HomeMy WebLinkAbout1950 CAMINO VIDA ROBLE; 100; CBC2021-0362; PermitPERMIT REPORT
(city of
Carlsbad
Commercial Permit
Print Date: 05/31/2022 Permit No: CBC2021-0362
Job Address: 1950 CAMINO VIDA ROBLE, # 100, CARLSBAD, CA 92008-6599 Status: Closed -Finaled
Permit Type: BLDG-Commercial
2120931200
$817,227.00
Work Class: Tenant Improvement
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Project Title:
Track#:
Lot#:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#:
Plan Check#:
Description: ALPHATEC SPINE: Tl OFFICE(l5,080 SF) & INDUSTRIAL(2491SF)FROM SHELL
Applied: 09/17/2021
Issued: 11/23/2021
Finaled Close Out: 04/08/2022
Inspector:
Final Inspection:
TKers
04/08/2022
Property Owner: Contractor:
RAF PACIFICA GROUP-REAL ESTATE FUND IV SPW CONSTRUCTION DBA WHITE
FEE
LLC
111 CST, # 200
ENCINITAS, CA 92024
SB1473 -GREEN BUILDING STATE STANDARDS FEE
COMM/IND USES-STRUCTURAL
BUILDING PLAN CHECK
GREEN BUILDING STANDARDS PLAN CHECK & INSPECTION
STRONG MOTION -COMMERCIAL (SMIP)
BUILDING PLAN REVIEW-MINOR PROJECTS (PLN)
BUILDING PLAN REVIEW-MINOR PROJECTS (LOE)
FIRE F Occupancies Tl
BUILDING PLAN CHECK FEE (manual)
Total Fees: $10,232.78 Total Payments To Date: $10,232.78
CONSTRUCTION
2524 GATEWAY RD
CARLSBAD, CA 92009
(760) 931-1130
Balance Due:
AMOUNT
$33.00
$4,652.84
$2,693.37
$175.00
$228.82
$98.00
$194.00
$691.00
$1,466.75
$0.00
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a), and file the
protest and any other required information with the City Manager for processing in accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
1635 Faraday Avenue I Carlsbad, CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
( City of
Carlsbad
COMMERCIAL
BUILDING PERMIT
APPLICATION
B-2
Plan Check Ci3c2° '},/-031P ;J.-
Est. Value
PC Deposit -----,~-------~-q -17--7/ Date-----'--=-~,,,,_,:::__:_ __
Job Address 1950 Camino Vida Roble
CT/Project#: tJL/?hc.rkc ,5;2117~_,
Suite: ____ APN: 212-093-05, 12
Lot#: ___ _
Fire Sprinklers: 0 YES O NO Air Conditioning: 0 YES O NO Electrical Panel Upgrade: 0 YES O NO
BRIEF DESCRIPTION OF WORK: 17,571 s.f. tenant improvement Including structural, mechanical, plumbing and electrical for a new corporate
office and R&D facility, no site work Is part of this application
0 Addition/New: _____ Living SF, ____ Deck SF, ___ Patio SF, ____ Garage SF
Is this to create an Accessory Dwelling Unit? OY 0 N New Fireplace? OY 0 N, if yes how many? __
0Remodel: _1_7,_57_1 __ SF of affected area Is the area a conversion or change of use ? 0 Y ON
0 Pool/Spa: ____ SF Additional Gas or Electrical Features? ____________ _
□solar: ___ KW, __ Modules, Mounted:0Roof0Ground, Tilt:0 YON, RMA: OYON,
Battery:OY ON, Panel Upgrade: OY ON
D Reroof: n/a --------------------------------
□ Plumbing/Mechanical/Electrical Only: _______________________ _
D Other: ______________________________ _
e ,s&;v
APPLICANT (PRIMARY CONTACT)
Name: Andrew Tarango, SCA Architecture
Address: 13280 Evening Creek Drive, suite 125
City: San Diego State:CA Zip: 92128
Phone: 858-793-4777 1
Email: andrewt@sca-sd.comfl( !{ ·
)I,@ /yt'J&t,!,.~ t H1.,J
DESIGN PROFESSIONAL
Name: Cheryl D. Smith, SCA Architecture
Address: 13280 Evening Creek Drive, Suite 125
City: San Diego State:CA Zip: 92128
Phone: 858-793-4777
Email: _________________ _
Architect State License: C11,701 ----'-----------
PROPERTY OWNER
Name: Adam Robinson, RAF Pacifica Group
Address: 315 S. Coast Hwy 101, Suite U-12
City: Encinitas State: CA Zip: _9_20_2_4 __ _
Phone: 760-473-8838
Email: adam@RAFPacificaGroup.com
CONTRACTOR BUSINESS
Name: SPW Construction, Inc.
Address: 2524 Gateway Road
City: Carlsbad State: CA Zip: _e2_0_0_8 ___ _
Phone: 760-931-1130
Email: sean@whiteconstructioninc.com
State License: 1023856 Bus. License:BLNR000431-02-2017
(Sec. 7031.5 Business and Professions Code: Any City or County which requires a permit to construct, alter, improve, demolish or repair any structure, prior to Its
issuance, also requires the applicant for such permit to file a signed statement that he/she is licensed pursuant to the provisions of the Contractor's License Law
{Chapter 9, commending with Section 7000 of Division 3 of the Business and Professions Code} or that he/she is exempt therefrom, and the basis for the alleged
exemption. Any vlolatlon of Section 7031.5 by any applicant for a permit subjects the applicant to a civil penalty of not more than five hundred dollars {$500}).
1635 Faraday Ave Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: Building@carlsbadca.gov
B-1 Page 1 of2 Rev. 06/18
( OPTION A): WORKERS'COMPENSATION DECLARATION:
I hearby affirm under penalty of perjury Q!le. of the following dee/orations: DI have and will maintain a certificate of consent to self-Insure for workers' compensation provided by Section 3700 of the labor Code, for the performance of the
work which this permit is issued.
0 I have and will maintain worker's compensation, as required by Section 3700 of the Labor Code, for the performance of the work for which this permit ls Issued.
My workers' compensation insurance carrier and pollcy number are: Insurance Company Name: State Compensation Ins. Fund
Polley No. 9243036-19 Expiration Date: 01/01/2022
D Certificate of Exemption: I certify that In the performance of the work for which this permit Is Issued, I shalt not employ any person in any manner so as to be come
subject to the workers' compensation Laws of California. WARNING: Failure to secure workers compensation covera1e ls unlawful, and shall subjed an employer to
criminal penalties and civil fines up to $100,000.00, In addition the to the cost of compensation, dama1es as provided for In Section 3706 of the Labor Code,
Interest and attorney's fees.
CONTRACTOR SIGNATURE: /_,(/~c / , Vice President □AGENT DATE: -----------'--------------------
( OPTION B ): OWNER-BUILDER DECLARATION:
I hereby affirm that I am exempt from Contractor's License Low for the following reason:
0 I, as owner of the property or my employees with wages as their sole compensation, will do the work and the structure Is not Intended or offered for sale (Sec.
7044, Business and Professions Code: The Contractor's license Law does not apply to an owner of property who builds or improves thereon, and who does such work
himself or through his own employees, provided that such improvements are not Intended or offered for sale. If, however, the building or Improvement is sold within
one year of completion, the owner-builder will have the burden of proving that he did not build or improve for the purpose of sale).
0 I, as owner of the property, am exclusively contracting with licensed contractors to construct the project (Sec. 7044, Business and Professions Code: The
Contractor's license Law does not apply to an owner of property who builds or Improves thereon, and contracts for such projects with contractor(s) licensed
pursuant to the Contractor's License Law).
0 I am exempt under Section _______ Business and Professions Code for this reason:
1. I personally plan to provide the major labor and materials for construction of the proposed property improvement. QYEs Q NO
2. I (have/ have not) signed an application for a building permit for the proposed work.
3. I have contracted with the following person (flrm) to provide the proposed construction (Include name address/ phone/ contractors' license number):
4. I plan to provide portions of the work, but I have hired the following person to coordinate, supervise and provide the major work (include name/ address / phone /
contractors' license number):
5. I will provide some of the work, but I have contracted (hired) the following persons to provide the work Indicated (include name/ address/ phone/ type of work):
OWNER SIGNATURE: □AGENT DATE: _____ _ ----------------------
CONSTRUCTION LENDING AGENCY, IF ANY:
I hereby affirm that there is a construction lending agency for the performance of the work thls permit Is Issued (Sec. 3097 (I) Civil Code).
Lender's Name: ____________________ Lender's Address: ___________________ _
ONLY COMPLETE THE FOLLOWING SECTION FOR NON-RESIDENTIAL BUILDING PERMITS ONLY:
Is the applicant or future building occupant required to submit a business plan, acutely hazardous materials registration form or risk management and prevention
program under Sections 25505, 25533 or 25534 of the Presley-Tanner Hazardous Substance Account Act? Yes
Is the applicant or future building occupant required to obtain a permit from the air pollution control district or air quality management district? No
Is the facility to be constructed within 1,000 feet oft he outer boundary of a school site? No
IF ANY OF THE ANSWERS ARE YES, A FINAL CERTIFICATE OF OCCUPANCY MAY NOT BE ISSUED UNLESS 111E APPLICANT HAS MET OR 15 MEETING 111E
REQUIREMENTS OF 111E OFFICE OF EMERGENCY SERVICES AND THE AIR POLLUTION CONTROL DISTRICT.
APPLICANT CERTIFICATION:
I certify that I have read the applicatlon and state that the above Information Is correct and that the Information on the plans Is accurate. I agree to comply with all
City ordinances and State laws relating to bullding construction.
I hereby authorize representative of the City of Carlsbad to enter upon the above mentioned property for Inspection purposes. I ALSO AGREE TO SAVE, INDEMNIFY AND KEEP
HARMLESS 111E CllY OF CARISBAO AGAINST ALL UABILITlES, JUDGMENTS. COSTS AND EXPENSES WHICH MAY IN ~y WAY ACCRUE AGAINST SAID CllY IN CONSEQUENCE OF
THE GRANTING OF THIS PERMIT.OSHA: An OSHA permit is required for excavations over 5'0' deep and demolition or construction of structures over 3 stories in height
EXPIRATION: Every permit issued by the Building Official under the provisions of this Code shall expire by limitation and become null and void If the bu lid Ing or work authorized
by such permit is not commenced within 180 days from the date of such permit or If the building or work authorized by such permit is suspended or abandoned at any time
after the work is commenced for a period of 180 days (Section 106.4.4 Uniform Building Code).
APPLICANT SIGNATURE: __ cd_J, _________________ DATE: __ __;0e:9"-'.1"'3=.2.,_1 __
1635 Faraday Ave Carlsbad, CA 92008
B-1
Ph: 760-602-2719 Fax: 760-602-8558
Page 2 of 2
Email: Building@carlsbadca.gov
Rev. 06/18
e,:0 ' c10 ,,
PERMIT INSPECTION HJSTOR'(, for,z,(CBC2021-0362)
Permit Type: BLDG-Commercial Application Date:
Work Class: Tenant Improvement Issue Date:
Status: Closed -Finaled Expiration Date:
IVR Number:
Scheduled Actual Inspection Type Inspection No.
Date Start Date
Tuesday, May 31, 2022
Checklist Item
BLDG-Building Deficiency
BLDG-Plumbing Final
BLDG-Mechanical Final
BLDG-Structural Final
BLDG-Electrical Final
COMMENTS
09/17/2021 Owner: RAF PACIFICA GROUP-REAL ESTATE
FUND IV LLC
11/23/2021 Subdivision: CARLSBAD TCT#81-46 UNIT#02
08/31/2022 Address: 1950 CAMINO VIDA ROBLE, # 100
35953 CARLSBAD, CA 92008-6599
Inspection Primary Inspector Reinspection Inspection
Status
Passed
Yes
Yes
Yes
Yes
Yes
Page 3 of 3
' -
PERMIT INSPECTI<)N HISTORY: for (CBC2021-0362)
Permit Type: BLDG-Commercial Application Date: 09/17/2021 Owner: RAF PACIFICA GROUP-REAL ESTATE
FUND IV LLC
Work Class: Tenant Improvement Issue Date: 11/23/2021 Subdivision: CARLSBAD TCT#81-46 UNIT#02
Status: Closed -Finaled Expiration Date: 08/31/2022 Address: 1950 CAMINO VIDA ROBLE, # 100
IVR Number: 35953 CARLSBAD, CA 92008-6599
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Reinspection Inspection
Date Start Date Status
01/19/2022 01/19/2022 BLDG-17 Interior 174785-2022 Partial Pass Tim Kersch Reinspection Incomplete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
02/04/2022 02/04/2022 BLDG-11 175984-2022 Passed Tim Kersch Complete
Foundation/Ftg/Piers
(Rebar)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
02/10/2022 02/10/2022 BLDG-17 Interior 176419-2022 Passed Tony Alvarado Complete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency February 1 O, 2022: Yes
1. Drywall/gypsum board: type, size, and
attachment pattern, Phase 2-drywall
completed-approved.
02/25/2022 02/25/2022 BLDG-44 177306-2022 Partial Pass Tim Kersch Reinspection Incomplete
Rough/Ducts/Dampers
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
03/04/2022 03/04/2022 BLDG-85 T-Bar, Ceiling 177755-2022 Passed Tim Kersch Complete
Grids, Overhead
Checklist Item COMMENTS Passed
BLOG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
03/31/2022 03/31/2022 BLDG-Final Inspection 179411-2022 Partial Pass Tim Kersch Reinspection Incomplete
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-Plumbing Final No
BLDG-Mechanical Final No
BLDG-Structural Final Yes
BLOG-Electrical Final Yes
04/08/2022 04/08/2022 BLDG-Final Inspection 180050-2022 Passed Tim Kersch Complete
Tuesday, May 31, 2022 Page 2 of 3
Building Permit Inspection History Finaled
(city of
Carlsbad
PERMIT INSPECTION HISTORY for (CBC2021-0362)
Permit Type: BLDG-Commercial Application Date: 09/17/2021 Owner: RAF PACIFICA GROUP-REAL ESTATE
FUND IV LLC
Work Class: Tenant Improvement Issue Date: 11/23/2021 Subdivision: CARLSBAD TCT#81-46 UNIT#02
Status: Closed -Finaled Expiration Date: 08/31/2022 Address: 1950 CAMINO VIDA ROBLE, # 100
IVR Number: 35953 CARLSBAD, CA 92008-6599
Scheduled Actual Inspection Type Inspection No. Inspection Primary Inspector Reinspection Inspection
Date Start Date Status
02/09/2022 BLOG-17 Interior 176418-2022 Cancelled Tim Kersch Re inspection Incomplete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
11/30/2021 11/30/2021 BLDG-22 Sewer/Water 171509-2021 Passed Tim Kersch Complete
Service
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-24 Rough/Topout 171510-2021 Passed Tim Kersch Complete
Checklist Item COMMENTS Passed
BLOG-Building Deficiency Yes
BLDG-31 171511-2021 Passed Tim Kersch Complete
Underground/Conduit -
Wiring
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
12/10/2021 12/10/2021 BLDG-14 172480-2021 Partial Pass Tim Kersch Reinspection Incomplete
Frame/Steel/Bolting!We
lding (Decks)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
12/17/2021 12/17/2021 BLDG-17 Interior 172903-2021 Partial Pass Tim Kersch Reinspection Incomplete
Lath/Drywall
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
01/13/2022 01/13/2022 BLDG-84 Rough 174450-2022 Partial Pass Tim Kersch Reinspection Incomplete
Combo(14,24,34,44)
Checklist Item COMMENTS Passed
BLDG-Building Deficiency Yes
BLDG-14 Yes
Frame-Steel-Bolting-Welding
(Decks)
BLDG-24 Rough-Topout Yes
BLDG-34 Rough Electrical Yes
BLDG-44 Yes
Rough-Ducts-Dampers
Tuesday, May 31, 2022 Page 1 of 3
I:: c·s I:: N '\/IR(_) NM I:: N 'I i-\. L. IN<...:.
C
July 8, 2019
Andrew R. Tarango
Senior Project Manager
SCA Architecture
"-,f'LL1\LlZ11'C 1:-S: LL\D -SlULD -A'>LJL">lU',
\ VVV \V.FCS-EN VIRO~J\lE '.',;T\ I . ..,ER\'ICEC...CCt\1
13280 Evening Cree Drive South, Suite 125
San Diego, California 92128
RE: Asbestos Testing-Commercial Building
1950 Camino Vida Roble, Carlsbad, Callfornla 92008-6505
Drywall/Joint Compound, Floor Glue and Celling Tile
Dear Mr. Tarango;
This report documents the laboratory analytical results of the Asbestos PLM sampling conducted
by AH ERA Certified Building Inspector, Mason Riley, working under the direction of Bond L.
Mccowan, Sr. CAC. The thirteen (13) samples of drywall/joint compound, floor glue and ceiling
tile were collected on July 1, 2019, and submitted to Analytical Services in Rancho Cucamonga,
California, for processing. A total of twenty (20) samples were analyzed, including all layers.
The laboratory analytical results of the samples indicate 1JJ1.Asbestos Containing Materials (ACM)
were detected.
Should you have any questions after reviewing the conclusions and recommendations contained
within this report, please do not hesitate to contact the undersigned at (800) 511-6364. ECS
Environmental, Inc. remains available to assist you in any way possible.
Sincerely,
ECS Environmental, Inc.
Bond L. Mccowan, Sr.
