HomeMy WebLinkAbout2525 EL CAMINO REAL; 114; FPC2017-0224; Permit(7city of
Carlsbad
Print Date: 12/13/2021 Permit No: FPC2017-0224
Job Address: 2525 EL CAMINO REAL, # 114, CARLSBAD, CA 92008-1206 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm
Parcel #: 1563020900 Track #: Applied: 08/09/2017
Valuation: $1,253,304.97 Lot #: Issued: 09/06/2017
Occupancy Group: Project U: Finaled Close Out: 02/01/2021
#of Dwelling Units: Plan U:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check U: Inspector:
Plan Check U: Final Inspection:
Project Title:
Description: H&M - FIRE ALARM TI
Applicant: FPContractor:
JOHNSON CONTROLS FIRE PROTECTION LP JOHNSON CONTROLS FIRE PROTECTION LP
DOUGLAS DANIELS P0 BOX 3042
3568 RUFFIN RD BOCA RATON, FL 33431-0942
SAN DIEGO, CA 92123-2597 (561) 341-7780
(858) 633-9123
FEE AMOUNT
FIRE TI Fire Alarm System $601.00
Total Fees: $601.00 Total Payments To Date: $601.00 Balance Due:
---
$0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 760-602-8561 f I www.carlsbadca.gov
SimplexGrinnel! LP
3568 Ruffin Road
San Diego, California 123
P: 858-633-9100 tq Sirnp/exGrmnnel/ =OnnelI. corn
Fire Detection and Alarm System
Product Submittal
Project: H&M
The Shoppes at Carlsbad
2525 El Camino Real Suite 114
Carlsbad, CA
TILE COPY
FPC20I7-0224
2525 EL CAMINO REAL
UN1T114
For any questions regarding this submittal, please contact Douglas Daniels, 858-
633-9123 or ddaniels(äsimplexqrinnelI.com
8/8/2017 REV.#: 0 PROJECT
Safer. Smarter. Tyco.TM
tqco
Sunp/exGrinnell
SimplexGnnnell LP
3568 Ruffin Road
San Diego, California 92123
P: 858-633-9100
F: 858-633-9101
www.simplexgrinnell.com
Fire Detection and Alarm System Products
Qty Model No. Description C.S.F.M. No.
2 4009-9601 IdNAC Repeater 7300-0026:0375
4 2081-9272 6.2 AH Battery N/A
1 4098-9792 Detector Base 7300-0026:0217
1 4098-9714 Smoke Sensor 7272-0026:0218
5 4098-9755 Duct Detector 3420-0026:0241
6 4090-9010 Relay 1AM 7300-0026:0311
7 4906-9204 Strobe 7125-0026:0235
20 49SV-APPLC Speaker Strobe 7125-0026:0384
Business Information
Warranty Information
8/8/2017 REV.#: 0 PROJECT
Safer. Smarter. Tyco .TM
* B5impIEx
UL, ULC, CSFM Listed; "'Milo FM Approved*
TrueAlert Addressable Notification
4009 IDNAC Repeater;
Power and Distance Extender
4009 IDNAC Repeaters provide enhanced power
delivery to TrueAlert/TrueAlert ES addressable
notification appliances controlled by IDNAC SLCs:
Output voltage is maintained by efficient switching
regulator at 29 VRMS during both AC and battery
backup conditions allowing strobes to operate at lower
current
With lower current strobes and regulated output
voltage, wiring distance can be extended 2 to 3 times
that of conventional notification, appliance loading can
be increased, or smaller wire gauge can be used, all
resulting in installation savings with high assurance
that appliances that operate during normal system
testing will operate during worst case alarm conditions
4009 IDNAC Repeaters receives an IDNAC SLC
input and provide a repeated 3 A SLC output to
extend SLC distance and power:
Appliance control remains with the host IDNAC
control panel and Repeater operation is essentially
transparent; Repeater status is communicated to the
control panel for system diagnostics and also
locally indicated
Input SLC connection can be Class B or Class A
Repeater output can be a Class A loop or a Class B
output with internal connections for up to four (4)
1-tapped output branches (Class A output requires
4009-9814 Class A Adapter)
Operation requires one IDNAC SLC address;
Repeaters can be connected as one in series, or up
to five (5) in parallel
AC power input is 120 VAC or 220-240 VAC,
50/60 Hz, auto-select
An on-board battery charger is provided with low
AC battery disconnect selectable per Repeater
(required for ULC listed applications)
Operation is compatible with TrueAlert ES and
TrueAlert addressable notification appliances and
accessones
Available with platinum or red cabinet
Listed to UL 864 and ULC S527
Multiple wiring options are available:
Wiring options include Class B multiple branch (up to 4)
output, Class A loop extension, and Class A riser to
Class B branches or a Class A loop output
When the Repeater is part of a Class A loop from the
IDNAC SLC source panel, up to twice the distance for
the loop is available; (Class A loop repeating requires
4009-9814 Class A Adapter)
Class A Adapter 4009-9814:
Required when extending a Class A loop or to provide a
Class A local loop SLC output
Operation provides short circuit isolation between input
and output terminals for improved IDNAC SLC
survivability
I—
F
I#
RE
Extended
distance and
current
Repeated IDNAC SLC
4009 IDNAC
Repeater
-
4100ES with EPS
Power Supply
4009 IDNAC Repeater Extends Distance
and Current of IDNAC SLC
Ffe!tes (Continued)
Built-in battery Charger
Power supply charges up to 12.7 Ah batteries for in
cabinet mounting and up to 25 Ah batteries with model
4009-9801 external battery cabinet
Available auxiliary output:
A 200 mA, 29 VDC constant auxiliary output is
available; operation is maintained during battery backup
This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7300-0026:0375 for allowable values and/or conditions concerning material presented in this
document. Additional listings may be applicable; contact your local Simplex product supplier
for the latest status. Listings and approvals under Simplex Time Recorder Co. are the
property of Tyco Fire Protection Products.
S4009-0004-2 7/2013
durtk
Repeating IDNAC SLCs. 4100ES fire alarm control
panels with an EPS or EPS+ (enhanced power supply)
provide individual address and control of TrueAlert and
TrueAlert ES addressable notification appliances using
IDNAC SLCs. When an IDNAC SLC reaches the current
limit or the distance limit of the source IDNAC SLC, use
of 4009 IDNAC Repeaters extends the IDNAC SLC with
an additional 3 A of SLC current.
With IDNAC SLCs, a constant 29 VRMS source voltage
is maintained, even during battery standby, allowing
strobes to operate at higher voltage with lower current and
ensuring a consistent current draw and voltage drop
margin under both primary power and secondary battery
standby. Efficiencies include wiring distances up to 2 to 3
times farther than with conventional notification, or
support for more appliances per IDNAC SLC, or use of
smaller gauge wiring, or combinations of these benefits,
all providing installation and maintenance savings with
high assurance that appliances that operate during normal
system testing will operate during worst case-alarm
conditions.
I'I*H i1tT1
Three wiring configurations are available to provide
a variety of system solutions: Class B branch extension,
Class A loop extension, and Class A riser to Class B
branch extension or Class A loop output.
I'i4.-!.1lF1rT(fflm1iTiI
Class B branch input wiring allows T-tapped
connections to up to five (5) parallel connected 4009
IDNAC Repeaters. Each Repeater has on-board output
terminal connections for up to four (4) output branch
circuits, and additional branch circuits can be externally
T-tapped as required. (Refer to diagram on page 3 for
additional details.)
Class A loop extensions use a single 4009 ]DNAC
Repeater to extend the current and distance of a single
Class A loop allowing the loop distance to be doubled.
The Repeater communicates and repeats bi-directionally
allowing Class A loop operation to be maintained in the
event of an open circuit. This wiring connection requires
use of the 4009-9814 Class A adapter. (Refer to diagram
on page 4 for additional details.)
Class A Riser to Class B Branches or Class A
Loops. For applications requiring a combination of
wiring types, a Class A riser can drive up to five (5) 4009
IDNAC Repeaters with each Repeater capable of driving
either single or multiple Class B branch output(s) or a
Class A loop output. In this wiring application, the
Repeater does not repeat in the Class A riser loop, it is
connected as an appliance with Class A in/out wiring. To
create a Class A loop output, the Repeater must be
equipped with a 4009-9814 Class A Adapter. (Refer to
diagram on page 5 for additional details.)
Model* Cabinet Color Description
4009-9601(BA) Platinum 4009 IDNAC Repeater with cabinet; provides a single 3 A IDNAC SLC output, 200 mA auxiliary
4009-9602(BA) Red power output, and battery charger; 120/240 VAC, 50/60 Hz input, auto-select
* Add suffix BA to select 4009 IDNAC Repeaters assembled in the USA.
Aftermarket Accessories (installed on-site, select per system requirements)
Model I Description
4009-9814 I Class A Adapter Module, mounts on repeater controller board; required for Class A output
2975-9813 Platinum semi-flush box trim 1 /i ' (37 mm) wide, four corners and trim pieces for top, bottom, and sides; (will
2975-9812 Red semi-flush box trim need to be cut to fit 4009 IDNAC Repeater cabinet)
External Accessories (select per system requirements)
Model I Description I Comments
4905-9929 Remote TrueAlert Communications Isolator I Refer to data sheet S4905-0001 for details
116 %" W 13 %" H x 5%" D(413 mm x 343 mm x 146 mm); refer to 4009-9801 External Battery Cabinet for 25 Ah batteries data sheet S2081-0006 for details
Battery Selection (select battery size per system requirements; two batteries are required for 24 VDC operation)
Model I Description II Model Description
2081-9272 I 6.2 Ah Battery, 12 VDC 2081-9275 I 18 Ah Battery, 12 VDC Requires 4009-9801 External Battery Cabinet 2081-9274 10 Ah Battery, 12 VDC 2081-9287 25 Ah Battery, 12 VDC
2081-9288 12.7 Ah Battery, 12 VDC
S4009-0004-2 7/2013
Wiring Notes:
Up to five (5) 4009 IDNAC Repeaters can be
wired in parallel as shown on this diagram.
IDNAC SLC communications can be repeated
only once between the source and the
addressable appliance.
The 4009 IDNAC Repeater extends distance
and current of the input IDNAC SLC; it
requires one address and consumes four (4)
unit loads.
M C
L...! ...J LflaaJ z~IRE
Class B IDNAC SLC
Fine I A aqw~~6
Class B IDNAC SLC
Each 4009 IDNAC Repeater has duplicate output
terminals rated for two wires each, allowing up to
four (4) Class B branch circuit 1-taps to be made
in the cabinet; additional 1-taps may be made in
external wiring junction cabinets or boxes
FIRE FIRE
-I inS ~FIHE~~
FIRE L ------- -[U r - Fin. ~Rs
Class B IDNAC SLC
Branch Circuits
Wiring Reference, Class B Input with Class B Branch Circuit Outputs
4100ES with EPS
Power Supply
4009 IDNAC Repeaters Class B Branch Extensions
(5 maximum)
IDNAC SLC input IDNAC SLC output
4 i FIRE FIRE FIRE Fin L
Class B IDNAC SLC Class B IDNAC SLC
Class B wiring can IRE PuRe
be 1-tapped'
Class B IDNAC SLC
3 S4009-0004-2 7/2013
Wiring Reference, Class A Loop Extension
Class A IDNAC SLC Loop with 4009 IDNAC Repeater Extending Loop Range and Power
4009 IDNAC Repeater Requires optional 4009-9814
Class A Adapter Module set for Loop mode
1- Class A loop secondary direction 1----
FIRE- -FIRE-
Class A loop primary direction
Class loop secondary direction
4100ES with EPS Power Supply, requires optional
4100-6103 Dual Class A IDNAC Isolator (DCAl)
Notes:
Only one 4009 IDNAC Repeater can be wired in a Class A loop. (IDNAC SLC
communications can be repeated only once between the source and the
addressable appliance.)
The 4009 IDNAC Repeater extends distance and current of the Class A IDNAC
SLC loop; it requires one address and consumes four (4) unit loads.
Under normal operating conditions (no open circuit wiring), appliances 1
through 4 are powered by the 4100ES EPS Power Supply and appliances 5
through 9 are powered from the 4009 IDNAC Repeater.
Under open circuit conditions, an open circuit in the panel side of the primary
path will result in the 4100ES EPS Power Supply powering appliances 5
through 9 and the 4009 IDNAC Repeater will receive IDNAC SLC input from
the return path and then power appliances I through 4, or as many as remain
connected.
