Permi No: CBR2018-3392
Status: Closed - Finaled
Applied: 12/07/2018
Issued: 03/12/2019
Permit
Fináled:
Inspector: CRenf
Final
Inspection: 9/6/2019 2:19:30PM
Print Date: 09/06/2019
Job Address: 2839 Vista Acedera
Permit Type: BLDG-Residential
Parcel No: 2553111100
Valuation: $10,135.18
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
Description: JUREWITZ: 506 SF DECK (NO FIREPLACE ON THIS PERMIT)
Applicant: Owner:
WATERLINE POOLS AND SPAS INC TRUST JUREWITZ FAMILY TRUST 04-17-17
PIETER DREEUWS 2839 Vista Acedera
CARLSBAD, CA 92009
760-815-6733
Co-Applicant:
WATERLINE POOLS AND SPAS INC
P0 Box 605
CARDIFF, CA 92007-0605
760-815-6733
BUILDING PERMIT FEE ($2000+) $123.83
BUILDING PLAN CHECK FEE (BLDG) $86.68
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL $41.00
581473 GREEN BUILDING STATE STANDARDS FEE $1.00
STRONG MOTION-RESIDENTIAL S
$1.32
Total Fees: $253.83 Total Payments To Date: $253.83 Balance Due: $0.00
Please take NOTICE that approval of your project includes the "Imposition of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes; nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
1635 Faraday Avenue, Carlsbad, CA 92008-7314 1 760-602-2700 1 760-602-8560 f I www.carlsbadca.gov
I
(~'Citv of Building Permit Application
1635 Faraday Ave., Carlsbad, CA 92008
Plan Check No. Q'çcLtj 1'.. 3 9c
Est. Value
Ph: 760-602-272.9 Fax: 760-602-8558 Cdflsbad email: building@carlsbadca.gov Plan Ck. Deposit
www.carlsbadca.ov Date / 7 ..... ;
JOB ADDRESS V Ac: SUITE#/SPACE#/UNIT# APN
- 31 - - O o
CT/PROJECT# LOT# PHASE# BOFUNITS 1 11 BEDROOMS #BATHROOMS TENANT BUSINESS NAME CONSTR. TYPE OCC. GROUP
DESCRIPTION OF WORK: Include Square Feet of Affected Area(s)
(o- co
FIRE EXISTING USE PROPOSED USE GARAGE (SF) PATIOS (S: DECKS (SF) AIR CONDITIONING
1 YES #........ NOD YES 0 NOD
IFIRESPRINKLERS
YES 0 NOD
APPJ4CANT NAME (Primary Contact)
Yieicr ruui Jhtef'oo1s4C#~
PROPEB3Y OWNER NAM ko ss
ADDRESS
R . Box 665-
ADDRESS
CITYJa -06
STATE
W CA Zig CITYf) ) ST ZIP
PHONE
7o — 81 73 3 FAX
I
PHONE
'' -Q 4a oo
FAX
EMAIL
\tJoC.rte pcop&$_c_yaI'oo. Co v
EMAIL
DESIGN PROFESSIONAL NAME ABOVE CONTRACTORBUS. NAME
\A) Po I E its a* &- Ii ra e o
ADDRESS ADDRESS
P- o. ôx
CITY STATE ZIP CITY TATE S
C,a._+-4
ZIP
PHONE FAX PHONE
7('O —
FAX
EMAIL IL EWAh,i le pools c..c@ Cswv-._
y
aiico.
__________________________
STATE LIC. # STATE LIC #
q,5-7 &o
CLASS I CITY BUS. LIC.#
I
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to its issuance, also requires the applicant for such permit to file a signed statement that he is licensed pursuant to the provisions of the Contractor's License Law jChapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code) or that he is exempt therefrom, and the basis for the alleged exemption. Any violation of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars ($500)).
Workers' Compensation Declaration: I hereby affirm under penally of perjury one of the following declarations:
I have and will maintain a certificate of consent to self-insure for workers' compensation as provided by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
(] I have and will maintain
.
workers' corn ensation, as required by Section 37 0 of the Labor Code, for the erformance of the work for F
/
h this permit is issued. My workers' compensation nsyrance carrier and policy
number are: Insurance Co. co fYI OV'- ml sump 7No. 9 24 Expiration Date 7 /1
This section need not be completed if the permit is for one hundred dollars ($100) or less.
