HomeMy WebLinkAbout2700 RANCHO PANCHO; ; AS140199; PermitUity 01 Uarlsbad
Sprinkler Permit
Permit No: AS140199
2700 RANCHO
Job Address:
PANCHO
Permit Type: SPRINK
Parcel No: 2226000100
Lot #: 0
Reference No.:
PC #:
Status: ISSUED
Applied 7/29/2014
Approved: 8/11/2014
Issued: 8/11/2014
Inspector:
Project Title: FAITH COMMUNITY CHURCH ALL SPRINKLER SYSTEMS SHALL BE
MONITORED BY AN OFF-SITE CENTRAL STATION INCLUDING
TAMPER SWITCHES ON ALL CONTROL VALVES AND SYSTEM WATER
FLOW SWITCHES. -SPRINKLER DESIGN, INSPECTIONS,
HYDROSTATIC TEST AND INSTALLATION SHALL BE PER NFPA 13. -
ALL PIPING TO BE BLACK STEEL, ASTM 795 OR ASTM 53 APPROVED
UNLESS NOTED OTHERWISE. -ALL PIPE LENGTHS SHOWN ARE CUT
DIMENSIONS UNLESS NOTED OTHERWISE. -HANGERS AND THE
SIZE OF THE FASTENERS TO BE PER NFPA 13. -SEE HANGER
SCHEDULEAND DETAILS FOR TYPE OF HANGERS USED. -ONLY
MATERIALS NEW, LISTED, AND/OR APPROVED SHALL BE USED. -ALL
WELDING TO BE DONE IN SHOP BY QUALIFIED WELDERS.
Applicant:
EPIC FIRE PROTECTION, INC.
765 TURTLE POINT WY
SAN MARCOS, CA
760-310-6122
Owner:
FAITH COMMUNITY CHURCH BY-THE-SEA
P 0 BOX 231460
ENCINITAS CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
1,445. 0 1,445 0
Parsley Consulting
Plan Review Comments for Faith Community Church page 2 of 2
Field verify that all "risers" between levels have flexible couplings at the top and bottom.
2) Field verify that a pressure relief valve as required by section 7.1.2 is provided.
In the event that the t-bar ceilings are not rigidly braced per ASME E580, the sprinklers to be
installed in the suspended panels will require either a 2" clearance around the penetration
through the panel, or the use of a flexible drop fitting, per ASCE7-10, section 13.5.6.2.1
through 15.6.3, which is attached. However, gypsum board ceilings are assumed to be rigidly
braced. All the above conditions can be field verified.
File: I:\Plan Reviews\Rev2 14296.1 .Docx
CHAPTER 13 SEISMIC DESIGN REQUIREMENTS FOR NONSTRUCTURAL COMPONENTS
13.5 ARCHITECTURAL COMPONENTS
13.5.1 General
Architectural components, and their supports and
attachments, shall satisfy the requirements of this
section. Appropriate coefficients shall be selected
from Table 13.5-1.
EXCEPTION: Components supported by chains
or otherwise suspended from the structure are not
required to satisfy the seismic force and relative
displacement requirements provided they meet all of
the following criteria:
The design load for such items shall be equal to
1.4 times the operating weight acting down with a
simultaneous horizontal load equal to 1.4 times the
operating weight. The horizontal load shall be
applied in the direction that results in the most
critical loading for design.
Seismic interaction effects shall he considered in
accordance with Section 13.2.3.
The connection to the structure shall allow a 3600
range of motion in the horizontal plane.
13.5.2 Forces and Displacements
All architectural components, and their supports
and attachments, shall be designed for the seismic
forces defined in Section 13.3.1.
Architectural components that could pose a
life-safety hazard shall be designed to accommodate
the seismic relative displacement requirements of
Section 13.3.2. Architectural components shall be
designed considering vertical deflection due to joint
rotation of cantilever structural members.
13.5.3 Exterior Nonstructural Wall Elements
and Connections
Exterior nonstructural wall panels or elements
that are attached to or enclose the structure shall be
designed to accommodate the seismic relative dis-
placements defined in Section 13.3.2 and movements
due to temperature changes. Such elements shall be
supported by means of positive and direct structural
supports or by mechanical connections and fasteners
in accordance with the following requirements:
Connections and panel joints shall allow for the
story drift caused by relative seismic displacements
(Dr) determined in Section 13.3.2, or 0.5 in. (13
mm), whichever is greatest.
Connections to permit movement in the plane of
the panel for story drift shall be sliding connections
using slotted or oversize holes, connections that
permit movement by bending of steel, or other
connections that provide equivalent sliding or
ductile capacity.
The connecting member itself shall have sufficient
ductility and rotation capacity to preclude fracture
of the concrete or brittle failures at or near welds.
All fasteners in the connecting system such as
bolts, inserts, welds, and dowels and the body of
the connectors shall be designed for the force (F)
determined by Section 13.3.1 with values of R,, and
a1, taken from Table 13.5-1 applied at the center of
mass of the panel.
Where anchorage is achieved using flat straps
embedded in concrete or masonry, such straps shall
be attached to or hooked around reinforcing steel
or otherwise terminated so as to effectively transfer
forces to the reinforcing steel or to assure that
pullout of anchorage is not the initial failure
mechanism.
13.5.4 Glass
Glass in glazed curtain walls and storefronts
shall be designed and installed in accordance with
Section 13.5.9.
13.5.5 Out-of-Plane Bending
Transverse or out-of-plane bending or deforma-
tion of a component or system that is subjected to
forces as determined in Section 13.5.2 shall not exceed
the deflection capability of the component or system.
13.5.6 Suspended Ceilings
Suspended ceilings shall be in accordance with
this section.
EXCEPTIONS:
Suspended ceilings with areas less than or equal to
144 ft2 (13.4 m2) that are surrounded by walls or
soffits that are laterally braced to the structure
above are exempt from the requirements of this
section.
Suspended ceilings constructed of screw- or
nail-attached gypsum board on one level that are
surrounded by and connected to walls or soffits
that are laterally braced to the structure above are
exempt from the requirements of this section.
13.5.6.1 Seismic Forces
The weight of the ceiling, W, shall include the
ceiling grid; ceiling tiles or panels; light fixtures if
attached to, clipped to, or laterally supported by the
ceiling grid; and other components that are laterally
supported by the ceiling. W shall be taken as not less
than 4 psf (192 N/rn2).
RM
1.0 2.5
1.0 2.5
1.01, 2.5
1.0 2.5
1.0 2.5
1.25 1.0
1.0 2.5
1.0 1.5
2.5 3.5
1.0 2.5
1.0 2.5
1.0 2.5
1.0 2.5
1.0 2.5
1.0 1.5
2.5 2.5
2.5 3.0
1.0 3.5
1.0 2.5
1.0 1.5
5 3.5
2.5
2.5 1.5
1.0 2.5
MINIMUM DESIGN LOADS
Table 13.5-1 Coefficients for Architectural Components
Architectural Component R,,
Interior non tural walls and partitionsb
Plain (unreiied) masonry walls
All other wallspartitions
Cantilever elements braced or braced to structural frame below its center of mass)
Parapets and cantilenterioi nonstructural walls
Chimneys where latera raced or supported by the structural frame
Cantilever elements (Bracedructural frame above its center of mass)
Parapets
Chimneys
Exterior nonstructural walls"
Exterior nonstructural wall elements an nnections"
Wall element
Body of wall panel connections
Fasteners of the connecting system
Veneer
Limited deformability elements and attachments
Low deformability elements and attachments
Penthouses (except where framed by an extension of the b •ng frame)
Ceilings
All
Cabinets
Permanent floor-supported storage cabinets over 6 ft (1,829 mm) talY luding contents
Permanent floor-supported library shelving, book stacks, and bookshel over 6 ft (1,829 mm) tall,
including contents
Laboratory equipment
Access floors
Special access floors (designed in accordance with Section 13.5.7.2)
All other
Appendages and ornamentations
Signs and billboards
Other rigid components
High deformability elements and attachments
Limited deformability elements and attachments
Low deformability materials and attachments
Other flexible components
High deformability elements and attachments
Limited deformability elements and attachments
Low deformability materials and attachments
Egress stairways not part of the building structure
1.0 1.5
1.0 2.5
2.5 2.5
2.5 2.5
A lower value for a,, shall not be used unless justified by detailed dynamic analysis. The value for a,, shall not be less than 1.00. The value
a,, = I is for rigid components and rigidly attached components. The value of a = 2.5 is for flexible components and flexibly attached corn]
'Where flexible diaphragms provide lateral support for concrete or masonry walls and partitions, the design forces for anchorage to the
diaphragm shall be as specified in Section 12.11.2.
The seismic force, F, shall be transmitted 13.5.0.2 i,uIusiry Standard co,forAcjj
through the ceiling attachments to the building cal Tile or La -in Panel ( ,l,n,L's
structural elements or the ceiling-structure k igncd in .tI1L with Sectto
boundary. I - or rial1y ia1jtiI in accordanceytj
117
CHAPTER 13 SEISMIC DESIGN REQUIREMENTS FOR NONSTRUCTURAL COMPONENTS
Section 13.2.5 or 13.2.6, acoustical tile or lay-in panel
ceilings shall be designed and constructed in accor-
dance with this section.
(13 56
lay n p -ianel ce iing .in structures assigned,:
Simic Dig'ii Cgory C shall be,designed'i
Rnstalled in accordance with ASTM C635, ASTM
'C636,.and ASTM E5 0. Section 4—Sei7sqTvCDe~i7gn,
ategory,,çTl
Dcag9Tg7j
tAcoustica tile or, lay in panel ceilings in Seism'2
DesignCategoriesD ,E,andFsha1iedesigncand
installed in accordance with ASTMC635, ASTM)
C636and'KSTM E580ti5—Seismic Desij
CategoriesD E and Fas modified by,this sectiofl)
Acoustical tile or lay-in panel ceilings shall also
comply with the following:
The width of the perimeter supporting closure
angle or channel shall be not less than 2.0 in. (50
mm). Where perimeter supporting clips are used,
they shall be qualified in accordance with approved
test criteria. In each orthogonal horizontal direc-
tion, one end of the ceiling grid shall be attached
to the closure angle or channel. The other end in
each horizontal direction shall have a 0.75 in. (19
mm) clearance from the wall and shall rest upon
and be free to slide on a closure angle or channel.
For ceiling areas exceeding 2,500 ft2 (232 m2), a
seismic separation joint or full height partition that
breaks the ceiling up into areas not exceeding
2,500 ft2 (232 rn2), each with a ratio of the long to
short dimension less than or equal to 4, shall be
provided unless structural analyses are performed
of the ceiling bracing system for theprescribed
seismic forces
- and closure angles or channels tprovidesufficien)
learance accommodate the anticipated lateral!
ement. Each area shall be provided with
closure angles or channels in accordance with
Section 13.5.6.2.2.a and horizontal restraints or
bracing.
13.5.6.3_ Integral _Construction
an alternate to providir
nkier system and ceiling, grid ,are
med and tied together as an intet
lity of
involved, including the ceili
ght fixtures, and mechanical
118
P Such PefiedbY
7rq
13.5.7 Access Floors
13.5.7.1 General
The weight of the access floor, W,,, shall include
the weight of the floor system, 100 percent of the
weight of all equipment fastened to the floor, and 25
percent of the weight of all equipment supported by
but not fastened to the floor. The seismic force, F,
shall be transmitted from the top surface of the access
floor to the supporting structure.
Overturning effects of equipment fastened to the
access floor panels also shall be considered. The
ability of "slip on" heads for pedestals shall be
evaluated for suitability to transfer overturning effects
of equipment.
Where checking individual pedestals for overturn-
ing effects, the maximum concurrent axial load shall
not exceed the portion of W',, assigned to the pedestal
under consideration.
13.5.7.2 Special Access Floors
Access floors shall be considered to be "special
access floors" if they are designed to comply with the
following considerations:
Connections transmitting seismic loads consist of
mechanical fasteners, anchors satisfying the
requirements of Appendix D of ACi 318, welding,
or bearing. Design load capacities comply with
recognized design codes and/or certified test
results.
Seismic loads are not transmitted by friction,
power actuated fasteners, adhesives, or by friction
produced solely by the effects of gravity.
The design analysis of the bracing system includes
the destabilizing effects of individual members
buckling in compression.
Bracing and pedestals are of structural or mechani-
cal shapes produced to ASTM specifications that
specify minimum mechanical properties. Electrical
tubing shall not be used.
Floor stringers that are designed to carry axial
seismic loads and that are mechanically fastened to
the supporting pedestals are used.
13.5.8 Partitions
13.5.8.1 General
Partitions that are tied to the ceiling and all
partitions greater than 6 ft (1.8 m) in height shall be
Dewatering Water Mains
Note: Includes flow testing and flushing
DewateringWater. Mains
Estimated Discharge Flow: GPM
Start Time 1040.
Carlsbad Municipal Water District
Potable Water Discharge Event Report
Date: L II
Location: -
Reason for Discharge Event: ----------------LEiu)
Type of Event Initial
Unscheduled Water Discharge N(fr
Clear flow path of debris, surface
contaminants and/or hazardous
materials. Do not remove native
vegetation.
Erosion control, i.e.
sandbags, silt fencing, hay bales,
gravel bags, decreasing the
velocity of discharged water.
End Time .k'-'
Pie-Dechlorination Residual: ....9
Post-Dechlorination Residual: J200
(Less than 0.1 mg/L)
PH within limits of 6.0 and 9.0 4'
Upon completion of dewatering,
ensure that the flow path is free
of all temporary erosion
prevention materials. ..._/A
Upon completion of dewatering,
ensure that any sediments or
silted areas are cleared. '('ES
Water Sampling Performed by: -------------------------------------
comments:
Submitted by: Reviewed by:
(Name & Date) (Name & Date)
[1'Iow Test Record
Location e*-Tcu=~
FlydrantID'No.—t Main_
Static
Residual .........140
Pressure Drop...J4..(PDJI).....Kfactor for PDfl 4j
Flow Hydrant(s)
Hydrant I location rz g*_ 4 -
Hydrant 2 location
Hydrant 3 location
Hydrant I Pitot PSI GPM: 1O Size of Orifice_ eZAZ _________ Hydrant 2 Pitot PSI GPM: Size of Orifice__________
Hydrant 3 Pitot PSI GPM: Size of Orifice.___________
T L J+ L II..
frl7\
Calculated test and flow data - 0 x PD2 k =Q2
PDI*k
Static: .................... 194-
Desired Residual.......20
Pressure Drop (PD 2)..t'4- K factor PD 2:l4.2_.
____ x 4.2. i' divided by 4. tG equals 5) 4( GPM at 20 psi residual
Qi PD2k PD1k Q2
Comments:
Test conducted for:
Conducted by: Ft RE-
Date.- Time:LO'43O1
Flow Test Record Formulas
GPM-Flow
2'/" 4"
PSI GPM PSI GPM PSI G}M PSI' GPM '-
1 170 16 670 .1 430 16 1720
2 240 17 690 2 610 17 1770
3 290 18 710 3 740 18 1820
4 340 19 730 4 860 19 1870'
5 380 20 750 5 960 20 1920
6 410 22 790 . 6 1050 22 2020
7 440 24 820 7 1140 24 2110
8 480 26 860 8 1220 26 2190
9 500 28 890 9 1290 28 2280
10 530 30 920 . ..' 10 . 11360 '30 . 2,330
11 560 33 950 11 1430 32 2430
12 580 34 980 12 1490 34 2510
13 610 36 1010 13 1550 36 2580
14 630: 38 1040 14 1610 38 250
15 650 40 1060 15 1660 40 2720
K Factor Formula
PD K PD K PD K PD K PD K
1= 1.0 21= 5.18 41= 7.43 61= 9.21 81= 10.73
2= 1.45 22= 5.31 42= 7.53 62= 9.29 82= 10.80
3= 1.81 23= 5.44 43= 7.62 63= 9.37 83= 10.87
4= 2.11 24= 5.56 44= 7.72 64= 9.45 84=. 10.94
5= 2.39 25= 5.69 45= 7.81 65= 9.53 85= 11.01
6= 2.63 26= 5.81 46= 7.91 66= 9.61 86= 1108
7= 2.86 27= 5.93 47=. 8.00 67= 9.69 87= 11.15
8= 3.07 28= 6.05 48= 8.09 68= 916 88= 1122 '
9= 3.28 29= 6.16 49= 8.18 69= 9.84 89= 11.29
10= 3.47 30= 6.28 50= 8.27 70= 9.92 90= 11.36
11= 3.65 31= 6.39 51= 8.36 71= 9.99 91= 11.43
12= 3.83 32= 6.50 52= 8.44 72= 10.07 92= 11.49
13= 4.00 33= 6.61 53= 8.53 73= 10.14 93= 11.56
14= 4.16 34= 6.71 54= 8.64 74= 10.22 94= 11.63
15= 4.32 35= 6.82 55= 8.71 75=, 10.29 95= 11.69
16= 4.48 36= 6.93 56= 8.7 76= 10.37. 96= '1176
17= 4.72 37= 7.03 57= 8.88 77= 10.44 97= 11.83
18= 4.76 38= 7.13 58= 8.96 78= 10.51 98= 11.89
9= 4.90 39= 7.23 59=. 9.04 79= io:sg 99= 11.96
20= 5.04 40= 7.33 60= 9.12 80= 10.66 100= 12.02
*PD = Pressure drop K = K factor . •. .