,
SXL, MXL, PXL, FireFinder
XLS and System 3 T
Mechanical Specifications
Model 5128
Dimensions: 83/4"Hx4"Wx11/4"D
Enclosure: Vinyl/Acrylic meets U L94V0
Color: Black
Weight: 2 Lb.
Model 5129
Dimensions: 10/8" H x 101 /9"W x 3" D
Enclosure: Sheet Metal Cabinet
Color: Red
Weight: 6 Lb.
Accessories.'
Model 5230 Programmer/Annunciator with
harness
5561 Downloading software/modem kit
5128 Telephone interface kit - includes
RJ-31X block and cord, 3 ft., with
spade connectors
Mounting Suggestions
System 3 - mount in rear of enclosure or on
mounting rails
SXL-EXIPXL -mount on inside front door below
viewing window, or left side backbox
MXL - mount on inside of MHD-2 or MSR-1 rail kit
Ordering Information
Model
Number Description Part Number
5128 Silent Knight 4-Channel, Dual Line Digital
Fire Communicator - Internal
500-693213
5129 Silent Knight 4-Channel, Dual Line Digital
Fire Communicator . Remote
500-693214
5230 Programmer/Annunciator with Harness 500-693215
5561 Downloading Software/Modern Kit 500-693216
TlK-512 Telephone Interface Kit 500-293218
CSI-35 System 3 Central Station Interface Module 500-892318
Refer to Installation Instructions P/N 315-093223
Siemens Building Technologies
Fire Safety
Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (973) 593-6670
Website: www.sbt.siemens.com/fis
1/04
SFSG
Printed in U.S.A.
Fire Safety
2 Kenview Boulevard
Brampton, Ontario
Canada L61 5E4
Tel: (905) 799-9937
FAX: (905) 799-9858
January 2004
Supe,sedes sheet dated 9102
RCC-2
(Door Closed)
(Door Open)
I
L SIEMENS Fire Safety
I RCC=2 Remote Control Center
I RSE=1 Remote Serial Interface
I ENGINEER AND ARCHITECT SPECIFICATIONS
Remote MXL Display and Control
80 Character LCD Display
Auto Backlight
Flush Mount Option
Supertwist High Resolution Display
Full Command Keypad
MXL Network Interface (Style 4 or Style 7)
Metal Enclosure with Keylock Door
Restricts Keypad Access
Optional Printer/Peripheral Interface (PIM-1)
Supervised
I • Listed
I
I
I
I
I
Description
The Siemens Fire Safety Model RCC-2 Remote Control
Center annunciates MXL and MXL-Q system status.
The product includes an 80-character LCD display and
system status LED's. The RCC-2 includes system
acknowledge, silence and reset functions. The RCC,
plus the RSE-1, provide for mounting and control of the
PIM-1 printer interface module. The RCF-1 is a flush
trim ring for each of the controls.
Features
The RCC-2 annunciates all events that occur within an
MXL system. The LCD display includes scroll keys
that allow the operator to view sequential events. In
this manner the display reports each event by its type,
specific device, location and time. The RCC-2 key
switches allow individual or global acknowledge of
events by type, system silence, resound and reset.
All switches are protected by a clear cover and se-
cured by a lockset that matches the MXL system.
The unit enclosure is black.
The RCC/RSE products connect directly to the MXL
system network in style 4 or style 7 wiring. Multiple
units can be connected to any system for annunciation
at various locations throughout a facility. Up to three
units can be supervised with additional unsupervised
controls. Power is provided by any listed 24 Volt
supply.
All units include a mounting location and control of
the PIM-1 printer driver. Therefore, any of them can
operate a printer, video display terminal, alphanumeric
pager interface or remote diagnostics module. Each of
these system options is available from Siemens Fire
Safety.
CATALOG NUMBER 5073
I
n
I
U
I
I
I
Ordering Information
Model Description
Part
Number
RCC2 Remote Control Center with System Control
Functions and Sequential Event Display
500-699160
RSE-1 Remote Serial Interface Enclosure 500-699162
RCF-1 I Remote Control Flush Trim 500-699163
PIM-1 Power Interference Module 500-691324
T-45 Siemens Key 315-221182
Refer to Installation Instructions 315-099160
Approvals
The RCC series of annunciators and the RSE-1 are
listed by Underwriters Laboratories as compatible
with MXL-IQ, MXL and MXLV systems for indoor
applications.
Dimensional Data
5 in
RCC-2, RSE-1 Dimensions
RCC-2/RSE-1
BACKBOX
AL)
KBOX
RCC-2 Exploded View
RSE-1 Exploded View
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview, Boulevard
Florham Park, NJ 07932 9/01 Brampton, Ontario
Siemens Building Technologies Tel: (973) 593-2600
FAX: (973) 593-6670
Fire Safety Website: www.cerbpyro.com
10M
SFS-IG
Printed in U.S.A.
Canada L6T 5E4
Tel: 19051 799-9937
FAX: (905) 799-9858
September 2001
New Issue
SIEMENS Fire Safety
PAD 3
Auxiliary Power Supply - Notification Appliance Extender
ENGINEER AND ARCHITECT SPECIFICATIONS
I
I
I
I
6 amps of Notification Appliance Power
Advanced Microprocessor Control
24VDC Output Voltage
Four Power-Limited Notification Outputs
Strobe Synchronization Option Built In
Synchronized ANSI Temporal Pattern
Class 'A Selectable
Ground Fault Detection
Battery Supervision
3 Amp Auxiliary Power Output
Trouble Contact for Monitoring
Multiple Module Mounting in
System 3 Enclosures
Multiple Modules Share Battery Set
UL, ULC Listed, CSFM, NYMEA
and FM Approved
I
I
I
I
I
I
I
Introduction
The Model PAD-3 (PAD-3C for Canada) is a notification
appliance circuit expander with a built-in auxiliary
power output. It is designed for use with Siemens
BuildingTechnologies, Fire Safety Division fire alarm
control panels. This power source is designed to provide
the extra power required in buildings conforming to the
Americans with Disabilities Act.
Features
The PAD-3 provides 6 amps of 24 VDC power for
multiple uses. All 6 amps can be directed to 4 Notifi-
cation Appliance Circuits (NAC s). Each is rated at 3
amps and is power limited. Either 1 or 2 inputs can
control the four outputs. These outputs are compatible
with all Fire Safety 24VDC notification appliances. .
The PAD-3 can be configured so that the inputs can be
programmed as steady outputs, ANSI temporal
outputs, or synchronized strobe outputs. It can also
be programmed so that one input will silence U-MHU-
Series horn/strobe horns while the strobes remain on
using one set of wires.
The PAD-3 also offers a 3 amp auxiliary output for driving
other portions of your fire alarm system such as door
holders.This 24VDC filtered output is power limited.
When using this output, the total power available from
the PAD-3 will not exceed 6 amps.
A trouble contact is provided for monitoring the PAD-3
with a fire alarm panel through the input. It also has a
Form C dry contact for trouble monitoring. Therefore,
the user has the option of connecting it to a conven-
tional fire alarm panel's existing notification circuit, or
controlling it with aTRI Series device on intelligent fire
systems.
The PAD-3 offers battery supervision and management
as is required of fire alarm system components.
Ground faults are transmitted as are any other trouble
conditions. Trouble conditions not only change the
state of the trouble contact in the unit, but they also
break the notification circuit input to create a trouble
signal in the fire alarm control unit.
CATALOG NUMBER 3362
I
I
I
I
I
I
I
I
This product is packaged in its own sheet metal enclosure
with enough space to house the 7 amp-hour battery set
required for back-up.The enclosure comes in black or red.
System 3 enclosures may also be used to house multiple
PAD-3 modules in a single enclosure. Two modules are
capable of sharing the same battery set when mounted in
the same enclosure.
Options
One or both PAD-3 signal inputs control the notification
outputs, depending on the specific configuration setup
Possible configurations for the PAD-3 are:
For These Control These
Option: Inputs: Outputs: As:
1 Input 1 All Outputs Class 8 Circuits
2 Input 1 All Outputs Class 8 Circuits
Input 2* Silences horns on 1
3 Input 1 Outputs 1 and 2 Class 8 Circuits
Input 2 Outputs 3 and 4 Class B Circuits
4 Input 1 Output 1 Class 8 Circuits
Input 2 Outputs 2,3 and 4 Class B Circuits
5 Input 1 Outputs 1-2,3 and 4 Class A Circuit Pairs
6 Input 1 Outputs 1-2,3 and 4 Class A Circuit Pairs
Input 2* Silences horns on 1
7 Input 1 Outputs 1 and 2 Class A Circuit Pairs
Input 2 Outputs 3 and 4 Class A Circuit Pairs
8 Input 1 Outputs 1-2 Class A Circuit Pairs
Input 2 Outputs 3 and 4 Class B Circuits
*When used with U-MHU-Series horn/strobe units
Supervision
The Model PAD-3 supervises a variety of functions
including:
Low AC power
Low battery condition
Earth ground fault
Auxiliary output power limit condition
EOL supervision trouble or power limited condition
at an output
When a trouble condition occurs, the PAD-3 creates a
trouble condition on the fire control signal circuits to
which it is connected. It still maintains the ability to be
activated by the fire control. In addition, the PAD-3
provides a Form 'C' trouble relay output as an alterna-
tive to using the notification circuit trouble.
Electrical Specifications
AC Input: 120VAC @2.5 amps
Output: 24VDC @ 6 amps
Auxiliary Power Circuit: 1
Notification Circuits: 4
Output Configuration: 2 Class A or 4 Class B or
1 Class A & 2 Class B
Amps per Output
Circuit: 3.0
Notification Circuit
Outputs: 24VDC at 3.0 amps each,
24K ohm EOL resistor
required on each Class
B circuit
No. of Inputs: 2
Input Configuration: 2 Class B or 2 Class A
Input Voltage Range: 9-32VDC
Maximum Input Current: 0.006 Amps
Battery Charging
Capacity: 15.OA.H
Trouble contact rating: 2.5A @250 VAC, 30VDC
Ambient Temperature: 32°F to 120°F
Mechanical Specifications
Single Module Enclosure Model EN-PAD
Dimensions: 12'Wx16"Hx3'D
Color: Black
Indicator Lights
AC Power On: Green
BatteryTrouble: Yellow
Ground Fault: Yellow
AuxiliaryTrouble: Yellow
Output 1 Trouble: Yellow
Output 2Trouble: Yellow
Ordering Information
Model Description
Part
Number
PAO-3 Aux. power supply w/black enclosure 599-699189
PAD-3R Aux. power supply w/red enclosure 599-699190
PAD-3-MB Aux. power supply - main board only 500-699080
EN-PAD Black enclosure for PAD-3 310-099073
EN-PADR Red enclosure for PAO-3 310-099150
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 8/05 Brampton, Ontario
Tel: (973) 593-2600 Siemens Building Technologies FAX: (973) 593-6670
10M
SFS-lG
Canada LIST 5E4
Tel: (905) 799-9937
Fire Safety Website: www.siemens.com/fis Printed in U.S.A. FAX: (905) 799-9858
August 2005
Supersedes sheet doted 9/03
need for cumbersome, unreliable mechanical program-
ming methods and reduces installation and service
costs by electronically programming and testing the
detector prior to installation.
The FP-11 fire detector is compatible with the MXL
family of control panels including the MXL, MXL-IQ,
and MXLV.
The FP-11 detector is Underwriters Laboratories and
Underwriters Laboratories of Canada Listed.
Description
The FP-11 is a plug-in, two-wire, multi-sensor detector
with both photoelectric and thermal inputs and is
compatible with the MXL family of control panel
systems. Each detector consists of a dust resistant,
field cleanable photo chamber, a solid state
SIEMENS Fire Safety
FP-11 FirePrintTM Detector
Intelligent Fire Detector for MXL, MXL-IQ, and MXLV Control Panels
ENGINEER AND ARCHITECT SPECIFICATIONS
Most Sophisticated "Detector Intelligence" available today
Multi-Criteria fire detection for the price of a
photoelectric detector
FirePrintTMTechnology to discriminate between deceptive
phenomena and an actual fire
Easily programmed to match specific hazard profiles from the
control panel
Pre-Alarm reporting based on fire profile selected
Remote sensitivity measurement capability
System logic activation based on any of three inputs from
detector (smoke, heat or neural network)
Field cleanable chamber with replaceable chamber
parts available
Multi-color detector status LED
Two-wire operation
-. Compatible with Model DPU or FPl-32 field
programmer/tester
Supports EnviroLlNK software based automatic
environmental compensation
Backward compatible with older MXL systems
(Rev.2 and above) -
Optional fully programmable relay base, audible base, and
-duct housing
UL Listed, ULC Listed, CSFM, FM, NYMEA Ui Approved
Introduction
The FP-11 Intelligent Fire DetectOr provides the life
safetyindustry with the most highly evolved detection
system available today. The FP-11 utilizes advanced
detection technology that allows the detector to
distinguish nonthreatening deceptive phenomena, such
as cigarette smoke, from actual fire hazards, while
optimizing detection for the area in which it is in-
stalled. No other detection system available today
offers a higher level of protection or nuisance
alarm- immunity. The FP-11 uses state-of-the-art
microprocessor circuitry with error check, detector
selfdiagnostics and supervision programs.
The FP-ii intelligent fire detector is compatible with
the Siemens Building Technologies, Fire Safety Divi-
sion, Model DPU or FPI-32 field programmer/tester,
which is a compact, portable, menu-driven accessory
for electronically programming and testing detectors,
easily and reliably. The DPU or F P1-32 eliminates the
CATALOG NUMBER 6175
non-mechanical thermal sensor, microprocessor based
electronics with a low-profile plastic cover and base.
The FP-11 utilizes state-of-the-art ASIC and surface
mount technology for maximum reliability. Every FP-11
fire detector is shipped with a protective dust cover.
The FP-11 fire detector utilizes an infrared light
emitting diode (IRLED), and light sensing photodiode.
Under normal conditions, light transmitted by the LED
is directed away from the photodiode and scattered
through the smoke chamber in a controlled pattern.
The smoke chamber is designed to manage light
dissipation and extraneous reflections from dust
particles or other non-smoke airborne contaminants in
such a way as to maintain stable, consistent detector
operation. When smoke enters the detector chamber,
light emitted from the IRLED is scattered by the
smoke particles and is received by the photodiode.
The FP-11 also utilizes a modern, accurate, shock-
resistant thermistor to sense temperature changes.
