Loading...
HomeMy WebLinkAbout1 LEGOLAND DR; ; FS160007; PermitCity of Carlsbad Fixed Systems Permit Permit No: FS160007 Job Address: I LEGOLAND DR Status: ISSUED Permit Type: FIXSYS Applied 4/28/2016 Parcel No: 2111000900 Approved: 4/28/2016 Lot #: 0 Reference No.: Issued: 4/28/2016 PC #: Inspector: Project Title: NINJA KITCHEN TRAILER KITCHEN HOOD Applicant: NATIONAL PROTECTION INDUSTRIES 77570 SPRINGFIELD LANE PALM DESERT, CA 92260 619-345-1816 Owner: LEGOLAND CALIFORNIA L L C PLAY U S ACQUISI C/O PROPERTY TAX SERVICE CO P0 BOX 543185 DALLAS TX Fees ($) Add'I Fees ($) Total ($) Balance ($) 213 0 213 0 I KITCHEN KNIGHT® II: RESTAURANT FIRE SUPPRESSION SYSTEM - PC L-1 601300/460/600 P _ yri IC TECHNICAL MANUAL DESIGN FS 1 60007 I LEGOLMD DR Manual No. PN551274(4) Revised March 1, 2006 Chapter 3 - System Design Page 3-1 REV. 4 CHAPTER III SYSTEM DESIGN This chapter will detail the basic information necessary for proper design of the PYRO-CHEM KITCHEN KNIGHT II Restaurant Fire Suppression System. However, before attempting any installation, it is necessary to attend a Factory Certification Training Class and become Certified to design the PYRO-CHEM KITCHEN KNIGHT II Restaurant Fire Suppression System. The chapter is divided into three (3) sections: Nozzle Coverage and Placement Piping Limitations Detector Requirements Each of these sections must be completed before attempting any installation. NOZZLE COVERAGE AND PLACEMENT This section will provide guidelines for determining nozzle type, positioning, and quantity for duct, plenum, and appli- ance protection. Duct Protection It is not required that the fan be shut down or the exhaust duct be dampered for the system to operate properly. All duct protection is UL listed without limitation of maximum duct length (unlimited length). This includes all varieties of ductworks both horizontal and vertical including ducts that run at angles to the horizontal and ducts with directional bends. Duct protection requires that a nozzle be positioned to discharge into the duct. Two nozzles are available for duct protection. The Model IL Nozzle, Part No. 551026, is a one (1) flow nozzle. A single IL nozzle is capable of protecting square or rectangular ducts with a maximum perimeter of 50 in. (127 cm), with the diagonal being a maximum of 18 3/4 in. (47.6 cm). It can also protect a round duct with a maximum diameter of 16 in. (40.6 cm). The Model 2D duct nozzle, Part No. 551038, is a two (2) flow nozzle. A single 2D nozzle is capable of protecting square or rectangular ducts with a maximum perimeter of 100 in. (254 cm), with the diagonal being a maximum of 37 3/8 in. (94.9 cm). It can also protect a round duct with a maximum diameter of 31 7/8 in. (81 cm). When two (2) 2D duct nozzles are used to protect a single duct, the cross sectional area of the duct must be divided into two equal symmetrical areas. The nozzle must then be installed on the centerline of the area it protects and aimed directly into the duct opening. The nozzle(s) must be installed on the centerline of the duct, with the tip located 0 to 6 in. (15.2 cm) into the opening, and aimed directly into the duct opening. See Figure 3-1a. In installations where a UL listed damper assembly is employed, the duct nozzle can be installed beyond the 6 in. (15.2 cm) maximum, to a point just beyond the damper assembly that will not interfere with the damper. Exceeding the maximum of 6 in. (15.2 cm) in this way will not void the UL listing of the system. 0-6 IN. INTO DUCT IL OR 2D NOZZLE I ii4l ---,---- 1/2L Figure 3-la. ULEX 3830 March 1, 2006 Chapter 3 - System Design Page 3-2 REV.3 Modularizing Ducts DUCT SIZES GREATER THAN 100 IN. (254 cm) PERIMETER] Ducts over 100 in. perimeter must be modularized using 2D nozzles (Part No. 551038) No round duct option available Follow the design chart to determine maximum module size for each 2D nozzle When determining number of nozzles required, it is some- times an advantage to check the chart using the shortest side as Side 'A" and then recheck it using the longest side as Side "A'. This comparison may reveal a need for a lesser quantity of nozzles one way versus the other way. When working with Chart 1, the quantity of nozzles deter- mined must be equally divided within the duct area. CHART NO. 1 A• : . SIDE B" When working with Chart 2, one half of the quantity of nozzles determined must be equally positioned in the top half of the area of the duct and the remaining half of the nozzles must be positioned in the bottom half of the duct area. Example: The duct to be protected has a Side "A" of 40 in. and a Side "B" of 60 in. Referring to the design chart, this duct requires 4 nozzles. One half of 4 = 2. Therefore, 2 nozzles must be equally positioned in each of the two duct areas. See Figure 3-lb. SIDE "B" 30 IN. (76cm) 30 IN. (76cm) - 20 IN. (51 cm) SIDE 40 IN. "A" - - - - (102 cm) 20 IN. (51 cm) I 60 IN. (152 cm) Figure 3-1b. 006523 mmmmmmmmmmmmommmoommmmmmmmoommmommommmmmmmmm uun•uuauuua•uu•uau•u N•SUIMUSUUS•PIR•I$RUI•U CHART NO.2 B A IS S 3 36 37 38 40 [ 42 44 45 46 47 48 ULEX 3830 March 1, 2006 SIDE "A" 006522 - DUCT 0061 75PC Chapter 3 - System Design Page 3-3 REV. 3 I rJ1 Transition Ducts - The protection of non-standard ducts should be reviewed by the authority having jurisdiction. PYRO-CHEM KITCHEN KNIGHT II recommends that transi- tion ducts be protected as follows: a. Transition ducts - larger to smaller In cases where the duct/plenum interface opening is larger than the final exhaust duct, measure the perime- ter/diameter of the duct halfway between the largest and smallest section (or the average perimeter/diame- ter). The nozzle is to be located within 0-6 in. (15.2 cm) of the duct/plenum interface (not at the point where the measurement was taken), centered under the final exhaust duct opening. See Figure 3-1c. c. Multiple risers In cases of multiple rises, each riser is protected as an individual duct. See Figure 3-1e. PLENUM Figure 3-le PERIMETER —•-'-f- - - - MEASUREMENT / 006173PC Figure 3-1c. b. Transition ducts - smaller to larger In cases where the duct/plenum interface opening is smaller than the final exhaust duct, measure the perimeter/diameter of the final exhaust duct. The nozzle(s) is to be located within 0-6 in. (15.2 cm) of the duct/plenum interface, centered in the opening. See Figure 3-1d. PERIMETER -----*'- - - - MEASUREMENT 006 174PC Figure 3-1d Electrostatic Precipitator - Ducts utilizing electrostatic precipitators must be protected above and below the unit. Standard duct nozzles are used in this application. See Figure 3-1f. 20 NOZZLE - PRECIPITATOR PLENUM 20 NOZZLE 006176PC Figure 3-1t Plenum Protection The Model 1H nozzle, Part No. 551029, is a one (1)flow nozzle used for plenum protection. A single 1 H nozzle can protect a plenum (with single or V-bank filters) 10 ft. (3.1 m) long by 4 ft. (1.2 m) wide. Dividing the length into sections equal to or less than 10 ft. (3.1 m) in length and positioning a nozzle at the start of each section can be done to protect longer plenums. Y INTO ;ITION ULEX 3830 0. March 1, 2006 V BANK 1/fl LI OO6l77bPC SINGLE BANK ULEX 3830 Figure 3-2 March 1, 2006 Chapter 3 - System Design Page 3-4 REV. 3 On V-bank plenums, the nozzle(s) must be located at the center of the V-bank width, 1/3 of the vertical height of the filters. On single filter bank plenums, the nozzle must be located 2 in. (5.1 cm) from the back edge of the fiter, 1/3 down from the vertical height. For either application, the nozzle must be located within 6 in. (15.2 cm) of the end of the plenum (or module) and aimed directly down the length of the plenum. The nozzles may point in the opposite directions as long as the entire plenum area is protected, and the loft. (3.1 m) limitation is not exceeded. See Figure 3-2. Appliance Protection Note: When protecting appliances which are larger than single nozzle coverage, multiple nozzles can be used. Larger appliances can be divided into several modules, each equal to or smaller than single nozzle coverage. Exception: Fryers must not exceed a maximum of 864 sq. in. (5574 sq. cm). For modularizing fryers, refer to FRYER - MULTIPLE NOZZLE PROTECTION." Design Chart Appliance Maximum Cooking Type Hazard Area per Nozzle P. Fryer Without 19 in. x 19 1/2 in. maximum Drip Board (48 x 49.5 cm) Fryer With 18 in. x 273/4 in. (45.7 x 70.5 cm) Drip Board maximum; 19 1/2 in. x 25 3/8 in. (49.5 x 64.5 cm) maximum Small Range Maximum area of 336 sq. in. (2168 sq. cm) with the longest side to be a maximum of .. 28 in. (71--cm) Large Range Maximum area of 784 sq. in. (5058 sq. cm) with the longest side to be a maximum of 28 in. (71 cm) Small Wok 24 in. diameter x 6 in. deep (61 x 15.2 cm) maximum Large Wok 30 in. diameter x 8 in. deep (76.2 x 20.3 cm) maximum Small Maximum area of 1080 sq. in. (6968 sq. cm) Griddle with the longest side to be a maximum of 36 in. (91.4 cm) Large Maximum area of 1440 sq. in. (9290 sq. cm) Griddle with the longest side to be a maximum of 48 in. (122 cm) Gas Radiant Maximum area of 624 sq. in. (4025.8 sq. cm) Char-Broiler with the longest side to be a maximum of 26 in. (66 cm) Gas Radiant Maximum area of 864 sq. in. (5574 sq. cm) Char-Broiler with the longest side to be a maximum of 36 in. (91.4 cm) Lava Rock Maximum area of 624 sq. in. (4025.8 sq. cm) Char-Broiler with the longest side to be a maximum of 26 in. (66 cm) Natural Maximum area of 480 sq. in. Charcoal (3096.8 sq. cm) with the longest side to Broiler be a maximum of 24 in. (61 cm) Mesquite Maximum area of 480 sq. in. Char-Broiler (3096.8 sq. cm) with the longest to be a- maximum of 24 in. (61 cm) Upright/ Maximum area of 1064 sq. in. Salamander (6865 sq. cm) with the longest side Broiler to be a maximum of 36 in. (91 cm) Chain Broiler Maximum area of 1026 sq. in. (6619 sq. cm) with the longest side to be a maximum of 38 in. (97 cm) 1 I Chapter 3 - System Design Page 3-5 REV. 4 la. Fryers without Drip Board (19 in. x 19 1/2 in. nozzle must be located anywhere on the perimeter of maximum) cooking surface of the appliance and aimed at the center (48 x 49.5 cm) the hazard area, 13 in. to 24 in. (33 to 61 cm) above the Two nozzles are available for fryer protection: High prox- of the cooking area. See Figure 3-3b. imity and low proximity. 