California Certified Asbestos Consultant
Attachments: Table 1
Laboratory Analytical Results
Chain of Custody
Field Sketch
Inspector Certification
4876 SANTA MONICA AVE. SUITE 172 ~ SAN DIEGO, CA 92107
(0) 1-800-511-6364-(F) 480-719-4-465 WWW.ECS-ENVIRONMENTAlSERVICFS.COM
Area Tested Type of Material Sample
Number(s)
Interior Drywall and Joint 001 Compound
Interior Drywall and Joint 002 Compound
Interior Drywall and Joint 003 Compound
Interior Drywall and Joint 004 Compound
Interior Drywall and Joint 005 Compound
Interior Drywall and Joint 006 Compound
Interior Drywall and Joint 007 Compound
Interior Floor Glue 008
Interior Floor Glue 009
Interior Floor Glue 010
TABLE 1
Asbestos Results
1950 Camino Vida Roble
Carlsbad, California 92008-6505
July I, 2019
Sample Quantity Sample Description Locations
Area#! NIA Joint Compound (White)
Drvwall (White)
Area#5 NIA Joint Compound (White)
Drywall (White)
Area#3 NIA Joint Compound (White)
Drywall (White)
Area#2 NIA Joint Compound (White)
Drywall (White)
Area#6 NIA Joint Compound (White)
Drywall (White)
Area#4 NIA Joint Compound (White)
Drywall (White)
Area#2 NIA Joint Compound (White)
Drywall (White)
Area#2 NIA Floor Glue (Yellow)
Area #I NIA Floor Glue (Yellow)
Area#3 NIA Floor Glue (Yellow)
ND = None Detected CH=Chrysotile CR=Crocidolit A=Amosite N/ A=Not Analyzed A/P=Assume Positive
***Contractor shall follow all OSHA regulations with samples less <1%
Condition PLM Percent Results
Good ND 0%
ND 0%
Good ND 0%
ND 0%
Good ND 0%
ND 0%
Good ND 0%
ND 0%
Good ND 0%
ND 0%
Good ND 0%
ND 0%
Good ND 0%
ND 0%
Good ND 0%
Good ND 0%
Good ND 0%
Area Tested Type of Material Sample
Number(s)
Interior Ceiling Tile 011
Interior Ceiling Tile 012
Interior Ceiling Tile 013
TABLE 1
Asbestos Results
1950 Camino Vida Roble
Carlsbad, California 92008-6505
July 1, 2019
Sample Quantity Sample Description Locations
Area#3 NIA Ceiling Tile (White)
Area#l NIA Ceiling Tile (White)
Hallway NIA Ceiling Tile (White)
ND= None Detected CH=Chrysotile CR=Crocidolit A=Amosite N/ A=Not Analyzed A/P=Assume Positive
•••contractor shall follow all OSHA regulations with samples less <1%
Condition PLM Percent Results
Good ND 0%
Good ND 0%
Good ND 0%
Client:
Project:
Client#
001
002
003
004
Page 1 of 3
Analytical Services
Bond McCowan Report#: 0719028
ECS Environmental, Inc. Date of Receipt: 07/05/2019
4876 Santa Monica Avenue Report Date: 07/05/2019
San Diego Ca 92107 Date of Analysis: 07/05/2019
1950 CAMINO VIDA ROBLE, CARLSBAD CA
Sample Material
Location Description Detection Composition
LAYER 1 None Detected Non-Fibrous Material 100%
Joint Compound, White, Non-
homogeneous, Chalky, Non-
Friable
LAYER2 None Detected Cellulose Fiber 10%
Drywall, White, Non-Non-Fibrous Material 90%
homogeneous, Chalky-Fibrous,
Non-Friable
LAYER 1 None Detected Cellulose Fiber 1%
JointOJIT\pound,Whlte,Non-Non-Fibrous Material 99% homogeneous, Chalky, Non-
Friable
LAYER2 None Detected Cellulose Fiber 10%
Drywall, White, Non-Non-Fibrous Material 90% homogeneous, Chalky-Fibrous,
Non-Friable
LAYER 1 None Detected Cellulose Fiber 1%
Joint Compound, White, Non-Non-Fibrous Material 99% homogeneous, Chalky, Non-
Friable
LAYER 2 None Detected Cellulose Fiber 10%
Drywall, White, Non-Non-Fibrous Material 90% homogeneous, Chalky-Fibrous,
Non-Friable
LAYER 1 None Detected Cellulose Fiber 1%
Joint Compound, White, Non-Non-Fibrous Material 99%
homogeneous, Chalky, Non-
Friable
LAYER 2 None Detected Cellulose Fiber 10%
Drywall, White, Non-Non-Fibrous Material 90%
homogeneous, Chalky-Fibrous,
Non-Friable
ANALYTICAL SERVICES
1.0744 HILLBROOK AV~ BATON ROllG~ LOUISIANA 7081.0
Phone: {321) B37-9B37 Fax: {225) 478-9731
Report Number
0719028
NVLAP CODE 200670·0
Client:
Project:
Client#
005
006
007
008
009
Page 2 of 3
Analytical Services
Bond McCowan Report#: 0719028
ECS Environmental, Inc. Date of Receipt: 07/05/2019
4876 Santa Monica Avenue Report Date: 07/05/2019
San Diego Ca 92107 Date of Analysis: 07/05/2019
1950 CAMINO VIDA ROBLE, CARLSBAD CA
Sample Material
Location Description Detection Composition
LAYER 1 None Detected Non-Rbrous Material 100%
Joint Compound, White, Non-
homogenerus, Chalky, Non-
Friable
LAYER 2 None Detected Cellulose Fiber 10%
Drywall, White, Non-Non-Fibrous Material 90% homogeneous, Chalky-Fibrous,
Non-Friable
LAYER 1 None Detected Non-Fibrous Material 100%
Joint Compound, White, Non-
homogeneous, Chalky, Non-
Friable
LAYER 2 None Detected Cellulose Fiber 10%
Drywall, White, Non-Non-Fibrous Material 90%
homogeneous, Chalky-Fibrous,
Non-Friable
LAYER I None Detected Non-Fibrous Material 100%
Joint Compound, Whitt?, Non-
homogeneous, Chalky, Non-
Friable
LAYER 2 None Detected Cellulose Fiber 10%
Drywall, White, Non-Non-Fibrous Material 90% homogeneous, Chalky-Rbrous,
Non-Friable
Floor Glue, Yellow, Non-None Detected Non-Fibrous Material 100%
homogeneous, Resinous, Non-
Friable
Floor Glue, Yellow, Non-None Detected Non-Fibrous Material 100%
homogeneous, Resinous, Non-
Friable
ANALYTICAL SERVICES
10744 HILLBROOK A~ BATON ROUGE, LOUISIANA 70810
Phone: {321) 837-9837 Fax: {225) 478-9731
Report Number
0719028
NVLAP CODE 200670-0
Analytical Services
Client: Bond McCowan Report#:
ECS Environmental, Inc. Date of Receipt:
4876 5anta Monica Avenue Report Date:
San Diego Ca 92107 Date of Analysis:
Project: 1950 CAMINO VIDA ROBLE, CARLSBAD CA
Sample Material
Client# Location Description Detection
010 Floor Glue, Yellow, Non-None Detected
hanogeneous,Resinous,Ncn-
Friable
011 Celling TIie, White, Non-None Detected
homogeneous, Rbrous, Friable
012 Ceiling Tile, White, Non-None Detected
homogeneous, Rbrous, Friable
013 Celling Tile, White, Non-None Detected
homogeneous, Fibrous, Friable
ASBESTOS TYPES:
Chrysotlle, Crocldollt.e, Anthophylllte, Tremollte, Amaslte, Ac:tlnollt.e
The samples listed abow were 8U6pecl Df containing asbastD&. A result of •Non Detect• means a thorough eeard1 using epproFJiatc
techniques was oonduded and no type of asbe&kll wa1 discovered. Sampl• subrnlned to this facility will be diaposed of unless lhe
clent requests the sa,.aes be retumcd. Reports will be archived for a period of no more than 3 years. The analys'9 performed Is in
accordance Nth EPA 800IM4-82-020 and EPA 800/R~93/116. Teat results apply only to the samples submitted. It Is not our
policy to distribute the custamllni information without the 'Mitten consent of Ile cu&lomcr. The test report 6hall net be reproducad
except inful, wilhout the 'Wlillan approval oftha laboratory. This rapcrt may not be usBd bytha above ciemto claim product
certification. approval or endonement: by NIST. National Vduntary Labcretory Accredilation Program or the Federal Government.
Shawn Kearney
Labontary Director / Analyst
Angela Kearney
President
ANAL YT.le.AL SERVICES
0719028
07/05/2019
07/05/2019
07/05/2019
Composition
Non-Abrous Material
Cellulose Fiber
Mineral Wool
Non-Fibrous Material
Cellulose Fiber
Mineral Wool
100%
30%
40%
30%
30%
40%
Non-Abrous Material 30%
Cellulose Aber
Mineral Wool
30%
40%
Non-Fibrous Material 30%
10744 HILLBROOK AVE;. BATON ROUGE, LOUISIANA 70810
Phone: {321} 837-9837 Fax: {225} 478-9731
Report Number
0719028
Page 3 of 3 NVLAP CODE 200670·0
CHAIN OF CUSTODY AnalyUcal Servk:e9.
2856 E Via Terrano
Ontario CA 91764
Phone (321) 837-9837 Fax (225t 478-9731
~[bM@~
company Name: ECS Environmental, Inc. send Results Via:
4876 Santa Monica Avenue #172 Fax
Contact:
Phone I Fax#:
Email:
San Diego, CA 92107
Bond Mccowan J Jim Begin
800-511-6364 / 480-719-4465
info@ecs-env ironmentalserv Ices.corn FED EX: 295736198 ~
_., \nl."L '11
(..' ' ·.
,!.~around Time: Type?' Analysis: a?·· if An~~sis Instructions:
/RUSH ; 24Hour 2Day '.~ --~ · ~1~ AnalynALllayers "--" ~--'· ?o 3 Day 5 Day 'PLM (Point Count [1000 PtaJ) Sto . 1 o/o}
Composite Samples
Vennlcuflte Attfc Insulation {EPAJSDDIR•Cl4100-4)
Disposal Instructions:
Retum to Clf&nt {At Clients E.xpens&)
Dl•pose of at GIC
Speciul ln1tructlom; ______________ _ !'CM -Psyment terms are Net 30 Days
1~ ....... (. ~\'11;," .. ,
Project Name: 1 •• ') ~ -' . \; ~ p t ! · 0.1 ~, 1 PO#~ L ~~\'\ r"",Q _·"i_ ~ ,c 1"t-Project#: -.
GIC Sampi. Cllfflt Sample Lccatlon and Type of Material Date& Tlme Samples PCMlmo:
filumb&r Number -or-Sampled Accepted? TOTAL
SS#, Naill$, and Location (PCM) Yor N ON OFF FLOW VOL
v ,1) ' n,'i v~ H / .Jn, ,,'1 ,J1, l 1 I~
tC)(O,-• "\.,J _,. 1
·cJ:O? 1
~O.....:i
,n01 ---· {) 0 !:~
~107
1:1 tJ ~( 'C \'1;),~; IJ.~
·'D ~·~ ,
1,.' ... ·'\)
' 'I
-C ! i C ~-\ '~"-~ ~\\~ ·-·---·--·-----
~ i" 1 I ' ·I/ •
Cll ' !
1 ...
~~ 7~
Sig i: './ ~-0 -
: --z/Wlt ,. y,r ft-~ -, 1 ... --1,~.-:. .,,,,. : -. ~ Relinquished By: O.tamme: ________ Received By: _____________ oatemme: _____ _
--z
~ It I It ~ 111 I I :,11 ,, U..--.
:: ....
I 1:
INT!c~WESl
DATE: 11/10/2021
JURISDICTION: CARLSBAD
PLAN CHECK#.: CB-CBC2021-0362
PROJECT ADDRESS: 1950 Camino Vida Roble
PROJECT NAME: Alphatec Spine-Com-TI
SET II
□ APPLICANT
□ JURIS.
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at lnterwest
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
SCA Architecture/ Andrew Tarango
~ lnterwest staff did not advise the applicant that the plan check has been completed.
D lnterwest staff did advise the applicant that the plan check has been completed.
Person contacted: (\ O
I
Telephone#: 858-793-4777
Date contacted: (by:\..A.I) Email: andrewt@sca-sd.com
Mail Telephone
0 REMARKS:
By: Steven Miller
lnterwest
Fax In Person
Enclosures:
10/12
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
• HV
INTERWEST
DATE: 10/12/2021
JURISDICTION: CARLSBAD
PLAN CHECK#.: CB-CBC2021-0362
PROJECT ADDRESS: 1950 Camino Vida Roble
PROJECT NAME: Alphatec Spine-Com-TI
SET: I
□ APPLICANT
D JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
C8J The check list transmitted herewith is for your information. The plans are being held at lnterwest
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
C8J The applicant's copy of the check list has been sent to:
SCA Architecture/ Andrew Tarango
D lnterwest staff did not advise the applicant that the plan check has been completed.
~ lnterwest staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted:
Mail Telephone
0 REMARKS:
By: Steven Miller
lnterwest
(by:
Telephone#: 858-793-4777
) Email: andrewt@sca-sd.com
Fax In Person
Enclosures:
10/12
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
•
CARLSBAD CB-CBC2021-0362
10/12/2021
PLAN REVIEW CORRECTION LIST
COMMERCIAL
PLAN CHECK#.: CB-CBC2021-0362 JURISDICTION: CARLSBAD
OCCUPANCY: B,Fl,Sl USE: Office
TYPE OF CONSTRUCTION: VB?? ACTUAL AREA: TI 17,571sq ft
EXISTING 121,541sq ft
ALLOWABLE FLOOR AREA: 25,500 STORIES: 2
SPRINKLERS?: Yes
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION:
DATE INITIAL PLAN REVIEW
COMPLETED: 10/12/2021
FOREWORD (PLEASE READ):
HEIGHT: 35'
OCCUPANT LOAD: 1297
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 09/20/2021
PLAN REVIEWER: Steven Miller
This plan review is limited to the technical requirements contained in the California version of
the International Building Code, Uniform Plumbing Code, Uniform Mechanical Code, National
Electrical Code and state laws regulating energy conservation, noise attenuation and access for
the disabled. This plan review is based on regulations enforced by the Building Department.
You may have other corrections based on laws and ordinances enforced by the Planning
Department, Engineering Department, Fire Department or other departments. Clearance from
those departments may be required prior to the issuance of a building permit.
Code sections cited are based on the 2019 CBC, which adopts the 2018 IBC.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2018 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
CARLSBAD CB-CBC2021-0362
10/12/2021
NOTICE: CITY AND ESGIL'S HOURS OF OPERATION ARE AFFECTED BY
THE CURRENT COVID-19 EPIDEMIC. PLAN REVIEWER MAY NOT BE
AVAILABLE TO ANSWER QUESTIONS BY PHONE, BUT MAY BE
REACHED BY E-MAIL AT stmiller@esgil.com . (858) 225-2775
GENERAL
1. Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to lnterwest and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring TWO corrected set of plans and calculations/reports to lnterwest, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to lnterwest only will not be reviewed by
the City Planning, Engineering and Fire Departments until review by lnterwest is
complete.
2. Plans may be submitted in electronic format, subject to the jurisdiction's
approval. If so, they must have restrictions removed from the security settings.
Electronic plans with restrictions to markups, printing, or stamping will not be
approved.
3. A reminder that due to Covid-19, the city will not permit counter corrections.
Please make sure all the items are satisfied; otherwise, another round of
corrections will be necessary.
PLANS
4. All sheets of the plans and the first sheet of the calculations are required to be
signed by the licensed architect or engineer responsible for the plan preparation.
California Business and Professions Code.
5. Page TS1 The max allowable square feet according to the construction type is
25,500 for type VB sprinklered and the existing square feet is 121,541 square
feet. Please provide justification for the overage of the maximum allowable
square feet. Please Clarify the Construction Type.
CARLSBAD CB-CBC2021-0362
10/12/2021
6. Page A 101 Per Keynote #8 the maximum distance between fire extinguishers is
75' and the plan only show 2 extinguishers on gridline c. Please clarify the fire
extinguisher distance.
7. Page AD100 Please provide notes on the plans to show the suspended ceilings
in Seismic Design Categories D, E & F comply with ASCE 7-16 Section
13.5_6.2.2 as follows:
a_ The width of the perimeter supporting closure angle or channel shall be
not less than 2.0 in. unless qualified perimeter supporting clips are used.
b. Closure angles or channels shall be screwed or otherwise positively
attached to wall studs or other supporting structures. Perimeter supporting clips
shall be qualified in accordance with approved test criteria per Section 13.2.5_
c. Perimeter supporting clips shall be attached to supporting closure angle or
channel with a minimum of two screws per clip and shall be installed around the
entire ceiling perimeter.
d. In each orthogonal horizontal direction, one end of the ceiling grid shall be
attached to the closure angle, channel, or perimeter supporting clip_ The other
end of the ceiling gird in each horizontal direction shall have a minimum 0. 75-in
clearance from the wall and shall rest upon and be free to slide on a closure
angle, channel, or perimeter supporting clip.
e. Ceiling areas over 2500 ft.2 must have seismic separation joints or full
height partitions.
f. Ceilings without rigid bracing must have 2" oversize trim rings for
sprinklers and other ceiling penetrations.
ADDITIONAL
8. There are no comments for the Mechanical, Electrical, and Plumbing.
9. To speed up the review process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, note or detail number,
calculation page, etc.
10. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
Have changes been made to the plans not resulting from this correction
list? Please indicate: □ Yes □ No
11. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Steven Miller at Esgil. Thank you_
END OF DOCUMENT
CARLSBAD CB-CBC2021-0362
10/12/2021
[DO NOT PAY-THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: CARLSBAD
PREPARED BY: Steven Miller
PLAN CHECK#.: CB-CBC2021-0362
DATE: 10/12/2021
BUILDING ADDRESS: 1950 Camino Vida Roble
BUILDING OCCUPANCY: B,Fl,Sl
/BUILDING I AREA Valuation Reg.
(Sq.Ft.) Mijtipier Mod. PORTION
Tl F1 OccUDancv 17571
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code #NIA
B B ii in P rmi F 1997 U C u d g e t ee ... ;
I t>ll :~t:
1997 UBC Plan Check Fee •
Type of Review: Complete Review
D Other
VALUE
D Structural Only
D Repetiti'le Fee
•' Repeats D Hoi.ly
EsGilFee 1-----11 Hr. @ *
Comments:
($)
$4,160.121
Sheet 1 of 1
Hazardous Materials Questionnaire
County of San Diego, Department of Environmental Health and Quality
PO Box 129261, San Diego, CA 92112-9261
(858) 505-6700 (800) 253-9933 www.sdcdehq.org
Business Name
Alphatec Spine
Project Address
1950 CAMINO VIDA ROBLE
Applicant
Mike Dendinger
Business Contact
Mike Dendinger
City
CARLSBAD
State
CA
Applicant E-Mail
MDendlnger@atecspine.com
Record ID#: DEH2020-HUPFP-006761
Plan Check#: DEH2021-HHMBP-010861
Balance Due: $73.00
Telephone# Plan File#
(858) 209-0850
Zip Code
92008-6505
Applicant Telephone#
(858) 209-0850
APN#
212-093-12-00
The following questions represent the facility's activities, NOT the specific project description.