0 Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become subject to the Workers' Compensation Laws of
California. WARNING: Failure to secure workers' corn sation coverage is unlawful, and shalt subject an employer to criminal penalties and civil fines up t9 one hundred thousand dollars (&100,000), in
addition to the cost of compensation, damages as p ided for in Section 3706 of the Labor code, interest and attorney's fees. / /
CONTRACTOR SIGNATURE . AGENT DATE % tf .h/ I
J
I hereby affirm that lam exempt from Contractor's License Law for the following reason:
0 I, as owner of the properly or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec. 7044, Business and Professions Code: The Contractor's
License Law does not apply to an owner of property who builds or improves thereon, and who does such work himself or through his own employees, provided that such improvements are not intended or offered for
sale. If, however, the building or improvement is sold within one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
O I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of
property who builds or improves thereon, and contracts for such projects with contractor(s) licensed pursuant to the Contractor's License Law).
o i am exempt under Section ______________Business and Professions Code for this reason:
I personally plan to provide the major labor and materials for construction of the proposed property improvement. 0 Yes 0 No
I (have / have not) signed an application for a building permit for the proposed work.
I have contracted with the following person (firm) to provide the proposed construction (include name address / phone / contractors' license number):
I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name! address! phone! contractors' license number):
I will provide some of the work, but I have contracted (hired) the following persons to provide the work indicated (include name I address I phone! type of work):
.PROPERTY OWNER SIGNATURE DAGENT DATE
'4
rVO~~P LE TE ft:IIL 1EI.JJI1I l*'IIJ I gVI:III Ii O NLY
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention program under Sections 25505, 25533 0125534 of the
Presley-Tannyr Hazardous Substance Account Act? 0 Yes 0 No
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? C3 Yes 0 No
Is the facility to be constructed within 1,000 feet of the outer boundary of a school site? 0 Yes 0 No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS THE APPLICANT HAS MET OR IS MEETING THE REQUIREMENTS OF THE OFFICE OF
EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
ICONS TR U CTI O NC*aKSgfJuuII.iIA G E N CY it
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name Lender's Address
I certify that i have mad the application and state that the above information is correct and that the information on the plans is accurate. I agree to comply with all City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD
AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPNSES WHICH MAY IN ANYWAY RUE AGAINST SAID CITY INCONSEQUENCE OF THE GRANTING OF THIS PERMIT.
OSHA: An OSHA permit is required for excavations over 5'0èp and demolition or construction o trüctures over 3 stories in height.
EXPIRATION: Every permit issued by the Building Offlciaj,(nder the provisions of this Code shal xpim by limitation and become null and void it the building or work apthorized by such permit is not commenced within
180 days from the date of such permit or if the buildiydwork authorized by such permit is su ended or abandoned at any time after the work is commenced for afenT (Section 106.4.4 Uniform Building Code).
.APPLICANT'S SIGNATURE DATE
Permit Type: BLDG-Residential Application Date: 12/07/2018 Owner: TRUST JUREWITZ FAMILY TRUST
04-17-17
Work Class: Deck Issue Date: 03/12/2019 Subdivision: CARLSBAD TCT#88-03-03
ARROYO LA COSTA UNIT#03
Status: Closed - Finaled Expiration Date: 12/17/2019 Address: 2839 Vista Acedera
Carlsbad, CA 92009-6900
IVR Number: 15904
Scheduled
Date
Actual
Start Date Inspection Type Inspection No. In Status Primary Inspector Reinspection Complete
03/21/2019 03/21/2019 BLDG-11 086652-2019 Partial Pass Chris Renfro Reinspection Incomplete
Foundatlon!FtglPier
S (Rebar)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
04/1512019 04/15/2019 BLDG-14 088875.2019 Failed Chris Renfro Reinspection Complete
• Frame/Steel/Bolting!
Welding (Decks)
• Checklist Item COMMENTS Passed
BLDG-Building Deficiency See card for corrections. No
06/06/2019 06/06/2019 BLDG-34 Rough 093901-2019 Partial Pass Chris Renfro Reinspection Incomplete
Electrical
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Rough electrical on deck/patio cover lids. Yes
OK towrap
06/20/2019 06/20/2019 BLDG-18 Exterior 095143.2019 Passed Chris Renfro Complete
Lath/Drywall
Checklist Item • COMMENTS • Passed
• BLDG-Building Deficiency Yes
09/06/2019 09/06/2019 BLDG-Final 103224-2019 Passed Chris Renfro Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency • Yes
BLDG-Plumbing Final • Yes
BLDG-Mechanical Final Yes
BLDG-Structural Final Yes
BLDG-Electrical Final Yes
September 06, 2019 • Page 1 of 1
EsGil
A SAFEbuUtCompany
DATE: 02/11/19 U APPLICANT
U JURIS.