2H HIGH The Model 2H nozzle, Part No. 551028, is used for high PROXIMITY proximity fryer protection. This nozzle is a two (2) flow / I LOCATED NOZZLE 0 nozzle. The nozzle must be located anywhere within the / I I ANYWHERE I I WITHIN THE / i perimeter of the hazard area, 24 in. to 48 in. (61 to 122 2H, 2L PERIMETER cm) above the cooking surface of the appliance and aimed 48 IN >'— _ LOW I I PROXIMITY at the center of the cooking area. See Figure 3-3a. 1/ (122 cm) i NOZZLE The Model 2L nozzle is used for low proximity fryer protec- LOCATED ANYWHERE / / 2L 24 IN. tion. This nozzle is a two (2) flow nozzle. The nozzle must / /(61 Cm) I ON THE PERIMETER II / be located anywhere on the perimeter of the hazard / / 13 INJJ I I 33cm) surface of the appliance and aimed at the center of the 03OPC ( area, 13 in. to 24 in. (33 to 61 cm) above the cooking __ a I i EDGE OF DRIPBOARDS FRYERS WITH cooking area. See Figure 3-3 2H HIGH OF i i HAZARD PROXIMITY I -------I AREA / I NOZZLE HAZARD I 006178PC / I LOCATED AREA / II ANYWHERE Figure 3-3b WITHIN THE / 2H, 2L PERIMETER 2. Small Range (336 sq. in. (2168 sq. cm) maximum, 28 in. LOW 48" (122 cm) PROXIMITY (71 cm) longest side maximum). Use this when nozzle is NOZZLE center located. / 2L I II I LOCATED I, ANYWHERE Two nozzles are available for small range protection: 24" ON THE PERIMETER High proximity and low proximity. ' 13" (61 cm) The Model 1H nozzle, Part No. 551029, is used for high proximity small range protection. This nozzle is a one (1) FRYERS WITHOUT flow nozzle. When using high proximity protection, the EDGE OF DRIPBOARDS range cannot be under a backshelt. This nozzle must be OF HAZARD HAZARD AREA located on the front./back centerline of the appliance, 40 in. AREA 006178PC to 50 in. (102 to 127 cm) above the cooking surface, and aimed directly down within the "Nozzle Location Area" Figure 3-3a depending on the size of the hazard area. See "Nozzle lb. Fryers with Drip Board Placement" chart below. See Figure 3-4a. The maximum single nozzle protection dimensions NOZZLE FLEXIBILITY PLACEMENT CHART (When depend on the dimensions of the fry pot only. using nozzle flexibility, the maximum width that can be protected is 12 in. (31 cm)) For fry pots with maximum dimensions of 18 in. Length — L Width — W Front/Rear (45.7 cm) on the longest side and 324 sq. in. (2090 in. (cm) in. (cm) in.* (cm)* sq. cm) max. area, use overall dimensions of 27 3/4 in. (70.5 cm) on the longest side and 500 sq. in. (3226 13 (33) 12 (31) 7 1/2 (19) sq. cm) max. area. 14 (36) 12 (31) 7 (18) For fry pots with maximum dimensions exceeding 18 in. 15 (38) 12 (31) 61/2 (17) x 324 sq. in. (2090 sq. cm), but no greater than 19 1/2 16 (41) 12 (31) 6 (15) F in. (49.5 cm) on the longest side and 371 sq. in. (2394 17 (43) 12 (31) 51/2 (14) sq. cm) max area, use overall dimensions of 25 3/8 in. 18 (45) 12 (31) 5 (13) (64.5 cm) on the longest side and 495 sq. in. 19 (48) 12 (31) 41/2 (11) (3194 sq. cm) area. 20 (51) 12 (31) 4 (10) Two nozzles are available for fryer protection: High prox- 21 (53) 12 (31) 3 1/2 (9) imity and low proximity. 22 (56) 12 (31) 3 (8) The Model 2H nozzle, Part No. 551028, is used for high 23 (58) 12 (31) 2 1/2 (6) proximity fryer protection. This nozzle is a two (2) flow 24 (61) 12 (31) 2 (5) nozzle. The nozzle must be located anywhere within the 25 (64) 12 (31) 11/2 (4) perimeter of the hazard area, 24 in. to 48 in. (61 to 26 (66) 12 (31) 1 (3) 122 cm) above the cooking surface of the appliance and 27 (69) 12 (31) 1/2 (1) aimed at the center of the cooking area. See Figure 3-3b. 28 (71) 12 (31) 0 (0) *Distance from centerline, either toward front or toward back, of hazard The Model 2L nozzle is used for low proximity fryer area, starting from the reference point. protection. This nozzle is a two (2) flow nozzle. The ULEX 3830 March 1, 2006 Chapter 3 - System Design Page 3-6 REV.4 REFERENCE NOZZLE POINT LOCATION >< AREA 12 IN. ( 28 IN. (71 cm) (31 cm) MAXIMUM MAXIMUM LENGTH (L) WIDTH (W) HIGH PROXIMITY 006180PC Figure 3-4a. The Model 1L nozzle, Part No. 551066, is used for low prox-imity small range protection. This nozzle is a one (1) flow nozzle. The range can be equipped either with or without a backshelf. Either type requires the same nozzle require- ments. The nozzle must be located 22 in. (56 cm) from either end of the hazard area centered from left to right. It must be 13 in. to 24 in. (33 to 61 cm) above cooking surface, and aimed at a point one half the distance of whatever the height dimension of the nozzle is. When determining nozzle and aim point locations, both measurements are to be taken from the same end of the hazard area. Example: The nozzle is mounted 20 in. (51 cm) above the cooking surface. The aim point from the edge of the hazard would then be 10 in. (25 cm) which is one half the nozzle mounting height dmension. See Figure 3-4b. Note: Nozzles must be placed at or below the shelf, within the nozzle height limitations. EDGE OF HAZARD AREA (FRONT OR BACK) 2. (5 22 IN. (56 CM) - 1L 7 / 1L 24 IN. (H) - (61 cm) 13 IN. (H) (33 Cm) ----I, Fi12 1 I HAZARDI 006181PC SURFACE Figure 3-4b. 2a. High-Proximity Backshelf Protection - When using the 2L nozzle for range protection with high-proximity backshelf, the maximum length of burners being protected must not exceed 28 in. (71 cm) and the maximum area of the burners must not exceed 336 sq. in. (2167 sq. cm). The backshelf must be a minimum of 18 in. (45.7 cm) above the top of the range and may overhang the burner by a maximum of 11 in. (28 cm). NOTE: Although most shelves exceed 11 in. (28 cm) in over- all depth, make sure the shelf does not exceed 11 in. (28 cm) overhang of the burner. Nozzle must be located on the front edge of the front burner and aimed at a point 10 in. (25 cm) forward from the back edge of the back burner on the front-to-rear centerline. Nozzle must be mounted 24 to 35 in. (61 - 89 cm) above the hazard surface. See Figure 3-5a. - CENTERLINE HIGH PROXIMITY BACK SHELF PROTECTION WITH THE 2L NOZZLE. AREA OF PROTECTION PER NOZZLE: MAX. LENGTH OF BURNER GRATES 28 IN. (71 cm) AND MAX. AREA OF BURNER GRATES NOT TO EXCEED 336 SQ. IN. (2168 sq. cm) Figure 3-5a. ULEX 3830 March 1, 2006 34 IN. 48 IN. (86 cm) (122 cm) 006411 Figure 3-5. K Chapter 3 - System Design Page 3-7 REV. 3 3. Larger Burner Range (784 sq. in. (5085 sq. cm) maxi- mum, 28 in. (71 cm) longest side maximum) One nozzle is available for large range protection: High proximity. The Model 2L nozzle, Part No. 551027, is used for high proximity large range protection. This nozzle is a two (2) flow nozzle. When using high proximity protection, the range cannot be under a backshelf. This nozzle must be located 34 in. to 48 in. (86 to 122 cm) above the cooking surface, and aimed directly down within the mounting area, based on the hazard size, as described in the Nozzle Positioning Chart. See Figure 3-5. Example: A four burner range has a hazard size of 20 in. (51 cm) in length and 27 in. (69 cm) in width. Follow down the Range Length column in the Nozzle Positioning Chart until you come to 20 in. (51 cm). Continue down this column until the correct width appears in the width column. When the width of 27 in. (69 cm) is arrived at, read across to the radius column to determine the size of radius allowed, for positioning of the nozzle, from the hazard area centerline. In this example, the correct radius is 3 in. (8 cm) The nozzle can be aimed straight down anywhere within a 3 in. (8 cm) radius of the hazard area centerline. Nozzle Positioning Chart Range Range Length - L Width - W Radius - P in. (cm) in. (cm) in. (cm) 18 (46) 18 (46) 7 1/8 (18) 18 (46) 19 (48) 63/4 (17) 18 (46) 20 (51) 63/8 (16) 18 (46) 21 (53) 6 (15) 18 (46) 22 (56) 55/8 (14) 18 (46) 23 (58) 5 1/4 (13) 18 (46) 24 (61) 43/4 (12) 18 (46) 25 (64) 43/8 (11) 18 (46) 26 (66) 4 (10) Range Range Length - L Width - W Radius - R in. (cm) in. (cm) in. (cm) 18 (46) 27 (69) 35/8 (9) 18 (46) 28 (71) 31/8 (8) 19 (48) 18 (46) 63/4 (17) 19 (48) 19 (48) 63/8 (16) 19 (48) 20 (51) 6 (15) 19 (48) 21 (53) 55/8 (14) 19 (48) 22 (56) 51/4 (13) 19 (48) 23 (58) 47/8 (12) 19 (48) 24 (61) 41/2 (11) 19 (48) 25 (64) 41/8 (10) 19 (48) 26 (66) 33/4 (9) 19 (48) 27 (69) 31/4 (8) 19 (48) 28 (71) 27/8 (7) 20 (51) 18 (46) 63/8 (16) 20 (51) 19 (48) 6 (15) 20 (51) 20 (51) 55/8 (14) 20 (51) 21 (53) 51/4 (13) 20 (51) 22 (56) 4 7/8 (12) 20 (51) 23 (58) 41/2 (11) 20 (51) 24 (61) 41/8 (10) 20 (51) 25 (64) 33/4 (9) 20 (51) 26 (66) 33/8 (8) 20 (51) 27 (69) 3 (7) 20 (51) 28 (71) 25/8 (6) 21 (53) 18 (46) 6 (15) 21 (53) 19 (48) 55/8 (14) 21 (53) 20 (51) 5 1/4 (13) 21 (53) 21 (53) 5 (12) 21 (53) 22 (56) 45/8 (11) 21 (53) 23 (58) 41/4 (10) 21 (53) 24 (61) 37/8 (10) 21 (53) 25 (64) 31/2 (9) 21 (53) 26 (66) 31/8 (8) 21 (53) 27 (69) 23/8 (7) 21 (53) 28 (71) 21/4 (6) 22 (56) 18 (46) 55/8 (14) 22 (56) 19 (48) 51/4 (13) 22 (56) 20 (51) 47/8 (12) 22 (56) 21 (53) 45/8 (11) 22 (56) 22 (6) 41/4 (10) 22 (56) 23 (58) 37/8 (10) 22 (56) 24 (61) 3 1/2 (9) 22 (56) 25 (64) 31/8 (8) 22 (56) 26 (66) 23/4 (7) 22 (56) 27 (69) 23/8 (6) 22 (56) 28 (71) 2 (5) 23 (58) 18 (46) 51/4 (13) 23 (58) 19 (48) 47/8 (12) 23 (58) 20 (51) 41/2 (11) 23 (58) 21 (53) 41/4 (10) 23 (58) 22 (56) 37/8 (10) 23 (58) 23 (58) 31/2 (9) 23 (58) 24 (61) 31/8 (8) 23 (58) 25 (64) 27/8 (7) 23 (58) 26 (66) 2 1/2 (6) 23 (58) 27 (69) 21/8 (5) 23 (58) 28 (71) 1 5/8 (4) ULEX 3830 March 1, 2006 Chapter 3 - System Design Page 3-8 REV. 3 Range Range Length - L Width —W Radius - R in. (cm) in. (cm) in. (cm) 24 (61) 18 (46) 43/4 (12) 24 (61) 19 (48) 41/2 (11) 24 (61) 20 (51) 41/8 (10) 24 (61) 21 (53) 37/8 (10) 24 (61) 22 (56) 31/2 (9) 24 (61) 23 (58) 31/8 (8) 24 (61) 24 (61) 27/8 (7) 24 (61) 25 (64) 2 1/2 (6) 24 (61) 26 (66) 21/8 (5) 24 (61) 27 (69) 1 3/4 (4) 24 (61) 28 (71) 1 3/8 (3) 25 (64) 18 (46) 43/8 (11) 25 (64) 