S4009-0004-2 7/2013
III Wiring Reference, Class A Riser Input with Class A-Loop and Class B Branch Outputs
4100ES with EPS Power Supply, requires optional
4100-6103 Dual Class A IDNAC Isolator (DCAI)
Requires optional 4009-9814 Class A Adapter
Module set for Branch Mode to create a local
Class A loop circuit output
Class A Loop Extension
IDNAC SLC input
Class A Loop
4009 IDNAC Repeaters
--E Class B Branch Extension
FIRE
Wiring detail reference (repeaters
- are wired same as appliances)
IDNAC SLC shown as a Class A Riser with each
IDNAC Repeater wired in/out (not T-tapped); IN
only two (2) are shown, maximum is five (5)
4009 IDNAC Repeater Mounting and Module Placement Reference
cabinet depth
16-1/4" (413 m 4-1/8(105mm)
Door, 5/8"
(16 mm) thick
Exposed cabinet
dimension for
semi-flush mount
1', (25.4 mm),
1-3/8" (35 mm) with
semi-flush trim
0-29132' (277
iIii*I1 _ alJIIJ
dotted line) no conduit entry
or wiring in this area, 12.7 Ah maxim—um--F i
0
rr0
13-1/2"
(343 mm)
Knockouts for screw
or nail mounting holes
I
Optional Semi-Flush Trim Kit -.
Shaded Area is Non-power limited - 1-3/16" wide (30 mm),
3/8" (9.5 mm) thick
Wall surface reference for semi-flush
5 S4009-0004-2 7/2013
4009 IDNAC Repeater Specifications
Input Ratings
Voltage Range 120 VAC, 50/60 Hz, or 220/230/240 VAC, 50/60 Hz, +10%, -15%, auto-select
AC Input
Ratings 120 VAC Current 2.5A
220/230/240 VAC Current 1.25A
Panel IDNAC Appliances Auxiliary Load
70 mA 0.8 mA each Output current
(voltage is from battery) Standby Currents
24 VDC Requirements
for Battery Calculations 4.5 A maximum with 3 A IDNAC SLC load 1.37 x output current
Alarm Currents 96 mA and 200 mA Auxiliary output load (actual (voltage converter is on alarm current depends on connected and when in Alarm) activated appliances and devices)
17 VRMS minimum
IDNAC Input Ratings
1 address, 4 unit loads
Output Ratings
IDNAC SLC Output 3 A maximum @ 29 VRMS for Special Application appliances
Compatible Special Application Appliances Simplex TrueAlert ES and TrueAlert addressable notification appliances; contact your
Simplex product representative for compatible appliances
IDNAC SLC Ratings and Loading
Up to 62 total addressable appliances; one address is required for the Repeater
Up to 75 total unit loads (appliances are 1 unit load, Repeater and Isolators are 4 unit
loads)
Up to 62 compatible strobes can be synchronized per IDNAC SLC
Current
Auxiliary Output Voltage
200 mA maximum
29 VDC nominal with AC present or when Repeater is on battery standby and in Alarm
24 VDC nominal when on battery standby and not in Alarm
IDNAC SLC Wiring Specifications (refer to installation instructions for more information)
Recommended wire type UTP, unshielded twisted pair
Maximum wire length allowed with 10,000 ft (3048 m)
"T -Taps" for class _B_wiring
Maximum wire length to any appliance 4000 ft (1219 m)
Maximum wiring resistance between 260
appliances
Wiring Connections Terminal blocks for 18 to 12 AWG
Repeater Status Indicators
Green AC Power LED On with AC present, off during brownout or no AC condition
Red Communications LED (COMM) Blinks when Repeater is communicating with the host control panel
Yellow System Status LEDs 4 LEDs provide up to 16 different trouble status indications; an on-board trouble scroll
button allows review should multiple troubles occur
4009-9814 Class A Adapter Module Option (required for Class A loop extension or for Class A output)
IDNAC SLC Output Voltage
3 A maximum @ 29 VRMS for Special Application appliances
Two connections, Port A and Port B, function vanes by application (loop extension or
local loo. Port A and Port B are isolated from each other
Status LEDs I Two yellow trouble LED indicators, one per Port
Environmental and Technical Publications Reference
Operating Temperature 32° to 120° F (0° to 49° C)
Operating Humidity Range Up to 93% RH at 90° F (32° C)
Installation 4009 IDNAC Repeater 579-1019
Instructions Class AAdaoter Module 579-1080
TYCO, SIMPLEX, and the product names listed in this material are mark and/or registered marks. Unauthorized use is strictly prohibited.
Tyco Fire Protection Products Westminster, MA 01441-0001 USA S4009-0004-2 7/2013
www.simplexgrinnell.com
0 2013 Tyco Fire Protection Products. All rights reserved All specifications and other information shown were current as ofdocument revision date and are subject to change without notice.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No.
CATEGORY:
LISTEE:
DESIGN:
RATING:
7300-0026:0375 Page 1 of 1
7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
Simplex100 Simplex Drive, Westminster, MA 01441-0001
Contact: Jim Goyette (978) 731-8580 Fax (978) 731-8881
Email: jgoyette@tycoint.com
Models 4009-9601, 4009-9601 BA, 4009-9602 and 4009-9602 BA IDNAC repeaters. Model
4009-9814 Class A Adapter card. Refer to listee's data sheet for detailed product description
and operational consideration.
120V/240V
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as an accessory for use with listee's separately listed compatible fire alarm control
units. Authority having jurisdiction should be consulted prior to installation.
04-23-13 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2017 Listing Expires June 30, 2018
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
!iSimpIEx Fire Alarm Control Panel Accessories
Listings* System Batteries, Sealed Lead-Acid; with Applications
Reference for Battery Cabinets, and Battery Cabinets with Charger
I'k!M_
Rechargeable, sealed lead-acid batteries:
Lead-calcium grid structure with immobilized
electrolyte in absorbent separator
Low maintenance with no need to add water
Low self-discharge characteristics
One-piece, high impact polystyrene cell cover with high
reliability dual seal construction
UL 924 recognized pressure relief valves
Available in a variety of capacities:
Batteries for internal mounting range from 6.2 Ali up to
50 Ah, depending on control panel cabinet size
Larger batteries, up to 110 Ali, mount in external battery
cabinets with models available with internal chargers
Battery cabinets with chargers:
Battery cabinets with charger communicate with their
connected fire alarm control panel and are available for
4100ES/4010ES/4100U Series and 4010 Series panels
I'i*- r1rTN
Simplex® rechargeable sealed-lead acid batteries provide
reliable and repeatable discharge and recharge
characteristics for use in fire alarm and other systems
applications. They are designed with immobilized
electrolyte in an absorbent separator, allowing them to
provide rated capacity on the first cycle.
Because of their sealed construction, packaging is allowed
within the system electronics enclosure (see illustration
on page 2). When this is applicable, the quantity of
system cabinets and the battery wiring distances are both
minimized. Where required, external battery cabinets can
be close-nippled to the control panel to house larger
batteries with battery chargers available in some battery
cabinet sizes.
Charging. These batteries are intended to be used with
compatible Simplex battery chargers.
Series Connections. These batteries are required to be
connected in series to produce 24 V system voltage.
Battery sets must be of identical voltage, model number,
appearance, and approximately the same date of
manufacture for proper operation.
Testing. Battery capacity testing is recommended to be
performed by using a sealed lead-acid battery tester
designed to withdraw a minimum of battery charge. The
preferred tester applies a variety of amplitude and
duration controlled test pulses that compares terminal
voltage against those predicted for the specific battery
size. (Testing is available through your local Simplex
product supplier.)
Compatible Sealed Lead-Acid Batteries can be
Installed Inside Fire Alarm Control Panel Cabinets
Remote Battery Cabinets are Available for
Larger Battery Requirements
IMUMIMM(IIiTffluJI1!!ij
Shipping. Sealed lead-acid batteries are shipped via
ground or sea transportation only. They are not shipped
via air.
Disposal. Battery chemicals and materials can be
recycled. Refer to information shipped with the battery or
on its case. Return to the battery manufacturer or to a
similarly qualified battery processing facility for proper
disposal.
Seismic Activity Applications. Battery brackets are
available for systems tested for compliance with specific
batteries. Please refer to data sheet S2081-0019 for
details.
* Refer to details on page 4 and to the referenced individual product data sheets for agency
listing status of battery cabinets and chargers. The batteries detailed in this document
meet the requirements of UL, ULC, and Factory Mutual for use with respective equipment
battery chargers as listed on page 3. Contact your local Simplex product supplier for
proper battery selection per system requirements. Listings and approvals under Simplex
Time Recorder Co. are the property of Tyco Fire Protection Products.
S2081-0006-21 12/2014
Battery Size Specifications
Battery Model Capacity ® 20 Hour Width* Depth* Height with Approximate
Discharge Rate Terminals Weight*
2081-9272 6.2 Ah 6-1/3" (156 mm) 2-5/8" (67 mm) 4" (102 mm) 5.75 lbs (2.6 kg)
2081-9274 10Ah (153 mm) 4-1/16" (103 mm) 4" (102 mm) 9.2 lbs (4.2 kg)
2081-9288 12.7 Ah 6" (153 mm) (102 mm) 4" (102 mm) 9 lbs (4.1 kg)
2081-9275 18 Ah 7-1/4" (184 mm) 3-3/8" (86 mm) 6-5/8" (168 mm) 14.3 lbs (6.5 kg)
2081-9287 . 25 Ah 6-5/8" (168 mm) (127 mm) (178 mm) 19.4 lbs (8.8 kg)
2081-9271
(rectangular case, 33 Ah 12-1/2" (318 mm) 3-3/8" (86 mm) 7-1/16" (179 mm) 26.6 lbs (12.1 kg)
typically for service)
2081-9276
("square" case, 33 Ah 7-3/4" (197 mm) 5-1/4" (133 mm) 6-3/4" (171 mm) 26.5 lbs (12 kg)
use for new)
2081-9296 50 Ah 9" (229 mm) 5-1/2" (140 mm) 8-7/8" (225 mm) 41.8 lbs (19 kg)
2081-9279 110 Ah 11-3/16" (284 mm) 10-1/2" (267 mm) 9" (230 mm) 82 Lbs (37 kg)
N
Battery Construction Reference
Actual appearance will vary with battery size.
Sealed outer cover
Vent hole Quick connect or post type terminal Potting material, black for (type varies with battery size) negative, red for positive
(polarity is also clearly
lit marked with + and -)
Pressure relief valve
Inner
Absorbent separator used
to immobilize electrolyte
Semi-permeable
Lead-calcium grids / membrane separator
Cell group~T '4_~ .
Cell case (high impact
polystyrene)
* Dimensions and weight are per battery and are for reference only. Exact size may-vary. Refer to the tables on page 3 for
mounting compatibility. These batteries are 12 V each and series connected for 24 V system use.
NOTE: When wired in series for 24 V output, these batteries are to be of identical voltage, appearance, model number, and
approximately the same date of manufacture.
General Battery Specifications
Nominal Voltage Rating 12 Volts per battery
Discharge Rating 20 Hour Rate
Typical Charge/Discharge Cycles 100 to 150
Preferred Charge Temperature Range 60° F to 90° F (15.6°C to 32.2" C)
S2081-0006-21 12/2014
INK Battery Compatibility for Fire Alarm Control Panel Mounting
NOTE: Refer to individual fire alarm control panel product data sheets for additional battery application information
Simplex Control Panel Model Series (see legend and notes below) Battery Capacity
4003EC 4004R 4007ES & 4006 & 4009 4010 4OIOES 4I00ESI 4100 & 4120 Model
4005 4008 (all models) 4100U (2, 4 or 6-Unit)
2081-9272 6.2 Ah / / / / / / / / I
2081-9274 10 Ah I / 1 1 / / / It
2081-9288 12.7 Ah I I / / I / / / /
2081-9275 18 Ah Ext Note / Ext Ext Note 1 / If
2081-9287 25 Ah Ext Note 3 Ext Ext NA / / 1 /
2081-9271 33 Ah Ext Note 3 Ext NA NA Note 3 1 1 Ext rectangular
2081-9276 33 Ah Ext Note 3 Ext NA NA Note 3 ' square"
2081-9296 50 Ah NA Note 3 NA NA NA Note 3 Note 6 2 or 3 bay Ext
2081-9279 110 Ah Requires external battery cabinet, compatible with 4100ES, 4010ES, 4100, and 4120 Series only
/ = Can be placed in the respective equipment cabinet
Ext = External battery cabinet is required, refer to selection chart on page 4
NA = Not applicable/not compatible
NOTES:
1 These batteries meet the requirements of UL, ULC, and Factory Mutual for use with respective equipment battery chargers
listed above. Contact your local Simplex product supplier for proper battery selection per system requirements.
4010 Cabinets will accommodate 2081-9275, 18 Ah batteries, but will not allow bottom entry conduit.
Use 4081 series companion cabinet and charger, refer to page 4.
