HomeMy WebLinkAboutPD 2019-0032; GOERTZEN RESIDENCE; GEOTECHNICAL RESPONSE TO THIRD PARTY 1ST REVIEW; 2019-12-19'I-• :,._
jlH, TllnEII------------------------~------
December19, 2019
P.O. Box 119E
Lakeside, Califorrtfa
. 9204(
Greg Goertzen
3466 Camino Michelle
Carlsbad, California 92009
SUBJECT: File No. 1127H6-19
SITE INSPECTION
Response to Third Party Geotechnical Review
Proposed Residential Building Site
El Fuerte Street and Acuna Court
City of Carlsbad
Dear Mr. Goertzen:
In response to the third party review by Hetherington Engineering, dated October 3, 2019.
1. The consultant should review the project grading plan and foundation plans.
We have reviewed the grading plan for Lot 84-El Fuerte Street by Pasco Laret Suiter
& Associates, dated February 15, 2017, Drawing No. 520-8A (sheets 1 through 5) and
find it confonns to the recommendations in our Site Inspection dated June 7, 2019.
We have not been provided with the structural or architectural plans.
2. The consultant should provide a geotechnical map/plot plan utilizing the latest grading
plan.
Please see Plate IV and V attached.
3. The consultant should provide a geotechnical cross section.
Please see Plate VI attached.
4. The consultant should provide a detailed description of the proposed site grading,
structures/improvements, foundation type.
The proposed grading is a cut/fill to create a 17 foot high 2: 1 fill slope to create a level
building pad for the single family structure with a slab on grade construction. There
will be a 2 to 3 foot retaining wall at the base of slope on north side of the site.
I
~T,'i~~~.,,,. r~p..,
rli ""' ~ . .., '•·..... ;; . t, ·~ .. • _ _,_:·
LA1\,Ji'.) Dt:VELOPMENT
. Ei\lGINEERING.
(619) 443-006(
' .
Greg Goertz File No. 1127H6-19 December 19, 2019
5. The consultant should discuss regional geologic conditions, geologic structure and
faulting.
The site is underlain with Mesozoic volcanic and metavolcanics structure. No known
faulting in located in the area of the site ..
6. The consultant should provide a statement regarding the impact of the proposed
grading and construction on adjacent properties and improvements.
The proposed grading and construction should have no impact on adjacent properties
and improvements.
7. The consultant should provide a description of approved foundation embedment
materials.
The foundation for the proposed structures should be founded a minimum of 18
inches into the fill soils compacted to 90 percent compaction. The proposed
structures and other improvements should be located at least 7 from the top of
compacted fill slopes. If proposed foundations and footings are located closer than
7 feet inside the top of compacted fill slopes, then must be deepened so that the face
of footing at the elevation of the bottom is at least 7 feet back from the face of slope
at that level.
8. The consultant should address expected total and differential settlement due to
foundation loads.
The estimated maximum values for the Total Settlement is 1 inch and for the
Differential Settlement is 1/2 inch.
9. The consultant should provide hardscape recommendations (thickness, reinforcement,
joints etc.).
Recommendation of Portland Cement Concrete Pavement Section: (For
Mechanical Equipment Utility Pad, Loading Slab)
• Design Daily ESALs : 18
• Concrete Thickness = 6 inches with #4 deformed rebar @ 12" on center
(O.C.) each way (E.W.) or 4.5 inches of asphalt.
• Type II Aggregate Base = 6 inches (Compacted to 95 % of relative
compaction)
2
'.
' .
Greg Goertz File No. 1127H6-19 December 19, 2019
• Concrete tnix design: Type V Cement, Water/Cement Ratio, Max W/C, =
0.45, 28 days compressive strength = 4500 psi. Special Inspection not
required.
• Scarify the existing sub-base soil 12" and compacted to 95% or greater.
• Slab Contraction Joint:
Control Joint: Sawcut ¼ of slab thickness @ plus, minus 6' O.C.
Expansion joint: @ the maximum of 24' plus · and minus O. C. with 1"
diameter x 18" length smooth dowel @ 12" O.C. with 9" into each side of
joint, with one fixed one with grease or wrapped with plastic for debond and
temperature movement. Place½" expansion joint filler alone the joint.
10, The consultant should specify the sulfate exposure category (ACI 318) based on
soluble sulfate testing and provide recommendations for sulfate resistant concrete if
necessary.
Sulfate testing was not required. We can provide this testing during the grading
operation if necessary. ·
11. The consultant should provide a list of recommended observation and testing during
site grading.
Please see our previously referenced report under Recommended Grading
Specifications.
12. The consultant should provide the site seismic design category.
Please see our report, page 2, #3 for seismic category D.
13. The foundation and slab design criteria for soils should be consistent with Section
1808.6 ofthe2016 California Building Code.
The foundation and slab recommendations in our previously referenced report are
consistent with Section 1808.6 of the 2016 California Building Code for moderately
expansive soils (EI 65).
