HomeMy WebLinkAbout1944 KELLOGG AVE; ; FPC2020-0185; PermitPERMIT REPORT
(Laty of
Carlsbad
Print Date: 12/07/2020
Job Address: 1944 KELLOGG AVE. CARLSBAD, CA 92008-6581
Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm
Parcel #: 2120922900 Track #:
Valuation: $0.00 Lot U:
Occupancy Group: Project U:
#of Dwelling Units: Plan U:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #:
Plan Check U:
Permit No: FPC2020-0185
Status: Closed - Finaled
Applied: 10/22/2020
Issued: 11/02/2020
Finaled Close Out: 12/07/2020
Inspector:
Final Inspection:
Project Title:
Description: BDR COMMUNICATIONS -REPLACE FIRE ALARM CONTROL PANEL, ADD CELLULAR COMMUNICATOR, CONNECT DEVICES
Applicant: FPContractor:
JOHNSON CONTROLS SECURITY SOLUTIONS JOHNSON CONTROLS SECURITY SOLUTIONS
LLC LLC
ROBERT HAUl P0 BOX 3042
3870 MURPHY CANYON RD, U STE 140 BOCA RATON, FL 33431-0942
SAN DIEGO, CA 92123-4403 (561) 226-8210
(858) 243-4901
FEE AMOUNT
FIRE Sprinkler Monitoring $383.00
Total Fees: $383.00 Total Payments To Date: $383.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1760-602-8561 1 I www.carlsbadca.gov
9tZom -5
Project:
BDR Communications
1944 Kellogg Ave.
Carlsbad, CA 92008
Sprinkler Monitoring System Replacement
Contractor:
Johnson Of(#
Controls
3870 Murphy Canyon Rd Ste. 140
San Diego, CA 92123
Contact:
Robert Haut
858-243-4901
1111:,, ,
t% G-cRtCAC. I4*4
O CLASSIFICATION — z
12
c-la
J) LICENSE No. -i&
977249
Honeywell Home Control Panels
VISTA-12 8FBPT
VISTA7 Commercial PartitiOned Fire
and Bu rglary AlarrrY COntrol Panel
The VISTA-128FPT provides the ultim ate protection
for Life and property, This commercial fire and burglary
control pa net supports up to eight partitions and up to
128 zones/points using hardwired, wireless and V-Plex
addressabletechnologies. A diverse Line of Honeywell
Home initiating devices, hotification appLiances,
communication devices, keypads, RF receivers and relays
satisfy a.wide range of installation requirements. and synagogues, banks, schools, strip mall and factory
or warehouse environments.
The VISTA-128F9PT control is suitable for fire-only
applications, as welt as foiñstallations requiring
i ntegrated fire/burglary systems. Itis the perfect solution
for medical and professional office buildings, churches
VISTA-12F8PT is compatible with a number of Alarm Net@
comm unication products for alarm reporting, uploading!
downloadi no and ResldeoTotal Connect Remote Services.
i—ri nrc' !_c_&II .r-tL3
a Eight hardwired zones standard,
expandable to 120 V-Plex
add ressable points/zones or
128 wireless points/zones
Supports upto 128 wireless zones
(fewer if using hardwired and/or
V-Plex zones)
a Can control eight separate areas
independently (8 partitions)
+ Common Lobby partition -auto
arm or disarm based upon assigned
partitions
Master partition - used for viewing
status of alipartitions
Supports commercial wirelessfire
and burglary devices
Stores up to 512 events
Accommodates 150 user codes and
upto 250 access card holdersusing
VI STAKE
Supports V-Plex addressable
VISTAKEY access control
(ito B doors)
Two on-board NACS delivering a
total of2.3Ai2V
'Automatic smoke detector
sensitivity maintenance testing*
Four-wire smoke reset using on-
board Form Crelay
Supports Dynamic Signaling for
AlarmN eCorn municators
Supports Internet and GSM
alarm reporting
Supports graphical user interfaces
for burglary use (e.g. 6280 and
Tuxedo Touch")
'Supports 6160cP-2 multi-LED
fire keypad
cyvif via Alarm Net
Communicators
Carbon monLlde (CO)
zone support
On-board serial port for
communication with WIN-PAK,
Pro-Watch'and approved third
party applications
Supports Tota t Connect Remote
Services*
* Ent report ing on FMforfire partition.
