B U I L D I N G P E R M I T Permit No: CB980621
0.9/16/98 12:04: Project No: A9800794
Page 1 of 1 Development No:
Job Address: 1902 WRIGHT PL Suite: 300
Permit Type: COMMERCIAL TENANT IMPROVEMENT
Parcel No: Lot#:
Valuation: 431,080
Occupancy Group: B Reference#:
Description: CTI 16580 SF,ELEC,PLUM,HVAC
RUBIOS BAJA GRILL
Appl/Ownr : AUGUSTINE MILLER
1905 MISSION CLIFF DRIVE
SAN DIEGO CA 92116
*** Fees Required ***
Fees: 9,049.09"
Adjustments: .)0
Total Fees: 9,0400 coo
Fee description
Building Permit / &D
Plan Check
Strong Motion Fee VeeEnter Traffic Impact FJ
Enter "Y" for Plumbiiig Issue
Each Plumbing Fixturê or Trap
Each Install/Repair Vter Lin
Each Water Heater and/or Vent
Gas Piping System \ , Enter "Y 1' for Electric Issué
Remodel/Alter Per AMP Enter 'Y' for Mechanical
Install Furn/Ducts/Heat Pump,
Each Exhaust Fan
FINAL Ad )VAL
F
INSP.O : //
CLEARANCE____________________
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
Construction Type: Vi
Status: ISSUED
Applied: 02/26/98
Apr/Issue: 09/16/98
Entered By: JM
619 29636jL6 09/16/98 0001 01 02
C-PRMT 7999.00
'1 L/2oaQ
SEWER PERMIT
09/16/98 12:09 Permit No: SE980116
Page 1 of 1 Bldg PlanCk#: CB980621
Job Address: 1902 WRIGHT PL Suite: 300
Permit Type: SEWER - OFFICE/WAREHOUSE • 1165 91161'98 OD01 01010740
Parcel No:
Description: CTI 16580 SF,ELEC,PLUM,HVAC
RUBIOS BAJA GRILL
Permitee: AUGUSTINE MILLER
1905 MISSION CLIFF DRIVE
SAN DIEGO CA 92116
Status: ISSUED
Applied: 06/30/98
Apr/Issue: 09/16/98
619 296-3615 Expired:
Prepared By: MAIl
II
*** Fees Required ***
----------------------------
Fees: 10,74300/
Adjustments:
Total Fees: 10,7y .00
Fee description &
Enter Office Square oo
<Enter CREDIT EDUs> CZ!
Total EDUs
Sewer Fee Q~:~ Enter Sewer EDUs and Benef:
* SEWER TOTAL
FeeGq.cted & Credits
/\ N.....................
.00 \ .00
\ 10,743.00.
rriit\ Ext fee Data -
9.21
-3.32
31 5.89
10743.00
00
10743.00
-T-talAC- tedits I
Total Payment.s,:
Bal•-aace( Due.:
Atw A0v
00
\
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
VOLf2-O/
PERMIT APPLICATION
CITY OF CARLSBAD-BUILDING-DEPARTMENT
2075 Las Palmas Dr., Carlsbad' CA 92009
(760)438-1161
FOR OFFICE USE ON
PLAN CHECK NO
ESL VAL.
Dian Ck. Deposit
Validated By_______
OJ
'
E I JJNFORMATION - ig- -- -
Addr ss (include Bldg/Suite #) Business Name (at this address) h - I C-frs p— - U ci )
Legal Description- - Lot No. Subdivision Name/Number Unl't?t/./ jalT3Jjihits
Assess's Parcel # Existing Use Proposed Use
'.&- 1to58O 3ai'
Descriptipn of Work SQ. FT. #f Stories ' # of Bedrooms # of Bathrooms
'J,L.L.O?JtALL.S1I - 62_ Th h ILL. _
12.
1ccy. I'1icao- _i D -- -CA ?IiCo (,92q136 T Name - Address - - City - - State/Zip -- Telephone #
AEICANT Dar DAgen(forui 'tJ jr QL
Name - - Address, - - - -- City - State/Zip - Telephone #
PROPERTY OWNER - çOfCJJ€(STD-' .CQZP. CA—'TIZ LL — /O1Js—tJf2O,f' Ai 3—'-- -D/
Name So 5—DMdress City Statelip ç'elephone #
15 1 0 i 2
- r_.DPMT- 11w') 00 (Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repairi.any structure, priorto-its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
[Chapter 9, commending with Section 7000 of Division 3 of the Business-and Professions Code] or that he is exempt'therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars [$5001).
-Name - Address City State/Zip Telephone #
State License # - License Class - 'City Business License #
Designer Name - . -. Address , , , - City - - , State/Zip Telephone
State License # - - - - - -
L6_i T1
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations:
I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued. My worker's compensation insurance carrier and policy number are: -
Insurance Company - - Policy No. - Expiration Date
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS [$1001 OR LESS)
CERTIFICATE OF EXEMPTION: I certify that in the performance of the work for which this permit is issued,. I' shall not employ any person in any manner so as -
to become subject to the Workers' Compensation Laws of California.
WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred
thousand dollars ($100,000), in addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees,. -
SIGNATURE' - ' - - - - DATE -
I hereby affirm that I am exempt from the Contractor's License Law for the following reason: - - -
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License. Law, does not apply to in owner of property who builds or improves thereon, and who does
,such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is
sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale). --
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, 'Business and Professions Code: The
contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's, License Law).
o I am exempt under Section Business and Professions Code for this reason: - - - -
-
I personally plan to provide the major labor and materials-for construction of the proposed property improvement. 0 YES kNO -
I (have / have not) signed an application for a building permit for the proposed work.
.1 have co tractod with the following person (firm) to provide the proposed on uction (include name / address / phone number / contractors license number):
I plan to provide portions of 'the work, but I have hired the follovling person to coordinate, supervise and provide the major work (include name / address I phone
,number contractors license number):
I will provide some of the w , t I Ipa co tedJtfd( the following persons to provide the work indicated (include name / address / phone number / type
of. work): - - - - - ' - - - - - -- -
PROPERTY OWNER SIGNATURE ' 0 P 44--k.L.. OI..I"bATE - -
Is the applicant or future building occupJtit required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
-
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance AccountAct? 0 YES 0 NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 YES 0 NO
Is the facility to be constructed within 1,000 feet of the outer boundary of aschoOl site? 0 YES 0 - NO
- IF ANY OF THE ANSWERS ARE-YES, A FINAL CERTIFICATE OF OCCUPANCY MAY-NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
[?I.ONSTRUCTION_LENDING_AGENCY - =
I hereby affirm that there is -a construction lending agency for the performance-of the work for which-this permit is issued (Sec.3097(i) Civil Code).
LENDER'S NAME -' ---- - - LENDER'S ADDRESS ------
I1,IAPPLICANLCERTIFICATION
I certify that I have read the application and state that the above information is correct and that the information on the plans is accurate. i agree to comply with all
City ordinances and State laws relating to building construction. I- hereby authorize representatives of the Citt' of Carlsbad to enter upon the above mentioned
property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA An OSHA permit is required for excavations over 5 0 deep and demolition or construction of structures over 3 stories in height
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null- and void if the building or
work authorized by such permit is not commenced within 365 days from the date of such permit or if the building or work authorized by such permit is suspended
or abandoned at any time after tbp is comrner1ced for a period of 180 days (Section 106.4.4 Uniform Building Code). -
APPLICANT'S SIGNATURE ---- ' - DATE - -
WHITE: File YELLOW: Applicant - PINK: Finance
List 1- Permit-Type
From the following list, determine the permit-type that best describes the work you propose to do. Please put the code of that
permit-type in the blank at the top of the page on the front of this application. Residential permits (only) also require the
identification of the structure-type to be associated with the permit. Choose a structure-type from 'List 2 - Structure-Types' and put
its code in the appropriate blank on the front of this application.
