Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAbout2810 CARIBOU CT; 160; FPC2020-0187; Permit(-City of
PERMIT REPORT Carlsbad
Print Date: 06/23/2021 Permit No: FPC2020-0187
Job Address: 2810 CARIBOU CT, # 160, CARLSBAD, CA 92010 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2091200300 Track #: Applied: 10/27/2020
Valuation: $637,791.63 Lot #: Issued: 11/10/2020
Occupancy Group: Project U: Finaled Close Out: 03/09/2021
#of Dwelling Units: Plan U:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check U: Inspector:
Plan Check U: Final Inspection:
Project Title:
Description: SPY OPTIC - 2ND REVISIONS TO SPRINKLER TI (60 HEADS)
Applicant: FPContractor:
A AND D FIRE SPRINKLERS INC A AND D FIRE SPRINKLERS INC
TREVOR TORRES 7130 CONVOY CT
7130 CONVOY CT SAN DIEGO, CA 92111-1019
SAN DIEGO, CA 92111-1019 (858) 277-3473
(858) 277-3473
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $553.00
FIRE Plan Review Per Hour - Office Hours $204.00
FIRE Plan Review Per Hour - Office Hours $272.00
Total Fees: $1,029.00 Total Payments To Date: $1,029.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
Fire Protection by Computer Design
A&D FIRE SPRINKLERS INC.
7130 CONVOY COURT
SAN DIEGO, CA 92111
858-277-3473
Job Name : D-3425_Spy_0ptics2_CC#2
Building
Location
System
Contract
Data File : D-3425_Spy_0ptics2_CC#2 Area 2.WXF
Computer Programs by Hydratec Inc. Revision: 50.52.1
Water Supply Curve C
A&D FIRE SPRINKLERS INC. Page
D-3425_Spy_0ptics2_CC#2 Date
City Water Supply: Demand: Cl - Static Pressure : 72 Dl - Elevation : 5.054
C2 - Residual Pressure: 62.77 D2 - System Flow : 302.353
C2 - Residual Flow : 1495.1 D2 - System Pressure : 55.260
Hose ( Demand) : 250
D3 - System Demand : 552.353
Safety Margin : 15.277
150
140
130
p120
R 11
E10°
590
580 --:j---
u 70 - C2
60 D2
E 50 D3
40
30
20
10
....I I I I I I I
200 400 600 800 1000 1200 1400 1600 1800
FLOW (N" 1.85)
Computer Programs by Hydratec Inc. Revision: 50.52.1
Fittings Used Summary
A&D FIRE SPRINKLERS INC. Page 2
D-3425_Spy_0ptics2_CC#2 Date
Fitting Legend
Abbrev. Name 1/2 11/4 1% 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
E NFPA 13 90 Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
T NFPA 139OFlowthruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Unit Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with *• The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Revision: 50.52.1
Pressure / Flow Summary - STANDARD
A&D FIRE SPRINKLERS INC.
D-3425_Spy_0pt1cs2_CC#2
Page
Date
3
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
52 13.17 5.6 10.81 na 18.41 0.15 73 7.0
53 13.17 11.33 na
54 13.17 5.6 11.51 na 19.0 0.15 37 7.0
55 13.17 5.6 13.37 na 20.47 0.15 88 7.0
