HomeMy WebLinkAbout1190 TAMARACK AVE; ; CBR2017-2521; Permit(-City of
Carlsbad
Print Date: 08/19/2019 Permit No: CBR2017-2521
Job Address: 1190 Tamarack Ave
Permit Type: BLDG-Residential Work Class: Addition Status: Closed - Expired
Parcel No: 2054302100 Lot #: Applied: 10/20/2017
Valuation: $42,669.76 Reference #: Issued: 03/23/2018
Occupancy Group: Construction Type Permit
Finaled:
# Dwelling Units: Bathrooms: Inspector: AKrog
Bedrooms: Orig. Plan Check U: Final
Plan Check U: Inspection:
Project Title:
Description: EKERLING: 301 SF ADDITION TO BACK OF HOME/ ADD AC
Applicant: Owner: Co-Applicant:
VERNON MCCASLIN JOANNE EKERLING VERNON MCCASLIN
1025 Olive St JOANNE EKERLING 1025 Olive St
SANTA BARBARA, CA 93101-1408 10860 Alta View Dr SANTA BARBARA, CA 93101-1408
818-642-4490 STUDIO CITY, CA 91604 818-642-4490
323-650-5011
FEE AMOUNT
BUILDING PERMIT FEE ($2000+) $361.20
BUILDING PLAN CHECK FEE (BLDG) $252.84
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL $41.00
GREEN BUILDING STANDARDS PLAN CHECK & INSPECTION $170.00
MECHANICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL $42.00
PLUMBING BLDG RESIDENTIAL NEW/ADDITION/REMODEL $62.00
S61473 GREEN BUILDING STATESTANDARDS FEE $2.00
STRONG MOTION-RESIDENTIAL $5.55
SWPPP INSPECTION FEE TIER 1 - Medium BLDG $238.00
SWPPP PLAN REVIEW FEE TIER 1 - MEDIUM $56.00
Total Fees: $ 1,230.59 Total Payments To Date : $ 1,230.59 Balance Due: $0.00
Please take NOTICE that approval of your project includes the 'Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction.. You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees /exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Building Division
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-2700 1 760-602-8560 f I www.carlsbadca.gov
,ç Building Permit Application Plan Check NofI3R2O17 7J5 2.1
%_AL UI 1635 Faraday Ave., Carlsbad, CA 92008 Est. Value Ph: 760-602-2719 Fax: 760-602-8558 Cdlsbad email: building@carlsbadca.gov Plan Ck. Deposit
www.carIsbadca.ov
Date 10/20/11
JOB ADDRESS SUITE#/SPACE#/UNIT# APN - - -
CVPROJLFCT# LOT# [PHASE# #0FUNITS I #BEDROOMS #BATHROOMS I TENANT BUSINESS NAME CONSTR.TYPE OCC.GROUP
DESCRIPTION OF WO K: Include Square Feet of AffectedArea(s)
30' c
EXISTING USE I PROPOSED USE I GARAGE (SF) PATIOS (SF) DECKS (SF) IFIREPLACE IAIRCONDITIONING..IRESPRINKLERS
YES #_N0"t YES 0 NO1 YES 0 NO
APPLIgANT NAME (Primary Contact) PR,2ggTY OWNER NAME — j'1Zs i ADDRESS ADDRESS ADDIESS
CITY
41,17;,
STATE ZIP CITY STATE ZIP 4 F3 ' ' '
PHONE FAX PHONE FAX
EMAIL
I. EMAIL
DESIGN PROFESS1NAL NAME CONWACTOR BUS NAME W -r Zic- Vcri',i'o,'/ L1 ADDRESS g7g1 iiow//,//t 7>
ADDRESS
/2/,L4 LZ3
CITY STATE ZIP f13/5,q 14-
CITY STATE ZIP 3?Zi/ 7 PHONE I
s
FAX PHONE
?'9O
FAX
EMAIL EMAIL a -
STATE LIC. # STATE LiC.#
I
I ci.Ass I CITY BUS LIC #
(Sec. (UJ1.b business and Proressions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any Structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License LawiChapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($5001).
90030 ®O®&J
Workers' Compensation Declaration: thereby affirm under penalty of perjury one of the following declarations:
IJ I have and will maintain a cehificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
IJ I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued. My workers' compensation insurance carrier and policy
number are: Insurance Co. Policy No. Expiration Date
This section need not be completed if the permit is for one hundred dollars ($100) or less.
lP'"ertiricate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees.
CONTRACTOR SIGNATURE []AGENT DATE
®°O1®
thereby affirm that tam exempt from Contractor's License Law for the following reason:
C3 i, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 704.4, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
O I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
O I am exempt under Section ______________Business and Professions Code for this reason:
I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0 Yes 0 No
I (have / have not) signed an application for a building permit for the proposed work.
I have contracted with the following person (firm) to provide the proposed construction (include name address / phone! contractors' license number):
I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name / address / phone / contractors' license number):
I will provide some of the work, bull have contracted (hired) the following persons to provide the work indicated (include name! address / phone / type of work):
PROPERTY OWNER SIGNATURE DAGENT DATE
0911Pt@J0 I730 1iO® 0003 000-0300000906)(b001EO1® PONIM ®J?
