HomeMy WebLinkAbout2415 TUTTLE ST; ; CB020624; PermitCity of Carlsbad
1635 Faraday Av Carlsbad, CA 92008
04-24-2003 Residential Permit Permit No: CB020624
Building Inspection Request Line (760) 602-2725
Job Address: 2415 TUTTLE ST CBAD
Permit Type: RESDNTL Sub Type: RAD Status: ISSUED
Parcel No: Lot #: 0 Applied: 02/28/2002
Valuation: $24,137.00 Construction Type: NEW Entered By: JM
Occupancy Group: Reference #: Plan Approved: 02/28/2003
# Dwelling Units: 0 Structure Type: Issued: 02/28/2003
Bedrooms: 0 Bathrooms: 0 Inspect Area: JE
Project Title: FISHBECK - ENCLOSE EXISTING Orig PC#:
BALCONY TO HABITABLE 217 SF & NEW BALCONY 70 SF Plan Check#:
Applicant: Owner: 353 04/24/03 0002 01 02 FISHBECK DON COP 6040
2415 TUTTLE STREET
CARLSBAD CA 92008
760-720-9868
Building Permit $215.19 Meter Size
AddI Building Permit Fee $0.00 AddI Red. Water Con. Fee $0.00
Plan Check $139.87 Meter Fee $0.00
AddI Plan Check Fee $0.00. SDCWA Fee $0.00
Plan Check Discount $0.00 CFD Payoff Fee $0.00
Strong Motion Fee $2.41 PFF $0.00
Park in Lieu Fee $0.00 PFF (CFD Fund) $0.00
Park Fee $0.00 License Tax $0.00
LFM Fee $0.00 License Tax (CFD Fund) $0.00
Bridge Fee $0.00 Traffic Impact Fee $0.00
Other Bridge Fee $0.00 Traffic Impact (CFD Fund) $0.00
BTD #2 Fee $0.00 Sidewalk Fee $0.00
BTD #3 Fee $0.00 PLUMBING TOTAL $49.00
Renewal Fee $0.00 ELECTRICAL TOTAL $20.00
AddI Renewal Fee $0.00 MECHANICAL TOTAL $24.00
Other Building Fee $60.00 Housing Impact Fee $0.00
Pot. Water Con. Fee $0.00 Housing InLieu Fee $0.00
Meter Size Housing Credit Fee $0.00
AddI Pot. Water Con. Fee $0.00 Master Drainage Fee $0.00
Red. Water Con. Fee $0.00 Sewer Fee $0.00
Additional Fees $0.00
TOTAL PERMIT FEES $510.47
Total Fees: $510.47 Total Payments To Date: $450.47 Balance Due: $60.00
FINAL APPROVAL
Date: Clearance:
NOTICE: Please take NO E that your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter collectively
referred to as "fees/exactions." You v 90 days from the date this permit was issued to protest imposition of these fees/exactions. If you protest them, you must
follow the protest procedures set forth n Government Code Section 66020(a), and file the protest and any other required information with the City Manager for
processing in accordance with Carlsbad Municipal Code Section 3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack,
review, set aside, void, or annul their imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection fees and capacity
changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this project. NOR DOES IT APPLY to any
1 ' PERMIT APPLICATION
CITY OF CARLSBAD BUILDING DEPARTMENT
1635 Faraday Ave., Carlsbad, CA 92008
FOR OFFICE USE ONLY
PLAN CHECK tolz
EST. VAL. /rf..)i
Plan Ck. Depoj'' £
Validated Bv.J"1'\i
'PR!! CTJMFO~M4TL
Address (include Bldg/Suite #) Business Name (at this address)
i s Tfrr L. ST.
Legal Description Lot No Subdivision Name/Number U if N3 ' 'PFa NQ.r tal #61unit9 1. .07
Proposed Use,
l6criptiofl of Work # of Bedrooms
J , 0&t%J (1
Name
Name Address City State/Zip Telephone #
OPERTYONER1
Name - Address City State/Zip Telephone #
-
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its
issuance, also requires theapplicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law
(Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code] or that he is exempt therefrom, and the basis for the alleged
exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty'of not more than five hundred dollars ($500]).
Name Address City State/Zip Telephone #
State License # License Class City Business License #
Designer Name Address City . State/Zip Telephone
State License # '
COMPENSATIO
Workers' Compensation Declaration: I hereby affirm under penalty of perjury one of the following declarations: -
I have and will maintain a certificate of consent to. self.insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance
of the work for which this permit is issued.
I have and will maintain workers' compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is
issued. My worker's compensation insurance carrier and policy number are:
Insurance Company Policy No. Expiration Date__________________
(THIS SECTION NEED NOT BE COMPLETED IF THE PERMIT IS FOR ONE HUNDRED DOLLARS ($1001 OR LESS) . . .
CERTIFICATE OF EXEMPTION: I certify that in the performance of the work for which this permit is issued, I shall not employany person in any manner so as
to become subject to the Workers' Compensation Laws of-California. . . .
WARNING: Failure to secure workers' compensation coverage is unlawful, and shall subject an employer to criminal penalties and civil fines up to one huhdred
thousand dollars ($100,000). in addition to the cost of compensation, damages as provided for in Section 3706 of the Labor code, interest and attorney's fees.
SIGNATURE DATE
I7T0WNER BUILDER oECLARATlONiTT ___
/ I hereby affirm that I am exempt from the Contractor's License Law for the following reason
1 0 I, as owner of, the property or my employees with wages as their sole compensation, will do the work and the structure isnot intended or offered for sale
(Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does
such work himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is
sold within one year of completion the owner builder will have the burden of proving that he did not build or improve for the purpose of sale)
I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law). - 0 I am exempt under Section Business and Professions Code for this reason
I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0 YES ONO
I (have / have not) signed an application for a building permit for the proposed work.
I have contracted with the following person (firm) to provide the proposed construction (include name I address / phonenumber / contractors license number):
4 I plan to provide portions of the work but I have hired the following person to coordinate supervise and provide the major work (include name /.address / phone
number / contractors license number):
\ 5.' I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name / address / phonenumber / type -
\of work): -
OWNER SIGNATURE
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505 25533 or 25534 of the Presley Tanner Hazardous Substance Account Act? 0-YES 0 NO
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? 0 YES 0 NO
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 YES 0 NO
IF ANY OF THE ANSWERS ARE YES A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE
REQUIREMENTS OF THE OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
8 TCONSTRUCT ION, LENDING AGENCI'T LJ T:iTE—'—T
I hereby affirm that there is -a construction lending agency for the performance of the work for which this permit is issued (Sec 3097(0 Civil Code)
LENDER'S NAME LENDER'S ADDRESS_______________________________________________________
- TJ
I certify that I have read the application and state that the above information is correct and thatthe information on the plans is accurate. I agree to comply with all
City ordinances, and State laws relating to 'building construction. I hereby authorize representatives of the Cif' of Carlsbad to enter upon the above mentioned
property for inspection purposes. I ALSO AGREE TO SAVE. INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES,
JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over. 5'0" deep and demolition or construction of structures over 3 stories in height.