Residential Permits
Code Description
APT Apartments'- new construction. -
CONDO Condominiums - new construction.
CVNNR Conversion. Convert all, or a portion of a non-residential building to residential use, creating one or more new
residential units.
CVNRN Conversion. Convert one or more residences in a building to non-residential usage.
CVNRR Conversion. Increase or reduce the number of dwelling units in a residential structure through interior modifications
(i.e.: a four bedroom house converted to a duplex, with 2 bedrooms each).
DEMO Demolition permit. (Also specify type of structure from List 2). - -
DUP Duplex- new construction. -
MOHO Mobile home, renovation, repair, or addition of accessory structure not yielding a new living unit.
MOHON Mobile home, pre-fabricated house, or trailer installed (plumbed, wired) in a mobile home park (see distinction from
single-family residence, below).
RAD Residential addition/alteration, creating no new dwelling unit(s).
RREISSUE Residential permit re-issue.
RREPAIR Residential building repair. Damage, fire, etc.
RREPLACE Residential building replacement (no additional units).
SFA Single-family, attached - new construction. A one-family house attached to one or more other houses, with one or
more common walls extending from foundation to roof at, or forming, a lot line. Has own plumbing and heating
system (e.g.: townhouse, row house, half-plex)
SFD Single-family,. detached - new construction: A one-family house with open area on all four sides. May have an
attached or detached garage, or a business. May be a detached 'granny flat'. May be a mobile home or trailer on an
individual lot, but not in a mobile home park.
Non-Residential/Accessory Permits
Code Description
COM Commercial structure, new construction.
CREISSUE Commercial permit re-issue.
CREPAIR Commercial building - repair. Damage, fire, etc.
CREPLACE Commercial building - replacement.
CT! Commercial tenant improvement.
DEMO Demolition permit.
ELEC Electrical permit, for electrical work only.
HOTEL Hotel or motel (including Managed Living Unit hotel) - new construction.
HOTELR Hotel renovation.
INDUST Industrial structure, new construction.
IT! Industrial tenant improvement.
MECH Mechanical permit, for mechanical work only.
MISC Miscellaneous. Use only if proposed work doesn't fit another activity type.
PATIO Patio and/or deck.
PLUM Plumbing permit, for plumbing work only.
POOL Gunite pools and spas.
RETAIN Retaining wall permit.
SIGN Sign construction/installation permit.
SOLAR Solar energy system installation permit (specify structure type to be served).
SPA 1 Factory-made or Gunite.
List 2 - Structure-Type (Use with Residential Permit Only)
From the following list, determine the type of residential structure that best describes the structure on which you will be working.
Please put the code of that structure-type in the appropriate blank at the top of the page on the front of this application.
Code Description
SFA Single-family, attached. A one-family house attached to one or more other houses, with one or more common walls
extending from foundation to roof at, or forming, a lot line. Has own plumbing and heating system (e.g.: townhouse,
row house, half-plex).
SFD Single-family detached: A one-family house with open area on all four sides. May have an attached or detached
garage, or a business. May be a detached 'granny flat'. May be a mobile home or trailer on an individual lot, but not
in a mobile home park.
MF2-4 Multi-family, 2 to 4 units. A residential structure on a single lot, containing two, three, or four dwelling units. Units
may share master heating, plumbing, or electrical service (e.g.: duplex, triplex, quad-plex).
MFS+ Multi-family, 5 or more units. Same as M172-4, except the building has a t least five attached units on the same lot.
MOHO Mobile home, pre-fabricated house, or trailer installed (plumbed, wired) in a mobile home park (see distinction from
single-family residence, above). -
inspection List
CB980621 CTI CTI 16580 SF,ELEC,PLUM,HVAC
RUBIOS BAJA GRILL
Date Inspection Item Inspector Act Comments
12/15/98 89 Final Combo TP AP
12/10/98 39 Final Electrical TP WC
12/10/98 89 Final Combo TP NR PART WALK THRU
12/9/98 39 Final Electrical TP NS
12/2/98 39 Final Electrical DH CO NEED FIRE TO SIGN OFF
12/1/98 34 Rough Electric DH CO COMP FIX @ ELEV LOBBY <M
11/25/98 34 Rough Electric TP AP SUB PNLS,TRANS
11/20/98 14 Frame/Steel/Bolting/Weldin TP AP T-BAR CElL
11/20/98 24 Rough/Topout TP WC
11/20/98 34 Rough Electric TP AP CElL LITES
11/20/98 44 Rough/Ducts/Dampers TP AP DUCTS, H P UNITS
11/19/98 84 Rough Combo TP CO CElL INSP
11/2/98 14 Frame/Steel/Bolting/Weldin TP AP
11/2/98 34 Rough Electric TP AP HARD CElL @ RECP. AREA
11/2/98 44 Rough/Ducts/Dampers TP AP
10/1/98 14 Frame/Steel/Bolting/Weldin TP AP WALLS
10/1/98 24 Rough/Topout TP WC
10/1/98 34 Rough Electric TP AP WALLS
10/1/98 44 Rough/Ducts/Dampers TP WC
9/29/98 84 Rough Combo TP NR
9/25/98 14 Frame/Steel/Bolting/Weldin TP CO
9/25/98 34 Rough Electric TP CO
9/22/98 21 Underground/Under Floor TP AP
9/22/98 24 Rough/Topout TP AP
Monday, February ci, 1999 Page 1 of 1
as electo ® teit GROUND FAULT SYSTEM
TEST REPORT
CLIENT: , - C//2,'c ENGINEER: £.A,i'r - ETI JOB NUMBER: 22gy-
LOCATION- /'- '-'.L3/ c, S WITNESS DATE: j•c-orr
SWITCI-1GEAR DESIGNATION: TEST EQUIP. ASSE.T # CALIBRATION DATE:
2-2-'/2-2--7
FIELD DATA
SWITCHBOARD MANUFACTURER SHOP ORDER NO. UL NO.
- /2 //-2 D3 -7
MAIN OVERCURRENT DEVICE MFGR.
E1RCUITBREAKER FUSEDSWITCH
TYPE MODEL/CAT. NO. CURRENT RATING SYSTEM VOLTAGE VOLTAGE RATING
S7-/ 2- co c 2- 7 -7 L--
GROUN15 FAULT SYSTEM MFGR.
0 NEUTRAL-GROUND STRAP ZERO-SEQUENCE
MODEL ICAT. NO. PICK-UP RANGE TIME RANGE 0, SENSOR/C.T.
AS FOUND SETTING, ETTIN . SELT GSU9ED BY
PICKUP
1
C ~_j
AAS PLEFT
S
ICKUP URRENT -A TIME CURRENT TIME A/ 5cI-J. , c
INSRECTION
SERVICE ENTRANC, CONDUCTORS MAIN BONDING JUMPER GROUND ELECTRODE CONDUCTOR,
2' "V PER PHASE 5Oc- //CA-1 '(7 13 AWG MCM
NEUTRAL-GROUND LOCATION CONTROL POWER TRANSFORMER
E E RRECT INCORRECT CORRECTED BYCONTRACTOR VA
MONITOR/TEST PANEL OPERATION </ OTHER
EI CORRECT INCORRECT CORRECTED
BREAKER/SWITCH REACTION TIME (RT)
TESTSELECTRICAL
REDUCED VOLTAGE TEST (55% RATED VOLTAGE)
.SECONDS CYCLES 11 CORRECT 0 INCORRECT
PICK-UP CU RRENT PICK-UP CURRENT MINUS 25% (2Lf AMPS)
AMPS l EJINO TRIP (CORRECT) 0 TRIP (INCORRECT)
SYSTEM NEUTRAL INSULATION RESISTANCE TO GROUND OTHER
-
7QC-,MEGOHMS
PRIMARY CURRENT PERCENT TOTAL REACTION RELAY MFGR.