Is the applicat or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 or 25534 of the
Presley-Tanner Hazardous Substance Account Act? 0 Yes 0 No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 Yes 0 No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 Yes 0 No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
€®3W?O®&J &JO@ @O13S
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lenders Name Lenders Address
Oi0 (&090(70®
I certifythat I have read the application and state that the above information is cenectand thatthe information on the.plans is accurate. I agree to cemplywith all City ordinances and State laws retatingto building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 50' deep and demolition or construction of structures over 3 stories in height
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void tithe building or work authorized by such permit is not commenced within
180 days from the date of such permit or tithe buildi rwork authorized by such permit is suspended or abandoned at any time after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code).
.APPLICANT'S f.:::'::_ 4,/ DATE 2 ETh •- /
/
Prmit Type: BLDG-Residential Application Date: 10/20/2017 Owner: JOANNE EKERLING
Work Class: Addition Issue Date: 03/23/2018 Subdivision: WOODLAND HEIGHTS
Status: Closed - Expired Expiration Date: 05/06/2019 Address: 1190 Tamarack Ave
Carlsbad, CA 92008
IVR Number: 7104
Scheduled Actual Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete Date Start Date
10/29/2018 10/29/2018 BLDG-16 Insulation 074427-2018 Passed Andy Krogh Complete
11/07/2018 11/07/2018 BLDG-17 Interior 075385-2018 Passed Andy Krogh Complete
Lath/Drywall
August 19, 2019 Page 2 of 2
Permit Type: BLDG-Residential Application Date: 10/20/2017 Owner: JOANNE EKERLING
Work Class: Addition Issue Date: 03/23/2018 Subdivision: WOODLAND HEIGHTS
Status: Closed - Expired Expiration Date: 05/06/2019 Address: 1190 Tamarack Ave
Carlsbad, CA 92008
IVR Number: 7104
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete
05/0812018 05/08/2018 BLDG-11 057303.2018 Passed Andy Krogh Complete
Foundation/Ftg!Pier
s (Rebar)
BLDG-12 Steel/Bond 057304-2018 Passed Andy Krogh Complete
Beam
08/14/2018 08/14/2018 BLDG-22 066819-2018 Partial Pass Andy Krogh Reinspection Incomplete
Sewer/Water Service
BLDG-33 Service 066820-2018 Passed Andy Krogh Complete
Change/Upgrade
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Temp service permanent base Yes
BLDG-84 Rough 066818-2018
Combo(14,24,34,44)
Checklist Item
BLDG-Building Deficiency
BLDG-14
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout
BLDG-34 Rough Electrical
BLDG-44
Rough-Ducts-Dampers
09/25/2018 09/25/2018 BLDG-13 Shear 070950-2018
Panels/HD (Ok to
wrap)
Checklist Item
BLDG-Building Deficiency
Failed Andy Krogh
COMMENTS
Not ready
Failed Andy Krogh
COMMENTS
Requires additional straps at plate breaks,
missing stamp sheet s-2
Reinspection Complete
Passed
No
No
No
No
No
Reinspection Complete
Passed
No
BLDG-IS 070951-2018 Passed Andy Krogh Complete
Roof/ReRoof (Patio)
10/24/2018 10/24/2018 BLDG-lB Exterior 073996.2018 Passed Andy Krogh Complete
Lath/Drywall
10/25/2018 10/25/2018 BLDG-84 Rough 074133-2018 Passed Andy Krogh Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-14 V 0 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
0 BLDG-34 Rough Electrical Yes
V BLDG-44 Yes
Rough-Ducts-Dampers V
August 19, 2019 0 Page 1 of 2
Carlsbad CBR20 17-2521
01/04/2018
SPECIAL INSPECTION FEB 624ST,pment Services
CITY OF AGREEMENT CITY OF CPRLSB Dl0h1 Faraday Avenue
CARLSBAD B-45 BUILDING DIVISI) 760-602-2719
www.carlsbado.gov
In accordance with Chapter 17 of the California Building Code the following must be completed when work being performed
requires special Inspection, structural observation and construction material testing.
'roject/Permit: _.. .. - Project Address J/.9 i/ 41?lfr-/< itve C..4 tL gi4ô, C/sr
THIS SECTION MUST BE COMPLETED BY THE PROPERTY OWNERIAUTHORIZED AGENT. Please check if you are Owner-Builder
J. (It you checked as owner builder you must also complete Section B of this agreement.)
Name, (Please Prim) JNAL/ _ qL/,I&. --
('iI 1
Mailing AddressJ J (oQ i (.r-4—.V/ ew - A/-~_:, iTO ( £1
Email: /?I/At.. PIC. .,\[er Phone:3. ? --
I am: Alperty Owner UProperty Owner's Agent of Record UArchitect of Record UEngirieer of Record
State of California Registration Number // 4 Expiration Date:__________________
AGREEMENT: I, the undersigned, declare under penalty of perjury under the laws of the State of California, that I have read,
understand, acknowledge and promise to comply with the City of Carlsbad requirements for special inspections, structural
observations, construction materials testing and off-site fabrication of building components as prescribed in the statement of
special inspections noted on the approved plans and, as required by the California Building Code.
Date: _L I4...JLi
U 64
CONTRACTOR'S STATEMENT OF RESPONSIBILITY (07 CBC, Ch 17, Section 1706). This section must be completed by the
contractor I builder / owner-builder,
Contractor's Company Name: ')_4. Please check If you are Owner-Builder,'!