The "on-board" FirePrint technology allows the
detector to gather smoke and thermal data, and to
analyze this information in the detector's "neural
network' By comparing data received with the
common characteristics of fires, or fire fingerprints,
the FP-11 can compare these "Fire Prints" to those of
deceptive phenomena that cause other detectors to
alarm. The advanced FirePrint technology allows the
FP-11 to accurately determine a true fire hazard from
a nonthreatening deceptive phenomena WITHOUT
needing to use alarm delaying verification and confir-
mation techniques, which can increase the probability
of losses due to fire.
The FP-11 provides the highest level of detector
intelligence available today with a detector/control
panel link that allows the user to program the detector
for the specific hazard profile Detectors are optimized
by selecting one of the following applications:
Office/Retail
Lobby
Computer Room
Dormitory
Healthcare
Parking Garage
Utility/Transformer Room
Hostile Environment
Precious Storage
Air Duct
Warehouse/Light Manufacturing
The software does the rest; no guessing on detector
sensitivities or alarm verification; the control panel
programs the FP-11 detector for the protected area
without hassle and without confirmation delays.
Once optimized for the hazards in the protected area,
the FP-11 provides the best detection you can buy.
Should the operator or installer forget to program the
detector, the FP-11 will revert to a default setting that
allows it to operate as a standard photoelectric or
photothermal detector.
The FP-11s FirePrint technology monitors input from
both the photo chamber and the thermal sensor,
evaluating this information with sophisticated
mathematical formulas, or algorithms, comparing this
input to characteristics of both threatening fires and
deceptive phenomena that would "fool" any ordinary
detector. This technology was developed over years of
research and reviewing the results of over 20 years of
fire test data in one of the world's most advanced fire
research centers. The results of this research are the
mathematical models that form the algorithms used in
FirePrint. No other fire detector has this level of
intelligence or this amount of research and develop-
ment supporting it's design.
The microprocessor's software can identify and
disregard false input caused by radio frequency (RFl)
and electromagnetic (EMI) interference, and validates
all trouble conditions before annunciating or reporting
to the control panel. The FP-11 detector's microproces-
sor uses an integral EEPROM to store the detector's
address and other critical operating parameters which
include the assigned program values for alarm and
trouble thresholds. Communications within the
detector itself and between the FP-11 and the control
panel, or with the FPl-32 field programmer/tester, are
supervised and safeguarded against disruption by
reliable, microprocessor based error checking routines.
Additionally, the microprocessor supervises all
EEPROM memory locations and provides a high
degree of EEPROM failure fault tolerance.
In MXL(V) applications, the FP-11 determines its
operating status to be normal, in alarm, or in trouble
depending on the difference between the alarm
threshold values stored in the detector's memory and
the detector's latest analog measurement. The
detector then communicates changes in its status to
the control panel.
In addition, the MXL(V) control panel will sample the
value of the FP-11's analog signal over a period of time
in order to determine if those values indicate exces-
sive buildup in the photo chamber; if so, the MXL(V)
will indicate that the particular detector requires
maintenance.
The FP-11 is listed as a self-testing device. The FP-11's
visible light emitting diode (LED) flashes green every
4 seconds to indicate it is communicating with the
control panel and that it has passed its internal self-
test. Should the detector sense a fault or failure within
its systems, the LED will flash amber and the detector
will transmit that information to the control panel.
A quick visual inspection is sufficient to indicate the
condition of the detector at any time. If more detailed
information is required, a printed report can be
provided from the MXL panel indicating the status
and settings assigned to each individual detector.
When the FP-11 moves to the alarm mode, it will flash
amber and transmit that information to the control
panel. When the MXL(V) confirms the detectors
condition, the panel will instruct the FP-11 to flash red
and to continue flashing until the system is reset at
the control panel. At that same time, any user defined
system alarm functions programmed into the system
are activated. Each FP-11 detector can operate one
remote alarm indicator, one auxiliary relay, or one
audible base.
Detector sensitivity, calibration, and identification are
dynamically supervised by the control panel. Detector
sensitivity and pre-alarm levels are a function of the
application chosen at the control panel and are
controlled by the panel. If an alternate, non-FirePrint
mode is selected, then the sensitivity can be changed
from the control panel.
The DPU or F P1-32 Program/Test accessory is used to
program and verify the detector's address. The
technician selects the accessory's program mode to
enter the desired address. The DPU or FPl-32 auto-
matically sets and verifies the address and tests the
detector. It also allows the user to change the device
ID from that of an FP-11 to an older detector ID such as
an lLP-i, lLPT-1, lLP-2, ID-60P or lD-60PT to allow for
easy replacement of older detectors without the need
of reprogramming the control panel.
The FPI-32 operates on AC power or rechargeable
batteries, providing flexibility and convenience in
programming and testing equipment almost anywhere.
When in the test mode, the DPU or FPl-32 will perform
a series of diagnostic tests without altering the
address or other stored data, allowing technicians to
determine if the detector is operating properly.
All FP-11 detectors can be cleaned in the field, when
required, by simply removing the detector cover and
unsnapping the photo chamber. There is also the
option of cleaning the interior of the detector with a
clean, soft cloth or brush, or replacing the labyrinth and
bug screen included in the detector maintenance kit,
model DMK-ii.
The FP-11 uses the low profile surface mounting base,
model DB-11. This base mounts on a 4-inch octagon,
square, or a single gang electrical box. The base
utilizes screw clamp contacts for electrical connections
and self-wiping contacts for increased reliability. The
base can be used with the optional LK-11 detector
locking kit which contains 50 detector locks and an
installation tool, to prevent unauthorized removal of
the detector head. The DB-11 base has integral decora-
tive plugs to cover the outer mounting screw holes.
The FP-ii is electrically compatible with existing MXL
detector accessories including relays, remote lamps,
duct housings, and audible bases. With duct housings,
a base adapter and new detector housing cover are
required (order AD-li UK upgrade kit). To use existing
DB-3S base or audible base, the FP-11 requires a DB-
ADPT base adapter.
All FP-11 detectors are approved for operation within
the UL specified temperature range of 32 to 100
degrees F (0 to 38 degrees Q.
Application Data
Installation of the FP-11 series of fire detectors
requires a two-wire circuit of 18 AWG (minimum)
thermoplastic fixture wire enclosed in conduit, or 18
AWG limited energy, shielded cable without conduit,
if permitted by local codes. Field wiring should
conform to local and National Electric Codes and the
control panel wiring specifications.
"T-tapping" is permitted only for Style 4 (Class B)
wiring.
FP-11 fire detectors can be applied within the maxi-
mum 30 foot center spacing (900 sq. ft. areas) as
referenced in NFPA 72. This applications guideline is
based on ideal conditions, specifically, smooth ceiling
surfaces, minimal air movement, and no physical
obstructions between potential fire sources and the
detector. Do not mount detectors in close proximity
to ventilation or heating and air conditioning outlets.
Exposed joints or beamed ceilings may also affect safe
spacing limitations for detectors. Should questions
arise regarding detector placement, observe NFPA
72 guidelines.
Good fire protection system engineering and common
sense dictate how and when fire detectors are
installed and used. Contact your local Siemens
Building Technologies, Fire Safety Division authorized
sales outlet whenever you need assistance applying
FirePrint in unusual applications. Be sure to follow
NFPA guidelines, U L/U LC approved installation
instructions, which are included with every detector,
and local codes as for all fire protection equipment.
Dimensions
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I The FP-11 fire detector may be installed on the same
initiating circuit with IL or ID series detectors (Photo-
electric, thermal, or ionization), MSI series manual
I
stations, TRI series interfaces, ICP output control
devices, or CZM series of addressable, conventional
zone modules.
I
Technical Specifications
Current Requirements: Normal 750 pa Alarm 750 pa
Operating Temperature: +32°F (0°C) to 100°F (38°C)
per UL 268/268A
Humidity: 0-93% Relative Humidity
Non-Condensing
Ordering Information
Model Description
Part
Number
FP-11 Addressable FirePrint Fire Detector 500-095112
OBil Detector Mounting Base for Series 11 500-094151
DB-11E Detector Base (Small) 500-094151E
AD2-P Air Duct Housing for use with FP-11, HFP-ii, HFPO-11,
PE-11
500-649706
AD2-XHR Air Duct Housing for use with FP-11, HFP-11, HFPO-11
with relay
500-649708
ADBX-11 Audible Base 500-096181
DB-X11RS Relay Base for Series 11 Intelligent Detectors 500-096125
RU-1 Remote (red) alarm indicator- 4 octagon box mount 500-390613
RU-2 Remote (red) alarm indicator- single gang box mount 500-390614
LK-11 Base Locking Kit for Series 11 detectors 500-695350
DMK-ii Series ii Maint Kit (replacement labyrinth and bug
bug screen)
500-695338
DB-ADPT Base Adapter to OB-35 Base 500-094187
In Canada Order.
FP-11C Addressable FirePrint Fire Detector (ULC( 500-095112C
DB-11C Detector Mounting Base for Series il(ULC) 500-095687
AD-11 PC Air Duct Housing )IJLC( 500-095984
D8-X11 RSC Relay Base for Series 11 Intelligent Detectors (ULC) 500-096125C
ADBX-11C Audible Base for Series 11 Intelligent Detector (ULC( 500-096181C
Siemens Building Technologies
Fire Safety
Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (973) 593-6670
Website: www.sbt.siemens.com/fis
Fire Safety
2 Kenview Boulevard
5/06 Brampton, Ontario
1OM Canada L6T 564
SFS-IG Tel: (905) 799-9937 May 2006 Printed in U.S.A. FAX: (905) 799-9858 Supetsedes sheet doted 6/03
Catalog Sheet SIEMENS Fire Safety & Security Products
MXL, MXL-IQ -and MXLV' Control Panels
Intelligent Thermal Detector
Model FPT-11
ARCHITECT AND ENGINEER SPECIFICATIONS
Microprocessor-based design
Rate compensated
I
F
I
Innovative technology provides high-speed;
fault-tolerant System I Detector
communications
MUlti-color detector status LED
Optional fully-programmable relay and
audible bases
Two-wire operation
Backward compatible with older MXL systems '
(Rev 2and Above)
Compatible with DPU or FPI-32 field
programmer'! tester
® UL and 0 ULC Listed;
FM, CSFM & NYMEA Approved
Product Overview
I
F
I
I
I
I
I
I
The FPT-1 1 Intelligent Thermal Detector, which operates
with the MXL family of control panels: MXL, MXL-IQ and
MXLV, provides an advanced method of detection /
address programming and supervision —combined with
sophisticated control-panel communication. The FPT-1 1
detector uses a state-of-the-art thermistor that provides
up to 135°F (57.2°C) rate-compensated temperature.
The FPT-1 1 Intelligent Thermal Detector is compatible
with the DPU and FPl-32 Field Programmer / Testers.
These testers are compact, portable and menu-driven
accessories that make programming and testing
detectors faster, easier and more reliable than other
methods. The FPI-32 Field Programmer/ Testers
eliminate the need for cumbersome, unreliable
mechanical programming methods, and reduce
installation and service costs, via electronically
programming addresses and functionally testing
the FPT-11's performance before the detector is
installed.
The FPT-1 1 Intelligent Thermal Detector is Underwriters'
Laboratory listed' and Underwriters' Laboratory of
Canada listed.
Specifications
The FPT-1 1 is a plug-in, two-wire thermal detector,
compatible with the MXL family of control panels.
Each FPT-1 1 has microcomputer-chip technology and
highly stable, solid-state electronic circuitry.
TheFPT-1 1 utilizes a modern, accurate and shock-
resistant thermistor to sense temperature, changes.
This electronic sensing method virtually eliminates
thermal lag associated with mechanical-temperature
sensing devices, and provides almost instantaneous
temperature information to the control panel.
I
I
I
F
'I MXL Control Panels 6176
Building Technologies
I
Fire Safety & Security Products
Specifications - (continued)
The FPT-1 1 is a 1 35°F (57.2°C) rate-compensated
detector. The microprocessor for the FPT-1 1 detector
uses an integral EEPROM to store the detector's
address. Communications within the detector, as well
as between the FPT-1 1 and the control panel (or with
the FPl-32 field programmer I tester) are supervised
and safeguarded against disruption by reliable
microprocessor-based error-checking routines.
Additionally, the microprocessor supervises all EEPROM
memory locations, and provides a high degree of
EEPROM failure fault tolerance.
The FPT-1 us listed as a self-testing device. The visible
Light-Emitting Diode (LED) from the FPT-1 1 flashes
green every four seconds to indicate it is
communicating with the control panel and to notify it
has passed its internal self-test. Should the detector
sense a fault or failure within its systems, the LED will
flash amber, and the detector will transmit that
information to the control panel. A quick, visual
inspection is sufficient to indicate the condition of the
detector at any time. If more detailed information is
required, a printed report can be provided from the
MXL panel indicating the status and settings assigned
to each individual detector.
When the FPT-1 1 moves to the 'Alarm' mode, the FPT-
11 will flash amber and transmit that data to the
control panel. When the MXL (V) confirms the current
condition of the FPT-1 1, the panel will instruct the FPT-
11 detector to flash 'red' until the system is reset at the
control panel. At that same time, any user-defined,
system-alarm functions programmed into the MXL
System are activated. Each FPT-1 1 detector can
operate (1) remote alarm indicator, (1) auxiliary relay,
or (1) audible base, and only (1) accessory per
detector.
A DPU or FPl-32 programmer I tester is used to
program and verify the address for the FPT-1 1. The
user selects the 'Program' mode to enter the desired
address. The programmer I tester then automatically
sets and verifies the address as well as test the
detector. The programmer I tester contains
rechargeable batteries, in order for the address of the
FPT-1 1 to be programmed by the user from the most
convenient location. The user can also separately test
the FPT-1 1 detector for functionality. When the user
selects the 'Test' Mode, a series of tests are
automatically conducted, and the user is informed
whether the FPT-1 1 detector has passed or failed.
The FPT-1 1 detector is compatible on the same
MXL- initiating circuit with other IL Series, FP Series or
ID-60 Series addressable ionization, photoelectric, or
thermal detectors, MSI addressable manual stations,
TRI Series addressable interfaces, or CZM Series
addressable conventional zone modules.
Building Technologies
Fire Safety & Security Products
Each FPT-1 1 thermal detector is capable of operating
one "X" or "I" Series remote alarm indicator or auxiliary
relay or audible base. The FPT-1 1 detectors use a
surface mounting base, Model DB-1 1, which mounts
on a 4-inch octagonal, square or single gang electrical
box. Relay base Model DB-X1 1 RS mounts to a 4-inch
square deep electrical box. Audible base Model ADBX-
11 also mounts to a 4-inch square deep electrical box.
