HomeMy WebLinkAbout2800 WHIPTAIL LOOP; ; FPC2022-0029; PermitPERMIT REPORT
Fire Permit
Print Date: 03/31/2022
Job Address: 2800 WHIPTAIL LOOP, CARLSBAD, CA 92010-6751
Permit Type: FIRE-Construction Commercial Work Class:
Parcel#: Track#:
Valuation: $1,345,069.20 Lot#:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Project Title:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#:
Plan Check#:
Fire Sprinklers
{_ City of
Carlsbad
Permit No: FPC2022-0029
Status: Closed -Finaled
Applied: 02/15/2022
Issued: 03/08/2022
Finaled Close Out: 03/31/2022
Inspector:
Final Inspection:
Description: AETHERCOMM -NEW SPRINKLERS FOR RELOCATED UTILITY ROOM/PARTITIONS. REPLACE ESFR PENDENTS IN SHIPPING Rom
W/ QUICK RESPONSE SPRINKLER {37 HEADS)
FEE
FIRE NFPA 13 or 13R System 7-100 heads
Total Fees: $607.00 Total Payments To Date: $607.00
Fire Department
FPContractor:
INDUSTRIAL FIRE SPRINKLER CO INC
3845 IMPERIAL AVE
SAN DIEGO, CA 92113-1702
( 619) 266-6030
Balance Due:
AMOUNT
$607.00
$0.00
Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-4665 I 760-602-8561 f I www.carlsbadca.gov
Project:
Industrial Fire Sprinkler CO Inc
3845 Imperial Ave San Diego CA 92113
(619) 266 6030
AETHERCOMM T.I.
2800 WHIPTAIL LOOP W., STE C6
CARLSBAD CA 92010
Material Cut Sheets
Model ESFR-25
25.2 K-factor Pendent Sprinkler
Early Suppression, Fast Response
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci .com/tycofi re/
model-esfr-25_25-2K
General
Description
The TYCO Model ESFR-25 Pendent
Sprinklers are Early Suppression, Fast
Response (ESFR) sprinklers with a
nominal K-factor of 25.2. The sprinkler
assembly is shown in Figure 1. They are
suppression-mode sprinklers that are
especially advantageous as a means of
eliminating the use of in-rack sprinklers
when protecting high-piled storage.
The Model ESFR-25 Sprinklers are pri-
marily used for ceiling-only sprinkler
protection of, but not limited to, the fol-
lowing storage applications:
Page 1 of 6
• Most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
• Uncartoned (exposed) expanded
plastics in accordance with NFPA 13
and FM Global standards
• Some storage arrangements of rub-
ber tires, roll paper, flammable liq-
uids, aerosols, and automotive
components
For more specific criteria, see Table B
and the applicable design standard.
The Model ESFR-25 Pendent Sprin-
klers provide the system designer
with hydraulic and sprinkler place-
ment options not presently available to
the traditional ESFR sprinklers having
nominal K-factors of 14.0 and 16.8. In
particular, the Model ESFR-25 Sprin-
kler is designed to operate at substan-
tially lower-end head pressures, as
compared to ESFR Sprinklers having
nominal K-factors of 14.0 and 16.8.
This feature offers flexibility when
sizing system piping, as well as pos-
sibly reducing or eliminating the need
for a system fire pump.
The Model ESFR-25 Sprinklers can
eliminate the use of in-rack sprinklers
when protecting high-piled storage of
specific materials up to the following
heights:
• NFPA: 40 ft (12,2 m) with ceilings up
to 45 ft (13,7m)
• FM: 45 ft (13,7 m) with ceilings up to
50 ft (15,2 m)
For more specific criteria, see Table B
and the applicable design standard.
The Model ESFR-25 Sprinklers are
listed by Underwriters Laboratories
(UL) for specific applications with
a maximum storage height of 43 ft
(13,1 m) with a maximum ceiling height
of 48 ft (14,6 m) without the require-
ment for in-rack sprinklers. Refer to the
Specific Application Listing (UL) for the
design criteria.
lt!eJi@◄
The Model ESFR-25 Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
NOVEM BER 2021
Worldwide www.tyco-fire.com Contacts
tection Association (NFPA), in addition
to the standards of any authorities
having jurisdiction, such as FM Global.
Failure to do so may impair the perfor-
mance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
In all cases, the appropriate NFPA or
FM Global installation standard, or
other applicable standard, must be
referenced to ensure applicability and
to obtain complete installation guide-
lines. The general guidelines in this
data sheet are not intended to provide
complete installation criteria.
Sprinkler
Identification
Number (SIN}
See Table A
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
VdS Approved
NYC Approved under MEA 356-01-E
LPCB Certified (Cert. Nos. 094b and 0071
TFP312
TFP312
Page 2 of 6
Components:
1 -Frame
2 -Deflector
3 -Compression
Screw
4 -Hook
5 -Strut
6 -Link Assembly
7 -Button
8 -Sealing
Assembly
8
7
6
5
4
3
2
3-13/16"
(96,8 mm)
9/16"
(14,3 mm)
NOMINAL
MAKE-IN
WRENCH
FLATS
FIGURE 1
1" NPT
1-13/16"
(46,0 mm)
CENTERLINE
THERMAL
SENSING
ELEMENT
TEMPERATURE
RATING
2" (50,8 mm) -----l
MODEL ESFR-25 PENDENT SPRINKLER, 25.2K
EARLY SUPPRESSION, FAST RESPONSE
Finish
Natural Brass
Physical Characteristics
Frame ............................. Brass
Deflector .......................... Bronze
Compression Screw .......... Stainless Steel
Hook ............................ MONEL
Strut. ............................ MONEL
Link Assembly ................ Solder, Nickel
Button ............... Copper/Stainless Steel
Sealing Assembly .. Beryllium Nickel w/TEFLON
Additional Technical Data
See Table A
Operation
The fusible link assembly is com-
prised of two link halves that are joined
together by a thin layer of solder. When
the rated temperature is reached, the
solder melts and the two link halves
separate, activating the sprinkler and
flowing water.
Design
Criteria
The following general guidelines pro-
vided for the TYCO Model ESFR-25
Pendent Sprinklers can be used for a
quick reference.
The National Fire Protection Associa-
tion (NFPA) and FM Global (FM Approv-
als) provide installation standards that
must be used to properly design an
automatic sprinkler system utilizing
Early Suppression, Fast Response
(ESFR) Sprinklers. The guidelines pro-
vided by NFPA and FM Global may
Item Description
Sprinkler Identification Number (SIN) TY9226
K-factor, gpm/psi½ (Lpm/bar½) 25.2 gpm/psi½ (362,9 Lpm/bar½)
Temperature Rating °F (°C) 165°F (74°C)
212°F (1 oo·c)
Thread Size 1 in. NPT or ISO 7-R 1
Sprinkler Orientation Pendent
Maximum Working Pressure, psi (bar) 175 psi (12,1 bar)
TABLE A
MODEL ESFR-25 PENDENT SPRINKLER
TECHNICAL DATA
differ. Consequently, the appropri-
ate standard must be used for a given
installation.
General guidelines are not intended to
provide complete installation criteria.
In all cases, the appropriate NFPA or
FM Global installation standard must
be referenced to ensure applicabil-
ity and to obtain complete installation
guidelines. For more information, see
Table B.
Roof Construction
Unobstructed or obstructed construc-
tion, such as smooth ceiling, bar joists,
beam and girder.
Note: Where the depths of the solid
structural members, as in beams and
stem, exceed 12 in. (302 mm), install
ESFR Sprinklers in each channel
formed by the structural members.
Ceiling Slope
Maximum 2 in. rise for 12 in. run (16.7%)
Maximum Coverage Area
100 ft2 (9,3 m2)
Minimum Coverage Area
64 ft2 (5,8 m2) per
NFPA 13 / FM Global 2-0
Maximum Spacing
• 12 ft (3,7 m) for building heights up
to 30 ft (9,1 m)
• 10 ft (3,1 m) for building heights
greater than 30 ft (9,1 m)
Minimum Spacing
8 ft (2,4 m)
Minimum Clearance to Commodity
36 in. (914 mm)
NFPA
Deflector-to-Ceiling Distance
6 in. to 18 in. (152 mm to 457 mm)
Storage Type NFPA
Sprinkler Type ESFR
Response Type FR
System Type Wet
Temperature Rating °F (°C) 165°F (74°C)
212°F (100°C)
Open Frame (i.e., no solid shelves), Single, Double, Multiple-
Row, or Portable Rack Storage of Class I-IV and Group A or Refer to N FPA 13
B Plastics
Solid Pile or Palletized Storage of Class I-IV and Group A or Refer to NFPA 13 B Plastics
Idle Pallet Storage Refer to NFPA 13
Rubber Tire Storage Refer to NFPA 13
Roll Paper Storage Refer to NFPA 13 (Refer to the Standard)
Flammable/Ignitable Liquid Storage Refer to NFPA 30 (Refer to the Standard)
Aerosol Storage Refer to NFPA 308 (Refer to the Standard)
Automotive Components in Portable Racks Refer to N FPA 13 (Control mode only; refer to the Standard)
N/A -Not Applicable
TABLE B
MODEL ESFR-25 PENDENT SPRINKLER
TFP312
Page 3 of 6
FM Global
Storage
QR
Wet
165°F (74°C)
212°F (100°C)
Refer to FM Global
2-0 and 8-9
Refer to FM Global
2-0 and 8-9
Refer to FM Global
2-0, 8-9, and 8-24
Refer to FM Global
2-0 and 8-3
Refer to FM Global 8-21
Refer to FM Global 7-29
Refer to FM Global 7-31
N/A
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
FM Global
Centerline of Thermal Sensing
Element-to-Ceiling Distance
Refer to FM Global 2-0 for Storage
Sprinklers.
Specific
Application
Listing (UL}
TYCO Model ESFR-25 Pendent Sprin-
klers are listed by Underwriters Labo-
ratories (UL) for Specific Applications
with a ceiling height greater than 45
ft (13,7 m) up to and including 48 ft
(14,6 m), and a storage arrangement up
to and including 43 ft (13,1 m).
For guidelines about the TYCO Model
ESFR-25 Pendent Sprinkler Specific
Applications Listing (UL) Design Crite-
ria, see Table C.
Installation
TYCO Model ESFR-25 Early Suppres-
sion, Fast Response 25.2K Pendent
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Damage to the fusible link assembly
during installation can be avoided by
handling the sprinkler by the frame
arms only and by using the appropriate
sprinkler wrench. Do not apply pres-
sure to the fusible link assembly. Failure
to do so can lead to an unstable link
assembly and premature activation of
the sprinkler. Damaged sprinklers must
be replaced.
A leak-tight 1 in. NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 20 to 30
lb-ft (26,8 to 40,2 N·m). Higher levels
of torque can distort the sprinkler inlet
with consequent leakage or impairment
of the sprinkler.
Installing the Sprinkler
To install the sprinkler, perform the fol-
lowing steps:
Note: Install the Model ESFR-25
Pendent Sprinkler in the pendent posi-
tion as shown in Figure 2.
Step 1. With pipe thread sealant
applied, hand-tighten the sprinkler into
the sprinkler fitting. Do not apply pres-
sure to the link assembly, and handle
the sprinkler only by the frame arms.
Step 2. Wrench-tighten the sprin-
kler using only the W-Type 1 Sprinkler
Wrench as shown in Figure 2, and by
fully engaging (seating) the wrench on
the sprinkler wrench flats as shown in
Figure 1.
Step 3. After installation, inspect the
link assembly of each sprinkler for
damage. In particular, verify that the
link assembly and hook are posi-
tioned as shown in Figure 1, and that
the link assembly is not bent, creased,
or forced out of normal position in any
way. Replace damaged sprinklers.
TFP312
Page 4 of 6
Sprinkler Type
Description
Temperature Rating °F (°C)
Response Type
Sprinkler Position
System Type
Maximum Area of Coverage
Minimum Area of Coverage
Maximum Slope Ceiling
Maximum Spacing
Minimum Spacing
Deflector Distance from Walls
Deflector to Top of Storage
Deflector to Ceiling Distance
Maximum Ceiling Height
Maximum Storage Height
Storage Arrangement
Commodity
Sprinkler System Design
Obstruction Criteria
Minimum Aisle Width
Specification, UL
ESFR
165°F (74°C)
212°F (100°C)
QR
Pendent, frame arms aligned with pipe,
deflectors parallel with ceiling or roof
Wet
100 ft2 (9,3 m2)
64 ft2 (5,8 m2)
2 in. rise for 12 in. run (16.7%)
10 ft (3,1 m)
8 ft (2,4 m)
Minimum of 4 in. (100 mm) from walls but no more than 1/2 the
allowable distance permitted between sprinklers
Minimum of 36 in. (914 mm)
6 in. to 14 in. (152 mm to 356 mm)
48 ft (14,6 m)
43 ft (13,1 m)
Palletized, solid piled, open frame; single row or double row
Class I -IV, Cartoned unexpanded plastic
NFPA 13 for ESFR Sprinklers based upon 45 psi (3,1 bar) design
pressure 169 gpm (640 Lpm) with 12 sprinkler remote area
Reference NFPA 13, Chapter 8
5 ft (1,5 m)
Hose Stream allowance and Water Supply Duration 250 gpm for 60 minutes (950 Lpm for 60 minutes)
TABLEC
MODEL ESFR-25 PENDENT SPRINKLER
SPECIFIC APPLICATION LISTING (UL)
COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW
I
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
FIGURE2
W-TYPE 1
SPRINKLER WRENCH
Care and
Maintenance
TYCO Model ESFR-25 Early Suppres-
sion, Fast Response 25.2K Pendent
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. For more informa-
tion, see the Installation section.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with the following docu-
ments and standards:
• This technical data sheet
• Applicable standards of the National
Fire Protection Association such as
NFPA 25
• Standards of any authorities having
jurisdiction
Contact the installing contractor
or product manufacturer with any
questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
TFP312
Page 5 of 6
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and part number
(P/N).
Sprinkler Assemblies with
1 in. NPT Thread Connection
Specify: Model ESFR-25 (TY9226),
K=25.2, Early Suppression, Fast
Response Pendent Sprinkler with
1 in. NPT thread connection, (specify)
temperature rating, Natural Brass,
P/N (specify):
165°F (74°C} .................. 58-441-1-165
212°F (100°C} ................. 58-441-1-214
Special Order
Sprinkler Assemblies with
ISO 7-1 Thread Connection
Specify: Model ESFR-25 (TY9226),
K=25.2, Early Suppression,
Fast Response Sprinkler with
ISO 7-1 thread connection, (specify)
temperature rating), Natural Brass,
P/N (specify):
165°F (74°C} .................. 58-442-1-165
212° F (100°C) ................. 58-442-1-214
Sprinkler Wrench
Specify: W-Type 1 Sprinkler Wrench,
P/N 56-872-1-025
"IKINGj ® TECHNICAL DATA
Page 1 of 5
VK3021 QUICK RESPONSE
PENDENT SPRINKLER (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1. DESCRIPTION
The Viking VK3021 Quick Response Pendent Sprinkler is a small thermosensitive
glass bulb spray sprinkler available with various finishes and temperature ratings
to meet design requirements. The special Polyester and Electroless Nickel PTFE
(ENT) coatings can be used in decorative applications where colors are desired.