Name: (Please p,Int) '.-i..J_ 1.' I
Mailing Address:)2s
Email: C2, .L,s. Phone.J2Q
State of California Contractors License Number_" Expiration Date-
0 I acknowledge and, am aware, of special requirements contained in the statement of special inspections noted on
the approved plans;
I acknowledge that control will be exercised to obtain conformance with the construction documents approved by the
building official,
I will have in-place procedures for exercising control within our (the contractors) organization, for the method and
frequency of reporting and the distribution of the reports, and
I certify that I will have a qualified person within our (the contractors) organization to exercise such control.
I will provide a final repoft / letter in conwljance with CBC Section 1704.1.2 prior to requestlnq final
Inspection.
signature:7.4 . Date:
F,-45 Page 1 of Rev 08111
Technical Field Services, Inc.
(.:il ng neering Inspection
Project Name: Project#: 1Date:II Day:(,yA
Project Address: W1D k 4 lAuthor: C
City: C. Client:
Building Permit #: C ofl 742 Contractor: P7 Ic—
Plan File #: Foreman:
Type of Inspection: TOA. %if ALAWA S ,Weather:
Code- Report of work irspected9/ observed:
C.__ L J' ("A 1
w - r1 Alt L? Q€
_____ a4 bL,o- 'tte tixill üc.L !ry
A.AA '1L -OV' I,4If
t1,,'Ao k 4,, rL,r L 4L1- PX.c1-. a.,
c6L -L 4-.
Qe,eAc4 24 h-J, f(iIrLr,1klt, 4(I hd,' frddLhllM e 42,
1 retz- I/ (J( It'iic'It..
____ tF' '- (i& Iuzir 1
Samples Taken: Yes NO r
Type: Sise:
Quantity in Sample:
Inspector: ,'__fli L.. 1C)
Cert. # -,j
1 I Jobsite RepreseniBtive: -;
.
,
''..
x - Type:C I P'\I 'tI '
.:--.- .---..•
Inspector Signature.
-. •
Hours j_01
1199 Taniarack Avenue, Carlsbad. Caiforiiia92008 .(760) 497-1164
April 16, 2019
city of
Carlsbad
VERNON MCCASLIN
1025 OLIVE ST
SANTA BARBARA, CA 93101-1408
PERMIT NUMBER: :CBR2017-2521 -
ISSUE DATE: 03/23/2018
RE: BUILDING PERMIT EXPIRATION ADDRESS: 1190 Tamarack Av
PERMIT TYPE: BLDG-Residential, Addition Carlsbad, Ca 92008-3417
Our records indicate that your building permit will expire by limitation of time on 05/06/2019.
18.04.030 Section 105.5 amended - Expiration:
Every permit issued by the Building Official under the provisions of this code shall expire by
limitation and become null and void if the building or work authorized by such permit is not
commenced within 180 calendar days from the date of such permit, or if the building or work
authorized by such permit is stopped at any time after the work is commenced for a period of 180
calendar days, or if the building or work authorized by such permit exceeds three calendar years
from the issuance date of the permit. Work shall be presumed to have commenced if the permittee
has obtained a required inspection approval of work authorized by the permit by the Building
Official within 180 calendar days of the date of permit issuance. Work shall be presumed to be
stopped if the permittee has not obtained a required inspection approval of work by the Building
Official within each 180 day period upon the initial commencement of work authorized by such
perm it.
Before such work can be recommenced, a new permit shall be obtained to do so, and the fee
therefore shall be one half the amount required for a new permit for such work, and provided that
no changes have been made or will be made in the original plans and specifications for such work,
and provided further that such suspension or abandonment has not exceeded one year. In order, to
renew action on a permit after expiration, the permittee shall pay a new permit fee.
Any permittee holding an unexpired permit may apply for an extension of time within which work
may commence under that permitwhen the permittee is unable to commence work within the time
period required by this section for good and satisfactory reasons.
Please check below indicating your intentions and return this letter to us.
0 Project abandoned. A new permit will be obtained prior to commencing work.
0 Permit 180 day extension request, with written explanation including phone number and email address.
Request will not be considered without explanation
O Renewal permit requested.
If the project has been completed and only a final inspection is needed, please call the
inspection request line at (760) 602-2725.
If you have any questions, please contact the Building Inspection Division at 760-602-2700.
Community & Economic Development
Building Division 1 1635 Faraday Avenue, Carlsbad, CA 92008-7314 1 760-602-2700 1 760-602-8560 f I www.carlsbadca.gov
4 City of
February 28, 2019 Carlsbad
VERNON MCCASLIN
1025 OLIVE ST
SANTA BARBARA, CA 93101-1408
RE: BUILDING PERMIT EXPIRATION
PERMIT TYPE: BLDG-Residential, Addition
PERMIT NUMBER: CBR2017-2521
ISSUE DATE: 03/23/2018
ADDRESS: 1190 Tamarack Ave
Carlsbad, Ca 92008-3417
Our records indicate that your building permit will expire by limitation of time on 05/06/2019.