The DB-1 1, and the DB-X1 1 RS and ADBX-1 1 use screw-
clamp terminals for all electrical connections and self-
wiping contacts for reliability. The bases also contain a
provision for an optional concealed locking mechanism
to prevent unauthorized removal of the detector head,
Model LK-1 1.
Application Data
The MXL uses ALD loop circuits with each circuit
capable of supporting up to (60) FPT-1 1 intelligent
detectors.
The detector, or group of detectors, require a two-wire
circuit of minimum 18 AWG thermoplastic fixture wire
enclosed in conduit, or minimum 18 AWG limited
energy, shielded cable without conduit if permitted by
local building codes. Wiring should conform to local and
National Electrical Codes, and to the control panel's
wiring specifications. T-tapping is permitted only for
Style 4 (Class B) wiring.
Locate the FPT-1 1 on the ceiling, at least 4 inches from
the side walls. For an ideal, smooth ceiling condition,
place the detectors at a maximum center spacing of 50
feet (2,500 square feet), 25 feet from side walls or room
partitions. For FM-approved installations, the FPT-1 1 has
a RTI rating of 'QUICK.' Use a maximum center spacing of
20 feet (400 square feet), 10 feet from side walls or
room partitions.
Actual job conditions and sound engineering judgment
must determine detector spacing. Consider
environmental factors including ambient temperature
fluctuation, and the nature of the fire hazard. Room or
area configuration and ceiling type (sloped or flat,
smooth or beamed) also dictates placement.
Should questions arise regarding detector placement,
follow the drawings provided and I or approved by
Siemens Building Technologies - Fire Safety Division or
by its authorized distributors.
Technical Data
Current Requirements: Normal 750 pa
Alarm 750 pa
Operating Temperatures: +32°F (0°C) to
100° F (38°C)
Humidity: 0-93% Relative Humidity
Non-condensing
Mountina Diaaram
Details for Ordering
Model No. Part No. Description
FPT:11 -' 500-095918 Addressable Thermal fire Detector
081 500-094151 Detector Mounting Base for Series 11
DO-11E 500-094151E Small 4.5 inch Diameter Detector Base
08-X1IRS 500-096125 Relay Base for Series 11 Intelligent
Detectors
ADBX-ll 500-096181 Audible Base for Series Ii Intelligent
Detector
RU-i 500-390673 Remote (red) alarm indicator-octagon
box mount
RLl-2 500-695350 Remote (red) alarm indicator-single
gang box mount
LK-11 500-695350 Base locking Kit for Series 11
DB-ADPT 500-094187 Base Adapter to D8-3S Base
In Canada Order:
Model No. Part No. Description
FPI tic 500-095918C Addressable Thermal Fire Detector (ULCI
DB-HC 500-095687 Detector Mounting Base for Series i1lULC)
08-X11RSC 500-096125C Relay Base for Series Ii Intelligent
Detectors (ULC)
AOBX-11C 500-096181C Audible Base for Series 11 Intelligent
Detector (1JLCl
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety 8 Femwood Road 2 Kenview Boulevard Building Technologies Florham Park, NJ 07932 Brampton, Ontario J 2009 Fire Safety & Security Products Tel: (973) 593-2600 srs L6T 5E4 / Canada FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 Supd ht dated 12/03
(Rev.l) URL: www.SBT.Siemens.com/FIS FAX: (905) 799-9858
I
I
I
LI
The MSI-10B and 20B manual fire alarm boxes operate
with the MXL, IXL/lCON-1 and XL3 control panels.
The manual fire alarm box's microcomputer chip has the
capacity of storing, in memory, identification information
as well as important operating status information.
Fire Safety's innovative technology also allows all MSI
Series Intelligent manual fire alarm boxes to be pro-
grammed by using the Model DPU or F P1-32 Program-
mer/Tester. The Programmer/Tester is a compact,
portable, menu driven accessory which makes pro-
gramming and testing a manual fire alarm box device
faster, easier and more dependable than previous
methods. The DPU or FPI-32 eliminates the need for
the device's mechanical addressing mechanisms, such
as program jumpers, dipswitches or rotary dials
because the Programmer/Tester electronically sets the
manual fire alarm box's address into its microcomputer
chip, nonvolatile memory. Vibration, corrosion and
CATALOG NUMBER 6187
Replaces Catalog No. 6162
I
I
I
I
I
SIEMENS-,..
Intelligent Initiating Devices
Manual Fire Alarm Boxes
MSI:10B and MSI-20B Intelligent Manual Fire Alarm
for MXL, IXL, and XL3 Control Panels
ENGINEER AND ARCHITECT SPECIFICATIONS
Fire Safety
Boxes
Durable Design
Shock and Vibration Resistant
'. Pull Down Lever Remains Down Until Reset
Custom Microcomputer ChipTechnology
Dynamic Supervision
Reset with Allen Key
No Break Rods Necessary
TwoWire Operation
Surface or Semiflush Installation .
DPU or F P1-32 Programs and Verifies Device's
Address and Tests Device's Functionality
Electronic Address Programming is Easier
and More Dependable
Single and Double Action Models Available
®, Listed, CSFM, FM and NYMEA Approved
Introduction
Siemens BuildingTechnologies, Fire Safety MSI-10B
and 20B intelligent manual fire alarm boxes provide the
markets' most advanced method of address programming
and supervision, combined with sophisticated control panel
communication. Each MSI manual fire alarm box incorpo-
rates a new custom microcomputer chip.The microcom-
puter chip technology, and its sophisticated bi-directional
communication capabilities with the control panel, achieves
the state of an "Intelligent Initiating Device"
Description
The MSl-10B and 20B are constructed of durable molded
polycarbonate material which is matte finished in red with
raised white lettering.The housing accommodates a "pull-
down" lever which, when operated, locks in position
indicating the manual fire alarm box has been activated.
The pull down lever remains down and locked until the
manual fire alarm box is reset.The manual fire alarm box
is reset only by opening the hinged housing cover with
an allen key and then closing and locking the cover.
I
I
I
I
I
1
I
I
I
I
I
I
I
I
other conditions which deteriorate mechanical addressing
mechanisms are no longer a cause for concern.
The MSI-10B and 20B are fitted with screw terminals for
connection to an addressable circuit.They can be either
surface or semif lush mounted.
The MSI Series manual fire alarm boxes derive their
power, communicate information and receive com-
mands over a single pair of wires.
The MSI Series is compatible on the same circuit with
all IL and ID-60 Series ionization, photoelectric or
thermal detectors, TRI Series interfaces or CZM Series
addressable conventional zone modules.
The MSI-10B and 20B intelligent manual fire alarm
boxes are Underwriters Laboratories, Inc. listed.
Current Draw
1 mA
Ordering Information
Model Description
Shipping WI
Lb. Kg.
MSll0B Addressable Manual Fire
Alarm Box, Single Action
2 .90
MSI-208 Addressable Manual Fire
Alarm Box, Double Action
2.5 1.13
SB-SR Surface Mounting Box 1.5 .68
LIP Reset Tool Package (Contains 2 Tools) .5 .23
Mounting Data
HOUSING
HINGED TO NAMEPLATE
BACKPLATE
1 Y,6 in s'
HOUSING ,A,
ll,
Nil LOCKING \ \.
" SCREW BACKPL.ATE
SURFACE MOUNTING ENCLOSURE
'S •'
SB5R
3 in
3½ in DEEP
SWITCH BOX
USER SUPPLIED)
If-0 01 IX-1,
0
0
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 12/04 Brampton, Ontario
Tel: (973) 593-2600 Siemens Building Technologies FAX: (973) 593-6670
Fire Safety Website: www.sbt.siemens.com/fis
10M
SFS-IG
Printed in U.S.A.
Canada L6T 5E4
Tel: (905) 799-9937 December 2004
FAX: (905) 799-9858 Supersedes shoot dated 7/03
11
I
I SIEMENS
I TRI Series
I
Intelligent Initiating Devices Interface Modules
for MXL Fire Detection Panels TRI-S,TRI-D,TRI-R
ENGINEER AND ARCHITECT SPECIFICATIONS
Interfaces and Supervises Normally Open Contacts
Integral SPDT Relay (up to 4 amps) onTRl-R Model
I
I
Fire Safety
Dual Input onTRl-D Model
Multi-color L.E.D. indicates status (green, amber, red)
Easy front access to programming port and
wiring terminals
Mounts in 4 inch square 21/4 deep box, or double
gang box
Dynamic Supervision
Comes with 5x5 inch faceplate
Two wire operation
SensorLink Model FPl-32 Programs and Verifies
Device's Address and Tests Device's functionality
Electronic Address Programming is Easy
and Dependable
UL Listed, ULC Listed
CFSM, FM, NYMEA Approved
I
I
I
I
I
I
Introduction
The TRI Series' Intelligent interface modules are
designed to provide the means of interfacing direct
shorting devices to the MXL system's ALD loop
circuit.
The TRI Series Intelligent interface modules provide
the market's most advanced method of address
programming and supervision, combined with sophis-
ticated control panel communication. Each TRI Series
interface module incorporates a microcomputer chip.
The TRI Series microcomputer chip technology and its
sophisticated bi-directional communication capabilities
with the control panel, achieve the state of an "Intelli-
gent Device."
Description
The TRI Series Intelligent interface modules are avail-
able in three models. The TRI-S and TRI-R are designed
to monitor a normally open dry contact. The interface
module reports the contact's status to the control
panel. The TRI-S model can only monitor and report the
status of the contact, while the TRI-R incorporates an
addressable Form C relay. The TRI-R relay and contact
device input are controlled at the same address. For
the MXL system, the relay and input contact can be
controlled as a separate function. The relay is typically
used where control or shunting of external equipment
is required.
The TRl-D is a dual input module and is designed to
supervise and monitor two sets of dry contacts. This
interface module requires two address settings. The
TRI-D is ideal for monitoring a waterf low switch and its
respective valve tamper switch.
The TRI has a multi-color Light Emitting Diode that
flashes green when operating normally, amber if unit
CATALOG NUMBER 6179
I
I
I
I
I
I
I
is in trouble condition, and red to indicate a change of
state. The TRI-D flashes twice, once for each address,
the TRl-R red L.E.D. indicates a change of state in
the relay.
The device's microcomputer chip has the capacity of
storing, in memory, identification information as well
as important operating status information.
SIEMENS Fire Safety's innovative technology allows
all TRI Series intelligent interface modules to be
programmed by using the SensorLink model FPl-32
Programmer/Tester. The F P1-32 Programmer/Tester is a
compact, portable, menu driven accessory that makes
programming and testing an interface device faster,
easier and more dependable than previous methods.
The FPI-32 eliminates the need for mechanical
addressing mechanisms, such as program jumpers,
DIP switches or rotary dials, because the FPI-32
electronically sets the TRI interface's address into the
interface's microcomputer chip nonvolatile memory.
Vibration, corrosion and other conditions that deterio-
rate mechanical addressing mechanisms are no longer
a cause for concern.
The TRI Series is fitted with screw terminals for
connection to an addressable circuit.
TheTRI Series is fully compatible' on the same MXL
circuit with all intelligent F9 IL and ID-60 Series
detectors, MSI Series addressable manual stations
or any other addressable intelligent modules, such
as the CZM or ICR
All TRI Series intelligent interface modules are
UL listed.
Environmental operating conditions for all TRI Series
modules are 32°F (°C) to 120°F (49°C) with a relative
humidity of not greater than 93% non-condensating.
Ordering Information
Model Description
Shipping Wt.
Lb. Kg.
TRI-S Single Input loz. 2
'3111:4 Single Inputw/Relay loz. 2
TRI-Di Dual Input loz. 2
Mounting Data
Addressable interface Model TRI-S, TRI-D, TRI-R
mounts directly into a 4 inch square 21/4 deep box
or a double gang box (user supplied). A 5 inch square
off-white faceplate is included with each TRI.
MOUNTING SLOTS
FOR 4 INCH
SWITCHBOX
TRI-S/-D/-R
MODULE
OUNTING
)LES FOR
VITCH PLATE
MOUNTING SLOTS
FOR DOUBLEGANG
S WITCH BOX
Figure A
Mounting the TRI-S/-R/-D
Siemens Building Technologies
Fire Safety
Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (973) 593-6670
Website: wwwcerbpyro.com
Fire Safety
2 Kenview Boulevard
4/02 Brampton, Ontario
10M Canada L6T 5E4
SFS-IG Tel: (905) 799-9937
Printed in U.S.A. FAX: (905) 799-9858
April 2002
S,,o,sodos slot dated 60
LI
SIEMENS Fire Safety
TR1=B6M
I Intelligent Device Interface Module
ENGINEER AND ARCHITECT SPECIFICATIONS
I
I
I
I
I
I
I
Intelligent Interface Modules For
MXL and IXL Control Panels
Interfaces and Supervises Normally Open (Fire Detection)
or Normally Closed Contacts (Security Detection)
Compact Size Allows Mounting in Single Gang Box
Behind Equipment
Operates with MXL ALD Loop, MXL XLD Loop
or IXL ICon Loop
Microcomputer Chip Technology
Innovative Technology Supports Comprehensive System
and Interface Communication
Dynamic Supervision
Two Wire Operation
SensorLiNK, model FPI-32 Programs and Verifies
Device's Address and Tests Device's Functionality
Electronic Address Programming is Easier and
More Dependable
@ Listed, ULC Listed, CSFM and NYMEA Approved
V • &'
' .- ,j
-.
Introduction
TheTRI-B61VI Intelligent interface module is designed
to provide the means of interfacing direct shorting
devices to the MXL system's ALD loop circuit, MXL XLD
loop or the IXL system's ICon loop circuit.
TheTRl-B6M Intelligent interface module provides the
market's most advanced method of address program-
ming and supervision, combined with sophisticated
control panel communication. Each TRI-B6M interface
module incorporates microcomputer chip technology
and its sophisticated bi-directional communication
capabilities with the control panel.
Description
The TRl-B6M is designed to monitor a normally open or
closed dry contact and reports the contact's status to
the control panel.
The device's microcomputer chip has the capacity of
storing, in memory, identification information as well
as important operating status information.
