HomeMy WebLinkAbout2708 OLYMPIA DR; ; CBR2021-1039; PermitPERMIT REPORT
Residential Permit
Print Date: 01/11/2022
Job Address: 2708 OLYMPIA DR, CARLSBAD, CA 92010-2179
Permit Type: BLDG-Residential Work Class: Addition
Parcel#: 1674322400 Track#:
Valuation: $10,761.20 Lot#:
Occupancy Group: Project#:
#of Dwelling Units: Plan#:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check#:
Plan Check#:
Project Title:
Description: WESTON: 58 SF ADDITION FOR WALK IN CLOSET// MASTER BATH REMODEL
Property Owner:
ROBERT AND CLAUDIA WESTON
2708 OLYMPIA DR
CARLSBAD, CA 92010-2179
FEE
BUILDING PLAN CHECK FEE (BLDG)
GREEN BUILDING STANDARDS PLAN CHECK & INSPECTION
SB1473 GREEN BUILDING STATE STANDARDS FEE
BUILDING PERMIT FEE ($2000+)
ELECTRICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
MECHANICAL BLDG RESIDENTIAL NEW/ADDITION/REMODEL
PLUMBING BLDG RESIDENTIAL NEW/ADDITION/REMODEL
STRONG MOTION-RESIDENTIAL
Total Fees: $516.91 Total Payments To Date: $516.91
(city of
Carlsbad
Permit No: CBR2021-1039
Status: Closed -Finaled
Applied: 04/15/2021
Issued: 07/26/2021
Finaled Close Out: 01/11/2022
Inspector:
Final Inspection:
Contractor:
TKers
11/04/2021
GOMEZ CONSTRUCTION COMPANY LLC
431 W REDONDO DR
OCEANSIDE, CA 92057-4316-SAN DIEGO
(442) 266-2733
Balance Due:
AMOUNT
$86.68
$175.00
$1.00
$123.83
$41.00
$39.00
$49.00
$1.40
$0,00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition ofthese
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
("cicyof
Carlsbad
RESIDENTIAL
BUILDING PERMIT
APPLICATION
B-1
Plan Check C\::>BWa-1030\
Est. Value 10 {1\11 \;-
PC Deposit
Date
Job Address 2708 Olympia Drive Suite: ____ ,APN: 167-432-24-00
CT/Project #:. __________________ ,Lot#: 158 Year Built: _1_9_8_4 _______ _
Fire Sprinklers: QYES0 No Air Conditioning:® YES ONO
BRIEF DESCRIPTION OF WORK:
Electrical Panel Upgrade: QvEs0 NO
Master bath remodel and new walk in closet.
Ii] Addition/New: closet Living SF, 58 Deck SF, ____ Patio SF, ____ Garage SF __ _
Is this to create an Accessory Dwelling Unit? 0 Y ON New Fireplace? 0 Y ON , if yes how many? __
Iii Remodel: 20 SF of affected area -----· Is the area a conversion or change of use? Ov 0 N
0 Pool/Spa: ____ SF Additional Gas or Electrical Features? ___________ _
osolar: ___ KW, ___ Modules, Mounted: 0Roof 0Ground, Tilt: 0 vO N, RMA: Ov ON,
Batterv:Ov ON, Panel Upgrade: Ov 0N
D Reroof: ------------------------------------□ Plumbing/Mechanical/Electrical
0 Only: Other:
This permit is to be issued in the name of the Property Owner as Owner-Builder, licensed contractor or Authorized Agent of the
owner or contractor. The person listed as the Applicant below will be the main point of contact throughout the permit process.
PROPERTY OWNER APPLICANT O PROPERTY OWNERS AUTHORIZED AGENT APPLICANT Ill
Name: Robert & Claudia Weston Name: Scott Piddinqton
Address: 2708 Olympia Drive Address: 14781 Pomerado Road #149
City: Carlsbad State: CA Zip: 92010 City: Poway State: CA Zip:_9_20_6_4 __ _
Phone: _________________ Phone: 858-361-8271
Email: pacdesiqnstudios@qmail.com Email: pacdesiqnstudios@qmail.com
DESIGN PROFESSIONAL
Name: Scott Piddington
APPLICANT 0
Address: ________________ _
City: ________ .State: ___ ,Zip: ___ _
Phone: ________________ _
Email: pacdesignstudios@gmail.com
Architect State License: __________ _
CONTRACTOR OF RECORD APPLICANT 0
Name: Jose Gomez
Address: 6072 Corte del Cedro
City: Carlsbad State: CA Zip:_9_20_1_1 ____ _
Phone: 760-644-4897
Email: G.construction20@gmail.com
State License/class: 1065094 B Bus. License: q ~ pl J,(CI
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
REV. 08/20
IDENTIFY WHO WILL PERFORM THE WORK BY COMPLETING (OPTION A) OR (OPTION B) BELOW:
(OPTION A): LICENSED CONTRACTOR DECLARATION:
I hereby affirm under penalty of perjury that I am licensed under provisions of Chapter 9 (commencing with Section 7000) of Division 3
of the Business and Professions Code, and my license is in full force and effect. I also affirm under penalty of perjury one of the
following declarations:
DI have and will maintain a certificate of consent to self-insure for workers' compensation provided by Section 3700 of the Labor Code, for the performance of the
work which this permit is issued. Policy No. _________________________________________ _
0 I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit is issued.
My workers' compensation insurance carrier and policy number are: Insurance Company Name: ______________________ _
Policy No. ____________________________ Expiration Date: _______________ _
~ Certificate of Exemption: I certify that in the performance of the work for which this permit is issued, I shall not employ any person in any manner so as to become
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation coverage is unlawful and shall subject an employer to
criminal penalties and civil fines up to $100,000.00, in addition the to the cost of compensation, damages as provided for in Section 3706 of the Labor Code,
interest and attorney's fees.
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work this permit is issued (Sec. 3097 (i) Civil Code).
Lender's Name: ______________________ Lender's Address: _____________________ _
CONTRACTOR PRINT: Jose Gomez S tt P"dd"ngt O,g,lally5'gMObyScottP1dd1ngton SIGN: co I I on oa .. ·2021orn103603-U1'00' DATE: 07-13-2021
(OPTION B): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Law for the following reason:
DI, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure is not intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's License Law does not apply to an owner of property who builds or improves thereon, and who does such work
himself or through his own employees, provided that such improvements are not intended or offered for sale. If, however, the building or improvement is sold within
one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
DI, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's License Law does not apply to an owner of property who builds or improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License law).
0 I am exempt under Business and Professions Code Division 3, Chapter 9, Article 3 for this reason:
D•owner Builder acknowledgement and verification form" has been filled out, signed and attached to this application.
0 Owners "Authorized Agent Form" has been filled out, signed and attached to this application giving the agent authority to obtain the permit on the owner's behalf.
By my signature below I acknowledge that, except for my personal residence in which I must have resided for at least one year prior to completion of the
improvements covered by this permit, I cannot legally sell a structure that I have built as an owner-builder if it has not been constructed in its entirety by licensed
contractors. I understand that a copy of the applicable law, Section 7044 of the Business and Professions Code, is available upon request when this application is
submitted or at the fol/awing Web site: http://www.leginfo.ca.gav/calaw.html.
OWNER PRINT: SIGN: __________ DATE: ______ _
APPLICANT CERTIFICATION: SIGNATURE REQUIRED AT THE TIME OF SUBMITTAL
By my signature below, I certify that: I am the property owner or State of California Licensed Contractor or authorized to act on the property
owner or contractor's behalf. I certify that I have read the application and state that the above information is correct and that the information on
the plans is accurate. I agree to comply with all City ordinances and State laws relating to building construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for inspection purposes. I ALSO AGREE TO SA VE,
INDEMNIFY AND KEEP HARMLESS THE CITY OF CARLSBAD AGAINST ALL LIABILITIES, JUDGMENTS, COSTS AND EXPENSES WHICH MAY IN ANY WAY ACCRUE
AGAINST SAID CITY IN CONSEQUENCE OF THE GRANTING OF THIS PERMIT. OSHA: An OSHA permit is required for excavations over 5'0' deep and
demolition or construction of structures over 3 stories in height.
APPLICANT PRINT: Scott Piddington Scott P"1dd"1ngt DlgllellysignedbyScollPiddington 04 12 2021 SIGN: on Dale:2021.04,1220"57:30-07'00' DATE: ----------
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
2 REV. 08120
{''cicyof
Carlsbad
OWNERS
AUTHORIZED
AGENT FORM
B-62
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
OWNER'SAUTHORIZED AGENT FORM
Only a property awner, contractor or their authorized agent may submit plans and applications for building
permits. To authorize a third-party agent to sign for a building permit, the owner's third party agent must bring
this signed form, which identifies the agent and the owner who s/he is representing, and for what jobs s/he
may obtain permits. The form must be completed in its entirety to be accepted by the City for each separate
permit application.
Note: The following Owner's Authorized Agent form is required to be completed by the
property owner only when designating an agent to apply for o construction permit
on his/her behalf.
AUTHORIZATION OF AGENT TO ACT ON PROPERTY OWNER'S BEHALF
Excluding the Property Owner Acknowledgement, the execution of which I understand is my personal responsibility,
I hereby authorize the following person(s) to act as my agent(s) to apply for, sign, and file the documents necessary
to obtain an Owner-Builder Permit for my project.
Master bath remodel and new walk in closet. Scope of Construction Project (or Description of Work): ____________________ _
Project Location or Address: 2708 Olympia Drive
Name of Authorized Agent: _S_c_o_tt_P_i_d_d_i_n_g_t_o_n ____ Tel No. _8_5_8_-_3_6_1_-8_2_7_1
Address of Authorized Agent: 14 781 Pomerado Road #149
Poway, CA 92064
I declare under penalty of perjury that I am the property owner for the address listed above and I personally filled
out the above information and certify its accuracy.
Scott P'1dd1'ngton Digitally signed by Scott Piddington
Date: 2021.04.12 21 :00:52 -07'00' Property Owner's Signature: _____________________ Date: _______ _ 04-12-2021
1
("city of
Carlsbad
PURPOSE
CLIMATE ACTION PLAN
CONSISTENCY CHECKLIST
B-50
Development Services
Building Division
1635 Faraday Avenue
(760) 602-2719
www.carlsbadca.gov
This checklist is intended to assist building permit applicants identify which Climate Action Plan (CAP) ordinance
requirements apply to their projects. The completed checklist must be included in the building permit application. It may be
necessary to supplement the completed checklist with supporting materials, calculations or certifications, to demonstrate
full compliance with CAP ordinance requirements. For example, projects that propose or require a performance approach
to comply with energy-related measures will need to attach to this checklist separate calculations and documentation as
specified by the ordinances.
NOTE: Th.e loHowing type of permitS are not required to fill out this form
❖ Patio I ❖ Decks I ❖ PME (w/o panel upgrade) I ❖ Pool
_. If an item in the checklist is deemed to be not applicable to a project, or is less than the minimum required by ordinance,
an explanation must be provided to the satisfaction of the Building Official.
_. Details on CAP ordinance requirements are available on the city's website.
_. A CAP Building Plan template (form B-55) shall be added to the title page all building plans. This template shall be
completed to demonstrate project compliance with the CAP ordinances. Refer to the building application webpage and
download the latest form.
Project Name/Building
Permit No.: Weston Residence BP No.:
Property Address/APN: 167-432-24-00
Applicant Name/Co Scott Piddington
ApplicantAddress: 14781 Pomerado Road #149
Contact Phone 858-361-8271 Contact Email pacdesignstudios@gmail.com
Contact information of person completing this checklist (if different than above):
Name:
Company
name/address:
Applicant Signature: Scott Piddington
B-50
Contact Phone:
Contact Email:
Date 04-12-2021
Page 1 of 6 Revised 06/18
-~ ~' -
, PERMIT INSPECTION HISTORY for (CBR2021-1039)
Permit Type: BLDG-Residential Application Date: 04/15/2021 Owner: COOWNER ROBERT AND CLAUDIA
Work Class: Addition
Status: Closed -Finaled
WESTON
Issue Date: 07/26/2021 Subdivision: CARLSBAD TCT#74-04
Expiration Date: 03/14/2022
IVR Number: 32764
Address: 2708 OLYMPIA DR
CARLSBAD, CA 92010-2179
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Reinspection Inspection
Date Start Date
11/04/2021 11/04/2021 BLDG-Final Inspection 170029-2021
Tuesday, January 11, 2022
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
COMMENTS
Status
Passed Tim Kersch
Passed
Yes
Yes
Yes
Yes
Yes
Complete
Page 3 of 3
-
PERMIT INSPECTION HISTORY for (CBR2021-1039)
Permit Type: BLDG-Residential Application Date: 04/15/2021 Owner: COOWNER ROBERT AND CLAUDIA
WESTON
Work Class: Addition
Status: Closed -Finaled
Issue Date: 07/26/2021
Expiration Date: 03/14/2022
IVR Number: 32764
Subdivision: CARLSBAD TCT#74-04
Address: 2708 OLYMPIA DR
CARLSBAD, CA 92010-2179
Scheduled
Date
Actual Inspection Type
Start Date
Inspection No. Inspection
Status
Primary Inspector Reinspection Inspection
Tuesday,January11,2022
Checklist Item
BLDG-Building Deficiency
COMMENTS
September 15, 2021: (virtual inspection).
1. No gypsum board, exterior stucco lath,
insulation and gas test deficiencies.
2. Exterior stucco wire lath , metal weep
screed, corner beads, attachment
anchoring, and all penetrations sealed with
silicone caulking, scope of work-approved.
3. Gypsum/drywall board; type, size,
method of attachment anchoring
system/schedule -approved.
4. Gas line, under air pressure leak test -
approved.
5. Energy-efficient thermal
insulation-approved.
BLDG-17 Interior
Lath/Drywall
166544-2021 Passed Tony Alvarado
Checklist Item
BLDG-Building Deficiency
COMMENTS
September 15, 2021: (virtual inspection).
1. No gypsum board, exterior stucco lath,
insulation and gas test deficiencies.
2. Exterior stucco wire lath , metal weep
screed, corner beads, attachment
anchoring, and all penetrations sealed with
silicone caulking, scope of work-approved.
3. Gypsum/drywall board; type, size,
method of attachment anchoring
system/schedule -approved.
4. Gas line, under air pressure leak test -
approved.
5. Energy-efficient thermal
insulation-approved.
BLDG-18 Exterior
Lath/Drywall
166598-2021 Passed Tony Alvarado
Checklist Item
BLDG-Building Deficiency
COMMENTS
September 15, 2021: (virtual inspection).
1. No gypsum board, exterior stucco lath,
insulation and gas test deficiencies.
2. Exterior stucco wire lath , metal weep
screed, corner beads, attachment
anchoring, and all penetrations sealed with
silicone caulking, scope of work-approved.
3. Gypsum/drywall board; type, size,
method of attachment anchoring
system/schedule -approved.
4. Gas line, under air pressure leak test-
approved.
5. Energy-efficient thermal
i nsu latio n-a p proved.
Passed
Yes
Complete
Passed
Yes
Complete
Passed
Yes
Page2of3
Building Permit Inspection History Finaled
(city of
Carlsbad
PERMIT INSPECTION HISTORY for {CBR2021-1039)
Permit Type: BLDG-Residential Application Date: 04/15/2021 Owner: COOWNER ROBERT AND CLAUDIA
WESTON
Work Class: Addition Issue Date: 07/26/2021 Subdivision: CARLSBAD TCT#74-04
Status: Closed -Finaled Expiration Date: 03/14/2022 Address: 2708 OLYMPIA DR
IVR Number: 32764 CARLSBAD, CA 92010-2179
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Reinspection Inspection
Date Start Date Status
07/30/2021 07/30/2021 BLDG-SW-Pre-Con 163177-2021 Passed Tony Alvarado Complete
Checklist Item COMMENTS Passed
BLDG-Building Deficiency July 29, 2021: (Virtual inspections). No
1. No stormwater preconstruction/Building
Deficiencies.
2. Informed Jose Gomez-contractor
representative, preconstruction meeting
guidelines to be observed, city of Carlsbad.
Pre-Construction-policies and
procedures-approved.
08/18/2021 08/18/2021 BLDG-81 Underground 164484-2021 Passed Tim Kersch Complete
Combo(11, 12,21,31)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-11 Foundation-Ftg-Piers No
(Rebar)
09/09/2021 09/09/2021 BLDG-84 Rough 166122-2021 Passed Tim Kersch Complete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
09/15/2021 09/15/2021 BLDG-16 Insulation 166543-2021 Passed Tony Alvarado Complete
Tuesday,January11,2022 Page 1 of3
DATE: 07/06/2021
JURISDICTION: City of Carlsbad
PLAN CHECK#.: CBR2021-1039
EsGil
SET: II
PROJECT ADDRESS: 2708 Olympia Drive
0 APPLICANT
0 JURIS.
PROJECT NAME: SFD Closet Addition + Bathroom Remodel
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
~ The plans transmitted herewith will substantially comply with the jurisdiction's building codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
Scott Piddington
~ EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
~
Person contacted: Scott Pidington Telephone#: 858-361-8271
Date contacted: (by: ) Email: pacdesignstudios@gmail.com
Mail Telephone
FIii I I
By: Ali Doudar
EsGil
Fax In Person -
06/28/2021
Enclosures:
ll;J/A -~ioA
LJrvG-Ul 1.,0~
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
I
.,,,
J
DATE: 05/07/2021
JURISDICTION: City of Carlsbad
PLAN CHECK#.: CBR2021-1039
✓• EsG1I
SETI
PROJECT ADDRESS: 2708 Olympia Drive
PROJECT NAME: SFD Closet Addition + Bathroom Remodel
□ APPLICANT
□ JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
~ The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
~ The applicant's copy of the check list has been sent to:
Scott Piddington
D EsGil staff did not advise the applicant that the plan check has been completed.
~ EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Scott Pidington Telephone#: 858-361-8271
Date contacted: (by: ) Email: pacdesignstudios@gmail.com
Mail Telephone
0 REMARKS:
By: Ali Doudar
EsGil
Fax In Person
Enclosures:
04/19/2021
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
City of Carlsbad CBR2021-l 039
05/07/2021
PLAN REVIEW CORRECTION LIST
SINGLE FAMILY DWELLINGS AND DUPLEXES
PLAN CHECK#.: CBR2021-1039 JURISDICTION: City of Carlsbad
PROJECT ADDRESS: 2708 Olympia Drive
FLOOR AREA: 58 SF Addition. 20 SF Remodel STORIES: 1
HEIGHT: 8' TOP
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 05/07/2021
FOREWORD (PLEASE READ):
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 04/19/2021
PLAN REVIEWER: Ali Doudar
This plan review is limited to the technical requirements contained in the California Residential
Code, California Building Code, California Plumbing Code, California Mechanical Code,
California I Electrical Code and state laws regulating energy conservation, noise attenuation and
access for the disabled. This plan review is based on regulations enforced by the Building
Department. You may have other corrections based on laws and ordinance by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Present California law mandates that construction comply with the 2019 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2019 CRC, 2019 CBC,
2019 CPC, 2019 CMC and 2019 CEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2019 California Building Code, the approval of the plans does not permit the violation of any
state, county or city law.
To speed up the recheck process. please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
City of Carlsbad CBR2021-1039
05/07/2021
PLANS
Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to EsGil, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil is complete.
1. A reminder that due to Covid-19, the City will not permit counter corrections.
Please make sure all the items are satisfied; otherwise, another round of
corrections will be necessary.
2. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
3. Specify on the Title Sheet of the plans the gross floor area of each element of
this project, including dwelling, garage, carport, patio, deck and balcony. Section
R106.2.
4. Section R106.2. Please include the following on the site plan:
a) North arrow.
b) Property lines/easements.
5. Clearly dimension building setbacks from property lines, street centerlines, and
from all adjacent buildings and structures on the site plan. Section R106.2.
