HomeMy WebLinkAbout1969 KELLOGG AVE; ; FPC2018-0382; PermitPERMIT REPORT
(qity of
Cdlsbad
Fire Sprinklers
Print Date: 11/03/2021
Job Address: 1969 KELLOGG AVE. CARLSBAD, CA 92008-6582
Permit Type: FIRE-Construction Commercial Work Class:
Parcel #: 2120921200 Track #:
Valuation: $275,000.00 Lot #:
Occupancy Group: Project #:
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #:
Plan Check #:
Permit No: FPC2018-0382
Status: Closed - Finaled
Applied: 11/21/2018
Issued: 12/18/2018
Finaled Close Out: 11/03/2021
Inspector:
Final Inspection:
Project Title:
Description: KELLOGG FLOWER MARKET COOLER PROJECT -SPRINKLER TI (77 HEADS)
Applicant: FPContractor:
WEST COAST FIRE PREVENTION INC WEST COAST FIRE PROTECTION
DAN AMATO 271 ROYMAR RD, # SUITE F
5416 LOGANBERRY WAY OCEANSIDE, CA 92058-1301
OCEANSIDE, CA 92057-4640 (760) 754-8472
(760) 754-8472
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $553.00
Total Fees: $553.00 Total Payments To Date: $553.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
tqL:L70 Worldwide Contacts I www.tyco-fire.com
Model DSB-2
Dry Sprinkler Boot
For Use With TFP Dry Type Sprinklers
General
Description
The TYCO Model DSB-2 Dry Sprinkler
Boot (Ref. Figure 1) is designed for use
with TFP Dry Type Sprinklers. When
properly installed, it will help close the
air gap created by the clearance hole
through a wall or ceiling through which
the dry type sprinkler has penetrated.
The DSB-2 is intended predominately
for use with clearance holes through
freezer ceiling structures. In these
types of installations, due to the greater
temperature difference between the
inside and outside of the freezer than
found with other type installations, the
potential for the formation of conden-
sation in the sprinkler and subsequent
ice build-up is increased. If this con-
densation is not controlled, ice build-up
can occur that might damage the dry
type sprinkler and/or prevent proper
operation in a fire situation.
The DSB-2 is intended to help stop the
air exchange between the inside and
outside of the freezer (or any other type
of similar construction) to help prevent
transfer of moist air into the freezer
space. The use of the DSB-2 provides
a quick and efficient means of closing
the air gap created by the dry type
sprinkler clearance hole. The DSB-2
provides the added feature of eliminat-
ing the occurrence of cracking of some
commonly used sealants, that subse-
quently allows the passage of moist air.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
L(s1ItII
The Model DSB-2 Dry Sprinkler Boot
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the NATIONAL
FIRE PROTECTION ASSOCIATION, in
addition to the standards of any other
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Technical
Data
Approvals
The TYCO Model DSB-2 Dry Sprin-
kler Boot does not require laboratory
approval to be installed in accordance
with the applicable standards of the
NATIONAL FIRE PROTECTION ASSO-
CIATION. The use of the DSB-2 does
not alter any of the applicable labo-
ratory approvals for TFP Dry Type
Sprinklers.
The 2007 edition of NFPA 13, Section
8.4.10.2 requires that dry sprinklers
connected to wet pipe sprinkler
systems protecting insulated freezer
structures, the clearance space around
the sprinkler barrel shall be sealed.
Dry Type Sprinkler Compatibility
and Technical Data Sheet
Reference
Series DS-1, Standard Response
Standard Coverage,
Pendent, Upright
and HSW ....................TFP500
Series DS-1, Quick Response
Standard Coverage,
Pendent, Upright
and HSW ....................TFP51O
Series DS-C, Standard Coverage
Concealed Pendent ............TFP515
Series DS-ECC, Extended Coverage
Concealed Pendent ............TFP518
AUGUST 2018
Series DS-1, Extended Coverage
Horizontal Sidewall ............TFP52O
Series DS-2, Standard
Coverage Pendent ............. TFP53O
Series DS-2, Extended
Coverage Pendent .............TFP54O
Series DS-3, ECOH
Horizontal Sidewall ............TFP55O
NOTE: Use of the Model DSB-2 Dry
Sprinkler Boot with non-TFP Dry Type
Sprinklers will void the warranty. Failure
may result due to dimensional differ-
ences in the outside diameter of the
barrel. The DSB-2 has not been tested
with any non-TFP Dry Type Sprinklers
with regard to fit or performance.
Physical Characteristics
The Boot is EPDM, the Strap Ties are
nylon, and the Adhesive is ethyl cyano-
acrylate based. The adhesive is formu-
lated for instant bonding of the Boot to
metal, plastic, or rubber surfaces.
Design
Criteria
There are four items to be considered:
Dry Type Sprinklers, Clearance Hole,
Exposure Length, and Sprinkler Fitting.
Dry Type Sprinklers
This Technical Data section provides
a list of all of the compatible dry type
sprinklers and their associated techni-
cal data sheets. Refer to the applicable
technical data sheet for installation and
maintenance information for the sprin-
kler being utilized.
TFP591
'ADHESIVE' 3-3/4' DIA. STRAP TIES
(953 mm) REF. (ENDS ON
OPPOSING
SIDES OF
BOOT)
2 (50,8 mm)
REF.
1-3/4 DIA.
(44,5 mm)
CLEARANCE
HOLE
INSULATED
FREEZER
STRUCTURE
V
TFP
.- DRY TYPE
SPRINKLER
FIGURE 1
TYPICAL INSTALLATION OF MODEL DSB-2 DRY SPRINKLER BOOT
WITH SERIES DS-1 DRY PENDENT SPRINKLER
TFP59I
Page 2 of 4
NOTICE
The TFP Dry Type Sprinklers must be
installed and maintained in compli-
ance with the applicable technical data
sheet. Failure to do so may impair the
performance of these devices.
Clearance Hole
The Model DSB-2 Dry Sprinkler
Boot may be used with a maximum
2-1/2 in. (63,5 mm) diameter clearance
hole (i.e., the diameter of the hole in
the ceiling or wall being penetrated by
the dry type sprinkler, Ref. Figures 1 or
2). Based on the diameter of the Dry
Type Sprinkler Barrel, the designated
maximum clearance hole will com-
pensate for non-centering of the Dry
Type Sprinkler Barrel within the clear-
ance hole. Where centering can be
maintained, a clearance hole as large
as 3 in. (76,2 mm) in diameter can be
accommodated.
NOTE: The clearance hole adjacent
to the DSB-2 cannot be larger than
2-1/2 in. (63,5 mm) diameter for a
non-concentric installation or 3 in.
(76,2 mm) diameter for a concentric
installation. Otherwise, the DSB-2
cannot perform as intended by closing
the air gap.
NOTE: Clearance holes greater than
specified cannot be filled in with foam
insulation, etc. In order for the DSB-2
to be effective in closing the air gap it
must seat and seal against the smooth
material of the ceiling or wall.
Exposure Length
When Dry Sprinklers are to be used in
wet pipe sprinkler systems protecting
areas subject to freezing temperatures
(e.g., sprinkler drops into freezers), con-
sideration must be given to the appro-
priate length of the sprinkler that will
prevent freezing of the water in the con-
necting pipes due to conduction. When
the temperature surrounding the wet
pipe sprinkler system is maintained at
a minimum temperature of 40°F (4°C),
the following are the minimum recom-
mended lengths between the face of
the sprinkler fitting and the outside sur-
face of the protected area (i.e., length
exposed to minimum ambient tempera-
ture of 40°F (4°C) - Ref. Figure 3):
12 inches (300 mm) when the tem-
perature within the protected area is
-20°F (-29°C)
18 inches (450 mm) when the tem-
perature within the protected area is
-40°F (-40°C)
24 inches (600 mm) when the tem-
perature within the protected area is
-60°F (-51°C)
For protected area temperatures
between those given above, the
minimum recommended length from
TFP59I
Page 3 of 4
SPRINKLER
FITTING
Ir ' EXPOSURE LENGTH
'°B
-
2 (SEE DESIGN CRITERIA
SECTION)
I1
hi1 1iI TFP
DRY TYPE
SPRINKLER
FIGURE 3
EXPOSURE LENGTH
TO WET
SYSTEM
SPRINKLER
FITTING
(SEE DESIGN SIDE CRITERIA OUTLET SECTION) PLUGGED
DSB-2
S]L)~J
FIGURE 4
SPRINKLER FITTING IN HEATED AREA
DRY RUN
SYSTEM OUTLET
PLUGGED
SPRINKLER
FITTING
(SEE DESIGN
CRITERIA
SECTION)
DSB-2
FIGURE 5
SPRINKLER FITTING IN UNHEATED AREA
the face of the fitting to the outside of
the protected area may be determined
by interpolating between the indicated
values.
NOTE: The temperature within the
protected area must be based on
the lowest expected temperature.
For example: a freezer may be rated
at -20°F (-290C), yet the condenser is
emitting -30°F (-350C). The dry sprin-
kler length must be calculated based
on the lower temperature of -30°F
(-35°C).
Sprinkler Fitting
TEP Dry Type Sprinklers must be
installed in the 1 in. NPT outlet or run
of a malleable or cast iron threaded tee
as described in the applicable technical
data sheets. With reference to Figure
4 and in conjunction with use in a wet
pipe system, the sprinkler drop may be
installed as shown. The information in
Figure 4 may only be used where the
sprinkler fitting and water filled pipe
above the sprinkler fitting is not subject
to freezing. In areas subject to freez-
ing, the pipe connected to the dry type
sprinkler must be configured to allow
complete drainage as shown in Figure
5.
Installation
The TYCO Model DSB-2 must be
installed in accordance with this
section.
!FAY:IL'IIA'(cI
The Adhesive contains cyanoacrylate
ester. Irritation will occur when inhaled.
This adhesive bonds skin in seconds.
Contact through clothing may cause
bums. EYE IRRITANT
Always refer to the Material Safety Data
Sheet for additional adhesive handling
recommendations. The Material Safety
Data Sheet should be obtained from
the adhesive manufacturer via their
web site noted on the adhesive con-
tainer label before using the adhesive.
In case of skin contact, flush with
water, and for eye contact seek medical
attention.
Provide adequate ventilation in area
of usage. When possible ventilation
should be achieved by the use of local
exhaust ventilation and good general
ventilation. Vapors are heavier than air,
therefore, downward ventilation should
be used. When handling cyanoacrylate
adhesives, goggles or safety glasses
should always be worn. Polyethylene
gloves should be used to protect the
hands.
TFP59I
Page 4 of 4
'IY:lJII'(CI
DO NOT USE RUBBER OR CLOTH
GLOVES. RUBBER GLOVES WILL
BOND WHEN BROUGHT IN CONTACT
WITH THE ADHESIVE AND POROUS
COTTON GLOVES WILL ABSORB THE
ADHESIVE AND BOND THE GLOVES
TO THE SKIN.
Step 1. Prepare the clearance hole per
the applicable TFP Dry Sprinkler Tech-
nical Data Sheet.
Step 2. Insert the dry sprinkler through
the clearance hole and slide the Boot
over threaded inlet of the dry sprinkler.
NOTE: When installing on Series DS-2
Dry Sprinklers, the Boot will require
stretching. The use of a grooved cou-
pling gasket lubricant will ease installa-
tion. Use only a petroleum free silicone
grooved coupling gasket lubricant to
avoid freezing of the Dry Sprinkler Boot
to the Dry Sprinkler.
NOTE: When sliding the Boot over the
length of the Dry Sprinkler, sliding is
easily accomplished by slightly squeez-
ing the Boot around the cone area.
Step 3. Thread the dry sprinkler into
the sprinkler fitting per the applicable
TFP Dry Sprinkler technical data sheet.
NOTE: Refer to the sprinkler technical
data sheet for tightening torque spec-
ifications. The use of higher levels of
torque then specified may distort the
sprinkler inlet with consequent leakage
or impairment of the sprinkler.
Step 4. Clean the contact surfaces of
the Boot and the building (ceiling or
wall) structure with a damp cloth. Moist
surfaces will aid in a quick adhesion.
NOTE: Use only a cloth that has been
dampened with water. The use of other
cleaning techniques, solvents, etc.
may render the adhesive incapable of
sealing.
Step 5. Apply the provided Adhesive
to the building structure in a zig-zag
pattern. Refer to Warning regarding
the adhesive.
Step 6. Slide the Boot so that it comes
in contact with the building structure,
and then press the Boot firmly against
the building structure to help ensure
that the Adhesive is fully applied to
both surfaces.
NOTE: When sliding the Boot over the
length of the Dry Sprinkler, sliding is
easily accomplished by slightly squeez-
ing the Boot around the cone area.
Step 7. Wait two minutes to allow the
Adhesive to sufficiently cure and then
apply the two Strap Ties. The Strap
Ties are to be applied to the straight
section of the Boot as shown in Figure
1 and so that the ends are on opposing
sides of the Boot.
NOTE: The ties are to be pulled suf-
ficiently tight to the point that there is
no gap between Dry Sprinkler Boot
and the Dry Sprinkler. When properly
installed a paper clip or wire of similar
dimension cannot be slipped between
the Dry Sprinkler Boot and the Dry
Sprinkler.
Care and
Maintenance
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accor-
dance with local requirements and/or
national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Model DSB-2:
Specify: Model DSB-2 Dry Sprinkler Boot*, P/N 63-000-0-002
* Includes one Boot, two Strap Ties, and
1/3 oz of Adhesive (quantity of adhesive is
sufficient for installing one Boot).
1400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700
02018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
NFPA ororogoierodcwle,eofuof Natoosi Fire Pratoccon itasoatafun
Johnson •Z'0
Controls
FPC20I8-0382
1969 KELLOGG AVE
KELLOGG FLOWER MARKET COOLER PROJECT -
SPRINKLER TI (77 HEADS)
2120921200
11/21/2018
FPC20I 8-0382
Worldwide I tqca Contacts www.tyco-fire.com
Series DS-1 Dry-Type Sprinklers
56K Pendent, Upright1 and Horizontal Sidewall
Quick Response, Standard Coverage
General
Description
TYCO Series DS-1 Dry-Type Sprinklers,
5.6K Pendent, Upright, and Horizontal
Sidewall, Quick Response (3 mm bulb)
and Standard Coverage are decora-
tive glass bulb automatic sprinklers
designed for commercial use. Dry-type
sprinklers are typically used where:
pendent sprinklers are required on
dry pipe systems that are exposed
to freezing temperatures (e.g.,
sprinkler drops from unheated
portions of buildings)
sprinklers and/or a portion of the
connecting piping are exposed to
freezing temperatures; for example,
sprinkler drops from wet systems
into freezers, sprinkler sprigs
from wet systems into unheated
attics, or horizontal piping exten-
sions through a wall to protect an
unheated areas such as loading
docks, overhangs, and building
exteriors
sprinklers are used on systems that
are seasonally drained to avoid
freezing (e.g., vacation areas)
NOTICE
The Series DS-1 Dry-Type Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association (NFPA), in addition
to the standards of any authorities
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 10
having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condi-
tion. Contact the installing contrac-
tor or product manufacturer with any
questions.
The Series DS-1 Dry-Type Sprinklers
must only be installed in fittings that
meet the requirements of the Design
Criteria section.
Sprinkler
Identification
Numbers (SINs)
3/4 in. NPT:
1Y3935 -Pendent
TY3735 - Horizontal Sidewall
1 in. NPT:
1Y3235 —Pendent
TY3135 - Upright
TY3335 - Horizontal Sidewall
Technical
Data
Approvals
UL and C-UL Listed
FM Approved
NYC Approved under MEA 352-01-E
Previous New York City Approval and
MEA certification numbers apply to
product as shown in this data sheet.
In accordance with Section BC 3502
of the Construction Code, current NYC
Approvals for use in the City of New
York apply to all products that contain
UL or FM Approvals and Listings;
therefore, not all products currently
Approved for use in the City of New
York will carry an actual MEA Certifi-
cation number.
Refer to Tables A and B.
Maximum Working Pressure
175 psi (12,1 bar)
Inlet Thread Connections
3/4 in. NPT
1 in. NPT or ISO 7-R 1
Discharge Coefficient
K=5.6 gpm/psil/2 (80,6 Ipm/barl/2)
AUGUST 2018
EI!
Temperature Ratings
Refer to Tables A and B
Finishes
Sprinkler: Natural Brass, Chrome Plated,
or Signal White
Escutcheon: Signal White, Chrome Plated,
or Brass Plated
Physical Characteristics
Inlet .............................Copper
Plug............................Copper
Yoke.......................Stainless Steel
Casing .............Galvanized Carbon Steel
Insert ...........................Bronze
Bulb Seat...................Stainless Steel
Bulb...............................Glass
Compression Screw .................Bronze
Deflector .........................Bronze
Frame ............................Bronze
Guide Tube .................Stainless Steel
Water Tube .................Stainless Steel
Spring .....................Stainless Steel
Plug Spring*Stainless Steel
Sealing Assembly. Beryllium Nickel w/TEFLON
Escutcheon ...................Carbon Steel
For 3/4 inch NPT only
TFP5IO
TFP5IO
Page 2 of 10
PLUG WITH INLET
SEALING
ASSEMBLY
ME INLET
YOKE
PLUG
SPRING BAND
II
SPRING WATER
TUBE CASING
GUIDE INSERT
TUBE
BULB
/ SEAT FRAME
3 mm BULB
VENT HOLE
COMPRESSION
DEFLECTOR SCREW
FIGURE 1
SERIES DS-1, 3/4 INCH NPT, DRY-TYPE SPRINKLER
ASSEMBLY
PLUG WITH INLET
SEALING
ASSEMBLY
YOKE
SPRING INLET
BAND
WATER II
TUBE - CASING
GUIDE - INSERT
TUBE
BULB
FRAME / SEAT
3 mm BULB VENT HOLE _____
COMPRESSION
DEFLECTOR SCREW
FIGURE 2
SERIES DS-1, 1 INCH NPT AND ISO 7-R 1 DRY-TYPE SPRINKLER
ASSEMBLY
Operation
When the TYCO Series DS-1 Dry-Type
Sprinklers, 5.6K Pendent, Upright, and
Horizontal Sidewall, Quick Response
(3 mm bulb) and Standard Coverage
are in service, water is prevented from
entering the assembly by the Plug with
Sealing Assembly in the Inlet of the
Sprinkler. See Figures 1 and 2.
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter
the glass Bulb, and the Bulb Seat is
released.
The compressed Spring is then able
to expand and push the Water Tube as
well as the Guide Tube outward. This
action simultaneously pulls inward on
the Yoke, withdrawing the Plug with
Sealing Assembly from the Inlet and
allowing the sprinkler to activate and
flow water.
Design
Criteria
The TYCO Series DS-1 Dry-Type Sprin-
klers, 5.6K Pendent, Upright, and Hor-
izontal Sidewall, Quick Response
(3 mm bulb) and Standard Cover-
age are intended for use in fire sprin-
kler systems designed in accordance
with the standard installation rules
recognized by the applicable Listing
or Approval agency; for example,
UL Listing is based on NFPA 13
requirements.
Sprinkler Fittings
Install the 3/4 or 1 inch NPT Series
DS-1 Dry-Type Sprinklers in the 3/4 or
1 inch NPT outlet or run of the follow-
ing fittings:
malleable or ductile iron threaded
tee fittings that meet the dimen-
sional requirements of ANSI B16.3
(Class 150)
cast iron threaded tee fittings that
meet the dimensional requirements
of ANSI B16.4 (Class 125)
Do not install the DS-1 Sprinklers
into an elbow fittings. The Inlet of the
sprinkler can contact the interior of the
elbow, potentially damaging the Inlet
seal.
The unused outlet of the threaded tee is
plugged as shown in Figure 13.
You can also install the Series DS-1
Dry-Type Sprinklers in the 3/4 or 1 inch
NPT outlet of a GRINNELL Figure 730
Mechanical Tee. However, the use of
the Figure 730 Tee for this arrangement
is limited to wet pipe systems.
TFP5IO
Page 3 of 10
3/4 Inch NPT
TY3935 Pendent TY3935 Pendent TY3735 Horizontal Sidewall
with Top of Deflector-to-Ceiling
with Recessed Escutcheon with Standard Escutcheon Distance of 4 to 12 inches
(Figure 4) (Figure 3) (100 to 300 mm)
with Deep Escutcheon
(Figure 5)
with Standard Escutcheon
(Figure 8)
without Escutcheon
(Figure 6)
with Deep Escutcheon
(Figure 9)
without Escutcheon
(Figure 10)
Temperature
Rating
Bulb
Color Code
Finish
Natural
Brass
Chrome
Plated
White
Polyester
Natural
Brass
Chrome
Plated
White
Polyester
Natural
Brass
Chrome
Plated
White
Polyester
135°F (57°C) Orange
1,2 1,2
Blue
1*,2* 155°F (68°C) Red
(79°C) Yellow
f
(93°C)Green
(141°C)
Notes:
I. Listed by underwriters Laboratories, Inc. (maximum order length of 48 inches)
2. Listed by Underwriters Laboratories for use in Canada (maximum order length of 48 inches)
* Light and Ordinary Hazard occupancies only
TABLE A
3/4 INCH NPT SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
1 Inch NPT (and ISO 7-R 1)
TY3235 Pendent 1Y3235 Pendent TY3335 Horizontal Sidewall
with Top of Deflector-to-Ceiling
with Recessed Escutcheon with Standard Escutcheon Distance of 4 to 12 inches
(Figure 4) (Figure 3) (100 to 300 mm)
with Deep Escutcheon with Standard Escutcheon
(Figures) (Figure 8)
without Escutcheon with Deep Escutcheon
(Figure 6) (Figure 9)
TY3135 Upri9ht
without Escutcrteont without Escutcheon
(Figure 10) (Figure 7)
Finish Bulb
Natural
___________________________ Chrome White Natural Chrome White Natural Chrome White Color Code
6Temperature
Brass Plated Polyester Brass Plated Polyester Brass Plated Polyester
Orange
2 3 4
' ' '
Green
1 2 4
' ' 1, 2, 3, 4 1, 2, 4
1,2,4
1',2-,3-14 1*1 2*1 4
Red 1 Yellow
200°F (93°C)
286°F (141°C) Blue
Notes:
Listed by Underwriters Laboratories, Inc. (maximum order length of 48 inches)
Listed by Underwriters Laboratories for use in Canada (maximum order length of 48 inches)
Approved by Factory Mutual Research Corporation (maximum order length of 48 inches)
Approved by the City of New York under MEA 352-01-E
The Upright Sprinkler without an Escutcheon (TY3135) is available in I inch NPT Only
* Light and Ordinary Hazard occupancies only
** Light Hazard occupancies only
TABLE B
1 INCH NPT (AND ISO 7-R 1) SERIES DS-1 QUICK RESPONSE, STANDARD COVERAGE DRY-TYPE SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
TFP5IO
Page 4 of 10
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER
FIUING
ORDER LENGTHS:
2-3/4 to 48" 1-3/4' DIA. (69,9 to 1219,2 mm) (44,5 mm)
IN 1/4(6,4 mm)
INCREMENTS
FACE OF
CEILING
2-3/16±1/8' 3" DIA.
(55,6 ± 3,2 mm) -
(76,2 mm)
FIGURE 3
PENDENT TY3235 AND TY3935
WITH STANDARD
ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER
FITTING
ORDER LENGTHS:
3-3/4' to 48'
(95,3 to 1219,2 mm)
IN 1/4" (6,4 mm) 2-1/4' DIA.
INCREMENTS (57,2 mm)
F OF ACE .1j, ,
CEILING
mm)
FIGURE 4
PENDENT TY3235 AND TY3935
WITH RECESSED
ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER
FIlliNG
ORDER LENGTHS: 3-1/2' DIA
1/2 to 46" (88,9 mm)
(12,7t01168,4mm)
IN 1/4° (6,4 mm) 2-1/2 DIA
INCREMENTS (6 3,5
FACE OF
CEILING
4-1/4'± 1/8
(108,0±3,2 mm)
FIGURE 5
PENDENT TY3235 AND TY3935
WITH DEEP
ESCUTCHEON
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FACE OF
SPRINKLER
FITTING
ORDER LENGTHS:
5" to 48
(127,0 to 1219,2 mm)
IN 1/4 (6,4 mm)
INCREMENTS
MINIMUM
1-3/4" (44,5 mm)
DEFLECTOR
TO CEILING
FIGURE 6
PENDENT TY3235 AND TY3935
WITHOUT
ESCUTCHEON
TOP OF
DEFLECTOR
ORDER LENGTHS:
5' to 48"
(127,0 to 1219,2 mm)
IN 1/4° (6,4 mm)
INCREMENTS
FACE OF
SPRINKLER
FITTING
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
FIGURE 7
UPRIGHT TY3135
WITHOUT ESCUTCHEON
1 INCH NPT ONLY
SPRINKLER FITTING
(REFER TO DESIGN
CRITERIA SECTION)
1-314 UIPI.
(44,5 mm) CENTERLINE
OF WATERWAY
3" DIA.
(76,2 mm)
5/16"
(7,9 mm)
FIGURE 8
TY3335 AND TY3735 HORIZONAL SIDEWALL
WITH STANDARD ESCUTCHEON
ORDER LENGTHS:
1/2 to 45-3/4" (12,7 to 1162,1 mm)
IN 1/4" (6,4 mm) INCREMENTS 4-1/4" ± 1/8"
' 2-1/2" DIA. FACE OF - (108,0 ± 3,2 mm)
FACE OF (63,5 mm) fl MOUNTING
SPRINKLER
FITTING I JSURFACE
SPRINKLER FITTING !77
(88,9 mm)
3-1/2" DIA.
(REFER TO DESIGN CENTERLINE 5/16"
CRITERIA SECTION) OF WATERWAY (7,9 mm)
FIGURE 9
TY3335 AND TY3735 HORIZONAL SIDEWALL
WITH DEEP ESCUTCHEON
ORDER LENGTHS:
5-1/2" to 48" (139,7 to 1219,2 mm)
IN 1/4"(6,4 mm) INCREMENTS
FACE OF
I- SPRINKLER
FITTING
MINIMUM
2-1/4" (57,2 mm)
DEFLECTOR TO
MOUNTING
SURFACE
TFP5IO
Page 5 of 10
ORDER LENGTHS:
2-3/4 to 48" (69,9 to 1219,2 mm)
IN 1/4 (6,4 mm) INCREMENTS 2-3/8" ± 1/8
(60,3 ± 3,2 mm)
The configuration shown in Figure 12
is only applicable for wet pipe systems
where the sprinkler fitting and water-
filled pipe above the sprinkler fitting are
not subject to freezing and where the
length of the Dry-Type Sprinkler has the
minimum exposure length depicted in
Figure 11. Refer to the Exposure Length
section.
For wet pipe system installations of
the 1 inch NPT Series DS-1 Dry-Type
Sprinklers connected to CPVC piping,
use only the following TYCO CPVC
fittings:
1" x 1" NPT Female Adapter (P/N
80145)
1" x 1" x 1" NPT Sprinkler Head
Adapter Tee (P/N 80249)
For wet pipe system installations of the
the 3/4 inch NPT Series DS-1 Sprin-
klers connected to CPVC piping, use
in the 3/4" x 3/4" NPT Female Adapter
(P/N 80142).
For dry pipe system installations, use
only the side outlet of maximum 2-1/2-
inch reducing tee when locating the
Series DS-1 Sprinklers directly below
the branch line. Otherwise, use the
configuration shown in Figure 13 to
assure complete water drainage from
above the Series DS-1 Dry-Type Sprin-
klers and the branch line. Failure to do
so may result in pipe freezing and water
damage.
NOTICE
Do not install the Series DS-1 Dry-Type
Sprinkler into any other type fitting
without first consulting the Technical
Services Department Failure to use the
appropriate fitting may result in one of
the following:
failure of the sprinkler to operate
properly due to formation of ice
over the inlet Plug or binding of the
Inlet Plug
insufficient engagement of the
Inlet pipe threads with consequent
leakage
Drainage
In accordance with the minimum
requirements of the National Fire Pro-
tection Association for dry pipe sprin-
kler systems, branch, cross, and
feed-main piping connected to Dry
Sprinklers and subject to freezing tem-
peratures must be pitched for proper
drainage.
Exposure Length
When using Dry Sprinklers in wet pipe
sprinkler systems to protect areas
subject to freezing temperatures, use
5/16"
SPRINKLER FITTING (7,9 mm)
(REFER TO DESIGN CENTERLINE
CRITERIA SECTION) OF WATERWAY
FIGURE 10
TY3335 AND TY3735 HORIZONAL SIDEWALL
WITHOUT ESCUTCHEON
TFP5IO
Page 6 of 10
FACE OF
SPRINKLER - -
FITTING
EXPOSURE
LENGTH
(SEE DESIGN
DSB-2 CRITERIA
INTENDED SECTION)
FOR FREEZER
STRUCTURES
77ulci
FIGURE 11
EXPOSURE
LENGTH
STRAP TIES
J
(ENDS ON
OPPOSING
SIDES OF
BOOT)
DSB-2 BOOT
ADHESIVE
f
1-3/4 DIA.
(44,5 mm)
CLEARANCE
HOLE
INSULATED
FREEZER
STRUCTURE
DS-1
SHOWN WITH
STANDARD
ESCUTCHEON
FIGURE 14
MODEL DSB-2 SPRINKLER
BOOT WITH PENDENT SERIES
DS-1 DRY SPRINKLER
TO WET SIDE
SYSTEM OUTLET
PLUGGED
cm
DSB-2 SPRINKLER
INTENDED FITTING
FOR FREEZER (SEE DESIGN
STRUCTURES CRITERIA
SECTION)
FIGURE 12
SPRINKLER FITTING
HEATED AREA
1-3/4 DIA.
(44,5 mm)
CLEARANCE INSULATED HOLE FREEZER
ADHESIVE I STRUCTURE
DSB-2
BOOT
STRAP TIES DS-1 (ENDS ON SHOWN WITH OPPOSING STANDARD SIDES OF ESCUTCHEON BOOT)
FIGURE 15
MODEL DSB-2 SPRINKLER
BOOT WITH SIDEWALL SERIES
DS-1 DRY SPRINKLER
RUN
OUTLET
PLUGGED
SPRINKLER
FITTING TO DRY (SEE SYSTEM DESIGN
CRITERIA
SECTION)
I DSB-2
INTENDED
FOR FREEZER
STRUCTURES
ThJL"1it
FIGURE 13
SPRINKLER FITTING
UNHEATED AREA
WRENCH
RECESS
WRENCH I FLAT
0120
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 16
W-TYPE 7
SPRINKLER
WRENCH
Temperatures for Heated Areal
40°F I 50°F I 60°F Ambient Temperature
Exposed to (4°C) (10°C) (16°C)
Discharge End of Sprinkler Minimum Exposed Barrel Length2,
Inches
(mm)
40°F 0 0 0
(4°C)
30°F 0 0 0
(-1°C)
20°F 4 0 0
(-7°C) (100)
10°F 8 1 0 (-12°C) (200) (25)
0°F 12 3 0 (-18°C) (305) (75)
-10°F 14 4 1
(-23°C) (355) (100) (25)
-20°F 14 6 3
(-29°C) (355) (150) (75)
-30°F 16 8 4
(-34°C) (405) (200) 1 (100)
-40°F 18 8 4
(-40°C) (455) (200) (100)
-50°F 20 10 6
(-46°C) (510) (255) (150)
-60°F 20 10 6
(-51°C) (510) (255) (150)
Notes:
For protected area temperatures that occur between values listed above, use the next
cooler temperature.
These lengths are inclusive of wind velocities up to 30 mph (18,6 kph).
TABLE C
EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS
MINIMUM RECOMMENDED LENGTHS
TFP5IO
Page 7 of 10
Table C to determine a sprinkler's
appropriate exposed barrel length to
prevent water from freezing in the con-
necting pipes due to conduction. The
exposed barrel length measurement
must be taken from the face of the
sprinkler fitting to the surface of the
structure or insulation that is exposed
to the heated area. Refer to Figure 11
for an example.
Clearance Space
In accordance with NFPA 13, when
connecting an area subject to freez-
ing and an area containing a wet pipe
sprinkler system, the clearance space
around the sprinkler barrel of Dry-Type
Sprinklers must be sealed. Due to
temperature differences between two
areas, the potential for the formation of
condensation in the sprinkler and sub-
sequent ice build-up is increased. If
this condensation is not controlled, ice
build-up can occur that might damage
the dry-type sprinkler and/or prevent
proper operation in a fire situation.
Use of the Model DSB-2 Dry Sprin-
kler Boot, described in Technical Data
Sheet TFP591 and shown in Figures 14
and 15, can provide the recommended
seal.
Installation
The TYCO Series DS-1 Dry-Type Sprin-
klers, 5.6K Pendent, Upright, and Hori-
zontal Sidewall, Quick Response (3 mm
bulb) and Standard Coverage must
be installed in accordance with this
section.
General Instructions
The Series DS-1 Dry-Type Sprinklers
must only be installed in fittings that
meet the requirements of the Design
Criteria section. Refer to the Design
Criteria section for other important
requirements regarding piping design
and sealing of the clearance space
around the Sprinkler Casing.
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) rating to
1/8 inch (3,2 mm) for the 286°F (141 °C)
rating.
A leak-tight 3/4 inch NPT sprinkler
joint should be obtained by applying
a minimum-to-maximum torque of
10 to 20 ft.-lbs. (13,4 to 26,8 Nm).
A leak-tight 1 inch NPT sprinkler
joint should be obtained by applying
a minimum-to-maximum torque of
20 to 30 ft.-lbs. (26,8 to 40,2 Nm).
Higher levels of torque can distort the
sprinkler Inlet with consequent leakage
or impairment of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in an Escutch-
eon Plate by under or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Step 1. Install pendent sprinklers only
in the pendent position, and install
upright sprinklers only in the upright
position. The deflector of a pendent or
upright sprinkler must be parallel to the
ceiling.
Install horizontal sidewall sprinklers in
the horizontal position with their cen-
terline of waterway perpendicular to
the back wall and parallel to the ceiling.
Ensure the word "TOP" on the Deflector
faces the ceiling.
Step 2. With a non-hardening pipe-
thread sealant such as TEFLON tape
applied to the Inlet threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Wrench-tighten the sprinkler
using either:
a pipe wrench on the Inlet Band or
the Casing (Ref. Figures 1 and 2)
the W-Type 7 Sprinkler Wrench on
the Wrench Flat (Ref. Figure 16)
Apply the Wrench Recess of the
W-Type 7 Sprinkler Wrench to the
Wrench Flat.
TFP5IO
Page 8 of 10
Note: If sprinkler removal becomes
necessary, remove the sprinkler using
the same wrenching method noted
above. Sprinkler removal is easier when
a non-hardening sealant was used
and torque guidelines were followed.
After removal, inspect the sprinkler for
damage.
Step 4. After installing the ceiling or
wall and applying a ceiling finish, slide
on the outer piece of the escutcheon
until it comes in contact with the ceiling
or wall. Do not lift the ceiling panel out
of its normal position.
When using the Deep Escutcheon,
hold the outer piece in contact with the
mounting surface (ceiling or wall). Then
rotate the inner piece approximately 1/4
turn with respect to the outer piece,
to hold the Deep Escutcheon firmly
together.
Care and
Maintenance
The TYCO Series DS-1 Dry-Type Sprin-
klers, 5.61K Pendent, Upright, and Hori-
zontal Sidewall, Quick Response (3 mm
bulb) and Standard Coverage must be
maintained and serviced in accordance
with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover a
clearance hole, can delay the time to
sprinkler operation in a fire situation.
A Vent Hole is provided in the Bulb
Seat (Ref. Figures 1 and 2) to indicate
if the Dry-Type Sprinkler is remaining
dry. Evidence of leakage from the Vent
Hole indicates potential leakage past
the Inlet seal and the need to remove
the sprinkler to determine the cause of
leakage (e.g., an improper installation
or an ice plug). Close the fire protec-
tion system control valve and drain the
system before removing the sprinkler.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
DS-1 Dry-Type Sprinklers
When ordering TYCO Series DS-1
Dry-Type Sprinklers, 5.6K Pendent,
Upright, and Horizontal Sidewall,
Quick Response (3 mm bulb) and Stan-
dard Coverage, specify the following
information:
SIN:
Pendent - TY3935 or TY3235
Sidewall - TY3735 or TY3335
Upright - TY3135
5.6 K-factor
Deflector Style:
Upright, Pendent, or Horizontal
Sidewall
Quick Response, Standard Cover-
age, Dry-Type Sprinkler
Order Length:
Dry-Type Sprinklers are furnished
based upon Order Length as
measured per Figures 3 through
10. After taking the measurement,
round it to the nearest 1/4 inch
increment.
Inlet Connections:
3/4 in. NPT, 1 in. NPT, or ISO 7-R 1
Temperature Rating
Sprinkler Finish
Escutcheon Style and Finish, as
applicable
Part Number (P/N) from Table D
The Upright Sprinkler without an
Escutcheon (TY3135) is available in
1 in. NPT only.
Part Numbers are for 3/4 in. and
1 in. NPT standard order sprin-
klers. Orders for all other sprinkler
assemblies must be accompanied
by a complete description. Refer to
the Price List for a complete listing
of Part Numbers.
Sprinkler Wrench
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
Sprinkler Boot
Specify: Model DSB-2 Dry Sprinkler
Boot, P/N 63-000-0-002
This Part Number includes one (1)
Boot, two (2) Strap Ties, and 1/3 oz.
of Adhesive (a sufficient quantity for
installing one boot).
TFP5IO
Page 9 of 10
P/N*60_ XXX- X- XXX
F- SIN
H
01 Pendent with Standard TY3935
Escutcheon (3/4° NPT) (Figure 3)
02 Pendent with Deep TY3935
Escutcheon (3/4 NPT) (Figure 5)
03 Pendent with Recessed TY3935
Escutcheon (3/4° NPT) (Figure 4)
04 Pendent without TY3935
Escutcheon (3/4° NPT) (Figure 6)
05 Sidewall with Standard TY3735
Escutcheon (3/4 NPT) (Figure 8)
06 Sidewall with Deep TY3735
Escutcheon (3/4° NPT) (Figure 9)
07 Sidewall without TY3735
Escutcheon (3/4' NPT) (Figure 10)
36 Pendent with Standard TY3235
Escutcheon (1° NPT) (Figure 3)
33 Pendent with Deep TY3235
Escutcheon (1" NPT) (Figure 5)
37 Pendent with Recessed 1Y3235
Escutcheon (1 NPT) (Figure 4)
32 Pendent without TY3235
Escutcheon (1" NPT) (Figure 6)
34 Sidewall with Standard TY3335
Escutcheon (1° NPT) (Figure 8)
43 Sidewall with Deep TY3335
Escutcheon (1° NPT) (Figure 9)
44 Sidewall without TY3335
Escutcheon (1° NPT) (Figure 10)
I SPRINKLER ESCUTCHEON
FINISH FINISH1
0 CHROME PLATED SIGNAL WHITE
(RAL9003)
1 NATURAL BRASS SIGNAL WHITE (RAL9003)
2 NATURAL BRASS BRASS PLATED
SIGNAL WHITE SIGNAL WHITE
(RAL9003) (RAL9003)
9 CHROME PLATED CHROME PLATED
I TEMPERATURE
RATINGS
0 135-F (57-C)
1 155°F (68°C)
2 175-F (79-C)
3 200°F(93°C)
4 286°F (141°C)
055
082
180
187
372
480
SAMPLE
I ORDER
LENGTHS2
5.50"
8.25"
18.00"
18.75"
37.25"
48.00"
Notes:
Escutcheon Finish applies to sprinklers provided with escutcheons.
Dry-Type Sprinklers are furnished based upon "Order Length" as measured
per Figures 3 through 10, as applicable, and for each individual sprinkler
where it is to be installed. After the measurement is taken, round it to the
nearest 1/4 inch increment.
Use Prefix °l" for ISO 7-R 1 Connection (e.g., 1-60-010-4-055).
38 Upright without TY3135
Escutcheon (1" NPT) (Figure 7)
TABLED
SERIES DS-1 DRY-TYPE SPRINKLERS
PART NUMBER SELECTION