PART I· FIRE DEPARTMENT-HAZARDOUS METERIALS DIVISION: OCCUPANCY CLASSIFICATION: (Not required for projects within the City of San Diego.)
Indicate by selecting the item, whether your business will use, process, or store any of the following hazardous materials. If any of the items are selected, Applicant must
contact the Fire Protection Agency with jurisdiction prior to plan submittal.
Occupancy Rating: B, F1 & S1
D Explosive or Blasting Agents
Facility's Square Footage (including proposed project): 121541
□ Organic Peroxides □ Water Reactives li<J Corrosives
"' "' □
Compressed Gases
Flammable/Combustible Liquids
Flammable Solids
□
□
□
Oxidizers
Pyrophorics
Unstable Reactives
□ Cryogenics □ other Health Hazards
□
□
Highly Toxic or Toxic Materials
Radioactives
□ None of These
PART II· SAN DIEGO COUNTY DEPARTMENT OF ENVIRONMENTAL HEAL TH -HAZARDOUS MATERIALS DIVISION (HMD): If the answer to any of the questions is
yes, applicant must contact the County of San Diego Hazardous Materials Division, in person at 5500 Overland Ave., Suite 110, San Diego, CA 92123, or by phone al (858) 505-6700 prior to issuance of a building permit. FEES ARE REQUIRED.
Project Completion Date: 5/1/2022
YES
1. "' 2. "' 3. "' 4. □
5. □ 6. □ 7. □
8. □
NO
□ □
□
□ "' "' "' "'
Is your business listed on the reverse side of this form? (check all that apply).
Will your business dispose of Hazardous Substances or Medical Waste in any amount?
Will your business store or handle Hazardous Substances in quantities equal to or greater than
55 gallons, 500 pounds, or 200 cubic feet?
Will your business handle carcinogens or reproductive toxins in any quantity?
Will your business use an existing, or install an underground storage tank?
Will your business store or handle Regulated Substances (CalARP)?
Will your business use or install a Hazardous Waste Tank System (Title 22, Article 10)?
Will your business store petroleum in tanks or containers al your facility with a total storage capacity
equal to or greater than 1,320 gallons? (California's Aboveground Petroleum Storage Act).
□ □ □
CalARP Exempt
CalARP Required
CalARP Complete
Review Date:
PART Ill· SAN DIEGO COUNTY AIR POLLUTION CONTROL DISTRICT (APCD): If the answer to Question #1 is 'Yes' and the answer to Question #2 is 'No', the applicant
must contact the APCD prior to the issuance of a building or demolition permit. If any answer to Questions #3, #4, or #5 is 'Yes', the applicant must contact the APCD prior to
the issuance of a building or demolition permit. If the answer to Question #3 or #4 is 'Yes', the applicant may need to submit an asbestos notification form to the APCD at
least 10 working days prior to commencing demolition or renovation {some residential projects may be exempt from the notification requirements). Contact the APCD at
10124 Old Grove Road, San Diego, CA 92131 or telephone (858) 586-2600 for more information.
1.
2.
3.
4.
YES NO
□ "' "' □ □ "' □ "'
Will any existing building materials be disturbed as part of this project? (If the answer is 'Yes', an asbestos survey may be required.)
Has a survey been performed to determine the presence of asbestos containing materials?
Will the project involve handling or disturbance of any asbestos containing materials?
5.
6.
□
□
"'
□
Will the project involve the removal of any load supporting structural member?
Will the subject facility or construction activities include operations or equipment that emit or are capable of emitting an air contaminant? (See the APCD
factsheet at http://www.sdapcd.org/info/facts/permits.pdf
(ANSWER ONLY IF QUESTION 5 IS 'YES') Will the subject facility be located within 1,000 feet of the outer boundary of a school (K through 12)? Search
the California School Directory at http://www.cde.ca.gov/re/sd/ for public and private schools or contact the appropriate school district.
Briefly describe business activities: Briefly describe proposed project:
Office. R&D Addition of office space
I declare under penally of perjury that to the best of my knowledge and belief, the responses made herein are true and correct. !El; Fees Acknowledged: !El
Melissa Hanner 11/19/2021
Name of Owner or Authorized Agent Date
FOR OFFICIAL USE ONLY
FIRE DEPARTMENT OCCUPANCY CLASSIFICATION:
BY: DATE: __________ _
EXEMPT OR NO FURTHER INFORMATION RELEASED FOR BUILDING PERMIT BUT NOT FOR RELEASED FOR OCCUPANCY REQUIRED OCCUPANCY
COUNTY-HMO* APCD COUNTY-HMO APCD COUNTY-HMO APCD
~-t"i Of-S,\A_-;t;i
o:S ~Q
u RE: VIFWEr.-0
M. Martinez
'SIGNATURE
11/19/2021
(JI.ff
/Am
*A stamp 1n this box only exempts businesses from completing or updating a Hazardous Materials Business Plan. Other permIltIng requirements may still apply.
DEHQ HMD HMBP Questionnaire v 2.0 (812021)
Printed-on: 11/19/2021 @ 1 :57 PM
OFFICE USE ONLY -• SAN DIEGO REGIONAL
HAZARDOUS MATERIALS
QUESTIONNAIRE
RECORD ID# _______________ --!
PLAN CHECK# _______________ I
Business Name
Alphatec Spine
Bus ness Contacl Telephone
Mike Dendlnger, VP of Operations 760-431-9286
BP DATE
ro)ec ddress
1950 Camino Vida Roble CI S ale Z p Code APN#
Carlsbad CA 92008 212-093-05,12
Malling Address
5818 El Camino Real Clly S ate ip Co e Plan i e#
Carlsbad CA 92008
ProJec Con acl -ma,
Andrew Tarango, SCA Architect r andre -sci.com
: n ice e y ore mg e em, w e er your us ness WI use, process, or_ sore any o e opp Icant must contact tho Fire Protection Agency wllh Jurisdichon prior to plan submlllal
Occupancy Roting: Faclllty'a Square Footage (including proposed projecl): 121,541 total Project SF (17,571 SF for Tl)
1 Explosive or Blasting Agenls 5 Organic Peroxides 9 Waler Reactives /13)Corrosives
@ Compressed Gases . 6 Oxidizers 10 Cryogenics 14 Olher Heallh Hazards
(!) Flammable/Combustible Liquids 7 Pyrophorics 11 Highly Toxic or Toxic Malerlals 15 None of These
4 Flammable Solids 8 tJnslablo Reactives 12 Radioactlves
PART II: S D EGO COUNTY D PART E T F ENVtRO M NTAL HE T -H RDOUS ATERIALS I ISION MD· If the answer to any of the ques ons 1s yes, app can mus con ac e oun o an 1ego aza ous a e as 1v1s on, an Diego, CA 92123 Cell (858) 505-6700 prior to Iha issuance of a bull Ing permit.
FEES ARE REQUIRED Projecl Completion Dale. Expected Date of Occupancy O CalARP Exempt
YES NO (for new construcllon or remodeling projecls)
1. [I D Is your busin.ess !isled on the reverse side of this form? (check all lhat apply) Date lnlttalS
2 [I D Will your business dispose of Hazardous Subslances or Medical Waste In any amount?
3 D [I WIii your business store or handle Hazardous Substances in quantllles greater than or equal to 55 gallons, 500 D CalARP Required
pounds and/or 200 cubic feet?
4 D [I WIii your business store or hondlo carcinogens/reproductive toxins In any quantily? Dale InmaIs
5. D [I Will your business use an existing or Install an underground storege tank?
6 D [I Will your business store or handle Regulated Substances (CalARP)? D ColARP Complete
7. D [I Will your business use or inslall a Hazardous Waste Tank SyStem (TIiie 22, Article 10)?
B D [I Will your business store petroleum In tanks or containers al your focilily with a total facllily storage capacity equal to Dale Initials
or mater than 1 320 allons? California's Above round Petroleum Stora e Act
?" ~ ~'@!!:~ ~~ ~,!ffk.~~r.~il ~1"1 !APCQl· Any YES' answer requires a stamp from APCD 10124 Old Grove Road, San ,ego, 7 -~ 7--~ j__ B -) o s mp required d Q1 Yes .llild Q3 Yes .llild Q4.Q6 No) The following questions are Intended to identify the majontyOBlr P0Ui1on 1ssueS8 t e panning stage Projects may require edditionfflmeesures not kienUfled t>y these questions. For comprehensive
requirements contact APCD Residences are lyplcally exempt except -lhose wllh more !hen one building' on the pro~erty; single buildings with more lhen four dwelling units, townhomas, condos, mixed-commercial use, deliberate bums, residences formmg part of a larger project. !'Excludes garages & small oulbuildings]
YES NO
1. [I O WIii the project disturb 160 square feel or more of existing building materials?
2. D [I Will any load supporting structural members be removed? Notification may be required 10 working days prior to commencing demolillon
3 [I D (ANSWER ONLY IF QUESTION 1 or 2 IS YES) Hos an asbestos smvey been performed by a Certified Asbestos Consullant or Sile Surveillance
Technician?
4 D ll!J (ANSWER ONLY IF QUESTION 3 IS YES) Based on the survey resulls, will !he project disturb any asbestos containing malortel? Notffication
may be required 10 working days prior to commencing asbestos removal
5 D [I Will the project or associated conslructlon equipment emit air contaminants? See the reverse side of this form or APCD factsheet
(www.sdepcd orgljnfoM11cts/peImils odfl for typical equlpmenl requiring an APCD permit
6 D D (ANSWER ONLY IF QUESTION 5 IS YES) Will the project or associated construction equipment be located wilhln 1,000 feet of a school
boundaru
Briefly describe business activities Briefly describe proposed project.
Blotechnicat research and development (spinal Implants) ·17 ,571 ""-f. office/R&D tenant improvement
~~•re under pen~(tyAof perjury that to the best of my knowledge and belief ~respon~m e true and correct
tJ_ l ,~ Ir '1 ·-1\uA,!"" . ·· -• A<"" ../ l Name ofibwner or Authorized Aoent Slanat " er .i..' uthorized Aaent Date
FIRE DEPARTMENT OCCUPANCY CLASSIFICATION. FOROFFICAL ISE ONLY
BY ., DATE. I I
EXEMPT OR NO FURTHER INFORMATK>N REQUIRED RELEASED FOR BUILDING PERMIT BUT NOT FOR OCCUPANCY RELEASED FOR OCCUPANCY
COUNTY-HMO' APCO COUNTY-HMO APCO COUNTY-HMO APCO
• m In this box e em ts businesses from com letin or u atin a Hazardous Materials Business Plan other ermlttln re ulrements ma still a Asta p p g pd g p g q y
z. £
I ppy
HM-9171 (08/15) Counly of San Diego -DEH •· Hazardous Materials Division
·,----------·----------------------------,,
ALPHATEC SPINE,, INC',
PERMIT No. 2425
In accordance with the provisions of Section 3 of the Pretreatment Ordinance the
Encina Wastewater Authority
hereby authorizes
Alphatec Spine, Inc.
1950 Camino Via Roble
Carlsbad, CA 92008
Located in the City of Carlsbad
to discharge locally regulated wastewater from the above identified facility into the
Encina Wastewater Authority (EWA) sewer system in accordance with the
conditions set forth in this permit and EW A's Pretreatment Ordinance. NO
DISCHARGE OF FEDERALLY REGULATED WASTEWATER IS
AUTHORIZED. Compliance with this permit does not relieve the User of its
obligation to comply with any or all applicable pretreatment regulations, standards
or requirements under local, State, and Federal laws, including any such regulations,
standards, requirements, or laws that may become effective during the term of this
permit. No vested rights shall be given by issuance of this permit. The validity of
this permit is conditioned upon the validity of the User's connection permit with the
city or district in whose jurisdiction the User is located. Nothing in this permit grants
the User a right to discharge at a volume that exceeds the allowable discharge volume
set forth in the User's connection permit with that city or district.
By accepting the terms of this permit, the User hereby gives consent and
acknowledges that EWA personnel have the lawful authority to enter upon the
User's premises at any reasonable time to determine compliance with the conditions
of this permit.
rrhis Class II(per111lt shall become effective on M;iy 14, 202{ and shall expii:.e on MaYJ
~. 2025) -r:: ,-I
Q12.t-e\1J1GC1 0 ~, :;,-G 2. Issued on: f/\1\'f OS I J..02..I
ill<k\Vt1) b'/ , ~:___,-By: Encina Wastewater Authority
6200 Avenida Encinas
Carlsbad, CA 92011-1095
,~C::,r~
Robert Grigg, Source Control Manager
POST PERMIT IN PLAIN VIEW THIS PERMIT IS NONTRANSFERABLE
Sf:RVING TIIE CITY OF VISTA, CITY Oi' CARLS HAil, BUENA SANITATION DISTRICT, VALLECJTOS WATER DISTRICT,
LCUCADIA WASTEWATER DISTRICT AND CITY or ENCINJTAS
( City of
Carlsbad
CAP Building Plan
Template
B-55
INSTRUCTIONS: The following certificate shall be included on the title sheet of all building plans:
CLIMATE ACTION PIAN (CAP) COMPLIANCE
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
The following demonstrates project compliance with the applicable Climate Action Plan ordinances of the Carlsbad Municipal Code and California
Green Building Standards Code (CALGreen), current version:
1. ENERGY EFFICIENCY APPLICABLE:
Complies with CMC l& 30 lDQ
& 18.21.155
Existing Structure, year built: 1997
Prepared Energy Audit?
Energy Score: _____ _
Efficiency Measures included in scope:
2. PHOTOVOLTAIC SYSTEM APPLICABLE:
!YES~NO
~/No
Yes,!!§]
YES,tiQ]
Complies with CMC section 18.30.13C and ?OJA California Frersv
€ode scdio11 l:58.l:fc)l:4 Yes/No
Regyired Provided
Size of PV system (kWdc):
Sizing PV by load calculations
If by Load Calculations:
Total calculated electrical load:
80% of load:
Hardship Requested
Hardship Approved
Yes/No
Yes/No
Yes/No
3. ALTERNATIVE WATER HEATING SYSTEM APPLICABLE: YESAN!l]
Complies with CMC sections 18.30.150
diid l3.~0.170f
Alternative Source:
□ Electric
□ Passive Solar
Hardship Requested
Hardship Approved
4. ELECTRIC VEHICLE {EV) CHARGING APPLICABLE:
Complies with CMC 18.21 .150
seCCIUii l8.21.t40T
Panel Upgrade?
Yes/No
Yes/No
Yes/No
YESANO I
Yes/No
Yes/No
Required provided
Total EV Parking Spaces:
No. of EV Capable Spaces:
No. of EV Ready Spaces:
No. of EV Installed Spaces:
Hardship Requested
Hardship Approved
5. TRAFFIC DEMAND MANAGEMENT APPLICABLE:
Compliant?
TDM Report on file with city?
Yes/No
Yes/No
~NO
!Yiil/ no
~/no
PERMIT REPORT
Revision Permit
Print Date: 05/31/2022
Job Address: 1950 CAMINO VIDA ROBLE, # 100, CARLSBAD, CA 92008-6599
{city of
Carlsbad
Permit No: PREV2022-0038
Status: Closed -Fina led
Permit Type: BLDG-Permit Revision Work Class: Commercial Permit Revis
Parcel#: 2120931200 Track#: Applied: 03/22/2022
Valuation: $0.00 Lot#: Issued: 04/06/2022
Occupancy Group: Project#: Fina led Close Out: 05/31/2022
#of Dwelling Units: Plan#:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check#: Inspector: TKers
Plan Check#: Final Inspection:
Project Title:
Description: ALPHATEC SPINE: REV 2 (SHEET AX-100) Tl OFFICE (15,080 SF) & INDUSTRIAL(2491SF)FROM SHELL
FEE
BUILDING PLAN REVIEW-Revisions
Total Fees: $129.00
Property Owner:
RAF PACIFICA GROUP-REAL ESTATE FUND IV
LLC
111 CST, # 200
ENCINITAS, CA 92024
Total Payments To Date: $129.00
Contractor:
SPW CONSTRUCTION DBA WHITE
CONSTRUCTION
2524 GATEWAY RD
CARLSBAD, CA 92009
(760) 931-1130
Balance Due:
AMOUNT
$129.00
$0.00
1635 Faraday Avenue I Carlsbad, CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
\. t~rrv (>f
Carlsbad
PLAN CHECK REVISION OR
DEFERRED SUBMITTAL
APPLICATION
B-15
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
Original Plan Check Numbert:!etl.()2/,. 03(;.~ Plan Revision Number ?a.~\lt0'2--0o38
ProjectAddress_/?'SP C,,'ll'HI~ O 1//G,4 P..oB_I£. ____ _
General Scope of Revision/Deferred Submittal: M&!!A ,2 .SIH;.e-T ,4 ')( -/()0 __ _
CONTACT INFORMATION:
Na me __.i-t1 I> ,tf,.,,v Tit /2./V} 6-1 0 Phone ~~3-'1777 Fax
Address_LUo t:14MJl')O Vlbd-72.olot-£ __ City .cfi,a.Us-4 Zip 1l..01'_fS' __
Email Address -~l)/2..~ t{J2 .,sea.. -5~, '-cn'1 ____ _
Original plans prepared by an architect or engineer, revisions must be signed & stamped by that person.
1 . Elements revised: ~ Plans D Calculations D Soils D Energy D Other
2.
Describe revisions in detail
12../l,. V ~ Fi,. A --.. ,-~,--. /i.-<LI T~/C-/(;. I boo~.J,
4.
5.
Does this revision, in any way, alter the exterior of the project?
Does this revision add ANY new floor area(s)?
6. Does this revision affect any fire rel21ted issues?
7. Is this a complete set? D Yes ~No
:£,'Signature __
D Yes
11<1 Yes
~Yes
~No
0 No
3.
List page/s) where each
revision is shown
Ax .,-1nn
0 No
1635 Faraclay Avenue, Ccirlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: building@carlsbc1dca.gov
scaA R C H I T E C T u R E
TRANSMITTAL RECE\VE\)
To: Jason Pasuit
UAR 2 2 2022
I'll/-\ Date: March 21, 2022
Company: City of Carlsbad CITY OF Ptc$}e.Ia;fl~-,;•;aiso34.T04 Ull Q\tS:G Ui\/\~v-=--"-'-"--'-------
-'-16""0""5""F""a"'r-"'a"-da""y""A'-'v'-e""n"'u""e ______ B __ ' ~ Project: RAF fu.sion -1950 C.V.R.
Carlsbad, California 92008 Atec Phase 2 T.I.
ATTACHED:
Description No. Copies
2
Date
3/21/22 Atec Phase 2 Tl egress plan (sheet AX-100)
TRANSMITTED VIA:
D FAX (Sheet 1 of __ ) Fax No.
D Mail
181 Messenger
D Overnight Delivery
D Other
REMARKS:
Jason,
ACTION
181 For your approval
181 For your review and comment
181 As requested
D For your use / files
D Reviewed as noted
D No exceptions taken
D Revise / Resubmit
Please find attached the above referenced drawings for your review and approval as discussed
with Tim Obrist. If you have any questions, comments or need additional information, please call me.
DISTRIBUTION:
SCA File
With Encl.
BY: Andrew Tarango
D
D
D
D
W/O Encl.
181
D
D
D
13280 Evening Creek Drive South. Suite 125 I San Diego, CA 92128 I 858.793.4777 I sca-sd.com
PERMIT REPORT
Revision Permit
Print Date: 05/31/2022
( City of
Carlsbad
Permit No: PREV2021-0151
Job Address: 1950 CAMINO VIDA ROBLE, # 100, CARLSBAD, CA 92008-6599 Status: Closed -Finaled
Permit Type: BLDG-Permit Revision Work Class: Commercial Permit Revis
Parcel#: 2120931200 Track#: Applied: 12/20/2021
Valuation: $0.00 Lot#: Issued: 01/18/2022
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Project Title:
Project#: Fina led Close Out: 05/31/2022
Plan#:
Construction Type:
Orig. Plan Check#: CBC2021-0362
Plan Check#:
Inspector: TKers
Final Inspection:
Description: ALPHATEC SPINE: STRUCTURAL PLANS TO SUPPORT HVAC AND MINOR FLOOR PLAN CHANGES
Applicant:
MELISSA HANNER
13280 EVENING CREEK DR
SAN DIEGO, CA 92128
(858) 793-4777
FEE
BUILDING PLAN REVIEW -Revisions
BUILDING PLAN CHECK FEE (manual)
Total Fees: $274.50
Property Owner:
RAF PACIFICA GROUP-REAL ESTATE FUND IV
LLC
111 CST, # 200
ENCINITAS, CA 92024
Total Payments To Date: $274.50
Contractor:
SPW CONSTRUCTION DBA WHITE
CONSTRUCTION
2524 GATEWAY RD
CARLSBAD, CA 92009
(760) 931-1130
Balance Due:
AMOUNT
$64.50
$210.00
$0.00
1635 Faraday Avenue I Carlsbad, CA 92008-7314 I 442-339-2719 I 760-602-8560 f I www.carlsbadca.gov
{city of
Carlsbad
PLAN CHECK REVISION OR
DEFERRED SUBMITTAL
APPLICATION
B-15
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov
Original Plan Check Number CBc2021 -0362 Plan Revision Number f&:\£::,{)a I -{)IS:: I
Project Address 1950 CAMINO VIDA ROBLE, CARLSBAD, CA 92008
General Scope of Revision/Deferred Submittal: Addition of structural plans to support HVAC
units that have been relocated on interior as well as minor floor plan changes
CONTACT INFORMATION:
Name Melissa Hanner Phone 8587944777 Fa ----------
Address 13280 Evening Creek Dr. South #125 City San Diego, CA Zip 92128
Email Address melissah@sca-sd.com
Original plans prepared by an architect or engineer. revisions must be signed & stamped by that person.
1 . Elements revised: Iii Plans Iii Calculations D Soils D Energy D Other
2. 3.
Describe revisions in detail List page(sJ where each
revision is shown
door swing revisions, restroom plan mirrored to avoid footing A-101
soffit revision & two new down lights A-111
new plan showing the "roof" tops & new units on top of interior office structures A-112
interior section to clarify the interior office structures. A-300
updated door schedule A-600
revised finishes AF-101
updated egress resulting from door swing change AX-100
4. Does this revision, in any way, alter the exterior of the project? D Yes Iii No
5. Does this revision add ANY new floor areafs)7 D Yes Iii No
6. Does this revision affect any fire related issues? Iii Yes D No • exiting revised
7. Is this a complete set? D Yes Iii No
Date 12.10.21
1635 Faraday Avenue, Carlsbad, CA 92008 fh: 760-602-2719 Eax: 760-602-8558 fmait building@carlsbadca.gov
www carlsbadca gov
DATE: 01-05-2022
JURISDICTION: CARLSBAD
INTERWEST
□ APPLICANT
□ JURIS.
PLAN CHECK#.: CB-CBC2021-0362 (PREV2021-0151) ___ SETI
PROJECT ADDRESS: 1950 Camino Vida Roble
PROJECT NAME: Alphatec Spine-TI-Revision #1-New Structural Engineer and Owner
Changes
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's codes
when minor deficiencies identified below are resolved and checked by building department staff.
D The check list transmitted herewith is for your information. The plans are being held at lnterwest
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
~ lnterwest staff did not advise the applicant that the plan check has been completed.
D lnterwest staff did advise the applicant that the plan check has been completed.
Person contacted:
Date contacted: (by:
Telephone#:
) Email:
Mail Telephone Fax In Person
0 REMARKS:
By: Erich A. Kuchar, P.E.
lnterwest
Enclosures: Approved Set
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: CARLSBAD
PREPARED BY: Steven Miller
PLAN CHECK#.: CB-CBC2021-0362
DATE: 10/12/2021
BUILDING ADDRESS: 1950 Camino Vida Roble
BUILDING OCCUPANCY: B,Fl,S1
BUILDING AREA Valuation Reg.
PORTION ( Sq. Ft.) Multiplier Mod.
Revision #1 17571
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
1997 UBC Buildin g Permit Fee ...
j 1997 UBC Plan Check Fee ~
Type of Review: r Complete Review
r Other
VALUE
r Structural Only
r Repetitive Fee .. I~ Repeats r., Hourllr'. ~Hrs.@*
EsGil Fee 0
~ ~ ~
* Based on hourly rate
($)
$210.00J
Sheet 1 of 1
PRIME STRUCTURAL ENGINEERS
13272 Jacaranda Blossom Dr.
Valley Center, California 92082
Tel (760) 751-3300
STRUCTURAL
CALCULATIONS
Atec Tenant Improvement
Phase 2
Structural Calculations
Carlsbad, CA
2K21-170
Pages 1 thru 57
PREV2021-0151
> 1--0
1950 CAMINO VIDA ROBLE #100
ALPHATEC SPINE: STRUCTURAL PLANS TO SUPPORT
HVAC AND MINOR FLOOR PLAN CHANGES
2120931200
CBC2021-0362 12/20/2021
PREV2021-0151
,,
0
11
11 II
ii ll
.....
1----·-•·----, I {IV)''),,
Ii-----,! t===~: 1-----;,
1----_--, I 0-: '},-
~
:: ~=~cf , ............... ...,__ __ j ••-~;-,\
II : 11 -. '
11 : ! ~~'"" ' I I
I
I
•-····· ··----~
I
I I
I I
i
I
I
; Iii
: r.=====;;;==.n
.. \ .r .L'-llVlJ:. JUtl:2~21-17V
, ~~ STRUCTURAL DATE: 12/21
ENGINEERS SHT: 1
: . .,~ tZ--c
C,({-&
"
"
([,l';,..,-7 · . . '
. H 64-f 1'-ElJ:;z: .
-~a,{4
; M L-S, .e--:
n
! '2 Ci . ,r' .
I , c:;i,
I· J'•
I I Z,
. . .
~ J~tf,
~ 10~vp
PRIME J0B:2K21-170
STRUCTURAL DATE: 12121
ENGINEERS SHT: 2
~:: t-bx./~ 1/o'~A :
,'I~ cJ_._ i
. '
I
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
CJ-1
SECTION DESIGNATION: 600S162-43 [33] Single
Input Properties:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Punchout Width =
6.000 in
1.625 in
1.625 in
0.500 in
1.500 in
Design Thickness =
Inside Corner Radius =
Yield Point, Fy =
Fy With Cold-Work, Fya =
Punchout Length =
Ceiling Solver Design Data -Simple Span
Joist Span 11.00 ft Deflection Limit U180
Joist Spacing 24.0 in
Dead Load = 6. 0 psf
Live Load= 10.0 psf
Check Flexure
DL Multiplied by 1.00 for Strength Che ks
LL Multiplied by 1.00 for Strength Che ks
PRIME JOB:2K21170
STRUCTURAL DATE: 12121
ENGINEERS sHT: 3
0.0451 in
0.0712 in
33.0 ksi
36.3 ksi
4.000 in
Flexural Bracing: KyLy = 48.0 in
Cb=1.00
Me = 4297 Ft-Lb My = 2123 Ft-Lb .56 My< Me< 2.78 My
Mc= 2035 Ft-Lb Sc/Sf= 1.00
Mmax = 484 Ft-Lb<= Ma= 1205 Ft-Lb (Distortional Buckling Controls)
K-phi for Distortional Buckling = 0 lb*in/in
Check Deflection
Deflection Limit: U180
Maximum Deflection = 0.154 in
Check Shear
Deflection Ratio = L/855
Vmax = 176 lb (Including Flexural Load Multiplier)
Shear capacity not reduced for punchouts near ends of member
Va= 1416 lb>= Vmax
Check Web Crippling
Rmax = 176 lb (Including Flexural Load Multiplier)
Web Crippling capacity not reduced for punchouts near ends of member
End Bearing Length = 1.00 in
Ra = 259 lb >= Rmax, stiffeners not required
'
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
CJ-2
SECTION DESIGNATION: 600S162-43 [33] Single
Input Properties:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Punchout Width =
6.000 in
1.625 in
1.625 in
0.500 in
1.500 in
Design Thickness=
l~side Corner Radius=
Yield Point, Fy =
Fy With Cold-Work, Fya =
Punchout Length =
Ceiling Solver Design Data -Simple Span
Joist Span 13.67 ft Deflection Limit U180
Joist Spacing 24.0 in
Dead Load= 6.0 psf
Live Load = 10.0 psf
Check Flexure
DL Multiplied by 1.00 for Strength Che ks
LL Multiplied by 1.00 for Strength Che ks
PRIME JOB:2K27-170
STRUCTURAL DATE: 12121
ENGINEERS SHT: 4
0.0451 in
0.0712 in
33.0 ksi
36.3 ksi
4.000 in
Flexural Bracing: KyLy = 48.0 in
Cb= 1.00
Me= 4297 Ft-Lb My= 2123 Ft-Lb _56 My< Me< 2.78 My
Mc = 2035 Ft-Lb Sc/Sf = 1.00
Mmax = 747 Ft-Lb<= Ma= 1205 Ft-Lb (Distortional Buckling Controls)
K-phi for Distortional Buckling = 0 lb*in/in
Check Deflection
Deflection Limit: L/180
Maximum Deflection = 0.368 in
Check Shear
Deflection Ratio = U446
Vmax = 219 lb (Including Flexural Load Multiplier)
Shear capacity not reduced for punchouts near ends of member
Va= 1416 lb>= Vmax
Check Web Crippling
Rmax = 219 lb (Including Flexural Load Multiplier)
Web Crippling capacity not reduced for punchouts near ends of member
End Bearing Length = 1.00 in
Ra = 259 lb >= Rmax, stiffeners not required
i
• PT-lk
Hee#' (~r) ~ i~tf-:x ~
f
: l v-
t->l? o; I c>p Sr-V 2,, C--2,) /4 J, '.
tvL-/4fSFX '2 I ~-.z:~,'1
trJ :[/P:0 /f .:
I I ! i : : !
-(Y'l'L 1-~ .
tl~e;-· 08'
. . . ,
"--
PRIME JOB:2K21-170
STRUCTURAL DATE: 12121
ENGINEERS! SHT: 5
-j
Un!'/-1? ' •
f X IG,0\-:
e;,~
. !
IJ1s G : U 11F-v l~CZl
• ~-· -f--LIJ":...... lo!..:{) ":..=c...,.::..:...•--'--
PJ-1
PRIME JOB:2K21170
STRUCTURAL DATE: 12121
ENGINEERS SHT: 6
11/30/21
2K21-150
(8U(slp12v1s0b4148TBEAM ANALYSIS PROGRAM(slp9vl Ob4148T
SPAN LENGTH= 15.50 ft
(6.43) (BU(sOp
(Simple Span)
UNIFORM LOADS (k/ft & ft)
Xl wd wl
0.020 0.000 0.00
POINT LOADS
Pd
(k
Pl
& ft)
0.600
0.000
0.000
0.250
REACTIONS (k)
LOAD
Dead
Live
Total
MAXIMUM FORCES
V max = 0.580
X.
7.75
7.75
LEFT
0.455
0.125
0.580
@
DEFLECTJ:ONS (El: = kinA2)
LOAD Defl (in)
Total 139925/EJ:
Live 33515/EI
X2
15.50
RJ:GHT
0.455
0.125
0.580
ft
X !ft)
7.75
7.75
Dead 106410/EJ: midspan
TOTAL Defl El:
L I 180 135411
L I 240 180548
L. I 360 270822
LIVE Defl EI
L I 240 43245
L I 360 64868
L I 480 86490
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
PJ-1
SECTION DESIGNATION: 800S162-54 [50] Single
Input Properties:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Punchout Width =
8.000 in
1.625 in
1.625 in
0.500 in
1.500 in
Design Thickness =
Inside Corner Radius=
Yield Point, Fy =
Fy With Cold-Work, Fya =
Pu nchout Length =
Ceiling Solver Design Data -Simple Span
Joist Span 15.50 ft Deflection Limit L/180
Joist Spacing 24.0 in
Dead Load = 1 o.o psf
Live Load = 20. 0 psf
Check Flexure
DL Multiplied by 1.00 for Strength Che ks
LL Multiplied by 1.00 fo~ Strength Che ks
PRIME JOB:2K21170
STRUCTURAL DATE: 12121
ENGINEERS SHT: 1
0.0566 in
0.0849 in
50.0 ksi
50.0 ksi
4.000 in
Flexural Bracing: KyLy = 48.0 in
Cb= 1.00
Me= 7491 Ft-Lb My= 5975 Ft-Lb .56 My< Me< 2.78 My
Mc= 5168 Ft-Lb Sc/Sf= 0.90
Mmax = 1802 Ft-Lb <= Ma = 2734 Ft-Lb (Distortional Buckling Controls)
K-phi for Distortional Buckling = 0 lb*in/in
Check Deflection
Deflection Limit: L/180 .
Maximum Deflection = 0.469 in
Check Shear
Deflection Ratio = L/397
Vmax = 465 lb (Including Flexural Load Multiplier)
Shear capacity not reduced for punchouts near ends of member
Va = 2091 lb >= Vmax
Check Web Crippling
Rmax = 465 lb (Including Flexural Load Multiplier)
Web Crippling capacity not reduced for punchouts near ends of member
End Bearing Length = 1.50 in
Ra = 651 lb>= Rmax, stiffeners not required
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
PJ-1A
SECTION DESIGNATION: 800S162-54 [50] (2) Back-to-Back
Input Properties:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Punchout Width =
8.000 in
1.625 in
1.625 in
0.500 in
1.500 in
Design Thickness =
Inside Corner Radius=
Yield Point, Fy =
Fy With Cold-Work, Fya =
Punchout Length=
Header/Beam Solver Design Data -Simple Span Deflection Limit U180 Header/Beam Span 15.50 ft
Dead Load = 20.0 lb/ft
Live Load = 110.0 lb/ft
Check Flexure
Flexural Bracing: KyLy = 48.0 in
Cb= 1.00
DL Multiplied by 1.00 for Strength Che ks
LL Multiplied by 1.00 for Strength Che s
PRIME JOB:2K21-170
STRUCTURAL DATE: 12121
ENGINEERS SHT: s
0.0566 in
0.0849 in
50.0 ksi
50.0 ksi
4.000 in
lye= 0.276 inA4
Me = 23227 Ft-Lb My = 11949 Ft-Lb .56 My< Me< 2.76 My
Mc= 11380 Ft-Lb Sc/Sf= 0.87
Mmax = 3904 Ft-Lb<= Ma= 5469 Ft-Lb (Distortional Buckling Controls)
K-phi for Distortional Buckling = 0 lb*in/in
Check Deflection
Deflection Limit: U180
Maximum Deflection= 0.508 in
Check Shear
Deflection Ratio = L/366
Vmax = 1008 lb (Including Flexural Load Multiplier)
Shear capacity not reduced for punchouts near ends of member
Va= 4183 lb>= Vmax
Check Web Crippling
Rmax = 1008 lb (Including Flexural Load Multiplier)
Web Crippling capacity not reduced for punchouts near ends of member
End Bearing Length= 1.50 in
Ra = 3202 lb >= Rmax, stiffeners not required
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
PJ-1A
SECTION DESIGNATION: 8005162-54 [50] (2) Back-to-Back
Section Dimensions:
Web Height= 8.000 in
Top Flange= 1.625 in
Bottom Flange = 1.625 in
Stiffening Lip = 0.500 in
Inside Corner Radius = 0.0849 in
Punchout Width = 1.500 in
Punchout Length = 4.000 in
Design Thickness = 0.0566 in
Steel Pro(!erties:
Fy = 50.000 ksi
Fu= 65.000 ksi
Fya = 50.000 ksi
Gross Pro(!erties
A(gross) Weight A(net) Sxx lxx
(inA2) (lb/ft) (in•2) (in•3) (in•4)
1.3391 4.5566 1.1693 1.4339 11.4714
Effective Pro(!ertles
lxx(defl) Sxx Ma-xx Ma-x(dlst) Vag
(in•4) (in•3) (Ft-Lb) (Ft-Lb) (lb)
11.2731 2.4576 6131.8 5468.6 4183
K-phi for Distortional Buckling= 0.00 lb*in/ln
Lateral Buckling Pro(!erties for Flexure
Moment of Inertia of Compression Portion (lye)= 0.2757 in•4
Web Cri(!(!ling -Allowable Loads. Pa flbl Total for 12) Members
End Bearing .Length = 1.50 (in)
Rx
(in)
2.9269
Vanet
(lb)
4183
Interior Bearing Length = 3.50 (in) Cond. 1 (E1 F) Cond. 2 (11 F) Cond. 3 (E2F)
3202 4261 1662
P\Jnchout Reduction Factor Cond. 1, Rc(E1 F) = 0.947 + 0.083x/h <= 1.0
Punchout Reduction Factor Cond. 2, Rc(l1 F) = 0.891 + 0.053x/h <= 1.0
I
(in 4)
0.5 14
PRIME JOB:2K21-170
STRUCTURAL DATE: 12/21
ENGINEERS SHT: s
Ry
(in)
0.6417
Cond. 4 (12F)
4148
~'5'7 , f-'11 '> .. r7 ,
~,if;'
'
PRIME JOB:'2K21-170
STRUCTURAL DATE: 12121
ENGJNEllRS SHT: 10
)(l~xlttA
~U'-~ #>/'r?-/.C.,
I
--
d'--f2-:-31 fYF
eiu iJ•
I '
L,l B· 'U't. I F/yx ((, CA '
1 e, uf ().c.
PJ-2A
PRIME J0B:2K21 170
STRUCTURAL DATE: 12121
ENGINEERS SHT: 11
11/30/21
2K21-150
(8U(slpl2vls0b4148TBEAM ANALYSIS PROGRAM(slp9vl Ob4148T (6.43) (8U(s0p
SPAN LENGTH = 6.75 ft
(Simple Span)
UNIFORM LOADS (k/ft & ft)
wd wl Xl X2
0.020 0.000 0.00 6.75
POINT .LOADS (k & ft)
Pd Pl X
0.600 0.000 3.38
0.000 0.250 3.38
REACTIONS (k)
LOAD LEFT RIGHT
Dead 0.368 0.368
Live 0.125 0.125
Total 0.493 0.493
MAXIMUM FORCES
V max = 0.493 k @ 0.00 ft
Vd max = 0 .. 368 k @ 0.00 ft
M max = 1.548 kft @ 3.38 ft
Md max -1.126 kft @ 3.38 ft
DEFLECTIONS (EI = kin"2)
LOAD Defl (in) X (ft)
Total 10345/EI 3.38
Live 2768/EI 3.38
Dead 7577/EI midspan
TOTAL Defl EI
L I 180 22989
L I 240 30652
L I 360 45978
LIVE Defl EI
L I 240 8201
L I 360 12302
L I 480 16403
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
PJ-2
SECTION DESIGNATION: 600S162-54 [50] Single
Input Properties:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Punchout Width =
6.000 in
1.625 in
1.625 in
0.500 in
1.500 in
Design Thickness =
Inside Corner Radius =
Yield Point, Fy =
Fy With Cold-Work, Fya =
Punchout Length =
Ceiling Solver Design Data -Simple Span
Joist Span 6.75 ft Deflection Limit L/180
Joist Spacing 24.0 in
Dead Load = 10.0 psf
Live Load= 37.0 psf
Check Flexure
Flexural Bracing: KyLy = 48.0 in
Cb= 1.00
DL Multiplied by 1.00 for Strength Che ks
LL Multiplied by 1.00 for Strength Chee s
PRIME JOB:2K21-170
STRUCTURAL DATE: 12121
ENGINEERS SHT: 12
0.0566 in
0.0849 in
50.0 ksi
55.3 ksi
4.000 in
Me = 5275 Ft-Lb My = 3973 Ft-Lb .56 My< Me< 2.78 My
Mc= 3491 Ft-Lb Sc/Sf= 0.99
Mmax = 535 Ft-Lb <= Ma = 2077 Ft-Lb
Check Bending and Torsion
Torsional Bracing: KILi = 48.0 in
One Brace Kilt from End Controls
Input Torsional Lever Arm: to Web Center Uniform Torq e = 5.197 in-lb/in
Fb = 6.78 ksi_ Ft= 2.33 ksi R = Fb/(Fb+ t) = 0.856
Flange/Web junction controls, 1.15 increase in R has been applied
Mcritical = 517.00 Ft-Lb <= R • MaFy=2162.16 Ft-Lb
Check Deflection
Deflection Limit: U180
Maximum Deflection= 0.052 in
Check Shear
Vmax = 317 lb (Including Flexural Load Multiplier)
Deflection Ratio = U1557
Shear capacity not reduced for punchouts near ends of member
Va = 2823 lb >= Vmax
Check Web Crippling
Rmax = 317 lb (Including Flexural Load Multiplier)
Web Crippling capacity not reduced for punchouts near ends of member
End Bearing Length = 1.50 in
Ra = 679 lb >= Rmax, stiffeners not required
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
PJ-2A
SECTION DESIGNATION: 600S162-54 [50] (2) Back-to-Back
Input Properties:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Punchout Width =
6.000 in
1.625 in
1.625 in
0.500 in
1.500 in
Design Thickness =
Inside Corner Radius =
Yield Point, Fy =
Fy With Cold-Work, Fya =
Punchout Length =
Header/Beam Solver Design Data -Simple Span
Deflection Limit U180 Header/Beam Span 6. 75 ft
Dead Load = 20.0 lb/ft
Live Load = 251. 0 lb/ft
Check Flexure
Flexural Bracing: KyLy = 48.0 in
Cb= 1.00
DL Multiplied by 1.00 for Strength Che ks
LL Multiplied by 1.00 for Strength Che s
PRIME JOB:2K21 170
STRUCTURAL DATE: 12121
ENGINEERS SHT: 13
0.0566 in
0.0849 in
50.0 ksi
55.3 ksi
4.000 in
lye= 0.276 inA4
Me = 17 414 Ft-Lb My = 7946 Ft-Lb .56 My< Me< 2.78 My
Mc = 7709 Ft-Lb Sc/Sf = 0.98
Mmax = 1543 Ft-Lb<= Ma= 4317 Ft-Lb (Distortional Buckling Controls)
K-phi for Distortional Buckling = 0 lb*infln
Check Deflection
Deflection Limit: U180
Maximum Deflection = 0.075 in
Check Shear -
Vmax = 915 lb (Including Flexural Load Multiplier)
Deflection Ratio = L/1080
Shear capacity not reduced for punchouts near ends of member
Va = 5646 lb >= Vmax
Check Web Crippling
Rmax = 915 lb (Including Flexural Load Multiplier)
Web Crippling capacity not reduced for punchouts near ends of member
End Bearing Length = 1.50 in
Ra= 3208 lb>= Rmax, stiffeners not required
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
PJ-2A
SECTION DESIGNATION: 600S162-54 [50) (2) Back-to-Back
Section Dimensions:
Web Height= 6.000 in
Top Flange= 1.625 in
Bottom Flange = 1.625 in
Stiffening lip = 0.500 in
Inside Corner Radius = 0.0849 in
Punchout Width = 1.500 in
Punchout Length = 4.000 in
Design Thickness = 0.0566 in
Steel Pro11erties:
Fy = 50.000 ksi
Fu= 65.000 ksi
Fya = 55.318 ksi
Gross Pro11erties
A(gross) Weight A(net) Sxx
(in'2) (lb/ft) (in'2) (in'3)
1.1127 3.7862 0.9429 0.9535
Effective Pro11erties
lxx(defl) Sxx Ma-xx Ma-x(dist)
(in'4) (in'3) (Ft-Lb) (Ft-Lb)
5.7208 1.8310 5054.2 4316.7
K-phi for Distortional Buckling = 0.00 lb*in/in
Lateral Buckling Pro11erties for Flexure
lxx
(in'4)
5.7208
Vag
(lb)
5646
Moment of Inertia of Compression Portion (lye)= 0.2756 in'4
Web Cril!l!ling -Allowable Loads, Pa {lb) Total for 121 Members
End Bearing Length = 1.50 (in)
Interior Bearing Length = 3.50 (in)
Rx
(in)
2.2675
Vanet
(lb)
3895
Cond. 1 (E1 F) Cond. 2 (11 F) Cond. 3 (E2F)
3208 4283 1865
Punchout Reduction Factor Cond. 1, Rc(E1 F) = 0.925 + 0:083x/h <= 1.0
· Punchout Reduction Factor Cond. 2, Rc(l1 F) = 0.888 + 0.053x/h <= 1.0
I
(in 4)
0.5 12
PRIME JOB:2K21-170
STRUCTURAL om: 121?1
ENGINEERS SHT: 14
Ry
(in)
0.7039
Cond. 4 (12F)
4654
f
' i
i
d ' ' ..,_ i
....-'
!
'
:c.ix-1:'ir
' I
~
PRIME JOB:2K21-110
• ST~UCTURAL DATE: 12/21
• ENGINEERS sttr: l 5
ri.K tt e,p.
0~4--
. / ✓-
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
CJ-4
SECTION DESIGNATION: 800S162-43 [33] Single
Input Properties:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Punchout Width =
8.000 in
1.625 in
1.625 in
0.500 in
1.500 in
Design Thickness =
Inside Corner Radius =
Yield Point, Fy =
Fy With Cold-Work, Fya =
Punchout Length =
Ceiling Solver Design Data -Simple Span
Joist Span 15.50 ft Deflection Limit U180
Joist Spacing 24.0 in
Dead Load = 6.0 psi
Live Load = 10.0 psi
Check Flexure
Flexural Bracing: KyLy = 48.0 in
Cb= 1.00
DL Multiplied by 1.00 for Strength Che ks
LL Multiplied by 1.00 for Strength Che s
PRIME JOB:2K21-170
STRUCTURAL DATE: 12121
ENGINEERS SHT: 16
0.0451 in
0.0712 in
33.0 ksi
33.0 ksi
4.000 in
Me= 6114 Ft-Lb My= 3185 Ft-Lb .56 My< Me< 2.78 My
Mc = 3027 Ft-Lb Sc/Sf= 0.89
Mmax = 961 Ft-Lb<= Ma= 1527 Ft-Lb (Distortional Buckling Controls)
K-phi for Distortional Buckling= 0 lb*in/in
Check Bending and Torsion
Torsional Bracing: Kilt= 48.0 in
Multiple Braces Centered on Mid-Span Controls
Input Torsional Lever Arm: to Web Center
Fb = 11.31 ksi Ft= 0.58 ksi
Uniform Torq e = 1.601 in-lb/in
R = Fb/(Fb+ t) = 0.952
Mcritical = 961.00 Ft-Lb <= R * MaFy = 1597.16 Ft-Lb
Check Deflection
Deflection Limit: U180
Maximum Deflection= 0.311 in
Check Shear
Vmax = 248 lb (Including Flexural Load Multiplier)
Deflection Ratio = U598
Shear capacity not reduced for punchouts near ends of member
Va= 1051 lb>= Vmax
Check Web Crippling
Rmax = 248 lb (Including Flexural Load Multiplier)
Web Crippling capacity not reduced for punchouts near ends of member
End Bearing Length = 1.50 in
Ra= 281 lb>= Rmax, stiffeners not required
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
CJ-5
SECTION DESIGNATION: 600S162-43 (33] Single
Input Properties:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Punchout Width =
6.000 in
1.625 in
1.625 in
0.500 in
1.500 in
Design Thickness =
Inside Corner Radius =
Yield Point, Fy =
Fy With Cold-Work, Fya =
Punchout Length=
Ceiling Solver Design Data -Simple Span
Joist Span 12.00 ft Deflection Limit L/180
Joist Spacing 24.0 in
Dead Load= 6.0 psf
Live Load = 10.0 psf
. Check Flexure ·
DL Multiplied by 1.00 for Strength Che ks
LL Multiplied by 1.00 for Strength Che s
PRIME JOB:2K21-170
STRUCTURAL DATE: 12121
ENGINEERS SHT: 11
0.0451 in
0.0712 in
33.0 ksi
36.3 ksi
4.000 in
Flexural Bracing: KyLy = 48.0 in
Cb= 1.00
Me= 4297 Ft-Lb My= 2123 Ft-Lb .56 My< Me< 2.78 My
Mc= 2035 Ft-Lb Sc/Sf= 1.00
Mmax = 576 Ft-Lb<= Ma= 1205 Ft-Lb (Distortional Buckling Controls)
K-phi for Distortional Buckling = 0 lb*in/in
Check Bending and Torsion
Torsional Bracing: KILi = 48.0 in
Three Braces Centered on Mid-Span Controls
Input Torsional Lever Arm: to Web Center
Fb = 9.01 ksi Ft= 0.85 ksi
Uniform Tor e = 1.788 in-lb/in
R = Fb/(Fb+ t) = 0.914
Mcritical = 576.00 Ft-Lb <= R * MaFy = 1270.74 Fl-Lb
Check Deflection
Deflection Limit: U180
Maximum Deflection= 0.219 in
Check Shear
Vmax = 192 lb (Including Flexural Load Multiplier)
Deflection Ratio = U659
Shear capacity not reduced for punchouts near ends of member
Va= 1416 lb>= Vmax
Check Web Crippling
Rmax = 192 lb (Including Flexural Load Multiplier)
Web Crippling capacity not reduced for punchouts near ends of member
End Bearing Length= 1.50 in
Ra = 295 lb >= Rmax, stiffeners not requi!"ed
' 1cr841 ;[11:tl ~4 e ~~~~ ,-,4;,.
' l / ;G)~x 111)4
'U>/ffY 's-_r;-1'
'0--' 3 f 1-L-r--" r
.,.JI/ lpf '$
c-z,;t 'M
: ; ':. i(~)
Pr'?FX' i,~r( ~: 9 { /-? ,.
C-~ ~ /; io/_ Yr> ✓(171-#-): ~ : -C I t) ! t/f ~
'? ~<f { vfoi':)! { ',r-1b/ • : : -zfo
'2, o/'.' ;~ '1
jr,,1 ?-",
I .
Gp;, f1srx,:1J;c9z_-~J,7 r~f:;;i
~~-1(?f$f41' /J.{;. 3/z-'"' ijIZ.• ·. •.
. 7'11
I
PRIME Jok>: 2K21-170
S'!RLICTURAL Dale: __ _
ENGINEERS Shi: 1 9
RECTANGULAR/SQUARE HSS -SUBJECT TO FLEXURE AND AXIAL FORCE
(ASD DESIGN PER ANSI/AISC 360-05)
DESCRIPTION: 2K21-170 ATEC CEILING
CB-1
DESIGN PROPERTIES:
Shape= HSS4X4X1/4
E = 29000 ksi
F,= 46.00 ksi
A= 3.37 in'
d=
b=
t.design =
bit=
hit=
Apt=
Art=
4.00 in
4.00 in
0.233 in
14.20
14.20
28.12
35.15
Apw = 60.76
I.,,,= 143.12
MAJOR AXIS:
COMPACT FLANGE
COMPACT WEB
APPLIED LOADS:
Loads applied shall be in ASD
Axial, P, = 0.000 k
kx=
k,=
Lx=
Ly=
(KUr),=
(KUr), =
Stress Increase =
HSS, Qc=
HSS, Ob=
MINOR AXIS:
COMPACT FLANGE
COMPACT WEB
Bending, M, = 2.45 k-ft = 29.40 k-in (+ in 3-1 Direction)
Bending, M, = 0.36 k-ft = 4.27 k-in (+ in 4-2 Direction)
CAPACITY:
INTERACTION:
Pn /Qc = 62.31 k
Mnx /Qb = 1 o. 77 k-ft = 129.19 k-in
Mny /Ob= 10.77 k-11 = 129.19 k-in
1.00 Ix= 7.8 in4
1.00 Zx= 4.69 in'
9.75 ft Sx= 3.9
9.75 ft rx= 1.52
76.97
76.97 I,= 7.8 in4
1.00
1.67
1.67
z,= 4.69 in'
s,= 3.9
ry= 1.52
Add'I Loads
DL LL
P,= 0.00k 0.00k
P,= 0.00 k 0.00 k
P,= 0.00k 0.00 k
P•= 0.00 k 0.00 k
(Interpolate ISC Table 4-3)
(See AISC able 3-12 & 3-13)
(See AISC able 3-12 & 3-13)
st
0.00 in
0.00 in
0.00 in
0.00 in
Mr/Mc= 0.26 < 1 HSS4X4X1/4 ... OK!
PRIME Job: 2K21-l 70
SIBUCTURA!. Dali!>: __ _
ENGINEERS Sht 2 o
RECTANGULAR/SQUARE HSS -SUBJECT TO FLEXURE AND AXIAL FORCE
(ASD DESIGN PER ANSI/AISC 360-05)
DESCRIPTION: 2K21-170 ATEC CEILING
CB-2
DESIGN PROPERTIES:
Shape = HSS6X4X 114
E = 29000 ksi
F,= 46.00 ksi
A= 4.3 in2
d = 6.00 in
b=
I.design=
bit=
hit=
Apr=
A,r =
4.00 in
0.233 in
14.20
22.80
28.12
35.15
A,w= 60,76
A"'= 143.12
MAJOR AXIS:
COMPACT FLANGE
COMPACT WEB
APPLIED LOADS:
Loads applied shall be in ASD
Axial, P, = 0.000 k
kx=
k = y
Lx=
L = y
(KUr), =
(KUr), =
Stress Increase =
HSS, Oc=
HSS, Ob=
MINOR AXIS:
COMPACT FLANGE
COMPACT WEB
Bending, M, = 7.87 k-ft = 94.44 k-in (+ in 3-1 Direction)
Bending, M, = 0.98 k-ft = 11.76 k-in (+ in 4-2 Direction)
CAPACITY:
INTERACTION:
Pn /Qc = 44.50 k
Mnx /Ob = 19.58 k-ft = 234.96 k-in
Mny /Ob= 14.81 k-ft = 177.66 k-in
1.00 Ix= 20.s in4
1.00 Z)(= 8.53 in'
16.17 ft Sx= 6.96
16.17 ft rx= 2.2
88.20
120.52
1.00
1.67
1.67
I,= 11.1 in4
z,= 6.45 in'
s,= 5.56
ry= 1.61
Add'! Loads
DL LL
P,= 0.00k 0.00 k
P,= 0.00 k 0.00 k
P3= 0.00k 0.00 k
P,= 0.00k 0.00 k
(Interpolate ISC Table 4-3)
(See AISC able 3-12 & 3-13)
(See AISC able 3-12 & 3-13)
Mr/Mc= 0.47 < 1 HSS6X4X1/4 ... OKI
!l
0.00in
0.00 in
0.00 in
0.00 in
i?<Jb , • t1.7i' x
:Wt, ~-0f'/r X
I
!t.c,v.;: ~ ! ,/;f'fi . /~.,7y.,_ _J / 5-1
I '
3/,' ttj lk ✓ .( -f 2-, S-,:'i. f
I .
I.
~ PRIME JOB:2K21-170 S~'&, STRUCTURAL DATE: 12121 · ENGINEERS SHT: 21
RECTANGULAR/SQUARE HSS -SUBJECT TO FLEXURE AND AXIAL FORCE
(ASD DESIGN PER ANSI/AISC 360-05)
DESCRIPTION: 2K21-170 ATEC CEILING
CB-3
DESIGN PROPERTIES:
Shape= HSSBX4X1/4
E = 29000 ksi
F,= 46.00 ksi
A= 5.24 in'
d= 8.00 in
b= 4.00 in
I.design= 0.233 in
bit= 14.20
hit= 31.30
Ap1 = 28.12
A"= 35.15
Apw= 60.76
Arw = 143.12
MAJOR AXIS:
COMPACT FLANGE
COMPACT WEB
APPLIED LOADS:
kx= 1.00
k,= 1.00
L)(= 19.75 ft
L = y 19.75 ft
(KUr), = 83.16
(KUr), = 142.77
Stress Increase ;;;:; 1.00
HSS,Oc= 1.67
HSS, Ob= 1.67
MINOR AXIS:
NON-COMPACT FLANGE
COMPACT WEB
Loads applied shall be in ASD Add'I Loads
Axial, P, = 0.000 k
Bending, M, = 17.44 k-ft = 209.28 k-in (+ in 3-1 Direction)
Bending, M, = 1.46 k-ft = 17.52 k-in (+ in 4-2 Direction)
CAPACITY:
P, = Pn /Qc = 38.64 k
M~ = Mnx /Qb = 30.53 k-ft = 366.35 k-in
Moy= Mny /Qb = 17.80 k-ft = 213.59 k-in
INTERACTION:
P,=
P,=
P,=
P,=
(Interpolate
(See AISC
(See AISC
Mr/Mc= 0.65 < 1 HSS8X4X1/4 ... OK!
PRIME Job: 2K21-l 70
STRUCTURAL oaie: __ _
ENGINEERS sh1: 2 2
Ix= 42.5 in4
Z,= 13.3 in3
S= ' 10.6
r = ' 2.85
I,= 14.4 in4
Z,= 8.2 in3
s,= 7.21
r = y 1.66
DL LL ll
O.OOk O.OOk 0.00 in
O.OOk 0.00 k 0.00 in
0.00k 0.00 k 0.00in
O.OOk 0.00k O.OOin
ISC Table 4-3)
able 3-12 & 3-13)
able 3-12 & 3-13)
:,.'-=t-==4=' =-~===!( I I '-o V'
.\ ~ ' '
l{J\.JD'°' : rvOf (J.,J ' L \:) f 5'f Y l ' . ,_. ' lb 1'J.vf >··
lA.lA\,\:_-"-(OfSf x7,t-P-'"--1'-{f'-f' N f
; (;J l)' <Z,:,I p ~~ \ ( CC-cu, fVf;
PRIME JOB:2K21-170
. STRUCTURAL DATE: 1 ?1?1
ENGINEERS SHT: 23
t 1r' ><' l"i1'1-
~e¢.-
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
CJ-6
SECTION DESIGNATION: 600S162-54 [50] (2) Boxed
Input Properties:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Punchout Width =
6.000 in
1.625 in
1.625 in
0.500 in
1.500 in
Header/Beam Solver Design Data -Simple Span
Design Thickness =
Inside Corner Radius =
Yield Point, Fy =
Fy With Cold-Work, Fya =
Punchout Length =
Deflection Limit L/240 Header/Beam Span 14.00 ft
Dead Load= 90.0 lb/ft
Live Load = 40.0 lb/ft
DL Multiplied by 1.00 for Strength Che ks
LL Multiplied by 1.00 for Strength Che s
Check Flexure
Flexural Bracing: KyLy = 48.0 in
Cb= 1.00
lyy (Box) = 1.994 inA4
J (Box) = 4.463 inA4
Lu= 646.0 in
Mmax = 3185 Ft-Lb<= Ma= 5054 Ft-Lb
Check Deflection
Deflection Limit: L/240
Maximum Deflection = 0.666 in
Check Shear
Deflection Ratio = L/252
Vmax = 910 lb (Including Flexural Load Multiplier)
Shear capacity not reduced for punchouts near ends of member
Va = 5646 lb >= Vmax
Check Web Crippling
Rmax = 910 lb (Including Flexural Load Multiplier)
Web Crippling capacity not reduced for punchouts near ends of member
End Bearing Length = 1.50 in
Ra = 1358 lb >= Rmax, stiffeners not required
PRIME J0B:2K21170
STRUCTURAL DATE: 12121
ENGINEERS SHT: 24
0.0566 in
0.0849 in
50.0 ksi
55.3 ksi
4.000 in
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
CJ-6
SECTION DESIGNATION: 600S162-54 [SO] (2) Boxed
Section Dimensions:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Inside Corner Radius=
Punchout Width =
Punchout Length =
Design Thickness =
Steel Properties:
Fy =
Fu=
Fya =
Gross Properties
A(gross) Weight
(inA2) (lb/ft)
1.1127 3.7862
Effective Properties
lxx(defl) Sxx
(inA4) (inA3)
5.7208 1.8310
Torsional Properties
6.000 in
1.625 in
1.625 in
0.500 in
0.0849 in
1.500 in
4.000 in
0.0566 in
50.000 ksi
65.000 ksi
55.318 ksi
A(net)
(inA2)
0.9429
Ma-xx
(Ft-Lb)
5054.2
Sxx
(inA3)
0.9535
Vag
(lb)
5646
St. Venant Torsion Constant (J) = 4.4630 inA4
Lateral Buckling Properties for Flexure
lxx
(inA4)
5.7208
Vanet
(lb)
3895
Rx
(in)
2.2675
Maximum Unbraced Length for Full Moment Capacity, Lu= 646.0 in
Web Crippling -Allowable Loads. Pa llbl Total for (21 Members
End Bearing Length = 1.50 (in)
Interior Bearing Length= 3.50 (in)
Cond. 1 (E1 F) Cond. 2 (11 F) Cond. 3 (E2F)
1358 3426 1037
Punchout Reduction Factor Cond. 1, Rc(E1 F) = 0.925 + 0.083xlh <= 1.0
Punchout Reduction Factor Cond. 2, Rc(l1F) = 0.888 + 0.053x/h <= 1.0
I
(in 4)
1.9 38
PRIME JOB:2K21170
STRUCTURAL DATE: 121?1
ENGINEERS SHT: 2s
Ry
(in)
1.3386
Cond. 4 (12F)
3603
& PRIME JOB:2K21-170 ~ STRUCTURAL DATE: 12121
~-"',a, ENGINEERS SHT: 26
f 9 [<f r"rJ< /'1;,.l7/~)+ t0 ('9FX/ t.r)}X f; ~-Joi/ fi -;.-('//"Of">,;. )< p .. (,7 / y iJ..--✓ I~:;,_ 1/--: . "I ,,,,-..,__ ,,_, . I .
t..,,.,rr. p 8"~1 "')(1A .... 71 .11
i ---I
ltt# c: > 1 er-X l 1/f-X I ~/l,-
(!!' 14 •r i ""r ~ ,);, .
I
!_
I_
I --!
i
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 11/29/2021
2K21-170ATEC STUDS@PODS
SECTION DESIGNATION: 362S162-43 [33] Single
Input Properties:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Punchout Width =
3.625 in
1.625 in
1.625 in
0.500 in
1.500 in
Wall Solver Design Data -Simple Span
Wall Height 12.00 ft
Lateral Pressure 5.00 psi
Stud Spacing 16.0 in
Check Flexure
Load Multiplier for Flexural Strength = 1.00
Design Thickness =
Inside Corner Radius =
Yield Point, Fy =
Fy With Cold-Work, Fya =
Punchout Length =
Deflection Limit U240
Axial Load 1057 lb
Flexural Bracing: KyLy = 48.0 in Cb= 1.00
Me = 2361 Ft-Lb My = 1077 Ft-Lb
Mc= 1045 Ft-Lb Sc/Sf= 0.95
Mmax = 120 Ft-Lb <= Ma = 595 Ft-Lb
Check Bending and Torsion
Torsional Bracing: Kilt= 48.0 in
A PRIME JOB:2K21-170 H'£ STRUCTURAL DATE: 12121 Jf!la, ENGINEERS SHT: 21
0.0451 in
0.0712 in
33.0 ksi
33.0 ksi
4.000 in
.56 My< Me< 2.78 My
Three Braces Centered on Mid-Span Controls
Input Torsional Lever Arm: to Web Center
Fb = 3.87 ksi Ft= 0.31 ksi
Uniform Tor e = 0.434 in-lb/in
R = Fb/(Fb+ t) = 0.925
Mcriti.cal = 120.00 Ft-Lb <= R * MaFy = 566.10 Ft-Lb
Check Deflection
Deflection Limit: U240
Load Multiplier for Deflection = 1.00
Maximum Deflection = 0.149 in Deflection Ratio = U969
Check Shear
Vmax = 40 lb (Including Flexural Load Multiplier)
Shear capacity not reduced for punchouts near ends of member
Va = 1739 lb >= Vmax
Check Web Crippling
Rmax = 40 lb (Including Flexural Load Multiplier)
Web Crippling capacity not reduced for punchouts near ends of member
End Bearing Length = 1.50 in
Ra= 315 lb>= Rmax, stiffeners not required
Check Axial Interactions
P = 1057 lb (Including Axial Load Multiplier)
Axial Loads Multiplied by 1.00 for Interaction Checks
Max unbraced length, KyLy and Kilt = 48.0 in Max Ur = 100
Allowable Pure Axial Load, Pa= 2397 lb : Axial Load Ratio, P/Pa = 0.441
K-phi for Distortional Buckling = 0 lb*in/in
Check Equation C5.2.1-1 Check Equa ion C5.2.1-2
Cmx= 1.00
Per= 9966 lb Alpha= 0. 796
Equation C5.2.1-1 = 0.694
Maximum Interaction = 0.694 <=1.0
A PRIME JOB:2K21170 ~ STRUCTURAL DATE: 12121
,g'~~ ENGINEERS SHT: 2a
Pao= 542 lb
Equati n C5.2.1-2 = 0.435
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 11/29/2021
2K21-170 ATEC STUDS@ PODS
SECTION DESIGNATION: 362S162-43 [33) Single
& PRIME JOB:2K21170 ~ STRUCTURAL DATE: 12121
~~~ ENGINEERS SHT: 29
3 ___ _
I Section Dimensions:
Web Height= 3.625 in
Top Flange= 1.625 in
Bottom Flange = 1.625 in
Stiffening Lip = 0.500 in
Inside Corner Radius = 0.0712 in
Punchout Width = 1.500 in
Punchout Length = 4.000 in
Design Thickness = 0.0451 in
Steel Pror;1erties:
Fy = 33.000 ksi
Fu= 45.000 ksi
Fya = 33.000 ksi
Gross Proeerties
A(gross) Weight A(net) Sxx
(in'2) (lb/ft) (in'2) (in'3)
0.3398 1.1562 0.2721 0.3916
Effective Proeerties
lxx(defl) Sxx Ma-xx Ma-x(dist)
(in'4) (in'3) (Ft-Lb) (Ft-Lb)
0.7098 0.3716 612.0 634.9 .
K-phi for Distortional Buckling = 0.00 lb*in/in
Torsional Proeerties
Jx1000 Cw
(in'4) (in'6)
0.2304 0.3759
Xo
(in)
-1.297
Warping Torsional Properties
a Sxx(lip) Wn(1)
(in'3) (in'3) (in'2)
65,3 0.5092 2.5560
m
(in)
0.782
Wn(2)
(in'2)
1.4284
Web Criepling -Allowable Loads. Pa (lbl
End Bearing Length = 1.50 (in)
Interior Bearing Length = 3.50 (in)
lxx
(in'4)
0.7098
Vag
(lb)
1739
Ro
(in)
2.036
Wn(3)
(in'2) ·
-1.3996
4
Rx
(in)
1.4453
Vanet
(lb)
676
Beta
0.594
Wn(4)
(in'2)
1.3996
Cond.1 (E1F) Cond. 2 (I1F) Cond. 3 (E2F)
315 767 256
Punchout Reduction Factor Cond. 1, Rc(E1 F) = 0.866 + 0.083x/h <= 1.0
Punchout Reduction Factor Cond. 2, Rc(l1 F) = 0.879 + 0.053x/h <= 1.0
I
I ~
(in 4)
0.1 68
Sy
(in 3)
0.1 54
w, (5)
(in 2)
-1.-' 284
Ry
(in)
0.6109
Ma-y
(Ft-Lb)
173.6
Wn(6)
(in'2)
-2.5560
Cond. 4 (I2F)
836
11
',
I
! .,
!
' ' h \
r·
I
i !
I [,
T
I '
i . , ...... ,,
l
I ·'' ~ ,:;~<
I l
i I r
I
i I I
I i
i I I ., i:
i
I !
j
.,
I
i
! I
'
I j, , .. ,
I !
i I
·\
I
i ,_
i !
i ,.
I I -l
i I
I
I
I -;.
!
I
I ].
'
I I i I
i !
\ ..
,-
i
! i
'\
,~, : , PRlM~ JPB:21<21 -170
'. ~ : STRUCTURAL DATE: ·,12/21 ~ ENGINEERS SHT: : 30 ! . . ' . . . .
! ''
i 'i
I .. t
i . '
,,
i
I i
i i !
'' ., I i I ·t
I ,,
I
!,
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 11/29/2021
2K21-170 ATEC HEADER
SECTION DESIGNATION: 600S162-54 [50) (2) Boxed
Section Dimensions:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Up =
Inside Corner Radius =
Design Thickness =
Steel Properties:
Fy =
Fu =
Fya =
6.000 in ·
1.625 in
1.625 in
.0.500 in
0.0849 in
0.0566 in
50.000 ksi ·
65.000 ksi
55.318 ksi
ALLOWABLE UNIFORM LOADS
INPUt PARAMETERS
Deflection Limit: U360
Listed load multiplied by 1.00 for deflection check .
Listed Allowable Loads Not Modified for Duration of Load for Strength Checks
Member Configuration: (2) BOXED MEMBERS
End Bearing Length for Web Crippling= 1.5 in
Flexural Bracing: NONE
TOTAL ALLOWABLE UNIFORM LOADS (lb/ft)
SPAN LENGTH (ft)
6.00 8.00 10.00
Without Web
Stiffeners 452.7 339.5 250.0
With Web
Stiffeners 1123.2 488.3 250.0
II
II
&._ P RIME JOB:2K21 -170 a STRUCTURAL DATE: 12/21
.la'£~ ENGINEERS SHT: 31
ATC I-la'zards by Location https://hazards.atcouncil.or seismic?lat=33. l 228816&lng=-I 17.2 ...
L\TC Hazards by Location
Search Information
Address:
Coordinates:
Elevation:
Timestamp:
Hazard Type:
Reference
Document:
Risk Category:
Site Class:
1950 Camino Vida Roble, Carlsbad, CA 92008, USA_
33.1228816, -117.2832261
254 ft
2021-12-06T23:24:54.333Z
Seismic
ASCE7-16
II
D
Basic Parameters
·-.... ·-........ -··. ·-·· ................. ,.,-,., ....
Name Value Description
Ss 0.997 MCER ground motion (period=0.2s)
S1 0.363 MCER ground motion (period=1.0s)
SMS 1.098 Site-modified spectral acceleration value
SM1 • null Site-modified spectral acceleration value
Sos 0.732 Numeric seismic design value at 0 .2s SA
S01 • null Numeric seismic design value at 1.0s SA
* See Section 11 -4.8
..-Additional" Information
Name
soc
Fa
Fv
CRs
CR1
PGA
FPGA
PGAM
TL
SsRT
Value
• null
1.101
• null
0.898
0.908
0.436
1.164
0.508
8
0.997
Description ·
Seismic design categol)'
Site amplification factor at 0.2s
Site amplification factor at 1.0s
Coefficient of risk (0.2s)
Coefficient of risk (1.0s)
MCEG peak ground acceleration
Site amplification factot at PGA
Site modified peak ground acceleration
Long-period transition period (s)
Probabilistic risk-targeted ground motion (0.2s)
. .......... ,_ I"'"
SsUH 1.11 Factored uniform-hazard spectral acceleration (2% probability of
1 of2
PRIME JOB:2K21 -170
STRUCTURAL DATE: 12/21
NGINEERS SHT: 32
12/6/2021, 3:25 PM
j .. ~ . . . ! .. .
I
. 'i •-••··
' ' I I I . • • : I .! t , . . ! ~ ~~ ~ e : P;"1J:
;
I l·• -~·. I
I i i ,·
' I
·-· ! I
1 ·
!
!
: ...... ; ..
I
I
I
I
I. I
' i-·
I I ·1
i '
I .I
i
! i .
I !
\ /k._ i=JR]ME J~B:2~21-170
: J'r£ : STRUCTURAL DATE: n12, ~ ENGINEE~S Sll_T: 1 33 ' •. . f
'.> {, )?if i j I I
' !
i i ~ i P:~r~,.~;d ~/:
! ~--~-l;-2--
' '
Ctt~f: {;,~ r,'--~b:=--:
I ½,,~f 'i ~ 24.'' !?6-Vc :"'. ~
: : w 1.,-' ' 'P--
:~ v J... , (Pi ( 2-. I -I
r "' /tcJit
A_ P ;RIME JOB:2K21 -170
,R~ . STRUCTURAL DATE: 12/21 ~ ENGINEERS SHT: , 34
. !
J I·
I i
·,·
www.hilti.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
Specifier's comments:
1 lnputdata
Anchor type and diameter:
Effective embedment depth:
Material:
Evaluation Service Report:
Issued I Valid:
Proof:
Stand-off installation:
Anchor plate:
Profile:
Base material:
Installation:
Reinforcement:
Seismic loads (cat. C, D, E, or F)
Geometry [in.] & Loading [lb, in.lb]
~ PRIME JOB:2K21-170 A.. STRUCTURAL DATE: 12/21
.411S'£~ ENGINEERS SHT:---="-----f
Kwlk Bolt TZ -CS 1/2 (2)
h.1.ac1 = 2.000 in., hn"!" = 2.375 in.
Carbon Steel
ESR-1917
5/1/2013 j 5/1/2015
Design method ACI 318-11 / Mech.
eb = 0.000 in. (no stand-off); t = 0.125 in.
Page:
Project:
Sub-Project I Pos.
Date:
1:1,-;;.1
Profis Anchor 2.5.5
1
21<21-170 ATEC
TYPICAL BOT TRACK
12/7/2021
I, x ly x t = 24.000 in. x 4.000 in. x 0.125 in.; (Recommended plate ickness: not calculated)
no profile
cracked ooncrete, 2500, fc' = 2500 psi; h = 4.000 in.
hammer drilled hole, Installation condition: Dry
tension: ccndition B, shear: ccndition B; no supplemental splitting inforcement present
edge reinforcement: none or < No. 4 bar
Tension load: yes (D.3.3.4.3 (d))
Shear load: yes (D.3.3.5.3 (a))
z:
'
'
'
Input data and results must be checked for agreement with the existing conditions and for plaualbllltyl
PROF!$ Anchor ( c) 2003-2009 Hilt! AG, FL-9494 Schaan Hllti is a registered Trademark of Hilti AG, Schaan
www.hiltl.us
Company:
Specifier:
/k._ PRI ME JOB:2K21 -170 £. STRUCTURAL DATE: 12121
AlliiiT-"~ ENGINEERS SHT: 36
Page:
Project:
1:11-;;.1
Profis Anchor 2.5.5
2
Address: Sub-Project I Pos. II o.:
21<21-170 ATEC
WPICAL BOT TRACK
121712021 Phone I Fax:
E-Mail:
2 Load case/Resulting anchor forces
Load case: Design loads
Anchor reactions [lb]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x
1 o 160 160
max. concrete compressive strain: -[%,]
max. concrete compressive stress: -[psi]
resulting tension force in (x/y)=(0.000/0.000): 0 [lb]
resulting compression force in (x/y)=(0.000/0.000): O [lb]
3 Tension load
Date:
Shear force y
0
Load N •• [lb] Capacity ~. [lb]
Steel s trength*
Pullout Strength*
Concrete Breakout Strength**
NIA
NIA
N/A
• anchor having the highest loading ••anchor group (anchors in tension)
Input data and results must be checked for agreement with Ille existing conditlons and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of HilU AG, Scllaan
NIA
NIA
N/A
I 1
Utilizatlc n 1!N = N.J.i.N..
NIA
NIA
N/A
X
Status
NIA
NIA
N/A
I
~ PRIME JOB:2K21-170 a STRUCTURAL DATE: 12/21
..s'~~ ENGINEERS SHT: 37
www.hilti.us
Company: Page:
Specifier: Project:
Address:
Phone I Fax:
Sub-Project I Pas.
Date:
E-Mail:
4 Shear load
Load Vu, [lb] Capacity V n [lb]
tee trengt • 16
Steel failure (with lever arm)* NIA
Pryout Strength.. 160
Concrete edge failure in direction x+•• 160
• anchor having the highest loading '*anchor group (relevant anchors)
4.1 Steel Strength
V,a,eq = ESR value
cj, V., •• ,:.Vua
Variables
n
1
Calculations
v .. ,ffi[lb]
54 5
Results
v .. ;.,.[lb] 5495
4.2 Pryout Strength
refer to ICC-ES ESR-1917
ACI 318-11 Table 0.4.1.1
0.10
~111 .. 1 0.650
futa [psi]
106000
~V .. [lb]
3572
Vu, [lb]
160
572
NIA
1683
5973
Yep = kcp [ (t:) lj/ed,N lj/c,N lj/cp,N Nb]
q,Vcp:.V00
ACI 318-11 Eq. (D-40)
ACI 318-11 Table D.4.1.1
~ seeACI 318-11, PartD.5.2.1, Fig. RD.5.2.1(b)
~co= 9h!,
lj/ec,N = (1 + ~ eN) S 1.0 ~
lj/ed,N = 0.7 + 0.3 (~~:,) S 1.0
= MAX(C.,mln 1.5h•t) S 1 0 _IJ!cp.N Cec , C.c .
Nb = kc ,_.; ..ff. h!i5
Variables
kcp h0,lin.]
1 2.000
\VcN C80 [in.]
1.oBo 5.500
Calculations
AN, [in.2] ~0 [in.2]
36.0 36.00
Results
Vcp [lb] concrete
4 0.7
801,N [in.]
0.000
17
ec1,N
1.000
.0
ACI 318-11 Eq. (D-5)
ACI 318-11 Eq. (D-8)
ACI 318-11 Eq. (D-10)
ACI 318-11 Eq. (D-12)
ACI 318-11 Eq. (D-6)
802,N [in.]
0.000
1.000
ec2 N
1.0
nonductila
1. 0
Input data and results must be checked for agreement v.ith the exisUng condrtions and for ptau~bllltyl
PROFIS Anchor ( c) 200$-2009 Hilti AG. FL-9494 Schaen HIii! is a registered Trademark or HilU AG. Schaan
C.,mn [in.]
24.000
2500
ed.N
1.000
V (lb]
1683
Utlllzatl
I:11S~•
Profis Anchor 2.5.5
3
21<21-170 ATEC
TYPICAL BOT TRACK
12m2021
n = v.J 110 Status
5
NIA NIA
10 OK
3 OK
N
1.000 2404
Vua [lb]
. A PRIME JOB:2K21-170 Ws..i STRUCTURAL DATE: 12/21 ~ ENGINEERS SHT: 38 I = I I s • I
www.hilti.us
Company:
Specifier:
Address:
Phone I Fax:
E-Mail:
4.3 Concrete edge failure in direction x+
(Ave ) Vcb = Avr;, \Jled,V IVc.v 'Vh,V \Jlparallel.V vb
$Vcb~Vua
Ave seeACI 318-11, PartD.6.2.1, Fig. RD.6.2.1(b)
Avr;, = 4.5 ~1
IVec.v = (1 + \e,.) S 1.0
3c01
\Jled,V = 0.7 + 0.3( 1.~.J S 1.0
IVh,V = ~~ 1.0
vb = ( 1 (<t)02 .Jcia) "-v7c c!l
Variables
C.1 [in.]
16.000
1. [in.]
2.000
Resul~
Vcb [lb]
85 2
5 Warnings
Ca2 [in.]
24,000
'-• 1.000
concrete
.700
ecV [in.]
0.000
da [In.]
Q.500
ACI 318-11 Eq. (D-30)
ACI 318-11 Table 0.4.1.1
ACI 318-11 Eq. (D-32)
ACI 318-1 1 Eq. (D-36)
ACI 318-11 Eq. (D-38)
ACI 318-11 Eq. (D-39)
ACI 318-11 Eq. (D-33)
ljlc,V
1.000
f.(psi]
2500
Page:
Project:
Sub-Project I Pos.
Date:
h, [in.]
4.000
Y,peralel,V
1.000
h,V
2.44 0 0
V00 [lb]
Profis Anchor 2.5.5
4
21<21-170 ATEC
TYPICAL BOT TRACK
12m2021
• Load re-distributions on the anchors due to elastic deformations of the anchor plate are not considered. e anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the loading I Input data and results must e checked for agreement with the
existing conditions and for plausibility!
• Condition A applies when supplementary reinforcement is used. The <I> factor is increased for non-steel esign Strengths except Pullout
Strength and Pryout strength. Condition B applies when supplementary reinforcement is not used and fo Pullout Strength and Pryout
Strength. -Refer to your local standard. ·
• Refer to the manufacturer's product literature for cleaning and installation instructions.
• Checking the transfer of loads into the base material and the shear resistance are required in accordan
standard!
• An. anchor design approach for structures assigned to Seismic Design Category C, D, E or F is given in
D.3.3.4.3 (a) that requires the governing design strength of an anchor or group of anchors be limited by
case, the connection design (tension) shall satisfy the provisions of Part 0.3.3.4.3 (b), Part D.3.3.4.3 (c),
connection design (shear) shall satisfy the provisions of Part D.3.3.5.3 (a), Part D.3.3.5.3 (b), or Part D.3
with ACI 318 or the relevant
Cl 318-11 Appendix D, Part
ctile steel failure. If this is NOT the
r Part D.3.3.4.3 (d). The
.5.3 (C).
, Part D.3.3.4.3 (b) / part 0.3.3.5.3 (a) requires that the attachment the anchors are connecting to the stru ure be designed to undergo ductile
yielding·at a load level corresponding to anchor forces no greater than the controlling design strength. P D.3.3.4.3 (c) / part 0.3.3.5.3 (b)
waives the ductility requirements and requires that the anchors shall be designed for the maximum tensi n / shear that can be transmitted to
the anchors by a non-yielding attachment Part D.3.3.4.3 (d) / part D.3.3.5.3 (c) waives the ductility requi ments and requires the design
strength of the anchors to equal or exceed the maximum tension I shear obtained from design load com nations that include E, with E
increased by no.
• J:liltl post-installed anchors shall be installed in accordance with the Hilti Manufacturer's Printed lnstallatl Instructions (MPII). Reference
ACI 318-11, PartD.9.1
Fastening meets the design criteria!
Input data and n,sutts must be checked for agreement with the existing conditions and for plauslbilityl
PROFIS Anchor ( e) 200$-2009 Hlltl AG, FL-9494 Schaan Hlltl Is_ a registered Trademark of Hllti AG, Schaan
· ..
(
I n
! L
I
\
i '
. i
I I
I
I .. I .
I .
' '. ' ~L) ~AW§i,5 : @
' ! '. ' ' : . l
j I : ; l i i r • ' i ; ' : i I i I : I i .
I i :r~v i J,
I
... ! I '
I (f,;,.., ~ lf
• I
1
'
i ' .
' I ... !
' -,.
I
_!_
J't ; 7 If-.
~t: 9!~1.
. !
I ·1
I ·,·
! . i
. I -.. I I I ·+ •• 1 .
!
! .,
.! i '
' . .
•• '• I
' i -! .
j.
I
! ·
' l n
/~1\-1½,~ ~I
i ;
I
·\ •~ ; I I : ' :
~1/4~! f"_rz,;~':?◄-'--'--.~'----.::....::=-=-··. ---,-w-_fil~1~pe_7S_: "'~N____..._ · ( f'-VA-X ; <;f~ ,J 4:
I I '
i •• I
'· i !
j.
I
I ·;
I .. ·i
i · I
I
'I
I • l I I
! /• , CJ7 --t
: I / /\ I •
l ! ! !
~~</)-~
I I '{?~ ,
i
I
t J r">~ x:
~t\f '(
I.
I
< .. ;
i ; I
I //~.:,
l
lA ' .
I I 1. :
I .l.
I I ; : I I i :
1 & , P:R,IME JdB:2K21-1~0 ·N~ 1 srmucTURAL oATE: 1212,l 'Ba,, EN;GIN~E~S SHT: i 40
I '
l l
1~~/) l ,( :t1rd.) ;
I I I
l I I I !
;
i. i
I
i.
RECTANGULAR/SQUARE HSS -SUBJECT TO FLEXURE AND AXIAL FORCE
(LRFD DESIGN PER ANSI/AISC 360-05)
DESCRIPTION: 2K21-170 ATEC SCREEN WALL
FLAGPOLE COL
DESIGN PROPERTIES:
Shape= HSS6X6X1/4
E = 29000 ksi
F, = 46.00 ksi
A= 5.24 in'
d= 6.00 in
b= 6.00 in
\.design= 0.233 in
bit= 22.80
hit= 22.80
A"= 28.12
Art= 35.15
11,,w = 60.76
Arw = 143.12
MAJOR AXIS:
COMPACT FLANGE
COMPACT WEB
APPLIED LOADS:
Loads applied shall be in LRFD
Axial, P,= 0.190k
kx;;::
ky=
L,=
L= y
· (KUr),=
(KUr),=
Stress Increase =
HSS, <l>c =
HSS, <l>b =
MINOR AXIS:
COMPACT FLANGE
COMPACT WEB
Bending, M, = 5.08 k-ft = 60.96 k-in (+ in 3-1 Direction)
Bending, M, = 0.00 k-ft = 0.00 k-in (+ in 4-2 Direction)
CAPACITY:
INTERACTION:
<l>c·Pn = 55.42 k
<l>b·Mnx = 38.64 k-ft = 463.68 k-in
<l>b·Mny = 38.64 k-ft = 463.68 k-in
2.00
2.00
14.25 ft
14.25 ft
146.15
146.15
1.00
0.9
0.9
Add'I Loads:
P, =
P,=
P3=
P•=
(Interpolate
(SeeAISC
(SeeAISC
Pr/2Pc + [Mr/Mc] = 0.13 < 1 HSS6X6X1/4 ... OK!
PRIME Job: 2K21-l 70
STRUCTURAL □ate: __ _
ENGINEERS Shi: _41 __
I= ' 28.6 in4
z = ' 11.2 in'
Sx= 9.54
r = ' 2.34
I= y 28.6 in4
Z= y 11.2 in'
s,= 9.54
r = y 2.34
DL LL
0.00 k 0.00k
0.00 k 0.00 k
0.00k 0.00k
0.00 k 0.00k
ISC Table 4-3)
ble 3-12 & 3-13)
ble 3-12 & 3-13)
~
0.00 in
0.00 in
0.00 in
0.00 in
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
SCREEN WALL
SECTION DESIGNATION: 600S162-33 [33] Single
Input Properties:
Web Height=
Top Flange=
Bottom Flange =
Stiffening Lip =
Punchout Width=
6.000 in
1.625 in
1.625 in
o.500 in
1.500 in
Wall Solver Design Data -Simple Span
Wall Height 14.25 ft
Lateral Pressure 5.00 psf
Stud Spacing 16.0 in
Check Flexure
Design Thickness =
Inside Corner Radius =
Yield Point, Fy =
Fy With Cold-Work, Fya =
Punchout Length =
Deflection Limit U240
Axial Load 190 lb
Load Multiplier for Flexural Strength = 1.00
Flexural Bracing: Full
Mmax = 169 Ft-Lb <= Ma= 951 Ft-Lb & Ma(distortional) = 789 Ft-Lb
K-phi for Distortional Buckling= 0 lb*in/in
Check Deflection
Deflection Limit: U240
Load Multiplier for Deflection = 1.00
Maximum Deflection= 0.117 in
Check Shear
Vmax = 48 lb (Including Flexural Load Multiplier)
Deflection Ratio = L/1462
Shear capacity not reduced for punchouts near ends of member
Va = 638 lb >= Vmax
Check Web Crippling
Rmax = 48 lb (Including Flexural Load Multiplier)
Web Crippling capacity not reduced for punchouts near ends of member
End Bearing Length = 1.50 in
Ra = 175 lb >= Rmax, stiffeners not required
Check Axial Interactions
P = 190 lb (Including Axial Load Multiplier)
A PRIME JOB:2K21-170
J'if'.i;;, STRUCTURAL DATE: 12121 82, ENGINEERS SHT: 42
0.0346 in
0.0765 in
33.0 ksi
33.0 ksi
4.000 in
Axial Loads Multiplied by 1.00 for Interaction Checks
Max unbraced length, KyLy and KILi = 171.0 in Max Ur= 294
Allowable Pure Axial Load, Pa= 427 lb : Axial Load Ratio, P/Pa = 0.445
K-phi for Distortional Buckling = 0 lb*in/in
Check Equation C5.2.1-1
Cmx = 1.00
Per= 17851 lb Alpha= 0.980
Equation CS.2.1-1 = 0._664
Maximum Interaction = 0.664 <=1.0
Check Equa ion C5.2.1-2
Pao= 3244 lb
Equa on CS.2.1-2 = 0.273
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
TOP TRACK
SECTION DESIGNATION: 600T150-54 [50] Single
Section Dimensions:
Web Height=
Top Flange=
Bottom Flange =
Inside Corner Radius=
Design Thickness=
Steel properties:
Fy =
Fu=
Fya =
6.198 in
1.500 in
1.500 in
0.0849 in
0.0566 in
50.000 ksi
65.000 ksi
50.000 ksi
ALLOWABLE UNIFORM LOADS
INPUT PARAMETERS
Deflection Limit: L/240
Listed load multiplied by 1.00 for deflection check
Listed Allowable Loads Not Modified for Duration of Load for Strength Checks
Member Configuration: SINGLE MEMBER
End Bearing Length for Web Crippling = 1.5 in
Flexural Bracing: 24.0 in
Include Torsion? Yes
Torsional Lever Arm to: Web Center
TOTAL ALLOWABLE UNIFORM LOADS jib/ft)
SPAN LENGTH (ft)
6.00 8.00 10.00
Without Web s Stiffeners 171.6 128.7
With Web
Stiffeners 307.5 180.0 117.4
A PRIME JOB:2K21170 ~ STRUCTURAL DATE: 1 2121
-,;.,~ ENGINEERS SHT: 43
ClarkWestern Building Systems
CW Tech Support: (888) 437-3244
clarkwestern.com
2007 North American Specification ASD
DATE: 12/8/2021
TOP TRACK
SECTION DESIGNATION: 600T150-54 [50) Single 3~ ____ :
Section Dimensions:
Web Height=
Top Flange=
Bottom Flange =
Inside Corner Radius=
Design Thickness =
Steel Properties:
Fy =
Fu=
Fya =
Gross Propertjes
A(gross) Weight
(lb/ft)
6.198 in
1.500 in
1.500 in
0.0849 in
0.0566 in
50.000 ksi
65.000 ksi
50.000 ksi
A(net)
(in'2)
Sxx
(in'3) (in'2)
0.5087 1.7310 0.5087 0.8425
Effective Properties
lxx(defl) Sxx Ma-xx Vag
(in'4) (in'3) (Ft-Lb) (lb)
2.4077 0.6091 1519.8 2728
Torsional Properties
Jx1000 Cw Xo m
(in'4) (in'6) (in) (in)
0.5432 0.6325 -0.675 0.434
Warping Torsional Properties
a Sxx(lip) Wn(1) Wn(2)
(in'3) (in'3) (in'2) (in'2)
55.1 0.6091 3.1865 3.1865
Wei! CriDpllng • Allowable Loads, Pa (lb}
End Bearing Length = 1.50 (in)
Interior Bearing Length= 3.50 (in)
Cond. 1 (E1 F) Cond. 2 (11 F)
515 1128
4
lxx Rx 11
(in'4) (in) (in
2.6110 2.2655 0.0
Syy Ma-y
(in'3) (Ft-Lb)
0.0367 91.5
Ro Beta
(in)
2.401 0.921
Wn(3) Wn(4) WI
(in'2) (in'2) (in
-1.3327 1.3327 -3.1
Cond. 3 (E2F)
361
A PRIME JOB:2K21-170 N~ STRUCTURAL DATE: 12121 ~ ENGINEERS SHT: 44
. Ry
4) (in)
07 0.4222
(5) Wn(6)
2) (in'2)
365 -3.1865
Cond. 4 (I2F)
815
A PRIME JOB:2K21-170 ~ STRUCTURAL DATE: 12121
~~~ ENGINEERS SHT: 4s
DEPTH REQUIREMENTS FOR EMBEDDED POLI S
Per Sec. 1807.3, 2019 C.B.C
DESCRIPTION: FTG. @ CANTILEVER COL.
ALLOWABLE LATERAL EARTH PRESSURES
Allowable Passive Pressure =
Maximum Allowable Passive Pressure =
Does lateral restraint at ground surface exist?
Load Duration Factor=
LOADING DATA
Applied point load, P = 356.0 lbs. ✓
125 p f / ft of deph✓
0 p f
(For No Lim , enter "0")
1 (' =1, N=0)
1.33
Point Load
Load height above base, h= 14.3 ft./ Moment@ ase = 5,073 ft-#
Uniform lateral load = 0.0 plf
Distance from base to bottom = 0.0 ft. Uniform Lo,
Distance from base to top = 0.0 ft. Moment@
Total Mome
POLE TYPE (1=ROUND, 2=RECTANGULAR): 1
POLE WIDTH NOMINAL TO FORCE : 18 in. ✓
MINIMUM REQUIRED EMBEDMENT
Non-Restrained (EQ. 18-1) :
Depth = (A/2)*{1 +SQRT(1+4.36*h/A)} =
where A=2.34*P/(S1*b)
#N/A I
Restrained (EQ 18-2) :
Depth = SQRT(4.25* P*h/S3*b) =
LATERAL PRESSURES
Allowable@ 1/3 of Embedment =
Actual @ 1 /3 of Embedment =
Allowable @ base of Embedment =
Actual @ 1 /3 of Embedment =
Surface Restraint Force=
243 psf
#N/A psf
728 psf
749 psf
2,060 #
4.44 1
j
ase = 0 ft-#
11 = 5,073 ft-#
2K21-170 ATEC
HP at PODS
FLOOR MOUNTED MECHANICAL UNITS ASCE 7-16 (13.3.1)
tJNIT
Wp
l Fp "· y -,
7
,,,. Y/2 i , I,
CtJIUI ,I ..
,I
t I'd t I'd
L X L .., .,
Wp=
Y=
y=
X=
Sos =
ap =
Rp =
Ip=
z/h =
SEISMIC DEMANDS ON NONSTRUCTURAL COMPONENTS -ASCE 7-16 13.3.1
Fp= 0.211 WP
Fp,me,c = 1.171 WP
Fp.min = 0.220 WP
Fp = 0.220 WP
FP= 197.64 lbs.
Fp,v = 0.146 Wp
UPLIFT CHECK (ASD)
P0 = 0.7·[Fp·(Y/2+y)/X + Fp_,/2) = 0.132 WP = 118.78 lbs.
Based on 50% of Wp Pd = 0.500 WP = 450.00 lbs.
LOADING CHECK (ASD)
Pe = 0.132 WP
Based on 67% of Wp Pd = 0.667 WP ----0.799 WP/ 1.33 = 0.599 WP
(A
(A
(A
>
D
4-#(() <;'~
PRIME Job:2K21-l 70
SlRUCTURAL Date: __ _
ENGINEERS Sht: 4 6
00.00 lbs.
30.25 in.
0.00 in.
29.75 in.
0.732
1.00
2 .50
1.00
0.40
CE 7-1613.3-1)
CE 7-1613.3-2)
CE 7-16 13.3-3)
e NO UPLIFT ✓
+ LL GOVERNS ../
v/< (.,fl,{5t,,,...> == , # & k .
2K21-170 Atec Tenant Improvement
HP-11 and HP-12
ROOF MOUNTED MECHANICAL UNITS ASCE 7-16 (13.3.1)
mm
Wp
l Fp y
7
.... Yn
i I/ l,O
C1JllB I/ T
,
i Pe 1P•
t Pd t Pd
~(
X ~ 'I
PRIME Job: 2K21-170
SJRIJC'lil.lRAL Dale: __ _
ENGINEERS Sht 4 7
Wp, =. 6 2.00 lbs.
Y= 0.10 in.
y= 4.00 in.
X= 1.00 in.
Sos = .732
ap = .00
R -p-.50
Ip= .00
z/h = .00
Roof Curb Wp2= 5.00 lbs.
SEISMIC DEMANDS ON NONSTRUCTURAL COMPONENTS -ASCE 7-16 13.3.1
Fp= 0.351 Wp
Fp,max = 1.171 Wp
Fp,min = 0.220 Wp
Fp = 0.351 Wp
Fp1 = 239.63 lbs.
Fp2 = 8.78 lbs.
Fp,v = 0.146 WP
Fp,v = 103.50 lbs.
UPLIFT CHECK (ASD)
P. = 0.7·[Fp,-(Y/2+y)/X] +0.7*[ Fpv/2] +0.7*Fp2*y/2/X=
0.5Pd.mln =
LOADING CHECK (AS0)
Pe=
Pd.max (2/3*Wp)=
Sum P/1 .33=
176.58 lbs.
467.17 lbs.
482.81 lbs. 2/3 * Wp= 467.167 lbs
176.58 lbs.
353.50 lbs.
(AS E 7-16 13.3-1)
(AS E 7-16 13.3-2)
(AS E 7-16 13.3-3)
> P NO UPLIFT
DL + SEISMI GOVERNS
2K21-170 Atec Tenant Improvement
CU-2
ROOF MOUNTED MECHANICAL UNITS ASCE 7-16 (13.3.1)
mm
Wp
l Fp y
7
l'p,v yn,
i I✓
CURB I✓>' '
i Pe t Pe
t Pd t Pd
~, X ~ '1
PRIME Job: 2K21-170
STRIJC1URA1 Date: __ _
ENGINEERS Sht 4 B
Wp1 = 6 2.00 lbs.
Y= 1.63 in.
y = .00 in.
X = in.
Sos = .732
ap= .00
. Rp= .50
Ip = .00
z/h = .Od
Roof Curb W p2= .00 lbs.
SEISMIC DEMANDS ON NONSTRUCTURAL COMPONENTS -ASCE 7-1613.3.1
Fp = 0.351 Wp
Fp,max = 1.171 WP
Fp,mln = 0.220 W p
Fp= 0.351 Wp
Fp1 = 239.63 lbs.
Fp2= 0.00 lbs.
0.2·Sos·(Wp1+wp2) = · Fp,v = 0.146 W P
Fp.v = 99.84 lbs.
UPLIFT CHECK (ASD)
P0 = 0.7·[Fp1·(Y/2+y)/X] +0.7*[ Fpv/2) +0.7*Fp2*y/2/X=
LOADING CHECK (ASD)
Pe=
Pd.max (2/3*Wp)=
Sum P/1 .33=
· 0.5P d.min =
259.51 lbs.
454.67 lbs.
535.63 lbs. 2/3 * W p= 454.667 lbs
259.51 lbs.
341.00 lbs.
E 7-16 13.3-1)
E 7-16 13.3-2)
E 7-16 13.3-3)
> P NO UPLIFT
DL + SEISMI GOVERNS
PRIME J0B:2K21-l 70
STRUCTURAL o,\re __
ENGINEERS sJIT:--1.L
WIND LOAD CALCULATION: COMPONENTS AND CLADDING (ASCE 7-10 CHAPTER 30)
PROJECT DESCRIPTION: 21<21-170 Atec Phase 2 Tl
WIND DESIGN CRITERIA:
BASIC WIND SPEED, V35 (ASCE 7-10, FIG. 26.5-1A)
DIRECTIONALITY FACTOR, Kd (ASCE 7-10, T.26.6-1)
IMPORTANCE FACTOR, I
EXPOSURE, (ASCE 7-10, 26.7.3)
VELOCITY PRESSURE EXPOSURE COEFF., KZ (ASCE 7-10 T. 3C
TOPOGRAPHIC FACTOR, Kzr (ASCE 7-10 §26.8)
(KZT = 1.0 WILL BE USED, STRUCTURE IS NOT NEAR A RIDGE OR ESCARPMENTI
MEAN ROOF HEIGHT, h
ROOF ANGLE, 8
LEAST HORIZ. BUILDING DIM.
a=
OCCUPANCY CATEGORY
Velocity Pressure, qh = 0.00256·Kz·Kzt"f<.i-V2·I (Eq. 30.3-1)
qh = 19.70 psf
lnt.PressureCoeff,GCp1 = ±0.18 (T.26.11-1)
th"" i ~ (c__t;r) X It-<;; =
fv ~ iv (t,t;~)" As ~
96 MPH
0.85
1.00
C
0.98
1.00
30 FT.
0.00 °
224.5 FT.
12 FT.
II
Wind Zo s (Fig. 30.4-1)
n
) 61-t~~-·· ·.,
I ! ; I ; I ,
: ~h>'lCQ~c--: q4t,:x ~}~f-i1 ,,
. ~~ -q~t ,)( -l{. . ' ..
I /2
. I
~ (L{NtT). C
i ~ '2:6~:#-i
I
, )11'-X v.l v;ry-~
use~ : tf,'i. Dr-st ii i
-C)1..(rf'U,;
~ " q</DttXO,e,. ,_. _ct,(-" :-<.f(;{~
I ' ' t./,)~..5 : a
r)t::ff-D0/v~t_;,~ : L/iz> ~ : : : ~ ?-2:S-~ .)~~: . . . · . /2 5~-t;.J S •
'fri/: >It'¥ . ~s~>
l ,: I ' I I . : ,
\ ' . . ' ' .
. ~ I ;, : C 4J: : /~t, If X /. b =
~::--:/-~ < ;.J ~/~
ufe: ·· ~1.(4 Utt .r~ . .s :
'2:-f e,v eifil.n o rJ . I . e :&4-f ~Bn-... ~-
New 4x
A_ PRIME JOB:2K21-170 "ii;;:, STRUCTURAL DATE: 12/21 ~ ENGINEERS SHT: 51
12/09/21
2K21-170
(8U(slpl2vls0b4148TBEAM ANALYSIS PROGRAM(slp9vl 0b4148T (6 . 43) (SU (s0p
SPAN LENGTH• 8 .00 ft
(Simple Span)
UNIFORM LOADS (k/ft & ft)
wd wl. Xl X2
0 .022 0 .040 0.00 8 .00
POINT LOADS (k & ft)
Pd Pl. X
1.109 0 .000 4 .00
REACTIONS (k)
LOAD LEFT RIGHT
Dead 0.642 0.642
Live 0.160 0.160
Total. 0 .803 0 .803
MAXIMUM FORCES
V max = 0 .803 k @ 0 .00 ft
Vd max = 0.642 k @ 0.00 ft
M max = 2.714 kft @ 4 .00 ft
Md max = 2 .394 kft @ 4 .00 ft
DEFLECTIONS (EI = kin"2)
LOAD Defl. (in) X (ft)
Total. 26155/EI 4.00
Live 3686/EI 4.00
Dead 22469/EI midspan
Pos. Moment Lu= 1 .00 ft
Brace Spacing = 1 .00 ft
Gov. Defl.ection Total.= L/240
Required EI= 65388 kinA2
4 X 8 #2
Actual. : 3 .5" x 7.25"
Dougl.as Fir-Larch (N)
STRESSES (psi)
Shear @ 'd'
*V = 0.63 k @
*Fv = 86 fv
Fb' = 1563 fb
Live LDF = 1.25
0.60 ft
= 37
= 1062
44 %
68 %
* Governed by Dead LDF = 0.90
DEFLECTIONS (in)
Total.= 0 .14 =
Live = 0 .02 =
Dead = o.·12
(E = 1700 ksi)
L / 694 35 %
L /4921 7 %
f\'
n
. I
)-J\ND : ~'. ~-7
' • I
tto~\'l!;:.
v11%1~1
d~Pr ;· Q.7~ '._2oS-#= ;,_ .:bt7~
1>~~ ~• (r~'-~i-~-+-ili~
'
A PRIME JOB:2K~1-170 1 A ; STRUCTiURAL DATE: 1:2121 .
~A\~· ENGINEERS SHT: 1 52 . I ; I 1 I j . j
i I ~~:~-ir
·:-z-u,---4
14~'3,.: )(QJ6=.'.-= ;-J2,#,
I ;
i~fd-, =-:C/tr(:,t-)(.ok ~c;~ . ~ ( b¾~
~c-ic.7 ~,;~~s -3 s/0~
: j
1l-, ,· !(_;tt:{J'/;J 5 , :
-rirfLM7~~
i •
• I
~oi• ' . U((_, v
! -···
I" .l
.i
' ··••·-•.. -·. t ! I •
••·1• ..... ,
i ' -
I -·--+-. ·-~--· --l
i I
I -, n ' ,-..
I j
I i --1 ..... -·i· ...... , •..•.•. l
I
!
. ' -·
I I "i '
' ·-, ---· i
I : ..
. ---· l-·· .. ; i '
i --~
! I
!----
·,·
,·
I .!
) ..
i
I
I i'
I
-,-
i
i
• I
' I \ I .
-~ ' P ·Rl'ME JOB:2K21-170
~: STRUCTURAL DA'.fE: a 2121
£:II~~ ENGINEERS SHT: : s3 ' ! : .
.l
2x@ pl.atform
A._ P RIME J0B:2K21-170 a STRUCTURAL DATE: 12,21
E7~~ ENGINEERS SHT: 54
12/09/21
2K21-l.70
(8U(slpl2v1s0b4148TBEAM ANALYSIS PROGRAM(slp9vl Ob4148T ( 6 . 4 3) ( BU ( s Op
SPAN LENGTH = 8 .00 ft
(Simpl.e Span)
UNIFORM LOADS (k/ft & ft)
wd wl. Xl X2
0 .015 0 .027 0 .00 .8 .00
POINT LOADS (k & ft)
Pd Pl. X
0.000 1 .213 4.00
REACTIONS (k)
LOAD
Dead
Live
Total.
MAXIMUM FORCES
LEFT
0 .060
0 .715
0.775
V max = 0.775 k @
M max = 2.762 kft@
DEFLECTI:ONS
LOAD
Total.
Li.ve
Dead
{EI: = ki.n"2)
Defl. (in)
26229/EI
24846/EI
1382/EI
Pos. Moment Lu= 1 .00 ft
Brace Spacing = 1.00 ft
RIGHT
0.060
0.715
0.775
0 .00 ft
4 .00 ft
X (ft)
4 .00
4 .00
midspan
Gov. Defl.ecti.on Live= L/240
Required EI= 62116 kin"2
2 X 8 SS
Actual : 1.5" x 7 .25"
Dougl.as Fir-Larch {N)
STRESSES (psi)
Shear@ 'd'
V = 0 .75 k@
Fv = 127 fv
Fb' = 2733 fb
0. 60 ft
= 103
= 2522
Live LDF = 1.33
Repetitive Use Member
82 %
92 %
DEFLECTIONS (in) {E = 1800 ksi)
Total= 0.31 =
Live = 0.29 =
Dead = 0.02
L / 314 57 %
L / 331 72 %
I ~~~' -tfXLfil~(
... , ...
i
(
' .. ! ---; . -"i
j . I
i !
n
i i I . /zt'tt=,~t i r .i-,.
'17'.'.'. ~ /t 1 l t'J ' ' . I',_<! /2 ,r~--:!
1&-. 4-i~~(ll.i~~ (?. i . i . ·;
.;IN~~9-~ _p.,~!---i
-1~~-<?.. 18(,~~ . ·-1-..f-. ! .
. ;H~ ~i-E~./ .. ;.lc..f .
. ;1..P~MI~; J.~
; -~LS t---I \.. .. :,/' J.
· : ___ ; . · i __ , ''--r ?. r
' . -t-.
L
'
\ '
i
vJ
i l . I
2o
i .. I.
1 A_ P;RI(ME JOB:2K21 -170 "&.. ST~UCTURAL DATE': i2121;
~£,a; ENGINEERS S~T: ; 55 .
!. '
l .
! i -1
I i i
' ' ' ·1-·;' 1C:P-. !
• I
I
♦
Existing 36LH
.A PRIME JOB:2K21-170 £._ STRUCTURAL DATE:· 12121
EE~~ ENGINEERS SHT: 56
l.2/09/21.
2K21-170
(8U(slpl2vls0b4148TBEAM ANALYSIS PRQGRAM(slp9vl 0b4148T (6.43) (8U (s0p
SPAN LENGTH = 58.00 ft
(Simple Span)
UNIFORM LOADS (k/ft & ft)
wd w1 Xl -X2
0.088 0 .1.l.8 0 .00 58.00
REACTIONS (k)
LOAD LEFT RIGHT
Dead 2 .552 2.552
Live 3 .422 3.422
Total 5 •. 974 5 .974
MAXIMUM FORCES
V max = 5.97 k @ 0.00 ft
M max = 86.62 kft@ 29 .00 ft
DEFLECTIONS (EI= kinA2)
LOAD Def]. (in)
Total. 52451958/EI
Live 30045296/EI
Dead 22406659/EI
TOTAL Defl. EI
L I 180 · 13565162
L I 240 18086882
L I 360 27130324
LIVE Defl. EI
L I 240 10360447
L / 360 15540670
L / 480 20720894
X (ft)
29.00
29 .00
midspan
Existing 36LH w/ new load
A PRIME JOB:2K21 -170 a.. STRUCTURAL DATE: 12121
1/a/i:>~ .ENGINEERS SHT: s1
_12/09/21
2K21-170
(8U(slpl2vls0b4148TBEAM ANALYSIS PROGRAM(slp9vl 0b4148T (6. 43) (SU (s0p
SPAN LENGTH = 58.00 ft
(Simpl.e Span)
UNIFORM LOADS (k/ft & ft)
wd wl. Xl X2
0.088 0 .118 0.00 58.00
POINT LOADS (k & ft)
Pd Pl X
0.227 0.000 4.00
REACTIONS (k)
LOAD LEFT RIGHT
Dead 2.763 2.568
Live 3 .422 3 .422
Total 6 .185 5.990
MAXIMUM FORCES
V max = 6.19 k @ 0.00 ft
M max : 87.08 kft@ 28.92 ft
DEFLECTIONS (EI= kin~2)
LOAD Defl (in)
Total 52779792/EI
Live 30045286/EI
Dead 22734457/EI
TOTAL Defl EI
L I 180 -13649946
L I 240 181-99928
L I 360 27299892
LIVE Defl EI
L I 240 10360443
L I 360 15540665
L I 480 20720886-
X (ft)
28.98
29.00
midspan