In addition, these coatings have been investigated for installation in corrosive
environments and are Listed and Approved as indicated in the Approval Chart.
2. LISTINGS AND APPROVALS
c@us
<8> -0\IED
CE
UL Listed: Category VNIV
FM Approved: Classes 2017, 2015, 2043
Also approved for use in FM Approved vacuum dry sprinkler systems with a
maximum supervisory vacuum pressure of -3 PSI (-207 mbar)
CE: Standard EN12259-1, DOP _XT1A_ 1-3-21
Refer to the Approval Chart and Design Criteria for requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 PSI (0.5 bar)
Rated to: UL -250 PSI (24 bar) \NWP
FM -175 PSI (12 bar) \NWP
Factory tested hydrostatically to 500 PSI (34.5 bar)
Thread size: 1/2" NPT (15 mm BSPT)
Nominal K-factor: 5.6 U.S. (80.6 metric*)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
~ WARNING: Cancer and Reproductive Harm-~ www.P65Warnings.ca.gov
* Metric K-factor measurement shown is in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass CW602N , UNS-C84400 or QM Brass
Deflector: Stainless Steel UNS S30400
Pip Cap Shell -Stainless Steel UNS-S44400
Pip Cap Disc -Stainless Steel UNS-S30100
Belleville Spring -Nickel Alloy
Pip Cap Seal -Polytetrafluoroethylene (PTFE)
Compression Screw: Brass CW612N , CW508L, UNS-C36000 or UNS-C26000
Shipping Cap: Polyethylene
Bulb: Glass, nominal 3 mm diameter
Ordering Information: (Refer to Table 1 and the current Viking List Price Book.)
4. INSTALLATION
Refer to appropriate NFPA, FM Global, and/or any other applicable installation standards.
Risk of permanent damage.
Over-tightening the sprinkler can cause permanent damage.
> Tighten the sprinkler to a MAXIMUM torque of 14 ft-lbs (19 N-m).
5. OPERATION
During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in the
glass bulb expands, causing the bulb to shatter, releasing the pip cap assembly. Water flowing through the sprinkler orifice strikes
the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinklers are available through a network of domestic and international distributors. See the Viking website for the closest
distributor or contact Viking.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Form No. F _110720 21 .04.19 Rev 21 .2 Replaces Form No. F _110720 Rev 21.1
(Added Models E-1 , E-2 and E-3 Escutcheons)
Page 2 of 5
TECHNICAL DATA VK3021 QUICK RESPONSE
PENDENT SPRINKLER (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
TABLE 1: ORDERING INFORMATION
Instructions: Using the sprinkler base part number,
(1) add the suffix for the desired Finish
(2) add the suffix for the desired Temperature Rating.
Sprinkler Size 1: Finishes 2: Temperature Ratings
Base Part NPT BSPT Max. Ambient Ceiling Number Description Suffix1 Nominal Rating Bulb Color Suffix Inch mm Temperature3
238707 1/2 Brass A 135 °F (57 °C) Orange 100 °F (38 °C) A
238827 15 Chrome F 155 °F (68 °C) Red 100 °F (38 °C) B
White Polyester 4•6 M-/W 175 °F (79 °C) Yellow 150 °F (65 °C) D
Black Polyester 4·6 M-/B 200 °F (93 °C) Green 150 °F (65 °C) E
ENT 4,s,6 JN 286 °F (141 °C) Blue 225 °F (107 °C) G
OPEN ----z
Example: 23870MB/W = VK3021 with white polyester finish and 155 °F (68 °C) nominal temperature rating. This sprinkler is to be
installed into an area with a maximum ambient temperature of 100 °F (38 °C) meaning if the area will experience temperatures above
the maximum ambient rating, you shall use a higher temperature-rated sprinkler.
Accessories
Sprinkler Wrenches (see Figure 1 ):
A. Standard Wrench: Part number 23559M B
B. Recessed Socket Wrench: Part number 23560MB2
Sprinkler Cabinet:
A. Up to 6 sprinklers: Part number 01724A
B. 6-12 sprinklers: Part number 01725A
Footnotes
1-Where a dash(-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
2. Requires a 1 /2" ratchet which is not available from Viking.
3-Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
4. UL Listed as corrosion resistant.
s. FM Approved as corrosion resistant.
s. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and
do not represent all possible corrosive environments. Prior to installation , verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
1. UL Listed for 250 PSI (17 bar) VW.JP.
A
Top View -
Figure 1: Sprinkler Wrenches
Form No. F _ 110720 21.04.19 Rev 21 .2
B
7/16" (11 mm)
Nominal Pipe l Engagement r
1/2" NPT
15 mm BSPT
1-15/16"
(49mm)
Figure 2: Sprinkler Dimensions
Page 3 of 5
"IKINGi® TECHNICAL DATA VK3021 QUICK RESPONSE
PENDENT SPRINKLER (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
APPROVAL CHART Finish(es) +
Viking Quick Response Pendent Sprinkler Temperature(s) ►A1X
VK3021 K5.6 (80.6 metric) Escutcheon(s), If applicable~
Thread Size Listings and Approvals2·6
Sprinkler Base NPT BSPT cULus FM CE6
Part Number1
KEY
Inch mm Approval Listings Maximum \/VWP Approval Listings Maximum \/VWP Approval Listings
23870 1/2 --A1, B2X, B3Y 250 PSI (17 bar) A1, B2X, B3Y 175 PSI (12 bar) C1,D2X,D3Y
23882 --15 A1, B2X, B3Y 250 PSI (17 bar) A1, B2X, B3Y 175 PSI (12 bar) C1, D2X,D3Y
Approved Temperature Ratings:
A = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C) and 286 °F (141 °C)
B = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
C = 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C) and 286 °F (141 °C)
D = 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
Approved Finishes:
1 = Brass, Chrome, White Polyester 3.4, Black Polyester 3.4, and ENT4·5
2 = Brass, Chrome, White Polyester 3.4, and Black Polyester 3·4
3 = ENT4•5
Approved Escutcheon Code:
X = Installed with Viking Recessed Escutcheons Models E-1, E-2, E-3, NP-1, NP-2, and NP-3, or Viking Standard Surface Mounted
Escutcheons
Y = Installed with Viking Recessed Escutcheons Models E-1 and NP-1 , or Viking Standard Surface Mounted Escutcheons
Footnotes
1 Base Part number is shown. For complete part number, refer to Viking's current price schedule.
2 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
3 Other colors are available upon request with the same Listings and Approvals as the standard colors.
4 cULus Listed as corrosion resistant.
5 FM Approved as corrosion resistant.
6 CE: Standard EN12259-1 , Declaration of Performance DOP_XT1A_1-3-21 .
DESIGN CRITERIA -UL
cULus Listing Reguirements:
The Viking VK3021 Quick Response Pendent Sprinkler is cULus Listed as indicated in Approval Chart for installation in accordance
with the latest edition of NFPA 13 for standard spray sprinklers.
• Designed for use in Light and Ordinary Hazard occupancies.
• The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers shall be followed.
IMPORTANT: Always refer to Form Number F _091699 -Care and Handling of Sprinklers. Also refer to Form Number
F _080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance
with the latest edition of Viking Technical Data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar
organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
DESIGN CRITERIA -FM
FM AggrQVs!I R~gyir~m~nt§:
The Viking VK3021 Quick Response Pendent Sprinkler is FM Approved as quick response Non-Storage Pendent sprinkler as
indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss
Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not
limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable
spacing, and deflector distance below the ceiling.
NOTE: The FM Installation guidelines may differ from UL and/or NFPA criteria.
IMPORTANT: Always refer to Form Number F _091699 -Care and Handling of Sprinklers. Also refer to Form Number
F _080614 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance
with the latest edition of Viking Technical Data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar
organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
FormNo.F_110720 21.04.19 Rev21.2
'\IIKINai® TECHNICAL DATA
Page 4 of 5
VK3021 QUICK RESPONSE
PENDENT SPRINKLER (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1. Install the escutcheon inner ring
onto the sprinkler threads.
tt
2. Carefully slide the wrench** sideways
around the protective cap then push
upwards to engage with the sprinkler
wrench flats.
3. Install the sprinkler and escutcheon
assembly into the pipe fitting. Be sure
the escutcheon outer ring contacts
the surface of the finished ceiling.
t t
Figure 3: Recessed Installation (with Recessed Socket Wrench)
**A 1/2" ratchet is required (not available from Viking).
1. Install the escutcheon onto the
sprinkler threads.
FormNo.F_110720 21 .04.19 Rev21.2
2. Carefully slide the wrench onto the
sprinkler wrench flats.
Figure 4: Installation (with Standard Wrench)
3. Install the sprinkler and escutcheon
assembly into the pipe fitting. Be sure
the escutcheon contacts the surface
of the finished ceiling.
'JIKINCG ® TECHNICAL DATA
Page 5 of 5
VK3021 QUICK RESPONSE
PENDENT SPRINKLER (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Models E-1 or NP-1
Recessed Escutcheon 2-1/8" (54 mm) Ceiling opening size:
Minimum: 2-5/16" (59 mm)
Maximum: 2-1/2" (64 mm)
Ceiling opening size:
Minimum: 2-5/16" (59 mm)
Maximum: 2-1/2" (64 mm)
Max. 1-3/4"
(44mm)
!
1-7/16"
(37mm)
t
Standard Surface-Mounted Escutcheon
Models E-2, E-3, NP-2 or
NP-3 Thread-Recessed
Escutcheon
(E-3 and NP-3 Outer rings
have larger diameters)
Figure 5: Installation Dimensions with Viking Escutcheons
Form No. F _ 110720 21 .04.19 Rev 21.2 Replaces Form No. F _110720 Rev 21.1
(Added Models E-1 , E-2 and E-3 Escutcheons)
"IKINGi BULLETIN
Page 1 of 4
CARE AND HANDLING
OF SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
SPRINKLERS ARE FRAGILE -HANDLE WITH CARE!
General Handling and Storage:
• Store sprinklers in a cool, dry place.
• Protect sprinklers during storage, transport, handling, and after installation.
• Use the original shipping containers. DO NOT place sprinklers loose in boxes, bins,
or buckets.
• Keep sprinklers separated at all times. DO NOT allow metal parts to contact sprinkler
operating elements.
For Pre-Assembled Drops:
• Protect sprinklers during handling and after installation.
• For recessed assemblies, use the protective sprinkler cap (Viking Part Number 10364).
Sprinklers with Protective Shields or Caps:
• DO NOT remove shields or caps until after sprinkler installation and there no longer is
potential for mechanical damage to the sprinkler operating elements.
• Sprinkler shields or caps MUST be removed BEFORE placing the system in
service!
• Remove the sprinkler shield by carefully pulling it apart where it is snapped together.
• Remove the cap by turning it slightly and pulling it off the sprinkler.
Sprinkler Installation:
• DO NOT use the sprinkler deflector or operating element to start or thread the sprinkler
into a fitting.
• Use only the designated sprinkler head wrench! Refer to the current sprinkler tech-
nical data page to determine the correct wrench for the model of sprinkler used.
• DO NOT install sprinklers onto piping at the floor level.
• Install sprinklers after the piping is in place to prevent mechanical damage.
• DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings, pipe,
or couplings in close proximity to sprinklers. Sprinklers can be damaged from direct or
indirect impacts.
• DO NOT attempt to remove drywall, paint, etc., from sprinklers.
• Take care not to over-tighten the sprinkler and/or damage its operating parts!
Maximum Torque:
1/2" NPT: 14 ft-lbs. (19.0 N-m)
3/4" NPT: 20 ft-lbs. (27.1 N-m)
1" NPT: 30 ft-lbs. (40.7 N-m)
AWARNING
(Original container used) (P'~cei O" ,e in box,
(Protected with caps) (Protective caps not used)
CORRECT INCORRECT
(Piping is in place at the (Sprinkler at floor level)
ceiling)
CORRECT
(Special installation
wrenches)
INCORRECT
(Designated wrench not
used)
A\. WARNING: Cancer and Reproductive Harm-
~ www.P65Warnings.ca.gov
Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed. Never install sprinklers
that have been dropped, damaged, or exposed to temperatures exceeding the maximum ambient temperature allowed. Sprinklers that
have been painted in the field must be replaced per NFPA 13. Protect sprinklers from paint and paint overspray in accordance with
the installation standards. Do not clean sprinklers with soap and water, ammonia, or any other cleaning fluid. Do not use adhesives
or solvents on sprinklers or their operating elements.
Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance
instructions. For additional product and system information Viking data pages and installation instructions are available on
the Viking Web site at www.vikinggroupinc.com.
Form No. F _091699 18.10.11 Rev 16.1.P65 Replaces Form No. F _091699 Rev 16.1
(Added P65 Warning)
BULLETIN
Page 2 of 4
CARE AND HANDLING
OF SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
PROTECTIVE SPRINKLER SHIELDS AND CAPS
General Handling and Storage:
Many Viking sprinklers are available with a plastic protective cap or shield temporarily covering the operating elements. The snap-
on shields and caps are factory installed and are intended to help protect the operating elements from mechanical damage during
shipping, storage, and installation. NOTE: It is still necessary to follow the care and handling instructions on the appropriate sprin-
kler technical data sheets* when installing sprinklers with bulb shields or caps.
WHEN TO REMOVE THE SHIELDS AND CAPS:
NOTE: SHIELDS AND CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE!
Remove the shield or cap from the sprinkler only after checking all of the following:
• The sprinkler has been installed*.
• The wall or ceiling finish work is completed where the sprinkler is installed and there no longer is a potential for mechanical damage
to the sprinkler operating elements.
SHli=LOo A D CAPS MUST BE REMOVED FROM SPRINKLERS BEF) E PLACING THE SYSTEM IN SERVICE1
Figure 1: Sprinkler shield being
removed from a pendent sprinkler.
Figure 2: Sprinkler cap being
removed from a pendent sprinkler.
Figure 3: Sprinkler cap being re-
moved from and upright sprinkler.
HOW TO REMOVE SHIELDS AND CAPS:
No tools are necessary to remove the shields or caps from sprinklers. DO NOT use any sharp objects to remove them! Take care
not to cause mechanical damage to sprinklers when removing the shields or caps. When removing caps from fusible ele-
ment sprinklers, use care to prevent dislodging ejector springs or damaging fusible elements. NOTE: Squeezing the sprinkler cap
excessively could damage sprinkler fusible elements.
• To remove the shield, simply pull the ends of the shield apart where it is snapped together. Refer to Figure 1.
• To remove the cap, turn it slightly and pull it off the sprinkler. Refer to Figures 2 and 3.