19 (48) 41/8 (10) 25 (64) 20 (51) 33/4 (10) 25 (64) 21 (53) 31/2 (9) 25 (64) 22 (56) 31/8 (8) 25 (64) 23 (58) 27/8 (7) 25 (64) 24 (61) 21/2 (6) 25 (64) 25 (64) 2 1/8 (5) 25 (64) 26 (66) 1 3/4 (4) 25 (64) 27 (69) 13/8 (3) 25 (64) 28 (71) 1 (2) 26 (66) 18 (46) 4 (10) 26 (66) 19 (48) 33/4 (10) 26 (66) 20 (51) 33/8 (9) 26 (66) 21 (53) 31/8 (8) 26 (66) 22 (56) 23/4 (7) 26 (66) 23 (58) 2 1/2 (6) 26 (66) 24 (61) 21/8 (5) 26 (66) 25 (64) 1 3/4 (4) 26 (66) 26 (66) 1 3/8 (3) 26 (66) 27 (69) 1 (2) 26 (66) 28 (71) 3/4 (2) 27 (69) 18 (46) 35/8 (9) 27 (69) 19 (48) 31/4 (8) 27 (69) 20 (51) 3 (8) 27 (69) 21 (53) 23/4 (7) 27 (69) 22 (56) 23/8 (6) 27 (69) 23 (58 21/8 (5) 27 (69) 24 (61) 1 3/4 (4) 27 (69) 25 (64) 1 3/8 (3) 27 (69) 26 (66) 1 (2) 27 (69) 27 (69) 3/4 (2) 27 (69) 28 (71) 3/8 (1) 28 (71) 18 (46) 31/8 (8) 28 (71) 19 (48) 27/8 (7) 28 (71) 20 (51) 25/8 (7) 28 (71) 21 (53) 21/4 (6) 28 (71) 22 (56) 2 (5) 28 (71) 23 (58) 1 5/8 (4) 28 (71) 24 (61) 1 3/8 (3) 28 (71) 25 (64) 1 (2) 28 (71) 26 (66) 3/4 (2) 28 (71) 27 (69) 3/8 (1) 28 (71) 28 (71) 0 (0) ULEX 3830 March 1, 2006 4. Small Wok (24 in. (61 cm) diameter x 6 in. (15 cm) depth maximum) Two nozzles are available for small wok protection: High proximity and low proximity. The 1H nozzle, Part No. 551029, is used for high proxim- ity wok protection. This nozzle is a one (1) flow nozzle. The nozzle must be located anywhere on the perimeter of the appliance, 24 in. to 48 in. (61 to 122 cm) above the top edge of the wok and aimed at the center of the wok. See Figure 3-6. The 1L nozzle, Part No. 551026, is used for low proxim- ity wok protection. This nozzle is a one (1) flow nozzle. The nozzle must be located anywhere on the perimeter of the appliance, 13 in. to 24 in. (33 to 61 cm) above the top edge of the wok and aimed at the center of the wok. See Figure 3-6. iN ,1 I' It , 1H, 1L / 481N. (122 cm) 24 IN. (61 cm) 131N. I (33 cm) I Il/I I / I I I - NOZZLE LOCATED ON PERIMETER 24 IN. (61 cm) 006183PC DIAMETER MAXIMUM Figure 3-6. I Chapter 3 - System Design J Page 3-9 REV.3 5. Large Wok (Greater than 24 in. to 30 in. (61 to 76 cm) EDGE OF HAZARD AREA diameter x 8 in. (20 cm) depth maximum) NOZZLE (ANY— .1 ________.01 ________________ I Two nozzles are available for large wok protection: High CORNER) 12 IN. proximity and low proximity. 12 IN. The 2H nozzle, Part No. 551028, is used for high proxim- (31 cm) AIM POINT ity wok protection. This nozzle is a two (2) flow nozzle. The nozzle must be located anywhere on the perimeter 1H of the appliance, 24 in. to 48 in. (61 to 122 cm) above the top edge of the wok and aimed at the center of the wok. See Figure 3-7. The 2L nozzle, Part No. 551027, is used for low proxim- 1H IL ity wok protection. This nozzle is a two (2) flow nozzle. The nozzle must be located anywhere on the perimeter 48 IN. \ of the appliance, 13 in. to 24 in. (33 to 61 cm) above the (122 cm) 1L \ top edge of the wok and aimed at the center of the wok. L24 1N y HAZARD See Figure 3-7. 1 cm) I ' SURFACE 10 IN. ' 2H (25cm) ij2 IN. J 0061 / I (31 CM) / I Figure 3-8. / 2H, 2L 6a. Small Griddle (1080 sq. in. (6968 sq. cm) x 36 in. 481N. (91 cm) longest side maximum) Alternate Protection (122 cm) Two nozzles are available for small griddle alternate 2L protection: High proximity and low proximity. 7 The 2H nozzle, Part No. 551028, is used for high proxim- ,' ,' I I ity griddle protection. This nozzle is a two (2) flow 13 IN. nozzle. The nozzle must be located 0 to 6 in (0 to 15 cm) from short side of the hazard surface, 24 in. to I '*I NOZZLE LOCATED - - 48 in. (61 to 122 cm) above the cooking surface of the ON PERIMETER appliance and aimed at the center of the hazard area. 006183PC 30 IN. (76 cm) DIAMETER See Figure 3-8a. MAXIMUM The 2L nozzle, Part No. 551027, IS used for low proxim- Figure 3-7. ity griddle protection. this nozzle is a two (2) flow nozzle. The nozzle must be located 0 to 6 in. (0 to 6. Small Griddle (1080 sq. in. (6968 sq. cm) x 36 in. 15 cm) from the short side of the hazard surface, 13 in. (91 cm) longest side maximum) to 24 in. (33 to 61 cm) above the cooking surface of the Two nozzles are available for small griddle protection: appliance and aimed at the center of the hazard area. High proximity and low proximity. See Figure 3-8a. 2H The 1H nozzle, Part No. 551029, is used for high proxim- ity griddle protection. This nozzle is a one (1) flow nozzle. The nozzle must be located above any corner of the hazard surface, 24 in. to 48 in. (61 to 122 cm) above the cooking surface of the appliance and aimed at EDGE OF a point 12 in. (31 cm) over and 12 in. (31 cm) in from the HAZARD AREA 2H,2L 48 corner below the nozzle. See Figure 3-8. / (122cm) \ The 1L nozzle, Part No. 551026, is used for low proxim- 6 IN. I H6IN "\ \ r 2L'.... ity griddle protection. This nozzle is a one (1) flow 21114. nozzle. The nozzle must be located above any corner J m) NOZZLE 13 IN. of the hazard surface, 10 in. to 24 in. (25 to 61 cm) LOCATION I I (33 cm) ___ I I above the cooking surface of the appliance and aimed at l/2 L ZONE ' -- a point 12 in. (31 cm) over and 12 in. (31 cm) in from the -a—.-- L corner below the nozzle. See Figure 3-8. -.- Figure 3-8a. ULEX 3830 March 1, 2006 Chapter 3 - System Design Page 3-10 REV. 3 7. Large Griddle (1440 sq. in. (9290 sq. cm) x48 in (122 cm) longest side maximum) Two nozzles are available for large griddle protection: High proximity and low proximity. The 2H nozzle, Part No. 551028, is used for high proxim- ity griddle protection. This nozzle is a two (2) flow nozzle. The nozzle must be located above any corner of the hazard surface, 24 in. to 48 in. (61 to 122 cm) above the cooking surface of the appliance and aimed at a point 12 in. (31 cm) over and 12 in. (31 cm) in from the corner below the nozzle. See Figure 3-9. The 2L nozzle, Part No. 551027, is used for low proxim- ity griddle protection. This nozzle is a two (2) flow nozzle. The nozzle must be located above any corner of the hazard surface, 10 in. to 24 in. (25 cm to 61 cm) above the cooking surface of the appliance and aimed at a point 12 in. (31 cm) over and 12 in. (31 cm) in from the corner below the nozzle. See Figure 3-9. EDGE OF HAZARD AREA CORNER) '(31) - - 12 IN. NOZZLE (ANY --i _ K r12 IN. 1(31 cm) AIM POINT 2H 2H, 2L 481N. (122 cm) 2L 241N. HAZARD T \ (61 cm) \ \ SURFACE I lOIN. \\'I (25 cm) \'I 12 IN. 1 31 CTJ 006184PC Figure 3-9. 8. Radiant Char-Broiler (624 sq. in. (4026 sq. cm) x 26 in. (66 cm) longest side maximum) Note: Radiant charbroilers are distinguished by the use of heated metal strips (radiants) that are used for cook- ing. Two nozzles are available for radiant char-broiler protec- tion. High proximity and low proximity. The 1H nozzle, Part No. 551029, is used for high proximity radiant char-broiler protection. This nozzle is a one (1) flow nozzle. The nozzle must be located anywhere within the perimeter of the hazard area, 24 in. to 48 in. (33 to 61 cm) above the cooking surface of the appliance and aimed at the center of the broiler surface. See Figure 3-10. The 1L nozzle, Part No. 551026, is used for low proxim- ity radiant char-broiler protection. This nozzle is a one (1) flow nozzle. The nozzle must be located anywhere on the perimeter of the hazard surface, 13 in. to 24 in. (33 to 61 cm) above the cooking surface of the appli- ance and aimed at the center of the broiler surface. See Figure 3-10. I H NOZZLE LOCATED ANYWHERE WITHIN THE PERIMETER FOR HIGH PROXIMITY PROTECTION - - 1L NOZZLE LOCATED ANYWHERE ON THE PERIMETER FOR LOW IH1L,\ PROXIMITY --- PROTECTION 481N. (122 cm) 1L 241N. (61 cm) 131N. (33 cm) 1---- QftflIAMT 006187PC BROILER EDGE OF HAZARD AREA Figure 3-10. ULEX 3830 March 1, 2006 Chapter 3 - System Design Page 3-11 REV. 3 The 2L nozzle, Part No. 551027, is used for low proxim- ity lava rock char-broiler protection. This nozzle is a two (2) flow nozzle. The nozzle must be located anywhere on the perimeter of the hazard surface, 15 in. to 24 in. (38 to 61 cm) above the cooking surface of the appli- ance and aimed at the center of the broiler surface. See Figure 3-12. 2L NOZZLE LOCATED ANYWHERE WITHIN THE PERIMETER 2L FOR HIGH PROXIMITY PROTECTION 2L NOZZLE LOCATED ANYWHERE ON THE PERIMETER 2L FOR LOW PROXIMITY T" 351N. PROTECTION (89cm) 2L ' 241N. \ (61 cm) \\ \\ I 151N. '. It 1(36 cm) ' LAVA ROCK 006187PC CHAR-BROILER EDGE OF HAZARD AREA Figure 3-12. 11. Natural Class "A" Charcoal Char-Broiler (480 sq. in. (3097 sq. cm) x 24 in. (61 cm) longest side maximum) Note: Class "A" (natural) charbroilers are distinguished by the use of charcoal, mesquite chips, chunks, and/or logs that are used for cooking. Two nozzles are available for natural charcoal char- broiler protection. High proximity and low proximity. The maximum depth of fuel (charcoal) must not exceed 6 in. (15 cm). The 1H nozzle, Part No. 551029, is used for high proxim- ity natural charcoal char-broiler protection. This nozzle is a one (1) flow nozzle. The nozzle must be located anywhere within the perimeter of the hazard area, 24 in. to 35 in. (61 to 89 cm) above the cooking surface of the appliance and aimed at the center of the broiler surface. See Figure 3-13. The 1L nozzle, Part No. 551026, is used for low proxim- ity natural charcoal char-broiler protection. This nozzle is a one (1) flow nozzle. The nozzle must be located anywhere on the perimeter of the hazard surface, 15 in. to 24 in. (38 to 61 cm) above the cooking surface of the appliance and aimed at the center of the broiler surface. See Figure 3-13. 