Siemens Building Technologies, Fire Safety Division
innovative technology allows allTRl-B6M intelligent
interface modules to be programmed by using the
SensorLiNK model FPI-32 Programmer/Tester. The
FPI-32 Programmer/Tester is a compact, portable, menu
driven accessory that makes programming and testing an
interface device faster, easier and more dependable than
previous methods. The FPI-32 eliminates the need for
mechanical addressing mechanisms, such as program
jumpers, DIP switches or rotary dials, because it electroni-
cally sets theTRl-B6M interface's address into the
interface's microcomputer chip non-volatile memory.
Vibration, corrosion and other conditions that deteriorate
mechanical addressing mechanisms are no longer a cause
for concern. ThisTRl-B6M is connected to the programmer/
tester with the programming cable provided with the
tester. This cable utilizes two (2) alligator clip connec-
tors, to attach to the TRl-B6M. (P/N 110-694927)
The TRI-B6 Series has five leads, one for grounding,
which are wired to the system with user supplied
wire nuts.
I
I
I
I
I
I
I
CATALOG NUMBER 6170
The TRI-B6M is fully compatible on the same MXL
circuit with all intelligent IL and ID-60 Series detectors,
MSI Series addressable manual stations or any other
addressable intelligent modules, such as the CZM or
ICR The TRI-B6M is also fully compatible on the IXL
(ICon) circuit with all intelligent IL and ID-60 detectors
and MSI manual stations.
AIITRI-B6M intelligent interface modules are UL and ULC
listed.
Environmental operating conditions for alITRI-B6M mod-
ules are 32°F (°C) to 120°F (49°C) with a relative humidity
of not greater than 93% non-condensating.
Engineer & Architect Specifications
The addressable interface module shall incorporate a
custom microprocessor based integrated circuit that
shall provide communication with its compatible
control panel.
The addressable interface module shall be a Fire Safety
TRI-136M that shall be compatible with a IXL or MXL
control panel.
TheTRI-B6M intelligent interface modules shall provide
the means of interfacing direct shorting devices to the
control panel's addressable circuits. The interface
module shall report the contact's status to the control
panel.
The TRI Series devices shall be capable of and listed for
interfacing normally closed security switches to the
MXL (per UL 1076).
The addressable interface module shall be UL and ULC
listed.
The addressable interface module shall be dynamically
supervised and uniquely identifiable by the control
panel.
The addressable interface module's address shall be
programmed with the use of a portable programming
accessory. The programming accessory shall be a Fire
Safety FPl-32 Programmer/Tester. The portable program-
mer shall be menu driven. Once the desired address is
entered the programmer shall set and verify the address.
The programming accessory shall also be capable of
testing the interface's functionality. The addressable
interface module's address shall be set by electronic
means only. No mechanical means such as programming
pins, DIP switches or rotary dials shall be required.
TheTRl-B6M shall be compatible on the same MXL circuit
with other intelligent IL and ID-60 Series detectors,TRI
Series addressable interfaces, MSI Series addressable
manual stations or any other MXL addressable intelligent
module. ThelRl-B6M shall be compatible on the same
IXL (ICon) circuit as other intelligent IL and ID-60 Series
detectors, MSI Series manual stations andTRI Series
interfaces.
Ordering Information
Model Description
Shipping Wt.
oz. Kg.
TRl86M Single Input 3.5 .1
TRI-86M-C ULC Model for Canada 3.5 .1
Typical Wiring
(Refer to Figures 1, 2, 3 or 4) Refer to the appropriate
wiring diagram below and wire the addressable inter-
face module accordingly.
Note: Recommended wire size:
18AWG minimum
14 AWG maximum
I
I
Installing A Security Point
I WARNING: These circuits intended for 24 hour
alarm monitoring only.
UL 1076 requires a TSW-1 tamper switch as well as a
TSP-40 printer. A COMMUNICATION FAILURE with a
TRI device configured for SECURITY results in a SECU-
RITY ALARM as well as a communication trouble.
When installing aTRI device in the CSG-M, be sure to
set the device usage to security. When setting the
device address using the FPl-32, select the normally
closed alarm causing input.
Connect only one switch perTRl input.
Reminder: Proper installation procedure for TRI Devices
As part of the normal installation practice each TRI
device must be functionally tested. This includes
testing the supervision through the end of the line
resistor. The following steps must be followed for each
TRI device installed:
Open the end of line resistor.
Check that the system annunciates the programmed
trouble message.
3, Return the resistor to its proper connection.
Change the state of the switch to confirm that the
system's programmed response is executed.
Return the switch to its normal state.
I
I
E
Mounting Diagram
two
- - - - -
9 L TRI-136M
SINGLE GANG
SWITCHPLATE (BLANK)
(USER SUPPLIED)
I
I
I
I
I
I
I
NOTE: DO NOT USE
REAR CONDUIT ENTRY
LSINGLE GANG
SWITCHBOX
(USER SUPPLIED)
I
I
1
I
I
I
NOTICE: The use of other than Fire Safety detectors and buses with Fire Safety equipment will be considered a misapplication of Fire Safety
equipment and as such void all warranties either expressed or implied with regard to loss, damage, liabilities and/or service problems.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
Florham Park, NJ 07932 12/03 Brampton, Ontario
Tel: (973) 593-2600 Siemens Building Technologies 10M Canada L6T 5E4
FAX: (973) 593-6670 SFSG Tel: (905) 799-9937 December 2003 Fire Safety Website: www.sbt.siemens.comlfis Printed in U.S.A. FAX: (905) 799-9858 Sopercedes sheet dated 12/01
(ZR 'g
ZH Series ZR Series Mountun
Catalog Sheet SIEMENS Fire Safety & Security Products
'08 Series Notification Appliances
ZH & ZR - Strobes, Horns, & Horn I Strobes Application: Indoor
Product Overview
- Strobes can be synchronized using the Siemens DSC sync modules, FS-250 panel,
XLS panel, or PAD-3 power supply with built-in sync protocol
- Selectable Continuous Horn or Temporal (Code-3) Tones with 90 or 95 dBA selectable setting (ZH)
- Ceiling-mount models feature field-selectable Candela settings of 1513017519 5cd and 1151177cd
- Wall-mount models feature field-selectable Candela settings of 15/30/75/110cd and 1351185cd
- Base plate is protected by a disposable cover, and the appliances can quickly snap
onto the base after the walls are painted
- Strobes produce 1 flash per second . .
- "Special Applications" listed with Siemens panels. .. .
-, EZ Mount Universal Mounting Plate (ZBB) - uses single plate for ceiling and wall mount installations
- EZ Mount design - with separate base plate - provides ability to pre-wire the base
and test the circuit wiring before the walls are covered
- ®UL Listed & ®ULC Listed;
FM, CSFM & NYMEA Approved
- ADA! NFPA compliant
Specifications
General
- AudiblelVisual notification appliances shall be listed for indoor use only
- Appliances shall be listed under ®UL Standard 1971 (Standard for Safety Signaling Devices
for Hearing Impaired) and ®UL Standard 464 (Fire Protective Signaling)
- Appliances shall use a universal back plate, which shall allow mounting to a
single-gang, double-gang, 4-inch-square, 4"-octal, or a 3-1/2"-octal backbox
- Two-wire appliance wiring shall be capable of directly connecting to the mounting back plate
- Continuity check shall occur for entire NAC circuit prior to attaching
any audible I visual-notification appliances
- Dust cover shall fit and protect the mounting plate
- Dust cover shall be easily removed when the appliance is installed over the back plate
- Removal of an appliance shall result ma trouble condition by the Fire Alarm Control Panel, (FACP)
'08 Series Notification Appliances 2584
SIEMENS Industry, Inc.
Building Technologies Division
Specifications - (continued)
Strobes
- Strobe appliances shall produce a minimum flash rate of 60 flashes per minute
(1 flash per second) over the Regulated Input Voltage Range, and shall incorporate a
Xenon flashtube enclosed in a rugged Lexan® lens
- Strobes shall be available with two or four field-selectable settings in one unit, and shall be
rated - per ®UL 1971 - for up to:
15/30175/110cd for wall mounted
1351185cd for wall mounted
1 5130175195cd for ceiling mounted
115/177cd for ceiling mounted
- Strobes shall operate over an extended temperature range of 32°F to 120°F (0°C to 490C), and be listed
for maximum humidity of 95% RH
- Strobe inputs shall be polarized for compatibility with standard reverse-polarity supervision of circuit
wiring by a Fire Alarm Control Panel (FACP)
Audibles and Audible! Strobe Combinations
- Horns and horn I strobes shall be listed for Indoor use under ®UL Standard 464
- Horns shall be able to produce continuous synchronized output or a
temporal code-3 synchronized output
- Horns shall have at least 2 sound-level settings of 90 and 95 dBA
Synchronization Modules
- The strobe portion, when synchronization is required, shall be compatible with
DSC sync modules, FS-250 panel, XLS panel, or PAD-3 power supply with built-in sync protocol
- The strobes shall not drift out of synchronization at any time during operation
- Audibles and strobes shall be able to synchronize on a 2-wire circuit with the capability
to silence the audible, if required
- Strobes shall revert to a non-synchronized flash-rate, if the sync module or
Power Supply should fail to operate (i.e. - contacts remain closed)
- All notification appliances shall be listed for Special Applications:
Strobes are designed to flash at 1-flash-per-second minimum over their
"Regulated Input Voltage Range"
' Note: NFPA-72 specifies a flash rate of 1-to-2 flashes per second, and ADA Guidelines
specify a flash rate of 1-to-3 flashes per second
All candela ratings represent minimum-effective Strobe intensity, based on ®UL Standard 1971
Series ZH Strobe products are listed under ®UL Standards 1971 and 464 for indoor use
with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%)
Series ZH horns are listed under ®UL Standard 464 for audible signal appliances (Indoor use only)
SIEMENS Industry, Inc.
Building Technologies Division
I
I Mounting Diagram
I
1 a - - zm- -
EWA
(Shown In Inches)
Mounting Options
SECURING kk SCREWS
Fip.as3: tt.rion Fiaae4: Rsnve1 (See t€o B ti;-2znj
I. Instal mounbtg ptate as shown in igure I to a single-gang, Impoitant: Device cs.y has one mcwthng orientatco. Ma:th the
double-gang, 4 square. 4' octagon, or a 3 " octagon bactbcx top cf the base-to the top of the device.
with the provfded pan head s:rews. To remove dwst cover, If it is desired to furtherse.ure the device to the base, then two
place thtrmib and index finger on top edges of cover and pull oft optional screws are provided. To install these screws punch cut
cover, the screw holes located a: the top and bottom of the device.
Canned field wiring per figures 2 and 3 S. To remove the appliance, push a small f)at-bladed screwdnver
Addresvires back into backboL into the side opening. The screwdiwer must clear the snap
Place dust cover over mounting ptole to protect the tewninas release opening by % to disengage the snap. Do not prg off
while perforatng wiring ccnlinuiy deck. housing with the screw driver. Apply pwssure with screw driver,
Remove dust cover before snapçdtg or installing the aplrarce inserted in either side opening, as shown in, Fig 4 to reease the
onto the mounting pfae per fig 3. housing.
Technical Data
ZH and ZH-MC Hcwn
Rev.rbrant dBA
PJ ®L1L464 ZH Horn Current Draw
[ZH-MC and ZH at 24V] HOM 16-33 Volts (All?ps)
16.OV 24V 33.OV High 0.044 DC Lowa 0.018 Continuous High 83 87 90
Horn FWR 0.075 ________ Low' 0.045
Low 77 81 83
Code3Hornor High ig -ici n-s oi
March Time
*entwi5 the sarnefor the Conlinut
140m. Code .3 Etotn and March Tine Seth Low 1 72 1 76 79
*Available in sync mode only
SIEMENS Industry, Inc.