Some control panel models are listed for battery replacement reference only.
For 2 bay international applications only, 50 Ah batteries will fit in the cabinet.
External Battery Cabinet Compatibility Reference
Battery Cabinets without Chargers (connects to charger in panel)
Battery
Cabinet Panel Compatibility 2081-9275 2081-9287 2081-9271 2081-9276 2081-9296 2081-9279
18 Ah* 25 Ah Rectangular 33 Ah Square 33Ah 50 Ah 110Ah
2081 -9280 4100ES, 4O1OES, NA NA NA NA NA /
4100U, and 4100+
2081-9281 multiple / / / / / NA
2081-9282
4009-9801 multiple / I NA NA NA NA
4009-9802 multiple / NA / NA NA NA
Battery Cabinets with Chargers
2081-9275 2081-9287 2081-9271 2081-9276 2081-9296 2081-9279
Cabinet Panel Compatibility 18 Ah* 25 Ah Rectangular 33 Ah Square 33 Ah 50 Ah 110 Ah
4081-9301 4004R and 4010 / / / / / NA
4081-9302
4081-9306 4100ES, 4010ES, NA NA NA NA
4081-9308 and 4100U
* Batteries smaller than those listed are normally mounted in the product cabinet
** 25 Ah capacity was effective as of 7/2005.
/ = Can be placed in the respective equipment cabinet
NA = Not applicable/not compatible
S2081-0006-21 12/2014
External Battery Cabinet Specification Reference
_
Battery Cabinets Without Chargers; Shallow Design with Front Door
Model Color Listings Description Dimensions
2081-9281 Beige UL and
FM
2-Unit, 4100 style cabinet without charger; with locking
solid door and battery shelf, primarily for use with 50 Ah
batteries
25-3/4" W 20-3/4" H x 6-3/4" D
(654 mm x 527 mm x 171 mm) 2081-9282 Red
4003-9860 Beige Multiple Intended for use with 4003EC systems, for up to 33 Ah 9-1/2" H x 24" W x 9" D
batteries (refer to 4003EC data sheet S4003-0002) (241 mm x 610 mm x 229 mm)
40099801* Beige UL and For up to 25 Ah I External battery cabinet without charger, 16-1/4" W X 13-1/2" H X 5-3/4" ID
FM batteries* I with locking solid door and battery
I harness; for close-nippled mounting to
(413 mm x 343 mm x 146 mm)*
4009-9802 Beige UL For up to 33 Ah 25-3/4" W 20-3/4" H x 4-1/8" D
batteries fire alarm control panel cabinet (654 mm x 527 mm x 105 mm)
* Depth increased for 25 Ah batteries effective 7/2005.
Chargers for use with 4010 Fire Alarm Control Panels and 4004R Suppression Release Systems
(refer to data sheet S4081-0001)
Model Color Input Voltage Description Dimensions
Battery cabinet with charger for the 4010 and 4081 -9301 Beige I 4004R fire alarm control panel; for up to 50 Ah
120 VAC I batteries; with front door 22-1/2" W x16-3/4" H x 8-3/8" D
(572 mm x 425 mm x 213 mm)
4081-9302 Red Listings include: UL, ULC, FM, CSFM, and MEA
(NYC), see data sheet for details
Battery Cabinet Without Charger for 110 Ah Batteries; for use with compatible panel mounted chargers
(refer to data sheet S2081-0012)
Model &
Listings Color Cabinet Description Compatible Charger Description Chargers Dimensions
4010-9xxx 401OES Main System Supply
Series (MSS)
4100-9xxx 4100ES/4100U System Power
Series Supplies (SPS)
4100-5111 Battery cabinet for
2081-9279, 110 Ah 4100-5112 4100E5/4100U Additional SPS
2081-9280 batteries; includes 4100-5113
4100-5125 Listings Red 80 A battery fuse, 26-1/2" W x 12" H x 12" D
include: UL terminals and 4100-5126 4100E5/4100U Remote Power (673 mm x 305 mm x 305 mm)
and CSFM battery connection 4100-5127 Supply (RPS)
cables; see data 4100-5120 sheet for details 4100-5121 4100E5/4100U TrueAlert
4100-5122 Addressable Power Supply (TPS)
4100-0104
4100-0114 4100 Legacy power supplies
4100-0124
4I00ES/40I0ES/4100U Compatible Battery Cabinet With Charger for 110 Ah Batteries (for ULC listed systems
and for other applications unable to use panel mounted power supply charger; refer to data sheet S4081-0002)
Model Color Input Voltage Description Dimensions
Battery cabinet with charger for up to 110 Ah
4081-9306 Red 120 VAC batteries;
NOTE: Required for ULC listed charging of 27-7/8" W 13-1/2" H x 14-5/8" D
110 Ah batteries; Listings include: UL, ULC, FM, (708 mm x 343 mm x 371 mm)
4081-9308 Red 20/230/24
' CSFM, and MEA (NYC), see data sheet for multi-tapped details
4100-9837 Green LED Power-on Indicator Kit, required for ULC listing, mounts above access panel using knockout provided
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.
®S i rn p1 EX Tyco Fire Protection Products • Westminster, MA 01441-0001 USA - S2081-0006-21 12/2014
02014 Tyco Fire Protection Products. All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice.
BSimpIEx
UL, ULC, CSFM Listed; FM Approved;
MEA (NYC) Acceptance*
I11!lt*1
TrueAlarm analog sensing provides:
Digital transmission of analog sensor values via IDNet
or MAPNET II two-wire communications
For use with the following Simplex® products:
4007ES, 4010, 4010ES, 4100ES, and 4100U Series
control panels; and 4008 Series control panels with
reduced feature set (refer to data sheet S4008-0001 for
details)
4020, 4100, and 4120 Series control panels, Universal
Transponders, and 2120 TrueAlarm CDTs equipped
for MAPNET H operation
Fire alarm control panel provides:
Peak value logging allowing accurate analysis of each
sensor for individual sensitivity selection
Sensitivity monitoring satisfying NFPA 72 sensitivity
testing requirements; automatic individual sensor
calibration check verifies sensor integrity
Automatic environmental compensation, multi-stage
alarm operation, and display of sensitivity directly in
percent per foot
Ability to display and print detailed sensor
information in plain English language
Photoelectric smoke sensors provide:
Seven levels of sensitivity from 0.2% to 3.7%
(refer to additional information on page 3)
Heat sensors provide:
Fixed temperature sensing
Rate-of-rise temperature sensing
Utility temperature sensing
Listed to UL 521 and ULC-S530
General features:
Operation is for ceiling or wall mounting
Listed to UL 268 and ULC-S529
Louvered smoke sensor design enhances smoke
capture by directing flow to chamber; entrance areas
are minimally visible when ceiling mounted
Designed for EMI compatibility
Magnetic test feature is provided
Different bases are available to support a supervised
or unsupervised output relay, and/or a remote LED
alarm indicator
Additional base reference:
For isolator bases, refer to data sheet S4098-0025
For sounder bases, refer to data sheet S4098-0028
For photo/heat sensors, refer to data sheet S4098-0024
(single address) and S4098-0033 (dual address)
* These products have been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listings
7272-0026:218, 7271-0026:231 7270-0026:216, and 7300-0026:217 for allowable values
and/or conditions concerning material presented in this document. Accepted for use - City of
New York Department of Buildings - MEA35-93E. Additional listings may be applicable,
contact your local Simplex product supplier for the latest status. Listings and approvals under
Simplex Time Recorder Co. are the property of Tyco Elm Protection Products.
TrueAlarm Analog Sensing
TrueAlarm Analog Sensors - Photoelectric
and Heat; Standard Bases and Accessories
4098-9714 TrueAlarm Photoelectric
Sensor Mounted in Base
Description
Digital Communication of Analog Sensing.
TrueAlarm analog sensors provide an analog
measurement digitally communicated to the host control
panel using Simplex addressable communications. At the
control panel, the data is analyzed and an average value is
determined and stored. An alarm or other abnormal
condition is determined by comparing the sensor's present
value against its average value and time.
Intelligent Data Evaluation. Monitoring each sensor's
average value provides a continuously shifting reference
point. This software filtering process compensates for
environmental factors (dust, dirt, etc.) and component
aging, providing an accurate reference for evaluating new
activity. With this filtering, there is a significant reduction
in the probability of false or nuisance alarms caused by
shifts in sensitivity, either up or down.
Control Panel Selection. Peak activity per sensor is
stored to assist in evaluating specific locations. The alarm
set point for each TrueAlarm sensor is determined at the
host control panel, selectable as more or less sensitive as
the individual application requires.
Timed/Multi-Stage Selection. Sensor alarm set points
can be programmed for timed automatic sensitivity
selection (such as more sensitive at night, less sensitive
during day). Control panel programming can also provide
multi-stage operation per sensor. For example, a 0.2%
level may cause a warning to prompt investigation while a
2.5% level may initiate an alarm.
Sensor Alarm and Trouble LED Indication. Each
sensor base's LED pulses to indicate communications
with the panel. If the control panel determines a sensor is
in alarm, or is dirty or has some other type of trouble, the
details are annunciated at the control panel and that sensor
base's LED will be turned on steadily. During a system
alarm, the control panel will control the LEDs such that
an LED indicating a trouble will return to pulsing to help
identify the alarmed sensors.
S4098-0019-20 1/2015
TrueAlarm Sensor Bases and Accessories
Base mounted address selection:
Address remains with its programmed location
Accessible from front (DIP switch under sensor)
General features:
Automatic identification provides default sensitivity when
substituting sensor types
Integral red LED for power-on (pulsing), or alarm or trouble
(steady on)
Locking anti-tamper design mounts on standard outlet box
Magnetically operated functional test
F1] iI.1fM*
4098-9792, Standard Sensor Base
4098-9789, Sensor Base with wired connections for:
2098-9808 Remote LED alarm indicator or 4098-9822 relay
(relay is unsupervised and requires separate 24 VDC)
Supervised Relay Bases (not compatible with 2120 CDT):
4098-9791, 4-Wire Sensor Base, use with remote or
locally mounted 2098-9737 relay, requires separate 24 VDC
4098-9780, 2-Wire Sensor Base, use with remote or
locally mounted 4098-9860 relay, no separate power
required
Supervised relay operation is programmable and can be
manually operated from control panel
Includes wired connections for remote LED alarm indicator
or 4098-9822 relay (relay is unsupervised and requires
separate 24 VDC)
2098-9737, Remote or local mount supervised relay:
DPDT contacts for resistive/suppressed loads, power limited
rating of 3 A @28 VDC; non-power limited rating of 3 A
@ 120 VAC (requires external 24 VDC coil power)
4098-9860, Remote or local mount supervised relay:
SPDT dry contacts, power limited rating of 2 A @ 30 VDC,
resistive; non-power limited rating of 0.5 A @ 125 VAC,
resistive
4098-9822, LED Annunciation Relay:
Activates when base LED is on steady, indicating local
alarm or trouble
DPDT contacts for resistive/suppressed loads, power limited
rating of 2 A @ 28 VDC; non-power limited rating of
1/2 A @ 120 VAC, (requires external 24 VDC coil power)
4098-9832, Adapter plate:
Required for surface or semi-flush mounting to 4" square
electrical box and for surface mounting to 4" octagonal box
Can be used for cosmetic retrofitting to existing 6-3/8"
diameter base product
2098-9808, Remote red LED Alarm
Indicator:
Mounts on single gang box (shown in
illustration to right) ALARM
asimpl
flisirintinn
TrueAlarm sensor bases contain integral addressable
electronics that constantly monitor the status of the
detachable photoelectric or heat sensors. Each sensor's
output is digitized and transmitted to the system fire alarm
control panel every four seconds.
Since TrueAlarm sensors use the same base, different
sensor types can be easily interchanged to meet specific
location requirements. This feature also allows intentional
sensor substitution during building construction. When
conditions are temporarily dusty, instead of covering the
smoke sensors (causing them to be disabled), heat sensors
may be installed without reprogramming the control
panel. Although the control panel will indicate an
incorrect sensor type, the heat sensor will operate at a
default sensitivity providing heat detection for building
protection at that location.
rcererence
Electrical Box Requirements: (boxes are by others)
Without 1glay in the box: 4" octagonal or 4" square, 1-1/2" deep:
single gang, 2' deep
With relay in the box : 4" octagonal or 4" square, 1-1/2" deep.
with 1-1/2" extension ring
4" (102 mm) Square Box 4" (102 mm) Octagonal Box
Surface mount reference-,
I)
o[I+fio oft
1-1/2" (38 mm) I
minimum box depth Flush mount reference, mount even with final
surface, or with up to 1/4" (6.4 mm) maximum recess
2098-9737 Supervised Relay 4098-9822 Relay (mounts
(mounts in base electrical box or in base electrical box)
remotely)
S,:2-1/2" X
3.75 in3) (64 mm X 38 mm X 25.4 mm)
4098-9860 Supervised Relay (mounts in base
electrical box or remotely: 2-3/8" X 1-1/4" X 11/32
(1 in 3)(60.4 mm X 31.8 mm X 8.6 mm)
t~Mf
NOTE: Review total wire count, wire size, and accessories being
wired to determine required box volume.