EXPIRATION: Every permit issued by the building Official under the provisions of this Code shall expireby limitation and become null and void if the building or work
authorized by Such permit is not commenced within 180 days from the date of such permit or if the building or work authorized by such l5ermit is suspended or abOndoned
at any time after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code)
APPLICANT'S SIGNATURE - 4'4/'LG-p- L,1f4'42,, ' DATE '
1
(o -
WHITE: File YELLOW: Applicant PINK: Finance ...
List 1- Permit-Type
From the following list, determine the permit-type that best describes the work you propose to do. Please put the code of that
permit-type in the blank at the top of the page on the front of this application. Residential permits (only) also require the
identification of the structure-type to be associated with the permit. Choose a structure-type from "List 2 - Structure-Types" and put
its code in the appropriate blank on the front of this application. -.
Residential Permits
Code Description
APT Apartments - new construction.
CONDO Condominiums - new construction.
CVNNR Conversion. Convert all or a portion of a non-residential building to residential use, creating one or more new
residential units.
CVNRN Conversion. Convert one or more residences in a building to non-residential usage.
CVNRR Conversion. Increase or reduce the number of dwelling units in a residential structure through interior modifications
(i.e.: a four bedroom house converted to a duplex, with 2 bedrooms each).
DEMO Demolition permit. (Also specify type of structure from List 2).
DUP Duplex - new construction.
MOHO Mobile home, renovation, repair, or addition of accessory structure not yielding a new living unit.
MOHON Mobile home, pre-fabricated house, or trailer installed (plumbed, wired) in a mobile home park (see distinction from
single-family residence, below).
RAD Residential addition/alteration, creating no new dwelling unit(s).
RREISSUE Residential permit re-issue.
RREPAIR Residential building repair. Damage, fire, etc.
RREPLACE Residential building replacement (no additional units).
SFA Single-family, attached - new construction. A one-family house attached to one or more other houses, with one or
more common walls extending from foundation to roof at, or forming, a lot line. Has own plumbing and heating
system (e.g.: townhouse, row house, half.plex)
SFD Single-family, detached - new construction: A one-family house with open area on all four sides. May have an
attached or detached garage, or a business. May be a detached "granny flat". May be a mobile home or trailer on an
individual lot, but not in a mobile home park.
Non-Residential/Accessory Permits
Code Description
COM Commercial structure, new construction.
CR.EISSUE Commercial permit re-issue.
CREPAIR Commercial building - repair. Damage, fire, etc.
CREPLACE Commercial building - replacement.
CII Commercial tenant improvement.
DEMO Demolition permit.
ELEC Electrical permit, for electrical work only.
HOTEL Hotel or motel (including Managed Living Unit hotel) - new construction.
HOTELR Hotel renovation.
INDUST Industrial structure, new construction.
III Industrial tenant improvement.
MECH Mechanical permit, for mechanical work only.
MISC Miscellaneous. Use only if proposed work doesn't fit another activity type.
PATIO Patio and/or deck.
PLUM Plumbing permit, for plumbing work only.
POOL Gunite pools and spas.
RETAIN Retaining wall permit.
SIGN Sign construction/installation permit.
SOLAR Solar energy system installation permit (specify structure type to be served).
SPA Factory-made or Gunite.
List 2 - Structure-Type (Use with Residential Permit Only)
From the following list, determine the type of residential structure that best describes the structure on which you will be working.
Please put the code of that structure-type in the appropriate blank at the top of the page on the front of this application.
Code Description
SFA Single-family, attached. A one-family house attached to one or more other houses, with one or more common walls
extending from foundation to roof at, or forming, a lot line. Has own plumbing and heating system (e.g.: townhouse,
row house, half-plex).
SFD Single-family detached: A one-family house with open area on all four sides. May have an attached or detached
garage, or a business. May be a detached "granny flat". May be a mobile home or trailer on an individual lot, but not
in a mobile home park.
MF2-4 Multi-family, 2 to 4 units. A residential structure on a single lot, containing two, three, or four dwelling units. Units
may share master heating, plumbing, or electrical service (e.g.: duplex, triple; quad-plex).
MFS+ Multi-family, 5 or more units. Same as MF2-4, except the building has a t least five attached units on the same lot.
MOHO Mobile home, pre-fabricated house, or trailer installed (plumbed, wired) in a mobile home park (see distinction from
single-family residence, above).
1(0' • - '•
City of Carlsbad Bldg Inspection Request
For: 06/27/2003
Permit# CB020624 Inspector Assignment: JE
Title: FISHBECK - ENCLOSE EXISTING
Description: BALCONY TO HABITABLE 217 SF & NEW BALCONY 70 SF
Type: RESDNTL Sub Type: RAD
Job Address: 2415 TUTTLE ST
Suite: Lot 0
Location:
APPLICANT FISHBECK DON
Owner: FISHBECK SHARON M
Remarks:
Total Time:
Phone: 6195726800
Inspector:
Requested By: DON
Entered By: ROBIN
CD Description
19 Final Structural
29 Final Plumbing
39 Final Electrical
49 Final Mechanical
Mt Comment
/ri2/
flow, ci*Mo o& tc,7ze
Associated PCRs/CVs
Inspection History
Date Description Act Insp Comments
05/09/2003 17 Interior Lath/Drywall AP JE
05/09/2003 18 Exterior Lath/Drywall AP JE
05/05/2003 17 Interior Lath/Drywall AP JE
05/05/2003 24 Rough/Topout AP JE
05/05/2003 44 Rough/Ducts/Dampers CO JE COMPLETE DUCT WORK
05/01/2003 24 RàughlTopout CO JE INSTALL PLUMBING PER CODE - SEE NOTICE
04/30/2003 14 Frame/Steel/Bolting/Welding AP JE 1106-E4
04/30/2003 15 Roof/Reroof AP JE OK TO COVER
04/30/2003 24 Rough/Topout CO JE ADD VENT
04/30/2003 34 Rough Electric AP JE
04/24/2003 11 Ftg/Foundation/Piers AP JE OK TO PLACE CONCRETE
04/23/2003 11 Ftg/Foundation/Piers CO JE NOT READY 9:18 AM - PAY FEE
04/09/2003 11 Ftg/Foundation/Piers CO JE SEE NOTICE, INSTALL REBAR PER PLAN #4 IN - PROTECT POOL
PLUMBING PASSING THROUGH FOOTING
F ;Domw
fActE IF
XST1 I
I c- Z.ma4
-
--4--
.::41!X.9' PO ST.
vcc. Z1. YZ •__ • t . ' I I
:•; W. 15"4
,41 t4V
. _2ox
zo•I:4:L ; ' PE.Lp.
4i -T- xis
..T1.T3 °TT7Nt-THQU___FTC- 4 PT.
£c I-$ 1) A 117 VEP- 2. 0 '. T u E on L s7vc. Is
FESS,
L.
ui (i( No. C34613
cr Exp: 9-30-03
J•R'JI
Civi
EsGil Corporation
In Partners1iip with government for (Building Safety
DATE: February 28, 2003
JURISDICTION: Carlsbad
PLAN CHECK NO.: 02-624
PROJECT ADDRESS: 2415 Tuttle Street
PROJECT NAME: SFD Addition for Fishback
SET:V
APPLICANT
U JURIS.