JURISDICTION: Carlsbad
PLAN CHECK #.: CBR2018-3392 SET: III
PROJECT ADDRESS: 2839 Vista Acedera
PROJECT NAME: New Deck for the Jerwetz Residence
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
LI The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Pieter Dreeuws
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Pieter 9euws Telephone #: 760 815 6733
Date contacted: ) Email: waterlinepoolsspas@yahoo.com
Mail Telephone Fax In Person
REMARKS: Fireplace to be on separate permit.
By: Javier Snider Enclosures:
EsGil
02/04/19
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax(858)560-1576
EsGilV/S
A SAFEbulif Company
DATE: 01/31/19
JURISDICTION: Carlsbad
PLAN CHECK #.: CBR2018-3392 SET: II
PROJECT ADDRESS: 2839 Vista Acedera
PROJECT NAME: New Deck for the Jerwetz Residence
U APPLICANT
U JURIS.
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
LI The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Pieter Dreeuws
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Pieter Dreeuws Telephone #: 760 815 6733
Date contacted: (by: ) Email: waterlinepoolsspasyahoo.com
Mail Telephone Fax In Person
LI REMARKS:
By: Javier Snider Enclosures:
EsGil
01/24/19
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax (858) 560-576
Carlsbad CBR2018-3392
01/31/19
NOTE: The items listed below are from the previous correction list. These
remaining items have not been adequately addressed. The numbers of the items
are from the previous check list and may not necessarily be in sequence. The
notes in bold font are current.
PLANS
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil and the Carlsbad Planning,
Engineering and Fire Departments.
Bring TWO corrected set of plans and calculations/reports to EsGil, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments. Please provide complete sets upon resubmittal. Also small
project shall be provided on not less that 11" by 8" sheets
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil is complete.
2. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
Plans deviating from conventional wood frame construction shall have the
structural portions signed and sealed by the California state licensed engineer or
architect responsible for their preparation, along with structural calculations.
(California Business and Professions Code).
Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 2016 California Residential Code, which adopts the 2015 IRC,
2015 UMC, 2015 UPC and the 2014 NEC. Section R106.1.
Provide a fully dimensioned site plan drawn to scale. Section R106.2. Please
include the following:
a) North arrow.
ROOFS/DECKS/BALCONIES
Specify on the plans the following information for the deck/balcony surfacing
materials, per Section R106.1.1: Note ESR 2201 of plans.
Manufacturer's name and product name/number.
ICC approval number, or equal.
Carlsbad CBR2018-3392
01/31/19
ELECTRICAL
A balcony, deck, or porch that is accessible from the interior of the dwelling will
require a minimum of one receptacle outlet. CEC 210.52(E) (3). This receptacle
must be GFCI protected. Show on plans.
MISCELLANEOUS
Please provide the listing for the fireplace. Show manufacturer specified offsets
from combustible surfaces.
If the fireplace is not a listed or approved design. Please see 2111 of the CBC.
Note special inspection for masonry fireplace.
Please coordinate scope and permit to both include the masonry fireplace and
spiral stair case.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes El No U
14. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Javier Snider at EsGil. Thank you.
EsGil
A SAFEbuittCompariy
DATE: 12/17/18 0 APPLICANT
D JURIS.
JURISDICTION: Carlsbad
PLAN CHECK #.: CBR2018-3392 SET: I
PROJECT ADDRESS: 2839 Vista Acedera
PROJECT NAME: New Deck for the Jerwetz Residence
The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
The applicant's copy of the check list has been sent to:
Pieter Dreeuws
EsGil staff did not advise the applicant that the plan check has been completed.
EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Pieter Dreeuws Telephone #: 760 815 6733
Date contacted: (by: ) Email: waterlinepoolsspas@yahoo.com
Mail Telephone Fax In Person
FI REMARKS:
By: Javier Snider Enclosures:
EsGil
12/10/18
9320 Chesapeake Drive, Suite 208 • San Diego, California 92123 • (858) 560-1468 • Fax(858)560-1576
Carlsbad CBR2018-3392
12/17/18
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK #.: CBR2018-3392 JURISDICTION: Carlsbad
PROJECT ADDRESS: 2839 Vista Acedera
FLOOR AREA: Deck=506sf
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 12/17/18
STORIES:
HEIGHT:
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 12/10/18
PLAN REVIEWER: Javier Snider
FOREWORD (PLEASE READ):
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBR2018-3392
.12/17/18
[DO NOT PAY- THIS IS NOTAN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK #.: CBR2018-3392
PREPARED BY: Javier Snider DATE: 12/17/18
BUILDING ADDRESS: 2839 Vista Acedera
BUILDING OCCUPANCY: R-3
BUILDING
PORTION
AREA
(Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code I I #N/A
1997 UBC Building Permit Fee
1997 LJBC Plan Check Fee wi
Type of Review: El Complete Review El Structural Only
El Repetitive Fee
Repeats
El Other
El Hourly Hr. @ *
EsGil Fee
Comments:
Sheet 1 of 1
Carlsbad CBR2018-3392
12/17/18
PLANS
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil is complete.
2. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
3. Plans deviating from conventional wood frame construction shall have the
structural portions signed and sealed by the California state licensed engineer or
architect responsible for their preparation, along with structural calculations.
(California Business and Professions Code).
4. Provide a statement on the Title Sheet of the plans stating that this project shall
comply with the 2016 California Residential Code, which adopts the 2015 IRC,
2015 UMC, 2015 UPC and the 2014 NEC. Section R106.1.
5. Provide a fully dimensioned site plan drawn to scale. Section R106.2. Please
include the following:
North arrow.
Property lines/easements.
Streets/alleys.
Existing and proposed buildings and structures.
EXITS, STAIRWAYS, AND RAILINGS
6. Guards (Section R312):
a) Shall be detailed to show capability to resist a concentrated load of 200
pounds in any direction along the top rail. Table R301.5.
Carlsbad CBR2018-3392
12/17/18
ROOFS/DECKS/BALCONIES
7. Enclosed framing in wood exterior balconies and decks shall be provided with
openings that provide a net free cross ventilation area not less than 1/150 of the
area of each separate space. CBC Section 2304.12.2.6, as amended by
emergency building standards.
8. Specify on the plans the following information for the deck/balcony surfacing
materials, per Section R106.1.1:
Manufacturer's name and product name/number.
ICC approval number, or equal.
9. Specify minimum 1/4 inch per foot roof slope for drainage. Section R905.9.1.
STRUCTURAL
10. The plans shall indicate that special inspection will be provided for the following
work. (CBC Chapter 17 and Section 107.2)
a) Welding. Welding inspection should be provided in accordance with
Section 1705.2.
11.
ELECTRICAL
A balcony, deck, or porch that is accessible from the interior of the dwelling will
require a minimum of one receptacle outlet. CEC 210.52(E) (3). This receptacle
must be GFCI protected.
MISCELLANEOUS
Is this deck replacing an existing deck? If it is not, are you creating a new portal
to gain access to the deck? Please clarify the existing conditions and all work
that is to be done to achieve the project scope.
To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Carlsbad CBR2018-3392
12/17/18
Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes E3 No L3
16. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Javier Snider at EsGil. Thank you.
Carlsbad CBR2018-3392
12/17/18
fDO NOTPA Y— THIS IS NO TAN/NVOICEJ
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad PLAN CHECK#.: CBR2018-3392
PREPARED BY: Javier Snider DATE: 12/17/18
BUILDING ADDRESS: 2839 Vista Acedera
BUILDING OCCUPANCY: R-3
BUILDING
PORTION
AREA
(Sq. Ft.)
Valuation
Multiplier
Reg.
Mod.
VALUE ($)
506 20.01 10,125
Air Conditioning
Fire Sprinklers
TOTAL VALUE 10,125
Jurisdiction Code ICb IByOrdinance I
1997U6C Building Permit Fee V
1.997 UBC Plan Check Fee
Type of Review: R] Complete Review . 0 Structural Only
E) Repetitive Fee Repeats V
O Other
.
Hourly
EsGil Fee
Hr. @ *
Comments:
Sheet 1 of 1
PLANNING DIVISION
404h> BUILDING PLAN CHECK
Development Services
Planning Division
CITY OF REVIEW CHECKLIST 1635 Faraday Avenue
(760) 602-4610 CARLSBAD P28
DATE: 2/21/19 PROJECT NAME: PATIO COVER PROJECT ID:
PLAN CHECK NO: CBR20I8-3392 SET#: 2 ADDRESS: 2839 VISTA ACEDERA APN:
LI This plan check review is complete and has been APPROVED by the
Division.
By: HECTOR SALGADO
A Final Inspection by the PLANNING Division is required Ej Yes E No
You may also have corrections from one or more of the divisions listed below. Approval
from these divisions may be required prior to the issuance of a building permit.
Resubmitted plans should include corrections from all divisions.
This plan check review is NOT COMPLETE. Items missing or incorrect are listed on
the attached checklist. Please resubmit amended plans as required.
Plan Check Comments have been sent to:
WATER LINEPOOLSSPAS@YAHOO.COM
For questions or clarifications on the attached checklist please contact the following reviewer as marked:
PLANNING ENGINEERING FIRE PREVENTION
760-602-4610 760-602-2750 760-602-4665
Hector Salgado [II 760-602-4624
Hector.Salgado@carlsbadca.gov
Gina Ruiz
760-602-4675
Gina.Ruiz@carlsbadca.gov
Sarah Cluff
760-602-4619
Sarah.Cluff@carIsbadca.gov
Remarks:
Plan Check No. CBR2018-3392 Address 2839 VISTA ACEDERA Date 2/21/19 Review
#2
Planner HECTOR SALGADO Phone (760) 602- 4624
APN:
Type of Project & Use: Net Project Density: DU/AC
Zoning: P-C General Plan: &i Facilities Management Zone: 12
CFD (in/out) #_Date of participation: Remaining net dev acres:_____
(For non-residential development: Type of land use created by this permit:
REVIEW #:
1 2 3 Legend: Z Item Complete LI Item Incomplete - Needs your action
LI El Environmental Review Required: YES El NO El TYPE
DATE OF COMPLETION:
Compliance with conditions of approval? If not, state conditions which require action.
Conditions of Approval:
El El Discretionary Action Required: YES El NO El TYPE
APPROVAL/RESO. NO. DATE
PROJECT NO.
OTHER RELATED CASES:
Compliance with conditions or approval? If not, state conditions which require action.
Conditions of Approval:
El El Coastal Zone Assessment/Compliance
Project site located in Coastal Zone? YES Eli NO Li
CA Coastal Commission Authority? YES Li NO Li
If California Coastal Commission Authority: Contact them at - 7575 Metropolitan Drive,
Suite 103, San Diego, CA 92108-4402; (619) 767-2370
Determine status (Coastal Permit Required or Exempt):
El El Habitat Management Plan
Data Entry Completed? YES El NO El
If property has Habitat Type identified in Table 11 of HMP, complete HMP Permit application
and assess fees in Energov
El El Inclusionary Housing Fee required: YES El NO D
(Effective date of Inclusionary Housing Ordinance - May 21, 1993.)
Data Entry Completed? YES El NO El
For construction of inclusionary units, email notification provided to HNS?: YES El NO El
(Email Susan Steinkemp in HNS with project number and contact info)
El El Housing Tracking Form (form P-20) completed: YES LI NO El N/A El
P-28 Page 2 of 4 07/11
Site Plan:
LI LI EJ Provide a fully dimensional site plan drawn to scale. Show: North arrow, property lines,
easements, existing and proposed structures, streets, existing street improvements, right-of-
way width, dimensional setbacks and existing topographical lines (including all side and rear
yard slopes). Provide legal description of property and assessor's parcel number.
City Council Policy 44— Neighborhood Architectural Design Guidelines
LI 1. Applicability: YES LI NO LI
LI LI 2. Project complies: YES LI NOD
Zoning:
LI LI LI 1. Setbacks:
Front: Required Shown
Interior Side: Required Shown
Street Side: Required Shown
Rear: Required Shown
Top of slope: Required Shown
LI LI 0 2. Accessory structure setbacks:
Front: Required Shown
Interior Side: Required Shown
Street Side: Required Shown
Rear: Required Shown
Structure separation: Required Shown
LI LI LI Lot Coverage: Required Shown
LI LI LI Height: Required Shown
Z LI LI Parking: Spaces Required Shown
(breakdown by uses for commercial and industrial projects required)
Residential Guest Spaces Required Shown
LI LI LI Additional Comments PLAN CHECK #2.
#1. PLEASE REVISE PLANS TO SHOW FULL SITE PLAN TO SCALE.
v #2. PLEASE REVISE PLANS TO SHOW SETBACK TO PROPERTY LINES AT FRONT
AND OF PATIO AND STAIRCASE TO NEAREST PROPERTY LINE.
./#2. PLEASE REVISE PLANS TO SHOW LOT COVERAGE CALCULATION (PLEASE BE
SURE TO INCLUDE GARAGE AND ANY PATIO COVER OR TRELLIS AND STAIRCASE).
OK TO ISSUE AND ENTERED APPROVAL INTO COMPUTER DATE
P-28 Page 3 of 4 . 07/11