Building Technologies Division
I
I
I
I
I
I
I
I
I
I
I
I
Ii
I
I
I
Technical Data - (continued)
Models*
€UL Listed Models and Ratings
Operating Voltage
(Special Application)
[Per ®UL1971]
(VDCNRMS)
Voltage Range r
' 526-021
per@
(VDCNRMS)
Horn
-
Mounting
Strobe
Candela
(C)
ZRMC 16.0-33.0 20.0-31.0 - Wall 15/30175/110
ZR-HMC 16.0-33.0 20.0-31.0 - Wall 1351185
ZR-MC-C 16.0-33.0 20.0-31.0 - Ceiling 15/30f75195
ZR-HMC-C 16.0-33.0 20.0-31.0 - Ceiling 1151177
ZH-MC 16.0-33.0 20.0-31.0 X Wall 15130i751110
ZH-HMC 16.0-33.0 20.0-31.0 X Wall 1351185
ZH-MC-C 16.0-33.0 20.0-31.0 X Ceiling 15/30175/95
ZH-HMC-C 16.0-33.0 20.0-31.0 X Ceding 115/171
ZH 16.0-33.0 20.0-31.0 X Wall or Ceiling - -
0AvabIe in red and white
DC 16-33VDC
FV 18-33VRM
® UL Current Ratings (ZR Strobe Only)
Maximum RMS CurrentjAMPS)
MC H (MC-C l-IMC-C
15cd I 30cd I 75cd 1110cdl 135cd 185cd 15cd 30cd I 75cd I 95cd 715cd 177cd
0.064 JU98 10.17510-233 0.318 1 0.445 0.069 0.111 10.20D 0.264 0.318 0445
0.105 0.164 0.268 0368 11482 0.684 0.117 0.160 0.297 0.398 0.482 0.684
Horn
Setting
® UL Current Rat/n gZH Horn/Strobe
Maximum tRMS Current (AMPS)
MC I-IMC (MC-C i-IMC-C
15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95 c 1115cd 177cd
DC I
-
16 33VDC 78 0.113 0.195 0.259 0.371 0.506 0.087 0.131 0222 0.292 0.371 0.506
70 0.107 0.188 0.246 0.324 0.455 0.075 0.121 0.213 0 277 0.324 0.4
FW E imoo-cl,
41 0200 0.302 0.406 0.521 0 722 0.149 0.216 0.331 0.436 0.521 0.722 16-33Vl 23 0.179 0.290 0.391 0.497 0.699 0.131 0.195 0.319 0.421 0.497 0.699
gent uraw is me same tor me conunuous riom; Code 3 Horn and March Time Settings
Details for Ordering - (Including Mounting Options & Agency Approvals) I
Agency Approvals
Model
Number
Part
Number Description Mounting
Options* UL
-
ULC
-
FM
-
CSFM
-
ZH-R 500-636159 ZHorn: Red B,D,E,F X X X X
ZH-W 500-636160 ZHorn: White B,D,E,F X X X X
ZH-MC-R 500-636161 Z Horn: Multi Candela (Wall), Red B,D,E,F X X X X
ZH-MC-W 500-636162 Z Horn: Multi Candela (Wall), White B,D,E,F X X X X
ZH-HMC-R 500-636163 Z Horn: Hi Multi Candela (Wall), Red B,D,E,F X X X X
ZH-HMC-W 500-636164 ZHorn: Hi Multi Candela (Wall), White B,D,E,F X X X X
I ZH-MC-CR 500-636165 Z Horn: Multi Candela (Ceiling), Red B,D,E,F X X X X
ZH-MC-CW 500-636166 ZHorn: Multi Candela (Ceiling), White B,D,E,F X X X X
ZH-HMC-CR 500-636167 Z Horn: Hi Multi Candela (Ceiling), Red B,D,E,F X X X X
ZH-HMC-CW 500-636168 Z Horn: Hi Multi Candela (Ceiling), White B,D,E,F X X X X
ZR-MC-R 500-636169 Z Strobe: Multi Candela (Wall), Red B,D,E,F X X X X
ZR-MC-W 500-636170 ZStrobe: Multi Candela (Wall), White B,D,E,F X X X X
ZR-HMC-R 500-636171 Z Strobe: Hi Multi-Candela (Wall), Red B,D,E,F X X X X
ZR-HMC-W 500-636172 Z Strobe: Hi Multi-Candela (Wall), White B,D,E,F X X X X
IZR-MC-CR 500-636173 Z Strobe: Multi Candela (Ceiling), Red B,D,E,F X X X X
ZR-MC-CW 500-636174 Z Strobe: Multi Candela (Ceiling), White B,D,E,F X X X X
ZR-HMC-CR 500-636175 Z Strobe: Hi Multi Candela (Ceiling), Red B,D,E,F X X X X
ZRS-HMC-CW 500-636176 Z Strobe: Hi Multi Candela (Ceiling), White B,D,E,F X X X X
ZBB-R 500-636193 Accessory - (lncludes base, dust cover, mounting screws and installation sheet)
ZBB-W 500-636194 Accessory - (lncludes base, dust cover, mounting screws and installation sheet)
X listed! approved * Refer to catalog sheet #: 2585 for detailed mounting options
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
cirMrdc Indiictru mr Florham Park NJ 07932 Rrmntnn Ontario
Building Technologies Division (9 December 2009
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 7/07
URL: www.SBTSiemens.com/FIS FAX: (905) 799-9858
TI
I
I
I
I
I
I
SIEMENS Catalog Sheet I
Fire Safety & Security Products
'08 Series Notification Appliances
Mounting Options
Mounting Diagrams I Mounting Matrixes I Mounting Notes
ARCHITECT AND ENGINEER SPECIFICATIONS
(A) UNIVERSAL MOUNTING PLATE 4" SQUARE, DEEP, FLUSH (60) (I) WPBBS
• ORDER CODE— RED: 500-636137
0 o o (1 () i'tasliebackbox for surface mxrthrg
AS series westherprooi.outdoor products.
mc
o
244
Used w1h Series Used with Series iI. AS
Used wth Series
AS,6.B1QHS,M9:DC.MH115. huH.
AS (weatherproof)
(B) SINGLE-GANG,
FLUSH (60)
(C) SINGLE-GANG,
SURFACE (BC) (J) BBS BACKBOX NH. NS,SETSF, SETULC,ST,Zii.ZR ORDER CODE— RED: 500-636110
Standard steel backbox with knockouts
DOUBLE-GANG, FLUSH (BO) for interior surface reounting, eonceaed con dcsitmouoig orsemi-fiush
sppc-atons.
000,
*1
>
HOLES 0.0
0
Deep PRO'4tOEDWlT3i KNOCKOUTS
FOR W C t5' COiOOiC5.
Used with Series Used with Series Used with Sertes Used with Series
AH, AS.B, AH, AS, MI'& NH, US. ST2t4,2R MH AH,AS. HSMTH.NI-I.ST,2H.ZA MHilATH-id-115, NI-t,ST
(D) 4i1 SQUARE, FLUSH (BC) DOUBLE-GANG, SURFACE (BC) (K) WBBS WEATHER RESISTANT BACKBOX
ORDER CODES— RED: 500636129
WHITE: 500-636131
-'. Sturdy die cast housing, threaded conduit hole and
C) ,,__•
and knockout for outdoor applaticws.
L
Deep 44
P
Used with Series wCcio
AH, AS, B6.B1OKS. MBDC,hlHllfi, MTH Used wth Series Used with Series
NH, NS.SETSE SET-ULC. ST, ZHZR AH, AS, NH. NS, ST AH,88,610,MBDC,141-1115MTH-15-15 S:EfiF
'08 Series Notification Appliances . 2 5 8 5
SIEMENS Industry, Inc.
Building Technologies Division
I
I
I
I
I
I
I
1
I
I
I
1
I
I
I
I
I
I
I
(L) ISPS2 SURFACE ADAPTER (P) SBBS BACKBOX (1) WPSBBS
ORDER CODES- WHITE: 500-636195 ORDER CODES— RED: 500-636119, ORDER CODES— RED: 500-636139,
RED: 500-636196 WHITE: 500-636120 WHITE: 500-636140
t4 S0 For surface mounting speakers,
chimes, and eIecronta applications.
1rir - r-'" -1 I•- 3-ME•'--•1
4
lap-
Pill
5-5115." 3i6 4 2 S OEI _AC. S OS?
with Series Used s Used wfTh Series Used with Series
HS
Ce
.PTrI, B6. SW. CH. SEF. SET. SETFL ST-VP
HS. M9C,Mi1{, NH NS, ST
(M) FTT-SUR-BOX BACKBOX (Q) 4" SQUARE DEEP W/ EXTENSION (U) 5" SQUARE BACKBOX WI
ORDER CODES- RED: 500-693168 RING, FLUSH (BO) EXTENSION RING? FLUSH (80)
WHITE: 500-636118
-Ifa 30,1
1'1O[lh1_r Used with Series
CK.StSEF.SETFL,SET
(R) SFPS SEMI-FLUSH PLATE
Used
FT UI 0
wjith Series
HS, SET ORDER CODES- RED: 500-636124, Used with Series
(UTH, hlTW: For surface mounting on MT products.) WHITE: 500-636125 CftSE,SEF. SET
Stamped alucnium surface wal ptate. (N) DBBS BACKBOX whioh mcsrnts betsind the basic una, (V) SSB-4 CEILING SUPPORT BRIDGE
ORDER CODE - RED: 500-636111 and rvesrccever recessed backboxes
in arm-tiush mounsng appbcaiicns. -
0
Standard steel back box prcw th ded w knocous
for interior surface mounting, concealed conduit
mo?.rnting or semi-flush applications.
-
-
'00 f[
0 HOLES
HOLES
} TAP
Oo I Used with Series
MI, SET, SE, NH, MS, ST Provisions for (4) J-nuts #8-32 lb 3-si?
?ROVioEOWirAseOoKOUTa—' FOR ?4'.cOOUn5.
Square Matetiaf: Steel
Used with Series {S} APS ADAPTER PLATE
Used with Series ORDER CODE - RED: 500-636109 St A.' 1, AS, 86, SW, HS, MBDC,
MH115, MTH, NH, SETSF, ST Stamped aluminum adapter plaze designed for (X) SHBBS applications whee aerni-8ush installations cannot
or round backboxes s~ngle or double gang
SQUARE, SURFACE BACKBOX
ORDERCODES - RED 500 636126, (0) RETROFIT PLATE C,agon
ORDERCODES - [PENDING) boxes or plaster rings. The, bacbx and basic unit WHITE: 500-636127
are then fastened to the plate. This type of mounting
is referred to -as'ccnceeled conduit installation.'
Site..
4 ___ _ I a-jlE" Ii_I_
_ __
I —--i 1
(4)___________
HOLES Doe,
Cm a C3
Used withSeries Used with Series Used with Series
86, 8W,MBOC,MTH NH, SE 88, 810,MSDC AV, AS, NH, ST
SIEMENS Industry, Inc.
Building Technologies Division
(Y) SERS SQUARE SEMI-FLUSH (BB) SPSSB (EE) SPEXT EXTENSION RING
EXTENSION RING ORDER CODES- RED: 500-636114, ORDER CODES- RED: 500-636116,
ORDER CODES- RED: 500-636122
WHITE: 500-636123
WHITE: 600-636115 WHITE,* 50G-636117
l_ F
i
TOP
tT
/
r
oz _
73251 13 D'S0.644
Used with Series _ Used with Series
SE I e) CH, SE, SEF, SET (wall mount Used with Se~s
SMC-CciIin Mount Strobe) Z) SBL2S BACKBOX (CC) SB-W 6" CEILING SUPPORT BRIDGE
(FF) ZBB ORDERCODE- RED: 500-636121 ORDERCODE - WHITE: 500-634682
I-is4,. r - _ - - - ________ 237u •'YP Sri
ORDER CODES - RED: 500-636193.
WHITE: 500-636194
—L8U"--
I
lk 03
J0
*1
_1I
ri I- 1 PORWO ThPAD
e.So , ex8-•32
Used with Series Used with Sèiies with3ei1es
S__8 Ceiling Speakers z_____________________
(AA) SPSB (DD)!j.G PHR (GG) WFPS PLATE (HH) WFPAS PLATE
ORDER CODES- RED: 500-636112,
OX
WHITE: 50636113
ORDER CODE
11
- -
ORDERCODES -
RED: 500-636135.
WHITE: 500-636136
13
ORDER CODES -
RED: 500-363133.
WHITE: 500-656134
1-7
TOP 1r'
113
L___ 1l I V1 f I
Used with Series Used withSeries Used with Series
MI HAiP. .
Used with Senes
AS-WP SE (.Speakers) S 8' Ceiling Speakers
I
I
I
I
I
SIEMENS Industry, Inc.
Building Technologies Division
1
I
I
I
I
F7
I
I
I
I
I
I
1
NJ (I t U V V V - U' > U' . U' NJ NJ - - C
-
CD
-
_•-
>C CD -n NJ DC DC C CD CD - CJ NJ - )< X w -
0
- o - C j CD CD CD >( DC C.Jr NJ 0
0 - O .- -o o -v - - DCgO 0 CD CD C
m to
C
cu () m Ln m CD
o -
CD
-
DC
-
DC
Ow .
CD
(0 Ln
a —
C')
2.
0• 0 -. CCC
CD
(A > Q C
- 0
0
0
CD
>< >< > '<
- - -
Series SET-C
>< >< >< >< >< >< >< )< X > > >< Series ST
>( >< > > Series ST-MC-RETRO
>< >< < > > X x Series MHII5
>< >< > Series SE
< > > I ><
-
>< >< >< >< > >
- - -
Series BI0-115
>< x >< X >< >< Series CH
> > >< >< x > Series SETSF-B
>< > >< Series SETSF
> >< >< x >< < > )< >< >
- -
Series MBDC
>< Series S-HQ
'< >< > x >
- - Series SET/SET wall Mount
> > >< Series SE-C
>< ><
-
ISeries
Series MH
>< >< >< >< >( >< x Series MTH
> >< >< > >< >< > >< NS/NH
>< x x x > >< I Series HS
><I >< > < >< x l x >< > SeriesAS/AH
w
ASeries
Series AH-WB(3), MT-WP(4), MTH
>< >< >< Z - - - - - - - - - - - - - - - -
I
I Mounting Matrix (by Model Number)
'I II IIh1 I
Urrw I! .r•i' 'pr _____________
ii
ii
EIihi rj
'
I
'! inhi
rII!IU ,Ip ri
iliuiEkiihI iIiIiII1II h .rrrr' .rr'!! r:I1IIII•I'• ________ ihu
oi l ,hiIhiII1111
,
11
ii I .111
iiI Ihili
:
• F
u uIii
______________________ iv!uI!Iur!!! U!!IIuI 11111 I I I i
...........
I I!iP
iiih IiiFIilil I uu i
IIiIIIiIik •iiiiflIhiIIII iIhIii
ci
Nil ! I' I b
IIIIi
tP!uII!
IriIIb
SIEMENS Industry, Inc.
Building Technologies Division
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Mounting Notes
Caution: The mounting options figures
show the maximum number of field wires
(conductors) that can enter the back box
used with each mounting option.
If these limits are exceeded, there may be
insufficient space in the back box to
accommodate the field wires
and stresses from the wires could damage
the product.
Although the limits shown for each
mounting option comply with the National
Electrical code (NEC), Siemens
recommends use of the largest back box
option and the use of approved field wires
whenever possible to provide additional
wiring room for easy installation and
minimum stress on the product from
wiring.
Caution: Check that the installed product
will have sufficient clearance and wiring
room prior to installing back-boxes and
conduit, especially if sheathed multi-
conductor cable or 3/4" conduit fittings are
used.
Mounting hardware for each
mounting option is supplied.
Conduit entrances to the back box
should be selected to provide
sufficient wiring clearance for the
installed product.
When extension rings are required,
conduit should enter through the
back box, not the extension ring.
Use Steel City #53151 (1-1/2" deep)
or #53171 (2-1/8" deep) extension
rings (as noted in the mounting
options) or equal with the same cut-
out area.
When terminating field wires, do not
use more lead length than required.
Excess lead length could result in
insufficient wiring space for the
appliance.
SIEMENS Industry, Inc.
Building Technologies Division
Use care and proper techniques to
position the field wires in the back box
so that they use minimum space and
produce minimum stress on the
product. This is especially important
for stiff, heavy gauge wires and wires
with thick insulation or sheathing.
Do not pass additional wires (used for
other than the appliance) through the
back box "unless the back box is of a
sufficient size to permit additional
wiring as described in NEC 314.16 (B)".
Such additional wires could result in
insufficient wiring space for the
appliance.
Note: Due to continuous development of our
products, specifications and offerings are subject
to change without notice, in accordance with
Siemens Industry, Inc. standard terms and
conditions.
Back Box Mounting
Siemens Wall-Mounted, Horizontal Strobe
Appliances NFPA-72 (2007)
7.5.4.1 * —Wall-mounted appliances shall be
mounted such that the entire lens is not less
than 2030 mm (80 in.) and not greater than
2440 mm (96 in.) above the finished floor or at
the mounting height specified using the
performance-based alternative 7.5.4.5
7.5.4.2 - Where low ceiling heights do not
permit mounting at a minimum of 2030 mm
(80 in.), visible appliances shall be mounted
within 150 mm (6 in.) of the ceiling. The room
size covered by a strobe of a given value shall
be reduced by twice the difference between
the minimum mounting height of 2030 mm
(80 in.) and the actual, lower mounting height.