O PLAN REVIEWER
O FILE
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
0 The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
fl The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Telephone #:
Date contacted: (by: ) Fax #:
Mail Telephone Fax In Person
REMARKS: 1) Designer to hand carry the plans. 2) Please have the designer slip sheet the
other set of plans to the city's set IV plans.
By: Bert Domingo Enclosures:
Esgil Corporation
D GA D MB U EJ U PC Log tmsmtl.dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
EsGil Corporation
In Partnership with Government for Building Safety
DATE: February 13, 2003
JURISDICTION: Carlsbad
'PLAN CHECK NO.: 02-624 SET: N
PROJECT ADDRESS: 2415 Tuttle St.
PROJECT NAME: SFD Addition for Fishbeck
U APPLICANT
U PLAN REVIEWER
U FILE
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes..
F-1 The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
111 The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
F-1 The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Don Fishbeck
2415 Tuttle St., Carlsbad, CA 92008
LI Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Don Telephone #: (760) 720-9868
Date contacted: 1 sy/o3 (by: 1.. ) Fax #:
Mail ....._—Telephone b...- Fa- In Person
LI REMARKS:
By: Bert Domingo Enclosures:
Esgil Corporation
El GA [I MB DEJ El PC 2/6/03 tmsmti.dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
Carlsbad 02-624
February 13, 2003
RECHECK PLAN CORRECTION LIST
JURISDICTION: Carlsbad
PROJECT ADDRESS: 2415 Tuttle St.
DATE PLAN RECEIVED BY
ESGIL CORPORATION: 2/6/03
REVIEWED BY: Bert
PLAN CHECK NO.: 02-624
SET: IV
DATE RECHECK COMPLETED:
February 13, 2003
FOREWORD (PLEASE READ):
This plan review is-limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and disabled access. This plan review is
based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
Please make all corrections on the original tracings and submit two new sets of prints to:
ESGIL CORPORATION.
To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
The following items have not been resolved from the previous plan reviews. The original
correction number has been given for your reference. In case you did not keep a copy of
the prior correction list, we have enclosed those pages containing the outstanding
corrections. Please contact me if you have any questions regarding these items.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
DYes ONo
-S
IV Carlsbad 02-624
February 13, 2003
IPLANS
1. Please make all corrections on the original tracings, as requested in the correction list.
Submit three sets of plans for commercial/industrial projects (two sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one of
two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700.
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments.
Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the-City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete.
2. All sheets of plans must be signed by the person responsible for their preparation.
(California Business and Professions Code). This will be checked when all the
items below are met.
3. Plans, specifications and calculations shall be signed and sealed by the California
state licensed engineer or architect responsible for their preparation, for nians
deviating from conventional wood frame construction. Snecifvexniration date of
license. (California Business and Professions Code). This will be checked when all
the items below are met.
EXITS, STAIRWAYS, AND RAILINGS
8. Guardrails (Section 509.1):
b) Shall be detailed showing adequacy of connections to resist the horizontal force
prescribed in Table 16-B. Please submit calculations. 1) THE DETAIL IS NOT
CLEAR. PLEASE SUBMIT CALCULATIONS. 2)11 SEEMS THAT THE GUARDRAIL
IS MADE UP OF GLASS. ALL THE EDGES OF THE SAME SHOULD BE FULLY
SUPPORTED OR SUBMIT CALCULATIONS OFTHE GLASS TO VERIFY
STRUCTURAL INTEGRITY OF THE SAME. No calculations submitted.
FRAMING
18. Provide calculations for main vertical and horizontal framing members and
footings. Section 106.3.3. This is to verify the existing structural elements being
affected by this addition.,.,—PLEASE SUBMIT CALCULATIONS FOR THE EXISTING
FOUNDATION.
Sheet SI shows sections A & BISO-0 but no sheet SO-0 submitted.
Sheet S2 referenced details 1. 2 & 41S1-0 but not comnatible.
Please show how the deck is laterally sunnorted.
Carlsbad 02-624
February 13, 2003
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they are located in the plans.
Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes L3 No U
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform
the plan review for your project. If you have any questions regarding these plan review
items, please contact Bert Domingo at Esgil Corporation. Thank you.
EsGilCorporation
2n Partners/ip With government for Bui!ithig Safety
DATE: January 22, 2003
JURISDICTION: Carlsbad
PLAN CHECK NO.: 02-624 SET: III
PROJECT ADDRESS: 2415 Tuttle St.
PROJECT NAME: SFD Addition for Fishbeck
O ANT uQis'.
0 PLAN REVIEWER
U FILE
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
F1 The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
fl The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
LI The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Don Fishbeck
2415 Tuttle St., Carlsbad, CA 92008
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Don Telephone #: (760) 720-9868
Date contacted: if 2?,(t3, (by: !c- ) Fax #:
Mail —,telephone -' Fax In Person
LI REMARKS:
By: Bert Domingo Enclosures:
Esgil Corporation
0 GA 0 MB 0 EJ 0 PC 1/13/03 trnsmtl.dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
L
Carlsbad 02-624
January 22, 2003
RECHECK PLAN CORRECTION LIST
JURISDICTION: Carlsbad
PROJECT ADDRESS: 2415 Tuttle St.
DATE PLAN RECEIVED BY
ESGIL CORPORATION: 1/13/03
REVIEWED BY: Bert
PLAN CHECK NO.: 02-624
SET: III
DATE RECHECK COMPLETED:
January 22, 2003
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and disabled access. This plan review is
based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
Please make all corrections on the original tracings and submit two new sets of prints to:
ESGIL CORPORATION.
To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
The following items have not been resolved from the previous plan reviews. The original
correction number has been given for your reference. In case you did not keep a copy of
the prior correction list, we have enclosed those pages containing the outstanding
corrections. Please contact me if you have any questions regarding these items..
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
UYes UNo
Ift
Carlsbad 02-624
January 22, 2003
PLANS
1. Please make all corrections on the original tracings, as requested in the correction list.
Submit three sets of plans for commercial/industrial projects (two sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one of
two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700.
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments.
Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete.
2. All sheets of plans must be signed by the person responsible for their preparation.
(California Business and Professions Code).
3. Plans, specifications and calculations shall be signed and sealed by the California
state licensed engineer or architect responsible for their preparation, for plans
deviating from conventional wood frame construction. Specify expiration date of
license. (California Business and Professions Code).
. FIRE PROTECTION
5. Show locations of permanently wired smoke detectors with battery backup: Please see
item 6 below. Can not find note b as responded. Please show the locations.
Inside each bedroom. Any bedroom on the 2nd floor?
Centrally located in corridor or area giving access to sleeping rooms.
On each story.
d When sleeping rooms are upstairs, at the upper level in close proximity to
the
stair.
e) In rooms adiacent to hallways serving bedrooms, when such rooms have a
ceiling height 24 inches or more above the ceiling height in the hallway.
NOTE: Detectors shall sound an alarm audible in all sleeping areas of the unit. Section
310.9.1.
