HomeMy WebLinkAbout2210 FARADAY AVE; 150; FPC2020-0199; PermitPERMIT REPORT (r(ity of Carlsbad Print Date: 05/21/2021 Job Address: 2210 FARADAY AVE, # 150, CARLSBAD, CA 92008-7226 Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers Parcel #: 2121205500 Track #: Valuation: $220,317.87 Lot #: Occupancy Group: Project #: #of Dwelling Units: Plan #: Bedrooms: Construction Type: Bathrooms: Orig. Plan Check #: Plan Check U: Project Title: Description: NEMKO USA -SPRINKLER TI (39 HEADS) Permit No: FPC2020-0199 Status: Closed - Finaled Applied: 11/17/2020 Issued: 12/03/2020 Finaled Close Out: 05/21/2021 Inspector: Final Inspection: Applicant: FPContractor: COSCO FIRE PROTECTION COSCO FIRE PROTECTION INC MICHAEL LOVELY 1075 W LAMBERT RD 4990 GREENCRAIG LN BREA, CA 92821-2944 SAN DIEGO, CA 92123-1673 (858) 444-2000 (858) 444-2000 x1727 FEE AMOUNT FIRE NFPA 13 or 13R System 7 - 100 heads $553.00 Total Fees: $553.00 Total Payments To Date: $553.00 - - Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov . I .000000. 'I .. I •.. cosco 00 . SI •.' Fire Protection San Diego Branch Office 4990 Greencraig Lane San Diego, CA 92123 (858) 444-2000 fax: 444-2056 CA Lie.: C-16 #577621 www.coscofire.com MATERIAL SUBMITTAL Date: 11-16-20 NEMKO USA T.I. 22 10 FARADAY AVE. CARLSBAD, CA. 92064 JOB # 10.CD_5999 All material submitted, may be substituted by material of equal performance & design, & shall be deemed acceptable by purchaser. Submitted by: HUGO A. Los Angeles 0 San Francisco 0 Orange 0 Fresno 0 San Diego • Seattle FM Approved and Fully Listed Sprinkler Pipe Wheatland's Schedule 10 and Schedule 40 steel fire sprinkler pipe is FM Approved and UL, C-UL and FM Listed. Approvals and Specifications Both products meet or exceed the following standards: ASTM A135, Type E, Grade A (Schedule 10) ASTM A795, Type E, Grade A (Schedule 40) NFPA13 Manufacturing Protocols. Schedule 10 and Schedule 40 are subjected to the toughest possible testing protocols to ensure the highest quality and long-lasting performance. Finishes and Coatings All Wheatland black steel fire sprinkler pipe up to 6" receives a proprietary mill coating to ensure a clean, corrosion-resistant surface that outperforms and outlasts standard lacquer coatings. This coating allows the pipe to be easily painted, without special preparation. Schedule 10 and Schedule 40 can be ordered in black, or with hot-dip galvanizing, to meet FM/UL requirements for dry systems that meet the zinc coating specifications of ASTM A795 or A53. All Wheatland galvanized material is also UL Listed. __ Product Marking Each length of Wheatland fire sprinkler pipe is continuously stenciled to show the manufacturer, type of pipe, grade, size and length. Barcodirig is acceptable as a supplementary identification method. SCHEDULE 10 SPECIFICATIONS NOMINAL NOMINAL NPS NOM OD NOM ID WALL WEIGHT UL PIECES [ Lift J in. in. ][mm]=1- [bs./ft.jI k9/mJ[1 1% 1.660 42.2 . 1.442 36.6 .109 2.77 1.81 2.69 7.3 61 J[1.9o0 ] 1.682 42.7 2.09 3.11 5.8 61 2 2.375 60.3 2.157 54.8 .109 2.77 2.64 3.93 4.7 37 2.635 66.9 20 [3.05 j 1 3.53 5.26 IL_ 30 3 3.500 88.9 3.260 82.8 .120 3.05 4.34 6.46 2.6 19 -ir--- r--- i 4.500 4.260 108.2 r- 'r ---i ,i[ 3.05 5.62 8.37 r 19 5 5.563 141.3 5.295 134.5 .134 3.40 7.78 11.58 1.5 13 6[625_j3 6.357 161.5 .[T 9.30 13.85 l[_o 10 8 8.625 219.1 8.249 209.5 .188 4.78 16.96 25.26 2.1 7 Calculated using Standard UL CPR formula, UL Fire Protection Directory, Category VIZY. The CRR Is a ratio value used to measure the ability of a pipe to withstand corrosion. Threaded Schedule 40 steel pipe is used as the benchmark (value of 1.0). SCHEDULE 40 SPECIFICATIONS NOMINAL NOMINAL NPS NOM OD NOM ID WALL WEIGHT UL PIECES [7nT]jjrin. ] mm II In. 1LIIbs./ft.Jt rnjCRR'[ EE] 1 1.315 33.4 1.049 ' 26.6 .133 3.38 1.68 2.50 1.00 70 1.380 35.1 .140 if 3.56 ____ 2.27 3.39 ____ 51 11/2 1.900 48.3 1.610 40.9 .145 3.68 2.72 4.05 1.00 44 fl[2fl[1J_2.067JtjI.154 [ 3.91 jJLJo][ I Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY. The CRR is a ratio value used to measure the ability of a pipe to withstand corrosion. Threaded Schedule 40 steel pipe Is used as the benchmark (value of 1.0). @ C@ APPROVED PROJECT: CONTRACTOR: DATE: ENGINEER: SPECIFICATION REFERENCE: SYSTEM TYPE: LOCATIONS: COMMENTS: BLACK n HOT-DIP GALVANIZED Wheatland Tube 700 South Dock Street Sharon, PA 16146 P 800.257.8182 1 F 724.346.7260 1 info@wheatland.com I wheatland.com FireLock® V27, K5.6 Models V2703, V27079 V2704, V2708 Standard Spray Upright, Pendent and Recessed Pendent Standard and Quick Response n•'1 . V2703/V2704 V2707/V2708 V2707/V2708 Upright Pendent Recessed Pendent Approvals/Listings: c®@® 7i See Victaulic Publication 10.01 for more details. Product Description: \q4taulicr 40.10 Technical Specifications: Models: V2703, V2704, V2707, V2708 Style: Pendent, Upright or Recessed Pendent Nominal Orifice Size: 1/2713 mm K Factor: 5.6 Imp./8.1 S.1.1 Nominal Thread Size: ½ NPT/15 mm Max. Working Pressure: 175 psi/1200 kPa (FM) 250 psi/1725 kPa (UL) Factory Hydrostatic Test: 100% @ 500 psi/3450 kPa Mm. Operating Pressure: 7 psi/48 kPa 0.35 bar/5 psi (VdS for upright only) Temperature Rating: See chart For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.0. These Model V27 standard spray sprinklers are designed to produce a hemispherical spray pattern for standard commercial applications. They are available with either standard or quick response bulbs. It is cast with a hex-shaped wrench boss to allow easy tightening from many angles, reducing assembly effort. This sprinkler is available in various temperature ratings (see chart on page 3) and finishes to meet many design requirements. The recessed pendent should be utilized with a Model V27 recessed escutcheon which provides Up to /4/19 mm of adjustments. Coverage For coverage area and sprinkler placement, refer to NFPA 13 or applicable standard. èi Exaggerated for clarity Job/Owner Engineer System No. Spec Section Location Paragraph Contractor Approved Submitted By Date Date victaulic.com I Sprinklers I FireLock® I K5.6, V27 I Publication 40.10 40.10 2544 Rev. J Updated 07/2014 © 2014 Victaulic company. All rights reserved. 1 ,Ltauiicr victaulic.com I Sprinklers I FireLock® I K5.6, V27 I Publication 40.10 Material Specifications: Upright Deflector: Bronze per UNS C11000 Pendent Deflector: Bronze per UNS C51000 Bulb: Glass with glycerin solution Bulb Nominal Diameter: Li Standard: 5.0 mm Li Quick Response: 3.0 mm Load Screw: Bronze per UNS C65100 Pip Cap: Bronze per UNS C65100 Spring: Beryllium nickel Seal: Teflon2 tape Frame: Die cast brass 65-30 Lodgement Spring: Stainless steel per UNS S30200 Accessories Installation Wrench: LII Open End: V27 Li Recessed: V27-2 Sprinkler Finishes: Li Plain Brass Li Chrome plated Li White painted3 Li Black painted3 Li Custom painted3 Li Proprietary Nickel Teflon2 coating3 Li VC-2504 155, 200, 286 SR Only: Li Wax3 For cabinets and other accessories refer to separate sheet. 2 Teflon is a registered trademark of Dupont Co. UL Listed for corrosion resistance. UL Listed and FM Approved for corrosion resistance. 