VISTA-i 28 FBPT
VISTAS Commercial Partitioned Fire and Burglary Alarm Control Panel
ADDITIONAL FEATURES
Notification Appliance Circuits (two):
- Programmable
- Individuallysilenceable
False alarm reduction features:
- Exit error logic
- Exit delay reset
- Cross zoning
-Call waiting defeat
- Recent close report
Supports commercial hardwired,
addressable V-Plex7 polling loop
and wireless zones
Hardwired zones
- Provides eight style B
.hardwired zones
- EOLR supervised for Fire and UL
burglary installations
- Supports N.C. or N.0 sensors
- Individually assignable to any
of eight partitions (all fire zones
on partition 1)
- Up to 16 two-wire smoke detectors
each on zone one and two
(32 total)
Patented addressable V-Ptex
polling loop technology
- Class B, Style 3 SLC
- Supports 120 two-wire
addressable points
- Global polling technology for
faster processing
- Supervised by panel
- Zones individually assignable to
partitions, notification circuit (bell)
output or auxiliary relay
- 4,000 ft. capability without the use
of shielded cable
- Extender/Isolation bus modules
- Eight zone - ClassA and 8
expander module
- Eight zone - Class B expander
module
- Single-zone supervised contact
module
- Single relay module for auxiliary
fire functions
- Supports anti-masking feature
on 'smart" motion detectors
(e.g, DT7500SN)
UL Listed wireless expansion
- Supports up to 128 wireless
zones/points
- Supervised bycontrolfor
check-in signals
- Tamper protection for transmitters
Individually assignable up to
eight partitions
- Supports commercial wireless
smoke detectors
Up to eight doors using VISTAKEY®
V-Plex Access Control
Event reporting
Local printer for event log printing
Communication
- Phone line. GSM and IP
communicator support
- Panel operation during download
- Four or 10-digit subscriber
account numbers
Extra security feature that requires
master code to allow installer into
program mode (enabled through
Compass Downloader)
VISTA-128FBPT
VISTA Commercial Partitioned Fire and BurglaryAlarm Control Panel
SPECIFICATIONS
Electrical:
Primary power: 18VAC @ 7 2V
Honeywell Home No. 1451-UL9
Control panel quiescent current
draw: 300mA
Backup battery:
12VDC, 12AH min to 34.44H max
Lead acid battery (gel type)
Alarm power: 12VDC, 1.7A max
for each notification (bell) circuit
output Total 2.3Al2V
Aux. standby pwr: 12VDC, 1A max
Total power: 2.3A at 12VDC
Standby time: 24 hours with 14
standby load using 34.44H battery
Fusing: Battery input, aux. and
notification (bell) circuit outputs are
protected using PTC circuit protectors
All outputs are power limited.
Optional 24-volt kit
Communications
Dialer:
Line seize: Double Pole
Ringer equiv: 0.7 B
Formats: AD EM CO* Low Speed,
ADEMCO4+2 Express, ADEMCO
High Speed, ADEMCO Contact ID,
Sescoa and Radionics
Backup Communication:
Dual phone line capability using
5140DLM module
AlarmNet® Communicators:
GSM, i-GSM and IP Communicators
Cabinet Dimensions:
18 H x 14.5Wx4.3D
Environmental:
Storage temp: 14°F to 158°F
(-10°C to 70°C)
Operating temp: 32°F to 122°F
(0°C to 50°C)
Humidity: 85°Io RH
EMI: Meets or exceeds the following
requirements:
- FCC Part 15, Class B Device
- FCC Part 68
- lEC EMC Directive
Agency Listings:
UL864/NFPA72 Local, Central
Station and Remote Station
ULC-5559-04 -Equipment for Fire
Signal Receiving Centers and Systems
UL1076 - Proprietary Burglar Alarm
Units and Systems
UL1610—Central Station Burglar
Alarm Units
CAN/U LC-S304-06 - Signal Receiving
Centre and Premise Burglar Alarm
Control Units
UL1635— Digital Alarm Communicator
System Units
UL365 - Police Station Connected
Burglar Alarm Units and Systems
UL609-. Local Burglar Alarm Units and
Systems
UL985 - Household Fire Warning
System Units
UL1023 - Household Burglar Alarm
System Units
ULC-5545-02 - Residential Fire
Warning System Control Units
ULC/0RD-C1023-74— Preliminary
Standard for Household Burglar Alarm
System Units
ULC-5303-M91 —Standard for Local
Burglar Alarm Units and Systems
Factory Mutual (FM)
California State Fire Marshal (CSFM)
FDNY Certificate #6140
COMPATIBLE DEVICES
Auxiliary Devices 4190SN Remote Point Module -
6160CR-2 - Red Fire Keypad two zones
4193SN and 4193SNP Two-zone 6160— Burglary Keypad Expander Modules
6280, Tuxedo Touch, Tuxedo Touch V-Plex Extender/Isolation Modules with Wi-Fi Graphic Keypads - Burglary
4297 Extender/Isolator Module
4204— Relay Module, four Form C VSI Isolator Module contacts
4204CF - Two supervised NAC circuits
5881ENHC Series RF receivers
5883H RF receiver
6220S— System printer
Two-Wire Smoke Detectors
Conventional
System Sensor
ESL
DSC
Horn/Strobes
System Sensor
Wheelock
G entex
Manual Pull Stations
5140M PS-i
5i40M PS-2
V-Plex (Addressable) Devices
4208U Universal Eight-zone
Expansion Module
4208EX Universal Eight-zone
Expansion Module (Canada)
42085N Eight-zone Expansion Module
4101SN Single Relay/Zone Module
42085NF Class A/B Expander Module
V-Ptex Smoke Detectors
51935D
5193SDT
5193SDTA
V-Plex Passive Infrared Detectors
IS2500SN
DT7 500SN
V-Plex (Addressable) Contacts
49395N-WH
49595N
V-PLex Glassbreak Detectors
FGI62SSN
Seismic Detectors
SCiOO
SC1OS
Commercial Wireless Devices
5808W3/5808W3A- Photoelectric
Smoke/Heat Detector
5806W3 - Photoelectric Smoke
Detector
5809 - Wireless Heat Detector
5817C8 - Wireless Commercial
Transmitter
5869- Hold-Up Transmitter
ORDERING
V128FBPT Commercial Fire and Partitioned Burglary Alarm Control Panel 12V Model
V128FBPT24KT Commercial Fire and Partitioned Burglary A[arm Control Panel with External
J.S. Only) 24V Power Supply (13A four outputs, synchronized)
For more information
security.honeywellhom e.com
Resideo Technologies, Inc.
2 Corporate Center Drive, Suite 103
P.O. Box 9040
Melville, NY 11747
1-800-645-7492
resideo.com
Atttrademarks are property
of their respective owners
LJVSI28FBPTO/D I 11119
Cli) 2019 ResideoTechnotogies Inc
This product is manufactured
by Resideo and its affiLiates. The
koneywett Home trademark is
used under license from Honeywell.
International Inc. All rig hts reserved.
VISTA-128FBPT
VISTAS Commercial Partitioned Fire and Burglary Alarm Control Panel
580000/580000A - Carbon
Monoxide Detector
5800P1R-COM - Commercial PIR
Access Control
VISTAKErV-Plex (addressable)
Access Control
VISTAKEY-SK Starter Kit
VISTA KEY-EX Expansion Kit
Integrates with WIN-PAK and
Pro-Watch systems
Alarm Communications
U.S.
GSMV4G - Digital Cellular
Communicator with Two-way Voice
Transport Capability
iGSMV/iGSMV4G - Internet and Digital
Cellular Communicator
iGSMCF/iGSMCFP4G - Commercial
Fire Digital Cellular Communicator with
Internet
iGSMHS/iGSMHS4G - High
Security Internet and Digital Cellular
Communicator
7845i-ENT - Internet/Intranet
Enterprise Communicator
78471 - Internet Communicator
Canada
GSMV4GCN - Digital Cellular
Communicator with Two-way Voice
Transport Capability
iGSMVCN/iGSMVCN4G - Internet and
Digital Cellular Communicator
Product specifications subject to change
Honeywell Home
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL -
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7165-1645:0197 Page 1 of 2
CATEGORY: 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL)
LISTEE: ADEMCO INC.2 Corporate Center Drive, Melville, NY 11747
Contact: Issa Khouryawad (516) 577-2312 Fax (516) 577-3540
Email: issa.khouryawadHoneywell.com
DESIGN: Models Vista-32FBPT, Vista-128FBPT, Vista-250FBPT, *C250F *TYCMSM250
FA1670CT and FA1700CT control units. Suitable for local, remote station, proprietary and
central station applications. Minimum system configuration may include any of the following
components:
SAVISI00-24;Main Board
1451 Transformer
COM-UL; Enclosure
700-00709-02; Enclosure(for use with Vista-32FBPT)
6160CR-2;Alpha Keypad (for use with Vista series)
FA570CR;Alpha Keypad (for use with First Alert series)
ECP; Isolator
4146;Keyswitch
5I400LM;Dialer Module
7845i-ENT; Internet Communicator
4208U ; Remote Conventional Zone Expander
4208SNF V-Plex Class A Adapter
Vplex VSI; Short Isolator
4204CF;Supervised
41905N; Expansion Module
4193;Serial Number Interface Module
4297;Polling Loop Extender
5881 ENHC, 5883-H;Short Range RF Receiver
For additional accessories and devices refer to the manufacturer's installation instructions.
RATING: 120 Vac, 60 Hz
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and a manner acceptable to the authority having jurisdiction
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as a fire alarm control unit for use with separately listed compatible initiating and
indicating devices. Refer to manufacturer's installation manual for details.
*Rev 11-04-15gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2020 Listing Expires June 30, 2021
Authorized By: DAVID CASTILLO,, ME., F.P.E.
Fire Engineering Division
Listing No. 7165-1645:0197
Page 2 of 2
NOTE: Burglary and other non-fire functions were not examined.
*Rev 11-04-15 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other, data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2020 Listing Expires June 30, 2021
Authorized By: DAVID CASTILLO,, M.E., F.P.E.
Fire Engineering Division
6160CR-2
COMMERCIAL FIRE ALPHA KEYPAD
UL864 REV 9 LISTED
The 61 6OCR-2 is an addressable remote keypad intended
for use in commercial fire applications with Honeywell's
commercial fire control panels. The keys are continuously
backlit for convenience and easy visibility. The LCD display
FEATURES
is backlit only when a key is depressed*, or when the
system is in alarm or trouble condition.
*Note. The LCD may be programmed to remain on at all times (see panel
instructions for details).
Four programmable
function keys
Built-in sounder
Seven Status LEDs
- Armed (Red)
- Ready (Green)
- Power (Green)
- Fire Alarm (Red)
- Silenced (Yellow)
- Supervisory (Yellow)
Trouble (Yellow)
Large easy-to-read display
Red removable door
Physical
5.250" W x 7.437" H x 1.312' D
SPECIFICATIONS
Sounder
High-quality speaker
Electrical
45mA standby 1 60mA in alarm (sounder, back light and
LED on)
Compatibility
Supports Control Panels
- VISTA-32FB Rev 5 and higher
- VISTA-1 28FBP Rev 4 and higher
- VlSTA-250FBP Rev 4 and higher
UL/CUL and residential Listed for commercial fire and burglary installations.
To be employed with manufacturer's listed control units as indicated in the
installation instructions.
Product specifications subject to change.
ORDERING
6160CR-2 Commercial Fire Alpha Keypad
For more information: www.honeywell.com/security/hsc
Automation and Control Solutions
Honeywell Security & Communications
2 Corporate Center Dr. Suite 100
Melville, NY 11747
1.800.467.5875
www.honeywell.com
LJ6160CR2o/D
September 2009
0 2009 Honeywell International Inc.
Honeywell
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-1645:0115 Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: ADEMCO lNC.2 Corporate Center Drive, Melville, NY 11747
Contact: Issa Khouryawad (516) 577-2312 Fax (516) 577-3540
Email: issa.khouryawadresideo.com
DESIGN: Models 6139, 6139R, 6160VADT, 6160V, 6270, 6270ADT, FA700KP, 6160CR, 6150V,
6I50VADT, CPI50KP, FA560VKP, FA615OKP-GP, 6160VBAY, 6164, 61645P, 8132i,
8142i, FA800KPi, FA850Kpi, 6270PL2, 6271V, 6271 VADT, FA270VKP, FA570VKP,
FA270KP, FA570KP, FA574KP, 6271 C, 6271 CV, FA701CKP, FA701CVKP, FA701VKP,
FA570CR, 6160CR-2, 6164U5, FA27IKP, 6149EX, 6165EX remote keypads, 4146
keyswitch, and *6280s *6280w *TUXS *TUXW touchscreen keypads. Refer to listee's data
sheet for detailed product description and operational considerations.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, UL and ETL label.
APPROVAL: Listed as remote keypads for use with listee's separately listed compatible fire alarm control
units. Refer to listee's installation Instruction Manual for details.
rev. 09-23-11 mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2020 Listing Expires June 30, 2021
Authorized By: DAVID CASTILLO,, M.E., F.P.E.
Fire Engineering Division
SYSTEM
$ SENSOR®
Photoelectric
Smoke Detectors
System Sensor series smoke detectors represent
significant advancement in conventional detection.
The J3 family is founded on three principles: installation
ease, intelligence, and instant inspection.
t
Features
Plug-in detector line, mounting base included
Large wire entry port
In-line terminals with SEMS screws
Mounts to octagonal and single-gang back boxes, 4-square back
boxes, or direct to ceiling
Stop-Drop 'N Lock attachment to base
Removable detector cover and chamber
Built-in remote maintenance signaling
Drift compensation and smoothing algorithms
Simplified sensitivity measurement
Wide-angle, dual-color LED indication
Loop testing via EZ Walk feature
Built-in test switch
Agency Listings
&
LISTED
<~> 0 MEA MSFM
APPROVED approved approved AVU8
5911 3011446 7272-1653:152 290-01-E 2093 3180932
Installation ease. The i3 line redefines installation ease with its
plug-in design. This allows an installer to pre-wire bases (included
with heads). The large wire entry port and in-line terminals provide
ample room for neatly routing the wiring inside the base. The base
accommodates a variety of back box mounting methods as well as
direct mounting with drywall anchors.To complete the installation, i
heads plug into the base with a simple Stop-Drop 'N Lock' action.
Intelligence. i3 detectors offer a number of intelligent features
to simplify testing and maintenance. Drift compensation and
smoothing algorithms are standard with the j3 line to minimize
nuisance alarms. 2-wire i3 detectors can generate a remote LED-
indicated maintenance signal when connected to the 2W-MOD2
loop test/maintenance module or a panel equipped with the i
protocol. The SENS-RDR, a wireless device, displays the sensitivityofi3
detectors in terms of percent-per-foot obscuration.
Instant inspection. The j3 series provides wide-angle red and
green LED indicators for instant inspection of the detector's
condition: normal standby, out-of-sensitivity, alarm, or freeze trouble.
When connected to the 2W-MOD2 loop test/maintenance module
or a panel with the P protocol, the EZ Walk loop test feature is
available on 2-wire i3 detectors. This feature verifies the initiating loop
wiring by providing LED status indication at each detector.
1j Smoke Detector Specifications
Smoke detector shall be a System Sensor il Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems.The
detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 135°F
(57.2°C).The detector shall include a mounting base for mounting to 31/2-inch and 4-inch octagonal, single-gang, and 4-inch square back boxes with a plaster
ring, or direct mount to the ceiling using drywall anchors.Wiring connections shall be made by means of SEMS screws.The detector shall allow pre-wiring of the
base and the head shall be a plug-in type.The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box. The
detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms.The detector shall provide dual-
color LED indication that blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When used
in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel
and shall provide a loop testing capability to verify the circuit without testing each detector individually.
Electrical Specifications
Operating Voltage Nominal: 12/24V non-polarized
Minimum: 8.5V
Maximum: 35V
Maximum Ripple Voltage 30% peak to peak of applied voltage
Standby Current 2-wire: 50 u maximum average; 4-wire: 50 qA maximum average
Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12 V, 23 mA @ 24V
Peak Standby Current 2-wire: 100 qA; 4-wire: n/a
Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @ 30 V AC/DC
Dimensions (including base) 5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height.
Weight 6.3 oz (178 g)
Operating Temperature Range 2W-B and 4W-B: 32°F to 120°F (0°C to 49°C); 2WT-B and 4WT-B: 32°F to 100°F (0°C to 37.8°C)
Operating Humidity Range 0 to 95% RH non-condensing
Thermal Sensor 135°F (57.2°C) fixed
FreezeTrouble . 2WT-B and 4WT-B only: 41°F (5°C)
Sensitivity 2.50/o/ft nominal
InputTerminals 14 to 22 AWG
Mounting 31/2-inch octagonal back box
4-inch octagonal back box
Single-gang back box
4-inch square back box with a plaster ring
Direct mount to ceiling
LED Modes Power-Up Sequence for LED Indication
LED Mode Green LED Red LED Condition Duration
Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds
Normal (standby) Blink every S seconds off
Out of sensitivity off Blink every 5 seconds
Freeze trouble off Blink every 10 seconds
Alarm off Solid
Ordering Information
2W-B No 2-wire 130 mA max. limited by control panel
2WT-B Yes 2-wire 130 mA max. limited by control panel
4W-B No 4-wire 20 mA @ 12 V, 23 mA @ 24V
4WT-B Yes 4-wire 20 mA@ 12V,23 mA@ 24V
Accessories
2W-MOD2 2-wire loop test / maintenance module RT Removal / replacement tool
SENS-RDR Sensitivity reader A77-AB2 Retrofit adapter bracket, 6.6 inch (16.76 cm) diameter
SY'STEA7 3825 Ohio Avenue. St. Charles, IL 60174 2OOgSYst&nSeeSO,
P,oductspec,tcat,ons subject to change without notice. Visit systen'oensor.com to,
5ff J5Q° Phone: 800-SENSOR2 . Fax' 630-377-6495 current productinfcrrnaton, including the latest version of this data sheet.
A05-0318-007 .6/09.#2t69
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
fl~qj
LISTING No. 7272-1653:0152 Page 1 of 1
CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL
60174
Contact: Megan Sisson (203) 484-6544 Fax (203) 484-7309
Email: megan.sisson@honeywell.com
DESIGN: Models 2W-B, 2W1-B, 4W-B and 4W1-B photoelectric type smoke detectors. Models 2W-B
and 2W1-B are 2-wire and model 4W-B and 4VVT-B are 4-wire detectors. Models 2WT-B and
4WT-B employ a thermistor type heat sensor (135°F). The heat sensor is are supplemental
to the detector and is not intended for use as a required heat detector. Refer to listee's
printed data sheet for additional detailed product description and operational considerations.
RATING: 8.5 - 35 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. For vertical wall or ceiling
mount.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm
control units. Suitable for installation in open areas with air velocity range from 0-1000 ft/mm.
NOTE: Formerly 7272-1209:210
06-20-05
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2020 Listing Expires June 30, 2021
Authorized By: DAVID CASTILLO,, M.E., F.P.E.
Fire Engineering Division
Honeywell Home Alarm Communications
LiG LTE+IP
LIE and Internet Multi-Path
Communicators
Honeywell Home is focused on providing the best alarm
communication solutions for the security industry. Alternative
communication methods are critical in the marketplace due to
inconsistencies in VoiP, migration from POTS and the
evolution of cellular networks. LTE network connectivity
provides the longest viable cellular lifespan available.
All sig nals are delivered to the AlarmNet' Network Control
Center, which routes the information to the appropriate central
station. The state-of-the-art AlarmNet Network Control Center
is fully redundant and monitored 24/7. AlarmNet has the ability
to route messages using AlarmNet-i and 800 PLUS services,
providing true redundancy and multi-path message delivery.
Honeywell Home End-to End Solutions
0criONS
Sensors
LTE+IP Control
WO Communications Panels
DEALERS w
LU co
2\\ One -Stop
AlarmNet
360 j -\\ Support
Totat
Connecr
-
OlNG suPPO
s$o
FEATURES
LeG LTE network and I
compatibility
. Fu IL Contact ID
Contact ID reporting using
ECP mode with compatible
Honeywell Home control
panels.
.256-bit AES Encryption
Advanced encryption
standard used for secure
communications.
Upload/DownLoad
Available with select
Honeywell Home control
panels. Requires Compass
version 1.5.8.54a or higher.
Diagnostic LEDs
Provide signal strength
and status indications.
QOS
Quality of Service
diagnostics via AlarmNet
supply vital information
including when a message
was received, battery
voltage, input voltage,
signal strength and
message path.
ALarmNet360 Online
Management Platform
Remote programming
and diagnostics to improve
business efficiencies
and reduce truck rolls.
www.alarmnet360.com
Remote Services
Capability*
Optional Resideo Total
Connect Remote Services -
Boost RMR while providing
on-the-go security and
home control, video viewing,
and real-time alerts,
anytime, anywhere, on
any PC or smart device.
FOTA Firmware Upgrading
Complete over-the-air
firmware upgrading
capability. Provides remote
service management ability.
Dual Technology
Reporting
Provides I P and cellular
transmission paths
with added flexibility
and reliability.
(LTE-IV, LTE-IA, LTE-IC)
Six Input Zones
Used for universal control
panel compatibility.
(LTE-IV, LTE-IA, LTE-IC)
Built-in Power Supply!
Backup Battery
On-board charging circuit
design accommodates
back-up battery.
Includes primary power
and battery supervision.
6V 3.1Ah battery supplied
to deliver up to 24 hours of
standby operation.
*Service subscription required.
SPECIFICATIONS
VISTA 4G LTE
Multi-Path
Communicators
(LTE-IV/LTE-IA/
LTE-IC)
VISTA 4G LTE
Multi-Path
Communicators
(LTE-CFA/LTE-CFV)
Multi-path IP and Cellular Technologies
DESCRIPTION Integrated VISTA ECP design
LTE CAT1
PANEL COMPATIBILITY All VISTA® controls with ECP radio support.
Universal panel compatible using zone inputs.
DIMENSIONS 8.4"x 8.0"x 1.5"
(2 1.3cm x 20.3cm x 3.8cm)
Input Power: 16.5VAC, 40VA transformer,
ELECTRICAL Model No. 1361
Backup Battery: 6V, 3.IAH
RF Antenna: Internal Penta-Band antenna with
receive diversity for LTE CATI. Average 3.8dBi gain.
Operating Temperature:
-41 to 131° F (-201 to 55° C) ENVIRONMENTAL Storage Temperature:
-400 to 158° F (-401 to 70° C)
AGENCY LISTINGS ETL Listed
DESCRIPTION Commercial Fire Internet and LTE Communicator
PANEL COMPATIBILITY VISTA-32F8, VISTA-32FBT, VISTA-I28FBP,
VISTA-128FBPT, VISTA-250FBP, VISTA-2508PT.