6. When the valuation of a room addition or repair exceeds $1,000, or when sleeping rooms
are created, smoke detectors shall be provided per the above, except that smoke
detectors added at existing construction need only be battery powered. Section
310.9.1.2. See item 5 above.
Carlsbad 02-624
January 22, 2003
EXITS, STAIRWAYS, AND RAILINGS
8. Guardrails (Section 509.1):
b) Shall be detailed showing adequacy of connections toresist the horizontal force
prescribed in Table 16-13. Please submit calculations. 1) THE DETAIL IS NOT
CLEAR. PLEASE SUBMIT CALCULATIONS. 2) IT SEEMS THAT THE GUARDRAIL
IS MADE UP OF GLASS. ALL THE EDGES OF THE SAME SHOULD BE FULLY
SUPPORTED OR SUBMIT CALCULATIONS OF THE GLASS TO VERIFY
STRUCTURAL INTEGRITY OF THE SAME.
FRAMING
18. Provide calculations for main vertical and horizontal framing members and
footings. Section 106.3.3. This is to verify the existing structural elements being
affected by this addition. PLEASE SUBMIT CALCULATIONS FOR THE EXISTING
FOUNDATION.
. ENERGY CONSERVATION
32. The regulations require a properly completed and properly signed Form CF-1 R to be
either imprinted on the Dlans, tabed to the plans or "sticky backed" on the plans.
to allow the building inspector to readily compare the actual construction with the
requirements of the approved energy design. The owner/designer should sign the
space provided for on the. CF-1 R form.
MISCELLANEOUS
Please show the size of the existing foundation supporting the addition. The size is not
shown on sheet I as responded. PLEASE SEE ITEM 18 ABOVE.
Please show how the addition would be heated. Please show on the plans. WHERE
IS IA SHEET I GEN. NOTES AS RESPONDED?
Carlsbad 02-624
January 22, 2003
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page; etc.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they are located in the plans.
Have changes been made to the plans not resulting-from this correction list? Please
indicate:
Yes.D No lJ
The jurisdiction has contracted with Esgil Corporation !ocated at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to perform
the plan review for .your project. If you have any questions regarding these plan review
items, please contact Bert Domingo at Esgil Corporation. Thank you.
4
EsGil Corporation
In Partnership with Government for Building Safety
DATE: July 11, 2002
JURISDICTION: Carlsbad
PLAN CHECK NO.: 02-624
PROJECT ADDRESS: 2415 Tuttle St.
PROJECT NAME: SFD Addition for Fishbeck
SET:!!
nPAN
ANT
EVIEWER
U FILE
jlj The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved' and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
Corporation until corrected plans are submitted for recheck.
LI The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Don Fishbeck
2415 Tuttle St., Carlsbad, CA 92008
Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Don 4-4 Telephone #: (760) 720-9868
Date contacted: i2J2.(by:i3P ) Fax #:
Mail -1e1eph0ne..-1 Fax In Person
LI REMARKS:
By: Bert Domingo Enclosures:
Esgil Corporation
fl GA 0 MB 0 EJ D PC 711102 tmsmtl.dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
Carlsbad 02-624
July 11, 2002
RECHECK PLAN CORRECTION LIST
JURISDICTION: Carlsbad
PROJECT ADDRESS: 2415 Tuttle St.
DATE PLAN RECEIVED BY
ESGIL CORPORATION: 7/1/02
REVIEWED BY: Bert Domingo
PLAN CHECK NO.: 02-624
SET: II
DATE RECHECK COMPLETED:
July 11, 2002
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and disabled access. This plan review is
based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinances enforced by the Planning Department, Engineering Department
or other departments.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
Please make all corrections on the original tracings and submit two new sets of prints to:
ESGIL CORPORATION.
To facilitate rechecking, please identify, next to each item, the sheet of the plans upon
which each correction on this sheet has been made and return this sheet with the
revised plans.
The following items have not been resolved from the previous plan reviews. The original
correction number has been given for your reference. In case you did not keep a copy of
the prior correction list, we have enclosed those pages containing the outstanding
corrections. Please contact me if you have any questions regarding these items.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and where
they are located on the plans. Have changes been made not resulting from this list?
DYes UNo
Carlsbad 02-624
July 11, 2002
. PLANS
1. Please make all corrections on the original tracings, as requested in the correction list.
Submit three sets of plans for commercial/industrial projects (two sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted in one of
two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760) 602-2700.
The City will route the plans to EsGil Corporation and the Carlsbad Planning, Engineering
and Fire Departments.
Bring one corrected set of plans and calculations/reports to EsGil Corporation, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad Building
Department for routing to their Planning, Engineering and Fire Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by EsGil Corporation is
complete.
2. All sheets of plans must be signed by the person responsible for their preparation.
(California Business and Professions Code). This will be checked when all the items
below are met.
3. Plans, specifications and calculations shall be signed and sealed by the California state
licensed engineer or architect responsible for their preparation, for plans deviating from
conventional wood frame construction. Specify expiration date of license. (California
Business and Professions Code).). This will be checked when all the items below
are met.
. FIRE PROTECTION
5. Show locations of permanently wired smoke detectors with battery backup: Please see
item 6 below. Can not find note b as responded. Please show the locations.
Inside each bedroom.
Centrally located in corridor or area giving access to sleeping rooms.
On each story.
When sleeping rooms are upstairs, at the upper level in close proximity to the
stair.
In rooms adjacent to hallways serving bedrooms, when such rooms have a ceiling
height 24 inches or more above the ceiling height in the hallway.
NOTE: Detectors shall sound an alarm audible in all sleeping areas of the unit. Section
310.9.1.
6. When the valuation of a room addition or repair exceeds $1,000, or when sleeping rooms
are created, smoke detectors shall be provided per the above, except that smoke
detectors added at existing construction need only be battery powered. Section
310.9.1.2. See item 5 above.
Carlsbad 02-624
July 11, 2002
EXITS, STAIRWAYS, AND RAILINGS
Guardrails (Section 509.1):
b) Shall be detailed showing adequacy of connections to resist the horizontal force
prescribed in Table 16-13. Please submit calculations.
. ROOFING
Specify on the plans the following information for the roof materials, per Section 106.3.3:
Sheet 10 as responded did not show the information requested.
a). Manufacturer's name.
Product name/number.
ICBO approval number, or equal.
. FRAMING All the items below will be checked when items 18 & 19 are met.
Provide roof framing plan and floor framing plan. Section 106.3.3.
Provide framing sections through proposed and existing structures to verify
structural relationship and shear transfer requirements. Section 106.3.3.
Specify all header sizes for openings over 4' wide. Please see also the existing
headers on the 111 floor being affected by the addition. Section 2320.11.6.
Provide calculations for main vertical and horizontal framing members and
footings. Section 106.3.3. This is to verify the existing structural elements being
affected by this addition.
19 Provide calculations for lateral loads, shear panels, shear transfer and related.
Section 106.3.3. This is required to verify conformance to section 3401 of the 97
UBC.
20 Show on the plans all structural requirements developed in the structural
calculations. Section 106.3.3.
Specify nail size and spacing for all shear walls, floor and roof diaphragms.
Indicate required blocking. Maintain maximum diaphragm dimension ratios.
Sections 2315 and 2513.
In Seismic Zone 4, aspect ratios are limited to 2:1 for wood shear panels. Table 23-
II-G.