40.10 2544 Rev. J Updated 07/2014 © 2014 Victaulic Company. All rights reserved. victaulic.com 2 _1::tauuiC• victaulic.com I Sprinklers I FireLock® I K5.6, V27 I Publication 40.10 Approvals/Listings: Model APPROVALS/LISTINGS V2703 V2707 V2707 V2704 V2708 V2708 Orifice Size (inches) 1/2" 1/2" 1/2" 1/2" 1/2" Orifice Size (mm) 13 13 13 13 13 13 Nominal K Factor Imperial 5.6 5.6 5.6 5.6 5.6 5.6 Nominal K Factor S.1.1 8.1 1 8.1 1 8.1 8.1 8.1 8.1 Response Standard Standard Standard Quick Quick Quick Deflector Type Upright Pendent Recessed Upright Pendent Recessed Pendent Pendent Approved Temperature Ratings F°/C° 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C cULus 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 155°F/68°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 175°F/79°C 286°F/141°C 286°F/141°C 286°F/141°C 286°F/1 41°C 286°F/141°C 200°F/93°C 360°F/182°C 360°F/1 82°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 135°F/57°C 155°F/68°C 155°F/68°C FM 175°F/79°C 175°F/79°C 155°F/68°C 175°F/79°C 175°F/79°C 155°F/68°C 200°F/93°C 200°F/93°C 175°F/79°C 200°F/93°C 200°F/93°C 175°F/79°C 286°F/141°C 286°F/141°C 200°F/93°C 286°F/141°C 286°F/141°C 200°F/93°C 360°F/1 82°C 360°F/1 82°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C NYC/MEA 62-99-E 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 155°F/68°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 175°F/79°C 286°F/141 °C 286°F/1411C 286°F/141°C 286°F/141°C 286°F/141 °C 200°F/93°C 360°F/182°C 360°F/182°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 155°F/68°C 135°F/57°C CSFM 7690-0531:112 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 175°F/79°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 175°F/79°C 286°F/141°C 286°F/141°C 286°F/141 °C 286°F/141°C 286°F/141°C 200°F/93°C 360°F/1 82°C 360°F/182°C 135°F/57°C 155°F/68°C 135°F/57°C LPCB 175°F/79°C None None 155°F/68°C None None 200°F/93°C 175°F/79°C 286°F/141°C 200°F/93°C 360°F/182°C 135°F/57°C 135°F/57°C 135°F/57°C 135°F/57°C 155°F/68°C 155°F/68°C 135°F/57°C 155°F/68°C 155°F/68°C VNIIPO 175°F/79°C 175°F/79°C 155°F/68°C 175°F/79°C 175°F/79°C 200°F/93°C 200°F/93°C 175°F/79°C 200°F/93°C 200°F/93°C 286°F/141°C 286°F/141°C 200°F/93°C 286°F/141°C 286°F/141°C 360°F/1 82°C 360°F/1 82°C ZSTZ ZSTX K-ZSTZ K-ZSTZ CCC 155°F/68°C 155°F/68°C None 155°F/68°C 155°F/68°C None 200°F/93°C 200°F/93°C 200°F/93°C 200°F/93°C 135°F/57°C 155°F/68°C VdS 175°F/79°C None None 175°F/79°C None None 200°F/93°C 286°F/141°C 360'F/1 82'C i35°F/57°C 155°F/68°C CE 175°F/79°C None None 175°F/79°C None None 200°F/93°C 200°F/93°C 286°F/141°C 360°F/i 82°C For K Factor when pressure is measured in Bar, multiply S.I. units by 10.0 FM Approved with 1/2" adjustment escutcheon only - quick response Note: Listings and Approvals as of printing. All are approved open. 40.10 2544 Rev. J Updated 07/2014 © 2014 Victaulic Company. All rights reserved. victaulic.com 3 -1 4 ll, Ai -C —ts I —U1 i e 17A6/ 37 mm 2 60 1W! 2W! 41 mm 60 mm I victaulic.com I Sprinklers I FireLock® I K5.6, V27 I Publication 40.10 Dimensions: Standard Pendent - Standard Upright - V2707, V2708 V2703, V2704 2W/60 mm Max. Hole I 2/51 mm Min. Hole I ____ WI Typical Ceiling Tile zz 17mm 30jm f t P146/ 43 mm Finished Surface 30 T MAXIMUM RECESS 215Ao/ 75 mm MAXIMUM EXTENSION ½ Adjustment Recessed - V2707, V2708 (drawing not to scale) 2W160 mm Max. Hole 2'Isl mm Mm. Hole 1V/ Al3 T _________37mm Typical Ceiling Til18mm 24 mm Finished Surface __________________ 1W/ 24 mm MAXIMUM RECESS 2X67 75 mm MAXIMUM EXTENSION W Adjustment Recessed - V2707, V2708 (drawing not to scale) 40.10 2544 Rev. J Updatd 07/2014 © 2014 Victaulic Company. All rights reserved. victaulic.com 4 taUIiC victaulic.com I Sprinklers 1 FireLock® I K5.6, V27 I Publication 40.10 Disfribution Patterns: Models V2707, V2708 K5.6 Standard Pendent and Recessed Pendent Distribution Patterns - Trajectory 10, 3am 8. 2Am 6 1.8m 4, 1.2m 2' 0.6n1 iuiiuiamm iiiiii•i• u-.-.iiiu ia•uiumuuuu UIURikUUI* iiauiuuuia IUUIIIUIRUIU uRIIIIII-I iauiiaua.• IMMMMMMMMMM 2' 4' 5' 8' 10' 12' 14' 0.6n 1.2m ion, 2.4n, 3.0m 3m, 4.3m Models V2703, V2704 K5.E. Standard Upright Distribution Patterns - Trajectory 7 psi 48 kPa 15 psi 103 kPa 30 psi 207 kPa 7psi 48 kPa 15 psi 103 kPa 30p51 207 kPa mmmmmmmmii iuuimu•u•ua iiiiiui•u•iu uiuuuuuii uauuu•aiiuuu mmmmmmmm MM ivaiu••uutiuu MMMMMMMMME 2' 4' 6' 8' 10' 12' 14' 16' 0.6m un, Lon, 2.4m 3.on, 3.7m 4.3n, 4gm NOTES: Data shown is approximate and can vary due to differences in installation. These graphs illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are provided as information for guidance in avoiding obstuctions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to the appropriate NFPA National Fire Code or the Authority Having Jurisdiction for specific information regarding obstructions, spacing limitations and area of coverage requirements. Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and Warranties. All patterns are symmetrical to the centerline of the waterway. 40.10 2544 Rev. J Updated 07/2014 © 2014 Victaulic Company. All rights reserved. victaulic.com .5 . \Atculicrta ICY 3.Om 8' 2.4nn 6' 1.8m 4, 1.2m 2- 0.6m 0 victaulic.com I Sprinklers I FireLock® I K5.6, V27 I Publication 40.10 Ratings: Available Wrenches: All glass bulbs are rated for temperatures from -67°F (-55°C) to those shown in the table below. Sprinkler Temperature Classification Victaulic Part Identification Temperature - °F/°C Glass Bulb Color Nominal Temperature Rating Maximum Ambient Temperature Allowed Ordinary A 1350F/570C 100°F/38°C Orange Ordinary C 155017/680C 100°F/380C Red Intermediate E 1750F/790C 150°F/650C Yellow Intermediate F 200°F/930C 150°F/650C Green High J 2860F/1410C 225°F 8/1070C Blue Extra High 7 K 360°F/1820C 300°F/1490C Purple - M Open - No Bulb Standard response only. 8 150/65 if wax coated. V27-2 Recessed V27 Open End V2707,V27O8Pendent / / V2707, V2708 Recessed Pendent / - V2703, V2704 Upright WARNING Always read and understand installation, care, and maintenance instructions, supplied with each box of sprin- klers, before proceeding with installation of any sprinklers. Always wear safety glasses and foot protection. Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products. Installation rules, especially those governing obstruction, must be strictly followed. Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed. Failure to follow these instructions could result in serious personal injury and/or property damage. The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For O minimum maintenance and inspection requirements, refer to the current National Fire Protection Association pam- phlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional maintenance, testing, and inspection requirements that must be followed. If you need additional copies of this publication, or if you have any questions about the safe installation of this product, contact Victaulic World Headquarters: P.O. Box 31, Easton, Pennsylvania 18044-0031 USA, Telephone: 001.610.559-3300. Installation Note Reference should always be made to the 1.40 Victaulic FireLock Automatic Sprinklers This product shall be manufactured by Victaulic or to Victaulic specifications. All products Installation and Maintenance Sheet for the product you are installing. This installation sheet to be installed in accordance with current Victaulic installation/assembly instructions. is included with each shipment of Victaulic products for complete installation and assembly Victaulic reserves the right to change product specifications, designs and standard data, and is available in PDF format on our website at victaulic.com. equipment without notice and without incurring obligations. Warranty Trademarks Refer to the Warranty section of the current Price List or contact Victaulic for details. Victaulic is a registered trademark of Victaulic Company. 