I
I
Back box
Mounting Options*
Series
ASIAH
Audible
Strobe
Series ST-MC-RETRO
(Flush and Surface
Retrofit Plate)
Horn
Series NS
Strobe
Series Z and ST
Strobe
Series MTH
Multi-tone
-
801N.
-
61N.
____
801N.
____
61N.
_____
801N. 61N. 801N.
____
61N. 801N. 61N.
(B) 1-Gang x 2" Deep - Flush (80) 77'/f 81/f 78 I8 7 Is" 79 'Ia" 6 'Is"
(D)4"x4"x 1.5' Deep- Flush (BO) 77" 9" 83 15/16" 77 7/ '18 78 I8" 7 Is" 79 15/" 6 1116 6 '16
(E) 4" x 4" x 2.125" Deep - Flush (80) 77" 9" 83 '/l6" 77 'Is" 8 '/" 78 Is" 7 i/s" 79 /16" 6 1116 6 1116
(F) 2-Gang x 3.5" Deep - Flush (BO) 77 112' 81/f 78 3/8" 7 Is" 79 1/8" 6 7/8 80 5 71,s" 5 116
(G) 2-Gang x 1.75" Deep - Surface (80) 77 '/2' 81/2' 78 /8" 7 Is" 79 'Is" 6 /8" 80 116 5 "isV 5 71,6
(M) MT-SUR-BOX Surface & Weatherproof (SP)
- 79 3/s" 6 s/s" 6 5/8"
(P) SBBS Surface (SP) 79 1/4 6 3/4" 6 3/4"
(U) 5" Square Back box w/ Extension Ring, Flush (80) 591/f 81/f 83 71je 77 3/81, 7 5/8" 78 'Ia" 6 /8" 79 'us" 5 116 5 9i
(X) SHBBS (SP) Shallow Surface 76 i/f 9 1/f 7 7 3/s" 8 5/8" 78 1/8 7 '/a"
(Z)SBL2S Surface (SP)
- -
78"
(FF) ZBB 78 '/8" 7 '/"
More Back box Series CH Series SET-V Series SEF-C Series SET-C
Chime Strobe Speaker Strobe Speaker Strobe Speaker Strobe
Mounting options* 80 IN. 6 IN. 80 IN. 6 IN. 80 IN. 6 IN. 80 IN. 6 IN.
SBB Surface (SP) 77-3/4" 8-1/4" 79-3/16" 6-13/16' 77-3/4" 8-1/4" 77-3/4" 8-1/4"
4" x 4" x 2.125" Box wl 1.5 77-1/2' 7-1/2" 80 6" 78-1/2" 7-1/2" 78-1/2" 7-1/2"
Extension Flush _Ring _-_ _(BO)
(U) 5" Square Back box with 78" 7" 79-1/2" 5-1/2" 78' 7" 78" 7"
_Ring _- Extension Flush (BO)
SHBB (SP) Shallow Surface ________
4"x 4"x 1.5" Box wl 1.5" 78-1/2' 7-1/2" 80" 6"
Extension-Ring Plate - Flush (BO) 1 1
* Measured from Bottom of Back box
Notes: (BO) = By Others (SP) = Siemens Product
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Notice: This marketing catalog sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product's installation instructions.
Fire Safety Fire Safety
8 Fernwood Road 2 Kenview Boulevard
SIEMENS Industry, Inc. Florham Park, NJ 07932 Brampton, Ontario
Building Technologies Division Tel: (973) 593-2600 IsHI L6T 5E4 / Canada December 2009
FAX: (908) 547-6877 Printed in U.S.A. Tel: (905) 799-9937 hct dated 7/07
URL: www.SBT.Siemens.com/FIS FAX: (905) 799-9858
- Fig. 1 MODEL 302
For interior mounting in any
JJ atmosphere that is compat-
ible with terminal screw type
connections.
I
I
I
I
I
I
I
I
I
I,
I
1
I
I
I
I
I
I
I
Four BasicModels
MODEL DESCRIPTION REFER TO:
302-135 135°F - Interior Vertical Mounting FM &UL F 1 Fig. 302-194 194°F - Interior Vertical Mounting FM & UL
-l35 135°F - All Weather Vertical Mounting FM & UL F 2 Fig. 302-ET-194 194°F - All Weather Vertical Mounting FM & UL
302-AW-1 35 135°F - All Weather Vertical Mounting FM & UL Fig. 3 302AW-194 194°F - All Weather Vertical Mounting FM & UL
302-EPM-135 135°F- Explosion Proof Mounting UL Fig.4 302-EPM-194 194°F - Explosion Proof Mounting UL
Decorative white plastic adapter plate for mounting 302, 302Ff Fig. 5 g. and 302AW to any 3" outlet box or 4" octagon outlet box.
Fig. 2 MODEL 302-El
Hermetically sealed for moisture proof or,
dust proof installations. Requires no
special back box. Has plastic hexago-
threads for attachment to
threaded hub cover, or any
nal grip bushing with 1/2" conduit
outlet box. Must be hand
• Fig. 3 MODEL 302-AW
I
Hermetically sealed for moisture proof or dust
proof installations. Requires no special back tightened only. For
- box. For indoor and outdoor use. Protect from indoor and outdoor direct sunlight and adverse weather conditions. A use. Protect from
direct sunlight
and adverse
weather
& V
Fig 4 MODEL 302-EPM
; Explosion proof for installation in hazardous locations. Has
hexagonal grip bushing with 1/2' conduit threads for attach-
ment to threaded hub cover of series JL fixture fitting as manu-
factured by Killark Electric Co., or equal. Must be hand tightened
only. For Interior use.
General
Each model is a normally open device designed especially for fire
detection and alarm systems. These rate compensation type detectors
are available in either 1350 F. or 1940 F. ratings. All four basic models
are self restoring, hermetically sealed, shock and corrosion resistant,
and are tamper proof. Refer to NFPA STANDARD 72, STANDARD FOR
AUTOMATIC FIRE DETECTORS for application requirements, testing
and maintenance.
Principal of Operation
All models operate on the principles of a rate compensation detec-
tor. The detector consists of a high expansion aluminum tube which
encases two insulation struts with opposing open constant points (see
cut-away view). The high expansion sensing shell and the expan-
sion struts have a different coefficient of expansion. A slow rate of
temperature rise allows the heat to penetrate the inner expansion
struts. Therefore, the tubular shell and the struts expand slowly until
the total device has been heated to its rated temperature level of 135°
F/i 94°F. At this point, the silver contact points close which initiates
the alarm. When subjected to a rapid rate temperature rise there
is not as much time for heat to penetrate the inner strut. The rapid
lengthening of the shell allows the struts to come together at a lower
level which compensates for thermal lag inherent in conventional
fixed temperature detectors. When the surrounding air temperatures
goes below the rated temperature level, the shell contracts which
forces contacts to open, thus automatically resetting the detector.
(actual size)
liver contact points
sion struts
xpansion sensing
040 anodized
;ontrol sleeve
g screw
hermetic seal
Dimensions (Model 302): Total overall length 4 1/8
Special Considerations Base Diameter: Z.
Temp. Rating OF Max Ceiling Temp. °E
135 115
194 155 Approvals/Listings
Detectors are not directionally effected, can be mounted horizontally
Signaling
or vertically. Detectors have a smooth ceiling UL rating of 50' x 50' Underwriters' Laboratories
(2500 sq. ft.) on 8 to 10 ft. ceilings. Detectors, hub covers, or outlet Listed
boxes must never be installed in direct sunlight. Refer to NFPA STAN-
DARD 72 for spacing and other considerations. For further information ______ Factory Mutual
refer to www.thermotechheatdetectors.com Ap(0V•d
Electrical Rating California State Fire Marshall. Listing No. 7270-0021:001
Voltage Current
MEA Acceptance # 193-03-E
6-125 VAC 5 amps
6-25 VAC 1 amp
125 VDC 0.5 amp
'I
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. k7 650067 0144, Page 1 of 1
CATEGORY: 7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: Siemens Industry, Inc. Building Technologies Division, 8 Fernwood Road, Florham Park, NJ 07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
I Email: Peter.pawchak@siemens.com
DESIGN: ModeiMXL and MXL-IQ fire alarm control units. Coded or noncoded; local, auxiliary,
I
remote and central station proprietary service; automatic, manual waterflow, releasing
service and sprinkler supervisory service when used as a remote station (protected
premise) unit or proprietary fire receiving unit. Refer to listee's data sheet for additional.
detailed product description and operational considerations. Basic components:
(MM-11, -21,31VSMB-12, -22, -32 Main Control Board
I MKB)-1 1, 214, -51, -62 Keyboard/Annunciator Panel
MPS6-12Power Supply
CRM Relay Module
CSM-4 Signal Module
I CZM-4 Conventional Zone Module
BTX-1, BP-61 Battery Set Module
MSE-21, -32, -3M2 Enclosure
MSE-3M-D Enclosure Door I iléntKni6ht51285129 Dialer/DACT (Listing No. 7300-0559:120)
1 - For use with Model MXL only.
2 - For use with Model MXL-IQ only.
I RATING:
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
I MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as fire alarm control units for use with listee's listed Model VoiceCom system (CSFM
Listing No. 6911-0067:173) and separately listed compatible initiating and indicating I devices. See (CSFM Listing No. 7300-0067:172) for optional control unit accessories. *Also
suitable for high-rise applications. Refer to listee's Installation Instructions Manual for
details.
I These control units can generate the distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal as required per NFPA 72, 2002 Edition.
This control unit meets the requirements of UL-864, *9th Edition Standard
NOTE: For Fire Alarm Verification Feature (Delay of fire alarm), the maximum
I Retard/Reset/Restart period must be adjusted to 30 seconds or less.
Combined with 7170-0067:154
I *Rev. 06-23-2009 fm
I This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
\ the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
I ' requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
I
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7007017 Page 1 of 3
CATEGORY: 7300 - MISC. DEVICE/CONTROL UNIT ACCESSORIES
LISTEE: Siemens Industry, Inc. Building Technologies Division, 8 Fernwood Road, Florham Park, NJ 07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
I
I
I
I
I
DESIGN: Control Unit Accessories. Refer to listee's data sheet for additional detailed product
description and operational considerations. Accessories are listed as follows:
MODELS DESCRIPTION
ICP-86 Intelligent Control Point Module
CZM-1, -1 B6 Remote Conventional Zone Module
FS-CZM Conventional Zone Module
ALD-2/ALD-21 Analog Loop Driver Module
TSP-40, TSP-40A Logging Printer
PSR-1 Remote Power Supply
MOI-1/M0I-7 Voice/Annunciator Drive
MOD-16 Output Driver
NET-4/NET-7/NET-7M Communication Interface
MOM-4/MOM-2 Module Card Cage
TSW-1 Tamper Switch
CMI-300 Modem Interface Module
PIM-i Printer Interface Module
PAL-1 Printer
CP-2297/CP-2341 Line Suppressor
XL Graphic Software
MXL-G Graphic Interface
PS-5A/-35, -5N/-5N7 Power Supply/Network Node
LIM-1 Loop Isolator Module
DC-355 Voltage Regulator Module
CSG-M Compare Program
MMM-i Coil Cord Microphone
TMM-i Master Telephone Handset
TBM-1/TBM-2 Terminal Block Module
EL-410C/410D Signaling Amplifier
VSM-i Visual Switch Module
OMM-1/OMM-2 Output Master Module
OCC-1/OCC-2 Output Control Card
ASC-1/ASC-2 Supervisory Module
BTC-i Backup Tone Card
ACM-1 Audio Control Module
CCU/M Pager Interface
RDM-PC, -MXL Diagnostic Interface Modules
I
I
I
I
I
I
I
I
I
I *Rev. 05-04-09 bh
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed !\ the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
I
I
I
I
TSM-1 Test Switch Module
ZCx-8B-XX/ZCx-4Abxx Control Card Modules
ZCT-8 Telephone Module
MBR-2fME-3/MLE-6 Enclosure Backbox
MDR-2 Enclosure Door
cMBR-MP/M BR-3MP Enclosure Plate Insert
MHD-X 'Enclosure Inner Door Panels
MDACT Multi-Pont Digital Communicator Transmitter
CAB1-COM, CAB1-X Enclosure
CAB2, CAB3 Expanded Enclosure
HUB-4 Communication Card Module
NCCNT-WAN Wide Area Network
VSB-1 Inner Door Blank
MKB-1 /-2/-3 Keypad/Annunciator Modules
MID-16 Input Module
NIM-1 RIREP-1 Network Interface/Repeater
NCC/NCC-G, -GL/NCC-T Computer
D2300CP, D2300CPS, D2325CPS Fiber Optic Repeater
BI-35 Power Supply Interface
BC-35 Battery Charger
AE-30U Class B Bell Circuit
BB-55 Battery Enclosure
ALI-8, ALI-813 Remote Phone Enclosure
MTE-2 Interface Enclosure
ZAC-30 Zone Amplifier Module
XLD-1 Analog Loop Driver
XED-1/-2 Back Box
XEA-1I-2 Adapter Plate
ACM-RKIMKB-RK/MMB/RK Rack Mount Kit
MOM-RK/MPS-RKITSP-RKNSM-RK Rack Mount Kit
VFM-1 Fan Control Module
MEM-1 Memory Expander Module
RCM-1 Distributed Audio Card
MSE-3U-3LR Enclosure Backbox
MET-3U-3LR Flush trim Kit
IQ-DFU-BLANK Dead Front Panel
VLM-1 Visual LED Module
PLC-4 Power Limited Module
DMC-1 Digital Message Card
NIM-1M Modem Assembly
NlM-1W Network Interface Module
NCCNT-G, -GL, -T Network Command Center
DFM, DFM-BRK DNet Fiber Module, Bracket
FJ-303, -304 Phone Accessories
HCP Intelligent Control Point Module
OD-LP, -BP, -GP, -BP-R, -GP-R Outer Door (Black or Red)
MOM2-XMP Mounting Plate for MOM2 Module
XMl MDACT Interface
I
I
I
I
I
I
k
I
I
I
I
I
I
I
I
Listing No. 7300-0067:0172
Page 2 of 3
*Rev. 05-04-09 bh
This listing is based upon technical e the test results and/or other data but
endorsement or recommendation of
requirements or installation criteria.
information sources.