Carlsbad 02-624
July 11, 2002
23. In Seismic Zones 3 and 4, where allowable shear values exceed 350 plf in wood
structural panel shear walls, foundation sill plates and all framing members
receiving edge nailing from abutting panels shall not be less than a single 3"
nominal member. In shear walls where the total wall design shear does not exceed
600 plf, a single 2" nominal sill plate may be used, provided the anchor bolts are
designed for a load capacity of 50% or less of the allowable capacity. Plywood
joint and sill plate nailing shall be staggered in all cases. Table 23-I1-I-I, footnote
3.
25. Specify plywood and/or particle board thickness, grade and panel span rating.
Table 23-II-E-1.
. ENERGY CONSERVATION
Detail or note on the plans: "The return air plenum serving the mechanical equipment
must be fully ducted from the equipment to the conditioned space. Drop ceilings, wall
cavities and equipment platforms may not be used as plenums." Not shown on sheet I
as responded.
The regulations require a properly completed and properly signed Form CF-1 R to be
either imprinted on the plans, taped to the plans or "sticky backed" on the plans,
to allow the building inspector to readily compare the actual construction with the
requirements of the approved energy design. The owner/designer should sign the
space provided for on the CF-1 R form.
MISCELLANEOUS
36. Please show the size of the existing family south window to verify lighting and ventilation
requirement. Where is the window schedule?
Please show the size of the existing foundation supporting the addition. The size is not
shown on sheet I as responded.
Please show how the addition would be heated. Please show on the plans.
Please show the specifications on the plans the construction materials to be used. The
inspectors could do their job better if they do not leaf thru the submitted different
sizes of plans and 8 I/2X11 specifications and notes. The plans submitted may
not be acceptable to the City.
Carlsbad 02-624
July 119 2002
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a result of
corrections from this list. If there are other changes, please briefly describe them and
where they. are located in the plans.
Have changes been made. to the plans not resulting from this correction list? Please
indicate:
Yes El No IJ
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding these plan
review items, please contact Bert Domingo at Esgil Corporation. Thank you.
EsGil Corporation
In Partnership with government for Bui(1ing Safety
DATE: March 11, 2002
JURISDICTION: Carlsbad
PLAN CHECK NO.: 02-624
PROJECT ADDRESS: 2415 Tuttle St.
PROJECT NAME: SFD Addition for Fishbeck
SET:I
U
'CANT
U
~PFANkEVIEVVER U
U FILE
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
J The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at Esgil
- Corporation until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Don Fishbeck
2415 Tuttle St., Carlsbad, CA 92008
El Esgil Corporation staff did not advise the applicant that the plan check has been completed.
Esgil Corporation staff did advise the applicant that the plan check has been completed.
Person contacted: Don Telephone #: (760) 720-9868
Date contacted: .3 /,3/0 2{by: 14-) Fax #:
Mai1-"'Telephone - Fax In Person
J REMARKS:
By: Bert Domingo Enclosures:
Esgil Corporation
E] GA 0MB DEJ DPC 3/4/02 tmsmtl.dot
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-1576
p
Carlsbad 02-624
March 11, 2002
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK NO.: 02-624 JURISDICTION: Carlsbad
I PROJECT ADDRESS 2415 Tuttle St.
FLOOR AREA: 217 SQ. Fr. STORIES: TWO
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: March 11, 2002
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 3/4/02
PLAN REVIEWER: Bert Domingo
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the Uniform Building Code,
Uniform Plumbing Code, Uniform Mechanical Code, National Electrical Code and state laws
regulating energy conservation, noise attenuation and access for the disabled. This plan review
is based on regulations enforced by the Building Department. You may have other corrections
based on laws and ordinance by the Planning Department, Engineering Department, Fire
Department or other departments. Clearance from those departments may be required prior to
the issuance of a building permit.
Present California law mandates that residential construction comply with the 1998 edition of
the California Building Code (Title 24), which adopts the following model codes: 1997 UBC,
1997 UPC, 1997 UMC and 1996 NEC (all effective 7/1/99).
The above regulations apply to residential construction, regardless of the code editions adopted
by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 106.4.3,
1997 Uniform Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section. etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad 02-624
March 11, 2002
PLANS
1. Please make all corrections on the original tracings, as requested in the
correction list. Submit three sets of plans for commercial/industrial projects (two
sets of plans for residential projects). For expeditious processing, corrected sets
can be submitted in one of two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil Corporation and the Carlsbad
Planning, Engineering and Fire Departments.
Bring one corrected set of plans and calculations/reports to EsGil Corporation,
9320 Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468.
Deliver all remaining sets of plans and calculations/reports directly to the City of
Carlsbad Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil Corporation only will not be
reviewed by the City Planning, Engineering and Fire Departments until review by
EsGil Corporation is complete.
2. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
3. Plans, specifications and calculations shall be signed and sealed by the
California state licensed engineer or architect responsible for their preparation,
for plans deviating from conventional wood frame construction. Specify
expiration date of license. (California Business and Professions Code).
4. Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 1998 edition of the California Building Code (Title 24), which
adopts the 1997 UBC, UMC and UPC and the 1996 NEC.
. FIRE PROTECTION
5. Show locations of permanently wired smoke detectors with battery backup:
Please see item 6 below.
Inside each bedroom.
Centrally located in corridor or area giving access to sleeping rooms.
On each story.
In the basement, if part of the dwelling unit.
When sleeping rooms are upstairs, at the upper level in close proximity to
the stair.
In rooms adjacent to hallways serving bedrooms, when such rooms have
a ceiling height 24 inches or more above the ceiling height in the hallway.
NOTE: Detectors Shall sound an alarm audible in all sleeping areas of the unit.
Section 310.9.1.
91
Carlsbad 02-624
March 11, 2002
6. When the valuation of a room addition or repair exceeds $1,000, or when
sleeping rooms are created, smoke detectors shall be provided per the above,
except that smoke detectors added at existing construction need only be battery
powered. Section 310.9.1.2.
. GENERAL RESIDENTIAL REQUIREMENTS
7. Glazing in the following locations should be of safety glazing material in
accordance with Section 2406.4 (see exceptions):
Fixed and sliding panels of sliding door assemblies and panels in swinging
doors other than wardrobe doors.
Glass railings, regardless of height, above a walking surface (including
structural baluster panels and nonstructural in-fill panels).
EXITS, STAIRWAYS, AND RAILINGS
8. Guardrails (Section 509.1):
Shall have a height of 36".
Shall be detailed showing adequacy of connections to resist the horizontal
force prescribed in Table 16-13. Please submit calculations.
Openings between railings shall be less than 4". The triangular openings
formed by the riser, tread and bottom element of a guardrail at a stair shall
be less than 6".
ROOFING
9. Specify on the plans the following information for the roof materials, per Section
106.3.3:
Manufacturer's name.
Product name/number.
ICBO approval number, or equal.
10. Specify roof slope.
11. Show the required ventilation for attics (or enclosed rafter spaces formed where
ceilings are applied directly to the underside of roof rafters). The minimum vent
area is 1/150 of attic area (or 1/300 of attic area if at least 50% of the required
vent is at least 3 feet above eave vents or cornice vents). Show area required
and area provided. Section 1505.3.
Carlsbad 02-624
March 11, 2002
12. Where eave vents are installed, insulation shall not block the free flow of air. A
minimum of 1" of air space shall be provided between the insulation and the roof
sheathing. To accommodate the thickness of insulation plus the required 1"
clearance, member sizes may have to be increased for rafter-ceiling joists.