40.10 2544 Rev. J Updated 07/2014 © 2014 Victaulic Company. All rights reserved. victaulic.com 6 Ill 4taulicr tqC170 Worldwide www.tyco-fire.com Contacts Series EC-8 - 80 K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description The Series EC-8 Extended Coverage Pendent Sprinklers are decorative glass bulb sprinklers designed for use in light hazard occupancies. They are intended for use in automatic sprinkler systems designed in accordance with standard installation rules (e.g., NFPA 13) for a maximum coverage area of 400 ft2 (37,2 rn2), as compared to the maximum coverage area of 225 ft2 (20,6 m2) for standard coverage sprin- klers used in light hazard occupancies. The recessed version of the EC-8, intended for use in areas with a fin- ished ceiling, uses either the two-piece Style 30 or 40 Recessed Escutch- eon. The Style 30 Recessed Escutch- eon provides up to 1/2 in. (12,7 mm) of total adjustment from the flush pendent position, whereas, the Style 40 provides 3/4 in. (19,1 mm) of verti- cal adjustment from the flush pendent position. The adjustment provided by the Recessed Escutcheons reduces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmo- spheres. Although corrosion resistant coated sprinklers have passed the standard corrosion tests of the appli- cable approval agencies, the testing is IMPORTANT Refer to Technical Data Sheet TFP2300 for warnings pertaining to regulatory and health information. Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and installation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 not representative of all possible cor- rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitabil- ity of these corrosion resistant coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/ chemical velocity, should be consid- ered, as a minimum, along with the cor- rosive nature of the chemical to which the sprinklers will be exposed. IAL•)IIII The Series EC-8 Extended Coverage Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main- taining their fire protection system and devices in proper operating con- dition. Contact the installing contrac- tor or product manufacturer with any questions. Sprinkler Identification Number (SIN) TY4232............Pendent, 8.0K TY4232 is a re-designation for C4232 Technical Data Approvals UL and C-UL Listed. FM Approved NYC Approved. (Refer to Table A for complete approval information including corrosion resistant status. The Approvals apply to the service conditions indicated in the Design Criteria section.) Maximum Working Pressure 175 psi (12,1 bar) SEPTEMBER 2018 Pipe Thread Connection 3/4 in. NPT Discharge Coefficients K=8.0 gpm/psi½ (115,2 1pm/bar") Temperature Ratings 135°F (57°C) 155°F (68°C) Refer to Table A for approvals Finish Sprinkler: Refer to Table A Recessed Escutcheon: Natural Brass, Signal White, Chrome Plated Physical Characteristics Frame ............................Bronze Button ............................Bronze Sealing Assembly. . Beryllium Nickel w/TEFLON Bulb.....................Glass (3 mm dia.) Compression Screw .................Bronze Deflector ...........................Brass TFP223 TFP223 Page 2 of 6 Components: 3/4 ESCUTCHEON PLATE 1 - Frame NPT SEATING SURFACE Button Sealing Assembly Bulb i Compression 2 I8° Screw 3 (54,0 mm) Deflector * (12,7 mm) * Temperature rating is 4NOMINAL /16 indicated on Deflector. MAKE-IN (36,5 mm) ** Pipe thread connections per ISO 7-1 can be provided 6 * on special request. FIGURE 1 SERIES EC-8 (TY4232) EXTENDED COVERAGE PENDENT SPRINKLER SPRINKLER FINISH (See Note 4) HAZARD TYPE TEMP. BULB LIQUID NATURAL I CHROME I POLYESTER* BRASS PLATED Light Pendent 135°F (57°C) Orange 12,3,5 155°F(68°C) Red Refer to Table B for UL and C-UL Rec. Pendent 135°F (57°C) Orange 1,2,3, 5 Sensitivity Rating and w/ Style 30 Esc. 155°F (68°C) Red 1, 2, 5 Refer to Table C for FM Sensitivity Rating Rec. Pendent 135°F (57°C) Orange 1,2,5 155°F (68°C) Red w/Style 40 Esc. NOTES: Usted by Underwriters Laboratories, Inc. (UL). Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL). Approved by Factory Mutual (FM). Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers. Approved by the City of New York under MEA 113-04-E. Frame and Deflector only. TABLE A LABORATORY LISTINGS AND APPROVALS (Refer to the Design Criteria Section) Operation The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and flow water. Design Criteria The Series EC-8 Extended Cover- age Pendent Sprinklers must only be installed in accordance with the applicable UL and C-UL Listing or FM Approval requirements as indi- cated below. Only the Style 30 or 40 Recessed Escutcheon is to be used for recessed installation, as applicable (Ref. Table A, B, and C). UL and C-UL Listing Requirements The Series EC-8 Sprinklers may be used for the coverage areas shown in Table D, based on maintaining the minimum specified flow rate as a function of coverage area and hazard group for all of the sprin- klers in the design area. With respect to heat sensitivity, the Series EC-8 Sprinklers can be used with unobstructed construction consisting of flat, smooth ceilings (including bar joists) with a maxi- mum pitch of one in six as defined and permitted by NFPA 13. The minimum allowable spacing between the Series EC-8 Sprin- klers, to prevent cold soldering, is 8ft(2,4m). The Series EC-8 Sprinklers are to be installed in accordance with all other requirements of NFPA 13 for extended coverage pendent sprinklers. FM Approval Requirements The Series EC-8 Extended Coverage Sprinklers are to be installed in accor- dance with the applicable Factory Mutual Loss Prevention Data Sheet. Information provided in the FM Loss Prevention Data Sheet relate to, but are not limited to, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector-to-ceiling distance. TFP223 Page 3 of 6 Area Style 135°F (57°C) 155°F (68°C) 16x16 Pendent OR OR 16 x 16 Style 30 Recessed OR OR 16 x 16 Style 40 Recessed OR OR 18x18 Pendent OR OR 18 x 18 Style 30 Recessed OR SR 18 x 18 Style 40 Recessed OR SR 20 x 20 Pendent OR SR 20 x 20 Style 30 Recessed OR SR 20 x 20 Style 40 Recessed SR SR OR: Quick Response SR: Standard Response TABLE B SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-8 SPRINKLERS Area Style 135°F (57°C) 155°F (68°C) 16x16 Pendent OR OR 16 x 16 Style 30 Recessed OR N/A 16 x 16 Style 40 Recessed N/A N/A 18x18 Pendent OR OR 18 x 18 Style 30 Recessed OR N/A 18 x 18 Style 40 Recessed N/A N/A 20x20 Pendent OR OR 20 x 20 Style 