AMPERE-TURNS PICK-UP TIME TIME TIME TOLERANCE
TIME-CURRENT
CALIBRATION - - -
AA
TESTS
REMARKS - - ' ' .-?-- • -, ' / "
GFSTR/90
01990 ETI PAGE ' 0F _____
FINAL -• LDING INSPECTION
DEPT: BUILDING ENGINEERING PLANNING CMWD ST LITE
PLAN CHECK#: CB980621 DATE: 12/10/98
PERNIT#: CB980621 PERMIT TYPE: CTI
PROJECT NAME: CTI 16580 SF,ELEC,PLUN,HVAC -
RUBIOS BAJA GRILL
ADDRESS: 1902 WRIGHT PL SUITE# 300 ::c15 1998
CONTACT PERSON/PHONE#: B/JEFF/804-0117
SEWER DIST: WATER DIST:
INSPECTED DATE t
BY: __ INSPECTED: APPROVED kl DISAPPROVED -
INSPECTED DATE
BY: INSPECTED: APPROVED DISAPPROVED -
INSPECTED DATE
BY: INSPECTED: APPROVED DISAPPROVED -
-------------------
COMMENTS:
EsGil Corporation
In Partnership with government for Building Safety
DATE: 4/27/98
JURISDICTION: Carlsbad
PLAN CHECK NO.: 98-621
PROJECT ADDRESS: 1902 Wright P1. #300
SET: III
O APPLICANT
JURIS.
o PLAN REVIEWER
U FILE
PROJECT NAME: Rubio's Restaurants Office TI
LII The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
U The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified in Remarks below are resolved and checked by building
department staff.
Li The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
Li The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
Li The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
LI The applicant's copy of the check list has been sent to:
LI Esgil Corporation staff did not advise the applicant that the plan check has been completed.
U Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Jillon Augustine In person plan recheck
Date contacted (by: ) Fax #:
Mail Telephone Fax In Person
U REMARKS: Please have Jillon Augustine slip sheet the perforated M sheets and A-I sheet
into the City Set II and change to City Set Ill. Jillon will carry the complete and perforated
Owner Set III and the perforated M and A-I sheets to the City of Carlsbad today. She was
advised that a permit may not be issued at this time. O.K.'d with John.
By: Mike Puckett Enclosures:
Esgil Corporation
El GA [1 CM [1 EJ El PC log trnsmtl.dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (619) 560-1468 • Fax (619) 560-1576
EsGil Corporation
In Partnership with Government for Building Safety
DATE: 4/13/98
JURISDICTION: Carlsbad
PLAN CHECK NO.: 98-621
PROJECT ADDRESS: 1902 Wright P1. #300
SET: II
El APPT
VIEWER
U FILE
PROJECT NAME: Rubio's Restaurants Office TI
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department
staff:
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The checklist transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Jillon Augustine
1905 Mission Cliff Dr. San Diego, Ca. 92116 FAX# 619-296-4630
Esgil Corporation staff did not advise the applicant, except by FAX, that the plan check has
been completed.
LI Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Fax #:
Mail Telephone Fax In Person
LI REMARKS:
By: Mike Puckett Enclosures:
Esgil Corporation
EJ GA 0 CM fl EJ fl PC 4/6/98 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (619) 560-1468 • Fax (619) 560-1576
Carlsbad 98-621
4/13/98
GENERAL PLAN CORRECTION LIST
JURISDICTION: Carlsbad PLAN CHECK NO.: 98-621
PROJECT ADDRESS: 1902 Wright P1. #300
DATE PLAN RECEIVED BY DATE REVIEW COMPLETED:
ESGIL CORPORATION: 4/6/98 4/13/98
REVIEWED BY: Mike Puckett
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, noise attenuation and disabled access. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,-
1994 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
Please make all corrections on the original tracings and submit two new sets of prints to:
ESGIL CORPORATION.
To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the revised
plans.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
UYes
The following items are corrections that were not completely addressed from the
previous plan review.
Item # 2. Each sheet of the plans must be signed by the person responsible for their
preparation, even though there are no structural changes. Business and Professions Code.
The M sheets are not signed.
Carlsbad 98-621
4/13/98
Item # 10 In buildings having floors and roofs of wood frame construction, other than dwelling
or hotel occupancies, draft stop the area between the ceiling and roof above so that no
concealed space exceeds 3,000 s.f. and no horizontal dimension exceeds 60 L.F. (if space has
sprinklers, then 9,000 s.f. and 100 L.F.). Section 708. Please show on the floor plan the
location of the draft stops. No horizontal space can exceed 100 L.F. between draft stops.
Please add draft stop as needed at the tenant space above room 324.
Item # 13. The maximum number of required exits and their required separation must be
maintained until egress is provided from the structure. Section 1003.1. Do the existing exit
stair enclosures when they reach the ground level extend separately to the public way or
yard and do not converge into one exit? The reduced Architectural floor plan is not
attached.
Item # 16. Once a person enters a corridor it must be fire rated to the point of exit from the
building for the tenant improvement shown. This includes any reception areas. When a room
does not exit through an adjoining room as prescribed by the code and into a hallway, that
hallway must be a rated corridor or conform to the non rated corridor requirements of the UBC
when the occupant load exceeds 30 in the Office spaces and does not meet one of the
exceptions listed below. Please consider this in the fire rating of all hallways in the path of
travel for egress. Also, in corridors that are only twice as long as their width and no more the
local Chapter of ICBO has made this an exception to the fire rated corridor requirement. The
hallways and reception area must be made into rated corridors for egress.
Item # 18. Elevators opening into a corridor (in buildings having more than two levels) shall be
provided with an elevator lobby at each floor containing such a corridor. The lobby shall
completely separate the elevator(s) from the corridor by the construction prescribed in
Section 1005.10. Please show the elevator fire rated separation.
Item # 19. One-hour fire-rated corridors shall have interior door openings protected by tight--
fitting smoke and draft control assemblies rated 20 minutes, except openings in interior walls of
exterior exit balconies. Doors shall be maintained self-closing or be automatic closing by action
of a smoke detector per Section 713.2. Doors shall be gasketed to provide a smoke and draft
seal where the door meets the stop on sides and top. Section 1005.8.1. Please create a door
schedule or show on the plans all doors required to be fire rated.
Item # 20. Show rated corridors, lobbies, reception or foyers cross-hatched on the floor plans.
Item # 21. Provide a complete architectural section of the corridor, or exterior exit balcony,
showing all fire-resistive materials and details of construction for all floors, walls, ceiling and all
penetrations. Section 1005.7.
Item # 22. If a room with an exhaust fan has a door opening into a rated corridor, show how
makeup air will be provided to the room. The door cannot be undercut, nor can a louver in the
door be provided. Section 1005.8.1. This applies to the created fire rated corridors.
Carlsbad 98-621
4/13/98
Item # 23. If building exceeds two stories and has an elevator opening into a rated corridor,
show how the smoke and draft control provision of Section 1005.8.1 will be met. Either provide
a separated elevator lobby or a second door at the elevator entry meeting the provision.
Section 1005.10. Note if the Elevator Lobby is protected by the doors at each end of the
corridor, the fire rated corridors must not exit through this area.
Because of the created fire corridors please show the protection of all duct openings
with fire and smoke dampers on the mechanical sheets.
Item # 42. Fire rated corridors are not to be used to convey air to or from rooms. UMC Section
601.1.1. Show how make up air/return air is to be provided in all rooms adjacent to the
corridor and in the corridor.
Item # 45. Show the P & T valve drain to point of discharge.