1 H NOZZLE LOCATED ANYWHERE WITHIN THE 1H PERIMETER FOR HIGH PROXIMITY PROTECTION 1 L NOZZLE LOCATED ANYWHERE ON THE PERIMETER IL, 1H \ FOR LOW PROXIMITY 35 IN. PROTECTION (89 CM) 1L ' 24 iN. (61 cm) \ 15 IN. \ (38 cm) FUEL DEPTH MUST NOT EXCEED 6 IN. (15 cm) - NATURAL CHARCOAL omiswc cHAH-HuILK EDGE OF HAZARD AREA Figure 3-13. LJLEX 3830 March 1, 2006 Li I 9. Radiant Char-Broiler (864 sq. in. (2195 sq. cm) x 36 in. ' (91 cm) longest side maximum) Two nozzles are available for radiant char-broiler protec- tion: High proximity and low proximity. I The 2H nozzle, Part No. 551028, is used for high proximity radiant char-broiler protection. This nozzle is a two (2) flow nozzle. The nozzle must be located above any corner of the hazard surface, 36 in. to 48 in. (91 to 122 cm) above I the cooking surface of the appliance and aimed at the center of the broiler surface. See Figure 3-ha. EDGE OF - It HIGH PROXIMITY 006185PC RADIANT BROILER Figure 3-ha. The 2L nozzle, Part No. 551027, is used for low proximity radiant char-broiler protection. This nozzle is a two (2) flow nozzle. The nozzle must be located anywhere on the perimeter of the hazard surface, 13 in. to 36 in. (33 to 91 cm) above the cooking surface of the appliance and aimed at the center of the broiler surface. See Figure 3-11 b. NOZZLE LOCATED ANYWHERE ALONG 2L PERIMETEF, - - - - - - OF HAZARD - - -- - AREA 2L \ I 361N" (91 CM) 131N (33 cm) - - - - - - - 006186PC LOW PROXIMITY 1IMUIAN I UHUILK EDGE OF HAZARD AREA Figure 3-11 b. 10. Lava Rock Char-Broiler (624 sq. in. (4026 sq. cm) x 26 in. (66 cm) longest side maximum) Note: Synthetic rock charbroilers are distinguished by the use of lava, pumice, or synthetic rocks that are used for cooking. One nozzle is available for lava rock char-broiler protec- tion. The 2L nozzle, Part No. 551027, is used for both high proximity and low proximity. I The 2L nozzle, Part No. 551027, is used for high proximity lava rock char-broiler protection. This nozzle is a two (2) flow nozzle. The nozzle must be located anywhere within the perimeter of the hazard area, 24 in. to 35 in. (61 to I 89 cm) above the cooking surface of the appliance and aimed at the center of the broiler surface. See Figure 3-12. 2H NOZZLE (ANY CORNER) 7 481N. \ (122 cm) ' 361N. (91 cm) \' Chapter 3 - System Design Page 3-12 REV.3 12. Mesquite Char-Broiler (480 sq. in. x (3097 sq. cm) 24 in. (61 cm) longest side maximum) Two nozzles are available for mesquite char-broiler protection. High proximity and low proximity. The maxi- mum depth of fuel (wood) must not exceed 6 in. (15 cm) The 1H nozzle, Part No. 551029, is used for high proxim- ity mesquite char-broiler protection. This nozzle is a one (1) flow nozzle. The nozzle must be located anywhere within the perimeter of the hazard area, 24 in. to 35 in. (61 to 89 cm) above the cooking surface of the appli- ance and aimed at the center of the broiler surface. See Figure 3-14. The 1L nozzle, Part No. 551026, is used for low proxim- ity mesquite charcoal char-broiler protection. This nozzle is a one (1) flow nozzle. The nozzle must be located anywhere on the perimeter of the hazard surface, 15 in. to 24 in. (38 to 61 cm) above the cooking surface of the appliance and aimed at the center of the broiler surface. See Figure 3-14. 1H NOZZLE LOCATED ANYWHERE WITHIN THE PERIMETER 11.1 FOR HIGH PROXIMITY PROTECTION IL NOZZLE LOCATED ANYWHERE ON THE PERIMETER I IL, 1H ' FOR LOW PROXIMITY 1\ 351N. PROTECTION \ (89 cm) 1L 24 IN. f\ (61 cm>) 15 IN. \ (38 cm) FUEL DEPTH MUST NOT EXCEED 6 IN. (15 cm) Figure 3-14. 13. Upright/Salamander Broiler (internal chamber 1064 sq. in. x 36 in. (6865 sq. cm x 91 cm) longest side maximum) One nozzle is available for upright/salamander broiler protection. The 1L nozzle, Part No. 551026, is used for broiler protection. This nozzle is a one (1) flow nozzle. The nozzle must be located above the grate, at the front edge of the appliance, outside the broiling chamber, and pointed at the back opposite corner of the broiler cham- ber. The nozzle must be aimed parallel to the broiler grate surface. See Figure 3-15. 1L NOZZLE AIMED' SALAMANDER BROILER AT BACK OPPOSITE CORNER 1L NOZZLE AIMED AT BACK OPPOSIT CORNER BROILER CHAMBER UPRIGHT BROILER Figure 3-15. - MESQUITE \ 006187PC MRNbNUILtM EDGE OF HAZARD AREA ULEX 3830 March 1, 2006 ER Chapter 3 - System Design Page 3-13 REV. 3 I 1 14. Chain Broiler (internal chamber 1026 sq. in. (6619 sq. cm) x 38 in. (97 cm) longest side maximum) One nozzle is available for chain broiler protection. The 1L nozzle, Part No. 551026, is used for broiler protection. This nozzle is a one (1) flow nozzle. The nozzle must be located 1 to 3 in. (3 to 8 cm) above the surface of the chain, at the front edge of the appliance, and pointed at the opposite diagonal corner. The nozzle must be aimed parallel to the chain surface. See Figure 3-16. Figure 3-16. 15. Tilt Skillet/Braising Pan Protection for tilt skillet or braising pans is to be based upon the coverage limitations provided for deep fat fryer protection. Coverage limitations are based on fryer sizes including drip boards. Exception: Tilt skillets and braising pans may exceed the maximum of 6 sq. ft. (.6 sq. m) total when modularizing. Tilt skillets and braising pans generally utilize a hinged cover. Fryer protection nozzles are to be placed toward the front of the appliance to minimize the potential for the tilt skillet or braising pan cover to interfere with the nozzle discharge. See Figure 3-17. COVER MUST NOT INTERFERE WITH NOZZLE DISCHARGE J/9 (.6 m) 000011 4 FT. (1.2 m) THE NOZZLE IS TO BE PLACED TOWARD THE FRONT OF THE APPLIANCE TO MINIMIZE THE POTENTIAL FOR THE SKILLET OR BRAISING PAN COVER TO INTERFERE WITH THE NOZZLE DISCHARGE. I NOT INTERFERE WITH EDGE OF DISCHARGE PATTERN COVE7//I / FOR MINIMUM / AND MAXIMUM I NOZZLE HEIGHTS, REFER / TO FRYER / NOZZLE PARAMETERS 000071 P~ LI FRYER NOZZLE USED FOR TILT SKILLET OR BRAISING PAN PROTECTION MUST BE POSITIONED NEAR THE FRONT EDGE OF THE PAN AND AIMED AT THE FRONT TO BACK CENTERLINE OF THE PAN. THE DISCHARGE FROM THE NOZZLE(S) MUST COMPLETELY CLEAR THE PAN COVER WITH AN UNOBSTRUCTED VIEW TO THE BACK OF THE PAN. Figure 3-17. ULEX 3830 I March 1, 2006 Chapter 3 - System Design Page 3-14 REV. 4 Fryer - Multiple Nozzle Protection Fryers exceeding the coverage of a single nozzle can be divided into modules. Each module must not exceed the maximum area allowed for a single nozzle. However, when utilizing multiple nozzle protection, the longest side allowed for a fryer with drip board can be used, regardless of whether the fryer has a drip board or not. The maximum size fryer that can be modularized is 864 sq. in. (5574 sq. cm). Design requirements for multiple nozzle fryers are broken down as follows: If the fryer includes any dripboard areas, measure both the internal length (front to back) and width of the frypot portion. Then measure the internal length and width of the overall hazard area including any dripboard areas. Determine the area of both the frypot and the area of the overall vat by multiplying corresponding length and width dimensions. Divide the frypot or overall vat into modules, each of which can be protected by a single nozzle, based on the maximum dimension and area coverage of the nozzle as specified in 'Design Chart.' If the module considered does not include any portion of the dripboard, use only the maximum frypot area and maximum dimension listed in the 'Design Chart." If the module considered includes any dripboard areas, use both the maximum frypot area and dimen- sion listed in the Design Chart", and the maximum overall area and dimension listed in the "Design Chart." 3. None of the maximum dimensions may be exceeded. If either the maximum frypot or the overall sizes are exceeded, the area divided into modules will need to be redefined with the possibility of an additional nozzle. ULEX 3830 March 1, 2006 PIPING LIMITATIONS Once the nozzle placement and quantity of tanks has been determined, it is necessary to determine the piping configu- rations between the tank and the nozzles. This section contains the guidelines and limitations for designing the distribution piping so that the wet chemical agent will discharge from the nozzles at a proper flow rate. These limi- tations must also be referred to when selecting the mounting location for the tanks. The maximum pipe lengths are based on internal pipe volume. Each size tank is allowed a minimum and maximum total volume of piping, calculated in milliliters. There is no need to distinguish between what portion of the piping is supply line and what portion is branch line. Only the total volume of the complete piping network has to be considered. Volume Chart 1/4 in. pipe = 20.5 mls./ft. 3/8 in. pipe = 37.5 mls./ft. 1/2 in. pipe = 59.8 mls./ft. 3/4 in. pipe = 105.0 mls./ft. Tank Chart Maximum Volume Allowed • Maximum Between First Maximum Pipe Nozzle and Tank Flow Volume Last Nozzle Size Numbers (milliliters) (milliliters) 1.6 Gallon 5 1500 600 PCL-160 3.0 Gallon 10 1910 1125 PCL-300 4.6 Gallon 14 3400 3000 PCL-460 4.6 Gallon 15 2600 2000 PCL-460 6.0 Gallon 19 4215 1688 PCL-600 per side 6.0 Gallon 20 3465 1313 PCL-600 per side Minimum Pipe Volumes for a Fryer, Range, and Wok Cylinder Size Entire System At or before appliance PCL 160 239 ml - 1 Flow Pt 180 ml - 1 Flow Pt PCL 300 300 ml - 4 Flow Pts 239 ml - 2 Flow Pts PCL 460 660 ml - 10 Flow Pts 180 ml -2 Flow Pts PCL 600 960 ml - 14 Flow Pts 120 ml -2 Flow Pts Chapter 3 - System Design Page 3-15 REV. 3 I I I I General Piping Requirements Split piping and straight piping are both allowed on a PCL-160, PCL-300 and PCL-460 system. PCL-600 systems must use split piping only, with no nozzle located before the split, and with a maximum of 14 flow points per side. 1/2 in. mini- mum piping must be used up to the first split. Maximum volume for 1/4 in. pipe between a nozzle and the preceding tee is 410 mIs. Maximum flow numbers for 1/4 in. pipe is 6. Maximum number of elbows between a nozzle and the preceding tee is 5. SUPPLY PIPE MUST ENTER SIDE OF TEE PIPING (REQUIRED L600 SYSTEMS) I I I I Maximum of 25 elbows are allowed in the total piping system. Maximum difference in elevation between the tank outlet and any nozzle, or the tank outlet and the highest or lowest horizontal pipe run, is 10 ft. (3.1 m). No traps are allowed in the piping network. Pipe lengths are measured from center to center of fittings. The internal equivalent length volume of fittings does not have to be considered as part of the total pipe volume. When utilizing