6. On the cover sheet of the plans, specify any items that will have a deferred
submittal (trusses, fire sprinklers/alarms, etc.). Additionally, provide the
following note on the plans: "Submittal documents for deferred submittal items
shall be submitted to the registered design professional in responsible charge,
who shall review them and forward them to the building official with a notation
indicating that the deferred submittal documents have been reviewed and that
they have been found to be in general conformance with the design of the
building. The deferred submittal items shall NOT be installed until their design
and submittal documents have been approved by the building official."
City of Carlsbad CBR2021-1039
05/07/2021
FIRE PROTECTION
7. Please indicate on the plans whether the existing residence has a fire sprinkler
system installed. If so, then provide a note stating that any additions/alterations
will be provided with an automatic residential fire sprinkler system. Section
R313.2.
GENERAL RESIDENTIAL REQUIREMENTS
8. Please detail extent of proposed master bathroom remodel by providing and
existing floor plan. Please specify and show on the plans all changes. More
comments may apply after scope is understood.
ROOFS/DECKS/BALCONIES
9. Specify roof material and application. Chapter 9.
a) In California, roofing shall be a fire-retardant roof covering that is at least
Class C. Section R902.1.3.
10. Specify on the plans the following information for the roof materials, per Section
R106.1.1:
a) Manufacturer's name and product name/number.
b) ICC approval number, or equal.
11. Show the required ventilation for attics (or enclosed rafter spaces formed where
ceilings are applied directly to the underside of roof rafters). The minimum vent
area is 1/150 of attic area (or 1/300 of attic area if at least 40% (but not more
than 50%) of the required vent is located no more than 3' below the ridge) and
remaining vents located at the lower third of the of the attic space. Show on the
plans the area required and area provided. Section R806.2.
a) When using a radiant barrier, California energy design affects the attic
ventilation area requirement: If using the Prescriptive method for energy
compliance, then the attic vent area must be at the 1/150 area: If using
the Performance method, either the 150 or 300 areas may be used, as
documented on the energy forms. Section RA4.2.1.
12. Enclosed rafter spaces do not require venting if the following specific insulation
design is used, per Sections R806.5/EM3.9.6:
• If the insulation is air-permeable and it is installed directly below the roof
sheathing with rigid board or sheet insulation with a minimum R-5 value installed
above the roof sheathing. (or)
• If the insulation is air-impermeable and it is in direct contact with the underside
of the roof sheathing. (or)
City of Carlsbad CBR2021-1039
05/07/2021
+ If two layers of insulation are installed below the roof sheathing: An air-
impermeable layer in direct contact with the underside of the roof sheathing and
an additional layer of air permeable insulation installed directly under the air-
impermeable insulation.
♦ In climate zones 3-15, air permeable insulation installed as part of one of the
previous insulation assemblies in unvented attics must comply with section
R806.5.5.2
13. Where eave vents are installed, insulation shall not block the free flow of air. A
minimum of 1" of air space shall be provided between the insulation and the roof
sheathing. To accommodate the thickness of insulation plus the required 1"
clearance, member sizes may have to be increased for rafter-ceiling joists.
Section R806.3.
14. Note on the plans: "Attic ventilation openings shall be covered with
corrosion-resistant metal mesh with 1/16" minimum to¼" maximum openings.
Section R806.1.
STRUCTURAL
15. Specify stud size, species and grade for the proposed addition
16. Specify nail size and spacing for roof diaphragms on the plans. Table R602.3(1 ).
Specify plywood and/or particle board thickness, grade and panel span rating.
Table R503.2.1 (1)
17. You have chosen to use the conventional construction bracing
provisions outlined in the CRC. Provide documentation to show that the plans
comply with the Braced Wall provisions of Section R602.10. Include the
following:
a) Documentation to show there are sufficient Braced Wall Panels in each
Braced Wall Line(Specify Bracing method), per Section 602.10.1.1. Be
sure to include all length factor adjustments from Section 602.10.
18. The plans shall indicate that special inspection will be provided for the following
work. (CBC Chapter 17 and Section 107 .2)
a) Expansion anchors/Epoxy Dowels .. Periodic special inspection should
be provided for anchors installed in hardened concrete. Please specify
special Inspection for Epoxy dowels per ICC ESR-7508. Section 1705.3.
ELECTRICAL
19. Please provide an electrical plan for the proposed bathroom remodel. The
following electrical comments may be applicable depending on the extent of the
remodel. ..
City of Carlsbad CBR2021-1039
05/07/2021
20. Show on the Electrical plan the following specifications for electrical devices
installed in dwellings: CEC Article 210 & 406
a) GFCI protected outlets for locations described in NEC 210.8(A): Laundry
areas, kitchen dishwashers, kitchens, garages, bathrooms, outdoors,
within 6' of a sink, etc.
21. Show on the plans a wall receptacle within 36" of each lavatory in the bathroom.
CEC 210.52(0).
22. Show at least one wall switch-controlled lighting outlet to be installed in every
habitable room; in bathrooms. CEC Article 210.70.
