City of Carlsbad
Sprinkler Permit
Permit No: AS050144
1935 CAMINO VIDA
Status: ISSUED
ROBLE
SPRINK Applied 6/22/2005
2120921800 Approved: 7/12/2005
0
Issued: 7/12/2005
Inspector:
SPEC SUITES Tl FIRE SPRINKLER PLAN CHECK & INSPECTIONS
Owner:
A & D FIRE PROTECTION 1935 CAMINO VIDA ASSOCIATES L L C
C/O DOUG MCCORMICK
10759 WOODSIDE AVE
SANTEE, CA 92071
619-448-1962
Fees($)
115
Add'I Fees ($)
0
165 S UNION BLVD #510
LAKEWOOD CO
Total($) Balance($)
115 0
1/1
FIRE PROTECTION INC.
1935 CAMINO VIDA ROBLE T.L
CARLSBAD,CA
Install Fire Sprinklers
FIRE PROTECTION SUBMITTALS
MANUFACTURE'S DATA SHEETS
ITV F CARLSBAD
FIRE DEPARTMENT
APPROVED
** Mate1ials of equal design, utility, and performance may be su sti~~sta, · · ell ins · ti(m tt 11equlMlfys i the
construction schedule and shall be de m4~s t1'tOlatf m, ~-conditions in
correspondence and conformance with
applicable regulations. The stamping
of th~A' ns s II not be held to permit
or e.opr . th .elation of any law.
• . ~w~-Date __ . . ~-. __ , ___ __,
>-
CENTRAL H 2-01
Model H Recessed
5.6 K-factor
Standard Response
Standard Coverage
Recessed Pendent Fusible Solder Type Sprinkler
Tyco Fire Products ---www.centralsprinkler.com
451 North Cannon Avenue, Lansdale, Pennsylvania 19446 ---USA
Customer Service/Sales: Tel: (215) 362-0700 / Fax: (215) 362-5385
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
.-. General ~ Description
The Central Model H, 5.6 K-factor
Recessed Pendent Sprinklers are
automatic sprinklers of the fusible solder
type. They are standard response -
standard orifice spray sprinklers
intended for use in fire sprinkler
systems designed in accordance with
the standard installation rules recog-
nized by the applicable Listing or
Approval agency (e.g., UL Listing is
based on NFPA 13 requirements).
The Central Model H Recessed
Pendent Sprinklers incorporate a center
strut mechanism with a special two-
piece recessed escutcheon assembly
permitting 1 /211 of field-adjustment.
Unlike most other recessed sprinklers,
the upper escutcheon support piece is
factory installed on the base of the
sprinkler frame, assuring a Listed
installation. The ceiling escutcheon
plate is easily installed after the
sprinkler is in place either by the
standard "push-on" escutcheon or the
special "thread-on" escutcheon. This
feature allows removal of ceiling panels
for easy access to ceiling equipment
without taking the system out of service
to remove the sprinkler.
Operation: A fusible alloy is sealed into
a bronze actuating rod (center strut) by
a stainless steel ball. When the alloy
melts at its rated temperature, the ball is
forced upward into the center strut,
releasing the two ejectors and operating
the sprinkler.
WARNING
The Model H Recessed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authorities
having jurisdiction. Failure to do so may
impair the integrity of these devices.
The owner is responsible for maintain-
ing their fire protection "System and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Arechnical
Uoata
Sprinkler Identification Number
SIN C3711
Approvals
UL & ULC Listed. FM & NYC Approved
(Refer to Table 1. The approvals apply
only to the service conditions indicated
in the Design Criteria Section)
Maximum Working Pressure
175 psi (12, 1 bar)
250 psi (17,3 bar) UL & ULC
Pipe Thread Connection
1/2 inch NPT
Discharge Coefficient
K = 5.6 GPM/psi112 (80,6 LPM/bar112)
Temperature Ratings
165°F/74°C or 212°F/100°C
Finishes
Sprinkler: White Polyester, Chrome
Plated, or Natural Brass
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
The Model H Recessed Pendent
Sprinklers utilize a dezincification resistant
(DZR) bronze frame and a brass deflector.
The waterway is sealed with copper seal
disk, and the fusible assembly is con-
structed of bronze and stainless steel
components.
CENTRAL
Standard Spray
Recessed
Pendent
Sprinklers
No. 1-3.0
Figure 1 -Model H Recessed Sprinkler
with Push-on Escutcheon
I
~ I
\ 2-3/4"(69,9 mm) Max.
~ 2-1 /2" (63,5 mm)Min. /
I I ____ I _I
15/
(23,8 mm± , mm)
L_ ___ c:c::~:i::q:=
FACE OF SPRINKLER
FITTING
1-----3-1/4" (82,6 mm)-----
Figure 3 -Cross Section
Model H Recessed Sprinkler
CAP
ACTUATING
ROD
SPRINKLER
FRAME
DEFLECTOR
SEAL DISK
SUPPORT
EJECTOR
SPRING
MODEL N H
RECESSED
ESCUTCHEON
Figure 2 -Model H Recessed Sprinkler
with Threaded Escutcheon
15/16"±1/4" (23,8 mm± 6,4 mm)
L_ __ ~~=
FACE OF SPRINKLER
FITTING
WRENCH
FLAT
1-+-----3-1/4" (82,6 mm)----
Figure 4 -Universal Wrench
(Part #1122)
Figure 5 -Recessed
Escutcheon Tool
(Part #10654000)
Design
___ Criteria
The Model H Recessed Pendent Sprinklers are UL, ULC Listed and MEA Approved for use in accordance with current NFPA
standards. The Recessed Pendent Sprinklers are only listed with the Series NH Recessed Escutcheon Assemblies.
The Model H Recessed Pendent Sprinklers are FM Approved for use in accordance with the FM Loss Prevention Data
Sheets. The Recessed Pendent Sprinklers are only listed with the Series NH Recessed Escutcheon Assemblies.
The Model H Recessed Pendent Sprinklers are availabe with a two types of support cups, one that accepts a push-on
escutcheon and one that accepts a threaded escutcheons. The recessed escutcheons are manufactured out of a metal or
plastic material that has been specifficaly tested and listed for use with the Model H Recessed Pendent Sprinklers. The
plastic recessed escutcheon is only listed for use with the push-on support cup assembly.
Do not install the Model H Recessed Pendent Sprinklers in ceilings which have positive pressure in the space above.
Table 1 -Laboratory Listings and Approvals
SPRINKLER FINISH
Temperature Frame Natural Chrome Rating Color Code Brass Plated
165°F/74°C Unpainted 1,2,3,4 1,2,3,4
212°F/100°C White 1,2,3,4 1,2,3,4
Notes:
1. Listed by Underwriters Laboratories, Inc.
2. Listed by Underwriters' Laboratories of Canada.
3. Approved by Factory Mutual Research Corporation.
4. Approved by the City of New York under BSA 375-75-SA
~ Installation
The Model H Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
NOTES
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7 to
14 ft.lbs. (9,5 to 19,0 Nm). A maximum
of 21 ft.lbs. (28,5 Nm) of torque is to be
used to install 1/2 inch NPT sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.
Do not attempt to make up for insuffi-
cient adjustment in the escutcheon plate
by under-or overtightening the sprin-
kler. Readjust the position of the
sprinkler fitting to suit.
Step 1. Pendent sprinklers must be
installed only in the pendent position.
The deflector is to be parallel to the
ceiling, roof, or mounting surface, as
applicable.
Step 2. With pipe thread sealant applied
to the pipe threads, hand tighten the
sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the Universal
Wrench (Ref. Figure 4). With reference
to Figure 1 or 2, the Universal Wrench
is to be applied to the sprinkler wrench
flats only.
After the ceiling has been installed or
the finish coat has been applied, slide
on the Model A/H Recessed Escutcheon
over the Model H Recessed Sprinkler
and push-on or thread on the recessed
escutcheon until its flange comes in
contact with the ceiling.
Polyester
Coated
1
1
Installation of the Model A/H Reccesed
Escutcheon can be accomplished by
hand or by using the Recessed
Escutcheon Tool (Ref. Figure 5) and a
telescoping pole assembly. Every
Model H Recessed Escutcheon has 4
tabs on the interior opening of the
escutheon. By matching these tabs to
the corresponding groove on the
Recessed Escutcheon Tool and with
the telescoping pole attached, the
recessed escutcheon can be installed
without the aid of a ladder. Care should
be exercised to assure that the Actuator
Rod and Ejector Springs of the sprinkler
are not dammaged during the installa-
tion of the recessed escutcheon.
ITTTICare& LI Maintenance
The Model H Recessed Pendent
Sprinklers must be maintained and
serviced in accordance with the
following instructions.
NOTES
Absence of an escutcheon which is
used to cover a clearance hole, may
delay the time to operation in a fire
situation.
Before closing a fire protection
system main control valve for
maintenance work on the fire
protection system it controls,
permission to shut down the
affected fire protection systems
must be obtained from the proper
authorities. All personnel who may
be affected by this action must be
notified.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
shipped or stored where their
temperatures will exceed 100°F/
38°C and they must never be
painted, plated, coated or otherwise
altered after leaving the factory.
Modified sprinklers must be
replaced. Sprinklers that have been
exposed to corrosive products of
combustion, but have not operated,
should be replaced if they cannot
be completely cleaned by wiping the
sprinkler with a cloth or by brushing
it with a soft bristle brush.
Care must be exercised to avoid
damage -before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/
slippage, or the like, must be
replaced.
The owner is responsible for the
inspection, testing, and mainte-
nance of their fire protection system
and devices in compliance with this
document, as well as with the
applicable standards of the National
Fire Protection Association (e.g.,
NFPA 25), in addition to the
standards of any other authorities
having jurisdiction. The installing
contractor or sprinkler manufacturer
should be contacted relative to any
questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a
qualified Inspection Service.
tqca/Flow Control/ Tyco Fire Products
""'Limited
~ Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and
workmanship when paid for and
properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by Tyco Fire
Products. No warranty is given for
products or components manufactured
by companies not affiliated by owner-
ship with Tyco Fire Products or for
products and components which have
been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained,
modified or repaired in accordance
with applicable Standards of the
National Fire Protection Association,
and/or the standards of any other
Authorities Having Jurisdiction.
Materials found by Tyco Fire Products
to be defective shall be either repaired
or replaced, at Tyco Fire Products'
sole option. Tyco Fire Products neither
assumes, nor authorizes any person
to assume for it, any other obligation
in connection with the sale of products
or parts of products. Tyco Fire
Products shall not be responsible for
sprinkler system design errors or
inaccurate or incomplete information
supplied by Buyer or Buyer's repre-
sentatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY
OR UNDER ANY OTHER LEGAL
THEORY, FOR INCIDENTAL,
INDIRECT, SPECIAL OR CONSE-
QUENTIAL DAMAGES, INCLUDING
BUT NOT LIMITED TO LABOR
CHARGES, REGARDLESS OF
WHETHER TYCO FIRE PRODUCTS
WAS INFORMED ABOUT THE
POSSIBILITY OF SUCH DAMAGES,
AND IN NO EVENT SHALL TYCO
FIRE PRODUCTS' LIABILITY EX-
CEED AN AMOUNT EQUAL TO THE
SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS
OR IMPLIED. INCLUDING WARRAN-
TIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR
PURPOSE.
HOrdering lt:t1 Information
Ordering Information: When
placing an order, indicate the full
product name. Please specify the
quantity, model, style, orifice size,
temperature rating, type of finish or
coating, and sprinkler wrench. Refer
to price list for complete listing of Part
Numbers.
Teflon is a trademark of the DuPont Corp.
Printed in U.S.A. 2-01
~-chedule-10®/Schedule-40®
· ully Listed and FM Approved Sprinkler Pipe
When you specify Schedule-IO /Schedule-40 sprinkler pipe you get UL listed and FM approved product. Although these
products do not require separate approvals, Schedule-10/Schedule-40 gives you the extra quality assurance you demand.
Our Sch-10 (1-1/4"-8") pipe and Sch-40 (1 "-2-1/2") pipe have passed the same thorough lab testing as our other listed
pipe products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality.
-: Galvanized Pipe .
Schedule-IO /Schedule-40 product
can be "hot-dip" galvanized to
meet FM requirements for dry
systems in accordance with the
zinc coating specifications of
ASTM A-123.
· · Superior Coating
Our advanced formula mill coating
offers a clean, durable surface. It is
also paint-ready for custom color
)lications without special
· ··eparation.
· American Made
Meets "Buy American" requirement
and is available through distributors in
the USA, Canada and Mexico.
· Specifications & Approvals _
Schedule-! 0 /Schedule-40 pipe are in
compliance with the following:
ASTM A-135, and NFPA 13.
Both pipe products have a working pressure
rating of 300 psi maximum and also
meet the stringent requirement for the
following tests :
• Welded Outlets
• Hydrostatic Pressure
• Side Wall Rupture
• Vibration Test
f;J" allied
TUBE & CONDUIT
Approved Listed
16100 S. Lathrop
Harvey, IL 60426
·. . . . . Sch-40 Specifications · ·. x~lnches ·*=Metric .
Product Nominal Wt/Ft Wt/Ft Pcs/ Wt/Lift Wt/Lift Wt/Lift
NPS I.D. H20 Filled Lift 21' 24' 25'
X 1" 1.049 1.680 2.05 70 2470 2822 2940
* 25 26.6 2.5 3.05 70 1120 1280 1334
X 11/4" 1.380 2.270 2.93 51 2431 2778 2894
* 32 35.1 4.36 4.36 51 1103 1260 1313
X 11/2" 1.610 2.720 3.61 44 2513 2872 2992
*40 40.9 4.0 5.37 44 1140 1303 1357
X 2 " 2.067 3.650 5.13 30 2300 2628 2738
* 50 52.5 5.4 7.63 30 1043 1192 1242
X 2 1/2" 2.469 5.790 7.86 19 2310 2640 2750
* 65 62.7 8.6 11.73 19 1048 1197 1247
Sch-10 Specifications . . . x=lnches *=Metric
Product Nominal Wt/Ft Wt/Ft Pcs/ Wt/Lift Wt/Lift Wt/Lift
NPS I.D. H20 Filled Lift 21' 24' 25'
X 1" 1.097 1.400 1.81 91 2675 3053 3185
* 25 27.9 2.1 2.70 91 1213 1385 1445
X 11/4" 1.442 1.810 2.52 61 2319 2664 2760
* 32 36.6 2.7 3.75 61 1052 1208 1252
X 11/2" 1.682 2.080 3.04 61 2664 3045 3172
* 40 42.7 3.1 4.52 61 1208 1381 1439
X 2 " 2.157 2.640 4.22 37 2051 2344 2442
* 50 54.8 3.9 6.28 37 930 1063 1108
X 2 1/2" 2.635 3.530 5.89 30 2224 2542 2648
* 65 66.9 5.3 8.77 30 1009 1153 1201
X 3" 3.260 4.330 7.94 19 1728 1975 2057
* 80 82.8 6.4 11.82 19 784 896 933
X 4" 4.260 5.610 11.78 19 2238 2558 2665
* 90 108.2 8.3 17.53 19 1015 1160 1209
X 6" 6.357 9.290 23.03 10 1951 2230 2322
* 150 161.5 13.8 34.27 10 885 1012 1053
X 8 " 8.249 16.490 40.15 7 2424 2770 2885
* 200 209.5 24.5 59.75 7 1100 1256 1309
11350 Norcom Rd.o 2525 N. 27th Ave . Customer Service:
Philadelphia, PA 19154 Phoenix, AZ 85009 1-800-797-6210
Fax 708~339-1806