different size pipe in the system, the largest size must start first and the addi- tional pipe must decrease as it approaches the nozzle. Elbow(s) or swivel adaptors located at the nozzles do not have to be counted in the 25 elbow maxi- mum requirement. Reducing bushings are allowed when reducing to a smaller pipe size. Additional piping requirements when protecting a range, wok, or a fryer: PCL-160 - Minimum of 239 ml and one (1) flow number required in total system. Of that mini- mum, 180 ml must be utilized at or before the range, wok, or fryer. PCL-300 - Minimum of 300 ml and four (4) flow numbers required in total system. Of that mini- mum, 239 ml and two (2) flow numbers must be utilized at or before the range, wok, or fryer. PCL-460 - Minimum of 660 ml and ten (10) flow numbers required in total system. Of that mini- mum, 180 ml and two (2) flow numbers must be utilized at or before the range, wok, or fryer. PCL-600 - Minimum of 960 ml and fourteen (14) flow numbers required in total system. Of that minimum, 120 ml and 2 flow numbers must be STRAIGHT PIPING 006191 PC Figure 3-18. Design Steps Step No. 1 Determine number of flow points required based on duct size, plenum size and type, and size of all appliances. Step No. 2 Determine size and quantity of tanks required. Refer to the chart in 'General Piping Requirements to determine the maximum amount of flow numbers allowed per each tank size. Step No. 3 Layout nozzles, piping diagram, and tank loca- tion. Determine pipe lengths as accurate as possible. Make certain maximum number of elbows is not exceeded. Note: Tanks cannot be manifolded together. Each tank must have a separate piping network. Step No. 4 Add all the lengths of each pipe run and multi- ply by the mls./ft. listed in the Volume Chart. If the sum falls within the acceptable range noted in general Piping Requirements, that pipe size is acceptable. If the calculated volume is too large, recalculate the volume using the ml per foot of a smaller pipe size. Pipe sizes can be mixed but Rule No. 11 of the General Piping Requirements must be followed. Step No. 5 Check to make certain minimum volumes, maxi- mum volumes and maximum volume allowed between first nozzle and last nozzle is not exceeded (Tank Chart). Check each rule in "General Piping Requirement" to make certain none have been exceeded. If any requirement is exceeded, change to a different pipe size and recalculate. ULEX 3830 March 1, 2006 I I (2)18 IN. (46 cm) X 24 IN. (61 cm) FRYERS (1)30 IN. (61 cm)X36IN. (91 cm) GRIDDLE (1) 24 IN. (61 cm) DIAMETER WOK 0061 92Pc Figure 3-19. r 2 6' 61 5, 6 Figure 3-20. Chapter 3 - System Design Page 3-16 REV. 3 Example The cooking area that requires protection consists of a single 56 in. (142 cm) perimeter exhaust duct, a 10 ft. (3.1 m) long 'V' bank plenum, (2) 18 in. (46 cm) wide x 24 in. (61 cm) fryers, a 30 in. (76 cm) x 36 in. (91 cm) wide griddle, and a 24 in. (61 cm) diameter wok. See Figure 3-19. Step No. 1 Determine number of flow points required. 56 in. (142 cm) perimeter duct requires one, two flow nozzle 10 ft. (3.1 m) "V' bank hood requires one, one flow nozzle 18 in. x 24 in. (46 x 61 cm) fryer requires one, two flow nozzle 18 in. x 24 in. (46 x 61 cm) fryer requires one, two flow nozzle 30 in. x 36 in. (76 x 91 cm) griddle requires one, one flow nozzle 24 in. (61 cm) diameter wok requires one, one flow nozzle TOTAL FLOW NUMBERS — 9 Step No. 2 Determine size and quantity of tanks required. Referring to the chart in "General Piping Requirements," a PCL-300 and a PCL-460 can supply 10 flows, therefore, a PCL-300 can be utilized. ULEX 3830 March 1, 2006 Step No. 3 Make an accurate sketch of the cooking lineup and the hood. Sketch in the tank location and all the piping required for the total system. Make certain all pipe lengths and number of elbows are as accurate as possible. Check the "General Piping Requirements" to determine that the mini- mum and maximum requirements are met. See Figure 3-20. Figure 3-21. Step No. 4 Total all pipe lengths. Refer to the Volume Chart. Chose a given pipe size and multiply the ml per foot by the total length of all the pipe. If the sum falls within the acceptable range noted in Tank Chart, that pipe size is acceptable. If the calculated volume is too large, recalculate the volume using the ml per foot of a smaller pipe size. See Figure 3-21. Add section A-B = 0-6' + 5'+ 14'+ 2'+ 0'-6" = 22' (.2+1.5+4.3+.6+.2=6.8m) Add section B-C = 1'-6" (.5 m) Add section C-D = 1'(.3 m) Add section D-E = 2'(.6 m) Add section E-F = 0'-6" (.2 m) Add section F-L = 3'+ 2'+ 2" = 7'(2.1 m) Add section B-G = 0'-6" (.2 m) Add section C-H = 2'+ 2'= 4'(.6 + .6 = 1.2 m) Add section 0-I = 2'+ 2'= 4' (.6 + .6 = 1.2 m) Add section E-J = 0'-6" + 0-6" = 1'(.3 m) Add section F-K = 2'+ 2' 4'(.6 + .6 = 1.2 m) Total length of all pipe = 47'-6" (14.5 m) I I I I I I I I I I I I I 1 I I I I I P. Chapter 3 - System Design Page 3-17 REV. 2 Refer to Volume Chart. The pipe size chosen is 3/8 inch. The volume per foot of 3/8 in. pipe is 37.5 ml. Multiply 37.5 by the total pipe length of 47.5 ft. 37.5 ml x 47.5 ft. = 1781 ml total volume The maximum volume allowed for a PCL-300 is 1910 ml, therefore, 3/8 in. pipe is acceptable for this system. ULEX 3830 March 1, 2006 The internal equivalent length volume of fittings does not have to be considered as part of the total pipe volume. (Example system OK) When utilizing different size pipe in the total system, the largest size must start first and the additional pipe must decrease as it approaches the nozzle. (Example system N/A) Elbow(s) or swivel adaptors located at the nozzles do not have to be counted in the 25 elbow maximum requirement. (Example system OK) Additional piping requirements when protecting a range, wok, or a fryer: PCL-300 - Minimum of 300 ml and four (4) flow numbers required in total system. Of that minimum, 239 ml and two (2) flow numbers must be utilized at or before the range, wok, or fryer. (Example system has 1781 ml and 10 -- flow numbers, therefore - OK. The exam- ple system has 1050 ml and 3 flows including the fryer, therefore, OK) PCL-460 - Minimum of 660 ml and ten (10) flow numbers required in total system. Of that minimum, 180 ml and two (2) flow numbers must be utilized at or before the range, wok, or fryer. PCL.600 - Minimum of 960 ml and four- teen (14) flow numbers required in total system. Of that minimum, 120 ml and 2 flow numbers must be utilized at or before the range, wok, or fryer. GEN. PIPING RULE NO. 1 8,9 TANK CHART MINIMUM/MAXIMUM PIPE VOLUME GEN. 1 PIPING RULE NO. 10 TANK CHART GEN I MAX. VOL. I I BETWEEN FIRST PIPING ...i AND LAST NOZZI RULE NO.7 GEN. PIPING RULE NO.6 GEN. PIPING RULE NO. 13 J PIPING RULE NO.5 TANK CHART MAX. VOL. BETWEEN FIRST AND LAST NOZZLE GEN. PIPING RULE NO. 12 006193PC Figure 3-22. Chapter 3 - System Design Page 3-18 REV. 2 Step No. 5 Check to make certain minimum volumes and maximum volume allowed between first nozzle and last nozzle are not exceeded (Tank Chart). Check each rule in 'General Piping Requirements" to make certain none have been exceeded. If any requirement is exceeded, change to a different pipe size and recalculate. See Figure 3-22. Refer to Tank Chart Minimum Pipe Volume for PCL-300 is 300 milliliters protecting a fryer, wok, or range (Example system pipe volume is 1781 milliliters, therefore OK) Maximum Pipe Volume for PCL-300 is 1910 milliliters (Example system pipe volume is 1781 milliliters, therefore OK) Maximum Volume Allowed Between First Nozzle and Last Nozzle for PCL-300 is 1125 milliliters (Example system, the amount of 3/8 in. piping between G and L, is 25.5 feet. 25.5 feet x 37.5 mIs/ft. = 956.3 ml, therefore, OK) Refer to General Piping Requirements Split piping and straight piping are both allowed on PCL-300 and PCL-460 systems. (Example system OK) PCL-600 systems must use split piping only, with no nozzle located before the split, and with a maximum of 14 flow points per side. 1/2 in. minimum piping must be used up to the first split. (Example system N/A) Maximum volume for 1/4 in. pipe between a nozzle and the preceding tee is 410 mIs. (Example system N/A) Maximum flow numbers for 1/4 in. pipe is 6. (Example system N/A) Maximum number of elbows between a nozzle and the preceding tee is 5. (Example system has a maximum number of 2, therefore, OK) Maximum of 25 elbows are allowed in the total piping system. (Example system has 11 elbows, therefore, OK) Maximum difference in elevation between the tank outlet and any nozzle, or the tank outlet and the highest or lowest horizontal pipe run, is 10 ft. (3.1 m) (Example system has 5-6' (1.7 m), therefore, OK) No traps are allowed in the piping network. (Example system has no traps, therefore, OK) Pipe lengths are measured from center to center of fittings. (Example system pipe lengths were measured from center to center of fittings, therefore, OK) ULEX 3830 March 1, 2006 Chapter 3 - System Design Page 3-19 REV. 2 DETECTOR PLACEMENT Detectors are required over cooking appliances and in the duct(s) of protected ventilation hoods. Detectors shall be located in the plenum area of the ventilation hood. Exhaust Duct(s). Each exhaust duct must have at least one (1) detector installed in the duct entrance, located in the air stream of the cooking vapors at a maximum of 12 feet (3.7 m) into the duct. See Figure 3-23. Figure 3-23. 