Section 1505.3.
13. Note on the plans: "Attic ventilation openings shall be covered with
corrosion-resistant metal mesh with mesh openings of 1/4-inch in dimension."
Section 1505.3.
FRAMING
14. Show or note fire stops at the following locations per Section 708.2.1:
In concealed spaces of stud walls and partitions, including furred spaces,
at the ceiling and floor levels and at 10 foot intervals both vertical and
horizontal;
At all interconnections between concealed vertical and horizontal spaces
such as occur at soffits, drop ceilings and cove ceilings;
In openings around vents, pipes, ducts and similar openings which afford
a passage for fire at ceiling and floor levels, with noncombustible
materials.
15. Provide roof framing plan and floor framing plan. Section 106.3.3.
16. Provide framing sections through proposed and existing structures to verify
structural relationship and shear transfer requirements. Section 106.3.3.
17. Specify all header sizes for openings over 4' wide. Please see also the existing
headers on the floor being affected by the addition. Section 2320.11.6.
18. Provide calculations for main vertical and horizontal framing members and
footings. Section 106.3.3. This is to verify the existing structural elements being
affected by this addition.
19. Provide calculations for lateral loads, shear panels, shear transfer and related.
Section 106.3.3. This is required to verify conformance to section 3401 of the 97
UBC.
20. Show on the plans all structural requirements developed in the structural
calculations. Section 106.3.3.
Carlsbad 02-624
March 11, 2002
Specify nail size and spacing for all shear walls, floor and roof diaphragms.
Indicate required blocking. Maintain maximum diaphragm dimension ratios.
Sections 2315 and 2513.
In Seismic Zone 4, aspect ratios are limited to 2:1 for wood shear panels. Table
23-II-G.
In Seismic Zones 3 and 4, where allowable shear values exceed 350 plf in wood
structural panel shear walls, foundation sill plates and all framing members
receiving edge nailing from abutting panels shall not be less than a single 3"
nominal member. In shear walls where the total wall design shear does not
exceed 600 plf, a single 2" nominal sill plate may be used, provided the anchor
bolts are designed for a load capacity of 50% or less of the allowable capacity.
Plywood joint and sill plate nailing shall be staggered in all cases. Table 23-I1-I-
1, footnote 3.
Show location of attic access with a minimum size of 22"x30", unless the
maximum vertical headroom height in the attic is less than 30". Access must be
provided to each separated attic area, shall be located in a hallway or other
readily accessible location and 30" headroom clearance is required above the
opening. Section 1505.1.
Specify plywood and/or particle board thickness, grade and panel span rating.
Table 23-I1-E-1.
. ENERGY CONSERVATION
Provide plans, calculations and worksheets to show compliance with current
energy standards.
The requirements for the prescriptive package components have been updated
as of June 1, 2001. If using the prescriptive compliance approach, show
compliance with the new Package C or D, or the alternate component package
for C or D (Packages A and B have both been eliminated).
The window schedule shall clearly describe the required U-factor and solar heat
gain coefficient (SHGC) values and demonstrate compliance with the Title 24
energy calculations.
Carlsbad 02-624
March 11, 2002
29. The version of the computer program that you have used is no longer current.
Provide new calculations, using acceptable updated residential computer energy
programs. As of June 1, 2001, they are the following:
Micropas 6.01
EnergyPro 3.1
CalRes1.4
Cloth backed duct tape is no longer permitted to be used as the sole connection
for mechanical ducting. Note on the plans that duct tape, as a minimum, meeting
the requirements of UL181, 181A, or 181B, shall be used or additional duct
attachment devices such as tie wraps or mastic will be required for installing
mechanical ducting.
Detail or note on the plans: "The return air plenum serving the mechanical
equipment must be fully ducted from the equipment to the conditioned space.
Drop ceilings, wall cavities and equipment platforms may not be used as
plenums."
The regulations require a properly completed and properly signed Form CF-1 R
to be either imprinted on the plans, taped to the plans or "sticky backed" on the
plans, to allow the building inspector to readily compare the actual construction
with the requirements of the approved energy design.
All sheets of the latest CF-1 R form must be imprinted onto the plans (sheets I of
3,2 of 3 and 3 of 3 must be included).
A mechanical duct sealing certification test must be performed by a certified
HERS inspector or compliance with the "Alternate to Package 0" requirements
shall be shown on the CFI-R form. (This requirement is valid for all new low rise
residential construction including room additions greater than 100 square
feet that are using the Prescriptive energy calculation method.)
Note on the plans: "The manufactured windows shall have a label attached
certified by the National Fenestration Rating Council (NFRC) and showing
compliance with the energy calculations."
MISCELLANEOUS
Please show the size of the existing family south window to verify lighting and
ventilation requirement.
The guardrail glass should be supported on all its edges or submit complete
calculations for the glass.
Carlsbad 02-624
March 11, 2002
The exterior wp and the near sink electrical receptacles should be GFCI
protected.
Please show the size of the existing foundation supporting the addition.
Please show how the addition would be heated.
Please show the specifications on the plans the construction materials to be
used.
To speed up the review process, note on this list (or a copy) where each correction item
has been addressed, i.e., plan sheet, note or detail number, calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a result
of corrections from this list. If there are other changes, please briefly describe them and
where they are located in the plans.
Have changes been made to the plans not resulting from this correction list? Please
indicate:
Yes E3 No E3
The jurisdiction has contracted with Esgil Corporation located at 9320 Chesapeake
Drive, Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding these plan
review items, please contact Bert Domingo at Esgil Corporation. Thank you.
Carlsbad 02-624
March 11, 2002
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK NO.: 02-624
PREPARED BY: Bert Domingo DATE: March 11, 2002
BUILDING ADDRESS: 2415 Tuttle St.
BUILDING OCCUPANCY: R 3 TYPE OF CONSTRUCTION: V N
BUILDING
PORTION
AREA
(Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
24,137
Air Conditioning
Fire Sprinklers
TOTAL VALUE
24,137 Jurisdiction Code Icb IBy Ordinance
Bldg. Permit Fee by Ordinance v 1 I $215.191
Plan Check Fee by Ordinance [v J I $139.871
Type of Review: El Complete Review 0 Structural Only
0 Repetitive Fee 0 Other Repeats Hourly Hour *
Esgil Plan Review Fee $120.51
Comments:
Sheet I of I
macvalue.doc
Cit of Carlsbad
BUILDING PLANCHECK CHECKLIST
DATE: 3- J-o5 PLANCHECK NO.: CBe - Q
BUILDING ADDRESS:
PROJECT DESCRIPTION: DESCRIPTION: - -
ASSESSOR'S PARCEL NUMBER:
ENGINEERING DEPARTMENT
APPROVAL
The item you have submitted for review has been
approved. The approval is based on plans"
information and/or • specifications provided in your
submittal; therefore any changes to these items after
this date, including field modifications, must be
reviewed by this office to insure continued
conformance with applicable codes. Please review
carefully all comments attached, as failure to comply
with instructions in this report can- result in
suspension of permit to build.
D A Right-of-Way permit is required prior to
construction of the following improvements: By: . Date:
By: Date:
:: .Z. ... FOR OFFICIAL USE ONLY
-, ENGINEERING AUTHORIZATION TO ISSUE BUILDING PERMIT
.•
....