I. 6-3/8" (162 mm)
t 4098-9832 Adapter Plate, required for 1/4" mounting to surface mounted boxes
(6.4 mm) .gmm flush box
4-7/8" (124 mm) RI
15/16" fl (24 mm) 0
TrueAlarrn Bases
4098-9780, 4098-9789, 4098-9791, & 4098-9792
S4098-0019-20 1/2015
TrueAlarm Sensors
Sealed against rear air flow entry
Interchangeable mounting
EMl/RFI shielded electronics
Heat sensors:
Selectable rate compensated, fixed temperature
sensing with or without rate-of-rise operation
Rated spacing distance between sensors:
Fixed Temp.
Setting
UL & ULC
Spacing
FM Spacing, Either Fixed
Temperature Setting
135° F 60 ft x60 ft 20ftx20 ft(6.1 m) for fixed
(57.2° C) (18.3 m) temperature only; RTI = Quick
50ftx50 ft (15.2 m) for fixed 155° F 40 ft X 40 ft temperature with either rate-of-rise (68° C) (12.2 m) selection; RTI = Ultra Fast
Smoke Sensors:
Photoelectric technology sensing
3600 smoke entry for optimum response
Built-in insect screens
TrueAlarm photoelectric sensors use a stable, pulsed
infrared LED light source and a silicon photodiode
receiver to provide consistent and accurate low power
smoke sensing. Seven levels of sensitivity are available
for each individual sensor, ranging from 0.2% to 3.7% per
foot of smoke obscuration. Sensitivities of 0.2%, 0.5%,
and 1% are for special applications in clean areas.
Standard sensitivities are 1.5%, 2.0%, 2.5%, 3.0%, and
3.7%. Application type and sensitivity are selected and
then monitored at the fire alarm control panel.*
TrueAlarm heat sensors are self-restoring and provide rate
compensated, fixed temperature sensing, selectable with
or without rate-of-rise temperature sensing. Due to its
small thermal mass, the sensor accurately and quickly
measures the local temperature for analysis at the fire
alarm control panel.
Rate-of-rise temperature detection is selectable at the
control panel for either 15° F (8.3° C) or 20° F (11.1° C)
per minute. Fixed temperature sensing is independent of
rate-of-rise sensing and programmable to operate at
135° F (57.2° C) or 155° F (68° Q. In a slow developing
fire, the temperature may not increase rapidly enough to
operate the rate-of-rise feature. However, an alarm will be
initiated when the temperature reaches its rated fixed
temperature setting.
TrueAlarm heat sensors can be programmed as a utility
device to monitor for temperature extremes in the range
from 32° F to 155° F (0° C to 68° C). This feature can
provide freeze warnings or alert to HVAC system
problems. Refer to specific panels for availability.
f -I 4-7/8" (124 mm)
LED status indicator
2-3/8'
(60 mm)
4098-9733 Heat Sensor with Base
The sensor head design provides 360° smoke entry for I WARNING: In most fires, hazardous levels of smoke I
optimum response to smoke from any direction. Due to its and toxic gas can build up before a heat detection
photoelectric operation, air velocity is not normally a device would initiate an alarm. In cases where Life
factor, except for impact on area smoke flow. Safety is a factor, the use of smoke detection is highly I
I recommended. I
f 4 4-7/8' (124 mm)
I LED status indicator
2-1/8'
(54 mm)
4098-9714 Photoelectric Sensor with Base
[Annliratinn
Sensor locations should be determined only after careful
consideration of the physical layout and contents of the
area to be protected. Refer to NFPA 72, the National Fire
Alarm and Signaling Code. On smooth ceilings, smoke
sensor spacing of 30 ft (9.1 m) may be used as a guide.*
* For detailed application information including sensitivity
selection, refer to Installation Instructions 574-709.
S4098-0019-20 1/2015
\ TrueAlarm Sensor Bases (for use with Sensors 4098-9714 and 4098-9733)
(Refer to Application Manual 574-709 and Installation Instructions 574-707 for additional information)
Model I Description I Compatibility Mounting Requirements
4098-9792 Standard Sensor Base No options 4" octagonal or 4" square box, 1-1/2" mm.
depth; or single gang box, 2" mm. depth
N
Sensor Base with connections for 2098-9808 Remote Alarm Indicator or 4098-9789 Remote LED Alarm Indicator or
Unsupervised Relay 4098-9822 Unsupervised Relay 4" octagonal or 4" square box
Note: Box depth requirements depend on 4-Wire Sensor Supervised Relay 2098-9737 Supervised Remote Relay
4098-9791°° Base with connections for LED total wire count and wire size, refer to 2098-9808 Remote Alarm Indicator or
Indicator or Unsupervised Relay 4098-9822 Unsupervised Relay accessories list below for reference.
** NOTE: 4098-9791 and 4098-9780 are NOT 2-Wire Sensor Supervised Relay 4098-9860 Supervised Remote Relay
40989780** Base with connections for LED compatible with the 2120 CDT 2098-9808 Remote Alarm Indicator or
Indicator or Unsupervised Relay 4098-9822 Unsupervised Relay
TrueAlarm Sensors
Model I Description
4098-9714 Photoelectric Smoke Sensor
4098-9733
Compatibility
Bases 4098-9792, 4098-9789,
4098-9791, and 4098-9780
Mounting Requirements
Refer to base requirements
TrueAlarm Sensor/Base Accessories
Model Description Compatibility Mounting Requirements
2098-9737 Supervised Relay, mounts remote or in base For use with 4098-9791 base Remote Mounting requires 4" octagonal
electrical box - or 4" square box, 1-1/2" minimum depth
Base Mounting requires 4" octagonal 4098-9860 Supervised Relay, mounts remote or in base For use with 4098-9780 base electrical box box, 2-118" deep with 1-1/2" extension ring
2098-9808 Remote Red LED Alarm Indicator on single Bases 4098-9789, 4098-9791, Single gang box, 1-1/2" minimum depth gang stainless steel plate and 4098-9780
4098-9822 Unsupervised Relay, tracks base LED status; Bases 4098-9789, 4098-9791, 4" octagonal box, 2-1/8" deep with 1-1/2"
Note: Mounts only in base electrical box and 4098-9780 extension ring
Bases 4098-9792, 4098-9789, Required for surface or semi-flush
4098-9832 Adapter Plate 4098-9791, and 4098-9780 mounted 4" square box and for surface mounted 4" octagonal box
0-TTIOMT, M,
General Operatinq Specifications
Communications and Sensor Supervisory Power IDNet or MAPNET II communications, auto-selected, 1 address per base
Communications Connections Screw terminals for in/out wiring, 18 to 14 AWG (0.82 mm2 to 2.08 mm2)
Remote LED Alarm Indicator Current 1 mA typical, no impact to alarm current
Remote LED Alarm Indicator and Relay Connections Color coded wire leads, 1&AWG (0.82 mm2 )
UL Listed Operating Temperature Range 32" to 100" F (0° to 38° C)
Operating Temperature with 4098-9733 Heat Sensor
Range with 4098-9714 Smoke Sensor
32° to 122° F (0° to 50° C)
15° to 122° F (-9° to 50° C)
Storage Temperature Range 0° F to 140° F (-18° C to 60° C)
Humidity Range 10 to 95% RH
4098-9714 Smoke Sensor Air Velocity Rating 0-4000 ft/mm (0-1220 rn/mm)
Housing Color Frost White
4098-9791 Base With Supervised Remote Relay 2098-9737 (see page 2 for contact ratings)
Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC)
Supervisory Current 270 sA, from 24 VDC supply
Alarm Current with 2098-9737 Relay 28 mA, from 24 VDC supply
4098-9780 Base With Supervised Remote Relay 4098-9860 (see page 2 for contact ratings)
Power I Supplied from communications
4098-9822 Unsupervised Relay, Requirements for Bases 4098-9789. 4098-9791, and 4098-9780 (see page 2 for contact ratings)
Externally Supplied Relay Coil Voltage 18-32 VDC (nominal 24 VDC)
Supervisory Current Supplied from communications
Alarm Current 13 mA from separate 24 VDC supply
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and
Signaling Code are trademarks of the National Fire Protection Association (NFPA).
J1.SiMpJ1EX Tyco Fire Protection Products• Westminster, MA 01441-0001 USA - S4098-0019-20 1/2015
www.simplex-fire.com
02015 Tyco Fire Protection Products. All rights reserved All specifications and other information shown were current as ofdocument revision date and are subject to change without notice.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0026:0217 Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: SimplexlOO Simplex Drive, Westminster, MA 01441-0001
Contact: Jim Goyette (978) 731-8580 Fax (978) 731-8881
Email: jgoyette@tycoint.com
_______
DESIGN: Models 4098-9780,-9780E, *9772 -9789, -9789E, 9789TSP, -9789TT1,9791E,
-9791TSP, 97911TP,-9792, -9792E, -9792TSP, 9792TTP, -9793, -9793E, -9793T5P,
-9793TTP, -9794, -9794TSP, -97941TP, -9795, -9795TSP, -9795TTP, -9796, -9796T5P,
-979611P; G5A4098-9780, -9792, -9793, -9795 and -9796 smoke detector bases. These
bases act as an interface between the sensor and the MAPNET controller. Bases are
intended for use with the following units: Models 4098-9714 and G5A4098-9714 series
photoelectric smoke detector (CSFM Listing No. 7272-0026:218); Model 4098-9717
ionization smoke detector (CSFM Listing No. 7271-0026-.231)-, and Models 4098-9733,
G5A4098-9733, *4098.9734 and *GsA4098.9734 heat detectors (CSFM Listing No.
7270-0026:216). Models 4098-9795, -9795T5P, -9795TTP, -9796, -9796TSP, -9796TTP;
GSA4098-9795, and -9796 are only intended for use with Models 4098-9754 or
G5A4098-9754 photoelectric smoke detector (CSFM Listing No.7272-0026:218). Refer to
listee's printed data sheet for additional detailed product description and operational
considerations.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name, model number, electrical rating, and UL label.
APPROVAL: Listed as detector bases for use with listee's separately listed compatible fire alarm control
units. Refer to listee's Installation Instruction Manual for details.
Models 4098-9794, -9794TSP, -97941TP, -9795, -9795T5P, -97951TP, *9772 and
G5A4098-9795 employ a sounder, which is also suitable for use as a fire alarm audible
signaling device. These base/sounders CAN NOT produce the temporal code pattern in
accordance with NFPA 72, 2002 Edition. If this temporal code is required, the sounder/base
unit must be used with the control unit that can produce the temporal pattern.
*Rev. 04-21-16 dc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2017 Listing Expires June 30, 2018
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7272-0026:0218 Page 1 of 1
CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC
LISTEE: SimplexlOo Simplex Drive, Westminster, MA 01441-0001
Contact: Jim Goyette (978) 731-8580 Fax (978) 731-8881
Email: jgoyettetycoint.com
DESIGN: Models 4098-9714, *.9774 -9714T5P, -9714TTP, -9754 -9754T5P, -9754TTP;
G5A4098-9714, and -9754 analog photoelectric type smoke detectors. Units are intended for
use with smoke detector bases Models 4098-9789 9789T5P, -9789TTP, -9791, -9791TSP, *
9775 * -9776, *..9777 -979111P, -9792, -9792T5 P, 97921TP, -9793, 9793T5P, -9793TTP,
-9794, -9794T5P,-9794TTP; GSA4098-9792, and -9793 (CSFM Listing No. 7300-0026:217).
Models 4098-9714, -9714T5P and -97141TP are listed for use with Models 4098-9750-9751,
-9752 and -9753 duct detector units (CSFM Listing No. 3240-0026:220) and Models
4098-9755, -9755T5P and -97551TP duct detector units (CSFM Listing No. 3240-0026:241).
Models 4098-9754, *..9779 -9754TSP, -9754TTP; G5A4098-9754 analog photoelectric type
smoke detectors employ an integral supplemental heat sensor (1350 F fixed temperature
and 1200 F rate of rise). This heat sensor is intended for use as a supplemental device to the
smoke detector and is not intended for use in lieu of required heat detectors.
Refer to listee's printed data sheet for additional detailed product description and operational
considerations.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. Model 4098-9714 with Model
4098-9751 is suitable for installations inside air ducts with air velocities between 0-2000 fpm.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as photoelectric smoke detectors for use with listee's separately listed compatible fire
alarm control units. Refer to listee's Installation Instruction Manual for details.