18.04.030 Section 105.5 amended -Expiration:
Every permit issued by the Building Official under the provisions of this code shall expire by
limitation and become null and void if the building or work authorized by such permit is not
commenced within .180 calendar days from the date of such permit,, or if the building or work
authorized by such permit is stopped at any time after the work is commenced for a period of 180
calendar days, or if the building or work authorized by such permit exceeds three calendar years
from the issuance date of the permit Work shall be presumed to have commenced if the permittee
has obtained a required inspection approval of work authorized by the permit by the Building
Official within 180 calendar days of the date of permit issuance. Work shall be presumed to be
stopped if the permittee has not obtained a required inspection approval of work by the Building
Official within each 180 day period upon the initial commencement of work authorized by such
permit.
Before such work can be recommenced, a new permit shall be obtained to do so, and the fee
therefore shalt be one half the amount required for a new permit for such work, and provided that
no changes have been made or Will be made. in the original plans and specifications for such work,
and provided further that such suspension or abandonment has not exceeded one year. in order to
renew action on a permit after expiration, the permittee shalt pay ar new permit fee.
Any permittee holding an unexpired permit may apply for an extension of time within which work
may commence,under that parm•itwhen the permittee is unable to commence work within the time
period required by this section far good and satisfactory reasons.
Please check below indicating your intentions and return this letterto us.
D Project abandoned. A new permit will be obtained prior to commencing work.
D Permit 180 day extension request, with written explanation including phone number and email address.
Request will not beconsidered without explanation
D Renewal permit requested.
If the project has been completedd and only a final inspection is needed, please call the
inspection request line at (760) 602-2725.
if you have any questions, please contact the Building inspection Division at 760-602-2700.
Community & Economic Development
Building Division 1 1635 Faraday Avenue, Carlsbad, CA 92008-7314 1 760-602-2700 1 760-602-8560 f I www.carlsbadca.gov
EsGil
A SAFEbulltCornpary
DATE: February 26, 2018 El APPLICANT
JURIS.
JURISDICTION: Carlsbad
PLAN CHECK #.: CBR2017-2521 SET: IV
PROJECT ADDRESS: 1190 Tamarack Ave.
PROJECT NAME: Joan Ekerling Remodel & Addition
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
LI The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Vernon L. McCascin
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Vernon Telephone #: (818) 642-4490
Date contacted: .-y:) Email: one55goalkeeperhotmail.com
Mail Telephone Fax In Person
Z REMARKS: 1. Slip sheets were provided, please update all other setsTieVsheetsS1&S2,.1,
2. City to provide soils stamp for applicant to sign prior to final appro' 1. 11
By: Kat Frankowski for RJM Enclosures:
EsGil
LI GA [- EJ [1 MB [I PC 2/20/2018
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax(858)560-1576
EsGilV/0
A SAFEbuiLf Company
DATE: January 25, 2018 U APPLICANT
JURIS.
JURISDICTION: Carlsbad
PLAN CHECK #.: CBR2017-2521 SET: III
PROJECT ADDRESS: 1190 Tamarack Ave.
PROJECT NAME: Joan Ekerling Remodel & Addition
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
LI The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Vernon L. McCascin
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Vernon
,Pate concted: \ \/s (by:C')
Mail fele'phone Fax In Person
LI REMARKS:
Telephone #: (818) 642-4490
Email: one55goalkeeperhotmail.com
By: Kat Frankowski for RJM Enclosures:
EsGil
LIGA LIEJ LIMB F1 PC 1/18/2018
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax(858)560-1576
Carlsbad CBR2017-252 1
January 25, 2018
NOTE: The items listed below are from the previous correction list. These remaining
items have not been adequately addressed. The numbers of the items are from the
previous check list and may not necessarily be in sequence. The notes in bold font are
current.
Please make all corrections, as requested in the correction list. Submit FOUR new complete sets
of plans for commercial/industrial projects (THREE sets of plans for residential projects). For
expeditious processing, corrected sets can be submitted in one of two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will
route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire
Departments.
Bring TWO corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets
of plans and calculations/reports directly to the City of Carlsbad Building Department for routing to
their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by EsGil Corporation is complete.
. PLANS
Will reverify, all sheets of plans are signed by the person responsible for their
preparation. (California Business and Professions Code). To be reverified.
. STRUCTURAL
22. Framing plan on sheet S-2 appears to be incomplete. Please call out existing headers in
vicinity of living room as well as new header required for modified opening between living
room and dining room. Framing plan is still incomplete. How is the existing roof
being supported at all exterior bearing walls that were removed? No beams are
shown on the framing plan. Please provide a complete framing plan with
appropriate connection details. Clearly show existing framing and proposed
framing.
FRAMING PLAN IS MORE DETAILED, BUT IT DOES NOT APPEAR STABLE.
PLEASE USE A STRUCTURAL ENGINEER AND PROVIDE CALCS. (EX: CEILING
JOISTS CANNOT BE PERPENDICULAR TO ROOF RAFTERS. NEW CEILING JOIST
SHOWN IS NOT LARGE ENOUGH.)
ALSO, SHOW DIMENSIONS FOR FOUNDATION TO VERIFY IT CAN SUPPORT
SHOWN POSTS.
. MISCELLANEOUS
59. City to provide soils notice stamp for applicant to sign prior to final approval.
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
Carlsbad CBR2017-252 1
January 25, 2018
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they are located in the plans.
Have changes been made to the plans not resulting from this correction list? Please
indicate:
YesU No U
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite 208,
San Diego, California 92123; telephone number of 858/560-1468, to perform the plan
review for your project. If you have any questions regarding these plan review items,
please contact Kat Frankowski for RJM at EsGil. Thank you.