30 Recessed OR N/A 20 x 20 Style 40 Recessed N/A N/A OR: Quick Response SR: Standard Response N/A: Not Applicable TABLE C SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-8 SPRINKLERS I Description I Area I GPM I PSI I I TY4232 (K=8.0) I 16x16 I 26 10.6 I Pendent I 33 I 17.0 I 20x20 40 j. 25.0 1 ft=0.3048m 1 ft2 = 0.093 m2 1 gpm = 3.785 1pm 1 psi = 0.06895 bar 1 gpm/ft2 = 40.74 mm/mm TABLED FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-8 SPRINKLERS Installation The Series EC-8 Sprinklers must be installed in accordance with this section. General Instructions Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin- kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 in. (1,6 mm). A leak tight 3/4 in. NPT sprinkler joint should be obtained with a torque of 10 to 20 lb-ft (13,4 to 26,8 N.m). Higher levels of torque may distort the sprin- kler inlet with consequent leakage or impairment of the sprinkler. Do not attempt to compensate for insufficient adjustment of an escutch- eon plate by under-or over-tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit. Step 1. The sprinkler must be installed with the deflector parallel to the mount- ing surface. Pendent sprinklers must be installed in the pendent position. Step 2. After installing the Style 30 or 40 mounting plate (or other escutch- eon, as applicable) over the sprinkler pipe threads, and with pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step 3. Wrench tighten pendent sprin- klers using only the W-Type 3 (End A) Sprinkler Wrench. Wrench tighten the recessed pendent sprinklers using only the W-Type 23 Sprinkler Wrench. The wrench recess of the applicable sprin- kler wrench (Ref. Figures 4 and 5) is to be applied to the sprinkler wrench flats (Ref. Figure 1). TFP223 Page 4 of 6 Care and Maintenance The Series EC-8 Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection systems must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or other- wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin- klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin- kler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installa- tion Section.) Frequent visual inspections are rec- ommended to be initially performed for corrosion resistant coated sprin- klers, after the installation has been completed, to verify the integrity of the corrosion resistant coating. Thereafter, "FITTING SIDE" TOWARDS SPRINKLER FITTING WRENCH RECESS / (END "A") FIGURE 4 W-TYPE 3 SPRINKLER WRENCH WRENCH RECESS - _ I _ - 4-1 LJ FIGURE 5 W-TYPE 23 RECESSED SPRINKLER WRENCH annual inspections per NFPA 25 should suffice; however, instead of inspecting from the floor level, a random sampling of close-up visual inspections should be made, so as to better determine the exact sprinkler condition and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the NATIONAL FIRE PROTECTION ASSOCIATION (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The installing contractor or sprinkler man- ufacturer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec- tion Service in accordance with local requirements and/or national codes. 2-7/8' DIA. - 7/16±1/8" (73,0 mm) 1/2" (12,7 mm) (11,1±3,2 mm) 2-1/4' DIA. 1/4' (6,4 mm) FACE OF (57,2 mm) - SPRINKLER FITTING(.7_ _() (3,2 mm) KIM I SURFACE / NG /MOUNTING PLATE CLOSURE 1-5/16" (33,3 mm) 1-1/16" (27,0 mm) FIGURE 2 SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 30 RECESSED ESCUTCHEON - 2-7/8" DIA. - 9/16±1/4" (73,0 mm) - 3/4" (19,1 mm) (14,3±6,4 mm) 2-1/4" DIA. _ 1/4" (6,4 mm) FACE OF (57,2 mm) _________ / SPRINKLER 1/8" FITTING L\ (3,2 mm) MIA I MOUNTING SURFACE MOUNTING PLATE PLATE CLOSURE 1-5/16" (33,3 mm) 13/16" (20,6 mm) FIGURE 3 SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON TFP223 Page 5 of 6 Limited Warranty For warranty terms and conditions, visit www.tyco-fire.com. Ordering Procedure Contact your local distributor for avail- ability. When placing an order, indicate the full product name and Part Number (P/N). Sprinkler Assemblies with NPT Thread Connections Specify: Series EC-8 (TY4232), K=8.0, Extended Coverage (Light Hazard) Pendent Sprinkler, (specify) tem- perature rating, (specify) finish, P/N (specify): 135°F (57°C) Natural Brass .............PSN 50-801-1-135 Signal White (RAL9003) Polyester ................PSN 50-801-4-135 Chrome Plated ............PSN 50-801-9-135 155°F (68°C) Natural Brass .............PSN 50-801-1-155 Signal White (RAL9003) Polyester ................PSN 50-801-4-155 Chrome Plated ............PSN 50-801-9-155 Recessed Escutcheon Specify: Style (30 or 40) Recessed Escutcheon with (specify*) finish, P/N (specify*) Refer to Technical Data Sheet TFP770 Sprinkler Wrench Specify: W-Type 3 Sprinkler Wrench, P/N 56-895-1-001 Specify: W-Type 23 Recessed Sprinkler Wrench, P/N 56-000-6-838 TFP223 Page 6 of 6 1400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700 0 02018 Johnson Controls. All rights reservod. All specifications and other Information shown were current as of document revision dale and are subject to change without notice. Johnson / (' NATIONAL FIRE PROTECTION ASSOCIATION and NFPA ore rcglclerod trademarks ci National Firs PinlccticnAonoclallcn;Controls TEFLON Inc rnçlOtorod trademark of DrIPOrrI FireLock® Outlet-I ILPCB] USM 491a/27 SEE VICTAULIC PUBLICATION 10.01 FOR DETAILS STYLE 922 The Style 922 Outlet-T provides a convenient method of incorporating ½, 3/4, and 1/15, 20 and 25 mm outlets for directly connecting sprinklers, drop nipples, sprigs, gauges, drains and other outlet products. Available for 1% through 76.1 mm/32 to 76.1 mm piping systems, Style 922 outlets are UL/ULC Listed, LPCB and FM Approved for branch connections and VdS Approved for direct sprinkler connection only on wet and dry systems. The locating collar engages into the hole prepared in the pipe. When tightened, the assembly compresses the gasket onto the OD of the pipe. The Style 922 Outlet-T is UL/FM rated up to 300 psi/2068 kPa and VdS rated up to 16 bar at the ambient temperatures typical for fire protection systems. Style 922 is suitable for use on standard, lightwall, Schedule 5 and other specialty pipes.