HomeMy WebLinkAboutPD 13-03; CANNON SUBSTATION MODIFICATION; FINAL SOILS REPORT; 2015-02-26 FINAL REPORT AS-BUILT GEOTECHNICAL REPORT CANNON SUBSTATION MODIFICATION SAN DIEGO GAS AND ELECTRIC CARLSBD, CALIFORNIA Prepared for Mr. Edwin Reese San Diego Gas & Electric Company 8316 Century Park Court, CP-52G San Diego, California 92123 URS Project No. 27661308.50000 February 26, 2015 4225 Executive Square, Suite 1600 La Jolla, CA 92037 858.812.9292 Fax: 858.812.9293 URS URS February 26, 2015 Mr. Edwin Reese San Diego Gas & Electric Company 83 16 Century Park Court, CP-52G San Diego, California 92123 Subject: Dear Mr. Reese: As-Built Geotechnical Report Cannon Substation Modification San Diego, California 92103 URS Project No. 27661308. 10000 URS Corporation Americas (URS) has prepared this As-Built Geotechnical Report summarizing the findings and conclusions from the geotechnical services we provided during construction of the Cannon Substation Modification. The primary purpose of this report is to provide a professional opinion that the geotechnical engineering aspects of the project have been constructed according to the intent of the design specified in the geotechnical report and the project plans and specifications. We appreciate the opportunity to be a part of this project. If you have any questions, please contact us at (858) 812-9292. Sincerely, URS CORPORATION ~~ Kelly Giesing, G.E. 27 Senior Project Geotechnic KCG\MEH:kl URS Corporation 4225 Executive Square, Suite 1600 La Jolla, CA 92037 Tel: 858.812.9292 Fax: 858.812.9293 Michael E. Hatch, C.E.G. 1925 Principal Engineering Geologist \ls082nas031wpdata\27661308\ 10000-b-r docx TABLE OF CONTENTS \\s082nas03\wpdata\27661308\10000-b-r.docx i Section 1 Introduction ...................................................................................................... 1-1  1.1 Project Description ................................................................................................ 1-1  1.2 Background ............................................................................................................ 1-1  1.3 Scope of Services ................................................................................................... 1-1  Section 2 Observation and Testing ................................................................................. 2-1  2.1 Geotechnical Observation and Testing .................................................................. 2-1  2.1.1 Foundation Excavation Observation ......................................................... 2-1  2.1.2 Earthwork and Paving Observation and Testing ....................................... 2-1  2.2 Geotechnical Laboratory Testing........................................................................... 2-1  Section 3 Conclusions ...................................................................................................... 3-1  Section 4 Limitations ........................................................................................................ 4-1  URS List of Figures and Appendices \\s082nas03\wpdata\27661308\10000-b-r.docx ii Figures Figure 1 Vicinity Map Figure 2 Site Plan Appendices Appendix A Field Compaction Test Results Appendix B Laboratory Test Reports URS SECTIONONE Introduction \\s082nas03\wpdata\27661308\10000-b-r.docx 1-1 SECTION 1 INTRODUCTION URS Corporation Americas (URS) has prepared this final As-Built Geotechnical Report to present the findings and conclusions from the geotechnical services we provided during construction of the Cannon Substation Modification. The site is located immediately east of the existing SDG&E Encina Power Plant and west of Interstate 5 (I-5) as shown on Figure 1. The primary purpose of this report is to provide a professional opinion that the geotechnical engineering aspects of the project have been constructed according to the intent of the design specified in the geotechnical report and the project plans and specifications. 1.1 PROJECT DESCRIPTION The substation site is shown on Figure 2. The modified substation includes structures such as bus supports, disconnect switch stands, circuit breakers, transformers, metal enclosed switchgear, a masonry control house and “A” Frame or “H” Frame deadend structures. Foundations for such equipment and structures are primarily shallow continuous footings or pads. The “A” Frame and “H” Frame deadend structures are supported on drilled pier foundations. The project was constructed in two phases to maintain functionality of the substation during construction. The majority of the improvements were constructed during Phase 1. The Phase 1 and 2 areas are shown on Figure 2. 1.2 BACKGROUND URS completed the geotechnical investigation for the project and prepared a report titled, “Geotechnical Investigation, Cannon Substation Modification, Carlsbad, California, URS Project No. 276661308.50000” and dated July 18, 2013. URS also reviewed following additional reports:  “Preliminary Geotechnical Investigation, Proposed Cannon Substation, Carlsbad, California, prepared by Leighton and Associates, dated July 16, 1982.  “Report on Compacted Filled Ground, Cannon Substation, East Side of Railway and North of Cannon Road, Carlsbad, California, prepared by Benton Engineering, Inc., dated September 14, 1982. The grading plan approved by the City of Carlsbad Engineering Department is titled Cannon Substation Modification (Drawing No. 478-6A), revised date October 8, 2013. Foundation drawings were released in various stages, with the latest Foundation Layout drawing (CAN-S-661) dated April 5, 2014. 