HomeMy WebLinkAbout2841 LOKER AVE E; ; AS160270; Permit12/8/2020 AS160270 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS160270
2841 LOKERAV
Job Address: Status: ISSUED
EAST
Permit Type: SPRINK Applied 8/31/2016
Parcel No: 2090831400 Approved: 9/21/2016
Lot #: 0
Reference No.: Issued: 9/21/2016
PC #: Inspector:
Project Title: ARGONAUT CLEAN ROOM T.I.: ADD FIRE SPRINKLER
PROTECTION IN CLEAN ROOM ADD NEW SPRINKLER DRY
PENDENTS IN NEW COLD BOX
Applicant:
SYMONS FIRE PROTECTION
12155 PAINE PL
POWAY, CA 92064
619-588-6364
Owner:
HARRIS GORDON L&PHYLLIS K INTER
VIVOS TRUST 05-1
2500 6TH AVE #8
SAN DIEGO CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
528 0 528 0
1/1
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
8/26/2016 C:\PROGRAN FILES\HRS SYSTEMS\HASS83\16-323.SDF
JOB TITLE: ARGONAUT CLEAN ROOM - 16 HEAD CALC.
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 120.0 109.0 8000.0 119.9 625.0 71.5
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 625.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 250.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 375.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 0.0 SOURCE 71.5 375.0
2 2.0 - - - - 70.4 - - -
3 4.0 - - - - 69.5 - - -
4 4.0 - - - - 67.5 - - -
5 2.0 - - - - 68.3
6 2.0 - - - - 68.3 - -
7 8.0 - - - - 65.7 - - -
8 23.0 - - - - 59.2 - -
9 23.0 - - - - 59.1
10 23.0 - - - - 57.3 - - -
10A 8.0 - - - -
58.9
11 8.0 - - - - 51.3 - - -
12 8.0 - - - - 46.8 - - -
13 8.0 - - - - 42.1 - - -
14 8.0 - - - - 40.4 - - -
15 8.0 - - - - 37.8 - - -
16 8.0 - - - - 37.1 - - -
17 8.0 - - - - 37.0 - - -
18 8.0 - - - - 32.1 - -
19 8.0 - - - - 31.5
20 8.0 - - - - 29.0 - - -
21 8.0 - - - 28.5 - - -
22 8.0 K= 5.60 17.7 23.5
23 8.0 - - - - 28.8 - - -
24 8.0 K= 5.60 17.8 23.7
25 8.0 - - - - 30.6 - - -
26 8.0 K= 5.60 19.0 24.4
27 8.0 - - - - 27.3
28 8.0 K= 5.60 24.3 27.6
29 8.0 K= 5.60 23.6 27.2
30 8.0 K= 5.60 23.7 27.3
31 8.0 - - - - 26.9 - - -
32 8.0 - - - - 24.3 - - -
33 8.0 K= 5.60 15.3 21.9
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
ATE:8/26/2016 C:\PROGRAM FILES\HRS SYSTEMS\HA5583\16-323.SDF
JOB TITLE: ARGONAUT CLEAN ROOM - 16 HEAD CALC.
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
34 8.0 K= 5.60 23.1 26.9
35 8.0 - - - - 23.1 - - -
36 8.0 - - - - 23.1 - - -
37 8.0 K= 5.60 14.5 21.4
38 8.0 - - - - 24.6 - - -
39 8.0 K= 5.60 15.5 22.0
40 8.0 - - - 27.2 - - -
41 8.0 - - - - 26.9 - -
42 8.0 - - - 26.9 - - -
43 8.0 - - - - 24.2 - - -
44 8.0 K= 5.60 15.3 21.9
45 8.0 - -
- -
23.5
46 8.0 K= 5.60 14.8 21.5
47 8.0 - - - - 23.5 - - -
48 8.0 K= 5.60 14.8 21.5
49 8.0 - - - - 24.4 - - -
50 8.0 K= 5.60 12.9 20.1
51 8.0 K= 5.60 12.3 19.6
52 8.0 - - - - 27.3
53 8.0 - - - - 26.3 - - -
54 8.0 K= 5.60 19.0 24.4
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: ,8/26/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS83\16-323.SDF
JOB TITLE: ARGONAUT CLEAN ROOM - 16 HEAD CALC.
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (PT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 375.0 7.660 PL 200.00 PF 0.2
1 0.0 SRCE 71.5 (N/A) 2.6 150 FTG 2.0 PE -0.9 2 2.0 0.0 70.4 0.0 0.001 TL 202.00 PV
Pipe: 2 375.0 9.050 PL 3.00 PF 0.0 2 2.0 0.0 70.4 0.0 1.9 120 FTG 14.0 PE -0.9 3 4.0 0.0 69.5 0.0 0.001 TL 17.00 PV
Pipe: 3 FIXED PRESSURE LOSS DEVICE 3 4.0 0.0 69.5 0.0 2.0 psi, 375.0 gpm 4 4.0 0.0 67.5 0.0
Pipe: 4 375.0 9.050 PL 3.00 PF 0.0 4 4.0 0.0 67.5 0.0 1.9 150 FTG 14.0 PE 0.9
5 2.0 0.0 68.3 0.0 0.001 TL 17.00 PV
Pipe: 5 375.0 7.660 PL 15.00 PF 0.0
5 2.0 0.0 68.3 0.0 2.6 150 FTG 7.0 PE 0.0
6 2.0 0.0 68.3 0.0 0.001 TL 22.00 PV
Pipe: 6 375.0 9.050 PL 3.00 PP 0.0
6 2.0 0.0 68.3 0.0 1.9 150 FTG 7.0 PE -2.6
7 8.0 0.0 65.7 0.0 0.001 TL 10.00 PV
Pipe: 7 375.0 8.329 PL 15.00 PP 0.0
7 8.0 0.0 65.7 0.0 2.2 120 FTG 6.0 PE -6.5
8 23.0 0.0 59.2 0.0 0.001 TL 21.00 PV
Pipe: 8 375.0 6.357 PL 7.00 PF 0.1
8 23.0 0.0 59.2 0.0 3.8 120 FTG 15.0 PE 0.0
9 23.0 0.0 59.1 0.0 0.005 TL 22.00 PV
Pipe: 9 375.0 4.260 PL 42.00 PP 1.8
9 23.0 0.0 59.1 0.0 8.4 120 FTG 14.0 PE 0.0
10 23.0 0.0 57.3 0.0 0.032 TL 56.00 PV
Pipe: 9A 375.0 2.635 PL 15.00 PF 4.8
10 23.0 0.0 57.3 0.0 22.1 150 FTG 7.0 PE 6.5
10A 8.0 0.0 58.9 0.0 0.220 TL 22.00 PV
Pipe: 10 375.0 2.635 PL 8.00 PP 7.6
10A 8.0 0.0 58.9 0.0 22.1 120 FTG 15.0 PE 0.0
11 8.0 0.0 51.3 0.0 0.332 TL 23.00 PV
Pipe: 11 320.2 2.635 PL 5.00 PF 4.5
11 8.0 0.0 51.3 0.0 18.8 120 FTG 13.0 PE 0.0
12 8.0 0.0 46.8 0.0 0.248 TL 18.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE:'8/26/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS83\16-323.SDF
JOB TITLE: ARGONAUT CLEAN ROOM - 16 HEAD CALC.