NOTE: The photoelectric type detectors are generally more effective at detecting slow, smoldering
fires which smolder for hours before bursting into flames. Sources of these fires may include
cigarettes burning in couches or bedding. The ionization type detectors are generally more
effective at detecting fast, flaming fires that consume combustible materials rapidly and
spread quickly. Sources of these fires may include paper burning in a waste container or a
grease fire in the kitchen.
*Revision 12-13-2016 dc
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2017 Listing Expires June 30, 2018
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
BSimpIEx TrueAlarm Analog Sensing
UL, ULC, CSFM Listed; FM Approved; Addressable Duct Sensor Housings with TrueAlarm
MEA (NYC) Acceptance* Photoelectric Sensor; Available with Multiple Relay Control
I11uI *1
Compact air duct sensor housing with clear
cover to monitor for the presence of smoke**
Includes factory installed TrueAlarm
photoelectric smoke sensor and features:
Individual sensor information processed by the host
control panel to determine sensor status
Digital transmission of analog sensor values via IDNet
or MAPNET II, 2-wire communications
Programmable sensitivity, consistent accuracy,
environmental compensation, status testing, and
monitoring of sensor dirt accumulation
Model 4098-9755:
Basic duct sensor housing (no relay output) powered
by IDNetJMAPNET II communications
Model 4098-9756:
Duct sensor housing with supervised output for
multiple remote relays; requires separate 24 VDC;
includes one relay
Relay output is under panel control
At the panel, relay output can be activated manually or
in response to a separate alarm or other input
General features:
UL listed to Standard 268A
Clear cover allows visual inspection
Test ports provide functional smoke testing access
with cover in place
Mounts to rectangular ducts or round ducts; minimum
size is 8" (203 mm) square or 18" (457 mm) diameter
Magnetic test feature for alarm initiation at housing
Optional weatherproof enclosure is available
separately (refer to data sheet S4098-0032)
Diagnostic LEDs (on interface board):
Red Alarm/Trouble LED for sensor status and
communications polling display
Yellow LED for open or shorted trouble indication of
supervised relay control (4098-9756 only)
Sampling tubes (ordered separately):
Available in multiple lengths to match duct size
Installed and serviced with housing in place
Remote module options (ordered separately):
Remote red status/alarm LED (2098-9808)
Remote test station with LED (2098-9806)
4098-9843 remote relays (refer to page 2 for details)
* These products have been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13/44.1 of the California Health and Safety Code. See CSFM Listing 3240-0026.241
for allowable values and/or conditions concerning material presented in this document. It is
subject to re-examination, revision, and possible cancellation. Accepted for use - City of New
York Department of Buildings - MEA35-93E. Additional listings may be applicable: contact
your local Simplex product supplier for the latest status. Listings and approvals under Simplex
Time Recorder Co. are the property of Tyco Fire Protection Products.
Duct Sensor Housing, Front and Bottom View
& m
0
0
2098-9808 2098-9806
Remote Status/Alarm Indicator and Test Station
jrIuctir
Operation. Simplex® compact air duct smoke sensor
housings provide TrueAlarm operation for the detection of
smoke in air conditioning or ventilating ducts. Sampling
tubes are installed into the duct allowing air to be directed to
the smoke sensor mounted in the housing.
IIlit7..F1 E1II..1 ii.] £11 N i1(Ii1i1
Digital Communication of Analog Sensing.
Analog information from the sensor is digitally
communicated to the control panel where it is analyzed.
Sensor input is stored and tracked as an average value
with an alarm or abnormal condition being determined by
comparing the sensor's present value against its average.
Intelligent Data Evaluation. Monitoring each
photoelectric sensor's average value provides a software
filtering process that compensates for environmental
factors (dust, dirt, etc.) and component aging, providing
an accurate reference for evaluating new activity. The
result is a significant reduction in the probability of false
or nuisance alarms caused by shifts in sensitivity, either
up or down.
** Please note that smoke detection in air ducts is intended to provide
notification of the presence of smoke in the duct. It is not intended
to, and will not, replace smoke detection requirements for open
areas or other non-duct applications.
S4098-0030-9 11/2012
I21f(fTi7llfliF1JJj
Typically duct sensor applications require less sensitive
settings (such as 2.5% per foot obscuration) due to the
ducts being a relative dirty environment. However, the
standard seven levels of TrueAlarm sensor sensitivity are
available for each individual sensor, ranging from 0.2% to
3.7% per foot of smoke obscuration. Sensitivity is
selected and monitored at the fire alarm control panel.
Individual smoke sensitivity selection
Sensitivity monitoring that satisfies NFPA 72
sensitivity testing requirements
Peak value logging allows accurate analysis for
sensitivity selection
Automatic, once per minute individual sensor
calibration check verifies sensor integrity
Automatic environmental compensation
Smoke sensitivity is displayed in percent per foot
Ability to display and print detailed sensor
information in plain English language
Relays of model 4098-9756 are under panel control
I IBM for ON, OFF, or override
\\
\
Ii ,ii.i&ISi;1;1
Duct Smoke Sensor Housing with Photoelectric Sensor*
Model Description - Compatibility
Basic Duct Sensor Housing; Simplex fire alarm control panel models: 4100ES,
operating power is supplied by 4O1OES, 4008, 4010, 4100U, and legacy products 4098-9755 either IDNet or MAPNET II commLnications (no relay 4020, 4100/4100+, and 4120. Also 2120 CDT if output) configured for MAPNET II, TrueAlarm operation
Duct Sensor Housing with supervised multiple relay output, Same as above except relay operation is not
4098-9756 requires separate 24 VDC fire alarm power and 4081-9008 compatible with 2120 CDT;
end-of-line resistor harness; includes one 4098-9843 relay Relay output is for up to 15 total 4098-9843 Relays
(additional relays are ordered separately)
Remote LED Indicator and Test Station, Select One if Required
Model Description
2098-9808 Red LED status indicator on single-gang stainless steel plate
Test Station with keyswitch and red LED status indicator, on
2098-9806 single-gang stainless steel plate; (turning switch to TEST"
initiates alarm for system testing)
Epoxy Encapsulated Remote Relay and End-of-Line Resistor
Model Description
Relay; single Form C (7 A @ 120 VAC); refer to pages 3 and 4
4098-9843 for additional relay information; one included with 4098-9756;
wiring is 18 AWG (0.82 mm2 ) color coded wire leads
Compatibility
4098-9755
4098-9756
Compatibility
4098-9756 only;
connect up to 15
Mounting
Use single gang box,
3" Hx2"Wx2" D
(76 mm x 51 mm x 51 mm)
Location
Locate relays within 3 ft
(1 m) of device being
controlled per NFPA 72
4081-9008 I End-of-Line Resistor Harness; 10 kQ, 1/2W; (ref. 733-894);
required to supervise remote relay coil connection 4098-9756 At last relay location
* Each duct housing includes an internally mounted model 4098-9714 TrueAlarm photoelectric sensor and an exhaust tube. A correctly
sized sampling tube (ordered per application) is required, refer to chart below.
Sampling Tube Selection Chart, Ordered Separately Per Duct Width, Select One
Overall Duct Width
(305 mm)
Tube Required
4098-9854
Suggested Cut Length
1/2" (12.7 mm) longer than duct width
to 23" (330 mm to 584 mm) 4098-9855 1/2" (12.7 mm) longer than duct width
24" to 46" (610 mm to 1168 mm) 4098-9856 3 in" (76 mm) longer than duct width
46" to 71" (1168 mm to 1803 mm) 4098-9857 3 in" (76 mm) longer than duct width
71" to 95" (1803 mm to 2413 mm) 4098-9858 3 in" (76 mm) longer than duct width
S4098-0030-9 11/2012
flT 1I1I,.] &.i.i T(TII1iTh1iJ
Control Panel Selection. Peak activity per sensor is
stored to assist in evaluating specific locations. The alarm
set point for each sensor is determined at the control
panel, selectable as the individual application requires.
Sensor Status LED. Each sensor housing's red status
LED (located on the electrical interface board) pulses to
indicate communications with the panel. If the control
panel determines that a sensor is in alarm, or that it is
dirty or has some other type of trouble, the details are
annunciated at the control panel and that sensor housing's
status LED will be turned on steadily. During a system
alarm, the control panel will control the LEDs such that
an LED indicating a trouble will return to pulsing to help
identify any alarmed sensors. (Remote Status/Alarm
LEDs track the operation of the sensor housing LED.)
ii-rnnti
TrueAlarm photoelectric sensors use a stable, pulsed
infrared -LED light source and a silicon photodiode
receiver to provide consistent and accurate low power
smoke sensing.
IBM r F ni iniuR1 14 M I IM
NOTE: Refer to Installation Instructions 574-776 for additional installation detail and maintenance information.
—11-3/8(289 mm)—
rExhaust tube access hole
6-3/4
(171 mm)
4098-9714 Smoke sensor, mounted
in soecial interface base (suDolied) al plate with dual holes
3/4(19mm) conduit, plug
olied for unused hole
amp1ing tube
access hole
Yellow LED, relay control trouble
indicator (4098-9756 Only)
MKIF
Red sensor]
status LEDJ of duct
screws
11
3-318'
(86 mm)
!(.asKetea sensor area
NOTE: Orientation shown is for reference
only, refer to General Location Notes and
End View illustration below for alternate
mountina reference.
(21 mm) I
Test ports (2) provided
for measuring airflow
and for aerosol injection
Sampling tube, ordered
separately per duct width
4098-9843 Remote Relay
(7 A © 120 VAC, for use with 4098-9756 only)
NOTE: Mount in separate electrical box within
3 ft (1 m) of device being controlled per
NFPA 72
1-3/16"
(30 mm)
1-1/2" 13/16"
(38 mm) (21 mm)
reference outline
Alternate location
(jf aoorooriate)
18" Round duct outline
(minimum diameter) Sampling tube, keyed for proper hole alignment with holes facing
into airflow (template is provided for proper tube installation).
(Housing is shown as position 2 per note 2 below.)
Ll
Duct
. .
I
Nam==
General Location Notes:
1 Testing performed under the auspices of the Fire Detection
Institute (FDI) recommended when sampling tubes are not
located vertically, that they be positioned horizontally in the
upper half of the duct to account for possible stratification.
2. Three duct side mounting options are available as shown below.
Mount housing at 90° to airflow for all orientations.
Arrows indicate allowed airflow directions.
Square duct outlinel
(minimum width)
DO NOT MOUNT ON
BOTTOM OF DUCT
/\
3 S4098-0030-9 11/2012
Duct Sensor Location Reference
Exhaust Damper Sensor OK
Exhaust II Return Air
Do not locate
sensor here
Return air
damper
Fresh air-'- Supply Air
Do not locate Filter bank Sensor OK
sensor here
Additional Information. Refer to NFPA 90A, Standard
for the Installation ofAir Conditioning and Ventilating
Systems; NFPA 72, the National Fire Alarm and Signaling
Code; and the NEMA Guide for Proper Use of Smoke
Detectors in Duct Applications, and Installation Instructions
574-776.
Duct Sensor Location Considerations:
I. Proper duct smoke detection location must ensure
adequate airflow within the duct housing.
Duct air velocity rating is 300 to 4000 ft/min (91 to
1220 mlmin). Pressure differential between intake
and exhaust tubes is required to be between 0.015 to
1.55 inches of water (0.381 to 39.37 mm).
Ensure accessibility for test and service.
Proper Locations: downstream side of filters to detect
fires in the filters; in return ducts, ahead of mixing
areas; upstream of air humidifier and cooling coil.
Other locations and orientations may be required for
proper duct smoke detection depending on duct
access, system design, and duct airflow testing.
Contact your local Simplex product supplier for
assistance.
Locations to Avoid:
Where dampers closed for comfort control would
interfere with airflow.
Next to outside air inlets (unless the intent is to
monitor smoke entry from that area).
In return air damper branch ducts and mixing areas
where airflow may be restricted.