.
.••• ..D .te; -/.. Id/
EST. VALUE: c9 I3
DENIAL
Please see the attached report of deficiencies
marked with 0. Makenecessary corrections to plans
or specifications for compliance with .applicable
codes and standards. Submit corrected plans and/or
specifications to this office for review.
By: Date:
ATTACHMENTS
D Dedication Application
D Dedication Checklist
0 Improvement Application
O Improvement Checklist
Future Improvement Agreement
Grading Permit Application
0 Grading Submittal Checklist
o Right-of-Way Permit Application
O Right-of-Way Permit Submittal Checklist
and Information Sheet
Sewer Fee Information Sheet *
NiINLKINti DEPT. GUN IALI KUN
Name: TANIYA WADE
City of Carlsbad
Address: 1635 Faraday Avenue, Carlsbad, CA 92008
Phone: (760) 602-2773
CFD INFORMATION
Parcel Map No:
Lots:
Recordation: :
Carlsbad Tract:
A-4
CA 92008-7314 • (760) 602-2720 • FAX (760 -8562 ®
r#of ,23Lq3 C_v
BUILDING PLANCHECK CHECKLIST.
SITE PLAN
1ST 4ND 3RD
J 1. Provide a fully dimensioned site plan drawn to scale. Show:
A. North Arrow F. Right-of-Way Width & Adjacent Streets
B. Existing & Proposed Structures G. Driveway widths
C. Existing Street Improvements H. Existing or proposed sewer lateral
D. Property Lines I. Existing or proposed water service
E. Easements J. Existing or proposed irrigation service
0 2. Show on site plan
• A. Drainage Patterns
Building pad surface drainage must maintain a minimum slope of one
percent towards an adjoining street or an approved drainage course.
ADD THE FOLLOWING NOTE: "Finish grade will provide a minimum positive
drainage of 2% to swale 5' away from building."
Existing & Proposed Slopes and Topography
Size, type, location, alignment of existing or proposed sewer and water service
(s) that serves the project. Each unit requires a separate service, however,
second dwelling units and apartment complexes are an exception.
Sewer and water laterals should not be located within proposed driveways, per
standards.
0 0 3. Include on title sheet:
Site address
Assessors Parcel Number
Legal Description
For commercial/industrial buildings and tenant improvement projects, include:
total building square footage with the square footage for each different use,
existing sewer permits showing square footage of different uses (manufacturing,
warehouse, office, etc.) previously approved.
EXISTING PERMIT NUMBER DESCRIPTION
HWORDDOcSCHXLSTBIiIlI PaniediCIt Fctm (Genedc).c 2 •
TI14CO
BUILDING PLANCHECK CHECKLIST
1ST ND 3 rd DISCRETIONARY APPROVAL COMPLIANCE
V1iâ 0 0 4a. Project does not comply with-the following Engineering Conditions of approval for
1(1! Project No.______________________________________________________
0 0 0 4b. All conditions are in compliance. Date:
DEDICATION REQUIREMENTS
1121" 0 D 5. Dedication for all street Rights-of-Way adjacent to the building site and any storm
drain or utility easements on the building site is required for all new buildings and
for remodels with a value at or exceeding $15.000, pursuant to Carlsbad
V-N
Municipal Code Section 18.40.030.
Dedication required as follows:
Dedication required. Please have a registered Civil Engineer or Land Surveyor
prepare the appropriate legal description together with an 8 W x 11" plat map
and submit with a title report. All easement documents must be approved and
signed by owner(s) prior to issuance of Building Permit. Attached please find an
application form and submittal checklist for the dedication process. Submit the
completed application form with the required cheôklist items and fees to the
Engineering Department in person. Applications will not be accept by mail or fax.
Dedication completed by: Date:
IMPROVEMENT REQUIREMENTS
0 0 6a. All needed public improvements upon and adjacent to the building site must be
constructed at time of building construction whenever the value of the
construction exceeds $75.000, pursuant to Carlsbad Municipal Code Section
18.40.040.
Public improvements required as follows:
Attached please find an application form and submittal checklist for the public
improvement requirements. A registered Civil Engineer must prepare the
appropriate improvement plans and submit them together with the requirements
on the attached checklist to the Engineering Department through a separate plan
check process. The completed application form and the requirements on the
H:WORDDOCSCHKLSfl8uiIdk Plaflthedt cIcst Form (RIDDLE- HNWEY 7-IM)Aoc 3 Rev. 12126196
BUILDING PLANCHECK CHECKLIST
1ST 2ND 3RD
checklist must be submitted in person. Applications by mail or fax are not
accepted. Improvement plans must be approved, appropriate securities posted
and fees paid prior to issuance of building permit.
Improvement Plans signed by: Date:
0 0 0 6b. Construction of the public improvements may be deferred pursuant to Carlsbad
Municipal Code Section 18.40. Please submit a recent property title report or
current grant deed on the property and processing fee of $310 so we may
prepare the necessary Future Improvement Agreement. This agreement must be
signed, notarized and approved by the City prior to issuance of a Building permit.
Future public improvements required as follows:
000
ODD
Enclosed please find your Future Improvement Agreement. Please return
agreement signed and notarized to the Engineering Department.
Future Improvement Agreement completed by:
Date.
No Public Improvements required. SPECIAL NOTE: • Damaged or defective
improvements found adiacent to building site must be repaired to the satisfaction
of the City Inspector prior to occupancy.
GRADING PERMIT REQUIREMENTS
The conditions that invoke the need for a grading permit are found in Section
11.06.030 of the Municipal Code.
7a. Inadequate information available on Site Plan to make a determination on grading
requirements. Include accurate grading quantities (cut, fill, import, export).
0 0 0 7b. Grading Permit required. A separate grading plan prepared by a registered Civil
Engineer must be submitted together with the completed application form
attached. NOTE: The Grading Permit must be issued and rough grading
approval obtained prior to issuance of a Building Permit.
Grading Inspector sign off by: Date:
E] 0 0 7c. Graded Pad Certification required. (Note: Pad certification may be required even
if a grading permit is not required.)
H:WORDDOCStCl4ICL$TlBu1dh19 PlejxheckGldel Form (Genetic 7.14.00).doc 4 Rev. 7114100
BUILDING PLANCHECK CHECKLIST.
1ST ND 3RD
L1 0 7d .No Grading Permit required.
O 0 0 7e. If grading is not required, write No Grading" on plot plan.
MISCELLANEOUS PERMITS
IA7k 0 0 8. A RIGHT-OF-WAY PERMIT is required to do work in City Right-of-Way and/or
I (Y/ private work adjacent to the public Right-of-Way. Types of work include, but are
not limited to: street improvements, tree trimming, driveway construction, tying
into public storm drain, sewer and water utilities.
Right-of-Way permit required for:
14 if 0 0 9. INDUSTRIAL WASTE PERMIT If your facility is located in the City of Carlsbad
sewer service area, you need to contact the Carlsbad Municipal Water District,
located at 5950 El Camino Real, Carlsbad, CA 92008. District personnel can
provide forms and assistance, and will check to see if your business enterprise is
on the EWA Exempt List. You may telephone (760) 438-2722, extension 7153,
for assistance.