56 13.17 5.6 14.94 na 21.64 0.15 88 7.0
57 13.17 19.33 na
59 29.0 30.28 na
8 29.0 38.12 na
9 28.17 43.14 na
10 28.17 43.15 na
11 28.17 43.22 na
12 28.17 43.25 na
13 28.17 43.27 na
14 28.17 43.3 na
15 28.17 43.33 na
TOR 28.17 43.58 na
BOR 1.5 55.26 na 250.0
60 13.17 5.6 11.3 na 18.82 0.15 114 7.0
61 13.17 5.6 12.0 na 19.4 0.15 88 7.0
62 13.17 5.6 12.91 na 20.12 0.15 88 7.0
63 13.17 5.6 14.89 na 21.61 0.15 88 7.0
64 13.17 18.72 na
65 13.17 5.6 10.93 na 18.51 0.15 114 7.0
66 13.17 5.6 11.61 na 19.08 0.15 88 7.0
67 13.17 5.6 12.49 na 19.79 0.15 88 7.0
68 13.17 5.6 14.41 na 21.26 0.15 88 7.0
69 13.17 5.6 13.27 na 20.4 0.15 136 7.0
70 13.17 5.6 14.89 na 21.61 0.15 132 7.0
71 13.17 5.6 15.76 na 22.23 0.15 88 7.0
7 29.0 34.06 na
6 11.0 43.7 na
36 11.0 43.73 na
23 11.0 44.22 na
24 29.0 38.51 na
25 29.0 42.2 na
38. 29.0 42.86 na
39 29.0 42.9 na
40 28.17 43.27 na
41 28.17 43.27 na
42 28.17 43.27 na
43 . 28.17 43.27 na
44 29.0 42.92 na
45 29.0 42.94 na
46 29.0 42.97 na
47 29.0 42.89 na
48 29.0 42.91 na
49 29.0 42.91 na
50 29.0 42.91 na
51 29.0 42.94 na
The maximum velocity is 21.76 and it occurs in the pipe between nodes 59 and 8
Computer Programs by Hydratec Inc. Revision: 50.52.1
Final Calculations - Hazen-Williams - 2007
A&D FIRE SPRINKLERS INC. Page 4
D-3425_Spy_0ptics2_CC#2 Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
52 18.41 1.049 E 2.0 2.680 10.809 K Factor = 5.60
to 120.0 0.0 2.000 0.0
53 18.41 0.1118 0.0 4.680 0.523 Vel = 6.83
53 0.0 1.38 0.0 6.060 11.332
to 120.0 0.0 0.0 0.0
54 18.41 0.0294 0.0 6.060 0.178 Vel = 3.95
54 19.00 1.38 2E 6.0 11.030 11.510 K Factor =5.60
to 120.0 0.0 6.000 0.0
55 37.41 0.1090 0.0 17.030 1.856 Vel = 8.02
55 20.47 1.38 0.0 6.420 13.366 K Factor =5.60
to 120.0 0.0 0.0 0.0
56 57.88 0.2444 0.0 6.420 1.569 Vel = 12.42
56 21.65 1.38 T 6.0 4.000 14.935 K Factor= 5.60
to 120.0 0.0 6.000 0.0
57 79.53 0.4400 0.0 10.000 4.400 Vel = 17.06
57 222.82 2.635 3E 24.711 55.100 19.335
to 120.0 0.0 24.711 -6.856
59 302.35 0.2230 0.0 79.811 17.801 Vel = 17.79
59 -74.81 2.067 T 10.0 3.230 30.280
to 120.0 E 5.0 15.000 0.0
8 227.54 0.4301 0.0 18.230 7.840 Vel = 21.76
8 0.0 2.067 T 10.0 0.830 38.120
to 120.0 0.0 10.000 0.359
9 227.54 0.4300 0.0 10.830 4.657 Vel = 21.76
9 0.0 6.357 0.0 10.000 43.136
to 120.0 0.0 0.0 0.0
10 227.54 0.0019 0.0 10.000 0.019 Vel = 2.30
10 74.81 6.357 0.0 20.000 43.155
to 120.0 0.0 0.0 0.0
11 302.35 0.0030 0.0 20.000 0.061 Vel = 3.06
11 -4.95 6.357 0.0 10.000 43.216
to 120.0 0.0 0.0 0.0
12 297.4 0.0030 0.0 10.000 0.030 Vel = 3.01
12 -3.17 6.357 0.0 10.000 43.246
to 120.0 0.0 0.0 0.0
13 294.23 0.0029 0.0 10.000 0.029 Vel = 2.97
13 1.53 6.357 0.0 10.000 43.275
to 120.0 0.0 0.0 0.0