Date Issued: July 01, 2010
data submitted by the applicant. CSFM Fire Engineering staff has reviewed
does not make an independent verification of any claims. This listing is not an
the item listed. This listing should not be used to verify correct operational
Refer to listees data sheet, installation instructions and/or other suitable
Listing Expires June 30, 2011
I
I
I Authorized By: FRANCIS MATEO, Program Coordinator
11
Fire Engineering Division
Listing No. 7300-0067:0172
Page 3 of 3
SSD-INTL, SSD-C-INTL Systems Status Display
ALCC* Audio Level Conversion Card
RATING:
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name or Siemens, model number, electrical rating and UL label.
APPROVAL:
NOTE:
I
I
I
I
I
U
I
I
I
I
I
I
I
Rev. 05-04-09 bh
TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
' the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
I
I
I
I
I
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No 1307Q 0067 0152 Page 1 of 2
CATEGORY: 7300 -- MISC. DEVICE/CONTROL UNIT ACCESSORIES
LISTEE: Siemens Industry, Inc. Building Technologies Division, 8 Fernwood Road, Florham Park, NJ 07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Control unit accessories as listed below. Refer to listee's data sheet and control unit's
installation instructions for additional detailed product description and operational
considerations.
PSR-1 Remote Power Supply
NET-4, -7, -7M Communications Interface
MOI-1/MOI-7 Voice and Annunciator Driver
MOD-16 Output Driver
VCP-25 Remote Indicating Device Zone Output Module
FT-301/C/CL, FT-302/C/CL Remote Telephone Station
FJ-303, PT-303, -304, Remote Telephone Station
FJ-30355, -304, -304SS Remote Telephone Station
CP-2297 Signal Line Suppressor
CP-2341 Supply Line Suppressor
PAL-1 Printer
MID-16 Input Module
VDT Video Display Terminal
ICP, ICP-136 Intelligent Control Point Module
PIM-2, RSE-i Printer Interface Module
RCC-1, RCC-1 FfRCC:2, RCC-3, RCC-3F Remote Command Center
CP 7537-394 Computer
CP 7554-001, CP-7574, CP-7574T Monitor
SCD-19M, -19TM, SCD-21M, -21TM Monitor
*SCD17L -1 71-T, -19L, -1 91-T Monitor (Flat Screen)
MXL-G/CXL-G Graphic Interface
CPP Multiplexer
LLM-i Leased Line Module
CP-7585-33/-661-1 00/-Pi 33 Computer
SCD-550, -550T, -550-DOS Computer
AIC-4Z, NCC-i F Interface Card
RATING:
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as control unit accessories for use with listee's separately listed compatible
*Rev. 07-17-2007 jw
, This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
\./ endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
I
I
NOTE:
I
I
I
Listing No. 7300-0067:0152
Page 2 of 2
control units. Refer to listee's Installation Instruction Manual for details.
I
I
I
I
I
I
I
*Rev. 07-17-2007 jw
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
I
I
I
I
I
I
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. CJT-o067:O221 Page 1 of 1
CATEGORY: 7315— POWER UNITS
LISTEE: Siemens Industry, Inc. Building Technologies Division, 8 Fernwood Road, Florham Park, NJ 07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Model(!AD-3 notification appliance extender/distributed power module/power supply and
Models EN-PAD, EN-PADR enclosure. Unit comprises of a printed circuit board housed in
the EN-PAD or EN-PADR enclosure. The PAD-3 monitors with the polarity of its two input
circuits to determine when to operate its four notification circuits. The PAD-3 also provides
on trouble relay contact and an auxiliary power circuit. Refer to listee's installation/operation
manual for additional detailed product description and operational considerations.
RATING: 120 VAC, 24 VDC.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. Unit shall be fully
supervised and shall have the 24-hr battery back up as required per code.
MARKING: Listees name or Cerberus Pyrotronics, model number, electrical rating and UL label.
APPROVAL: Listed as notification appliance extender for use with listee's separately listed compatible
fire alarm control units.
This unit can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation
Signal (for total evacuation) in accordance with NFPA 72, 2002. Refer to manufacturer's
Installation Manual for details.
NOTE:
I
U
I
I
I
I
I
I
I
*Rev. 10-26-2002
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
\/ endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
I
I
I
I
I
I
I
I
I
1
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
.
LISTING SERVICE
LISTING No. c72-op67c2o3 Page 1 of 1
CATEGORY: 7272 -- PHOTOELECTRIC SMOKE DETECTOR
LISTEE: Siemens Industry, Inc. Building Technologies Division, 8 Fernwood Road, Florham Park, NJ 07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Models FP-11HFP-11, and *HFpo.11 analog and FPO-11 photoelectric type smoke
detectors. Models FP-1, and HFP-11 also have a supplemental 1350F heat sensor. Model
DGH-1 1 detector guard housing suitable for use with Models HFP-1 1, *HFPo11 and
FP-1 1 smoke detectors. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING:
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. These detectors are
intended for installation on a vertical wall surface or the ceiling. They are also acceptable
for duct application with an air velocity of 0-4000 ft/mm. when used with Models DB-1 1
DB-HR or DB-X11RS bases.
MARKING: Listee's name, model number, and UL label.
APPROVAL: Listed as photoelectric type smoke detectors for use with listee's separately listed base
Model DB-11, DB-HR or DB-X11RS (CSFM Listing No. 7300-0067:134) and separately
listed compatible fire alarm control units. Model DGH-1 1 detector guard housing is listed for
use only with FP-1 1 and HFP-1 1. Refer to listee's Installation Instruction Manual for details.
NOTE:
I
I
I
I
I
I
I
I
I
*Rev. 09-27-2004
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
\ the test results and/or other data but does not make an independent verification of any claims. This listing is not an
\/ endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
I
III
I
I
1
I
I
I
I
[I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. J27070067026 Page 1 of 1
CATEGORY: 7270 - HEAT DETECTOR
LISTEE: Siemens Industry, Inc. Building Technologies Division, 8 Fernwood Road, Florham Park, NJ 07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Model.FT-1f'electronic fixed temperature heat detector. Refer to listee's data sheet for
additional detailed product description and operational considerations.
RATING: 1350F fixed temperature
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name or Cerberus Pyrotronics, model number, temperature rating and UL label.
APPROVAL: Listed as heat detector for use with separately listed compatible fire alarm control units.
Intended for use with listee's Model DB-11 base (CSFM Listing No. 7300-0067:134).
NOTE:
I
I
I
I
I
I
I
I
I
I
I
Rev. 10-26-2002
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
. the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
I
Li
I
I
I
I
I
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION .... .
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300:0067 0134, Page 1 of 1
CATEGORY: 7300 - MISC. DEVICE/CONTROL UNIT ACCESSORIES
LISTEE: Siemens Industry, Inc. Building Technologies Division, 8 Fernwood Road, Florham Park, NJ 07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Models D134T, D134TS, DB4F, DB4TF, DB4FS, D133S, AD133, ADBX3, DB-HR, DBX3RS,
DB-11: DB-X1 1 RS, ADBI60, ADB-1 1, ADBH-1 1, ADBX-1 1 and 8837 detector bases and
Model DB-ADPT detector/base adapter. Suitable for use with Models RR2 or RR3 auxiliary
relays. Model DB-11 is suitable for use only with Model RR-1 1 or RR-1 1 F auxiliary relay.
Models DB-11 base, ADBH-11 audible base, and DB-HR relay base are intended to be
used with Models HFP-1 1 and HFPT-1 1 Intelligent Series smoke and heat detectors
(CSFM Listing No. 7272-0067:223 and 7270-0067:224). Refer to listee's data sheet for
additional detailed product description and operational considerations.
RATING:
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. Model DB-1 1, ADBH-1 1
and DB-HR may be installed on the ceiling or on the wall.
MARKING: Listee's name or Cerberus Pyrotronics, model number, electrical rating and UL label.
APPROVAL: Listed as detector bases for use with separately listed compatible smoke detector heads
and fire alarm control units.
NOTE:
*Rev. 10-28-2002 JW
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
\. the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
cfr requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. C71O0967'003 Page 1 of 1
CATEGORY: 7150-- FIRE ALARM PULL BOXES
LISTEE: Siemens Industry, Inc. Building Technologies Division, 8 Fernwood Road, Florham Park, NJ 07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Models MS-5,-51,-52,-52C,-53 through -57,-60,-6ODAP,-6ODP,-6OKS,-151,-157,
-500 through -507, -511, -512,-512C,-513, -513C, -514, -514C,-515,-516, -517, -517C,
-518, and MS-MI; MH-51, -57, -501, -507, -511, -517, -517C, -518; MSX-1, -2, -21D, -100;
MHX-1, -100rMl-1, -2, -10, 0B -20,-20B, -60, -6ODA; MSI-MB6; HMS-S, -D, -M
noncoded manual pull stations. Single action, double action, and double action distinct
type. Refer to listee's data sheet for additional detailed product description and operational
considerations.
RATING:
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name or Cerberus Pyrotronics, model number, electrical rating and UL label.
APPROVAL: Listed as manual pull stations for use with separately listed electrically compatible fire
alarm control units. Models with prefix MH are suitable for use with Halon extinguishing
system. Models HMS-S, -D, -M are addressable.
* These manual pull boxes do not meet the requirements of UL Standard 38, 1999 Edition
and California amendments.
NOTE:
I
I
I
I
I
I
I
I
I
*Updated 06-22-2009 fm
, This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed e the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
I
I
I
I
I
Li
I
I
I
I
I
I CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE I
LISTING No. ö0-0067:0i46 Page 1 of 1
I CATEGORY: 7300 -- MISC. DEVICE/CONTROL UNIT ACCESSORIES
LISTEE: Siemens Industry, Inc. Building Technologies Division, 8 Fernwood Road, Florham Park, NJ 07932 ' Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Models TRI-2, TRI-2D, TRI-2R, TRI-60, TRI-60D, TRI-60R, TRI-136, TRI-136D, TRI-136R,
'.TRI B6M TRIDTRI Iand TRI S addressable modules and TRI CB supervisory module
I
Refer to listees data sheet for additional detailed product description and operational
considerations.
RATING:
I INSTALLATION: In accordance with listees printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
I MARKING:
APPROVAL:
Listee's name or Cerberus Pyrotronics, model number and UL label.
Listed as control unit accessories for use with Model XL3 (CSFM Listing No.
7165-0067:104 and 7170-0067:151), Model MXL (CSFM Listing No. 7165-0067:144 and
7170-0067:154) or IXL (CSFM Listing No. 7165-0067:138 and 7170-0067:153) fire alarm I control units. The TRI-CB module is designed for use with the TRI-2, TRl-2D and TRI-2R
modules when interfaced with the INX module.
NOTE:
I
I
I
I
I
I *Rev. 10-26-2002
I This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
\ the test results and/or other data but does not make an independent verification of any claims. This listing is not an
Js endorsement or recommendation of the item listed. This listing should not be used to verify correct operational I requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
I Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-O067:0252 Page 1 of 1
CATEGORY: 7125— FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Siemens Industry, Inc. Building Technologies Division, 8 Fernwood Road, Florham Park, NJ 07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Models ST-MC-RETRO-R, ZR-MC-W, ZR-MC-R, ZR-HMC-R, ZR-HMC-W intended for
indoor use on walls. -
Models ST-MC-CW, ST-HMC-CW, R-MC-CR, ZR-MC-CW, ZR-HMC-CR, and
ZR-HMC-CW multi candela intended for indoor use mounted on the ceiling only.
Z -series strobes are intended for use with models ZB-R or ZB-W back boxes. ST - series
strobes are intended for use with models SHBBS surface back boxes. Model numbers may
be followed by alpha characters indicating lens orientation, lettering, and color. Refer to
listee's data sheet for additional detailed product description and operating considerations.
RATING: Electrical 16-33VDC/FWR
Candela: ST-MC-RETRO-R 15cd, 30cd, 75cd, 110cd
ZR-MC-W, ZR-MC-R 15cd, 30cd, 75cd, 110cd
ZR-MC-CR, ZR-MC-CW 15cd, 30cd, 75cd, 95cd
ST-MC-CW 15cd, 30cd, 75cd, 95cd
ZR-HMC-R, ZR-HMC-W 135/185cd
ZR-HMC-CR, ZR-HMC-CW 115/177cd
Flash Rate: 60 flashes / minute
INSTALLATION: In accordance with Listee's printed installation instructions, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction. Models with
suffix -Ware wall mount only. Models with suffix -C are ceiling mount only. All models are
for indoor use only.
MARKING: Listee's name, model number, electrical / candela rating and UL label.
APPROVAL: Listed as strobe light suitable for the hearing impaired when used with separately listed
electrically compatible fire alarm control units. Refer to listee's installation instruction
manual for details.
NOTE:
9-1 O-2007mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed e the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 712-0067:0248 Page 1 of 1
CATEGORY: 7125 - FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Siemens Industry, Inc. Building Technologies Division, 8 Fernwood Road, Florham Park, NJ 07932
Contact: Peter Pawchak (973) 593-2662 Fax (973) 593-6652
Email: Peter.pawchak@siemens.com
DESIGN: Models NH-R, NH-W, NH-CR, NH-CW, ZH-R, and ZH-W horns and models NS-MC-R,
NS-MC-W, ZH-MC-R, ZH-MC-W, ZH-HMC-R, AND ZH-HMC-W Horns / Strobes. Models
NS-MC-CR, NS-MC-CW, NS-HMC-CR, NS-HMC-CWZH-MC-CR, ZH-MC-CW,
ZH-HMC-CR, ZH-HMC-CW are horn / strobes for ceiling mount only. Suffix CR or CW are
for ceiling and color. Units are synchronized or non-synchronized strobes. Refer to Listee's
data sheet for additional detailed product description and operational
RATING: Electrical 16-33VDC/FWR
Candela: NS-MC-C, ZH-MC-C = 15/30/75/95 candela
NS-HMC-C, ZH-HMC-C = 115/177 cd
NS-MC, ZH-MC = 15/30175/110 cd
ZH-HMC, = 135/185 cd
Flash Rate: 60 flashes I minute
INSTALLATION: In accordance with Listee's printed installation instructions, applicable codes &
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical / candela rating and UL label.