■+"f •JihlM Refer to the current sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used.
I Aw ARNING I Never install sprinklers that have been dropped, damaged, or exposed to temperatures in excess of the maximum ambient
temperature allowed.
* Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data
pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www.
vi kinggroupi nc.com.
Form No. F _091699 18.10.11 Rev 16.1.P65
Page 3 of 4
'JIKll'IGi BULLETIN CARE AND HANDLING
OF SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1 ACAUTION 1--NCEALED COVER ASSEMBLIES ARE FRAGILE!
T St:ACTORY PERFORMANCE OF THE PRODUCT. HANDLE WITH CARE.
Concealed Sprinkler and Adapter
Assembly (Protective Cap Removed)
~: Al I • •
: .... · = .... ~ 4 .,
Concealed Sprinkler and Adapter
Assembly with Protective Cap Cover Plate Assembly
(Pendent Cover 12381 shown)
.., ":'. · .
. tetf t :)I~~<?;'i:./L:/l)'.:t
GENERAL HANDLING AND STORAGE INSTRUCTIONS:
• Do not store in temperatures exceeding 100 °F (38 °C). Avoid direct sunlight and confined areas subject to heat.
• Protect sprinklers and cover assemblies during storage, transport, handling, and after installation.
--Use original shipping containers.
--Do not place sprinklers or cover assemblies loose in boxes, bins, or buckets.
• Keep the sprinkler bodies covered with the protective sprinkler cap any time the sprinklers are shipped or handled, during testing of the system, and
while ceiling finish work is being completed.
• Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is
temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
• Do not over-tighten the sprinklers into fittings during installation.
• Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation.
• Do not attempt to remove drywall, paint, etc., from the sprinklers.
• Remove the plastic protective cap from the sprinkler before attaching the cover plate assembly. PROTECTIVE CAPS .M.U..S..I BE REMOVED FROM
SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE!
Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data
pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www.
vikinggroupinc.com.
Form No. F _091699 18.10.11 Rev 16.1.P65
"IKll'-ICG BULLETIN
Page 4 of 4
CARE AND HANDLING
OF SPRINKLERS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
USE THE FOLLOWING PRECAUTIONS WHEN HANDLING WAX-COATED SPRINKLERS
Many of Viking's sprinklers are available with factory-applied wax coating for corrosion resistance. These sprinklers MUST receive
appropriate care and handling to avoid damaging the wax coating and to assure satisfactory performance of the product.
General Handling and Storage of Wax-Coated Sprinklers:
• Store the sprinklers in a cool, dry place (in temperatures below the maximum ambient temperature allowed for the sprinkler temperature rating. Refer
to Table 1 below.)
• Store containers of wax-coated sprinklers separate from other sprinklers.
• Protect the sprinklers during storage, transport, handling, and after installation.
• Use original shipping containers.
• Do not place sprinklers in loose boxes, bins, or buckets.
Installation of Wax-Coated Sprinklers:
Use only the special sprinkler head wrench designed for installing wax-coated Viking sprinklers (any other wrench may damage
the unit).
• Take care not to crack the wax coating on the units.
• For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after
sprinkler installation to protect the corrosion-resistant properties of the sprinkler.
• Use care when locating sprinklers near fixtures that can generate heat. Do not install sprinklers where they would be exposed to temperatures exceed-
ing the maximum recommended ambient temperature for the temperature rating used.
• Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant coating. Thereafter, inspect representative
samples of the coated sprinklers in accordance with NFPA 25. Close up visual inspections are necessary to determine whether the sprinklers are being
affected by corrosive conditions.
TABLE 1
Sprinkler Temperature Rating Wax Part Wax Melting Point Maximum Ambient Wax Color (Fusing Point) Number Ceiling Temperature1
155 °F (68 °C) / 165 °F (74 °C) 02568A 148 °F (64 °C) 100 °F (38 °C) Light Brown
175 °F (79 °C) 04146A 161 °F (71 °C) 150 °F (65 °C) Brown
200 °F (93 °C) 04146A 161 °F (71 °C) 150 °F (65 °C) Brown
220 °F (104 °C) 02569A 170 °F (76 °C) 150 °F (65 °C) Dark Brown
286 °F (141 °C) 02569A 170 °F (76 °C) 150 °F (65 °C) Dark Brown
1 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
I Aw ARNING I Never install sprinklers that have been dropped, damaged, or exposed to temperatures in excess of the maximum ambi-
~---~ ent temperature allowed.
Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data
pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www.
vi ki ngg roupi nc.com.
Form No. F_091699 18.10.11 Rev 16.1.P65 Replaces Form No . F _091699 Rev 16.1
(Added P65 Warning)
~IKINCG TECHNICAL DATA
I
I
Page 1 of 3
SPRINKLER OVERVIEW
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
1. DESCRIPTION
Viking fire sprinklers consist of a threaded frame with a specific waterway or orifice size and a deflector for distributing water in a
specified pattern. A closed or sealed sprinkler refers to a complete assembly, including the thermosensitive operating element. An
open sprinkler does not use an operating element and is open at all times. The distribution of water is intended to extinguish a fire
or to control its spread.
Viking sprinklers are available in several models and styles. Refer to specific sprinkler technical data pages for available styles,
finishes, temperature ratings, thread sizes, and nominal K-Factors for the particular model selected.
2. LISTINGS AND APPROVALS
Refer to the Approval Charts on the appropriate sprinkler technical data page(s) and/or
approval agency listings.
A\. WARNING: Cancer and Reproductive Harm-~ www.P65Warnings.ca.gov
3. TECHNICAL DATA
Pressure Ratings:
Maximum allowable water working pressure is 175 psig (12 Bar) unless rated and specified for high water working pressure [250
psig (17.2 bar)].
Sprinkler Identification:
Viking sprinklers are identified and marked with the word "Viking", the sprinkler identification number (SIN) consisting of "VK" plus
a three digit number*, the model letter, and the year of manufacture.
Available Finishes:
Viking sprinklers are available in several decorative finishes. Some models are available with corrosion-resistant coatings or are
fabricated from non-corrosive material. Refer to the sprinkler technical data page for additional information.
Available Temperature Ratings:
Viking sprinklers are available in several temperature ratings that relate to a specific temperature classification. Applicable installa-
tion rules mandate the use and limitations of each temperature classification. In selecting the appropriate temperature classifica-
tion, the maximum expected ceiling temperature must be known. When there is doubt as to the maximum temperature at the
sprinkler location, a maximum-reading thermometer should be used to determine the temperature under conditions that would
show the highest readings to be expected. In addition, recognized installation rules may require a higher temperature classifica-
tion, depending upon sprinkler location, occupancy classification, commodity classification, storage height, and other hazards. In
all cases, the maximum expected ceiling temperature dictates the lowest allowable temperature classification. Sprinklers located
immediately adjacent to a heat source may require a higher temperature rating.
K-Factors:
Viking sprinklers are available in several orifice sizes with related K-Factors. The orifice is a tapered waterway and, therefore, the
K-Factor given is nominal. Nominal U.S. K-Factors are provided in accordance with the 1999 edition of NFPA 13, Section 3-2.3.
Refer to the specific data page for appropriate K-Factor information.
Available Styles:
Viking sprinklers are available for installation in several positions as indicated by a stamping on the deflector. The deflector style
dictates the appropriate installation position of the sprinkler; it breaks the solid stream of water issuing from the sprinkler orifice to
form a specific spray pattern. The following list indicates the various styles and identification of Viking sprinklers.
UPRIGHT SPRINKLER: A sprinkler intended to be installed with the deflector above the frame so water flows upward through the
orifice, striking the deflector and forming an umbrella-shaped spray pat-
tern downward. Marked "SSU" (Standard Sprinkler Upright) or "UPRIGHT"
on the deflector.
PENDENT SPRINKLER: A sprinkler intended to be oriented with the deflec-
tor below the frame so water flows downward through the orifice, striking
the deflector and forming an umbrella-shaped spray pattern downward.
Marked "SSP" (Standard Sprinkler Pendent) or "PENDENT" on the de-
flector.
Viking Technical Data may be found on
The Viking Corporation's Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
CONVENTIONAL SPRINKLER: An "old style" sprinkler intended to be installed with the deflector in either the upright or pendent
position. The deflector provides a spherical type pattern with 40 to 60 percent of the water initially directed downward and a
proportion directed upward. Must be installed in accordance with installation rules for conventional or old style sprinklers. DO
NOT USE AS A REPLACEMENT FOR STANDARD SPRAY SPRINKLERS. Marked "C U/P" (Conventional Upright/Pendent) on
the deflector.
Form No. F_080814 18.12.06 Rev 14.1.P65 Replaces Form No. F _080814 Rev 14.1
(Added P65 Warning.)
Page 2 of 3
TECHNICAL DATA SPRINKLER OVERVIEW
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
VERTICAL SIDEWALL (VSW} SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a
water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow
arrow in the direction of discharge. Marked "SIDEWALL" on the deflector with an arrow and the word "FLOW'. (Note: Some
vertical sidewall sprinklers can only be installed in the upright or pendent position-in this case, the sprinkler will also be marked
"UPRIGHT" or "PENDENT".)
HORIZONTAL SIDEWALL (HSW} SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The special deflector
provides a water spray pattern outward in a quarter-spherical pattern. Most of the water is directed away from the nearby wall
with a small portion directed at the wall behind the sprinkler. The top of the deflector is oriented parallel with the ceiling or roof.
The flow arrows point in the direction of discharge. Marked "SIDEWALL" and "TOP" with an arrow and the word "FLOW'.
EXTENDED COVERAGE (EC) SPRINKLER: A spray sprinkler designed to discharge water over an area having the maximum
dimensions indicated in the individual listings. Maximum area of coverage, minimum flow rate, orifice size, and nominal K-Factor
are specified in the individual listings. EC sprinklers are intended for Light-Hazard occupancies with smooth, flat, horizontal ceil-
ings unless otherwise specified. In addition to the above markings, the sprinkler is marked "EC".
QUICK RESPONSE (QR) SPRINKLER: A spray sprinkler with a fast-actuating operating element. The use of quick response
sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having Jurisdiction (AHJ) prior to installing.
QUICK RESPONSE EXTENDED COVERAGE (QREC) SPRINKLER: A spray sprinkler designed to discharge water over an area
having the maximum dimensions indicated in the individual listing. This is a sprinkler with an operating element that meets the
criteria for quick response. QREC sprinklers are only intended for Light Hazard occupancies. The sprinkler is marked "QREC".
FLUSH SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The unit is mounted
flush with the ceiling or wall, with the fusible link exposed. Upon actuation, the deflector extends beyond the ceiling or wall to
distribute water discharge. The sprinkler is marked "SSP", "PEND", or "SIDEWALL" and "TOP".
CONCEALED SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The sprinkler is
hidden from view by a cover plate installed flush with the ceiling or wall. During fire conditions, the cover plate detaches, and
upon sprinkler actuation, the deflector extends beyond the ceiling or wall to distribute water discharge. The sprinkler is marked
"SSP", "PEND", or "SIDEWALL" and "TOP".
RECESSED SPRINKLER: A spray sprinkler assembly intended for installation with a concealed piping system. The assembly con-
sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond
the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity. Refer to the appropriate technical data page
for allowable sprinkler models, temperature ratings, and occupancy classifications. DO NOT RECESS ANY SPRINKLER NOT
LISTED FOR USE WITH THE ESCUTCHEON.
CORROSION-RESISTANT SPRINKLER: A special service sprinkler with non-corrosive protective coatings, or that is fabricated
from non-corrosive material, for use in atmospheres that would normally corrode sprinklers.
DRY SPRINKLER: A special-service sprinkler intended for installation on dry pipe systems or wet pipe systems where the sprinkler
is subject to freezing temperatures. The unit consists of a sprinkler permanently secured to an extension nipple with a sealed
inlet end to prevent water from entering the nipple until the sprinkler operates. The unit MUST be installed in a tee fitting. Dry
upright sprinklers are marked with the "B'' dimension [distance from the face of the fitting (tee) to the top of the deflector]. Dry
pendent and sidewall sprinklers are marked with the "A" dimension [the distance from the face of fitting (tee) to the finished
surface of the ceiling or wall].
LARGE DROP SPRINKLER: A type of special application sprinkler used to provide fire control of specific high-challenge fire haz-
ards. Large drop sprinklers are designed to produce an umbrella-shaped spray pattern downward with a higher percentage of
"large" water droplets than standard spray sprinklers. The sprinkler has an extra-large orifice with a nominal K-Factor of 11.2.
Marked "HIGH CHALLENGE" and "UPRIGHT".
EARLY SUPPRESSION FAST-RESPONSE (ESFR) SPRINKLER: A sprinkler intended to provide fire suppression of specific high-
challenge fire hazards through the use of a fast response fusible link, 14.0, 16.8, or 25.2 nominal K-Factor, and special deflector.
ESFR sprinklers are designed to produce high-momentum water droplets in a hemispherical pattern below the deflector. This
permits penetration of the fire plume and direct wetting of the burning fuel surface while cooling the atmosphere early in the
development of a high-challenge fire. Marked "ESFR" and "UPRIGHT" or "PEND".
INTERMEDIATE LEVEL/RACK STORAGE SPRINKLER: A standard spray sprinkler assembly designed to protect its operating
element from the spray of sprinklers installed at higher elevations. The assembly consists of a standard or large orifice upright
or pendent sprinkler with an integral upright or pendent water shield and guard assembly. Use only those sprinklers that have
been tested and listed for use with the assembly. Refer to the technical data page for allowable sprinkler models.
RESIDENTIAL SPRINKLER: A sprinkler intended for use in the following occupancies: one-and two-family dwellings with the fire
protection sprinkler system installed in accordance with NFPA 130; residential occupancies up to four stories in height with the
fire protection system installed in accordance with NFPA 13R; and where allowed by the Authority Having Jurisdiction in resi-
dential portions of any occupancy with the fire protection system installed in accordance with NFPA 13.
Form No. F_080814 18.12.06 Rev 14.1.P65
Page 3 of 3
"IKINCG TECHNICAL DATA SPRINKLER OVERVIEW
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Residential sprinklers have a unique distribution pattern and utilize a "fast response" heat sensitive operating element. They en-
hance survivability in the room of fire origin and are designed to provide a life safety environment for a minimum of ten minutes. For
this reason, residential sprinklers must not be used to replace standard sprinklers unless tested for and approved by the Authority
Having Jurisdiction. In addition to standard markings, the unit is identified as "RESIDENTIAL SPRINKLER" or "RES".
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
Refer to the appropriate sprinkler technical data page(s).
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site
for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
IMPORTANT: Always refer to Bulletin Form No. F _091699-Care and Handling of Sprinklers and the appropriatesprin-
klergeneral care, installation, and maintenance guide. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar
organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
The sprinkler technical data page may contain installation requirements specific for the sprinkler model selected.
The use of certain types of sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having
Jurisdiction prior to installation.