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 12 270.1 2.635 PL 11.00 PF 4.7
12 8.0 0.0 46.8 0.0 15.9 120 FTG 15.0 PE 0.0
13 8.0 0.0 42.1 0.0 0.181 TL 26.00 PV
Pipe: 13 214.7 2.635 PL 2.00 PF 1.8
13 8.0 0.0 42.1 0.0 12.6 120 FTG 13.0 PE 0.0
14 8.0 0.0 40.4 0.0 0.118 TL 15.00 PV
Pipe: 14 154.6 2.635 PL 22.00 PF 2.5
14 8.0 0.0 40.4 0.0 9.1 120 FTG 17.0 PE 0.0
15 8.0 0.0 37.8 0.0 0.065 TL 39.00 PV
Pipe: 15 102.0 2.635 PL 11.00 PF 0.7
15 8.0 0.0 37.8 0.0 6.0 120 FTG 13.0 PE 0.0
16 8.0 0.0 37.1 0.0 0.030 TL 24.00 PV
Pipe: 16 39.5 2.635 PL 7.00 PF 0.1
16 8.0 0.0 37.1 0.0 2.3 120 FTG 13.0 PE 0.0
17 8.0 0.0 37.0 0.0 0.005 TL 20.00 PV
Pipe: 17 54.8 1.380 PL 64.00 PF 19.2
11 8.0 0.0 51.3 0.0 11.8 120 FTG 23.0 PE 0.0
18 8.0 0.0 32.1 0.0 0.221 TL 87.00 PV
Pipe: 18 50.1 1.380 PL 64.00 PF 15.3
12 8.0 0.0 46.8 0.0 10.7 120 FTG 18.0 PE 0.0
19 8.0 0.0 31.5 0.0 0.187 TL 82.00 PV
Pipe: 19 54.8 2.067 PL 5.00 PF 0.6
18 8.0 0.0 32.1 0.0 5.2 120 FTG 13.0 PE 0.0
19 8.0 0.0 31.5 0.0 0.031 TL 18.00 PV
Pipe: 20 104.9 2.067 PL 11.00 PF 2.6
19 8.0 0.0 31.5 0.0 10.0 120 FTG 14.0 PE 0.0
20 8.0 0.0 29.0 0.0 0.103 TL 25.00 PV
Pipe: 21 55.4 1.380 PL 37.00 PF 11.5
13 8.0 0.0 42.1 0.0 11.9 120 FTG 14.0 PE 0.0
25 8.0 0.0 30.6 0.0 0.226 TL 51.00 PV
Pipe: 22 24.4 0.824 PL 4.00 PF 11.6
25 8.0 0.0 30.6 0.0 14.7 120 FTG 15.0 PE 0.0
26 8.0 5.6 19.0 24.4 0.610 TL 19.00 PV
Pipe: 23 31.0 1.380 PL 11.00 PF 1.8
25 8.0 0.0 30.6 0.0 6.7 120 FTG 13.0 PE 0.0
23 8.0 0.0 28.8 0.0 0.077 TL 24.00 PV
Pipe: 24 23.7 0.824 PL 4.00 PF 10.9
23 8.0 0.0 28.8 0.0 14.2 120 FTG 15.0 PE 0.0
24 8.0 5.6 17.8 23.7 0.575 TL 19.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE:' 8/26/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS83\16-323.SDF
JOB TITLE: ARGONAUT CLEAN ROOM - 16 HEAD CALC.
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 25 7.4 1.380 PL 40.00 PF 0.3
23 8.0 0.0 28.8 0.0 1.6 120 FTG 13.0 PE 0.0
21 8.0 0.0 28.5 0.0 0.005 TL 53.00 PV
Pipe: 26 23.5 0.824 PL 4.00 PF 10.8
21 8.0 0.0 28.5 0.0 14.2 120 FTG 15.0 PE 0.0
22 8.0 5.6 17.7 23.5 0.570 TL 19.00 PV
Pipe: 27 -16.2 1.380 PL 7.00 PF 0.5
21 8.0 0.0 28.5 0.0 3.5 120 FTG 13.0 PE 0.0
20 8.0 0.0 29.0 0.0 0.023 TL 20.00 PV
Pipe: 28 88.7 2.067 PL 9.00 PF 1.7
20 8.0 0.0 29.0 0.0 8.5 120 FTG 13.0 PE 0.0
27 8.0 0.0 27.3 0.0 0.075 TL 22.00 PV
Pipe: 29 48.4 1.380 PL 4.00 PF 3.0
27 8.0 0.0 27.3 0.0 10.4 120 FTG 13.0 PE 0.0
28 8.0 5.6 24.3 27.6 0.176 TL 17.00 PV
Pipe: 30 18.9 1.380 PL 11.00 PF 0.7
28 8.0 5.6 24.3 27.6 4.0 120 FTG 13.0 PE 0.0
29 8.0 5.6 23.6 27.2 0.031 TL 24.00 PV
Pipe: 31 -8.3 1.380 PL 13.00 PF 0.2
29 8.0 5.6 23.6 27.2 1.8 120 FTG 13.0 PE 0.0
30 8.0 5.6 23.7 27.3 0.007 TL 26.00 PV
Pipe: 32 60.0 1.380 PL 35.00 PF 14.1
14 8.0 0.0 40.4 0.0 12.9 120 FTG 19.0 PE 0.0
53 8.0 0.0 26.3 0.0 0.261 TL 54.00 PV
Pipe: 33 1.9 1.380 PL 9.00 PF 0.0
28 8.0 5.6 24.3 27.6 0.4 120 FTG 13.0 PE 0.0
32 8.0 0.0 24.3 0.0 0.000 TL 22.00 PV
Pipe: 34 -45.0 1.380 PL 4.00 PF 2.6
32 8.0 0.0 24.3 0.0 9.7 120 FTG 13.0 PE 0.0
31 8.0 0.0 26.9 0.0 0.154 TL 17.00 PV
Pipe: 35 40.3 2.067 PL 9.00 PF 0.4
27 8.0 0.0 27.3 0.0 3.9 120 FTG 13.0 PE 0.0
31 8.0 0.0 26.9 0.0 0.017 TL 22.00 PV
Pipe: 36 -4.7 2.067 PL 6.00 PF 0.0
31 8.0 0.0 26.9 0.0 0.5 120 FTG 13.0 FE 0.0
41 8.0 0.0 26.9 0.0 0.000 TL 19.00 PV
Pipe: 37 21.9 0.824 PL 3.00 PF 9.0
32 8.0 0.0 24.3 0.0 13.2 120 FTG 15.0 PE 0.0
33 8.0 5.6 15.3 21.9 0.499 TL 18.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
'DATE:' 8/26/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS83\16-323.SDF
JOB TITLE: ARGONAUT CLEAN ROOM - 16 HEAD CALC.
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 38 25.1 1.380 PL 10.00 PF 1.2
32 8.0 0.0 24.3 0.0 5.4 120 FTG 13.0 PE 0.0
34 8.0 5.6 23.1 26.9 0.052 TL 23.00 PV
Pipe: 39 0.0 0.824 PL 3.00 PF 0.0
34 8.0 5.6 23.1 26.9 0.0 120 FTG 15.0 PE 0.0
35 8.0 0.0 23.1 0.0 0.000 TL 18.00 PV
Pipe: 40 -1.9 1.380 PL 12.00 PF 0.0
34 8.0 5.6 23.1 26.9 0.4 120 FTG 13.0 PE 0.0
36 8.0 0.0 23.1 0.0 0.000 TL 25.00 PV
Pipe: 41 21.4 0.824 PL 3.00 PF 8.6
36 8.0 0.0 23.1 0.0 12.9 120 FTG 15.0 PE 0.0
37 8.0 5.6 14.5 21.4 0.476 TL 18.00 PV
Pipe: 42 -23.2 1.380 PL 12.00 PF 1.4
36 8.0 0.0 23.1 0.0 5.0 120 FTG 20.0 PE 0.0
38 8.0 0.0 24.6 0.0 0.045 TL 32.00 PV
Pipe: 43 22.0 0.824 PL 3.00 PF 9.1
38 8.0 0.0 24.6 0.0 13.3 120 FTG 15.0 PE 0.0
39 8.0 5.6 15.5 22.0 0.504 TL 18.00 PV
Pipe: 44 -45.2 1.380 PL 4.00 PF 2.6
38 8.0 0.0 24.6 0.0 9.7 120 FTG 13.0 PE 0.0
40 8.0 0.0 27.2 0.0 0.155 TL 17.00 PV
Pipe: 45 7.4 1.380 PL 33.00 PF 0.3
40 8.0 0.0 27.2 0.0 1.6 120 FTG 18.0 PE 0.0
41 8.0 0.0 26.9 0.0 0.005 TL 51.00 PV
Pipe: 46 -52.6 1.380 PL 31.00 PF 10.7
40 8.0 0.0 27.2 0.0 11.3 120 FTG 21.0 PE 0.0
15 8.0 0.0 37.8 0.0 0.205 TL 52.00 PV
Pipe: 47 2.6 2.067 PL 12.00 PF 0.0
41 8.0 0.0 26.9 0.0 0.3 120 FTG 13.0 PE 0.0
42 8.0 0.0 26.9 0.0 0.000 TL 25.00 PV
Pipe: 48 62.5 1.380 PL 29.00 PF 12.7
16 8.0 0.0 37.1 0.0 13.4 120 FTG 16.0 PE 0.0
49 8.0 0.0 24.4 0.0 0.282 TL 45.00 PV
Pipe: 49 39.5 1.380 PL 64.00 PF 9.8
17 8.0 0.0 37.0 0.0 8.5 120 FTG 17.0 PE 0.0
52 8.0 0.0 27.3 0.0 0.120 TL 81.00 PV
Pipe: 50 42.1 1.380 PL 7.00 PF 2.7
42 8.0 0.0 26.9 0.0 9.0 120 FTG 13.0 PE 0.0
43 8.0 0.0 24.2 0.0 0.136 TL 20.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7
'DATE:' 8/26/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS83\16-323.SDF
JOB TITLE: ARGONAUT CLEAN ROOM - 16 HEAD CALC.