EsGil
A SAFEbuLtCompany
DATE: 01/04/2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBR2017-2521 SET: II
PROJECT ADDRESS: 1190 Tamarack Ave.
PROJECT NAME: Joan Ekerling Remodel & Addition
LJ APPLICANT
JURIS.
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a bomplete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Vernon L. McCascin
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Vernon Telephone #: (818) 642 4450
Date contacted: II4Jl (by—f Email: one55goalkeeper@hotmai1.com
Telephone Fax In Person
REMARKS:
By: Ryan Murphy Enclosures:
EsGil
EGA LEJEMB F-1 PC 12/27/2017
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
Carlsbad CBR2017-252 1
01/04/2018
NOTE: The items listed below are from the previous correction list. These remaining
items have not been adequately addressed. The numbers of the items are from the
previous check list and may not necessarily be in sequence. The notes in bold font are
current.
Please make all corrections, as requested in the correction list. Submit FOUR new complete sets
of plans for commercial/industrial projects (THREE sets of plans for residential projects). For
expeditious processing, corrected sets can be submitted in one of two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City of Carlsbad
Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700. The City will
route the plans to EsGil Corporation and the Carlsbad Planning, Engineering and Fire
Departments.
Bring TWO corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets
of plans and calculations/reports directly to the City of Carlsbad Building Department for routing to
their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by EsGil Corporation is complete.
. PLANS
Will reverify, all sheets of plans are signed by the person responsible for their
preparation. (California Business and Professions Code). To be reverified.
. FIRE PROTECTION
5. Please indicate on the plans whether the existing residence has a fire sprinkler system
installed. If so, then provide a note stating that any additions/alterations will be provided
with an automatic residential fire sprinkler system. Section R313.2. No response found,
please provide a note on the plans.
. FOUNDATION REQUIREMENTS
Please show minimum reinforcement for proposed continuous footing and concrete stem
wall. I see the horizontal reinforcement but what about vertical tying the stem wall
to the foundation?
Detail D/52 shows all existing construction, all proposed walls are being built on new
footings. Please clarify. Detail D is still lacking. It is still showing existing framing on
a new footing and is not fully dimensioned. Also, needs to show a minimum
embedment of 12" into undisturbed soil. Please revise the detail to match the
proposed conditions
Carlsbad CBR2017-252 1
01/04/2018
. STRUCTURAL
13. Please detail all braced wall connections, please provide and callout typical shear
transfer detail at eaves and gable ends of each room addition, complete with EN, shear
panel, and shear transfer hardware (A34,35 etc) at top plate. Section R602.10.8.
Provided detail B/S-2 applies to California fill to existing shear transfer. Provide braced
wall connection details. Shear transfer detailing still incomplete. Detail X must be
called out with a symbol and leader line to applicable walls (at eaves). Please
provide and call out a shear transfer detail for the gable ends of roof diaphragm.
18. At proposed master bedroom addition, please indicate either an existing or new braced
wall panel of adequate length at wall shared between bedroom and proposed master
bedroom addition in vicinity of window I (within 10' of corner with appropriate hold down)
conforming with Section 602.10. The bracing shown is still not conventional. For a
one story building the max spacing between braced wall lines is 30'. To meet
conventional:
Call out entire length of wall at existing interior wall between bedroom closet
and hall way at the center of structure as a shearwall (about 9.5').
Call out 4' minimum shear panel at existing wall between garage and closet.
Framing plan on sheet S-2 appears to be incomplete. Please call out existing headers in
vicinity of living room as well as new header required for modified opening between living
room and dining room. Framing plan is still incomplete. How is the existing roof
being supported at all exterior bearing walls that were removed? No beams are
shown on the framing plan. Please provide a complete framing plan with
appropriate connection details. Clearly show existing framing and proposed
framing.
Please fill out the City of Carlsbad Special Inspection Agreement attached to the end of
this list. No response, to be verified at city prior to final approval.
. MISCELLANEOUS
59. City to provide soils notice stamp for applicant to sign prior to final approval.
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they are located in the plans.
Have changes been made to the plans not resulting from this correction list? Please
indicate:
YesU No U
Carlsbad CBR2017-252 1
01/04/2018
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite 208,
San Diego, California 92123; telephone number of 858/560-1468, to perform the plan
review for your project. If you have any questions regarding these plan review items,
please contact Ryan Murphy at EsGil. Thank you.
BEST MANAGEMENT PRACTICES (BMP) SELECTION TABLE
Erosion Control Tracking Non-Storm Water Waste Management and Materials
Sediment Control BMPs. ' Control BMPs Management BMPs Pollution Control BMPs BMPs
0 '
h 1
.2
.
-
. ,
Best Management Practice* C cr) = co
E 0 0 Lii 0
(BMP) Description -3 .