Item # 50. The completed and signed ENV-1, LTG-1, and MECH-1 forms must be imprinted on
the plans. Please have designer sign the MECH-1 document on the plans.
Item # 56. Please show on detail 11T24 that the door does not encroach into the inscribed circle
as per Title 24 requirements. Change the swing of the door.
The following correction was not seen by the plan reviewer at the previous correction. Please
provide design and calculations for the butt edge glazing or provide other means to firmly
support all the edges of the glazing per Section 2404.1 UBC.
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive, Suite
208, San Diego, California 92123; telephone number of 619/560-1468, to perform the plan
review for your project. If you have any questions regarding these plan review items, please
contact Mike Puckett at Esgil Corporation. Thank you.
EsGil Corporation
In Partnership with government for Building Safety
DATE: 311 1/98 1 0 APPLICANT
JURIS.
JURISDICTION: Carlsbad U P N REVIEWER
U FILE
PLAN CHECK NO.: 98-621 SET: I
PROJECTADDRESS: 1902 Wright P1. #300
PROJECT NAME: Rubio's Restaurants Office TI
LI The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department
staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
I The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Jillon Augustine
1905 Mission Cliff Dr. San Diego, Ca. 92116
• Esgil Corporation staff did not advise the applicant that the plan check has been completed.
LI Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Fax #:
Mail Telephone Fax In Person
LI REMARKS:
By: Mike Puckett Enclosures:
Esgil Corporation
LI GA [1 CM LI EJ LI Pc 3/2/98 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (619) 560-1468 • Fax (619) 560-1576
Carlsbad 98-621
3/11/98
PLAN REVIEW CORRECTION LIST
TENANT IMPROVEMENTS
PLAN CHECK NO.: 98-621
OCCUPANCY: B
TYPE OF CONSTRUCTION: V-lhr
ALLOWABLE FLOOR AREA:
SPRINKLERS?: Yes
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 2/26/98
DATE INITIAL PLAN REVIEW
COMPLETED: 3/11/98
JURISDICTION: Carlsbad
USE: Office
ACTUAL AREA: 16,580sf TI
STORIES: 3
HEIGHT:
OCCUPANT LOAD: 160
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 3/2/98
PLAN REVIEWER: Mike Puckett
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building
Code, Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state
laws regulating energy conservation, noise attenuation and access for the disabled. This plan
review is based on regulations enforced by the Building Department. You may have other
corrections based on laws and ordinances enforced by the Planning Department, Engineering
Department, Fire Department or other departments. Clearance from those departments may be
required prior to the issuance of a building permit.
Code sections cited are based on the 1994 UBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1994 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
LIST NO. 40, TENANT IMPROVEMENTS WITHOUT SPECIFIC ENERGY DATA OR POLICY SUPPLEMENTS (1994UBC) tirorw.dot
Carlsbad 98-621
3/11/98
Please make all corrections on the original tracings, as requested in the correction
list.
Submit three sets of plans for commercial/industrial projects (two sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City
of Carlsbad Building Department, 2075 Las Palmas Drive, Carlsbad, CA 92009,
(619) 438-1161. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
Bring one corrected set of plans and calculations/reports to EsGil
Corporation, 9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (619) 560-
1468. Deliver all remaining sets of plans and calculations/reports directly to the City
of Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
2. Each sheet of the plans must be signed by the person responsible for their
preparation, even though there are no structural changes. Business and
Professions Code.
Provide a statement on the Title Sheet of the plans that this project shall comply
with Title 24 and. 1994 UBC, UMC and UPC and 1993 NEC.
Is the existing building construction classified as v-I hr with sprinklers in lieu of the
1 h protection or is the building protected as 1 h and sprinklered as well?
On the first sheet of the plans indicate:
The floor where the tenant improvement is located,
The occupant load of the remodel area(s).
6. Glazing in the following locations should be of safety glazing material in accordance
with Section 2406.4 (see exceptions):
Fixed or operable panels adjacent to a door where the nearest exposed edge of the
glazing is within a 24-inch arc of either vertical edge of the door in a closed position and
where the bottom exposed edge of the glazing is less than 60 inches above the walking
surface. Please revise note of TS sheet of plans to show this statement Label
glazing to be tempered on the floor plan or create a glazing table and identify.
Carlsbad 98-621
3/11/98
7. Individual fixed or operable panels, other than those locations described above, that
meet all of the following conditions:
Exposed area of an individual pane is greater than 9 square feet, and:
Exposed bottom edge is less than 18 inches above the floor, and:
Exposed top edge is greater than 36 inches above the floor, and:
One or more walking surfaces are within 36 inches horizontally of the plane of the
glazing.
Provide notes and/or details to show that the floor and wall finish in toilet rooms are
surfaced with a smooth hard non-absorbent material extending five inches up the
wall. Similar surfacing shall be provided on the walls from the floor to a height of 4
feet around urinals and within water closet compartments. Section 807.
Note on plan that suspended ceilings shall comply with UBC Tables 25-A, 16-0 and
16-B.
In buildings having floors and roofs of wood frame construction, other than dwelling•
or hotel occupancies, draft stop the area between the ceiling and roof above so that
no concealed space exceeds 3,000 s.f. and no horizontal dimension exceeds 60
L.F. (if space has sprinklers, then 9,000 s.f. and 100 L.F.). Section 708. Please
show on the floor plan the location of the draft stops.
Smoke dampers shall be installed per Section 713.10 at all ducted or unducted air
openings at penetrations of:
The fire-resistive construction of corridors, or horizontal exit walls.
Elevator lobbies required by Section 3002.
12.flcdampers shall be installed per Section 713.11 at all ducted or unducted air
openings at penetrations of:
Ceilings of fire-resistive floor-ceiling assemblies or roof-ceiling assemblies.
The fire-resistive construction of corridors, or horizontal exit walls.
The maximum number of required exits and their required separation must be
maintained until egress is provided from the structure. Section 1003.1. Do the
existing exit stair enclosures when they reach the ground level extend
separately to the public way or yard and do not converge into one exit?
Exit signs are required whenever two exits are required. Show all required exit sign
locations. Section 1013.1.
Carlsbad 98-621
3 /11/98
Show that exits are lighted with at least one foot candle at floor level. Section
1012.1.
Corridors must provide continuous protection to the exterior of the building.
Interruptions by an intervening room is not permitted. Foyers, lobbies or reception
rooms constructed as required for corridors are not considered intervening rooms.
Section 1005.1.
Once a person enters a corridor it must be fire rated to the point of exit from the
building for the tenant improvement shown. This includes any reception areas.
When a room does not exit through an adjoining room as prescribed by the code
and into a hallway, that hallway must be a rated corridor or conform to the non
rated corridor requirements of the UBC when the occupant load exceeds 30 in the
Office spaces and does not meet one of the exceptions listed below. Please
consider this in the fire rating of all hallways in the path of travel for egress. Also, in
corridors that are only twice as long as their width and no more the local Chapter of
ICBO has made this an exception to the fire rated corridor requirement.
Corridors serving 30 or more occupants shall have walls and ceilings of one-hour
construction. Show compliance or clearly show on plans which of the following
exceptions has been satisfied:
Corridors greater than 30 feet wide when the occupants have an exit independent
from the corridor.
Exterior sides of exterior exit balconies.
Corridor walls and ceilings need not be of fire-resistive construction within office
spaces having an occupant load of 100 or less when the entire story in which the
space is located is equipped with an automatic sprinkler system throughout and an
automatic smoke-detection system is installed within the corridor. The actuation of
any detector shall activate alarms audible in all areas served by the corridor.
Within office spaces occupied by a single tenant, partial height partitions which form
corridors and which do not exceed 6 feet in height need not be fire resistive,
provided they are constructed in accordance with Section 601.5 and are not more
than three fourths of the floor-to-ceiling height. Section 1005.7.