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 51 21.9 0.824 FL 3.00 PF 9.0
43 8.0 0.0 24.2 0.0 13.2 120 FTG 15.0 PE 0.0
44 8.0 5.6 15.3 21.9 0.497 TL 18.00 PV
Pipe: 52 20.2 1.380 PL 8.00 PF 0.7
43 8.0 0.0 24.2 0.0 4.3 120 FTG 13.0 PE 0.0
45 8.0 0.0 23.5 0.0 0.035 TL 21.00 PV
Pipe: 53 21.5 0.824 PL 3.00 PF 8.7
45 8.0 0.0 23.5 0.0 13.0 120 FTG 15.0 PE 0.0
46 8.0 5.6 14.8 21.5 0.483 TL 18.00 PV
Pipe: 54 -1.3 1.380 PL 11.00 PF 0.0
45 8.0 0.0 23.5 0.0 0.3 120 FTG 13.0 PE 0.0
47 8.0 0.0 23.5 0.0 0.000 TL 24.00 PV
Pipe: 55 21.5 0.824 PL 3.00 PF 8.7
47 8.0 0.0 23.5 0.0 13.0 120 FTG 15.0 PE 0.0
48 8.0 5.6 14.8 21.5 0.483 TL 18.00 PV
Pipe: 56 -22.8 1.380 PL 9.00 PF 1.0
47 8.0 0.0 23.5 0.0 4.9 120 FTG 13.0 PE 0.0
49 8.0 0.0 24.4 0.0 0.044 TL 22.00 PV
Pipe: 57 20.1 0.824 PL 5.00 PF 11.5
49 8.0 0.0 24.4 0.0 12.1 120 FTG 22.0 PE 0.0
50 8.0 5.6 12.9 20.1 0.427 TL 27.00 PV
Pipe: 58 19.6 0.824 PL 8.00 PF 12.2
49 8.0 0.0 24.4 0.0 11.8 120 FTG 22.0 FE 0.0
51 8.0 5.6 12.3 19.6 0.406 TL 30.00 PV
Pipe: 59 -39.5 2.067 PL 8.00 PF 0.4
42 8.0 0.0 26.9 0.0 3.8 120 FTG 13.0 PE 0.0
52 8.0 0.0 27.3 0.0 0.017 TL 21.00 PV
Pipe: 60 24.4 0.824 PL 3.00 PF 7.3
53 8.0 0.0 26.3 0.0 14.7 150 FTG 15.0 PE 0.0
54 8.0 5.6 19.0 24.4 0.403 TL 18.00 PV
Pipe: 61 35.6 1.380 PL 18.00 PF 2.5
53 8.0 0.0 26.3 0.0 7.6 150 FTG 20.0 PE 0.0
30 8.0 5.6 23.7 27.3 0.066 TL 38.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8
DATE:' 8/26/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS83\16-323.SDF
JOB TITLE: ARGONAUT CLEAN ROOM - 16 HEAD CALC.
NOTES (HASS)
Calculations were performed by the HASS 8.6 computer program
in accordance with NFPA13 (2016)
under license no. 38071930 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.002 gpm and a maximum
imbalance at any node of 0.091 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 22.1 ft/sec at pipe 10.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
Available pressure at source node 1 under full flow conditions is
119.86 psi compared to the minimum required pressure of 20.00 psi.
PIPE FITTINGS TABLE
Pipe Table Name: FSS.PIP
PAGE: * MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
0.824 0.62 1.54 0.62 1.54 1.85 0.31 3.09 3.09 1.54
1.380 3.00 6.00 2.00 7.00 6.00 1.00 10.00 10.00 6.00
2.635 8.24 16.47 5.49 19.22 9.61 1.37 13.73 13.73 16.47
4.260 13.17 26.33 7.90 28.97 15.80 2.63 26.33 26.33 26.33
6.357 17.60 37.72 11.32 40.23 12.57* 3.77 35.21 35.21 37.72
7.660 43.65 93.53 28.06 99.76 31.18 9.35 87.29 87.29 93.53
8.329 22.16 43.09 16.00 55.40 14.77 4.92 38.16 38.16 43.09
9.050 33.20 64.55 23.98 83.00 22.13 7.38 57.18 57.18 64.55
PAGE: A MATERIAL: SCH40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Ell Tee
1.380 3.00 6.00 2.00 7.00 6.00 1.00 1.00 1.00
2.067 5.00 10.00 3.00 11.00 6.00 1.00 4.00 6.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 DATE:' 8/26/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS83\16-323.SDF
JOB TITLE: ARGONAUT CLEAN ROOM - 16 HEAD CALC.
PAGE: B MATERIAL: THNWL HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
2.635 6.00 12.00 400 14.00 7.00 1.00 0.00 0.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 'DATE:' 8/26/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS83\16-323.SDF JOB TITLE: ARGONAUT CLEAN ROOM - 16 HEAD CALC. 7; ci) U) 1. C,) 0. E Q. c-ia 0. 0t' 0.Q C 00 (a c) 0 00 00 E CO CO LO (dLf) Ii) • - CnC'J Lr) N ELU U) 110 CflC'J (0 0r- (dl)) (I) )) (1) C(fl I-la) 11) -I->lCl) ((JO 0. 0) -H @12 -H 0. CO-H -I-) 00) H CU) -H-H OEId H Q "0 Cl) 0 0. to CI) > (I) H 00. CC. 4J -,I U) 00 I-I .0 0 C) HO) -H • -HID 0' HO) -H ID ' CO U) 0)01 C' • 00) (3'. >,
l)H Ur- 1lH N 0.In0
C.
I II
N
(D 0 0 0 0 0
0 (N 0' W X) 0 0' rH 03 10 (N H
0DC)U) 0U)U)U)(3U) -Q.u)•H---
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 11
DATE: 8/26/2016 C:\PROGRAM FILES\HRS SYSTEMS\HASS83\16-323.SDF
JOB TITLE: ARGONAUT CLEAN ROOM - 16 HEAD CALC.
WATER SUPPLY CURVE
120*0\\\\\\\\\\\\\\\
I \\\\\\\\\\\\\\\\
I \\\\\\\\\\\\\\\\
\\\\\\\\\\\\\\\\ 110+ 109.0 Psi @ 8000 gpm-> *
Flow Test Point
100+
90+
P80+
R I
E
S IX
S 70+
U
R
E
60+
P I
S l•
I 50+
40+
30+
20+ LEGEND
I!
X = Required Water Supply
71.46 Psi @ 625.0 gpm
10+
I 0 = Available Water Supply
119.90 Psi 8 625.0 gpm
0++-+---+----+-----+------+--------+--------+---------+-----------+
16002400 3200 4000 4800 5600 6400 7200 8000
FLOW (GPM)
tJJCJ7 Fire Suppression
& Building Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Email: techserv@tycofp.com
Series RFII - 56 K-factor
"Royal Flush II" Concealed Pendent Sprinklers
Quick & Standard Response, Standard Coverage
General
Description
The Tyco® Series RFll Quick Response
(3-mm bulb) and Standard Response
(5-mm bulb), 5.6 K-Factor, "Royal
Flush II" Concealed Pendent Sprin-
klers are decorative sprinklers featur-
ing a flat cover plate designed to con-
ceal the sprinkler. These sprinklers are
optimal for architecturally sensitive ar-
eas such as hotel lobbies, office build-
ings, churches, and restaurants.
Each sprinkler includes a Cover Plate!
Retainer Assembly and a Sprinkler!
Support Cup Assembly. The separa-
ble, two-piece assembly design pro-
vides the following benefits:
Allows installation of the sprinklers
and pressure testing of the fire pro-
tection system prior to installation
of a suspended ceiling or applica-
tion of the finish coating to a fixed
ceiling.
Permits the removal of suspended
ceiling panels for access to building
service equipment without having
to first shut down the fire protection
system and remove sprinklers.
Provides for 1/2 inch (12,7 mm) of
vertical adjustment to allow a mea-
sure of flexibility in determining the
length of fixed piping to cut for the
sprinkler drops.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fall to
operate in a fire situation or cause it
to operate prematurely.
The Series RFII Sprinklers are shipped
with a Disposable Protective Cap. The
Protective Cap is temporarily removed
during installation and replaced to help
protect the sprinkler during ceiling in-
stallation or finish. The tip of the Pro-
tective Cap can be used to mark the
center of the ceiling hole into plaster
board or ceiling tiles by gently push-
ing the ceiling product against the Pro-
tective Cap. When ceiling installation
is complete, the Protective Cap is re-
moved and the Cover Plate/Retainer
Assembly is installed.
As an option, the Series RFll Standard
Response (5-mm bulb) "Royal Flush II"
Concealed Pendent Sprinklers can be
fitted with a silicone Air and Dust Seal.
(Refer to Figure 5.) The Air and Dust
Seal is intended for sensitive areas
where it is desirable to prevent air and
dust from the area above the ceiling to
pass through the cover plate.
The Series RFlI Concealed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document and with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Sprinkler
Identification
Number (SIN)
TY3531 - 3 mm bulb
TY3551 - 5 mm bulb
Page 1 of 6 OCTOBER 2009 TFPI8I
TFPI8I
Page 2 of 6
Technical
Data
Sprinkler Approvals
Approvals apply only to the service
conditions indicated in the Design Cri-
teria section.
1/2' NPT SEALING
ASSEMBLY
FRAME
CAP
SUPPORT
CUP WITH BULB
ROLL FORMED
THREADS
- COMPRESSION
SCREW
GUIDE
PINS (2)
DEFLECTOR
DEFLECTOR POSITION)
SPRINKLER/SUPPORT CUP
ASSEMBLY
THREAD INTO 14 RETAINER
SUPPORT CUP WITH THREAD
UNTIL MOUNTING 0 DIMPLES
SURFACE IS
FLUSH WITH EJECTION
CEILING
'- I
SPRING
SOLDER J
.
COVER
TABS (3) COVER PLATE/RETAINER PLATE ASSEMBLY
FIGURE 1
MODEL RFII CONCEALED SPRINKLER
ASSEMBLY
TY3531 (3-mm Bulb) is UL Listed,
C-UL Listed, LPCB Approved (Ref.
No. 094a/10), VdS Approved (Cer-
tificate No. G 4090007), and NYC
Approved (MEA 353-01-E) as Quick
Response.
1Y3531 (3-mm Bulb) is FM Ap-
proved as Standard Response.
Factory Mutual does not approve
any concealed sprinklers for quick
response.
TY3551 (5-mm Bulb) is UL Listed,
C-UL Listed, FM Approved, LPCB
Approved (Ref. No. 094a/9), and
NYC Approved (MEA 353-01-E) as
Standard Response.
Approvals for Air and Dust Seal
UL and C-UL Listed for use with the
RFll Standard Response Concealed
Sprinkler (TY3551).
Maximum Working Pressure
Maximum 250 psi (17,3 bar) by UL,
C-UL, and NYC
Maximum 175 psi (12,1 bar) by FM,
VdS, and LPCB
Temperature Rating
155°F/68°C Sprinkler with
1 39°F/59°C Plate
200°F/93°C Sprinkler with
1 65°F/74°C Plate
Discharge Coefficient
K= 5.6 GPM/psi112 (80,6 LPM/barl'2)
Adjustment
1/2 inch (12,7 mm)
Finishes
See the Ordering Procedure section.
Physical Characteristics
Frame ...................Bronze
Support Cup... Chrome Plated Steel
Guide Pins .........Stainless Steel
Deflector.................Bronze
Compression Screw.........Brass
Bulb ......................Glass
Cap.............Bronze or Copper
Sealing Assembly.........Beryllium
Nickel w/ Teflont
Cover Plate................Brass
Retainer ..................Brass
Ejection Spring......Stainless Steel
tDuPont Registered Trademark
Design
Criteria
The Tyco® Series RFlI Concealed Pen-
dent Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard instal-
lation rules recognized by the appli-
cable Listing or Approval agency; for
example, UL Listing is based on NFPA
13 and VdS Approval is based on the
CEA 4001.
For more information on LPCB and
VdS Approvals, contact Tyco Fire Sup-
pression & Building Products at the
following office:
Enschede, Netherlands
Telephone: 31-53-428-4444
Fax: 31-53-428-3377
The Series RFll Concealed Pendent
Sprinklers are only listed and approved
with the Series RFII Concealed Cover
Plates having a factory applied finish.
Do not use the Series RFII in applica-
tions where the air pressure above the
ceiling is greater than that below. Down
drafts through the Sprinkler/Support
Cup Assembly can delay sprinkler op-
eration in a fire situation.
FACE OF
SPRINKLER
FITTING
SPRINKLER
SUPPORT CUP
ASSEMBLY
1/2k (12,7 mm)
THREADED
D ADJUSTMENT
FACE OF CEILING,
RETAINING RING
MOUNTING
SURFACE
CLEARANCE HOLE
- DIAMETER
DIMENSION
TmdTT /-
CLEARANCE
HOLE
TFPI8I
Page 3 of 6
Operation
When exposed to heat from a fire, the
Cover Plate, normally soldered to the
Retainer at three points, falls away to
expose the Sprinkler/Support Cup
Assembly.
The Deflector—supported by the
Guide Pins—then drops down to its
operational position.
The glass Bulb contains a fluid that ex-
pands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, activating the sprinkler and
allowing water to flow.
I I I V
MANUFACTURER DEFLECTOR COVER PLATE
PRESET GAP IN DROPPED RETAINER
3/32 (2,4 mm) POSITION ASSEMBLY
COVER PLATE
DIAMETER
DIMENSION A
3-1/4 inches (82,6 mm) C: 2-3/8 to 2-5/8 inches (60,3 to 66,7 mm)
3/16 inches (4,8 mm) D: 1-3/4 to 2-1/4 inches (44,5 to 57,2 mm)
FIGURE 2
SERIES CONCEALED SPRINKLER INSTALLATION DIMENSIONS
3/16to11/16
(4,8 to 17,5 mm)
REFERENCE
COVER PLATE
PROFILE DEPTH
DIMENSION B
FIGURE 4
DISPOSABLE PROTECTIVE CAP
TFPISI
Page 4 of 6
Installation
The Tyco® Series RFII must be in-
stalled in accordance with the follow-
ing instructions.
A(I)IfP
Do not install any bulb-type sprinkler if
the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bub-
ble should be present. The diameter
of the air bubble is approximately 1/16
inch (1,6 mm) for the 1550F/680C and
3/32 inch (2,4 mm) for the 200°F/930C
temperature ratings.
Obtain a 1/2 inch NPT sprinkler joint
by applying a minimum to maximum
torque of 7 to 14 ft-lbs. (9,5 to 19,0
Nm). Higher levels of torque can dis-
tort the sprinkler Inlet with consequent
leakage or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Sprinkler
by under- or over-tightening the Sprin-
kler/Support Cup Assembly. Re-adjust
the position of the sprinkler fitting to
suit.
Step 1. Install the sprinkler only in the
pendent position with the center-line
of the sprinkler perpendicular to the
mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, hand-tighten
the sprinkler into the sprinkler fitting.
Step 4. Wrench-tighten the sprinkler
using only the RFII Sprinkler Wrench.
(Refer to Figure 3.) Apply the RFll
Sprinkler Wrench to the Sprinkler as
shown in Figure 3.
Step 5. Replace the Protective Cap
by pushing it upwards until it bottoms
out against the Support Cup. (Refer
to Figure 4.) The Protective Cap helps
prevent damage to the Deflector and
Arms during ceiling installation and/or
finish. You can also use the Protective
Cap to locate the center of the clear-
ance hole by gently pushing the ceiling
material up against the center point of
the Protective Cap.
As long as the Protective Cap remains
in place, the system is considered
"Out of Service".
Step 6. After the ceiling has been com-
pleted with the 2-1/2 inch (63,5 mm)
diameter clearance hole and in prepa-
ration for installing the Cover Plate/Re-
tainer Assembly, remove and discard
the Protective Cap. Verify that the De-
flector moves up and down freely.
If the Sprinkler is damaged and the
Deflector does not move up and down
freely, replace the entire Sprinkler.
Do not attempt to modify or repair a
damaged sprinkler.
Step 7. When installing an Air and Dust
Seal, refer to Figure 5; otherwise, pro-
ceed to Step 8. To attach the Air and
Dust Seal, verify the angle of the out-
side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
the Retainer in the grooved slot of the
Air and Dust Seal and continue around
the retainer until the entire Air and Dust
Seal is engaged.
Step 8. Screw on the Cover Plate/
Retainer Assembly until the Retainer
(shown in Figure 2) or the Air and Dust
Seal (shown in Figure 5) contacts the
ceiling. Do not continue to screw on
the Cover Plate/Retainer Assembly
so that it lifts a ceiling panel out of its
normal position. If you cannot engage
the Cover Plate/Retainer Assembly
with the Support Cup or you cannot
engage the Cover Plate/Retainer As-
sembly sufficiently to contact the ceil-
ing, you must reposition the Sprinkler
Fitting.
Care and
Maintenance
The Tyco® Series RFll must be
maintained and serviced in accordance
with the following instructions.
Before closing a fire protection sys-
tem main control valve for maintenance
work on the fire protection system that
it controls, obtain permission to shut
down the affected fire protection sys-
tem from the proper authorities and no-
tify all personnel who may be affected
by this action.
Absence of the Cover Plate/Retainer
Assembly can delay sprinkler opera-
tion in a fire situation.
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap be-
tween the lip of the Cover Plate and the
ceiling, as shown in Figure 2.
This air gap is necessary for proper
operation of the sprinkler. If the ceil-
ing requires repainting after sprinkler
installation, ensure that the new paint
does not seal off any of the air gap.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Replace sprinklers that:
are leaking or exhibiting visible signs
of corrosion.
were modified or over-heated.
Never paint, plate, coat, or otherwise
alter automatic sprinklers after they
leave the factory. Never repaint facto-
ry-painted Cover Plates. If necessary,
replace them with factory-painted
units. Non-factory applied paint can
adversely delay or prevent sprinkler
operation in the event of a fire.
Exercise care to avoid damage to
sprinklers before, during, and after in-
stallation. Replace sprinklers damaged
by dropping, striking, wrench twisting,
wrench slipping, or the like. Also, re-
place any sprinkler that has a cracked
bulb or that has lost liquid from its
bulb. (Refer to the Installation section.)
If you must remove a sprinkler, do not
reinstall it or a replacement without re-
installing the Cover Plate/Retainer As-
sembly. If a Cover Plate/Retainer As-
sembly becomes dislodged during
service, replace it immediately.
Responsibility lies with sprinkler own-
ers for the inspection, testing, and
maintenance of their fire protection
system and devices in compliance with
this document, as well as with the ap-
plicable standards of the National Fire
Protection Association (for example,
NFPA 25), in addition to the standards
of any other authorities having jurisdic-
tion. Contact the installing contractor
or sprinkler manufacturer regarding
any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national code.
SUPPORT SPRINKLER FACE OF ORIENT
CUP CEILING SEAL
BEVEL AS
SHOWN COVER
PLATE
RETAINER
ASSEMBLY
CLEAN
ROOM
LIP OF COVER SEAL
RETAINER PLATE
FIGURE 5
OPTIONAL AIR AND DUST SEAL FOR SERIES RFII (TY3551)
TFPI8I
Page 5 of 6
Limited
Warranty
Products manufactured by Tyco Fire
Suppression & Building Products
(TFSBP) are warranted solely to the
original Buyer for ten (10) years against
defects in material and workmanship
when paid for and properly installed
and maintained under normal use and
service. This warranty will expire ten
(10) years from date of shipment by
TFSBR No warranty is given for prod-
ucts or components manufactured by
companies not affiliated by ownership
with TFSBP or for products and com-
ponents which have been subject to
misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by TFSBP to be defective
shall be either repaired or replaced, at
TFSBP's sole option. TFSBP neither
assumes, nor authorizes any person
to assume for it, any other obligation
in connection with the sale of prod-
ucts or parts of products. TFSBP shall
not be responsible for sprinkler system
design errors or inaccurate or incom-
plete information supplied by Buyer or
Buyer's representatives.
In no event shall TFSBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFSBP
was informed about the possibility of
such damages, and in no event shall
TFSBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
Contact your local distributor for
availability. When placing an order,
indicate the full product name.
Sprinkler/Support Cup Assembly
Specify: (SIN), (temperature rating
from below) Series RFll Concealed
Pendent Sprinkler, P/N (specify).
155FI68°C 2OOF/93°C
TY3531 51-792-1-155 51-792-1-200
1Y3551 51-790-1-155 51-790-1-200
Separately Ordered Cover Plate/
Retainer Assembly:
Specify: (temperature rating from be-
low) Series RFll Concealed Cover Plate
with (finish), P/N (specify).
139F/59°C(a) 165°F/74°C(b)
Brass..........56-792-1-135 56-792-1-165
Chrome........56-792-9-135 56-792-9-165
Signal White
(RAL 9003).... 56-792-4-135 56-792-4-165
Grey White
(RAL 9002).... 56-792-0-135 56-792-0-165
Pure White (c)
(RAL 9010).... 56-792-3-135 56-792-3-165
Custom ........56-792-X-135 56-792-X-165
For use with 155°F/68°C sprinklers.
For use with 200°F/93°C sprinklers.
Eastern Hemisphere sales only.
Sprinkler Wrench
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075.
Air and Dust Seal
Specify: Air and Dust Seal,
P/N 56-908-1-001.
tqco
Ffre Protection
Products
Worldwide I Contacts www.tyco-fire.com
Series DS-1 - 56 K-factor, Dry-type Sprinklers
Pendent, Upright, and Horizontal Sidewall
Standard Response, Standard Coverage
General
Description
TYCO Series DS-1 5.6K Pendent,
Upright, and Horizontal Sidewall, Stan-
dard Response (5 mm bulb), Standard
Coverage Dry-type Sprinklers are dec-
orative glass bulb automatic sprinklers
typically used where:
pendent sprinklers are required on
dry pipe systems that are exposed
to freezing temperatures (e.g., sprin-
kler drops from unheated portions of
buildings)
sprinklers and/or a portion of the
connecting piping may be exposed
to freezing temperatures (e.g., sprin-
kler drops from wet systems into
freezers, sprinkler sprigs from wet
systems into unheated attics, or hor-
izontal piping extensions through a
wall to protect unheated areas of a
building such as loading docks, over-
hangs, and building exteriors)
sprinklers are used on systems that
are seasonably drained to avoid
freezing (e.g., vacation resort areas)
NOTICE
Series DS-1 Dry-type Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association (NFPA), in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Series DS-1 Dry-type Sprinklers must
only be installed in fittings that meet
the requirements of the Design Crite-
ria section.
Sprinkler
Identification
Numbers (SINs)
TY3255 - Pendent
TY3155 - Upright
TY3355 - Horizontal Sidewall
Technical
Data
Approvals
UL and C-UL Listed FM Approved
VdS Approved
TY3255 w/Standard Escutcheon only NYC Approved
under MEA 352-01-E LPCB Approved Reference No. 094a/11
CE Certified Certificate of Conformity No. 0832- CPD-201 5
(Refer to Tables A and B for details.)
Maximum Working Pressure 175 psi (12,1 bar)
Inlet Thread Connections 1 inch NPT
ISO 7-R 1
Discharge Coefficient K=5.6 gpm/psi112 (80,6 1pm/barl'2)
Temperature Ratings Refer to Tables A and B.
Finishes Sprinkler: Refer to Table D. Escutcheon: Refer to Table D.
JANUARY 2015
-
Physical Characteristics
Inlet.........................Copper
Plug ........................Copper
Yoke ..................Stainless Steel
Casing ........Galvanized Carbon Steel
Insert .......................Bronze
Bulb Seat ..............Stainless Steel
Bulb (5 mm dia.) ................Glass
Compression Screw............Bronze
Deflector.....................Bronze
Frame .......................Bronze
Guide Tube.............Stainless Steel
Water Tube.............Stainless Steel
Spring.................Stainless Steel
Sealing Assembly.......Beryllium Nickel
w/TEFLON
Escutcheon .............Carbon Steel
TFP500
TFP500
Page 2 of 10
SPRINKLER
TYPE
ESCUTCHEON
TYPE
TEMPERATURE
RATING
BULB
COLOR CODE
SPRINKLER FINISH
NATURAL
BRASS
CHROME
PLATED V P0 * L
PENDENT
(TY3255)
STANDARD
135°F (57°C) Orange
1,2,3,4,5,6 1
'
2 4 5 6
155°F (68°C) Red
175-F (79-C) Yellow
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve 1, 2, 3, 6 1, 2, 6
RECESSED
135°F (57°C) Orange
1,2,3,5 1,2,5
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue 1,2
360°F (182°C) Mauve N/A
DEEP
135°F (57°C) Orange
1, 2,3,4,5 1,2,4, 5
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve
WITHOUT
135°F(57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve 1,2, 3 1,2
UPRIGHT
(TY3155) WITHOUT
_
135°F (57°C) Orange
1, 2, 3, 4, 5 1, 2, 4, 5
155°F (68°C) Red
175°F (79°C) Yellow
200°F (93°C) Green
286°F (141°C) Blue
360°F(182°C) Mau,e 1,2,3 1,2
Notes:
Listed by Underwriters Laboratories, Inc. (UL), maximum order length of 48 inches
Listed by Underwriters Laboratories for use in Canada (C-UL), maximum order length of 48 inches
Approved by FM Global (FM Approvals), maximum order length of 48 inches
Loss Prevention Certification Board (LPCB) and CE conformity apply to these temperature ratings only
Approved by the City of New York under MEA 352-01-E
Approved by VdS
* Frame and deflector only
N/A - Not Applicable
TABLE A
SERIES DS-1 PENDENT & UPRIGHT DRY-TYPE SPRINKLERS, 5,6K, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
TFP500
Page 3 of 10
SPRINKLER ESCUTCHEON TEMPERATURE BULB SPRINKLER FINISH
NATURAL
BRASS
CHROME
PLATED POLYESTER'
TYPE TYPE RATING COLOR CODE
135°F (57°C) Orange
155-F (68-C) Red
175°F (79°C) Yellow STANDARD
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve
135°F (57°C) Orange
155°F(68°C) Red
HSW*
(TY3355) DEEP 175°F (79°C) Yellow 3*** 4, 5 1**, 2**, 4 5
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve
135°F (57°C) Orange
155°F (68°C) Red
175°F (79°C) Yellow
WITHOUT
200°F (93°C) Green
286°F (141°C) Blue
360°F (182°C) Mauve 2°, 5 1°°, 2°°
Notes:
Listed by Underwriters Laboratories. Inc. (UL), maximum order length 0148 inches
Listed by Underwriters Laboratories for use in Canada (C-UL), maximum order length of 48 inches
Approved by FM Global (FM Approvals), maximum order length of 48 inches
Loss Prevention Certification Board (LPCB) and CE conformity apply to these temperature ratings only
Approved by the City of New York under MEA 352-01-E * Horizontal sidewall with top of deflector-to-ceiling distance of 410 12 inches (100 to 300 mm)
Light and ordinary hazard occupancies only
Light hazard occupancies only
Frame and deflector only
TABLE B
SERIES DS-1 HORIZONTAL SIDEWALL (HSW) DRY-TYPE SPRINKLER, 5.6K, STANDARD RESPONSE
LABORATORY LISTINGS AND APPROVALS
PLUG WITH INLET
SEALING
ASSEMBLY
YOKE H -.-.... SPRING INLET
BAND
WATER
II ii
TUBE CASING
GUIDE - INSERT
TUBE
BULB
FRAME —*'/ SEAT
.- 5 mm BULB VENT HOLE
COMPRESSION
DEFLECTOR SCREW
FIGURE 1
SERIES DS-1 DRY-TYPE SPRINKLER, 5.6K, STANDARD RESPONSE
ASSEMBLY
WRENCH
RECESS
WRENCH I FLAT
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 2
W-TYPE 7
WRENCH
TFP500
Page 4 of 10
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER
FITTING
ORDER LENGTHS:
2-3/4 to 48" 1-3/4 DIA. (69,9 to 1219,2 mm) (44,5 mm) IN 1/4" (6,4 mm)
INCREMENTS I I I
FACOF[_I
CEILING
2-3/16' ± 1/8 3' DIA.
(55,6 ± 3,2 mm) (76,2 mm)
FIGURE 3
PENDENT (TY3255)
WITH STANDARD ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER
FITTING
ORDER LENGTHS:
3-3/4" to 48"
(95,3 to 1219,2 mm)
IN 1/4" (6,4 mm) 2-1/4" DIA.
INCREMENTS (57,2 mm)
FACE OF
CEILING
FIGURE 4
PENDENT (TY3255)
WITH STANDARD
RECESSED ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER
FITTING
ORDER LENGTHS: 3-1/2" DIA.
1/2" to 46" h(88,9 mm) -
(12,7 to 1168,4 mm) I
IN 1/4" (6,4 mm) 2-1/2" DIA.
INCREMENTS I (635 mm)
FACE
CEILING
4-1/4" ±1/8"
(108,0 ± 3,2 mm)
FIGURE 5
PENDENT (TY3255)
WITH DEEP ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER
FITTING
ORDER LENGTHS:
5' to 48"
(127,0 to 1219,2 mm)
IN 1/4" (6,4 mm)
INCREMENTS
MINIMUM
1-3/4" (44,5 mm)
DEFLECTOR
TO CEILING
FIGURE 6
PENDENT (TY3255)
WITHOUT ESCUTCHEON
TOP OF
DEFLECTOR
ORDER LENGTHS:
5' to 48"
(127,0 to 1219,2 mm)
IN 1/4" (6,4 mm)
INCREMENTS
FACE OF
SPRINKLER
FITTING -
\
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FIGURE 7
UPRIGHT (TY3155)
WITHOUT ESCUTCHEON
TFP500
Page 5 of 10
ORDER LENGTHS:
2-3/4 to 48° (69,9 to 1219,2 mm)
IN 1/4(6,4 mm) INCREMENTS 2-3/8' ± 1/8"
(60,3±3,2 mm)
FACE OF FACE OF
SPRINKLER MOUNTING
FITTING SURFACE mAi
_ Ti4 3"DIA.
(76,2 mm)
3.5° 1-3/4° DIA. SPRINKLER FITTING
(REFER TO DESIGN (44,5 mm) CENTERLINE 5/16'
CRITERIA SECTION) OF WATERWAY (7,9 mm)
FIGURE 8
HORIZONTAL SIDEWALL (TY3355)
WITH STANDARD ESCUTCHEON
ORDER LENGTHS:
1/2° to 45-3/4" (12,7 to 1162,1 mm)
IN 1/4(6,4 mm) INCREMENTS 4-1/4" ± 1/8"
L 2-1/2" DIA. FACE OF (108,0 ± 3,2 mm)
FACE OF
(63,5 mm) MOUNTING
SPRINKLER
FITTING
SURFACE
FIGURE 9
HORIZONTAL SIDEWALL (TY3355)
WITH DEEP ESCUTCHEON
ORDER LENGTHS:
5-1/2' to 48' (139,7 to 1219,2 mm)
IN 1/4" (6,4 mm) INCREMENTS MINIMUM
2-1/4' (57,2 mm)
FACE OF 1 - DEFLECTOR To
- SPRINKLER I MOUNTING
FITTING SURFACE
EIIIIIIIiIIIIIIIIIIIIIIIIII1I 3.5*I
5/16" / SPRINKLER FITTING (7,9 mm)
(REFER TO DESIGN CENTERLINE
CRITERIA SECTION) OF WATERWAY
FIGURE 10
HORIZONTAL SIDEWALL (TY3355)
WITHOUT ESCUTCHEON
Operation
When TYCO Series DS-1 5.6K Pendent,
Upright, and Horizontal Sidewall, Stan-
dard Response, Standard Coverage
Dry-type Sprinklers are in service,
water is prevented from entering the
assembly by the Plug with Sealing
Assembly (Ref. Figure 1) in the Inlet of
the sprinkler.
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter
the glass bulb, and the Bulb Seat is
released.
The compressed Spring is then able
to expand and push the Water Tube as
well as the Guide Tube outward. This
action simultaneously pulls inward on
the Yoke, withdrawing the Plug with
Sealing Assembly from the Inlet, allow-
ing the sprinkler to activate and flow
water.
Design
Criteria
TYCO Series DS-1 5.6K Pendent,
Upright, and Horizontal Sidewall, Stan-
dard Response, Standard Coverage
Dry-type Sprinklers are intended for
use in fire sprinkler systems designed
in accordance with the standard instal-
lation rules recognized by the applica-
ble listing or approval agency (e.g., UL
Listing is based on NFPA 13 require-
ments). For more information on LPCB
Approval, contact Tyco Fire Suppres-
sion & Building Products at the follow-
ing office:
Kopersteden 1
7547 TJ Enschede
The Netherlands
Tel: +31-(0)53-428-4444
Fax: +31-(0)53-428-3377
Sprinkler Fittings
Install 1 inch NPT Series DS-1 Dry-type
Sprinklers in the 1 inch NPT outlet or
run of the following fittings:
malleable or ductile iron threaded
tee fittings that meet the dimen-
sional requirements of ANSI B16.3
(Class 150)
cast iron threaded tee fittings that
meet the dimensional requirements
of ANSI B16.4 (Class 125)
Do not install Series DS-1 Dry-type
Sprinklers into elbow fittings. The Inlet
of the sprinkler can contact the interior
of the elbow.
The unused outlet of the threaded tee is
plugged as shown in Figure 12.
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
3-1/2° DIA.
T (88,9 mm)
- / 3.5°
CENTERLINE 5/16°
OF WATERWAY (7,9 mm)
TFP500
Page 6 of 10
Temperatures for Heated Area(1)
Ambient Temperature 4°F 50°F 60°F
Exposed to (4 C) (10-C) (16-C)
Discharge End of Sprinkler Minimum Exposed Barrel Length(2), Inches
(mm)
40°F
(4°C) 0 0 0
30°F
(-1°C) 0 0 0
20°F 40 0 (-7°C) (100)
10°F 8 1 0 (-12°C) (200) (25)
0°F 12 30 (-18°C) (305) (75)
-10°F 14 4 1
(-23°C) (355) (100) (25)
-20°F 14 6 3
(-29°C) (355) (150) (75)
-30°F 16 8 4
(-34°C) (405) (200) (100)
-40°F 18 8 4
(-40°C) (455) (200) (100)
-50°F 20 10 6
(-46°C) (510) (255) (150)
-60°F 20 10 6
(-51°C) (510) (255) (150)
Notes:
For protected area temperatures that occur between values listed above, use the next cooler temperature.
These lengths are inclusive of wind velocities up to 30 mph (18,6 kph).
TABLE C
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS
MINIMUM RECOMMENDED LENGTHS
You can also install Series DS-1 Dry-
type Sprinklers in the 1 inch NPT outlet
of a GRINNELL Figure 730 Mechanical
Tee and GRINNELL G-FIRE Figure 522;
however, the use of the Figure 730 Tee
and Figure 522 for this arrangement is
limited to wet pipe systems.
The configuration shown in Figure 13
is only applicable for wet pipe systems
where the sprinkler fitting and water-
filled pipe above the sprinkler fitting are
not subject to freezing and where the
length of the dry-type sprinkler has the
minimum exposure length depicted in
Figure 11. Refer to the Exposure Length
section.
For wet pipe system installations of 1
inch NPT Series DS-1 Dry-Type Sprin-
klers connected to CPVC piping, use
only the following TYCO CPVC fittings:
1" x 1" NPT Female Adapter (P/N
80145)
1" x 1" x 1" NPT Sprinkler Head
Adapter Tee (P/N 80249)
For dry pipe system installations, use
only the side outlet of maximum 2-1/2
inch reducing tee when locating Series
DS-1 Dry-type Sprinklers directly
below the branchline; otherwise, use
the configuration shown in Figure 12 to
assure complete water drainage from
above Series DS-1 Dry-type Sprin-
klers and the branchline. Failure to do
so may result in pipe freezing and water
damage.
NOTICE
Do not install Series DS-1 Dry-type
Sprinklers into any other type fitting
without first consulting the Tyco Fire
Protection Products (TFPP) Technical
Services. Failure to use the appropriate
fitting may result in one of the following:
failure of the sprinkler to operate
properly due to formation of ice
over the Inlet Plug or binding of the
Inlet Plug
insufficient engagement of the
Inlet pipe-threads with consequent
leakage
Drainage
In accordance with the minimum
requirements of the National Fire Pro-
tection Association for dry pipe sprin-
kler systems, branch, cross, and
feed-main piping connected to Dry
Sprinklers and subject to freezing tem-
peratures must be pitched for proper
drainage.
Exposure Length
When using Dry Sprinklers in wet pipe
sprinkler systems to protect areas
subject to freezing temperatures, use
Table C to determine a sprinkler's
appropriate exposed barrel length to
prevent water from freezing in the con-
necting pipes due to conduction. The
exposed barrel length measurement
must be taken from the face of the
sprinkler fitting to the surface of the
structure or insulation that is exposed
to the heated area. Refer to Figure 11
for an example.
For protected area temperatures
between those given above, the
minimum recommended length from
the face of the fitting to the outside of
the protected area may be determined
by interpolating between the indicated
values.
Clearance Space
In accordance with Section 8.4.9.2 of
the 2010 edition of NFPA 13, when con-
necting an area subject to freezing and
an area containing a wet pipe sprinkler
system, the clearance space around
the sprinkler barrel of dry-type sprin-
klers must be sealed. Due to tempera-
ture differences between two areas, the
potential for the formation of conden-
sation in the sprinkler and subsequent
ice build-up is increased. If this con-
densation is not controlled, ice build-up
can occur that might damage the dry-
type sprinkler and/or prevent proper
operation in a fire situation.
Use of the Model DSB-2 Dry Sprinkler
Boot, described in technical data sheet
TFP591 and shown in Figures 14 and
15, can provide the recommended seal.
TFP500
Page 7 of 10
FACE OF -
SPRINKLER -a -
FITTING
Ir EXPOSURE
LENGTH
(SEE DESIGN
DSB-2 CRITERIA
INTENDED SECTION)
FOR FREEZER
STRUCTURES
FIGURE 11
EXPOSURE LENGTH
T-
RUN
OUTLET
PLUGGED
TO DRY
SPRINKLER
FI1TING
SYSTEM (SEE DESIGN
CRITERIA
SECTION)
DSB-2
FOR FREEZER
INTENDED
STRUCTURES
zz
—c
ICJ
FIGURE 12
SPRINKLER FITTING
UNHEATED AREA
TO WET SIDE
SYSTEM OUTLET
PLUGGED
DSB-2 SPRINKLER
INTENDED FITTING
FOR FREEZER (SEE DESIGN
STRUCTURES CRITERIA
SECTION)
7
-4--
]cj
FIGURE 13
SPRINKLER FITTING
HEATED AREA
STRAP TIES
(ENDS ON
OPPOSING
SIDES OF
BOOT)
DSB-2 BOOT
ADHESIVE
1-3/4" DIA.
(44,5 mm)
CLEARANCE
HOLE
INSULATED
FREEZER
STRUCTURE
t1J DS-1
SHOWN WITH
STANDARD
ESCUTCHEON
FIGURE 14
MODEL DSB-2 DRY SPRINKLER
BOOT WITH PENDENT SERIES
DS-1 DRY-TYPE SPRINKLER
1-3/4' DIA.
(44,5 mm)
CLEARANCE INSULATED HOLE FREEZER
ADHESIVE
D\
STRUCTURE
SB-2
BOOT
STRAP TIES DS-1 (ENDS ON SHOWN WITH OPPOSING STANDARD SIDES OF ESCUTCHEON BOOT)
FIGURE 15
MODEL DSB-2 DRY SPRINKLER
BOOT WITH SIDEWALL SERIES
DS-1 DRY-TYPE SPRINKLER
TFP500
Page 8 of 10
Installation
TYCO Series DS-1 5.6K Pendent,
Upright, and Horizontal Sidewall, Stan-
dard Response, Standard Coverage
Dry-type Sprinklers must be installed
in accordance with this section.
General Instructions
Series DS-1 Dry-type Sprinklers must
only be installed in fittings that meet
the requirements of the Design Crite-
ria section. Refer to the Design Criteria
section for other important require-
ments regarding piping design and
sealing of the clearance space around
the Sprinkler Casing.
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) rating to
1/8 inch (3,2 mm) for the 360°F (182°C)
rating.
Obtain a leak-tight 1 inch NPT sprinkler
joint by applying a minimum-to-maxi-
mum torque of 20 to 30 lbs.-ft. (26,8 to
40,2 Nm). Higher levels of torque may
distort the sprinkler Inlet with conse-
quent leakage or impairment of the
sprinkler.
Do not attempt to compensate for
insufficient adjustment in an Escutch-
eon Plate by under or over-tightening
the Sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Notes:
Install pendent sprinklers only in
the pendent position; install upright
sprinklers only in the upright posi-
tion. The deflector of a pendent or
upright sprinkler is to be parallel to
the ceiling.
install horizontal sidewall sprinklers
in the horizontal position with their
centerline of waterway perpendicu-
lar to the back wall and parallel to
the ceiling. Ensure the word "TOP"
on the Deflector faces the ceiling.
Step 1. With a non-hardening pipe-
thread sealant such as TEFLON applied
to the inlet threads, hand-tighten the
sprinkler into the sprinkler fitting.
Step 2. Wrench-tighten the sprinkler
using either:
a pipe wrench on the Inlet Band or
the Casing (Ref. Figure 1)
the W-Type 7 Sprinkler Wrench on
the Wrench Flat (Ref. Figure 2)
Apply the wrench recess of the W-Type
7 Sprinkler Wrench to the wrench flat.
Note: If sprinkler removal becomes
necessary, remove the sprinkler using
the same wrenching method noted
above. Sprinkler removal is easier when
a non-hardening sealant was used
and torque guidelines were followed.
After removal, inspect the sprinkler for
damage.
Step 3. After installing the ceiling or
wall and applying a ceiling finish, slide
on the outer piece of the escutch-
eon until it comes in contact with the
ceiling/wall. Do not lift the ceiling panel
out of its normal position.
When using the Deep Escutcheon,
hold the outer piece in contact with the
mounting surface (ceiling or wall). Then
rotate the inner piece approximately 1/4
turn with respect to the outer piece,
to hold the Deep Escutcheon firmly
together.
Care and
Maintenance
TYCO Series DS-1 5.6K Pendent,
Upright, and Horizontal Sidewall,
Standard Response, Standard Cover-
age Dry-type Sprinklers must be main-
tained and serviced in accordance with
this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover a
clearance hole, may delay the time to
sprinkler operation in a fire situation.
A Vent Hole is provided in the Bulb
Seat (Ref. Figure 1) to indicate if the Dry
Sprinkler is remaining dry. Evidence of
leakage from the Vent Hole indicates
potential leakage past the Inlet seal
and the need to remove the sprinkler
to determine the cause of leakage;
for example, an improper installation
or an ice plug. Close the fire protec-
tion system control valve and drain the
system before removing the sprinkler.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb (Ref. Installa-
tion section).
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
TFP500
Page 9 of 10
12
PIN* 60
- XXX
I
- X - XXX
I
SIN SPRINKLER ESCUTCHEON
FINISH FINISH(1)
96 Pendent with TY3255 CHROME SIGNAL WHITE Standard Escutcheon (1" NPT) (Figure 3) 0 PLATED (RAL9003)
POLYESTER
93 Pendent with TY3255
Deep Escutcheon (1" NPT) (Figure 5) NATURAL SIGNAL WHITE
-
97 Pendent with 1 TY3255 BRASS (RAL9003)
POLYESTER Recessed Escutcheon (1° NPT) (Figure 4) -
92 Pendent without TY3255 2 NATURAL BRASS Escutcheon (1 NPT) (Figure 6) BRASS PLATED
Sidewall with TY3355 94 Standard Escutcheon (1" NPT) (Figure 8)
53 Sidewall with TY3355
-
Deep Escutcheon (1" NPT) (Figure 9)
54 Sidewall without TY3355
Escutcheon (1' NPT) (Figure 10)
98 Upright without TY3155 I
I I Escutcheon (1° NPT) I (Figure 7)
Notes:
Escutcheon Finish applies to sprinklers provided with escutcheons.
360"F (182"C) temperature rating applies to non-recessed sprinkler
assemblies.
Dry-type Sprinklers are furnished based upon "Order Length" as mea-
sured per Figures 3 through 10, as applicable, and for each individual
sprinkler where it is to be installed. After the measurement is taken,
round it to the nearest 1/4 inch increment.
* Use Prefix "I" for ISO 7-R1 connection (e.g., -60-961-1-180).
SIGNAL WHITE
4 (RAL9003)
POLYESTER
CHROME
PLATED
TEMPERATURE
RATING(2)
0 135°F (57°C)
1 155°F(68°C)
2 175-F (79-C)
3 200°F (93°C)
4 286-F (141-C)
5 360-F (182-C)
SIGNAL WHITE
(RAL9003)
POLYESTER
CHROME
PLATED
ORDER
LENGTH(3)
055 5.50"
082 8.25"
180 18.00"
187 18.75"
372 37.25"
480 48.00"
TABLED
SERIES DS-1 DRY-TYPE SPRINKLERS, 5.6K, STANDARD RESPONSE
PART NUMBER SELECTION
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indi-
cate the full product name, including
description and part number (P/N).
Dry-type Sprinklers
When ordering Series DS-1 5.6K
Pendent, Upright, and Horizontal Side-
wall, Standard Response, Standard
Coverage Dry-type Sprinklers, specify
the following information:
SIN:
TY3255 - Pendent
1V3155 - Upright
TY3355 - Horizontal Sidewall
Order Length:
Dry-type Sprinklers are furnished
based upon Order Length as mea-
sured per Figures 3 through 10, as
applicable. After the measurement is
taken, round it to the nearest 1/4 inch
increment.
Inlet Connections:
1 Inch NPT
(Standard)
ISO 7-R 1
(For information on ISO Inlet Thread
Connections, contact your Tyco
Sales Representative.)
Temperature Rating
Sprinkler Finish
Escutcheon Type and Finish, as
applicable
P/N from Table D
Part numbers are for 1 inch NPT
standard order sprinklers. Orders
for all other sprinkler assemblies
must be accompanied by a complete
description.
Sprinkler Wrench
Specify W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Sprinkler Boot
Specify Model DSB-2 Dry Sprinkler
Boot, P/N 63-000-0-002
This part number includes one (1) Boot,
two (2) Strap Ties, and 1/3 oz. of Adhe-
sive (a sufficient quantity for installing
one boot).