0 L - c_) w CD
CD - . c Li.. - L. - ' - - E Cl) 0 i_ Cl) 0
E. C
. i- .0 C - .2 C - C ' - 'o o
. o
=
C NC 0 C
o 0
0
._ -
2 .. - ) Cl)
r2
CD
C -b C L C .i- C '
* 0 " C i_
> C C 0
_
CI) Cl) -- C o - C ... 0 0 D C C 0 C 0 p C) . Lii C U)' Cl) Cl) Cl) - 0 Li. L C) (1)> Cl) Cl) Cl. C/) (I) Q O. Q 0 0 > 0 Cl) Cl) Cl) 0 Cl)
CASQA Designation - , N ,- r) - LD CO N- CO 2 I
-
I .1 I I l'I
ND -
I
IC)
I
CO
.1
CO
I I 0 '
I w I wui I w I w I w I LU I I ' U) Cl) Cl) Cl)
Construction Activity Li LU Lii LU Cl) Cl) Cl) C/) Cl) (l) C/') U) I— I— . . .
'Gading/SoilDiturbane .
Trenchin'g/Excavation - - - - -
- Stockpiling . - - . - - .- - - - - -
Drilling/Boring
- - - - -
- Concrete/Asphalt Sawcutting - - - - - - - -
--
Concrete Flatwork,--
---
-
Paving
.Conduit/Pipe Installation' ' . - - - .- - - - - - - - - - - - - - - - -' - -
Stucco/Mortar 'Work
'Waste Disposal ' --- -
— Staging/ ay Down Area - - - - - - - - - - - - - -
Equipment Maintenance and Fueling. ,
Hazardous Substance UsejStorage -
Dewdtering -' - - - - - - - - - - - - - - - - - - - - -
-
— Site Access Across Dirt
Other (list):'
Instructions:
1. Check the box to the left of all applicable construction activity (first column) expected to occur, during construction.
Located along the top of the BMP Table is a list of BMP's with it's corresponding California Stormwater Quality Association (CASQA) designation number. Choose one
or more BMPs you intend to use during construction from the list. Check the box where the chosen activity row intersects with the BMP column.
Refer to the CASQA construction handbook for information and details of the 'chosen BMPs and how to apply them to the project.
STORM WATER COMPLIANCE FORM
TIER I CONSTRUCTION SWPPP
STORM WATER POLLUTION PREVENTION NOTES
ALL NECESSARY EQUIPMENT AND MATERIALS SHALL BE
AVAILABLE ON SITE TO FACILITATE RAPID INSTALLATION
OF EROSION AND SEDIMENT CONTROL BMPs WHEN RAIN
IS EMINENT.
THE OWNER /CONTRACTOR SHALL RESTORE ALL EROSION
CONTROL DEVICES TO WORKING ORDER TO THE SATISFACTION
OF THE CITY INSPECTOR AFTER EACH RUN—OFF PRODUCING
RAINFALL.
THE OWNER/CONTRACTOR SHALL INSTALL ADDITIONAL EROSION
CONTROL MEASURES AS MAY BE REQUIRED BY THE CITY
INSPECTOR DUE TO INCOMPLETE GRADING OPERATIONS OR
UNFORESEEN CIRCUMSTANCES WHICH MAY ARISE.
ALL REMOVABLE PROTECTIVE DEVICES SHALL BE IN PLACE
AT THE END OF EACH WORKING DAY WHEN THE FIVE (5)
DAY RAIN PROBABILITY FORECAST EXCEEDS FORTY PECENT
(40%). SILT AND OTHER DEBRIS SHALL BE REMOVED AFTER
EACH RAINFALL.
ALL GRAVEL BAGS SHALL CONTAIN 3/4 INCH MINIMUM
AGGREGATE.
ADEQUATE EROSION AND SEDIMENT CONTROL AND PERIMETER
PROTECTION BEST MANAGEMENT PRACTICE MEASURES MUST
BE INSTALLED AND MAINTAINED.
THE CITY INSPECTOR SHALL HAVE THE AUTHORITY TO ALTER
THIS PLAN DURING OR BEFORE CONSTRUCTION AS NEEDED
TO ENSURE COMPLIANCE WITH CITY STORM WATER QUALITY
REGULATIONS.
OWNER'S CERTIFICATE:.
I UNDERSTAND AND ACKNOWLEDGE THAT I MUST: (1) IMPLEMENT
BEST MANAGEMENT PRACTICES (BMPS) DURING CONSTRUCTION
ACTIVITIES TO THE MAXIMUM EXTENT PRACTICABLE TO AVOID
THE MOBILIZATION OF POLLUTANTS SUCH AS SEDIMENT AND TO
AVOID THE EXPOSURE OF STORM WATER TO CONSTRUCTION
RELATED POLLUTANTS; AND.(2) ADHERE TO, AND AT ALL TIMES,
COMPLY WITH THIS CITY APPROVED TIER 1, CONSTRUCTION SWPPP
THROUGHOUT THE DURATION OF THE CONSTRUCTION ACTIVITIES
UNTIL THE CONSTRUCTION WORK IS COMPLETE AND APPROVED
BY THE CITY OF CARLSBAD.
OWNER(S)/OWNER'S AGENT NAME (PRINT)'
OWNER(S)/OWNER'S AGENT NAME (SIGNATURE) DATE
E-29
PROJECT INFORMATION
Site Address:_(lo 2 17-i .Zq
Assessor's Parcel Number:
Emergency Con act:
Name:
24 Hour Phone,: 9 14 50
Construction Threat to Storm Water Quality
(Check Box)
MEDIUM
Page 1 of 1 REV 02/16
4L(7city of
Carlsbad
Print Date: 08/19/2019 Permit No: PREV2018-0207
Job Address: 1190 Tamarack Ave
Permit Type: BLDG-Permit Revision Work Class: Residential Permit Revisi Status: Closed - Expired
Parcel No: 2054302100 Lot #: Applied: 07/25/2018
Valuation: $ 0.00 Reference U: Issued: 10/24/2018
Occupancy Group: Construction Type Permit
Fináled:
U Dwelling Units: Bathrooms: Inspector: AKrog
Bedrooms: Orig. Plan Check U: CBR2017-2521 Final
Plan Check U: Inspection:
Project Title:
Description: EKERLING: REMOVE INTERIOR WALL AND RELOCATE TOILET
Applicant: Owner: Co-Applicant:
VERNON MCCASLIN JOANNE EKERLING VERNON MCCASLIN
1025 Olive St JOANNE EKERLING 1025 Olive St
SANTA BARBARA, CA 93101-1408 10860 Alta View Dr SANTA BARBARA, CA 93101-1408
818-642-4490 STUDIO CITY, CA 91604 818-642-4490
323-650-5011
FEE AMOUNT
MANUAL BUILDING PLAN CHECK FEE $281.25
Total Fees: $ 281.25 Total Payments To Date : $ 281.25 Balance Due: $0.00
Building Division
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-2700 1 760-602-8560 f I www.carlsbadca.gov
PLAN CHECK REVISION OR Development Services (CitY of DEFERRED SUBMITTAL Building Division
Carlsbad APPLICATION 1635 Faraday Avenue
760-602-2719 B-I 5 www.carlsbacica.gov
Original Plan Check Number4'i€..2c'f'7 ,5lhan Revision Number "W 18 -00
Project Address //'9
General Scope of Revision/Deferred Submittal:
CONTACT INFORMATION:
Namet/,tJo J li 'H 7% 2/A/ Phone iR'2- 4qO F
Address /t225 tY/U City Zip 7370 /
Email Address
Original plans prepared by an architect or engineer, revisions must be signed & stamped by that person.
1. Elements revised: Plans LI Calculations LI Soils LII Energy LI Other
2.
Describe revisions in detail
3.
List page(s) where each
revision is shown
p --O Ub- 4A/
Does this revision, in any way, alter the exterior of the project? LI Yes LII No
Does this revision add ANY new floor area(s)? LI Yes LI No
Does this revision affect any fire related issues? LI Yes LI No
Is this a complete set? LII Yes LI No
S ig natu re /i' - Date /O ?
1635 Faraday Avenue, Carlsbad, CA 92 08 t: 60-602- 2719 f: 760-602-8558 E /ail:b~uilding@carlsbacica.gov
- www.carlsbadca.gov
EsGil
A SAFEbuiLf Company
DATE: October 18, 2018 LI APPLICANT
w-EnURIS.
JURlSDlCTlONCrlil -
PLAN CHECK #.: CBR2017-2521.rev (PREV2O18-0207) SET: III
PROJECT ADDRESS: 1190 Tamarack Ave.
PROJECT NAME: Ekerling Residence Remodel & Addition
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check listtransmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Vernon L. McCascin
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise the applicant that the plan check has been completed.
-
-.
Person contacted: Vernon Telephone #: (818) 642-4490
Date contacted: ----by ?) Email: one55goalkeeperhotmail.com
Mail Telephone Fax In Person
) ev
li REMARKS:.Severalcorrections were made onsheeLS-2-.(clouded -in red).-Rleasernake these
.. ... -'rrections:on - other.s.ets.
By: Kat Frankowski Enclosures:
EsGil
LI GA LI EJ LI MB 171 PC 7/30/2018
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
EsGil
A SAFEbuiUCornpany
DATE: August 23, 2018
JURISDICTION: Carlsbad
PLAN CHECK #.: CBR2017-2521.rev (PREV2ó18-0207)
PROJECT ADDRESS: 1190 Tamarack Ave.
PROJECT NAME: Ekerling Residence Remodel & Addition
I APPLICANT
JURIS.
SET: II
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Vernon L. McCascin
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise, the applicant that the plan check has been completed.
Person contacted: Vernon Telephone #: (818) 642-4490
Date contacted: 81Z31W (by--M Email: one55goalkeeperhotmail.com
Fax In Person
LI REMARKS:
By: Kat Frankowski Enclosures:
EsGil
LI GA LI EJ LI MB LI PC 7/30/2018
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax(858)560-1576
Carlsbad CBR20 17-2521.rev (PREV2018-0207)
August 23, 2018
NOTE: The items listed below are from the previous correction list. These remaining
items have not been adequately addressed. The numbers of the items are from the
previous check list and may not necessarily be in sequence. The notes in bold font are
current.
PLANS
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one of
two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700.
The City will route the plans to EsGil and the Carlsbad Planning, Engineering and Fire
Departments.
Bring TWO corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake
Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of
plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by EsGil is complete.
2. All sheets of plans must be signed by the person responsible for their preparation.
(California Business and Professions Code).
Will be checked on final
Plans deviating from conventional wood frame construction shall have the structural
portions signed and sealed by the California state licensed engineer or architect
responsible for their preparation, along with structural calculations. (California Business
and Professions Code).
Will be checked on final
New walls are shown, provide new framing plan.
Framing plan is incomplete
There was a shear wall shown by the kitchen (in the approved set of plans), where now
there is a door. Please address.
