HomeMy WebLinkAbout5857 OWENS AVE; 300; FA160019; Permit12/14/2020 FA160019 Permit Data
City of Carlsbad
Fire Alarm Permit
Permit No: FA160019
Job Address: 5857 OWENS AV4&0 Status: ISSUED
Permit Type: • FALARM Applied 5/4/2016
Parcel No: 2120923200 Approved: 5/13/2016
Lot #: 0
Reference No.: Issued: 5/13/2016
PC #: Inspector:
Project Title: AVANTI TI TI: NEW FIRE ALARM DEVICES TO THE EXISTING FIRE
ALARM SYSTEM TO ACCOMMODATE NEW TI CONSISTING OF THE
EQUIPMENT SHOWN IN THE DEVICE LEGEND. PROGRAM THE
FACP PER DEQUENCE OF OPERATIONS.
Applicant:
JJJ ENTERPRISES
5335 VINEWOOD ST
ESCONDIDO CA
760-747-3050
Owner:
PALOMAR HEIGHTS HOLDINGS L L C
595 S RIVERWOODS PKWY #400
LOGAN UT
Fees ($) Add'I Fees ($) Total ($) Balance ($)
362 0 362 0
1/1
FIRE ALARM - SECURITY - LOW VOLTAGE SYSTEMS
AVANTI TENANT IMPROVEMENT
5857 OWENS AVENUE SUITE 300
CARLSBAD CA 92008
.EA. SYSTE Mff
ARIAi 2. TSFIEETS.
FA160019
5857 OWENS AV
FIRE ALARM SYSTEM BILL OF MATERIALS
NOTIFIER FCPS-24S6 REMOTE POWER SUPPLY
CSFM# 7315-0028:0225
NOTIFIER F4M-1 MONITOR MODULE
CSFM# 7300-0028:0219
NOTIFIER FRN-1 RELAY MODULE
CSFM# 7300-0028:0219
SYSTEM SENSOR SCW - CEILING MOUNTED STROBES
CSFM# 7125-1653:0186
SYSTEM SENSOR PC2W - CEILING MOUNTED HORN /STROBES
CSFM# 7125-1653:0188
SYSTEM SENSOR SCWK - CEILING MOUNTED OUTDOOR STROBES
CSFM# 7300-1653:0187
& FCPS. gCW
6- & 8-Amp 24-Volt
Remote Power SuoDlies
General
The FGPS-24S6E (6-amp) and FCPS-24S8E (8-amp) are
remote power supplies with battery charger. The FGPS-24S6/-
24S8 may be connected to any 12 or 24 volt fire alarm control
panel (FACP) or may be used as stand-alone supplies. Pri-
mary applications include notification appliance (bell) circuit
(NAG) expansion (to support ADA requirements and NAG syn-
chronization) or auxiliary power to support 24 volt system
accessories. The FGPS-24S6/-24S8 provides regulated and
filtered 24 VDG power to four notification appliance circuits
configured as either four Glass B (Style Y) or Glass A (Style Z,
with ZNAC-4 option module). Alternately, the four outputs may
be configured as all non-resettable, all resettable or two non-
resettable and two resettable. The FGPS-2456/-24S8 also
contains a battery charger capable of charging up to 18 AH
batteries. FGPS-24S6G & FGPS-24S8G are ULG-listed.
NOTE: Unless otherwise specified, the terms FCPS-24S6 and
FCPS-24S8 used in this document refers to the standard FCPS-
24S6 and FCPS-24S8, FCPS-24S6C and FCPS-24S8C, the
FCPS-24S6E and FCPS-24S8E
Features
UL-Listed NAG synchronization using System Sensor,
Wheelock, or Gentex "Gommander2" appliances.
Operates as a sync-follower" or as a "sync-generator"
(default). See note on page 2.
Contains two fully-isolated input/control circuits - triggered
from FAGP NAG (NAG expander mode) or jumped perma-
nently 'ON" (stand-alone mode).
Four Glass B (Style Y) or four Glass A (Style Z, with
ZNAG-4 module) NAGs.
6-amp (FGPS-2456) or 8-amp (FGPS-24S8) full load out-
put, with 3 amps maximum/circuit, in NAG expander mode
(UL 864).
4-amp (FGPS-24S6) or 6-amp (FGPS-2458) continuous
output in stand-alone mode (UL 1481).
Compatible with coded inputs; signals passed through.
Optional power-supervision relay (EOLR-1).
In stand-alone mode, output power circuits may be config-
ured as: resettable, (reset line from FAGP required),
non-resettable, or a mix of two and two.
Fully regulated and filtered power output - optimal for pow-
ering four-wire smoke detectors, annunciators, and other
system peripherals requiring regulated/filtered power.
Power-limiting technology meets UL power-limiting require-
ments.
Form-G normally-closed trouble relay.
Fully supervised power supply, battery, and NAGs.
Selectable earth fault detection.
AG trouble report selectable for immediate 2-hour delay.
Works with virtually any UL 864 fire alarm control which uti-
lizes an industry-standard reverse-polarity notification cir-
cuit (including unfiltered and unregulated bell power).
Requires input trigger voltage of 9 - 32 VDG.
Self-contained in compact, locking cabinet - 15"H x 14.5W
x 2.75"D (cm: 38.1H x 36.83W x 6.985D).
dn-6927:a
NOTIFIER®
by Honeywell
•
____
Includes irtegral battery charger capable of charging up to
18 AH bateries Gabine' capable of housing 7.0 AH batter-
ies.
Battery charger may be disabled via DIP switch for applica-
tions reqJiing larger batteries.
Fixed, clamp-tyJe terminal blocks accommodate up to 12
AWG (3m m2) wire.
Specifications
Primary (AC Power:
FGPS-2456G/-24S8G: 120 VAC, 60 Hz, 3.2A maximum.
FGPS-24S6E/-4S8E 240 VAC, 50 Hz, 1.6A maximum.
Wire Size: minimum #14 AWG (2.0mm) with 600 V insula-
tion.
Control Input Circuit:
Trigger Input Voltage: 9 to 32 VDG.
Trigger Current: 2.0 mA (16-32 V); Per Input: 1.0 mA (9
- 16 V).
Trouble Con-act Rating: 5 A at 24 VDG.
Auxiliary Power Outpul: Specific application power 500 mA
maximum.
Output Circuits:
+24 VDC filtered, regulated.
3.0 A maxmun for any one circuit.
Total conti.iuous current for all outputs (stand-alone mode):
- FGPS-24S6: 4.0 A maximum.
- FGPS-2458: 6.0 A maximum.
Total sholterm currert for all outputs (NAG expander mode):
- FGPS-24S6: 6.0 A maximum.
- FGPS-24S8: 8.0 A maximum.
Secondary Power (Battery) Charging Circuit:
Supports lead-acid batteries only.
Float-charge votage: 27.6 VDG.
dn-6927:a • 04/30/09 - Page 1 012
Maximum current charge: 1.5 A.
