Product Description
The Reliable Model G Automatic Sprinkler utilizes the
center strut solder in compression principle of
construction. The fusible alloy is captured in the
cylinder of the solder capsule by a stainless steel ball.
When the fusible alloy melts, the ball moves into the
cylinder allowing the cylinder to fall away from the
sprinkler. When this happens, the lever is released to
spring free from the sprinkler so that all of the operating
parts clear from the waterway allowing the deflector to
distribute the discharging water.
Except for the parts in the cylinder as mentioned
above, the sprinkler components are made from
copper based alloys for maximum corrosion
protection. Lead plated, wax coated or wax over lead
plated sprinklers are available for specially severe
environments. Chrome plated sprinklers are available
for decorative purposes.
All sprinklers are individually hydrostatically tested.
All sprinklers are identified as to their fusing point by
markings that appear on several of the operating parts
and by an identifying color that appears on the frame.
Sprinkler Types
Standard Upright -This deflector configuration is
normally used with exposed piping installations. Water
is distributed laterally and downward in a wide pattern
approximating a hemisphere which is completely and
uniformly filled with water in the form of small drops or
spray. At a sprinkler height of 10 feet (3m), a circular
area of approximately 20 feet (6.1 m) in diameter is
covered by the water discharged at the minimum
pressure.
Standard Pendent -This deflector configuration is
normally used where the space above the piping is not
adequate or where a concealed piping installation is
employed. The discharge characteristics of the
standard pendent are virtually identical to the
standard upright as described above.
Large and Small Orifice-By varying the orifice
size, a large or small orifice sprinkler is created that
will distribute as much as 40% more water or 65% less
water than the normal ½" (15mm) orifice sprinkler.
These sprinklers are identified by the orifice size that
is stamped in the base of the sprinkler and by the
pintle that extends from the deflector-the exception is
the large orifice sprinkler with the¾" NPT (R¾) inlet
thread where the size of the inlet is sufficient to
classify this sprinkler as one having a larger than
standard orifice.
Model G
Automatic Sprinklers
Spray Upright,
Spray Pendent
And Conventional
A..sos-0021
Upright Pendent
Small Orifice Upright Conventional
Conventional-This deflector configuration is used pri-
marily in those countries where the LPC installation rules
have precedence. The sprinkler is designed to distribute
a portion of its water discharge upward against the ceil-
ing with the balance downward. It may be installed in ei-
ther the upright or the pendent position. Sprinklers with
conventional deflectors are available with orifice sizes
corresponding to light, ordinary and extra-high hazard
installations.
Application and Installation
Standard sprinklers are used in fixed fire protection systems:
Wet, Dry, Deluge or Preaction. Care must be exercised that the
orifice sizes, temperature ratings, deflector styles and sprinkler
spacings are in accordance with the latest published stan-
dards of the National Fire Protection Association or the approv-
ing authority having jurisdiction.
The sprinklers must be installed with the Reliable Model D
Sprinkler Wrench. Any other type of wrench may damage the
sprinkler.
The approvals or listings of Reliable Automatic Sprinklers by
major approving organizations are shown in the tabulated list
provided on the back of this bulletin.
*Patent No. 4,440,234
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
-.I.
-.I.
0
::0 (D ~
::0
Technical Data
"K" Factor
Sprinkler Type us
Standard-Upright (SSU) and Pendent (SSP)
Deflectors Marked to Indicate Position
X." (15 mm) Standard Orifice with X." NPT (RX.) Thread 5.62
Y,6" (11 mm) Small Orifice with X." NPT (RX.) Thread 4.24
¾" (10 mm) Small Orifice with X." NPT (RX.) Thread 2.82
Y,6" (8 mm) Small Orifice with X." NPT (RX.) Thread 1.98
%" (20 mm) Large Orifice with X." NPT (RX.) Thread 7.96
1½t (20 mm) Large Orifice with ¾" NPT (R¾)Thread 8.20
20 mm XHH with 20 mm Thread 8.20
10 mm XLH with 10 mm Thread 4.10
Conventional-Installed in UpriQht or Pendent Position
10mm XLH with 10mm Thread 4.10
15mm Standard Orifice with (RX.) Thread 5.62
20mm XHH with (R¾) Thread 8.20
T emperature Rf a 1ngs
Maximum
Sprinkler Ambient
Rating Temperature Frame (1>
Classification OF oc OF oc Color
Ordinary 135 57 100 38 Black
Ordinary 165 74 100 38 Uncolored
Intermediate 212 100 150 66 White
High 286 141 225 107 Blue
(1) Frame color does not apply to painted or plated sprinklers-Use
sprinkler rating as identified on operating parts.
Finishes(1>
Standard Finishes
Bronze -All Temperature Ratings
Chro~~ -All Temperature Ratings
White l -All Temperature Ratings
Only Frame and Deflector are Painted
Special Application Finishes
Metric
81 .0
61 .0
40.6
28.5
114.7
118.2
118.2
59.1
59.1
81 .0
118.2
Sprinkler Identification
Sprinkler Number (SIN)
Height Approvals ssu SSP
2 ½" (73mm) 1,2,3,4,5,6, 7 R1025 R1015
2 ½" (73mm) 1, 3, 7 R1023 R1013
2 ½" (73mm) 1, 2, 3, 7 R1021 R1011
2 ½" (73mm) 1, 3, 7 R1022 R1012
2½" (73mm) 1, 2, 3, 7 R1026 R1016
2 %" (75mm) 1, 2, 3, 7 R1027 R1017
75.4 mm 4,5,6 R1027 R1017
73mm 4,5,6 R1024 R1014
73mm 5 R1074
73mm 4,5,6 R1075
75.4 mm 4,5 R1077
Maintenance
Model G Sprinklers should be inspected quarterly and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove any sprinkler that has been painted
( other than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or
non-operation. Use only the Model D Sprinkler Wrench for
sprinkler removal and installation. Any other type of wrench may
damage the sprinkler.
Approval Organizations
1. Underwriters Laboratories, Inc.
2. Factory Mutual Research Corporation
3. Underwriters' Laboratories of Canada
4. Loss Prevention Council
5. Pleniere Assemblee
6. Verband der Schadenversicherer eV
Bright Brass Plated -Only frame, deflector and cap are plated. 135°F (57°C), 165°F 7. N.Y.C. BS&A No. 587-75-SA (74°C), 212°F (100°C) Temp. Rating.
Black Plated -Only frame, deflector and cap are plated. All Temp. Ratings.
Polyester Coated (2) -Only frame and deflector are coated.
Lead Plated -165°F (74°C), 212°F (100°C) and 286°F (141 °C) Temp. Ratings.
Wax-Coated (3) -165°F (74°C) Clear Wax, 212°F (100°C) Brown Wax.
Wax-Coated Over
Lead Plated (3) -165°F (74°C) Clear Wax, 212°F (100°C) Brown Wax.
(1) Other colors and finishes are available. Consult factory for details.
(2) UL listed and NYC MEA Approved only.
{3) 212°F (100°C) brown wax may be used on 286°F (141 °C)
sprinklers when maximum ambient temperatures do not exceed 150°F
(66°C). UL Listed, FM Approved, NYC MEA 258-93-E.
8. N.Y.C. MEA 258-93-E
Ordering Information
Specify
1. Model G
2. Deflector
• Upright
• Pendent
• Conventional
3. Nominal Orifice
4. Inlet Thread
5. Temperature Rating
6. Finish
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual
Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and
reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
Reliable1 (800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 668-3470 Corporate Offices
~ R8()'tled
~ Paper
Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 4/03 PIN 999997CXX)5
Reliabld
The Concealer®
A Concealed Sprinkler
With½" (13mm) or
1½" (38mm) Adjustment
Features
1. Push-on{fhread-off cover plate assembly
attachment with ½" (13mm) adjustment.
Does not require clips or springs.
2. 1½" (38mm) Total adjustment provided by
adjustable inlet versions.