* Contact Victaulic for other optional coatings. *Consult Section 10.01 for specific listings/approvals. MATERIAL SPECIFICATIONS Housing: Ductile iron conforming to ASTM A-536, grade 65-45-12. Ductile iron conforming to ASTM A-395, grade 65-45-15, is available upon special request. Gasket: Grade "E" EPDM - Type A (Violet color code). FireLock products have been Listed by Underwriters Laboratories Inc. and Approved by Factory Mutual Research for wet and dry (oil free air) sprinkler services up to the rated working pressure using the Grade "E" Type A Gasket System. Bolts/Nuts: Heat-treated plated carbon steel, trackhead meeting the physical and chemical requirements of ASTM A-449 and physical requirements of ASTM A-183. Housing Coating: Orange enamel (North America, Latin America, Asia Pacific) Red enamel (Europe) JOB/OWNER CONTRACTOR ENGINEER System No Submitted By Spec Sect Para Location Date Approved www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV C JtaUIiC 10.52 1 IPS CARBON STEEL PIPE - HOLE CUT PRODUCTS FireLock® Outlet-T _t=- inches/mm i18iI 9jib 1;,L] 1¼ ½ 13/16 130 1.83 1.10 3.87 2.56 1.0 32 > 15 30.2 33.0 46.5 27.9 98.3 65.0 0.45 3/4 13/16 1.28 1.83 1.10 3.87 2.56 1.1 20 30.2 32.5 46.5 27.9 98.3 65.0 0.50 1 13/16 1.52 2.18 1.10 3.87 2.56 1.2 25 30.2 38.6 55.4 27.9 98.3 65.0 0.54 1 ½ ½ 13/16 1.42 1.95 1.22 4.08 2.56 1.2 40 15 30.2 36.1 49.5 31.0 103.6 65.0 0.54 1/4 13/16 1.40 1.95 1.22 4.08 2.56 1.2 20 30.2 35.6 49.5 31.0 103.6 65.0 0.54 1 13/16 1.64 2.30 1.22 4.08 2.56 1.3 25 30.2 41.7 58.4 31.0 103.6 65.0 0.59 2 x ½ 13/16 1.66 2.19 1.46 4.60 2.56 1.3 50 15 30.2 42.2 55.6 37.1 116.8 65.0 0.59 3/4 13/16 1.64 2.19 1.46 4.60 2.56 1.4 20 30.2 41.7 55.6 37.1 116.8 65.0 0.64 1 13/16 1.88 2.54 1.46 4.60 2.56 1.5 25 30.2 47.8 64.5 37.1 116.8 65.0 0.68 21/2 1/2 13/16 1.91 2.44 1.71 5.40 2.56 1.6 65 15 30.2 48.5 - 62.0 43.4 137.2 65.0 0.73 3/4 13/16 1.89 2.44 1.71 5.40 2.56 1.6 20 30.2 48.0 62.0 43.4 137.2 65.0 0.73 1 13/16 2.13 2.79 1.71 5.40 2.56 1.6 25 30.2 54.1 70.9 - 43.4 137.2 65.0 -0.73 76.1 mm X ½13/16 1.91 2.44 1.71 5.50 2.56 1.6 15 30.2 - 48.5 62.0 43.4 139.7 1 65.0 0.73 -Y4 13/16 1.89 2.44 1.71 5.50 2.56 1.6 20 30.2 48.0 62.0 43.4 139.7 65.0 0.73 1 13/16 2.13 2.79 1.71 5.50 2.56 1.7 25 30.2 54.1 70.9 43.4 139.7 65.0 0.80 STYLE 922 DIMENSIONS Ii. .uJ II 1• f Victaulic female threaded products are designed to accommodate standard NPT or BSPT (optional) male pipe threads only. Use of male threaded products with special features, such as probes, dry pen- dent sprinklers, etc., should be verified as suitable for use with this Victaulic product. Failure to verify suitability in advance may result in assembly problems or leakage. Center of run to engaged pipe end for NPT threads (dimensions are approximate). www.victaulic.com VICTAULIC IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. 10.52 2 . \4taulico REV G IPS CARBON STEEL PIPE- HOLE CUT PRODUCTS PERFORMANCE Run Size Inches/mm x Outlet Size Equivalent Length of 1 inch Schedule 40 Steel Pipe (per UL 213, Section 16) (C=120), FT FeeUmeters 32 25 40 25 2.6 I. L 216 . 65 25 76.1 Min x - Hazen-Williams coefficient of friction is 120 FireLock® Outlet-I STYLE 922 www.victaulic.com VICTAULIC IS REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. REV ( /taUIiC 1fl2 FireLock® Outlet-I STYLE 922 INSTALLATION Reference should always be made to the 1-100 Victaulic Field Installation Handbook for the product you are installing. Handbooks are included with each shipment of Victaulic products for complete installation and assembly data, and are available in PDF format on our website at www.victaulic.com. WARRANTY Refer to the Warranty section of the current Price List or contact Victaulic for details. NOTE This product shall be manufactured by Victaulic or to Victaulic specifications. All products to be installed in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations. For complete contact information, visit www.victaulic.com 10.52 3355 REV G UPDATED 12/2009 iCtaUlic viciuuc IS A REGISTERED TRADEMARK OF VICTAULIC COMPANY. © 2009 VICTAULIC COMPANY. ALL RIGHTS RESERVED. 10.52 STED APPROVED 'Approval Details and Limitations, cebsite at www.anvilintj.com or AnviP Sales Representative. 4E~~~ DUCTILE IRON THREADED FITTINGS ANVIL FIG. 3201 9O Elbow A FIGURE 3' 900 ELBOW Nominal Size MaximumDimension A Approx. Wt. Each Working PressureA In. (mm) PSI (kPa) In. (mm) his. (kg) - 1 500 1.50 0.62 20 3450 38.10 0.28 -. 1½ 500 1.75 0.90 32 3450 44.45 0.41 1½ 500 1.94 1.20 40 3450 49.216 0.54 2 500 2.25 1.85 50 3450 51.15 0.84 A - Working Pressure Ratings are for reference only and based on 5ch. 40 pipe. For the latest UL/ULC, and FM pressure ratings versus pipe schedule, please visit anvilinll.com or contact your local Anvil Representative. Dimensions: ASME 816.3 Material: ASIM A536 Grade 65-45-12 Finish: Black Threads: NPT per ASME B1.20.1 Agency Approvals: All ductile iron threaded fittings are UL/ULC Listed and FM Approved. NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threcids which may cause leakage. Ductile iron fittings should be tightened approximately three turns beyond hand tight, but no more than four turns. PROJECT INFORMATION APPROVAL STAMP Project: . []Approved Address: . []Approved as noted Contractor: 0 Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/Dl-1 .15 DUCTILE IRON THREADED FITTINGS 1~).AWIL FIG. 3224 Cap c®uS USTED APPROVED For Listings/Approval Details and Umitations, visit our website at wane.anviiinticem or contact an Anvil Sales Representative. FIGURE 32Z 'n Nominal Size Maximum Dimension A Approx. Wt. Each Working PressureA In. (mm) PSI (kPo) In. (mm) lbs. (kg) —> 1 500 1.16 0.32 25 3450 29.46 0.15 11/4 500 1.28 0.43 32 3450 32.51 0.20 1½ 500 1.33 0.60 40 3450 1 33.78 1 0.21 2 500 1.45 0.91 50 3450 36.83 0.41 A - Working Pressure Ratings are for reference only and based on Sch. 40 pipe. For the latest UI/ULC, and FM pressure ratings versus pipe schedule, please visit anvilintl.com or contact your local Anvil Representative. Dimensions: ASME B16.3 Material: ASTM A536 Grade 65-45-12 Finish: Black Threads: NPT per ASME B1.20.1 Agency Approvals: All ductile iron threaded fittings are UL/ULC Listed and FM Approved. NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile iron fittings should be tightened approximately three turns beyond hand tight, but no more than four turns. PROJECT INFORMATION APPROVAL STAMP Project: Approved Address:[]Approved as noted Contractor: Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/Dl-1 .15 c®uS <3> LISTED APPROVED For Listings/Approval Details and Limitations, visit our website at w.anvltinll.com or contact an Anvil' Sales Representative. 4E~~NVIL DUCTILE IRON THREADED FITTINGS FIG. 3221 Coupling FIGURE 3221 - COUPLIRIc Nominal Size MaximumDimension A Approx. Wt. Each Working PressureA In. (mm) PSI (kPa) In. (mm) lbs. (kg) -. 1 500 1.67 0.40 25 3450 42.42 0.18 Ph 500 1.93 0.57 32 3450 49.02 0.26 P!2 500 2.15 0.75 40 3450 54.61 0.34 2 500 2.53 1.15 50 3450 64.26 0.52 A - Working Pressure Ratings are for reference only and based on 5th. 40 pipe. For the latest ULJULC, and FM pressure ratings versus pipe schedule, please visit anvilintl.com or contact your local Anvil Representative. Dimensions: ASME B16.3 Material: ASTM A536 Grade 65-45-12 Finish: Black Threads: NPT per ASME B 1 .20.1 Agency Approvals: All ductile iron threaded fittings are UL/ULC Listed and FM Approved. NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile iron fittings should be tightened approximately three turns beyond hand tight, but no more than four turns. PROJECT INFORMATION APPROVAL STAMP Project: EJApproved Address: []Approved as noted Contractor: EJ Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/Dl-1 .15 NVIL DUCTILE IRON THREADED FITTINGS (~)'4ww FIG. 3221R Reducing Coupling c®us €e USTED APPROVED For Ussngs/Approval Details and Limitations, visit our webSite at www.anvilintLm co or contact an ArtvlP Sales Representative. FIGURE14-i I : REDUCING COU ] I[e Nominal Size Maximum Dimension A Approx. Wt. Each Working PressureA In. (mm) PSI (kPo) In. (mm) Lbs. (kg) ' 1 x ½ 500 1.69 0.39 25x 15 3450 42.92 0.18 