14. the consultant should provide a location map.
See Plate I.
15. The consultant should provide the test exploration logs.
See Plate II through III
3
Greg Goertz File No. 1127H6-19 December 19, 2019
16. The consultant should discuss potential geologic hazards including landslides, slope
instability, liquefaction, tsunami potential, etc.
The subject site is located approximately 7 miles from the nearest known fault (Rose
Canyon Fault) and is not within a City designated fault zone or State of California
Designated Alquist-Priolo Earthquake Fault Studies Zone. No known active faults
underlie the site. Fault movement beneath the proposed improvements is considered
to be low. During our on site visit, no visual seismic fissures were observed.
The subject site is approximately 4 miles from the Pacific Ocean and approximately
360 feet above mean sea level. According to McCulloch (1985) the potential in the
San Diego County coastal area for 100 year and 500 year tsunami waves is
approximately five and eight feet or less. This suggests that there is a low probability
of a tsunami reaching the site based on elevation above sea level.
Based on the location of the site, elevation above sea level, no ground water
encountered and the soil type it is our opinion the potential for liquefaction is
considered to be negligible. "
Reference to the geologic and Landslide Hazard Identification Map of the Rancho
Santa Fe Quadrangle Tan (1986) indicates that the property is a marginally
susceptible area. Based on the 8 percent grade, it is our professional opinion that
landslide potential is negligible.
17. The consultant should provide a statement as to the feasibility of the project. We
conclude that the proposed development of the site is feasible from a geotechnical
standpoint provided· the recommendations in this report are incorporated into the
design and construction of the project.
18. The consultant should provide a statement with respect to the stability of the slopes.
The natural slope of the property is approximately 30 feet high with an 8 percent
degree of inclination from the northeast to southwest.. This site demonstrates that
inactions of 1.5: 1 (H: V) or flatter. No visual evidence of slope disturbance was noted
at the time of our inspection of the site. Based on our experience with similar
conditions, the slope, which is comprised of dense, very old volcanic and sedimentary
rock, will demonstrate a minimum factor of safety against deep seated failures in
excess 1.5. The proposed grading with the 2:1 slopes for the proposed construction
will not significantly affect the overall stability of the slope or subject site.
4
Greg Goertz File No. 1127H6-19 December 19, 2019
19. The consultant should clarify remedial grading recommendations.
Please see the Recommended Grading Specincations in our report in addition to the
following:
The cut portion of the cut/fill transition shall be undercut and over-excavated to a
minimum of 3 feet in depth from finish grade.
There should be a minimum of 12 inches of uniformly compacted fill under the
proposed footings.
Utility trench backfill beneath structures, pavements and hardscape should be a SE 30
soil or less and compacted to a minimum of 90% relative compaction. The upper 12
inches of subgrade beneath slabs and paved areas should be compacted to al least 95%
relative compaction. Any organic or other deleterious material that may be
encountered should be removed prior to recompaction.
All graded fill slopes should be graded to a maximum of a 2: 1 gradient. Graded cut
slopes will be stable at a 1.5:1 gradient
20. The consultant should provide recommendations for temporary excavations.
There are no temporary excavations.
21. The consultant should provide recommendations for foundation slope setback.
The proposed improvements meet the foundation slope setback.
r/
l:'ur SI: I foot= 304.8 mm.
FACE OF
STRUCTURE
TbPOF
FACE OF
FOOTING
SLOPE ---------1-~,..,...,.-'----';-
--~ H
AT LEAST THE SMALLER
OF H/3 AND 40 FEET
. AT LEAST THE SMALLER OF Hl2 AND 15 FEET
FIGURE 1808.7.1
FOUNDATION CLEARANCES FROM SLOPES
22. The consultant should provide retaining wall recommendations, if necessary.
The proposed retaining wall is approximately 2 to 3 feet in height and is considered a
landscape wall.
5
Greg Goertz File No. 1127H6-19 December 19, 2019
23. The consultant should provide a list of references utilized in the preparation of the
report.
Please see reference sheet attached.
If we can be of any further assistance, please do not hesitate to contact our office. This
opportunity to be of service is sincerely appreciated.
Respectfully submitted,
Chin C. Chen, RPE C34442
CCC/mlj
6
CITY OF OCEANSIDE
PACIFIC
OCEAN
78
VICINITY MAP
PLATE I
CITY OF ENCINITAS
1127H6-19
12-30-19
CITY OF VISTA
TY OF
N MARCOS
~ NO SCALE~
P.O. Box 1195
Lakeside, CA 92040
619-443-0060
'
Greg Goertz
Plate No. II
EXPLORATION NUMBER 1
Date Logged:
Date Reported:
n th U •fi d Cl ep, m ~e
0 to 6" SM
6 to 30" SC
05/02/19
11/29/19
'fi a.ss1 1cations
Red brown,
lawn roots
Red brown,
File No. 1127H6-19 December 19, 2019
Equipment Used: Hand dug
Groundwater: Not Encountered
01 . escnpt10n S 'ID S ·1 T 01 ype
dry, loose, SILiYSANDS
(Topsoils)
dry, dense, SIL iY CLAYEY SANDS 1
with some decomposed granite (Native)
•J
30 to 48" SM Yellow tan, dry, dense, SILTY SANDS
(Native)
I
,
bottottt of excavation
Greg Goertz
Plate No. III
EXPLORATION NUMBER 2
Date Logged:
Date Reported:
05/02/19
11/29/19
D th U 'fi d Cl 'fi f ep Ill Je ~SSl 1ca lOilS
0 to 5" SM Dark brown,
lawn roots
5 to 16" SM Light brown,
with some clay
16 to 48" SM Orange brown,
with some clay
-------------·-·· --· ---· -· --· ·------
..