A 4' shear wall is shown in a 7' wall section. Show the actual location of shear
wall.
Wall that is being removed in living room appears to be load bearing, show caics.
Not addressed. Same wall segment in living room is still shown demolished.
Show header sizes for new doors.
Many headers and beams are missing from plans.
Carlsbad CBR2017-252 1.rev (PREV2018-0207)
August 23, 2018
New calcs are needed, along with new S sheets (and possibly new details), engineer
needs to stamp and sign the new structural sheets.
SET 2 OF PLANS IS SHOWN WITH SIGNIFICANT CHANGES FROM THE APPROVED
SET. THE FRAMING PLAN IS COMPLETELY DIFFERENT, MANY BEAMS ARE
MISSING OR REPLACED WITHOUT JUSTIFICATION, ROOF FRAMING APPEARS
DIFFERENT, FOUNDATION PLAN IS MISSING MANY DETAILS AND NO LONGER
SHOWS SPREAD FOOTING.
THESE PLANS NEED TO BE REWORKED SO THAT THEY ARE CONSISTENT
THROUGHOUT. COMPLETE PLANS MAY NEED BE SUBMITTED.
NEW CALCS MUST BE PROVIDED, THE FRAMING IS COMPLETELY DIFFERENT.!
NGINEER TO WET STAMP AND SIGN THE CALCS AND STRUCTURAL SHEETSJ
More corrections may follow when structural details are updated.
MISCELLANEOUS
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they are located in the plans.
Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes No E3
The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite 208,
San Diego, California 92123; telephone number of 858/560-1468, to perform the plan
review for your project. If you have any questions regarding these plan review items,
please contact Kat Frankowski at EsGil. Thank you.
EsGil
A SAFEbuItt Company
DATE: August 6, 2018 0 APPLICANT
,iI JURIS.
JURISDICTION: Carlsbad
PLAN CHECK #.: CBR2017-2521.rev (PREV2O18-0207) SET: I
PROJECT ADDRESS: 1190 Tamarack Ave.
PROJECT NAME: Ekerling Residence Remodel & Addition
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Vernon L. McCascin
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Vernon Telephone #: (818) 642-4490
e con a Ic,k' (by_--5 Email: one55goalkeeper@hotmail.com
Mail Telephone Fax In Person
LII REMARKS.
By: Kat Frankowski Enclosures:
EsGil
L GA LI EJ [1 MB LI PC 7/30/2018
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
Carlsbad CBR2017-252 l.rev (PREV2018-0207)
August 6, 2018
[DO NOT PAY— THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK #.: CBR2017-2521.rev
(PREV2018-0207)
PREPARED BY: Kat Frankowski DATE: August 6, 2018
BUILDING ADDRESS: 1190 Tamarack Ave.
BUILDING OCCUPANCY:
BUILDING
PORTION
AREA
(Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code Icb IBY Ordinance
1997 UBC Building Permit Fee V
1997 UBC Plan Check Fee V
Type of Review: E Complete Review Structural Only
E Repetitive Fee Repeats
* Based on hourly rate
D Other
Hourly 2.5 Hrs. @ *
EsGil Fee $90.00 I $226.001
Comments:
Sheet 1 of 1
Carlsbad CBR2017-252 l.rev (PREV2018-0207)
August 6,2018
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK #.: CBR2017-2521.rev (PREV2018-0207) JURISDICTION: Carlsbad
PROJECT ADDRESS: 1190 Tamarack Ave.
FLOOR AREA:
Addition = 301 SF
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 7/25/2018
DATE INITIAL PLAN REVIEW
COMPLETED: August 6, 2018
FOREWORD (PLEASE READ):
STORIES: 1
HEIGHT:
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 7/30/2018
PLAN REVIEWER: Kat Frankowski
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised
Carlsbad CBR2017-252 1.rev (PREV2018-0207)
August 6, 2018
PLANS
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one of
two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700.
The City will route the plans to EsGil and the Carlsbad Planning, Engineering and Fire
Departments.
Bring TWO corrected set of plans and calculations/reports to EsGil, 9320 Chesapeake
Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all remaining sets of
plans and calculations/reports directly to the City of Carlsbad Building Department for
routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the City
Planning, Engineering and Fire Departments until review by EsGil is complete.
2. All sheets of plans must be signed by the person responsible for their preparation.
(California Business and Professions Code).
Plans deviating from conventional wood frame construction shall have the structural
portions signed and sealed by the California state licensed engineer or architect
responsible for their preparation, along with structural calculations. (California Business
and Professions Code).
New walls are shown, provide new framing plan.
There was a shear wall shown by the kitchen (in the approved set of plans), where now
there is a door. Please address.
Wall that is being removed in living room appears to be load bearing, show calcs.
Show header sizes for new doors.
New calcs are needed, along with new S sheets (and possibly new details), engineer
needs to stamp and sign the new structural sheets.
More corrections may follow when structural details are updated.
MISCELLANEOUS
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they are located in the plans.
Carlsbad CBR2017-252 1.rev (PREV2018-0207)
August 6, 2018
Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes No U
12. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive, Suite 208,
San Diego, California 92123; telephone number of 858/560-1468, to perform the plan
review for your project. If you have any questions regarding these plan review items,
please contact Kat Frankowski at EsGil. Thank you.