Form No. F_080814 18.12.06 Rev 14.1.P65 Replaces Form No. F _080814 Rev 14.1
(Added P65 Warning.)
TECHNICAL DATA
Page 1 of 4
SPRINKLER GENERAL CARE,
INSTALLATION, AND
MAINTENANCE GUIDE
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page.
1. DESCRIPTION -STANDARD RESPONSE, QUICK RESPONSE, EXTENDED COVERAGE, AND DRY SPRINKLERS
Viking thermosensitive spray sprinklers consist of a small frame and either a glass bulb or a fusible operating element. Available
styles include pendent, flush pendent, concealed pendent, upright, horizontal sidewall, vertical sidewall, or conventional, depending
on the particular sprinkler model selected.
Viking sprinklers are available with various finishes, temperature ratings, responses, and K-Factors to meet design requirementst.
Used in conjunction with one of the corrosion-resistant coatings (for frame style sprinklers), the units provide protection against
many corrosive environments. In addition, the special Polyester or PTFE coatings can be used in decorative applications where
colors are desired.
t Refer to the sprinkler technical data page for available styles, finishes, temperature ratings, responses, and nominal K-Factors for specific sprinkler models.
2. LISTINGS AND APPROVALS
Refer to the Approval Charts on the appropriate sprinkler technical data page(s) and/or approval agency listings.
3. TECHNICAL DATA
Specifications:
Refer to the appropriate sprinkler technical data sheet.
Material Standards:
Refer to the appropriate sprinkler technical data sheet.
4. INSTALLATION
NOTE: Take care not to over-tighten the sprinkler and/or damage its operating parts!
Maximum Torque:
1/2" NPT: 14 ft-lbs. (19.0 N-m)
3/4" NPT: 20 ft-lbs. (27.1 N-m)
1" NPT: 30 ft-lbs. (40.7 N-m)
~ WARNING: Cancer and Reproductive Harm-
~ www.P65Warnings.ca.gov
A. Care and Handling (also refer to Bulletin -Care and Handling of Sprinklers, Form No. F _091699.)
Sprinklers must be handled with care. They must be stored in a cool, dry place in their original shipping container. Never install
sprinklers that have been dropped, damaged, or exposed to temperatures exceeding the maximum ambient temperature al-
lowed (refer to the temperature chart on the sprinkler technical data page). Never install any glass-bulb sprinkler if the bulb is
cracked or if there is a loss of liquid from the bulb. A small air bubble should be present in the glass bulb. Any sprinkler with a
loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately. (Note: Installing glass bulb
sprinklers in direct sunlight (ultraviolet light) may affect the color of the dye used to color code the bulb. This color change does
not affect the integrity of the bulb.)
Sprinklers must be protected from mechanical damage during storage, transport, handling, and after installation. Sprinklers subject
to mechanical damage must be protected with an approved sprinkler guard.
Use only sprinklers listed as corrosion resistant when subject to corrosive environments. When installing corrosion-resistant sprin-
klers, take care not to damage the corrosion-resistant coating. Use only the special wrench designed for installing coated or
recessed Viking sprinklers (any other wrench may damage the unit).
Concealed sprinklers must be installed in neutral or negative pressure plenums only!
Use care when locating sprinklers near fixtures that can generate heat. Do not install sprinklers where they could be exposed to
temperatures exceeding the maximum recommended ambient temperature for the temperature rating used.
Wet pipe systems must be provided with adequate heat. Sprinklers supplied from dry systems in areas subject to freezing must
be listed dry sprinklers, upright, or horizontal sidewall sprinklers installed so that water is not trapped. For dry systems, pendent
sprinklers and sidewall sprinklers installed on return bends are permitted, where the sprinklers, return bend, and branch line
piping are in an area maintained at or above 40 °F (4 °C).
B. Installation Instructions -Standard Spray Sprinklers
Viking sprinklers are manufactured and tested to meet the rigid requirements of approving agencies. They are designed to be
installed in accordance with recognized installation standards. Deviation from the standards or any alteration to sprinklers or cover
plate assemblies after they leave the factory including, but not limited to: painting, plating, coating, or modification, may render them
inoperative and will automatically nullify the approvals and any guarantee made by The Viking Corporation.
Form No. F_080614 18.10.1 1 Rev 16.1.P65 Replaces Form No. F _080614 Rev 16.1
(Added P65 Warning.)
"IKINGi TECHNICAL DATA
Page 2 of 4
SPRINKLER GENERAL CARE,
INSTALLATION, AND
MAINTENANCE GUIDE
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page.
Before installation, be sure to have the appropriate sprinkler model and style, with the correct K-Factor, temperature rating, and
response characteristics. Sprinklers must be installed after the piping is in place to prevent mechanical damage. Keep sprinklers
with protective caps or bulb shields contained within the caps or shields during installation and testing, and any time the sprinkler
is shipped or handled.
1 a. For frame-style sprinklers, install escutcheon (if used), which is designed to thread onto the external threads of the sprinkler.
Refer to the appropriate sprinkler data page to determine approved escutcheons for use with specific sprinkler models.
1 b. For flush and concealed style sprinklers: Cut the sprinkler nipple so that the ½" or 3/4" (15 mm or 20 mm)* NPT outlet of the
reducing coupling is at the desired location, and centered in the opening* in the ceiling or wall.
*Size depends on the sprinkler model used. Refer to the sprinkler technical data page.
2. Apply a small amount of pipe-joint compound or tape to the external threads of the sprinkler only, taking care not to allow a
build-up of compound in the sprinkler inlet. NOTE: Sprinklers with protective caps or bulb shields must have the caps or shields
kept on them when applying pipe-joint compound or tape. Exception: For domed concealed sprinklers, remove the protective
cap for installation, and then place it back on the sprinkler temporarily.
3. Refer to the appropriate sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used.
DO NOT use the deflector or fusible element to start or thread the sprinkler into a fitting.
a. Install the sprinkler onto the piping using the special sprinkler wrench only, taking care not to over-tighten or damage the
sprinkler.
b. For flush and concealed style sprinklers: the internal diameter of the special sprinkler installation wrench is designed for use
with the sprinkler contained in the protective cap. Exception: For domed concealed sprinklers, remove the protective cap for
installation, and then place it back on the sprinkler temporarily. Thread the flush or concealed sprinkler into the ½" or 3/4"
(15 mm or 20 mm)* NPT outlet of the coupling by turning it clockwise with the special sprinkler wrench. *Thread size depends
on the particular sprinkler model used. Refer to the sprinkler technical data page.
C. Installation Instructions -Dry Sprinklers
WARNING: Viking dry sprinklers are to be installed in the 1" outlet (for dry and preaction systems), or run of malleable, ductile
iron, or Nibco CPVC* threaded tee fittings (for wet systems) that meet the dimensional requirements of ANSI B16.3 (Class 150),
or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125), even at branch line ends. The
threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth.
This prevents condensation from accumulating and freezing over the sprinkler seal. *NOTE: When using CPVC fittings with
Viking dry sprinklers, use only new Nibco Model 5012-S-BI. When selecting other CPVC fittings, contact Viking Technical
Services.
1. DO NOT install the dry sprinkler into a threaded elbow, coupling, or any other fitting that could interfere with thread penetration.
Such installation would damage the brass seal.
2. DO NOT install dry sprinklers into couplings or fittings that would allow condensation to accumulate above the seal when the
sprinkler is located in an area subject to freezing .
3. NEVER try to modify dry sprinklers. They are manufactured for specific "A" or "B" dimensions and cannot be modified.
The dry sprinkler must be installed after the piping is in place to prevent mechanical damage. Before installation, be sure to have
the correct sprinkler model and style, with the appropriate "A" or "B" dimension(s), temperature rating, orifice size, and response
characteristics. Keep sprinklers with protective caps or bulb shields contained within the caps or shields during installation and
testing, and any time the sprinkler is shipped or handled. Exception: For concealed and adjustable recessed dry sprinklers, the
protective caps and shields are removed for installation.
To install the dry sprinkler, refer to the instructions below and the appropriate sprinkler technical data page for illustrated instruc-
tions.
Dry upright sprinklers must be installed above the piping, in the upright position only. When installing dry upright or plain barrel style
vertical sidewall sprinklers on piping located close to the ceiling, it may be necessary to lower the sprinkler into the fitting from above
the ceiling. When installing dry upright or plain barrel vertical sidewall sprinklers from below the ceiling, verify that the opening in the
ceiling is a minimum 1-1/2" (38.1 mm) in diameter.
For dry upright or plain barrel vertical sidewall sprinklers in the upright position: First, install the escutcheon (if used) over the
threaded end of the sprinkler barrel. Slide the escutcheon past the external threads. NO TE: When installing the dry upright or plain
barrel vertical sidewall sprinkler from above the ceiling, it will be necessary to install the escutcheon after lowering the threaded
end of the sprinkler through the ceiling penetration.
A. For all dry sprinklers: Apply a small amount of pipe-joint compound or tape to the external threads of the sprinkler barrel only,
taking care not to allow a build-up of compound or tape over the brass inlet and seal. NOTE: Sprinklers with protective caps or
bulb shields must be contained within the caps or shields before applying pipe-joint compound or tape.
Form No. F_080614 18.10.11 Rev 16.1.P65
"IKll'KG TECHNICAL DATA
Page 3 of 4
SPRINKLER GENERAL CARE,
INSTALLATION, AND
MAINTENANCE GUIDE
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page.
B. Refer to the appropriate sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used.
C. Install the dry sprinkler on the piping using the special dry sprinkler wrench only, while taking care not to damage the sprinkler.
NOTE: Thread the sprinkler into the fitting hand tight, plus 1/2 turn with the dry sprinkler wrench.
D. For adjustable standard and adjustable recessed dry pendent and sidewall sprinklers: Escutcheons can be installed after the
sprinklers have been installed onto the piping. Refer to the appropriate sprinkler technical data page for escutcheon installation
instructions and illustrations.
D. Installation Instructions -Testing
4. After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the installation stand-
ards. Viking high pressure sprinklers may be hydrostatically tested at a maximum of 300 psi (20.7 bar) for limited periods of time
(two hours), for the purpose of acceptance by the Authority Having Jurisdiction.
a. Make sure the sprinkler is properly tightened. If a thread leak occurs, normally the sprinkler must be removed, new pipe-joint
compound or tape applied, and then reinstalled. This is due to the fact that when the joint seal is damaged, the sealing
compound or tape is washed out of the joint. Air testing [do not exceed 40 psi (2. 76 bar)] the sprinkler piping prior to testing
with water may be considered in areas where leakage during testing must be prevented. Refer to the Installation Standards
and the Authority Having Jurisdiction.
b. Remove plastic protective sprinkler caps or bulb shields AFTER the wall or ceiling finish work is completed where
the sprinkler is installed and there no longer is a potential for mechanical damage to the sprinkler operating ele-
ments. To remove the bulb shields, simply pull the ends of the shields apart where they are snapped together. To remove
caps from frame style sprinklers, turn the caps slightly and pull them off the sprinklers. SPRINKLER CAPS OR BULB
SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! Retain a protective
cap or shield in the spare sprinkler cabinet.
5. For flush style sprinklers: the ceiling ring can now be installed onto the sprinkler body. Align the ceiling ring with the sprinkler
body and thread or push it on (depends on sprinkler model) until the outer flange touches the surface of the ceiling. Note the
maximum adjustment is 1/4" (6.35 mm). DO NOT MODIFY THE UNIT. If necessary, re-cut the sprinkler drop nipple as required.
6. For concealed sprinklers: the cover assembly can now be attached.
a. Remove the cover from the protective box, taking care not to damage the cover plate assembly.
b. Gently place the base of the cover plate assembly over the sprinkler protruding through the opening in the ceiling.
c. Push the cover plate assembly onto the sprinkler until the unfinished brass flange of the cover plate base (or the cover
adapter, if used) touches the surface of the ceiling.
d. Refer to the applicable technical data sheet to determin the maximum adjustment available for concealed sprinklers. DO NOT
MODIFY THE UNIT. If necessary, re-cut the sprinkler drop nipple.
NOTE: If it is necessary to remove the entire sprinkler unit, the system must be taken out of service. See section 6. INSPECTIONS,
TESTS AND MAINTENANCE and follow all warnings and instructions.
5. OPERATION
Refer to the appropriate sprinkler technical data page(s). During fire conditions, the operating element fuses or shatters (depending
on the type of sprinkler), releasing the pip cap and sealing assembly. Water flowing through the sprinkler orifice strikes the sprinkler
deflector, forming a uniform spray pattern to extinguish or control the fire.
IMPORTANT: Always refer to Bulletin Form No. F _091699 -Care and Handling of Sprinklers. Viking
sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appro-
priate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with
the provisions of governmental codes, ordinances, and standards, whenever applicable. The sprinkler
technical data page may contain installation requirements specific for the sprinkler model selected.
The use of certain types of sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having
Jurisdiction prior to installation.
FormNo.F_080614 18.10.11 Rev 16.1.P65
"IKll'KG TECHNICAL DATA
Page 4 of 4
SPRINKLER GENERAL CARE,
INSTALLATION, AND
MAINTENANCE GUIDE
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page.
6. INSPECTIONS, TESTS AND MAINTENANCE
NOTICE: Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. NOTICE: The owner is responsible for having
the fire-protection system and devices inspected, tested, and maintained in proper operating condition in accordance with this
guide, and applicable NFPA standards. In addition, the Authority Having Jurisdiction may have additional maintenance, testing, and
inspection requirements that must be followed.
A. Sprinklers must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. Frequency of inspec-
tions may vary due to corrosive atmospheres, water supplies, and activity around the sprinkler unit.
B. Sprinklers or cover plate assemblies that have been field painted, caulked, or mechanically damaged must be replaced im-
mediately. Sprinklers showing signs of corrosion shall be tested and/or replaced immediately as required. Installation standards
require sprinklers to be tested and, if necessary, replaced after a specified term of service. Refer to NFPA 25 and the Authority
Having Jurisdiction for the specified period of time after which testing and/or replacement is required. Never attempt to repair
or reassemble a sprinkler. Sprinklers and cover assemblies that have operated cannot be reassembled or re-used, but must
be replaced. When replacement is necessary, use only new sprinklers and cover assemblies with identical performance char-
acteristics.
C. The sprinkler discharge pattern is critical for proper fire protection. Therefore, nothing should be hung from, attached to, or
otherwise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers
installed.
D. When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description and/
or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration should
be given to employment of a fire patrol in the affected area.
1. Remove the system from service, drain all water, and relieve all pressure on the piping.
2a. For frame-style sprinklers, use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to
unthread it from the piping.
2b. For flush and concealed style sprinklers: Remove the ceiling ring or cover plate assem-
bly before unthreading the sprinkler body from the piping. Ceiling rings and cover plates can be removed ei-
ther by gently unthreading them or pulling them off the sprinkler body (depends on the sprinkler model used).
