HomeMy WebLinkAbout1890 RUTHERFORD RD; ; AS040008; Permit10/27/21, 10:20 AM AS040008 Permit Data
City of Carlsbad
Sprinkler Permit
1890 RUTHERFORD
Job Address:
RD
Permit Type: SPRINK
Parcel No: 2121203500
Lot #: 0
Reference No.:
PC #:
Permit No: AS040008
Status: ISSUED
Applied 1/29/2004
Approved: 2/4/2004
Issued: 2/4/2004
Inspector:
Project Title: ISIS SCIF ROOM OH AS PLAN CHECK & INSPECTIONS
Applicant:
WEST COAST FIRE PROTECTION
512 W. CALIFORNIA AVE.
SUITE #105
VISTA, CA
(760)754-8472
Owner:
PDG CARLSBAD 47&48 L P
4330 LA JOLLA VILLAGE DR #110
SAN DIEGO CA
Fees ($) Add'l Fees ($) Total ($) Balance ($)
100 0 100 0
1/1
.4-
o
S
tqcul Fire & Building
Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
AddaL
(ENTRAL
Customer Service/Sales:
Tel: (215) 362-0700 /(800) 523-6512
Fax: (215) 362-5385
Series TYFRB - 289r 42,56, and 80 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY-FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response - standard cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20(1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
Page 1 of 8
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers are
detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the integrity of these devices.
The owner is responsible for maintain-
ing their tire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.
Model/Sprinkler
Identification
Numbers
TY1131 - Upright 2.8K, 1/2"NPT
TY1231 - Pendent 2.8K, 1/2"NPT
1V2131 - Upright 4.2K, 1/2"NPT
TY2231 - Pendent 4.2K, 1/2"NPT
TY3131 - Upright 5.6K, 1/2"NPT
TY3231 - Pendent 5.6K, 1/2"NPT
TY4131 - Upright 8.0K, 3/4"NPT
TY4231 - Pendent 8.0K, 3/4NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
APRIL, 2003
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.8 GPM/psi1/2 (40,3 LPM/bar1/2)
K = 4.2 GPM/psi112 (60,5 LPM/bar1/2)
K = 5.6 GPM/p5i112 (80,6 LPM/bar112)
K = 8.0 GPM/psi"2 (115,2 LPM/bar1I)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame ............Bronze
Button ........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ..............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K=2.8) .......Bronze
TFPI 71
Page 2 of 8 TFPI7I
ESCUTCHEON
PLATE SEATING
SURFACE
\c
-
2-1/4" ______
(57,2 mm)
1-9116"
39,7 mm)
SSP DEFLECTOR* 2-7/8" (73,0 mm) DIA
SSU'
DEFLECTOR
7/16"
(11,1 mm) I
1
NOMINAL I
MAKE-IN
I 2-3/16"
WRENCH t (55,6 mm)
FLATS
1
1/2' NPT** f
7/16"(111,11 mm) STYLE 100r20
0 ** NOMINAL RECESSED
NPT MAKE-IN ESCUTCHEON
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
2- Button Assembly 5- Compression 7- Bushing orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY113I) AND PENDENT (7Y1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
T__
2-3/16"
6mm)
(55,6mm)
1
(38,
7/160(11,1 mm)
,** NOMINAL
NPT MAKE-IN
STYLE 100r20
RECESSED SSU* ESCUTCHEON DEFLECTOR
/ 7/16°
(11,1 mm) I I I c_IL II \ NOMINAL .1 MAKE-IN
WRENCH (55,6 mm
MA
)
2-3/16"
FLATS
1I2"NPT t
6*
lii
SSP DEFLECTOR* h— 27/80 (73,0 mm) DIA.
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4- Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5- Compression orifice seat on frame. Screw Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT(TY2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
TFPI7I Page 3of8
ESCUTCHEON 7/16"(11,1 mm) STYLE 10 or 20
PLATE SEATING ** NOMINAL RECESSED * SURFACE NPT MAKE-IN ESCUTCHEON SSU
DEFLECTOR
(55,6 mm) NOMINAL 4
No it
(38,1 mm) v V R E NN (C Ht (55,6 mm) J
SSP DEFLECTOR * 2-7/8"(73,0 mm) DIA. 1/2" NPT**
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4- Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5- Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm)
PLATE SEATING ** NOMINAL
SURFACE MAKE-IN NPT
2J16., \ $
(58,7 mm) I I
(9,m) \i i J
SSP DEFLECTOR 2
PENDENT REC
STYLE 30 or 40
RECESSED SSU' ESCUTCHEON DEFLECTOR
_I 6*
TrI \ (12,7 mm) I
-u-7 j1 NOMINAL I :
1/2' 1
MAKE-IN
2-1/4"
57,2 mm) / 3
3/4NPT** t
UPRIGHT CROSS SECTION
WRENCH
FLATS
-7/8"(73,0 mm) DIA.
ESSED PENDENT
1 - Frame 3- Sealing 4- Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to 2- Button Assembly 5- Compression orifice seat on frame. Screw Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Usting is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Page 4 of 8 TFPI7I
SPRINKLER FINISH (See Note 7)
K I TYPE TEMP. BULB
LIQUID
NATURAL I
BRASS
CHROME
PLATED
I WHITE
IPOLYER
2.8
PENDENT
(TY1231)
and
UPRIGHT
(TY1131)
135°F/57°C Orange
1,2,3,5 155°F/68°C Red
175°F/79°C Yellow
200°17193°C Green
286°F/141°C Blue
1/2°
NPT 135°17/571C Orange
1,2,5
RECESSED
PENDENT
(TY2231)*
Figure 5
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
135°F/57*C Orange
RECESSED
PENDENT
(TY2231)
Figure 6
155°F/68°C Red
175°F179°C Yellow
200°F/93°C Green
4.2
1/2°
NPT
PENDENT
(TY2231)
and
UPRIGHT
(rY3131)
135°F157°C Orange
1,2
155°F168°C Red
175°F/79°C Yellow
200°F/93°C Green
286°F1141°C Blue
135°F/57°C Orange
RECESSED
PENDENT
(TY2231)°
Figure 7
155°F/68°G Red
175°F179°C Yellow
200°F/93°C Green
135°F/570C Orange
RECESSED
PENDENT
(rY2231)°
Figures
155°F/68°C Red
175°F179°C Yellow
200°F193°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response
Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10(1/2° NPT) or Style 40 (3/4° NPT) 3/4° Total Adjustment Re-
cessed Escutcheon, as applicable.
Installed with Style 20(1/2° NPT) or Style 30 (3/4° NPT) 1/2° Total Adjustment Re-
cessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to all colors (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
Installation
The Series TY-FRB Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 286°F1141°C
temperature ratings.
A leak tight 1/2 inch NPT sprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. tbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft. lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nrn) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRO Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 13).
With reference to Figures 1, 2, 3, and
4, the W-Type 6 Sprinkler Wrench is to
be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the