14 295.76 0.0029 0.0 10.000 0.029 Vel = 2.99
14 2.20 6.357 0.0 10.000 43.304
to 120.0 0.0 0.0 0.0
15 297.96 0.0030 0.0 10.000 0.030 Vel = 3.01
15 4.39 6.357 3E 52.808 26.720 43.334
to 120.0 0.0 52.808 0.0
TOR 302.35 0.0031 0.0 79.528 0.243 Vel = 3.06
TOR 0.0 6.357 E 17.603 25.670 43.577
to 120.0 0.0 17.603 11.551
BOR 302.35 0.0031 0.0 43.273 0.132 Vet = 3.06
Computer Programs by Hydratec Inc. Revision: 50.52.1
Final Calculations - Hazen-Williams
A&D FIRE SPRINKLERS INC. Page 5
D-3425_Spy_0ptics2_CC#2 Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "CO or Ftng's Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
250.00 Qa = 250.00
552.35 55.260 K Factor 74.30
60 18.82 1.049 0.0 6.060 11.296 K Factor = 5.60
to 120.0 0.0 0.0 0.0
61 18.82 0.1162 0.0 6.060 0.704 Vel = 6.99
61 19.40 1.38 0.0 8.000 12.000 K Factor = 5.60
to 120.0 0.0 0.0 0.0
62 38.22 0.1135 0.0 8.000 0.908 Vel = 8.20
62 20.12 1.38 0.0 8.000 12.908 K Factor= 5.60
to 120.0 0.0 0.0 0.0
63 58.34 0.2480 0.0 8.000 1.984 Vel = 12.51
63 21.61 1.38 T 6.0 4.000 14.892 K Factor = 5.60
to 120.0 0.0 6.000 0.0
57 79.95 0.4443 0.0 10.000 4.443 Vel = 17.15
57 -222.83 2.635 0.0 11.000 19.335
to 120.0 0.0 0.0 0.0
64 -142.88 -0.0557 0.0 11.000 -0.613 Vel = 8.41
0.0
-142.88 18.722 K Factor = -33.02
65 18.51 1.049 0.0 6.060 10.925 K Factor = 5.60
to 120.0 0.0 0.0 0.0
66 18.51 0.1127 0.0 6.060 0.683 Vel = 6.87
66 19.08 1.38 0.0 8.000 11.608 K Factor = 5.60
to 120.0 0.0 0.0 0.0
67 37.59 0.1100 0.0 8.000 0.880 Vel = 8.06
67 19.79 1.38 0.0 8.000 12.488 K Factor = 5.60
to 120.0 0.0 0.0 0.0
68 57.38 0.2405 0.0 8.000 1.924 Vel= 12.31
68 21.26 1.38 T 6.0 4.000 14.412 K Factor = 5.60
to 120.0 0.0 6.000 0.0
64 78.64 0.4310 0.0 10.000 4.310 Vel = 16.87
0.0
78.64 18.722 K Factor= 18.17
69 20.40 1.049 0.0 12.000 13.270 K Factor =5.60
to 120.0 0.0 0.0 0.0
70 20.4 0.1350 0.0 12.000 1.620 Vel = 7.57
70 21.61 1.38 0.0 6.420 14.890 K Factor = 5.60
to 120.0 0.0 0.0 0.0
71 42.01 0.1352 0.0 6.420 0.868 Vel = 9.01
71 22.23 1.38 T 6.0 4.000 15.758 K Factor = 5.60
to 120.0 0.0 6.000 0.0
64 64.24 0.2964 0.0 10.000 2.964 Vel = 13.78
0.0
64.24 18.722 KFactor= 14.85
59 74.82 2.067 T 10.0 58.880 30.280
to 120.0 0.0 10.000 0.0
7 74.82 0.0549 0.0 68.880 3.784 Vel = 7.15
Computer Programs by Hydratec Inc. Revision: 50.52.1
FinaICaIcuIations - Hazen-Williams
A&D FIRE SPRINKLERS INC. Page 6
D-3425_Spy_0ptics2_CC#2 Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
7 0.0 2.067 1 10.0 18.440 34.064
to 120.0 E 5.0 15.000 7.796
6 74.82 0.0549 0.0 33.440 1.837 Vel = 7.15
6 0.0 2.067 0.0 0.660 43.697
to 120.0 0.0 0.0 0.0
36 74.82 0.0545 0.0 0.660 0.036 Vel = 7.15
36 0.0 2.067 0.0 8.900 43.733
to 120.0 0.0 0.0 0.0
23 74.82 0.0549 0.0 8.900 0.489 Vel = 7.15