After the ceiling ring or cover plate assembly has been removed from the sprinkler body, place the plastic protective cap
(from the spare sprinkler cabinet) over the sprinkler to be removed and then fit the sprinkler wrench over the cap. Then
use the wrench to unthread the sprinkler from the piping. Exception: Domed concealed sprinklers are removed without the
plastic cap.
3. Install the new sprinkler unit by following the instructions in section 4. INSTALLATION. Care must be taken to ensure that the
replacement sprinkler is the proper model and style, with the correct K-factor, temperature rating , and response character-
istics. A fully stocked spare sprinkler cabinet should be provided for this purpose. For flush or concealed sprinklers: stock of
spare ceiling rings or cover plates should also be available in the spare sprinkler cabinet.
E. Place the system back in service and secure all valves. Check for and repair all leaks. Sprinkler systems that have been sub-
jected to a fire must be returned to service as soon as possible. The entire system must be inspected for damage, and repaired
or replaced as necessary. Sprinklers that have been exposed to corrosive products of combustion or high ambient temperatures,
but have not operated, should be replaced. Refer to the Authority Having Jurisdiction for minimum replacement requirements.
7. AVAILABILITY
Viking sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site
for the closest distributor or contact The Viking Corporation. ·
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Form No. F_080614 18.10.11 Rev 16.1.P65 Replaces Form No. F _080614 Rev 16.1
(Added P65 Warning.)
'\IIKINCG ® BULLETIN
Page 1 of 1
REGULATORY AND HEALTH
WARNINGS
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
1. DESCRIPTION
Regulatory and Health Warnings applying to materials used in the manufacture and construction of fire protection products are
provided herin as they relate to legally mandated jurisdictional regions.
A.WARNING
STATE OF CALIFORNIA, USA
Installing or servicing fire protection products such as sprinklers, valves, piping etc. can expose you to chemicals including, but not Ii-
mited to, lead, nickel, butadiene, titaninum dioxide, chromium, carbon black, and acrylonitrile which are known to the State of California
to cause cancer or birth defects or other reproductive harm.
For more information, go to www.P65Warnings.ca.gov
2. WARRANTY TERMS AND CONDITIONS
For details of warranty, refer to Viking's current list price schedule at www.vikinggroupinc.com or contact Viking directly.
Form No. F_111218 18.11 .15 Rev 18.1 New Bulletin
tqca Worldwide Contacts www.tyco-fire.com
Series TY-FRB -2.8, 4 .2, 5.6, and 8.0 K-Fac tor
Upright, Pendent, and Recessed Pendent Sp rinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent,
and Recessed Pendent Sprinklers
described in herein are quick response,
standard coverage, decorative 3 mm
glass bulb-type spray sprinklers. They
are designed for use in light or ordinary
hazard, commercial occupancies such
as banks, hotels, and shopping malls.
The TY-FRB Recessed Pendent Sprin-
kler, where applicable, is intended for
use in areas with a finished ceiling. This
recessed pendent sprinkler uses one of
the following Recessed Escutcheons:
• A two-piece Style 10 (1/2 in. NPT)
or Style 40 (3/4 in. NPT) Recessed
Escutcheon with 1/2 in. (12,7 mm) of
recessed adjustment or up to 3/4 in.
(19,1 mm) of total adjustment from
the flush pendent position.
• A two-piece Style 20 (1/2 in. NPT)
or Style 30 (3/4 in. NPT) Recessed
Escutcheon with 1/4 in. (6,4 mm) of
recessed adjustment or up to 1/2 in.
(12,7 mm) of total adjustment from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Corrosion-resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
what would be obtained when exposed
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 12
to corrosive atmospheres. Although
corrosion-resistant coated sprinklers
have passed the standard corrosion
tests of the applicable approval agen-
cies, the testing is not representative
of all possible corrosive atmospheres.
Consequently, it is recommended that
the end user be consulted with respect
to the suitability of these coatings for
any given corrosive environment. The
effects of ambient temperature, con-
centration of chemicals, and gas/
chemical velocity, should be consid-
ered, as a minimum, along with the cor-
rosive nature of the chemical to which
the sprinklers will be exposed.
An intermediate level version of the
Series TY-FRB Pendent Sprinklers
is detailed in Technical Data Sheet
TFP356. Sprinkler Guards are detailed
in Technical Data Sheet TFP780.
14•Ji@j
The Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent,
and Recessed Pendent Sprinklers
described herein must be installed
and maintained in compliance with
this document and with the applicable
standards of the National Fire Protec-
tion Association (NFPA), in addition to
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
NFPA 13 prohibits installation of 1 /2 in.
NPT sprinklers with K-factors greater
than 5.6 in new construction. They are
intended for retrofit in existing sprinkler
systems only.
DECEMBER 2 0 2 0
Sp rin k le r
I dentification
N umber (SIN}
TY1131 ... Upright 2.8K, 1/2 in. NPT
TY1231 .. Pendent 2.8K, 1/2 in. NPT
TY2131 ... Upright 4.2K, 1/2 in. NPT
TY2231 .. Pendent 4.2K, 1/2 in. NPT
TY3131 ... Upright 5.6K, 1/2 in. NPT
TY3231 .. Pendent 5.6K, 1/2 in. NPT
TY4131 ... Upright 8.0K, 3/4 in. NPT
TY4231 .. Pendent 8.0K, 3/4 in. NPT
TY4831 ... Upright 8.0K, 1/2 in. NPT
TY4931 .. Pendent 8.0K, 1/2 in. NPT
Technical
D a ta
Approvals
UL and C-UL Listed
FM , LPCB, and NYC Approved
See Tables A, B, C and D for complete
approval information including corrosion-
resistant status.
Maximum Working Pressure
See Table E
TFP171
TFP171
Page 2 of 12
* Temperature rating
is indicated on
Deflector.
** Pipe thread connections per
ISO 7-1 can be provided on
special request. ESCUTCHEON
PLATE SEATING
SURFACE
1 -Frame
2 -Button
3 -Sealing
Assembly
4 -Bulb
5 -Compression
Screw
6 -Deflector*
7 -Bushing
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
_._,___________~_L~
~~/~·~) I I.....J....__J----......_____,
7
3
2-3/16"
(55,6 mm)
1/2" NPT** WRENCH
1-9/16"
(39,7 mm)
L 2-7/8" (73,0 mm) DIA.
--'-'----4
1.r=-:;;----5
FLATS
UPRIGHT PENDENT
STYLE 10 or 20
RECESSED
ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 IN. NPT
* Temperature rating
is indicated on
Deflector.
** Pipe thread connections per
ISO 7-1 can be provided on
special request. ESCUTCHEON
PLATE SEATING
SURFACE
1 -Frame
2 -Button
3 -Sealing
Assembly
4 -Bulb
5 -Compression
Screw
6 -Deflector*
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
2-3/16"
(55,6 mm)
1/2" NPT** WRENCH
2-3/16"
(55,6 mm)
1-1/2"
(38,1 mm)
~ 2-7/8" (73,0 mm) DIA.
FLATS
UPRIGHT PENDENT
STYLE 1 0 or 20
RECESSED
ESCUTCHEON RECESSED PENDENT CROSS SECTION
FIGURE2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 112 IN. NPT
Discharge Coefficient
K=2.8 GPM/psi½ (40,3 LPM/bar½)
K=4.2 GPM/psi½ (60,5 LPM/bar½)
K=5.6 GPM/psi½ (80,6 LPM/bar½)
K=8.0 GPM/psi½ (115,2 LPM/bar½)
Temperature Rating
See Tables A and B
Finishes
Sprinkler: See Table D
Recessed Escutcheon: Signal or Pure White,
Grey Aluminum, Jet Black, Chrome Plated,
or Natural Brass
Physical Characteristics
Frame ............................ Bronze
Button ...................... Brass/Copper
Sealing Assembly .. Beryllium Nickel w/TEFLON
Bulb ............................... Glass
Compression Screw ................. Bronze
Deflector ................... Copper/Bronze
Bushing (K=2.8) .................... Bronze
Poly-Stainless
Physical Characteristics
Frame ............................ Bronze
Button ................ L316 Stainless Steel*
Bulb ............................... Glass
Compression Screw ..... L316 Stainless Steel*
Deflector ................... Copper/Bronze
Sealing Assembly . Gold Plated Beryllium Nickel
w/TEFLON
•Type L316 stainless steel (UNS 31603) per ASTM
A479/479M or BS EN 1008 WN1.4404.
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent,
and Recessed Pendent Sprinklers are
intended for fire protection systems
designed in accordance with the stan-
dard installation rules recognized by
the applicable Listing or Approval
agency, such as UL Listing based on
the requirements of NFPA 13 and FM
Approval based on the requirements
of the FM Global Loss Prevention Data
Sheets. Use only the style 10, 20, 30, or
40 Recessed Escutcheon, as applica-
ble, for recessed pendent installations.
\..-
TFP171
Page 3 of 12
* Temperature rating
is indicated on
Deflector.
** Pipe thread connections per
ISO 7-1 can be provided on
special request.
1 -Frame
2 -Button
3 -Sealing
Assembly
4 -Bulb
5 -Compression
Screw
6 -Deflector*
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
' I 2-3116" __j_ (55,6 mm)
~ j
STYLE 1 0 or 20 l---2-7 /8" (73,0 mm) DIA.
RECESSED 1/2"N~ENCH
FLATS
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
ALL FINISHES EXCEPT POLY-STAINLESS
WRENCH 1/2" ESCUTCHEON 1 -Frame 3 -Sealing 5 -Compression * Temperature
rating indicated
on Deflector.
FLATS NPT PLATE SEATING 2 -Button Assembly Screw
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
2-3/16"
(55,6 mm)
--,---1
SURFACE
2-3/16"
(55,6 mm)
STYLE 10
RECESSED
4 -Bulb 6 -Deflector*
1
3
UPRIGHT PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
POLY-STAINLESS FINISH ONLY
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 IN. NPT
Installation
The TYCO Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent, and
Recessed Pendent Sprinklers must
be installed in accordance with this
section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) and
3/32 in. (2,4 mm) for the 286°F (141°C)
temperature ratings. A leak-tight 1/2 in.
NPT sprinkler joint should be obtained
by applying a minimum-to-maximum
torque of 7 to 14 lb-ft (9,5 to 19,0 N·m).
A leak tight 3/4 in. NPT sprinkler joint
should be obtained with a torque of
10 to 20 lb-ft (13,4 to 26,8 N·m). Higher
levels of torque can distort the sprinkler
inlet and cause leakage or impairment
of the sprinkler. Do not attempt to com-
pensate for insufficient adjustment in
the escutcheon plate by under-or over-
tightening the sprinkler. Re-adjust the
position of the sprinkler fitting to suit.
Series TY-FRB Upright and Pendent
Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions:
Step 1. Install pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type 6
Sprinkler Wrench (Ref. Figure 14). With
reference to Figure 1 to Figure 5, apply
the W-Type 6 Sprinkler Wrench to the
sprinkler wrench flats.
Series TY-FRB Recessed Pendent
Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions:
Step 1. After installing the Style 10, 20,
30, or 40 Mounting Plate, as applica-
ble, over the sprinkler threads and with
pipe-thread sealant applied to the pipe
threads, hand-tighten the sprinkler into
the sprinkler fitting.
Step 2. Tighten the sprinkler into the
sprinkler fitting using only the W-Type 7
Recessed Sprinkler Wrench, see Figure
15. With reference to Figure 1 to 4,
apply the W-Type 7 Recessed Sprinkler
Wrench to the sprinkler wrench flats.
Step 3. After the ceiling is installed or
the finish coat is applied, slide on the
Style 10, 20, 30, or 40 Closure over
the Series TY-FRB Recessed Pendent
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
TFP171
Page 4 of 12
* Temperature rating
is indicated on
Deflector.
** Pipe thread connections per
ISO 7-1 can be provided on
special request.
1 -Frame
2 -Button
3 -Sealing 5 -Compression
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
_J 2-1/4"
(57,2 mm)
~ j
3/4" NP~ENCH
FLATS
UPRIGHT
ESCUTCHEON
PLATE SEATING
SURFACE
Assembly Screw
4 -Bulb 6 -Deflector*
---------..-=r _L ~
~~~:) I L-1-.---r-------,
1-9/16"
(39,7 mm)
STYLE 30 or 40 L RECESSED 2-7/8" (73,0 mm) DIA.
PENDENT ESCUTCHEON RECESSED PENDENT CROSS SECTION
ALL FINISHES EXCEPT POLY-STAINLESS
WRENCH
FLATS
3/4"
NPT
ESCUTCHEON
PLATE SEATING
SURFACE
1 -Frame 3 -Sealing 5 -Compression
2 -Button Assembly Screw
4 -Bulb 6 -Deflector*
* Temperature
rating indicated
on Deflector.
~-----,---1
1/2"
(12,7 mm)
NOMINAL
MAKE-IN _..___ _ ___._,.. _ _J 2-1/4"
(57,2 mm)
---i--1
UPRIGHT
2-5/16"
(58,7 mm)
STYLE 40
RECESSED
PENDENT ESCUTCHEON RECESSED PENDENT
POLY-STAINLESS FINISH ONLY
FIGURE4
CROSS SECTION
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 IN. NPT
3
2
CEILING PLATE
SEATING SURFACE
1 -Frame
2 -Button
3 -Sealing
5 -Compression
Screw
7/16"
(11,1 mm)
NOMINAL
MAKE-IN
,, I 2-3116"
__J_ (55,6 mm) 1
~ ~ j
1/2"N~ENCH
FLATS
I
2-1/4"
(57,2 mm)
UPRIGHT PENDENT CROSS SECTION
FIGURES
Assembly
4 -Bulb
6 -Deflector *
* Temperature rating is
indicated on Deflector.
** Pipe thread connections
per ISO 7-1 can be
provided on special
request.
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K-FACTOR, 1/2 IN. NPT
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,o mm) 3/4" (19, 1 mm)
2-1/4" DIA. 114" (6.4 mm)
(57'2 mm) MOUNTING
PLATE
1/8"
(3,2mm) « ...--.-~ j
-'----M-OU-NTIN~G ......----r'l----tl ,__~
SURFACE _______ ...,...
CLOSURE SERIES 1-5/16" (33,3 mm)
TY-FRB 13/16" (20,6 mm)
FIGURE6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 IN. NPT
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,o mm) 3/4" (19,1 mm)
2-1/4" DIA. 1/4" (6,4 mm)
(57•2 mm) MOUNTING
PLATE
1/8"
(3,2mm) « ...--.-~ j
~M-OU-NTIN~.........--.,t----1 ..._~
SURFAC1/ ~-: -------........
CLOSURE SERIES 1-1/4" (31,8 mm)
TY-FRB 3/4" (19,1 mm)
FIGURE8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 IN. NPT
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
\
MOUNTING
SURFACE
CLOSURE
TFP171
Page 5 of 12
2-7/8" DIA.