File No. 1127H6-19
Equipment Used:
Groundwater:
o.i escnp 10n S 'ID . f
dry, loose,
dry, firm to dense,
dry, dense,
--------------··--·------------·--::-
bottom of ex9avation
December 19, 2019
.Hand dug
Not Encountered
01 ype
SILTY SANDS
(Topso.ils)
SILTY SANDS
(Native)
SILTY SANDS
(Native)
----------------
' ' .
3'SLOPE·
I
I
I
I
I
I
I
I
I 1
I L_ _ ____ _,___ --SIDEWALK ----
EL FUERTE STREET
~ · EXPLORATION TRENCH
-=-RETAINING WALL
II._ PROPOSED TOP OF SLOPE
. . PROPOSED TOE OF SLOPE
.~ EXISTING TOPOGRAPHY
LOCATION OF
EXPLORATION TRENCHES
~1tftf!i11itltkf4~li&\U.&11!~.~~t:t{;tfttrii
1127H6-19
JRK
PLATE IV
:),/:··;;::i;~,:,·,:.'3:·:::>:,:>]:iA'ir'.~;;~::;.{,:i'.~:.1ff.ii~~·i:i:/
12-31-19
\
I
I
~ ::>
0 u
<( z ::> u <(
,..., NO SCALE,...,
P.O. Box 1195
Lakeside, CA 92040
619-443-0060
. ' . •
GE OLO GIC MAP
PLATE V
SIIJff MD.
" . 10 " "'
lWllll!W<CI -
L TESTERS LEGEND
APPROXIMATE TEST TRENCH LOCATION
APPROXIMATE LIMITS OF THE 5-ITE
1z ARTIFICIAL FILL OVER
11 27H6-1 S
NRCS-EXCHEQUER SURFACE SOILS-, ROCKY
· 5-ILT LOAM, 9-TO 30% SLOPES.
JURASSIC "AND CRETACEOUS
METAMORPHOSED AND UNMETAMORPH05-ED
VOLCANIC AND SEDIMENTARY ROCK
FORMATION LOW-GRADE METAMORPHOS-ED
ROCK CONGLOMERATE, SANDSTONE, AND
SILTSTONE, SURFACE DESCRIPTION,
" REDDIS-H-BROWN, YELLOW-BROWN, LIGHT
BROWN AND ORANGE-BROWN COARSE TO
FINE SAN-D·
"AS BUILT"
UITER
OCIATES RCO __ ""'·--OATE
.INSPECTOR DATE [7JI CITJ...2!.,~~~AD IITI .
lWllJIC Pl.INS" P0lt
GOERTZEN RESIDENCE
LOT 84 -EL FUERTE STREET
11-00JQ
e+. :::::&Ljf P11<U:cr NO. I[ -~G "o1 ~ ~.1 P02011-DO.l2 . 520--M
I
l
.~.
: .I Cf
l"V 0
:~
n ;c a.
Vl
tn
V')
m n -, --0 z
A
370
355
· GEOLOGIC SEClJON· A -A
GOERTZEN RESIDENCE
LOT -84, Et FUERTE STREET
CARLS6AD, CALlFORNIA
L•:.•· '.'::J Approximate limits of q9eumentec;tgradin9 ,an
during s-tteet improvements
. Muz Metamorphosed andunmetamo.r:phosed Vdkanic
~nd sedtmenta.ryrock formati.on, Redcbrown to Light
. btown·sandstone and rock congtomerate
BEST IMAGE ~
POSSIBLE
t ••
'
Greg Goertz File No. 1127H6-19 December 19, 2019
References
Grading Plan by Pasco Laret Suiter, Project No. PD2019-0032, Drawing No. 520-8A
Tan, S.S., 1986, Landslide Hazards in the Rancho Santa Fe Quadrangle, San Diego
County, California
Landslide Hazard Identification Map No. 6, OFR 86-15 -LA
NRCS Soil Resource Report
Geologic Map of the San Diego 30'x60' Quadrangle, California
Hart, 1994, Fault-Rupture Hazard Zones in California, Earthwork Fault Zoning Act with Index
to Earthquake Fault Zones Maps: California Division of Mines and geology, Special Publication
42,33 p.