1 xY4 500 1.69 0.53 25x20 3450 42.92 0.24 A - Working Pressure Ratings are for reference only and based on Sch. 40 pipe. For the latest UL.JULC, and FM pressure ratings versus pipe schedule, please visit anvilintl.com or contact your local Anvil Representative. Dimensions: ASME B16.3 Material: ASTM A536 Grade 65-45-12 Finish: Black Threads: NPT per ASME B1.20.1 Agency Approvals: All ductile iron threaded fittings are UL/ULC Listed and FM Approved. NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile iron fittings should be tightened approximately three turns beyond hand tight, but no more than four turns. PROJECT INFORMATION Project: Approved Address: []Approved as noted Contractor: . J Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/DI-1 .15 FIG. 3205R Reducing Tee LISTED APPROVED rings/Approval Details and Umilations, our websita at www.anvllinll.com or tact an Anvil* Sales Representative. <F~~ DUCTILE IRON THREADED FITTINGS (~)AWIL FIGURE 3205R - REDUCING I: Nominal Size Max. Working Dimensions PPtIC 0Xj1 1 x 2 x 3 Pressurea, A B C • In. (mm) PSI (kPo) In. (mm) In. (mm) In. (mm) tbs. (kg) lX 1/2 x 1 500 1.50 1.36 1.50 0.64 25x 15x25 3450 38.10 34.54 38.10 0.29 1 x 3/4 x 1 500 1.50 1.45 1.50 0.73 25x 20x25 3450 38.10 36.83 38.10 0.33 lxi xVt 500 1.26 1.26 1.36 0.71 25x25x15 3450 32.00 32.00 34.54 0.32 1 x 1 x Y4 500 1.37 1.37 1.45 0.76 25x25x20 3450 34.80 34.80 36.83 0.34 1 X x 1V4* 500 1.67 1.67 1.58 0.98 25x25x32 3450 42.41 42.41 40.13 0.44 1 x x 11/2* 500 1.80 1.80 1.65 1.16 25x25x40 3450 45.12 45.12 41.91 0.53 1¼ x 1 x 1/2* 500 1.34 1.26 1.53 0.82 32x25x 15 3450 34.04 32.00 38.86 0.31 11/4 x 1 x Y4 500 1.45 1.37 1.62 0.90 32x25x20 3450 36.83 34.80 41.15 0.41 ) 1¼ x 1 x 1 500 1.58 1.50 1.67 1.00 32x25x25 3450 40.13 38.10 42.42 0.45 1/4 X 1 X 11/4 500 1.75 1.67 1.75 1.08 32x25x32 3450 44.45 42.42 44.45 0.49 1¼ x 1 x 11/2 500 1.88 1.80 1.82 1.42 32x25x40 3450 47.15 45.72 46.22 0.64 1¼ x 1¼ x 1/2 32x32x 15-t 500 1.34 1.34 1.53 0.86 3450 34.04 34.04 38.86 0.39 Dimensions: ASME B16.3 Material: ASTM A536 Grade 65-45-12 Finish: Black Threads: NPT per ASME B1.20.1 Agency Approvals: All ductile iron threaded fittings are UL/ULC Listed and FM Approved. NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile iron fittings should be tightened approximately three turns beyond hand tight, but no more than four turns. FIGURE 320.1: REDUCING TEE Nominal Size Max. Working PressureA Dimensions P t. P 0X Ea( j1 1 x 2 x 3 A B C In. (mm) PSI (kPo) In. (mm) In. (mm) In. (mm) tbs. (kg) 1¼ x 1¼ x Y4 32x32x20 500 3450 1.45 1 36.83 1.45 36.83 1.62 41.15 0.92 0.42 1¼ x 1¼ x 1 32x 32x25 500 3450 1.58 40.13 1.58 40.13 1.67 42.42 0.95 0.43 1¼ x 1144 x 11/2* 32x32x40 500 3450 1.88 41.75 1.88 47.15 1.82 46.22 1.45 1 0.66 A Working Pressure Ratings ore for reference only and based on Sch. 40 pipe. For the latest UL/ULC, and FM pressure ratings versus pipe schedule, please visit anvilintl.com or contact your local Anvil Representative. * Part supplied as 'Bull Head Tee. PROJECT INFORMATION APPROVAL STAMP Project: 0 Approved Address: J Approved as noted Contractor: . U Not approved Engineer: Remarks: Submittal Date: Notes 1: Notes 2: SPF/Dl-1 .15 Per NFPA 1 - 3/80 or 1/2" Lag Bolts Up to 4" (100mm) pipe 2 -#16x2" Drive Screws 1/2' (15mm) -4(100mm) pipe Upper Attachments TOLCOW Fig. 58 - Threaded Side Beam Bracket < Size Range: /8"-16 rod, pipe sizes 1/20 (15mm) thru 4' (100mm) Material: Pie-Galvanized Steel Function: Practical and economical bracket used to support piping from wood, concrete or steel beams. Features: Unique design allows rod to be easily threaded into bracket. Offset design permits unlimited rod adjustment. Center mounting hole will accept /8' and 1/20 fastener bolts. Per NFPA 13: 1/2' (15mm) thru 2" (50mm) pipe requires /' fastener, 21/2' (65mm) thru 4' (100mm) pipe requires 1/2" fastener.* Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL), and Factory Mutual Engineering approved thru 4" (100mm) pipe. Finish: Pre-Galvanized Order By: Part number and finish *Note: Additionally UL has listed the Fig. 58 with fasteners as shown in table below. 2-1/4'x2" Lag Bolts (No Pie-Drilling Up to 4' (loOmm) pipe :cüs iSTIO • AM= UI Listed Fastener Table Pipe Size I on Fastener Type Material 2" 2 #16 x 2" Drive screws Wood 2" 1 /8" Lag bolt Wood 21/2" -4" 1 1/2' Lag bolt - Wood 31/2' 2 /4" x 11I2" Lag bolts Wood 4' 2 1/4" x 2' Lag bolts ** Wood 40 2 #14 x 1" or 1/4" x 1" Tek type screws Metal (15 gauge) 40 2 #14 x 1" or 1/4" x 1" Tek type screws Metal (16 gauge) ** No pre-drilling 2-#14x1'0r1/4"x1" Tek Type Screws Into Mm. 16 Gauge Steel Up to 4" (lo0mm( pipe Bolt & Hex Nut Up to 4 (100mm( pipe Part No. Pipe Size Rod A B C Max. Rec. Load Approx. Wt/100 in. (mm) Size in. (mm) in. (mm) in. (mm) Lbs. (kN) Lbs. (kg) 58 1/2'-4" (15-100) /8"-16 2/4" (69.8) 11/2" (38.1) 11/8" (28.6) 300*** (1.33) 14 (6.3) With Safety Factor of 5. All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line series Pipe Hangers & Supports 233 Eaton Pipe Hangers TOLCO Fig. 1CBS - Clevis Bolt Spacer Size Range: Size 1° (25mm) thru 20' (500mm) clevis hanger Material: Steel Function: Used as a spacer at a seismic brace location to keep clevis hanger from collapsing during seismic event. Approvals: Included in our Seismic Engineering Guidelines approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to our Seismic Engineering Guidelines OPM-0052-13, for 21/2' - 8" (B3100) only Installation Note: Fig. 1CBS fits easily over the cross bolt and attaches by pinching tabs down. Finish: Pre-Galvanized. Contact customer service for alternative finishes and materials. Order By: Figure number and finish. OPM Pipe Size Approx. Wt./100 Part No. in. (mm) lbs. (kg) I 1CBS-1 1" (25) 3.2 (1.4) 1CBS-11/4 1/4" (32) I 1CBS-1'/z 1'/2" (40) 4.1 4.8 (1.8) 1CBS-2 LJLPBS.2'I2 2" 21/2 (65) (50) 9.4 11.4 (4.2) 1CBS.3 1CBS-31I2 1CBS-4 3V2"(90) (75) (100) 13.9 16.0 18.0 (6.8) (72)_J (8.1) I 1CBS-5 (125) 27.3 (12.4) 1CBS-6 11501 32.5 (14.7) [ 1CBS.8 8" (200) 42.5 (19.2) j 1CBS-10 10" (250) 72.7 (32.9) [15R52 12" (300) 86.3 (39.1)jj 1CBS.14 14" (350) 157.6 (71.5) 1CBS.16 16" (400) 183.7 (83.3)__J 1CBS-18 18" (450) 224.6 (101.9) T1cBs.20 20" (500) 254.0 (115.2) 1 TOLCO Fig. 25 - Surge Restrainer Size Range: - One size fits 3/4 (20mm) thru 2' (40mm) pipe. Material: - Pre-Galvanized Steel Function: - Designed to be used in conjunction with Fig. 200 band hangers to restrict the upward movement of piping as it occurs during sprinkler head activation or earthquake type activity. The surge restrainer is easily and efficiently installed by snapping into a locking position on the band hanger. This product is intended to satisfy the requirements as indicated in the National Fire Protection Association NFPA 13, 2016 edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to restrain either steel pipe or CPVC plastic Pipe. Approvals: - Underwriters Laboratories Listed only when used with band hanger Fig. 200, in the USA (UL) and Canada (cUL). Finish: Pre-Galvanized Order By: Figure number and band hanger, size from 3/4w (20mm) thru 2' (40mm). Patent #5,344,108 Approx. Wt./100 Part No. lbs. (kg) 25 4.8 (2.2) J All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise Eaton Revised 8/8/2074 22 B-Line series Fire Protection Solutions A X @ us Overall Height USTED, APPROVED B Center of pipe to top of knurled hanger rod nut. 0 Top of pipe to bottom of hanger rod nut. Fig. 200-/2& 44 200/4 44 200-11 to 200-2 Fig. 200.21/2 to 200-8 Pipe Hangers Jr < TOLCOTh Fig. 200F - "Trimline" Adjustable Band Hanger with Felt Lining for Copper Tubing TOLCO Fig. 200C - "Trimline" Adjustable Band Hanger with Plastic Coated TOLCO Fig. 200S - "Trimline" Adjustable Band Hanger with Removable Nut (For sizes 1" thru 2") Size Range: Fig. 200 - 1/2" (15mm) thru 8" (200mm) pipe Material: Steel, Pre-Galvanized Function: For fire sprinkler and other general pipirg purposes. Knurled swivel nut design permits hanger adjustment after installation. Features: 1/2" (15mm) thru 2" (50mm) sizes have flared edges for ease of installation on all pipe types and protects CPVC plastic pipe from abrasion. Captured knurled nut design (flared top) on 1" thru 2" sizes keep nut from separating with hanger. Hanger is easily installed around pipe. 1/2" (15mm), 3/4" (20mm), and 21/2" (65mm) thru 8" (200mm)) Spring tension on nut holds it securely in hanger before installation. Knurled nut is easily removed. For 1/2" (15mm) and 3/4" (20mm) sizes with non-captured knurl nuts order Fig. 200S Approvals: Underwriters Laboratories listed (1/2" (15mm) thru 8" (200mm)) in the USA (UL) and Canada (cUL) for steel and CPVC plastic pipe and Factory Mutual Engineering Approved (FM) (3/4" (20mm) thru 8" (200mm)). Conforms to Federal Specifications WW-H-171 E & A-A-1 192A, Type 10 and Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58, Type 10. Maximum Temperature: 650°F (343°c) Finish: Pre-Galvanized. Stainless Steel materials will be supplied with ) hex nuts in place of a knurl nut. Order By: Part number and pipe size Q Note: For metric hanger rod sizes add the metric rod size to the figure number. Example: 200M8-11/2 or200M10-11/2 Fig. 200C Fig. 200F Fig. 200 Fig. 200& Fig. 200S 200C-1 '/z shown 200E-11/2 shown shown with captured nut shown with 1" thru 2" sizes only non-captured nut Pipe Size Rod Size A B D Max. Rec. Load Approx. Wt./100 Part No." in. (mm) in. mm" in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg) [ 200-1/2 1/2" (15) /8"-16 M8 or MiD 31/8' (79.4) 2/8" (66.1) 111/32" (34.1) 400 (1.78) 11 (5.0)__j 200./4 3/4' (20) /8'-16 M8 or MiD 31/8"(79.4) 21/2'(63.5) 11/16"_(21.0) 400 (1.78) 11 (5.0) [ 200-1 1" (25) /8"-16 MB or MiD 3/8" (85.7) 2/8" (66.1) 11/8" (28.6) 400 (1.78) 12 (5.5) 200-11/4 11/4' (32) /8'-16 MB or MiD 33/4" (94.0) 2/8" (73.0) 1/32' (29.3) 400 (1.78) 13 (5.9) 200.11/2 11/2' (40) /8'-16 MB or MiD 3/8" (98.4) 2/8' (73.0) 1/16" (30.2) 400 (1.78) 14 (64)] 200-2 2" (50) /8"-16 MB or MiD 41/2" (114.3) 3' (76.3) 1/16' (30.2) 400 (1.78) 15 (6.9) 200-2/2 21/2" (65) - /8'-16 M10 5/8" (142.9) 41/8' (104.1) 1/16' (36.5) 600 (2.67) 27 (12.3) ] 200.3 3" (75) 3/a'-16 MiD 5/8" (149.1) 4' (101.6) 11/4" (31.7) 600 (2.67) 29 (13.3) I 200-3/z 31/f(9)() I8'-l6 Mb - 7/8' (187.3) 51/4" (133.3) 23/16" (55.6) 600 (2.61) - 34 200-4 4" (100) /8"-16 MiD 7/8" (187.3) 5" (127.0) 1/8' (34.9) 1000 (4.45) 35 (16.0) L_200-5 5'(125)1/2'_13 _M12 -91/8"(231.8)61/4"(158.7)311/32'_(84.9)1250 (5.56)66(30.2)1 200-6 6" (150) 1/2"13 M12 101/8" (257.2) 6/4" (171.4) 2/32" (56.3) 1250 (5.56) 73 (33.4) 1 200-8 B'(200) 1/2"_13 M12 131/8" (333.4) 8/4" (222.2) 37/33" (81.7) 1250 (5.56) 136 (62.3) All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line series Fire Protection Solutions 23 Eaton TL Specify Length TL Thread Threaded Accessories - Threaded Rod (right-hand threads - both ends) NThreaded Rod (right & left hand threads) Size Range: 3/8' .thru /8"-9 rod Material: Steel Function: Recommended fo)"'qe as a hanger support in hanger assemblies. Rod is threaded on both ends wih".d,ht hand threads of the length shown. Also available with left and right hand thre- specify Fig. B3205L when ordering. Maximum Temperature: 750°F (399°cl Finish: Plain or Electro-Galvanized. Contact cust l,r service for alternative finishes and materials. Order By: Figure number, rod size, length and finish Standard Design Thread Size Thread Length TI 650°F (343°C) - ~Lb C) Part No. A in. (mm) Lbs. (kN) ) 1!!5-318 )CL' /8-16 21/2 (63.5) - 730 (3.25) 572 B3205-1/2 X L '/2"-13 21/2" (63.5) 1350 (6.00) 1057 (4.70) I B3205-5/8 X 'I? /8"-11 21/2" (63.5) 2160 (9.61) 1692 (7.52—)-7 B3205-3/4 x 1 /4°-10 3" (76.2) 3230 (14.31) 2530 (11.25) I B3205-7I8 X L /8-9 - 31/2" (88.9) 4480 (19.93) 3508 (15.60) 1 For larger sizes consult full line pipe hanger catalog. AIR - All Threaded Rod - 120" (3.05m) Lengths <- - TOLCO Fig. 99 - All Threaded Rod Cut To Length Size Range: 1/4"20 thru /8"-9 rod in 120' lengths or cut to length Material: Steel Maximum Temperature: 750°F (399°c) Finish: Plain or Electro-Galvanized. Contact customer service for alternative finishes and materials. Approvals: Included in our Seismic Engineering Guidelines approved by the State of California Office of Statewide Health Planning and Development (OSHPD). For additional load, spacing and placement information relating to OSHPD projects, please refer to our Seismic Engineering Guidelines, OPM-0052-13. Order By: Figure number, rod size, length and finish OPM Part No.- Size x length ATR I Fig. 99 Threads Per Inch Recommended load Lbs. (kN) Approx. Wt.I100 Ft. Lbs. (kg) ATR 1/4" x 120 99.1/4" xlength 20 240 (1.07) 12 (5.44)__J ATR Io" x 120 [AfR1/iO' 99-/8" x length 5 1/2'1jjjgiIj" 16 730 (3.24) 29 (13.15) 13 135016.00) 53 (24.04) ATR /" x 120 E!3' 995/8" x length /4"iliii 11 2160 (9.60) 89 (40.31) 10 3230 (14.37) 123 (55.19) ] ATR /" x 120 99-/8" x length 9 4480 (19.93) 170 (77.11) For larger sizes consult full line pipe hanger catalog. All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Eaton 96 B-Line series Fire Protection Solutions B Overall Height 2/8' (73.0) For 1/4' Flat Head Machine Screws or Wood Screws '—A (Rod or Pipe Thread) Hanger Rod or Pipe Not Included D (2 Holes) Upper Attachments B31.R - Ceiling Flange B3199RCkiling Flange Dura-Copper Coated Size Range: /8'-&..'