(73,0 mm) ;l 1/2" (12,7 mm)
2-1/4" DIA. --:-J 1/4" (6,4 mm)
(57•2 mm) r I MOUNTING 11,:;~E
i.==;z..'1::1::::=~it.ll~ L_l_m)
SERIES
TY-FRB
FIGURE 7
1-5/16" (33,3 mm)
1-1/16" (27,0 mm)
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 IN. NPT
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE SERIES
TY-FRB
FIGURE9
1-1/4" (31 ,8 mm)
1" (25,4 mm)
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 112 IN. NPT
TFP171
Page 6 of 12
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,o mm) 3/4" (19, 1 mm)
2-1/4" DIA. 114" (6.4 mm)
(57•2 mm) MOUNTING
PLATE
1/8"
(3,2mm) ~ ~~ j
_._____M--.-OU-NTI N~G --•-,.__.s:::z=,
SURFACE -------+-
CLOSURE SERIES 1-1/4" (31,8 mm)
TY-FRB 3/4" (19,1 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5/8±1/4"
(15,9±6,4 mm)
5.6 K-FACTOR, 1/2 IN. NPT
2-7/8" DIA.
2_114,, DIA. 1/4" (6,4 mm)
FACE OF
SPRINKLER
FITTING
(73,0 mm) =;13/4" (19,1 mm)
(57•2 mm) ---J MOUNTING _JI PLATE
~,-~m)
_.____M--.-OU-NTI~
SURFACE
~=:2tca
CLOSURE SERIES
TY-FRB
FIGURE 12
1-5/16" (33,3 mm)
13/16" (20,6 mm)
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 IN. NPT
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 14
W-TYPE 6 SPRINKLER
WRENCH
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
\
MOUNTING
SURFACE
CLOSURE
2-7/8" DIA.
(73,o mm) ;11/2" (12,7 mm)
2-1/4" DIA. --:-j 1/4" (6,4 mm)
(57•2 mm) r I MOUNTING 11,~;~E
i.==;;:c..\1:il:::=td!4~ L_l_m)
SERIES
TY-FRB
FIGURE 11
1-1/4" (31,8 mm)
1" (25,4 mm)
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 IN. NPT
2-7/8" DIA.
112±1/8" (73,0 mm) =;11/2" (12,7 mm)
(12,7±3,2 mm) 2_11411 DIA. 1/4" (6,4 mm)
FACE OF ~ (
57
'2 mm) ---J MOUNTING
SPRINKLER _J I PLATE
FITTING ~
I
1/8"
_,__ _ ___.__ __ 4-------=----"""'===----,,■ (3,2 mm)
-,--.--~ ~--■m.;-=1 MO~NTIN0. SURFACE
~;;;cctCII
CLOSURE SERIES 1-5/16" (33,3 mm)
TY-FRB 1-1/16" (27,0 mm)
FIGURE 13
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1 /2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 IN. NPT
WRENCH
RECESS
t
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
K-Factor Type Temperature Bulb Liquid
Color Natural
Brass
135°F (57°C) Orange
155°F (68°C) Red
Pendent 175°F (79°C) Yellow (TY1231)
200°F (93°C) Green
286°F (141°C) Blue
135°F (57°C) Orange
155°F (68°C) Red
Upright (TY1131) 175°F (79°C) Yellow
2.8 200°F (93°C) Green
1/2 in. NPT 286°F (141°C) Blue
135°F (57°C) Orange
Recessed 155°F (68°C) Red Pendent
(TY1231)3 175°F (79°C) Yellow Figure 6
200°F (93°C) Green
135°F (57°C) Orange
Recessed 155°F (68°C) Red Pendent
(TY1231)b 175°F (79°C) Yellow Figure 7
200°F (93°C) Green
NOTES
a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable.
b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
c. Frame and Deflector only.
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
Sprinkler Finishs
I Chrome Plated I
1,2,3,4
1,2,4
TFP171
Page 7 of 12
Polyesterc
5. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corrosion-resistant
sprinklers.
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
2.8 K-FACTOR SPRINKLERS
TFP171
Page 8 of 12
K-Factor
4.2
1/2 in. NPT
NOTES
Type
Pendent
(TY2231}
Upright (TY2131}
Recessed
Pendent
(TY2231}3
Figure 8
Recessed
Pendent
(TY2231)b
Figure 9
Temperature
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141 °C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
Bulb Liquid Natural Color
Brass
Orange
Red
Yellow
Green
Blue
Orange
Red
Yellow
Green
Blue
Orange
Red
Yellow
Green
Orange
Red
Yellow
Green
a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable.
b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
c. Frame and Deflector only.
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Sprinkler Finish3
I Chrome Plated I Polyesterc
1, 2
3. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corrosion-resistant
sprinklers.
TABLEB
LABORATORY LISTINGS AND APPROVALS FOR
4.2 K-FACTOR SPRINKLERS
TFP171
Page 9 of 12
Sprinkler Finishs
K-Factor Type Temperature Bulb Liquid
I I Polyester' Lead Color Natural Chrome Poly-Stainlessc Brass Plated Coated
135°F (57°C) Orange
155°F (68°C) Red
Pendent 175°F (79°C) Yellow 1,2,3,4,5,6, 7 1, 2 1,2,3, 5 (TY3231)
200°F (93°C) Green
286°F (141°C) Blue
135°F (57°C) Orange
155°F (68°C) Red
Upright 175°F (79°C) Yellow 1,2,3,5,6 1, 2 1,2,3,5 (TY3131)
200°F (93°C) Green
5.6 286°F (141°C) Blue 1/2 in. 135°F (57°C) Orange NPT
Recessed 155°F (68°C) Red
Pendent 175°F (79°C) Yellow 1,2,4,5 1, 2 N/Ad (TY3231)8
Figure 10 200°F (93°C) Green
286°F (141°C) Blue
135°F (57°C) Orange
Recessed 155°F (68°C) Red
Pendent 175°F (79°C) Yellow 1,2,3,4,5 N/A N/A (TY3231)b
Figure 11 200°F (93°C) Green
286°F (141°C) Blue
NOTES
a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable.
b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
C. Frame and Deflector only.
d. Not available (N/A).
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 00?k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed
sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31 -53-428-4444/Fax 31-53-428-3377.)
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where
Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers.
TABLEC
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
TFP171
Page 10 of 12
Sprinkler Finish8
K-Factor Type Temperature Bulb Liquid
I Chrome I Polyesterc Lead Color Natural
Brass Plated Poly-Stainlessc Coated
135°F (57°C) Orange
155°F (68°C) Red
Pendent 175°F (79°C) Yellow (TY4231)
200°F (93°C) Green
286°F (141°C) Blue 1,2,3,4,5,6, 7 1, 2 1,2,5 135°F (57°C) Orange
155°F (68°C) Red
Upright 175°F (79°C) Yellow (TY4131)
200°F (93°C) Green
8.0 286°F (141°C) Blue 3/4 in. 135°F (57°C) Orange NPT
Recessed 155°F (68°C) Red Pendent 175°F (79°C) Yellow 1,2,5 1, 2 N/Ad (TY4231)a
Figure 12 200°F (93°C) Green
286°F (141°C) Blue
135°F (57°C) Orange
Recessed 155°F (68°C) Red
Pendent 175°F (79°C) Yellow 1,2,3,5 N/A N/A (TY4231)b
Figure 13 200°F (93°C) Green
286°F (141°C) Blue
135°F (57°C) Orange
155°F (68°C) Red
Pendent 175°F (79°C) Yellow (TY4931)
200°F (93°C) Green
8.0 286°F (141°C) Blue 1/2 in. 1,2,4,5,6 N/A 1, 2, 5
NPT 135°F (57°C) Orange
155°F (68°C) Red
Upright 175°F (79°C) Yellow (TY4831)
200°F (93°C) Green
286°F (141°C) Blue
NOTES
a. Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable.
b. Installed with Style 20 (1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
C. Frame and Deflector only.
d. Not available (N/A).
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers. However, LPCB does not rate the thermal sensitivity of recessed
sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377.)
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead-Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers. Where
Lead-Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a Corrosion-Resistant Sprinklers.
TABLED
LABORATORY LISTINGS AND APPROVALS FOR
5.6 AND 8.0 K-FACTOR SPRINKLERS
K-Factor Type
Pendent (TY1231)
and 2.8 Upright (TY1131) 1/2 in.
NPT Recessed
Pendent (TY1231)
Pendent (TY2231)
and
4.2 Upright (TY2131)
1/2 in.
NPT Recessed
Pendent (TY2231)
Pendent (TY3231)
and 5.6 Upright (TY3131)
1/2 in.
NPT Recessed
Pendent (TY3231)
Pendent (TY4231)
and
8.0 Upright (TY4131)
3/4 in.
NPT Recessed
Pendent(TY4231)
8.0 Pendent (TY4931)
1/2 in. and
NPT Upright (TY4831)
NOTES
Sprinkler Finish
Natural I Chrome I Brass Plated Polyester
175 psi (12,1 bar)
175 psi (12,1 bar)
250 psi (17,2 bar)
or 175 psi (12,1 bar)1
175 psi (12,1 bar)
175 psi (12,1 bar)
TFP171
Page 11 of 12
Lead Coated
N/A2
N/A
175 psi
(12,1 bar)
N/A
175 psi
(12,1 bar)
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in
Canada (C-UL); and, the Approval by the City of New York.
2. Not available (N/A).
Care and
Maintenance
The TYCO Series TY-FRB 2.8, 4.2, 5.6,
and 8.0 K-factor Upright, Pendent, and
Recessed Pendent Sprinklers must be
maintained and serviced in accordance
with this section. Before closing a fire
protection system main control valve
for maintenance work on the fire pro-
tection system that it controls, obtain
permission to shut down the affected
fire protection systems from the proper
authorities and notify all personnel who
may be affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
TABLEE
MAXIMUM WORKING PRESSURE
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be taken to avoid damage
to the sprinklers before, during, and
after installation. Sprinklers damaged
by dropping, striking, wrench twist/
slippage, or the like, must be replaced.
Also, replace any sprinkler that has
a cracked bulb or that has lost liquid
from its bulb. For more information, see
Installation section.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Associ-
ation such as NFPA 25, in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or sprinkler manufac-
turer regarding any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified lnspec-
tion Service in accordance with local
requirements and/or national codes.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. For more informa-
tion, see Installation section.
Initial and frequent visual inspections of
random samples are recommended for
corrosion-resistant sprinklers to verify
the integrity of the corrosion-resis-
tant material of construction. There-
after, annual inspections per N FPA 25
should suffice. Inspections of corro-
sion-resistant sprinklers are recom-
mended at close range, instead of from
the floor level per NFPA. Inspection at
close range can better determine the
exact sprinkler condition and the long-
term integrity of the corrosion-resistant
material, which can be affected by the
corrosive conditions present.
TFP171
Page 12 of 12
P/N 57 -XXX -X -XXX
I I
TEMPERATURE SIN SPRINKLER RATINGS
FINISH
330 2.8K UPRIGHT (1/2 in. NPT) TY1131 135 135°F (57°C)
1 NATURAL BRASS
331 2.8K PENDENT (1/2 in. NPT) TY1231 POLY-STAINLESS GREY 155 155°F (68°C)
2 ALUMINUM (RAL9007)1
340 4.2K UPRIGHT (1/2 in. NPT) TY2131 POLYESTER 175 175°F (79°C)
3 PURE WHITE
341 4.2K PENDENT (1/2 in. NPT) TY2231 POLYESTER (RAL9010)2 200 200°F (93°C)
4 SIGNAL WHITE
370 5.6K UPRIGHT (1/2 in. NPT) TY3131 POLYESTER (RAL9003) 286 286°F (141°C)
5 JET BLACK
371 5.6K PENDENT (1/2 in. NPT) TY3231 POLYESTER (RAL9005)3
390 8.0K UPRIGHT (3/4 in. NPT) TY4131 7 LEAD COATED
391 8.0K PENDENT (3/4 in. NPT) TY4231 9 CHROME PLATED
360 8.0K UPRIGHT (1/2 in. NPT) TY4831 NOTES
1. Available only on TY3131, TY3231 , TY4131 , and TY4231
2. Eastern Hemisphere sales only.
361 8.0K PENDENT (1/2 in. NPT) TY4931 3. Available in only 2.8K, 4.2K, and 8.0K, 155°F {68°C) and 200°F (93°C); requires longer
lead time to manufacture.
TABLE F
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
PART NUMBER SELECTION
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name and Part
Number (P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB (Specify SIN),
(specify K-factor), (specify Pendent or
Upright) Sprinkler (specify) temperature
rating, (specify) finish or coating, P/N
(specify from Table F)
Recessed Escutcheon
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify*)
finish, P/N (specify*)
• Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
1400 Pennbrook Parkway, Lansdale, PA 19446 I Telephone +1-215-362-0700
C 2020 Johnson Controls. All rights reserved. All specifications and other Information shown were current as of document revision date and are subject to change without notice.
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; TEFLON is a registered trademark of DuPont
Johnson ~Jt;
Controls
GENERAL INFORMATION
GENERAL INFORMATION
HANGERMATE®
Rod Hanging Anchors
PRODUCT DESCRIPTION
Hangermate is an all steel threaded fastening system for suspending steel threaded rod vertically
overhead in pipe hanging, fire protection, electrical conduit and cable-tray applications. They are
available in versions which can be installed in a variety of base materials including steel purlins, bar
joists and beams, wood frame columns and beams, as well as concrete ceilings, beams and columns.
Steel threaded rods in 1 /4" and 3/8" diameters can be vertically suspended with Hangermate
(a 1 /2" diameter size is also available for wood). They are also offered in a side mount style for
lateral installation of 1/4" and 3/811 diameter steel threaded rods onto joists, columns and overhead
members. For all steel and wood hangers, a Hangermate Socket Driver is recommended to provide
proper installation with a drill screw gun. For concrete hangers, a powered impact tool with a clutch
is recommended.
A pivot head version is also available for flexible connection angle and positioning of rod hangers.
An acoustical ceiling eyelet version is also available for hanging wire or cable attachments.
GENERAL APPLICATIONS AND USES
• Hanging Pipe and Sprinkler Systems • HVAC Ductwork and Strut Channels
• Suspending Conduit and Cable Trays • Suspended Ceilings
• Lighting Systems and Overhead Utilities • Mounting Security Equipment
FEATURES AND BENEFn'S
+ Ease and speed of overhead installation
+ Lower in-place cost, when compared to beam clamps, lag bolts and dropins
+ Steel and wood Hangermate can be installed with a drill screw gun
+ Side mount versions available for steel and wood Hangermate
+ Socket drivers, pole tool and accessories to optimize ease of installation
APPROVALS AND LISTINGS
• FM Approvals (FM) -see listing for applicable sizes and types
Pipe Hangers components for automatic sprinkler systems -File No. JI 3015153
• Underwriters Laboratory (UL) -see listing for applicable sizes and types
Pipe Hangers -File No. EX 1289
GUIDE SPECIFICATIONS
CSI Divisions: 03 16 00 -Concrete Anchors, 05 05 23 -Metal Fastenings and 06 05 23 -Wood,
Plastic, and Composite Fastenings. Rod Hangers shall be Hangermate anchors as supplied by
DEWALT, Towson, MD. Anchors shall be installed in accordance with published instruction and the
§ Authority Having Jurisdiction.
z ~
G> C: ~
I
3:::
i ~
! ~ en ;
;
~
I
~
0
DEWALT.