Maximum battery capacity: 18 AH.
Applications
Example 1: Expand notification appliance power an additional
6.0 A (FCPS-24S6) or 8.0 A (FCPS-24S8). Use up to four
Class B (Style Y) outputs or four Class A (Style Z) outputs
(using ZNAC-4). For example, the FACP notification appliance
circuits will activate the FCPS when reverse-polarity activation
occurs. Trouble conditions on the FCPS are sensed by the
FACP through the notification appliance circuit.
Example 2: Use the FCPS to expand auxiliary regulated 24-
volt system power up to 4.0 A (FCPS-2456) or up to 6.0 A
(FCPS-24S8). Both resettable and non-resettable power
options are available. Resettable outputs are created by con-
necting the resettable output from the FACP to one or both of
the FCPS inputs.
Example 3: Use addressable control modules to activate the
FCPS instead of activating it through the FACP notification
appliance circuits. This typically allows for mounting the FCPS
at greater distances* away from the FACP while expanding
system architecture in various applications.
For example, an addressable control module is used to acti-
vate the FCPS, and an addressable monitor module is used to
sense FCPS trouble conditions. Local auxiliary power output
from the FCPS provides power to the addressable control
module.
*NOTE: Addressable FACPs are capable of locating control and
monitor modules at distances of up to 12,500 feet (3,810 meters).
Sync Follower/Generator Note
In some installations, it is necessary to synchronize the flash
timing of all strobes in the system for ADA compliance.
Strobes accomplish this by monitoring very short timing pulses
on the NAC power which are created by the FACP. When
installed at the end of a NAC wire run, the FCPS-24S6/-2458
can track (i.e. 'follow") the strobe synchronization timing
pulses on the existing NAC wire run. This maintains the overall
system flash timing of the additional strobes attaches to the
FCPS.
When the FCPS-24S6/-2458 is configured (via DIP switch set-
tings) as a "sync follower," the FCPS's NAC outputs track the
strobe synchronization pulses present at the FCPS's sync
input terminal. The pulses originate from an upstream FACP or
other power supply.
When the FCPS-2456/-2458 are configured (via DIP switch
settings) as a "sync generator," the FCPS's sync input termi-
nals are not used. Rather, the FCPS is the originator of the
strobe synchronization pulses on the FCPS's NAC outputs. In
sync generator" mode, the sync type (System Sensor, Whee-
lock, or Gentex) is selectable via DIP switch settings.
Standards and Codes
The FCPS-24S6 and FCPS-2458 comply with the following
standards:
NFPA 72 National Fire Alarm Code.
UL 864 Standard for Control Units for Fire Alarm Systems
(NAC expander mode).
UL 1481 Power Supplies for Fire Alarm Systems.
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
UL Listed: S635, S674
ULC Listed: S635 (FCPS-2456C & FCPS-24S8C)
: CSFJpproved:
FM Approved
Ordering Information
FCPS-24S6: 6.0 A. 120 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15"H x 14.5W x 2.75"D [cm: 38tH x 36.83W x 6.985D]), and
installation instructions.
FCPS-24S6C: Same as above, ULC-listed.
FCPS-24S6R: Same as FCPS-24S6 with red enclosure.
FCPS-24S6E: 6.0 A, 240 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15"H x 14.5W x 2.75"D [cm: 38.1 H x 36.83W x 6.9850]), and
installation instructions.
FCPS-24S8: 8.0 A, 120 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15"H x 14.5W x 2.75"D [cm: 38.1 H x 36.83W x 6.985D]), and
installation instructions.
FCPS-24S8C Same as above, ULC-listed.
FCPS-24S8R: Same as FCPS-24S8 with red enclosure.
FCPS-24S8E: 8.0 A, 240 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15"H x 14.5W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
ZNAC-4: Class A (Style Y) NAC option module.
EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire
smoke detector power.
BAT-1270: Battery, 12-volt, 7.0 AH (two required, see BAT
Series data sheet DN-6933).
PS-1270: Battery, 12-volt, 7.0 AH (two required, see PS
Series data sheet DN-1 109)
System Sensor® and NOTIFIER® are registered trademarks of Honeywell
International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
I so ooi This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
g • We cannot cover all specific applications or anticipate all requirements. KTV =1 :31
ENCINEERINI III MANUFACTURING All specifications are subject to change without notice.
QUALITY SYSTEMS Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2— dn-6927:a • 04/30/09
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE 0
LISTING No. Page 1 of 1
CATEGORY: 7315--POWER UNITS
LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: vladimir.kireyev@honeywell.com
DESIGN: Models FCPS-2456 and FCPS-2458 are power limited power supply/battery chargers used
for supervision and expanded power driving capability of up to four Notification Appliance
Circuits (FACP Fire Circuits, Signaling Devices) or resettable/non resettable outputs. Model
ZNAC-4 Class A converter. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING: 120 VAC, 24 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as a Power Supply/Battery Charger for use with separately listed compatible fire alarm
control units.
XLF: 7315-0075:0206
1-24-03KK
TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2016 Jujii2O7
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
FCM-1(A)
Series
Control and Relay Modules
General
FCM-1(A) Control Module: The FCM-1(A) Addressable Con-
trol Module provides Notifier intelligent fire alarm control pan-
els a circuit for Notification Appliances (horns, strobes,
speakers, etc.). Addressability allows the FCM-1 (A) to be acti-
vated, either manually or through panel programming, on a
select (zone or area of coverage) basis.
FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay
Module provides the system with a dry-contact output for acti-
vating a variety of auxiliary devices, such as fans, dampers,
control equipment, etc. Addressability allows the dry contact to
be activated, either manually or through panel programming,
on a select basis.
FlashScan® (U.S. Patent 5,539,389) is a communication pro-
tocol developed by NOTIFIER Engineering that greatly
enhances the speed of communication between analog intelli-
gent devices. Intelligent devices communicate in a grouped
fashion. If one of the devices within the group has new infor-
mation, the panel CPU stops the group poll and concentrates
on single points. The net effect is response speed greater than
five times that of other designs.
Features
Built-in type identification automatically identifies these
devices to the control panel.
Internal circuitry and relay powered directly by two-wire
SLC loop. The FCM-1(A) module requires power (for horns,
strobes, etc.), or audio (for speakers).
Integral LED 'blinks" green each time a communication is
received from the control panel and turns on in steady red
when activated.
LED blink may be deselected globally (affects all devices).
High noise immunity (EMF/RFI).
The FCM-1 (A) may be used to switch 24-volt NAG power,
audio (up to 70.7 Vrms).
Wide viewing angle of LED.
SEMS screws with clamping plates for wiring ease.
Direct-dial entry of address 01— 159 for FlashScan loops,
01 - 99 for CLIP mode loops.
Speaker, and audible/visual applications may be wired for
Class B or A (Style V or Z).
Applications
The FCM-1 (A) is used to switch 24 VDC audible/visual power,
high-level audio (speakers). The FRM-1(A) may be pro-
grammed to operate dry contacts for applications such as door
holders or Air Handling Unit shutdown, and to reset four-wire
smoke detector power.
NOTE: Refer to the SLC Manual (PN 51253) for details regarding
releasing applications with the FCM- 1(A). Refer to the FCM- 1-REL
datasheet (DN-60390) for new FlashScanO releasing applications.
Construction
The face plate is made of off-white heat-resistant plastic.
Controls include two rotary switches for direct-dial entry of
address (01-159).
DN-6724:B3
NOTIFIER®
by Honeywell
FCM-1 (A)
The FCM-1(A) is configured for a single Class B (Style Y) or
Class A (Style Z) Notification Appliance Circuit.
The FRM-1(A) provides two Form-C dry contacts that
switch together.
Operation
Each FCM-1(A) or FRM-1(A) uses one of 159 possible module
addresses on a SLC loop (99 on CLIP loops). It responds to
regular polls from the control panel and reports its type and
status, including the open/normal/short status of its Notifica-
tion Appliance Circuit (NAG). The LED blinks with each poll
received. On command, it activates its internal relay. The
FCM-1(A) supervises Class B (Style Y) or Class A (Style Z)
notification or control circuits.
Upon code command from the panel, the FCM-1(A) will dis-
connect the supervision and connect the external power sup-
ply in the proper polarity across the load device. The
disconnection of the supervision provides a positive indication
to the panel that the control relay actually turned ON. The
external power supply is always relay isolated from the com-
munication loop so that a trouble condition on the external
power supply will never interfere with the rest of the system.
Rotary switches set a unique address for each module. The
address may be set before or after mounting. The built-in
TYPE CODE (not settable) will identify the module to the con-
trol panel, so as to differentiate between a module and a sen-
sor address.
Specifications for FCM-1(A)
Normal operating voltage: 15 to 32 VDC.
Maximum current draw: 6.5 mA (LED on).
Average operating current: 350 pA direct poll, 375 pA group
poll with LED flashing, 485 pA Max. (LED flashing, NAC
shorted.)
DN-672433 • 2/17/2011 - Page 1 of 2
Maximum NAC Line Loss: 4 VDC.
External supply voltage (between Terminals T10 and
T1: Maximum (NAC): Regulated 24 VDC; Maximum
(Speakers): 70.7 V RMS, 50W.
Drain on external supply: 1.7 mA maximum using 24 VDC
supply; 2.2 mA Maximum using 80 VRMS supply.
Max NAC Current Ratings: For class B wiring system, the
current rating is 3A; For class A wiring system, the current rat-
ing is 2A.
Temperature range: 32°F to 120°F (0°C to 490C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5° (114.3 mm) high x 4" (101.6 mm) wide x
1.25 (31.75 mm) deep. Mounts to a 4° (101.6 mm) square x
2.125° (53.975 mm) deep box.
Accessories: SMBSOO Electrical Box; CB500 Barrier
S .çjficaE nfoERMj(},
N14mal operating voltage: 15 to 32 VDC.
ou W6 &m LED on).
255 pA group
EOL resistance: not used.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% non-condensing.
Dimensions: 4.5° (114.3 mm) high x 4" (101.6 mm) wide x
1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x
2.125° (53.975 mm) deep box.
Accessories: SMBSOO Electrical Box; CB500 Barrier
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
UL: S635
ULC: S3705 (A version only)
FM Approved
4.7-390-0
FDNY: COA #6067, #6065
Contact Ratings for FRM.1(A)
Current Maximum Load Application Rating Voltage Description
3 A 30 VDC Resistive Non-Coded
2 A 30 VDC Resistive Coded
.9A 110 VDC Resistive Non-Coded
.9A 125 VDC Resistive Non-Coded
A .5 30 VDC Inductive Coded (LJR=5ms)
1 A 30 VDC Inductive Coded (LJR=2m5)
.3A 125 VAC Inductive Non-Coded (PF=0.35)
Inductive
1.5 A 25 VAC (PF=0.35) Non-Coded
Inductive
.7 A 70.7 VAC (PF=0.35) Non-Coded
Inductive
2 A 25 VAC (PF=0.35) Non-Coded
NOTE: Maximum (Speakers): 70.7 V RMS, 50 W
Product Line Information
NOTE: "A" suffix indicates ULC Listed model.
FCM-1 (A): Intelligent Addressable Control Module.
FRM-1 (A): Intelligent Addressable Relay Module.
A2143-20: Capacitor, required for Class A (Style Z) operation
of speakers.
SMB500: Optional Surface-Mount Backbox.
CB500: Control Module Barrier - required by UL for separat-
ing power-limited and non-power limited wiring in the same
junction box as FCM-1(A).
NOTE: For installation instructions, see the following documents:
FCM-1(A) Installation document 156-1169.
FRM-1(A) Installation document 156-3502.
Notifier SLC Wiring Manual, document 51253.
Notifier® and FlashScan® are registered trademarks of Honeywell
International Inc.
©2011 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes. ISO 9001 We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements. I I I I
BCINEERING & MANUFACTURING All specifications are subject to change without notice.
QUALITY SYSTEMS Made in the U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 2 of 2- DN-6724:83 • 2/17/2011
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. Page 1 of 1
CATEGORY: 7300 --FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: vladimir.kireyev©honeywell.com
DESIGN: Models XP6-R relay module, XP6-C, supervising control module, XP10-M input monitor
module, XP6-MA six zone interface module, FMM-1, FMM-101, FZM-1, FSM-101, FDM-1,
FTM-1 monitor modules, FCM-1, FRM-1 control modules, and *FDRM1 with 2 input/2 output
relay module. All devices are intended to be connected between the signaling line circuit of a
compatible fire alarm control panel. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING: 16-33 VDC Primary
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, product number and UL label.
APPROVAL: Listed as control unit accessories for use with listee's separately listed compatible fire alarm
control units. Model FTM-1 is intended to be used with Notifier Models NFS-640, NFS2-640
(CSFM Listing No. 7165-0028:214), NFS-3030, NFS2-3030 (CSFM Listing No.
7165-0028:224) Fire Alarm Control Units.
NOTE: If an external power supply is used for Model XP6-MA, the negative of the external power
supply is referenced to the negative of the auxiliary supply of the compatible control panel.
This is done in order to detect ground faults on the initiating circuit.
*Rev. 10-24-11 mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2016
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
DN-6720:C • H-220
FMM-1 (A), Mf(AJ,
FZM-1 (A) & FDM.1 (A)
Monitor Modules with FlashScan®
General
Four different monitor modules are available for Notifier's intel-
ligent control panels for a variety of applications. Monitor mod-
ules supervise a circuit of dry-contact input devices, such as
conventional heat detectors and pull stations, or monitor and
power a circuit of two-wire smoke detectors (FZM-1(A)).
FMM-1(A) is a standard-sized module (typically mounts to a 4"
[10.16 cm] square box) that supervises either a Style D (Class
or Style B (Class B) circuit of dry-contact input devices.
FMM-1 01 (A) is a miniature monitor module a mere 1.3" (3.302
cm) H x 2.75" (6.985 cm) W x 0.5' (1.270 cm) D that super-
vises a Style B (Class B) circuit of dry-contact input devices.
Its compact design allows the FMM-101 (A) to be mounted in a
single-gang box behind the device it monitors.
FZM-1(A) is a standard-sized module that monitors and super-
vises compatible two-wire, 24 volt, smoke detectors on a Style
D (Class A) or Style B (Class B) circuit.
FDM-1(A) is a standard-sized dual monitor module that moni-
tors and supervises two independent two-wire Style B (Class
dry-contact initiating device circuits (lDCs) at two separate,
consecutive addresses in intelligent, two-wire systems.
FlashScan® (U.S. Patent 5,539,389) is a communication pro-
tocol developed by NOTIFIER that greatly increases the speed
of communication between analog intelligent devices. Intelli-
gent devices communicate in a grouped fashion. If one.of the
devices within the group has new information, the panel CPU
stops the group poll and concentrates on single points. The
net effect is response speed greater than five times that of
other designs.
FMM-1(A) Monitor Module
Built-in type identification automatically identifies this device
as a monitor module to the control panel.
Powered directly by two-wire SLC loop. No additional power
required.
High noise (EMF/RFI) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry of address: 01 - 159 on FlashScan loops;
01 —99 on CLIP loops.
LED flashes green during normal operation (this is a pro-
grammable option) and latches on steady red to indicate
alarm.
The FMM-1(A) Monitor Module is intended for use in intelli-
gent, two-wire systems, where the individual address of each
module is selected using the built-in rotary switches. It pro-
vides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator. The FMM-1(A) can be used to replace MMX-1(A)
modules in existing systems.
FMM- 1(A) APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normally-
open dry-contact alarm activation devices. May also be used
to monitor normally-open supervisory devices with special
supervisory indication at the control panel. Monitored circuit
may be wired as an NFPA Style B (Class B) or Style D (Class
NOTIFIER®
by Honeywell
$SJP*I flflLOflAUP.OMIlEO
;E?.1
FMM-1(A) (Type H)
A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor
(provided) terminates the Style B circuit. No resistor is
required for supervision of the Style D circuit.
FMM-1(A) OPERATION
Each FMM-1(A) uses one of the available module addresses
on an SLC loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC). A flashing LED indicates
that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limita-
tions on the loop).
FMM-1(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 350 pA (LED flashing), 1 com-
munication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 40 ohms.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 491C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4' (10.16 cm) square x
2.125" (5.398 cm) deep box.
DN-6720:C • 10/06/2010— Page 1 of 4
FMM-1 01(A) Mini Monitor Module
Built-in type identification automatically identifies this device
as a monitor module to the panel.
Powered directly by two-wire SLC loop. No additional power
required.
High noise (EMF/RFI) immunity.
Tinned, stripped leads for ease of wiring.
Direct-dial entry of address: 01 - 159 on FlashScan loops;
01 —99 on CLIP loops.
o 1415 0 1 I_ ADDRESS I o 1
10~~
15
11 LOOP
"
, 8 7 8 76
TENS ONES
II II
oIl Lij Ii o Lull q lO
The FMM-101(A) Mini Monitor Module can be installed in a
single-gang junction directly behind the monitored unit. Its
small size and light weight allow it to be installed without rigid
mounting. The FMM-101(A) is intended for use in intelligent,
two-wire systems where the individual address of each module
is selected using rotary switches. It provides a two-wire initiat-
ing device circuit for normally-open-contact fire alarm and
security devices. The FMM-1 01(A) can be used to replace
MMX-101(A) modules in existing systems.
FMM-101(A) APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke
detectors, manual fire alarm pull stations, waterflow devices, or
other normally-open dry-contact devices. May also be used to
monitor normally-open supervisory devices with special super-
visory indication at the control panel. Monitored circuit/device
is wired as an NFPA Style B (Class B) Initiating Device Circuit.
A 47K ohm End-of-Line Resistor (provided) terminates the cir-
cuit.
FMM-101(A) OPERATION
Each FMM-101(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/nor-
mal/short) of its Initiating Device Circuit (IDC).
FMM-101(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Average
5 seconds, EOLI 600 ax, Zo`nhTiu—nicating, IDC
Maximum IDC wiring resistance: 40 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 400 pA.
EOL resistance: 47K ohms.
Temperature range: 32°F to 120°F (0°C to 490C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 1.3" (3.302 cm) high x 2.75' (6.985 cm) wide x
0.65" (1.651 cm) deep.
Wire length: 6" (15.24 cm) minimum.
FZM.1 (A) Interface Module
Supports compatible two-wire smoke detectors.
Supervises IDC wiring and connection of external power
source.
High noise (EMF/RFI) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry of address: 01 - 159 on FlashScan loops,
01 —99 on CLIP loops.
LED flashes during normal operation; this is a programma-
ble option.
LED latches steady to indicate alarm on command from
control panel.
The FZM-1(A) Interface Module is intended for use in intelli-
gent, addressable systems, where the individual address of
each module is selected using built-in rotary switches. This
module allows intelligent panels to interface and monitor two-
wire conventional smoke detectors. It transmits the status (nor-
mal, open, or alarm) of one full zone of conventional detectors
back to the control panel. All two-wire detectors being moni-
tored must be UL compatible with the module. The FZM-1(A)
can be used to replace MMX-2(A) modules in existing sys-
tems.
FZM-1(A) APPLICATIONS
Use the FZM-1 (A) to monitor a zone of two-wire smoke detec-
tors. The monitored circuit may be wired as an NFPA Style B
(Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K
ohm End-of-Line Resistor (provided) terminates the end of the
Style B or D (class B or A) circuit (maximum IDC loop resis-
tance is 25 ohms). Install ELR across terminals 8 and 9 for
Style D application.
FZM-1(A) OPERATION
Each FZM-1(A) uses one of the available module addresses
on an SLC loop. It responds to regular polls from the control
panel and reports its type and the status (open/normal/short)
of its Initiating Device Circuit (IDC). A flashing LED indicates
that the module is in communication with the control panel.
The LED latches steady on alarm (subject to current limita-
tions on the loop).
FZM-1(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 ohms.
Average operating current: 300 pA, 1 communication and 1
LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K ohms.
External supply voltage (between Terminals T3 and T4):
DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms
maximum. Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4° (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
Page 2 of 4 - DN-6720:C • 10/06/2010
FDMI (A) Dual Monitor Module
The FDM-1 (A) Dual Monitor Module is intended for use in intelli-
gent, two-wire systems. It provides two independent two-wire
initiating device circuits (lDCs) at two separate, consecutive
addresses. It is capable of monitoring normally open contact fire
alarm and supervisory devices; or either normally open or nor-
mally closed security devices. The module has a single panel-
controlled LED.
NOTE: The FDM-1(A) provides two Style B (Class B) IDC circuits
ONLY. Style D (Class A) IDC circuits are NOT supported in any
application.
FDM-1(A) SPECIFICATIONS
Normal operating voltage range: 15 to 32 VDC.
Maximum current draw: 6.4 mA (LED on).
Average operating current: 750 pA (LED flashing).
Maximum IDC wiring resistance: 1,500 ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 240 pA
EOL resistance: 47K ohms.
Maximum SLC Wiring resistance: 40 Ohms.
- 161.002/23/3 (AFP-200: FMM-1/-101, FZM-1)
- 161.002142/1 (NFS-640: FMM-1/-101)
Lloyd's Register:
—03/60011/El (FMM-1/-101, FZM-1)
- 94/60004/E2 (AFP-200: except FDM-1)
- 02/60007 (NFS -640: FDM- 1)
FDNY: COA #6038 (NFS2-640, NFS-320), COA# 6058
(NFS2-3030)
Product Line Information
NOTE: "A" suffix indicates ULC-listed model.
FMM-l(A): Monitor module.
FMM-1 01 (A): Monitor module, miniature.
FZM-1 (A): Monitor module, two-wire detectors.
FDM-l(A): Monitor module, dual, two independent Class B cir-
cuits.
SMB500: Optional surface-mount backbox.
NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN51253.
Temperature range: 32° to 120°F (0° to 490C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
2.125" (5.398 cm) deep.
FDM-1(A) AUTOMATIC ADDRESSING
The FDM-1 (A) automatically assigns itself to two addressable
points, starting with the original address. For example, if the
FDM-1(A) is set to address "26", then it will automatically
assign itself to addresses "26" and "27".
NOTE: "Ones" addresses on the FDM-1(A) are 0, 2, 4, 6, or8 only.
Terminals 6 and 7 use the first address, and terminals 8 and 9 use
the second address.
JL CAUTION:
Avoid duplicating addresses on the system.
Installation
FMM-1(A), FZM-1(A), and FDM-1(A) modules mount directly
to a standard 4" (10.16 cm) square, 2.125' (5.398 cm) deep,
electrical box. They may also be mounted to the SMB500 sur-
face-mount box. Mounting hardware and installation instruc-
tions are provided with each module. All wiring must conform
to applicable local codes, ordinances, and regulations. These
modules are intended for power-limited wiring only.
The FMM-101(A) module is intended to be wired and mounted
without rigid connections inside a standard electrical box. All
wiring must conform to applicable local codes, ordinances, and
regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
UL: S635
(JLC: S635
FM Approved
79
U.S. Coast Guard:
DN-6720:C • 10/06/2010 - Page 3 of 4
FlashScan® and NOTIFIER® are registered trademarks and Fire Watch is
a trademark of Honeywell International Inc. 02010 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
I So 000i This document is not intended to be used for installation purposes.
We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
BlNEEINC & MANUFACTIRING
QUALITY SYSTEMS
All specifications are subject to change without notice. Madeinthe U.S. A.
For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118.
www.notifier.com
Page 4 of 4— DN-6720:C • 10/06/2010
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Vladimir Kireyev (203) 484-6277 Fax (203) 484-7309
Email: vladimir.kireyev@honeywell.com
DESIGN: Models XP6-R relay module, XP6-C, supervising control module, XP10-M input monitor
module, XP6-MA six zone interface module, FMM-1, FMM-101, FZM-1, FSM-101, FDM-1,
FTM-1 monitor modules, FCM-1, FRM-1 control modules, and *FDRM..1 with 2 input/2 output
relay module. All devices are intended to be connected between the signaling line circuit of a
compatible fire alarm control panel. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING: 16-33 VDC Primary
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, product number and UL label.
APPROVAL: Listed as control unit accessories for use with listee's separately listed compatible fire alarm
control units. Model FTM-1 is intended to be used with Notifier Models NFS-640, NFS2-640
(CSFM Listing No. 7165-0028:214), NFS-3030, NFS2-3030 (CSFM Listing No.
7165-0028:224) Fire Alarm Control Units.
NOTE: If an external power supply is used for Model XP6-MA, the negative of the external power
supply is referenced to the negative of the auxiliary supply of the compatible control panel.
This is done in order to detect ground faults on the initiating circuit.
*Rev. 10-24-11 mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2016
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
SYSTEM Z~-4 SENSOR®
Indoor Selectable-
Output Strobes and
Horn Strobes for
Ceiling Applications
SpectrAlert Advance audible visible notification products
are rich with features guaranteed to cut installation times
and maximize profits. SPECTRAlert
Syt Senor
Features
Plug-in design with minimal intrusion into the back box
Tamper-resistant construction
Automatic selection of 12- or 24-volt operation at 15 and
15/75 candela
Field-selectable candela settings on ceiling units: 15, 15/75, 30
75, 95, 110, 115, 135, 150, 177, and 185
Horn rated at 88+ dBA at 16 volts
Rotary switch for horn tone and three volume selections
Universal mounting plate for ceiling units
Mounting plate shorting spring checks wiring continuity before
device installation
Electrically Compatible with legacy SpectrAlert devices
Compatible with MDL sync module
The SpectrAlerl Advance series offers the most versatile and
easy-to-use line of -iorns, strobes, and horn strobes in the industry.
With white and red plastic housings, wall and ceiling mounting
options, and plain and FIRE-printed devices, SpectrAlert Advance
can meet vir:ually any application requirement.
Like the entire SpectrAler: Advance product line, ceiling-mount
strobes and horn strobes include a variety of features that increase
their application versatility while simplifying installation. All devices
feature plug-in designs with minimal intrusion into the back box,
making installations fast and foolproof while virtually eliminating
costly and tina-co-isumirig ground faults.
To further simplify nstallation and protect devices from construction
damage, SpectrAlert Advance utilizes a universal mounting plate
with an onboard shorting spring, so installers can test wiring
continuity befcre the devce is installed.
Listed for ceiling or wall mounting Installers can also easily adapt devices to a suit a wide range of
application equirements using field-selectable candela settings,
automatic selecticn of 12- or 24-volt operation, and a rotary switch
for horn tones with three volume selections.
Agency Listings
SIGNALING I
Fj MEA-
LISTED APPROVEDAPPROVED approved
S4011 (ct(mes, horn srrobes, horns) 3023572 MEA452-05-E
S5512 (strobes) 7135-1653 189 (horns, chimes)
SpectrAlert Advance Specifications
General
SpectrAlert Advance strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double-
gang back box. Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used for
mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, SpectrAlert
Advance products, when used with the Sync.Circuit° Module accessory, shall be powered from a non-coded notification appliance circuit
output and shall operate on a nominal 120124 volts. When used with the SynceCircuit Module, 12-volt-rated notification appliance circuit
outputs shall operate between 9 and 17.5 volts 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts.
Indoor SpectrAlert Advance products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified
unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95, 110, 115, 135,
150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and shall be approved for fire protective service
The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1971 and UL 464 and shall be approved for
fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light
shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch
between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. On four-wire
products, the strobe shall be powered independently of the sounder. The horn on horn strobe models shall operate on a coded or non-coded
power supply.
Synchronization Module
The module shall be a System Sensor Sync-Circuit model MDL listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 411/16 x 411/16 x 21/8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Electrical Specifications,~
Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity Range 10 to 93% non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1
Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Input Terminal Wire Gauge 12to18AWG
Ceiling-Mount Dimensions (including lens) 6.8-diameter x 25" high (173 mm diameter x 64 mm high)
Ceiling-Mount Back Box Skirt Dimensions (BBSC-2, BBSCW-2) 7.1 "diameter x 2.2-high (180 mm diameter x 57 mm high)
Ceiling-Mount Trim Ring Dimensions (sold as a 5 pack) (TRC-HS, 6.9"diameter x 0.35-high (175 mm diameter x 9 m high)
TRCW-HS)
Notes:
Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs
F, 5, PC, and SC products will operate at 12 V nominal only for 15 and 15/75 cd.
AVDSOO5O1
UL Current Draw Data
JUnax.5trooe current
8-17.5 Volts 16-33 Volts
Candela DC FWR DC FWR
Standard Candela Range 15 123 128 71
15/75 142 148 77 81
30 NA NA 96
High
Candela Range
75 - NA NA 153
95 NA NA C=NWO 176
110 NA NA 202 195
115 NA NA 210 205
135 NA NA 228 207
150 NA NA 246 220
177 NA NA 281 251
185 NA NA 286 258
UL Max. Current Draw (mA
DC Input
RMS), 2-Wire
8-17.5 Volts
15
Horn Strobe,
15175
Standard
16-33 Volts
15
Candela
15175
Range (15-115
30
cd)
75 95 110 115
Temporal High 137 147 90 107 212 (21
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non-Temporal High 141 152 91 100 116 176 201 221 229
Non-Temporal Medium 133 145 75 85 102 163 187 207 216
Non-Temporal Low 131 144 68 79 96 156 182 201 210
FWR Input
Temporal High 136 155 88 97 112 168 190 210 218
Temooral Medium 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 86 101 160 184 194 201
Non-Temporal High 142 161 103 112 126 181 203 221 229
Non-Temporal Medium 134 155 85 95 110 166 189 208 216
Non-Temporal Low
WRIT
DC Input
132 154
Mug=
16-33 Volts
135 150
80
177 185
90 105 161
FWR Input
184
16-33 Volts
135 150
202
177
211
185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281
Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267
Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262
Horn Strobe Tones and Sound Output Data
Switch
Position Sound Pattern dB
8-17.5
DC FWR
16-33
DC
Volts Volts Reverberant Anechoic
FWR
24-Volt Nominal
DC FWR DC FWR
1 Temporal High 78 78 84 84 88 88 99 98
2 Temporal Medium 74 74 80 80 86 86 96 96
3 Temporal Low 71 73 76 76 83 80 94 89
4 Non-Temporal High 82 82 88 88 93 92 100 100
5 Non-Temporal Medium 78 78 85 85 90 90 98 98
6 Non-Temporal Low 75 75 81 81 88 84 96 92
Coded High 82 82 88 88 93 92 101 101
8t Coded Medium 78 78 -85 85 90 90 97 98
9t Coded Low 75 75 81 81 88 85 96 92
tSeflings 7, 8, and 9 are not available on 2-wire horn strobes.
AVDSOO5O1
6.8
a.
SpectrAlert Advance Dimensions
7.1"
Dia. I4_2.25'1
2.5"
Ceiling-mount horn strobes Ceiling back box skirt
SpectrAlert Advance Ordering Information
In IL
Ceiling Horn Strobes
PC2R* 2-Wire Horn Strobe, Standard Cd, Red
PC2RH 2-Wire Horn Strobe, High Cd, Red
PC2W*t 2-Wire Horn Strobe, Standard Cd, White
PC2WH* 2-Wire Horn Strobe, High Cd, White
PC4R 4-Wire Horn Strobe, Standard Cd, Red
I
Ceiling Strobes
SCR Strobe, Standard Cd, Red
SCRH Strobe, High Cd, Red
SCW* Strobe, Standard Cd, White
SCWH Strobe, High Cd, White
Accessories
PC4RH 4-Wire Horn Strobe, High Cd, Red BBSC-2 Back Box Skirt, Ceiling, Red
PC4W 4-Wire Horn Strobe, Standard Cd, White Back Box Skirt, Ceiling, White
TRC-HS Trim Ring, Ceiling, Red
TRCW- Trim Ring, Ceiling, White
HS
Notes:
* Add "-P" to model number for plain housing (no "FIRE" marking on cover), e.g., P2RP,
t Add "-SP" to model number for "FUEGO" marking on cover, e.g., P2R-SP.
t "Standard cd" refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. "High Cd" refers to strobes that include 135, 150, 177, and 185
candela settings.
SYSTEM 02012 System Sensor.
3825 Ohio Avenue • St. Charles, IL 60174 Product specifications subject to change without notice. Visit nystemsensor.com
SENSOR' Phone' 800-SE NSOR2 • Fax' 630-377-6495 tsr current product information, Including t
AVOS00501 •
he latest version of this data sheet.
3/12
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM 1
LISTING SERVICE
LISTING No. Page 1 of 1
CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Irish Linhart (630) 762-5025 Fax (630) 377-7245
Email: trish.linhartsystemsensor.com
DESIGN: Synchronous type strobe lights, Models SR, SRH, SW, SW-CLR-ALERT, SWH, SCR,
SCRH, SCW, SCW-CLR-ALERT and SCWH followed by the suffix -P, -SP, -PG, or none.
Intended for indoor use mounted on the wall or the ceiling. Refer to listee's data sheet for
additional detailed product description and operational considerations.
RATING: 8-17.5 or 16-33 VDC/FWR
Candela: 15, 15/75, 30, 75, 95, 110, 115, *135, *150 *177 *185cd
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as strobe lights suitable for hearing impaired application when used with separately
listed compatible fire alarm control units. Suitable for indoor use, wall or ceiling mounted.
Refer to listee's Installation Instruction Manual for details.
*Rev. 03-11-10fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2016 Listing e-pi!~e
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL fi
LISTING SERVICE
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM t5
LISTING No. coi88 Page 1 of 1
CATEGORY: 7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: System Sensor, Unincorporated Div of Honeywell Intl lnc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245
Email: trish.linhart©systemsensor.com
DESIGN: Models CHSR and CHSW Chime/Strobes.
Models P2R, P2W, P21RH and P2WH Horn/Strobes two-wire type, rectangular enclosure.
Models PC2R, PC2W, PC21RH and PC2WH Horn/Strobes two-wire type, round enclosure
Models P4R, P4W, P4RH and P4WH Horn/Strobes four-wire type, rectangular enclosure.
Models PC4R, PC4W, PC4RH and PC4WH Horn/Strobes* four-wire type, round enclosure.
All models are intended for indoor use only unless other wise indicated. Models may be
followed by the suffix "K" indicating indoor or outdoor use, or may be followed by suffix "P' for
plain housing with no lettering. "K" suffix models are suitable for outdoor applications at
temperatures from -40°F to +151°F (-40°C to +66°C) and are rated NEMA 4X when used with
the System Sensor weather proof back boxes models SA-WBB (Wall), SA-WBBW (Wall),
SA-WBBC (Ceiling) and *SAWBBCW (Ceiling). Refer to listee's data sheet for additional
detailed product description and operational considerations.
RATING: Standard Horn/Strobes and Chime/Strobes 8- 17.5 or 16-33 VDC/FWR
Hi CD Horn/Strobes 16-33 VDC/FWR
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as *horn/strobes or chime/strobes suitable for signaling appliances and equipment for
the hearing impaired applications when used with separately listed compatible fire alarm
control units. Horn/strobes with -K suffix are suitable for indoor or outdoor use, ceiling or wall
mount. Chime section is suitable for private mode and indoor use only.
Horn/Strobes or chime/strobes* can generate the distinctive three-pulse audible Temporal
Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72,
2010 Edition. Refer to listee's Installation Instruction Manual for details.
"Corrected 12-15-11 bh
TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2016 Listing Expires tf
Authorized By: DAVID CASTILL.O, Program Coordinator
Fire Engineering Division
SYSTEM
$ SENSOR®
Outdoor Selectable.
Output Strobes and
Horn Strobes for
Ceiling Applications
SpectrA lertO Advance outdoor audible visible products
are rich with features that cut installation times and
maximize profits.
Features
Weatherproof NEMA 4X, 1P56 rated
Listed to UL 1638 (strobe) and UL 464 (horn)
Compatible with System Sensor synchronization protocol and
legacy SpectrAlert products
Field-selectable candela settings: 15, 15/75, 30, 75, 95, 110, 115
135, 150, 177, and 185
Automatic selection of 12- or 24-volt operation at 15 and
15/75 candela
Rotary switch for horn tone and three volume selections
Horn rated at 88+ dBA at 16 volts
Rated from —40°F to 151°F
Universal mounting plate with an onboard shorting spring that
tests wiring continuity before devices are installed
Plug-in design with minimal intrusion into the back box
Tamper-resistant construction
Listed for ceiling or wall mounting
Agency Listings
SIGNALING
LISTED IVIEA N toutdoor strobes)
d 7125-1653:188 (horn strobes.
S4011 chimes, horn strobes, horns) APPROVED approve
chime strobes)
S3593 (outdoor and alert strobes) 3023572 MEA452-05.E 7135-1653:189 (hems, chimes)
W17' X A& I L—Mil,
m..'Sflsor
SpectrAlert Advance offers the broadest line of outdoor horns,
strobes, and horn strobes in the industry. With white or red plastic
housings, wall or ceiling mounting options, and plain or FIRE-printed
devices, SpectrAlert Advance can meet virtually any application
requirement, including indoor, outdoor, wet, and dry applications in
temperatures from —40°F to 151°F.
Like the entire SpectrAlert Advance line, outdoor strobes and horn
strobes for ceiling applications include a variety of features that
increase application flexibility and simplify installation. First, field-
selectable settings, including candela, automatic selection of 12- or
24-volt operation, horn tones, and three volume options enable
installers to easily adapt devices to meet requirements.
Next, SpectrAlert Advance devices use a universal mounting plate
for both wall and ceiling applications. This mounting plate includes
an onboard shorting spring that ensures wiring continuity before
devices are installed, so installers can verify proper wiring without
mounting the devices and exposing them to potential construction
damage. Once the plates are mounted, all SpectrAlert Advance
devices utilize a plug-in design with a single captured screw to
speed installation and virtually eliminate costly ground faults.
Outdoor devices ship with weatherproof plastic back boxes (metal
back boxes are available separately) that accommodate in-and-
out wiring for daisy chaining devices. Plastic back boxes feature
removable side flanges and improved resistance to saltwater
corrosion. Plastic and metal weatherproof back boxes come with
3,4-inch top and bottom conduit entries and 3/a-inch knock-outs at the
back. Three screw-in NPT plugs with 0-ring gaskets for a watertight
seal is included with each back box.
SpectrAlert Advance Outdoor Strobe, and Horn Strobe Specifications
General
SpectrAlert Advance outdoor horns, strobes, and horn strobes shall mount to a weatherproof back box. A universal mounting plate shall
be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate.
Also, SpectrAlert Advance products, when used with the Sync'Circuit ° Module accessory, shall be powered from a non-coded notification
appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync.Circuit Module, 12-volt-rated notification
appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between
16.5 and 33 volts. Outdoor SpectrAlert Advance products shall operate between -40 and 151 degrees Fahrenheit from a regulated DC or full-
wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 15/75, 30, 75, 95,
110, 115, 135, 150, 177, and 185.
Strobe
The strobe shall be a System Sensor SpectrAlert Advance Model listed to UL 1638 and shall be approved for fire protective service.
The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for
visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash
tube and associated lens/reflector system. The strobe must be installed with its weatherproof back box in order to remain outdoor approved
per UL. The strobe shall be suitable for use in wet environments.
Horn Strobe Combination
The horn strobe shall be a System Sensor SpectrAlert Advance Model ______ listed to UL 1638 and UL 464 and shall be approved for
fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with
Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light
shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have three audibility options and an option to switch
between a temporal three pattern and a non-temporal (continuous) pattern. These options shall be set by a multiple position switch. On four-
wire products, the strobe shall be powered independently of the sounder. The horn strobe on a 2-wire model shall work on a non-coded power
supply. The horn on 4-wire horn strobe models shall operate on a coded or non-coded power supply. The horn strobe must be installed with
its weatherproof back box in order to remain outdoor listed per UL. The horn strobe shall be suitable for use in wet environments.
Operating Temperature -40°F to 15 1°F (-40°C to 66°C)
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC/FWR or regulated 24 DC/FWR1
Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range with MDL3 Sync Module 8.5 to 17,5V (12 V nominal) or 16.5 to 33V (24 V nominal)
Input Terminal Wire Gauge 12to18AWG
Ceiling-Mount Dimensions (including lens) 6.8" diameter x 2.5" high (173 mm diameter x 64 mm high)
Strobe/Horn Strobe Dimensions 5.6'i x 4.7"W x 1.3"D (142 mm L x 119 mm W x 33 mm D)
Strobe / Horn Strobe Dimensions with Back Box 5.6" L x 4.7"W x 1.3" 0 (142 mm L x 119 mm W x 33 mm D)
Ceiling-Mount Weatherproof Back Box Dimensions 7.1" diameter x 2.0" high (180 mm diameter x 51 mm high)
Notes:
Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
Products will operate at 12 V nominal only for 15 and 15/75 cd.
AVDS114OI
UL Current Draw Data
VJ t'it1;
8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts
Candela DC FWR DC FWR Sound Pattern dB DC FWR DC FWR
Standard 15 123 128 66 71 Temporal High 57 55 69 75
Candela 15/75 142 148 77 81 Temporal Medium 44 49 58 69
Range 30 NA NA 94 96 Temporal Low 38 44 44 48
75 NA NA doI 153 Non-Temporal High 57 56 69 75
95 NA NA 181 176 Non-Temporal Medium 42 50 60 69
110 NA NA 202 195 Non-Temporal Low 41 44 50 50
115 NA NA 210 205 Coded High 57 55 69 75
High 135 NA NA 228 207 Coded Medium 44 51 56 69
Candela 150 NA NA 246 220 Coded Low 40 46 52 50
Range 177 NA NA 281 251
185 NA NA 286 258
8-17.5 Volts 16-33 Volts
DC Input 15 15175 15 15175 30 75 95 110 115
Temporal High 137 147 79 90 107 176 194 212 218
Temporal Medium 132 144 69 80 97 157 182 201 210
Temporal Low 132 143 66 77 93 154 179 198 207
Non-Temporal High 141 152 91 100 116 176 201 221 229
Non-Temporal Medium 133 145 75 85 102 163 187 207 216
Non-Temporal Low 131 144 68 79 96 156 182 201 210
FWR Input
Temporal High 136 155 88 97 112 168 190 210 218
Temporal Medium 129 152 78 88 103 160 184 202 206
Temporal Low 129 151 76 86 101 160 184 194 201
Non-Temporal High 142 161 103 112 126 181 203 221 229
Non-Temporal Medium 134 155 85 95 110 166 189 208 216
Non-Temporal Low
UL Max~ Current DraW (mA'RMS),
DC Input
132
2-Wire
16-33 Volts
135 150
154
Horn Strobe,
177
80
High
185
Candela
90 105 161
Range (135-185 cd)
FWR Input
184
16-33 Volts
135 150
202
177
211
185
Temporal High 245 259 290 297 Temporal High 215 231 258 265
Temporal Medium 235 253 288 297 Temporal Medium 209 224 250 258
Temporal Low 232 251 282 292 Temporal Low 207 221 248 256
Non-Temporal High 255 270 303 309 Non-Temporal High 233 248 275 281
Non-Temporal Medium 242 259 293 299 Non-Temporal Medium 219 232 262 267
Non-Temporal Low 238 254 291 295 Non-Temporal Low 214 229 256 262
Candela Derating
For K series products used at low temperatures, listed
candela ratings must be reduced in accordance with
this table.
I.1iTiT.I1111IlI
Horn Tones and Sound Output Data
8-17.5 16-33
Switch Sound Volts Volts
i.. .ID rr' ClAto fl(' rwo
24-Volt Nominal
Reverberant Anechoic
rI(' Pwn fl(' WR
Listed Candela Candela rating at -40°F
15
Do not use below 32°F
30
15/75
75 44
95 70
110 110
115 115
135 135
150 150
177 177
185 185
1 Temporal High 78 78 84 84 88 88 99 98
2 Temporal Medium 74 74 80 80 86 86 96 96
3 Temporal Low 71 73 76 76 83 80 94 89
4 Non- High 82 82 88 88 93 92 100 100 Temporal
5 Non- Medium 78 78 85 85 90 90 98 98 Temporal
6 Non- Low 75 75 81 81 88 84 96 92 Temporal
7t Coded High 82 82 88 88 93 92 101 101
8t Coded Medium 78 78 85 85 90 90 97 98
Coded Low 75 75 81 81 88 85 96 92
tSettings 7, 8, and 9 are not available on 2-wire horn strobe. AVDS11401
SpectrAlert Advance Diagrams
Ceiling-Mount Horn Strobes Ceiling Plastic Weatherproof Back Box
MIM
Ceiling-Mount Horn Strobe with Plastic Weatherproof Back Box
SpectrAlert Advance Ordering Information
Ceiling Horn Strobes
PC2RK 2-Wire Horn Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)
PC2RHK 2-Wire Horn Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box)
PC2WK 2-Wire, Horn Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)
PC2WHK 2-Wire, Horn Strobe, High cd, White, Outdoor (includes plastic weatherproof back box)
Ceiling Strobes
SCRK Strobe, Standard cd, Red, Outdoor (includes plastic weatherproof back box)
SCRHK Strobe, High cd, Red, Outdoor (includes plastic weatherproof back box)
SCWK Strobe, Standard cd, White, Outdoor (includes plastic weatherproof back box)
SCWHK Strobe, High cd, White, Outdoor (includes plastic weatherproof back box)
Accessories
SA-WBBC Red, Metal Weatherproof Back Box
SA-WBBCW White, Metal Weatherproof Back Box
MP120K
Notes:
"Standard Cd" refers to strobes that include 15, 15/75, 30, 75, 95, 110, and 115 candela settings. "High cd" refers to strobes that include 135, 150, 177, and 185
candela settings. When replacing outdoor units, both the device and back box must be replaced.
' S}'STEA,7 3825 Ohio Avenue • St. Charles, IL 60174 ©2015 System Serrsor
Product specrttcatl000 subject to change without notice. Visit systemse050r.com
SENSOR Phone 800-S ENSOR2 • Fax 630-377-6495 or current product information, rrcludirrg the latest version at this data sheet,
AVDSt14O2 • 02/15
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
LISTING SERVICE
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM t5
LISTING No. Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245
Email: trish.linhart@systemsensor.com
DESIGN: Models SWK, SWHK, SCWK, SCWHK, SRK, SRHK, SCRK and SCRHK strobe lights
intended for indoor or outdoor use and may be mounted on the wall or the ceiling. These
strobe lights are suitable for outdoor use at an operating temperature range of -40°F to 150°F
(-40°C to 66C)* rating and are NEMA 4X rated when used with the Listed models SA-WBB
(wall), SA-WBBW (Wall) or the model SA-WBBC (ceiling), SA-WBBCW (Ceiling)
weatherproof back boxes. May be followed by suffix -P for plain housing with no lettering.
Refer to listee's data sheet for additional detailed product description and operational
considerations.
RATING: 8-17.5 or 16-33 VDC/FWR
INSTALLATION: In accordance with listee's printed installation instruction, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as strobe lights for general signaling. For indoor or outdoor use. Refer to listee's
Installation Instruction Manual for details.
NOTE: Not approved for public mode and not to be used as an evacuation signal for the hearing
impaired.
*Corrected 07-22-10 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2016 Listing Expires
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division