3. Adjustable inlet version available with either
1" NPT ale or female threads eliminating
costly reducing coupling.
4. Smooth aesthetic ceiling profile.
5. Available in white or other color painted or
brass, chrome, or black plated finishes.
6. Ordinary and intermediate temperature
ratings.
7. Multiple orifices for design flexibility.
Approvals & Listings
1. Underwriters Laboratories Inc. (UL)
2. Underwriters Laboratories of Canada. (ULC)
3. N.Y.C. BS&A No. 587-75-SA.
Note: Approvals are for light and ordinary hazard, except for
small orifice sprinklers which are limited to light hazard
occupancies. The cup and skirt are fabricated from plated
steel and are intended for interior non corrosive applications.
U.S. Patent No. 4,880,063.
Application
The Reliable Model G4
Concealer® is the most versatile
concealed sprinkler available. It
provides the best form of fire pro-
tection while offering an attractive
appearance and ½" ( 13mm) of
cover adjustment for ease of instal-
lation. The adjustable 1" NPT inlet
versions have 1 ½" (38mm) of total
adjustment and also eliminates the need for a reducing cou-
pling. The small diameter Push-on/Thread-off cover plate
assembly is easily attached and blends into the ceiling, con-
cealing the most dependable fire protection available, an
automatic sprinkler system.
Bulletin 121 Rev.I
Model G4 Concealed
Automatic Sprinkler
The Concealer® is designed for use where aesthetic ap-
pearance is important. Offices, hospitals, motels and res-
taurants are but a few of the applications where it can be
used. It is available in different orifice sizes allowing the de-
signer to optimize system performance, thereby achieving a
most efficient installation.
The Concealer® can eliminate the need for precise cutting
of drop nipples. The Push-on/Thread-off cover plate assem-
bly can be adjusted without tools so it mates accurately with
the ceiling. The fire protection system need not be shut
down to adjust or remove the cover plate assembly.
Product Description
The Reliable Model G4 Concealer® uses the proven
Model G fusible element in a standard style sprinkler frame
with a drop-down deflector. This assembly is recessed into
the ceiling and concealed by a flat cover plate. The
Push-on/Thread-off cover plate and sprinkler cup assem-
blies are held tight by a flexible tooth engagement to the
threaded cup. This threaded engagement provides ½"
( 13mm) of cover adjustment. The flat cover plate is attached
to the skirt using an ordinary temperature classification sol-
der. This results in a strong cover plate assembly with an or-
dinary temperature rating, and an intermediate temperature
sprinkler which can be installed in 150°F (66°C) environ-
ments. When the ceiling temperature rises, the solder hold-
ing the cover plate to the skirt melts, the flat cover plate
released thus exposing the sprinkler inside to the rising am-
bient temperature.
The subsequent fusing of the sprinkler element opens the
waterway and causes the deflector to drop into position to
distribute the discharging water. Any secure engagement of
the threads between the cover plate and cup will assure that
the drop-down deflector is properly located below the ceil-
ing when a sprinkler operates.
The Reliable Automatic Sprinkler Co., Inc., 525 North MacQuesten Parkway, Mount Vernon, New York 10552
OJ C
ro ~-::J
.....I.
I\.)
.....I.
:0 CD ~
Installation
Do not install The Concealer® in ceilings which have positive
pressure in the space in the space above.
After a 2'5/4 inch diameter hole is cut in the ceiling, the sprinkler
is to be installed with the Model G4 Wrench. The wrench has
drive tangs which insert into cup slots. When installing a sprin-
kle~ the wrench is first positioned into the sprinkler/cup assembly
until the wrench tangs engage drive slots in the top of the cup
(there are two sets of mating drive slots in the cup). The sprinkler
is then tightened into the pipe fitting. When inserting or removing
the wrench from the sprinkler/cup assembly care should be
taken to prevent damage to the sprinkler. DO NOT WRENCH
ON ANY OTHER PART OF THE SPRINKLER/CUP ASSEMBLY.
The adjustable inlet versions are similar to the standard Model
G4 except that an addition 1" (25mm) of adjustment is provided
by means of a telescoping inlet section that threads in or out of a
stationary coupling reducer ( either 1 male or 1 female) as shown
in Fig. 2 or Fig. 3. These sprinklers must be installed before the
ceiling is in place, by wrenching on only the coupling reducer
Temperature Ratings
Classification Sprinkler Cover Plate Max. Ambient
Temp.
Ordinary 135°F/57°C 135°F/57°C 100°F/38°C
Ordinary 165°F/74°C 135°F/57°C 100°F/38°C
Ordinary 165°F/74°C 165°F/74°C 100°F/38°C
Intermediate 212°F/100°C 165°F/74°C 150°F/66°C
Installation Data
Nominal
Sprinkler Total Nominal K 1:.,.,.+,-.r Thread Inlet Adjustment Orifice us Metric
f\Jon--Adjustable X '(13mm) ½_"(15mm) 5.6 80 X''NPT(R½)
Non-Adjustable X"(13mm) 1/,/(11mm) 4.2 00 );;"NPT(R½)
f\Jon--Adjustable X"(13mm) ¾"(1Cmm) 2.8 40 );;"NPT(R½)
hex flats. After the ceiling has been installed with holes for the
sprinkler, each telescoping inlet section is to be adjusted with the
G4 Wrench. Install the push-on/thread-off cover plate assembly
over the sprinkler by holding and pressing it straight up into the
cup. Final adjustment of each cover assembly is made by hand
turning it clockwise until it is tight against the ceiling.
Maintenance
The Model G4 Concealer® should be inspected quarterly and
the sprinkler system maintained in accordance with NFPA 25.
Do not clean sprinklers with soap and water, ammonia or any
ot~er cleaning fluids. Remove any sprinkler that has been
painted (other tha_n factory applied) or damaged in any way. A
stock of spare sprinklers should be maintained to allow quick re-
placement of damaged or operated sprinklers. Prior to installa-
tion, sprinklers should be maintained in the original cartons and
packaging to minimize the potential for damage to sprinklers that
would cause improper operation or non-operation.
Ordering Information
1. Sprinkler Model
2. Temperature Rating
3. Nominal Orifice
4. Flat Cover Plate Finish
5. Inlet Type
Note: Unless otherwise
specified, the 165°F (74°C)
sprinkler will be provided with
the 165°F (74°C) cover.
Sprinkler
Identification Approvals Number
fCIM\
1,2,3 R2115
1,2,3 R2113
1,2,3 R2111
Cover Plate Finishes (1>
Standard Finishes
Bronze
Chrome Plated
White
Special Application
Finishes
Black Plated
Bright Brass
Off White
Black Paint
(1) Other colors and finishes are
available. Consult factory for
details
Adjustable 1);;''(38mm) ½_"(15mm) 5.6 80 1" NPT Male or Female 1,2,3 R2118
Note: Paint or any other
coatings applied over the
factory finish will void all
approvals and warranties.
Adjustable 1);;''(38mm) 1/,6"(11mm) 4.2
Adjustable 1)t (38mm) ¾"(1Cmm) 2.8
Fig. 1 -½" (R½) NPT Non-Adjustable Inlet
00 1" NPT Male or Female 1,2,3
40 1" NPT Male or Female 1,2,3
Fig. 2 -1" NPT Male-Adjustable Inlet
R2113
R2112 Installation Wrench
Model G4 Sprinkler Wrench
Fig. 3 -1" NPT Female-Adjustable Inlet
The equipment presented i~ this bulletin i~ tC? be install_ed \n accordance "".'ith the lates_t pertinent Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other s1m1lar organizations and also with the provIsIons of governmental codes or ordinances whenever applicable.
Prod.~cts manufactured an~ distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly
qual1f1ed and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliabl~ The Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Office
(800) 848-6051 Sales Fax
(914) 668-3470 Corporate Offices Revision lines indicate updated or new data.
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 06/02 P/N 9999970014