23 0.0 2.067 21 20.0 18.000 44.222
to 120.0 0.0 20.000 -7.796
24 74.82 0.0549 0.0 38.000 2.088 Vel = 7.15
24 0.0 2.067 E 5.0 62.110 38.514
to 120.0 0.0 5.000 0.0
25 74.82 0.0549 0.0 67.110 3.686 Vel = 7.15
25 0.0 2.067 T 10.0 0.830 42.200
to 120.0 0.0 10.000 0.359
10 74.82 0.0550 0.0 10.830 0.596 Vel = 7.15
0.0
74.82 43.155 KFactor= 11.39
11 4.96 2.067 T 10.0 0.830 43.216
to 120.0 0.0 10.000 -0.359
38 4.96 0.0003 0.0 10.830 0.003 Vel = 0.47
38 0.0 2.067 E 5.0 108.150 42.860
to 120.0 T 10.0 15.000 0.0
39 4.96 0.0004 0.0 123.150 0.045 Vel = 0.47
39 0.0 2.067 T 10.0 0.830 42.905
to 120.0 0.0 10.000 0.359
40 4.96 0.0004 0.0 10.830 0.004 Vel = 0.47
40 0.0 4.26 0.0 10.000 43.268
to 120.0 0.0 0.0 0.0
41 4.96 0.0 0.0 10.000 0.0 Vel = 0.11
41 3.16 4.26 0.0 10.000 43.268
to 120.0 0.0 0.0 0.0
42 8.12 0.0001 0.0 10.000 0.001 Vel = 0.18
42 -1.52 4.26 0.0 10.000 43.269
to 120.0 0.0 0.0 0.0
43 6.6 0.0 0.0 10.000 0.0 Vel = 0.15
43 0.0 2.067 T 10.0 0.830 43.269
to 120.0 0.0 10.000 -0.359
44 6.6 0.0006 0.0 10.830 0.006 Vel = 0.63
44 0.0 2.067 T 10.0 23.000 42.916
to 120.0 0.0 10.000 0.0
45 6.6 0.0006 0.0 33.000 0.020 Vel = 0.63
45 -2.21 2.067 21 20.0 95.140 42.936
to 120.0 E 5.0 25.000 0.0
46 4.39 0.0003 0.0 120.140 0.035 Vel = 0.42
46 0.0 2.067 T 10.0 0.830 42.971
to 120.0 0.0 10.000 0.359
15 4.39 0.0004 0.0 10.830 0.004 Vel = 0.42
Computer Programs by Hydratec Inc. Revision: 50.52.1
Final Calculations - Hazen-Williams
A&D FIRE SPRINKLERS INC. Page 7
D-3425_Spy_0ptics2_CC#2: Date
Hyd. Qa Dig. Fitting Pipe Pt Pt
Ref. "C' or Ftngs Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
4.39 43.334 K Factor= 0.67
12 3.17 2.067 T 10.0 0.830 43.246
to 120.0 0.0 10.000 -0.359
47 3.17 0.0001 0.0 10.830 0.001 Vel = 0.30
47 0.0 2.067 E 5.0 108.140 42.888
to 120.0 1 10.0 15.000 0.0
48 3.17 0.0002 0.0 123.140 0.019 Vel = 0.30
48 0.0 2.067 T 10.0 0.830 42.907
to 120.0 0.0 10.000 0.359
41 3.17 0.0002 0.0 10.830 0.002 Vel = 0.30
0.0
3.17 43.268 K Factor= 0.48
42 1.53 2.067 T 10.0 0.830 43.269
to 120.0 0.0 10.000 -0.359
49 1.53 0.0 0.0 10.830 0.0 Vel = 0.15
49 0.0 2.067 T 10.0 108.150 42.910
to 120.0 E 5.0 15.000 0.0
50 1.53 0.0 0.0 123.150 0.005 Vel = 0.15
50 0.0 2.067 T 10.0 0.830 42.915
to 120.0 0.0 10.000 0.359
13 1.53 0.0001 0.0 10.830 0.001 Vel = 0.15
0.0
1.53 43.275 K Factor= 0.23
14 -2.20 2.067 T 10.0 0.830 43.304
to 120.0 0.0 10.000 -0.359
51 -2.2 -0.0001 0.0 10.830 -0.001 Vel = 0.21
51 0.0 2.067 E 5.0 85.140 42.944
to 120.0 0.0 5.000 0.0
45 -2.2 -0.0001 0.0 90.140 -0.008 Vel = 0.21
0.0
-2.20 - 42.936 K Factor= -0.34
Computer Programs by Hydratec Inc. Revision: 50.52.1
F.TTIALI~lm
- - - Fire Protection by Computer Design
A&D FIRE SPRINKLERS INC.