Specifications
General Mechanical and Environmental
Air Velocity Range (linear ft/mm) 300 to 4000 ft/min (91 to 1220 rn/mm)
Sensor Sensitivity Range 0.2% to 3.7% per foot of obscuration, selectable at host control panel
UL Listed Temperature Range 32° F to 100° F (0° C to 38° C)
Operating Temperature Range 32° F to 122° F (0° C to 50° C)
Storage Temperature Range 0° F to 140° F (-18° C to 60° C)
Humidity Range 10% to 95% RH, non-condensing
Wiring Connections Terminal blocks, 18 to 12 AWG (0.82 mm2 to 3.31 mm2 )
Housing Color Black base with clear cover
Remote Status/Alarm LED and Test Station with Remote Status/Alarm LED
Remote Alarm LED Current 1.2 mA, no impact to 24 VDC alarm current (2098-9808 or 2098-9806)
Test Station Keyswitch Current 3.3 mA, no impact to 24 VDC alarm current (2098-9806)
Remote Alarm LED and Test Station Distance 250 ft (76 ml maximum
Addressable Operation
Data Communications lDNet or MAPNET II communications, auto-select, one address per housing;
provides operating power to model 4098-9755
Model 4098-9756 with Supervised Multiple Relay Control, Requires Separate Fused 24 VDC from Fire Alarm Power Supply
Input Voltage . 18-32 VDC (24 VDC nominal)
Standby Current 3 mA @ 24 VDC
Alarm Current 15 mA @ 24 VDC; add 15 mA for each 4098-9843 relay
Supervised Remote Relay Control Output
For use with 4098-9843 relay only, quantity of 15 maximum; distance of 500 ft
(152 m) maximum; requires 4081-9008 (ref. 733-894)10 k(), 1/2 Wend-of-line
resistor
4098-9843 Relay Output Ratings, Single Form C, use with Model 4098-9756 Only -
Coil Current 15 mA @24 VDC, up to 15 maximum per relay control output
Relay Contacts 7 A at 0.35 PF @ 28 VDC & 120 VAC; 250 iA @ 5 VDC
Location Distance 500 ft (152 m) maximum to relay coils; locate relays within 3 ft (1 m) of device
being controlled per NFPA 72
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and
Signaling Code are registered trademarks of the National Fire Protection Association (NFPA).
Siin p I EX Tyco Fire Protection Products Westminster, MA • 01441-0001 USA S4098-0030-9 11/2012
www.simplexgrinnell.com
0 2012 Tyco Fire Protection Products. All rights reserved All specifications and other information shown were current as of document revision date and are subject to change without notice.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 3240-0026:0241 Page 1 of 1
CATEGORY: 3240 -- DUCT SMOKE DETECTOR HOUSING/BASE
LISTEE: Simplexloo Simplex Drive, Westminster, MA 01441-0001
Contact: Jim Goyette (978) 731-8580 Fax (978) 731-8881
Email: jgoyette@tycoint.com
DESIGN: Models 4098-9755, *40989755Tsp *40989755up 4098-9756, *40989756TSp
*4098..9756up 4098-9685, 4098-9686, 4098-9687 and 4098-9688 photoelectric type air duct
smoke detector units and Model 4098-9841 relay (for Model 4098-9688 only). Unit consists
of a listed detector head, base, a sampling and an exhaust tube and an enclosure. Refer to
listee's data sheet for additional detailed product description and operational considerations.
RATING: Air Velocity: 300 -4000 feet/min
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listees name, model number, electrical & air velocity rating, and UL label.
APPROVAL: Listed as duct smoke detector units for installation in HVAC systems when used with
separately listed compatible fire alarm control units. Refer to listee's Installation Instruction
Manual for details.
NOTE:
*Rev. 11-06-03
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2017 Listing Expires June 30, 2018
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
S.Simplex
UL, ULC, CSFM Listed;
FM Approved*
It(Ii(41
Individual Addressable Relay Module (Relay lAM):
A single addressable point provides control and status
tracking of separate, 8 A Normally Open (Form A, NO)
and 8 A Normally Closed (Form B, NC) contacts
Low power latching relay design allows IDNet
communications to supply both data and module power
Operation upon loss and restoration of communications
is switch selectable to either reset the output relays to
normal or to keep them latched in the selected state
For use with following Simplex® control panels:
Model Series 4007E5, 4008, 4010, 4010ES, 4100ES,
and 4100U fire alarm control panels for IDNet
communications
Compact construction:
Mounts in standard 4" (102 mm) square electrical box,
optional adapter bracket is available to mount in a
4 / square electrical box
Screw terminals for wiring connections
Visible LED flashes to indicate communications, can be
selected at panel to indicate activated state
Optional 4" square box covers are available to allow
LED to be viewed after installation
UL listed to Standard 864
I I.i*i.iitlltlN
8 A Relay lAMs allow fire alarm control panels to
control a remotely located NO and NC contact using
IDNet addressable communications for both data and
module power. Typical applications would be for
switching local power for control functions such as
elevator capture, or control of HVAC components,
pressurization fans, dampers, etc. Relay status is also
communicated requiring only one device address.
Model Description
4090-9010 8 A Relay [AM
Optional Trim Plates and Adapter
Model Description
4090-9801 For semi-flush Trim plate, galvanized
mounted box steel, with LED viewing
4090-9802 For surface window; includes
mounted box mounting screws
4090-9813 Adapter plate to fit 4 11/fl (119 mm) square
electrical box
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7300-0026:0311 for allowable values and/or conditions concerning material presented in
this document. Additional listings may be applicable; contact your local Simplex product
supplier for the latest status. Listings and approvals under Simplex Time Recorder Co. are
the property of Tyco Fire Protection Products.
Multi-Application Peripherals
IDNet Communicating Devices
Model 4090-9010, 8 A Relay JAM
4090-9010 8 A IDNet Relay [AM Package
(shown approximately 1/2 size)
Communications IDNet communications 1 address per
device
Relay lAM Power Supplied by IDNet communications
Installation 579-1063 Instructions
Contact Ratings* (not rated for incandescent switching)
Type I Separate contacts; 1, NO and 1, NC
Maximum Voltage 250 VAC or 30 VDC Ratings
Current Ratings 8 A, resistive
3.5 A, inductive at 0.35 PF
* Provide circuit fusing and transient suppression as
required per application. DC inductive loads can typically
be diode suppressed; 120/240 VAC loads may require RC
networks or varistors, depending on device type. Refer to
Installation Instructions for additional information.
Wire .Connections Screw terminals for in/out wiring,
18 to 14 AWG wire (0.82 to 2.08 mm2)
Up to 2500 ft (762 m) from control
panel
IDNet
Communications Up to 10,000 ft (3048 m) total wiring
Wiring Reference distance (including T-Taps)
Compatible with Simplex 2081-9044
Overvoltage Protectors
Dimensions 4 %"H x 4" W x 1 %"D
(105 mm x 102 mm x 35 mm)
Mounting Plate Sheet metal, galvanized
Temperature 32° to 120° F (0° to 49° C),
Range intended for indoor operation
Humidity Range Up to 93% RH at 100° F (38° C)
S4090-0015-1 11/2014
8 A Relay lAM Mounting Information
4" (102 mm) square box, 2-1/8"
(54 mm) minimum depth, RACO
232 or equal (supplied by others)
Double gang blank cover plate and mounting screws, for
use when LED is not required to be externally viewed
(supplied by others)
Mounting Reference, Double Gang Blank Cover Plate
© © © ©
Add supplied label to
Av8nsso4T:I cover on-site if controlling AVTISSJT:
4-9/16" 120 or 240 VAC 4-5/16"
(116 mm) (109mm)
Light pipe for LED viewing
© ©
© ©
4-9/16" (116 mm) 41 -4-5/16" (109 mm)
4090-9801, Trim plate for 4090-9802, Trim plate for
semi-flush mounted box surface mounted box
Optional Trim Plates for Visible LED
TYCO, S1IvlPLE), and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.
S- IE Tyco Fire Protection Products• Westminster, MA 01441-0001 USA S4090-0015-1 11/2014
www.simplex-fire.com
0 2014 Tyco Fire Protection Products. All rights reserved All specf1catioss and other information shown were current as of document revision date and are subject to change without notice.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0026:0311 Page 1 of 1
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: SimplexloO Simplex Drive, Westminster, MA 01441-0001
Contact: Jim Goyette (978) 731-8580 Fax (978) 731-8881
Email: jgoyettetycoint.com
DESIGN: Models 4090-9118 relay lAM (individually addressable module) module, 4090-9119 relay lAM
module with unsupervised feedback, 4090-9008 dual relay lAM, *40909010 eight amp relay
lAM and 4090-9120 six-point I/O module. (lAM). Refer to listee's data sheet for detailed
product description and operational considerations.
RATING: 30 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as control unit accessories for use with listee's separately listed compatible fire alarm
control units.
*Rev. 04-24-13 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2017 Listing Expires June 30, 2018
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
®SimpIEx TrueAlert Addressable Notification Appliances
UL, ULC, CSFM Listed; FM Approved, Multi-Candela Visible Only (VIO)
MEA (NYC) Acceptance* Appliances (Strobes), Ceiling Mount
I
Individually addressed and controlled
multi-candela VIO (visible only) notification
appliances provide:
Multi-candela xenon strobe with synchronized 1 Hz
flash rate and with intensity programmable from the
control panel or jumper selected as 15, 30, 75, or
110 cd
Advanced addressable notification controlled by IDNAC
SLCs providing regulated 29 VDC allowing strobes to
operate with lower current even under battery backup
Wiring supervision to each strobe allowing
"T-tapped" connections for Class B circuits to
simplify wiring (Class A circuits require in/out
wiring)
TrueAlert Device Reports at the control panel
detailing appliance point ID, custom label, type, and
candela setting (see sample on page 2)
Magnet test diagnostics to assist checkout and testing
of appliances and wiring
Compatibility with ADA requirements
Compatibility with legacy TrueAlert addressable
systems for upgrade and replacement (see page 3)
UL listed to Standard 1971 and UtCS526*
LED indicator and magnet test feature:
Appliance LED can be selected to display each polling
cycle to indicate appliance supervision
In diagnostic mode, the magnet test pulses the LED to
indicate appliance address AND pulses to indicate the
intensity selection; a brief output of the strobe is also
selectable to confirm operation
Mechanical design features:
Rugged, high impact, flame retardant ceiling mount
thermoplastic housings are available in red or white
Rear of housing does not extend into box and easily
mounts to standard electrical boxes
Mounting options include red wire guards and
adapters for surface mounted electrical boxes
* See page 2 for wire guard listings. This product has been approved by the California State
Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety
Code. See CSFM Listing 7125-0026:235 for allowable values and/or conditions concerning
material presented in this document. Accepted for use - City of New York Department of
Buildings - MEA35-93E. Additional listings may be applicable; contact your local Simplex
product supplier for the latest status. Listings and approvals under Simplex Time Recorder
Co. are the property of Tyco Safety Products Westminster.
Ceiling Mount Addressable V/Os
I'i*N i111t1
Multi-Candela TrueAlert addressable strobes
provide convenient installation to standard electrical
boxes. The strobe is individually addressed and
individually controlled with power, supervision, and
control supplied from a Simplex fire alarm control panel
providing IDNAC Signaling Line Circuits (SLCs). (See
compatibility list on page 3.)
rM
Proper selection of visible notification is dependent on
occupancy, location, local codes, and proper applications
of: the National Fire Alarm and Signaling Code
(NFPA 72), ANSI A117. 1; the appropriate model
building code: BOCA, ICBO, or SBCCI; and the
application guidelines of the Americans with Disabilities
Act (ADA).
TrueAlert addressable appliances on IDNAC SLCs
provide separate visible (and audible) notification using a
single two-wire circuit that also confirms connection to the
individual notification appliance's electronic circuit. This
operation increases circuit supervision integrity by providing
supervision that extends beyond the appliance wiring
connections.
Reduced current allows efficient IDNAC SLC
operation. With IDNAC SLCs, a constant 29 VDC
source voltage is maintained, even during battery standby,
allowing strobes to operate at higher voltage with lower
current and ensuring a consistent current draw and voltage
drop margin under both primary power and secondary
battery standby. Efficiencies include wiring distances up
to 2 to 3 times farther than with conventional notification,
or support for more appliances per IDNAC SLC, or use of
smaller gauge wiring, or combinations of these benefits,
all providing installation and maintenance savings with
high assurance that appliances that operate during normal
system testing will operate during worst case alarm
conditions.
S4906-0004-4 212015
Reducing Installation and Testing Time. With
separate controls on the same two-wire SLC, installation
time and expense for both retrofit and new construction
can be significantly reduced. When Class B wiring is
used, wiring can be "T" tapped, allowing more savings in
distance, wire, conduit (size and utilization), and overall
installation efficiency. Use of the magnet test feature
improves installation efficiency. TrueAlert device reports
conveniently identify information about each connected
appliance.
M mil IT, ITY. III IT --i 'in MM MR ri1
Isolator Model 4905-9929 is available for remote
mounting on TrueAlert addressable circuits to isolate
short circuited wiring from functioning wiring. (Refer to
data sheet S4905-0001 for additional information.)
Test Features. Controllers can be selected to pulse each
appliance's LED when it receives a supervision poll.
When the controller is selected for diagnostic mode, the
appliance magnet test feature provides a response at the
individual appliance being tested.