ANCHORS & FASTENERS
SECTION CONTENTS
General Information ......................... 1
Material Specifications ................... 2
Installation Specifications .............. 2
Performance Data ............................ 3
Ordering Information ....................... 5
STEEL HANGERMATE
WOOD HANGERMATE
CONCRETE HANGERMATE
ANCHOR MATERIALS
• Zinc Plated Carbon Steel
ANCHOR SIZE RANGE (TYP.)
• 1/411 to 3/8" for Steel
• 1 /4" to 1 /2" for Wood
• 1/4" to 3/8" for Concrete
(Threaded Coupler Heads)
THREAD VERSION
• Unified Coarse Thread (UNC)
SUITABLE BASE MATERIALS
• Steel Purlins and Beams
• Wood and Timber
• Concrete Members
www.DEWALT.com
DEWAL1:
ANCHORS & FASTENERS MATERIAL SPECIFICATIONS
MATERIAL SPECIFICATIONS
r.omponent Component Materlal
Screw Body Case hardened carbon steel
Coupling (UNC thread) / Eyelet Case hardened carbon steel
Zinc Plating ASTM B633, SC1, Type Ill (Fe/Zn5)
INSTALLATION SPECIFICATIONS
Steel Hangermate Wood Hangennate
Rod Coupler Size 1/411 318" Rod Coupler Size 1/411 3/8" 1/211
Coupling Thread Size (UNC) 1/4-20 3/8-16 Coupling Thread Size (UNC) 1/4-20 3/8-16 1/2-13
Coupling Thread Depth (in.) 3/8 3/8 Coupling Thread Depth (in.) 3/8 3/8 3/8
Coupling Height (in.) 3/4 3/4 Coupling Height (in.) 13/16 13/16 13/16
Socket Driver Size (in.) 1/2 1/2 Socket Driver Size (in.) 5/8 5/8 5/8
Note: the side mount couplings have full thread depth (through head). Note: the side mount couplings have full thread depth (through head).
Concrete Hangennate
Rod Coupler Size 1/411
ANSI Drill Bit (in.) 1/4
Overall Screw Shank Length 1-1/4
Anchor Thread Length (in.) 1-1/8
Coupler/ Washing Height (in.) 27/64
Integral Washer 0.0. (in.) 31/64
Coupling Thread Size (UNC) 1/4-20
Coupling Thread Depth (in.) 3/8
Socket Driver Size (in.) 3/8
Installation Guidelines
1 . If pre-drilling is required (certain types of wood
truss/wood joist and all concrete base materials),
select the recommended drill bit type and diameter.
For Concrete Hangermate, drill a hole to the
appropriate embedment depth, adding at least 1/4"
to the drilling depth to prevent the tip of the fastener
from running into the back of the anchor hole during
installation.
318"
1/4
1-1/2
1-3/8
9/16
39/64
3/8-16
1/2
1/2
2. Select the appropriate socket driver for the anchor
size and type to be installed and mount into chuck of
installation tool. Insert the Hangermate coupling into
the socket driver, and install perpendicular to the base
material surface. Drive the fastener with a smooth
steady motion until the driver and coupling is seated
against the surface of the base material.
3. Thread the appropriate diameter steel threaded
rod or threaded bolt into the coupling. The threaded
rod or bolt should fully engage the thread length
of the coupling on a vertical mount fastener. The
threaded rod or threaded portion of the bolt can pass
through coupling of a side mount fastener.
When installing Hangermate, eye protection should be worn as a safety precaution.
For UL and/or FM listings for hangers Steel Hangermate should be installed with a retaining nut for parts that are packaged with a nut (see performance data and listings as applicable).
Suggested drill speed for Steel Hangermate installations is 1200 to 1800 rpm.
Steel Wood Concrete
Install with appropriate sized steel socket driver. Install with appropriate sized wood socket driver. Install with appropriate sized concrete socket driver.
(side and variable mount direction versions not pictured) (side and variable mount direction versions not pictured) (variable mount direction version not pictured)
1-aD0-4 DEWALT.
DEWALT.
PERFORMANCE DATA ANCHORS & FASTENERS
PERFORMANCE DATA
Hangermate for Steel -General
Rod Min. Max. UL FM
cat. No. Screw Mount Coupler Driver# 111lck. Thick. Description Direction Max. UL Max. FM Size In. In. Pipe Size Thick. Pipe Size Thick.
Hangennate For Steel -Vertical
PFM2231000 1/4-20 1" #3 Vert. 1/4" PFM2201200 (Silver) 0.060 0.210 ---
PFM2231100 1/4-20 X 1" #3 Vert. 3/8" PFM2201200 (Silver) 0.060 0.210 4" 0.060" -
PFM223110N 1/4-20 x 1" #3/nut Vert. 3/8" PFM2201200 (Silver) 0.060 0.210 4" 0.125" 4" 0.105"
PFM2231150 1/4"-20 X 1-1/2" #5 Vert. 3/8" PFM2201200 (Silver) 0.125 0.500 4" 0.060" 4" 0.060"
PFM223115N 1/4-20 x 1-1/2" #5/nut Vert. 3/8" PFM2201200 (Silver) 0.125 0.500 4" 0.125" 4" 0.105"
PFM2231200 1/4-20 X 1-1/2" #3 Vert. 3/8" PFM2201200 (Silver) 0.060 0.210 4" 0.060" -
PFM223120N 1/4-20 x 1-1/2" #3/nut Vert. 3/8" PFM2201200 (Silver) 0.060 0.210 4" 0.060" --
PFM2231250 1 /4-20 X 2" #3 Vert. 3/8" PFM2201200 (Silver) 0.060 0.210 4" 0.125"
Hangennate For Steel -Horizontal
PFM2241100 1 / 4-20 X 1 " #3 Side 3/8" PFM2201200 (Silver) 0.060 0.210 --
PFM224110N 1/4-20 x 1" #3/nut Side 3/8" PFM2201200 (Silver) 0.060 0.210 4" 0.060" 4" 0.060"
PFM2241150 1/4-20 X 1-1/2" #3 Side 3/8" PFM2201200 (Silver) 0.060 0.210 --
PFM224115N 1 /4-20 x 1-1 /2" #3/nut Side 3/8" PFM2201200 (Silver) 0.060 0.210 4" 0.060" 4" 0.060"
PFM2241200 1/4-20 X 1-1/2" #5 Side 3/8" PFM2201200 (Silver) 0.125 0.500 --
PFM224120N 1 /4-20 x 1-1 /2" #5/nut Side 3/8" PFM2201200 (Silver) 0.125 0.500 4" 0.060" 4" 0.060"
Hangennate Pivot For Steel -Angled Appllcatlons
PFM2281150 1/4-20 X 1" #3 Variable 3/8" PFM2201250 0.060 0.188 ---
PFM2281200 12-20 X 1-3/4" #5 Variable 3/8" PFM2201250 0.125 0.500 -
PFM2281250 1/4-14 X 1" #3 Variable 3/8" PFM2201250 0.060 0.188 --
Hangennate Few Steel -Acoustical Celllng Screw Eyelet
PFM2231500 1/4-14 x 7/8" #2 (3/16" eyelet) Variable PFM2201350 0.060 0.105 ---
PFM2231550 1 /4-14 x 2 #2 (3/16" eyelet) Variable -PFM2201350 0.060 0.105 --
Hangermate for Steel -Ultimate Load Capacities when Installed in Steel1
Mount Rod Steel Gauge I 1111ckness
Cal No. Screw Description Direction Coupler 1610.060 1410.075 1210.105 1/810.125 3/1610.187 1/410.250 1/210.500 Size lbs. lbs. lbs. lbs. lbs. lbs. lbs.
Hangennate For Steel -Vertical
PFM2231000 1/4-20 1" #3 Vertical 1/4 785 1,140 1,740 2,375 2,820 --
PFM2231100 1/4-20 X 1" #3 Vertical 3/8 785 1,140 1,740 2,375 4,695 --
PFM223110N 1 /4-20 x 1" #3/nut Vertical 3/8 3,435 4,025 4,280 4,690 5,810 --
PFM2231150 1/4 -20 X 1-1/2" #5 Vertical 3/8 ---3,675 5,205 5,205
PFM223115N 1/4-20 x 1-1/2" #5/nut Vertical 3/8 3,435 4,025 4,280 4,690 5,810 5,810 5,810
PFM2231200 1/4-20 X 1-1/2" #3 Vertical 3/8 785 1,140 1,740 2,375 4,695 --
PFM223120N 1/4-20 x 1-1/2" #3/nut Vertical 3/8 3,435 4,025 4,280 4,690 4,695 -
PFM2231250 1/4-20 X 2" #3 Vertical 3/8 785 1,140 1,740 2,375 4,695 --
Hangennate For Steel -Horizontal
PFM2241100 1/4-20 X 1" #3 Side 3/8 1,740 1,945 2,420 2,570 2,810 -
PFM224110N 1/4-20 x 1" #3/nut Side 3/8 2,755 2,810 2,570 2,810 2,810 -
PFM2241150 1/4-20 X 1-1/2" #3 Side 3/8 1,740 1,945 2,420 2,570 2,810
PFM224115N 1/4-20 x 1-1/2" #3/nut Side 3/8 2,755 2,810 2,570 2,810 2,810 -
PFM2241200 1/4-20 X 1-1/2" #5 Side 3/8 -2,205 2,810 2,810
PFM224120N 1/4-20 x 1-1/2" #5/nut Side 3/8 2,755 2,810 2,570 2,810 2,810 2,810 2,810
Hangennate Pivot For Steel -Angled Appllcatlons
PFM2281150 1/4-20 X 1" #3 Variable 3/8 635 -Vert. 635 -Vert. 1,130 -Vert. 1,130 -Vert. 1,640 -Vert. --(875@45°} (875@45°} (875@45°) (875@45°) (875@45°)
PFM2281200 12-20 X 1-3/4" #5 Variable 3/8 635 -Vert. 635 -Vert. 1,130-Vert. 1,130 -Vert. 1,640 -Vert. 1,640 -Vert. 1,640 -Vert.
(875@45°) (875@45°) (875@ 45°) (875@45°) (875@45°) (875 @45°) (875@ 45°)
PFM2281250 1 / 4-14 x 1 " #3 Variable 3/8 590 -Vert. 590 -Vert. 970 -Vert. 970-Vert. 1,640-Vert. --(875@45°) (875@45°) (875@45°) (875 @45°) (875 @45°)
Hangennate Few Steel -Acoustical Celling Screw Eyelet
PFM2231500 3/16 X 2" #2 Variable -800 800 1,245 ---
PFM2231550 3/16 X 3-1/4 #2 Variable -800 800 1,245 ---
1. The values listed above are ultimate load capacities which should be reduced by a minimum safety factor of 3.0 or greater to determine the allowable working load.
2. The strength of the threaded rod used with the Hangermate anchors must be considered when determining the controlling load capacity of the assembly.
www.DEWALT.com
DEWALT.
ANCHORS & FASTENERS PERFORMANCE DATA
Hangermate for Wood -Ultimate Load capacities when Installed in Wood1·2
Screw Mount Rod UL FM
cat. No. Description Direction Coupler Driver# Load lbs*
Size Max. Pipe Size Max. Pipe Size
Hangennata For Wood -Vertical
PFM2251000 1/4" X 2" Vert. 1/4" PFM2201150 (Red) 1,510 -
PFM2251050 1/4" X 1" Vert. 3/8" PFM2201150 (Red) 650 -
PFM2251100 1/4" X 2" Vert. 3/8" PFM2201150 (Red) 1,510 3"
PFM2251150 5/16" X 2-1/2" Vert. 3/8" PFM2201150 (Red) 2,670 4" 4"
PFM2251200 1/4" X 3" Vert. 3/8" PFM2201150 (Red) 2,075 3" -
PFM2251250 1/4" X 4" Vert. 3/8" PFM2201150 (Red) 2,075 3" -
PFM2251300 5/16" X 2-1/2" Vert. 1/2" PFM2201150 (Red) 2,670 --
Hangennate For Wood -Horizontal
PFM2261000 1/4" X 1" Side 1/4" PFM2201150 (Red) 650 -
PFM2261050 1/4" X 1" Side 3/8" PFM2201150 (Red) 650 -
PFM2261100 1/4" X 2" Side 3/8" PFM2201150 (Red) 1,800 3" -
PFM2261150 5/16" X 2-1/2" Side 3/8" PFM2201150 (Red) 1,450 3" -
Hangennata Pivot For Wood -Angled Applications
1,470 (Vert.) --PFM2281100 1/4" X 2" Variable 3/8" PFM2201250 1,155 (45°) -
Hangennata For Wood -Acoustical Celllng Screw Eyelet
PFM2251500 3/16" X 3-1/4" Variable PFM2201350 880
*Ultimate Loads In Douglas Fir, Pine and Spruce
1. Truss/joist manufacturers may require pre-drilled holes with wood depending on the location of the anchor installation. Consult with the truss/joist manufacturer for details.
2. The values listed above are ultimate load capacities that must be reduced by a minimum safety factor of 3.0 or greater to determine the allowable working load.
Concrete Hangermate -Ultimate Load Capacities when Installed in Normal-Weight Concrete1•2•3
Minimum Concrete Compressive Strength (fc)
Rod Coupler Screw Mount ANSI Drill Bit Embed. 2,000 psi 4,000 psi 6,000 psi Cat No. Size Diameter Depth
In. Description Direction In. In. Tension Shear Tension Shear Tension Shear
lbs. lbs. lbs. lbs. lbs. lbs.
PFM2217171 1/4 1/4" X 1-1/4" Vertical 1/4 1-1/4 1,390 1,810 1,950 2,440 2,070 2,570
PFM2217173 3/8 1/4" X 1-1/2" Vertical 1/4 1-1/2 1,760 2,580 2,595 2,640 2,770 2,700
1. The values listed above are ultimate load capacities for anchors installed in uncracked normal weight concrete.
2. The values listed above are ultimate load capacities which must be reduced by a minimum safety factor of 4.0 or greater to determine the allowable working load.
3. Linear interpolation may be used to determine load capacities for intermediate compressive strengths.
Concrete Hangermate -Ultimate Load Capacities when Installed Through Metal Deck into Lightweight Concrete1·2•3·4
Lightweight Concrete 0Ver Metal Deck f c ~ 3,000 psi
Rod Coupler Screw Mount ANSI Drlll Bit Embecmant 4-1/211 Wide Deck cat No. Size Description Direction Diameter Depth
In. In. In. Tension Load at45°
lbs. lbs.