7130 CONVOY COURT
SAN DIEGO, CA 92111
858-277-3473
Job Name : D-3425_Spy_0ptics2
Building
Location
System
Contract
Data File : D-3425_SpyOptics2 Area 1 .WXF
Computer Programs by Hydratec Inc. Revision: 50.52.1
Water Supply Curve C
A&D FIRE SPRINKLERS INC. Page
D-3425_Spy_0pt1cs2 Date
City Water Supply: Demand:
CI - Static Pressure : 72 Dl - Elevation : 3.248
C2 - Residual Pressure: 62.77 D2 - System Flow : 276.627
C2 - Residual Flow : 1495.1 D2 - System Pressure : 48.452
Hose ( Demand) :100
D3 - System Demand :376.627
Safety Margin : 22.827
150
140
130
p120
R 110
E10°
90
580 "j
U 70 :
R6° - ____ _____ ______ ________ _________ __________
2
E5°
40
30
20
10
.9.4s..
200 400 600 800 1000 1200 1400 1600 1800
FLOW (N A 1.85)
Computer Programs by Hydratec Inc. Revision: 50.52.1
Fittings Used Summary
A&D FIRE SPRINKLERS INC. Page 2
D-3425_Spy_0ptics2 Date
Fitting Legend
Abbrev. Name % % 1 11/4 11/2 2 21/2 3 3V2 4 5 6 8 10 12 14 16 18 20 24
E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
T NFPA 1390' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Unit Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with '. The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Revision: 50.52.1
Pressure / Flow Summary - STANDARD
A&D FIRE SPRINKLERS INC. Page .3
D-3425_Spy_0ptics2 Date
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
1 9.0 5.6 16.14 na 22.5 0.1 225 7.0
2 11.0 16.86 na
3 11.0 16.92 na
4 11.0 17.95 na
5 11.0 21.49 na
6 11.0 25.36 na
7 29.0 22.34 na
8 29.0 34.36 na
9 28.17 36.42 na
10 28.17 36.43 na
11 28.17 36.48 na
12 28.17 36.51 na
13 28.17 36.53 na
14 28.17 36.56 na
15 28.17 36.58 na
TOR 28.17 36.79 na
BOR 1.5 48.45 na 100.0
16 9.0 5.6 16.67 na 22.86 0.1 225 7.0
17 9.0 5.6 17.64 na 23.52 0.1 225 7.0
18 9.0 5.6 19.86 na 24.96 0.1 225 7.0
19 11.0 20.35 na
20 11.0 20.62 na
21 11.0 22.58 na
22 11.0 25.19 na
23 11.0 25.37 na
24 29.0 23.93 na
25 29.0 34.11 na
26 9.0 5.6 20.15 na 25.14 0.1 225 7.0
27 9.0 5.6 20.97 na 25.65 0.1 225 7.0
28 9.0 5.6 22.0 na 26.26 0.1 225 7.0
29 11.0 22.58 na
30 9.0 5.6 22.19 na 26.38 0.1 225 7.0
31 11.0 22.13 na
32 . 9.0 5.6 22.0 na 26.27 0.1 225 7.0
33 9.0 5.6 22.48 na 26.55 0.1 225 7.0
34 11.0 22.43 na
35 11.0 23.08 na
36 11.0 25.35 na
37 9.0 5.6 22.48 na 26.55 0.1 225 7.0
38 29.0 36.13 na
39 29.0 ' 36.16 na
40 28.17 36.53 na
41 28.17 36.53 na
42 28.17 36.53 na
43 28.17 36.53 na
44 29.0 36.17 na
45 29.0 36.19 na
46 29.0 36.22 na
47 29.0 36.15 na
48 29.0 36.17 na
49 29.0 36.17 na
50 29.0 36.17 na
51 . 29.0 36.2 na
The maximum velocity is 18.57 and it occurs in the pipe between nodes 5 and 6
Computer Programs by Hydratec Inc. Revision: 50.52.1
Final Calculations - Hazen-Williams - 2007
A&D FIRE SPRINKLERS INC. Page 4
D-3425_Spy_0ptics2 Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C',or Ftngs Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
1 22.50 1.083 2E 4.672 6.770 16.143 K Factor = 5.60
to 120.0 0.0 4.672 -0.866
2 22.5 0.1385 0.0 11.442 1.585 Vel = 7.84
2 0.0 1.442 0.0 1.740 16.862
to 120.0 0.0 0.0 0.0
3 22.5 0.0345 0.0 1.740 0.060 Vel = 4.42
3 22.86 1.38 0.0 6.600 16.922
to 120.0 0.0 0.0 0.0
4 45.36 0.1558 0.0 6.600 1.028 Vel = 9.73
4 23.52 1.442 0.0 13.000 17.950
to 120.0 0.0 0.0 0.0
5 68.88 0.2722 0.0 13.000 3.539 Vel = 13.53
5 25.65 1.442 T 7.432 0.490 21.489
to 120.0 0.0 7.432 0.0
6 94.53 0.4889 0.0 7.922 3.873 Vel = 18.57
6 38.49 2.157 E 6.153 18.440 25.362
to 120.0 T 12.307 18.460 -7.796
7 133.02 0.1295 0.0 36.900 4.777 Vet = 11.68
7 0.0 2.157 2T 24.613 62.110 22.343
to 120.0 E 6.153 30.766 0.0
8 133.02 0.1294 0.0 92.876 12.021 Vel = 11.68
8 0.0 2.157 T 12.307 0.830 34.364
to 120.0 0.0 12.307 0.359
9 133.02 0.1295 0.0 13.137 1.701 VeI= 11.68
9 0.0 6.357 0.0 10.000 36.424
to 120.0 0.0 0.0 0.0
10 133.02 0.0007 0.0 10.000 0.007 Vet = 1.34
10 143.61 6.357 0.0 20.000 36.431
to 120.0 0.0 0.0 0.0
11 276.63 0.0026 0.0 20.000 0.052 Vet = 2.80
11 -4.91 6.357 0.0 10.000 36.483
to 120.0 0.0 0.0 0.0
12 271.72 0.0025 0.0 10.000 0.025 Vet = 2.75
12 -3.11 6.357 0.0 10.000 36.508
to 120.0 0.0 0.0 0.0
13 268.61 0.0025 0.0 10.000 ' 0.025 Vet = 2.72
13 1.54 6.357 0.0 10.000 36.533
to 120.0 0.0 0.0 0.0
14 270.15 0.0025 0.0 10.000 0.025 , Vet = 2.73
14 2.15 6.357 0.0 10.000 36.558
to 120.0 0.0 0.0 0.0
15 272.3 0.0025 0.0 10.000 0.025 Vet = 2.75
15 4.33 6.357 3E 52.808 26.720 36.583
to 120.0 0.0 52.808 0.0
TOR 276.63 0.0026 ' 0.0 79.528 0.206 Vet = 2.80
TOR 0.0 6.357 E 17.603 25.670 36.789
to 120.0 0.0 17.603 11.551
BOR 276.63 0.0026 0.0 43.273 0.112 Vet = 2.80
Computer Programs by Hydratec Inc. Revision: 50.52.1
Final Calculations - Hazen-Williams
A&D FIRE SPRINKLERS INC. Page 5
D-3425_Spy_0ptics2 Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
100.00 Qa = 100.00
376.63 48.452 K Factor 54.11
16 22.86 1.083 T 5.84 2.000 16.669 K Factor= 5.60
to 120.0 0.0 5.840 -0.866
3 22.86 0.1427 0.0 7.840 1.119 Vel= 7.96
0.0
22.86 16.922 K Factor = 5.56
17 23.52 1.083 1 5.84 2.000 17.637 K Factor = 5.60
to 120.0 0.0 5.840 -0.866
4 23.52 0.1504 0.0 7.840 1.179 Vel= 8.19
0.0
23.52 17.950 K Factor = 5.55
18 24.96 1.083 2E 4.672 3.420 19.858 K Factor = 5.60
to 120.0 0.0 4.672 -0.866
19 24.96 0.1678 0.0 8.092 1.358 Vel = 8.69
19 0.0 1.442 0.0 6.390 20.350
to 120.0 0.0 0.0 0.0
20 24.96 0.0416 0.0 6.390 0.266 Vel = 4.90
20 25.13 1.442 0.0 13.000 20.616
to 120.0 0.0 0.0 0.0
21 50.09 0.1510 0.0 13.000 1.963 Vel = 9.84
21 26.27 1.442 T 7.432 0.500 22.579
to 120.0 0.0 7.432 0.0
22 76.36 0.3294 0.0 7.932 2.613 Vel = 15.00
22 52.64 2.157 0.0 1.480 25.192
to 120.0 0.0 0.0 0.0
23 129.0 0.1223 0.0 1.480 0.181 Vel = 11.33
23 14.60 2.157 2T 24.613 18.000 25.373
to 120.0 0.0 24.613 -7.796
24 143.6 0.1491 0.0 42.613 6.355 Vel = 12.61
24 0.0 2.157 E 6.153 62.110 23.932
to 120.0 0.0 6.153 0.0
25 143.6 0.1491 0.0 68.263 10.180 Vel = 12.61
25 0.0 2.157 T 12.307 0.830 34.112
to 120.0 0.0 12.307 0.359
10 143.6 0.1492 0.0 13.137 1.960 Vel = 12.61
0.0
143.60 36.431 K Factor = 23.79
26 25.14 1.083 1 5.84 2.000 20.149 K Factor = 5.60
to 120.0 0.0 5.840 -0.866
20 25.14 0.1700 0.0 7.840 1.333 Vel = 8.76
0.0
25.14 20.616 K Factor = 5.54
27 25.65 1.083 T 5.84 2.000 20.972 K Factor = 5.60
to 120.0 0.0 5.840 -0.866
5 25.65 0.1764 0.0 7.840 1.383 Vel = 8.93
0.0
Computer Programs by Hydratec Inc. Revision: 50.52.1
Final Calculations - Hazen-Williams
A&D FIRE SPRINKLERS INC. Page 6
D-3425_Spy_0ptics2 Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
25.65 21.489 K Factor = 5.53
28 26.26 1.083 T 5.84 2.000 21.996 K Factor = 5.60
to 120.0 0.0 5.840 -0.866
29 26.26 0.1844 0.0 7.840 1.446 Vel = 9.15
29 26.38 1.442 1 7.432 8.370 22.576
to 120.0 0.0 7.432 0.0
22 52.64 0.1655 0.0 15.802 2.616 Vel = 10.34
0.0
52.64 25.192 KFactor 10.49
30 26.38 1.083 E 2.336 2.000 22.187 K Factor =5.60
to 120.0 0.0 2.336 -0.866
31 26.38 0.1857 0.0 4.336 0.805 Vel = 9.19
31 0.0 1.442 0.0 9.750 22.126
to 120.0 0.0 0.0 0.0
29 26.38 0.0462 0.0 9.750 0.450 Vel = 5.18
0.0
26.38 22.576 K Factor = 5.55
32 26.27 1.083 T 5.84 2.000 21.999 K Factor = 5.60
to 120.0 0.0 5.840 -0.866
21 26.27 0.1844 0.0 7.840 1.446 Vel= 9.15
0.0
26.27 22.579 K Factor = 5.53
33 26.55 1.083 F 2.336 2.000 22.481 K Factor = 5.60
to 120.0 0.0 2.336 -0.866
34 26.55 0.1882 0.0 4.336 0.816 Vel = 9.25
34 0.0 1.442 0.0 14.000 22.431
to 120.0 0.0 0.0 0.0
35 26.55 0.0466 0.0 14.000 0.653 Vel = 5.22
35 26.55 1.442 T 7.432 6.060 23.084
to 120.0 0.0 7.432 0.0
36 53.1 0.1682 0.0 13.492 2.270 Vel = 10.43
36 -38.49 2.157 0.0 8.900 25.354
to 120.0 0.0 0.0 0.0
23 14.61 0.0021 0.0 8.900 0.019 Vel = 1.28
0.0
14.61 25.373 K Factor = 2.90
37 26.55 1.083 T 5.84 2.000 22.475 K Factor = 5.60
to 120.0 0.0 5.840 -0.866
35 26.55 0.1881 0.0 7.840 1.475 Vel = 9.25
0.0
26.55 23.084 K Factor = 5.53
36 38.49 2.157 0.0 0.660 25.354
to 120.0 0.0 0.0 0.0
6 38.49 0.0121 0.0 0.660 0.008 Vel = 3.38
0.0
38.49 25.362 K Factor= 7.64
11 4.90 2.157 T 12.307 0.830 36.483
to 120.0 0.0 12.307 -0.359
38 4.9 0.0002 0.0 13.137 0.003 Vel = 0.43
Computer Programs by Hydratec Inc. Revision: 50.52.1
fnal Calculations - Hazen-Williams
,- A&D FIRE SPRINKLERS INC. Page 7
D-3425_Spy_optics2 Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C or Ftngs Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
38 0.0 2.157 E 6.153 108.150 36.127
to 120.0 T 12.307 18.460 0.0
39 4.9 0.0003 0.0 126.610 0.037 Vel = 0.43
39 0.0 2.157 T 12.307 0.830 36.164
to 120.0 0.0 12.307 0.359
40 4.9 0.0003 0.0 13.137 0.004 Vel = 0.43
40 0.0 4.26 0.0 10.000 36.527
to 120.0 0.0 0.0 0.0
41 4.9 0.0 0.0 10.000 0.0 Vel = 0.11
41 3.12 4.26 0.0 10.000 36.527
to 120.0 0.0 0.0 0.0
42 8.02 0.0001 0.0 10.000 0.001 Vel = 0.18
42 -1.55 4.26 0.0 10.000 36.528
to 120.0 0.0 0.0 0.0
43 6.47 0.0 0.0 10.000 0.0 Vel = 0.15
43 0.0 2.157 T 12.307 0.830 36.528
to 120.0 0.0 12.307 -0.359
44 6.47 0.0004 0.0 13.137 0.005 Vel = 0.57
44 0.0 2.157 T 12.307 23.000 36.174
to 120.0 0.0 12.307 0.0
45 6.47 0.0005 0.0 35.307 0.018 Vel = 0.57
45 -2.15 2.157 2T 24.613 95.140 36.192
to 120.0 E 6.153 30.766 0.0
46 4.32 0.0002 0.0 125.906 0.028 Vel = 0.38
46 0.0 2.157 T 12.307 0.830 36.220
to 120.0 0.0 12.307 0.359
15 4.32 0.0003 0.0 13.137 0.004 Vel = 0.38
0.0
4.32 36.583 K Factor= 0.71
12 3.12 2.157 T 12.307 0.830 36.508
to 120.0 0.0 12.307 -0.359
47 3.12 0.0001 0.0 13.137 0.001 Vel = 0.27
47 0.0 2.157 E 6.153 108.140 36.150
to 120.0 T 12.307 18.460 0.0
48 3.12 0.0001 0.0 126.600 0.016 Vel = 0.27
48 0.0 2.157 T 12.307 0.830 36.166
to 120.0 0.0 12.307 0.359
41 3.12 0.0002 0.0 13.137 0.002 VeI= 0.27
0.0
3.12 36.527 K Factor= 0.52
42 1.55 2.157 T 12.307 0.830 36.528
to 120.0 0.0 12.307 -0.359
49 1.55 -0.0001 0.0 13.137 -0.001 Vel = 0.14
49 0.0 2.157 T 12.307 108.150 36.168
to 120.0 E 6.153 18.460 0.0
50 1.55 0.0 0.0 126.610 0.005 Vel = 0.14
50 0.0 2.157 T 12.307 0.830 36.173
to 120.0 0.0 12.307 0.359
13 1.55 0.0001 0.0 13.137 0.001 Vel = 0.14
Computer Programs by Hydratec Inc. Revision: 50.52.1
inal Calculations - Hazen-Williams
MD FIRE SPRINKLERS INC. Page 8
Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
1.55 36.533 K Factor = 0.26
14 -2.15 2.157 T 12.307 0.830 36.558
to 120.0 0.0 12.307 -0.359
51 -2.15 -0.0002 0.0 13.137 -0.002 Vel = 0.19
51 0.0 2.157 E 6.153 85.140 36.197
to 120.0 0.0 6.153 0.0
45 -2.15 -0.0001 0.0 91.293 -0.005 Vel = 0.19
0.0
-2.15 36.192 K Factor = -0.36
Computer Programs by Hydratec Inc. Revision: 50.52.1