Residential Energy Lighting Requirements: ES 150.0(k)
23. All installed luminaires shall be high-efficacy in accordance with ES TABLE
150.0-A.
a) Luminaries must have a label certified for airtight construction.
b) Light sources that are not marked "JAB-2019-E" shall not be installed
in enclosed luminaires. ES 150.0(k)
24. In bathrooms, garages, laundry rooms, and utility rooms at least one luminaire
shall be controlled by a vacancy sensor.
25. Dimmers or vacancy sensors shall control all LED style luminaires. Two
exceptions: Fixtures installed in hallways or (closets under 70 square feet).
26. Recessed can light fixtures shall be IC listed, air-tight labeled, and not be
equipped with a standard medium base screw shell lamp holder. ES 150.0(k)
27. Bathrooms require exhaust fans (minimum 50 cfm) to be ducted to the exterior.
A bathroom is defined "as a room with a bathtub, shower, or spa or some similar
source of moisture". Please Show proposed/existing fan.
PLUMBING
28. Specify on the plans: Water conserving fixtures: New water closets shall use no
more than 1.28 gallons of water per flush, kitchen faucets may not exceed 1.8
GPM, lavatories are limited to 1.2 GPM, and showerheads may not exceed 1.8
GPM of flow. CPC Sections 407, 408, 411, 412.
29. For additions or improvements to a residence built before 1994, note on the
plans that existing "noncom pliant" fixtures (toilets that use more than 1.6
gallons of water per flush, urinals that use more than one gallon of water
per flush, showerheads that have a flow capacity of more than 2.5 gallons
of water per minute, and interior faucets that emit more than 2.2 gallons of
' ' City of Carlsbad CBR2021-1039
05/07/2021
water per minute) shall be replaced. Certification of compliance shall be
given to the building inspector prior to final permit approval. California
SB407.
RESIDENTIAL GREEN BUILDING STANDARDS
The following mandatory requirements for residential construction must be included on
your plans. CGC Section 101.3. The Standards apply to newly constructed residential
buildings, along with additions/alterations that increase the building's conditioned
area, volume or size.
30. Indoor water use. Show compliance with the following table, per CGC Section
4.303.1.
FIXTURE FLOW RATES
FIXTURE TYPE MAXIMUM FLOW RA TE
Water closets 1.28 gallons/flush
Urinals (wall-mounted) 0.125 gallon/flush
Urinals (others) 0.5 gallon/flush
Showerheads 1.8 gpm @ 80 psi
Lavatory faucets 1.2 gpm @ 60 psi1
Kitchen faucets 1.8 gpm @ 60 psi
Metering faucets 0.20 gallons per cycle
1. Lavatory faucets shall not have a flow rate less than 0.8 gpm at 20 psi.
31. Note on the plans that when a shower is provided with multiple shower heads,
the sum of flow to all the heads shall not exceed 1.8 gpm @ 80 psi, or the
shower shall be designed so that only one head is on at a time. CGC Section
4.303.1.3.2.
32. Recycling. Note on the plans that a minimum of 65% of construction waste is to
be recycled. CGC Section 4.408.1.
33. Recycling. Note on the plans that the contractor shall submit a Construction
Waste Management Plan, per CGC Section 4.408.2.
34. Operation and maintenance manual. Note on the plans that the builder is to
provide an operation manual (containing information for maintaining appliances,
etc.) for the owner at the time of final inspection. CGC Section 4.410.1.
35. Note on the plans that the gas fireplace(s) shall be a direct-vent sealed-
combustion type. Woodstove or pellet stoves must be US EPA Phase II rated
appliances. CGC Section 4.503.1.
City of Carlsbad CBR202 l-1039
05/07/2021
36. Pollutant control. Note on the plans that during construction, ends of duct
openings are to be sealed, and mechanical equipment is to be covered. CGC
Section 4.504.1.
37. Pollutant control. Note on the plans that VOC's must comply with the
limitations listed in Section 4.504.3 and Tables 4.504.1, 4.504.2, 4.504.3 and
4.504.5 for: Adhesives, Paints and Coatings, Carpet and Composition Wood
Products. CGC Section 4.504.2.
38. Interior moisture control. Note on the plans that concrete slabs will be
provided with a capillary break. CGC Section 4.505.2.1.
39. Interior moisture control. Note on the plans that the moisture content of wood
shall not exceed 19% before ii is enclosed in construction. The moisture content
needs to be certified by one of 3 methods specified. Building materials with
visible signs of water damage should not be used in construction. The moisture
content must be determined by the contractor by one of the methods listed in
CGC Section 4.505.3.
40. Indoor air quality. Note on the plans that bathroom fans shall be Energy Star
rated, vented directly to the outside and controlled by a humidistat. CGC
4.506.1.
MISCELLANEOUS
41. To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
42. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction list?
Please indicate:
Yes □ No □
43. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Ali Doudar at EsGil. Thank you.
\
'
•
City of Carlsbad CBR2021-1039
05/07/2021
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: City of Carlsbad
PREPARED BY: Ali Doudar
PLAN CHECK#.: CBR2021-1039
DATE: 05/07/2021
BUILDING ADDRESS: 2708 Olympia Drive
BUILDING OCCUPANCY: R-3
BUILDING AREA Valuation
PORTION ( Sq. Fl.) Multiplier
Addition 20
Remodel 58
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
1997 BC Buildin Permit Fee u g ...
I /: I '.,
1997 USC Plan Check Fee •
I ·,,:.1 '
Type of Review: Complete Review
D Repetitive Fee
,.. Repeats
□ Other
lJ Hourly
EaGil Fee
Reg. VALUE
Mod.
r7 Structural Only
Comments: In addition to the above fee, an additional fee of$
$ /hr.) for the CalGreen review.
($)
10,761
10,761
is due ( hour@
Sheet of
STORM WATER POLLUTION PREVENTION NOTES
1. ALL NECESSARY EQUIPMENT AND MATERIALS SHALL BE
AVAILABLE ON SITE TO FACILITATE RAPID INSTALLATION
OF EROSION AND SEDIMENT CONTROL BMPs WHEN RAIN
IS EMINENT.
2. THE OWNER/CONTRACTOR SHALL RESTORE ALL EROSION
CONTROL DEVICES TO WORKING ORDER TO THE SA Tl SF ACTION
OF THE CITY INSPECTOR AFTER EACH RUN-OFF PRODUCING
RAINFALL.
3. THE OWNER/CONTRACTOR SHALL INSTALL ADDITIONAL EROSION
CONTROL MEASURES AS MAY BE REQUIRED BY THE CITY
INSPECTOR DUE TO INCOMPLETE GRADING OPERATIONS OR
UNFORESEEN CIRCUMSTANCES WHICH MAY ARISE.
4. ALL REMOVABLE PROTECTIVE DEVICES SHALL BE IN PLACE
AT THE END OF EACH WORKING DAY WHEN THE FIVE (5)
DAY RAIN PROBABILITY FORECAST EXCEEDS FORTY PECENT
( 40%). SILT AND OTHER DEBRIS SHALL BE REMOVED AFTER
EACH RAINFALL.
5. ALL GRAVEL BAGS SHALL CONTAIN 3/4 INCH MINIMUM
AGGREGATE.
6. ADEQUATE EROSION AND SEDIMENT CONTROL AND PERIMETER
PROTECTION BEST MANAGEMENT PRACTICE MEASURES MUST
BE INSTALLED AND MAINTAINED.
7. THE CITY INSPECTOR SHALL HAVE THE AUTHORITY TO ALTER
THIS PLAN DURING OR BEFORE CONSTRUCTION AS NEEDED
TO ENSURE COMPLIANCE WITH CITY STORM WATER QUALITY
REGULATIONS.
OWNER'S CERTIFICATE:
I UNDERSTAND AND ACKNOWLEDGE THAT I MUST: (1) IMPLEMENT
BEST MANAGEMENT PRACTICES (BMPS) DURING CONS1RUCTION
ACTIVITIES TO THE MAXIMUM EXTENT PRACTICABLE TO AVOID
THE MOBILIZATION OF POLLUTANTS SUCH AS SEDIMENT AND TO
AVOID THE EXPOSURE OF STORM WATER TO CONS1RUCTION
RELATED POLLUTANTS; AND (2) ADHERE TO, AND AT ALL TIMES,
COMPLY WITH THIS CITY APPROVED TIER 1 CONS1RUCTION SWPPP
THROUGHOUT THE DURATION OF THE CONS1RUCTION ACTIVITIES
UNTIL THE CONS1RUCTION WORK IS COMPLETE AND APPROVED
BY THE CITY OF CARLSBAD.