Silent Appliance Magnet Test. In this test mode, in
response to the magnet test, the appliance LED pulses
sequentially to conveniently indicate the appliance's
address.
Operational Appliance Testing. In this test mode,
after the address is indicated by pulsing the appliance
LED, the strobe will briefly flash to indicate proper
operation.
TrueStart Instrument Two (TSIT). The 2nd
generation of the Simplex TrueStart Test Instrument adds
testing of IDNAC SLC wiring and TrueAlert (and
TrueAlert ES) appliances to its ability to test 1DCs,
NACs, and IDNet communications before connection to
the control panel. Please contact your local Simplex
representative for additional information.
Product Selection
Multi-Candela Ceiling Mount Addressable Strobe
Model Housing
Color "FIRE" Lettering I :1 I Dimensions Description
4906-9202 Red I White I 4 % x 2 6" x 2 W D
(121 mmx75mmx67mm)
Multi-Candela Addressable Strobe;
intensity selectable as: 15, 30, 75, or
110 candela 4906-9204 White Red
VIO Adapters (see diagram on page 3)
Model I Description I Dimensions
4905-9910 I Ceiling Mount, Surface Mount Adapter Plate, zinc plated; required for I I 4%"x3W(124mmx79mm) ceiling surface mount
Wire Guards (see diagram on page 3)
Model I Description I Dimensions
49059926* Ceiling Mount Red wire guard with mounting plate, compatible with I 6 'h' x 4 3/' x 2 /8"
semi-flush or surface mounted boxes I (156 mm x 111 mm x 73 mm)
* UL listed by Space Age Electronics Inc
TrueAlert Device Reports Reference 1 0 --
Service
REPORT 5
Port
: TrueAlert Device Report
Page 1
12:34:56am TUE 27-Jan-15
DEVICE
POINT ID CUSTOM LABEL TYPE CANDELA
T14-1-1 Location Label . . . up to 40 characters V/O 15
T14-1-2 Break Room 5 A/V 110
T14-1-3 Boiler Room A/V 75
T14-1-4 Elec. Room 7 A/V 30
2 S4906-0004-4 2/2015
Ceiling Mount V/O and Guard Installation Reference
Handy box, 1-1/2" ( 38 mm) deep (RACO 650 or
Single gang box (Wiremold V5744S) equal) or single gang box, 2-1/2' (64 mm) deep
2-1/4" (57 mm) deep, supplied by others (RACO 519 or equal) supplied by others
Also can be attached to boxes mounted to drop
ceiling T-bar with clips (ERICO No. 512 or equal) Address setting DlPswitch is behind strobe
assembly, select address and strobe 4905-9910 Adapter Plate, required for surface
mount with handy box unless using the 4905-9926 candela setting before inserting into housing ° (ID
wire guard
(Ell i Ceiling mount strobe Magnetic - - Bottom view- -I-- test location Optional 4905-9926 wire
guard with mounng pte
-----------------------------------------
oi Strobe intensity viewing slot
Intensity selection plug,
accessible only from rear of lens
housing; factory setting is FACP,
LED indicator controlled by pan ------------------------------------------
hi] IL. 1IflZsiii.ifl 11lW1 It I,t41
Compatible Controllers Data Sheet
Reference Controller Output IDNAC SLC Output
Voltage
Appliance Voltage
Design Reference
4100ES with EPS+orEPS Power Supply S4100-0100
IDNAC SLC
S4010-0011
29 VDC
(regulated)
23 VDC
(with 6 VDC drop)
4009 IDNAC Repeater S4009-0004
4007ES with IDNAC Notification S4007-0002
4010ES with ESS Enhanced System Supply
Specifications
General Specifications (see page 2 for dimensions)
Environmental 32° to 122° F (0° to 50° C); 10% to 93%, non-condensing at 100° F (38° C)
Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm2 to 3.31 mm2); two wires per
terminal for in/out wiring
Installation Instructions 579-808
Strobe Specifications
Typical Operating Voltage Range 23-VDC to 31 VDC, Special Application (see below for 17 VDC rating)
Supervisory Requirements 1 unit load (= 0.8 mA control panel current)
Flash Rate and Synchronized SLC Loading 1 Hz; with up to 46 synchronized strobes maximum per NAC
Candela Setting 15 c I 30 c I 75 c 110 c
23 VDC RMS Current Ratings, for connection to
IDNAC Addressable SLCs
60 mA 92 mA 180 mA 240 mA
TrueAlert Strobe LEGACY Compatibility Reference
Compatible Controller Data Sheet
Reference Controller Output Available Strobe
Intensity
Appliance Voltage
Minimum
4100ES or4100U with TrueAlert Power Supply S4100-0031 TrueAlert
Addressable SLC
15, 30, 75, and
ll0cd
S4009-0003
17 VDC 4009 TPS, Remote TrueAlert Power Supply S4100-0037
TrueAlert Addressable Controller (4009T)
Electrical Ratings Difference for Retrofit Applications
Voltage Range 17 VDC to 31 VDC, Special Application
Candela Setting 15 c 30 c 75 c 110 c
17 VDC RMS Current Ratings, use when
connected to TrueAlert Addressable SLCs per 76 mA 128 mA 242 mA 328 mA
above
S4906-0004-4 2/2015
TYCO, SIMPLEX and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. NFPA 72 and National Fire Alarm and
Signaling Code are registered trademarks of the National Fire Protection Association (NFPA).
B®Si in plEx Tyco Fire Protection Products Westminster, MA • 01441-0001 • USA S4906-0004-4 2/2015
www.simplexgrinnell.com
02015 Tyco Fire Protection Products. All rights reserved. All specifications and other information shown were current as ofdocument revision date and are subject to change without notice.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0026:0235 Page 1 of 1
CATEGORY: 7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: Simplexloo Simplex Drive, Westminster, MA 01441-0001
Contact: Jim Goyette (978) 731-8580 Fax (978) 731-8881
Email: jgoyette@tycoint.com
DESIGN: Models "TrueAlert non-addressable "4904-9331, 4904-9342, 4904-9332, 4904-9343,
4904-9333 and 4904-9344 synchronized strobe lights.
Models "TrueAlert non-addressable" 4904-9168, 4904-9171, 4904-9169, 4904-9172,
4904-9170 and 4904-9173 non-synchronized strobe lights.
Models 'TrueAlert addressable' 4904-9350, 4904-9351, 4904-9352, 4904-9353, 4904-9354,
4909-9355 synchronized strobe lights.
Models "TrueAlert addressable" 4904-9356, 4904-9357, 4904-9358, 4904-9359, 4904-9360,
4909-9361 synchronized strobe lights.
Models "TrueAlert addressable" 4906-9201, -9202, -9203, -9204, and -9208 synchronized
multi-candela strobe lights are intended for indoor use. *Models 4906-9201, -9203 and -9208
are intended for wall mounted only. *Models 4906-9202 and -9204 are intended for ceilingl
mounted only. Intended for use with either Model 4209-9401 NAC Extender or with the
TrueAlert power supply of Model 4100U fire alarm control panel. Model 4906-9208 employs
two lenses, clear lens for "Fire" and amber for "Non-Fire".
Model 4905-9938 sync control module. Refer to listee's data sheet for detailed product
description and operational considerations.
RATING: 4904-9331, -9342, -9350, -9353, -9356, -9359, -9168, -9171: 15cd, 1 Hz.
4904-9332, -9343, -9351, -9354, -9357, -9360, -9169, -9172: 75cd, 1 Hz.
4904-9333, -9344, -9170, -9173, -9352, -9355, -9358, -9361: 11Ocd, 1 Hz.
Models 4906-9201, -9202, -9203, -9204, -9208: 15, 30, 75, 110cd, 1 Hz
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. Intended for indoor use and
wall mounting only.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as strobe lights suitable for the hearing impaired when used with listee's separately
listed fire alarm control units. For "TrueAlert non-addressable" synchronized strobes, Model
4905-9938 sync control module must be used.
*Rev 04-02-15 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
v" operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2017 Listing Expires June 30, 2018
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
55i m plEx TrueA!ert Addressable Notification Appliances
UL, ULC Listed* Wall and Ceiling Mount Addressable Speaker
H-H and Speaker Visible Notification Appliances
93-1m-
Individually addressed and controlled Speaker
(SIO) and Speaker Visible (SN) notification
appliances
Advanced addressable notification controlled by IDNAC
SLCs provides regulated 29 VDC for low current operation
even under battery backup.
Wiring supervision is electronically monitored and
allows audio wiring to be T-tapped for class B wiring,
reducing wiring costs and wiring distances.
Speaker selectivity is controlled by the panel. Only those
speakers that are needed are connected to the audio
NAC.
Separate appliance and cover selection greatly simplifies
the ordering and installation process.
Strobe intensity can be programmed from the control
panel or the device for S/V models.
Self-Test Mode allows on-board sensors to detect the
strobe and speaker output and then report their status to
the control panel.
Wiring terminals separate from the Audio terminals.
TrueAlert Device Reports at the control panel detailing
appliance point ID, custom label, type, and candela
setting.
Magnet test diagnostics to assist checkout and testing of
appliances and wiring.
Compatibility with ADA requirements.
LED indicator and magnet test feature
Appliance LED can be selected to display each polling
cycle to indicate appliance supervision
in diagnostic mode, the magnet test pulses the LED to
indicate appliance address and pulses to indicate the
intensity selection; a brief output of the strobe is also
selectable to confirm operation
Mechanical design features
Rugged, high impact, flame retardant thermoplastic
housings are available for wall or ceiling mount models
Covers are available in red or white with various
lettering options
Covers can be easily removed without disturbing the
connected housing and avoiding trouble conditions
In/out wiring terminals for 18 AWG to 12 AWG
Mounts to 4" square 2 J/8' gang US electrical boxes
Additional listings maybe applicable; contact your local Simplex product supplier for
the latest status. Listings and approvals under Simplex Time Recorder Co. are the
property of Tyco Fire Protection Products.
Ceiling and Wall Mount Addressable Speaker Only and
Speaker Visible Strobes
I1'I*mirn11l4I
Speaker design features
High quality voice and tone reproduction with taps for
¼,V2, 1,or2W,at25or70.7VRIv1S
Speakers have capacitor input for connection to DC
supervised NACs and are wired separately from strobes
Listed to UL 1480 and ULC S541*
Compliant with NFPA 72, 520 Hz Low Frequency
Signal Requirements for Sleeping Areas
High and low frequency response models available,
200-10000 Hz and 400-4000 Hz respectively.
lI1*i.iIiIffi]i1
Wall and ceiling mount addressable speaker and
speaker visible appliances provide convenient
installation to standard electrical boxes. The speaker is
individually addressed and individually controlled with
power, supervision, and control supplied from a Simplex
fire alarm control panel IDNAC Signaling Line Circuit
(SLC). Audio is provided by a panel that supports audio
output or from a separate audio source. Appliances use a
multi-tapped speaker for audio/tone notification.
Proper selection of visible notification is dependent on
occupancy, location, local codes, and proper applications
of: the National Fire Alarm and Signaling Code
(NFPA 72), ANSI A117.1; the appropriate model
building code: BOCA, ICBO, or SBCCI; and the
application guidelines of the Americans with Disabilities
Act (ADA).
S49SWC-0001-1 11/2015
ii .I.i .i f•I L'n1ij
TrueAlert Addressable speaker and speaker
visible appliances on IDNAC SLCs provide visible
and audio notification using two separate two-wire
circuits that also confirms connection to the individual
notification appliance's electronic circuit. This operation
increases circuit supervision integrity by providing
supervision that extends beyond the appliance wiring
connections.
Reduced current usage on IDNAC SLCs
A constant 29 VDC source voltage is maintained, even
during battery standby. This allows appliances to operate
at higher voltage with lower current and ensuring a
consistent current draw and voltage drop margin under
both primary power and secondary battery standby.
Efficiencies include wiring distances up to 2 to 3 times
farther than with conventional notification, support for
more appliances per IDNAC SLC, use of smaller gauge
wiring, or combinations of these benefits.
Reducing Installation and Testing Time
With separate controls on the same two-wire SLC,
installation time and expense for both retrofit and new
construction can be significantly reduced. When Class B
wiring is used, wiring can be "T" tapped, allowing more
savings in distance, wire, conduit (size and utilization), and
overall installation efficiency. Use of the magnet test feature
improves installation efficiency. TrueAlert device reports
conveniently identify information about each connected
appliance.
Isolator Model 4905-9929 is available for remote
mounting on TrueAlert addressable circuits to isolate short
circuited wiring from functioning wiring. Refer to data sheet
S4905-0001 for additional information.
ITflI*II1t*hr.i1t1
Test Features
Controllers can be selected to pulse each appliance's LED
when it receives a supervision poll. When the controller is
selected for diagnostic mode, the appliance magnet test
feature provides a response at the individual appliance being
tested.