PFM2217171 1/4 1/4" X 1-1/4" Vertical 1/4 1-1/4 800 1,140
PFM2217173 3/8 1/4" X 1-1/2" Vertical 1/4 1-1/2 1,780 1,500
1. The values listed above are ultimate load capacities for anchors installed in uncracked sand-lightweight concrete.
2. The metal deck shall not exceed 18 gauge (0.048-inch base metal thickness) and conform to ASTM A 653.
3, The values listed above are ultimate load capacities which must be reduced by a minimum safety factor of 4.0 or greater to determine the allowable working load.
4. The tabulated load values are for anchors installed with a mini'!]um lower flute edge distance of 1-1 /8-inch; or in the upper flute with consideration for integral washer clearance.
Concrete Hangermate -Ultimate Load capacities when Installed In Hollow Core Concrete Plank1 •2
Rod Coupler Size ANSI DrlU Bit Embedment Depth Tension, Tension,
cat No. Screw Description Mount Direction Diameter Center of Web Center of Cora In. In. in. lbs. lbs.
PFM2217171 1/4 1/4"x1-1/4" Vertical 1/4 1-1/4 2,775 1,920
PFM2217173 3/8 1/4" X 1-1/2" Vertical 1/4 1-1/2 3,700 2,570
1. Tabulated load values are for anchors installed in 8-inch-thick uncracked hollow core concrete with minimum compressive strength of 5,000 psi at the time of installation. The normal-weight
concrete must have 1-1 /2" cover above and below cores and a minimum web thickness of 1-1 /2".
2. The values listed above are ultimate load capacities which must be reduced by a minimum safety factor of 4.0 or greater to determine the allowable working load.
Concrete Hangermate -Factory Mutual (FM Global) Listings for Pipe Hangers
Rod Coupler Size ANSI Drlll Bit Embedment Depth FM Max. cat. No. Screw Description Mount Direction Diameter In. In. In. Pipe Size
PFM2217173 3/8 1/4"x1-1/2" Vertical 1/4 1-1/2 4"
1-BD0-4 DEWALT.
<n
@ s;? W o !ii; a ~ a: w c., z ◄ :c
Cl
it a:
I
~ a5 Cl
N 0 @
~ 0 o ~
3 ! ~
I LU Cl 5 0
3 ~
DEWAL1:
ORDERING INFORMATION ANCHORS & FASTENERS
ORDERING INFORMATION
Hangermate for Steel -Vertical
Cat.No. Description Driver # (Sliver) Mount Rod Size Box Qty. Carton Qty.
PFM2231000 1 / 4-20 X 1 " #3 PFM2201200 Vertical 1/4" 25 125
PFM2231100 1/4-20 X 1" #3 PFM2201200 Vertical 3/8" 25 125
PFM223110N 1/4-20 x 1" #3/nut PFM2201200 Vertical 3/8" 25 125
PFM2231150 1/4"-20 X 1-1/2" #5 PFM2201200 Vertical 3/8" 25 125
PFM223115N 1/4-20 x 1-1 /2" #5/nut PFM2201200 Vertical 3/8" 25 125
PFM2231200 1/4-20 X 1-1/2" #3 PFM2201200 Vertical 3/8" 25 125
PFM223120N 1/4-20x1-1/2" #3/nut PFM2201200 Vertical 3/8" 25 125
PFM2231250 1/4-20 X 2" #3 PFM2201200 Vertical 3/8" 25 125
Hangermate for Steel -Horizontal
cat. No. Description Driver # (Silver) Mount Rod Size Box Qty. Carton Qty.
PFM2241100 1 / 4-20 X 1 " #3 PFM2201200 Side 3/8" 25 125
PFM224110N 1/4-20 x 1" #3/nut PFM2201200 Side 3/8" 25 125
PFM2241150 1/4-20 X 1-1/2" #3 PFM2201200 Side 3/8" 25 125
PFM224115N 1/4-20 x 1-1/2" #3/nut PFM2201200 Side 3/8" 25 125
PFM2241200 1/4-20 X 1-1/2" #5 PFM2201200 Side 3/8" 25 125
PFM224120N 1/4-20 x 1-1/2" #5/nut PFM2201200 Side 3/8" 25 125
Hangermate Pivot for Steel -Angled Applications
Cat. No. Description Pivot Driver # Mount Rod Size Box Qty. Carton Qty.
PFM2281150 1/4-20 X 1" #3 PFM2201250 Variable 3/8" 25 125
PFM2281200 12-20 X 1-3/4" #5 PFM2201250 Variable 3/8" 25 125
PFM2281250 1/4-14 X 1" #3 PFM2201250 Variable 3/8" 25 125
Hangermate Acoustical Ceiling Eyelet for Steel
Cat.No. Description Eyelet Driver # Mount Eyelet Box Qty. Carton Qty. Hole
PFM2231500 3/16" X 2" PFM2201350 Variable 3/16" 25 125 1/4-14 x 7/8" #2 screw
PFM2231550 3/16" X 3-1/4" PFM2201350 Variable 3/16" 25 125 1/4-14 x 2" #2 screw
Hangermate for Wood -Vertical
Cat.No. Description Driver # (Red) Mount Rod Size Box Qty. Carton Qty.
PFM2251000 1/4" X 2" PFM2201150 Vertical 1/4" 25 125
PFM2251050 1/4" X 1" PFM2201150 Vertical 3/8" 25 125
PFM2251100 1/4" X 2" PFM2201150 Vertical 3/8" 25 125
PFM2251150 5/16" X 2-1/2" PFM2201150 Vertical 3/8" 25 125
PFM2251200 1/4" X 3" PFM2201150 Vertical 3/8" 25 125
PFM2251250 1/4" X 4" PFM2201150 Vertical 3/8" 25 125
PFM2251300 5/16"x 2-1/2" PFM2201150 Vertical 1/2" 25 125
Hangermate for Wood -Horizontal
Cat.No. Description Driver # (Red) Mount Rod Size Box Qty. Carton Qty.
PFM2261000 1/4" X 1" PFM2201150 Side 1/4" 25 125
PFM2261050 1/4" X 1" PFM2201150 Side 3/8" 25 125
PFM2261100 1/4" X 2" PFM2201150 Side 3/8" 25 125
PFM2261150 5/16" X 2-1/2" PFM2201150 Side 3/8" 25 125
Hangermate Pivot for Wood -Angled Applications
cat. No. Description Pivot Driver # Mount Rod Size Box Qty. Carton Qty.
PFM2281100 1/4" X 2" PFM2201250 Variable 3/8" 25 125
Hangermate Acoustical Ceiling Eyelet for Wood
I Cat.No. Description Eyelet Driver # Mount Eyelet Hole Box Qty. Carton Qty.
~ PFM2251500 3/16" X 3-1/4" PFM2201350 Variable 3/16" 25 125
CJ
www.DEWALT.com
DEWAL1:
ANCHORS & FASTENERS
Hangermate for Concrete -Vertical1
Cat.No. Description Driver # (Black) Mount Rod Size Box Qty. Carton Qty.
PFM2217171 1/4"x1-1/4" PFM1491050 Vertical 1/4" 100 600
PFM2217173 1/4" X 1-1/2" PFM1491100 Vertical 3/8" 100 600
1. Concrete Hangermate require a pre-drilled hole using a 1/4" ANSI carbide drill bit (e.g. DW5517).
Hangermate Pivot for Concrete -Angled Applications1·2
Cat. No. Description Pivot Driver # Mount Rod Size Box Qty. Carton Qty.
PFM2281300 3/16" X 2" PFM2201250 Variable 3/8" 25 125
1. The Hangermate Pivot for concrete require a pre-drilled hole using a 3/16" ANSI carbide drill bit (e.g. DW5402).
2. Ultimate load capacity for the Hangermate Pivot for concrete is 875 lbs. The ultimate load capacities must be reduced by a minimum
safety factor of 4.0 or greater to determine the allowable working load.
Concrete Installation Accessories and Tool Guide
Drllllng
Description Rotary Hammar SOS+ Bit Max Torque
(ft-lb.)
Cal No.
1/4" Vertical Hanger DW5416
PFM2217171 DCH273P2DH DW5517 1/4" X 1-1/4" (1/4'')
150
3/8" Vertical Hanger DW5416
PFM2217173 DCH273P2DH DW5517 1/4" X 1-1/2" (1/4")
150
Steel and Wood Hangermate Pole Tool
Cal.No. I Description I Std. Pack Qty. I carton Qty.
PFM2201100 I Hangermate Pole Tool (Kit) I 1 I 5
The Hangermate pole tool kit is designed for use with standard 1/2" steel conduit tubing (conduit not included) and can be customized to
various lengths and ceiling heights. Compatible with standard steel and wood Hangermate.
Steel and Wood Hangermate Pole Tool
Cat.No. Description Std. Pack Qty. carton Qty.
PFM2201200 1/4" & 3/8" Steel Hangermate Driver -5 25 Vertical and Horizontal Mounts (Silver)
PFM2201150 1/4" & 3/8" Wood Hangermate Driver -5 25 Vertical and Horizontal Mounts (Red)
PFM1491050 1/4" Concrete Hangermate Driver -Vertical Mount (Black) 5 25
PFM1491100 3/8" Concrete Hangermate Driver -Vertical Mount (Black) 5 25
PFM2201250 Hangermate Pivot Driver -Angled Mounts 5 25
PFM2201350 Hangermate Eyelet Driver -Angled Mounts 5 25
All Hangermate drivers have a 1 /4-inch hex for connection to tools.
Universal Installation Accessories
Cal. No. Description Std. Pack Qty. carton Qty.
PFM2201050 3/8" to 1/2" Adapter 25 125
The 3/8" to 1/2" adaptor has a 3/8-16 external thread and a 1/2-13 internal thread.
1-SD0-4 DEWALT.
ORDERING INFORMATION
Installation
rmpact-Rated
Socket / Driver #
<:n @ _g W o !;;
DCF887 PFM1491050 or &~ (1/4" Impact Driver) DWMT17311
DCF890 a:~ DW2284 (3/8") (3/8" Impact Wrench) w
DCF887 PFM1491100 or " (1/4" Impact Driver) DWMT17311 z DCF890
(3/8" Impact Wrench) DW2286 (1 /2") ◄ :c
a a:; a:
I
RING HANGERS
Fig. 69 (Formerly Afcon Fig. 300) Adjustable Swivel Ring, Tapped Per NFPA Standards
Size Range: 1/i" through 8"
Material: Carbon steel
Finish: Strap is Pre-Galvanized Zinc Material. Nut is Zinc Plated.
Service: Recommended for suspension of non-insulated stationary pipe line.
Maximum Temperature: 450° F
Approvals: Complies with Federal Specification A-A-1192A (Type 10), WW-H-171-E (Type 10},
and ANSI/MSS SP-58 (Type 10). UL Listed and FM Approved (Sizes 3// -8").
Features:
• 1/i" -2" sizes designed for use with steel and CPVC piping and manufactured with
FBC System Compatible oil.
• Threads are countersunk so that they cannot become burred or damaged.
• Knurled swivel nut provides vertical adjustment after piping is in place.
• Captured swivel nut in the 1/i" through 611 sizes. The capture is permanent in the bottom
portion of the band, allowing the hanger to be opened during installation if desired, but
not allowing the nut to fall completely out.
Ordering: Specify size, figure number and name.
Non-captured nut also available upon request.
jAj
1/i" through 1" pipe 11/4°' through 2" pipe
C B
G
21/i" through 8" pipe
FIG. 69: DIMENSIONS {IN) • LOADS (LBS) • WEIGHT (LBS)
Pipe Size Max Load Weight Rod Size B C F G
A Width
½ 0.10 2¼ 2 1%
¾ 0.10 2¾ 1¼ 13/,s
1 300 0.10 2% 111/is 1 5/s 1¼ 0.10 2¾ 1¾
1½ 0.10 ¾ 2¾ 1¼ ¼
2 0.11 3¼ 2¾ 1¼
2½ 525 0.20 4 2¾ 13/,s
3 0.20 313/,s 213/,s 1¾s
4 650 0.30 411/is 313/,s 1% ¼ 5 0.54 53/,s 4¾
6 1,000 0.65 ½ 611/is 5% 2¼
8 1.00 Bo/is 7% 3¼
PROJECT INFORMATION
Project: □Approved
1/i" through 2" Size
Rounded Edge Design
c@us <8>
LISTED APPROVED
21/i" through 8" Size
APPROVAL STAMP
Address: D Approved as noted
Contractor: D Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
PH-1.18
A Fcon. SEISMIC RESTRAINTS
Fig. AF310 (Formerly Afcon Fig. 310) Surge Restrainer
Size Range: l" thru 2" Figure 69, Swivel Ring Hanger
Material: Carbon steel
Finish: Pre-Galvanized per ASTM A653
Restrainer Service: Prevents vertical movement of horizontal sprinkler piping from thrust loads due to
sprinkler activation. The surge restrainer is intended to be installed with Anvil's Figure 69 Swivel Ring Hanger.
Restraint Service: May be installed as part of a branch line seismic restraint assembly per the requirements
of NFPA 13. The surge restrainer is intended to be installed with Anvil's Figure 69 Swivel Ring Hanger.
Approvals: cULus Listed {UL 203 and UL 203a). Complies with the hanging and restraint requirements
listed in NFPA 13.
Features:
• One universal size accommodates Fig. 69 sizes l" through 2''.
• Simple design allows for quick installation on existing sprinkler systems.
Installation Instructions:
• Snap surge restrainer onto the Fig. 69 knurl nut.
• The gap between the surge restrainer and service pipe shall not exceed 1/s''.
• Fire Protection applications shall also be installed per the requirements of NFPA 13.
Ordering: Specify figure number and description.
3/a" Rod
Fig. AF310
Fig. 69
Fig. 69 Knurl Nut
FIG. AF310:
LOADS (LBS) • DIMENSIONS (IN) • WEIGHT (LBS)
Service Rod UL Max Seismic Restraint Load Approx.
Pipe Size Size (UL 203a) Weight/100
1 thru 2 31a 300 4
PROJECT INFORMATION
Project:
Address:
Contractor:
Engineer:
Submittal Date:
Notes 1:
Notes 2:
PH-1.18
Surge Restraint
Assembly
f···:;;;;··· ~ ,!-, rv.J~~J
!! lF.
/1
Seismic Restraint
Assembly
Notes: Anvil International® brand bracing components are designed to be
compatible ONLY with other Anvil International® brand bracing components,
resulting in a Listed seismic bracing assembly. Updated UL listing information
may be viewed at www.ul.com
Disclaimer: Anvil International ("Anvil") does not provide any warranties and
specifically disclaims any liability whatsoever with respect to Anvil bracing
products and components that are used in combination with products, parts
or systems not manufactured or sold by Anvil. In no event shall Anvil be liable
for any incidental, direct, consequential, special or indirect damages or lost
profits where non-Anvil bracing components have been, or are used.
APPROVAL STAMP
□Approved
D Approved as noted
D Not approved
Remarks: