HomeMy WebLinkAbout6023 INNOVATION WAY; ; FPC2018-0336; Permit4ityof
PERMIT REPORT Carlsbad
Print Date: 10/21/2021 Permit No: FPC2018-0336
Job Address: 6023 INNOVATION WAY, CARLSBAD, CA 92009-1741 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: Track #: Applied: 10/05/2018
Valuation: $0.00 Lot #: Issued: 10/25/2018
Occupancy Group: Project #: Finaled Close Out: 09/26/2019
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #: Inspector:
Plan Check #: Final Inspection:
Project Title:
Description: LIFT SPEC STES -SPRINKLER TI (17 HEADS)
Applicant: FPContractor:
INDUSTRIAL FIRE SPRINKLER CO INDUSTRIAL FIRE SPRINKLER CO INC
STEVE SCOTT 3845 IMPERIAL AVE
3845 IMPERIAL AVE SAN DIEGO, CA 92113-1702
SAN DIEGO, CA 92113-1702 (619) 266-6030
(619) 266-6030 x107
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $553.00
Total Fees: $553.00 Total Payments To Date: $553.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
Frc ~'o (8 - o Z3(0
Page 1 of 6
MICROFAST® QUICK \J III l:II[.1u.yM.. RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
DESCRIPTION
The Viking Microfast Quick Response Pendent Sprinkler VK302 is a small ther-
mosensitive glass bulb spray sprinkler available with various finishes and tempera-
ture ratings to meet design requirements. The special Polyester and Electroless
Nickel PTFE ([NT) coatings can be used in decorative applications where colors
are desired. In addition, these coatings have been investigated for installation in
corrosive environments and are Listed and Approved as indicated in the Approval
Charts.
LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approved: Class Series 2000
VdS Approved: Certificates G414009, G414010, G4040095, and 4880045
A LPCB Approved: Certificate 096e/06
CE Certified: Standard EN 12259-1 certificate of constancy of performance 0832-CPR-50021
CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF)
MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003
Refer to Approval Chart 1 and Design Criteria cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria for
FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)
Rated to 175 psi (12 bar) water working pressure
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2" NPT, 15 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-1/4" (58 mm)
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Phosphor Bronze UNS-051000 or Copper UNS-C19500
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-530400
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For [NT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated.
Ordering Information: (Also refer to the current Viking price list.)
Order Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate
suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN
Temperature Suffix: 135°F (57 °C) =A, 155°F (68 °C) = B, 175°F (79 °C) = D, 200°F (93 °C) = E, 286°F (141 °C) = G
Form No. F_033314 18.06.21 Rev 18.1 Replaces Form No. F_033314 Rev 17.1
(Updated MED approval; added LPCB certificate number)
Page 2 of 6
MICROFAST® QUICK ''4I II(IIIGi RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
For example, sprinkler VK302 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12979AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the current Viking price list.)
Sprinkler Wrenches:
Standard Wrench: Part No. 10896W/B (available since 2000).
Wrench for Recessed Pendent Sprinklers: Part No. 13655W/B** (available since 2006)
Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010) **A 1/2 ratchet is required (not available from Viking).
***Allows use from the floor by attaching a length of 1" diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808.
Sprinkler Cabinets:
Six-head capacity: Part No. 01724A (available since 1971)
Twelve-head capacity: Part No. 01725A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
The Viking MicrofastO Quick Response Pendent Sprinkler VK302 is available through a network of domestic and international dis-
tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
-
Protective Sprinkler Wrench Flat
Clip
Protective Sprinkler
Cap
Figure 1: Standard Sprinkler Wrench 10896W/B
Form No. F_033314 18.06.21 Rev 18.1
Page 30f6
j
®
MICROFAST@ QUICK
RESPONSE PENDENT
SPRINKLER VK302 (K56)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum Ambient
Classification Temperature Rating' Ceiling Temperature' o Bulb Color u
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 C) 150 °F (65 °C) Green
High 286 F (141 C) 225 °F (107 °C) Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion-Resistant Coatings': White Polyester, and Black Polyester. ENT in all temperature ratings except 135 °F (57 °C)
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com-
patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces
only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated.
**
Sprinkler wrench 13655W/B**
for recessed pendent
sprinklers
** A 1/2" ratchet is required
(not available from Viking)
Carefully slide the wrench sideways around
the protective cap, ensuring engagement with
the sprinkler wrench flats
Figure 2: Wrench 13655W/B for Recessed Pendent Sprinklers
Form No. F_033314 18.06.21 Rev 18.1
Page 4 of 6
\J II(IIS1Gi®MICROFASTO QUICK
l.l:ll[.qi•'Yv RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Approval Chart I (UL) Temperature KEY The Viking Microfast Quick Response Finish
Pendent Sprinkler VK302 At I— Escutcheon (II applicable)
Maximum 175 PSI(12 Bar) WWP
Base Sprinkler Thread Size Nominal Overall Listings and Approvals'
Part SIN Style K-Factor Length (Refer also to Design Criteria.)
Number' NPT BSP U.S. metric' Inches mm cULus' VdS LPCB CE 8
12979 VK302 Pendent 1/2" 15 min 5.6 80.6 2-1/4 58 A1Z, B1Y, D2, C2X Al A1Z, B1Y D1Z, C1Y D1W
19780 VK302 Pendent 1/2" 5.6 80.6 2-1/4 58 -- -- -- -- -- 03
21354 VK302 Pendent -- 15mm 5.6 80.6 2-1/4 58 -- -- -- -- -- D3
• NOTICE !77I:1L lability (Contact Local Viking
06662B VK302 Pendent 1/2" 15 mm 1 5.6 1 80.6 2-1/4 58 A1Z, B1Y, D2, C2X I -- -- -- --
18021 VK302 I Pendent 1 1/2" 1 15 mm1 5.6 1 80.6 1 2-1/4 1 58 AiX, B1Y Al I AiX, B1Y I D1X, C1Y7 I 01W
Approved Temperature Ratings Approved Finishes Approved Escutcheons
A - 135 "F (57 "C), 155 F (68 "C), 175 "F 1 - Brass, Chrome, White w - Recessed with the Model Fl Adjustable Escutcheon only
(79 °C), 200 °F (93 SC), 286 ¶ (141 °C) Polyester66, Black Polyes- X - Standard surface-mounted escutcheon or the
B - 135 ¶ (57 °C), 155 "F (68 C), 175 F ter" Viking Micromatic Model E-1 Recessed Escutcheon
(79 "C), and 200 "F (93 C) 2 - ENT5 Y - Standard surface-mounted escutcheon or the
C - 155 °F (68 °C), 175 oF (79 "C), and 3 - Chrome Viking Microfast Model F-i Adjustable Escutcheon, or recessed with the Viking Micro-
200 °F (93 °C) mati& Model E-1 E-2, or E-3 Recessed Escutcheon
D - 155 "F (68 CC), 175 ¶ (79 °C), 200 ¶ Z - Standard surface-mounted escutcheon or the
(93 "C), 286 °F (141 °C) Viking Microfast Model F-i Adjustable Escutcheon
Footnotes
1 Base part number shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This table shows the listings and approvals available at the time of printing. Other approvals may be in process.
Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
cULus Listed as corrosion-resistant.
6 Other colors are available on request with the same Listings and Approvals as the standard colors.
CE Certified, Standard EN 12259-1, EC-certificate of constancy of performance 0832-CPR-S0021.
8 MED Certified, Standard EN 12259-1, EC-0832-MED-1003.
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1 above.)
cULus Listing Requirements:
The Viking Microfast' Quick Response Pendent Sprinkler VK302 is cULus Listed as indicated in the Approval Chart for installation in
accordance with the latest edition of NFPA 13 for standard spray sprinklers.
Designed for use in Light and Ordinary occupancies.
The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F 091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F_033314 18.06.21 Rev 18.1
Page 5of6
MICROFASTO QUICK
tJ II(JF1G ® — — lii:II[.1i.riv RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Approval Chart 2 (FM) Temperature KEY The Viking Microfast' Quick Response Finish
Pendent Sprinkler VK302 AiX 4— Escutcheon (if applicable)
Maximum 175 PSI (12 Bar) WWP
Base Part SIN Sprinkler Thread Size Nominal K-Factor Overall Length FM Approvals3
NPT BSP U.S. metric2 Inches mm Number' Style (Refer also to Design Criteria.)
12979 VK302 Pendent 1/2" 15 mm 5.6 80.6 2-1/4 58 . A1Z, B1Y, D2X, C2
NOTI l:f'1 Limited IAvailability (ContactIV7 Viking Office)
06662B VK302 Pendent 1/2" 15 mm 5.6 80.6 1 2-1/4 58 A1Z, 81Y, D2X, C2
18021 VK302 Pendent 1/2" 15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y
Approved Escutcheons
Approved Temperature Ratings X - Standard surface-mounted escutcheon or the
A - 135°F (57 °C), 155°F (68 °C), 175°F (79 °C), 200 °F Viking Micromatic Model E-1 Recessed
(93 °C), 286 °F'(141 °C) Approved Finishes Escutcheon
B -135°F (57 °C), 155°F (68 °C), 175°F (79 °C), and 1-Brass Chrome, White Polyester', Y - Standard surface-mounted escutcheon or the
200 °F (93 °C) and Black Polyester' Viking Microfast Model F-i Adjustable Escutcheon,
C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 2 - ENT5 or recessed with the Viking Micromatic8 Model E-1
°F (141 °C) or E-2 Recessed Escutcheon
D - 155°F (68 °C), 175 °F (79 °C), 200 °F (93 °C) Z - Standard surface-mounted escutcheon or the
Viking Microfast5 Model F-i Adjustable Escutcheon
Footnotes
1 Base part number shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
This table shows the FM Approvals available at the time of printing. Other approvals may be in process.
Other colors are available on request with the same Approvals as the standard colors.
FM approved as corrosion proofing for corrosive environments.
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
FM Approval Requirements:
The Viking Microfast' Quick 'Response Pendent Sprinkler VK302 is FM Approved as quick response Non-storage pendent sprinklers
as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss
Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not
limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable
spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F 080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza-
tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F_033314 18.06.21 Rev 18.1
Page 6 of 6
MICROFAST® QUICK "J J l:IIE•.ry RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
1/2"
(15 mm)
NPT
(57 m)
r
(4i5?m)
Installed with a standard
1/8" surface-mounted
escutcheon
Ceiling Opening Size:
2-5/16" (59 mm) minimum
2-1/2" (64 mm) maximum
11Th T(38
-1/2"
2"
(51mm
mm)
Installed with a Microfast Note: At maximum, adapter
Model F-I Adjustable is exposed 1/2"(13 mm)
Escutcheon from face of ceiling
Figure 3: Sprinkler Dimensions with a Standard Escutcheon and the Model F-I Adjustable Escutcheon
42.I/8
1-3/4"
(45 mm)
Max.
Ceiling Opening Size:
2-5/16" (59 mm) minimum
2-1/2" (64 mm) maximum
- ---2-1/8" -
/4
1-1/8" T T 1-1/8"
(29 mm) 2" I (29 mm)
Mm. 5;
Mm.
Max.
Installed with a Installed with a Model
Model E-I Recessed E-2 Thread-on Recessed
Escutcheon Escutcheon
Figure 4: Sprinkler Dimensions with the Model E-I and E-2 Recessed Escutcheons
Form No. F_033314 18.06.21 Rev 18.1 Replaces Form No. F_033314 Rev 17.1
(Updated MED approval; added LPCB certificate number)
Page 1 of 4
MICROFAST® QUICK rJ II(11IG RESPONSE UPRIGHT
SPRINKLER VK300 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
DESCRIPTION
The Viking Microfast Quick Response Upright Sprinkler VK300 is a small,
thermosensitive, glass-bulb spray sprinkler available in several differ-
ent finishes and temperature ratings to meet design requirements. The spe-
cial Polyester and Electroless Nickel PTFE (ENT) coatings can be used in
decorative applications where colors are desired. In addition, these coat-
ings have been investigated for installation in corrosive atmospheres and
are listed/approved as corrosion resistant as indicated in the Approval
Charts. (Note: FM global approves the ENT coating as corrosion resistant. FM
Global has no approval classification Polyester coatings as corrosion resistant.)
2. LISTINGS AND APPROVALS
C®L5 cULus Listed: Category VNIV
FM Approved: Classes 2002 and 2020
Refer to Approval Charts and Design Criteria for listing and approval requirements that must be followed.
TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Testing: U.S.A. Patent No. 4,831,870
Thread size: 1/2" NPT, 15 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-3/16" (56 mm)
cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Brass UNS-C23000 or Copper UNS-C 19500
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-530400
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated
Ordering Information: (Also refer to the current Viking price list.)
Order Viking Microfast5 Quick Response Upright Sprinkler VK300 by first adding the appropriate suffix for the sprinkler finish and
then the appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/\N, Black Polyester = M-/B, and ENT = JN
Temperature Suffix (°F/°C): 135°/57° =A, 155°/68° = B, 175°I79° = D, 200°/93° = E, and 286/141° = G
For example, sprinkler VK300 with a 1/2" NPT thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 12978AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the Viking website.)
Sprinkler Wrench: Standard Wrench: Part No. 21475M/B (available since 2017)
Sprinkler Cabinets:
Six-head capacity: Part No. 01724A (available since 1971)
Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
Form No. F_052114 17.10.05 Rev 17.1 Replaces Form No. F_052114 Rev 15.2
(Replaced wrench 10896W/B with 21475M/B)
Page 2 of 4
"J II(IIs1Gi® -MICROFASTO QUICK
ii1:II[.qiu.flf RESPONSE UPRIGHT
SPRINKLER VK300 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
The Viking Microfase Quick Response Upright Sprinkler VK300 is available through a network of domestic and international distributors.
See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
SprinkleçTemperature Sprinkler Nominal Maximum Ambient Bulb Col r Classificàtiön Temperature Rating1 Ceiling Temperature2:
Ordinary 135°F (57 °C) 100 °F (38 °C) Orange
Ordinary 155°F (68 °C) 100 °F (38 °C) Red
Intermediate 175°F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200°F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion-Resistant Coatings': White Polyester, Black Polyester, and Black PTFE. ENT in all temperature ratings except 135 °F (57 °C)
Footnotes
I The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-
ible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only.
Note that the spring is exposed on sprinklers with Polyester, ENT, and PTFE coatings. For ENT coated automatic sprinklers, the waterway is coated.
Form No. F_052114 17.10.05 Rev 17.1
Page 3 of 4
® MICROFAST® QUICK
J IF(Ir1G
l:II[ru.rriv RESPONSE UPRIGHT
SPRINKLER VK300 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
AprovaI Chart I (UL) --Temperature KEY
Microfast5 Quick Response Finish
All 4- Escutcheon (it appllcabte)I Upright Sprinkler VK300
Maximum 175 PSI (12 bar) WWP
Base Part Thread Size Nominal K-Factor Overall Length Listings and Approvals3 SIN Number' NPT I BSP U.S. metri0 Inches mm cULus VdS LPCB I NYC8 (E
12978 VK300 1/2" I 15 mm 5.6 I 80.6 2-3/16 56 Al, B2 -- -- 1See footnote .I --
I
'r.ittProduct Below - Limited Availability Viking Office)
066618 1 VK300 1/2" I 15 mm 1 5.6 I 80.6 1 2-3/16 56 1 Al, 132 1 -- -- ISee footnote 7.11 --
Approved Temperature Ratings Approved Finishes A- 135°F (57 °C), 155 °F (68 °C), 175°F (79 °C), 200°F (93 °C), and
286 °F(141°C) 1 - Brass, Chrome, White Polyester°'6, and Black Polyester-1.6
B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) 2 - ENT6
Footnotes
Base part number is shown. For complete part number, refer to Viking's current price schedule.
2Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
'This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
Listed by Underwriters Laboratories Inc. for us in the U.S. and Canada
° Other colors are available on request with the same Listings and Approvals as the standard colors.
cULus Listed as corrosion resistant.
Meets New York City requirements, effective July 1, 2008
8Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA and City of New York Department of Buildings, MEA 89-92-E, Vol. 16.
DESIGN CRITERIA - UL
(Also refer to Approval Chart 1 above.)
cULus Listing Requirements:
The Viking Microfast® Quick Response Upright Sprinkler VK300 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the
latest edition of NFPA 13 for standard spray sprinklers.
Designed for use in Light and Ordinary Hazard occupancies.
The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form
No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in
accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Form No. F_052114 17.10.05 Rev 17.1
Page 4 of 4
MICROFASTO QUICK tJ II(IFn1G® - RESPONSE UPRIGHT
SPRINKLER VK300 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
-
--
- Approval Chart 2(FM) I Temperature KEY I
Microfase Quick Response Finish I
Al X 4— Escutcheon Upright Sprinkler VK300
Maximum 175 PSI (12bar) WWP
Base Part Thread Size Nominal K-Factor Overall Length FM Approvals'
Number' SIN (Refer also to Design Criteria below.) NPT I BSP U.S. F metric2 Inches mm
12978 VK300 1/2" 1 15 mm 5.6 80.6 2-3/16 56 Al, B2
INOTICE Product Below Li mited ?Availability 1TNlLocal !I1!fl
06661B VK300 1/2" 1 15 mm 5.6 80.6 2-3/16 56 Al, 82
Approved Temperature Ratings Approved Finishes
A - 135°F (57 °C), 155°F (68 °C), 175°F (79 °C), 200 °F (93 °C), and 286°F (141°C) - Brass, Chrome, White Polyesters, and Black
B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) Polyester5
2 - ENT6
Footnotes
1 Base part number is shown. For complete part number, refer to Viking's current price schedule.
2Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3This table shows the FM Approvals available at the time of printing. Check with the manufacturer for any additional approvals.
Other colors are available on request with the same Approvals as the standard colors.
6 FM approved as corrosion resistant.
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
FM Aønroval Requirements:
The MicrofastO Quick Response Upright Sprinkler VK300 is FM Approved as a quick response Non-Storage upright sprinkler as indicated in the FM
Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic
design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form
No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in
accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Form No. F_052114 17.10.05 Rev 17.1 Replaces Form No. F_052114 Rev 15.2
(Replaced wrench 10896W/B with 21475M/B)