Silent Appliance Magnet Test
The appliance LED pulses sequentially to conveniently
indicate the appliance's address when a magnet is applied.
Operational Appliance Testing
In this test mode, after the address is indicated by pulsing the
appliance LED, the strobe will briefly flash to indicate
proper operation.
TrueStart Instrument Two (TSIT)
The 2nd generation of the Simplex TrueStart Test
Instrument adds testing of IDNAC SLC wiring and
TrueAlert (and TrueAlert ES) appliances to its ability to test
lDCs, NACs, and IDNet communications before connection
to the control panel. Please contact your local Simplex
representative for additional information.
IATflhI N 0=1I1l1iM7T I!TI.1 F1M
Wall Mount S/O Appliances* (Refer to data sheet S49SOW-0001 for full product selection including covers and mounting plates)
Model Dimensions I Description Data Sheet Reference
49S0-APPLW(-BM 5 V,' H x 5" W 1 1/," fl S/fl nnhirIrp only
\
49HF-APPLW(-BA) (139 mm 128 rnrnx38 mm) HighfideiityS/Oappliance only jS49SOW0001
Wall Mount SN Appliances* (Refer to data sheet S49SVW-0001 for full product selection including covers, mounting plates, and
multi-color strobe lens)
Model Series I Dimensions Description Data Sheet Reference AQ4ZX/_ADD1W(-BA) 7 /" H x 5" Wx 1 3,4 0
*Note: Wall mount models require separately ord
Wil all Ir ru
Ceiling Mount S/O Appliances (Refer to data sheet S49SOC-0001 for full product selection and installation requirements)
Model Dimensions Description Data Sheet Reference
49S0-APPLC(-BA) 7 %" H x 7 1/8 W x 1 1/," D S/0 appliance only S49SOC 0001 \ 49HF-APPLC(-BA) (180 mm x 180 mm x 32 mm) High fidelity S/0 appliance only -
Ceiling Mount SN
Model Series
49HFV-APPLC(-BA)
49HFVH-APP
49HFVH-APLCA-BA
49HFVH-APLCB-BA
8W H x 7W W 3" D
(206 mm x 180 mm x 76 mm)
Clear lens high fidelity high candela
SN aDpliance only
Amber lens high fidelity high
candela SN appliance only
Blue lens high fidelity high candela
SN appliance only
S49SVC-0001
Note: Select appliance, cover and mounting back plate (where required) separately. (-BA) indicates model is available either with or
without the -BA suffix. Model numbers ending in -BA are assembled in the USA
S49SWC-0001-1 11/2015
49HFV-APPLW(-BA) (187mm x 128mm x 43
Vapp uiai II.. UI II
High fidelity SN appliance only -j S49SVW-0001
back plate. See related datasheet for details.
49SV-APPLC(-BA)
liances (Refer to data sheet S49SVC-0001 for full product selection and installation requirements)
Dimensions Description Data Sheet Reference
SN appliance only
Hicih fidelity SN appliance only
IDNAC SLC Controller Compatibility Reference
Compatible Controllers Data Sheet Controller Output IDNAC SLC Output Appliance Voltage
Reference Voltage Design Reference
4100ES with EPS+ or EPS Power Supply S4100-0100
IDNAC SLC 29 VDC
(regulated)
23 VDC
(with 6 VDC drop)
4009 IDNAC Repeater S4009-0004
4100E5 Flex 35, 50, and 100 Amplifiers
S4100-0034 4100ES Constant Supervision and Signal
Cards
Specifications
General Specifications (refer to individual model data sheets. for further specifications, install and operation details)
Typical Operating Voltage Range 23 - 30 VDC, Special Application
Environmental 32° to 120° F (0° to 49° C); 10% to 93%, non-condensing at 104° F (40° C)
Connections Terminal blocks for 18 AWG to 12 AWG (0.82 mm to 3.31 mm'); two wires per terminal
for in/out wiring. Use Unshielded Twisted Pair (UTP) for IDNAC and audio wiring.
IDNAC SLC Loading Maximum of 127 addresses per SLC, 139 unit loads. See device and compatible fire
panel installation instructions for circuit current load limits.
Speaker Specifications
25 or 70.7 Vrms
/4, '/2, 1, and 2W Power Taps
400 to 4000 Hz and 200 to 10000 Hz, General Signaling = 125 to 12 kHz Frequency Response resoectivelv
Strobe Specifications
Typical Operating Voltage Range 23 - 30 VDC, Special Application
Supervisory Requirements 1 unit load (= 0.8 mA control panel current)
Flash Rate 1 Hz
IDNAC SLC Wiring Specifications
(refer to control panel installation instructions for
more information)
UTP, unshielded twisted pair recommended
Maximum wire length allowed with "1-Taps" for Class B wiring per SLC = 10,000 ft
(3048 m)
Maximum wire length to any appliance = 4000 ft (1219 m). This can be doubled to
8000ft (2438m) by using a 4009 IDNAC Repeater.
Note: Speakers are for connection to compatible fire alarm audio circuits only.
S49 Series Speaker Datasheet Reference
Model Data Sheet Reference
Wall Mount Speaker Only Appliance S49SOW-0001
Wall Mount Speaker Visible Appliance S49SVW-0001
Ceiling Mount Speaker Only Appliance 549S0C-0001
Ceiling Mount Speaker Visible Appliance S49SVC-0001
S49SWC-0001-1 11/2015
TYCO, SIMPLEX, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibiwd NFPA 72 and National Fire Alarm and
Signaling Code are registered trademarks of the National Fire Protection Association (?FPA).
Tyco Fire Protection Products• Westminster, MA 01441-0001 USA S49SWC-0001-1 11/2015
www.simplex-fire.com
0 2015 Tyco Fire Protection Products. All rights reserved All specifications znd other information shown were current as ofdocument revision dote and are subject to change without notice.
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0026:0384 Page 1 of 2
CATEGORY: 7125—FIRE ALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: SimplexioO Simplex Drive, Westminster, MA 01441-0001
Contact: Jim Goyette (978) 731-8580 Fax (978) 731-8881
Email: jgoyette@tycoint.com
DESIGN: Models:
495V-APPLC,49HFV-APPLC,49SV-APPLC-BA,49HFV-APPLC-BA,49SVH-APPLC-BA,
49HFVH-APPLC-BA,49SVH-APPLC,49HFVH-APPLC,49SV-CWF,49HFV-CWF,49SVH-CW
F and 49HFVH-CWS True Alert ES, Addressable ceiling mounted Speaker/Strobes.
Models:
495V-APPLW,49HFV-APPLW,49SV-APPLW-BA,49HFV-APPLW-BA,495V-WRF and
49HFV-WRF True Alert ES, Addressable wall mounted Speaker/Strobes.
Models:
49S0-APPLC, 49HF-APPLC, 4950-APPLC-BA, 49HF-APPLC-BA,4950-CW and 49HF-CW
True Alert ES, ceiling mounted Speakers.
Models:
4950-APPLW, 49HF-APPLW, 49S0-APPLW-BA, 49HF-APPLW-BA,4950-WRF and
49HF-WRF True Alert ES, wall mounted Speakers.
Models:
49SVC-CK,49SVC-CRALT,49SVC-CRFIRE,49SVC-CRS,49SVC-CRBC,49SVC-CWBC,
49SVC-CWFIRE,49SVC-CRFEU,49SVC-CRBF,49SVC-CWALT,49SVC-CWBA,49SVC-CRB
A,49SVC-CWS,49SVC-CWBF and 49SVC-CWFEU True Alert ES, Speaker/Strobe Ceiling
Mount Dress Covers.
Models:
49SVC-WRALT,49SVC-WRBA,49SVC-WRBC,49SVC-WRBF,49SVC-WRFEU,49SVC-WRFI
RE,49SVC-WRS,49SVC-NALT,49SVC-vwvBA,49SVC-WWBC,49SVC-V/WBF,49SVC-W
WFEU,49SVC-\M.NFIRE and 49SVC-WWS True Alert ES, Speaker/Strobe wall Mount Dress
Covers.
Models:
49SOC-CWFl RE,49SOC-CRFl RE,49S0C-CRS,49S0C-CWS,4950C-CK,4950C-CR,
49S0C-CW,4950C-CWALT and 49S0C-CRALT True Alert ES, Speaker Ceiling Mount
Dress Covers.
12-08-15 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2017 Listing Expires June 30, 2018
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
Listing No. 7125-0026:0384
Page 2of2
Models:
49S0C-WRFEU,49S0C-WRBF,4OSOCWRBC,49S0C-WRBA,49S0C-WIVS,49S0C-WtNFl
RE,49SOC-WRBLANK,49SOC-WRFlRE,49SOC-WRS,49SOC-WWBA,9SOC-WWBC,49S
OC-WWBF,49SOC-WNFEU,49SOC-WWBLANK,49SOC-WWALT and 49S0C-WRALT True
Alert ES, Speaker Wall Mount Dress Cover.
Models:
49MP-SVWR,49MP-SVWtN,49MP-SOWR and 49MP-SOWW True Alert ES,Back Plates.
Models:
49SV-LENS-AMBER,49SV-LENS-BLUE,49SV-LENS-RED and 49SV-LENS-GREEN
True Alert ES, Colored Lens Kit.
Refer to listee's data sheet for detailed product description and operational consideration.
RATING: 23-30 Vdc
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as signalling devices for the hearing impaired when used with listee's separately listed
electrically compatible fire alarm control units. For indoor use only. Refer to listee's
Installation Instruction Manual for details.
12-08-15 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
V,G operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2017 Listing Expires June 30, 2018
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
SimplexGrinnell LP
3568 Ruffin Road, South
San Diego, CA 92123-2597
Tele: (858) 633-9100
ell Fax: (858) 633-9101
www.simplexgrinnell.com
License
Number 986047
Business Information
SIMPLEXGRINNELL LP
12728 SHOEMAKER AVENUE
SANTA FE SPRINGS, CA 90670
Business Phone Number:(562) 405-3800
Entity Partnership
Issue Date 08/14/2013
Expire Date 08/31/2017
License Status
This license is current and active.
All information below should be reviewed.
Classifications
dO - ELECTRICAL
C16 - FIRE PROTECTION CONTRACTOR
Bonding Information
.ContractosBond
This license filed a Contractor's Bond with FEDERAL INSURANCE COMPANY.
Bond Number: 82332032
Bond Amount: $15,000
Effective Date: 10/01/2016
Bond of Qualifying Individual
This license filed Bond of Qualifying Individual number 82332031 for MAYLE RONALD GILBERT in the
amount of $12,500 with FEDERAL INSURANCE COMPANY.
Effective Date: 08/13/2013
This license filed Bond of Qualifying Individual number 82332035 for ROSTEN TIMOTHY PAUL in the
amount of $12,500 with FEDERAL INSURANCE COMPANY.
Effective Date: 08/13/2013
Workers' Compensaon I
This license has workers compensation insurance with the OLD REPUBLIC INSURANCE COMPANY
Policy Number:MWC308342
Effective Date: 10/01/2016
Expire Date: 10/01/2017
Workers' Compensation History
10/4/2016 REV.#: 0 PROJECT #: 480-XXXXXX-XX / X)000000(X
tqcn
Simple Grinnell
SimplexGrinnell LP
3568 Ruffin Road, South
San Diego, CA 92123-2597
Tele: (858) 633-9100
Fax: (858) 633-9101
www.simplexgrinnell.com
SIMPLEXGRINNELL WARRANTY
WARRANTY & DAMAGES: SimplexGrinnell hereby warranties for one (1) year from the date of beneficial use or
eighteen (18) months from date of delivery to the purchaser to replace, or at its option, to repair any equipment or
parts thereof which are found to be defective in material or workmanship. This warranty is made to the purchaser
of this equipment and is in lieu of all other warranties, expressed or implied, including any implied warranty of
merchantability of fitness for a particular purpose.
SimplexGrinnell shall not be liable for any direct, incidental or consequential loss of damage to the purchaser or
user of this equipment arising out of the failure of the equipment to operate in excess of the purchase price of said
equipment.
This warranty is solely limited to the equipment as provided by SimplexGrinnell in this submittal and excludes
associated field wiring and/or any equipment to which the submitted equipment may be attached or connected.
WARRANTY SERVICE HOURS:
8:00AM TO 17:OOPM, MONDAY THROUGH FRIDAY, EXCLUDING
LOCALLY OBSERVED SIMPLEX HOLIDAYS.
- OFF HOURS RESPONSE IS AVAILABLE AT EXTRA COST
10/4/2016 REV.#: 0 PROJECT #: 480-XX)000(-XX / XXX)O(XXXX