1.3 SCOPE OF SERVICES URS provided geotechnical observation and testing services during construction to evaluate the quality and compliance of the contractor’s work relative to requirements specified in the geotechnical report and URS SECTIONONE Introduction \\s082nas03\wpdata\27661308\10000-b-r.docx 1-2 the geotechnical aspects of the plans and specifications. For this project, our scope of services consisted of:  Performing laboratory testing of on-site and import soils to evaluate the physical characteristics and the relationship between dry unit weight and optimum moisture content (referred to as “compaction curves”);  Observing and performing field density tests during general site grading;  Observing and testing soil placed to backfill local excavations, foundation removals, around new foundations, trenches, etc.;  Observing and testing the Class 2 Base and Asphalt placement and compaction within roadways;  Observing the bottom of footing and pad excavations;  Observing drilled shaft excavations;  Consulting regarding geotechnical aspects of the construction; and  Preparing this as-graded geotechnical report. URS did not supervise, direct, or lay out the work performed by the contractor. Over the course of the project, both AM Ortega and Suffolk Construction Company performed grading, trenching, roadway construction, and foundation excavation. URS SECTIONTWO Observation and Testing \\s082nas03\wpdata\27661308\10000-b-r.docx 2-1 SECTION 2 OBSERVATION AND TESTING 2.1 GEOTECHNICAL OBSERVATION AND TESTING URS provided observation and field density tests during foundation excavation, earthwork and paving. Our field representatives prepared daily field reports; copies of these reports are contained in our project files. These daily field reports contain summaries of our observations and compaction testing. 2.1.1 Foundation Excavation Observation A representative from our firm intermittently observed excavations for shallow foundations from October 1, 2013 through October 28, 2014, as footing bottoms and pads were exposed. Drilled shaft excavations were observed between December 19, 2013 and October 2, 2014. At the design elevations, the shallow foundations were founded in competent native material. Drilled shafts were observed to be excavated to adequate dimensions per project plans, and excavation bottoms were cleaned of loose material. 2.1.2 Earthwork and Paving Observation and Testing Earthwork consisted of mass grading including overexcavation and recompaction of existing soil, utility trench backfill, and localized backfill. A cap of Class 2 Aggregate Base (AB) was placed in and around the substation. Substation roads and the main access road were paved with Asphalt Concrete (AC). A URS technician observed the earthwork and road paving on an intermittent basis between September 12, 2013 and January 6, 2015. Field density tests were performed in accordance with the latest version of ASTM Test Method D6938 (In-Place Density and Water Content of Soil and Soil-Aggregate at Shallow Depths by Nuclear Methods). The field compaction test results are presented in Appendix A. It is noted that a small area of subgrade material along the northwest fence line of the Phase 2 area probed soft following site grading. The owner was made aware of this observation and the soft material was left in place as non-structural fill. Field densities of the asphalt were evaluated using a combination of maximum density estimates from Vulcan Materials Company and laboratory test results (See Section 2.2). While some asphalt density tests resulted in calculated compactions slightly below the specified requirement of 95 percent, the contractor’s placement and compaction methodology was observed to be appropriate and the asphalt compaction is considered adequate. 2.2 GEOTECHNICAL LABORATORY TESTING Laboratory compaction tests were completed on representative samples of the on-site and imported soils (sample Nos. 1, 2, 3, 5 and 6) to evaluate the optimum dry unit weight and moisture content relationships (referred to as compaction curves) in accordance with the latest version of ASTM Test Method D1557. Laboratory compaction curve No. 6 was performed for an on-site stockpile of recycled material consisting of aggregated base and crushed asphalt. Additional laboratory testing (referred to as sample #4) was URS SECTIONTWO Observation and Testing \\s082nas03\wpdata\27661308\10000-b-r.docx 2-2 performed on this material; the additional testing consisted of particle size analysis, sand equivalent, R- Value and durability tests performed in accordance with the latest version of ASTM Test Method D422 and California Test Methods (CTM) 229 and 301. This data was used to form a basis for evaluating the suitability of the material for reuse as Class 2 Aggregate Base. The recycled material was ultimately used as aggregate base below the paved portions of the project. Graphical laboratory test reports are presented in Appendix B. URS SECTIONTHREE Conclusions \\s082nas03\wpdata\27661308\10000-b-r.docx 3-1 SECTION 3 CONCLUSIONS It is our professional opinion that the geotechnical engineering aspects of the project observed by URS are in compliance with the recommendations contained in the approved geotechnical report, and the referenced project plans and specifications. We provide the following specific conclusions:  The geotechnical engineering aspects of the grading and foundation excavations are in compliance with the approved geotechnical report and geotechnical aspects of the project plans.  