DIMENSIONS 15.0"H X12,75"Wx3.0"D
I2VDC supplied by the control panel ELECTRICAL 90mA Standby, 105Ma active
Frequency Peak Gain (dBi) Radiation
698 to 960 MHz 0.84 to 1.09 Omni-directional RF
1710 to 2170 MHz 1.81 to 1.87 Omni-directional
Operating Temperature:
0°Cto49°C ENVIRONMENTAL Storage Temperature:
-400 to 158° F-40° Cto 70° C
AGENCY LISTINGS UL864 1011 Edition, CSFM
VISTA 4G LTE
Multi-Path
Communicators
(LTE-HSV)
I
SPECIFICATIONS
DESCRIPTION High Security Internet and Cellular Communicator
PANEL COMPATIBILITY VISTA® Control panels with ECP radio support.
Universal panel compatible using zone inputs
DIMENSIONS 8.4" x 8.0" x 1.5"
(21.3cm x 20.3cm x 3.8cm)
Input Power: 16.5VAC, 40VA transformer, ELECTRICAL Backup Battery: 319mA Standby, 380Ma active
RF Antenna: Internal Penta-Band antenna with receive
diversity for LTE CATI Average 3.8dBi gain.
Operating Temperature:
ENVIRONMENTAL -41to1311 F(-20° to 55° C)
Storage Temperature:
-40° to 158° F (-40° to 70° C)
AGENCY LISTINGS UL365, UL1610, Encrypted Line Security, NIST
ORDERING
U.S. Canada
LIE-IA
LTE-IV
LTE-CFA/
LIE-CFV
AT&T
Verizon
AT&T!
Verizon
VISTA-15P
VISTA-20P
VISTA-I28BPT
VISTA-250BPT
(universal panel compatibility
using zone inputs)
VISTA-15P
VISTA-20P
VISTA-I28BPT
VISTA-250BPT
VISTA-32FB
VISTA-32FBT
VISTA-I28FBP
VISTA-I28FBPT
VISTA-250FBP
VISTA-250BPT
IGSMV4G
GSMX4G/CDMA-X
IGSMCFP4G
VISTA-I5PCN
VISTA-20PCN
VISTA-I28BPTCN
LIE-IC Bell VISTA-250BPTCN IGSMV4G
(universal panel
compatibility using
zone inputs)
LTE-HSV Verizon
VISTA-15P
VISTA-20P
VISTA-I28BPT
VISTA-250BPT
(universal panel compatibility
using zone inputs)
IGSMHS4G
For more information
security.honeyweLlhome.com
r
resideo
Resideo Technologies, Inc.
2 Corporate Center Drive, Suite 100
P.O. Box 9040
MeLviLle, NY 11747
1-800-645-7492
resideo.com
L/LTEIMPCD/D I 07/19
2019 Resideo Technologies,
Inc. This product is manufactured
by Resideo and its affiliates. The
Honeywell Hornetrademark is
used under license from Honeywell
International Inc. ALL rights reserved. Honeywell Home
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
~[im
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-1645:0509 Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: ADEMCO INC.2 Corporate Center Drive, Melville, NY 11747
Contact: Issa Khouryawad (516) 577-2312 Fax (516) 577-3540
Email: issa.khouryawad@Honeywell.com
DESIGN: Models LTE-CFA (AT&T) and LTE-CFV (Verizon) Commercial Internet and LTE
Communicator. The unit uses the Internet as its primary reporting path, and switches to cell
service (secondary path as backup) when the Internet is not available.
Refer to listee's product specification data sheets and installation, operation, and
maintenance manual for detailed product description and operational considerations.
RATING: 12VDC (supplied by the Control Panel)
90 mA standy
160 mA active
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as a control unit accessory for use with separately listed compatible commercial fire
alarm control units. Intended for use with specific Honeywell Security control units that
employ the ECP bus. Refer to listee's installation Instruction Manual for details.
05-28-2019 dcc
TO This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2020 Listing Expires June 30, 2021
Authorized By: DAVID CASTILLO,, M.E., F.P.E.
Fire Engineering Division