Wet Chemical Instruction Manual
AD-2 Designing for Plenum Protection
A single ADP nozzle (P /N B 120011) will protect a
single filter or 'V' filter bank plenum with the follow-
ing maximum dimensions:
Plenum Length
Plenum W"ulth
10 Feet (3.0 mJ
4 Feet (1.2 mJ
When no filters arc present. the nmzlc protecting
the plenum is used to discharge the wet chemical on
the underside of the hood. In this case. the hood may
not exceed a length of 10 ft. (3.0 m) or a width of 4 ft.
(1.2 m).
A plenum with either a single filter bank or "V" filter
bank and a length of 10 ft. (3.0 m) or less may be
protected by one ADP nmzle. The nozzle shall be
located at one end of the plenum. Longer plcnums may ·
be similarly protected with a single ADP nozzle being
used for each 10 ft. (3.0 m) of plenum length and each
4 ft. ( 1.2 m) of plenum width.
ADP nozzles may be used in combinations (see
Figure AD-2). Multiples may be installed facing in the
same direction. and/ or at the ends of the plenum
pointing in. Each nozzle shall provide a maximum of
10 feet of coverage.
ADP nozzles must be centrally located in the plenum .
with their discharge directed along the length of the
plenum and located in relation to the filters as shown
in FigureAD-2.
Note: All Range Guard systems are listed by
UL for use with the exhaust fan either on
or off when the system is discharged.
r10FEET1
4 FT. (1.2 M) PLENUM
WIDTH
NOZZLE LOCATED AT EITHER END
OF PLENUM LENGTH AIMED DOWN '
LENGTH OF PLENUM
t> I I
' • (3.0 M) PLENUM LENGTH
ADP NOZZLE
U.Ll. Ex 2458
~20~EET1 I 10 1 10 i
f> ~
ACCEPTABLE NOZZLE POSmONS
FOR MULTIPLE NOZZLES
ADP
NOZZLES
¾
1 FLOW NUMBER
f+--20 FEET-, I 10 I 10 I
P C> I
4FT.
+ 113Wf+-
I
I • "'l ~~;
i+-W~
SINGLE BANK FILTER
COVERAGE
Figure AD-2. Plenum Protection Nozzle PIN 8120011
A01-4 December. 1997
(
.. ,,
---I
I
AD-5 Designing for Larger Duct Protection
Ducts 50 to 100 inches in perimeter:
Two ADP nozzles. P /NB 120011, pointing in the same
direction are required for protection of ducts With
pertmeters greater than 50 inches and less than or
equal to 100 inches. Ducts can be of unlimited length
(Sec Figure AD-5).
For other option of ducts up to 75 perimeter inches
(See Figure AD-7 on page AD 1-9.
X [l'.1h■: ►1 X
I
I
I. • I. •
Note:
.. .. .. ..
DUCT
l
H00D
¼d ½d
t
Maxim um Diagonal:
11.78 inches
Maximum Diagonal: 11.78 inches
TYP. (2) ADP NOZZLES,
B120011
SQUARE RECTANGULAR ROUND
~
~
Wet Chemical Instruction Manual
All Range Guard systems are listed by UL for
use with the exhaust fan either on or off when
the system Is discharged.
Maximum Diameter: 31.83 inches
NOZZLES TO BE ALONG ONE
CENTERLINE AT THE '4 POINTS.
NOZZLES TO BE o· TO s· UP FROM
ENTRANCE OF VERTICAL DUCT
_J : r-~:~ NOZZLE )~_oJ_
/1 •
DUCT ENTRANCE .
ct OF VERTICAL DUCT
---~-----ct OF HORIZONTAL DUCT
I ~I I ,.._ ___ _
-----------~-. I 2 to • inches , ,
nozzle tip to duct hip ADP NOZZLE ,,' AIM POINT
VERTICAL/HORIZONTAL DUCT
Figure AD-5. Duct Protection Using Two ADP Nozzles, PIN 8120011
U.LI. Ex 2458 A01-7 December~ 1997
/ !
The Wet Chemical Fire Suppression System AANCE GIIAAD.
3-13 Range
RANGE
One 'R' nozzle will protect one four burner range with a maximum hazard area of 28" x 28" (71 cm x 71 cm).
The nozzle is to be located directly over the midpoint of the hazard area and anywhere within the area of a circle
generated by a 9" (23 cm) radius about the midpoint. The nozzle shall not be more than 42" (107 cm) nor less
than 20" (51 cm) from the midpoint of the hazard area. aimed at the midpoint. (See figure 3-25) NOTE: SHAPE
OF BURNER NOT IMPORTANT
14• (31 cm) MAX. BURNER
,~~~--.-IJIIP-+_,_+-_.,CENTERUNE TO CENTERLINE
Figure 3-25. Four Burner Range
SINGLE BORNER RANGE
Special care ts to be taken when aiming the 'R'
nozzle over a single burner range. The aiming point is
to be located 7" (18 cm) from the centerofthe burner.
The nozzle placement shall fall within a cylindrical
area generated by a 9" (23 cm) radius about the aiming
point. The nozzle must be placed no more than 42"
( 107 cm) nor less than 20" (51 cm) above the hazard
area. (See figure 3-27)
U.L.l. Ex 2458 3-13
I
1/ AIM POINT
Figure 3-26. Two Burner Aim Point Center of Hazard
20" (51cm) MIN
18" (46 cm) DIA.
-42" (107) MAX.
A •R' NOZZLE MAY BE
LOCATED ANYWHERE
WITHIN THE SHADED AREA.
7" (18 cm) FROM BURNER
CENTERLINETO AIM
POINT CENTERLINE
Figure 3-27. Single Burner-Range
Manual Part No. 9127100 (9/97) Badger Fire Protection
The Wet Chemical Fire Suppression System
3-5 Deep Vat Fryer and Griddle
SINGLE VAT DEEP FAT FRYER WITH DRIP
BOARDS
One F nozzle or Plenum nozzle Will protect one
Single Vat Deep Fat Frycrwtth a maximum hazard
area of 18" x 18" (46 cm x 46 cm) and an appliance
area 18" x 23" (46 cm x 58 cm) for fryers wtth a drip
board. The nozzle is located at an angle of 45 degrees
or more from the horizontal. It shall not be more than
45" (114 cm) nor less than 2r (69 cm) from the top of
the appliance and aimed at the midpoint of the hazard
area. The nozzle can be outside the perimeter of the
appliance. (Hazard Area 18" x 18 .. (46 cm x 46 cm) -
See Figure 3-7)
41"' ~---.-----'---U--~---,22.an,
30"
(7&an)
MAX
Ma
~✓----~----------.... ~-----~of~
AIII pt. J-Rldu frNI tllt
llldpolnt of Hazn Alu
Figure 3-8. Griddle -Flat Cooking Surface
SPLIT VAT DEEP FAT FRYER
One F nozzle or Plenum nozzle will protect a Split
Vat Deep Fat Fryerwtth a split vat hazard area maxi-
mum of 14" x 15" (36 cm x 38 cm) without drip board
and 14" x 21" (36 cm x 53 cm) with a drip board. The
nozzle is located at an angle of 45 degrees or more
from the hortzontal. It shall not be more than 45"
(114 cm) nor less than 2 7" (69 cm) from the top oUhe
appliance and aimed at the midpoint of the huarct·
area. The nozzle can be outside the perimeter of the--
appliance. (Hazard Area 14" x 15" (36 cm x 38 cm) -
See figure 3-9)
U.LI. Ex 2458 3-5
'5• (114cm)
MAX
1S-,-
(46 cm) MAX,.
'
AANCEGUAAD
AN F NOZZLE MAY BE LOCATED
ANYWHERE WITHIN THE GRID
DIAGONAL FROM
AIM POINT
23"
cm) AX ..
DRJPBOARD \
::::::::-1-s·_J,u._"_cm_) __ ~-------_-e1-~1--
Figure 3-7. Single Vat Deep Fat Fryer
GRIDDLE -FIAT COOKING SURFACE
One ADP nozzle will protect one griddle (with or
without raised ribs) with a maximum hazard area of
30" x 42" (76 cm x 107 cm). The nozzle ls located at
any point on the perimeter of the appliance and
aimed at a point 3" (7.6 cm) from the midpoint of the
hazard area. It shall not be more than 48" (122 cm)
nor less than 13" (33 cm) above the edge of the appli-
ance perimeter. Positioning the nozzle directly over
the appliance ls not acceptable. (See figure 3-8.)
AN F OR PLENUM NOZZLE MAY BE LOCATED
ANYWHERE WITHIN THE GRID
DIAGONAL FROM
AIM POINT
4s-
(114cm)
MAX-
AIM POINT:
MIDPOINT OF HAZARD
CENTERED ON DIVIDER
~ 21• (114 cm)
INTERICJR
OVERALL
\ :===~~~~.;.;1;;.;;.4...; .. ;;..;(3;.;.l.;;cm~)~====~:.1--
MAX,.
Figure 3-9. Split Vat Deep Fat Fryer
Manuat Part No. 9127100.(9/97) Badger Fire Protection
RANCE GUARD The Wet Chemical Fire Suppression System
3-22 'Cylinder Sizing
After finding how many nozzles of each type are required for a system. the sum of all the nozzle flow numbers is
used to determine the number and size of the cylinders required. in accordance with the cylinder flow number
limits given below.
Table 3-3. Cylinder Flow Number Limits
Maximum Flow Numbers of Cylinders
Cylinder Flow Number
RG-1.25G (4.7 L)
RG-4GT or RG-4GS
(15 L)(Long or Short
1 Cylinder
2 Cylinders
3Cylinders
4 Cylinders
f !~i!fl"
4
Single Cylinder Only
(Cannot Manifold)
12
24 Can Manifold •
36 Up to 4 Cylinders
48
~lf5i~.i
·only like cylinders can be manifolded (ie, four RG-4GS, two RG-6G.)
The system can be actuated through various controls, in accordance with Table 3-4. To actuate a single cylinder
system. use either the Mechanical or Electric Control Head or the A+ Control Box with pressure operated actuator.
To actuate two or three cylinders, use either one or two Tandem Control Heads and a Mechanical or Electric
Control Head or the A+ Control Box with 1-3 Pressure Operated Actuator(s). To actuate from 1 to 5 cylinders. the
A+ Control Box with ·Pressure Operated Actuator(s) must be used. For applications requiring 5-10 cylinders the
BMCS-1 nitrogen releasing system is recommended. Larger systems. 10-100 cylinders, the BMCS-7 nitrogen
releasing system is the recommended means of cylinder actuation. For complete details of the BMCS-1 and BMCS-
7 systems, refer to each respective manuals, P /N B900002 and P /N B9000003.
U.L.I. Ex 2458
Table 3-4. Actuation Controls
Mechanical or Electric Tandem A+Control
System Size Control Head Control Head Box BMCS-1
1 Cylinder ✓ ✓
2 Cylinders ✓-✓ ✓---
3 Cylinders ✓--✓ ✓***
4 Cylinders ✓--✓ ✓-··
5 Cylinders ✓--✓ ✓-··
5-10 Cylinders ✓--✓•·••
1 O+ Cylinders ✓--✓--·
• Requires both a mechanical or electric control head and tandem control head
•· Requires a mechanical or electric control head and multiple tandem control heads
•••sMCS series requires a mechnical or electric control head to actuate.
BMCS-7
✓-··
3-22 Manual Part No. 9127100 (9/97) Badger Fire Protection
J
Wet Chemical Instruction Manual
AD-10 Nozzle Summary
Table AD-1. Nozzle Summary
Perimeter Diameter Nozzle /
Hazard Max. Max. Length Flow No.
Duct
R{ifilfllll I -so· (165.1 cm)
p_qf(2$§uj,)
Length Width Nozzle /
Hazard Max. Max. Filters Flow No.
Plenum 10' (3.0 m) 4' (1.2 m) --v" Bank or
Single ADP / 1
Hazard Size Nozzle Height Notes Nozzle/
Hazard Inches/cm Inches/cm Inches/cm Flow
Four-Burner Range 28 X 28 (71 X 71) 20 to 42 (52 to 107) within 9 (23) rad.
of mid point. R / 1
Ail. ,· .. •", . ,, ~ . ... -:, -~-; '.3(): 1 :~ :. : ~,1310 ..
Single Vat Deep Fat Fryer (Drip Boards 1 to 6 [2.5 to18D 18 X 18 (46 x 46) 27to45(69to114) 45° to 90°
~mi:~tle&p,tau~fy~;~ ·.: · _:,7~~:x:24·t~x:61 Y -, ..
SplitVatDeepFatFryer 14x15(36x38) 27(69)to45(117) 45°to90° F/2
-~il~J!t··ffiY!fi@!:eto#i#Jt&tili*i'if!l§.~'{@] 38)8@;)sf(f1Jfm-~HH
Wo't<s 14 to 28 (36 to 71) Dia. within 2 {5)
3 to 8 (8 to 20) Deep 35 to 56 {89 to 142) of mid point. GRW / 1
Qe.19htBroiiers(Salamaiiiers=J~;1/;."""~;~-~t<.,,..,i;-,;f-~--j -ff·;;;~"'\i'"""!{~--~~-.~-:t,,_,·~~ .... ..,..,...t;:~_,,,:'.:.3025X~34-{77·x'.~§J;:f{i;;~s::t~h~, . .-.,~ .,.: ~. 1 ·ortf · *-*-*" · :~r .. ·
Closed Top Chain Broilers 28 X 29 (71 x 74) See3-12 See3-12 ADP/ 1
~PCham.Broilersfs!~~~;!;~~~r::!!j~·::;:t2a~29_(7t x.74l~Et:1~:~~s.~1?e!~l)f'C£iif{~~.1z:2 ~i!D~tL•~Jj
Pumice Rock (Lava, Ceramic) Charbroiler 22 X 23 (56 x 58) 24 (61) to 48 (122) 45° to 90°;
2 Layers of rock
~:::t!:~f;ar f-~:l-!i!~~lt~~Ji~t~~ to'~
1
ElectricCharbroiler(OpenGrid) ~~~~~ 24 X 21 (61 x 53) 24(61)to48(122)
Gas:Ra<fmnt~~ft:~ ·~-~~-t:-;2•_. X. _ -21 .. -81_ .. ·x. 53r_·iY\"".:.:F,;'.::.··.\~·:2i{sNJ~Jo~ ... ·. ~~~~~~.~~~
~,.___-~~ • -• • oY 1.,
Mesquite Charbroiler (Chips, Wood, Logs) 30 X 24 (76 x 61) 24 (61) to 48 {122) 45° to90°;
10 (25) Fuel depth
TIit Skillet and Braising Pan 24 X 24 (61 X 61) 27 .5 in (70 cm) to 46 in (117 cm)
within perimeter
Nozzle Nozzle Part
Identification No. Flow No.
ADP(Appliance-Duct-Plenum) 8120011 1
GRW (Gas Radiant-Wok) 8120013 1
DM (Mesquite) 8120015 3
U.L.L Ex 2458 AD1-13
DM/3
F/2
December, 1997