Shallow and deep foundations bottoms were observed to be in suitable bearing strata and were satisfactorily cleaned of loose material. The excavations were measured to have at least the minimum dimensions required by the project plans and the minimum embedment into bearing materials.  The results of our field testing performed indicate the placement and compaction of fill and subgrade achieved at least 90 percent relative compaction (95 percent where required, except where noted in Section 2.1.2), as determined in accordance with the latest version of ASTM D1557 at the test locations. URS SECTIONFOUR Limitations \\s082nas03\wpdata\27661308\10000-b-r.docx 4-1 SECTION 4 LIMITATIONS The conclusions and opinions drawn from the test results and site observations apply only to the improvements described in this report. We accept no responsibility for any subsequent changes made by others, by uncontrolled action of water, or by failure of others to properly repair damages by uncontrolled action of water. The reported tests represent the relative compaction and water content at the locations tested. The observations of construction and field density testing procedures used followed normally accepted procedures, which are inexact. Variations in relative compaction should be expected laterally and vertically. Professional judgments represented in this report are based partly on our evaluation of the technical information gathered, and partly on our general experience in the geotechnical field. Our monitoring does not imply a guarantee or warranty of the contractor’s work. URS warrants that our services were performed with the usual thoroughness and competence of the engineering profession. No other warranty or representation, expressed or implied, is included or intended in this report. URS Figures \\s082nas03\wpdata\27661308\10000-b-r.docx URS SITECamp Pendleton South Oceahside • Buccaneer Park SaJl Luis Rey Bvena Vista laq«)ll ® Carlsbad Mir.;iCosta <' ~ ~ "b-t 0. -------------------------REFERENCE: Google Maps, 2013 URS X:\27661308\Cannon Substation_Vicinity Map.dwg Feb 11, 2015 -2:13pm Carlsbad Osborne Sl Couhtry Cluh Vista Vista r. OceaJl Hills Buena Country Club j; Vjsta Park ... VICINITY MAP Lawrenc Welk Res~ Golf Cours • Walnul Grove Pa [ 1-Twin Oaks ~ Golf Course l1en-9q San Mar,cos @ p CANNON SUBSTATION MODIFICATION SAN DIEGO GAS & ELECTRIC, CARLSBAD, CA NOT TO SCALE CHECKED BY: KM FIG. NO: e---P-M-: _M_E_H ~-P-RO_J __ ~N-0-: -27_6_6-13_0_8_.1_0_00_0_____, 1 DATE: 02-09-15 • I " I / 0 c_?;;::;o 0 .. - -....;a.,"".'.,-.· .---"----_-: _::;,.=.:--=:-::::----~-~~ --( ___ i_""l~ I ,---FINAL SUBSTATION LIMITS --.... .. \ •. .) ·---,.....,, ___ . ',·, ..... '• . .....,....., ..... , ,, ,, \\ ,, ' I I I { ' 0 J -i ~ .. ~~· -~: .·. -: ··_, _ ........ ,____ .--' • • •• > Y, Reference: Base map from "Cannon Substation Modification", Drawing No. 4 78-6A, revision dated 6/5/14. J:\27661308 SDG&E -Connon Substation ExJ\014 WORK IN PROGRESS\As groded\Connon Substation Modificotion.dwg Feb 26, 2015 -3:45pm 4• ASPHALT CONCRETE-~l e• Cl.ASS U BASE --12 • REMOVE ANO RECOMPACT O 95X REI.A 1/VE COMPACTION 6" SCARIFY ANO RECOMPACT O 95K REI.A 1/VE COMPACTION ---''--IA\ TYPICAL SECTION: ACCESS ROADWAY ~ NO SCALE I I I I I I I 12• Cl.ASS U BASE 0 95X COMPACTION I 12• REMOVE ANO RECOMPACT O 95K REI.A 1/VE CO/JPACTION 6" SCARIFY ANO RECOMPACT O 95X I REI.A TIVE COMPACTION ----''--®TYPICAL SECTION: SUBSTATION NO SCALE 6" Cl.ASS U BASE ---,,--0 95X COMPACTION ___,,__ 12• REMOVE ANO RECOMPACT O 95X REI.A 1/VE CO/JPACTION 6" SCAHfFY ANO RECOMPACT O 95X REI.AT/VE COMPACTION ---''--©TYPICAL SECTION: OUTSIDE OF SUBSTATION NO SCALE ?t1+ -----SITE PLAN CANNON SUBSTATION MODIFICATION SAN DIEGO GAS & ELECTRIC, CARLSBAD, CA UBS 30 15 0 30 60 feet ---~ SCALE: 1 "= 30' CHECKED BY: KM DATE: 02-09-15 PM: MEH PROJ. NO: 27661308.10000 FIG. NO: 2 APPENDIXA Field Compaction Test Results \\s082nas03\wpdata\27661308\10000-b-r.docx URS Job Name:Job Number:DateTest No.Retest of LocationElevation (feet) or Depth of TestField Moisture Content (% dry wt)Field Density (pcf)Lab Sample No.Lab Density (pcf)Opt. Moist. (%)Field Rock (% dry wt)Adj. Lab Dens. (pcf)Adj. Moist. Content (% dry wt)Relative Compaction (% of lab dens.)Sept. 23F1General Fill below Subgrade North of Site46 9.8 127.1 1 133.5 8.0952013F2General Fill below Subgrade North of Site46 11.0 128.0 1 133.5 8.095F3General Fill below Subgrade North of Site46 11.8 102.7 2 108.0 10.595F4General Fill below Subgrade North of Site44 11.6 102.8 2 108.0 10.595Sept. 24F5General Fill below Subgrade East of Site46 12.2 103.0 2 108.0 10.5952013F6Mixed Soils Northeast Corner46 10.6 130.4 1 133.5 8.097F7Mixed Soils Northeast Corner46 10.8 128.4 1 133.5 8.096F8Mixed Soils Northwest Corner47 9.8 127.8 1 133.5 8.095Sept. 27F9Mixed Soils Northwest Corner47 13.4 103.1 2 108.0 10.5952013F10Mixed Soils Northwest Corner46 12.8 102.5 2 108.0 10.595F11Mixed Soils Northwest Corner45 12.8 102.8 2 108.0 10.595Sept. 30F12Mixed Soils Northwest Corner45 10.0 127.8 1 133.5 8.0952013F13Groundwire Southwest48 10.8 129.4 1 133.5 8.096F14Groundwire Northeast48 12.4 102.8 2 108.0 10.595F15Groundwire Northeast48 11.0 104.1 2 108.0 10.596Oct. 2F16Groundwire Northeast47 10.4 124.1 3 129.5 8.5952013F17Groundwire Northeast48 9.8 123.8 3 129.5 8.595F18Groundwire Northeast46 8.6 123.4 3 129.5 8.595F19Groundwire Northeast46 8.6 128.1 3 129.5 8.598Dec. 10F20PT Pad48 10.2 138.0 5 142.0 7.0972013F21BS Pad48 10.1 138.0 5 142.0 7.097F22BS Pad48 9.8 138.0 5 142.0 7.097Dec. 12F23BS Pad48 11.4 123.0 3 129.5 8.5952013F24BS Pad48 11.8 123.8 3 129.5 8.595F25BS Pad48 8.8 138.8 5 142.0 7.097COMPACTION TEST - FIELD RESULTSCannon Substation Modification27661308.10000Dates Covered: Type of Test FillSeptember 23, 2013 through September 10, 2014URSPage 1 of 2W:\CTR\27661308\10000-b-ctr.xlsx\Fill\2/26/2015\SDG Job Name:Job Number:DateTest No.Retest of LocationElevation (feet) or Depth of TestField Moisture Content (% dry wt)Field Density (pcf)Lab Sample No.Lab Density (pcf)Opt. Moist. (%)Field Rock (% dry wt)Adj. Lab Dens. (pcf)Adj. Moist. Content (% dry wt)Relative Compaction (% of lab dens.)COMPACTION TEST - FIELD RESULTSCannon Substation Modification27661308.10000Dates Covered: Type of Test FillSeptember 23, 2013 through September 10, 2014Dec. 20F26Groundwire Trenches Northwest48 8.8 134.8 5 142.0 7.0952013F27230kV Switch Pad West Groundwire48 9.2 135.2 5 142.0 7.095F28230kV Bus Pad Groundwire West48 9.8 135.8 5 142.0 7.095F29230kV Cable Stands TS Cable Risers48 8.8 135.0 5 142.0 7.095F30BS Pad Groundwire West End48 9.4 135.0 5 142.0 7.095Sep. 102014F31Northwest of Yard - Southeast Corner within Temporary FencingAB-3.5" 8.6 120.5 1 133.5 8.0 90F32Northwest of Yard - Middle/South Section within Temporary FencingAB -3 7.9 113.8 1 133.5 8.085F33 F32Northwest of Yard - Middle/South Section within Temporary FencingAB -3 10.7 126.8 1 133.5 8.0 95F34Northwest of Yard - Southwest Corner within Temporary FencingAB -3 7.9 124.7 1 133.5 8.093URSPage 2 of 2W:\CTR\27661308\10000-b-ctr.xlsx\Fill\2/26/2015\SDG Job Name:Job Number:DateTest No.Retest of LocationElevation (feet) or Depth of Test Field Moisture Content (% dry wt)Field Density (pcf)Lab Sample No.Lab Density (pcf)Opt. Moist. (%)Field Rock (% dry wt)Adj. Lab Dens. (pcf)Adj. Moist. Content (% dry wt)Relative Compaction (% of lab dens.)Sep. 12SG1South of Existing YardSG 8.0 128.1 1 133.5 8.0952014SG2South of Existing YardSG 8.0 126.4 1 133.5 8.095SG3South of Existing YardSG 8.0 126.4 1 133.5 8.095SG4North of Existing YardSG 8.2 128.1 1 133.5 8.095SG5North of Existing YardSG 9.8 128.1 1 133.5 8.096SG6North of Existing YardSG 9.4 126.4 1 133.5 8.095SG7North of Existing YardSG 9.8 127.1 1 133.5 8.095SG8North of Existing YardSG 10.0 128.1 1 133.5 8.095SG9Access RoadSG 9.2 126.8 1 133.5 8.095SG10South End of Access RoadSG 8.8 128.2 1 133.5 8.096SG11South of Existing YardSG 10.1 127.1 1 133.5 8.095SG12North on Access RoadSG 10.2 126.8 1 133.5 8.095SG13South on Access Road EntranceSG 11.2 126.4 1 133.5 8.095Dec 8SG13Access Road EntranceSG 5.8 127.7 3 129.5 8.5982014SG14Access Road EntranceSG 5.4 123.0 3 129.5 8.595SG15Access Road EntranceSG 5.7 123.0 3 129.5 8.595SG16Access Road EntranceSG 6.2 125.2 3 129.5 8.596SG17Access Road EntranceSG 6.5 123.2 3 129.5 8.595Dec 9SG18Access Road EntranceSG 4.7 124.0 3 129.5 8.5952014COMPACTION TEST - FIELD RESULTSCannon Substation ModificationDates Covered: September 12, 2014 through December 9, 201427661308.10000Type of Test SubgradeURSPage 1 of 1W:\CTR\27661308\10000-b-ctr.xlsx\Subgrade\2/26/2015\SDG Job Name:Job Number:DateTest No.Retest of LocationElevation (feet) or Depth of TestField Moisture Content (% dry wt)Field Density (pcf)Lab Sample No.Lab Density (pcf)Opt. Moist. (%)Field Rock (% dry wt)Adj. Lab Dens. (pcf)Adj. Moist. Content (% dry wt)Relative Compaction (% of lab dens.)Dec. 6WBF1West Wall to Control Shelter48 7.0 136.8 5 142.0 7.0962013WBF2West Wall to Control Shelter48 7.2 138.4 5 142.0 7.097COMPACTION TEST - FIELD RESULTSCannon Substation ModificationDates Covered: December 6, 201327661308.10000Type of Test Wall BackfillURSPage 1 of 1W:\CTR\27661308\10000-b-ctr.xlsx\Wallbackfill-Backfill\2/26/2015\SDG Job Name:Job Number:DateTest No.Retest of LocationElevation or Depth of Test (feet)Field Moisture Content (% dry wt)Field Density (pcf)Lab Sample No.Lab Density (pcf)Opt. Moist. (%)Field Rock (% dry wt)Adj. Lab Dens. (pcf)Adj. Moist. Content (% dry wt)Relative Compaction (% of lab dens.)Oct 3AB1Southwest of SiteAB 9.8 135.6 5 142.0 6.0952013AB2Northeast of SiteAB 10.0 136.1 5 142.0 6.095AB3Northeast of SiteAB 10.4 135.8 5 142.0 6.096Oct 4AB4South of SiteAB 10.1 136.1 5 142.0 6.0962013AB5East of SiteAB 9.8 137.4 5 142.0 6.096AB6West of SiteAB 8.1 136.8 5 142.0 6.096Jun. 25AB7Northeast of yard by 138kV Bank 43AB6.0 135.2 5 142.0 6.0 952014AB8Northeast of yard by 138kV Bank 43AB 6.0 135.6 5 142.0 6.095AB9Northeast of yard by 138kV Bank 43AB 5.8 136.2 5 142.0 6.096ABJun. 27AB10Bank 43 on Roadway Northeast QuadrantAB 7.2 135.0 5 142.0 6.0952014AB11Northeast by East Entrance to YardAB 6.8 135.0 5 142.0 6.095ABJun. 28AB12Southeast North of Southeast Entrance to YardAB6.0 135.8 5 142.0 6.0 952014AB13Southeast on Roadway in YardAB 5.8 135.2 5 142.0 6.096AB14Southeast on Roadway in YardAB 6.6 136.4 5 142.0 6.096AB15Southeast on Roadway in YardAB 5.8 135.4 5 142.0 6.095ABJun. 30AB16Southeast Northwest Corner Control RoomAB 6.0 136.2 5 142.0 6.0962014AB17Southwest West in YardAB 5.2 136.1 5 142.0 6.096AB18Southeast Bank 41 Bank 41AB 5.8 135.0 5 142.0 6.095AB19Southwest 138 Bus Tie GCBAB 6.1 135.2 5 142.0 6.095ABJul. 1AB20Southwest Roadway AccesswayAB 5.8 135.6 5 142.0 6.0952014AB21Southeast Roadway AccesswayAB 5.7 136.1 5 142.0 6.096AB22South by Bank AAB 5.2 136.2 5 142.0 6.096COMPACTION TEST - FIELD RESULTSCannon Substation ModificationDates Covered: October 3, 2013 through January 6, 201527661308.10000Type of Test Class 2 Aggegate BaseURSPage 1 of 4W:\CTR\27661308\10000-b-ctr.xlsx\Class 2\2/26/2015\SDG Job Name:Job Number:DateTest No.Retest of LocationElevation or Depth of Test (feet)Field Moisture Content (% dry wt)Field Density (pcf)Lab Sample No.Lab Density (pcf)Opt. Moist. (%)Field Rock (% dry wt)Adj. Lab Dens. (pcf)Adj. Moist. Content (% dry wt)Relative Compaction (% of lab dens.)COMPACTION TEST - FIELD RESULTSCannon Substation ModificationDates Covered: October 3, 2013 through January 6, 201527661308.10000Type of Test Class 2 Aggegate BaseSept. 22AB23South of Existing YardAB 8.2 135.4 5 142.0 6.0952014AB24South of Existing YardAB 8.3 135.0 5 142.0 6.095AB25South of Existing YardAB 9.2 135.8 5 142.0 6.096AB26South of Existing YardAB 8.9 135.6 5 142.0 6.095AB27North of Existing YardAB 7.8 135.8 5 142.0 6.096AB28North of Existing YardAB 7.1 136.2 5 142.0 6.096Sept. 23AB29On Access EntranceAB 6.0 125.8 6 132.6 5.0952014AB30Access RoadAB 6.0 126.1 6 132.6 5.095AB31Access RoadAB 6.0 126.4 6 132.6 5.095AB32Access RoadAB 5.7 127.0 6 132.6 5.096AB33Access RoadAB 6.8 127.0 6 132.6 5.096AB34Access RoadAB 6.8 128.1 6 132.6 5.097AB35Access RoadAB 6.8 126.8 6 132.6 5.096AB36Access RoadAB 6.7 125.7 6 132.6 5.095Oct. 29AB37Pad T40AB 5.5 138.2 5 142.0 6.0972014AB38Pad T40AB 5.7 139.2 5 142.0 6.098AB39Pad SS6AB 5.2 139.3 5 142.0 6.098AB40Pad SS6AB 5.5 135.0 5 142.0 6.095Oct. 30AB41Pad CB6AB 6.0 136.5 5 142.0 6.0962014Dec. 9AB42Access Road EntranceAB 6.1 128.8 6 132.6 5.4972014AB43Access Road EntranceAB 5.4 131.7 6 132.6 5.499AB44Access Road EntranceAB 4.2 131.8 6 132.6 5.499AB45Access Road EntranceAB 6.5 126.2 6 132.6 5.495Dec. 23AB46Substation PerimeterAB -3" 2.5 133.1 5 142.0 6.0942014AB47Substation PerimeterAB -3" 2.9 143.5 5 142.0 6.0100URSPage 2 of 4W:\CTR\27661308\10000-b-ctr.xlsx\Class 2\2/26/2015\SDG Job Name:Job Number:DateTest No.Retest of LocationElevation or Depth of Test (feet)Field Moisture Content (% dry wt)Field Density (pcf)Lab Sample No.Lab Density (pcf)Opt. Moist. (%)Field Rock (% dry wt)Adj. Lab Dens. (pcf)Adj. Moist. Content (% dry wt)Relative Compaction (% of lab dens.)COMPACTION TEST - FIELD RESULTSCannon Substation ModificationDates Covered: October 3, 2013 through January 6, 201527661308.10000Type of Test Class 2 Aggegate BaseDec. 29AB48Northern Substation AreaAB 1.8 146 5 142.0 6.01002014AB49Northern Substation AreaAB 2.0 142.7 5 142.0 6.0100AB50Northern Substation AreaAB 2.2 148.6 5 142.0 6.0100AB51Northern Substation AreaAB 1.5 135.6 5 142.0 6.095AB52Northern Substation AreaAB 2.6 145.5 5 142.0 6.0100AB53Northern Interior Road SubstationAB 3.0 141.3 5 142.0 6.099AB54Northern Interior Road SubstationAB 2.9 139.7 5 142.0 6.098AB55Northern Interior Road SubstationAB 1.8 144.1 5 142.0 6.0100AB56Northern Interior Road SubstationAB 3.9 144.7 5 142.0 6.0100AB57Western Interior Road SubstationAB 2.2 136.4 5 142.0 6.096AB58Western Interior Road SubstationAB 3.9 140.5 5 142.0 6.098AB59Western Interior Road SubstationAB 1.9 141.6 5 142.0 6.099AB60Northern Interior Road SubstationAB 2.1 141.0 5 142.0 6.099AB61Northern Interior Road SubstationAB 2.2 136.1 5 142.0 6.095Dec. 30AB62West Road NorthAB 3.7 139.3 5 142.0 6.0982014AB63West Road NorthAB 3.2 139.0 5 142.0 6.097AB64West Road NorthAB 4.6 141.4 5 142.0 6.099AB65West Road NorthAB 4.8 141.1 5 142.0 6.099AB66North Road WestAB 3.5 139.9 5 142.0 6.098AB67North Road WestAB 3.6 141.3 5 142.0 6.099AB68North Road WestAB 4.3 141.3 5 142.0 6.099AB69Northwest AreaAB 3.2 135.9 5 142.0 6.095AB70Northwest AreaAB 4.1 135.0 5 142.0 6.095AB71Northwest AreaAB 3.1 138.2 5 142.0 6.097AB72Northwest AreaAB 3.7 136.5 5 142.0 6.096AB73North Center AreaAB 4.5 135.9 5 142.0 6.095AB74North Center AreaAB 4.1 134.6 5 142.0 6.094AB75North Center AreaAB 4.3 136.2 5 142.0 6.095AB76North Center AreaAB 3.8 134.8 5 142.0 6.094AB77North Center AreaAB 2.9 140.3 5 142.0 6.098AB78Center AreaAB 2.7 135.9 5 142.0 6.095AB79Center AreaAB 3.6 136.7 5 142.0 6.096AB80Center AreaAB 3.5 136.5 5 142.0 6.096URSPage 3 of 4W:\CTR\27661308\10000-b-ctr.xlsx\Class 2\2/26/2015\SDG Job Name:Job Number:DateTest No.Retest of LocationElevation or Depth of Test (feet)Field Moisture Content (% dry wt)Field Density (pcf)Lab Sample No.Lab Density (pcf)Opt. Moist. (%)Field Rock (% dry wt)Adj. Lab Dens. (pcf)Adj. Moist. Content (% dry wt)Relative Compaction (% of lab dens.)COMPACTION TEST - FIELD RESULTSCannon Substation ModificationDates Covered: October 3, 2013 through January 6, 201527661308.10000Type of Test Class 2 Aggegate BaseAB81North of Northern Fence AreaAB 3.2 138.0 5 142.0 6.097AB82North of Northern Fence AreaAB 4.1 136.7 5 142.0 6.096AB83North of Northern Fence AreaAB 4.0 136.2 5 142.0 6.095AB84North of Northern Fence AreaAB 3.3 138.5 5 142.0 6.097AB85North of Northern Fence AreaAB 3.0 139.3 5 142.0 6.098AB86Class II Base Pad Inside Sub Northwest Corner AB 3.5 143.8 5 142.0 6.0100Jan 6AB87Class II Base Pad Inside Sub Northwest Corner AB 2.7 144.9 5 142.0 6.01002015AB88Inside Substation Middle Northern PadAB 2.9 149.4 5 142.0 6.0100AB89Inside Substation Middle Northern PadAB 2.8 146.4 5 142.0 6.0100AB90Inside Substation South of Access RoadAB 2.0 143.1 5 142.0 6.0100AB91Inside Substation South of Access RoadAB 2.8 142.1 5 142.0 6.0100URSPage 4 of 4W:\CTR\27661308\10000-b-ctr.xlsx\Class 2\2/26/2015\SDG Job Name:Job Number:DateTest No.Retest of LocationElevation (feet) or Depth of TestField Moisture Content (% dry wt)Field Density (pcf) Lab Sample No.Lab Density (pcf)Opt. Moist. (%)Field Rock (% dry wt)Adj. Lab Dens. (pcf)Adj. Moist. Content (% dry wt)Relative Compaction (% of lab dens.) *Dec. 30AC1South Road WestAC -2"136.1 AC +\- 145.2942014AC2South Road WestAC -2"136.7 AC +\- 145.294AC3South Road WestAC -2"136.9 AC +\- 145.294AC4South Road CenterAC -2"137.1 AC +\- 145.294AC5South Road CenterAC -2"138.4 AC +\- 145.295AC6South Road CenterAC -2"136.5 AC +\- 145.294AC7South Road EastAC -2"136.2 AC +\- 145.294AC8South Road EastAC -2"136.8 AC +\- 145.294AC9South Road EastAC -2"137.2 AC +\- 145.294AC10East Road SouthAC -2"137.8 AC +\- 145.295AC11East Road SouthAC -2"136.4 AC +\- 145.294AC12East Road NorthAC -2"138.5 AC +\- 145.295AC13North Road EastAC -2"136.9 AC +\- 145.294AC14North Road EastAC -2"136.8 AC +\- 145.294AC15North Road EastAC -2"136.1 AC +\- 145.294AC16North Road EastAC -2"137.2 AC +\- 145.294AC17North Road CenterAC -2"137.8 AC +\- 145.295AC18North Road CenterAC -2"138.4 AC +\- 145.295AC19North Road CenterAC -2"138.5 AC +\- 145.295AC20North Road WestAC -2"136.4 AC +\- 145.294AC21North Road WestAC -2"137.8 AC +\- 145.295AC22North Road WestAC -2"138.4 AC +\- 145.295AC23West Road NorthAC -2"137.2 AC +\- 145.294AC24West Road NorthAC -2"136.7 AC +\- 145.294AC25West Road NorthAC -2"137.7 AC +\- 145.295AC26West Road CenterAC -2"136.8 AC +\- 145.294AC27West Road CenterAC -2"137.1 AC +\- 145.294AC28West Road SouthAC -2"138.4 AC +\- 145.295AC29West Road SouthAC -2"138.5 AC +\- 145.295AC30Access Gate Road EntranceAC -2"139.8 AC +\- 145.296AC31Access Gate Road EntranceAC -2"139.9 AC +\- 145.296COMPACTION TEST - FIELD RESULTSCannon Substation ModificationDates Covered: December 30, 2014 through January 6, 201527661308.10000Type of TestAsphalt ConcreteURSPage 1 of 3W:\CTR\27661308\10000-b-ctr.xlsx\AC\2/26/2015\SDG Job Name:Job Number:DateTest No.Retest of LocationElevation (feet) or Depth of TestField Moisture Content (% dry wt)Field Density (pcf) Lab Sample No.Lab Density (pcf)Opt. Moist. (%)Field Rock (% dry wt)Adj. Lab Dens. (pcf)Adj. Moist. Content (% dry wt)Relative Compaction (% of lab dens.) *COMPACTION TEST - FIELD RESULTSCannon Substation ModificationDates Covered: December 30, 2014 through January 6, 201527661308.10000Type of TestAsphalt ConcreteJan. 5AC32Top Coat Asphalt Inside Substation AC 4.2 135.5 Carroll Canyon C2 143.0 +\- 2952015AC33Top Coat Asphalt Inside Substation AC 3.8 131.5 Carroll Canyon C2 143.0 +\- 292AC34Top Coat Asphalt Inside Substation AC 4.3 128.6 Carroll Canyon C2 143.0 +\- 290AC35Top Coat Asphalt Inside Substation AC 3.6 135.0 Carroll Canyon C2 143.0 +\- 294AC36Top Coat Asphalt Inside Substation AC 3.9 134.3 Carroll Canyon C2 143.0 +\- 294AC37Top Coat Asphalt Inside Substation AC 3.7 135.7 Carroll Canyon C2 143.0 +\- 295AC38Top Coat Asphalt Inside Substation AC 4.5 135.9 Carroll Canyon C2 143.0 +\- 295AC39Top Coat Asphalt Inside Substation AC 3.9 129.4 Carroll Canyon C2 143.0 +\- 290AC40Top Coat Asphalt Inside Substation AC 4.0 132.9 Carroll Canyon C2 143.0 +\- 293AC41 AC32Top Coat Asphalt Inside Substation AC4.0 140.4Carroll Canyon C2 143.0 +\- 298AC42 AC33Top Coat Asphalt Inside Substation AC4.3 135.6Carroll Canyon C2 143.0 +\- 295AC43 AC34Top Coat Asphalt Inside Substation AC4.0 130.9Carroll Canyon C2 143.0 +\- 292AC44 AC35Top Coat Asphalt Inside Substation AC4.1 135.9Carroll Canyon C2 143.0 +\- 295AC45 AC36Top Coat Asphalt Inside Substation AC4.0 135.7Carroll Canyon C2 143.0 +\- 295AC46 AC37Top Coat Asphalt Inside Substation AC4.4 139.4Carroll Canyon C2 143.0 +\- 297AC47 AC39Top Coat Asphalt Inside Substation AC4.0 131.2Carroll Canyon C2 143.0 +\- 292AC48 AC40Top Coat Asphalt Inside Substation AC4.2 132.0Carroll Canyon C2 143.0 +\- 292AC49Top Coat Asphalt Inside Substation AC3.8 136.3Carroll Canyon C2 143.0 +\- 295AC50Top Coat Asphalt Inside Substation AC4.1 134.6Carroll Canyon C2 143.0 +\- 294AC51Top Coat Asphalt Inside Substation AC4.3 134.6Carroll Canyon C2 143.0 +\- 294AC52Top Coat Asphalt Inside Substation AC4.1 136.0Carroll Canyon C2 143.0 +\- 295AC53Top Coat Asphalt Inside Substation AC4.0 135.7Carroll Canyon C2 143.0 +\- 295AC54Top Coat Asphalt Inside Substation AC3.8 134.4Carroll Canyon C2 143.0 +\- 294AC55Top Coat Asphalt Inside Substation AC4.1 135.5Carroll Canyon C2 143.0 +\- 295AC56Top Coat Asphalt Inside Substation AC4.1 137.5Carroll Canyon C2143.0 +\- 296AC57Top Coat Asphalt Inside Substation AC3.9 133.0Carroll Canyon C2 143.0 +\- 293URSPage 2 of 3W:\CTR\27661308\10000-b-ctr.xlsx\AC\2/26/2015\SDG Job Name:Job Number:DateTest No.Retest of LocationElevation (feet) or Depth of TestField Moisture Content (% dry wt)Field Density (pcf) Lab Sample No.Lab Density (pcf)Opt. Moist. (%)Field Rock (% dry wt)Adj. Lab Dens. (pcf)Adj. Moist. Content (% dry wt)Relative Compaction (% of lab dens.) *COMPACTION TEST - FIELD RESULTSCannon Substation ModificationDates Covered: December 30, 2014 through January 6, 201527661308.10000Type of TestAsphalt ConcreteAC58Top Coat Outside SubstationAC4.2 134.5Carroll Canyon C2 143.0 +\- 294AC59Top Coat Outside SubstationAC4.3 136.8Carroll Canyon C2 143.0 +\- 296AC60Top Coat Outside SubstationAC4.5 133.0Carroll Canyon C2 143.0 +\- 293AC61Top Coat Outside SubstationAC4.4 132.4Carroll Canyon C2 143.0 +\- 293AC62Top Coat Outside SubstationAC4.4 129.9Carroll Canyon C2 143.0 +\- 291Jan. 6AC63Top Coat Outside SubstationAC4.6 136.6Carroll Canyon C2 143.0 +\- 2962015AC64Top Coat Outside SubstationAC4.1 134.7Carroll Canyon C2 143.0 +\- 294AC65Top Coat Outside SubstationAC4.4 131.6Carroll Canyon C2 143.0 +\- 292AC66Top Coat Outside SubstationAC5.0 132.1Carroll Canyon C2 143.0 +\- 292AC67Top Coat Outside SubstationAC5.1 132.7Carroll Canyon C2 143.0 +\- 293AC68Top Coat Outside SubstationAC4.0 131.2Carroll Canyon C2 143.0 +\- 292Note: 1. Where test elevation is not indicated:AB = Top of Class 2 Aggregate Base layerSG = Top of Soil subgrate below Class 2 Aggregate Base layerAC = Top of asphalt concrete layer2. See report text for discussion of asphalt compaction acceptance criteria.URSPage 3 of 3W:\CTR\27661308\10000-b-ctr.xlsx\AC\2/26/2015\SDG APPENDIXB Laboratory Test Reports \\s082nas03\wpdata\27661308\10000-b-r.docx URS SOUTHERN CALIFORNIA SOIL AND TESTING, INC. 6280 RIVERDALE STREET, P. O. BOX 600627, SAN DIEGO, CA 92160 (619) 280-4321 Job Name:Job No.: Date:Street: CAL-TEST 301 Sample #:Station: ASTM D 2844 Source:By:DRB Description: A B C D 10/3/2013 10/3/2013 10/3/2013 PSI 350 350 350 %0.5 0.5 0.5 GRAMS 1100 1080 1100 ML 63 68 65 %5.8 6.3 5.9 %6.3 6.8 6.4 GRAMS 3200 3181 3216 GRAMS 1153 1137 1155 IN 2.5 2.45 2.49 PCF 131.5 131.7 132.1 PSI 660 130 310 PSF 39 4 22 PSI 10 11 10 PSI 18 20 19 Turns 6.75 7.05 6.85 75 71 73 FT 0.36 0.42 0.39 FT 0.3 0.03 0.17 0009 0001 0005 0 0 0 75 71 73 0.35 0.35 0.35 4.5 4.5 4.5 Reviewed By:10/4/13 Darren Hicks Date Laboratory Manager Net Weight of Briquette Displacement Test Specimen Moisture At Compaction Water Added Water Added Soil Wt. Added Initial Moisture Compactor Air Pressure Date Tested Exudation Pressure R' Value Modifier 73 76 73R-Value at Equivalent Gravel Equivalent R-Value by Exudation Pressure Corrected R-Value Traffic Index R-Value by Expansion Pressure G-Force #13600 1312123 10/03/13 Expansion Dial Reading PH at 2000 Pounds PH at 1000 Pounds Expansion Thickness Stabilometer Thickness R' Value Expansion Pressure Briquette Height Lab #9607, Sample #4 Density Weight of Briquette & Tare SOIL 8, TESTING. lHC. 0.42 0.39 0.36 Job Name: SOUTHERN CALIFORNIA By:DRB Date: SOIL AND TESTING, INC.Job No.:1312123 Sample No.: Gravel Equ:0.35 Plate No.: G-Force #13600 10/3/2013 Lab #9607, Sample #4 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2 2.3 2.4 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 3 3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 4 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 5 COVER THICKNESS BY STABILOMETER-FEET COVER THICKNESS BY EXPANSION PRESSURE-FEET EXPANSION PRESSURE CHART 0 1.0 0.8 0.6 0.42 1.2 1.4 1.6 1.8 2.0 0.2 2.2 2.4 2.6 2.8 3.0 3.2 3.4 3.6 3.8 4.0 4.2 4.4 4.6 4.8 5.0 I I I I I I I I I I I I I I I I I I I .. I •N y I I I SOIL & TESTING, INC. R-value 75 73 71 Job Name: SOUTHERN CALIFORNIA By:DRB Date: SOIL AND TESTING, INC.Job No.:1312123 Sample No.: R-Value by Ex.:73 Plate No.: G-Force #13600 10/3/2013 Lab #9607, Sample #4 0 10 20 30 40 50 60 70 80 90 100 0 100 200 300 400 500 600 700 800 R-value Exudation Pressure (psi) R-value By Exudation Pressure - - ---- - -- --- - - --- - ----- ----------- --- - - --- - -- - - --- - - -- - - --- - - -- - ----- - -- - ---- - - - - - --- - - - - - - --- - - 11 1111 111 11 11 11 111 1111 1111 1 11 11 11 11 1 11 1111 111 1111 11111 11 11 11 11 1 I I I I I I I I I- SOIL Ir TESTING, INC. Date: Job No: Client: Address: NV 5 BEYOND ENGINEERING PHYSICAL PROPERTIES OF ASPHALTIC CONCRETE January 7, 2015 149713 URS CORPORATION 4225 Executive Square, Suite 1600, San Diego, CA 92037 Repo1t No: 3556 Engineer: Kenneth Muntz Lab No.: I 10988 Project: SDG&E Cannon Substation Location: San Diego, CA Sampled: Date: 12/30/14 By: R. Alcaraz Type of Material: ¾" AC Type III B3 PG 64-1 0 Submitted: Date: 12/30/14 By: R. Alcaraz Location Sampled: AC-1 south road center of substation SIEVE ANALYSIS ASTM Cl36 TEST STANDARDS ARE ASTM (Unless otherwise specified) Sieve % Passing Specs. Size Accumulative 1" 100 3/4" 94 1/2" 78 3/8" 66 No.4 50 8 38 16 28 30 21 50 13 100 7 200 4.6 Respectfully submitted, NVS West, Jn, 114 Kenneth Muntz NV5 West, Inc. - 7895 Convoy Court, Suite 18 San Diego, CA. 92111 -- -- -- -- -- -- -- -- -- -- -- TEST RESULT TEST STD. ASPHALT CONTENT,% D6307 or CTM382 % OF TOTAL MIX 5.50 % BY WT. OF AGGREGATE 5.82 LAB COMPACTED UNIT WT., PCF D1561 & D2726 (HVEEM) ** **Average of three samples tested 145.2 ST ABILOMETER VALUE ** Dl560 **Average of three samples tested 46 UulEan Materials Company Western Division September 18, 2014 AM Ortega PROJECT: Cannon St Substation Ph 2 Gentlepersons: This is to certify that we will furnish asphalt-paving material for the above -referenced project to comply with Standard Specification for Public Works Construction Section 203-6.5.4. (Sec 400 Type Ill & Sec 203) per the 2013 supplement to Greenbook Asphalt Concrete. Our Submittal #38341 (Carroll Canyon) Mix: Type Ill B3 & C3 The Asphalt Cement will conform to PG64-10 for Performance Grade. Typically our HVEEM for Asphalt Concrete out of our Carroll Canyon 83 146 +/-2 Carroll Canyon C2 143 +/-2 Carroll Canyon E 141 +/-2 Otay 83 150 +/-2 Otay C2 149 +/-2 Otay E 148 +/-2 SAN DIEGO GAS & ELECTRIC Review is for general conformance with design concept and contract documents. Markings or comments shall not be construed as relieving the Contractor from compliance with the project plans and specifications, nor deparl!.RS therefrom. The Contrac•or remains solely responsible for delaJls and accuracy, for confirming and correlating all quantities and dimensions, for selecting fabrication processes, for techf'liQues of assembly, and for performing the work in a safe manner. V No Exceptions Taken □ Exceptions Noted Q Amend and Resubm,t ~-~ By ______ _ Rejected • See Remarks Date .9 -2."J -1"1 LOS ANGELES REGIONAL LABORATORY 16009 FOOTHHILL BOULEVARD•IRWINDALE. CALIFORNIA 9I706•TELEPHONE 626 856 6I90•FAX 626 969 2918 0%Location: I Carroll Canyon Uulcan~C•:::J AM ORTEGA Materials Company Attn:I GREG Mix Design#:l 38341-1 IMix Design Date:J 9/18/2014 Fax #:J_ ----------------------------------Pro· ect Linel: Cannon St Substation PH 2 J Project Line2:' [ fype of Mix: S.400 TYPE III CLASS B3 ~~phalt_ Grade: PG 64 -10 L AGG Type:I A L~-=S-M-ARA~J 91-37-0029 1 % 0 % 0% 16 % 19 % 24 % 40 % FILLER RECYCLE BIN#5 BIN#4 BIN#3 BIN#2 BIN#l 18.9 LBS 0 LBS 0 LBS 303 LBS 360 LBS 455 LBS 758 LBS I Pass I Use I I Pass I Use I I Pass I Use I I Pass I Use I I Pass I Use I I Pass I Use I I Pass Use I 100.0 1.0 100.0 0.0 100.0 0.0 100.0 16.0 100.0 19.0 100.0 24.0 100.0 40.0 100.0 1.0 100.0 0.0 100.0 0.0 100.0 16.0 100.0 19.0 100.0 24.0 100.0 40.0 100.0 1.0 100.0 0.0 100.0 0.0 100.0 16.0 100.0 19.0 100.0 24.0 100.0 40.0 100.0 1.0 100.0 0.0 100.0 0.0 85.0 13.6 100.0 19.0 100.0 24.0 100.0 40.0 100.0 1.0 100.0 0.0 100.0 0.0 7.0 1.1 83.0 15.8 100.0 24.0 100.0 40.0 100.0 1.0 97.0 0.0 100.0 0.0 1.0 0.2 21.0 4.0 96.0 23.0 100.0 40.0 100.0 1.0 71.0 0.0 100.0 0.0 1.0 0.2 1.0 0.2 32.0 7.7 100.0 40.0 100.0 1.0 53.0 0.0 100.0 0.0 1.0 0.2 1.0 0.2 2.0 0.5 87.0 34.8 100.0 1.0 42.0 0.0 0.0 0.0 0.0 0.0 1.0 0.2 1.0 0.2 57.0 22.8 99.0 1.0 33.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 43.0 17.2 98.0 1.0 20.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.0 10.8 95.0 1.0 13.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 6.4 90.0 0.9 8.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 8.0 3.2 RAP AC% ~ Mix Design Notes:! KM of Combined Aggregate----1.10 SURFACE AREA: 23.5 ··~~ Laboratory Manager Combiried Operating [ Sieve Size Passing Range ~ ~E SI 0 2-1/2" 50.0)_ 100.ol I I 111-112" (37.8)j 100.ol I 100 I 100 lit" (25.0)J 97.61 liiJ. 100 113/4" (19.0)j 81.91 I 11112" (12.5)1 68.21 I 65 80 113/8" (9.5)j 49.ol I 45 60 11#4 (4.75)1 36.61 30 45 ll#8 (2.36)] 24.21 11#16 (1.18)J 18.21 15 25 11#30 (0.60)1 11.81 11#50 (0.30)1 7.41 11#100 (0.15)] 4.11 3 7 11#200 (0.075)] % Asphalt -Outside-% Asphalt -Inside-Weight Per TON Batch WT: SELTEC Percent Mass BIN#l 37.9 758 BIN#2 22.7 455 BIN#3 18.0 360 BIN#4 15.2 303 BIN#5 0.0 0 RECYCLE 0.0 0 FILLER 0.9 19 Asphalt 5.3 106 TOTAL 100.0 2,000 5.61 % + 100% AGG 5.31 % Plus 94. 71 % Aggregate 106ILBS 2000ILBS 0%Uul1an Materials Company Location: Carroll Canyon Customer: AM ORTEGA Attn: GREG Project Linet: Cannon St Substation PH 2 Project Line2: Type of Mix: S400C3 Asphalt _§rode: PG 64 -10 [ AGG Type:[ ~ I SMARA:[ 91-37-0029 1% 0% 0% FILLER RECYCLE BIN#5 0% BIN#4 13 o/o BIN#3 38 o/o BIN#2 48 o/o BIN#l 18.9 LBS O LBS O LBS O LBS 245 LBS 717 LBS 905 LBS I Pass I Use 11 Pass I Use I ~ss I Use I 1·,,;;;rvs;::-1 [PassT:us;J I Pass I Use I [Pass I Use ! 100.0 1.0 100.0 0.0 100.0 0.0 100.0 0.0 100.0 13.0 100.0 38.0 100.0 48.0 100.0 1.0 100.0 0.0 100.0 0.0 100.0 0.0 100.0 13.0 100.0 38.0 100.0 48.0 100.0 1.0 100.0 0.0 100.0 0.0 100.0 0.0 100.0 13.0 100.0 38.0 100.0 48.0 100.0 1.0 100.0 0.0 100.0 0.0 85.0 0.0 100.0 13.0 100.0 38.0 100.0 48.0 100.0 1.0 100.0 0.0 100.0 0.0 7.0 0.0 83.0 10.8 100.0 38.0 100.0 48.0 100.0 1.0 97.0 0.0 100.0 0.0 1.0 0.0 21.0 2.7 96.0 36.5 100.0 48.0 100.0 1.0 71.0 0.0 100.0 0.0 1.0 0.0 1.0 0.1 32.0 12.2 100.0 48.0 100.0 1.0 53.0 0.0 100.0 0.0 1.0 0.0 1.0 0.1 2.0 0.8 87.0 41.8 100.0 1.0 42.0 0.0 0.0 0.0 0.0 0.0 1.0 0.1 1.0 0.4 57.0 27.4 99.0 1.0 33.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 43.0 20.6 98.0 1.0 20.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 27.0 13.0 95.0 1.0 13.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 16.0 7.7 90.0 0.9 8.5 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 8.0 3.8 RAP AC% ...§.:3.!l',, Mix Design Notes: I KM of Combined Aggregate----1 . l O SURFACE AREA: 27.2 nc~ Laboratory Manager Mix Design#: I 38341-2 jMix Design Date: 9/18/2014 Fax#: Combined Operating I Sieve Size _j Passing Range ~ 0 ~ E (SI)] 2-1/2" __ (?0.0) 100.ol 111-112" (37.8)1 100.ol 111 H __ (25.0)] 100.ol 100 100113/4" (19.0~ 97.81 95 10011112" (12.5}1 -88.21 75 90 113/8" (9.5}1 61.31 50 67 11#4 _(4.75)1 43.61 35 50 11#8 (2.36}1 28.91 11#16 (1.18)1 21.61 15 30 11#30 (0.60)1 13.91 1#50 0.30 8.61 I #100 0.15) 4.71 4 I 7 11#200 (0.075}1 % Asphalt -Outside-% Asphalt -Inside-Weight Per TON Batch WT: SELTEC Percent Mass BIN#1 45.3 905 BIN#2 35.8 717 BIN#3 12.3 245 BIN#4 0.0 0 BIN#5 0.0 0 RECYCLE 0.0 0 FILLER 0.9 19 Asphalt 5.7 114 TOTAL 100.0 2,000 61 o/o + 100% AGG 5. 71 o/o Plus 94. 3 I o/o Aggregate 1141 LBS 2000ILBS