Corridor walls and ceilings need not be of fire-resistive construction within office
spaces having an occupant load of 100 or less when the building in which the space
is located is equipped with an automatic sprinkler system throughout. Section
1005.7.
18. Elevators opening into a corridor (in buildings having more than two levels) shall be
provided with an elevator lobby at each floor containing such a corridor. The lobby
shall completely separate the elevator(s) from the corridor by the construction
prescribed in Section 1005.10. Please show the elevator fire rated separation.
Carlsbad 98-621
3/11/98
One-hour fire-rated corridors shall have interior door openings protected by tight--
fitting smoke and draft control assemblies rated 20 minutes, except openings in
interior walls of exterior exit balconies. Doors shall be maintained self-closing or be
automatic closing by action of a smoke detector per Section 713.2. Doors shall be
gasketed to provide a smoke and draft seal where the door meets the stop on sides
and top. Section 1005.8.1. Please create a door schedule or show on the plans
all doors required to be fire rated.
Show rated corridors, lobbies, reception or foyers cross-hatched on the floor plans.
Provide a completearchitectural section of the corridor, or exterior exit balcony,
showing all fire-resistive materials and details of construction for all floors, walls,
ceiling and all penetrations. Section 1005.7.
If a room with an exhaust fan has a door opening into a rated corridor, show how
makeup air will be provided to the room. The door cannot be undercut, nor can a
louver in the door be provided. Section 1005.8.1.
If building exceeds two stories and has an elevator opening into a rated corridor,
show how the smoke and draft control provision of Section 1005.8.1 will be met.
Either provide a separated elevator lobby or a second door at the elevator entry
meeting the provision. Section 1005.10. Note if the Elevator Lobby is protected by
the doors at each end of the corridor, the fire rated corridors must not exit through
this area.
Provisions in Chapter 7 require special treatment of penetrations at fire-resistive
assemblies. Provide typical details on the plans showing how the fire-resistive
integrity will be maintained at the following conditions (Include the manufacturers'
names and ICBO numbers (or equal) for any sealant):
THROUGH-PENETRATIONS (through the entire assembly):
Fire-resistive bearing walls and/or walls requiring protected openings shall have
penetrations protected with through-penetration fire stops having an F-rating,
T-rating or complying with UBC Standard 7-1, depending on their locations, sizes
and combustibility.
Fire resistive floor/ceiling assemblies shall have penetrations protected with
through-penetration fire stops having and F-rating, T-rating or complying with UBC
Standard 7-1, depending on their sizes, combustibility and whether the penetrations
are in walls above.
Carlsbad 98-621
3/11/98
MEMBRANE-PENETRATIONS (through only one side of an assembly):
Fire-resistive walls (whether bearing or not and whether requiring fire protected
openings or not) shall have penetrations protected with membrane-penetration fire
stops having an F-rating or complying with UBC Standard 7-1, depending on their
size and combustibility. Limited steel electrical outlet boxes (not exceeding 16 sq.
in., nor more than 100 sq. in. for any 100 sq. ft. of wall) require no protection.
Fire-resistive ceilings shall have no penetrations, except for noncombustible
sprinkler pipes and steel electrical outlet boxes as described above.
NOTE: The plans should indicate the various fire-stop ratings required for all
penetrations.
Provide a note on the plans stating: "Penetrations of fire-resistive walls, floor--
ceilings and roof-ceilings shall be protected as required in UBC Sections 709 and
710."
ELECTRICAL
Submit plan showing location of all panels.
Submit panels schedules.
Submit electrical load calculations.
Indicate existing main service size.
Indicate existing total main service load.
Indicate new additional loads.
Indicate wiring method, i.e. EMT, metal flex. Per the City of Carlsbad request please
make a note on the plans that "No AC cable or Romex wiring methods are
allowed".
Show exit signs on the electrical lighting plan(s). As per Sections 1012 and 1013 of
the 1994 UBC, provide two sources of power to exit signs and exit illumination.
Provide multiple switch lighting controls per Title 24, Part 6.
MECHANICAL
Show the size, location and type of all heating and cooling appliances or systems.
Provide mechanical ventilation in all rooms capable of supplying outside air at a
minimum rate of 15 cubic feet per minute per occupant. UBC, Section 1202.2.1
S
Carlsbad 98-621
3/11/98
Provide mechanical plans showing existing and proposed HVAC equipment, ducts
and access to equipment.
Detail access and working clearances to HVAC equipment.
Detail ladder access to .roof mounted HVAC equipment.
Detail disposal of main condensate -drainage from air conditioning units. (UMC
Section 310)
Detail overflow (secondary) condensate discharge from air conditioning units that
are in a ceiling space, to a readily observable location. (UMC Section 310.1.1.)
Fire rated corridors are not to be used to convey air to or from rooms. UMC Section
601.1.1.
PLUMBING
Provide complete plumbing pJàns, including:
Complete drain, waste and vent plans.
Provide gas line plans and calculations, showing pipe lengths and gas demands.
UPC Section 1217.0
Provide complete water line sizing calculations, including the water pressure,
pressure losses, water demands, and developed pipe lengths. UPC Section 610.0
Show water heater size, type and location on plans. UPC, Section 501.0
Show that water heater is adequately braced to resist seismic forces. Provide two
straps (one strap at top 1/3 of the tank and one strap at bottom 1/3 of the tank).
UPC, Section 510.0
Show P & T valve on water heater and detail drain line route from P & T valve to the
exterior. UPC Section 608.5.
Show 1/4" per 12" slope on drain and waste lines. UPC Section 708.0.
ENERGY
NOTE: Plans submitted after July 1, 1995 must comply with the new energy
standards.
Provide plans, calculations and worksheets to show compliance with current energy
standards.
Carlsbad 98-621
3/11/98
Provide complete energy designs for the proposed changes in envelope, lighting,
and mechanical systems. Provide the completed ENV-, LTG-, and MECH- forms
showing energy compliance.
On the plans clearly show the wall and roof insulation locations, thickness, and R-
values, as per the energy design.
The completed and signed ENV-1, LTG-1 and MECH-1 forms must be imprinted on
the plans.
DEPARTMENT OF STATE ARCHITECT NON RESIDENTIAL
TITLE24 DISABLED ACCESS REQUIREMENTS
51.The following disabled access items are taken from the 1995 edition of California
Building Code, Title 24. Per Section 101.17.11, all publicly and privately funded
public accommodations and commercial facilities shall be accessible to persons
with disabilities as follows:
Any building, structure, facility, complex, or improved area, or portions thereof,
which are used by the general public.
Any sanitary facilities which are made available for the public, clients, or employees
in such accommodations or facilities.
Any curb or sidewalk intended for public use that is constructed with private funds.
All existing accommodations when alterations, structural repairs or additions are
made to such accommodations.
NOTE: All Figures and Tables referenced in this checklist are printed in the
California Building Code, Title 24.
REMODELS, ADDITIONS AND REPAIRS
52. When alterations, structural repairs or modifications or additions are made to an
existing building, that building, or portion of the building affected is required to
comply with all of the requirements for new buildings, per Section 11 34B.2. These
requirements apply only to the area of specific alteration, repair or addition and
shall include:
53; A primary entrance to the building and the primary path of travel to the area in
question, and include the following items which serve the area in question:
Sanitary facilities.
Drinking fountains.
Public telephones.
Carlsbad 98-621
3/11/98
54. If an unreasonable hardship finding is granted, priority should be given to those
elements that will provide the greatest access, per Section 113413.2.1 Exception #1.
The order of priority shown below should be followed:
An accessible entrance.
An accessible route of travel.
At least one accessible restroom for each sex.
Accessible telephones.
Accessible drihking fountains.
When possible, additional accessible elements such as parking, storage and
alarms.
Please show that the reception desk has a disabled accessible areas of between
28" and 34" in height and for a length of 36" minimum.
Please show on detail 1/T24 that the door does not encroach into the inscribed
circle as per Title 24 requirements. Change the swing of the door.
To speed up the review process, note on this list (or a copy) where each correction
item has been addressed, i.e;, plan sheet, note or detail number, calculation page,
etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly describe
them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes L3 No L11
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 619/560-1468,
to perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Mike Puckett at Esgil Corporation.
Thank you.
Carlsbad 98-621
3/11/98
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 98-621
PREPARED BY: Mike Puckett DATE: 3/11/98
BUILDING ADDRESS: 1902 Wright P1. #300
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: V-lhr
BUILDING PORTION • BUILDING AREA
(ft.2)
VALUATION
MULTIPLIER
VALUE
($)
Tenant Improvement 16,580 26.00 431,080.00
Air Conditioning
Fire Sprinklers S S
TOTAL VALUE 431,080.00
I 1991 UBC Building Permit Fee fl Bldg. Permit Fee by ordinance: $ 1801.50
1991 UBC Plan Check Fee fl Plan Check Fee by ordinance: $ 1170.97
Type of Review: D Complete Review LI Structural Only LI Hourly
LI Repetitive Fee Applicable LI Other:
Esgil Plan Review Fee: $ 936.78
Comments:
Sheet I of I
macvalue.doc 5196
PERMIT NUMBER
ADDRESS
DATE
PLANNING/ENGINEERING APPROVALS
RESIDENTIAL IMPROVEMENT
RESIDENTIAL ADDITION MINOR PLAZA
(<$10,000.00)
CARLSBAD COMPANY STORES
VILLAGE FAIRE
COMPLETE OFFICE BUILDING
OTHER -0 —o,qc2e
PLANNER WAIM EW~ DATE
ENGINEER DATE/zi
Do/MIsforms/PlannIng Engineering Approvals
0 N
=s A 204--
=$ 7P
ENGINEERING DEPARTMENT
FEE CALCULATION WORKSHEET
0 Estimate based on unconfirmed information from applicant.
Calculation based on building plancheck plan submittal.
\
Address: I qô P Bldg. Permit NO.ce qR06 OZ
Prepared by:tT)k Date: Checked by: Date:
!)L' CALCULATIONS: List types and square footages for all uses. 90 cf
Types 'of Use: Sq. Ft./Units./6 5!O EDU's: 33
ADT CALCULATIONS: List types and square footages for all uses. 33d
Types of Use: _______ Sq. Ft./Units: /, 5 c?O7z ADT's:
-
cz
FEES REQUIRED:
WITHIN CFD: 0 YES (no bridge & thoroughfare fee, reduced Traffic Impact Fee)
o 1. PARK-IN-LIEU FEE PARK AREA:
FEE/UNIT: X NO. UNITS:______
4. TRAFFIC IMPACT FEE
ADT's/UNITS: X FEE/ADT: ?
pBR1DGE AND THOROUGHFARE FEE
AOl's/UNITS: X FEE/ADT:_________
CILITIES MANAGEMENT FEE ZONE:_________ a46'
UNIT/. FT. X FEE/SQ.FT./UNIT: $ \J.4.U(
U"5.,—SEWER FEE
PERMIT No.
EDU's: 5•1 ? X FEE/EDU:JcPc -1 =s /0) 743
BENEFIT AREA: DRAINAGE BASIN:_______
EDU's: X FEE/EDU:________
Wk. DRAINAGE FEES PLDA : HIGH /LOW
ACRES:
SEWER LATERAL ($2,500)
TOTAL OF ABOVE FEES*: $
*NOTE: This calculation sheet is NOT a complete list of all fees which may be due.
Dedications and Improvements may also be required with Building Permits.
P:OOCS\MISFORMSWEE CALCULATION WORKSHEET REV 01/28/97
X FEE/AC:__________
=$
::
f Carl 98074
- Fire Department • Bureau of Prevention
Plan Review: Requirements Category: Building Plan Check
Date of Report:Thursday, April 16, 1998 Reviewed by: -
Contact Name JillonAugustine
Address 9265 Activity Rd Ste 106
City, State San Diego CA 92126
g. DDept. 0. CB980621 Planning No. -
Job Name Rubio's Baja Grill
Job Address 1902 Wright Ste. or Bldg. No. 300
Approved - The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
O Disapproved - Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards: Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1st 2nd 3rd
Other Agency ID
CFD Job# _98074 File#__________
2560 Orion Way 0 Carlsbad, California 92008 0 (619) 931-2121
I Hazardous Materials
SAN DIEGO REGIONAL
HAZARDOUS MATERIALS QUESTIONNAIRE °c C
Management Division cssuvv u ass ails.
Business Name Contact Person - Telephone
0 r- .- - R%c-4A-(Z-0 Lh. i,g q i-is ti 0
Mailing Address City State Zip Plan Filet
c5 PL 5. b
Site Address City State Zip Plan Filet
Qo?&f
PART I: FIRE'DEPARTMENT- HAZARDOUS MATERIALS MANAGEMENT DIVISION: OCCUPANCY CLASSIFICATION
Indicate by circling the item, whether your business will use, process, or store any of the following hazardous materials. If any oi the items are
circled, applicant must contact the Fire Protection Agency with jurisdiction prior to plan submittal.
Explosive or Blasting Agents 4. Flammable Solids 7. Pyrophorics 10. Cryogenics 13. Corrosives
Compressed Gases S. Organic Peroxides S. Unstable Reactive. 11. Highly Toxic or Toxic Materials 14. Other Health Hazards
Flammable or Combustible Liquids S. Oxidizers 9. Water Reactive. 12. Radioactives
If the answer to any of the questions is yes, applicant must contact the County of San Diego Hazardous Materials Management
Division, 1255 Imperial Avenue, 3rd Floor, San Diego, CA 92186-5261. Telephone (819) 338-2222 prior to the issuance of a
building permit.
FEES MAY BE REQUIRED
Yes No
Is your business listed on the reverse side of this form?
Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities equal to or greater than 55 gallons.
500 pounds. 200 cubic feet or carcinogens/reproductive toxins in any quantity?
4.:/WIlI your business use an existing or install an underground storage tank?
S. Will your business store or handle Acutely Hazardous Materials?
OFFICE USE ONLY
RMPP Exempt
Date Initials
RMPP Required
Date Initials
RMPP Completed
Date Initials
PART III: SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT
If the answer to any of the questions is yes, applicant must contact the Air Pollution Control District, 9150 Chesapeake Drive, San Diego, CA 92123.
Telephone (619) 694-3307 prior to the issuance of a building permit.
YES NO
iII the intended occupant install or use any of the equipment listed on the Listing of Air Pollution Control District Permit Categories, on the
verse side of this form?
(ANSWER ONLY IF QUESTION 1 IS YES.) Will the subject facility be located within 1,000 feet of the outer boundary of a school (K through
1 2) as listed in the current Directory of School and Community College Districts, published by the San Diego County Office of Education and
the current California Private School Directory, compiled in accordance with provisions of Education Code Section 331907
Briefly describe nature of the intended business activity:
OfF.c—--
Name of Owner or Authorized Agent:
1YLE
Signature of Owner or Authorized Agent: I declare under penalty of perjury that to the best of my knowledge and belief the responses made herein are true
and correct.