APPROVAL: Listed as audible and audible II visual signaling devices for use with separately listed
electrically compatible fire control units. Models with strobe lights are suitable for the
hearing impaired. For indoor use only. All synchronization strobes shall be used with model
DSC sync control module (CSFM listing No. 7300-0067:212). Refer to manufacturer's
installation manual for details
Note: These appliances can produce a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
NOTE:
I
I
I
I
I
I
I
09-07-2007
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
I
FT
I
I,
I
I
I
I
I
I
I
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7270--002-1--0001A Page 1 of 1
CATEGORY: 7270 -- HEAT DETECTOR
LISTEE: Thermotech Inc.,2900 North 1000 West, Ogden, UT 84414
Contact: Sherman Barker (801) 782-2233 Fax (801) 782-1746
Email: thermotechinc@hotmail.com
DESIGN: Models 302, 302H, 302AWO2ET and 302EPM heat detectors. Units are open circuit,
c1350 F, 1940 F fixed temperature and rate-of-rise type heat detectors. Models 302 and
302-H are for indoor use. Models 302-ET or 302-AW are for all weather use. Model
302-EPM is suitable for use in Class I, Groups C and D and Class II, Groups E, F and G
hazardous locations. Refer to listees data sheet for additional detailed product description
and operational considerations.
RATING: 6-125 VAC or VDC, 125 VDC
1350 F, 1940 F fixed temperature and rate-of-rise
INSTALLATION: In accordance with listees printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. Models 302, 302-El and
302-AW are for intended for vertical mount and Models 302-H is intended for horizontal
mount only.
MARKING: Listee's name, model number, electrical and temperature rating and UL label.
APPROVAL: Listed as fixed temperature and rate of rise type heat detectors for use with separately
listed compatible fire alarm control units.
I
I
I
I
I
I
L
I
I
*Rev. 05-01-2003
TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not an
endorsement or recommendation of the item listed. This listing should not be used to verify correct operational
requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable
information sources.
Date Issued: July 01, 2010 Listing Expires June 30, 2011
Authorized By: FRANCIS MATEO, Program Coordinator
Fire Engineering Division
I
I
I
I
I
I
I
I
I
H
so 1' POWER COMMUNICATION SYSTEMS, INC
SALES - SERVICE - ENGINEERING
Public Address * Paging * Intercom * Fire Alarm * Nurse Call • CCTV
I
I : WARRANTY
Power Communication Systems, Inc., warrants its work and/or material supplied to be in substantial
I
compliance with plans and specifications as set forth.
Material purchased from, and installed by Power Communication Systems, inc., is warranted to be
free from defects in material or workmanship for a period of one year from date of acceptance, or
first beneficial usage, whichever occurs first.
The undersigned does hereby agree to repair or replace at their own expense, during normal
I working hours, any equipment or workmanship provided and installed by them found to be defective.
I
They also agree to repair or replace at their discretion any materials sold by them and installed by
others for a period of one year from date of sale. This is an over-the-counter warranty and is limited
to materials returned to them with proof of purchase.
This warranty shall not apply to any material sold' 'àr'installed by Power Communication Systems,
Inc.-, which has been subject to abuse, misuse, neglect, accident, or use contrary to instructions
I furnished. All requests for warranty service must be accompanied by a valid Purchase Order and
"Bill To" address. When applicable, invoices for warranty work will indicate "No Charge".
I In the event the undersigned fails to comply with the above within a 30 day period after official
written notification of failure or defect, the owner shall have the right to repair it at their discretion at
Power Communication Systems expense.
POWER COMMUNICATION SYSTEMS, INC.
Ernest Power Ill
DATE
P.O. Box 600066, San Diego, CA 92160-0066 4643-A Mission Gorge Place, San Diego, California 92120-4133
(619) 583-7400 • Fax: (619) 583-0647 License No. 636431—C7/C1O
05/25/2011 14:11 16i.5830647 FOt'ERCOM PAGE 02
- FILE COPY
POWER COMMUNICATIONSYSTEMS, INC. So
'L141 SALES - SERVICE - ENGINEERING
4Jl
Public Address' Paging * Intercom Fire Alarm * Nurse Call' CCTV
FIRE ALARM SYSTEM RECORD OF COMPLETION
f:A It O632.
1 PROTECTED PROPERTY INFORMATION
Name of property: Kaiser Permanente MOO Carlsbad
Address: .6860 Avenida Encinas, Carlsbad, CA 92008
Description of property: Medical Office Building
Occupancy type: 8
-- -.
Name of property representative:Kaiser Foundation Hospitals
-.
Address: 393 East Walnut Street, Pasadena, CA 91188
--
Phone: 714-970-4500 -- Fax:
-
E-mail:
Authority having jurisdiction over this property: City of Carlsbad - Fire Prevention Division
-
Phone: 760-602-4665 Fax: E-mail:
2. FIRE ALARM SYSTEM INSTALLATION, SERVICE AND TESTING INFORMATION
Installation contractor for this equipment: Power Communication Systems, Inc.
Address: 4643 Mission Gorge Place, Suite A San Diego, CA 92120
Phone: (619) 583-7400 Fax: (619) 583-0647 - E-mail:
Service organization for this equipment: Power Communication Systems, Inc.
Address: 4643 Mission Gorge Place, Suite A San Diego, CA 92120
-
Phone: (619) 583-7400 - Fax: (619) 583-0647 E-mail:
Location of as-built drawings: Location of historical test reports:
Location of system operation and maintenance manuals:
A contract for test and inspection in accordance with NFPA standards is In effect as of:
Contracted testing company:
--
Address:
Phone: Fax: E-mail:
Contract expires: Contract #:
Frequency of routine inspections:
3 TYPE OF FIRE ALARM SYSTEM OR SERVICE
NFPA 72 Chapter reference of System Type:
Name of organization receiving alarm signals with phone numbers (fcippIicabIe):
Alarm: Emergaricy24 Phone: 866-571-4146
Supervisory; Emergency 24 Phone: 866-571-4146
Trouble: Emergency 24 Phone: $66-571-4146
Entity to which alarms are retransmitted: Power Communication Systems, Inc. Phone: 619-583-7400
Method of retransmission of alarms to that organization or location: --
P.O. Box 600086, San Diego, CA 92160-0066 '4643-A Mission Gorge Place, San Diego,Caiifornla 92120-4133
(619) 583-7400 1, Fax: (619) 583-0847 License No. 636431—C7/CIO
05/25/2011 14:11 16195830547 POWERCOM PAGE 03
TYPE OF FIRE ALARM SYSTEM OR SERVICE (continued)
If Chapter 8, note the means of transmission from the protected premises to the central station:
E Digital Alarm Communicator McCulloh E Multiplex 2-way radio
E 1-way radio El N/A
If Chapter 9, note the type of connection: Local energy EJ Shunt E N/A
3.1 SYSTEM SOFTWARE
Operating system (executive) software revision lever: 4.0
Site-specific software revision d Revision completed by: 0. Jay Hill
SIGNALING LINE CIRCUITS
Characteristics of signaling line circuits connected to the system (see NFPA 72, Table 6.6.1):
Quantity:
-
2 1 Style: 4 Class: B
S. ALARM-INITIATING DEVICES AND CIRCUITS
Characteristics of initiating device circuits connected to this system (see NFPA 72, Table 6.5);
Quantity: 2 Style: 4 Class: B
5.1 MANUAL INITIATING DEVICES
5.1.1 MANUAL PULL STATIONS
Type of devices: El Addressable
IJ Transmitter
5.2 AUTOMATIC INITIATING DEVICES
5.2.1 AREA SMOKE DETECTORS
Type of coverage: Complete Area
E N/A
Type of devices; LJ Addressable
Transmitter
Type of smoke detector sensing technology:
5.2.2 DUCT SMOKE DETECTORS
Type of coverage:
Type of devices: E Addressable
Transmitter
Type of smokedetector sensing technology:
El Conventional EJ Coded
N/A
El Partial Area E Non-required partial area
Conventional Coded
E N/A
U Ionization Photoelectric
Number of luct smoke detectors:
U Conventional U Coded
II N/A
U Ionization El Photoelectric
6.1 SPRINKLER SYSTEM Number of valve supervisory switches:
Type of devices: LI Addressable LI Conventional LI Coded
LI Transmitter LI N/A
6.2 FIRE PUMP
Type of fire pump: LI electric LI Diesel
Type of fire pump supervisory devices: LI Addressable LI Conventional
LI Transmitter LI N/A
1
LI Coded
85/25/2011 14:11 16195830547 POWERCOM PAGE 04
5.2,3 HEAT DETECTORS
Type of coverage: CJ Complete Area LI Partial Area LI Non-required partial area
ED N/A
Type of devices: LI Addressable LI Conventional LI Coded
El Transmitter LI N/A
5.2.4 SPRINKLER WATERFLOW DETECTORS
Type of devices: Addressable LI
LI Transmitter LI
5.2.5 ALARM VERIFICATION
Alarm verification on this system is: LI Enabled
Conventional LI Coded
N/A
Number of devices subject to alarm verification
LI Disabled LI Set for seconds
6 SUPERVISORY SIGNAL-INmATING DEVICES AND CIRCUrrS
Fire Pump Functions Supervised
LI Fire pump power LI Fire pump running LI Fire pump phrase reversal
LI Selector switch not in auto LI Engine or control panel trouble 0 Low fuel
Other:
6.3 ENGINE-DRIVEN GENERATOR
Type of generator supervisory devices: LI Addressable LI Conventional LI Coded
LI Transmitter LI N/A LI Engine or control panel trouble LI Generator running
LI Selector switch not in auto LI Low fuel
7. ANNUNCIATORS
7.1 ANNUNCIATOR 1 LI Local LI Remote
Type: LI Addressable LI Directory LI Graphic LI N/A
Location: Building Entrance Courtyard
7.2 ANNUNCIATOR 2 LI Local LI Remote
Type: LI Addressable LI Directory LI Graphic LI N/A.
Location:
05/25/2e11 14:11 16195830647 POIIERCOM PAGE 05
7.3 ANNUNCIATOR 3 El Local El Remote
Type: El Addressable El Directory El Graphic 21 N/A
Location:
S. ALARM NOTIFICATION DEVICES AND CIRCUITS
8.1. EMEREGENCY VOICE ALARM SERVICE
Number of single voice alarm channels: Number of multiple voice alarm channels:
Number of speakers:
-
Number of speaker zones:
8.2 TELEPHONE JACKS
Number of telephone jacks installed: Number of telephone handsets stored on site;
Type of telephone system installed: Electrically powered El Sound powered E21 N/A
8.3 NON VOICE AUDIBLE SYSTEM
Characteristics of notification device circuits connected to this system (see NFPA 72 Table 6.5):
Quantity: 8 Style: V Class: B
8.4 TYPES AND QUANTITIES OF NONVOICE NOTIFICATION APPLIANCES INSTALLED
Bells: With visual device: Horns: 23 With visual device: 23
Chimes: -- With visual device: Bells: With visual device:
Visual devices without audible devices: 83 Other. (describe): -
EMERGENCY CONTROL FUNCTIONS ACTIVATED
El Hold-Open Door Releasing Devices El Smoke Management or Smoke Control
El boor Unlocking El Elevator Recall El Other
SYSTEM POWER SUPPLY
101 PRIMARY POWER
Nominal Voltage 120 VAC
-- Amps 2 AMPS
-
Overcurrent protection: Type Circuit Breaker Amps 20AMPS
Location (of primary supply panelboard): ElectricalRoom
Disconnecting means location:
10.2 SECONDARY POWER
Location: Type: Battery Nominal Voltage: 12V Current Rating;
Number of standby batteries: 2 Amp hour rating 18 A
Location of emergency generator:
05/25/2011 14:11 16195830647 POI4ERCOM PAGE 06
10.2 SECONDARY POWER (continued)
Location of fuel storage:
Calculated capacity of secondary power to drive the system
In standby mode: In alarm mode:
RECORD OF SYSTEM INSTALLATION
Fill out after all installation is complete and wiring has been checked for opens, shorts, ground faults, and improper
branching, but before conduction operational acceptance tests.
The system has been installed in accordance with the following NFPA standards: (Note any or all that apply.)
NFPA 72 Ei NFPA 70, National Electrical Code, Article 760
21 Manufacturer's published instructions E Other (please specify):
System deviations fr erenced NFPA standards:
Signed: Printed: D. Jay Hill Date: 5/4/2011
Organization: PowerCommunicationSystems,Inc. Title: Forman
Phone: (619)583-7400
RECORD OF SYSTEM OPERATION
All operational features and functions of this system were tested by or in the presence of the signer shown below, on
the date shown below, and were found to be operating properly in accordance with the requirements of:
El NFPA 72 0 NFPA 70, National Electrical Code, Article 760
Manufacturer's published instructions El Other (please specify):
Documeot1bR in accordance with Insoection and Testing Form lFieure 10.6.2.31 Is attached
Signed: Printed: D. Jay. HI II - Date: 5/4/2011
Organization: Power Communication Systems, Inc. Title: Forman
Phone: (619) 583-7400
CERTIFICATIONS AND APPROVALS
13.1 SYSTEM INSTALLATION CONTRACTOR
This system as 5 herein has been installed and tested according to all NFPA standards cited herein.
Signed: - Printed: D. Jay Hill Date: 5/4/2011
Organization,/
- -PowerçmrnunicationSystems,Inc.
-
Title: - Forman
-
Phone: '
-(619)583-7400
05/25/2011 14:11 16195830647 PO4ERCOM PAGE 07
13. CERTIFICATIONS AND APPROVALS (continued)
13.2 SYSTEM SERVICE CONTRACTOR
This system as spe herein has been installed and tested according to all NFPA standards cited herein.
Signed: Printed: 0. Jay Hill Date: 5/4/2011
Organization: ---.Power Communication Systems, Inc. litle:
-
Forman
Phone: (61)583-7400
13.3 CENTRAL STATION
This system as specifi in will be monitored according to all NFPA standards cited herein.
Signed: Printed: 0. Jay Hill Date:5/4/2011
Organization: Power Communication Systems, Inc. Title: - Forman
Phone: (619)583-7400
13.4 PROPERTY REPRESENTATIVE
I accept this system as having been installed and tested to its specifications and all NFPA standards cited herein.
Signed; _ Printed: Date: --
Organization: Title:
Phone:
13.5 AUTHORITY HAVING JURISDICTION
I have witnessed a satisfactory acceptance test of this systems and find It to be installed and operating properly In
accordance with its approved plans and specifications, Its approved sequence of operations, and with all NFPA standards
cited herein.
Signed: —Printed: Date:__________
Organization: ,/l<1i. - Title:
Phone: