HomeMy WebLinkAbout891 PALOMAR AIRPORT RD; KSK 3; FPC2019-0063; PermitPERMIT REPORT
(ity of
Carlsbad
Print Date: 11/03/2021 Permit No: FPC2019-0063
Job Address: 890 PALOMAR AIRPORT RD, # KSK 3, CARLSBAD, CA 92011-4443 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fixed Extinguishing Syste
Parcel #: 2110213600 Track U: Applied: 03/14/2019
Valuation: $981,155.20 Lot U: Issued: 07/17/2019
Occupancy Group: Project U: Finaled Close Out: 11/03/2021
#of Dwelling Units: Plan U:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check U: Inspector:
Plan Check U: Final Inspection:
Project Title:
Description: CROSS ST CHICKEN & BEER KIOSK 3 -NEW HOOD UL-300 SUPPRESSION SYSTEM
FPContractor:
SAN DIEGO FIRE PROTECTION
1934 BONUS DR
SAN DIEGO, CA 92110-1325
(619) 251-7241
FEE AMOUNT
FIRE Hood & Duct Extinguishing System Initial Sys $417.00
Total Fees: $417.00 Total Payments To Date: $417.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
Kitchen Mister
Restaurant Cooking Area
Fire Suppression System
TECHNICAL MANUAL
Components
Design
Installation
Maintenance
Recharge
Buckeye Fire Equipment BFR-TM
110 Kings Road ULEX 6885 ULC-EX 6885
Kings Mountain, NC 28086 January 1, 2013
Chapter 1
General Information
Chapter 1 - General
Page 1 - 1
Revision 5
Introduction
The Buckeye Fire Equipment Kitchen Mister Fire
Suppression System is a pre-engineered wet chemical
restaurant fire suppression system as defined by the
NFPA-17A Standard for Wet Chemical Extinguishing
Systems. It is designed to protect commercial restaurant
cooking appliances, hoods, and ducts as described in
this manual.
Installation and maintenance of the Kitchen Mister
System must be in compliance with the parameters set
forth in this manual and be performed by a factory
trained, Authorized Buckeye Fire Equipment Distributor.
CAUTION
This technical manual can in no way be considered
sufficient to completely understand the proper
design, installation, and/or maintenance of the
Kitchen Mister System. Buckeye Certified Training
is required to become Authorized to perform these
procedures. Buckeye Fire Equipment will not be
responsible for system(s) designed, installed, or
maintained by individuals or companies not trained
and Authorized by Buckeye Fire Equipment.
How the Kitchen Mister Works
The Kitchen Mister System utilizes a potassium based
liquid fire extinguishing agent specifically designed for
grease laden fires such as those associated with
restaurant cooking areas. The Kitchen Mister agent
works to suppress commercial kitchen fires in three
ways:
The agent interrupts the chemical chain reaction
causing combustion, thus extinguishing the fire.
The agent is discharged in a very fine mist, cooling
the fire to below its auto-ignition temperature.
The agent reacts with grease to form a foam-like
layer commonly called saponification that starves
the fire of oxygen, stopping combustion and
preventing re-ignition.
The system will automatically actuate upon detection of a
fire or can be manually actuated by using a remote
manual pull station positioned at the point(s) of egress
from the hazard area. When the system is actuated, a
pre-determined amount of fire extinguishing agent is
discharged through the piping network and fixed nozzles
to the duct, plenum, and cooking appliances. The agent
is discharged as a very fine mist that quickly acts to
suppress grease laden fires.
System Temperature Limitations
The operating temperature range of the Kitchen Mister
System is 32°F (0°C.) minimum to 120°F (490C.)
maximum.
Listings and Approvals
The Kitchen Mister Fire Suppression System is Listed
and Approved by the following agencies:
Underwriters Laboratories, Inc. (Listed to the
requirements of UL-300/UL-1254) UL-EX 6885
Underwriters Laboratories of Canada, ULC-EX 6885
Approved by the New York City Fire Department
COA# 5550
ISO-9001 Registered
Manufacturers Warranty
Buckeye Fire Equipment warrants the Kitchen Mister
System against defects in material and workmanship for
a period of one year from date of shipment to the
purchaser under normal use and service. Buckeye Fire
Equipment is not responsible for the installation and
maintenance of the system. All warranty claims must be
filed with Buckeye Fire Equipment within 30 days of the
discovery of the defect to be valid.
System Installation and Maintenance
Reciui rements
Any individual installing or performing maintenance on
the Kitchen Mister System MUST be; fully trained and
Authorized by Buckeye Fire Equipment, have a complete
understanding of this manual in full, and have a complete
understanding of all local, state, and federal
requirements that may apply. The Buckeye Kitchen
Mister System must be installed and maintained in
accordance with the NFPA-17A Standard for Wet
Chemical Extinguishing Systems, NFPA-96 Standard for
Ventilation Control and Fire Protection of Commercial
Cooking Operations, this manual, and all applicable
local, state, and federal regulations.
Buckeye Fire Equipment is not responsible for systems
installed or maintained by personnel that are not factory
trained and Authorized.
BPN: BFR-TM ULEX 6885 ULC-EX 6885
January 1, 2013
Chapter 2 - Components
Page 2-4
Revision 5
Figure 2-8.
Model MB-2,
Shown With BFR-20 Cylinder
Remote Mechanical Pull Station
The Model RPS-M Remote Mechanical Pull Station
provides remote mechanical actuation of the Systems
Releasing Module. It is connected to the Systems
Releasing Module with:
1/16" (0.16 cm) stainless steel cable enclosed in 1/2"
(1.3 cm) EMT conduit with a corner pulley at each
change of direction.
Buckeye Shielded Cable which does not require a
corner pulley at each change of direction or conduit.
A combination of both.
A remote pull station .is required at the point of egress
from the hazard area being protected. See Figure 2-9.
Figure 2-9.
Model RPS-M,
Remote Mechanical Pull Station
Mechanical Gas Shutoff Valves
A gas shutoff valve is required for all systems protecting
gas fueled appliances. A mechanical means of stopping
gas flow is provided by the Models BFGV-75 /100 /125
I 150 I 200 / 250 I 300 Gas Shutoff Valves. It is
connected to the Systems Releasing Module with:
1/16" (0.16 cm) stainless steel cable enclosed in 1/2"
(1.3 cm) EMT conduit with a corner pulley at each
change of direction.
Buckeye Shielded Cable which does not require a
corner pulley at each change of direction or conduit.
A combination of both.
The valves are rated for natural or LP gas (see Figure 2-
10) and are available in the following sizes:
Model
Number
Valve
Size
In (cm)
Maximum
Operating
Pressure
BFGV-75 %(1.9) 5 psi (.4 bar)
BFGV-100 1(2.5) 5 psi .4 bar)
BFGV-125 1 1/4 (3.2) 5 psi .4 bar)
BFGV-150 1%(3.8) 5 psi .4 bar)
BFGV-200 2(5.1) 5 psi .4 bar)
BFGV-250 2 ¼ (6.4) 5 psi .4 bar)
BFGV-300 3(7.6) 5 psi .4 bar)
Note: Gas valve size must be no smaller than the size of
the gas line it is connected to.
00
o
EUM
o o
Figure 2-10.
Model BFGV-XXX,
Mechanical Gas Valve
[NCASEOF (1)
FIRE
PULL HANDLE HARD
ACTU FIRE SU SYSTEM a) jV RPS-M a)
ULEX 6885 ULC-EX 6885 BPN: BFR-TM
January 1, 2013
i!l (5.16 cm) STAINLESS
DETECTION CABLE
!ISLE
Fusible Link Bracket Kit
The Model FLB-1 Fusible Link Bracket kit (see Figure 2-
11) includes the following:
Standard high profile 10° (25 cm) fusible link
bracket.
Two (2) ½" (1.3 cm) EMT connectors.
Two (2) cable crimps.
Two (2)'S" hooks.
Note: Fusible links must be ordered separately.
FUSIBLE LINK BRACKET
7 (1.3 cm) EMT J
CONNECTOR
—:ABLE CRIMP
Figure 2-11.
Model FLB-1,
10" (25 cm) Fusible Link Bracket Assembly
Fusible Link Holder
The Model FLH Fusible Link Holder is designed to allow
for the use of a continuous fusible link line, thus
eliminating the need to cut and crimp each individual
fusible link. They can be used either with or without
fusible link brackets. They are available in packages of
25 (Model FLH-25). See Figure 2-12.
STYLE)
Figure 2-12.
Model FLH,
Fusible Link Holder
Fusible Links
The Kitchen Mister System uses Globe ML Fusible Links
for automatic system activation. See Figure 2-13.
Fusible links are designed to separate at specific
temperatures, releasing tension from the fusible link
Chapter 2 - Components
Page 2 - 5
Revision 5
detection line and causing system actuation. Correct
fusible link selection is an essential element in the design
of any restaurant fire suppression system. After
performing a temperature study to determine the
maximum ambient temperature at the fusible link
location, the correct fusible link should be selected from
the following chart:
Fusible Link
Model Number
Max. Ambient
Temperature
FL-280 225° F. (107° C.)
FL-360 300° F. (149° C.)
FL450 375° F. (191° C.)
FL-500 4300 F.(221-C.)
Figure 2-13.
Globe ML Fusible Link
Buckeye Shielded Cable
As an alternative to using conduit and corner pulleys to
connect the fusible link system, gas valve, and/or remote
pull station to the Systems Releasing Module, the
Kitchen Mister System utilizes Buckeye Shielded Cable
to perform this function. Buckeye Shielded Cable is 1/16"
(0.16 cm) stainless steel cable encased in a protective,
flexible conduit. See Figure 2-14.
Buckeye Shielded Cable requires no conduit or corner
pulleys, as the name implies, provided it is installed in
accordance with the guidelines set forth in this manual.
Model BFR-SC-100 comes with 105 feet (32 m) of
flexible conduit with 210 feet (64 m) of 1/16" (0.16 cm)
stainless steel cable inside it.
BUCKEYE
SHIELDED
CABLE
1116 )O.16 cm)
STAINLESS STEEL
CABLE
Figure 2-14.
Model BFR-SC-100,
Buckeye Shielded Cable
BPN: BFR-TM ULEX 6885 ULC-EX 6885
January 1, 2013
10 Chapter 2 - Components
Page 2 - I
Revision 5
Chapter 2
System Components
Cylinder Sizes
The Buckeye Fire Equipment Kitchen Mister Fire Suppression System has available four (4) cylinder sizes; the Model
BFR-5 (5 flow points), Model BFR-10 (10 flow points), Model BFR-15 (15 flow points), and Model BFR-20 (20 flow
points). Cylinder sizes are based on the flow point capacity of the cylinder, for example, the BFR-5 is capable of
supporting a maximum of five (5) flow points. All cylinders are manufactured, marked, and tested in accordance with DOT
4BW240. Each cylinder is shipped pre-filled with extinguishing agent, and charged with dry nitrogen to a pressure of 195
psig (1344 KPa) @700 F (21° C). Cylinder and valve assembly dimensions are shown in Figure 2-1,
Note: Cylinders shall always be stored in an upright position.
SRM
"A"
- r ' B " ,, D
,, C
Figure 2-1.
Cylinder and Valve Assembly Dimensions.
Model
Number
A
inches
(cm)
B
inches
(cm)
C
inches
(cm)
D
inches
(cm)
Max.
Flow
Points
Weight
lbs.
(kg)
Mounting
Bracket
BFR-5 24.8 (63) 16.2 (41) 10 (25) 13,4 (34) 5 42 lbs. (19) MB-1
BFR-10 34,4 (87) 25.8 (66) 10 (25) 23 (58) 10 74 lbs. (33) MB-2
BFR-15 1 44.8 (114) 36.2 (92) 10 (25) 1 33.4 (85) 1 15 1 107 lbs. (48) MB-2
BFR-20 1 42.4 (108) 33.8 (86) 12 (31) 1 31 (79) 1 20 1 130 lbs. (60) MB-2
BPN: BFR-TM ULEX 6885 ULC-EX 6885
January 1, 2013
The Model MB-1 Mounting Bracket is used to mount the
Model BFR-5 cylinder. See Figure 2-7.
Figure 2-7.
Model MB-I,
Shown With BFR-5 Cylinder
The Model MB-2 Mounting Bracket is used to mount the
Model BFR-10, Model BFR-I5, or Model BFR-20
cylinders. See Figure 2-8.
10
Systems Releasing Module - SRM
The Model SRM Systems Releasing Module is a fully
mechanical control head that can be connected directly
or remotely to the system valve and is required for
system actuation. The Systems Releasing Module will
support the following system inputs and outputs:
One Fusible Link Detection Line
One Gas Valve Line
One Remote Pull Station Line
Two windows in the front cover of the Model SRM allow
for visual verification of the actuation cartridge presence
and the status of the puncture pin mechanism. See
Figure 2-5.
PM NT 0
SRM 0
Chapter 2 - Components
Page 2 - 3
Revision 5
Model BFR-AC-L is a larger nitrogen cartridge that can
actuate up to five agent cylinder (refer to Chapter 4 of
this manual for limitations). See Figure 2-6.
5.12 I' (13 cm) CL
01.57 IIIIiD (4 cm) IN I o1
Model BFR-AC-L
3.70
(9.4 cm)
01.00
(2.5 cm) WEE
Model BFR.AC-S
Figure U.
Model BFR-AC-S and BFR-AC-L,
Nitrogen Actuation Cartridges
Mounting Brackets
/
ACTUATION LEVER AND / ACTUAI1ON CARTRIDGE PUNCTURE PIN VIEWING
WINDOW VIEWING WINDOW
Figure 2-5.
Model SRM,
Systems Releasing Module
The Model SRM can actuate a maximum of three (3)
agent cylinders when using the Model BFR-AC-S
Nitrogen Activation Cartridge (included with SRM and
SRM-D) or five (5) agent cylinders when a Model BFR-
AC-L Nitrogen Activation Cartridge is installed.
Systems Releasing Module - SRM-D
The Model SRM-D (Systems Releasing Module —Dual) is
exactly the same as the Model SRM except that it
supports a second independent fusible link detection line.
Nitroaen Actuation Cartridaes
The Kitchen Mister System can use two types of
actuation cartridges for system actuation.
Model BFR-AC-S is a small nitrogen cartridge (included
with System Releasing Module) that can actuate up to
three (3) agent cylinders.
BPN: BFR-TM ULEX 6885 ULC-EX 6885
January 1, 2013
Chapter 2 - Components
Page 2-6
Revision 5
Shielded Cable Interface
The Model BFR-SCI Buckeye Shielded Cable Interface
is required for connecting Buckeye Shielded Cable to any
standard 1/2" (1.3 cm) EMT conduit connector or corner
pulley. See Figure 2-15.
Figure 2-15.
Model BFR-SCI,
Shielded Cable Interface
Note: A 3/32" (0.2 cm) hex wrench is required to tighten
the set screw.
Compression Type Corner Pulley
When Buckeye Shielded Cable IS NOT used to connect
the fusible link system, gas valve, and/or remote pull
station to the control head, a corner pulley is required
whenever a change in stainless steel cable direction is
necessary. The Model CPCT-1 corner pulley is equipped
with a compression type fitting that connects to standard
1/2" (1.3 cm) EMT conduit. See Figure 2-16.
Figure 2-16.
Model CPCT-1,
Compression Type Corner Pulley
Model
Number
Flow
Points
Band
Color
N-IHP I Blue
N-11P I Red
N-2HP 2 Green
N-21-P 2 Yellow
N-2W 2 White
Note: Details on specific nozzle applications can be
found in the Design Section of this manual.
13/16
(0.2 cm)
HEX.
TETHERED
/ BLOW-OFF CAP
COLOR
ID BAND tD( 1.50"
INTERNAL
SCREEN
\—RETAINING RING
Figure 2-17.
Discharge Nozzle
Swivel Nozzle Adaptor
The Model N-SA Swivel Adaptor can be used with any
discharge nozzle to facilitate the nozzle aiming process.
They are chrome plated and allow for a 300 rotation of
the nozzle in any direction. See Figure 2-18.
3/8" (1.0cm) NPT
FEMALE THREAD
Discharge Nozzles
Misting type discharge nozzles have been specifically
developed for appliance, duct, and plenum applications.
Each nozzle has a predetermined flow point value and
comes equipped with a blow-off cap to protect the end
orifice from blockage. Each nozzle is identified by the
model number stamped on the nozzle body and has a
unique color band for easy visual identification. See
Figure 2-17.
30° ROTATION
318 (1.0 cm) NPT
MALE THREAD
Figure 2-18.
Model N-SA,
Swivel Adaptor
ULEX 6885 ULC-EX 6885 BPN: BFR-TM
January 1, 2013
Chapter 2 - Components
Page 2-7
Revision 5
Digital Thermometer
The Model BFR-DT Digital Thermometer is used to
accurately determine the maximum ambient temperature
in the plenum in the air stream of each appliance. A
thorough temperature survey is necessary for proper
fusible link selection. The thermometer comes with a
digital readout and remote sensing wand for ease of use.
CAUTION
A temperature study is required before the
installation of any system in order to determine the
correct temperature fusible link at each fusible link
lOcation.
Pipe and Fittings
Pipe and fittings must be furnished by the installer. Pipe
shall be Schedule 40 black, chrome plated, or stainless
steel pipe. Fittings shall be rated 150 LB (68 kg).
BPN: BFR-TM ULEX 6885 ULC-EX 6885
January 1 2013
Chapter 3 - System Design
Page 3- 1
Revision 5
Chapter 3
System Design
OVERVIEW OF SYSTEM DESIGN (127 cm) perimeter and a maximum one side length of
12-1/2' (32 cm) (square) and 16-3/4" (43 cm)
(rectangular) respectively. It can also protect a round The following chapter will cover the proper design of the duct with a maximum circumference of 50" (127 cm) Buckeye Fire Equipment Kitchen Mister Fire [16" (41 cm) maximum diameter]. See Figure 3-1 & 3-2. Suppression System. It is divided into three sections:
Nozzle Coverages and Placements
Piping Limitations
Detector Placement
Design of the Kitchen Mister System must be in
compliance with the parameters set forth in this manual
and be performed by a factory trained, Authorized
Buckeye Fire Equipment Dealer. Buckeye Fire
Equipment is not responsible for systems installed or
maintained by personnel that are not factory trained and
Authorized.
NOZZLE COVERAGE, PLACEMENT,
AND AIMING
This section will give detailed guidelines for determining
nozzle type, positioning, and aim point for appliance,
plenum, and duct protection.
Duct Protection
It is not necessary to shut down or damper the exhaust
fan for the system to function properly. It is
recommended that the exhaust fan be left on during
system discharge to help distribute the extinguishing
agent throughout the ductwork.
Ducts - 50" (127 cm) Maximum Perimeter
Nozzle: N-1 LP (1 Flow Point)
Coverage: Unlimited length with:
50" (127 cm) Maximum Perimeter with a
longest side of 16-3/4" (43 cm) for
rectangular ducts and 12-1/2" (32 cm) for
square ducts
or
50" (127 cm) Maximum Circumference
(maximum diameter of 16" (41 cm)) for
round ducts.
Placement: Centered in duct opening, from 1-6" (2.5-
15 cm) into the duct opening.
Aim point: Center of duct.
The Model N-ILP nozzle is a one flow point nozzle that
can protect a square or rectangular duct of unlimited
length and changes of direction with a maximum 50"
BPN: BFR-TM
Ducts - 150" (381 cm) Maximum Perimeter
Nozzle: N-2W (2 Flow Point)
Coverage: Unlimited length with:
150" (381 cm) Maximum Perimeter with a
longest side of 50" (127 cm) for
rectangular ducts and 37-1/2" (95 cm) for
square ducts
or.
150' (381 cm) Maximum Circumference
[maximum diameter of 47-1/2" (121 cm)]
for round ducts.
Placement: Centered induct opening, from 0-6" (0-15
cm) into the duct opening.
Aim point: Center of duct.
AIM: CENTER OF
FOR DUCTS (VERTICAL OR HORIZONTAL)
WTHOUTA TRANSITION
AIM: CENTER OF
ENTRANCE TO
HORIZONTAL DUCT PLACEMENT:
1.6(2.5-15cm) 112L 1"-
0 to 50(0-127 cm), N-1LPJ
-. 0" - 6"(0-15 cm)
[Per. 0 to 150" (0-381 cm), N-2W]
INTO THE DUCT TRANSITION
FOR DUCTS WITH A VERTICAL TO HORIZONTAL
TRANSITION
Figure 3-1.
Proper Duct Nozzle Placement
ULEX 6885 ULC-EX 6885
January 1, 2013
NOZZLE PLACEMENT:
1"- 6" (2.5-15 cm)
Oto 50(0.127 cm), N-1LP]
0" -6" (0-15 cm)
o to 150" (0-381 cm), N-2q
INTONE DUCT
'0
Plenum Protection
Nozzle: N-1 HP (1 Flow Point)
Coverage: Length: 12 feet (3.7 m) max.
Width: 4 feet (1.2 m) max.
Placement: See Figure 3.7.
Aim point: See Figure 3.7.
The Model N-IHP nozzle is a one (1) flow point nozzle
that can protect a plenum (either single bank or V-bank)
of 12 feet (3.7 m) in length and 4 feet (1.2 m) in width
per nozzle. Larger plenums must be divided into 12 foot
(3.7 m) sections, with each section protected with a
separate nozzle. See Figure 3-7.
Plenum: V-bank Nozzle Placement
The nozzle must be located at the center of the V-bank
width and down 1/3 of the vertical height, within 6 inches
(15 cm) of the end of the plenum or plenum module and
aimed down the length of the plenum. See Figure 3-7.
Plenum: Single Filter Bank Nozzle Placement
The nozzle must be located at a point that is 2" (5.1 cm)
from the back edge of the filter and 1/3 of the vertical
height of the filter, within 6 inches (15 cm) off the end of
the plenum or plenum module and aimed down the
length of the plenum. See Figure 3-7.
V3ANK
12 FT (3Jm)- rT/1
r3.7m)
H
SINGLE BANK
110 Figure 3-7.
Model N-IHP
Plenum Nozzle Placement and Aiming
Note: These examples are typical and do not represent
every acceptable nozzle configuration, only a
representative sample of them.
Designer Note
For plenums that exceed 12 feet (3.7 m) in length
and therefore require multiple nozzles, it is
recommended that the total length be divided into
equally sized protection zones and protected
accordingly. So a 16 foot (4.9 m) long plenum
should be divided into two 8 foot (2.4 m) zones, with
a nozzle protecting each, as opposed to a 12 foot
(3.7 m) zone and a 4 foot (1.2 m) zone.
BPN: BFR-TM
Chapter 3 - System Design
Page 3-3
Revision 5
APPLIANCE PROTECTION
Each different appliance must be protected in a specific
manner with regard to nozzle selection, placement, and
aiming. No deviations from these parameters are
allowed and failure to comply completely with these
requirements will void the UL Listing of the system and
may render the system ineffective.
In order to properly understand this section, several key
terms need to be defined in advance.
DESIGN TERMINOLOGY
Nozzle Height: The distance from the tip of the
discharge nozzle to the top surface of the appliance
(except for woks, in which case the bottom of the wok is
used).
Hazard Area: All nozzle coverages include the
maximum size of the hazard area they can protect.
Hazard area is NOT the overall size of the appliance
being protected, but rather the actual size of the
portion of the appliance used for cooking.
Appliances Repuirina Multiple Nozzles
Some appliances may need to be protected by multiple
nozzles because of their size. If the size of an
appliance is larger than the approved coverage for that
appliance, multiple nozzles must be used. This is
accomplished by dividing the hazard area into individual
zones that comply with the parameters of the listing for
that appliance. In this case, each zone will be protected
as an individual appliance with respect to nozzle
placement and aiming.
RANGE PROTECTION
Two (2) Burner Ranae - LOW Proximit
Nozzle: N-1 LP (1 Flow Point)
Coverage: 12" (30.5 cm) x 24" (61 cm) Maximum
(measured burner edge to burner edge)
Nozzle Ht: 16" (41 cm) - 30" (76 cm)
Placement: 3" (7.6 cm) from either edge of appliance,
on appliance's long centerline.
Aim point: 6" (15 cm) from opposite edge of
appliance, on appliance's long centerline.
The Model N-ILP nozzle is a one (1) flow point nozzle
that can protect a range cooking area of 12" (30.5 cm)
wide by 24" (61 cm) deep. The nozzle must be located
16" (41 cm) to 30" (76 cm) above the cooking surface
and positioned on the appliance's long centerline within
3" (7.6 cm) of either the front or back edge of the
ULEX 6885 ULC-EX 6885
January 1, 2013
Chapter 3 — System Design
Page 3-4
Revision 5
appliance. The nozzle must be aimed at the appliance's
long centerline 6" (15 cm) off the opposite edge of the
appliance. See Figure 3-8.
MAXIMUM HEIGHT 30 (76Or,,)
NOZZLE
PLACEMENT
AREA
FRONT OR MACIl OF
APPLIANCE)
- AIM POINTS
(loom) FROM
RANGE - )CI.- OPPOSITE EDGE
NOZZLE LOCATED
FROM
FRONT OR EACH
HAZARD REGE
(NGTH 12 MAXIMUM
130.5 Xml HAZARD WIG
- 24 (Ri On,)
Figure 3-8.
Low Proximity, 12" (30.5 cm) x 24" (61 cm) Range
Model N-ILP Nozzle
Four (4) Burner Ranges:
I) Four Burner Range —HIGH Proximity
Nozzle: N-1 LP (1 Flow Point)
Coverage: 24" (61 cm) x 24' (61 cm) Maximum
(measured burner edge to burner edge)
Nozzle Ht: 30" (76 cm) —40" (102 cm)
Placement: Within 3" (7.6 cm) of the center of appliance.
Aim point: Center of appliance.
The Model N-ILP nozzle is a one (1) flow point nozzle
that can protect a range cooking area of 24" (61 cm)
wide by 24" (61 cm) deep. The nozzle must be located
30" (76 cm) to 40" (102 cm) above the cooking surface
and within 3" (7.6 cm) of the center of the appliance.
The nozzle must be aimed at the center of the cooking
area. See Figure 3-9.
MAXIMUM HEIGHT
46(1030m) -
NOZZLE r (P.R cm)
PLACEMENT FROM
AREA CENTER
MINIMUM HEIGHT
CENTER RANGE
S URN ER TO
BURNER To
LENGTH, BURNER WiDTH:
Figure 3-9.
High Proximity, 24" (61 cm) x 24" (61 cm) Range
Model NA LP Nozzle
ULEX 6885 ULC-EX 6885
January 1, 2013
2) Four Burner Ranae — LOW Proximity
Nozzle: N-2W (2 Flow Point)
Coverage: 24" (61 cm) x 24" (61 cm) Maximum
(measured burner edge to burner edge)
Nozzle Ht: 16" (41 cm) —30" (76 cm)
Placement: Center of appliance.
Aim point: Center of appliance.
The Model N-2W nozzle is a two (2) flow point nozzle
that can protect a range cooking area of 24" (61 cm)
wide by 24' (61 cm) deep. The nozzle must be located
16" (41 cm) to 30" (76 cm) above the cooking surface
and be centered over the appliance. The nozzle must be
aimed at the center of the cooking area. See Figure
3-10.
MAXIMUM HEIGHT
30' (76 ern)
NOZZLE PLACEMENT
AREA
MINIMUM HEIGHT
16"(41c) 1 RANGE CENTER
BURN BURNER TO BURNEI
LENGTH
ER 24" (61 cm)
Figure 3-10.
Low Proximity, 24" (61 cm) x 24" (61 cm) Range
Model N-2W Nozzle
Six (6) Burner Range
Nozzle: N-21-P (2 Flow Point)
Coverage: 36" (91 cm) x 24" (61 cm) Maximum
(measured burner edge to burner edge)
Nozzle Ht: 35" (89 cm)-43" (109 cm)
Placement: Centered over appliance.
Aim point: Center of appliance.
The Model N-2LP nozzle is a two (2) flow point nozzle
that can protect a range cooking area of 36" (91 cm)
wide by 24" (61 cm) deep. The nozzle must be located
35" (89 cm) to 43" (109 cm) above the cooking surface
and centered over the appliance. The nozzle must be
aimed at the center of the cooking area. See Figure
3-11.
BPN: BFR-TM
IF SHELF IS HIGHER,
THEN NOZZLE HEIGHT
MAY INCREASE J PROPORTIONALLY.
SHELF M02EMJM MAY BE
EXCEEDED IF NOZZLE15
(48 cm)
MIN.-
TIP IS PLACED BELOW
SHELF HEIGHT.
AIM: 6 (15 cm) FROM
OPPOSITE EDGE, ON
LONG CENTER LINE
Chapter 3 — System Design
Page 3 - 5
Revision 5
Model N-ILP Nozzle
'MAXIMUM HEIGHT 43 1100 cm)
NOZZLE
PLACEMENT
AREA
MINIMUM HEIGHTZE (90 cnl)
/• RANGE CENTER
BURNER TO SURNEJ 00XTF424(EIcn,)
J.
Figure 3-11.
36" (91 cm) x 24" (61 cm) Range
Model N-2LP Nozzle
Range I Griddle Combination Appliance
Nozzle: N-ILP(1 Flow Point)
Coverage: 30" (76 cm) x 24" (61 cm) Maximum
(measured burner edge to burner edge)
Nozzle Ht: 30" (76 cm) - 40" (102 cm)
Placement: Within 3" (7.6 cm) of the center of
appliance.
Aim point: Center of appliance.
The Model N-ILP nozzle is a one (1) flow point nozzle
that can protect a combination range / griddle with a
cooking area of 30" (76 cm) wide by 24" (61 cm) deep.
The nozzle must be located 30" (76 cm) to 40" (102 cm)
above the cooking surface and within 3" (7.6 cm) of the
center of the appliance. The nozzle must be aimed at
the center of the cooking area. See Figure 3-11.
- MAXIMUM HEGHT 40' (102 En)
NO
ZZ
LE 11.6 Cm)
PLA
AREA
CEMENT FROM CENTER
MINIMUM HEIGHT
3E"(lECM)
RANGERIDDLE CENTER
BURNER WOTh 12' cm (36.0 ) MA
BUP.NBR TO
BURNER TO GRIDDLE
URNSPJGRIXGLE
GEDTH
Em) ..44)3o GRIDDLE LBNOTN I
3E'(7Ecm)l 7
,
Figure 3-12.
30" (76 cm) x 24" (61 cm) Combination
Range I Griddle
BPN: BFR-TM
Protection For Appliances With a Back-
shelf
The protection of an appliance (such as a range) that
has a shelf that can interfere with a nozzle discharge
can be accomplished by either using the low proximity
coverage for that appliance or placing the nozzle in a
position within its stated limitation where the discharge
pattern will not be affected. Sample coverages for a
range with a back-shelf are shown in Figures 3-13 and
3-14.
EM ELP WIDTH: NOT TO
EXCEED THE CENTERLINE OF
THE RANGE UNLESS NOZZLE
IS LOCATED UNDER SHELF
MAX. HEIGHT: TIP LOCATED BELOW OR LEVEL PLACEMEN1
WITH THE BOTTOM OF THE OBSTRUCTION BUT, .CENTER OF
MOTTO EXCEED 30 (lB cm)
MIN. HEIGHT 16" (41 cm)
NOZZLE TIP MUST BE AIM: CENTER OF BELOW SHELF OR
RANGE DESTRUCTION.
6 ___*(30.5 Cm)
(30.5 C BURNER
ERBURN WiDTH: BURNER TO
BURNER (81 cm)
24"
LENGTH:
(61
Figure 3-13.
24" (61 cm) x 24" (61 cm) Range with Back-shelf
Model N-2W Nozzle
11(28 cm) MAX.'"
MAX. HEIGHT 24'(61 cm)—
MIN. HEIGHT 18 (41 cm)_,
RANGE CENT -
MAX.
HAZARD NOZZLE LOCATED 3" (7.8
LENGTH: 12 (30.5 cm) cm) FROM FRONT EDGE
MAX. HAZARD
WIDTH: 24" (61 cm)
Figure 3.14.
12" (30.5 cm) x 24" (61 cm) Range with Back-shelf
Model NA LP Nozzle
ULEX 6885 ULC-EX 6885
January 1, 2013
Chapter 2 - Components
Page 2 - 4
Revision 5
Figure 2-8.
Model M13-2,
Shown With BFR-20 Cylinder
Remote Mechanical Pull Station
The Model RPS-M Remote Mechanical Pull Station
provides remote mechanical actuation of the Systems
Releasing Module. It is connected to the Systems
Releasing Module with:
1/16 (0.16 cm) stainless steel cable enclosed in 112"
(1.3 cm) EMT conduit with a corner pulley at each
change of direction.
Buckeye Shielded Cable which does not require a
corner pulley at each change of direction or conduit.
A combination of both.
A remote pull station is required at the point of egress
from the hazard area being protected. See Figure 2-9.
Figure 2-9.
Model RPS-M,
Remote Mechanical Pull Station
Mechanical Gas Shutoff Valves
A gas shutoff valve is required for all systems protecting
gas fueled appliances. A mechanical means of stopping
gas flow is provided by the Models BFGV-75 /100 1125
I 150 I 200 I 250 I 300 Gas Shutoff Valves. It is
connected to the Systems Releasing Module with:
1/16" (0.16 cm) stainless steel cable enclosed in 1/2"
(1.3 cm) EMT conduit with a corner pulley at each
change of direction.
Buckeye Shielded Cable which does not require a
corner pulley at each change of direction or conduit.
A combination of both.
The valves are rated for natural or LP gas (see Figure 2-
10) and are available in the following sizes:
Model
Number
Valve
Size
In (cm)
Maximum
Operating
Pressure
BFGV-75 %(1.9) 5 psi (.4 bar)
BFGV-100 1(2.5) 5 psi (.4 bar)
BFGV-125 1 1/4 (3.2) 5 psi (.4 bar)
BFGV-150 1 1/2 (3.8) 5 psi (.4 bar)
BFGV-200 2(5.1) 5 psi (.4 bar)
BFGV-250 21/2 (6.4) 5 psi (.4 bar)
BFGV-300 3(7.6) 5 psi (.4 bar)
Note: Gas valve size must be no smaller than the size of
the gas line it is connected to.
00
I o o
_
A
00
Figure 2-10.
Model BFGV-XXX,
Mechanical Gas Valve
CD IN CASE OF CR) FIRE PULL HANDLE HARD
FrES12 CYSTEM CD jV RPS-M CD
ULEX 6885 ULC-EX 6885 BPN: BFR-TM
January 1, 2013
1/16' 10.16 cm) STAINLESS
DETECTION CABLE
I lB LB
Fusible Link Bracket Kit
The Model FLB-1 Fusible Link Bracket kit (see Figure 2-
II) includes the following:
Standard high profile 10' (25 cm) fusible link
bracket.
Two (2)1/2" (1.3 cm) EMT connectors.
Two (2) cable crimps.
Two (2) S' hooks.
Note: Fusible links must be ordered separately.
FUSIBLE LINK BRACKET,
112' (1.3 cm) EMT
CONNECTOR
LE CRIMP
Figure 2-11.
Model FLB-1,
10" (25 cm) Fusible Link Bracket Assembly
Fusible Link Holder
The Model FLH Fusible Link Holder is designed to allow
for the use of a continuous fusible link line, thus
eliminating the need to cut and crimp each individual
fusible link. They can be used either with or without
fusible link brackets. They are available in packages of
25 (Model FLH-25). See Figure 2-12.
ruww. L,rin
STYLE)
Figure 2-12.
Model FLH,
Fusible Link Holder
Fusible Links
The Kitchen Mister System uses Globe ML Fusible Links
for automatic system activation. See Figure 2-13.
Fusible links are designed to separate at specific
temperatures, releasing tension from the fusible link
Chapter 2 — Components
Page 2 - 5
Revision 5
detection line and causing system actuation. Correct
fusible link selection is an essential element in the design
of any restaurant fire suppression system. After
performing a temperature study to determine the
maximum ambient temperature at the fusible link
location, the correct fusible link should be selected from
the following chart:
Fusible Link
Model Number
Max. Ambient
Temperature
FL-280 225° F. (107° C.)
FL-360 300° F. (149° C.)
FL-450 375° F. (1910 C.)
FL-500 430° F. (2210 C.)
Figure 2-13.
Globe ML Fusible Link
Buckeye Shielded Cable
As an alternative to using conduit and corner pulleys to
connect the fusible link system, gas valve, and/or remote
pull station to the Systems Releasing Module, the
Kitchen Mister System utilizes Buckeye Shielded Cable
to perform this function. Buckeye Shielded Cable is 1/16"
(0.16 cm) stainless steel cable encased in a protective,
flexible conduit. See Figure 2-14.
Buckeye Shielded Cable requires no conduit or corner
pulleys, as the name implies, provided it is installed in
accordance with the guidelines set forth in this manual.
Model BFR-SC-100 comes with 105 feet (32 m) of
flexible conduit with 210 feet (64 m) of 1/16" (0.16 cm)
stainless steel cable inside it.
BUCKEYE
SHIELDED
CABLE
Ill
S (0.10 cm)
STAINLESS STEEL
CABLE
Figure 2-14.
Model BFR-SC-100,
Buckeye Shielded Cable
BPN: BFR-TM ULEX 6885 ULC-EX 6885
January 1, 2013
Chapter 3 - System Design
Page 3-6
Revision 5
Four Burner Rancie with a Back-shelf
- HIGH Proximity
Nozzle: N-21-P (2 Flow Point)
Coverage: 24" (61 cm) x 24" (61 cm) Maximum
(measured burner edge to burner edge)
Nozzle Ht: 30' (76 cm)-40" (102 cm)
Placement: 6" (15 cm) outside the front edge of the
burners within 9" (22.6 cm) from the
centerline.
Aim point: 6" (15 cm) from the back edge of the
burner on the centerline of the
appliance.
Shelf Height: Minimum of 16" (41 cm) from the top of
the appliance.
Wok Protection
Nozzle: N-1HP(1 Flow Point)
Coverage: 12" (30.5 cm) Mm. x 30" (76 cm) Max.
Nozzle Ht: 30" (76 cm) - 48" (122 cm) (measured
from bottom)
Placement: Anywhere over the surface of the
appliance.
Aim Point: Center of bottom of appliance.
MAXIMUM HEIGHT
NOZZLEAIM 48" (122 cm)
CENTER OF
WOK 80
NOZZLE
PLACEMENT
AREA
Shelf Width: A maximum of 11(28cm).
The Model N-21LP nozzle is a two (2) flow point nozzle
that can protect a range cooking area of 24" (61 cm)
wide by 24" (61 cm) deep. The nozzle must be located
30" (76 cm) to 40" (102 cm) above the cooking surface
6" (15 cm) from the front edge of the burners and within
9" (22.5 cm) of the centerline of the appliance. The
nozzle must be aimed 6" (15 cm) from the back edge of
the burner on the centerline of the appliance. The
backshelf shall not be less then 16" (41 cm) from the top
of the appliance and extend more then 11" (28 cm) over
the back edge of the burners. See Figure 3-14a.
MAXIMUM WOK
DIAMETER: 30 (76 cm)
MINIMUM WOK
DIAMETER: 12' (30.5 cm)
7tIVIUM FftI(iHT
(76 cm)
SHELF WIDTH: NOT 10
EXCEED 11 (28 cm)
MAX.HEIGHT: 40 (102cm)
NOZZLE PLACEMENT
AREA
MIN, HEIGHT 30 (76 cm)
AIM: V (15 cm) FROM BACK EDGE ON
CENTERLINE
NIMLEcI SHELF
EIGHT
16(41 cm)
Figure 3-14b.
Wok Protection
Model N-IHP Nozzle
The Model N-IHP nozzle is a one (1) flow point nozzle
that can protect a wok with a minimum diameter of 12"
(30.5 cm) up to a maximum diameter of 30" (76 cm).
The nozzle must be located 30" (76 cm) to 48" (122 cm)
above the bottom of the wok and positioned anywhere
over the cooking area. The nozzle must be aimed at the
center of the cooking area. See Figure 3-14b.
K MAX' AX L
9(22.5 cm)
BURNER EDGE TO
EDGE:
24(61 cm)
BURNER
- '6"
(15 cm)
BURNER EDGE TO BURNER EDGE:
24(61 cm)
Figure 3-14a.
24" (61 cm) x 24" (61cm) Range with Back-shelf
Model N-21-P Nozzle
ULEX 6885 ULC-EX 6885 BPN: BFR-TM
January 1, 2013
Chapter 3 - System Design
Page 3 - 7
Revision 5
Tiltina Brazina Skillet Protection
Nozzle: N-2HP (2 Flow Point)
Coverage: 20.25" (51 cm) x 24" (61 cm) per nozzle
Nozzle Ht: 24" (61 cm)-45" (114 cm)
Placement: Anywhere over the surface of the
appliance cooking area.
Aim Point: Center of the protected zone.
The Model N-2HP nozzle is a two (2) flow point nozzle
that can protect a tilting brazing pan I skillet with a
maximum cooking area of 20.25" (51 cm) wide by 24"
(61 cm) deep per nozzle. The nozzle must be located
24" (61 cm) to 45" (114 cm) above the cooking surface
and located anywhere over the appliance cooking area.
The nozzle must be aimed at the center of the cooking
area. See Figure 3-16.
MAXIMUM HEIGHT
45" (114 cm)
COVER MUST j ..'V NOZZLE NOT INTEFERE PLACEMENT WITH NOZZLE \ j' ./ i AREA DISCHARGE
MINIMUM HEIGHT
24(61 cml
Figure 3-16.
Tilting Skillet I Brazing Pan
Model N-2HP Nozzle
GRIDDLE PROTECTION
Deep Fat Fryer Protection
Nozzle: N-2HP (2 Flow Point)
Coverage: 20.25' (51 cm) x 24" (61 cm)
Nozzle Ht: 24" (61 cm)-45" (114 cm)
Placement: Anywhere over the surface of the
appliance cooking area.
Aim point: Center of appliance.
The Model N-2HP nozzle is a two (2) flow point nozzle
that can protect a deep fat fryer with a maximum
cooking area of 20.25" (51 cm) wide by 24" (61 cm)
deep. The nozzle must be located 24" (51 cm) to 45"
(114 cm) above the cooking surface and located
anywhere over the appliance cooking area. The nozzle
must be aimed at the center of the cooking area. See
Figure 3-15.
NOZZLE TO BE LOCATED
WITHIN THEPERIIETER
OF ThE KSZARD
MAXIMUM HEIGHT 45' (114 cm)
NOZZLE
PLACEMENT
AREA
MINIMUM HEIGHT 24" (61 cm)
NOZZLE AIMED
CENTER OF
HAZARD AREA
1
MAXIMUM
WIDTH: 24" (61 cm)
MAXIMUM
LENGTH: 20.25(51
Standard Griddle: 42"(107 cm) x 30" (76 cm
Figure 3-15.
20.25" (cm) x 24" (cm) Deep Fat Fryer
Model N-2HP Nozzle
Fryers Reguirini Multiple Nozzles
Fryers that exceed the coverage of a single nozzle can
be protected with multiple nozzles. The fryer must be
divided into equal sized modules, so that each module
does not exceed the maximum coverage allowed for a
single nozzle.
CAUTION
The maximum size fryer that can be modularized is
864 square inches (5,574 sq. cm).
BPN: BFR-TM
Nozzle: N-i LP (1 Flow Point)
Coverage: 42" (107 cm) x 30" (76 cm) Maximum
Nozzle Ht: 24" (61 cm) —48" (122 cm)
Placement: Directly over the edge of the cooking area.
Aim Point: 6" (15 cm) from center of appliance in-line
with the nozzle.
The Model N-ILP nozzle is a one (1) flow point nozzle
that can protect a griddle with a maximum cooking area
of 42" (107 cm) wide by 30" (76 cm) deep. The nozzle
must be located 24" (61 cm) to 48" (122 cm) above the
cooking surface and positioned directly above the edge
of the cooking area. The nozzle must be aimed 6" (15
cm) from the center of the cooking area in-line with the
nozzle. See Figure 3-17.
ULEX 6885 ULC-EX 6885
January 1, 2013
Chapter 3 — System Design
Page 3 - 8
Revision 5
NOZZLE TO BE LOCATED
I ON THE PERIMETER OF The Model N-ILP nozzle is a one (1) flow point nozzle
MAXIMUM HEIGHT I THEHAZARD
48(122cm) that can protect a griddle with a maximum cooking area
of 48" (122 cm) wide by 30" (76 cm) deep. The nozzle
must be located 30" (76 cm) to 43" (109 cm) above the NOZZLE -
PLACEMENT - - cooking surface, on the centerline of the appliance and
AREA -- 6" (15 cm) off the either short edge. The nozzle must be
MINIMUM HEIGHT aimed 3" (7.6 cm) from the center of the cooking area
24(61 cm)in-line with the nozzle. See Figure 3-18.
Extra Large Griddle — 60" (152 cm) x 30"
(76 cm)
NC ZZLEAlMEONI16n,I FROM CENTER
OFHAZAROAREA Nozzle: N-2LP (2 Flow Point) INLINE MTH NOZZLE -
-
MAXIMUM 15cm) > LENGTH: Coverage: 60" (152 cm)x 30" (76 cm) Maximum 42" (107 cm) MAXIMUM
WIDTH: 30' (76 cm)
Nozzle Ht: 24" (61 cm) —48" (122 cm)
Figure 3-17. Placement: Directly over the edge of the cooking area.
Standard Griddle: 42" (107 cm) x 30" (76 cm) Aim Point: 8" (20 cm) from center of appliance in-line Model N-ILP Nozzle with the nozzle.
Large Griddle - 4811 022 cm) x 30" (76 cm)
Nozzle: N-1LP(1 Flow Point)
Coverage: 48" (122 cm) x 30" (76 cm) Maximum
Nozzle Ht: 30" (76 cm)-43" (109 cm)
Placement: On the centerline of the appliance, 6" (15
cm) off the short edge.
Aim Point: 3" (7.6 cm) from center of appliance in-line
with the nozzle.
The Model N-2LP nozzle is a two (2) flow point nozzle
that can protect a griddle with a maximum cooking area
of 60" (152 cm) wide by 30" (76 cm) deep. The nozzle
must be located 24" (61 cm) to 48" (122 cm) above the
cooking surface and positioned directly above the edge
of the cooking area. The nozzle must be aimed 8" (20
cm) from the center of the cooking area in-line with the
nozzle. See Figure 3-19.
NOZZLE TO BE LOCATED ON
MAXIMUM HEIGHT THE PERIMETER OF THE
48(122cm) HAZARD
NOZZLE
PLACEMENT I MAXIMUM HEIGHT AREA
MINIMUM HEIGHT
24 (61 cm)
NOZZLE
I
A4
(109 cm)
I PLACEMENT
I AREA
MINIMUM HEIGHT
30' (76 cm)
MAXIMUM
(15cm) LENGTH: 48" (122
MAXIMUM
WIDTH:
30" (76 cm)
Figure 3-18.
Large Griddle: 48" (122 cm) x 30" (76 cm)
Model N-ILP Nozzle
NOZZLE AIMED 8"
INL"XEETh
FROM CENTER
OF HAZARD AREA
MAXIM> MAXIMUM
LENGTH: 60
(152 WIDTH: 30(76cm)
Figure 3-19.
Extra Large Griddle: 60" (152 cm) x 30" (76 cm)
Model N-2LP Nozzle
ULEX 6885 ULC-EX 6885 BPN: BFR-TM
January 1, 2013
0
Extra Low Proximity Griddle
Nozzle: N-2W (2 Flow Point)
Coverage: 42" (107 cm) x 30" (76 cm) Maximum
Nozzle Ht: 2" (5 cm) - 10" (25 cm)
Placement: Over any corner, at a 450 angle to the
surface.
Aim Point: At cooking surface, equal distance from
both edges.
The Model N-2W nozzle is a two (2) flow point nozzle
that can protect a griddle with a maximum cooking area
of 42" (107 cm) wide by 30" (76 cm) deep. The nozzle
must be located 2" (5 cm) to 10" (25 cm) above any
corner of the cooking surface and positioned on the
edge of the cooking area of the griddle. The nozzle
must be aimed at the point over the cooking surface
equal distance from both edges. See Figure 3-19a.
MAXIMUM HEIGHT
10(25cm)
NOZZLE
PLACEMENT
AREA
Chapter 3 - System Design
Page 3 - 9
Revision 5
of 60" (152 cm) wide by 30" (76 cm) deep. The nozzle
must be located 10" (61 cm) to 30" (122 cm) above the
cooking surface and positioned 0" to 3" (7.6 cm) outside
the short side edge of the cooking area of the griddle.
This allows the nozzle to be placed anywhere over the
short edge and up to 3" (7.6 cm) outside of the short
edge of the appliance. The nozzle must be aimed at the
point one-quarter the longest side length (1/4L) from the
griddle short edge, in-line with the nozzle. See Figure
3-19b.
MAXIMUM OF 3fl
(7.6cm) FROM EDGE//
MAXIMUM HEIGHT
30' (76 cm)
NOZZLE
PLACEMENT
AREA
10(25cm)
MAXIMUM
MAXIMUM LENGTh)L(: 6')" (152cm)
W 10 TN: 30 (76 cm)
Z! = '
MAXIMUM
LENGTH(L): 42" (107 cm)
MAXIMUM >_
WIDTH: 30 (76 cm)
Figure 3-19b.
60" (152 cm) x 30" (76 cm) Griddle
Model N-2W Nozzle
CHARBROILER PROTECTION
Figure 3-19a.
42" (107 cm) x 30" (76 cm) Griddle
Model N-2W Nozzle
Low Proximity Griddle
Nozzle: N-2W (2 Flow Point)
Coverage: 60" (152 cm) x 30" (76 cm) Maximum
Nozzle Ht: 10" (25 cm) - 30" (76 cm)
Placement: From 0" to 3(7.6 cm) outside the short
side edge of the cooking area,
Aim Point: One-quarter the length (114L) of the
longest side, in-line with the nozzle.
The Model N.2W nozzle is a two (2) flow point nozzle
that can protect a griddle with a maximum cooking area
Radiant Charbroiler
Nozzle: N-1 HP (1 Flow Point)
Coverage: 36" (91 cm) x 24" (61 cm) Maximum
Nozzle Ht: 30" (75 cm) —48" (122 cm)
Placement: Anywhere over the surface of the
appliance.
Aim Point: Center of appliance.
The Model N-IHP nozzle is a one (1) flow point nozzle
that can protect a radiant charbroiler with a cooking area
of 36" (91 cm) wide by 24" (61 cm) deep. The nozzle
must be located 30" (76 cm) to 48" (122 cm) above the
cooking surface and positioned anywhere over the
cooking area. The nozzle must be aimed at the center of
the cooking area. See Figure 3-20.
BPN: BFR-TM ULEX 6885 ULC-EX 6885
January 1, 2013
/NOZZLE TO BE
LOCATED WITHIN
THE PERIMETER OF
THE HAZARD
Chapter 3 - System Design
Page 3 - 10
Revision 5
NOZZLE TO BE
LOCATED WTHIN
MAXIMUM HGGHT THE PERIMETER OF
48 (122 em) AZARD MAXIMUM HEIGHT
40" (101 cm)
NOZZLE
PLACEMENT NOZZLE AREA PLACEMENT -
AREA MINIMUM HEIGHT
30 (76 cm) MINIMUM HEIGHT
24" (61 cm)
MAXIMUM
WIDTH: 24" (61 ED
CENTER OF
HAZARD AR
CENTER OF
HAZARD AREA
LENGTH: 36)91 cm) V IMDTh: 24 (El cm)
Figure 3-20.
Radiant Charbroiler
Model N-IHP Nozzle
Lava Rock Charbroiler Protection
Nozzle: N-2HP (2 Flow Point)
Coverage: 24" (61 cm) x 24" (61 cm) Maximum
Nozzle Ht: 24" (61 cm)-40" (102 cm)
Placement: Anywhere ovethe surface of the
appliance.
Aim Point: Center of appliance.
The Model N-2HP nozzle is a two (2) flow point nozzle
that can protect a lava rock charbroiler with a cooking
area of 24" (61 cm) wide by 24" (61 cm) deep. The
nozzle must be located 24" (61 cm) to 40" (102 cm)
above the cooking surface and positioned anywhere
over the cooking area. The nozzle must be aimed at the
center of the cooking area. See Figure 3-21.
LENGTH:
24" (61 ca
Figure 3-21.
Lava Rock Charbroiler
Model N-2HP Nozzle
Upright Broiler Protection
Nozzle: N-1 LP (1 Flow Point)
Coverage: 36" (91 cm) x 24" (61 cm) Maximum
Nozzle Ht: Upper corner of broiling chamber.
Placement: Positioned in the corner of the front
opening of the appliance.
Aim Point: Center of cooking grate.
The Model N-ILP nozzle is a one (1) flow point nozzle
that can protect an upright broiler (salamander broiler)
with a cooking area of 36" (91 cm) wide by 24" (61 cm)
deep. The nozzle must be located in the top front
corner of the broiler and aimed at the center of the
cooking grate. See Figure 3-22.
ULEX 6885 ULC-EX 6885 BPN: BFR-TM
January 1, 2013
Chapter 3 - System Design
Page 3 - 12
Revision 5
COVERAGE SUMMARY TABLE
'0
COVERAGE COLOR FLOW NOZZLE HT. PLACEMENT AIMING APPLICATION NOZZLE PAGE Inches (cm) BAND POINT Inches (cm) Inches (cm) Inches (cm)
DUCT, RECTANGLE UP 1050(127) PER.; MAX
SIDE OF 16-3/4 (43) N1LP RED 1 1-6 (2.5-15) INTO
DUCT OPENING CENTERED IN DUCT CENTER OF DUCT 3-1
DUCT, SQUARE UP TO 50 (127) PER.; MAX N-ILP RED 1 1-6 (2.5-15) INTO CENTERED IN DUCT CENTER OF DUCT 3-1 SIDE OF 12-1(2(32) DUCT OPENING
DUCT, ROUND UP 1050(127) CIRCUM N-ILP RED 1 1-6 (2.5.15) INTO CENTERED IN DUCT CENTER OF DUCT 3-1 [16 (41) DIA.] DUCT OPENING
DUCT, RECTANGLE UP TO 150 (381) PER.; N-2W WHITE 2 0-6 (0.15) INTO CENTERED IN DUCT CENTER OF DUCT 3.1 MAX. SIDE OF 50 (12 DUCT OPENING
DUCT, SQUARE UP 10150(381) PER.; N-2W WHITE 2 0-6 (0-15) INTO CENTERED IN DUCT CENTER OF DUCT 3-1 MAX. SIDE OF 37-1/2(95) DUCT OPENING
DUCT, ROUND UP TO 150 (381) CIRCUM N-2W WHITE 2 0-6 (0-15) INTO CENTERED IN DUCT CENTER OF DUCT 3-1 [47-1(2(121) DIA.] DUCT OPENING
PLENUM, SINGLE 12 FT (3.7 rn) IN LENGTH; N-1HP BLUE 1
1/3 H FROM TOP;
2(5) IN FROM 0-6 (0-15) FROM END OPPOSITE END OF 3-3 BANK 4 FT (1.2 m) IN WIDTH FILTER BOTTOM PLENUM
PLENUM, "V' BANK 12 FT (3.7 m) IN LENGTH; N-IHP BLUE 1 1/3 H FROM TOP; 0.6 (0.15) FROM END OPPOSITE END OF 3-3 4FT(i.2m)INWIDTH 1/2W PLENUM
RANGE, TWO 3(7.6) FROM FRONT OR 6(15) FROM
BURNER 12(30.5) X 24 (61) N-1LP RED 1 • 16 (41) -30 (76) BACK EDGE ON C'LINE OPPOSITE EDGE ON 3-3
(Back-shelf) * C'LINE
RANGE, FOUR 24 (61)X 24 (61) N-1LP RED 1 30 (76) -40 (102) WITHIN 3(7.6) OF CENTER OF 3-4 BURNER CENTER APPLIANCE
RANGE, FOUR
BURNER. LOW
PROXIMITY 24 (61)X 24 (61) N-2W WHITE 2 16 (41) -30(76) * CENTER OF APPLIANCE CENTER OF
APPLIANCE 3-4
(Back.shelf)*
RANGE, SIX BURNER 36 (91) X 24 (61) N-21L P YELLOW 2 35(89) .43(109) CENTER OF APPLIANCE CENTER OF 3-4 APPLIANCE
RANGE/GRIDDLE 30 (76)X 24 (61) N-1LP RED 1 30(76)- 40 (102) WITHIN 3(7.6) OF CENTER OF 3-5 COMBINATION CENTER APPLIANCE
RANGE, FOUR
BURNER w/B SHELF - 24 (61)X 24 (61) N-21L YELLOW 2 30(76) -40(102) 6(15) OFF FRONT 3-6P 6(15) from BACK
HIGH PROXIMITY EDGE EDGE
WOK 12 (30.5) TO 30 (76) DIA. N-1 HP BLUE 1 30 (76)- 48 (122) ANYWHERE OVER
HAZARD AREA BOTTOM CENTER 3-6
DEEP FAT FRYER, 20.25(51) X 24 (61) N-2HP GREEN 2 24 (61)- 45 (114) ANYWHERE OVER CENTER OF 3-7 SINGLE VAT HAZARD AREA APPLIANCE
TILTING SKILLET, 20.25(51) X24 (61) N-2HP GREEN 2 24(61)- 45 (114) ANYWHERE OVER CENTER OF 3-7 BRAISING PAN HAZARD AREA APPLIANCE
GRIDDLE,
STANDARD 42 (107) X 3 (76) N-1LP RED 1 24(61)- 48 (122) DIRECTLY OVER EDGE
OF HAZARD AREA
6(15) FROM
CENTER, IN-LINE 3-7
WITH NOZZLE
6(15) OUTSIDE OF 3(7.6) FROM
GRIDDLE, LARGE 48 (122) X30 (76) N-1 LP RED 1 30(76)- 43 (109) SHORTER EDGE OF CENTER, IN-LINE 3-8 HAZARD AREA ON WITH NOZZLE C'LINE
GRIDDLE, EXTRA 60 (152) X30 (76) N-2LP YELLOW 2 24(61)- 48 (122) DIRECTLY OVER EDGE 8(20) FROM
CENTER, IN-LINE 3-8 LARGE OF HAZARD AREA WITH NOZZLE
GRIDDLE, OVER ANY CORNER AT AT COOKING
STANDARD, EXTRA 42 (107) X 30 (76) N-2W WHITE 2 2 (5) -10 (25) A 450 ANGLE TO SURFACE, EQUAL 3-9 LOW PROXIMITY COOKING SURFACE DISTANCE FROM
EDGES
GRIDDLE, LOW
PROXIMITY 60(152) X30 (78) N-2W WHITE 2 10(25) —30 (76) 0 to 3(7.6cm) outade 1/4 Length of the
longest side, in-line 3-9 the short side edge with _the _nozzle
CHARBROILER, 36 (91) X 24 (61) N-1HP BLUE 1 30(76)-48(122) ANYWHERE OVER CENTER OF 3-9 RADIANT HAZARD AREA APPLIANCE
CHARBROILER, LAVA 24 (61)X 24(61) N-2HP GREEN 2 24(61)- 40(102) ANYWHERE OVER CENTER OF 3-10 ROCK HAZARD AREA APPLIANCE
CHARBROILER, UPPER CORNER FRONT CORNER OF CENTER OF UPRIGHT 36 (91) X 24 (61) N-1 LP RED I OF BROILING OPENING TO BROILER COOKING GRATE 3-10 (SALAMANDER) CHAMBER CHAMBER
* Coverages can be used when a range with a back-shelf or other type of obstruction, as long as the discharge pattern is not affected.
** Cover must not interfere with nozzle discharge.
For the High Proximity Back-shelf coverage the shelf shall not exceed more then 11(28 cm) over the back edge of the burners and be a minimum of 16" (41
cm) from the top of the appliance.
ULEX 6885 ULC-EX 6885 BPN: BFR-TM
January 1, 2013
cioz 'i kienu
9999 X3-31fl 9989 X1fl VLLth9 :Nd
seizzou () oml ue9dv49q
soqe o jeqwnu eqj io wess jad peoje
soqe jejol aqj PJMO4 junoo ION oa Bulwle
io ezzou aqj le pesn so;depe 18AIMS w (s)MoqI
e6uei Jo Je,cJ4 deep OM e 6u1io94oJd
U8M Aidde A1N0 suaweiinbai 6uidid wnwiuiJ :e;oj
s;ueweJunbGj bU!cl!d WflWiUflJ
8 1W 009 SI OèH8 JO 9I -Id8 944 UO
peMOe Budd (ao ww vLI) 81€ 40 ewnIOA ie;oi
'Jeewe!p Jallews 01 ja6je
WOJ SUflJ sieMe 6uidid o eizzou eqj qoeei
Aqqj se eseejoep 01 e.ie sezis pue JepuiiAo eqj o
sesojo eq Isnw adid Je4ewe1p Ise6jej eq wesAs
ewes 9q4 Ui pesn si l5uidid pazis juejagp ueuJ\\ L
4U!Od e6ieqosip Isel eqj Ised
spuexe 48q4 6uidid io jnOAel 6U!d!d aqj U! juiod MOI
e iaqie 'se qons 'elElnwnooe o p!nbil MOB PiflOM
1eqj adid o uoipes e se peuiep si dei,, '' :e;oj
wesAs 6U!did 9q4 ui paoe eie sde ON 9
(w 90) 1991 Z si eull Aiddns
eqj eoqe ejzzou Aue 40 es!i IeOIi.19A wnwixew eq
w919,cs 6uidid aqj ut
uiod Isamol io lseqBiq eqj pue 1,911no uej .io ezzou
seqiq eqj pue 1911no )jU4 ueeeq eoueJejip
u014ene19 wnwixew eqj ieqe Si 5114 '(w c) 1994
01. Si eU!j iddns eqj 4o asii I3I1J9A WnWIXCW eqj
'(g) 8A4 S! S8IZZOU
o Aue uaaeq soqe jo jaqwnu wnwixew eq c
wnwixew sMoqe 9 0I9 1.10 1.-8dS
wnwixew soqe o :g-g
009Z .009z 0z 0-8d9
009 009 91. S1.-d8
000Z 009Z 01. 01.-d
0001. 0091. 9 9-I9
('w) seizzoN (iw) Su!oâ W oAn Au azisewnion UM19 i°!t adid •xj
M01J
xej .I9PU!ilt3
adid 'LN
ZIS HMNIIIAO t13d ONidid ViflVgIXWJ
(lw oi. = (wflw1.) wiw
9L€ x (w 1.9) o] ewnion adid 40 -w OGL ol lenbe
si adid (ao ww 1.LI.) 8/€ JO (w i..9) 1991 o eidwx
(w11w961.) '14/lW 869 adid (co ww ) 'U! CII.
(wflw€) 'wiw 9L€ adid (00 ww VL1.) 'U! 8/C
4004 Jed
eLunOf,
saziSedid
alcIumoliv
11VHO 3010A ONidid
:eie wesAs
ed peoje soqe jo Jeqi.unu wnwixew eq
,(CIO ww
1. .io ww vL1.) g,'ç Jeqie eq Isnw 6uidid IIV
s;ueweJInbeJ bu!clld ieeueo
suiod
MO (€) 99jqj jo wnwuiw e oeq iieqs wesAs v
'(6 89) qi 09 1,
peej eq ieqs s6Uq4! 'adid eels sseiu!es .io 'peed
ewoqo 'peq o enpeqo eq lleqs ed!d 'JelieSu!
et.fl iq peqsuJn4 eq Isnw s6uiij pue adid :eON
'6uidid
euil Aiddns pue seqoueiq ueeeq uo!ou!s!p e eew
ou op pue 6u!d!d we4sAs jejol uo peseq ae sJalewejed
6uidid IIV 'pesn adid aqj jo Jeeweip aq 40 ssepie6ei
'awnion adid leuialui jejol uo peseq S! JaPU!io 4Ua6e
azis qoee JO; q;6ual adid wnw!u!w pue wnwixew eqj
S9Z15 iepuiiico Ile .io •1W 099
u9qj ssei eq jou lleqs ewnion adid wescs jejol eqj
lw 09€ uaql ssei
eq jou lleqs )JOM io 'eue 'jE)Ajl e l5uiloajoid eizzou
;sesoo eqj ejojeq ewnion 6uidid WflWUJ!W eq
0(9)
enij eq lleqs )jOM io e6uei 'jeicjj e 6uioeoid eizzou
sasoio eqj eoeq soqa o ieqwriu wnwiu!IAJ
9 UOSAO
u6!sea wasA - C iejdeq
6uisil
in eqj japun peoe OR suoie!wij GS9qj 01 suoieuen
ON 'eZIS iepuio qoee jol peqsIqe4se ueeq icpeejie
eneq seaweed Buidid wnw!u!w pue wnwixew 'adA
pejeeu!6ue-ejd eqj 40 Si we45,cs eqj asneoe 'wesi9
uoissejddng ej!d iespij uaqopj 4uewd!nb3 eii
eicaone eq jol Niomlau 6uidid eqj u6isep 01 Ajesseoeu
ee 1eqj suoijej!wil §uidid pe!eep suIeuoo uoqoes siq
1. SNOIIVJJINI1 0N1d1d
Chapter 3 - System Design
Page 3 - 14
Revision 5
DETECTOR PLACEMENT
Detectors (fusible links) are required to be placed in the
air stream of each appliance (one detector per
appliance) and in the opening of the exhaust duct(s) of
protected ventilation hoods. Detectors shall be located
in the plenum area of the ventilation hood behind the
filters, which provide protection for the detection system.
Exhaust Duct Detector Placement
Each exhaust duct must have at least one (1) detector
installed. The detector is to be centered in the duct
entrance and no more than 12" (30.5 cm) into ductwork.
Cooking Appliance Detector Placement
Each cooking appliance with a continuous cooking
surface area of less than 48" (122 cm) x 48" (122 cm)
must be protected by one (1) detector. The detector is
to be located over the surface of the appliance and in its
air stream when the ventilation system is turned on.
Cooking appliances with continuous cooking surfaces
larger than 48' (122 cm) x 48" (122 cm) must be
protected by multiple detectors, using one detector for
every 48" (122 cm) x 48" (122 cm) of continuous
cooking area.
Exception: If a cooking appliance or appliances are
located under a duct opening where a detector has
been mounted, it is not necessary to utilize an additional
detector as long the duct detector is not more than 12"
(30.5 cm) into the duct opening. See Figure 3-26.
APPLIANCE APPLIANCE APPLIANCE APPLIANCE
COVERED COVERED COVERED COVERED
BY BY BY BY
DETECTOR DETECTOR DETECTOR DETECTOR
A B B C
Figure 3-26.
Proper Detector Placement
Appliances and Duct
ULEX 6885 ULC-EX 6885 BPN: BFR-TM
January 1, 2013
Buckeye KITCHEN MISTER Coverage Summary Sheet
This summary sheet is provided as a quick reference, a complete understanding of the technical manual (BFR-TM) is required. The most current
Buckeye Kitchen Mister Restaurant Cooking Area Fire Suppression System Technical Manual (Part Number: BFR-TM) supersedes this reference sheet. It
Is essential that this reference sheet be compared with the current technical manual before using. Dimensions given in inches (cm) unless otherwise noted.
DUCT, SMALL [50" (127) MAXIMUM PERIMETER] DUCT, LARGE 1150" (381) MAXIMUM PERIMETER]
NOZZLE: N-1LP NOZZLE: N-2W
FLOW PTS.: 1 FLOW PTS,: 2
COLOR BAND: RED COLOR BAND: WHITE
DUCT DUCT NOZZLE TI NOZZLE TIP
LIP
8(1 5) "
NOZZLE NOZZLE
112 W
T IN NOZZLE ~TIP NOZZLE
112
w IN
HOOD/PLENUM
TIP
L
L
LONGEST SIDE: 16-3/4" (43)
____________ TIP
LONGEST SIDE: 50' (127) HOOD/PLENUM
PLENUM, SINGLE & 4 F —i---- r-113H
"V" BANK ,.-"1.2M) 112W
NOZZLE:
FLOW PTS.: 1 COLOR BAND This Section
mA,
V BANK Intentionally 12 FT 1/3H________
H 12'(54
Blank
12
7M
rs
MAX.
SINGLE BANK
RANGE, TWO BURNER CAN BE USED WITH RANGE, FOUR BURNER, RANGE, FOUR BURNER,
(LOW PROXIMITY) BACK-SHELF. SHELF
MUST NOT (HIGH PROXIMITY) (LOW PROXIMITY)
NOZZLE: N-ILP INTEFERE WiTh
NOZZLE DISCHARGE NOZZLE: N-1LP MAX. HEIGHT PLACEMENT:
NOZZLE: N-2W OF "GE
FLOW PTS.: I FLACEMENT: FLOW PTS.: I FLOW P15.: 2 — MAX. HEIGHT: 50" (78)
COLOR BAND: THIN 3' (1.6) COLOR BAND: COLOR BAND: WHITE RED AIM: 6'(lS)FROM RED —MIN. HEIGHT: 18" (41)
MAX. HEIGHT: OPPOSITE EDGE (78) AIM: CENTER 30" (76) ON LONG AIM CANBEUSEOWWI OF RANGE
MIN IEIGIcr• CENTER
LINE CENTER OF BAb1-SHELF. SHELF MUST NOT INTEFERE
,
jIGHT:0FCEjR
RANGE NTH NO
6" (15) DISCHARG
MAX HA )D MAX
WIDTH: 24 (61) B ER TO URN io BURNER BURNER BURNER LENGTH: 1? (308) :
•
BURNER
LENGTH: BURNER WIDTH: LENGTH 24 (61) 0 TO BURNER
PLACEMENT; 24" (61) 24"(61) 0TH: 24'
FROM FRONT OR BACK EDGE, ON ______________ LONG CENTER LINE _____________________________________________________ (81)
RANGEJGRIDDLECOMBINATION RANGE, SIX BURNER PLACEMENT: SHELFWER14NOIIO RANGE, WITH BACKSHELF,
CENTER OF RANGE NOZZLE: N-I LP
HEIGHT: NOZZLE: N-2LP FLOW PTS.: 43(109)
FLOW
COLOR BAND' MAX 40' I102I— FLOW PIS.: 2 COLOR BAND : - . : MIN HEIGHT RED HEIGHT:LACE ME I I . COLOR BAND:
YELLOW 35 (89) 43" (102) WITHIN 3' (7.6) MIN. HEIGHT.—YELLOW
MIN. HEIGHT: OF CENTER
IA CENTER 30(76) AIM: CENTER OF MINIMUM OF RANGE NGE-GRIDDLE
RECRE](HIGHPROMITY)
AIM; 6'(15) SHELFHEIGHT
NOZZLE
:N-2LP _jHEj
,
FROM BACK 10' (411. EDGE ON MAX12* CENTER-LINE
(30.5) (IS)
BURNER TO 0 <Z URNEREDGE
TO BURNER
BURNER 0 BURNERTO MAX. LEN TN: MAX WIDTH:
24 (81) BURNER EDGE 0'I2Z5) EDGE; 24 (81) CAN BE
USED LENGTH: 38" (91) BURNER 30' (76) TO BURNER 0' WITHOUTA WIDTH: 24" (61) EDGE: 24" (611 (15) BACK-SHELF ___________________________
DEEP FAT FRYER, LG. SINGLE VAT TILTING SKILLET
_
NOZZLE: N-2HP PLACEMENT: NOZZLE: N-21HP HAZARD COVERAGE AREA:
20.25"(51)x24"(61) FLOW PTS.: 2 WITHIN THE FLOW PTS.: 2
COLOR BAND: '-PERIMETEROF COLOR BAND:
GREEN THE HAZARD GREEN COVER MUST
FOR
NOT INTEFERE & MAX. WITH NOZZLE ;MIN. This Section MAX. HEIGHT 45"(114) / DISCHARGE
MIN. HEIGHT: 24'(61)
NOZZLE HEIGHTS, / POSITION AND AIM Intentionally
AIM: CENTER
OF HAZARD
/ POINT REFER TO
/ FRYER NOZZLE Blank
AREA PARAMETERS
Note:
Total hazard
____ area can not MAX. WIDTH: exceed 864 In' MAX LEN T 24'(61) (5,574 2), 20.28" (51
BPN: P1S10374 REV. 5; DATE: JANUARY 1, 2013
LENGTH:
36'(91) WIDTH:
24'(61)
AIM: CENTER OF
HAZARD AREA
MAX LENGTH:
24' (61)
24' (61)
AM:ATcENTENOF '
NOR 801mM
MAX
- HEIGHT:
48' (122)
MIN.
-HEIGHT;
30' (76)
PLACEMEN1
WITHIN THE
PERIMETER
OF THE
HAZARD
X.WOKDIA.:30
(.WOK DIAL: 12
WOK
NOZZLE:
N-1HP
FLOW
PTS.: I
COLOR
BAND:
BLUE
Buckeye KITCHEN MISTER Coverage Summary Sheet
This summary sheet is provided as a quick reference, a complete understanding of the technical manual (BFR.TM) is required. The most current
Buckeye Kitchen Mister Restaurant Cooking Area Fire Suppression System Technical Manual (Part Number: BFR-TM) supersedes this reference sheet. It
Is essential that this reference sheet be compared with the current technical manual before using. Dimensions given in Inches (cm) unless otherwise noted.
GRIDDLE, STANDARD [42"(107) MAX.]
NOZZLE: N-ILP
FLOW PTS,: I
COLOR BAND:
RED PLACEMENT: ON
THE PERIMETER
OF
AIM:8'(15) MAX. HEIGHT: FROM CENTER (122) OF HAZARD AREA. INUNE -MIN. HEIGHT: WIN NOZZLE
•
OF THE Z
A
24'(81)
MAX. LEN :
42' (7) MAX, DTH:
30'(76)
GRIDDLE, XLARGE [60" (152) MAX.]
NOZZLE: N-2LP PLACEMENT: ON
FLOW PTS,: 2 THE PERIMETER
COLOR BAND: OF T HAZARD
YELLOW
-HEIGHT:
NM: 6(35)
FROM CENTER MIN. OF=
AR
48. (122)
HE
HEIGHT:
WITH NOZZLE 24'(81)
MAX LEN
60'(152) AI WIDTH:
)
MAMUMOF GRIDDLE, LOW 3(7A)//'.. PROXIMITY MAXIMUM MAXIMUM
HEIGHT: NOZZLE: N-2W 35' (18) FLOW PIS.: 2
110551.! OLOR BAND WHITE PI.A55MENT
NASHUA HEIGHT: 1E'(28)
kLENGTKL)
WIDTH(P4
35' (18>
RADIANT CHARBROILER
NOZZLE: N.1HP .N PLACEMENT: WITHIN
FLOW PTS.: I ". THE PERIMEISROF
COLOR BAND: THE HAZARD
BLUE MAX
HEIGHT
-48'(122)
AIM: CENTER HEIGHT OF HAZARD
AREA -
GRIDDLE, EXTRA I
): PROXIMITY MAXIMUM NOZZLE: N-2W HEIGHT 10'(25( FLOW PTS.: 2 I NOZZLE PLACEMENT 'SHALL 05 ABOVE COLOR BAND: I
MINMUM %4
ANY
00
WHITE
HEIGHT
2'ISI
L'W
MAXIMUM MAXIMUM L%) WIOTh('A 30' (78)
LAVA ROCK CHARBROILER
NOZZLE: N-2HP
FLOW P18.: 2
COLOR BAND: PLACEMENT: WITHIN THE
GREEN PERIMETER OF THE HAZARD
MAX. HEIGHT
IAN HEIGHT:
FLOW PTS.:1
IL_....
COLOR BAND: RED NM CENTER OF COOKING
11
GRATE I
PLACEMENT:
TOP
CORNER OF
EN LEN,
FRONT
OPENING
36(91)
MAX. WID '24' 81)
MAXIMUM PIPING PER CYLINDER SIZE Piping Limitations:
>318"(17.1 mmOD) orl/2'(21.3mmOD)
Sch. 40 black pipe,
Minimum Piping Requirements
(Wok, Range, & DFFonly): CYLINDER MAX. FLOW MAX. PIPE VOLUME MAX. PIPE VOLBETWEEN MAX. # OF
SIZE POINTS ALLOWED (ml.) ANY TWO NOZZLES (mL) ELBOWS 'PIpe sized largest to smallest only.
'No "traps' allowed.
> Max. number of elbows between any (2) nozzles: 6
> Min.elbows before closest
nozzle: S.
> Mm. pipe volume before closest
nozzle: 360 mL.
BFR-5 5 1500 1000 20
BFR1O 10 2500 2000 25 'Max. vertical rise: 10 feet (3m). >Total system pipe volume: 600 mL. 2800* BFR-15 15 2500 25 > Max. vertical rise from nozzle to supply life: 2 feet
(0.6 m). 'Minimum number of flow points in
system: 3. BFR-20 20 2800° 2500 25
- I OtI vo'ume 01 3Iø PlPIfl9 aiowea IS ZDUU
CONDUIT AND BUCKEYE SHIELDED CABLE (BSC) LIMITATIONS {_PIPE SIZE (SCH. 40) PIPE VOLUME
FUNCTION
MAX.
CONDUIT
LENGTH
FT (M)
MAXIMUM
NUMBER
OF
CORNER
PULLEYS
MAX.
LENGTH
OF BSC
FT (M)
MAXIMUM
NUMBER OF
BENDS IN
THE BBC
(MIN. BEND
RADIUS)
BSC TO
CONDUIT
TRANSITIONS
(NUMBEROF
BSCI)
MAXIMUM
NUMBER OF
FUSIBLE
LINKSAND
HOLDERS
I WS In. (17.1 mm OD) pipe I 37.5 mL./ft. (I23mUm)
[1/2 in. (21. mm OD) pipe I 59.8 mL./ft, (196mL/m)
REMOTE CYLINDER
ACTUATION LIMITATIONS
ACTUATION
CARTRIDGE
PART
NUMBER
NUMBER OF
CYLINDER(S)
THAT CAN
BE
ACTUATED
MAX.
LENGTH OF
1/4' (0.6) OD
COPPER
TUBING
MAX.
LENGTH
OF TUBING
BETWEEN
CYLINDERS
FUSIBLE LINK LINE; CONDUIT & BSC 25(7.6) =8 35(10.7) 6 [9' (23)] 6 10
GAS VALVE LINE; CONDUIT & BSC 25(7.6) 8 - 35 (10.7) 6[9' (23)] 6 NA
RPS-M LINE; CONDUIT & BSC 25(7.6) 35(10.7) 6[9(23)] 6 NA
FUSIBLE LINK LINE; CONDUIT ONLY 150(45.7) 35 NA NA NA 20
GAS VALVE LINE; CONDUIT ONLY 150(45.7) 35 NA NA NA NA BFR-AC-S 1-3 15 FEET
(4.6 m)
3 FEET
(0.9 m) RPS-M LINE; CONDUIT ONLY 150(45.7) 35 NA NA NA NA
FUSIBLE LINK LINE; BSC ONLY NA NA 35(10.7) 6 [9" (23)] 6 10 BFR-AC-L 1-5 25 FEET
(7.6 m)
3FEET
(0.9 m) GAS VALVE LINE; BSC ONLY NA NA 35(10.7) 6(9' (23)1 6 NA
RPS-M LINE; BSC ONLY I NA NA 35(10.7) 6[9" (23)] 6 NA
BSC CAN NOT be coiled or looped when installed.
BPN: P1S10374 REV. 5 DATE: JANUARY 1, 2013
LiEyE
msII b •buckeyet.cani • Internet: hflp'Jtwww.buckeyet.com/tlre
September 17, 2008
Subject: Gyro Cooker Protection
To: Authorized Buckeye Kitchen MisterT4 Distributors
To Whom It May Concern:
Underwriters Laboratories Inc.. (UL) does not currently have a testing procedure for gyro
cookers, however, these appliances may require protection based on the judgment of
the local authority having jurisdiction. When protection is required, gyro cookers are
protected in the same manner as an upright broiler (see page 3-8 and 3-9 of the
Buckeye Technical Manual, P/N 8FRTM). One model N-ILP nozzle is used to protect a
gyro cooker with a maximum cooking area of 36' wide by 24" deep. For this application,
the nozzle is to be located in the top corner of the appliance and aimed at the bottom
center. If the appliance is equipped with doors, the nozzle must be positioned in such a
manner that the doors do not interfere with the discharge of the nozzle,
If you have any additional questions please do not hesitate to contact me.
Sincerely,
/~__ - - 0 ~Xj_
Bruce Euler
Pre-engineered Systems Manager
Buckeye Fire Equipment company
ISO 9001 Registered
M '.
0 1 ME
\1
'
E-mail; bfec@buckeyef.com Website: www.buckeyetire.com
June 29, 2017
Mr. James Wiseman
San Diego Fire Protection
Subject: Response to your inquiry regarding the applicable NFPA-96 requirements for
replacement air shut-down upon fire extinguishing system activation.
Dear Mr. Wiseman,
The NFPA-96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations,
Section 8.3.2, is the binding code requirement regarding replacement air (makeup air) shut-down during
system activation. The Kitchen Mister System, and any other restaurant area fire suppression system for
that matter, must comply with this requirement. It states:
"8.3.2 When the fire-extinguishing system activates, makeup air supplied internally to the hood shall be
shut off."
The term "internally", as sited in this section, is intended to specify that only makeup air that is supplied
directly into the hood itself (i.e., into the catch basin of the hood) is required to be shut off. Any makeup
air supplied outside of the hood itself is not required to be shut off.
I hope this information helps clarify the issue. I should point out that I am on the NFPA-96 Technical
Committee and have a very good working knowledge of both the current document and its history.
Kind Regards,
ktiAe_
William Vegso
Buckeye Fire Equipment
Buckeye Fire Equipment Company
ISO 9001-2008 Registered
of
rftfies that
sums.,
4iaizhr !Cr
11a1i±CflaflCC
X\I J)J >
r rmtn±ø-xirfl urkur ifr
iffri trehg ufrtzi ±a
thr. urh'gt ifren frr 3Et
¶J1fri uppreftrn /
L'qitipmnf 3i±r1n
in±xIL prfttrm
.hc,uranf Cauhing Area
3IEbucaftuxud rebit Mours J1Earn: 8
(Ierhficrthrn Vahb Until 09/08/2020
3Litn Nufuer
1r2stenf
Burheve Tire 3quipmenf Qlum