LAt \ . Date:
Do not write below this line
FIRE DEPARTMENT OCCUPANCY CLASSIFiCATION:_____________________________________________________________________
BY: Date:_______________________________________
EXEMPT FROM PERMIT REQUIREMENTS
COUNTY-HMMD APCD
APPROVED FOR BUILDING PERMIT BUT NOT OCCUPANCY
COUNTY-HMMD APCD
APPROVED FOR OCCUPANCY
COUNTY-HMMD APCD
Eaviroamcotal Hcalth Services . Coiiy of San Diego
DHS:HM-9171 (6/92) Dcpatt of Health Seevicca
UST OF BUSINESSES WHICH REQUIRE REVIEW AND APPROVAL FROM COUNTY OF SAN DIEGO 'HEALTH DEPARTMENT
THE HAZARDOUS MATERIALS MANAGEMENT DIVISION
AUTOMOTIVE CHEMICAL HANDLING OTHERS AND MISCELLANEOUS
Battery Manufacturing/Recycling
Boat Yard
Car Wash
Dealership Maintenance and Paint
Machine Shop
Painting
Radiator Shop
Rental Yard Equipment
Repair, Preventive Maintenance
Repair, Major Overhaul.
Transportation Services
Wrecking and Recycling
METAL WORKING
Anodizing
Chemical Milling/Etching
Finish-Coating, Painting
Flame Spraying
Foundry
Machine Shop-Drilling, Lathes, Mills
Metal Plating
Metal Prepping/Chemical Coating
Precious Metal Recovery
Sand Blasting, Grinding
Steel Fabricator
Wrought Iron Manufacturing
Agricultural Suppliers/Distributors
Chemical Suppliers/Distributors
Chemical Manufacturer
Coatings/Adhesives
Compressed Gas Supplier/Distributor
Dry Cleaning
Fiberglass/Resin Applications
Gas Station
Industrial Laundry
Laboratories
Laboratory Suppliers/Distributors
Oil and Fuel Bulk Supply
Pesticide Operator/Distributor
Photographic Processing
Pool Supplies/Maintenance
Printing/Blue Printing
Road Coatings
Swimming Pool (Gas Chlorination
Systems Only)
Toxic Gas Handler
Toxic Gas Mfg.
ELECTRONICS
Electronics Components Mfg
Electronics Assembly and Sub Assembly
Printed Circuit Board Mfg.
Asphalt Plant
Chiropractic Offices
Co-Generation Plant
Dental Clinic/Offices
Dialysis Centers
Frozen Food Processing Facilities
Government Agencies
Hazardous Waste Haulers
Hospitals/Convalescent Homes
Laboratories, Biological Laboratories
Medical Clinics/Offices
Public Utilities
Rock Quarry
Veterinary Clinic/Hospitals
Wood/Furniture Manufacturer/Refinishing
Ship Repair/Construction
AEROSPACE
Aerospace Industry
Aircraft Manufacturing
Aircraft Maintenance
NOTE: THE ABOVE LIST INCLUDES BUSINESSES WHICH TYPICALLY USE, STORE, HANDLE AND DISPOSE OF HAZARDOUS
SUBSTANCES. ANY BUSINESS NOT INCLUDED ON THIS LIST WHICH HANDLES, USES OR DISPOSES OF HAZARDOUS
SUBSTANCES MAY STILL REQUIRE HAZARDOUS MATERIALS MANAGEMENT DIVISION (HMMD) REVIEW OF BUSINESS PLANS.
FOR MORE INFORMATION CALL. (819)338-2222.
LISTING OF AIR POLLUTION CONTROL DISTRICT PERMIT CATEGORIES
Businesses which include any of the following operations or equipment will require clearance from the Air Pollution Control District.
CHEMICAL
47-Organic Gas Sterilizers
32-Acid Chemical Milling
33-Can & Coil Manufacturing
44-Evaporators, Dryers & Stills
Processing Organic Materials
24-Dry Chemical Mixing &
Detergent Spray Towers
35-Bulk Dry Chemical Storage
COATINGS & SURFACE PREPARATION
01-Abrasive Blasting Equipment
27-Coating & Painting
37-Plasma Arc & Ceramic
Deposition Spray Booths
38-Paint, Stain & Ink Mfg.
METALS
18-Metal Melting Devices
19-Oil Quenching & Salt Baths
32-Hot Dip Galvanizing
39-Precious Metals Refining
25-Gasoline & Alcohol Bulk Plans & Terminals
25-Intermediate Retuelers
26-Gasoline & Alcohol Fuel Dispensing
COMBUSTION
34-Piston Internal-Combustion Engines
13-Boilers & Heaters 0 Million
Btu/Hr. or larger)
13-Gas Turbines, and Turbine Test
Calls & Stands
14-Incinerators & Crematories
15-Bum Out Ovens
1 6-Core Ovens
ELECTRONICS
29-Solder Levelers
29-Hydrosqusegee.
42-Electronic Component Manufacturing
FOOD
12-Fish Canneries
12-Smoke Houses
50-Coffee Roasters
35-Bulk Flour & Powdered Sugar Storage
ROCK AND MINERAL
04-Hot Asphalt Batch Plants
05-Rock Drills
07-Sand Rock & Aggregate Plants
08-Concrete Batch, CTS, Concrete
Mixers, Mixers & Silos
10-Brick Manufacturing'
SOLVENT USE
28-Vapor & Cold Degreasing
30-Solvent & Extract Driers
31 Dry Cleaning
03-Asphalt Roofing Kettles and Tankers
46-Reverse Osmosis Membrane Mfg.
51-Aqueous Waste Neutralization
1 1-Tire Buffers
17-Brake Debonders
23-Bulk Grain & Dry Chemical Transfer &
Storage
45-Rubber Mixers
48-Landfill Gas Flare or Recovery Systems
21-Waste Disposal & Reclamation Units
36-Grinding Booths & Rooms
40-Asphalt Pavement Heaters
43-Ceramic Slip Casting
41-Perlite Processing
40-Cooling Towers-Registration Only
ORGANIC COMPOUND MARKETING {GASOUNE. ETC.)
NOTE: OTHER EQUIPMENT NOT LISTED HERE THAT IS CAPABLE OF EMITTING AIR CONTAMINANTS MAY REQUIRE AN AIR
POLLUTION CONTROL DISTRICT PERMIT. IF THERE ARE ANY QUESTIONS, CONTACT THE AIR POLLUTION CONTROL
DISTRICT AT (619) 694-3307.
Environment, l Health Services County of San Diego
DHS:HM-9171 (6/92) ' Depatect of Health Services
- - I '•
- Ba.lance'.,,D1e.:\ \
i-7 -. Units \Fe/Un1t / \ \r
* > i.Q900 \7
tAA
BUILDING PERMIT
09/16/98 12:05
Page 1 of 1
Job Address: 1902 WRIGHT PL Suite:
Permit Type: PLAN CHECK REVISION
Parcel No: Lot#:
Valuation: 0
Occupancy Group: Reference#:
Description: REVISION-FULL SET REVISION
RUBIOS BAJA GRILL
Appl/Ownr : AUGUSTINE MILLER 619
1905 MISSION CLIFF DRIVE
SAN DIEGO CA 92116
PCR No: PCR98141
Project No: A9800794
Development No:
300
1165 09/16/98 0001 01 02
Construction TytTEW 109.00
Status: ISSUED
Applied: 08/06/98
Apr/Issue: 09/16/98
Entered By: JM
296-3615
*** Fees Required *** Fees Coilected & Credits
p-Th
_____
___________________ Adjustments: .100 L~4o~~ta'4C edits:
Total Fees: 109<00 Total Pen:
Fee description ----------------
Plan Check Revision E
.00
.00
109.00
Ext fee Data ---------------
109.00
FINAL Al OVAL
INSP._________ 01
CLEARANCE___________________
CITY OF CARLSBAD
2075 Las Palmas Dr., Carlsbad, CA 92009 (619) 438-1161
PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
2075 Las Palmas Dr., CarlsbalA A 9009
438-1 10161 46v
FOR OFFICE USE ONLY
PLAN CHECK NO..,p/?,yq/
EST. VAL.