006884PC NOTICE When gas appliances are used and the flue gases from the burner are exhausted into the duct, the detector must be kept out of the air stream of these exhaust gases. These gases can be very hot and could actuate the system unnecessarily. Duct openings that are long and narrow or large enough to require multiple duct nozzles may require additional detectors. Electrostatic Precipitator. If an electrostatic precipitator is located at or near the base of the exhaust duct, it is necessary to locate a detector below the precipitator, at the base of the duct, and also locate one in the duct, just above the precipitator. See Figure 3-23a. When installing the detector bracket and system conduit, make certain they do not interfere with the operation of the precipitator. Figure 3-23a. 000268 Cooking Appliance(s). Each cooking appliance with a continuous cooking surface not exceeding 48 in. x 48 in. (122 x 122 cm) shall be protected by one (1) detector. Cooking appliances with a continuous cooking surface exceeding 48 in. x 48 in. (122 x 122 cm) shall be protected by one (1) detector per 48 in. x 48 in. (122 x 122 cm) cooking area. Detectors used for cook- ing appliances must be located above the protected appli- ance toward the exhaust duct side of the appliance. The detector should be located in the air stream of the appliance to enhance system response time. If a cooking appliance is located under a duct opening where a detector has been mounted, it is not necessary to utilize an additional detector provided the duct detector is not more than 12 in. (31 cm) into the duct opening. If two (2) appli- ances are located under a duct opening where a detector has been mounted, it is not necessary to utilize an additional detector provided the duct detector is not more than 12 in. (31 cm) into the duct opening. See Figure 3-24. APPLIANCE APPLIANCE APPLIANCE APPLIANCE COVERED COVERED COVERED COVERED BY BY BY BY DETECTOR DETECTOR DETECTOR DETECTOR A B B C Figure 3-24. Proper Detector Placement. 002943P0 ULEX 3830 March 1, 2006 Chapter 3 - System Design Page 3-20 REV. 1 NOTES: ULEX 3830 March 1, 2006 Chapter 2 - Components Page 2-1 REV. 4 CHAPTER II COMPONENTS CYLINDERS & VALVE The PYRO-CHEM KITCHEN KNIGHT II System has available four different size cylinders: Models PCL-160 (P/N 553163), PCL-300 (PIN 551194), PCL-460 (P/N 551193), and PCL-600 (PIN 551196). Cylinder sizes are expressed in terms of extin- guishing agent capacity (i.e., the PCL-300 uses 3.0 gallons (11.4 L) of extinguishing agent). The cylinder is manufactured, tested, and meets DOT requirements. Cylinders come pre-filled with extinguishing agent and are charged with dry nitrogen to a pressure of 225 psig @ 70° F (15.5 bar @ 21 °C). Cylinder and valve assembly dimensions are shown in Figure 2-1a. 14 Max. A B C D Flow Weight Mounting Model in. in. in. in. Point, lbs. Bracket No. (cm) (cm) (cm) (cm) Capaci (kg) Used PCL-160 7.00 19.62 25.37 17.31 5 33 MB-15 (17.8) (49.8) (64.4) (43.9) (15) PCL-300 8.00 25.06 30.81 22.75 10 53 MB-15 (20.3) (63.7) (78.3) (57.8) (24) PCL-460 10.00 25.06 30.81 22.75 15 83 MB-15 (25.4) (63.7) (78.3) (57.8) (37.7) PCL-600 10.po 35.81 41i€6 33.50 20 108 MB-1 (2.4) (91) (105.4) (85.1) (48.9) 1 Figure 2-la. Cylinder and Valve Assemblies. 00264 1PC All cylinders utilize the same wet valve assembly (P/N 551175). The wet valve assembly is a pressure sealed poppet type valve designed to provide rapid actuation and discharge of agent. See Figure 2-1b. Item Part No. Description Item Part No. Description Valve Body 8 550386 Shrader Valve Ass'y 2 550705 Conical Spring 3 550707 Piston 9 550714 Valve Cap 0-Ring 4 550716 1 Neck 0-Ring 10 550715 Piston 0-Ring 5 551236 Pressure Gauge 11 550989 Valve Stem 6 550028 Stem 0-Ring 12 551256 Pressure Regulator 7 550802 Wet Valve Adaptor 13 _______ 551261 Seal 14 17851 6-32x3/8 Screw 1/2 IN NPT Figure 2-lb. Wet Valve Cross Section. 00621 2PC WET VALVE REBUILDING EQUIPMENT Wet Valve Seal Rebuilding Kit (P/N 550698) After system discharge, the valve assembly must be rebuilt to ensure proper future operation. The Wet Valve Seal Rebuild- ing Kit (PIN 550698) should be used. It includes all compo- nents necessary to properly rebuild the valve. See Figure 2-2a. 4 b 60 5 Figure 2-2a. Wet Valve Seal Rebuilding Kit. 002906 PC Item Part Number Description 1 550705 Conical Spring 2 550716 Neck 0-Ring 3 550028 Stem 0-Ring 4 550715 Piston 0-Ring 5 1 550989 1 Valve Stem 6 1 550714 1 Valve Cap 0-Ring I - ULEX3S3O March 1, 2006 EXTERNAL 0-RING, PART NO. 551273 PISTON #8-32 X 3/8 IN. HOLDING SCREW, PART NO. 419045 Figure 2-2b. 0061 03 PC Model VT-1 (P/N 550788) The Model VT-1 wet valve tool is designed to facilitate the rebuilding of the wet valve assembly. It should be used to hold the wet valve piston while unscrewing the cap and stem assembly. See Figure 2-2c. Figure 2-2c. Model VT-11 Wet Valve Tool. 002907PC Chapter 2 - Components Page 2-2 REV. 4 Pressure Regulator Assembly (P/N 550985) The pressure regulator assembly is available if the complete regulator requires replacement (i.e., possible thread damage). Pressure Regulator Rebuilding Kit (P/N 551061) After system discharge, the pressure regulator must be rebuilt to ensure proper future operation. The rebuilding kit (P/N 551061) should be used. It includes all components and instructions necessary to properly rebuild the regulator. See Figure 2-2b. IN VALVE SEAL, PART BODY NO. 551261 #6-32 X 3/8 IN. SCREW, PART NO. 17851 CYLINDER BRACKETING Vertical bracketing of the PCL-160, PCL-300 and PCL-460 is provided by the Model MB-15 bracket kit (PIN 550054). Vertical bracketing of the PCL-600 is provided by the Model MB-i bracket kit (P/N 550053). These kits must be ordered separately with each cylinder/valve assembly. Cylinder instal- lation instructions are provided in the installation section of this manual. + A INTERNAL 0-RING, PISTON PART NO. 402745 0-RING, SPRING, PART - PART NO. \ J NO. 551,176 12837 B Figure 2-3. 006042PC Model No. A B C MB-15 15.69 in. 4.0 in. 3.13 in. (39.9 cm) (10.2 cm) (7.9 cm) MB-i 20.44 in. 4.0 in. 2.13 in. (51.9 cm) (10.2 cm) (5.4 cm) EXTINGUISHING AGENT The agent used in PYRO-CHEM KITCHEN KNIGHT II Systems is a potassium carbonate based solution that is extremely effective for grease-related kitchen fires. This agent is available for cylinder recharging in 1.6 Gallon and 3.0 Gallon containers. For MSDS information, contact PYRO-CHEM at 800-526-1079 or 715-732-3465 or www.pyrochem.com. 1.6 Gallon Shipping Assembly - P/N 553176 3.0 Gallon Shipping Assembly - P/N 551188 ULEX 3830 March 1, 2006 Chapter 2 - Components Page 2-3 REV. 2 CAUTION Precautions must be taken when handling and trans- ferring wet agents as they are caustic in nature. Goggles must be worn at all times. If any agent gets into the eyes, they should be flushed with clean water for 15 minutes and a physician contacted. If any agent contacts the skin, it should be flushed with cold water to prevent irritation. The agent is electrically conduc- tive. Care must be taken to thoroughly clean up any agent discharged around electrical appliances before turning the power on. After system discharge, agent must be cleaned up immedi- ately with hot, soapy water to prevent corrosion of effected surfaces. MODEL MCH3 - MECHANICAL CONTROL HEAD (PIN 551200) The Model MCH3 mechanical control head is a fully mechanical control head which can be connected to the PCL-300/460/600 cylinder valve. This control head will support a fusible link detection system, a remote mechanical pull station (Model RPS-M), and a mechanical or electric gas shut-off valve. A micro electric switch (Model MS-SPDT, MS- DPDT, MS-3PDT, or MS-4PDT) can be ordered separately and field installed. It is equipped with a local manual control handle that allows for mechanical system actuation. Operation of the local manual control requires removing the pull pin and rotating the handle clockwise. The Model MCH3 control head can actuate a maximum of five (5) cylinders with the 16 gram CO2 cartridge. See Figure 2-4. 0 0 MODEL MCH3 CONTROL HEAD PULL PIN. TURN HANDLE TO RELEASE FIRE SUPPRESSION SYSTEM PYRO.CHEM ONE STANTON STREET MUUIINETTE. Figure 2-4. Mechanical Control Head. 004790PC MODEL ECH3 — ELECTRIC CONTROL HEAD The Model ECH3 electric control head is an electrically operated control head which can be connected to the PCL- 300/460/600 cylinder valve. This control head will support an electric thermal detection system, a remote mechanical pull station (Model RPS-M), and an electric gas shut-off valve. It will not support a fusible link detection system. A micro elec- tric switch (Model MS-DPDT) is included. The Model ECH3 control head is available in both 120 VAC (Model ECH3-120, P/N 551202) and 24 VDC (Model ECH3-24, P/N 551201). It is equipped with a local manual control handle that allows for mechanical system actuation. Operation of the local manual control requires removing the pull pin and rotating the handle clockwise. The Model ECH3 control head can actuate a maximum of five (5) cylinders with the 16 gram CO2 cartridge. See Figure 2-5. 0 0 MODEL ECH3 I CONTROL HEAD IKKI PIN. TWIN HANDLE AEUEASE PRESSlRE SYSTEM SHE DTARTOSSTREET nul PYRoa II TI 54143-2542 Figure 2-5. Electric Control Head. OO4TUSPC MODEL NMCH3 - MECHANICAL CONTROL HEAD (PIN 551203) The Model NMCH3 Mechanical Control Head is a fully mechanical control head which can be connected to the PCL-300/460/600 cylinder valve. This control head will support a fusible link detection system, a remote mechanical pull station (Model RPS-M), and a mechanical or electric gas shut-off valve. A micro electrical switch (Model MS-SPDT, MS-DPDT, MS-3PDT, or MS-4PDT) can be ordered sepa- rately and field installed. There is no local manual actuation for the Model NMCH. The Model NMCH3 control head can actuate a maximum of five (5) cylinders with the 16 gram CO2 cartridge. o MODEL NMCH3 CONTROL HEAD r IRS PYRO CA SHE 5134105 STREET MARIRETTE. TI 54143-2542 0 Figure 2-5.1. Mechanical Control Head. TO6U43PC ULEX 3830 March 1, 2006 Chapter 2 - Components Page 2-4 REV. 3 MODEL EN-MCU3 ENCLOSURE (PIN 551208) The Model EN-MCU3 Enclosure is used for vertical mount- ing of a single PCL-300 or PCL-460. The EN-MCU3 also includes a mechanical control unit, eliminating the need for a Model MCH3 Control Head. See Figure 2-6. The PCL-600 cannot be mounted in an EN-MCU3. 0o 28.125 IN. (71.4 cm) 13.1251N. 1O.625 1N. I(333 cm)'1 r*270 cm) (FRONT) (SIDE) Figure 2-6. Model EN-MCU3 Enclosure. 