'-' I~• ,cl.in , \ 00>~[F -{K.o l,tv ,,+ WeS/o 0 ""~•ril{c! ""~•m's "'ENT NAME PRINT) 'C' ) I ... -7 ✓Jl,~
AGENT NAME (SIGNATURE) DA TE
E-29
STORM WATER COMPLIANCE FORM
TIER 1 CONSTRUCTION SWPPP ffi~G-\ -1a 3 0\
BEST MANAGEMENT PRACTICES (BMP) SELECTION TABLE
Erosion Control Sediment Control BMPs Tracking Non-Stam, Water Waste Management and Materials
BMPs Control BMPs Management BMPs Pollution Control BMPs
c:: -c:: c:: 0 -0 0 :;:; c:: c:: -0 :;:; :;:; en 0 Q) -0 Q) -0
"' c:: 0 0 c:: .!: en E c:: E c:: -0 -::, ::, 0 ·.: c_ a 0 a E Q) L L :;:; -0 L ·,, Q) Q)
::e -0 "' en L -->, en -c:: Q) L c:: Q) c "'"' "' 0 .!: '-a-L a c:: "' en c_ Q) c:: > L L ~ 0
Best Management Practice* oll c:: Ocj a 'ci_ ·.: -c::"' L (.') w c:: a
"' L CD L 0 Q) 0 Q) Q) Q) a :;:; -3=-:c "'~ c:: >-Q) 0 c:: (.) L '-' "' --0 al "' ~ Q) c:: c::
(BMP) Description ➔ "' 0 Q) (/) ·5 E "' en ., en CD "i5 C en c:: -0 "' ~ c:: ::e
-Q) "' Q) Q) 'S == (I)
Q) -a 0 ~ c:: LO ~~ -0 >, 0"' c:: c:: a Cl ::::, 13 E :;3 L 0 c:: Cl 0 CD (/) ·-en 0:.::, '-' Q) Oo en Q) Q) ::, E
X ::e Cl a, Cl c:: Q) Ck'. E 0 N <n :!la 0 en+' Q) Q) c:: E~ 0 ~ L-3= Q) 0 Q)
Q) a Q) E .Y. al -::, .0 E f;l :.::: f/) ~i L•-:0 o·c -~ CL E' en ~ en --0 .c c:: Q) u.. 0 L Q) ::, -0 :..c ~ Q) 1, c:: a 0 L 0 .Y. ---0 0 oa -·-c_ '5 > L-.0 0 -~ ~ ·-0 Q) L 0
0 0 Q) Q) I':' 0 c:: -a --o -= C ·-c:: NC:: LO 0 -a 0 0 o en .8 0 .c Q) 0
Q) 0 0L en Q) .c .0 L -o 0 -L en " OL 0 ~u o_ 0 -c_ 0 oo ao
(.') 3= WO vi (/) '-' [;:: (.') (/) > (/) (I) CL (/) Ck'. 3= CL CLO CL ::e (/) ::e (/) (/) '-' (/) ::e I ::,e
CASQA Designation ➔ r--00 cr, ~ "' .... 0 N "' r--00 N "' .... "' <O
'T "' <O r--00
I I I I I I I I I I 'T I I I I I I I I I I I I
'-' '-' '-' '-' w w w w w w w w g, g, (/) (/) (/) (/) ::e ::e ::e ::e ::e ::e
Construction Activity w w w w (/) (/) (/) (/) (/) (/) (/) (/) z z z z 3= 3= 3= 3= 3= 3=
Gradinn /Soil Disturbance )o
Trenchin° !Excavation
Stock□ilino
Drill inn /Barino
Concrete/Asohalt Sawcuttina 'v
Concrete Flatwork
Pavina
Conduit/Pioe Installation
Stucco/Mortar Work
Waste Disoosal
Staainn /Lav Down Area
Eauinment Maintenance and Fuelina
Hazardous Substance Use/Storaoe
Dewaterino
Site Access Across Dirt
Other !list):
Instructions: 1. Check the box to the left of all applicable construction activity (first column) expected to occur during construction.
2. Located along the top of the BMP Table is a list of BMP's with it's corresponding California Stormwater Quality Association (CASQA) designation number. Choose one or more BMPs you intend to use during construction from the list. Check the box where the chosen activity row intersects with the BMP column.
3. Refer to the CASQA construction handbook for information and details of the chosen BMPs and how to apply them to the project.
PROJECT INFORMATION
Site Addres2":7O'.t, G¼rnp\ d-A Assessor's Parcel Number: _______ _
Emergency Contact: ~
Name: .12alt>~r::t W€7 0 Yl
24 Hour Phone: f3 S t'.J -4--JlA----,.. .;i.3. ".<
-41-4--
Construction Threat to Storm Water Quality
(Check Box)
~EDIUM □ LOW
Q) -"' o-3= c:: Q) ., E
-Q) I':' en oo c:: c:: 0 0 '-' ::e
00 I ::e 3=
Page 1 of 1 REV 11/17
~-Citv of '--. Carlsbad
PURPOSE
CLIMATE ACTION PLAN
CONSISTENCY CHECKLIST
B-50
Building Division
1635 Faraday Avenue
(760) 602-2719
www.carlsbadca.gov
This checklist is intended to assist building permit applicants identify which Climate Action Plan (CAP) ordinance
requirements apply to their projects. The completed checklist must be included in the building permit application. It may be
necessary to supplement the completed checklist with supporting materials, calculations or certifications, to demonstrate
full compliance with CAP ordinance requirements. For example, projects that propose or require a performance approach
to comply with energy-related measures will need to attach to this checklist separate calculations and documentation as
specified by the ordinances.
NOTE: The following type of permits are not required to fill out this form
❖ Patio I ❖ Decks I ❖ PME (w/o panel upgrade) I ❖ Pool
.,; If an item in the checklist is deemed to be not applicable to a project, or is less than the minimum required by ordinance,
an explanation must be provided to the satisfaction of the Building Official.
.,; Details on CAP ordinance requirements are available on the city's weos•t_Ee .
.,; A CAP Building Plan template (form B-55) shall be added to the title page all building plans. This template shall be
completed to demonstrate project compliance with the CAP ordinances. Refer to the building application webpam, and
download the latest form.
Appllcationlnfonnatlon
Project Name/Building
Permit No.: Weston Residence
Property Address/APN: 167-432-24-00
Applicant Name/Co. Scott Piddington
Applicant Address. 14781 Pomerado Road #149
BP No.:
Contact Phone: 858-361-8271 Contact Email: pacdesignstudios@gmail.com