-13 rod Material: Malleable Iron 'tless Steel Type 304 available) Standard Finish: Plain or Electroa1anized B3199RCT is DURA-COPPER'TM coated Function: Designed for attaching a hanger or suDQft rod to beams, ceilings, or walls. Order By: Part number and finish. B3199RCT Part No. Thread Size B Design Load ApproxtW, A in. (mm) Lbs. (kN( Lbs. (kg) B3199R-3/8 B3199RCT-3/8 /8"-16 /16" (11.1) 180 (.80) 13 (5.9) B3199RJ/2 B3199RCT-1/2 1/2"_13 1/2" (12.7) 180 (.80) 17 (7.7) > (TOLCO Fig. 78 - All Steel Ceilin9± late) Size Range: 3/8"-16 rod Material: Pie-Galvanized Steel Function: Attachment to wood beams, ceilings, metal decks or walls. Can also be welded to steel beams. Approvals: Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Additionally, UL has listed the Fig. 78 with fasteners as shown in the table below. Finish: Plain. Contact customer service for alternative finishes and materials. - - - - Order By: Part number, rod size and finish c.us US Patent #5,702,077 LISTED. UL Listed Fastener Table Pipe Size I Qty I Fastener Type Material 1/2' - 2' 2 #14 x 11/4' A-point hex-washer-head sheet metal screw 1/4"X 11/2" wood screws* - 1A1 tek screws Wood 21/2" -4" 2 Wood [2 2 Metal (18 gauge) 1/2" - 2' 2 #14 x 11/4' A- point hex-washer-head sheet metal screw Wood fl/2'"Y ••T' #14x 2" A-point ithiihiidheet metal screw Wd thru 5/jpi rT "No pre-drilling Part No. Pipe Size A B C Hole Dia. D Thread Size Design load Approx. Wt./100 in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) E Lbs. (kN) Lbs. (kg) 1/2" - 2" (15-60) 3" (76.2) 21/8" (54.0( 11/8" (28.6) /16" (7.9) /8'-16 150 (0.67) 15 (6.8) All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. B-Line series Pipe Hangers & Supports 229 Eaton I'SAMMYW FOR WOOD Wood - Wood Joist Double Sheetrork Ceiling 1( _ tumrfor [mingmaybemdterGST1 page II. Ii Not less than 2" nominal width Not less than 1 3' nominal thickness (2-1/7) (depth or side rtical member) For vertical use - install in center of lower face. Minimum ernbedment into base materbe for NFPA'tiance. No pre-drilling required. Quick to install using the Sammy Nut Dver with an 18V cordless dnlUdnver. 'Saves time from traditional methods. Reduces installation costs. Manufactured in the U.S.A. Wwat a uideo demounvebnu wwwitwbulldex.comj ad (Ibs) Qty #14 Black Nut Driver Part #8113910 #14 SW Red Nut Driver Part #8114910 1/4' 8002957 GST 100 1/4 x1' 25 125 1/4 8003957 GST 200 1/4x2 1760 (Fir) . - 25 125- 3/8* 3/8 8007957 8008957 GST 10 GST2O 1/4 x11" 1/4x2 1760 ir) 300 850 25 U7525125 125 3/8" 8068925 GST 20-SS 114x2" 1760 (Fir) 850 - 25 125 3/8 8009925 GST 25 380 318x 21/2 2113 (Fir) 1500 25125 .. ? 318" 8010957 GST 30 1/403" 2060 (Fir) 1500 1475 25 125 E88069925 GST 30SS1/4x3 2060 (Fir) - 25125 fl 1/2' 1/2' 8013925 85925GST3 GST2 1/4x2 1/4x3" 1760 (Fir) 2275r) 25 TT 25 125 125 0 pwu&evcrsweousA \( SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into h contact with the material you are installing into, continue drilling until nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for installations. L 1/2' 8303957 SH-GST/CST2.0 5/16x 1-3/4" 140645°off vertical 25 125 Dim. Lumber IWI 6 9AffZZ Not less than 2" nominal width (1.1/21 up to 3-1/2' pipe; not less than 3" (2-1/2') nominal Width 4' & 5 pipe I * Minimum 2-1/2' from bottom for branch lines. Minimum 3" from bot- tom for main lines. Exception: This requirement shall not apply to 2' or thicker nailing strips resting on top of steel beams. ---- _________________ No pre-drilling required. L Quick to install using the Sammy Floor Joist T Nut Driver with an 1 8 cordless dlWdver. Saves time from traditional methods. Reduces installation costs. Manufactured in the U.S.A. - 1/4" 8019957 SWG 200 1/4x2" 1725 (Fir) 25 125 [_ 3/8 8020957 6WG10 1/4 x 622c) 300 25 125 3/8" -- 8021957 SWG2O - 1/4x2' 1725 (Fir) 1050 125.j 3/8 8073925 SWG2OSS 1/4x2 1725(Fx) - 850 25 125 _ 3/8'* 8022925 SWG25-380 318x2-1/2" 2249 (Fir) 1500 25 125 #14SWRed _L____ 8023925 SWG3O -- 1/4x3" 1884 (Fir)— 25 - - 125 Nut Driver Part # 8114910 May require pre-drilling; consult joist manufacturer. 211111111111111 Eliminates distortion of threaded rod. "Accommodates up to 31/2 x 12 pitch roof. '— -=-- "Allows 17° deflection from vertical. "Saves time from traditional methods. Reduces installation costs. "Manufactured in the U.S.A. #14 Black Nut Driver '1: 3/8" 8139957 SH-GST2O 1/4x2" 1257 (Fir) 1050 1475 25 125 Part#8113910 l — 1903 Dim. Lumber" 1500 - 3/8' 8269957 SH-GST/CST 20 5/16 x 1-3/4" 1406 @ 45°off vertical 850 45' 25 125 ] Dim. Lumber © I 903 Dim. Lumber May require pre-drilling; consult joist manufacturer. #14 SH Orange Nut Driver Part #8273910 8007957 GSI1O 3/8' Vertical CPVC1-112" 300 1-1/2' - 8020957 SWG 10 318' Horizontal CPVC 1-112' 300 1-1/2' 8008957 - 05120 3/8 - Vertical 21/2 850 - 11/2 4 - 1475 11/2 8068925 GST 20-SS 3/8' Vertical 2-1/2' - 850 1-1/2' -- L MOP ----05130 - 3/8' 1475 1-1121 8009925 GST25-380 3/8' Vertical 4" 1500 1-1/2' 8o22925 -SWG2S-38-3/8'Horizontal 3-i/2'-4--1500 1-1/2' 8021957 SWG2O 3/8' Horizontal 2-1/2"-3'"" 1050 1-1/2' 8073925 SWG 20-SS --------- ------- ----- --- ----- - ---------------------------------------- 8269957 SH-GST/CST2O 3/8' 45" Angle off Vertical 2-1/2' 850 1-1/2' - 82997__ SH-GST2O ST/CST - 45*Angle off Verti cal --------3/8' - 11-ig 8139957 3/8' 17" Angle off Vertical 1050 1-1/2" 4" 1475 1-1/2" I LQ!!DSTR-1 3/8' Vertical - -----.q 4" 1475 8037957 DSTR 1-1/2 3/8' Vertical 4' 1500 .035' 4' 1475 .105' 8039957 DSTR 516 3/8" Vertical 4' 1500 .037' 4' 1475 .105' 8045957 DST 516 3/8' Vertical 4' 1500 .188' 4" 1475 .188' 8046957 TEK5O 3/8 - Vertical - 4 1500 250 4 _______1475 188 8055957 SWDR 1 3/8' Horizontal 4' 1500 .037" 4" 1475 .060" - 8056957 SWDR 516 3/8' Horizontal 1500 .037' 4' 1475 .060" 8054957 SWDR 1-1/2 3/8" Horizontal 4' 1500 .037' 4' 1475 .060' 8137957 - SH-DSTR13/8' 17"AngleoffVertic 4"-------1500 .035"4'1475 .105' 8268957 SH-TEK 50 3/8' Vertical , 2-1/2' 850 - - _0gleotfVerticaL - 4. 1500 ; " 8150922 XP 20 3/8" Vertical 2-1/2' 850 .027' - -- 940 , 8153922 XP 35 3/8" Vertical 4' 1500 .060' 1 475 .125' 8_29492 SXP20 3/8 Verticalorupto45---750 --.027'---2 635 029 8295922 SXP35 3/8' Verti cal orupto89" 3-1/2' 1250 .060" 2' 635 .029" 8293957 SW XP 35 3/8' Horizontal 3-1/2' 1250 .060' SAMMYS FOR CONCRETE - PIPE HANGER LP!!1 CST 20 3/8' Vertical - 4' ----3000 8061957 SWC 20 3/8' Horizontal 4' 1475 3000 8150922 XP 20 3/8' Vertical 2-1/2' 850 Pre-Pour Structural © 3000psi 8150922 Part XP 20 3/8" Vertical 2-1/2' 850 Post-Pour Range II LWC :5 35 PCF (lbs/ft3) Number Model Rod Size Mount Direction UL Load Rating (lbs) UL Min Steel Thickness 81 XP 20 Vertical 185 .027" L_2 250 ------- 8153922 XP 35 3/8 Vertical 185 .027' 250 03 5. 8181922 XP 200 1/4' Vertical 185 .027' 8294922 S XP 20 / 8• Vertical 170 .027" 45" 80 .027" 8295922 - SXP3S 3/8" - - Vertical 250 .060" 90 80 .060' 8293957 SWXP35 3/8" Horizontal - 80 .060" 8150922 - XP 20 3/8' Vertical 283 .027' - Max 4 trade size EMT, RMC, and IMC & 5 trade size rigid PVC conduit 8153922 XP 35 3/8" Vertical 500 .060' Max 4 trade size EMT & 6 trade sze RMC, IMC, and rigid PVC conduit 29922-------SXP203/8' - -----------Vertical 283 .027" Max 4 trade size EMT, RMC, and lMC&5 trade size rigid PVC conduit 8295922 SXP 35 3/8" Vertical 500 .060" Max 4 trade size EMT & 6 trade sze RMC, IMC, and rigid PVC conduit 8293957 SWXP35 -3/8' -Horizontal .068'Max 4 trade size EMT &6 trade Sze RMC, MC and rigid PVC conduit 8149957 CZ2000 1/4 or 3/8 Onto Vertical Rod - - -- - UL Listed 4S16 - Cable Hanger, Cat. No. C-Z2000 Plenum Rated, Complies wl NEC Standards GaugeNo. - -- 229a. 20ga.18ga.16ga. 14ga-l2ga. - 118" 3116" Nominal Decimal Equivalent - - -- .030" .036' .048" .060' .075' .105' .125" .188" .250 "sWG 25-380 Maximum pipe size in composite wood joist allowed by UL is 3-1/2' UL compliance with NEC Standards. "SWG 25-380 Maximum pipe size in wood timber or joist allowed by UL is 4 UL and FM tests were performed in compliance with NFPA 13 Standards. "SWG 20 Maximum pipe size in composite wood joist allowed by UL is 21/2 Fastening requirement 5 times weight of water-tilled schedule 40 pipe plus 250 pounds /