002845PC MODEL EN-S ENCLOSURE (PIN 550966) The Model EN-S Enclosure is used for vertical mounting of a single PCL-300 or PCL-460 when it is used as a secondary agent cylinder in a system. Dimensions are the same as the Model EN-MCU3 enclosure (see Figure 2-6). The EN-S has no control mechanism, and must be used in conjunction with a Model EN-MCU3 Enclosure or a Model MCH3/ECH3 Control Head. The PCL-600 cannot be mounted in an EN-S. MODEL MB-P2 - CONTROL HEAD MOUNTING BRACKET (PIN 550853) The Model MB-P2 mounting bracket must be used to mount the Model MCH3, NMCH3, or ECH3 control heads if the control head is not mounted directly on a cylinder valve. See Figure 2-7. Figure 2-7. Model MB-P2 - Control Head - - - Mounting Bracket. 002846PC PNEUMATIC ACTUATING CYLINDERS Model PAC-10 (PIN 550104) The Model PAC-10 is a pneumatic actuating cylinder that can actuate a maximum of ten (10) agent cylinders simulta- neously. The Model PAC-lO includes a DOT 4BA350 cylinder pressurized with dry nitrogen to 350 psig @ 70 F. (24.1 bar @ 21 °C), a brass valve with pressure gauge, and a wall mounting bracket. A Model MCH3, NMCH3, or ECH3 control head must be purchased separately and connected to the PAC-10 to open the valve. See Figure 2-8. MODEL MCH3, NMCH3, OR CONTROL HEAD (SOLD SEPARATELY) 314 IN. DISCHARGE PORT 20.25 in. (51.4 cm) 14.50 in. (36.8 cm) 12.25 in. I ri (31.1 cm) 4.00 in. (10.2 cm) Figure 2-8. Model PAC-lo Pneumatic Actuating Cylinder 002847PC ULEX 3830 'March 1, 2006 Chapter 2 - Components Page 2-5 REV. 3 DETECTION EQUIPMENT Model FLH-1 (PIN 550876) Model FLK1 (P/N 550131) designed to simplify the installation of fusible links in the The Model PI H-1 fusible link hanger is an accessory fusible link line. It can be used with the Model FLK-1 fusible The Model FLK-1 fusible link kit includes a 10 in. (25.4 cm) link kit (kits must be ordered separately). The Fusible Link steel bracket, two (2) 1/2 in. EMT connectors, two (2) cable Hanger makes it possible to install fusible links without crimps, and two (2) "S" hooks. Fusible links must be ordered cutting and crimping loops in the fusible link line for each separately. See Figure 2-9a. link. They are available in packages of 25 (FLH-25) only. See Figure 2-9b. Model FLK-1A (P/N 550132) The Model FLK-1A fusible link kit includes an 8 in. (20.3 cm) steel bracket, two (2) 1/2 in. EMT connectors, two (2) cable crimps, and two (2) "5" hooks. Fusible links must be ordered separately. LINK DETECTOR BRACKET TERMINAL LINK S-HOOK 1/2 IN. EMT CONNECTOR 1/16 IN. STAINLESS STEELCABLE FUSIBLEUNK- N. CABLECMP SERIES LINK Figure 2-9a. Model FLK-1 Fusible Link. 002849PC Figure 2-9b. Model FLH-1 Fusible Link Hanger. 002850PC ULEX 3830 D. March 1, 2006 1/2-14 NPT-., / 1 IN. HEX J () 6IN. LEADS ( (152 MM) T4.9 IN. (125 m) 3.7 IN. (93 mm) 5/8 IN. (16 mm) Figure 2-11. Thermal Detector. MODEL RPS-M -R EMOTE MECHANICAL PULL STATION (P/N 551074) Remote manual control for the Model MCH3, NMCH3, or ECH3 control head is provided by the Model RPS-M remote mechanical pull station. It is connected to the system control head by stainless steel cable. This cable is enclosed in 1/2 in. EMT conduit with corner pulleys at each change in direction. The remote mechanical pull station shall be located at the point of egress. See Figure 2-12. IN CASE OF FIRE PULL l Forom - - STANDARD IN. x4 IN. ELEC. '-. JUNCTION BOX RIDGED BRUSHED ALUMINUM FACE PLATE RED PLASTIC BREAK ROD IDLE ON ALL CORNERS Figure 2-12. Model RPS-M Mechanical Pull Station 002852PC Chapter 2 - Components Page 2-6 REV.4 Fusible Links The fusible link is designed to separate at a specific temper- ature, releasing tension from the fusible link line, causing system actuation. See Figure 2-10. Figure 2-10. ML Style Fusible Link. 002851 PC After determining the maximum ambient temperature at the fusible link location, select the correct fusible link according to the temperature condition chart below: To Be Used Fusible Link Where Temperature Model No. Does Not Exceed Part Number FL-165 1000 F. (38° C.) 550368 FL-212 150° F. (66° C.) 550365 FL-280 225° F (107° C.) 550366 FL-360 290° F (143° C.) 550009 FL-450 360° F. (182° C.) 550367 FL-500 400° F. (204° C.) 56816 Thermal Detectors Fixed temperature thermal detectors are normally open, mechanical contact closure switches designed to operate at a factory preset temperature. They are available in four preset temperatures which meet NFPA standards and are UL Listed and FM Approved. After determining the maximum ambient temperature at the thermal detector location, select the correct thermal detector according to the temperature condition chart below: Thermal Detector Maximum Ambient Model No. Temperature Part Number TD-225 155° F. (68° C.) 13976 TD-325 255° F. (124° C.) 13975 TD-450 380° F. (193° C.) 13974 TD-600 530° F (277° C.) 13971 ULEX 3830 March 1, 2006 Chapter 2 - Components Page 2-7 REV. 4 GAS SHUT-OFF VALVES GV Mechanical Gas Shut-oft Valve A gas shut-off valve is required on all systems used to protect a gas fueled cooking appliance to stop gas flow in the event of system actuation. A mechanical gas valve can be used with the Model MCH3 control head. It is connected to the system control head by stainless steel cable. This cable is enclosed in 1/2 in. EMT conduit with a corner pulley at each change in direction. The valves are rated for natural and LP gas (see Figure 2-13a). Mechanical gas valves are available in the following sizes: Maximum Valve Operating Part Model No. Size Pressure Number GV-75 3/4 in. 5 psi (.4 bar) 550593 GV-100 1 in. 5 psi (.4 bar) 550594 GV-125 1-1/4 in. 5 psi (.4 bar) 550595 GV-150 1-1/2 in. 5 psi (.4 bar) 550596 GV-200 2 in. 5 psi (.4 bar) 551049 GV-250 2-1/2 in. 5 psi (.4 bar) 550185 GV-300 3 in. 5 psi (.4 bar) 550186 Maximum Valve Operating Part Model No. Size Pressure Number EGVSO-75 3/4 in. 50 psi (3.5 bar) 550358 EGVSO-100 1 in. 25 psi (3.5 bar) 550359 EGVSO-125 1-1/4 in. 25 psi (3.5 bar) 550360 EGVSO-150 1-1/2 in. 25 psi (3.5 bar) 550361 EGVSO-200 2 in. 25 psi (3.5 bar) 550362 EGVSO-250 2-1/2 in. 25 psi (3.5 bar) 550363 EGVSO-300 3 in. 25 psi (3.5 bar) 550385 Figure 2-13b. Electric Gas Shut-off Valve. 006844 PC SE C} Figure 2-13a. GV-Series Mechanical Gas Valve. 002853PC EGVSO Electric Gas Shut-oft Valve A gas shut-off valve is required on all systems used to protect a gas fueled cooking appliance to stop gas flow in the event of system actuation. A UL Listed electric gas valve can be used with either the Model MCH3 or ECH3 control head. The valves are rated for natural and LP gas. Valves are available in 120 VAC (see Figure 2-13b). Electric gas valves are available in the following sizes: Note: A UL Listed manual reset relay is required when using an electric gas valve. The PYRO-CHEM KITCHEN KNIGHT II Model SM-120 solenoid monitor may be used for this purpose. "QUIK-SEAL" ADAPTOR The "Quik-Seal" adaptor is a listed mechanical bulkhead fitting that produces a liquid-tight seal around both distribution piping and detection conduit which runs through restaurant hoods and ducts. The "Quik-Seal" adaptor accepts threaded pipe or conduit. The adaptor is available for 3/8 in. and 1/2 in. pipe or conduit sizes. When using with EMT conduit, a conduit connec- tor must be installed in each end of the adaptor. The "Quik- Seal" Adaptor Shipping Assembly can be ordered in single or package of 24. Shipping Assembly Hole Size Size Part No. Qty. Required 3/8 in. 550857 1 11/8 in. 1/2 in. 550859 1 1 1/8 in. 3/8 in. 550858 24 1 1/8 in. 1/2 in. 550860 24 1 1/8 in. ççi 1II.IJ ADAPTOR BODY GASKET LOCK WASHER NUT Figure 2-13c. [i 0 PyroC ahS VALVE $ ULEX 3830 March 1, 2006 Chapter 2 - Components Page 2-8 REV. 4 CORNER PULLEYS Model SBP-1 (PIN 415670) A corner pulley is used whenever a change in stainless steel cable direction is required. The Model SBP-1 corner pulley is equipped with a set screw fitting for connection to 1/2 in. EMT conduit. See Figure 2-14. Figure 2-14. Model SBP-1 Corner Pulley. 000160 Model CBP-1 (PIN 423250) A corner pulley is used whenever a change in stainless cable direction is required. The Model CBP-1 is a grease-tight corner pulley designed for areas likely to experience exces- sive deposit build-up. It is equipped with a compression fitting for connection to 1/2 in. EMT conduit. See Figure 2-15. Note: The Model CBP-1 is not a liquid tight seal for penetra- tion of hoods and/or ducts. D Figure 2-15. Model CBP-1 Corner Pulley. 000161 Model WBP-1 (PIN 550982) A corner pulley is used whenever a change in stainless cable direction is required. The Model WBP-1 is a weather- proof corner pulley designed for areas likely to be exposed to moisture. It is equipped with female pipe threads for connection to 1/2 in. rigid conduit. See Figure 2-15a. t1 Figure 2-15a. Model WBP-1 Corner Pulley. 006 194PC ULEX 3830 March 1, 2006 TEE PULLEY (P/N 550166) The Model TP-1 tee pulley is used to connect two mechani- cal gas valves or two remote mechanical pull stations to a single control head. The tee pulley replaces two standard 900 corner pulleys. See Figure 2-16. CAUTION The Tee Pulley must never be used to connect multi- ple fusible link lines to a single control head. Figure 2-16. Model TP-1 Tee Pulley. 