Industrial Waste permit accepted by:
Date:
0 0 10. NPDES PERMIT
Complies with the City's requirements of the National Pollutant Discharge
Elimination System• (NPDES) permit. The applicant shall provide best
management practices to reduce surface pollutants to an acceptable level prior to
discharge to sensitive areas. Plans for such improvements shall be approved by
the City Engineer prior to issuance of grading or building permit, whichever
occurs first.
•
V1EEI 0 • 11. 0 Reqdfees are attached
CU-Nølèes required
WATER METER REVIEW
0 0 0 • 12a. Domestic (potable) Use
Ensure that the meter proposed by the owner/developer is not oversized.
Oversized meters are inaccurate during low-flow conditions. • If it is oversized, for
the life of the meter, the City will not accurately bill the owner for the water used.
All single family dwelling units received "standard" 1" service with 5/8" service.
H:WORDOCSCOG.S1Bd Planthed, a* Fern, (Genedc)4oc 5 Ray. 7II4CO
BUILDING PLANCHECK CHECKLIST
1ST 2ND 3RD
If owner/developer proposes a size other than the "standard", then
owner/developer must provide potable water demand calculations,
which include total fixture counts and maximum water demand in gallons
per minute (gpm) A typical fixture count and water demand worksheet is
attached. Once the gpm is provided, check against the "meter sizing
schedule" to verify the anticipated meter size for the unit.
Maximum service and meter size is a 2" service with a 2" meter.
If a developer is proposing a meter greater than 2", suggest the
installation of multiple 2" services as needed to provide the anticipated
demand. (manifolds are considered on case by case basis to limit
multiple trenching into the street).
O 0 0 12b. Irrigation Use (where recycled water is not available)
All irrigation meters must be sized via irrigation calculations (in gpm) prior
to approval. The developer must provide these calculations. Please follow
these guidelines:
If the project is a newer development (newer than 1998), check the recent
improvement plans and observe if the new irrigation service is reflected on
the improvement sheets. If so, at the water meter station, the demand in
gpm may be listed there. Irrigation services are listed with a circled "I",
and potable water is typically a circled "W". The irrigation service should
look like:
_] STA 1+00 Install 2" service and
1.5: meter (estimated 100 gpm)
If the improvement plans do not list the irrigation meter and the
service/meter will be installed via another instrument such as the building
plans or grading plans (wl a right of way permit of course), then the
applicant must provide irrigation calculations for estimated worst-case
irrigation demand (largest zone with the farthest reach). Typically, Larry
Black has already reviewed this if landscape plans have been prepared,
but the applicant must provide the calculations to you for your use. Once
you have received a good example of irrigation calculations, keep a set for
your reference. In general the calculations will include:
Hydraulic grade line
Elevation at point of connection (POC)
Pressure at POC in pounds per square inch (PSI)
Worse case zone (largest, farthest away from valve
Total Sprinkler heads listed (with gpm use per head)
Include a 10% residual pressure at point of connection
3. In general, all major sloped areas of a subdivision/project are to be
irrigated via separate irrigation meters (unless the project is only SFD with
no HOA). As long as the project is located within the City recycled water
HW0RflOC1M.SBI P1aid,ecIdst Fonn (Gerc 6 Rev 7114100
BUILDING PLANCHECK CHECKLIST
1ST 2N0 3RD
service boundary, the City intends on switching these irrigation
services/meters to a new recycled water line in the future.
0 0 0 12c. Irrigation Use (where recycled water is available)
Recycled water meters are sized the same as the irrigation meter above.
If a project fronts a street with recycled water, then they should be
connecting to this line to irrigate slopes within the development. For
subdivisions, this should have been identified, and implemented on the
improvement plans. Installing recycled water meters is a benefit for the,
applicant since they are exempt from paying the San Diego County Water
Capacity fees. However, if they front a street which the recycled water is
there, but is not live. (sometimes they are charged with potable water until
recycled water is available), then the applicant must pay the San Diego
Water Capacity Charge. If within three years, the recycled water line is
charged with recycled water by CMWD, then the applicant can apply for a
refund to the San Diego County Water Authority (SDCWA) for a refund.
However, let the applicant know that we cannot guarantee the refund, and
they must deal with the SDCWA for this.
0 0 13. Additional Comments:
HWORDD005MKLS1'.BU1hI Pbndi Cklst Fain, (Genedc).0 7 Rev. 7114OO
r 0
Of
PLANNING DEPARTMENT
BUILDING PLAN CHECK REVIEW CHECKLIST
~,Z~4/~ Plan Check No. c5te52 Address 2y,~
Planner __ 7t.—%.__-Phone (760) 602- _______________
APN:
Type of Project & Use: Net Project Density: DU/AC -
Zoning:__ GeiPlan: Facilities Management Zone:
CFD (in/out) #_Date of participation: Remaining net dev acres:
Circle One (For non-residential development: Type of land used created by this
permit:) •1
Legend: Z Item Complete Item Incomplete - Needs your action
Environmental Review Required: YES NO TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
Discretionary Action Required: YES NO TYPE
APPROVAL/RESO. NO. - DATE
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval:_________________________________________________
Coastal Zone Assessment/Compliance
Project, site located in Coastal Zone? YES_ NO_
CA Coastal Commission Authority? YES_ NO
If California Coastal Commission Authority: Contact them at - 7575 Metropolitan Drive, Suite
103, San Diego CA 92108-4402;'(619) 767-2370
Determine status (Coastal Permit Required or Exempt):
Coastal Permit Determination Form already completed? YES NO
If NO, complete Coastal Permit Determination Form now.
Coastal Permit Determination Log #:
Follow-Up Actions:
Stamp Building Plans as "Exempt" or "Coastal Permit Required" (at minimum Floor Plans).
Complete Coastal Permit Determination Log-a-s needed.
El r-1 Inclusionary Housing Fee rguir YS - NO
(Effective date of ss nary Housing Ordinance - May 21, 1993.)
Z
tl ted? YES NO
ity Maintenance, enter CB#, toolbar, Screens, Housing Fees, Construct Housing
, UPDATE!)
H:\ADM nchkRevChklst Rev 9/01
Site Plan:
0 1. Provide a fully dimensional site plan drawn to scale. Show: North arrow, property lines,
easements, existing and proposed structures, streets, existing street improvements, right-
of-way width, dimensional setbacks and existing topographical lines (including all side and
rear yard slopes). .
Provide legal description of property and assessor's parcel number.
Policy 44 - Neighborhood Architectural Design Guidelines
0 1. Applicability: YES NO\,")
E] 2. Project complies YES NO________
Zoning:
0 1. Setbacks:
Front: Required Shown
Interior Side: Required Shown
Street Side: Required / Shown
Rear: Required r!!)/ Shown 3,.
Top of slope: Required ...._- Shown
r 0 2. Accessory structure setbacks:
Front: Required .._How n —
_____________ Interior Side: Shown
Street Side: Required Shown
Rear Required Shown
-, ructure separation: Required Shown
Lot Coverage: Required Z Shown
Height: AvL- Required Shown
0 5. Parking: Spaces Required 2!_.. Shown
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required . Shown
El 0 0 Additional Comments______________________________________________________
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER 2 DATE
H:\ADMIN\COUNTER\BldgPlnchkRevChklst Rev 9/01