Plan Ck. Deposit
Validated By
Date
Address (includ&BId6/Suite'#) / - ' Business Name (at this iddrssJ -
Legal Description Lot No. ISubdivision Name/Number Unit No. Phase No. Total # of units
Assessor's Parcel # Existing Use Proposed Use
Description of W6 SQ. FT. #of Stories # of Bedrooms - # of Bathrooms
OA fertjm .; / )
Name I Address City State/Zip TelephoØ'# Fax #
V2L3_ Age'it for çontractor. Downer Oiem for Owne ''
Name Address City State/Zip Tephone #
4. PROPERTY OWNER ' ..,, .
Name Address City State/Zip Telephone #
5: CONTRACTOR COMPANY NAME
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
(Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars 1$500fl.
Name Address City State/Zip Telephone #
State License # License Class City Business License #
Designer Name Address City State/Zip Telephone
State License #
- "
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one f the following declarations: o
0 I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
C3 I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued. My worker's compensation insurance carrier and policy number are:
-
Insurance company - Policy No. Expiration Date__________________
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS ($1001 OR LESS)
o CERTIFICATE OF EXEMPTION: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as
to become subject to the Workers' Compensation Laws of California.
WARNING: Failure to secure workers' compensation coverage Is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred
thousand dollars ($100,000), In addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, Interest and attorney's fees.
SIGNATURE DATE
lit WNERBuILDERECLARA1oN ': *
I hereby affirm that I am exempt from the Contractor's License Law for the following reason:
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is
sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
0 I am exempt under Section - Business and Professions Code for this reason:
I personally plan to provide the major labor and materials for Construction of the proposed property improvement. 0 YES ONO
I (have / have not) signed an application for a building permit for the proposed work.
I have contracted with the following person (firm) to provide the proposed Construction (include name / address / phone number / contractors license number):
I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone
number / contractors license number): -
I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (includee-name / address / phone number /type
of work): .
PROPERTY OWNER SIGNATURE DATE -
COTErHISSECtIOIF0R NoArREFDENrJAL UrwrNoEItS ONLY! t '1 "J
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management, and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? 0 YES 0 NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district orair quality management district? 0 YES 0 NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school Site? 0 YES 0 NO
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
8 CpNSTRUCT1ON LENDING AGENCYJ , 4.
I hereby affirm that there is a construction lending agency for the performance of the work for which this permit is issued (Sec. 30970) Civil Code).
LENDER'S NAME LENDER'S ADDRESS__________________________________________________________
7 r -
I certify thét I have read the appliCation and State that the above information is correct and that the information on the plans is accurate. I agree to comply with all
City ordinances and State laws relating to building construction. I hereby authorize representatives of the Cit' of Carlsbad to enter upon the above mentioned
property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0 deep and demolition or construction of structures over 3 Stories in height.
EXPIRATION: Every permit issued by the Building Official'under the provisions of this Code shall expire by limitation and become null- and void if the building or
work authorized by such permit is not commenced within 365 days from the date of such permit or if the building or work authorized by such permit is suspended
or abandoned at any time after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code).
APPLICANT'S SIGNATURE - DATE
WHITE: File YELLOW: Applicant PINK: Finance
TRANSMITTAL
AUGUSTINE
MILLER
DESIGN
STUDIO
TO City of Carlsbad Building Dept ATTENTION Mike Peterson
2075 Las Palmas Drive
Carlsabd, CA 920009 DATE 8/6/98
TEL 760.438.1161
JOB NO. 970017
FROM Jillon Augustine PROJECT Rubios-Permit #CB98062 1
DESCRIPTiON
(4) Sets Revised Construction Documents
REMARKS
Mike: Per our telephone conversation. Rubio's plans have had substantial revisions to the space plan. I do not
anticipate any issues with exiting, as we have actually reduced the overall occupant load and eliminated
corridors. Because of the space plan revisions all sheets have been revised, including Electrical Mechanical
& Plumbing. There are no "deltas" or clouds on this set as we have issued it as a full revision, please see
the note on sheet TS in the lower right corner. Please call with an estimated time of completion, so that we
can move forward with the tenant improvements. I appreciate your help and look forward to hearing from
you soon. Th
PLEASE CALL UPON RECEIVING YES) NOD
COPY TO FILE
Linda Tr. Rubios, via fax 619.452.0181
John Couvillion, Peniiss, via fax 760.438.0046
FaN 819.296.3615 FAX 619.298.4630
EsGil Corporation
In Partnership with government for Building Safety
DATE: 8/27/98
JURISDICTION: Carlsbad
PLAN CHECK NO.: PCR 98-141(Orig 98-621) SET: I
PROJECT ADDRESS: 1902 Wright Place
PROJECT NAME: Rubio's Restaurant Office TI/Revision
U APPLICANT
JU RI S.
0 PLAN REVIEWER
U FILE
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified in Remarks below are resolved and checked by building
department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
LI The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
I Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: 8 12--7 1%(by:) Fax #:
Mail Telephone Fax In Person
I REMARKS: Please have the person that prepared the plans print name and si Zneach
sheet of the plans. Please have the designer and the documentation author of the LTG
and MECH forms sign and date the LTG-1 àndVlECH-1 documents on the plans.
Building Department to please verify the accesibilty waiver and approval on detail
1f T24.
By: Mike Puckett Enclosures:
Esgil Corporation
E GA D CM U EJ L1 PC 8/10/98 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (619) 560-1468 • Fax (619) 560-1576
Carlsbad PCR 98-141(Orig 98-621)
8/27/98
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: PCR 98-141(Orig 98-621)
PREPARED BY: Mike Puckett DATE: 8/27/98
BUILDING ADDRESS: 1902 Wright Place
BUILDING OCCUPANCY: B TYPE OF CONSTRUCTION: Vlhr
BUILDING PORTION BUILDING AREA (ft. 2) VALUATION
MULTIPLIER
VALUE
($)
Plan Check Revision No Change See Comments
Air Conditioning
Fire Sprinklers
TOTAL VALUE See Comments
199 UBC Building Permit Fee Bldg. Permit Fee by ordinance: $
199 UBC Plan Check Fee F1 Plan Check Fee by ordinance: $
Type of Review: El Complete Review Structural Only fl Hourly
Fj Repetitive Fee Applicable fl Other:
Esgil Plan Review Fee: $ 87.15
Comments: Esgil Fee = lhr at $87.15/hr = $87.15
Sheet 1 of 1
macvalue.doc 5196
utvof Carlsbad 98074
- Fire Department 0 Bureau of Prevention
Plan Review: Requirements Category: Building Plan Check
Date of Report:Tuesday, August 18, 1998 Reviewed by:____________________
Contact Name Jillon Augustine
Address 9265 Activity Rd Ste 106
City, State San Diego CA 92126
BJg-DeptrNCB1iT1 Planning No.
Job Name Rubio's Baja Grill
Job Address 1902 Ste. or Bldg. No. 300
CK Approved - The item you have submitted for review has been approved. The approval is
based on plans; information and/or specifications provided in your submittal;
therefore any changes to these items after this date, including field modifica-
tions, must be reviewed by this office to insure continued conformance with
applicable codes. Please review carefully all comments attached, as failure
to comply with instructions in this report can result in suspension of permit to
construct or install improvements.
El Disapproved - Please see the attached report of deficiencies. Please make corrections to
plans or specifications necessary to indicate compliance with applicable
codes and standards. Submit corrected plans and/or specifications to this
office for review.
For Fire Department Use Only
Review 1st 2nd 3rd
Other Agency ID
CFD Job# 98074 File#___________
2560 Orion Way 41 Carlsbad, California 92008 a (619) 931-2121