002857PC WIRE ROPE The 1/16 in. diameter stainless steel wire rope must be used with actuators, detectors and gas valve components requir- ing a wire rope connection. The stainless steel wire rope is supplied in 50 ft. (15.2 m) lengths with P/N 15821, and 500 ft. (152 m) lengths with P/N 79653. Refer to the Components List for part numbers on crimps, stop sleeves, and S-hooks. "HOOD SEAL" ADAPTOR ASSEMBLY This adaptor is a mechanical bulkhead fitting that produces a liquid-tight seal around 1/2 in. EMT conduit when installing the detection line through restaurant hoods and duct. The adaptor accepts a high temperature pulley elbow and, when used, correctly positions the elbow or conduit in line with the conduit adaptor hole in the detector bracket. The "Hood Seal" eliminates the need for multiple elbows when penetrating the top of a hood when installing the detection line. "Hood Seal" Adaptors are available in quantities of 6 as Shipping Assembly P/N 423253. SEAL NUT SEAL __...WASHER ADAPTOR BODY 7EY GASKET PULL ELBO (NOT OF A ) USE ONLY PULLEY ELBOW, PART NO. 423250 Figure 2-16a. Chapter 2 - Components Page 2-9 REV. 2 ELECTRICAL SWITCHES The electrical switches are intended for use with electric gas valves, alarms, contactors, lights, contractor supplied electric power shut-off devices and other electrical devices that are designed to shut-off or turn on when the system is actuated. NOTE No electrical connections shall be made inside the control head. All electrical wiring shall exit the control head through the knock-out on the side of the box. All electrical connections must be made in an approved electrical box. Switches are available in kits: One Switch Kit, Part No. 551154; Two Switch Kit, Part No. 551155; Three Switch Kit, Part No. 551156, and Four Switch Kit, Part No. 551157. Mounting hardware and 12 in. wire assemblies are provided with each kit. Each switch has a set of single-pole, double- throw contacts rated: ULJcULICSA Rating ENEC Rating 250 VAC, 21A Resistive IE4T105p Approved 250 VAC, 2 HP 250V, 21A Resistive 125 VAC, 1 HP 8A Motor Load Co (RE N.C. (BROWN) Figure 2-17a. Model MS-SPOT Micro Switch. 001612 The Alarm Initiating Switch Kit, Part No. 550077, can be field mounted within the control head. This switch must be used to close a supervised circuit to the building main fire alarm panel when the control head actuates. This action will signal the fire alarm panel that there was a system actuation in the kitchen area. The switch kit contains all necessary mounting components along with a mounting instruction sheet. The switch is rated 50 mA, 28 VDC. TOWARD REAR OF SPACER WHEN SPACER AND CONTROL HEAD . SWITCH ARE PROPERLY MOUNTED, THIS DIVIDER MUST BE BETWEEN THE / N.C. AND N.C. TERMINALS COM N.O. See NFPA 72, "National Fire Alarm Code," Initiating Devices section, for the correct method of wiring connection to the fire alarm panel. MODEL SM-120124 SOLENOID MONITOR The Model SM-120/24 solenoid monitor is used in conjunc- tion with the Model ECH3 control head to supervise the actuation and detection circuits. In the event of a problem in the circuit, a light on the monitor goes out. The Model SM- 120 is used with the Model ECH3-120 control head. The Model SM-24 (P/N 550303) is used with the Model ECH3-24 control head. Two sets of NO/NC dry contacts are provided. The unit mounts directly to a three gang wall outlet box. The Model SM-120 (P/N 550302) acts as a reset relay when used with an electric gas valve. Electric gas valve wiring instructions are provided in the installation section of this manual. See Figure 2-18. S S Py,O-Cher' Soler'dd monitor []nc € Figure 2-18. Model SM-241120 Solenoid Monitor. 002860 PC PIPE AND FITTINGS Pipe and fittings must be furnished by the installer. Schedule 40 stainless steel, chrome plated, or black pipe and fittings must be used. Galvanized pipe and fittings are not to be used. N.O. (BLACK) N.C. Figure 2-17b. Alarm Initiating Switch. 004890 ULEX 3830 March 1, 2006 SWIVEL ADAPTOR (P/N 418569) The Swivel adaptor consists of a swivel nut, swivel body, and swivel ball. All are chrome-plated. The swivel adaptor allows the nozzle to be rotated approximately 300 in all directions. Swivel Adaptors can be ordered as a single Swivel Adaptor or Swivel Adaptor Shipping Assembly, Part No. 423572, which contains 25 swivel adaptors. See Figure 2-21. 3/8-18 NPT FEMALE THREAD 3O ROTATION Figure 2-21. Swivel Adaptor. 005003 NOZZLE AIMING DEVICE The Nozzle-Aiming Device, Part No. 551265, is required to properly aim each nozzle to the correct aiming point. The device clamps to the nozzle and emits a small laser light that reflects on the surface that it is aiming at. The nozzle can then be rotated to point at a predetermined aiming point and then tightened to hold that angle. The aiming device requires an adaptor, Part No. 550926, to attach it to the nozzle. The adaptor must be ordered separately. I I ADAPTOR (ORDER 0 SEPARATELY) NOZZLE,,.' AIMING DEVICE Figure 2-22. Nozzle Aiming Device. 006520 RUBBER BLOW-OFF CAPS The Rubber Blow-Off Cap helps keep the orifice of the nozzle free of grease or other substances that could interfere with agent distribution. A retaining strap attaches the blow-off cap to the nozzle. Rubber Blow-Off Caps must be ordered as a Shipping Assembly, Part No. 550016, which contains 12 blow- off caps. Chapter 2 - Components Page 2-10 REV. 4 Li I STAINLESS STEEL ACTUATION HOSE The Stainless Steel Actuation Hose is used to connect the actu- ation line compression tees and can also be connected end to end. The hose has the same thread, 7/16-20, as the fittings. See Figure 2-19. Hose Part No. Length 417582 8 in. (20 cm) 31809 16 in. (41 cm) 32336 24 in. (61 cm) 430815 42 in. (107 cm) Fitting Part No. Description 31810 Male Elbow (7/16-20 x 1/4 in. NPT) 31811 Male Tee (7/16-20 x 7/16-20 x 1/4 in. NPT) 32338 Male Straight Connector (7/16-20 x 1/4 in. NPT) jl m;:*Uj Ill. Figure 2-19. Stainless Steel Actuation Hose. 000433 NOZZLES Nozzles have been developed for appliance, plenum, and duct applications. All nozzles have a specific flow point value and are supplied with metal blow-off caps to prevent clog- ging. Each nozzle is stamped with the model number. See Figure 2-20. Application limitations are provided in the design section of this manual. Part No. Description Flow No. 551029 1H Nozzles, pack of ten (10) 1 551026 1L Nozzles, pack of ten (10) 1 551028 2H Nozzles, pack of ten (10) 2 551027 2L Nozzles, pack of ten (10) 2 551038 2D Nozzles, pack of ten (10) 2 Figure 2-20. Nozzles. 006171 PC ULEX 3830 March 1, 2006 STRAINER BODY lh 1L YRO 2R 2L 2D Chapter 2 - Components Page 2-11 REV. 2 COMPONENTS LIST MODEL NO. DESCRIPTION PART NO. MODEL NO. DESCRIPTION PART NO. PCL-160 1.6 GALLON CYLINDER ASSEMBLY 553163 EGVSO-75 ELECTRIC GAS SHUT-OFF VALVE 550358 PCL-300 3.0 GALLON CYLINDER ASSEMBLY 551194 3/4 IN. PCL-460 4.6 GALLON CYLINDER ASSEMBLY 551193 EGVSO-100 ELECTRIC GAS SHUT-OFF VALVE 1 IN. 550359 PCL-600 6.0 GALLON CYLINDER ASSEMBLY 551196 EGVSO-125 ELECTRIC GAS SHUT-OFF 550360 PAC-lO PNEUMATIC ACTUATING CYLINDER 550104 VALVE 1-1/4 IN. PCL-300 CANADIAN- 3.0 GALLON 551195 EGVSO-150 ELECTRIC GAS SHUT-OFF 550361 CYLINDER ASSEMBLY VALVE 1-1/2 IN. PCL-460 CANADIAN -4.6 GALLON 551192 EGVSO-200 ELECTRIC GAS SHUT-OFF VALVE 2 IN. 550362 CYLINDER ASSEMBLY EGVSO-250 ELECTRIC GAS SHUT-OFF 550363 PCL-600 CANADIAN - 6.0 GALLON 551197 VALVE 2-1/2 IN. CYLINDER ASSEMBLY EGVSO-300 ELECTRIC GAS SHUT-OFF VALVE 3 IN. 550385 PAC-lO CANADIAN - PNEUMATIC 551125 GV-75 MECHANICAL GAS SHUT-OFF 550593 ACTUATING CYLINDER VALVE 3/4 IN. MB-1 MOUNTING BRACKET (FOR PCL-600) 550053 GV-100 MECHANICAL GAS SHUT-OFF 550594 MB-15 MOUNTING BRACKET 550054 VALVE 1 IN. (FOR PCL-300/460) GV-125 MECHANICAL GAS SHUT-OFF 550595 MB-P2 MOUNTING BRACKET 550853 VALVE 1-1/4 IN. (FOR MCH3 ECH3-24/120) GV-150 MECHANICAL GAS SHUT-OFF 550596 MCH3 MECHANICAL CONTROL HEAD 551200 VALVE 1-1/2 IN. NMCH3 MECHANICAL CONTROL HEAD 551203 GV-200 MECHANICAL GAS SHUT-OFF 551049 (NO HANDLE) VALVE 2 IN. EN-MCU3 ENCLOSURE (FOR PRIMARY 551208 GV-250 MECHANICAL GAS SHUT-OFF 550185 CYLINDER) VALVE 2-1/2 IN. EN-S ENCLOSURE (FOR SECONDARY 550966 GV-300 MECHANICAL GAS SHUT-OFF VALVE 550186 CYLINDER) 3 IN. ECH3-24 24VDC ELECTRICAL CONTROL HEAD 551201 MS-SPDT MICRO SWITCH - SINGLE POLE 551154 DOUBLE THROW ECH3-120 120VAC ELECTRICAL CONTROL HEAD 551202 MS-DPDT MICRO SWITCH - DOUBLE POLE 551155 - - - 8 IN. S.S. ACTUATION HOSE 417582 DOUBLE THROW - - - 16 IN. S.S. ACTUATION HOSE 31809 MS-3PDT MICRO SWITCH -3 POLE DOUBLE 551156 - - - 24 IN. S.S. ACTUATION HOSE 32336 THROW - - - 42 IN. S.S. ACTUATION HOSE 430815 MS-4PDT MICRO SWITCH -4 POLE DOUBLE 551157 - - - MALE ELBOW 31810 THROW - - - MALE TEE 31811 - - - ALARM INITIATING SWITCH 550077 - - - MALE STRAIGHT CONNECTOR 32338 CO2-6 6 x CO2 CARTRIDGE (16 GM) 551059 1H WET NOZZLE (PACK OF 10) 551029 - - - 0-RING, ACTUATOR ASSEMBLY 55531 1L WET NOZZLE (PACK OF 10) 551026 CBP-i COMPRESSION BEARING 423250 2H WET NOZZLE (PACK OF 10) 551028 CORNER PULLEY 2L WET NOZZLE (PACK OF 10) 551027 SBP- 1 SCREW BEARING CORNER PULLEY 415670 2D WET NOZZLE (PACK OF 10) 551038 WBP-1 WEATHER PROOF BEARING 550982 CORNER PULLEY - - - SWIVEL ADAPTOR (PACK OF 25) 423572 TP-1 TEE PULLEY 550166 - - - RUBBER BLOW-OFF CAPS (PACK OF 12) 550016 WET VALVE CAP 550831 RPS-M REMOTE MECHANICAL PULL STATION 551074 - - - CONICAL SPRING (WET VALVE) 550705 FLK-1 10 IN. FUSIBLE LINK BRACKET KIT 550131 - - - PRESSURE GAUGE (WET VALVE) 551236 FLK-1A 8 IN. FUSIBLE LINK BRACKET KIT 550132 - - - PRESSURE REGULATOR ASSEMBLY 550985 FLH-25 25 x FUSIBLE LINK HANGER 550876 - - - WET VALVE REBUILDING KIT 550698 FL-165 FUSIBLE LINK 165°F 550368 - - - PRESSURE REGULATOR REBUILD KIT 551061 FL-212 FUSIBLE LINK 212°F 550365 - - - VT-i VALVE TOOL (WET VALVE) 550788 FL-280 FUSIBLE LINK 280°F 550366 NECK 0-RING (WET VALVE) 550716 FL-360 FUSIBLE LINK 360°F 550009 - - - PISTON (WET VALVE) 550707 FL-450 FUSIBLE LINK 450°F 550367 - - - PISTON 0-RING (WET VALVE) 550715 FL-500 FUSIBLE LINK 500°F 56816 - - - VALVE CAP 0-RING (WET VALVE) 550714 SM-24 24VDC SOLENOID MONITOR 550303 - - - RL-160 1.6 GALLON RECHARGE 553176 SM-120 120VAC SOLENOID MONITOR 550302 RL-300 3.0 GALLON RECHARGE 551188 TD-225 THERMAL DETECTOR 225°F 13976 PCL-300T TEST TANK 551024 TD-325 THERMAL DETECTOR 325°F 13975 PCL-460T TEST TANK 550902 TD-450 THERMAL DETECTOR 450°F 13974 PCL-600T TEST TANK 550901 TD-600 THERMAL DETECTOR 600°F 13971 RUBBER BLOW-OFF CAP 550016 ULEX 3830 P. March 1, 2006 Chapter 2 - Components Page 2-12 REV 2 COMPONENTS LIST (Continued) MODEL NO. DESCRIPTION PART NO. PCL-AK WC-100 10 x WET NOZZLE CAP 551528 10 x WET NOZZLE STRAINER 551529 10 WET NOZZLE 0-RING 551530 VALVE STEM 0-RING 550028 COMPLETE WET VALVE ASSEMBLY 551175 RECHARGE ADAPTOR KIT 551240 MEASURING STICK 551039 STAINLESS STEEL WIRE ROPE, 50 FT. 15821 STAINLESS STEEL WIRE ROPE, 500 FT. 79653 OVAL SLEEVE CRIMPS 550122 (100 PER PACKAGE) STOP SLEEVES (PACK OF 10) 24919 FLUSHING CONCENTRATE (32-OZ.) 79656 ULEX 3830 March 1, 2006 loam Oki Oki a m PLANS FOR PERMIT F5160007 1 LEGOLAND DR